TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan

Size: px
Start display at page:

Download "TEST REPORT. Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan"

Transcription

1 Architectural Testing TEST REPORT Report No.: A Rendered to: TUBELITE, INC. Walker, Michigan PRODUCT TYPE: Aluminum Side Hinge Door SERIES/MODEL: Thermal=Block Summary of Results Title Test Specimen #1 Test Specimen #2 Design Pressure ±2400 Pa (±50.13 psf) N/A Air Infiltration 1.1 L/s/m 2 (0.21 cfm/ft 2 ) 0.4 L/s/m 2 (0.07 cfm/ft 2 ) Water Penetration Resistance Test Pressure 000 Pa (00.00 psf) (LW) 220 Pa (4.59 psf) Uniform Load Structural Test Pressure ±3600 Pa (±75.19 psf) N/A Reference must be made to Report No. A , dated 04/28/11 for complete test specimen description and detailed test results.

2 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 1 of Report Issued To: Tubelite, Inc Walker Ridge Drive NW Suite G Walker, Michigan Test Laboratory: Architectural Testing, Inc. 130 Derry Court York, Pennsylvania Project Summary: 3.1 Product Type: Aluminum Side Hinge Door 3.2 Series/Model: Thermal=Block 3.3 Compliance Statement: Results obtained are tested values and were secured by using the designated test method(s). Test specimen description and results are reported herein. 3.4 Test Date: 02/22/ /23/ Test Location: Architectural Testing, Inc. test facility in York, Pennsylvania. 3.6 Test Sample Source: The test specimens were provided by the client. Representative samples of the test specimen(s) will be retained by Architectural Testing for a minimum of four years from the test completion date. 3.7 Drawing Reference: The test specimen drawings have been reviewed by Architectural Testing and are representative of the test specimen(s) reported herein. Test specimen construction was verified by Architectural Testing per the drawings located in Appendix B. Any deviations are documented herein or on the drawings. 3.8 List of Official Observers: Name Company Tram Trinh Steven Bucher Michael D. Stremmel, P.E. Scott Gill Tubelite, Inc. United Plate Glass Architectural Testing, Inc. Architectural Testing, Inc.

3 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 2 of Test Method(s): ASTM E , Test Method for Determining Rate of Airflow Through Exterior Windows, Curtain Walls and Doors Under Specified Pressure Differences Across the Specimen. ASTM E , Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. ASTM E , Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference. ASTM E , Test Method for Water Penetration of Exterior Windows, Curtain Walls and Doors by Cyclic Static Air Pressure Difference. ASTM E , Standard Test Method to Determine the Operating and Breakaway Forces of Sliding Windows and Doors. ANSI BHMA A156.2, American National Standard for Bored and Preassembled Locks and Latches. 5.0 Test Specimen Description: 5.1 Product Sizes: Test Specimen #1: Overall Area: Width Height 2.3 m² (24.3 ft 2 ) millimeters inches millimeters inches Overall size / /4 Panel size /4 Test Specimen #2: Overall Area: Width Height 2.3 m² (24.3 ft 2 ) millimeters inches millimeters inches Overall size / /4 Panel size /4

4 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 3 of Test Specimen Description: (Continued) 5.2 Frame Construction: The following descriptions apply to all specimens. Frame Member Material Description Head Aluminum Thermal improved, dual strutted extruded aluminum. The head utilized a snap on extruded aluminum door stop. Sill Aluminum Thermal improved, poured and debridged extruded aluminum. Thermal improved, dual strutted extruded aluminum. The jambs utilized a snap on extruded Jambs Aluminum aluminum door stop. The hinge jamb utilized a hinge mounting plate, secured to the jamb six #12 x 1/2" long screws. Head/jamb corners Threshold/jamb corners Joinery Type Square cut and butted Square cut and butted Detail Sealed with silicone and secured with three #10 x 1" long screws. Sealed with silicone and secured with an aluminum clip. The clip was secured to the jamb with two #12 x 1/2" long screws and secured to the threshold with one #12 x 1/2" long screw.

5 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 4 of Test Specimen Description: (Continued) 5.3 Leaf Construction: Leaf Member Material Description Leaf stiles Aluminum Thermal improved, dual strutted extruded aluminum. Leaf rails Aluminum Thermal improved, dual strutted extruded aluminum. The top and bottom rails utilized a full length snap on vinyl cap. The bottom rail utilized a metal sweep on the interior face, secured to the bottom rail with four #6 x 1/2" long screws spaced 10" on center. All corners Joinery Type Square cut and butted Detail Corners were secured using an aluminum clip that was snapped into the glazing grooves of each stile end with a 3/8" diameter threaded rod running through each clip along the full length of the top and bottom rails with a metal clip and hex nut at each end inside the stile hollow. 5.4 Weatherstripping: Test Specimen #1: Description Quantity Location 0.270" backed by 0.300" high polypile with fin 1 Row Head and jambs Custom shaped Kerf mounted vinyl flap seal 1 Row Interior of the bottom rail Test Specimen #2: Description Quantity Location 0.270" backed by 0.300" high vinyl hollow bulb seal 1 Row Head and jambs Custom shaped Kerf mounted vinyl flap seal 1 Row Interior of the bottom rail

6 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 5 of Test Specimen Description: (Continued) 5.5 Glazing: Glass Type 1" IG Spacer Type Aluminum box Interior Lite 1/4" thick tempered Exterior Lite 1/4" thick tempered Glazing Method The glass was channel glazed at each jamb with interior and exterior glazing gaskets. The glass was secured at the top and bottom with snap in interior and exterior glazing beads with vinyl wedge gaskets against the glass. Daylight Opening Location Quantity Glass Bite millimeters inches Leaf x /4 x 67 1/2" 5.6 Drainage: A sloped threshold was utilized. 5.7 Hardware: Description Quantity Location Lock with handle 1 Lock stile, 40" from the sill Continuous (piano) hinge 1 Hinge stile 5.8 Reinforcement: No reinforcement was utilized. 6.0 Installation: The specimen was installed into a Spruce Pine Fir wood buck. The rough opening allowed for a 1/16" shim space. The exterior perimeter of the window was sealed with sealant. Location Anchor Description Anchor Location Jambs 4" long extruded aluminum clip, snap fit into the jambs and secured to the wood buck with one 12" from each end #12 x 3 1/4" long flat head screw. Sill #12 x 3 1/4"long flat head screw 3" from each end and midspan

7 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 6 of Test Results: The temperature during testing was 22 C (71 F). The results are tabulated as follows: Test Specimen #1: Title of Test Results Allowed Note Operating Force, per ASTM E 2068 Air Leakage, per ASTM E 283 at 75 Pa (1.6 psf) Force to latch: 36 N (8.0 lbf) N/A 1.1 L/s/m 2 (0.21 cfm/ft 2 ) N/A Water Penetration, per ASTM E 331 at 000 Pa (00.00 psf) (limited water) Pass No leakage 1 Uniform Load Deflection, per ASTM E 330 taken at bottom rail Pa ( psf) 1440 Pa ( psf) Uniform Load Structural, per ASTM E 330 taken at bottom rail Pa ( psf) 2160 Pa ( psf) Uniform Load Deflection, per ASTM E 330 taken at bottom rail Pa ( psf) 2400 Pa ( psf) Uniform Load Structural, per ASTM E 330 taken at bottom rail Pa ( psf) 3600 Pa ( psf) 0.3 mm (0.01") 0.3 mm (0.01") N/A 2, 3 <0.3 mm (<0.01") <0.3 mm (<0.01") N/A 2, mm (0.03") 0.8 mm (0.03") N/A 2, 3 <0.3 mm (<0.01") <0.3 mm (<0.01") N/A 2, 3

8 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 7 of Test Results: (Continued) Test Specimen #2: Title of Test Results Allowed Note Air Leakage, per ASTM E 283 at 75 Pa (1.6 psf) 0.4 L/s/m 2 (0.07 cfm/ft 2 ) N/A Water Penetration, per ASTM E 547 and ASTM E 331 at 220 Pa (4.59 psf) Pass No leakage 1 General Note: All testing was performed in accordance with the referenced standard(s). Note 1: Without insect screen. Note 2: Loads were held for 10 seconds. Note 3: Tape and film were used to seal against air leakage during structural testing. In our opinion, the tape and film did not influence the results of the test.

9 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Page 8 of 8 The service life of this report will expire on the stated Test Record Retention End Date, at which time such materials as drawings, data sheets, samples of test specimens, copies of this report, and any other pertinent project documentation, shall be discarded without notice. If test specimen contains glazing, no conclusions of any kind regarding the adequacy or inadequacy of the glass in any glazed test specimen(s) can be made. This report does not constitute certification of this product nor an opinion or endorsement by this laboratory. It is the exclusive property of the client so named herein and relates only to the specimen(s) tested. This report may not be reproduced, except in full, without the written approval of Architectural Testing, Inc. For ARCHITECTURAL TESTING, Inc. Scott Gill Senior Technician Michael D. Stremmel, P.E. Senior Project Engineer SG:dem Attachments (pages): This report is complete only when all attachments listed are included. Appendix A: Photograph (1) Appendix B: Drawings (11) This report produced from controlled document template ATI 00479, issued 03/01/11.

10 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Appendix A Photograph Photo No. 1 View of Tested Door

11 Test Report No.: A Report Date: 04/28/11 Test Record Retention End Date: 02/23/15 Appendix B Drawings

12

13

14

15

16

17

18

19

20

21

22

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania

TEST REPORT. Report No.: B Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania Architectural Testing TEST REPORT Report No.: B2133.01-109-47 Rendered to: MI WINDOWS AND DOORS, INC. Gratz, Pennsylvania PRODUCT TYPE: PVC Single Hung Window (Fin) SERIES/MODEL: 3540 SPECIFICATION: AAMA/WDMA/CSA

More information

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina

TEST REPORT. Report No.: A Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina Architectural Testing TEST REPORT Report No.: A6303.08-250-44 Rendered to: DEALERS SUPPLY AND LUMBER CO., LLC Greenville, South Carolina PRODUCT TYPE: Double Hung Window SERIES/MODEL: VictorBilt Palmetto

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7795.01 109 44 Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT

More information

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.04-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum Outswing Casement Window SERIES / MODEL: W250C Test Summary

More information

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G6910.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure ±2640

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO)

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: ALUMIL US. SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: ALUMIL US SERIES/MODEL: M300 Falcon PRODUCT TYPE: Aluminum Horizontal Sliding Window (XO) Title Summary of Results Primary Product Designator HS-C30

More information

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina

PERFORMANCE TEST REPORT. Report No.: H Rendered to: VELUX America LLC Greenwood, South Carolina PERFORMANCE TEST REPORT Report No.: H0140.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Curb Mounted Skylight SERIES/MODEL: Specials Dome Skylight 0.118 Thickness PC

More information

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: C.R. LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G8680.01-303-47 Rendered to: C.R. LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Double Side Hinged Door - Outswing SERIES/MODEL: 925 Title Summary of Results Design Pressure

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5467.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window

TEST REPORT. Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California. SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window TEST REPORT Report No.: D8932.01-301-44 Rendered to: ALL WEATHER ARCHITECTURAL ALUMINUM Vacaville, California SERIES/MODEL: 6000 PRODUCT TYPE: Aluminum Awning Window SPECIFICATION: AAMA/WDMA/CSA 101/I.S.2/A440-08,

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5562.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5468.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (OXXO) SERIES/MODEL: 8920 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania

TEST REPORT. Report No.: F Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania TEST REPORT Report No.: F7299.01-109-47 Rendered to: MI WINDOWS AND DOORS, LLC Gratz, Pennsylvania PRODUCT TYPE: Polyvinyl Chloride (PVC) Picture Window SERIES/MODEL: HM155 SPECIFICATION(S): AAMA/WDMA/CSA

More information

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11

TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 TEST REPORT AAMA/WDMA/CSA 101/I.S.2/A440-11 REPORT NO.: 1391.02-106-11 RENDERED TO: PRODUCT TYPE: GAMCO CORPORATION Flushing, New York Aluminum fixed window SERIES / MODEL: W250C Test Summary of Results

More information

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly

PERFORMANCE TEST REPORT. Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly PERFORMANCE TEST REPORT Rendered to: TREMCO INC. SERIES/MODEL: Proglaze ETA - System 3 PRODUCT TYPE: Pre-Engineered Air Barrier Transition Assembly Title Summary of Results Air Infiltration

More information

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio

TEST REPORT. Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio TEST REPORT Report No.: E6273.02-501-47 Rendered to: EARTHWISE GROUP, LLC Liberty Township, Ohio PRODUCT TYPE: PVC Single Hung Window SERIES/MODEL: 143.095 Single Hung SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California

TEST REPORT. Report No.: G Rendered to: CR LAURENCE CO., INC. Vernon, California TEST REPORT Report No.: G9949.01-303-47 Rendered to: CR LAURENCE CO., INC. Vernon, California PRODUCT TYPE: Fixed Lite Storefront System SERIES/MODEL: IT451 Title Summary of Results Design Pressure ±1440

More information

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California

TEST REPORT. Report No.: E Rendered to: INTERNATIONAL WINDOW Fullerton, California TEST REPORT Report No.: E5564.01-301-44 Rendered to: INTERNATIONAL WINDOW Fullerton, California PRODUCT TYPE: Sliding Glass Door (XXO) SERIES/MODEL: 8880 SPECIFICATION(S): AAMA/WDMA/CSA 101/I.S.2/A440-11,

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors / Round Top Single PRODUCT TYPE: In-swing Round Top Single Door RH-4 Title Uniform Load Deflection Test

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Pa ge: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-115.0 Issue Date: Revision Date:

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7921.02 501 44 Rendered to: MGM WINDOW COMPANY Hendersonville, Tennessee PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: 4650DH

More information

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania

AAMA 506 TEST REPORT. Report No.: G Rendered to: VEKA INC. Fombell, Pennsylvania AAMA 506 TEST REPORT Report No.: G0434.01-501-44 Rendered to: VEKA INC. Fombell, Pennsylvania PRODUCT TYPE: PVC Double Hung Window SERIES/MODEL: DH57WW/AL-Insert Test Date(s): 06/28/16 Test Record Retention

More information

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY

PERFORMANCE TEST REPORT. Rendered to: GLASSCRAFT DOOR COMPANY PERFORMANCE TEST REPORT Rendered to: GLASSCRAFT DOOR COMPANY SERIES/MODEL: Buffalo Forge Steel Doors/Round Top Double PRODUCT TYPE: In-swing Round Top Double Door LH-4-5/8 Title Uniform Load Deflection

More information

INTERNATIONAL WINDOW TEST REPORT

INTERNATIONAL WINDOW TEST REPORT INTERNATIONAL WINDOW TEST REPORT SCOPE OF WORK AAMA/WDMA/CSA 101/I.S.2/A440-08 AND -11 TESTING ON 7223 O/X AWNING WINDOW REPORT NUMBER H5789.01-301-44 R1 TEST DATE(S) 09/13/17-09/18/17 ISSUE DATE REVISION

More information

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS:

TEST REPORT. ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio. Rendered to: PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: Architectural Testing TEST REPORT Report No.: D7201.01-901-44 Rendered to: ASSOCIATED MATERIALS, INCORPORATED Cuyahoga Falls, Ohio PRODUCT TYPE: Fixed Window SERIES/MODEL: A780 SPECIFICATIONS: AAMA/WDMA/CSA

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-109.0 Issue Date: Revision Date:

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-105.0 Issue Date: Revision Date:

More information

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310

Architectural Testing TEST REPORT. Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington. PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 Architectural Testing TEST REPORT Report No.: E2257.01-901-44 Rendered to: COEUR D'ALENE WINDOW Spokane Valley, Washington PRODUCT TYPE: PVC Fixed Window SERIES/MODEL: 3310 SPECIFICATIONS: AAMA/WDMA/CSA

More information

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC

ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT. Rendered to: BEKAERT SPECIALTY FILMS, LLC ASTM E 1886 / ASTM E 1996 AND ASTM E 283, ASTM E 330, ASTM E 331 TEST REPORT Rendered to: BEKAERT SPECIALTY FILMS, LLC SERIES/MODEL: Solar Gard Armorcoat 8-mil Film PRODUCT TYPE: Fixed Window with Applied

More information

Structural Performance Certification Authorization Report

Structural Performance Certification Authorization Report Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-113.0 Issue Date: Revision Date:

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A2653.02 401 44 Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama PRODUCT TYPE: Curtain Wall SERIES/MODEL: PW257 Captured

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE B PRODUCT TYPE: Venting Curb Mounted Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America Inc. SERIES/MODEL: VCM/VCE 4646 2004B PRODUCT TYPE: Venting Curb Mounted Skylight Report No: Test Date: 01/06/10 Report Date: 03/15/10 Expiration

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Report No.: B Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama Architectural Testing MIAMI-DADE COUNTY PERFORMANCE TEST REPORT This report contains in its entirety: Cover Page: 1 page Report Body: 10 pages Sketches: 2 pages Photographs: 4 pages Drawings: 7 pages Report

More information

Dennis Fassnacht Jr :59:35-04'00'

Dennis Fassnacht Jr :59:35-04'00' Document Title: Doc No: FRM B1-02 Rev No: Page: Of: 7 1 1 Required By: PRO B1-03 Structural Performance Certification Authorization Report CAR & Product ID Number: 757-103.0 Issue Date: Revision Date:

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC.

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: BUILDERS ACCESSORIES, INC. AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: BUILDERS ACCESSORIES, INC. SERIES/MODEL: 6490 PRODUCT TYPE: Polyvinyl Chloride (PVC) Casement Window Title Summary of Results Primary Product Designator

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A AAMA TEST REPORT SUMMARY AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 AAMA 910-93 TEST REPORT SUMMARY Rendered to: GIESSE NORTH AMERICA 2014 Holston Industrial Drive Blountville, TN 37617 PRODUCT TYPE: XO Sliding

More information

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC.

ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT. Rendered to: MASTER WINDOW SYSTEMS, INC. ANSI/AAMA/NWWDA 101/I.S.2-97 TEST REPORT Rendered to: MASTER WINDOW SYSTEMS, INC. SERIES/MODEL: Master 1000 Sliding Window PRODUCT: PVC Horizontal Sliding Window Summary of Results Title Test Specimen

More information

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to:

AAMA/WDMA/CSA 101/I.S.2/A AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT SUMMARY. Rendered to: AAMA/WDMA/CSA 101/I.S.2/A440-08 AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT SUMMARY Rendered to: AluminTechno LLC. 12 Selitskog Street, Room 211 FEZ Minsk, Minsk District, Minsk Region 220075 Republic

More information

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc.

Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT. Report Number: C Rendered to: Tubelite Inc. Architectural Testing ASTM E283, ASTM E330, ASTM E331 TEST REPORT Report Number: C0271.01-450-44 Rendered to: Tubelite Inc. Walker, Michigan MODEL DESIGNATION: 400 Series Curtainwall with 4 Sided SSG PRODUCT

More information

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey

TEST REPORT. Report No.: F Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey TEST REPORT Report No.: F399.01-109-44 Rendered to: FAIRFIELD METAL, LLC Fairfield, New Jersey PRODUCT TYPE: ACP Panel System (Dry Seal) SERIES/MODEL: Dry Econect-RS Title Design Pressure Air Infiltration

More information

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results

TEST REPORT. Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas. Cycles 2,000,000. Summary of Results Architectural Testing TEST REPORT Report No.: C0231.01-201-44 Rendered to: UNIVERSAL PULTRUSIONS, LLC Marshall, Arkansas PRODUCT TYPE: Side-Hinged Door SERIES/MODEL: 3070 Fiberglass Door SPECIFICATION:

More information

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS

AAMA/WDMA/CSA 101/I.S.2/A TEST REPORT. Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS AAMA/WDMA/CSA 101/I.S.2/A440-05 TEST REPORT Rendered to: WASHOE EQUIPMENT, INC. DBA SUNOPTICS PRISMATIC SKYLIGHTS SERIES/MODEL: 800MD Signature PRODUCT TYPE: Fixed Plastic Glazed Skylight Title Summary

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: SERIES/MODEL: FS S PRODUCT TYPE: Fixed Deck Mounted Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FS S06 2004 PRODUCT TYPE: Fixed Deck Mounted Skylight Report No: 96238.02-109-44 Test Date: 01/06/10 Report Date: 01/09/18

More information

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: G Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: G4210.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight with Curb SERIES/MODEL: Specials Dome Skylight 0.150 thickness 100% IMA smooth/0.118

More information

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio TEST REPORT Report No.: E9891.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: Vulkem 116 Illmod 600 Acrytec Panel SPECIFICATION: ASTM E 330, Standard

More information

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana

TEST REPORT. Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana Architectural Testing TEST REPORT Report No.: D0162.01-201-44 Rendered to: TFC A DIVISION OF CENTURION INDUSTRIES, INC. Garrett, Indiana PRODUCT TYPE: Pressure Equalized Rainscreen SERIES/MODEL: 4 mm Composite

More information

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series

TEST REPORT. Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California. PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Architectural Testing TEST REPORT Report No.: D5082.01-301-32 Rendered to: ALL WEATHER INSULATED PANELS Vacaville, California PRODUCT TYPE: Wall Panels SERIES/MODEL: DM45 Series Title Summary of Results

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX America LLC. SERIES/MODEL: FCM B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX America LLC SERIES/MODEL: FCM 4646 0004B PRODUCT TYPE: Fixed Glass Glazed Curb Mount Skylight Report No: 90752.03-109-44 Test Date: 07/27/09 Report Date:

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: FLEETWOOD WINDOWS & DOORS. SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: FLEETWOOD WINDOWS & DOORS SERIES/MODEL: Norwood 3070HI OOX PRODUCT TYPE: Sliding Glass Door This report contains in its entirety: Cover Page: 1 page

More information

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina

TEST REPORT. Report No.: F Rendered to: VELUX America LLC Greenwood, South Carolina TEST REPORT Report No.: F8969.01-109-44 Rendered to: VELUX America LLC Greenwood, South Carolina PRODUCT TYPE: Skylight SERIES/MODEL: Dynamic Double Dome Skylight 100% IMA Smooth/50% IMA Prismatic (5'

More information

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Report No.: B Rendered to: TREMCO, INCORPORATED Beachwood, Ohio Architectural Testing TEST REPORT Report No.: B2739.02-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Air Barrier System SERIES/MODEL: ExoAir 230, ProGlaze ETA System 1, Spectrem

More information

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight

OSHA FALL PROTECTION TEST REPORT. Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight OSHA FALL PROTECTION TEST REPORT Rendered to: VELUX AMERICA INC. SERIES/MODEL: CAP-1 PRODUCT TYPE: Fixed Acrylic Glazed Skylight Report No: Test Date: 04/01/09 Report Date: 10/20/09 Record Retention Date:

More information

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series

TEST REPORT. Rendered to: All Weather Insulated Panels Vacaville, California. PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Architectural Testing TEST REPORT Report No.: C6304.01-301-44 Rendered to: All Weather Insulated Panels Vacaville, California PRODUCT TYPE: Roofing Panels SERIES/MODEL: SR Series Title Summary of Results

More information

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio

TEST REPORT. Rendered to: TREMCO, INCORPORATED Beachwood, Ohio TEST REPORT Report No.: E9792.01-501-47 Rendered to: TREMCO, INCORPORATED Beachwood, Ohio PRODUCT TYPE: Wall Panel System SERIES/MODEL: ExoAir 230, Dymonic 100 SPECIFICATION: ASTM E 331, Standard Test

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC.

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: TUBELITE, INC. Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 300ES Curtainwall (8" System) TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal

More information

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall

MOCK-UP TEST REPORT. Rendered to: TUBELITE INC. PROJECT: 300 ES Interior Glazed Curtain Wall Architectural Testing MOCK-UP TEST REPORT Rendered to: TUBELITE INC PROJECT: 300 ES Interior Glazed Curtain Wall Report No: 94346.01-602-32 Test Completion Date: 09/10/09 Report Date: 09/14/09 Record Retention

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey. TYPE: Bi-fold Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: C.R. LAURENCE CO., INC. SERIES/MODEL: S80 Monterey TYPE: Bi-fold Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems

MIAMI-DADE COUNTY PERFORMANCE TEST REPORT. Rendered to: BRICK-IT. SERIES/MODEL: Brick Veneer Panel Systems PRODUCT TYPE: Wall Panel Systems This report contains in its entirety: Cover Page: 1 page Report Body: 15 pages Sketches: 7 pages Drawing: 1 page MIAMI-DADE COUNTY PERFORMANCE TEST REPORT Rendered to: BRICK-IT SERIES/MODEL: Brick Veneer

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite 1" IG Impact Glass with BTS Lite Frame Type: Side-Hinged Single

More information

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas

TEST REPORT ASTM E331. Report No.: E Rendered to: IMISON USA Houston, Texas TEST REPORT ASTM E331 Report No.: E2907.01-801-42 Rendered to: IMISON USA Houston, Texas PRODUCT TYPE: Foam and Plaster Wall System SERIES/MODEL: Fibrecote Title Water Penetration Resistance Test Pressure

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: THERMA-TRU CORPORATION ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: THERMA-TRU CORPORATION Series/Model: 3/0 x 6/8 Fiber-Classic/Smooth-Star, Full Lite Flush Glazed Type: Side-Hinged Single Door System Summary of

More information

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard

TEST REPORT. Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois. AD Skylight without Guard TEST REPORT Report No.: E6827.01-602-47 Rendered to: AD SKYLIGHTS, INC. Algonquin, Illinois PRODUCT TYPE: Fixed Curb Mount Skylight SERIES/MODEL: AD Skylight with guard AD Skylight without Guard SPECIFICATION:

More information

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel

PERFORMANCE TEST REPORT. Rendered to: ALL-WEATHER INSULATED PANELS. SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel PERFORMANCE TEST REPORT Rendered to: ALL-WEATHER INSULATED PANELS SERIES/MODEL: SM40 PRODUCT TYPE: Insulated Sandwich Wall Panel Title Summary of Results Air Infiltration

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: COASTAL INNOVATIVE PRODUCTS Architectural Testing AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: COASTAL INNOVATIVE PRODUCTS SERIES/MODEL: Outswing Aluminum Bi-Folding System TYPE: Swinging Door with Frame Summary of Results

More information

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia

TEST REPORT. Report No.: F Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia TEST REPORT Report No.: F7657.01-550-44 Rendered to: ALTECH PANEL SYSTEMS, LLC Cartersville, Georgia PRODUCT TYPE: Metal Wall Panel System SERIES/MODEL: Low Profile Accu-Trac System ES with Stiffeners

More information

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl

G R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Vinyl ACOUSTICAL PERFORMANCE TEST REPORT ASTM E9 Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 165 Vinyl TYPE: Double Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390. TYPE: Sliding Glass Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 390 TYPE: Sliding Glass Door Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 6/8 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 6/8 Sliding Patio Door ATI Data File No. 74387.01 74387.01A* Summary of Test Results Glazing (Nominal

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440. TYPE: Sliding Glass Door Architectural Testing AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 420/430/440 TYPE: Sliding Glass Door ATI Data File No. 71967.01 Summary of Test

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: UNITED STATES ALUMINUM. SERIES/MODEL: 900 Series. TYPE: Out-swing Double Terrace Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: UNITED STATES ALUMINUM SERIES/MODEL: 900 Series TYPE: Out-swing Double Terrace Door ATI Data File No. 63136.01 Summary of Test Results Glazing

More information

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window

H R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4. TYPE: Single Hung Window ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: SHA4 TYPE: Single Hung Window Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC OITC

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500. TYPE: Double Hung Window ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: ALL SEASONS DOOR & WINDOW, MFG SERIES/MODEL: A500 TYPE: Double Hung Window Data File No. 97455.01 Summary of Test Results Glazing (Nominal Dimensions)

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built)

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: Curtain Wall TYPE: Glazed Wall Systems (Site-built) Summary of Results Thermal Transmittance (U-Factor) 0.47 Condensation

More information

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning)

AAMA THERMAL PERFORMANCE TEST REPORT. Rendered to: GAMCO CORPORATION. SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) AAMA 1503-09 THERMAL PERFORMANCE TEST REPORT Rendered to: GAMCO CORPORATION SERIES/MODEL: W250C Awning TYPE: Projecting (Awning) Summary of Results Thermal Transmittance (U-Factor) 0.48 Condensation Resistance

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door with Impact Glass ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door with Impact Glass ATI Data File No. 74391.01 74391.01A* Summary of Test Results

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Classic-Craft, Fiber Classic, and Smooth Star TYPE: 3/8 Impact Rated Side Hinged Door ATI Data File No. 74385.01A*

More information

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250

E R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90. Rendered to: GAMCO CORPORATION. Series/Model: CW250 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E90 Rendered to: GAMCO CORPORATION Series/Model: CW250 Type: Two-Lite Curtain Wall System Summary of Test Results Data File No. Glazing (Nominal Dimensions) STC

More information

AAMA/WDMA/CSA 101/I.S.2/A440-08

AAMA/WDMA/CSA 101/I.S.2/A440-08 PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Manufactured under licence by: Report No.: AI-03820-C2 (Reissue-10) DOMINION DOORS AND WINDOWS LTD. 130 PENNSYLVANIA AVE. UNIT 8 CONCORD,

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC)

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, LLC. SERIES/MODEL: 1650 Polyvinyl Chloride (PVC) ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, LLC SERIES/MODEL: 1650 Polyvinyl Chloride (PVC) This product also is labeled under the following Series/Model names: 1555,

More information

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window

AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP. TYPE: Picture Window AAMA 1801 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: MI WINDOWS AND DOORS, INC. SERIES/MODEL: 185/3185 SP TYPE: Picture Window ATI Data File No. 71965.01A 71965.01B Summary of Test Results Glazing

More information

ETC Laboratories Measuring Up To Your Standards And More

ETC Laboratories Measuring Up To Your Standards And More ETC Laboratories Measuring Up To Your Standards And More Corporate Offices / Laboratories 460 Buffalo Rd. Rochester, NY 14611 (585) 328-7668 Fax: (585) 328-7777 Report Number: ETC-09-329-22959.2 Test Start

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: MGM INDUSTRIES. SERIES/MODEL: 4600 Double Hung NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: MGM INDUSTRIES SERIES/MODEL: 4600 Double Hung Baseline Product for Validation Testing Simulated Thermal Transmittance

More information

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 )

STRUCTURAL PERFORMANCE TEST REPORT. Series Casement (Rep/Impact/AAMA) C-C70 940mm x 1930mm (37 x 76 ) Element Materials Technology 115 South 84th Ave Wausau, WI 54401, USA 407-505-8102 Report No.: ESP101311P-6_012404P-6 Report Date: July 18, 2012 STRUCTURAL PERFORMANCE TEST REPORT Test Requested By: Earthwise

More information

AAMA/WDMA/CSA 101/I.S.2/A440-08

AAMA/WDMA/CSA 101/I.S.2/A440-08 PERFORMANCE TESTS IN ACCORDANCE WITH AAMA/WDMA/CSA 101/I.S.2/A440-08 Manufactured under licence by: Report No.: MI WINDOWS AND DOORS 650 W. MARKET STREET GRATZ, PA USA, 17030 AI-03810-V1 Rev.3 (Reissue-56)

More information

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door

ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT. Rendered to: THERMA-TRU DOORS. SERIES/MODEL: Slimline. TYPE: 8/0 Sliding Patio Door ASTM E 90 SOUND TRANSMISSION LOSS TEST REPORT Rendered to: THERMA-TRU DOORS SERIES/MODEL: Slimline TYPE: 8/0 Sliding Patio Door Summary of Test Results ATI Data File No. Glazing (Nominal Dimensions) STC

More information

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT

KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT KNOTWOOD, A DIVISION OF OMNIMAX INTERNATIONAL MIAMI-DADE TEST REPORT SCOPE OF WORK TAS 201, TAS 202, AND TAS 203 TESTING ON KNOTWOOD, ALUMINUM POWDER-COATED CLADDING REPORT NUMBER I6115.01-109-18 TEST

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC.

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. Rendered to: TUBELITE, INC. Architectural Testing NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT Rendered to: TUBELITE, INC. SERIES/MODEL: 400 Series Curtain Wall (6" Standard Tube Backmember) - Fiberglass

More information

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC

NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT. (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC NFRC U-FACTOR, SHGC, VT, & CONDENSATION RESISTANCE COMPUTER SIMULATION REPORT (Revised) Rendered to: CUSTOM VINYL PRODUCTS, LLC SERIES/MODEL: DHA4 Double Hung Report Number: Original Report Date: Revised

More information

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS

SECTION ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS SECTION 08 4113 ALUMINUM-FRAMED ENTRANCES AND STOREFRONTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Aluminum entrance doors and frames. 2. Glass infill panels. 3. Door hardware. B. Related Sections:

More information

Intertek NAFS-11 Testing

Intertek NAFS-11 Testing www.thedsgroup.com Tomorrow s Innovative Solutions for Today s Doors & Windows The DS Group Of Companies: Draftseal, Kristrack, Eclipse Architectural & DSD Hardware Intertek NAFS-11 Testing Intertek has

More information

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip Architectural Testing TEST REPORT Report No.: C2155.02-109-44 Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania PRODUCT TYPE: Drywall Clip Reference must be made to Report No. C2155.02-109-44, dated 04/05/13

More information

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post

TEST REPORT. Rendered to: SENTINEL FENCE AND RAIL. For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post TEST REPORT Rendered to: SENTINEL FENCE AND RAIL For: 120 in by 42 in Fully-Welded Aluminum Guardrail Assembly with Intermediate Support Post Report No: Report Date: 10/23/12 130 Derry Court York, PA 17406-8405

More information

TEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip

TEST REPORT. Report No.: C Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania. PRODUCT TYPE: Drywall Clip Architectural Testing TEST REPORT Report No.: C2155.01-109-44 Rendered to: ROCKSTEADY, LLC Lititz, Pennsylvania PRODUCT TYPE: Drywall Clip Summary of Results Drywall Size 6" Kick-Out 8' x 4' x 1/2" 425

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.03-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades

TEST REPORT. Rendered to: FAIRWAY BUILDING PRODUCTS, LP. For: Solutions Aluminum Guardrail System with Glass Balustrades TEST REPORT Rendered to: FAIRWAY BUILDING PRODUCTS, LP For: Solutions Aluminum Guardrail System with Glass Balustrades Report No: Report Date: 09/15/10 Revision 1: 09/23/10 130 Derry Court York, PA 17406-8405

More information

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT

CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT CR LAURENCE CO, INC. ACOUSTICAL PERFORMANCE TEST REPORT SCOPE OF WORK AAMA 1801 TESTING ON IT451, STOREFRONT WINDOW REPORT NUMBER H7645.02-303-11 R0 TEST DATE 11/03/17 ISSUE DATE 11/17/17 RECORD RETENTION

More information

TEST REPORT AAMA 501.5

TEST REPORT AAMA 501.5 TEST REPORT AAMA 501.5 REPORT NO.: RENDERED TO: PRODUCT TYPE: 1517.02-106-11-R0 DESANA PARTNERS Cranston, Rhode Island Back Drained and Ventilated Wall System SERIES / MODEL: Tru-Brix Rainscreen System

More information

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia

TEST REPORT. Report No.: H Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia TEST REPORT Report No.: H3615.01-550-44 Rendered to: GEORGIA-PACIFIC WOOD PRODUCTS, LLC Atlanta, Georgia PRODUCT TYPE: EIFS Panel Systems SERIES/MODEL: GP ForceField Air & Water Barrier Sheathing with

More information

SECTION ALUMINUM STORM WINDOWS

SECTION ALUMINUM STORM WINDOWS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 08 51 69.11 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Construction Consulting Laboratory, International

Construction Consulting Laboratory, International Construction Consulting Laboratory, International Test Report CCLI-14-060 Client MI Windows and Doors, LLC. 1001 West Crosby Road Carrollton, TX 75006 Product Type: Aluminum Fixed Window Series / Model:

More information