SAP Calculations. Project: Adjacent to Number 7 Dince Hill Close Exeter, Whimple, Devon, EX5 2TE
|
|
- Grace Ross
- 5 years ago
- Views:
Transcription
1 SAP Calculations Client: Stowford Homes Project: Adjacent to Number 7 Dince Hill Close Exeter, Whimple, Devon, EX5 2TE Contact: Jerry Gilby Coast 2 Coast Property Assessment jerryg@c2cpropertyassess.co.uk
2 SURVEY NOTES Survey Reference: 001 Prop Type Ref: Property: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE, SAP Rating: 75 C SAP version: SAP 2009, Regs Region: England and Wales (Part L1A 2010), Calculation Type: New Dwelling As Designed SURVEY NOTES - Last time updated on: Page 1 of 1 Based on the drawings provided and subsequent information provided by the developer, the design stage calculations show compliance with Part L1A Building Regulations The following assumptions have been made for the purpose of the calculations; 1. Heating and domestic hot water will be provided via a Worcester Greenstar 37cdi combi boiler with programmer, roomstats and TRVs 2. A Vent Axia Sentinel Kinetic Plus MHVR system or equivalent Appendix Q approved system will be installed. 3. An air pressure test result of 6.00 q50 or better will be achieved. 4. Glazing for windows will a have a u-value of 1.8 W/m 2 K or better. 5. Lighting will comply with current Building Regulations in respect of the provision of Low Energy Lighting. 13/6/12
3 Building Regulation Compliance Page 1 of 2 Survey Reference: 001 Prop Type Ref: Property: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE, SAP Rating: 75 C SAP version: SAP 2009, Regs Region: England and Wales (Part L1A 2010), Calculation Type: New Dwelling As Designed SUMMARY FOR INPUT DATA FOR New Build (As Designed) 1 TER and DER Fuel for main heating: Bulk LPG Fuel factor: 1.10 (LPG} Target Carbon Dioxide Emission Rate (TER) kg/m 2 Dwelling Carbon Dioxide Emission Rate (DER) kg/m 2 OK 2 Fabric U-values Element Average Highest External wall 0.21 (max. 0.30) 0.42 (max. 0.70) OK Floor 0.14 (max. 0.25) 0.14 (max. 0.70) OK Roof 0.15 (max. 0.20) 0.15 (max. 0.35) OK Openings 1.92 (max. 2.00) 2.40 (max. 3.30) OK 2a Thermal bridging Thermal bridging calculated using default y-value of Design air permeability Design air permeability at 50 pascals: 6.00 Maximum 10.0 OK 4 Heating efficiency Main heating system: Boiler system with radiators or underfloor - Bulk LPG Data from database Worcester Greenstar 37 CDi Combi boiler Efficiency: 90.4% SEDBUK2009 Minimum: 88.0% OK Secondary heating system: None 5 Cylinder insulation Hot water storage No cylinder 6 Controls Space heating controls: Programmer, room thermostat and TRVs OK Hot water controls: No cylinder Boiler interlock Yes OK 7 Low energy lights Percentage of fixed lights with low-energy 100% fittings: Minimum 75% OK 8 Mechanical ventilation Continuous supply and extract system Specific fan power: 0.49 Maximum 1.5 OK MVHR efficiency: 92%
4 Minimum: 70% OK 9 Summertime temperature Overheating risk (South West England): Slight OK Based On: Overshading: Windows facing North East: Windows facing South East: Windows facing South West: Windows facing North West: Ventilation rate: 3.00 Blinds/curtains: None 10 Key features Average 3.62 m 2, No overhang 8.82 m 2, No overhang 2.54 m 2, No overhang 2.54 m 2, No overhang External wall U-value 0.16 W/m 2 Floor U-value 0.14 W/m 2 Appendix Q: Vent Axia Kinetic Plus MHVR
5 Predicted Energy Assessment Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE Dwelling type: Bungalow, Detached Date of assessment: 13.Jun.2012 Produced by: Coast 2 Coast Property Assessment Total floor area: m 2 This document is a Predicted Energy Assessment for properties marketed when they are incomplete. It includes a predicted energy rating which might not represent the final energy rating of the property on completion. Once the property is completed, this rating will be updated and an official Energy Performance Certificate will be created for the property. This will include more detailed information about the energy performance of the completed property. The energy performance has been assessed using the Government approved SAP2009 methodology and is rated in terms of the energy use per square meter of floor area; the energy efficiency is based on fuel costs and the environmental impact is based on carbon dioxide (CO2) emissions. Energy Efficiency Rating Environmental Impact (CO2) Rating Very energy efficient - lower running costs (92 plus) (81-91) (69-80) (55-68) (39-54) (21-38) (1-20) A B C D E Not energy efficient - higher running costs EU Directive England & Wales 2002/91/EC The energy efficiency rating is a measure of the overall efficiency of a home. The higher the rating the more energy efficient the home is and the lower the fuel bills are likely to be. F G 75 Very environmentally friendly - lower CO2 emissions (92 plus) (81-91) (69-80) (55-68) (39-54) (21-38) (1-20) A B C D E F G Not environmentally friendly - higher CO2 emissions 81 EU Directive England & Wales 2002/91/EC The environmental impact rating is a measure of a home's impact on the environment in terms of carbon dioxide (CO2) emissions. The higher the rating the less impact it has on the environment.
6 Summary Information Survey Reference: 001 Prop Type Ref: Property: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE, SAP Rating: 75 C SAP version: SAP 2009, Regs Region: England and Wales (Part L1A 2010), Calculation Type: New Dwelling As Designed SUMMARY FOR INPUT DATA FOR New Build (As Designed) Page 1 of Property Type Bungalow, Detached 2.0 Number of Storeys Date Built Property Age Band 4.0 Sheltered Sides Sunlight/Shade Average or unknown 6.0 Measurements Internal Perimeter Internal Floor Area Average Storey Height Ground Floor: Living Area Thermal Mass Parameter Simple calculation 9.0 External Walls Description Construction U-Value Element Kappa Gross Area Nett Area External Wall 1 Wall to garage Cavity wall : plasterboard on dabs, AAC block, filled cavity, any outside structure Solid wall : dense plaster, insulation, any outside structure External Roofs Description Construction U-Value Element Kappa Gross Area Nett Area External Roof 1 Plasterboard, insulated at ceiling level HeatLoss Floors Description Construction U-Value Element Kappa Area Heat Loss Floor 1 Other Opening Types Description Data Source Type Glazing Glazing Gap Argon Filled Solar Trans Frame Type Frame Factor U value Opening Type 1 Opening Type 2 SAP table SAP table Window Half Glazed Door Double Low-E Soft 0.05 Double Low-E Soft mm No 0.63 PVC mm No 0.63 PVC Openings Name Opening Type Location Orientation Curtain Type Overhang Ratio Wide Overhang Width Height Count Area Curtain Closed North East South East South West North West Kitchen Door Window - Opening Type 1 Window - Opening Type 1 Window - Opening Type 1 Window - Opening Type 1 Half Glazed Door - Opening Type 2 External Wall 1 North East None 0 No External Wall 1 South East None 0 No External Wall 1 South West None 0 No External Wall 1 North West None 0 No External Wall 1 North East None 0 No
7 Entrance Door Half Glazed Door - Opening Type 2 External Wall 1 South West None 0 No Conservatory None 15.0 Draught Proofing Draught Lobby Yes 17.0 Thermal Bridging Default Y-value 0.15 Description 18.0 Pressure Testing Yes Designed q Property Tested? As Built q50 Same As Designed? 19.0 Mechanical Ventilation Mechanical Ventilation System Yes Present Approved Installation No Windows open in hot weather Windows half open Cross ventilation possible Yes Night Ventilation Yes Air change rate 3.00 Mechanical Ventilation data Type Database Type Balanced mechanical ventilation with heat recovery MV Reference Number Configuration 2 MVHR Duct Insulated Yes Manufacturer SFP 0.49 Duct Type Rigid MVHR Efficiency 92 Wet Rooms 2 Brand, Model 20.0 Fans, Open Fireplaces, Flues MHS SHS Other Total Number of Chimneys Number of open flues Number of intermittent fans 0 Number of passive vents 0 Number of flueless gas fires Cooling System No 22.0 Lighting Internal Total number of light fittings 26 Total number of L.E.L. fittings 26 Percentage of L.E.L. fittings External External lights fitted Yes Light and motion sensors Yes 23.0 Electricity Tariff Standard 24.0 Heating Systems Main Heating 1 Database Description Percentage of Heat Main Heating 2 None Description Percentage of Heat Community Heating Secondary Heating Water Heating Main Heating 1 Flue Gas Heat Recovery System No Waste Water Heat Recovery System No 1 Waste Water Heat Recovery System No 2 Solar Panel No 25.0 Main Heating 1 Database Ref. No Fuel Type Bulk LPG Main Heating BLW TestMethod SAP Code 104 Efficiency ( Split Efficiences ) % Efficiency ( Split Efficiences ) % In Winter 91.3 In Summer 81.2 Model Name Manufacturer Controls CBD
8 Delayed Start Stat No Sap Code 2106 Burner Control Boiler Compensator None HETAS approved System Oil Pump Inside FI Case FI Water Flue Type Balanced Smoke Control Area Fan Assisted Flue Yes Is MHS Pumped Pump in heated space Heat Emitter Radiators Underfloor Heating Electric CPSU Temperature Combi boiler type Standard Combi Combi keep hot type None Combi store type 27.0 Community Heating Space Community Heating Distribution Loss Distribution Loss Value Controls SAP Code Water Community Heating Distribution Loss Distribution Loss Value Charging Linked To Heat Use 28.0 Secondary Heating Description SHS efficiency % SAP Code HETAS Approved System Smoke Control Area Test Method Manufacturer Model Name 29.0 Water Heating HWP Water use <= 125 litres/person/day Yes SAP Code 901 Immersion Heater Summer Immersion Suplementary Immersion Immersion Only Heating Hot Water 29.1 Flue Gas Heat Recovery System Database ID Brand Model Details 29.2 Waste Water Heat Recovery System Total rooms with shower and/or bath 30.0 Hot Water Cylinder None Cylinder Stat Cylinder In Heated Space Independent Time Control Insulation Type Insulation Thickness Cylinder Volume Loss (kwh/day) Pipes insulation In Airing Cupboard 31.0 Solar Panel Solar Panel Area Area Type Panel Type n0, a1, A/G ratio Orientation Elevation Overshading Solar Storage Volume Pump electrically powered Combined Cylinder 32.0 Thermal Store None Thermal Store Pipework within a single casing 33.0 Photovoltaic Unit Apportioned KWh/Year 34.0 Wind Turbines Terrain Type Rural Wind Turbines Count
9 Apportioned Kwh/year Rotor Diameter Hub Height 35.0 Small-scale Hydro Electricity Generated Description Apportioned kwh/year 36.0 Special Features Energy Saved Fuel Saved Energy Used Fuel Used Description Monthly Air Change Rates Jan Feb Mar Apr May Jun Jul Aug Sep Oct Nov Dec 1060 Electricity 0 Vent Axia Kinetic Plus MHVR No Recommendations None Further measures to achieve even higher standards Solar water heating 61 C 77 B 83 Solar photovoltaic panels, 2.5 kwp 219 B 86 B 91 Wind turbine 78 B 89 A 94
10 U-value calculator report Survey Reference: 001 Type Ref: Project: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE SAP Rating: 75 C Building Elements: Roof Pitched roof - insulated at ceiling Roof Type: Pitched Roof, insulated flat ceiling Layer Description Thickness Lambda R Fraction Ext surface Layer 1 Roof space Main construction 0 mm % Layer 2 Mineral wool Main construction 150 mm % Corrections - Air Gap: Level 0, Fasteners: None or plastic Layer 3 Mineral wool quilt Main construction 150 mm % Bridging - Timber 150 mm % Corrections - Air Gap: Level 0, Fasteners: None or plastic Layer 4 Plasterboard, standard Main construction 13 mm % Layer 5 Plaster, standard Main construction 5 mm % Int surface Total resistance: Upper limit = m 2 K/W Lower limit = m 2 K/W Average = m 2 K/W U-value (unrounded) = 0.15 W/m 2 K Unheated space: None Total thickness: 318 mm U-value: 0.15 W/m 2 K
11 U-value calculator report Survey Reference: 001 Type Ref: Project: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE SAP Rating: 75 C Building Elements: Wall Layer Description Thickness Lambda R Fraction Ext surface Layer 1 Render - Cement and Sand Main construction 20 mm % Layer 2 Celcon Standard - Normal - Trad joint 10mm Main construction 100 mm % Bridging - Mortar 100 mm % Layer 3 Standard cavity Main construction 50 mm % Corrections - Cavity Unventilated, Emissivity: Normal Layer 4 Celotex CG5000 Main construction 100 mm % Corrections - Air Gap: Level 1, Fasteners: None or plastic Layer 5 Celcon Solar - Normal - Trad joint 10mm Main construction 100 mm % Bridging - Mortar 100 mm % Layer 6 airspace/plaster dabs Main construction 15 mm % Bridging - Mortar 15 mm % Corrections - Cavity Unventilated, Emissivity: Normal Layer 7 Gyproc Wallboard (*9.5mm) Main construction 10 mm % Corrections - Air Gap: Level 1, Fasteners: None or plastic Layer 8 Plaster, standard Main construction 5 mm % Int surface Total resistance: Upper limit = m 2 K/W Lower limit = m 2 K/W Average = m 2 K/W U-value (unrounded) = 0.16 W/m 2 K Unheated space: None Total thickness: 400 mm U-value: 0.16 W/m 2 K
12 U-value calculator report Survey Reference: 001 Type Ref: Project: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE SAP Rating: 75 C Building Elements: Wall Layer Description Thickness Lambda R Fraction Ext surface Layer 1 Celcon Solar - Normal - Trad joint 10mm Main construction 215 mm % Bridging - Mortar 215 mm % Layer 2 airspace/plaster dabs Main construction 15 mm % Bridging - Mortar 15 mm % Corrections - Cavity Unventilated, Emissivity: Normal Layer 3 Gyproc Wallboard (*9.5mm) Main construction 10 mm % Corrections - Air Gap: Level 1, Fasteners: None or plastic Layer 4 Plaster, standard Main construction 5 mm % Int surface Total resistance: Upper limit = m 2 K/W Lower limit = m 2 K/W Average = m 2 K/W U-value (unrounded) = 0.42 W/m 2 K Unheated space: Garage Total thickness: 245 mm U-value: 0.42 W/m 2 K
13 U-value calculator report Survey Reference: 001 Type Ref: Project: Adjacent to Number 7, Dince Hill Close, Whimple, Exeter, Devon, EX5 2TE SAP Rating: 75 C Building Elements: Floor Floor - suspended beam-and-block floor Floor Type: Suspended Floor Area = m 2, Perimeter = m, Wall thickness = mm, Soil: Depth of underfloor space below ground:0.200 m Floor wind shielding: Average (suburban) Floor height above ground:h = m U-value of walls above ground:uw = m Ventilation openings per perimeter length:e = % Mean wind speed:v = m/s Resistance on solum:rg = m 2 K/W Layer Description Thickness Lambda R Fraction Ext surface Layer 1 Layer 2 Layer 3 AAC (600 kg/m3)/ concrete Main construction 150 mm % Bridging - Mortar 150 mm % Celotex GA4000 Main construction 100 mm % Screed Corrections - Air Gap: Level 1, Fasteners: None or plastic Main construction 65 mm % Int surface Total resistance: Upper limit = m 2 K/W Lower limit = m 2 K/W Average = m 2 K/W Unheated space: None U-value (unrounded) = 0.14 W/m 2 K Total thickness: 315 mm U-value: 0.14 W/m 2 K
SAP Calculations. Project: Conversion of the Royal Oak Inn OSWESTRY, Kinnerley Dovaston, Shropshire, SY10 8DP
SAP Calculations Mr P Mellor Project: Conversion of the Royal Oak Inn OSWESTRY, Kinnerley Dovaston, Shropshire, SY10 8DP Contact: Julie Lock Energy Surveyor - Shropshire Council 01743 258748 Predicted
More informationBuilding Regulation Compliance Page 1 of 11
Building Regulation Compliance Page 1 of 11 Survey Reference: RNW/09.97 Prop Type Ref: New Build Property: Plot 9, High Trees, The Bailey, Skipton, BD23 SAP Rating: 84 B CfSH Results Version: ENE1 Credits:
More informationSAP Calculations. M & T Homes Limited. Project: Plot 2, Wombourne Road Wombourne, Swindon, South Staffordshire, DY3 4NB
SAP Calculations Client: M & T Homes Limited Project: Plot 2, Wombourne Road Wombourne, Swindon,, DY3 4NB Contact: Geoff Williams ECCO2 Limited geoffwilliams@ecco2ltd.co.uk Building Regulation Compliance
More informationSAP Calculations. Acheson Construction. Project: Plot 8, Neils View Maiden Newton. Contact: James Frampton Trinity Architecture
SAP Calculations Client: Acheson Construction Project: Plot 8, Neils View Maiden Newton Contact: James Frampton Trinity Architecture james@trinarch.com CODE FOR SUSTAINABLE HOMES - CfSH November 2010 Page
More informationSAP Calculations. Draft SAP Project: Bungalow Undercliff. Contact: Sandra Hardwick
SAP Calculations FitzArchitects Draft SAP 08.12.2015 Project: Bungalow Undercliff Contact: Sandra Hardwick Predicted Energy Assessment Page 2 of 16 Bungalow, Undercliff, Cleadon, SR6 7UX Dwelling type:
More informationSAP Report Submission for Building Regulations Compliance
SAP Report Submission for Building Regulations Compliance Client: BAUHU Project: 1 Final Design South, Plug & Play Modular House Contact: Guy Smith Easy EPC admin@easyepc.org Report Issue Date: 16/03/2017
More informationFull SAP Calculation Printout
Users Ref: Property: 7869-0001-0001158 Standard, 01, Example, example, example Full SAP Calculation Printout Issued on: 29.October.2008 Prop Type Ref: TER: 22.13 DER: 22.10 SAP Rating: 80 C SAP Energy
More informationSAP Calculations. Project: SITE 1 PHASE 2 MOYLAGH MEADOWS, MOYLAGH ROAD, BERAGH. Contact:
SAP Calculations Client: CHIEFTAN HOMES Project: SITE 1 PHASE 2 MOYLAGH MEADOWS, MOYLAGH ROAD, BERAGH Contact: Building Regulation Compliance Page 2 of 29 Property Reference: MOYLAGH MEADOWS, BERAGH Survey
More informationSAP. Standard Assessment Procedure for assessing the energy performance of dwellings. As Designed SAP. Redstone House
SAP Standard Assessment Procedure for assessing the energy performance of dwellings As Designed SAP Redstone House Redstone Road, Narberth SA67 7ES SAP Standard Assessment Procedure for assessing the energy
More informationAs Built SAP Report. New Dwelling E SITE ADDRESS:- 39 The Old Common Chalford Stroud Gloucestershire GL6 8HH
SITE ADDRESS:- 39 The Old Common Chalford Stroud Gloucestershire GL6 8HH As Built SAP Report New Dwelling E-1112-004 Mark Sheehan Building Consultancy Limited R egistered in England No. 5716834 Contents
More informationSAP Calculations. Persimmon South Coast. Project: Larcombe Road, Petersfield. Contact: George Leadley The FES Group
SAP Calculations Client: Persimmon South Coast Project: Larcombe Road, Petersfield Contact: George Leadley The FES Group george.leadley@thefesgroup.com Building Regulation Compliance Page 2 of 42 Property
More informationRegulations Compliance Report
Regulations Compliance Report Approved Document L1A 21 edition assessed by Stroma FSAP 29 program, Version: 1.5..32 Printed on 17 February 213 at 2:25:45 Project Information: Assessed By: Behdad Yazdani
More informationConversion SAP Checklist
Version 1.0 April 2016 Conversion SAP Checklist Call us today on 0800 917 8922 to speak with an adviser or visit Conversion SAP Checklist This checklist is split into three sections. Section 1 Project/dwelling
More informationThe calculation procedure will continue to be known as SAP 2005 but the SAP version number is incremented from 9.80 to 9.81.
Amendments to SAP 2005 (version 9.81) April 2008 The calculation procedure will continue to be known as SAP 2005 but the SAP version number is incremented from 9.80 to 9.81. 1 Very little overshading The
More informationABBE LEVEL 3 DIPLOMA IN ON CONSTRUCTION ENERGY ASSESSMENT ABBE LEVEL 3 CERTIFICATE IN DOMESTIC ON CONSTRUCTION ENERGY ASSESSMENT (QCF)
E LEVEL 3 IPLOM IN ON ONSTRUTION ENERGY SSESSMENT E LEVEL 3 ERTIFITE IN OMESTI ON ONSTRUTION ENERGY SSESSMENT (QF) SMPLE EXMINTION QUESTIONS The purpose of this document is to provide examples of typical
More informationThis draft design submission has been prepared from plans and specifications and may not reflect the property as constructed.
This Design Draft submission has been prepared by a Competent, registered with Faero Ltd. Faero Ltd. Scheme membership covers Criterion 1 of this checklist, that is, the requirement for the predicted carbon
More information> Performance requirements: Part L UK vs Energiesprong vs Passivhaus.
> Performance requirements: Part L UK vs Energiesprong vs Passivhaus. Introduction The purpose of this paper is to highlight and compare the difference in performance requirements between UK Building Regulations
More informationRdSAP Classification. New Transaction Types are now available. There are now the options of RHI Application and ECO Assessment
RdSAP 9.92 RdSAP is being upgraded to the new calculation engine of RdSAP 9.92 on Sunday 7 th December and there will be a number of changes to iq-energy to reflect this. The guidance below shows the changes
More informationNEARLY ZERO ENERGY BUILDING RETROFIT SAP Dr Luisa Brotas
NEARLY ZERO ENERGY BUILDING RETROFIT SAP 2012 Dr Luisa Brotas 4-8 July 2016 SAP EDITION 2012 SAP is the Government sstandard Assessment Procedure for Energy Rating of Dwellings. Assesses the energy performance
More informationDefining a Fabric Energy Efficiency Standard for zero carbon homes
Defining a Fabric Energy Efficiency Standard for zero carbon homes Appendix A Work Group 1 Form and Fabric The views and recommendations within this report are those of the Task Group and do not necessarily
More informationGuidance on U Values from Domestic Heating Design Guide
Guidance on U Values from Domestic Heating Design Guide The following U Values are from the Domestic Heating Design Guide, and the complete publication is available for purchase from members of the Domestic
More informationDwelling Energy Assessment Procedure (DEAP) Survey Guide
Dwelling Energy Assessment Procedure (DEAP) Survey Guide VERSION 2.1 DEAP is the official procedure for the calculation of energy performance of dwellings in Ireland for the purposes of producing Building
More informationEDEM detail description part 1: inputs and outputs
EDEM detailed description: Part 1 - inputs and outputs. Summary EDEM is a flexible approach to mapping the possible building carbon and energy performance universe in terms of a matrix of simulation models.
More informationThe effect of Building Regulations (Part L1 2002) on existing dwellings
GENERAL INFORMATION LEAFLET 70 The effect of Building Regulations (Part L1 2002) on existing dwellings Information for installers and builders for extensions and alterations in England and Wales " Insulation
More informationMicrogeneration Installation Standard : MCS 024 SOLAR DOMESTIC HOT WATER ENERGY CALCULATION. to be used in conjunction with MIS 3001:
Microgeneration Installation Standard : MCS 024 SOLAR DOMESTIC HOT WATER ENERGY CALCULATION to be used in conjunction with MIS 3001: REQUIREMENTS FOR CONTRACTORS UNDERTAKING THE SUPPLY, DESIGN, INSTALLATION,
More informationSAP Conventions. 12 September 2012 (v4.0)
SAP Conventions 12 September 2012 (v4.0) Conventions apply to all SAP versions throughout the UK except where otherwise indicated under 'Limitations'. Conventions applied for design stage calculations
More informationTable P1: Effective air change rate. Trickle vents only. Windows fully open. Windows slightly open (50 mm) Windows open half the time
Appendix P: Assessment of internal temperature in This appendix provides a method for assessing the propensity of a house to have high internal temperature in hot weather. It does not provide an estimate
More informationProject name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles
http://lowenergybuildings.org.uk Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles Project Description Projected build start date
More informationatspaceltd.co.uk SBEM Checklist Version 1.0 January 2017 Call us today on to speak with an adviser or visit atspaceltd.co.
Version 1.0 January 2017 SBEM Checklist Call us today on 0800 917 8922 to speak with an adviser or visit SBEM Checklist This checklist is split into four sections. Section 1 Project/Client details. Section
More informationEngineers Ireland Cork Region CPD lecture series
Engineers Ireland Cork Region CPD lecture series NZEB and Emerging Legislation & SEAI s Deep Retrofit Pilot Programme Orla Coyle NZEB Programme Manager Conor Hanniffy Deep Retrofit Pilot Programme Manager
More informationBRE RdSAP v9.91 software QSAP v9.0.0 April 2012
BRE RdSAP v9.91 software QSAP v9.0.0 April 2012 BREC Accreditation Scheme Part of the BRE Trust Q-SAP software & EPC changes Data Entry New data items Option for U-value entry Recommendations Reduced text
More informationMicrogeneration Installation Standard : MCS 024 SOLAR DOMESTIC HOT WATER ENERGY CALCULATION. to be used in conjunction with MIS 3001:
Microgeneration Installation Standard : MCS 024 SOLAR DOMESTIC HOT WATER ENERGY CALCULATION to be used in conjunction with MIS 3001: REQUIREMENTS FOR CONTRACTORS UNDERTAKING THE SUPPLY, DESIGN, INSTALLATION,
More informationProject name Old Dover Road Project summary Whole house retrofit and formation of new habitable roof structure
http://lowenergybuildings.org.uk Project name Old Dover Road Project summary Whole house retrofit and formation of new habitable roof structure Project Description Projected build start date Projected
More informationDwellings Energy Assessment Procedure (DEAP) for Building Regulations Compliance. Kevin O Rourke Head, Built Environment Sustainable Energy Ireland
IBCI Conference 2007: Bunratty Shannon Shamrock Hotel 22-23 March 2007 Dwellings Energy Assessment Procedure (DEAP) for Building Regulations Compliance Kevin O Rourke Head, Built Environment Sustainable
More informationSAP WorkSheet: New dwelling design stage
User Details: Assessor Name: Marco Valori Stroma Number: STRO7212 Software Name: Stroma FSAP 29 Software Version: Version: 1.4..72 Address :, Fife, KY11 4HT 1. Overall dwelling dimensions: Property Address:
More informationRadian Group. Performance Standards. Date November Author Rachel Mitchell. Version Final (V2)
Radian Group Performance Standards Date November 2011 Author Rachel Mitchell Version Final (V2) Radian Building performance standards Contents Introduction... 3 Design considerations for Radian Housing...
More informationProject Description. Projected build start date 15 Aug 2011 Projected date of occupation 19 Dec Existing external wall construction
http://lowenergybuildings.org.uk Project name Redlands Project summary Deep retrofit of 1955 brick house in Devon based on EnerPHit standard. House had old gas boiler, double glazing, cavity wall insulation
More informationProject name SOLAR HOUSE 80/50 Project summary
http://lowenergybuildings.org.uk Project name SOLAR HOUSE 80/50 Project summary Project Description Projected build start date 01 Mar 2010 Projected date of occupation 19 Jul 2010 Project stage Under construction
More informationSAP 2012 Conventions. 17 May 2016 (v 6.1) Conventions apply to SAP 2012 throughout the UK except where otherwise indicated under 'Limitations'.
SAP 2012 Conventions 17 May 2016 (v 6.1) Conventions apply to SAP 2012 throughout the UK except where otherwise indicated under 'Limitations'. Conventions applied for design stage calculations submitted
More informationCODE FOR SUSTAINABLE HOMES GUIDE TO MEET CODE LEVELS 3-6
CODE FOR SUSTAINABLE HOMES GUIDE TO MEET CODE LEVELS 3-6 File = Code-G2 A specification guide to meeting Code for Sustainable Homes Levels 3-6. Please note, this is meant as a guide only. Each site and
More informationBUILDING REGULATIONS PART L 2011 PROVISIONS & COSTS (STANDARD 3-BED SEMI-D, CIRCA 120 SQM)
BUILDING REGULATIONS PART L 2011 PROVISIONS & COSTS (STANDARD 3-BED SEMI-D, CIRCA 120 SQM) NOV 2012 OVERALL PRIMARY ENERGY, CO 2 & RENEWABLES TGD L 2005-2013 2005 2007/8 2011 2013? CO 2 % 100% 69% 46%
More informationPart L Review New Domestic Buildings Tom Lelyveld, AECOM
Part L Review New Domestic Buildings 2014 Tom Lelyveld, AECOM 11 th -13 th February 2014 What I will be talking about Introduction Background Key changes to Part L1A 2014 meeting the five new-build compliance
More informationEnergy Performance Certificate
Energy Performance Certificate Flat 59 Richmond Court 200 Sloane Street LONDON SW1X 9QU Dwelling type: Date of assessment: Date of certificate: Reference number: Total floor area: Mid-floor flat 24 February
More information# Limitations Topic Conventions Issue date
SAP 2012 Conventions 01 September 2018 (v 8.0) Conventions apply to SAP 2012 throughout the UK except where otherwise indicated under 'Limitations'. Conventions applied for design stage calculations submitted
More informationRdSAP Conventions for RdSAP 9.92
RdSAP Conventions for RdSAP 9.92 Issued 10 August 2015 (v8.1) New and amended conventions for v8.0 indicated by light blue background. Note: This list will be extended as appropriate. It contains additional
More informationElmhurst Energy RdSAP Survey Form
Elhurst Energy RdSAP Survey For Northern Ireland v9.91 Property Address......... Postcode:...Date of Survey:... Surveyor Nae:... RRN:... Surveyor ID : Property Tenure: Owner-occupied Rented (social) Rented
More informationBuilding Regulations - Part L (2002 Edition) User Guide
Building Regulations - Part L (2002 Edition) User Guide IES Virtual Environment Last update: Version 5.9 Copyright 2014 Integrated Environmental Solutions Limited. All rights reserved. No part of the manual
More informationOverview of DEAP Energy Rating of New Domestic Dwellings to IBCI Conference March 2008
IBCI Conference- Westport March 2008 Overview of DEAP Energy Rating of New Domestic Dwellings to IBCI Conference March 2008 Dr. Michael McLoughlin Department of Civil Engineering Athlone Institute of Technology
More informationAppendix S: Reduced Data SAP for existing dwellings
Appendix S: Reduced Data SAP for existing dwellings Reduced Data SAP (RdSAP) has been developed by government for use in existing dwellings based on a site survey of the property, when the complete data
More informationEnergy Performance Certificate
Energy Performance Certificate Dwelling type: Date of assessment: Date of certificate: Reference number: Total floor area: Mid-floor flat 09 December 2008 11 December 2008 0018-7944-6282-5358-5070 57 m²
More informationDomestic Green Deal Advice Training
Domestic Green Deal Advice Training Appendix T, PAS 2030, Building Physics, Regulations and Energy Efficient Lighting Appendix T, PAS 2030, and Funding Energy Efficiency Measures Appendix T What Appendix
More informationBRE Client Report. Ofgem Deemed Scores Methodology. Prepared for: Ofgem 9 Millbank, London, SW1P 3GE. BRE Watford, Herts WD25 9XX
BRE Client Report Ofgem Deemed Scores Methodology Prepared for: Ofgem Date: 26 Oct 2016 Report Number: P103305-1001 Issue: 4 BRE Watford, Herts WD25 9XX Customer Services 0333 321 8811 Prepared for: Ofgem
More informationConventions (v 10.0) for RdSAP 9.92 and RdSAP 9.93
Conventions (v 10.0) for RdSAP 9.92 and RdSAP 9.93 This document contains amended and additional conventions (v 10.0) applicable to the RdSAP 2012 version 9.92 and is aligned with the RdSAP version 9.93.
More informationCHAPTER 13: Sustainability
CONTENTS 13.1 THE CODE FOR SUSTAINABLE HOMES 13.2 LOW CARBON / LOW ENERGY HOMES 13.3 AIR TIGHTNESS AND ROBUSTNESS 13.4 RENEWABLE ENERGY SOURCES Chapter 13 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS
More informationCONSTRUCTION PROCESS. Rowner Research Project Phase One. March /5
CONSTRUCTION PROCESS Rowner Research Project Phase One March 2014 3/5 The Rowner research project was undertaken in Gosport and spanned from 2009-2013. The Project was funded by the Technology Strategy
More informationCODE FOR SUSTAINABLE HOMES GUIDE TO MEET CODE LEVELS 3-6
CODE FOR SUSTAINABLE HOMES GUIDE TO MEET CODE LEVELS 3-6 File = Code-G2 A specification guide to meeting Code for Sustainable Homes Levels 3-6. Please note, this is meant as a guide only. Each site and
More informationOne Size Fits All. Insulation A GUIDE TO BUILDING REGULATIONS / STANDARDS COMPLIANCE FOR NEW DWELLINGS USING STRUCTURAL INSULATED PANELS (SIPS)
Insulation Second Issue April 2018 One Size Fits All A GUIDE TO BUILDING REGULATIONS / STANDARDS COMPLIANCE FOR NEW DWELLINGS USING STRUCTURAL INSULATED PANELS (SIPS) Low Energy Low Carbon Buildings 2
More informationModule 15. Country Specific Legislation
Module 15 Country Specific Legislation Module 15 Country Specific Legislation On completion of this module learners will be able to: List the main pieces of legislation and standards which affect the energy
More informationEnergy Efficiency in Buildings SANS XA & SANS 204. Project Details
Energy Efficiency in Buildings SANS 10400-XA & SANS Competant Person Kobus Burger SACAP Reg.. D015 Project Details Type of Project ADDITION Street Address 106 Panorama Ave. Rooihuiskraal Erf Description
More informationSAP 2012 Conventions. 31 August 2017 (v 7.01) Conventions apply to SAP 2012 throughout the UK except where otherwise indicated under 'Limitations'.
SAP 2012 Conventions 31 August 2017 (v 7.01) Conventions apply to SAP 2012 throughout the UK except where otherwise indicated under 'Limitations'. Conventions applied for design stage calculations submitted
More informationApproved Document L1A and L2A
Guide to: Approved Document L1A and L2A For England and Wales NEWBUILD Conservation of fuel and power APPROVED DOCUMENTL1A Conservation of fuel and power APPROVED DOCUMENTL2A Talk to the SIG360 team at
More informationProject Description. Projected build start date Projected date of occupation. Existing external wall construction.
http://lowenergybuildings.org.uk Project name Admirals Hard Project summary FINALIST of the UK Passivhaus Awards 2015 - Situated on the Stonehouse peninsula, by the banks of the River Tamar, Number 3 Admirals
More informationEnergy efficiency and the Code for Sustainable Homes
CE290 Energy efficiency and the Code for Sustainable Homes Level 3 Also available: Energy efficiency guidance for level 4 Energy efficiency guidance for levels 5 and 6 Contents 1. Introduction 3 1.1 The
More informationBuilding Typology Brochure England September 2014
Building Typology Brochure England September 2014 Disclaimer The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion of the European
More informationA Design Guide to Part L: 2013
A Design Guide to Part L: 2013 The very fabric of new home energy efficiency Contents Foreword Foreword A revision to Approved Document L (Conservation of Fuel and Power) of the English Building Regulations
More informationUpgrading To An A-Rated Home
Upgrading To An A-Rated Home Homeowner Guide HOW SEAI CAN HELP YOU AND YOUR HOME The Sustainable Energy Authority of Ireland (SEAI) is Ireland s national energy authority, investing in and delivering appropriate,
More informationRdSAP Conventions. Issued 22 October 2014 (v7.0) New and amended conventions for v7.0 indicated by light blue background.
RdSAP Conventions Issued 22 October 2014 (v7.0) New and amended conventions for v7.0 indicated by light blue background. Appendix 1 on evidence requirements for quality assurance purposes has been added.
More informationThe effect of Building Regulations (Part L1 2002) on existing dwellings
Energy Efficiency Best Practice in Housing The effect of Building Regulations (Part L1 2002) on existing dwellings Information for installers and builders for extensions and alterations in England and
More informationSAP: The Essential Guide For Dwelling Designers And Architects By Mike Andrews
SAP: The Essential Guide For Dwelling Designers And Architects By Mike Andrews The overall aim is to give the dwelling designer a better understanding of what SAP is, how it is used to demonstrate compliance
More information6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services
domestic energy contents 2007 Contents 6.0 Introduction 6.1 Carbon dioxide emissions 6.2 Building insulation envelope 6.3 Heating system 6.4 Insulation of pipes, ducts and vessels 6.5 Artificial and display
More informationECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES
ECO-RETROFITTING VERY OLD DWELLINGS: CURRENT AND FUTURE ENERGY AND CARBON PERFORMANCE FOR TWO UK CITIES HANIYEH MOHAMMADPOURKARBASI, STEVE SHARPLES School of Architecture, University of Liverpool, Liverpool,
More informationEngland Building Regulations Part L 2013
England Building Regulations Part L 2013 Domestic buildings Tom Lelyveld, David Ross 08 October 2013 Content Introduction Background Changes to meeting the five new-build compliance steps Existing dwellings
More informationProject Description. Projected build start date 19 Apr 2010 Projected date of occupation 30 Sep
http://lowenergybuildings.org.uk Project name LB Greenwich - How low can we go? Project summary Our project has sought to produce a retrofit solution which is practical to build, easy to run and maintain,
More informationGreat Ocean Rd Ice Creamery
Great Ocean Rd Ice Creamery BCA Section J - JV3 Compliance Report Revision: 01 Job No: 2171 Date: 7 July 2015 ADP Consulting Pty Ltd Level 10, 10 Queens Rd, Melbourne Vic 3004 www.adpconsulting.com.au
More information6.4 Insulation of pipes, ducts and vessels. 6.6 Mechanical ventilation and air conditioning. 6.7 Commissioning building services
domestic energy contents 2007 Contents 6.0 Introduction 6.1 Carbon dioxide emissions 6.2 Building insulation envelope 6.3 Heating system 6.4 Insulation of pipes, ducts and vessels 6.5 Artificial and display
More informationBREDEM-12 Model description 2001 update
BRE Garston, Watford, WD25 9XX 2002 BREDEM-12 Model description 2001 update B R Anderson, P F Chapman, N G Cutland*, C M Dickson*, G Henderson, J H Henderson*, P J Iles*, L Kosmina and L D Shorrock* *BRE
More informationECOHOUSES - 21 st Century Ideal Buildings Minimal Imported Energy Safe in Extreme Climates Low running Costs
ECOHOUSES - 21 st Century Ideal Buildings Minimal Imported Energy Safe in Extreme Climates Low running Costs Susan Roaf, Professor of Architectural Engineering, Heriot Watt University, Edinburgh, s.roaf@hw.ac.uk
More informationd1b standard construction drawings new build aerated PART fill 6 digit product code unique to Travis Perkins Group
new build standard construction drawings d1b aerated PART fill 6 digit product code unique to Travis Perkins Group 1 Welcome to Sustainable Building Solutions (SBS) is a specialist division of the Travis
More informationResults from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments
Results from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments Charles Yousif Institute for University of Malta with Celia Pérez
More informationProject Description. Projected build start date 01 Mar 2010 Projected date of occupation 01 Aug Energy target.
http://lowenergybuildings.org.uk Project name Larch House, Ebbw Vale, Wales Project summary The Larch House, designed by bere:architects, is the UKs first zero carbon (code 6), low cost, Certified Passivhaus,
More informationRefurbishing cavity-walled dwellings
Energy Efficiency Best Practice in Housing Refurbishing cavity-walled dwellings A summary of Best Practice how to achieve better energy efficiency in existing housing measures to improve efficiency, reduce
More informationInsulation options. Calculating U-Values
April 2017 Data Sheet 8 Aggregate concrete blocks External walls thermal performance Uniclass L3221 :A4 CI/SfB EPIC F611 :X221 Ff2 (Ajv) Concrete Block Association The Old Rectory, 8 Main Street, Glenfield
More informationProject name Fulford Passivhaus, York Project summary New-build singe-family detached house for individual clients. Certified as Passivhaus Plus.
http://lowenergybuildings.org.uk Project name Fulford Passivhaus, York Project summary New-build singe-family detached house for individual clients. Certified as Passivhaus Plus. Project Description Projected
More informationProject Description. Projected build start date 10 Sep 2012 Projected date of occupation 03 May
http://lowenergybuildings.org.uk Project name Bristol Retrofit Project summary A full thermal retrofit of a mid-century, three-storey property built into a hill and located within a Conservation Area in
More informationBuilding Control. A Guide to Compliance When Designing Domestic Extensions
Building Control Technical Guidance Leaflet No. 18 Approved Document L1B 2010 Conservation of Fuel and Power This leaflet is one of a series produced by the Hertfordshire Building Control Technical Forum
More informationDepartment of Finance and Personnel Building Regulations (Northern Ireland) October 2012
Department of Finance and Personnel www.dfpni.gov.uk Building Regulations (Northern Ireland) 2012 G u i d a n c e Technical Booklet F1 Conservation of fuel and power in dwellings October 2012 Contents
More informationConsultation Paper: CONSP:13
SAP SUPPORTING DOCUMENT Consultation Paper: CONSP:13 Data on installation costs of measures for use in EPCs Issue 1.0 This document is the property of the Building Research Establishment Ltd (BRE), who
More informationThe Building Regulations Part L Conservation of Fuel & Power 2013 Edition
The Building Regulations 2010 Part L Conservation of Fuel & Power 2013 Edition Without looking into the technical input for SAP etc (subject to a further presentation), what does it mean in practical terms
More informationProject Description. Projected build start date 03 May 2010 Projected date of occupation 06 Aug
http://lowenergybuildings.org.uk Project name Retrofit - Appledore, Ashford Project summary The key project approach is to develop a solution that uses complementary technologies and techniques, and primarily
More informationProject Description. Projected build start date 24 Dec 2004 Projected date of occupation. Energy target. Existing external wall construction
http://lowenergybuildings.org.uk Project name Withy Cottage Project summary Timber Frame & Straw Bale self build with thermal bridge free construction (other than door and window frames). Simple flat raft
More informationExternal Walls Thermal Performance
External Walls Thermal Performance Data Sheet 8 October 2017 Uniclass L3221 :A4 EPIC F611 :X221 CI/SfB Ff2 (Ajv) Introduction This data sheet gives guidance for the specification of blocks in conjunction
More informationBuilding Regulations Part L1A (2006)
PART L1A GUIDE ENGLAND & WALES MAY 2006 High performance insulation for new mixed development housing Building Regulations Part L1A (2006) COST EFFECTIVE THERMAL SOLUTIONS House Type A House Type B House
More informationBuilding Regulations and the Future of Energy Efficient Buildings. Chris Hughes Programme Manager Energy Performance of Buildings Directive
Building Regulations and the Future of Energy Efficient Buildings Chris Hughes Programme Manager Energy Performance of Buildings Directive Overview SEAI Energy Efficiency Building Regulations Part L Conservation
More informationGreen Deal Presentation RdSAP and Green Deal
Green Deal Presentation RdSAP and Green Deal What is RdSAP and the EPC? Changes to RdSAP 9.91 Green Deal Measures an PAS 2030 Golden Rule Repayments What are EPCs and what is RDSAP? EPC Energy Performance
More informationProject Description. Projected build start date 01 Feb 2010 Projected date of occupation 31 May Queenborough and Rushenden, Kent, England
http://lowenergybuildings.org.uk Project name Low Carbon Sheppey Project summary The project involves 2 houses in Queenborough and Rushenden on the Isle of Sheppey in Kent, one a mid terrace 1974 built
More informationEnergy Performance Certificate
Energy Performance Certificate 101 Kidmore Road Caversham READING RG4 7NH Dwelling type: Detached house Date of assessment: 11 January 2012 Date of certificate: 11 January 2012 Reference number: 0991-2849-6291-9692-6045
More informationThe Building Regulations, Part L (2013)
Latest Release November 2013 Technical Briefing Note The Building Regulations, Part L (2013) www.xtratherm.com Technical Briefing Note The Building Regulations, Part L (2013) The latest revisions to energy
More informationProject Description. Projected build start date 02 Aug 2010 Projected date of occupation 03 Dec
http://lowenergybuildings.org.uk Project name Hounslow Council Passivhaus Retrofit - and the development of a decision making matrix Project summary The house is a 3-bedroom semi-detached single-family
More information