AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.
|
|
- Mark Gibson
- 5 years ago
- Views:
Transcription
1 AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT Rendered to: BUILDERS ACCESSORIES, INC. SERIES/MODEL: 6490 PRODUCT TYPE: Polyvinyl Chloride (PVC) Casement Window Title Summary of Results Primary Product Designator C-C x 1499 (32 x 59) Design Pressure ±1440 Pa (±30.08 psf) Operating Force (in motion) 17 N (3.8 lbf) Air Infiltration 0.05 L/s/m 2 (0.01 cfm/ft 2 ) Water Penetration Resistance Test Pressure 580 Pa (12.11 psf) Uniform Load Structural Test Pressure ±2160 Pa (±45.11 psf) Forced Entry Resistance Grade 10 Test Completion Date: 04/26/10 Reference must be made to Report No , dated 05/18/10 for complete test specimen description and data E. Jensen Ave Fresno, CA phone: fax:
2 AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT Rendered to: BULDERS ACCESSORIES, INC. 550 West Southern Avenue #101 Tempe, Arizona Report No.: Test Dates: 03/08/10 Through: 04/26/10 Report Date: 05/18/10 Expiration Date: 04/26/14 Project Summary: Architectural Testing, Inc. was contracted by Builders Accessories, Inc. to perform testing on a Series/Model 6490, Polyvinyl Chloride (PVC) Casement Window. The sample tested successfully met the performance requirements for a C-C x 1499 (32 x 59) rating. Test specimen description and results are reported herein. The sample was provided by the client. Test Specification: The test specimen was evaluated in accordance with AAMA/WDMA/CSA 101/I.S.2/A440-05, Standard/Specification for Windows, Doors, and Unit Skylights. Test Specimen Description: Series/Model: 6490 Product Type: Polyvinyl Chloride (PVC) Casement Window Overall Size: 800 mm (31-1/2") wide by 1499 mm (59") high Vent Size: 679 mm (26-3/4") wide by 1378 mm (54-1/4") high Overall Area: 1.20 m 2 (12.91 ft 2 ) Finish: All PVC was white Frame Construction: All members were constructed of extruded PVC. The corners were mitered and fully welded. Vent Construction: All members were constructed of extruded PVC. The corners were mitered and fully welded E. Jensen Ave Fresno, CA phone: fax:
3 Page 2 of 7 Test Specimen Description: (Continued) Weatherstripping: Description Quantity Location Wrapped foam gasket 3 Rows All members of vent. Glazing Details: The window utilized 7/16" thick overall sealed insulating glass. The insulating glass was comprised of two 1/8" thick clear annealed sheets with an aluminum Butyl composite (A8) spacer system. The glass was exterior glazed onto a 3/8" wide x 1/16" tall glazing tape and secured with a snap-in extruded PVC glazing bead. Drainage: No drainage was utilized. Hardware: Description Quantity Location Hinges (part# ) 2 Head and sill at hinge jamb secured to the vent with four #8 x 3/4" Phillips flat head screws and to the frame with four #6 x 1/2" Phillips flat head screws. Three Point Lock Assembly 1 Lock jamb with plastic guides 16- (part# / 45300) 3/4", 29-1/4", 39-1/2" and 44-1/4" from sill secured with two #8 x 3/4" Phillips flat head screws each. Lock Handle (part# ) 1 9" from sill secured to through lock jamb of frame with two x 9/16" Phillips pan head screws. Keepers (part# ) /2", 23-1/2" and 40-1/4" from bottom rail on lock stile of vent secured with two M4 x 1/2" Phillips flat head screws each.
4 Page 3 of 7 Test Specimen Description: (Continued) Hardware: (Continued) Description Quantity Location Rotor operator (part# ) /2" from hinge jamb on sill secured to frame with eight #8 x 3/4" Phillips flat head screws and to the vent with three 8-32 x 3/4" slotted oval head bolt with 1/2" sex nuts and three #8 x 3/4" Phillips flat head screws. Snubbers (part# 6301) 6 9-1/4" from each and end and midspan on hinge stile of vent and opposite on frame secured with two #8 x 3/4" Phillips flat head screws each. Reinforcement: No reinforcement was utilized. Installation: The window was installed into a 2 x 10 test buck constructed of Douglas Fir No. 2 lumber. The nailing fin was set against the test buck and secured using #6 x 1-5/8" drywall screws located 3" from each corner and 16" on center. The rough opening was 1/8" wider and a 1/2" taller than the window. The nailing fin was sealed to the test buck with silicone.
5 Page 4 of 7 Test Results: The temperature during testing was C (60-73 F). The results are tabulated as follows: Paragraph Title of Test - Test Method Results Allowed Operating Force per ASTM E 2068 Open Initiate motion 17 N (3.8 lbf) Report Only Maintain motion 17 N (3.8 lbf) 45 N (10.1 lbf) Latches 59 N (13.3 lbf) 100 N (22.5 lbf) Close Initiate motion 26 N (5.9 lbf) Report Only Maintain motion 13 N (3.0 lbf) 45 N (10.1 lbf) Latches 85 N (19.0 lbf) 100 N (22.5 lbf) Air Leakage Resistance per ASTM E Pa (1.57 psf) 0.05 L/s/m L/s/m 2 (0.01 cfm/ft 2 ) (0.3 cfm/ft 2 ) max. Note #1: The tested specimen meets (or exceeds) the performance levels specified in AAMA/WDMA/CSA 101/I.S.2/A for air leakage resistance Water Penetration Resistance per ASTM E 547 and E 331 See Note #2 Note #2: The client opted to start at a pressure higher than the minimum required. Those results are listed under "Optional Performance" Uniform Load Deflection per ASTM E 330 (Deflections were taken on the top rail of vent) (Loads were held for 10 seconds) 1440 Pa (30.08 psf) (positive) 1.5 mm (0.06") See Note # Pa (30.08 psf) (negative) 3.0 mm (0.12") See Note #3 Note #3: The deflections reported are not limited by AAMA/WDMA/CSA 101/I.S.2/A for this product designation. The deflection data is recorded in this report for special code compliance and information only Uniform Load Structural per ASTM E 330 (Permanent sets were taken on the top rail of vent)) (Loads were held for 10 seconds) 2160 Pa (45.11 psf) (positive) 0.3 mm (0.01") 2.1 mm (0.08") max Pa (45.11 psf) (negative) 0.5 mm (0.02") 2.1 mm (0.08") max.
6 Page 5 of 7 Test Results: (Continued) Paragraph Title of Test - Test Method Results Allowed Forced Entry Resistance per ASTM F 588 Type: B Grade: 10 Disassembly Test No entry No entry Test B1 No entry No entry Test B2 No entry No entry Test B3 No entry No entry Sash/Panel Manipulation Test No entry No entry Lock Hardware Manipulation Test No entry No entry Thermoplastic Corner Weld Test Meets as stated Meets as stated Sash Vertical Deflection Test 270 N (60.7 lbf) 2.5 mm (0.10") 13.5 mm (0.53") max Distributed Load Test 300 Pa (6.27 psf) No damage No damage Optional Performance Water Penetration Resistance per ASTM E 547 and E Pa (12.11 psf) No leakage No leakage Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test. Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen reported herein. List of Official Observers: Name David Douglass Mason Kelly Company Architectural Testing Inc. Architectural Testing Inc.
7 Page 6 of 7 Detailed drawings, data sheets, representative samples of test specimens, a copy of this report, or other pertinent project documentation will be retained by Architectural Testing, Inc. for a period of four years from the original test date. At the end of this retention period, such materials shall be discarded without notice and the service life of this report will expire. Results obtained are tested values and were secured by using the designated test methods. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in the test specimen can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, INC. Jeffrey T. Osugi Technician Leaton Kirk Director-Regional Operations JO: ms Attachments (pages): This report is complete only when all attachments listed are included. Appendix-A: Alteration Addendum (1) Appendix-B: Test Equipment (1) Appendix-C: Drawings (6)
8 Page 7 of 7 Revision Log Rev. # Date Page(s) Revision(s) 0 05/18/10 N/A Original report issue This report produced from controlled document template ATI 00159, revised 03/05/09.
9 Appendix A Alteration Addendum Alteration #1: Date-03/25/10 Cause for alteration- Failed uniform load test. Remedial action taken- Snubber changed from Truth (Part# ) to Mikron (part# 6301). Operator screws changed to sex nuts and bolts. Alteration #2: Date-04/26/10 Cause for alteration- Failed distributed load test. Remedial action taken- Operator changed from Truth split single arm to dual arm.
10 Appendix B Test Equipment
11 Instrument Manufacturer Asset # Torque Wrench CDI C Operating force gauge Chatillon Control Panel ATI Spray Rack ATI Linear Transducer Celesco Linear Transducer Celesco Linear Transducer Celesco Control Panel ATI Spring Scale Pelouze Bench Scale My Weigh C62323 Dial Indicator Starrett MULE (mini) ATI Load Cell 1K Interface
12 Appendix C Drawings
13
14
15
16
17
18
TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window
TEST REPORT Report No.: D8932.01-301-44 Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS SERIES/MODEL: 800MD Signature PRODUCT TYPE: Fixed Plastic Glazed Skylight Title Summary
More informationAAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)
AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: ALUMIL US SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) Title Summary of Results Primary Product Designator HS-C30
More informationTEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina
Architectural Testing TEST REPORT Report No.: A6303.08-250-44 Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina PRODUCT TYPE: Double Hung Window SERIES/MODEL: VictorBilt Palmetto
More informationINTERNATIONAL WINDOW TEST REPORT
INTERNATIONAL WINDOW TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-08 AND -11 TESTING ON 7223 O/X AWNING WINDOW REPORT NUMBER H5789.01-301-44 R1 TEST DATE(S) 09/13/17-09/18/17 ISSUE DATE REVISION
More informationTEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania
Architectural Testing TEST REPORT Report No.: B2133.01-109-47 Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania PRODUCT TYPE: PVC Single Hung Window (Fin) SERIES/MODEL: 3540 SPECIFICATION: AAMA/WDMA/CSA
More informationTEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11
TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.04-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum Outswing Casement Window SERIES / MODEL: W250C Test Summary
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5562.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5467.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5468.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio
TEST REPORT Report No.: E6273.02-501-47 Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio PRODUCT TYPE: PVC Single Hung Window SERIES/MODEL: 143.095 Single Hung SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Pa ge: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-115.0 Issue Date: Revision Date:
More informationArchitectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310
Architectural Testing TEST REPORT Report No.: E2257.01-901-44 Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 SPECIFICATIONS: AAMA/WDMA/CSA
More informationTEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania
TEST REPORT Report No.: F7299.01-109-47 Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania PRODUCT TYPE: Polyvinyl Chloride (PVC) Picture Window SERIES/MODEL: HM155 SPECIFICATION(S): AAMA/WDMA/CSA
More informationTEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California
TEST REPORT Report No.: E5564.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XXO) SERIES/MODEL: 8880 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,
More informationTEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:
Architectural Testing TEST REPORT Report No.: D7201.01-901-44 Rendered to: ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: AAMA/WDMA/CSA
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-109.0 Issue Date: Revision Date:
More informationPERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY
PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors/Round Top Double PRODUCT TYPE: In-swing Round Top Double Door LH-4-5/8 Title Uniform Load Deflection
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-113.0 Issue Date: Revision Date:
More informationStructural Performance Certification Authorization Report
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-105.0 Issue Date: Revision Date:
More informationTEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G6910.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure ±2640
More informationANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.
ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 1000 Sliding Window PRODUCT: PVC Horizontal Sliding Window Summary of Results Title Test Specimen
More informationDennis Fassnacht Jr :59:35-04'00'
Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-103.0 Issue Date: Revision Date:
More informationTEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11
TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.02-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum fixed window SERIES / MODEL: W250C Test Summary of Results
More informationTEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G8680.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Double Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure
More informationTEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan
Architectural Testing TEST REPORT Report No.: A2941.01 109 44 Rendered to: TUBELITE, INC. Walker, Michigan PRODUCT TYPE: Aluminum Side Hinge Door SERIES/MODEL: Thermal=Block Summary of Results Title Test
More informationAAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY
AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA 910-93 TEST REPORT SUMMARY Rendered to: GIESSE NORTH AMERICA 2014 Holston Industrial Drive Blountville, TN 37617 PRODUCT TYPE: XO Sliding
More informationPERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly
PERFORMANCE TEST REPORT Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly Title Summary of Results Air Infiltration
More informationAAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:
AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT SUMMARY Rendered to: AluminTechno LLC. 12 Selitskog Street, Room 211 FEZ Minsk, Minsk District, Minsk Region 220075 Republic
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE 4646 2004B PRODUCT TYPE: Venting Curb Mounted Skylight Report No: Test Date: 01/06/10 Report Date: 03/15/10 Expiration
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door
MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: FLEETWOOD WINDOWS & DOORS SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door This report contains in its entirety: Cover Page: 1 page
More informationPERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel
PERFORMANCE TEST REPORT Rendered to: ALL-WEATHER INSULATED PANELS SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel Title Summary of Results Air Infiltration
More informationTEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California
TEST REPORT Report No.: G9949.01-303-47 Rendered to: CR LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Fixed Lite Storefront System SERIES/MODEL: IT451 Title Summary of Results Design Pressure ±1440
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7921.02 501 44 Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: 4650DH
More informationPERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina
PERFORMANCE TEST REPORT Report No.: H0140.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Curb Mounted Skylight SERIES/MODEL: Specials Dome Skylight 0.118 Thickness PC
More informationASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC
ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Solar Gard Armorcoat 8-mil Film PRODUCT TYPE: Fixed Window with Applied
More informationAAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania
AAMA 506 TEST REPORT Report No.: G0434.01-501-44 Rendered to: VEKA INC. Fombell, Pennsylvania PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: DH57WW/AL-Insert Test Date(s): 06/28/16 Test Record Retention
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A2653.02 401 44 Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama PRODUCT TYPE: Curtain Wall SERIES/MODEL: PW257 Captured
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama
Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT This report contains in its entirety: Cover Page: 1 page Report Body: 10 pages Sketches: 2 pages Photographs: 4 pages Drawings: 7 pages Report
More informationTEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results
Architectural Testing TEST REPORT Report No.: C0231.01-201-44 Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas PRODUCT TYPE: Side-Hinged Door SERIES/MODEL: 3070 Fiberglass Door SPECIFICATION:
More informationTEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana
Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite
More informationETC Laboratories Measuring Up To Your Standards And More
ETC Laboratories Measuring Up To Your Standards And More Corporate Offices / Laboratories 460 Buffalo Rd. Rochester, NY 14611 (585) 328-7668 Fax: (585) 328-7777 Report Number: ETC-09-329-22959.2 Test Start
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: COASTAL INNOVATIVE PRODUCTS SERIES/MODEL: Outswing Aluminum Bi-Folding System TYPE: Swinging Door with Frame Summary of Results
More informationAAMA/WDMA/CSA 101/I.S.2/A440-08
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Manufactured under licence by: Report No.: AI-03820-C2 (Reissue-10) DOMINION DOORS AND WINDOWS LTD. 130 PENNSYLVANIA AVE. UNIT 8 CONCORD,
More informationTEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series
Architectural Testing TEST REPORT Report No.: C6304.01-301-44 Rendered to: All Weather Insulated Panels Vacaville, California PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Title Summary of Results
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FCM 4646 0004B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight Report No: 90752.03-109-44 Test Date: 07/27/09 Report Date:
More informationArchitectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.
Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT Report Number: C0271.01-450-44 Rendered to: Tubelite Inc. Walker, Michigan MODEL DESIGNATION: 400 Series Curtainwall with 4 Sided SSG PRODUCT
More informationMOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall
Architectural Testing MOCK-UP TEST REPORT Rendered to: TUBELITE INC PROJECT: 300 ES Interior Glazed Curtain Wall Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight Report No: Test Date: 04/01/09 Report Date: 10/20/09 Record Retention Date:
More informationASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut
Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7795.01 109 44 Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT
More informationOSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight
OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FS S06 2004 PRODUCT TYPE: Fixed Deck Mounted Skylight Report No: 96238.02-109-44 Test Date: 01/06/10 Report Date: 01/09/18
More informationMIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems
This report contains in its entirety: Cover Page: 1 page Report Body: 15 pages Sketches: 7 pages Drawing: 1 page MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT SERIES/MODEL: Brick Veneer
More informationTEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series
Architectural Testing TEST REPORT Report No.: D5082.01-301-32 Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Title Summary of Results
More informationTEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
TEST REPORT Report No.: E9891.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: Vulkem 116 Illmod 600 Acrytec Panel SPECIFICATION: ASTM E 330, Standard
More informationSTRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 )
Element Materials Technology 115 South 84th Ave Wausau, WI 54401, USA 407-505-8102 Report No.: ESP101311P-6_012404P-6 Report Date: July 18, 2012 STRUCTURAL PERFORMANCE TEST REPORT Test Requested By: Earthwise
More informationAAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door
Architectural Testing AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440 TYPE: Sliding Glass Door ATI Data File No. 71967.01 Summary of Test
More informationTEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC)
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 1650 Polyvinyl Chloride (PVC) This product also is labeled under the following Series/Model names: 1555,
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey TYPE: Bi-fold Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More informationTEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina
TEST REPORT Report No.: G4210.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.150 thickness 100% IMA smooth/0.118
More informationAAMA/WDMA/CSA 101/I.S.2/A440-08
PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Manufactured under licence by: Report No.: MI WINDOWS AND DOORS 650 W. MARKET STREET GRATZ, PA USA, 17030 AI-03810-V1 Rev.3 (Reissue-56)
More informationTEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey
TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance
More informationConstruction Consulting Laboratory, International
Construction Consulting Laboratory, International Test Report CCLI-14-060 Client MI Windows and Doors, LLC. 1001 West Crosby Road Carrollton, TX 75006 Product Type: Aluminum Fixed Window Series / Model:
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results
More informationTEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio
TEST REPORT Report No.: E9792.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: ExoAir 230, Dymonic 100 SPECIFICATION: ASTM E 331, Standard Test
More informationG R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E9 Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 165 Vinyl TYPE: Double Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)
More informationTEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina
TEST REPORT Report No.: F8969.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight SERIES/MODEL: Dynamic Double Dome Skylight 100% IMA Smooth/50% IMA Prismatic (5'
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC
More informationTEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard
TEST REPORT Report No.: E6827.01-602-47 Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois PRODUCT TYPE: Fixed Curb Mount Skylight SERIES/MODEL: AD Skylight with guard AD Skylight without Guard SPECIFICATION:
More informationASTM E 1886 & 1996-05B DECEUNINCK NORTH AMERICA 142.094 SH 003 Single Hung Window REPORT #CCLI-11-160 August 18, 2011 TABLE OF CONTENTS 1. PROJECT DATA...1 2. SUMMARY...1 3. TEST SPECIMEN...1 4. IMPACT
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 900 Series TYPE: Out-swing Double Terrace Door ATI Data File No. 63136.01 Summary of Test Results Glazing
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.
Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 300ES Curtainwall (8" System) TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal
More informationTEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas
TEST REPORT ASTM E331 Report No.: E2907.01-801-42 Rendered to: IMISON USA Houston, Texas PRODUCT TYPE: Foam and Plaster Wall System SERIES/MODEL: Fibrecote Title Water Penetration Resistance Test Pressure
More informationAAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)
AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal Transmittance (U-Factor) 0.47 Condensation
More informationAAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window
AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing
More informationTEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia
TEST REPORT Report No.: F7657.01-550-44 Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia PRODUCT TYPE: Metal Wall Panel System SERIES/MODEL: Low Profile Accu-Trac System ES with Stiffeners
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of
More informationASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star
ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star TYPE: 3/8 Impact Rated Side Hinged Door ATI Data File No. 74385.01A*
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single
More informationSECTION VINYL (PVC) WINDOWS
SECTION 085313 VINYL (PVC) WINDOWS SERIES 3000/3900 NEW CONSTRUCTION DOUBLE HUNG PART 1 GENERAL 1.01 SECTION INCLUDES A. All windows of the types and sizes called for in this specification shall be furnished
More informationNFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung
NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 4600 Double Hung Baseline Product for Validation Testing Simulated Thermal Transmittance
More informationAwning Windows Tuscany Vinyl Replacement Window
Awning Windows Tuscany Vinyl Replacement Window Full awning Double-top awning Double awning Double-bottom awning FULL DOUBLE BOTTOM/TOP DOUBLE AWNING - Min 1 3 1 4 Max 4 6 3 0 AWNING - Min 3 0 1 6 Max
More informationCasement Windows Montecito New Construction Window
Casement Windows Montecito New Construction Window Full casement Double-bottom casement FULL DOUBLE/SINGLE DOUBLE CASEMENT - Min 1 6 1 0 Max 3 0 5 0 or 2 6 6 0 CASEMENT - Min 3 0 1 6 Max 6 0 5 0 or 5 0
More informationAwning Windows Montecito New Construction Window
Awning Windows Montecito New Construction Window Full awning Double-top awning Double awning Double-bottom awning FULL DOUBLE BOTTOM/TOP DOUBLE AWNING - Min 1 3 1 4 Max 4 6 3 0 AWNING - Min 3 0 1 6 Max
More informationTEST REPORT. Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series. TYPE: Aluminum Level Guardrail System
TEST REPORT Rendered to: KEYLINK FENCING & RAILING, INC. For: PRODUCT: Lancaster Series TYPE: Aluminum Level Guardrail System Report No: Report Date: 07/05/13 130 Derry Court York, PA 17406-8405 phone:
More informationIntertek NAFS-11 Testing
www.thedsgroup.com Tomorrow s Innovative Solutions for Today s Doors & Windows The DS Group Of Companies: Draftseal, Kristrack, Eclipse Architectural & DSD Hardware Intertek NAFS-11 Testing Intertek has
More informationTEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia
TEST REPORT Report No.: H3615.01-550-44 Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with
More information7520 Casement Windows
Full casement Single casement Double-bottom casement Double casement FULL DOUBLE CASEMENT - Min 1 9 1 6 Max 3 0 5 0 or 2 6 6 0 CASEMENT W/ PICTURE - Min 4 6 1 6 Max 12 0 6 0 with 30 vent set - Minimum
More informationAAMAIWDMAlCSA S.2/ A "NAFS - North American Fenestration Standard/Specification for Windows, Doors and Skylights."
n Corporate Offices I Laboratories Buffalo Road Business Center 460 Buffalo Rd. Rochester, NY 14611 Phone: (5&5) 328 7668 Fax: (585) 328 7777 AAMAIWDMAlCSA 10111.S.2/ A440-08 "NAFS - North American Fenestration
More informationCasement Windows Tuscany Vinyl Replacement Window
Casement Windows Tuscany Vinyl Replacement Window Full casement Double-bottom casement FULL SINGLE DOUBLE CASEMENT - Min 1 6 1 0 Max 3 0 5 0 or 2 6 6 0 CASEMENT - Min 3 0 1 6 Max 6 0 5 0 or 5 0 6 0 CASEMENT
More informationSECTION SERIES 200 DOUBLE-HUNG VINYL WINDOWS
SERIES 200 DOUBLE-HUNG VINYL WINDOWS PART 1 GENERAL 1.1 SECTION INCLUDES A. Replacement Windows. 1. Double hung windows 1.2 RELATED SECTIONS A. Section 05450: Cold Formed Metal Framing. B. Section 06100:
More informationTEST REPORT. Rendered to: COLLINS LIMITED, LLC. For:
TEST REPORT Rendered to: COLLINS LIMITED, LLC For: 48 in Rook Post Mount and Structural Post Assembly Report No: Report Date: 03/11/10 130 Derry Court York, PA 17406-8405 phone: 717-764-7700 fax: 717-764-4129
More informationCR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT
CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION
More informationHeavy Commercial / Architectural Projected Windows Series L900T AW150
Heavy Commercial / Architectural Projected Windows Series L900T AW150 Section 08520...Aluminum Windows PART 1: WORK INCLUDED GUIDE SPECIFICATION A. The conditions of the contract and applicable sections
More information