1 July 22, 2011 via only: The Board of Directors of The Solace Condominium c/o Ms. Linda Schultz, Condominium Manager MCM Property Management Ltd th Avenue SW Calgary, Alberta T2P 1J2 Dear Board Members, Re: Parkade Leakage Investigation th Street SW, Calgary, Alberta Morrison Hershfield Limited (MH) was retained by Solace Condominium to a leakage investigation at the Solace Condominium (Solace), located at th Street SW, Calgary, Alberta. The investigation was authorized by Mr. Sheldon Thompson, Treasurer of the Board of Directors on behalf of Solace. The detailed scope of work, as outlined in our September 21, 2010 proposal, is as follows: Review available drawings and any previous reports with respect to the parkade. The purpose of the review is to determine the original design intent for the various related waterproofing assemblies and what reviews, testing and repairs have been completed to these components to date. Flood test the parkade foundation, beginning at grade and concluding at the base of the building exterior wall (or until the leak is identified). Each area may require a unique style of flood testing, depending on the nature of the building construction. Remove exterior overburden from the parkade podium slab to expose the slab/and or waterproofing membrane. Overburden items include, but not limited to, interlocking paving stones in the vicinity of the suspected infiltration points and retaining wall/fill. The overburden would be safely stored from pedestrians/vandals on the east end of the podium slab. MH would examine the membrane for signs of deterioration or lack of interfacing to adjoining envelope assemblies, and re-flood the suspected leakage area. Compile a report identifying the results of the review and providing recommendations accordingly, including estimated repair costs if applicable. Background: We understand that the Solace has experienced water penetration into the parkade area. On September 14, 2010, MH performed a cursory review of the parkade. During the review, active leakage was noted on the west elevation foundation wall between parking stalls 36 and 41. A similar active leak was also observed on the east elevation foundation wall at the parking stall 40.

2 - 2 - Documentation: MH was not provided with any documentation on the history of the parkade such as previous studies, nor were we provided with construction drawings or specifications. Our knowledge of the building envelope assemblies and subsequent recommendations are strictly based on exploratory openings and observations on site. Water Test Procedures: The following steps were taken to detect the leakage into the parkade: We examined the parkade for signs of leakage from the previous infiltration events to determine the areas to be tested. Excelsior Enterprises Ltd. (Excelsior), a landscaping contractor, was retained to assist MH with exploratory openings. Excelsior removed exterior overburden (unit paver stones, sand, etc.) from the parkade podium slab to expose the slab/and or waterproofing membrane at test areas. MH examined the condition of the existing waterproofing membrane at test openings and looked for signs of deterioration or lack of interfacing to adjoining envelope assemblies. Testing proceeded by spraying water on test openings (i.e. slab, foundation wall, and cladding). Water testing is designed to simulate actual storm events, thus, testing on each building component could require at least 45 minutes or more of water application for possible water penetration to be noticeable. Water testing is conducted by spraying building envelope elements from the base of the wall upward in order to control areas being wetted during different portions of the test (i.e. leakage path isolation technique). Finally, we observed and recorded points of water penetration, if any, which occurred during the test. Water testing, although somewhat reliable in identifying leakage locations, is not 100% accurate. The time required for leakage to occur may not be satisfied by the duration of the test, thereby leading to false results. Also, additional sources of leakage may exist that cannot be tested for during testing procedures due to saturation of previously found leakage paths. Observations: On July 8, 2011, Mr. Lawrence Zhang, P.Eng. of MH visually reviewed the site and performed water testing at test locations 1, 2, and 3 (discussed below). At each of the areas tested, the podium slab consisted of unit paver stones, approximately one inch thick sand/gravels, polyethylene slip sheet, and bituminous hot rubber membrane with approximately 3 to 4 inch upturns. The membrane appeared to be in fair condition with no signs of deterioration observed (Photograph 1). A typical podium slab waterproofing assembly consists of a protection board or drainage mat directly over the membrane to protect it from the sand/gravel bed above. Furthermore, a

3 - 3 - geotextile (filter fabric) is located below the sand bed, or is integrated into the drainage mat to prevent abrasion on the membrane. We not did undertake membrane cut tests for this exercise and therefore did not measure the thickness of the membrane, it adhesion to the concrete substrate, or determine the extent of reinforcing of the membrane (reinforcement is typically required between plies of liquid applied membrane by most waterproofing membrane manufacturers). Where reviewed; however, we did not note debonding membrane or deterioration as a result of a-typical installation. Photograph 1: Bituminous (hot rubber) waterproofing membrane observed on the horizontal surface of the podium slab Sign of water stains were observed on the west foundation wall between parking stalls 36 and 43; also at the east wall by parking stall 40. Concrete cracks were observed at the above mentioned locations. These water stains were noted under and north of the steps at the front entrance.

4 - 4 - Test #1: Location: Southwest corner of the north building (adjacent to the mailbox and above parking stall 43). Podium Slab Assembly: Unit paver stones; One inch thick sand/gravel bed; Polyethylene slip sheet; Liquid-applied hot rubber membrane; Concrete podium slab (as observed from inside the parkade). Spray testing began at 8:30 am on grade where the membrane was exposed. The area was flooded for 45 minutes, and no signs of water penetration were observed. Cracks in the parging north of the steps were observed. Water was sprayed onto the parging by the planter. After 15 minutes of applied water, penetration was observed on the west foundation wall at stall 43 through an existing crack (Photograph 2). Water testing was also conducted on the west entrance steps, as well as the parging to the south of the steps. Within 30 minutes of applied water, penetration was observed at the bottom of the foundation wall under the middle of the steps (Photograph 3) Photograph 2: Water penetration through existing wall crack stall 43

5 - 5 - Photograph 3: Water penetration at the bottom of the foundation wall below centre of steps Test #2: Location: Southeast corner of the parkade roof adjacent to the south steps. Podium Slab Assembly: Unit paver stones; One inch thick sand/gravel bed; Polyethylene slip sheet; Liquid-applied hot rubber membrane; Concrete podium slab (as observed from inside the parkade). A stucco wall with metal flashing was installed above the parkade foundation wall, separating the Solace from the adjacent building. Signs of stucco repairs were observed at the bottom of the wall above the metal flashing. Water was sprayed onto the hot rubber membrane above the parkade roof as well as the upturns. No signs of leakage were observed after 30 minutes of the water test. Testing was heightened to include the metal flashing above the stucco. Immediately, water penetration was observed coming through the joint between the foundation wall and the concrete steps (Photograph 4).

6 - 6 - Photograph 4: Water penetration observed coming through the joint between foundation wall and concrete steps Test #3: Location: Approximately 6 meters north of the west steps (above parking stall 36). Podium Slab Assembly: Unit paver stones; One inch thick sand/gravel bed; Polyethylene slip sheet; Liquid-applied hot rubber membrane; Concrete podium slab (as observed from inside the parkade). While the overburden removals were ongoing, ponding water was observed on the membrane as water drained onto the membrane from Test #1. During the initial site review, an existing crack was observed in the west foundation wall at parking stall 36. However, no water penetration was observed while water was applied directly above the podium slab at this location. Water was then applied into the planter at the west foundation wall. After approximately 30 minutes of spraying, water penetration was observed migrating through the crack at the above-mentioned location (Photograph 5).

7 - 7 - Photograph 5: Water penetration through the foundation wall at parking stall 36 Discussion and Recommendation: Based on the results of the water testing, there appears to be several locations of moisture penetration into the parkade. At all three locations, water applied directly to the surface of the podium slab did not result in leakage. When applied to the vertical plane of the wall (below the podium in Test #1 and #3; above in Test #2) moisture ingress was noted. We believe that the cracking in the foundation wall has been accepting moisture in heavy periods of rain, causing leakage into the parkade. The same conclusion can be related to Test#2; however, with the leakage originating from above the metal flashing, thus above the slab, there is potential that the stucco wall assembly was improperly installed. As a result, the transition joint between the concrete steps and the below-slab foundation wall is susceptible to moisture infiltration when saturated by wind-driven rain. Without chipping back the parging on the west foundation, it is not known if a waterproofing membrane has been installed on the exterior of the foundation wall. We do not suspect that there is moisture protection due to the termination of the membrane at approximately 3 to 4 inches above the slab, however. With respect to a repair strategy, we recommend one of the following two options: Crack injection or exterior foundation wall membrane. With crack injection (Option 1), a contractor would rout out and clean the cracks from the interior. A polyurethane grout could then be

8 - 8 - injected into the crack, filling it with an impervious, flexible material. The intention of the injection of polyurethane would be to block all incoming moisture while moving with any further cracking. Crack injection has a history of performing well provided that the foundation does not continue to crack. This solution is expected to work 50% of the time but is the less-expensive of the two options. Estimation of this work is approximately $200 per linear foot plus contractor mobilization and demobilization costs. This preliminary opinion of probable costs should be used only as an order of magnitude budget at this time. Option 2 would involve excavating the soil against the foundation wall, removing parging and/or planters and installing a waterproofing membrane. As we only identified areas of leakage at visible cracks on the foundation wall, we would recommend only excavating and waterproofing to approximately 12 inches beyond the cracks in all directions. The work would likely extend vertically from the top of the wall to the footing. This solution typically performs longer than Option 1 but involves a much higher cost due to the amount of soil removal and reinstallation required to access the exterior of the foundation wall. With respect to Test #2, there appears to be issues with the wall-flashing detail above the slab. The exact nature of the problem is unknown, but water penetration appears to be occurring between the stucco and the flashing intersection. This could be due to poorly installed and/or reverse moisture barrier lapping, disjointed/negatively sloped flashings, lack of seals, or a combination of these. In order to address the leakage at Test #2, we recommend removing of the lower stucco along the side of the above-slab wall to review and possibly replace the flashing at this level. Moisture protection elements can then be properly installed and interfaced. Further investigation is required. As a general note, the podium slab waterproofing assembly was not originally constructed to best-building practices. Due to a lack of drainage mat or protection board, and filter fabric, there is a greater chance or premature membrane failure. We recommend reducing the service life of the waterproofing assembly in your next reserve fund study (budgeting for full replacement sooner).

9 - 9 - Closing MH can assist with the repairs of this area by contacting contractors with experience in either of the above noted recommendations and requesting pricing. Generating a scope of work with a mini-specification would be required by MH prior to involving contractors. Follow-up with quality control site review would be recommended to ensure the scope is being properly undertaken. Should the Board wish to receive a proposal for these services, please contact the undersigned. We have enjoyed working with Solace on this assignment and look forward to a continued working relationship. Yours truly, Morrison Hershfield Limited Lawrence Zhang, P.Eng. Field Representative Building Science Division Jordan Bowie, C.Tech. Associate, Project Manager Building Science Division N:\PROJ\ THE SOLACE CONDOMINIUM - LEAKAGE INVESTIGATION\LZ- WATER TEST REPORT JULY 8, 2011 FINAL.DOC

1 Exam Prep The NRCA Waterproofing Manual 2005 Tabs and Highlights

1 Exam Prep The NRCA Waterproofing Manual 2005 Tabs and Highlights 1 Exam Prep The NRCA Waterproofing Manual 2005 Tabs and s These 1 Exam Prep Tabs are based on the National Roofing Contractors Association (NRCA) manual listed below: Waterproofing Manual - 2013 Each 1

More information

BENTONITE WATERPROOFING

BENTONITE WATERPROOFING SECTION 07 17 00 BENTONITE WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Furnish and install bentonite waterproofing system where shown on the drawings, as specified herein, and as needed for a complete

More information

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage. DELTA -DRAIN Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade drainage sheets. B. Plaza deck and planter drainage sheets. 1.2 RELATED SECTIONS A. Section

More information

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance www.epa.gov/iaq/moisture Foundations Issue Building foundations are vulnerable to moisture problems for a number of reasons, including: Water from rain and from plumbing leaks is drawn by gravity to foundations,

More information

Included in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations.

Included in our report are our visual observations, recommendations for follow-up evaluation, and conceptual repair recommendations. Ms. Pamela J. Irwin Community Management Associates 384 Ralph McGill Blvd Atlanta, GA 30312 Re: Phase I Condition Assessment Central City Condominiums Pool Deck Atlanta, Georgia Walter P Moore Project

More information

Limited Leak Assessment

Limited Leak Assessment Website:www.moistureconsultantsinc.com E-Mail:support@moistureconsultantsinc.com December 2th, 2005 Limited Leak Assessment Property Address US Naval Facility Building 484 Panama City Beach, Florida Report

More information

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications

EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications EverGuard Plaza Deck Roofing For Above-Grade Plaza Deck Applications Specifications Updated: 12/07 Quality You Can Trust Since 1886... From North America s Largest Roofing Manufacturer PLAZA DECK ROOFING

More information

REPORT OF ROOF CONDITION STUDY. YOUR FACILITY Your Facilities Location. Date YOUR FACILITY S IDENTIFICATION. Prepared for Your Company

REPORT OF ROOF CONDITION STUDY. YOUR FACILITY Your Facilities Location. Date YOUR FACILITY S IDENTIFICATION. Prepared for Your Company REPORT OF ROOF CONDITION STUDY YOUR FACILITY Your Facilities Location YOUR FACILITY S IDENTIFICATION Date Prepared for Your Company 1114 Grindstone, Union, Kentucky 41091 (859) 657-6677 [Report Date] [Client]

More information

Forensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX

Forensics Engineering 8th Congress Forging Forensic Frontiers November 29 December 2, 2018, Austin, TX This paper was published at the Forensic Engineering 8th Congress, held November 29-December 2, 2018 in Austin, TX. The published version of this paper is available for purchase and download at: https://ascelibrary.org/doi/book/10.1061/9780784482018

More information

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage. DELTA -DRAIN 6200 Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade waterproofing. B. Below grade drainage sheets. C. Plaza deck and planter drainage sheets.

More information

Building Envelope Investigation UTHSCSA - CTRC. San Antonio, Texas. June 20, 2016

Building Envelope Investigation UTHSCSA - CTRC. San Antonio, Texas. June 20, 2016 DRAFT DRAFT Building Envelope Investigation At UTHSCSA - CTRC San Antonio, Texas June 20, 2016 Zero/Six Consulting, LLC 2550 S. IH-35 Ste. 215 Austin, Texas 78739 512.806.0376 z6consulting.com Table of

More information

EXECUTIVE SUMMARY INTRODUCTION Terms of Reference Building Description Documents Reviewed SUMMARY OF FIELD DATA 4

EXECUTIVE SUMMARY INTRODUCTION Terms of Reference Building Description Documents Reviewed SUMMARY OF FIELD DATA 4 Abbott Place Wood Framed Window Condition Assessment May 30, 2012 TABLE OF CONTENTS EXECUTIVE SUMMARY 1 1.0 INTRODUCTION 2 1.1 Terms of Reference 2 1.2 Building Description 3 1.3 Documents Reviewed 3 2.0

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

FirstEnergy Program Overview

FirstEnergy Program Overview FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio

More information

March 5, Tatley Grund, Inc. Building Repair Specialists 1115 No. 97 th Street Seattle, WA Stace Grund, President

March 5, Tatley Grund, Inc. Building Repair Specialists 1115 No. 97 th Street Seattle, WA Stace Grund, President March 5, 2015 Tatley Grund, Inc. Building Repair Specialists 1115 No. 97 th Street Seattle, WA 98103 Attn: Re: Stace Grund, President Renaissance Condominiums Seattle, WA Dear Mr. Grund: OAC Services,

More information

FUNCTIONAL REQUIREMENTS

FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 7.6 BALCONIES Workmanship i. All workmanship must be within the tolerances defined in Chapter 1 of this manual. ii. All work is to be carried out by a technically

More information

SECTION SOILS REPORT

SECTION SOILS REPORT SECTION 02300 SOILS REPORT 1. GENERAL: 1.1 All work included under this heading shall be subject to the General Conditions of the entire operation. This Contractor is required to refer especially thereto.

More information

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate

Colphene BSW Training and Application Guide. Colphene BSW Waterproofing Membrane. 1. Prepare substrate Colphene BSW Training and Application Guide Colphene BSW Waterproofing Membrane. 1. Prepare substrate Substrate must be structurally sound. Surface must be free of voids, spalled areas, loose aggregate,

More information

A Design Review of Waterproofing Codes

A Design Review of Waterproofing Codes A Design Review of Waterproofing Codes Section 1807 of Chapter 18 of the International Building Code addresses waterproofing under the section title of Dampproofing and Waterproofing. The section defines

More information

SECTION (07100) - DAMPPROOFING AND WATERPROOFING

SECTION (07100) - DAMPPROOFING AND WATERPROOFING SECTION 07 10 00 (07100) - DAMPPROOFING AND WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Sheet Membrane Waterproofing 2. Under-Slab-On-Grade Vapor Barrier B. Related Sections: 1.02

More information

Thermal Patterns Created By Moisture Accumulation Within Exterior Masonry Walls by A. Colantonio* and G. Desroches ** * Public Works And Government Services Canada, Ottawa, Canada ** Public Works And Government

More information

Parapet Walls What Are They Good For?

Parapet Walls What Are They Good For? Published By: The Construction Specifier Date: September 2011 Author: John Koester Parapet Walls What Are They Good For? Parapet walls perform a number of important functions: They can be designed in various

More information

Alexandria Property Inspections Inc.

Alexandria Property Inspections Inc. Alexandria Property Inspections Inc. 14421 Broadwinged Drive Gainesville, VA 20155 Prepared for: Prepared by: National Property Inspections 15 Canterbury Road Great Neck, NY 11021 08:00 July 19, 2012 Page

More information

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE

SECTION FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE PART 1 - GENERAL 1.1 SUMMARY SECTION 07 27 26 FLUID-APPLIED MEMBRANE AIR BARRIERS, VAPOR PERMEABLE SPEC WRITER NOTE: 1. Delete text between // // not applicable to project. Edit remaining text to suit

More information

MasterSeal Roof systems. Solutions for all your roofing needs

MasterSeal Roof systems. Solutions for all your roofing needs MasterSeal Roof systems Solutions for all your roofing needs 2 MasterSeal Roof systems Working with some of the major builders and building owners, BASF can provide individual tailored solutions to meet

More information

PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT

PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT PHILMONT WAREHOUSE BUILDING PRELIMINARY STRUCTURAL ASSESSMENT Prepared for: GATTER ARCHITECTS 111 MAIN ST. PHILMONT, NY 12565 Prepared by: TACONIC ENGINEERING, DPC PO BOX 272 CHATHAM, NY 12037 TACONIC

More information

Sparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G

Sparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G Sparks Engineering, Inc. S T R U C T U R A L E V A L U A T I O N, D E S I G N A N D T E S T I N G February 29, 2008 Ms. Leslie Wolfenden Save Austin's Cemeteries PO Box 41814 Austin, TX 78704 (512) 917-1666

More information

Integral Waterproofing

Integral Waterproofing BCBEC Luncheon June 14, 2012 Integral Waterproofing Presented by Joel Schwartz, P.Eng, FEC, BEP Background Case study of two large high-rise projects at False Creek in Vancouver, BC Case Study 1: Site

More information

Keene Building Products

Keene Building Products Keene Building Products Keene Building Products is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported

More information

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers.

1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels. 3. Insulation. 4. Plaza deck pavers. SECTION 071413 HOT FLUID APPLIED RUBBERIZED ASPHALT WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Rubberized asphalt waterproofing membrane, reinforced. 2. Molded sheet drainage panels.

More information

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION

Gensler 2014/06/16 Hertz Global Headquarters ISSUE FOR BUILDING PERMIT Estero, Florida SECTION SECTION 072700 VAPOR PERMEABLE AIR BARRIER LIQUID MEMBRANE PART 1 GENERAL 1.1 GENERAL REQUIREMENTS A. The Work of this Section, as shown or specified, shall be in accordance with the requirements of the

More information

Waterproofing and Types of Drains

Waterproofing and Types of Drains Waterproofing and Types of Drains 4 PVC Downspout Burial w/ Y Fitting for Future Clean-out Yard Drain Box 12 Drain Box 12885 Old Frederick Road Sykesville, MD 21784 Office 410-442-2445 Fax 410-489-4312

More information

National Property Inspections

National Property Inspections Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)

More information

A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau

A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau Determination 2007/37 A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau 1. The matter to be determined 1.1 This is a determination under Part 3 Subpart

More information

AVM System 500. Aussie Membrane 500

AVM System 500. Aussie Membrane 500 Generic Spec TECH DATA SHEET Sections - 071000 / 071400 / 071416 ICC ESR-2503 L.A. RR#: 25550 Heavy Duty Below Grade Bituminous Waterproofing Membrane Sections 071000 / 071400 / 071416 Fluid Applied Waterproofing

More information

AVM System 500. Aussie Membrane 500

AVM System 500. Aussie Membrane 500 Generic Spec TECH DATA SHEET Sections - 071000 / 071400 / 071416 ICC ESR-2503 L.A. RR#: 25550 Heavy Duty Below Grade Bituminous Waterproofing Membrane Sections 071000 / 071400 / 071416 Fluid Applied Waterproofing

More information

Solving the Waterproofing Puzzle:

Solving the Waterproofing Puzzle: Solving the Waterproofing Puzzle: Plaza Decks and Green Roofs January 16, 2009 CRCA 26 th Annual Trade Show Speaker: Richard Koziol, AIA, NCARB Wiss, Janney, Elstner Associates, Inc. Copyright Materials

More information

2. The building envelope shall comply with all applicable requirements in Section of ANSI/ASHRAE/USGBC/IES Standard

2. The building envelope shall comply with all applicable requirements in Section of ANSI/ASHRAE/USGBC/IES Standard 5.2 Exterior Wall Systems 5.2.1 General Requirements for All Exterior Wall Systems 1. The design and detailing of exterior wall systems and assemblies will require significant input from U of C FM&D in

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

FLUID APPLIED WATERPROOFING

FLUID APPLIED WATERPROOFING SECTION 07120 FLUID APPLIED WATERPROOFING PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 03300 - Cast-In-Place Concrete. 2. 09200 - Metal Studs, Metal Lath, Suspension Ceilings, Plaster, and Stucco.

More information

SECTION FLUID-APPLIED WATERPROOFING

SECTION FLUID-APPLIED WATERPROOFING SECTION 07140 FLUID-APPLIED WATERPROOFING PART 1 GENERAL 1.1 SUMMARY A. Section includes fluid applied rubberized asphalt and/or elastomeric membrane waterproofing; and surface dusting and/or protective

More information

AS The External Waterproofing Membranes Standard

AS The External Waterproofing Membranes Standard AS 4654-2 The External Waterproofing Membranes Standard NOTE This external waterproofing standard contains solutions for problems which have not been addressed in other countries. CONFORMANCE CONDITIONS

More information

Prepared By. Accent Building Sciences Inc. For

Prepared By. Accent Building Sciences Inc. For ROOF LEAK INVESTIGATION & CONDITION ASSESSMENT REPORT For Toronto, Ontario Prepared By Accent Building Sciences Inc. For Client# 40105 Date: November 11, 2003 November 2003 Roof Leak Investigations & Condition

More information

SIKA EGYPT. Injection Systems. Scope: Highly expansion solvent free water-reactive two part Polyurethane foam injection system

SIKA EGYPT. Injection Systems. Scope: Highly expansion solvent free water-reactive two part Polyurethane foam injection system Method Statement for Application of Sika Injection 20 SIKA EGYPT Injection Systems Scope: Highly expansion solvent free water-reactive two part Polyurethane foam injection system INTRODUCTION: The water

More information

.2 Flashings at grade to extents shown on the Drawings. .3 Membrane and polyethylene slip sheets at perimeter of walls.

.2 Flashings at grade to extents shown on the Drawings. .3 Membrane and polyethylene slip sheets at perimeter of walls. RWPS Foundations and Concrete Structures Page 1 of 8 1. GENERAL 1.1 Work Included.1 Supply and installation of ethylene propylene diene monomer (EPDM) membrane and insulation to extents shown on the Drawings

More information

Perm-A-Barrier VPS (Vapor Permeable Sheet)

Perm-A-Barrier VPS (Vapor Permeable Sheet) VPS (Vapor Permeable Sheet) Self-adhering vapor permeable air barrier membrane Product Description VPS (Vapor Permeable Sheet) is a vapor permeable air barrier membrane consisting of a proprietary breathable

More information

Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland

Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland Determination 2011/095 Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland 1. The matter to be determined 1.1 This is a determination

More information

WeatherSmart Air Barrier Installation Guide

WeatherSmart Air Barrier Installation Guide WeatherSmart Air Barrier Installation Guide 1 The intent of this document is to provide a guide for the installation of WeatherSmart as both a Weather Resistive Barrier (W.R.B.) and an Air Barrier Material

More information

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT

CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 DISTRIBUTION ENGINEERING DISTRIBUTION EQUIPMENT SPECIFICATION EO-1007 REVISION 13 DECEMBER 2013 EFFECTIVE DATE DECEMBER 16,

More information

Background. Via October 23, 2018

Background. Via   October 23, 2018 Wiss, Janney, Elstner Associates, Inc. 601 Walnut Street, Suite 875W Philadelphia, Pennsylvania 19106 215.567.0703 tel 215.238.9659 fax www.wje.com Via E-mail: tgormley@pullman-services.com October 23,

More information

AS Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings

AS Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings AS4654.2 Interpretation of External Waterproofing as it applies to Melbourne, Class 1 buildings Climate Zone: 6 Wind Class: N1 Membrane Types: Liquid Applied Class II and Class III as defined and tested

More information

November 30, University of Virginia Facilities Management Engineering & Design Division P.O. Box Charlottesville, VA

November 30, University of Virginia Facilities Management Engineering & Design Division P.O. Box Charlottesville, VA University of Virginia Facilities Management Engineering & Design Division P.O. Box 400726 Charlottesville, VA 22904-4726 Attention: Reference: William Blodgett, AIA Project Manager University of Virginia

More information

LIQUID RUBBER INDUSTRIES ENGINEERING SPECIFICATIONS FOR ENGINEERS AND ARCHITECTS. Diagram 1: Standard Membrane Continuation 150 mm Overlap

LIQUID RUBBER INDUSTRIES ENGINEERING SPECIFICATIONS FOR ENGINEERS AND ARCHITECTS. Diagram 1: Standard Membrane Continuation 150 mm Overlap LIQUID RUBBER INDUSTRIES ENGINEERING SPECIFICATIONS FOR ENGINEERS AND ARCHITECTS Diagram 1: Standard Membrane Continuation 150 mm Overlap Ensure Membrane to Membrane Contact Diagram 2: Membrane Continuation

More information

SECTION SELF-ADHERING SHEET FLASHING

SECTION SELF-ADHERING SHEET FLASHING MANUFACTURER S GUIDE SPECIFICATIONS SECTION 076526 SELF-ADHERING SHEET FLASHING 900 Hensley Lane Wylie TX 75098 800-527-7092 www.carlisleccw.com 604129 03.24.15 Carlisle, Flexphalt, Sure-Seal and CAV-GRIP

More information

Groundwater Seepage. Causes of Basement Seepage and Leaks Hydrostatic Pressure

Groundwater Seepage. Causes of Basement Seepage and Leaks Hydrostatic Pressure Groundwater Seepage The following guide can be used by you and your crews when assessing seepage at a property. Bear in mind that this guide is not all-inclusive, and should be used in a supplementary

More information

Henri Fennell, CSI/CDT ABX 2015

Henri Fennell, CSI/CDT ABX 2015 Henri Fennell, CSI/CDT ABX 2015 Henri is an architect and building envelope specialist with over forty years of experience in the construction industry. He was a pioneer in the solar industry, introduced

More information

ALLNEX DAMP PROOF AND TANKING MEMBRANES. Product. Scope. Appraisal No. 805 [2013] Appraisal No. 805 (2013) Amended 26 January 2018.

ALLNEX DAMP PROOF AND TANKING MEMBRANES. Product. Scope. Appraisal No. 805 [2013] Appraisal No. 805 (2013) Amended 26 January 2018. ALLNEX DAMP PROOF AND TANKING MEMBRANES Amended 26 January 2018 BRANZ Appraisals Technical Assessments of products for building and construction. Allnex New Zealand Ltd PO Box 12841 Penrose, 1642 Auckland

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

Site Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks

Site Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks Site Bldg Fiscal Yr System Sub-System Site site 2014/15 Parking Paving Site site 2014/15 Sidewalks Skill Center L 2015/16 Architectural Partitions Site Site 2015/16 Parking Striping Arc Center M 2014/15

More information

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1

Louis Armstrong New Orleans International Airport NOAB Project # North Terminal Development Program Phase 1 Louis Armstrong New Orleans International Airport NOAB Project # 8910-01233 PART 1 - GENERAL SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS 1.1 RELATED DOCUMENTS A. Drawings and general provisions

More information

6. Moisture Design. Objectives: 3. Prevent vapor condensation (surface, concealed) 4. Prevent rain penetration

6. Moisture Design. Objectives: 3. Prevent vapor condensation (surface, concealed) 4. Prevent rain penetration 6. Moisture Design Objectives: 3. Prevent vapor condensation (surface, concealed) 4. Prevent rain penetration Vapor Condensation More new bldgs are susciptable to vapor condensation because of: 2. 1. 2.

More information

PEKAY T570 RUBBERSEAL

PEKAY T570 RUBBERSEAL PEKAY T570 RUBBERSEAL DESCRIPTION Pekay Rubberseal T570 is a rubber-latex modified anionic bitumen emulsion, which dries to a pliable, flexible, waterproof, black coating. It may be used for a variety

More information

CTIOA REPORT

CTIOA REPORT CERAMIC TILE INSTITUTE OF AMERICA, INC. 12061 Jefferson Blvd., Culver City, CA 90230-6219 CTIOA REPORT 2003-4-17 SUBJECT: FLASHING DETAILS EXTERIOR TILE DECK CONSTRUCTION By Mark Marsch Preface Having

More information

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage.

E. Section Polymer Modified Cement Waterproofing. K. Section Sub drainage: Foundation perimeter drainage. DELTA -MS CLEAR Section 07 10 00 Dampproofing and Waterproofing PART 1 GENERAL 1.1 SECTION INCLUDES A. Below grade waterproofing and dampproofing. 1.2 RELATED SECTIONS A. Section 07 11 13 - Bituminous

More information

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu

SLAB ON GRADE Insul-Joint or Expansion Joint Material as Required by A/E Specifications AquaCheck Liquid Coating 400 (Waterproofing Membrane) with Aqu INSTALLATION INSTRUCTIONS Note: The following installation instructions are based off of ASTM E 1643 (Standard Practice for Installation of Water Vapor Retarders Used in Contact with Earth or Granular

More information

2001 Building Failures Study

2001 Building Failures Study Página Web 1 de 5 Technical Series 01-140 2001 Building Failures Study Introduction In Canada, building rehabilitation for roofing and wall system repairs and replacement cost an estimated $7.5 billion

More information

SECTION THERMAL INSULATION

SECTION THERMAL INSULATION Pactiv Building Products 2100 RiverEdge Parkway Suite 175 Atlanta, GA 30328 Toll Free: (800) 241-4402 Web Site: www.green-guard.com SECTION 07210 THERMAL INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS

More information

Membranes for horizontal external constructions

Membranes for horizontal external constructions System Platon Membranes for horizontal external constructions Balconies and terraces Separation layer Ballasted roofs Roof parking Green roofs Walkways Artificial turf Dry and healthy buildings Solutions

More information

Ste-anne-des-pays-bas Church

Ste-anne-des-pays-bas Church Ste-anne-des-pays-bas Church Exterior wall siding assessment Type of Document Final Project Number Prepared By: Jean-Philippe Foisy, AANB Reviewed By: Stephen Skinner, AANB exp Architects Inc. 602 Rothesay

More information

Subject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation SCI Project Number:

Subject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation SCI Project Number: 27 June 2016 Mr. Shane Chism, AIA Breckenridge Group 4625 E. Fort Lowell Road Tucson, Arizona 85712 Subject: Amphitheater School District Reroofing Projects Amphi High School, Building 900 Roof Evaluation

More information

PRELIMINARY RESULTS FROM FIELD EXPERIMENTAL STUDY OF RAIN LOAD AND PENETRATION INTO WOOD-FRAME WALL SYSTEMS AT WINDOW SILL DEFECTS

PRELIMINARY RESULTS FROM FIELD EXPERIMENTAL STUDY OF RAIN LOAD AND PENETRATION INTO WOOD-FRAME WALL SYSTEMS AT WINDOW SILL DEFECTS PRELIMINARY RESULTS FROM FIELD EXPERIMENTAL STUDY OF RAIN LOAD AND PENETRATION INTO WOOD-FRAME WALL SYSTEMS AT WINDOW SILL DEFECTS E. Ngudjiharto, F. Tariku and P. Fazio ABSTRACT A field study is presented

More information

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING

INSTALLING WATER-RESISTIVE BARRIERS & FLASHING INSTALLING WATER-RESISTIVE BARRIERS & FLASHING IN A TWO-LAYER STUCCO APPLICATION Fortifiber Building Systems Group provides this guide to assist installers by demonstrating a two-layer installation of

More information

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards

1. Decks, balconies, and sun porches 2. Walkways, ramps, and stairways 3. Patios and courtyards SECTION 07185 TRAFFIC MEMBRANE PART 1 GENERAL 1.1 SECTION INCLUDES A. Traffic membrane, consisting of welded seam PVC waterproofing, over f following surfaces: 1. Decks, balconies, and sun porches 2. Walkways,

More information

Exterior Elevated Elements Inspection Guidelines

Exterior Elevated Elements Inspection Guidelines Exterior Elevated Elements Inspection Guidelines Planning and Development 1. Guideline Purpose These guidelines are intended to assist practicing professionals in complying with Berkeley Municipal Code

More information

Figure 2. By John H. Koester

Figure 2. By John H. Koester By John H. Koester Figure 2 There are numerous factors/phenomena that create misunderstandings that result in improper or inadequate moisture management design for the exterior building envelope. Let s

More information

SECTION DAMPPROOFING AND WATERPROOFING

SECTION DAMPPROOFING AND WATERPROOFING SECTION 07100 DAMPPROOFING AND WATERPROOFING PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Sheet Membrane Waterproofing 2. Under-Slab-On-Grade Vapor Retarder B. Related Sections: 1. Section 03300

More information

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING

SECTION COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING P.O. Box 599 - Mars, PA 16046 800-321-3337 SECTION 07555 COLD APPLIED RUBBER MODIFIED ASPHALT WATERPROOFING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including

More information

RECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION

RECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION RECREATIONAL EAGLE CENTER METAL ROOF ASSESSMENT AND SOLUTION Recreational Eagle Center (00550) La Crosse, WI DSF Project No. 07H1E SEG Project No. 10975 Prepared for Division of State Facilities 101 E.

More information

ROOF SUBSTRATE PREP MANUAL

ROOF SUBSTRATE PREP MANUAL ROOF SUBSTRATE PREP MANUAL ALDOCOAT Liquid Applied Roof Restoration Systems AFTER BEFORE JULY 2016 1604 N. Main St. Kannapolis, NC 28081 (800) 474-6019 www.aldoproducts.com ROOF SUBSTRATE PREPARATION Preparation

More information

SECTION MANUFACTURED ROOF EXPANSION JOINTS

SECTION MANUFACTURED ROOF EXPANSION JOINTS SECTION 07 71 29 - MANUFACTURED ROOF EXPANSION JOINTS PART 1 -GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

No structural deficiencies were observed to the west exterior elevation.

No structural deficiencies were observed to the west exterior elevation. August 9, 2016 Ms. Jennifer Spencer, AIA, NCARB Gary W. Anderson Architects 200 Prairie Street, Suite 201 Rockford, IL 61107 Subject: Structural Observations 227 North Wyman Street Rockford, IL Dear Ms.

More information

Eidem Farm Brooklyn Park, MN

Eidem Farm Brooklyn Park, MN Eidem Farm Brooklyn Park, MN East Farm House Structural Condition Assessment Prepared By 1 0 0 P O R T L A N D A V E N U E S O U T H, S U I T E 1 0 0 M I N N E A P O L I S, M I N N E S O T A 5 5 4 0 1

More information

DGM Consultants, P.A. Structural Engineering and Masonry Consulting FIELD REPORT #01

DGM Consultants, P.A. Structural Engineering and Masonry Consulting FIELD REPORT #01 DGM Consultants, P.A. Structural Engineering and Masonry Consulting FIELD REPORT #01 Project Carnegie Library Date 5/15/2012 DGM Project # 2012014 Location th 9 and Vermont Contractor The Garland Company,

More information

City of Lake Oswego City Hall

City of Lake Oswego City Hall City Hall 380 A Avenue, Lake Oswego, OR 97034 Presented To:, Public Works Department C/O Ms. Rachael Petersen, CFM P.O. Box 369, Lake Oswego, OR 97034 MH Project Number: P150162.00 July 08, 2015 Morrison

More information

CCIM Central Canada Chapter. Richard Weldon, P.Eng., LEED AP Carson Dunlop Weldon & Associates Ltd. October 5,

CCIM Central Canada Chapter. Richard Weldon, P.Eng., LEED AP Carson Dunlop Weldon & Associates Ltd. October 5, Minimizing Risk When Purchasing or Leasing CCIM Central Canada Chapter Richard Weldon, P.Eng., LEED AP Carson Dunlop Weldon & Associates Ltd. October 5, 2010 www.cdwengineering.com Who We Are CDW is a

More information

STRUCTURAL ASSESSMENT OBSERVATION REPORT

STRUCTURAL ASSESSMENT OBSERVATION REPORT Consulting Engineers THORSON BAKER & Associates, Inc. 3030 West Streetsboro Road (330) 659-6688 phone Richfield, Ohio 44286 (330) 659-6675 fax www.thorsonbaker.com STRUCTURAL ASSESSMENT OBSERVATION REPORT

More information

A. The work of this section includes, but is not limited to, the following:

A. The work of this section includes, but is not limited to, the following: SECTION 07 14 00 FLUID APPLIED WATERPROOFING SYSTEM PART 1: GENERAL 1.1 RELATED DOCUMENTS A. All of the Contract Documents, including General and Supplementary Conditions and Division 01 General Requirements,

More information

DURRELL DESIGN GROUP, PLLC ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI.

DURRELL DESIGN GROUP, PLLC ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON, MISSISSIPPI. DURRELL DESIGN GROUP, PLLC 500-G E. WOODROW WILSON AVENUE JACKSON, MISSISSIPPI 39216 PHONE: 601.708.4788 FAX: 601.488.4717 ROOF REPLACEMENT BARR ELEMENTARY SCHOOL JACKSON PUBLIC SCHOOL DISTRICT JACKSON,

More information

Redi Rock Specification and Installation Manual

Redi Rock Specification and Installation Manual Redi Rock Specification and Installation Manual 1.0 General Scope This Specification covers the Design, Materials and Installation of Redi Rock modular block Retaining and Freestanding Wall systems as

More information

Efficiently Produced Construction Documents are Quality Construction Documents

Efficiently Produced Construction Documents are Quality Construction Documents Efficiently Produced Construction Documents are Quality Construction Documents Creative Disruption - AIA Minnesota November 13, 2015; 10:15 am 11:45 am Micheal J. Lough Good design makes a difference CES

More information

Delivery, Storage, and Handling

Delivery, Storage, and Handling TECH DATA SHEET Sections - 071000 / 071300 / 071313 / 071326 / 071352 AVM Aussie Mate 580-AL UV Stable Heavy Duty 60 Mil Bellow Grade Bituminous Waterproofing Sheet Membrane, with Aluminum Backing Product

More information

SECTION 07530CP EPDM MEMBRANE ROOFING

SECTION 07530CP EPDM MEMBRANE ROOFING PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL

More information

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK

1993 SPECIFICATIONS CSJ SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1993 SPECIFICATIONS CSJ 581-1-95 SPECIAL SPECIFICATION ITEM 4110 CONCRETE ENCASED DUCT BANK 1. DESCRIPTION. This Item shall govern for the furnishing and installation of all materials and equipment for

More information

Construction Inspection Checklists

Construction Inspection Checklists III. Construction Inspection Checklists 33 Bioretention - Construction Inspection Checklist Project: Location: Site Status: Date: Time: Inspector: Construction Sequence Satisfactory / Unsatisfactory Comments

More information

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING

SECTION mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING SECTION 07143 CCW-MIRASEAL @ 120 mil thickness REINFORCED LIQUID-APPLIED WATERPROOFING PART 1 - GENERAL 1.1 SECTION INCLUDES: Installation of waterproofing membrane on surfaces indicated on drawings, consisting

More information

PROCOR Composite Waterproofing System

PROCOR Composite Waterproofing System PROCOR Composite Waterproofing System Fluid-applied and sheet waterproofing system Product Description PROCOR Composite Waterproofing System, combining PROCOR 75 fluid-applied membrane with PROCOR Composite

More information

SECTION BUILT-UP BITUMINOUS WATERPROOFING

SECTION BUILT-UP BITUMINOUS WATERPROOFING SECTION 07 12 00 BUILT-UP BITUMINOUS WATERPROOFING SPEC WRITER NOTE: Delete any item or paragraph not applicable in the section and renumber the paragraphs. PART 1 - GENERAL 1.1 DESCRIPTION: This section

More information