A Comparative Study of DGA and PD Test on Mineral and Biodegradable Based Transformer Insulation Oil
|
|
- Dinah Doyle
- 6 years ago
- Views:
Transcription
1 A Comparative Study of DGA and PD Test on Mineral and Biodegradable Based Transformer Insulation Oil Mohd Fikri Hilmi Mohd Taib, Yanuar Z. Arief, Nor Asiah Muhamad, Zuraimy Adzis Institute of Voltage & Current (IVAT) Fakulty of Electrical Engineering Universiti Teknologi Malaysia (UTM), Johor Bahru, Malaysia Abstract Power transformer is one of the most important equipment in electrical power system due to its cost and failure consequence. Mineral oil has been widely used as dielectric insulating fluid in transformers due to its excellent performance in service. Mineral oil is petroleum-based oil, which means it can potentially be hazardous to the environment as waste. Due to concerns on environmental issues and petroleum resources viability, the alternative insulating oil with biodegradable characteristics has been attracting lots of attention for the past couple of decades. This paper deals with the comparative study of the previous research on dissolved gas analysis (DGA) and partial discharge (PD) investigation done on biodegradable oil as transformer insulating oil. Keywords - Transformer insulation oil, biodegradable oil, mineral oil, dissolved gas analysis, partial discharge I. INTRODUCTION In high voltage power transmission, large amounts of electrical energy are transmitted from generating stations to the consumers [1]. The transformer is one of the most important equipment used in power transmission to step up or step down the voltage [2]. Normally, the petroleum based mineral oil is used in transformer as oil insulation and cooling system [1, 2]. Transformer oil is petroleum-based (mineral oil), widely known and used well in insulating liquid since 1900 s It has low viscosity, good ageing behavior, cheap and readily available [3, 4]. However, this type of oil is non-renewable since it was mined from the inside of the earth. In addition, this mineral oil gives bad impact to the environment and ecosystem due to the difficulty in decomposing it [2, 3, 5]. Due to concerns about being environmentally friendly, cost and its long term working life span, many researches are done in the previous decade to replace the use of petroleum based oil with a new type of insulation oil. The organic based oil (such as vegetable, soya bean, sunflower and etc.) are environmentally friendly, biodegradable, nontoxic and better fire safety features are showing good potentials for this replacement [5-17]. The insulating oil are considered good when it has low kinetic viscosity, high flash point, high breakdown voltage and low partial discharge [3]. The kinetic viscosity needs to be low to ensure rapid circulation inside the transformer [3]. flash point means that the oil will only give enough vapors to produce flammable mixture with air only at high temperatures [3]. Having high breakdown voltage means that the oil are able to withstand high electrical stress before breakdown [3]. Partial discharge (PD) needs to be low to minimise chemical changes and heat generation in oil due to partial discharge activities [3]. The comparative study on dissolved gas analysis (DGA) and partial discharge (PD) investigation of mineral and biodegradablebased oil is described in this work. II. ISSUES, CHALLENGES AND TRENDS A. Issues The usage of biodegradable oil are still limited on medium voltage transformer [5]. Silicone oil are studied in order to replace the mineral oil use due to the potential in being environmentally-friendly and flame retardant insulation [18]. The silicone oil is insulating oil made from silicon, which is the second most common element in the world and is chemically stable. The agricultural ester insulating oil is made from edible seed, widely produced and with high biodegradable [18]. However, it was found that the ester oil have more potential compared to silicon oil in term of charge density and breakdown voltage at high temperature[18]. Besides that, the operation of transformer may rise the insulation oil temperature. It s may reduce the insulation integrity [1, 19]. Due to present of defect and high electric stress, the partial discharge will present in the insulation oil [1, 20, 21]. This condition lead to degrade insulation oil and may lead to failure or breakdown [1]. DOI /IJSSST.a ISSN: x online, print
2 B. Challenges The ester oil are one of the biodegradable oil which is having problem in term of long stability and it has possibility to approach solid form when heated for long time [18]. The transformer oil are the most widely as electrical insulation liquids in the world [22]. It has been used more than 100 years. There have been many research are conduct in order to replace or as substitute oil for the transformer [11]. More consideration made for new insulation oil to maintain less dielectric loss, low values of degradation and high breakdown strength compare to previous oil (mineral oil base) [22]. It is found that silicone oil, ester oil are having some different characteristics from mineral oil, and this new substitution oil cannot directly replace mineral oil in service or repaired units [22]. Biodegradable oil like vegetable oil has high viscosity and low in long-term PD activity, which does not allow it to directly replace the mineral oil unless improvements are made [2]. C. Trends Nowadays, more development are achieved towards the use of artificial network as pattern recognition and decision making method. It is now able to recognize the PD pattern on transformer in order prevent the serious damage using artificial neural network as one method of artificial intelligent (AI) [23]. The artificial intelligent technique are been adopted into the electrical fields in many applications [24-30]. Online test is better compared to offline test for transformers. The acoustic emission are one of the method that can be used to detect the online PD detection compare to using shutdown period of equipment [23]. The pattern recognition of their faulty type can easily be determined by using statistical and neural network [23, 24]. As the PD pattern can be used to diagnosis the insulation condition in high voltage. By analyzing the PD pulse can show the PRPD (phase-resolved partial discharge) pattern and also got the (time vs. Frequency) map [5]. The cause of PD activity due to corona discharge, surface discharge and internal discharge can be found by analyze the PD distribution in time frequency map [5]. This work can be further extended by utilizing the pattern recognition system using this neural network method. The biodegradable oils are able to challenge the existing mineral oil performance using the polymer nano-composite as additive. There are various electrical properties of polymer nano-composites that gained interests among these researchers such as partial discharge (PD) resistance, tracking resistance, dielectric breakdown strength, permittivity, and loss tangent [31]. III. TYPE OF TESTS A. Dissolved Gas Analysis (DGA) During the faults, transformer insulation oil will release hydrocarbon gases that dissolved into the oil. Types and quantities of hydrocarbon gases produced give early indication of inception faults in transformer. Five types of hydrocarbon gases that commonly dissolved in transformer oil are H 2 (hydrogen), CH 4 (methane), C 2 H 6 (Ethane), C 2 H 4 (ethylene) and C 2H 2 (acetylene) [32]. Common faults can be detected using this method are partial discharge, overheating, and arcing or breakdown faults. Overheating fault can be detected by present of hydrogen together with methane, ethane and ethylene. The key gas for this type of fault is ethylene gas [1, [32] DGA is one of method able to determine the type of fault from the gas generated according to IEEE standard C : IEEE Guide for the Interpretation of Gases Generated in Oil-Immersed Transformers. There are common methods to evaluate or analysis the DGA, which is:- 1. Duval Triangle method, 2. Key Gases method, 3. IEC method, 4. Rogers Ratio method, 5. Nomograph method, 6. Doernenburg Ratio method 7. CIGRE Method. For both thermal and electrical faults, coconut oil contained only H 2, CO and CO 2 gases while transformer oil contained additional gases such as CH 4, C 2 H 4 and C 2 H 6. In most cases, gases such as H 2, CO and CO 2 found in coconut oil were in the same level as those in transformer oil. Usually CO and CO2 gases are formed as a result of the ageing of pressboard whereas H 2 is formed by overheating of oil. Therefore, formation of CO and CO 2 gases in both coconut oil and transformer oil was due to the added pressboard. to make the samples wet. When comparing the gas levels at different temperatures, one could expect high gas level for the coconut oil samples aged at 200 C. The results were opposite showing that even at a lower temperature level with higher duration gave high dissolve gas levels [17]. There is some information found:- There are negligible amount of hydrocarbon produce from coconut oil samples during the electrical and thermal faults [17]. The vegetable oil releases large amount of CO and CO 2, but the dielectric strength decreased lower compared to the mineral oil on the real transformer. The degradation of insulation paper can be determined by indicating the CO and CO 2 amount. Then the amount of CO and CO 2 of mineral oil and vegetable oil are differing due to different of kinetic DOI /IJSSST.a ISSN: x online, print
3 viscosity of them. The heat transfer from the insulation paper to the insulation oil are low than mineral oil due to high kinetic viscosity of vegetable oil [16]. The prediction for overheating fault in oil filled transformer using this method will give wrong fault interpretations when using Roger s ratio when applied for transformer using biodegradable oil as insulation compare to mineral oil which due to the methane amount are low compare to the hydrogen [32]. Figure 1. Arcing test without pressboard for normal oils [33]. Interpretation method Duval s Triangle Method Roger s Ratio Method Key Gas Method TABLE 1. DGA FAULT GAS ANALYSIS [33]. Oil Type Mineral Oil Biodegradable Oil Mineral Oil Biodegradable Oil Mineral Oil Biodegradable Oil Point to plane test (Without pressboard) Normal Dried Wet Low Low Low (Sparking) (Sparking) (Sparking) Low (Sparking) - - Low (Sparking) No Prediction - - Low (Sparking) No Prediction - - The prediction using Roger s Ratio Method are unable to detect the arching fault from the DGA data. This due to the smallest amount of methane produce compare to hydrogen from the biodegradable oil. [33] Figure 2. Arcing test without pressboard for dried oils [33]. Figure 3. Arcing test without pressboard for wet oils [33]. Figure 1, 2 and 3 show the amount of hydrocarbon gas produce by the arcing test without the pressboard. The arching (Breakdown voltage) test are done on point to plane followed the ASTM D877. The data from figure 1, 2, and 3 are analysis using Duval s Triangle Method, Roger s Ratio method and Key Gas Method are been shown in Table 1. B. Partial (PD) Partial discharge is the electrical discharge which are not completely bridging the distance between two electrodes under high voltage stress [24]. This PD can be seen as small electrical spark that happen within the electrical insulation of electrical equipment. This PD magnitude are normally small but it have potential to cause the ultimate failure [24, 34, 35]. PD may cause the insulation ageing, destroy the insulation and lead to electrical equipment failure [24]. Luckily, the prevention method can be taken at the early stage of PD presenting. In addition, the PD occurrence in electrical equipment emitted the several signals like electrical signal, chemical reaction and acoustic pulse, i.e. heat, gas, light and sound [24]. The occurrence of PD signal can be detect using electrical, chemical and acoustic detection [24, 36]. The basic partial detection is normally according to the test circuit as shown in Figure 4 below. DOI /IJSSST.a ISSN: x online, print
4 Figure 4. Basic PD detection measurement [24]. Where: U: high voltage supply, Z mi: input impedance of measuring system, CC: connector cable, C a : test object, C k: coupling capacitor, CD: coupling device, MI: measuring instrument, Z f: filter. PD can be classified into 4 types which are internal discharge, surface discharge, corona discharge and discharge in electrical trees [24, 34, 36]. One of the consequences of PDs is chemical change of material. (i.e. oil, solid and gas) [24, 37]. Acoustic detection of PD is based on the detection of the mechanical waves propagated from the discharge site to the surrounding medium. Acoustic detection has been widely used in diagnostics of transformers. The primary advantage of using acoustic detection is position information is readily available from acoustic systems using sensors at multiple locations [24, 38-40]. Electrical PD detection methods are based on the appearance of a PD pulse at the terminals of a test object. Electrical detection includes two methods: Pulse Current Method and Ultra Frequency Method (UHF) [24]. Pulse Current Method: This method gets the apparent charge by detecting the PD current in detecting impedance [24, 36, 41]. Pulse Current Method is easy for quantitative measurement and it has high sensitivity [24]. Ultra Frequency Method (UHF): UHF detection which is based on the detection of electrical resonance at ultrahigh frequencies can be applied to realize not only the phenomena but also the location of a PD source [24, 42-44]. PD detection can be done during off-line and on-line test on transformer. It is possible to determine the PD using Acoustic emission without shutdown the transformer [23]. Figure 5. PD charge trend during one hours of 10kVrms injection voltage[3]. Figure 6. PD charge trend during one hours of 30kVrms injection voltage [3]. Figure 5 and 6 show the PD charge trend of difference biodegradable oil (Soybean (SOY) Oil and Palm Fatty Acid Ester (PFAE) Oil) in 10 kv and 30 kv for during 1 hours injection time using electrode according to IEC It found that biodegradable oil have low PD charge trend compare to mineral oil in low voltage ad high voltage application [3]. IV. FUTURE OF BIODEGRADABLE OIL AS DIELECTRIC INSULATING FLUID IN TRANSFORMERS Many researches have been conducted on insulation oil with many tests including physical test, chemical test and electrical test. Future tests needs to be conducted on oil PD test on transformers online as it is necessary to investigate the PD activities instead just only using laboratory samples [3]. Biodegradable oils such as palm oil and corn oil lacks in viscosity and PD activity properties compared to mineral oil [2]. The improvement on viscosity and long-term PD are required for palm oil and corn-based oil to have potential as electrical insulation applications [2]. DOI /IJSSST.a ISSN: x online, print
5 The vegetable oil is comparable with mineral oil as insulating oil and need to be improved further for future investigation [5]. The electrical performance of real palm-based transformer has been investigated by the authors. The main objective of the research works is to compare the efficiency of the real power distribution of palm-based oil compared with mineral-based oil. Other characteristics such as DGA and polarization and depolarization current of the transformer also been investigated. Figure 7 shows the picture of two type of the power transformer which is observed in the research work. While Figure 8 shows the typical result for heat population of palm-based oil transformer under certain load condition. V. CONCLUSION The comparative study of the pass research on dissolved gas analysis (DGA) and partial discharge (PD) test done on biodegradable oil as transformer insulating oil has been performed in this work. Common faults can be detected using DGA method are partial discharge, overheating, and arcing or breakdown faults. PD detection can be done during off-line and on-line test on transformer. It is possible to determine the PD using acoustic emission without shutdown the transformer. There are needs a future test conduct on oil PD test on real transformers is necessary to investigate the PD activities instead just only using samples which mean it is better to conduct an on-line test beside just only off-line test. The vegetable oil is comparable with mineral oil as insulating oil and need to proceed for future investigation. ACKNOWLEDGMENT Authors gratefully acknowledge the Malaysia Ministry of Education (MOE) and Universiti Teknologi Malaysia (UTM) for the use of facilities and by awarding Research University Grants (RUG) under vote number Q.J H21. Figure 7. Research work on electrical performance of two type distribution power transformers, namely palm-based oil and mineral-based oil. Figure 8. Heat population at palm-based transformer in certain load condition REFERENCES [1] H. Sutikno, "Effects of temperature on the breakdown voltage and partial discharge patterns of biodegradable oil," in Electrical Engineering and Informatics (ICEEI), 2011 International Conference on, 2011, pp [2] S. Chandrasekar and G. C. Montanari, "Analysis of partial discharge characteristics of natural esters as dielectric fluid for electric power apparatus applications," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 21, pp , [3] M. R. Ramli, Y. Z. Arief, S. A. Azli, N. A. Muhamad, K. Lau, M. Farhan, et al., "Partial discharge characteristics of palm fatty acid ester (PFAE) as high voltage insulating material," in Power Engineering and Renewable (ICPERE), 2014 International Conference on, 2014, pp [4] I. Fofana and J. Sabau, "Application of petroleum-based oil in power transformer," Natural gas research progress, p. 23, [5] S. Banumathi, S. Chandrasekar, and G. C. Montanari, "Investigations on PD characteristics of vegetable oils for high voltage applications," in 2013 IEEE 1st International Conference on Condition Assessment Techniques in Electrical Systems (CATCON), [6] K. Kiasatina, M. Kamarol, M. Zulhilmey, and Y. Arief, "Breakdown characteristics of RBDPO and soybean oil mixture for transformer application," in Electrical, Control and Computer Engineering (INECCE), 2011 International Conference on, 2011, pp [7] A. Rajab and S. Aminuddin, "Properties of RBDPO Oleum as a candidate of palm based-transformer insulating liquid," in Electrical Engineering and Informatics, ICEEI'09. International Conference on, 2009, pp [8] A. Suleiman, N. Muhamad, N. Bashir, N. Murad, Y. Arief, and B. Phung, "Effect of moisture on breakdown voltage and structure of palm based insulation oils," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 21, pp , [9] F. S. Suwarno, I. Suhariadi, and L. Imsak, "Study on the characteristics of Palm Oil and its Derivatives as Liquid Insulating Materials," in 7th International Conference on Properties and Application of Dielectric Materials. Nagoya, 2003, pp [10] C. Perrier and A. Beroual, "Experimental investigations on insulating liquids for power transformers: mineral, ester, and DOI /IJSSST.a ISSN: x online, print
6 silicone oils," IEEE Electrical Insulation Magazine, vol. 6, pp. 6-13, [11] T. Oommen, "Vegetable oils for liquid-filled transformers," Electrical Insulation Magazine, IEEE, vol. 18, pp. 6-11, [12] S. Tenbohlen and M. Koch, "Aging performance and moisture solubility of vegetable oils for power transformers," Power Delivery, IEEE Transactions on, vol. 25, pp , [13] L. Yang, R. Liao, S. Caixin, and M. Zhu, "Influence of vegetable oil on the thermal aging of transformer paper and its mechanism," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 18, pp , [14] H. Wilhelm, L. Tulio, R. Jasinski, and G. Almeida, "Aging markers for in-service natural ester-based insulating fluids," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 18, pp , [15] M. A. G. Martins, "Vegetable oils, an alternative to mineral oil for power transformers-experimental study of paper aging in vegetable oil versus mineral oil," IEEE Electrical Insulation Magazine, vol. 6, pp. 7-13, [16] J.-I. Jeong, J.-S. An, and C.-S. Huh, "Accelerated aging effects of mineral and vegetable transformer oils on medium voltage power transformers," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 19, pp , [17] B. Matharage, M. Fernando, E. Tuncer, M. Bandara, and C. Kalpage, "Coconut oil as transformer liquid insulation Ageing and simulated thermal and electrical faults," in Electrical Insulation and Dielectric Phenomena (CEIDP), 2012 Annual Report Conference on, 2012, pp [18] K. Yasuda, S. Arazoe, T. Igarashi, S. Yanabu, G. Ueta, and S. Okabe, "Comparison of the insulation characteristics of environmentally-friendly oils," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 17, pp , [19] M. Pradhan, "Assessment of the status of insulation during thermal stress accelerated experiments on transformer prototypes," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 13, pp , [20] M. Pompili, C. Mazzetti, and R. Bartnikas, "Phase relationship of PD pulses in dielectric liquids under ac conditions," Dielectrics and Electrical Insulation, IEEE Transactions on, vol. 7, pp , [21] D.-w. Park, S.-y. Choi, and G.-s. Kil, "Measurement and Analysis of Acoustic Signal Generated by Partial s in Insulation Oil," in Proc. 7th WSEAS Int. Conf. on Power Systems, 2007, pp [22] R. R. Kanna and M. Ravindran, "Investigating the performance of transformer using insulating fluids," in Circuit, Power and Computing Technologies (ICCPCT), 2014 International Conference on, 2014, pp [23] C.-C. Kuo, "Particle swarm trained neural network for fault diagnosis of transformers by acoustic emission," in Advanced Intelligent Computing Theories and Applications. With Aspects of Artificial Intelligence, ed: Springer, 2007, pp [24] S. Boonpoke and B. Marungsri, "Pattern Recognition of Partial by Using Simplified Fuzzy ARTMAP," methods, vol. 1, p. 14, [25] B. Marungsri, N. Meeboon, and A. Oonsivilai, "Dynamic Model Identification of Induction Motors using Intelligent Search Techniques with taking Core Loss into Account," WSEAS TRANSACTIONS ON POWER SYSTEMS, vol. 1, p. 1438, [26] A. Oonsivilai and B. Marungsri, "Optimal PID tuning for AGC system using adaptive Tabu search," ACE, vol. 1, p. 2, [27] A. Oonsivilai and B. Marungsri, "Stability Enhancement for Multimachine Power System by Optimal PID Tuning of Power System Stabilizer using Particle Swarm Optimization," WSEAS transactions on power systems, vol. 3, pp , [28] A. Oonsivilai and B. Marungsri, "Optimal PID Tuning for Power System Stabilizers Using Adaptive Particle Swarm Optimization Technique," in International Conference on Power Control and Optimization: Innovation in Power Control for Optimal Industry, 2008, pp [29] B. Marungsri, A. Oonstvilai, and N. Mastorakis, "Partial discharges localization in oil insulating transformer using adaptive Tabu search," in WSEAS International Conference. Proceedings. Mathematics and Computers in Science and Engineering, [30] B. Marungsri and A. Oonsivilai, "Fuzzy ARTMAP technique for speech noise reduction," a a, vol. 1, p. 2, [31] W. A. Izzati, M. Shafanizam, Y. Z. Arief, M. Z. H. Makmud, Z. Adzis, and N. A. Muhamad, "Comparative Study on Partial Characteristic in Polymer-Nanocomposite as Electrical Insulating Material," in Applied Mechanics and Materials, 2013, pp [32] N. Muhamad, B. Phung, and T. Blackburn, "Dissolved gas analysis of overheating fault in bio-degradable transformer oil," in Power Engineering Conference, AUPEC'08. Australasian Universities, 2008, pp [33] N. A. Muhamad, B. Phung, and T. Blackburn, "Dissolved gas analysis (DGA) of arcing faults in biodegradable oil insulation systems," in Electrical Insulating Materials, 2008.(ISEIM 2008). International Symposium on, 2008, pp [34] F. Kreuger, "Partial Detection in -Voltage Equipment, 1989," ed: Butterworths, London, UK. Investigator Award, [35] J. Kuffel, E. Kuffel, and W. S. Zaengl, voltage engineering fundamentals: Newnes, [36] E. Gulski, Computer-aided recognition of partial dicharges using statistical tools: TU Delft, Delft University of Technology, [37] N. Muhamad, B. Phung, and T. Blackburn, "Dissolved gas analysis (DGA) of partial discharge fault in bio-degradable transformer insulation oil," in Power Engineering Conference, AUPEC Australasian Universities, 2007, pp [38] X. Wang, B. Li, H. T. Roman, O. L. Russo, K. Chin, and K. R. Farmer, "Acousto-optical PD detection for transformers," Power Delivery, IEEE Transactions on, vol. 21, pp , [39] A. Oonsivilai and B. Marungsri, "Application of artificial intelligent technique for partial discharges localization in oil insulating transformer," WSEAS Transactions on Systems, vol. 7, pp , [40] Y. Lu, X. Tan, and X. Hu, "PD detection and localisation by acoustic measurements in an oil-filled transformer," in Science, Measurement and Technology, IEE Proceedings-, 2000, pp [41] K. Vicetjindavat, "Pattern Recognition of Partial in Voltage Equipment," Master Degree Thesis, Chulalongkorn University, [42] A. Wichmann, P. Grünewald, and J. Weidner, "Early fault detection inelectrical machines by on-line RF monitoring," in Cigré Symp, 1987, pp [43] J. Phillipson, "Experience with RF techniques in the petrochemical industry," in Proc. 4th Int. Conf. Generator and Motor Partial Testing, [44] L. Yang, "Partial discharge monitoring for power transformer using UHF sensors. Part 2: field experience," IEEE Electrical Insulation Magazine, vol. 21, pp. 5-13, DOI /IJSSST.a ISSN: x online, print
Dissolved Gas Analysis of Transformer Oils: Effects of electric arc
Proceedings of the 6th WSEAS International Conference on Power Systems, Lisbon, Portugal, September 22-24, 26 376 Dissolved Gas Analysis of Transformer Oils: Effects of electric arc SUWARNO School of Electrical
More informationCIGRE 16 BRUGGE Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil. The University of New South Wales Australia
CIGRE 16 BRUGGE 2007 Partial Discharge and Dissolved Gas Analysis In bio-degradable transformer oil D. IMAMOVIC *, K.X. LAI, N.A. MUHAMAD, B.T. PHUNG and T.R. BLACKBURN # The University of New South Wales
More informationCondition Assessment of Power Transformer Using Dissolved Gas Analysis
Condition Assessment of Power Transformer Using Dissolved Gas Analysis Jagdeep Singh, Kulraj Kaur, Priyam Kumari, Ankit Kumar Swami School of Electrical and Electronics Engineering, Lovely Professional
More informationDGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing Quality of Power Transformer Insulation Oil
Modern Applied Science; Vol. 10, No. 1; 2016 ISSN 1913-1844 E-ISSN 1913-1852 Published by Canadian Center of Science and Education DGA Method-Based ANFIS Expert System for Diagnosing Faults and Assessing
More informationPower Transformers. Dissolved Gas Analysis Siemens Energy, Inc. All Rights Reserved
Power Transformers Dissolved Gas Analysis 2008 Siemens Energy, Inc. All Rights Reserved Application ü DGA allows to detect the presence and severity of faults: Air leaks Hot metal faults Arcing and partial
More informationEffects of Water Content on Dielectric Properties of Mineral Transformer Oil
Effects of Water Content on Dielectric Properties of Mineral Transformer Oil Suwarno, M. Helmi Prakoso Abstract Mineral oil is commonly used for high voltage transformer insulation. The insulation quality
More informationCondition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis
ISSN 348-7X September 5 Condition Assessment of High Voltage Power Transformer Using Dissolved Gas Analysis Jugasri Joy Sarma M.E. Scholar, EE Department, Assam Engineering College, Guwahati, India Dr.
More informationINTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC
INTELLIGENT DIAGNOSTIC METHOD FOR PREDICTION OF INTERNAL CONDITION OF TRANSFORMER USING FUZZY LOGIC by LAXMANRAO ALUR KARNATAKA POWER CORPORATION LTD.,INDIA alur.laxman@gmail.com 1 INDEX INTRODUCTION DISSOLVED
More informationPrediction of the Characteristics of Transformer Oil under Different Operation Conditions
Prediction of the Characteristics of Transformer Oil under Different Operation Conditions EL-Sayed M. M. EL-Refaie, Mohamed R. Salem, and Wael A. Ahmed Digital Open Science Index, Electrical and Computer
More informationDGA - Method in the Past and for the Future
DGA - Method in the Past and for the Future IVANKA ATANASOVA-HÖHLEIN Höhlein, Folie 1 Höhlein, Folie 2 -1970 Doerenburg introduced the differentiation between electrical and thermal failure mode and introduced
More informationPractical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian.A.R. Gray
Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter Ian.A.R. Gray Largest aluminium smelter in the Southern hemisphere South Africa's major producer of primary aluminium It
More informationFORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES
Int. J. Chem. Sci.: 13(4), 2015, 1777-1786 ISSN 0972-768X www.sadgurupublications.com FORECASTING THE NATURE OF POWER TRANSFORMER INSULATION OIL USING CHEMICAL PROPERTIES OF DISSOLVED GASES K. IYSWARYA
More informationAvailable online at ScienceDirect. Study on Dissolved Gas Due Tue Thermally Degraded Insulating Paper in Transformer Oil
Available online at www.sciencedirect.com ScienceDirect Procedia Technology 11 ( 2013 ) 257 262 The 4th International Conference on Electrical Engineering and Informatics (ICEEI 2013) Study on Dissolved
More informationTOGA PRESENTATION REVIEW OF CASE STUDIES. Paul Boman,
TOGA PRESENTATION REVIEW OF CASE STUDIES Paul Boman, paul_boman@hsb.com October 8, 2014 HSB s TOGA History TOGA Transformer Oil Gas Analyst Registered trademark of Hartford Steam Boiler Inspection and
More informationDEPARTMENT OF ELECTRICAL ENGINEERING DIT UNIVERSITY HIGH VOLTAGE ENGINEERING
UNIT 1: BREAKDOWN IN LIQUIDS 1.) Introduction: The liquid dielectrics due to their inherent properties appear as though they would be more useful as insulating materials than either solids or gases. The
More informationSmart Grid Monitoring of Transformers by DGA. Michel Duval. CIGRE Thailand, Bangkok 2013
Smart Grid Monitoring of Transformers by DGA Michel Duval CIGRE Thailand, Bangkok 2013 1 Electric Power 2 Power Transformers 3 Catastrophic Failures 4 Failures in Service - The failure rate of power transformers
More informationSoftware Implementation of Duval Triangle Technique for DGA in Power Transformers
International Journal of Electrical Engineering. ISSN 0974-2158 Volume 4, Number 5 (2011), pp. 529-540 International Research Publication House http://www.irphouse.com Software Implementation of Duval
More informationSilicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.
Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other
More informationAnil Kumar*, Ajay Rathore** Ashish Patra ***
Analysis of Power Transformer using fuzzy expert and neural network system Anil Kumar*, Ajay Rathore** Ashish Patra *** Electrical Department MITS Gwalior (MP)INDIA474002 Abstract- Power transformers being
More informationLeakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica
Leakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica F.L.Muhamedin, M.A.M.Piah, and N. F. Kasri Institute of High Voltage and High Current Faculty Of Electrical
More informationExpertise method to diagnose transformer conditions
Expertise method to diagnose transformer conditions J. BILBAO, C. M. REBOLLO, and P. GONZÁLEZ Applied Mathematics Department. University of the Basque Country Engineering School, Alda. de Urquijo s/n,
More informationTOGA Electrical Insulating Fluid Analysis. Improving performance and protecting assets.
TOGA Electrical Insulating Fluid Analysis Improving performance and protecting assets. It happens all the time - transformers fail unexpectedly, and there are often no external visual clues on what caused
More informationField experiences with the world s l argest natural e ster-filled transformer EVENTS LIQUID INSULATION ABSTRACT KEYWORDS
EVENTS LIQUID INSULATION ABSTRACT Electric utilities have a duty to supply electricity securely whilst being mindful of environmental needs and fire safety, especially in urban areas. Mineral oil in power
More informationOil Diagnostics - Test Information
Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks
More informationThe effectiveness of oil analysis for failure prediction of power transformers
The effectiveness of oil analysis for failure prediction of power transformers by Krige Visser and Yashin Brihmohan, University of Pretoria The availability of an electricity network is of utmost importance
More informationICM Project Station Infrastructure and Equipment
EB 0 00 ( pages) ICM Project Station Infrastructure and Equipment Stations Power Transformers Segment (THESL) EB 0 00 I EXECUTIVE SUMMARY. Project Description This segment consists of replacing power transformers
More informationFriday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems
Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one
More informationMoisture equilibrium charts
Moisture equilibrium charts For effective condition monitoring of natural ester fluid-filled green transformers 04/29/2016-5.18 pm Clean Grid Green transformer Power transformers Green transformers, which
More informationCHAPTER 6 ENHANCEMENT OF CRITICAL CHARACTERISTICS OF TRANSFORMER OIL USING NANOMATERIALS
120 CHAPTER 6 ENHANCEMENT OF CRITICAL CHARACTERISTICS OF TRANSFORMER OIL USING NANOMATERIALS 6.1 INTRODUCTION Transformer oil is typically a highly refined mineral oil that is stable at high temperature
More informationPERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS
International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10
More informationFAILURE ANALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH
FAILURE ALYSIS OF POWER TRANSFORMERS BY DGA, OIL TESTS AND MARKOV APPROACH Mohammed Abdul Rahman Uzair Research Scholar, Department of EEE, GITAM University, Hyderabad, Telangana, INDIA Dr. Basavaraja
More informationOil Regeneration in 132kV and 33kV Transformers 6 December 2017
1 Oil Regeneration in 132kV and 33kV Transformers 6 December 2017 Paul Marshall Innovation Project Manager Agenda Introduction Research IFI oil regeneration project Oil regeneration results Oil regeneration
More informationA REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES
A REVIEW ON FAULT ANALYSIS IN UNDERGROUND CABLES Siddharth Lohia 1, Usman Khan 2, Swati Dixit 3 1, 2 Students, Electrical Engineering Department Greater Noida Institutes of Technology, Gr.Noida, (India)
More informationREVIEW OF THE ELECTRICAL AND THERMAL BEHAVIOUR OF ESTER-BASED DIELECTRIC LIQUIDS FOR EXTRA HIGH VOLTAGE APPLICATIONS
REVIEW OF THE ELECTRICAL AND THERMAL BEHAVIOUR OF ESTER-BASED DIELECTRIC LIQUIDS FOR EXTRA HIGH VOLTAGE APPLICATIONS Mark Lashbrook, Dr Attila Gyore, Dr Russell Martin Products of M&I Materials Ltd. Agenda
More informationAccreditation Scope by Certification Test Order
Organization NEMA MW 1000 NEMA RE-2 Section 4.11 ASTM D149 ASTM D150 ASTM D256 ASTM D257 ASTM D495 ASTM D570 ASTM D635 ASTM D638 ASTM D790 ASTM D882 ASTM D1653 ASTM D1676 ASTM D1822 ASTM D1830 ASTM D1876
More informationEnhance Power Equipment Reliability with Predictive Maintenance Technologies
Enhance Power Equipment Reliability with Predictive Maintenance Technologies November 2012/1910DB1208 by S. Frank Waterer, Electrical Engineerinig, Fellow Schneider Electric USA, Inc. Make the most of
More informationA Novel Approach for Diagnosis of Power Transformers Internal Faults Using an Electronic Nose
808 J. Basic. Appl. Sci. Res., 1(7)808-815, 2011 2011, TextRoad Publication ISSN 2090-4304 Journal of Basic and Applied Scientific Research www.textroad.com A Novel Approach for Diagnosis of Power Transformers
More informationStudy on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil
Study on Thermal Ageing Characteristics of Silicone Rubber and Pressboard in Mineral Oil M.Sc. Smitha Karambar, Prof. Dr.-Ing. Stefan Tenbohlen University of Stuttgart, Institute of Power Transmission
More informationDissolved Gas Analysis for transformer. health. management. Precise DGA measurements are required to look for transformer condition changes COLUMN
COLUMN Precise DGA measurements are required to look for transformer condition changes ABSTRACT Complex studies have led to the development of powerful methods to assess the health of the insulation system,
More informationOnline dissolved gas analysis sensor
GAS Guard 8 Online dissolved gas analysis sensor Answers for energy. Dissolved Gas Analysis (DGA) Dissolved gas analysis is the single-most comprehensive tool for transformer condition assessment. The
More informationPROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS
PROGRESS IN PAPER DEGRADATION ASSESSMENT IN SERVICE-AGED TRANSFORMERS H. Ding, R. Heywood, J. Lapworth, S. Ryder and A. Wilson Presenter: Dr Hongzhi Ding Doble PowerTest Ltd UK INSUCON - 17 th May 2017
More informationElectrical Treeing in Polymer Nanocomposites
Electrical Treeing in Polymer Nanocomposites Sridhar Alapati 1 and M. Joy Thomas 2 Nanodielectrics Laboratory Department of Electrical Engineering Indian Institute of Science, Bangalore 560012 e-mail:
More informationThe Next Step In The World Of Transformers
The Next Step In The World Of Transformers Envirotran TM Transformers Set Higher Environmental, Fire Safety and Performance Standards Envirotran TM Transformers Advance the Evolution of Electrical Distribution
More informationData Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer
Data Mining Approach With IEC Based Dissolved Gas Analysis For Fault Diagnosis Of Power Transformer Ms Kanika Shrivastava M.E. in H.V.P.S. Electrical Engineering, JEC, Jabalpur, (M.P) Mr. Ashish Choubey
More informationExcellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification
Excellent Insulation and Cooling of Power Transformer Oil 25#&45# Brand Transformer Oil Specification 1 1. Description The chemical composition of transformer oil is made up of moderate low viscosity and
More informationRemnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference System
Faculty of Science and Engineering Department of Electrical and Computer Engineering Remnant Life Estimation of Power Transformers Based on Chemical Diagnostic Parameters Using Adaptive Neuro- Fuzzy Inference
More informationResidual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid insulation
International Journal of Scientific and Research Publications, Volume 6, Issue 7, July 2016 230 Residual Life assessment with DGA, Furan content in transformer oil and Degree of polymerization of solid
More informationFeatured Product. Transformer Monitoring and Diagnostic Systems
Featured Product Transformer Monitoring and Diagnostic Systems Transformer Predictive Analysis Owners of critical transformer equipment can realize the benefits of predictive analysis on transformer health
More informationImran Zulquifal Mamade
A METHODOLOGY TOWARDS CONDITION-BASED ASSET MANAGEMENT Imran Zulquifal Mamade Instituto Superior Técnico, Lisboa, Portugal, 2016 imran.mamade@tecnico.ulisboa.pt Abstract: Back on the 1970s, electric utilities
More informationSuperior client serv ice. Electrical confidence. CARGILL LIMITED Transformer Oil Sampling and Analysis. June 7, 2016 File: C
Superior client serv ice. Electrical confidence. CARGILL LIMITED 6 Transformer Oil Sampling and Analysis June 7, 6 File: C- Project Manager: George Shehata, P.Eng. info@magnaiv.com www.magnaiv.com Engineering
More informationOnline Condition Monitoring of Transformer
Online Condition Monitoring of Transformer ---------------------------------------------------- Heart of any power system An essential Part of a Cost efficient maintenance Program. It is well known that
More informationApplying Grey Theory Prediction Model on the DGA Data of the Transformer Oil and Using It for Fault Diagnosis
Applying Grey Theory Prediction Model on the DGA Data of the Transformer Oil and Using It for Fault Diagnosis ANJALI CHATTERJEE Electronics & Instrumentation. Central Mechanical Engineering Research Institute.
More informationMOISTURE MEASUREMENT IN ELECTRICAL EQUIPMENTS
REETA-2K16 ǁ PP. 605-610 MOISTURE MEASUREMENT IN ELECTRICAL EQUIPMENTS KAMBHAM ELLA REDDY PGstudent, Sree Vidyanikethan Engineering College, Andhra Pradesh, India, +91-8985857807, ellareddy1992@gmail.com
More informationIEEE Transformer Committee Atlanta Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation)
IEEE Transformer Committee Atlanta 2016 Arturo Núñez MISTRAS Group, Inc. (dba Physical Acoustics Corporation) A A A A A A A A A AE Sensor ACOUSTIC EMISSIONS INSTALLATION AE SENSORS HFCT Other info: DGA
More informationInvestigation of Critical Characteristics of Mineral Oil with Activated Carbon
Circuits and Systems, 2016, 7, 2521-2529 Published Online July 2016 in SciRes. http://www.scirp.org/journal/cs http://dx.doi.org/10.4236/cs.2016.79218 Investigation of Critical Characteristics of Mineral
More informationWeidmann Electrical Technology. Presenter Thomas A. Prevost, Weidmann-ACTI
Estimation of Insulation Life Based on a Dual Temperature Aging Model Weidmann-ACTI Inc. Fifth Annual Technical Conference Albuquerque, NM Nov. 13-15, 2006 Thomas A. Prevost, Hans Peter Gasser Weidmann
More informationTransformer Life Extension. CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units
Transformer Life Extension CJC V30 Transformer Oil Vacuum Filtration Unit and Ion Exchange Filtration Units Agenda Examples of V30 installations Background info Theory Field results Added safety Conclusion
More informationMOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL. GE Energy
MOISTURE IN PAPER ASSESSMENT FROM CONTINUOUS MONITORING OF MOISTURE IN OIL Jacques Aubin GE Energy Brian D Sparling Abstract Moisture content of solid insulation is a persistent concern for power transformer
More informationShunt Active Power Filter Wind Energy Conversion System
Proc. of the 3rd IASME/WSEAS Int. Conf. on Energy, Environment, Ecosystems and Sustainable Development, Agios Nikolaos, Greece, July 24-26, 2007 249 Shunt Active Power Filter Wind Energy Conversion System
More informationOXIDATION AGING AND RESULTING DIELECTRIC PERFORMANCE OF A NATURAL ESTER INSULATION SYSTEM FOR TRANSFORMERS
OXIDATION AGING AND RESULTING DIELECTRIC PERFORMANCE OF A NATURAL ESTER INSULATION SYSTEM FOR TRANSFORMERS Kevin RAPP Alan SBRAVATI John LUKSICH Cargill USA Cargill Brazil Cargill USA Kevin_Rapp@cargill.com
More informationPomona, CA May 24 25, 2016
Pomona, CA May 24 25, 2016 Transformer Technology Seminar Modular approach on economic condition assessment for power transformer; data management, Fleet screening and risk ranking Siemens AG 2014 All
More informationPARTIAL DISCHARGE TESTING: A PROGRESS REPORT
PARTIAL DISCHARGE TESTING: A PROGRESS REPORT PD GLOBAL VPI PROCESS 1 ABSTRACT V. Warren, G. Stone and H. Sedding, Qualitrol - Iris Power It has long been known that comparing the partial discharge results
More informationFundamental Aspects of Data Quality for HV Asset Condition Assessment
0609-137-Mep228 10/11/06 16:10 Page 46 Fundamental Aspects of Data Quality for HV Asset Condition Assessment WG D1.17, HV Asset Condition Assessment Tools, Data Quality - Expert Systems Convenor: E. GULSKI
More informationBachelor of Electrical Engineering (Industrial Power)
TRANSFORMER DISSOLVED GAS ANALYSIS USING DUVAL TRIANGLE METHOD VIA ANDROID Mohamad Hafiz Bin Abdul Wahid Bachelor of Electrical Engineering (Industrial Power) June 2014 " I hereby declare that I have read
More informationThe Effects of Electrical Degradation on the Microstructure of Metal Oxide Varistor
The Effects of Electrical Degradation on the Microstructure of Metal Oxide Varistor K.P. Mardira, T.K. Saha, Senior Member, IEEE, and R.A. Sutton Abstract--In this paper, the findings from systematic experiments
More informationMoisture Phenomena in Insulating Systems of Dry, Gas Insulated and Liquid Immersed Transformers & Reactors
Presenting Proposed New Reference Document Moisture Phenomena in Insulating Systems of Dry, Gas Insulated and Liquid Immersed Transformers & Reactors Prof. Valery G. Davydov, Consultant Melbourne, Australia
More informationTRANSFORMER OIL ANALYSIS
A member of the Set Point group I S S U E 3 6 TRANSFORMER OIL ANALYSIS By Neil Robinson, B.Sc. Hons. A basic introduction to an essential part of a cost-efficient maintenance programme It is well known
More informationA Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology
A Deep Insight on Improvement in HV and EHV XLPE AC Cable Technology Preet Khandelwal 1, Arun Pachori 2 1 preet_27sep@yahoo.co.in Abstract: This paper highlights on continuous improvement in Extra High
More information* 1 Engr. Muhammad Junaid, 2 Engr. Mehran Tahir, 3 Engr. Kamal Haider, * 4 Engr. Muhammad Aamir
International Journal of Engineering & Computer Science IJECS-IJENS Vol:13 No:03 16 HVAC Breakdown of R12, R12 Air Mixtures in Sphere gap Electrodes and Proposed Composite insulating Liquid to Reduce the
More informationPractical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter. Ian Gray Transformer Chemistry Services
Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter By Ian Gray Transformer Chemistry Services 1 Practical Experience Gained from Dissolved Gas Analysis at an Aluminium Smelter
More informationEXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION
EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani
More informationPotential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method
Potential and E-Field Calculation Along an Ice- Covered Composite Insulator with Finite Element Method Qing Yang, Caixin Sun, Wenxia Sima, Lichun Shu, Ji Yang, Jianlin Hu The Key Laboratory of High Voltage
More informationJournal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:
Journal of Operation and Automation in Power Engineering Vol. 1, No. 2, Summer & Fall 2013, Pages: 74-83 http://journals.uma.ac.ir/joape Impact of Pollution Location on Time and Frequency Characteristics
More informationThermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker
J Electr Eng Technol.2016; 11(?): 1921-718 http://dx.doi.org/10.5370/jeet.2016.11.3.1921 ISSN(Print) 1975-0102 ISSN(Online) 2093-7423 Thermal Recovery Characteristics of a CO 2 Mixture Gas Circuit Breaker
More informationPh. D. Thesis RESEARCH ON CREEPING DISCHARGE PHENOMENA IN INSULATING OILS: VEGETABLE-BASED OILS AS SUBSTITUTE OF MINERAL OIL.
Ph. D. Thesis RESEARCH ON CREEPING DISCHARGE PHENOMENA IN INSULATING OILS: VEGETABLE-BASED OILS AS SUBSTITUTE OF MINERAL OIL by Fri Murdiya Kanazawa Institute of Technology (KIT) Department of Electrical
More informationSGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens
SGC switchgears compatible with real service conditions : Solutions that address on-site conditions Pieter Himpens Pieter.Himpens@switchgearcompany.eu Frederik Delobelle Frederik.Delobelle@switchgearcompany.eu
More informationPerformance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions
Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various
More informationLow Voltage Hazardous Area Motors. Motors Energy Automation Coatings
Low Voltage Hazardous Area Motors Motors Energy Automation Coatings 1 EXPLOSIVE ATMOSPHERE An atmosphere is considered as explosive when the amount of gas, vapor, dust or fibers is such that a spark originated
More informationISOVOLTINE Transformer oils
ISOVOLTINE Transformer oils ISOVOLTINE TRANSFORMER OIL Safety and longevity In operation, a transformer reaches very high temperatures. It requires a lubricant to prevent overheating and break down. Each
More informationPower Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System
Power Transformer Fault Detection and Isolation based on Intuitionistic Fuzzy System 1 Manikandan Pandiyan, 2 Geetha Mani, Department of Instrumentation and Control Systems Engineering PSG College of Technology,
More informationMaintenance & Reliability Week South Africa. 24th of November 2010, Johan Grövik
Maintenance & Reliability Week South Africa 24th of November 2010, Johan Grövik Development from a different perspective Source: NASA picture Satellite photo of earth at night 2 Outline Trends and directions
More informationStudy on Predictive Maintenance Strategy
, pp.52-56 http://dx.doi.org/10.14257/astl.2016.137.10 Study on Predictive Maintenance Strategy Wang Hongxia, Ye Xiaohui, Yin Ming Naval University of Engineering, Wuhan 430033, China 25523224@QQ.com Abstract.
More informationInternational Journal of Mechatronics, Electrical and Computer Technology
Effect of Corona Ring on Potential Distribution and Electric Field on Silicon Insulator in Polluted Condition Rasool Feiz Kerendian 1*, Hasan Keshavarz Ziarani 1, Javad Ebrahimi 2 1 Electrical Eng. Dept.,
More informationIAS Accreditation Number ELTEK International Laboratories
IAS Accreditation Number TL-457 Company Name Address 248 Hughes Lane St. Charles, Missouri 63301 Contact Name Lisa Horner, Quality Manager Telephone +1 (636) 949-5835 Effective Date of Scope July 20, 2018
More informationQuality assessment of 11 KV transformer by internal dissolved gas analysis using CFD
INTERNATIONAL JOURNAL OF INNOVATIVE RESEARCH IN ELECTRICAL, ELECTRONICS, INSTRUENTATION AND CONTROL ENGINEERING Quality assessment of 11 KV transformer by internal dissolved gas analysis using CFD ithu
More informationImpact of Gearbox Oil Contamination on the Performance of the Wind Turbine Drivetrain
International Conference on Renewable Energies and Power Quality (ICREPQ 16) Madrid (Spain), 4 th to 6 th May, 2016 exçxãtuäx XÇxÜzç tçw céãxü dâtä àç ]ÉâÜÇtÄ (RE&PQJ) ISSN 2172 038 X, No.14 May 2016 Impact
More informationUniversity of Cape Town
The copyright of this thesis vests in the author. No quotation from it or information derived from it is to be published without full acknowledgement of the source. The thesis is to be used for private
More informationArtificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester
Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results
More informationDeveloping Dispersion System with Detecting Autonomic Leak Location
, pp.248-253 http://dx.doi.org/10.14257/astl.2014.63.55 Developing Dispersion System with Detecting Autonomic Leak Location Jeong Seok Oh Institute of Gas Safety R&D, Korea Gas Safety Corporation, 1390,
More informationIEC Publication [1] provides a coded list of faults
F E A T U R E A R T I C L E A Review of Faults Detectable by Gas-in-Oil Analysis in Transformers Key Words: Transformer, fault, dissolved gas analysis IEC Publication 60599 [1] provides a coded list of
More informationTRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING
TRANSFORMER S MOISTURE ASSESSMENT WITH ONLINE MONITORING Senja LEIVO Vaisala Oyj Finland senja.leivo@vaisala.com Jukka LEPPÄNEN Vaisala Oyj Finland jukka.leppanen@vaisala.com ABSTRACT This paper discusses
More informationSynthetic Ester-Based Oils and Their Application in Power Industry
European Association for the Development of Renewable Energies, Environment and Power Quality International Conference on Renewable Energies and Power Quality (ICREPQ 09) Valencia (Spain), 15th to 17th
More informationTransformer is gassing-what to do
Transformer is gassing-what to do V.V. Sokolov Scientific and Engineering Center ZTZ-Service Company, Dnepropetrovskoye shosse, 99 Zaporozhye, Ukraine Phone: (38)-()-595-87; Fax: (38)-()-5-498 Z. Berler,
More informationDevelopment of Composite Line Spacers for Distribution Lines
Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax
More informationQ & A on Moisture in Transformer Oil
Q & A on Moisture in Transformer Oil A unique opportunity to answer your specific questions about Moisture in Transformer Oil Behavior Steven Jiroutek Business Development Manager - Industrial Measurements
More informationEffect of Contaminant Flow-rate and Applied Voltage on the Current Density and Electric Field of Polymer Tracking Test
International Journal of Electrical and Computer Engineering (IJECE) Vol. 6, No. 2, April 2016, pp. 819~826 ISSN: 2088-8708, DOI: 10.11591/ijece.v6i2.9517 819 Effect of Contaminant Flow-rate and Applied
More informationAPEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer
APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape
More informationTECHNICAL PAPER PRESENTATION
1 W E L C O M E T O A C O M E T 2 1 7 TECHNICAL PAPER PRESENTATION 2 Analytics for Dissolved Gas Analysis BY RANDY COX A B O U T T H E A U T H O R Randy Cox is the Domain Expertise Manager for GE Grid
More informationComponents, Systems and Service for Transformers.
Components, Systems and Service for Transformers. HYDAC Headquarters in Germany HYDAC China Your Professional Partner for the Optimization of Transformers. With over 5,500 employees worldwide HYDAC is
More informationInfluence of discharge characteristics on methane decomposition in dielectric barrier discharge reactor
Influence of discharge characteristics on methane decomposition in dielectric barrier discharge reactor Sungkwon Jo 1), Dae Hoon Lee 2), Woo Seok Kang 3) and Young-Hoon Song 4) 1), 2), 3), 4) Plasma Laboratory,
More information