IEEE T&D Insulators 101

Size: px
Start display at page:

Download "IEEE T&D Insulators 101"

Transcription

1 Insulators 101 Section A Introduction Presented by Andy Schwalm IEEE Chairman, Lightning and Insulator Subcommittee IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

2 What Is an Insulator? An insulator is a dam*** poor conductor! And more, technically speaking! An insulator is a mechanical support! Primary function - support the line mechanically Secondary function electrical Air is the insulator Outer shells/surfaces are designed to increase leakage distance and strike distance

3 What Does an Insulator Do? Maintains an Air Gap Separates Line from Ground length of air gap depends primarily on system voltage, modified by desired safety margin, contamination, etc. Resists Mechanical Stresses everyday loads, extreme loads Resists Electrical Stresses system voltage/fields, overvoltages Resists Environmental Stresses heat, cold, UV, contamination, etc.

4 Where Did Insulators Come From? Basically grew out of the needs of the telegraph industry starting in the late 1700s, early 1800s Early history centers around what today we would consider very low DC voltages Gradually technical needs increased as AC voltages grew with the development of the electric power industry

5 History Glass plates used to insulate telegraph line DC to Baltimore Glass insulators became the norm soon thereafter typical collector s items today Many, many trials with different materials wood cement porcelain - beeswax soaked rag wrapped around the wire, etc. Ultimately porcelain and glass prevailed

6 History Wet process porcelain developed for high voltage applications Porcelain insulator industry started Application voltages increased Insulator designs became larger, more complex Ceramics (porcelain, glass) still only choices at high voltages

7 History US trials of first NCIs cycloaliphatic based Not successful, but others soon became interested and a new industry started up Europeans develop modern style NCI fiberglass rod with various polymeric sheds Now considered First generation

8 History NCI insulator industry really begins in US with field trials of insulators Since that time - new manufacturers, new designs, new materials NCIs at generation X there have been so many improvements in materials, end fitting designs, etc. Change in materials have meant changes in line design practices, maintenance practices, etc. Ceramic manufacturers have not been idle either with development of higher strength porcelains, RG glazes, etc.

9 History Domestic manufacturing of insulators decreases, shift to offshore (all types) Engineers need to develop knowledge and skills necessary to evaluate and compare suppliers and products from many different countries An understanding of the basics of insulator manufacturing, design and application is more essential than ever before

10 Insulator Types For simplicity will discuss in terms of three broad applications: Distribution lines (thru 69 kv) Transmission lines (69 kv and up) Substations (all voltages)

11 Insulator Types Distribution lines Pin type insulators -mainly porcelain, growing use of polymeric (HDPE high density polyethylene), limited use of glass (in US at least) Line post insulators porcelain, polymeric Dead end insulators polymeric, porcelain, glass Spool insulators porcelain, polymeric Strain insulators, polymeric, porcelain

12 Types of Insulators Distribution

13 Insulator Types Transmission lines Suspension insulators - new installations mainly NCIs, porcelain and glass now used less frequently Line post insulators mainly NCIs for new lines and installations, porcelain much less frequent now

14 Types of Insulators Transmission

15 Insulator Types Substations Post insulators porcelain primarily, NCIs growing in use at lower voltages (~161 kv and below) Suspension insulators NCIs (primarily), ceramic Cap and Pin insulators legacy type

16 Types of Insulators Substation

17 Insulator Types - Comparisons Ceramic Porcelain or toughened glass Metal components fixed with cement ANSI Standards C29.1 through C29.10 Non Ceramic Typically fiberglass rod with rubber (EPDM or Silicone) sheath and weather sheds HDPE line insulator applications Cycloaliphatic (epoxies) station applications, some line applications Metal components normally crimped ANSI Standards C29.11 C29.19

18 Insulator Types - Comparisons Ceramic Materials very resistant to UV, contaminant degradation, electric field degradation Materials strong in compression, weaker in tension High modulus of elasticity - stiff Brittle, require more careful handling Heavier than NCIs Non Ceramic Hydrophobic materials improve contamination performance Strong in tension, weaker in compression Deflection under load can be an issue Lighter easier to handle Electric field stresses must be considered

19 Insulator Types - Comparisons Ceramic Generally designs are mature Limited flexibility of dimensions Process limitations on sizes and shapes Applications/handling methods generally well understood Non Ceramic Material properties have been improved UV resistance much improved for example Standardized product lines now exist Balancing act - leakage distance/field stress take advantage of hydrophobicity Application parameters still being developed Line design implications (lighter weight, improved shock resistance)

20 Insulators 101 Section B - Design Criteria Presented by Al Bernstorf IEEE Chairman, Insulator Working Group IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

21 Design Criteria - Mechanical An insulator is a mechanical support! Its primary function is to support the line mechanically Electrical Characteristics are an afterthought. Will the insulator support your line? Determine The Maximum Load the Insulator Will Ever See Including NESC Overload Factors.

22 Design Criteria - Mechanical Suspension Insulators Porcelain - M&E (Mechanical & Electrical) Rating Represents a mechanical test of the unit while energized. When the porcelain begins to crack, it electrically punctures. Average ultimate strength will exceed the M&E Rating when new. - Never Exceed 50% of the M&E Rating NCIs (Polymer Insulators) - S.M.L. Specified Mechanical Load Guaranteed minimum ultimate strength when new. R.T.L. Routine Test Load Proof test applied to each NCI. - Never Load beyond the R.T.L.

23 Design Criteria - Mechanical Line Post insulators Porcelain - Cantilever Rating Represents the Average Ultimate Strength in Cantilever when new. Minimum Ultimate Cantilever of a single unit may be as low as 85%. - Never Exceed 40% of the Cantilever Rating Proof Test Load NCIs (Polymer Insulators) - S.C.L. (Specified Cantilever Load) Not based upon lot testing Based upon manufacturer testing - R.C.L. (Rated Cantilever Load) or MDC or MDCL (Maximum Design Cantilever Load) or MCWL or WCL (Working Cantilever Load) - Never Exceed RCL or MDC or MDCL or MCWL or WCL - S.T.L. (Specified Tensile Load) - Tensile Proof Test=(STL/2)

24 Design Criteria - Mechanical Other Considerations Suspensions and Deadends Only apply tension loads Line Posts - Cantilever is only one load - Transverse (tension or compression) on line post loading transverse to the direction of the line. - Longitudinal in the direction of travel of the line - Combined Loading Curve Contour curves representing various Longitudinal loads Available Vertical load as a function of Transverse loading Manufacturers have different safety factors!!!

25 Design Criteria - Mechanical 69 kv Post - 2.5" Rod V E R T I C A L L O A D, L B F Compr e ssion TRANSVERSE LOAD, LBF Ten sion 0 Longitudinal 500 Longitudinal 1000 Longitudinal 1500 Longitudinal 2000 Longitudinal LINE POST APPLICATION CURVES

26 Design Criteria - Electrical An Insulator is a mechanical support! Air imparts Electrical Characteristics Strike Distance (Dry Arcing Distance) is the principal constituent to electrical values. Dry 60 Hz F/O and Impulse F/O based on strike distance. Wet 60 Hz F/O - Some would argue leakage distance as a principal factor. - At the extremes that argument fails although it does play a role. - Leakage distance helps to maintain the surface resistance of the strike distance. Leakage Requirements do play a role!!!

27 Design Criteria - Electrical Dry Arcing Distance (Strike Distance) The shortest distance through the surrounding medium between terminal electrodes. 1 1 IEEE Std

28 Design Criteria - Electrical PICKING A SUITABLE INSULATOR ELECTRICAL PARAMETERS Define peak l-g kv A. NOMINAL SYSTEM LINE-TO-LINE VO LTAGE B. MAXIMUM SYSTEM LINE-TO-GROUND VOLTAGE (line A/1.732)* 1.05 C. MAXIMUM PEAK LINE-TO-GROUND VOLTAGE (e) e=(line B * 1.414) LEAKAGE DISTANCE REQUIREMENTS 69 kv (rms) 41.8 kv (rms) 59.1 kv (peak) Determine Leakage Distance Required CONTAMINATION LEVEL (typical val ues) D. ZERO E. LIGHT F. MODERATE G. HEAVY Enter inches/kv - SUGGESTED LEAKAGE (inches/(kv line-to-ground)) UP TO Switching Over-voltage Requirements Impulse Over-voltage H. INSULATOR LEAKAGE (MIN.) (li ne B)*(inches/kV) = 41.8 inches SWITCHING OVERVOLTAGE REQUIREMENTS I. SSV = (l ine B) * kv (peak) IMPULSE OVERVOLTAGE REQUIREMENTS J. PEAK IMPULSE WITHSTAND = (I(t) * R(f))+e I(t) = 20 ka (typical val ue = 50 ka) R(f) = 15 ohm (typi cal value = ohm) e = 59.1 (li ne C) K. IMPULSE WITHSTAND = 359 kv SELECT INSULATOR BASED ON REQUIREMENTS: Chart Courtesy of Ohio Brass/HPS EU1429-H SYSTEM REQUIREMENT H. LEAKAGE DISTANCE I. SWITCHING SURGE VOLTAGE K. IMPULSE W ITHSTAND T. SELECT INSULATOR VALUE FROM PAGE POLYMER VALUES NUMBER OF PORCELAIN BELLS

29 Design Criteria Leakage Distance What is Leakage Distance? The sum of the shortest distances measured along the insulating surfaces between the conductive parts, as arranged for dry flashover test. 1 1 IEEE Std

30 Design Criteria - Electrical What s an appropriate Leakage Distance? Empirical Determination - What s been used successfully? - If Flashovers occur add more leak? ESDD (Equivalent Salt Deposit Density) Determination - Measure ESDD Pollution Monitors Dummy Insulators Remove in-service insulators - Evaluate ESDD and select appropriate Leakage Distance

31 Design Criteria - Electrical Application Guide for Insulators in a Contaminated Environment by K. C. Holte et al F ESDD (mg/cm 2 ) Site Severity Leakage Distance I-string/V-string ( /kv l-g) Very Light 0.94/ Light 1.18/ Moderate 1.34/1.05 >0.1 Heavy 1.59/1.19

32 Design Criteria - Electrical IEC Standards ESDD (mg/cm 2 ) Site Severity Leakage Distance ( /kv l-g) <0.01 Very Light Light Medium Heavy 1.70 >0.40 Very Heavy 2.11

33 Design Criteria - Electrical Leakage Distance Recommendations 2.5 Leak ("/kv l-g) IEEE V IEEE I IEC Poly. (IEC) Poly. (IEEE V) Poly. (IEEE I) ESDD (mg/cm^2)

34 Improved Contamination Performance Flashover Vs ESDD Flashover Voltage CEA 280 T 621 SR units - leakage equal to porcelain EPDM Units - leakage 1.3 X Porc elain Porc elain New EPDM Aged EPDM New SR Aged SR ESD D (mg/cm^2)

35 Improved Contamination Performance Polymer insulators offer better contamination flashover performance than porcelain? Smaller core and weathershed diameter increase leakage current density. Higher leakage current density means more Ohmic Heating. Ohmic Heating helps to dry the contaminant layer and reduce leakage currents. In addition, hydrophobicity helps to minimize filming

36 Improved Contamination Performance the contamination performance of composite insulators exceeds that of their porcelain counterparts the contamination flashover performance of silicone insulators exceeds that of EPDM units the V 50 of polymer insulators increases in proportion to the leakage distance CEA 280 T 621, Leakage Distance Requirements for Composite Insulators Designed for Transmission Lines

37 Insulator Selection Where do I get these values? Leakage Distance or Creepage Distance Manufacturer s Catalog Switching Surge Wet W/S ((Wet Switching Surge W/S)/ 2) 60 Hz Wet Flashover (r.m.s.) Peak Wet 60 Hz value will be lower than Switching Surge Wet W/S Impulse Withstand Take Positive or Negative Polarity, whichever is lower If only Critical Impulse Flashover is available assume 90% (safe estimate for withstand)

38 Insulator Selection Select the 69 kv Insulator shown at right. PICKING A SUITABLE INSULATOR ELECTRICAL PARAMETERS A. NOMINAL SYSTEM LINE-TO-LINE VO LTAGE B. MAXIMUM SYSTEM LINE-TO-GROUND VOLTAGE (line A/1.732)* 1.05 C. MAXIMUM PEAK LINE-TO-GROUND VOLTAGE (e) e=(line B * 1.414) 69 kv (rms) 41.8 kv (rms) 59.1 kv (peak) I-string Mechanical Worst Case 6,000 lbs Suspension: 12k min ultimate Leakage Distance 42 Switching Surge 125 kv Impulse Withstand 359 kv LEAKAGE DISTANCE REQUIREMENTS CONTAMINATION LEVEL (typical val ues) D. ZERO E. LIGHT F. MODERATE G. HEAVY Enter inches/kv - H. INSULATOR LEAKAGE (MIN.) (li ne B)*(inches/kV) = SWITCHING OVERVOLTAGE REQUIREMENTS inches I. SSV = (l ine B) * kv (peak) IMPULSE OVERVOLTAGE REQUIREMENTS J. PEAK IMPULSE WITHSTAND = (I(t) * R(f))+e I(t) = 20 ka (typical val ue = 50 ka) R(f) = 15 ohm (typi cal value = ohm) e = 59.1 (li ne C) SUGGESTED LEAKAGE (inches/(kv line-to-ground)) UP TO K. IMPULSE WITHSTAND = 359 kv SELECT INSULATOR BASED ON REQUIREMENTS: SYSTEM REQUIREMENT H. LEAKAGE DISTANCE I. SWITCHING SURGE VOLTAGE K. IMPULSE W ITHSTAND T. SELECT INSULATOR VALUE FROM PAGE POLYMER VALUES NUMBER OF PORCELAIN BELLS

39 Insulator Selection Porcelain 5-3/4 X 10 bells X 4 units Characteristic Required Available Leakage Distance Wet Switching Surge W/S 125 kv 240 kv Impulse W/S 359 kv 374 kv M & E 12,000 lbs 15,000 lbs

40 Grading Rings Simulate a larger, more spherical object Reduce the gradients associated with the shielded object Reduction in gradients helps to minimize RIV & TVI Porcelain or Glass Inorganic breaks down very slowly NCIs Polymers are more susceptible to scissioning due to corona UV short wavelength range attacks polymer bonds. Most short wavelength UV is filtered by the environment UV due to corona is not filtered

41 NCIs and Rings Grading (Corona) Rings Due to corona cutting and water droplet corona NCIs may require the application of rings to grade the field on the polymer material of the weathershed housing. Rings must be: - Properly positioned relative to the end fitting on which they are mounted. - Oriented to provide grading to the polymer material. Consult the manufacturer for appropriate instructions. As a general rule rings should be over the polymer brackets should be on the hardware.

42 Questions?

43 Insulators 101 Section C - Standards Presented by Tony Baker IEEE Task Force Chairman, Insulator Loading IEEE/PES 2010 Transmission and Distribution Conference and Exposition New Orleans, Louisiana April 20, 2010

44 American National Standards Consensus standards Standards writing bodies must include representatives from materially affected and interested parties. Public review Anybody may comment. Comments must be evaluated, responded to, and if found to be appropriate, included in the standard. Right to appeal By anyone believing due process lacking. Objective is to ensure that ANS Standards are developed in an environment that is equitable, accessible, and responsive to the requirements of various stakeholders*. * The American National Standards Process, ANSI March 24, 2005

45 American Standards Committee on Insulators for Electric Power Lines ASC C-29 EL&P Group IEEE NEMA Independents

46 C29 ANSI C29 Insulator Standards (available on-line at nema.org).1 Insulator Test Methods.2 Wet-process Porcelain & Toughened Glass - Suspensions.3 Wet-process Porcelain Insulators - Spool Type.4 - Strain Type.5 - Low & Medium Voltage Pin Type.6 - High Voltage Pin Type.7 - High Voltage Line Post Type.8 - Apparatus, Cap & Pin Type.9 - Apparatus, Post Type.10 - Indoor Apparatus Type.11 Composite Insulators Test Methods.12 - Suspension Type.13 - Distribution Deadend Type.17 - Line Post Type.18 - Distribution Line Post Type.19 - Station Post Type (under development)

47 ANSI C29 Insulator Standards Applies to new insulators Definitions Materials Dimensions & Marking (interchangeability) Tests 1. Prototype & Design, usually performed once for a given design. (design, materials, manufacturing process, and technology). 2. Sample, performed on random samples from lot offered for acceptance. 3. Routine, performed on each insulator to eliminate defects from lot.

48 ANSI C 29 Insulator Standard Ratings Electrical & Mechanical Ratings How are they assigned? How is conformance demonstrated? What are application limits?

49 Electrical Ratings Average flashover values Low-frequency Dry & Wet Critical impulse, positive & negative Impulse withstand Radio-influence voltage Applies to all the types of high voltage insulators Rated values are single-phase line-to-ground voltages. Dry FOV values are function of dry arc distance and test configuration. Wet FOV values function of dry arc distance and insulator shape, leakage distance, material and test configuration. Tests are conducted in accordance with IEEE STD except test values are corrected to standard conditions in ANSI C Temperature 25 C - Barometric Pressure ins. of Hg - Vapor Pressure ins. of Hg - For wet tests: rate 5±0.5 mm/min, resistivity 178±27Ωm, 10 sec. ws

50 Dry Arcing Distance Shortest distance through the surrounding medium between terminal electrodes, or the sum of distances between intermediate electrodes, whichever is shortest, with the insulator mounted for dry flashover test.

51 Electrical Ratings Product is designed to have a specified average flashover. This is the manufacturer s rated value, R. Samples are electrically tested in accordance with standard This is the tested value, T. Due to uncontrollable elements during the test such as atmospheric fluctuations, minor differences in test configuration, water spray fluctuations, etc. the test value can be less than the rated value. Does T satisfy the requirements for the rating R? If T/R Yes where = 0.95 for Low-frequency Dry flashover tests = 0.90 for Low-frequency Wet flashover tests = 0.92 for Impulse flashover tests

52 Electrical Ratings Dry 60 Hz Flashover Data Suspension Insulator 1000 Flashover (kv) Station Post and Line Post Dry Arcing Distance (inches)

53 Electrical Ratings ANSI C2 Insulation Level Requirements 1400 ANSI C2-2007, 2007, Table Rated Dry FOV, kv Nominal Phase-to-Phase Voltage, kv Higher insulation levels required in areas where severe lightning, high atmospheric contamination, or other unfavorable conditions exist

54 Electrical Ratings - Application Customer determines needs and specifies electrical requirements: - 60 Hz Dry & wet flashover - Impulse flashover and/or withstand - Leakage distance Does offered product meet customer s specification S? If R S and T R yes, otherwise no.

55 Mechanical Ratings Sample & Routine Mechanical Tests are based on the primary in-service loading conditions STD. No. Insulator Type Sample test Routine test C 29.2 Ceramic Suspension M&E Tension C29.6 Pin Type Cantilever C29.7 Line Post Cantilever 4 quad. cantilever C29.8 Cap & Pin Cantilever Torsion Tension Tension C29.9 Station Post Cantilever Tension Tension, Cantilever or Bending Moment C29.12 Composite Suspension SML Tension C29.13 Deadend SML Tension C29.17 Line Post Cantilever Tension Tension C29.18 Dist. Line Post Cantilever Tension

56 Mechanical Ratings M&E Test Ceramic Suspensions Bending Tests Composite Posts Kinectrics Hubbell Power Systems

57 ANSI C29 High Voltage Insulator Standards Std. No. Insulator Type C29.2 Ceramic Suspension Ult. Strength QC Test Combined M&E strength of 10 units Lot Acceptance Criteria Ave. Std. dev. = S X 10 R +1.2 S s S Routine Test 3 sec. tension at 50% of R C29.7 Ceramic Line post Cantilever strength of 3 units X 3 R no one x i.85 R 4 quad. bending at 40% of R C29.8 Ceramic Apparatus Cap & Pin C29.9 Ceramic Apparatus Post Type Cantilever, tension, & torsion strength of 3 units each Cantilever & tension strengths of 3 units each X 3 R no one x i.85 R X 3 R no one x i.85 R 3 sec. tension at specified value Tension at 50% of R or 4 quad. bending at 40% of R C29.12 Composite Suspension Specified Mech. Load (SML) test of 3 units x i.r 10 sec. tension at 50% of R C29.13 Composite Distribution Deadend SML test of 3 units x i.sml rating 10 sec. tension at 50% of R C29.17 Composite Line Post Cantilever strength of 1 unit Tension test of 1 unit Strength R 10 sec. tension at 50% of R C29.18 Composite Distribution Line Post Cantilever strength of 1 unit Strength R 10 sec. tension at 50% of R

58 Lot Acceptance Criteria ANSI C29.2 Lot acceptance according to ANSI C Select ten random units from lot and subject to M&E test. Requirements are: M&E rating X S H & s S H s 10 is std. dev. of the 10 units S H is historical std. dev. If s 10 = S H then for minimally acceptable lot, ~ 11.5% of units in lot could have strengths below the rated value.

59 Lot Acceptance Criteria ANSI C29.2 Possible low strengths for ceramic suspension units in a lot minimally acceptable according to ANSI C29.2 Coefficient of variation, v R Strength value at -3σ 5% 90% of M&E rating 10% 79% of M&E rating 15% 67% of M&E rating

60 Lot Acceptance Criteria CSA C411.1 Possible low strengths for ceramic suspension units in a lot minimally acceptable according to CSA C411.1 Requirements Rating X S 3s & X i R On a -3 sigma basis, minimum strength that could be expected in a lot is the rated value regardless of the coefficient of variation for the manufacturing process that produced the lot.

61 Lot Acceptance Criteria ANSI C29 Possible low strengths for ceramic units in a lot minimally acceptable according to ANSI C29.7, C29.8 & C29.9 Cantilever rating X 3 & no x i < 85% of rating Coefficient of variation, v R Strength value at -3 σ 5% 85% of Cantilever rating 10% 70% of Cantilever rating 15% 55% of Cantilever rating

62 Lot Acceptance Criteria ANSI C29 Composite Insulators Random samples selected from an offered lot. Ultimate strength tests on samples. Requirement is: x i Rating The rated value is assigned by the manufacturer based on ultimate strength tests during design. However for a lot minimally acceptable according to the standard, statistical inference for the strength distribution for entire lot not possible. Composite Insulators have a well defined damage limit providing good application direction.

63 Mechanical Ratings Application Limits NESC ANSI C Table Allowed percentages of strength ratings Insulator Type % Strength Rating Ref. ANSI Std. Ceramic Suspension 50% Combined mechanical & electrical strength (M&E) C Line Post 40% 50% Station Post 4 40% 50% Station Cap & Pin 40% 50% Cantilever strength Tension/compression strength Cantilever strength Tension/compression/torsion strength Cantilever strength Tension/compression/torsion strength Composite Suspension 50% Specified mechanical load (SML) Line Post 50% Specified cantilever load (SCL) or specified tension load (STL) C C C C C C C Station Post 50% All strength ratings

64 Mechanical Ratings Application Limits Worst loading case load (% Table 277-1)(Insulator Rating) In most cases, % from Table is equal to the routine proof -test load. Bending tests on a production basis are not practicable in some cases, (large stacking posts, cap & pins, and polymer posts) and tension proof-load tests are specified.

65 Mechanical Ratings Application Limits Composite Post Insulators Combined Loading

66 Mechanical Ratings Application Limits Composite Post Insulators Combined Loading

67 Recent Developments for Application Limits Component strength cumulative distribution function F R and probability density function of maximum loads f Q.

68 Component Damage Limit DAMAGE LIMIT Strength of a component below ultimate corresponding to a defined limit of permanent damage or deformation. For composites the damage limit is fairly well understood.

69 Component Damage Limit Defining Damage Limit for ceramics more difficult to define as shown by comparing stress-strain curves for brittle and ductile materials. L&I WG on Insulators is addressing this problem now

70 Insulators 101 Section D Achieving Quality Presented by Tom Grisham IEEE Task Force Chairman, Insulators 101 IEEE/PES T&D Conference and Exposition New Orleans, LA April 20, 2010

71 Objectives of Quality Presentation Present ideas to verify the supplier qualification, purchasing requirements, manufacturer inspections of lots, shipment approval, material handling, and training information for personnel Routine inspection of the installation Identify steps to analyze field complaints To stimulate Quality improvement

72 Quality Defined QUALITY An inherent, basic or distinguishing characteristic; an essential property or nature. QUALITY CONTROL A system of ensuring the proper maintenance of written standards; especially by the random inspection of manufactured goods.

73 What Is Needed in a Quality Plan? Identifying critical design parameters Qualifying new suppliers Evaluating current suppliers Establishing internal specifications Monitoring standards compliance (audits) Understanding installation requirements Establishing end-of-life criteria Ensuring safety of line workers Communicating and training All aspects defined by the company plan

74 What Documents Should Be Included? Catalog specifications and changes Supplier audit records and lot certification Qualification testing of the design Utility-specific testing Additional supplier testing for insulators (vibration, temperature, long-term performance, etc) ANSI or equivalent design reports Storage methods Installation records (where, by whom, why?) Interchangeability with other suppliers product Handling methods (consult manufacturer) Installation requirements and techniques

75 Proven Installation Procedures

76 Handling of Ceramics NEMA HV Insulators should not be dropped or thrown.. Insulators strings should not be bent.. Insulator strings are not ladders.. Insulators with chips or cracks should be discarded and companion units should be carefully inspected.. Cotter keys should be individually inspected for twisting, flattening or indentations. If found, replace keys and retest the insulator.. The maximum combined load, including safety requirements of NESC, must not exceed the rating.. Normal operating temperature range for ceramics is defined as 40 to 150 Degrees F..

77 Handling of NCI s NEMA is working on a new application guide for NCI products. It will likely include Insulators should not be dropped, thrown, or bent Insulators should not be used as ladders Cotter keys for ball sockets should be inspected identically to the instructions for ceramic insulators The maximum combined loads should not exceed the RTL Normal operating temperature is 40 to 150 Degrees F Insulators should not be used as rope supports Units with damaged housings that expose the core rod should be replaced and discarded Units with cut or torn weathersheds should be inspected by the manufacturer Bending, twisting and cantilever loading should be avoided during construction and maintenance

78 Line outage Failures Your objective is to find the problem, quickly!

79 Inspection Techniques Subjective: What you already know Outage related Visual methods from the ground Previous problem Thermal camera (NCI live line) Objective: Answer is not obvious Leakage current measurements Daycor camera for live line inspections (live) Mechanical and electrical evaluations

80 Porcelain and Glass Failures Failures are typically visible or have a new history or upgrade on the site? New products may not be your Grandfather s Oldsmobile, however! Have the insulators deteriorated? Perform thermal-mechanical test before failing load and compare to ultimate failing load Determine current ultimate strength versus new Should the insulators be replaced? Establish internal criteria by location

81 Non-Ceramic (NCI) Failures Cause of failures may NOT be visible! More subjective methods used for live line replacement Some external deterioration may NOT be harmful Visual examples of critical issues are available to you Imperative to involve the supplier! Evaluate your expertise to define root cause condition Verify an effective corrective action is in place Utilize other sources in the utility industry Establish subjective baselines for new installations as future reference! Porcelain and glass, also!

82 What To Do for an Insulator Failure? Inspection of Failure Supplier Involvement What happened? Extraordinary factors? Save every piece of the unit! Take lots of pictures! Inspect other insulators! Verification of production date? Available production records? Determination of root cause? Recommended action? Safety requirements?

83 Summary of Quality Presentation In today s environment, this presentation suggests that the use of a well documented quality program improves long term performance and reduces outages. Application information that is communicated in the organization will help to minimize installation issues and reduce costs. Actively and accurately defining the condition, or determining the root cause of a failure, will assist in determining end-of-life decisions.

84 Source of Presentation

Composite Insulator Components

Composite Insulator Components Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the

More information

Veri*Lite Deadend, Suspension & Line Post Insulators for 15-69kV Applications

Veri*Lite Deadend, Suspension & Line Post Insulators for 15-69kV Applications Veri*Lite Deadend, Suspension & Line Post Insulators for 569kV Applications Section Warranty Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is defined

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

GROUP A. Polymeric Insulators.

GROUP A. Polymeric Insulators. GROUP A Polymeric Insulators PYUNGIL Bldg., 1475-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-6650~3 FAX : 82-31-424-7300 www.pyungil.com Silicone Railway

More information

General Requirements. Technical Specifications for Insulators of Transmission Lines

General Requirements. Technical Specifications for Insulators of Transmission Lines Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission

More information

Polymer Suspension Insulators 69kV to 765kV

Polymer Suspension Insulators 69kV to 765kV CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Transmission Silicone Insulators Line Post 69 kv to 230 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R PAGE: 1 Test Requests: R18-01-03 Report Number: R18-01-03 Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R18-01-03 Introduction: Sample Quadri*Sil line

More information

Polymer Post Insulators for 46 to 500kV Applications

Polymer Post Insulators for 46 to 500kV Applications CATALOG 142 Polymer Post Insulators for 46 to 500kV Applications NGK-Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Process and Design Features...2 Materials...3 Application

More information

INSULATOR REQUERIMENTS:

INSULATOR REQUERIMENTS: 2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL

More information

United States Department of Agriculture Rural Development Rural Utilities Service. RUS Bulletin 1724E-220

United States Department of Agriculture Rural Development Rural Utilities Service. RUS Bulletin 1724E-220 United States Department of Agriculture Rural Development Rural Utilities Service RUS Bulletin 1724E-220 SUBJECT: Procurement and Application Guide for Non-Ceramic Composite Insulators, Voltage Class 34.5

More information

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS

GUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6

More information

Polluted Outdoor Insulators Maintenance and Washing

Polluted Outdoor Insulators Maintenance and Washing Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان

More information

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv

TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv K-LINE INSULATORS LIMITED Catalogue TD-IPS TORONTO, ONTARIO, CANADA TRANSMISSION & DISTRIBUTION SILICONE INSULATORS InterPhase Spacers 15 kv to 400 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission &

More information

INSULATORS NEW. See page J-4 for more information.

INSULATORS NEW. See page J-4 for more information. INSULATORS INSULATORS NEW Improved 23613 Dead End/Suspension Insulator Salisbury s Improved 23613 Dead End/Suspension Insulator has aluminum end fittings. These new end fittings create a lightweight product

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS

CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC. INSULATORS

More information

Composite insulators. Features. Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems. siemens.com/rail-electrification

Composite insulators. Features. Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems. siemens.com/rail-electrification Composite insulators Sicat 8WL3068, 8WL3078 and 8WL3088 for overhead contact line systems siemens.com/rail-electrification The Sicat 8WL3068, 8WL3078 and 8WL3088 type silicone composite insulators in accordance

More information

What to Look for in a Good Quality Arrester

What to Look for in a Good Quality Arrester All good quality arresters have much in common. This first in a series of articles, sponsored by NEMA Surge Arrester Section members, covers what to look for in that quality arrester. Introduction We've

More information

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements

More information

Maharashtra State Electricity Distribution Co. Ltd.

Maharashtra State Electricity Distribution Co. Ltd. Maharashtra State Electricity Distribution Co. Ltd. SPECIFICATION NO. MSEDCL/ DIST:MM-III/06/2006 SPECIFICATION FOR H.T.DISC INSULATORS 1 TECHNICAL SPECIFICATION FOR 11 KV 45 KN / 70 KN DISC INSULATORS

More information

PS2: Lifetime management, deterioration and ageing of substation equipment

PS2: Lifetime management, deterioration and ageing of substation equipment PS2: Lifetime management, deterioration and ageing of substation equipment Ageing and deterioration of composite post insulators exposed to high electric field in 220 kv and 400 kv switchyards in Swedish

More information

Outdoor High Voltage Non-Ceramic Insulators

Outdoor High Voltage Non-Ceramic Insulators Outdoor High Voltage Non-Ceramic Insulators V.P. Karthika 1, P. Anitha 2, A. Hearty Rugesh 3 1 Teaching Fellow, 2 Assistant Professor, 3 UG Student 1, 2, 3 Department of EEE, Anna University, Thoothukudi

More information

Walk through the associated design considerations associated with transmission line design

Walk through the associated design considerations associated with transmission line design Walk through the associated design considerations associated with transmission line design Follow-up to Transmission Design 101 (2012) & Transmission Design 102 (2013) Additional design considerations

More information

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Cigré WG C Topics: The selection of insulators with respect to polluted conditions Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise

More information

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60

CONTENTS. IEC Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 IEC 61109 Ed. 2 /CDV IEC 2 36B/ /CDV 36B-MT10/Nuremberg3/60 CONTENTS FOREWORD...4 INTRODUCTION...5 1 Scope and object...7 2 Normative references...7 3 Definitions...8 4 Abbreviations...9 5 Identification...9

More information

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008

Notes Changed note Date. 1 (A) Changed template 09 / 07 / 2008 Revisions Notes Changed note Date 1 (A) Changed template 09 / 07 / 2008 2 Changed template. Clause 12.5.4.1 hot-rolled steel added. Clause 12.5.4.2, 12.5.2.4, 12.5.3.4, 12.5.4.4, 12.5.5.4, 12.5.6.4, 12.5.7.4

More information

Project number 36B/61952/Ed2. Date of circulation Supersedes document 36B/231/MCR. Safety EMC Environment Quality assurance

Project number 36B/61952/Ed2. Date of circulation Supersedes document 36B/231/MCR. Safety EMC Environment Quality assurance IEC/TC or SC: SC 36B Title of TC/SC: Insulators for overhead lines Also of interest to the following committees TC 11 Functions concerned: Project number 36B/61952/Ed2 Date of circulation 2004-03-19 Supersedes

More information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.

More information

Veri*Lite Silicone Rubber Line Post Insulators for 15-72kV Applications

Veri*Lite Silicone Rubber Line Post Insulators for 15-72kV Applications Section 2-2 Veri*Lite Silicone Rubber Line Post Insulators for 15-72kV Applications Warranty - Material Hubbell Power Systems, Inc. warrants all products sold by it to be merchantable (as such term is

More information

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to:

PI Electrical Equipment - tourse PI 30.2 INSULATION. On completion of this module the student will be able to: Electrical Equipment - tourse PI 30.2 INSULATION OB~ECTIYES On completion of this module the student will be able to: 1. Explain. in writing, the term "leakage current" and indicate the normal range of

More information

Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL

Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL Station Post Insulators (SPI), an Emerging Application for Composite Hollow Core Insulators PETER STAHL Composite Hollow Core Station Post Insulators (SPI) Peter Stahl, July 2015 Applications for composite

More information

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1

TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 I NDEPENDE N T POWER TR ANSM ISSION OP ER AT O R S.A. TRANSMISSION NEW PROJECTS DEPARTMENT TRANSMISSION LINES TOWER DESIGN AND SPECIFICATIONS SECTION ATHENS - GREECE SPECIFICATION TR-1 STRING INSULATOR

More information

Design of MO Surge Arresters with Polymeric Housings

Design of MO Surge Arresters with Polymeric Housings Design of MO Surge Arresters with Polymeric Housings Kai Steinfeld (Director R&D Surge Arresters) High Voltage Surge Arrester s Voltages in Electric Power Systems Voltage Limiting Effect of Surge Arresters

More information

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10

More information

ILMOS Insulator Leakage Current Monitor

ILMOS Insulator Leakage Current Monitor ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS

APDRP SCHEME, WESCO. Technical Specification for 33KV Air Break Switch PART 1: SCOPE AND CONDITIONS PART 1: SCOPE AND CONDITIONS 1. SCOPE This specification covers the design, engineering, manufacture, testing, supply, delivery, off-loading and performance requirements of 33kV, 200 amp, triple pole Gang

More information

Polymer Station Post Insulators for 69 to 345 kv Applications

Polymer Station Post Insulators for 69 to 345 kv Applications CATALOG 143 Polymer for 69 to 34 kv Applications NGK-Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Polymer... 1 Application Guidelines for Polymer Station Posts (SP)...

More information

ISO Rules Part 500, Facilities Division 502, Technical Requirements Section Bulk Transmission Technical Requirements

ISO Rules Part 500, Facilities Division 502, Technical Requirements Section Bulk Transmission Technical Requirements Part 500, Facilities Division 502, Technical Requirements Section 502.2 Bulk Transmission Technical Requirements Applicability 1 This section 502.2 applies to: Requirements the legal owner of any bulk

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels

CS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels Climate test equipment. Allows to perform test in various temperature and humidity conditions. CS type composite silicone insulators up to overhead lines for all pollution of the atmosphere levels Insulators

More information

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering

More information

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN )

Standard. Extra High Voltage (EHV) Post Insulators Standard R Version 1.0, June Tasmanian Networks Pty Ltd (ABN ) Standard Extra High Voltage (EHV) Post Insulators Standard R574184 Version 1.0, June 2018 Tasmanian Networks Pty Ltd (ABN 24 167 357 299) Authorisations Action Name and title Date Prepared by Michael Verrier,

More information

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's

NATIONAL ELECTRIC POWER COMPANY (NEPCO) TENDERNO. 9/2013 FOR THE SUPPLY OF INSULATORS AND FITTINGS FOR DOUBLE AND QUADRUPLE CIRCUITS 132 kv OHTL's TENDERNO. 9/2013 7. TECHNICAL SPECIFICATION 7.A SCOPE: This specification covers the design, manufacture, testing, packing, supply, CFR delivery to Aqaba Docks in Jordan and guarantee (maintain) the following

More information

Seismic Considerations of Circuit Breakers

Seismic Considerations of Circuit Breakers Seismic Considerations of Circuit Breakers Willie Freeman, IEEE 693 Working Group ABB Inc, Mt. Pleasant PA, USA IEEE Tutorial - 2008 Abstract: The tutorial covers the seismic qualification of high voltage

More information

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Human photo. Can be environmental/ documentaty style or portrait of engineer. industry photo.

More information

Understanding New IEC Mechanical Test Requirements of Arresters

Understanding New IEC Mechanical Test Requirements of Arresters Understanding New IEC Mechanical Test Requirements of Arresters ArresterFacts 007 Understanding New IEC Mechanical Test Requirements of Arresters New Cyclic Load Test (1000 cycles) 1 cycle every 2 seconds

More information

12-SDMS-01 Rev.02 SPECIFICATIONS FOR

12-SDMS-01 Rev.02 SPECIFICATIONS FOR 12-SDMS-01 Rev.02 SPECIFICATIONS FOR CABLE JOINTS, TERMINATIONS, AND ACCESSORIES UP TO 36 KV This specification is property of SEC and is subject to change or modification without any notice. TABLE OF

More information

RB 107 Specification DuraSeal Splices

RB 107 Specification DuraSeal Splices 00 Constitutional Drive 1 of 1 RB 107 Specification DuraSeal Splices 1.0 Introduction 1.1 Scope This specification covers a series of one-piece pre-insulated crimp splices having a heatshrinkable sleeve

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

SPECIFICATIONS FOR Gas-to-Cable termination

SPECIFICATIONS FOR Gas-to-Cable termination Product GSM-145 1.0 APPLICATION: Gas-to-cable termination is a part of high voltage gas insulated indoor switchgear equipment. The component is intended for a high voltage system of 132 kv (AC), 50 Hz.

More information

TEMPERED GLASS INSULATORS

TEMPERED GLASS INSULATORS TEMPERED GLASS INSULATORS SUSPENSION-TYPE» Non-conducing support composed of an insulating glass piece and iron fittings allowing other units to be connected in series. A fastening iron fitting is included

More information

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines

Technical Specification for. Insulators. Part 1. Insulators for High and Extra-High Voltage Overhead Lines Page: 1 / 18 for Insulators Part 1 Insulators for High and Extra-High Voltage Overhead Lines 1.2 Cap-and-pin insulators made of pre-stressed glass This technical specification is valid for the business

More information

Mechanical Testing and Evaluation of Braced Line Post Assemblies Composed of Non- Ceramic Insulators

Mechanical Testing and Evaluation of Braced Line Post Assemblies Composed of Non- Ceramic Insulators 1 Mechanical Testing and Evaluation of Braced Line Post Assemblies Composed of Non- Ceramic Insulators R. A. Bernstorf Hubbell Power Systems Abstract This paper discusses the elastic buckling load of braced

More information

DESIGN TEST REPORT. GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator..

DESIGN TEST REPORT. GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator.. December 4, 2010 DESIGN TEST REPORT Insulator Reference: GAMMA Insulators 6184R-70 ANSI Class 55-3 Pin Type Insulator.. Electrical Design Tests 1. Low-Frequency Dry Flashover Test: Three insulators were

More information

DESIGN TEST REPORT. GAMMA Insulators 7061R-70 ANSI Class 55-5 Pin Type Insulator.

DESIGN TEST REPORT. GAMMA Insulators 7061R-70 ANSI Class 55-5 Pin Type Insulator. December 6, 2010 DESIGN TEST REPORT Insulator Reference: GAMMA Insulators 7061R-70 ANSI Class 55-5 Pin Type Insulator. Electrical Design Tests 1. Low-Frequency Dry Flashover Test: Three insulators were

More information

DESIGN TEST REPORT. GAMMA Insulators 6183R-70 ANSI Class 55-4 Pin Type Insulator.

DESIGN TEST REPORT. GAMMA Insulators 6183R-70 ANSI Class 55-4 Pin Type Insulator. December 2, 2010 DESIGN TEST REPORT Insulator Reference: GAMMA Insulators 6183R-70 ANSI Class 55-4 Pin Type Insulator. Electrical Design Tests 1. Low-Frequency Dry Flashover Test: Three insulators were

More information

Qualification Test Report VAL-U-LOK* Connectors

Qualification Test Report VAL-U-LOK* Connectors Qualification Test Report VAL-U-LOK* Connectors 501-534 09Apr09 Rev A 1. INTRODUCTION 1.1. Purpose 1.2. Scope Testing was performed on VAL-U-LOK* Connectors to determine their conformance to the requirements

More information

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA

094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA 094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard

More information

Development of Composite Line Spacers for Distribution Lines

Development of Composite Line Spacers for Distribution Lines Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

Panagiotis Charalampidis

Panagiotis Charalampidis Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,

More information

Polymer Cutout Testing Recommendations

Polymer Cutout Testing Recommendations 1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)

More information

CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS

CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS 25 CHAPTER 2 STRUCTURE AND CRITICAL E-FIELDS 2.1 INTRODUCTION Polymeric insulators have been commercially produced and utilized for more than four decades now. Their demand is still increasing rapidly

More information

SPECIFICATION FOR DISC INSULATORS (Standard Type)

SPECIFICATION FOR DISC INSULATORS (Standard Type) Doc. KPLC1/3CB/TSP/04/015 1 Page 1 of 6 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6. MARKING,

More information

Diagnostic Techniques of Composite Insulators

Diagnostic Techniques of Composite Insulators Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI

More information

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan Substation Insulator Pollution Contamination Management PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION

More information

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate

More information

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE.

STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV. Approved by AMERICAN NATIONAL STANDARDS INSTITUTE. ANSI/ICEA S-108-720-2012 STANDARD FOR EXTRUDED INSULATION POWER CABLES RATED ABOVE 46 THROUGH 345 KV Approved by AMERICAN NATIONAL STANDARDS INSTITUTE November 27, 2012 Publication # ANSI/ICEA S-108-720-2012

More information

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines :, Lr.4 iecii 2009 ITIITtM iim i Now TerMrrkçes âi Tims,rsGq, OeJj & ConTnuniatNo A. Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission

More information

Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement

Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement Innovative New Live Line Tool and Framing Designs Facilitating Safe and Efficient Cross-arm Replacement A.J. Carreira, P.Eng., SMIEEE President Toronto, Canada carreira@k-line.net ISSUES WITH CURRENT CROSS

More information

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL

SECTION MEDIUM-VOLTAGE CABLES PART 1 GENERAL SECTION 260513 - MEDIUM-VOLTAGE CABLES PART 1 GENERAL 1.1 SECTION INCLUDES A. Medium voltage cable. B. Cable terminations. C. This specification describes single conductor EPR (Ethylene-propylene-rubber)

More information

Failure of a suspension or tension insulator

Failure of a suspension or tension insulator Failure of a suspension or tension insulator Abstract:Failure of a suspension or tension insulator is clearly something that every utility or insulator manufacturer wishes would never occur. However, it

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS

DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS The 20 th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, August 27 September 01, 2017 DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF

More information

Introduction to Substation Design TADP 542

Introduction to Substation Design TADP 542 Introduction to Substation Design TADP 542 Substation Structures - Design Loads Instructor: Dr. Yenumula Prasad Transmission & Distribution Program Substation Structures- Design Loads References Substation

More information

V. Design, Application, Maintenance & Operation Technical Requirements

V. Design, Application, Maintenance & Operation Technical Requirements V. Design, Application, Maintenance & Operation Technical Requirements V.A PJM Design & Application of Overhead Transmission Lines 69 kv & Above These design criteria have been established to assure acceptable

More information

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS

TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS SEAL & SIGNATURE OF THE TENDERER PAGE 1 OF 11 TECHNICAL SPECIFICATION FOR LT PIN/SHACKLE INSULATORS 1.0 Scope : The specification covers the manufacture,

More information

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,

More information

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA

093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA 093 : 2000 CEB STANDARD MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN POST INSULATORS AND HARDWARE CEB Standard 093 : 2000 CEYLON

More information

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854

QUALIFICATION UPDATE. Eric Rasmussen. Quality Cables Since 1854 QUALIFICATION UPDATE Eric Rasmussen Quality Cables Since 1854 90 C 60 year Four successful qualifications to date: QR-1305: Kerite Shielded MV Power Cables for 60 Year Life at 90 C (LOCA) QR-1403: Kerite

More information

Necessary Check Points & Testing for Screening the Quality of Insulators

Necessary Check Points & Testing for Screening the Quality of Insulators Necessary Check Points & Testing for Screening the Quality of Insulators J.M. George, E. Brocard, S. Prat, F. Virlogeux, D. Lepley Sediver Research Center, France Introduction The increasing demand for

More information

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS

TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS TURKISH ELECTRICITY DISTRIBUTION CO. TECHNICAL SPECIFICATION FOR POST (SUPPORT) INSULATORS FOR MEDIUM VOLTAGE SYSTEMS CONSULTANT: ELTEM-TEK ELECTRICAL INSTALLATIONS ENGINEERING SERVICES AND TRADE CO. JUNE,

More information

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.

More information

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units

Surge arrester 3EB1. with polymeric composite housing for operating aboard traction units Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders

More information

Design features - Polymer-housed arresters, PEXLIM

Design features - Polymer-housed arresters, PEXLIM features - Polymer-housed arresters, PEXLIM PEXLIM arresters, using the same ZnO blocks as the EXLIM arresters, match their electrical performance. Silicone as outer insulation material has been used for

More information

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines

Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines K. R. Suri a, A. Gupta b, Y. Anand b, S. Anand b General Manager (Retd.), Power Grid Corporation of India Limited School of Energy

More information

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216

More information

UNS 5kA Arrester. Certified Test Report IEC

UNS 5kA Arrester. Certified Test Report IEC CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS:

SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: SPECIFICATION FOR HT PIN (11KV & 22KV) AND 11KV DISC. INSULATORS: - [THIS TENDER IS FOR PURCHASE OF HT (11KV) PIN INSULATORS ONLY] 1. SCOPE: - This specification covers 11KV Disc Type & 11KV / 22KV Pin

More information

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA

Sediver toughened glass insulators for HVAC applications. Experts & Pioneers USA Sediver toughened glass insulators for HVAC applications Experts & Pioneers USA Sediver, Experts and Pioneers in insulation technology This catalog presents a selection of the Sediver toughened glass insulator

More information

Cutouts and Fuse Links Equipment to protect against faults and over-current conditions on power distribution systems. Open-Type Cutouts Linkbreak Cutouts Loadbreak Cutouts Cutout-Arrester Combinations

More information