BUILDING INTEGRITY SUMMARY REPORT

Size: px
Start display at page:

Download "BUILDING INTEGRITY SUMMARY REPORT"

Transcription

1 BUILDING INTEGRITY SUMMARY REPORT SUPPLIER NAME Kenpark Bangladesh Pvt.Ltd (Unit 1) UNITS AUDITED SUPPLIER ADDRESS Dry Process Building Sector 8, Plot 31-42, Chittagong Export Processing Zone, Chittagong, Bangladesh AUDIT DATE March 2014 AUDIT PERFORMED BY Department of Civil Engineering, Bureau of Research, Testing and Consultation, Bangladesh University of Engineering and Technology (BUET) AUDIT TEAM 2 auditors GRAVITY LOADING EVALUATION GREEN The building is fully safe. GREEN The building is fully safe. Dry Process Building AMBER The building's safety is not fully ensured. SEISMIC PERFORMANCE RATING POOR Possible significant structural and nonstructural damage POOR and/or result in falling hazards in a major seismic Dry Process Building POOR disturbance, representing appreciable life hazards. BRIEF DESCRIPTION OF METHODOLOGY Visual inspection and ASCE Tier-1 Analysis BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 1/6

2 DETAILED CONTENT VISUAL INSPECTION AND CONCLUDING REMARKS... 2 MAIN BUILDING... 2 WASH BUILDING... 2 DRY PROCESS BUILDING... 3 SEISMIC PERFORMANCE EVALUATION... 3 I. BASIC STRUCTURAL CHECKLIST NON-COMPLIANCES... 3 II. GEOLOGICAL SITE HAZARDS AND FOUNDATIONS CHECKLIST NON-COMPLIANCES... 4 III. BASIC NON-STRUCTURAL COMPONENT CHECKLIST NON-COMPLIANCES... 4 DETAILED DESCRIPTION OF METHODOLOGY... 4 VISUAL INSPECTION AND CONCLUDING REMARKS MAIN BUILDING Based on the Visual Assessment, we have decided that this building has fallen in safe, GREEN, category. There may be a potential cause of pounding due to different vibration modes of two dissimilar structures. The factory management has already arranged a Detail Engineering Assessment (DEA) from CUET and it has been concluded that the structure is properly designed as per code requirement. The single storied main factory building with a mezzanine floor and the single storied canteen have different framing system and both of them are connected at the ground floor level through a covered passageway. This may be a potential cause of pounding due to different vibration modes of two dissimilar structures. The fixed covered passageway need to be replaced with a sliding one to avoid pounding immediately. Bracings need to be provided to the steam pipes and other utility items which are hanging from the roof, immediately. The use of the building in its present condition may continue with due regards to the observations made above. WASH BUILDING This building has fallen in GREEN (safe) category considering the Factor of Safety (FOS) of all types of columns. From ASCE31 checklist, it is observed that some columns of ground floor do not satisfy the minimum requirements of shear stress. The affected columns need to be identified through DEA and strengthened immediately. The 3 storied extension building and the single storied washing plant have different framing system and both of them are connected at the ground & first floor levels; during occurrence of an earthquake pounding may occur. Sufficient gap based on DEA need to be provided to avoid pounding immediately. BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 2/6

3 Bracings need to be provided to the steam pipes and other utility items which are hanging from the roof, immediately. The use of the building in its present condition may continue with due regards to the observations made above. DRY PROCESS BUILDING The slender column used as central support appeared to be vulnerable under earthquake (strong beam weak column).the building has been tagged as AMBER with Detailed Engineering Assessment (DEA) to be commenced immediately and completed within the next 6 weeks. Bracings need to be provided to the steam pipes and other utility items which are hanging from the roof, immediately. The use of the building in its present condition may continue with due regards to the observations made above. SEISMIC PERFORMANCE EVALUATION I. BASIC STRUCTURAL CHECKLIST NON-COMPLIANCES Criteria Description of Conditions Comments Unit Building System - General The single-storied main factory building with a mezzanine floor and the single-storied canteen have The clear distance between the building different framing system and being evaluated and any adjacent both of them are connected Adjacent building shall be greater than 4 percent at the ground floor level Buildings of the height of the shorter building for through a covered Life Safety and Immediate Occupancy. passageway. Configuration The estimated distance between the story center of mass and the story center of rigidity shall be less than 20 Torsion percent of the building width in either plan dimension for Life Safety and Immediate Occupancy. Concrete Moment Frames Shear Stress Check The shear stress in the concrete columns, calculated using the Quick Check procedure of Section , shall be less than the greater of 100 psi or for Life Safety and Immediate Occupancy. Unreinforced Masonry Shear Walls Shear Stress The shear stress in the unreinforced Check masonry shear walls, calculated using There is a single story steel structure/shed connected with the extension building. The distance between story center of mass and center of rigidity is not less than the 20% of plan dimension in both direction due to mezzanine. The columns of ground floor are not satisfying the mentioned requirements. All unreinforced masonry shear walls do not satisfy the BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 3/6

4 the Quick Check procedure of Section , shall be less than 30 psi for clay units and 70 psi for concrete units for Life Safety and Immediate Occupancy. mentioned requirement. II. GEOLOGICAL SITE HAZARDS AND FOUNDATIONS CHECKLIST NON-COMPLIANCES Criteria Description of Conditions Comments Unit III. BASIC NON-STRUCTURAL COMPONENT CHECKLIST NON-COMPLIANCES Criteria Description of Conditions Comments Unit Lighting Fixtures Emergency lighting shall be anchored or Emergency Emergency lighting is not braced to prevent falling during an Dry Process Lighting securely fixed. earthquake. Building Building Contents and Furnishing Tall Narrow Contents Contents over 4 feet in height with a height-to-depth or height-to-width ratio greater than 3-to-l shall be anchored to the floor slab or adjacent structural walls. A height-to-depth or height-towidth ratio of up to 4-to-l is permitted where only the Basic Nonstructural Component Checklist is required. Mechanical and Electrical Equipment Attached Equipment Equipment weighing over 20 lb that is attached to ceilings, walls; or other supports 4 feet above the floor level shall be braced. The height to width ratio of tall rack is greater than 4 and are needed to be braced. External AC units may not be adequately braced. Dry Process Building All DETAILED DESCRIPTION OF METHODOLOGY 1. The following criteria are used for the building integrity inspection: A. Permit review and verification. B. Visual assessment. C. Detailed assessment following ASCE-31 standards. i. Level of Investigation ii. Level of Performance Evaluation to Life Safety Performance Level (L.S.) iii. Level of Seismicity According to BNBC (1993) and based on geotechnical investigation report 1. Zone coefficient 2. Site Class (as per BNBC 1993) Design short period response acceleration S DS BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 4/6

5 Design spectral response acceleration at 1 sec. SD 1 iv. Building Type v. Screening Phase (Tier 1) vi. Basic Structural Checklist vii. Geological Site Hazards and Foundation Checklist viii. Basic Non-structural Component Checklist 2. Gravity Loading Evaluation Definitions GREEN YELLOW AMBER RED Factor of Safety (FS) of Column Strength is greater than the building is fully safe Factor of Safety (FS) of Column Strength is between 1.5 and the building is marginally safe Factor of Safety (FS) of Column Strength is between 1.25 and the building's safety is not fully ensured Factor of Safety (FS) of Column Strength is less than the building is unsafe 3. Seismic Performance Ratings ( ) GOOD FAIR POOR VERY POOR Buildings and other structures whose performance during a major seismic disturbance is anticipated to result in structural and nonstructural damage and/or falling hazards that would not significantly jeopardize life. Buildings and other structures with a GOOD rating would represent an acceptable level of earthquake safety, such that funds need not be spent to improve their seismic resistance to gain greater life safety. Buildings and other structures whose performance during a major seismic disturbance is anticipated to result in structural and nonstructural damage and/or falling hazards that would represent low life hazards. Buildings and other structures with a FAIR seismic rating would be given a low priority for expenditures to improve their seismic resistance and/or to reduce falling hazards so that the building could be reclassified GOOD. Buildings and other structures expected to sustain significant structural and nonstructural damage and/or result in falling hazards in a major seismic disturbance, representing appreciable life hazards. Such buildings or structures either would be given a high priority for expenditures to improve their seismic resistance and/or to reduce falling hazards so that the building could be reclassified GOOD, or would be considered for other abatement programs, such as reduction of occupancy. Buildings and other structures whose performance during a major seismic disturbance is anticipated to result in extensive structural and nonstructural damage, potential structural collapse, and/or falling hazards that would represent high life hazards. Such buildings or structures either would be given BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 5/6

6 the highest priority for expenditures to improve their seismic resistance and/or to reduce falling hazards so that the building could be reclassified GOOD, or would be considered for other abatement programs, such as reduction of occupancy. BUILDING INTEGRITY INSPECTION SUMMARY KENPARK BANGLADESH PVT LTD (UNIT 1) PAGE 6/6

BUILDING INTEGRITY SUMMARY REPORT

BUILDING INTEGRITY SUMMARY REPORT BUILDING INTEGRITY SUMMARY REPORT SUPPLIER NAME SUPPLIER ADDRESS AUDIT DATE January 2014 AUDIT PERFORMED BY Cosmopolitan Industries Pvt Ltd Khejur Bagan, Bara Ashulia, Savar, Dhaka, Bangladesh Department

More information

BUILDING INTEGRITY SUMMARY REPORT

BUILDING INTEGRITY SUMMARY REPORT BUILDING INTEGRITY SUMMARY REPORT SUPPLIER NAME UNITS AUDITED Opex Mills 4X 6X Denim Rope Denim SSL SSL3 Utility Diesel SUPPLIER ADDRESS AUDIT DATE January 2014 AUDIT PERFORMED BY AUDIT TEAM Kanchpur,

More information

3.5 Tier 1 Analysis Overview Seismic Shear Forces

3.5 Tier 1 Analysis Overview Seismic Shear Forces Chapter 3.0 - Screening Phase (Tier ) 3.5 Tier Analysis 3.5. Overview Analyses performed as part of Tier of the Evaluation Process are limited to Quick Checks. Quick Checks shall be used to calculate the

More information

BUILDING INTEGRITY DEA SUMMARY REPORT

BUILDING INTEGRITY DEA SUMMARY REPORT BUILDING INTEGRITY DEA SUMMARY REPORT SUPPLIER NAME UNITS AUDITED Opex Mills SSL2 Building 4X Generator Building 6X Generator Building Denim Generator Building Rope Denim Generator Building SSL Generator

More information

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 4, Issue 05, 2016 ISSN (online): 2321-0613 Seismic analysis of RC Building Frame with Different Bracing Systems Mohammed Ali Khan

More information

ABA Fashions Ltd. Plot #9, Block F, Tongi, Gazipur-1710 ( N, E) 08 MARCH 2014

ABA Fashions Ltd. Plot #9, Block F, Tongi, Gazipur-1710 ( N, E) 08 MARCH 2014 ABA Fashions Ltd. Plot #9, Block F, Tongi, Gazipur-1710 (23.885176N, 90.399821E) 08 MARCH 2014 1 2 Observations 3 Highly stressed columns Cursory calculations indicate column at a high working stress.

More information

McMULLAN & ASSOCIATES, INC.

McMULLAN & ASSOCIATES, INC. McMULLAN & ASSOCIATES, INC. SEISMIC EVALUATION REPORT for the The Castle Building Prepared For Smithsonian Institution Washington, D.C. February 28, 2002 86 Seismic Evaluation G.2 THE CASTLE BUILDING WASHINGTON,

More information

"Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures

Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures "Impact of New IS 1893 & Related Codes on Design of tall Buildings, Including Trend Setting Structures Conference on Planning and Design of Tall Buildings including Earthquake and Wind Effects By S. C.

More information

Structural Inspection Report

Structural Inspection Report Revision: Issue 2 Date: 23 rd June 2014 Cherry Pvt. Ltd. Florence Fashions Ltd. Ultimate Ltd. Chandand Fashion Ltd. Joy Fashion Ltd. Structural Inspection Report Authors: Adrian Ryan, Cathal Mac an tsearraigh

More information

Volume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents

Volume 1. HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents Preparation of Seismic Design Manuals for Earthquake Disaster Mitigation Volume 1 HOW TO MAKE A DREAM HOUSE EARTHQUAKE RESISTANT Contents Part I: A house and its behavior during earthquake A House? How

More information

DESIGN CRITERIA. Allowable Stress Design (ASD) AISC-1999.

DESIGN CRITERIA. Allowable Stress Design (ASD) AISC-1999. DESIGN CRITERIA 1. INTRODUCTION This appendix summarizes the codes, standards, criteria, and practices that are generally used in the design and construction structural engineering system for the Sarker

More information

gwinnettcounty RACKING SHELVING CONVEYOR CONSTRUCTION CODE COMPLIANCE GUIDELINES Permitting Procedure

gwinnettcounty RACKING SHELVING CONVEYOR CONSTRUCTION CODE COMPLIANCE GUIDELINES Permitting Procedure Plan review and permitting requirements for storage systems such as storage racks, storage shelving, pallet racks, movable shelf racks, and conveyors. Permitting Procedure A Building Permit (BLD) is required

More information

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE

SEAU 5 th Annual Education Conference 1. ASCE Concrete Provisions. Concrete Provisions. Concrete Strengths. Robert Pekelnicky, PE, SE ASCE 41-13 Concrete Provisions Robert Pekelnicky, PE, SE Principal, Degenkolb Engineers Chair, ASCE 41 Committee* *The view expressed represent those of the author, not the standard s committee as a whole.

More information

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Plan Check/PCIS App #: Job Address: P.C. Engineer: Phone: (E -mail: first name.last name@ lacity.org) For instructions and other information,

More information

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS

NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS NON-LINEAR STATIC PUSHOVER ANALYSIS FOR MULTI-STORED BUILDING BY USING ETABS Polupalli Victor Paul 1, K Sampath Kumar 2 1 PG Student, Dept of Civil Engineering, Nova College of Engineering & Technology,

More information

Abanti Color Tex Ltd. Plot-S, A-646, Shashongaon Enayetnager, Fatullah, Narayangonj ( E, N) 28 June 2014

Abanti Color Tex Ltd. Plot-S, A-646, Shashongaon Enayetnager, Fatullah, Narayangonj ( E, N) 28 June 2014 1 Abanti Color Tex Ltd. Plot-S, A-646, Shashongaon Enayetnager, Fatullah, Narayangonj (90.476444E, 23.622806N) 28 June 2014 2 Preliminary calculations suggest columns in Units 1 and 2 are highly stressed

More information

Plan Check No. Checked by: An Appointment Is Required for Verification

Plan Check No. Checked by: An Appointment Is Required for Verification SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION

More information

PEER/CSSC Tall Building Design Case Study Building #1. J. Andrew Fry John Hooper Ron Klemencic Magnusson Klemencic Associates

PEER/CSSC Tall Building Design Case Study Building #1. J. Andrew Fry John Hooper Ron Klemencic Magnusson Klemencic Associates PEER/CSSC Tall Building Design Case Study Building #1 J. Andrew Fry John Hooper Ron Klemencic Magnusson Klemencic Associates Building Information Located in Los Angeles 42-Story 410 ft Tall 108 ft X 107

More information

EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai

EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS. By Ir. Heng Tang Hai EARTHQUAKE DESIGN CONSIDERATIONS OF BUILDINGS By Ir. Heng Tang Hai SYPNOSIS 1. Earthquake-Induced Motions 2. Building Configurations 3. Effectiveness Of Shear Walls 4. Enhancement Of Ductility In Buildings

More information

Seismic Behavior of Soft First Storey

Seismic Behavior of Soft First Storey IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 78-168 Volume, Issue 5 (Nov. - Dec. 1), PP 8-33 Seismic Behavior of Soft First Storey 1 P.B.Lamb, Dr R.S. Londhe 1 PG Student Applied

More information

The designer shall also submit additional information required by the University as described and underlined below.

The designer shall also submit additional information required by the University as described and underlined below. I. Structural Engineering Submissions The designer shall submit all information required by the State Construction Office (SCO) as described in the State Construction Manual Chapter 300 - Project Design

More information

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP

4.2 Tier 2 Analysis General Analysis Procedures for LSP & LDP 4.2 Tier 2 Analysis 4.2.1 General Four analysis procedures are provided in this section: Linear Static Procedure (LSP), Linear Dynamic Procedure (LDP), Special Procedure, and Procedure for Nonstructural

More information

DEFINING RIGID VS. FLEXIBLE NONSTRUCTURAL COMPONENTS

DEFINING RIGID VS. FLEXIBLE NONSTRUCTURAL COMPONENTS 10NCEE Tenth U.S. National Conference on Earthquake Engineering Frontiers of Earthquake Engineering July 21-25, 2014 Anchorage, Alaska DEFINING RIGID VS. FLEXIBLE NONSTRUCTURAL COMPONENTS B. E. Kehoe 1

More information

INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR)

INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR) INITIAL STRUCTURAL INTEGRITY ASSESSMENT REPORT (SIAR) Factory Name: Karardi, Shibpur, Narsingdi, Narsingdi Dhaka Bangladesh 10 May 2013 The Alliance for Bangladesh Worker Safety Page 1/15 10 May 2013 Introduction

More information

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS

LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS 1 LATERAL DRIFT DESIGN IN COLD FORMED STEEL WALL SYSTEMS Thomas Castle, S.E. 2 This presentation is published by the Cold-Formed Steel Engineers Institute ( CFSEI ). The information herein shall not constitute

More information

International Journal of Advanced Structural Engineering, Vol. 3, No. 1, Pages , July 2011

International Journal of Advanced Structural Engineering, Vol. 3, No. 1, Pages , July 2011 International Journal of Advanced Structural Engineering, Vol. 3, No. 1, Pages 111-120, July 2011 Archive of SID Islamic Azad University, South Tehran Branch Published online July 2011 at (http://journals.azad.ac.ir/ijase)

More information

Effect of Standard No Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel Systems

Effect of Standard No Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel Systems Engineering, Technology & Applied Science Research Vol. 7, No. 6, 2017, 2139-2146 2139 Effect of Standard No. 2800 Rules for Moment Resisting Frames on the Elastic and Inelastic Behavior of Dual Steel

More information

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000.

Index terms Diagrid, Nonlinear Static Analysis, SAP 2000. Pushover Analysis of Diagrid Structure Ravi K Revankar, R.G.Talasadar P.G student, Dept of Civil Engineering, BLDEA S V.P Dr P.G Halakatti College of Engineering & Technology Bijapur-586101 Associate Professor,

More information

Seismic Design Criteria for Structures, Systems, and Components in Nuclear Facilities

Seismic Design Criteria for Structures, Systems, and Components in Nuclear Facilities ASCE/SEI 43-05 American Society of Civil Engineers Seismic Design Criteria for Structures, Systems, and Components in Nuclear Facilities This document uses both the International System of Units (SI) and

More information

Structural Engineering

Structural Engineering Structural Engineering 4 4.0 TABLE OF CONTENTS 4.1 General Approach 115 Submission Requirements 4.2 Codes and Standards 116 Structural Design of New Buildings 116 Use of Recycled Materials 4.3 Structural

More information

Earthquake Resistant Design. Dr. S. K. PRASAD Professor of Civil Engineering S. J. College of Engineering, Mysore

Earthquake Resistant Design. Dr. S. K. PRASAD Professor of Civil Engineering S. J. College of Engineering, Mysore Earthquake Resistant Design Dr. S. K. PRASAD Professor of Civil Engineering S. J. College of Engineering, Mysore Email : skprasad@sjce.ac.in Natural Disasters Earthquake Tornado, Cyclone Floods Fire Natural

More information

EARTHQUAKE HAZARD REDUCTION IN EXISTING CONCRETE BUILDINGS AND CONCRETE WITH MASONRY INFILL BUILDINGS

EARTHQUAKE HAZARD REDUCTION IN EXISTING CONCRETE BUILDINGS AND CONCRETE WITH MASONRY INFILL BUILDINGS CHAPTER A5 EARTHQUAKE HAZARD REDUCTION IN EXISTING CONCRETE BUILDINGS AND CONCRETE WITH MASONRY INFILL BUILDINGS The provisions contained in this chapter have not been adopted by the City of Dallas. SECTION

More information

4.6 Procedures for Connections

4.6 Procedures for Connections 4.6 Procedures for Connections This section provides Tier 2 evaluation procedures that apply to structural connections: anchorage for normal forces, shear transfer, vertical components, interconnection

More information

ADVANCED PASSIVE CONTROL TECHNIQUES FOR RETROFIT OF EXISTING BUILDINGS IN SEISMIC ZONE

ADVANCED PASSIVE CONTROL TECHNIQUES FOR RETROFIT OF EXISTING BUILDINGS IN SEISMIC ZONE ADVANCED PASSIVE CONTROL TECHNIQUES FOR RETROFIT OF EXISTING BUILDINGS IN SEISMIC ZONE Fu Lin ZHOU 1, X Y GAO 2, W M YAN 3, Z G XU 4, W G LIU 5, J L XIE 6 And Joe CHUNG 7 SUMMARY A great number of existed

More information

International Journal of Scientific & Engineering Research, Volume 5, Issue 5, May ISSN

International Journal of Scientific & Engineering Research, Volume 5, Issue 5, May ISSN International Journal of Scientific & Engineering Research, Volume 5, Issue 5, May-2014 86 EFFECT OF DIFFERENT SHEAR WALL CONFIGURATIONS ON SEISMIC RESPONSE OF A MOMENT-RESISTING FRAME Anshul Sud 1, Raghav

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 07, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol., Issue, ISSN (online): - Importance of ing of Masonry and Effect of Soft Storey on Seismic Performance of R.C High Rise Building

More information

Thesis Proposal. Nasser Marafi. Center & Facility Service Building. St. Joseph Hospital of Orange Patient Care. Proposal

Thesis Proposal. Nasser Marafi. Center & Facility Service Building. St. Joseph Hospital of Orange Patient Care. Proposal St. Joseph Hospital of Orange Patient Care Center & Facility Service Building Proposal Professor Andres Lepage STRUCTURAL OPTION December 17th 2007 Executive Summary Thesis Proposal During the upcoming

More information

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION

FEMA P-593 STEP-BY STEP PRESCRIPTIVE RETROFIT FOR CRIPPLE WALL BRACING & ANCHORAGE TO FOUNDATION INTRODUCTION Objective of provisions: The provisions of IEBC Appendix Chapter A3 are intended to reduce hazard of earthquake-induced damage (IEBC A301.1). These provisions are not intended to eliminate

More information

A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool

A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool A Performance Based Evaluation of a Wall- Frame Structure Employing the Pushover Analysis Tool Kiran Kamath 1, Jose Camilo Karl Barbosa Noronha 2, Sachin Hirannaiah 3 Professor, Dept. of Civil Engineering,

More information

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower

Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower Linear and Nonlinear Seismic Analysis of a Tall Air Traffic Control (ATC) Tower A. Adnan, M. Vafaei & A.K. Mirasa Faculty of Civil Engineering, Universiti Teknologi Malaysia SUMMARY: Air Traffic Control

More information

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION:

SECTION SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED PART 1 GENERAL 1.1 DESCRIPTION: SECTION 13 05 41 SEISMIC RESTRAINT REQUIREMENTS FOR NON-STRUCTURAL COMPONENTS REVISED 1-25-13 PART 1 GENERAL 1.1 DESCRIPTION: A. Provide seismic restraint in accordance with the requirements of this section

More information

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale

Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale Nonlinear Pushover Analysis of Steel Frame Structure Dahal, Purna P., Graduate Student Southern Illinois University, Carbondale Abstract: The applicability of the SAP2000 software for the nonlinear pushover

More information

Panduit Corporation Tinley Park, Illinois. Outset and Inset Cabinets Seismic Load Rating and Anchorage Design

Panduit Corporation Tinley Park, Illinois. Outset and Inset Cabinets Seismic Load Rating and Anchorage Design Panduit Corporation Tinley Park, Illinois Outset and Inset Cabinets Seismic Load Rating and Anchorage Design February 13, 2013 Degenkolb Job Number B2439007.00 www.degenkolb.com 500 Degenkolb Engineers

More information

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011

INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011 INTERNATIONAL JOURNAL OF CIVIL AND STRUCTURAL ENGINEERING Volume 2, No 2, 2011 Copyright 2010 All rights reserved Integrated Publishing services Research article ISSN 0976 4399 Solution of Shear Wall Location

More information

PEER Tall Building Seismic Design Guidelines

PEER Tall Building Seismic Design Guidelines PEER Tall Building Seismic Design Guidelines Preliminary Design Recommendations & Performance Studies John Hooper Principal & Director of Earthquake Engineering Magnusson Klemencic Associates SEAW November

More information

DEFINITIONS AND GENERAL EQUIREMENTS

DEFINITIONS AND GENERAL EQUIREMENTS DEFINITIONS AND GENERAL EQUIREMENTS 1.1 INTRODUCTION 1.1.1 SCOPE The definitions providing meanings of different terms and general requirements for the structural design of buildings, structures, and components

More information

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls

Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls Pushover Analysis of High Rise Reinforced Concrete Building with and without Infill walls Phadnis P.P. 1, Prof. (Dr.) Kulkarni D. K. 2 1Research Scholar, Department of Technology, Shivaji University, Kolhapur,

More information

APPLICATION OF PERFORMANCE - BASED DESIGN TO UPGRADE UNSYMMETRICAL RC BUILDING

APPLICATION OF PERFORMANCE - BASED DESIGN TO UPGRADE UNSYMMETRICAL RC BUILDING Int. J. Struct. & Civil Engg. Res. 2013 Ravi K Sharma and S S Gehlot, 2013 Research Paper ISSN 2319 6009 www.ijscer.com Vol. 2, No. 3, August 2013 2013 IJSCER. All Rights Reserved APPLICATION OF PERFORMANCE

More information

AN ASSESSMENT OF SAFETY OF A REAL SIX STORIED R.C.C FRAME STRUCTURE BY NON LINEAR STATIC PUSHOVER ANALYSIS

AN ASSESSMENT OF SAFETY OF A REAL SIX STORIED R.C.C FRAME STRUCTURE BY NON LINEAR STATIC PUSHOVER ANALYSIS Proceedings of the 3 rd International Conference on Civil Engineering for Sustainable Development (ICCESD 2016), 12~14 February 2016, KUET, Khulna, Bangladesh (ISBN: 978-984-34-0265-3) AN ASSESSMENT OF

More information

Consideration of torsional irregularity in Modal Response Spectrum Analysis

Consideration of torsional irregularity in Modal Response Spectrum Analysis Earthquake Resistant Engineering Structures X 209 Consideration of torsional irregularity in Modal Response Spectrum Analysis O. A. Mohamed & O. A. Abbass Department of Civil Engineering, Abu Dhabi University,

More information

Available at: Last Modified: December 2012

Available at:  Last Modified: December 2012 6.3 Architectural Components 6.3.7 Chimneys and Stacks 6.3.7.1 Unreinforced Masonry Chimney Unreinforced masonry (URM) chimneys are extremely vulnerable to earthquake damage; their behavior has long been

More information

STATE UNIVERSITY CONSTRUCTION FUND

STATE UNIVERSITY CONSTRUCTION FUND STATE UNIVERSITY CONSTRUCTION FUND The following checklist show the general items required by the Agreement and the Program Directives. Unless included in the lump sum fee or the Schedule B of the Consultant

More information

Hilton Baltimore Convention Center Hotel Western Podium

Hilton Baltimore Convention Center Hotel Western Podium Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Thesis Proposal TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..

More information

Comparison of Chilean and US Seismic Design Provisions for Timber Structures

Comparison of Chilean and US Seismic Design Provisions for Timber Structures Comparison of Chilean and US Seismic Design Provisions for Timber Structures J. Daniel Dolan Professor and Director of Codes and Standards, Wood Materials and Engineering Laboratory, Washington Peter Dechent

More information

PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE

PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE PERIODS OF REINFORCED CONCRETE FRAMES DURING NONLINEAR EARTHQUAKE RESPONSE Arthur C HEIDEBRECHT And Nove NAUMOSKI SUMMARY This paper presents the results of a detailed evaluation of the relationships between

More information

CASE STUDY OF A 40 STORY BRBF BUILDING LOCATED IN LOS ANEGELES

CASE STUDY OF A 40 STORY BRBF BUILDING LOCATED IN LOS ANEGELES DESIGN INVESTIGATE REHABILITATE CASE STUDY OF A 40 STORY BRBF BUILDING LOCATED IN LOS ANEGELES Anindya Dutta, Ph.D., S.E. Ronald O. Hamburger, S.E., SECB www.sgh.com Background Study performed on behalf

More information

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS

EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS EVALUATION OF NONLINEAR STATIC PROCEDURES FOR SEISMIC DESIGN OF BUILDINGS By H.S. Lew 1 and Sashi K. Kunnath Presented at the rd Joint Meeting of the UJNR Panel on Wind and Seismic Effects ABSTRACT This

More information

Apparel Gallery Ltd.

Apparel Gallery Ltd. Apparel Gallery Ltd. 147-148, Norshinghpur, Asulia, Savar, Dhaka (23.929985N,90.304914E) 23 March 2014 1 2 Observations Building 1 Heavy loading due to raised floor area on Ground Floor 3 Building 1 Raised

More information

Distribution of Forces in Lateral Load Resisting Systems

Distribution of Forces in Lateral Load Resisting Systems Distribution of Forces in Lateral Load Resisting Systems Part 1. Vertical Distribution and Load Paths IITGN Short Course Gregory MacRae Many slides from 2009 Myanmar Slides of Profs Jain and Rai 1 Gravity

More information

Seismic Evaluation and Retrofit Manual MTPTC Training, April & May Build Change & Degenkolb Engineers

Seismic Evaluation and Retrofit Manual MTPTC Training, April & May Build Change & Degenkolb Engineers Seismic Evaluation and Retrofit Manual MTPTC Training, April & May 2011 Build Change & Degenkolb Engineers Section A: Introduction Page 2 Disclaimer These materials have been prepared for use by qualified

More information

HOTEL NORTHEAST U.S. JORDAN RUTHERFORD STRUCTURAL OPTION FACULTY ADVISOR DR. THOMAS BOOTHBY AE SENIOR THESIS APRIL 8, 2013

HOTEL NORTHEAST U.S. JORDAN RUTHERFORD STRUCTURAL OPTION FACULTY ADVISOR DR. THOMAS BOOTHBY AE SENIOR THESIS APRIL 8, 2013 HOTEL NORTHEAST U.S. JORDAN RUTHERFORD STRUCTURAL OPTION FACULTY ADVISOR DR. THOMAS BOOTHBY AE SENIOR THESIS APRIL 8, 2013 HOTEL N.E.U.S. BUILDING INFORMATION SITE Located in the Northeast United States

More information

Performance Based Seismic Design of Reinforced Concrete Building

Performance Based Seismic Design of Reinforced Concrete Building Open Journal of Civil Engineering, 2016, 6, 188-194 Published Online March 2016 in SciRes. http://www.scirp.org/journal/ojce http://dx.doi.org/10.4236/ojce.2016.62017 Performance Based Seismic Design of

More information

A Proposal on the Simplified Structural Evaluation Method for Existing Reinforced Concrete Buildings with Infilled Brick Masonry Walls

A Proposal on the Simplified Structural Evaluation Method for Existing Reinforced Concrete Buildings with Infilled Brick Masonry Walls A Proposal on the Simplified Structural Evaluation Method for Existing Reinforced Concrete Buildings with Infilled Brick Masonry Walls June 2017 Building Research Institute, Japan Matsutaro Seki Objective

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140)

PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140) PERFORMANCE STUDY OF RETROFITTED GRAVITY LOAD DESIGNED WALL FRAME STRUCTURES (SC-140) *A. Ahmed 1, K. H. Tan 1 1 Department of Civil and Environmental Engineering National University of Singapore, Singapore,

More information

PERFORMANCE ASSESMENT OF RC BUILDING FRAMES BY NON LINEAR ANALYSIS

PERFORMANCE ASSESMENT OF RC BUILDING FRAMES BY NON LINEAR ANALYSIS PERFORMANCE ASSESMENT OF RC BUILDING FRAMES BY NON LINEAR ANALYSIS Dain Thomas 1,Asst.Prof.Sruthi.K.Chandran 2 1 (Structural Engineering,Sreepathy Institute of Management and Technology, Vavanoor, India,

More information

CE 3150 Reinforced Concrete Design Design Project

CE 3150 Reinforced Concrete Design Design Project Problem Description For this design project you will work in your project groups to complete a partial design of an office building. Specifically, you will design and fully detail three components: 1.

More information

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online):

IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online): IJSRD - International Journal for Scientific Research & Development Vol. 2, Issue 09, 2014 ISSN (online): 2321-0613 Lateral Load Analysis of Shear Wall and Concrete Braced Multi- Storeyed R.C Frame with

More information

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis

Comparative Study on Concentric Steel Braced Frame Structure due to Effect of Aspect Ratio using Pushover Analysis 247 Comparative Study on Concentric Steel Structure due to Effect of using Pushover Analysis Kiran Kamath 1, Shruthi 2, Shashikumar Rao 2 1 Professor, Department of Civil Engineering, Manipal Institute

More information

ANALYTICAL INVESTIGATION ON THE PERFORMANCE OF TUBE-IN-TUBE STRUCTURES SUBJECTED TO LATERAL LOADS

ANALYTICAL INVESTIGATION ON THE PERFORMANCE OF TUBE-IN-TUBE STRUCTURES SUBJECTED TO LATERAL LOADS International Journal of Technical Research and Applications e-issn: 0-86, www.ijtra.com Volume, Issue4 (July-August 05), PP. 84-88 ANALYTICAL INVESTIGATION ON THE PERFORMANCE OF TUBE-IN-TUBE STRUCTURES

More information

CALIFORNIA BUILDING CODE

CALIFORNIA BUILDING CODE FINAL STATEMENT OF REASONS FOR PROPOSED BUILDING STANDARDS OF THE DIVISION OF THE SATATE ARCHTECT REGARDING THE CALIFORNIA BUILDING CODE CALIFORNIA CODE OF REGULATIONS, TITLE 24, PART 2 The Administrative

More information

DEVELOPMENT OF FLOOR DESIGN SPECTRA FOR OPERATIONAL AND FUNCTIONAL COMPONENTS OF CONCRETE BUILDINGS IN CANADA

DEVELOPMENT OF FLOOR DESIGN SPECTRA FOR OPERATIONAL AND FUNCTIONAL COMPONENTS OF CONCRETE BUILDINGS IN CANADA The 4 th World Conference on Earthquake Engineering October 2-7, 28, Beijing, China DEVELOPMENT OF FLOOR DESIGN SPECTRA FOR OPERATIONAL AND FUNCTIONAL COMPONENTS OF CONCRETE BUILDINGS IN CANADA M. Saatcioglu,

More information

International Journal of Scientific & Engineering Research, Volume 7, Issue 10, October ISSN Pushover Analysis of RC Building

International Journal of Scientific & Engineering Research, Volume 7, Issue 10, October ISSN Pushover Analysis of RC Building International Journal of Scientific & Engineering Research, Volume 7, Issue 10, October-2016 88 Pushover Analysis of RC Building Dona Mary Daniel, Shemin T. John Abstract In this study the seismic response

More information

Assessment of P-Delta Effect on High Rise Buildings

Assessment of P-Delta Effect on High Rise Buildings Assessment of P-Delta Effect on High Rise Buildings Prashant Dhadve 1, Alok Rao 2, Atul Rupanvar 3, Deokate K. 4, Admile P.R 5, Dr. Nemade. P. D. 6 1,2,3,4 under graduate student, Civil Engineering S.B.

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

SEISMIC DESIGN REQUIREMENTS FOR REINFORCED CONCRETE BUILDINGS

SEISMIC DESIGN REQUIREMENTS FOR REINFORCED CONCRETE BUILDINGS SEISMIC DESIGN REQUIREMENTS FOR REINFORCED CONCRETE BUILDINGS MODEL BUILDING CODES A model building code is a document containing standardized building requirements applicable throughout the United States.

More information

FEMA-310. Handbook for the Seismic Evaluation of Buildings, 1998

FEMA-310. Handbook for the Seismic Evaluation of Buildings, 1998 FEMA-310 Handbook for the Seismic Evaluation of Buildings, 1998 Introduction The American Society of Civil Engineers (ASCE) contracted with the Federal Emergency Management Agency (FEMA) to convert FEMA

More information

Shear Wall Analysis. Introduction. The Medical Office Building Malvern, PA 7

Shear Wall Analysis. Introduction. The Medical Office Building Malvern, PA 7 The Medical Office Building Malvern, PA 7 Shear Wall Analysis Introduction The current lateral system in the Medical Office Building consists of cast-in-place (CIP) concrete moment frames and torsion beams.

More information

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS

PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS PERFORMANCE BASED SEISMIC EVALUATION OF MULTI-STOREYED REINFORCED CONCRETE BUILDINGS USING PUSHOVER ANALYSIS S.P. AKSHARA Assistant Professor, Department of Civil Engineering, Federal Institute of Science

More information

Pushover analysis of RC frame structure using ETABS 9.7.1

Pushover analysis of RC frame structure using ETABS 9.7.1 IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) e-issn: 2278-1684,p-ISSN: 2320-334X, Volume 11, Issue 1 Ver. V (Feb. 2014), PP 08-16 Pushover analysis of RC frame structure using ETABS 9.7.1

More information

Seismic Performance of Multistorey Building with Soft Storey at Different Level with RC Shear Wall

Seismic Performance of Multistorey Building with Soft Storey at Different Level with RC Shear Wall Research Article International Journal of Current Engineering and Technology E-ISSN 2277 4106, P-ISSN 2347-5161 2014 INPRESSCO, All Rights Reserved Available at http://inpressco.com/category/ijcet Seismic

More information

HOW CONFINED MASONRY BUILDINGS FAIL IN EARTHQUAKES

HOW CONFINED MASONRY BUILDINGS FAIL IN EARTHQUAKES HOW CONFINED MASONRY BUILDINGS FAIL IN EARTHQUAKES DIGRESSION: How Confined Masonry Buildings Fail in Earthquakes Overturning (collapse) of masonry gable wall Out-of-plane failure of masonry wall In plane

More information

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012

AC R1 # Triangle Parkway Suite 100 Norcross, Ga Phone: Fax: AC R1. September 11, 2012 AC70-1012-R1 #12 AC70-1012-R1 #12 AC70-1012-R1 September 11, 2012 Mr. Brian Gerber Ms. Elyse Levy International Code Council Evaluation Service (ICC ES) 5360 Workman Mill Road Whittier, CA 90601 2256 RE:

More information

FEMA 356 Life Safety Building Performance Evaluation & PML Analysis

FEMA 356 Life Safety Building Performance Evaluation & PML Analysis FEMA 356 Life Safety Building Performance Evaluation & PML Analysis For 2 Dinkelspiel Station Ln. Atherton, California September 24, 2009 Prepared for: Prepared by: Town of Atherton Crosby Group Office

More information

SEISMIC PROVISIONS OF IBC 2006 AND ASCE 7-05

SEISMIC PROVISIONS OF IBC 2006 AND ASCE 7-05 Introduction This paper is meant for people studying for the ARE. Engineers and professors may not like the way some of the ideas are presented. They are meant to help understand the concepts and impacts

More information

Innovative Moment Resisting Frame System for Earthquake

Innovative Moment Resisting Frame System for Earthquake Website: www.ijetae.com (ISSN 225-2459, Volume 2, Issue 9, September 212) Innovative Moment Resisting Frame System for Earthquake S.M. Ashfaqul Hoq 1, Md. Ahsan Sabbir 2 1 Lecturer, Department of Civil

More information

BASE SHEAR CALCULATION OF RCC STRUCTURE

BASE SHEAR CALCULATION OF RCC STRUCTURE BASE SHEAR CALCULATION OF RCC STRUCTURE Hardik Desai 1,Taha bookseller 2, Prutha Vyas 3 1 Undergraduate student, 2 Undergraduate student, 3 Assistant professor Civil Engineering Department, Navrachna University,

More information

Seismic Retrofitting of Building with Soft Storey and Floating Column

Seismic Retrofitting of Building with Soft Storey and Floating Column Seismic Retrofitting of Building with Soft Storey and Floating Column Ganesh Kumbhar 1, Anirudhha Banhatti 2 1Department of Civil Engineering, G. H. Raisoni College of Engineering and Management, Wagholi,

More information

Best Buy Corporate Building D (4) Richfield, MN

Best Buy Corporate Building D (4) Richfield, MN Best Buy Corporate Building D (4) Thesis Proposal Professor Boothby December 12 th, 2008 Executive Summary: The Best Buy Corporate Building D is a 6 story building with a total area of 304,610 square feet.

More information

Comparative Study on Dynamic Analysis of Irregular Building with Shear Walls

Comparative Study on Dynamic Analysis of Irregular Building with Shear Walls Comparative Study on Dynamic Analysis of Irregular Building with Shear Walls Le Yee Mon Civil Engineering Department, Mandalay Technological University, Mandalay, Myanmar Abstract: South East Asia including

More information

SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL

SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL SEISMIC BEHAVIOUR OF RC BUILDING RESTING ON PLAIN AND SLOPING GROUND WITH BRACINGS AND SHEAR WALL Yashaswini R 1, Dr. Mahesh Kumar G 2 1M.Tech Student, CAD Structures, Shridevi Institute of Engineering

More information

Post-Disaster Safety Evaluations Using ATC-20/45

Post-Disaster Safety Evaluations Using ATC-20/45 Post-Disaster Safety Evaluations Using ATC-20/45 Presented by: Drew Martin, P.E., S.E. September 2, 2015 2015 APWA International Public Works Congress and Exposition Funded and Updated By: Office of Emergency

More information

3. CLASSIFICATION AND IMPLICATIONS OF DAMAGE

3. CLASSIFICATION AND IMPLICATIONS OF DAMAGE 3. CLASSIFICATION AND IMPLICATIONS OF DAMAGE 3.1 Summary of Earthquake Damage There are no modifications to the Guidelines or Commentary of Section 3.1 at this time. 3.2 Damage Types There are no modifications

More information

Seismic Damage Prediction of Reinforced Concrete Buildings Using Pushover Analysis

Seismic Damage Prediction of Reinforced Concrete Buildings Using Pushover Analysis Seismic Damage Prediction of Reinforced Concrete Buildings Using Pushover Analysis M.Mouzzoun 1, O.Moustachi 2, A.Taleb 3 1 PhD student, Mohammadia School of engineers, Rabat, Morocco, 2 Professor, Mohammadia

More information

STANDARD PLAN BULLETIN SP-2 (Structural)

STANDARD PLAN BULLETIN SP-2 (Structural) STANDARD PLAN BULLETIN SP-2 (Structural) Date: January 20, 2000 This Los Angeles Department of Building and Safety (LADBS) standard plan provides prescriptive details to facilitate the reconstruction of

More information

Structural Response Analysis of Reinforced Concrete Frame with Unreinforced Masonry Infill Walls

Structural Response Analysis of Reinforced Concrete Frame with Unreinforced Masonry Infill Walls Paper ID: SE 028 564 International Conference on Recent Innovation in Civil Engineering for Sustainable Development () Department of Civil Engineering DUET - Gazipur, Bangladesh Structural Response Analysis

More information

Seismic performance assessment of reinforced concrete buildings using pushover analysis

Seismic performance assessment of reinforced concrete buildings using pushover analysis IOSR Journal of Mechanical and Civil Engineering (IOSR-JMCE) ISSN: 2278-1684 Volume 5, Issue 1 (Jan. - Feb. 2013), PP 44-49 Seismic performance assessment of reinforced concrete buildings using pushover

More information

Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B

Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Building B Structural Comparison between Pan Joist Concrete and Steel Frame Systems for UMCP Student Housing Executive Summary The proposed thesis will include an investigation of two different alternative structural

More information

Seismic Performance and Design of Linked Column Frame System (LCF)

Seismic Performance and Design of Linked Column Frame System (LCF) Seismic Performance and Design of Linked Column Frame System (LCF) M. Malakoutian & J.W. Berman Department of Civil and Environmental Engineering, University of Washington, Seattle, WA, USA P. Dusicka

More information

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY

INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY INTERNATIONAL JOURNAL OF PURE AND APPLIED RESEARCH IN ENGINEERING AND TECHNOLOGY A PATH FOR HORIZING YOUR INNOVATIVE WORK SPECIAL ISSUE FOR NATIONAL LEVEL CONFERENCE "SUSTAINABLE TECHNOLOGIES IN CIVIL

More information