Yale University s Chemistry Research Building Employs Innovative Energy-Saving Measures

Size: px
Start display at page:

Download "Yale University s Chemistry Research Building Employs Innovative Energy-Saving Measures"

Transcription

1 Yale University s Chemistry Research Building Employs Innovative Energy-Saving Measures LEED-Certified Fume-Hood-Intensive Facility is Safe, Sun-filled, and Sustainable L aboratory buildings are notorious energy hogs, and organic chemistry research laboratory buildings are particular offenders. Not only do these buildings commonly employ once-through air systems, but they also require a rigorous approach to ventilation to protect researchers from breathing the harmful vapors of the volatile organic solvents omnipresent in organic chemistry research. Many research activities that just 10 years ago would have been performed on the benchtop are nowadays performed under exhaust ventilation via chemical fume hoods, snorkel exhaust, or other point exhaust systems, says Jim Blount, associate principal at Perkins+Will. Phoenix Controls Energy Saving Solutions for Yale University Chemistry Research Building Since reducing the building s energy usage while maintaining the safety of the researchers was a primary concern, Yale University installed Phoenix Controls equipment in its new chemistry facility. More than 380 venturi valves were installed at Yale s Chemistry Research Building for lab pressurization control and fume hood containment. Face velocity display fume hood monitors and Zone Presence Sensors were installed on the eight-foot combination fume hoods to reduce the face velocity from 100 to 60 FPM when the hoods were not occupied. The maximum hood exhaust was limited to only 840 CFM based on the horizontal sash opening. In addition, the minimum hood flows were reduced to 190 CFM, below the recommended minimum for an eight-foot hood, based on an investigation of chemical dilution rates by Yale s Environmental, Health and Safety department. The reduction in fume hood exhaust was possible because of the turndown (up to 20:1) and accuracy of Phoenix Controls flow-metering venturi valve. This reduction, combined with lower air change rates during unoccupied periods, provided Yale University significant operational savings within the first few years of building occupancy.

2 In addition, organic chemistry research, and scientific research in general, is using more equipment that requires direct exhaust, such as rotary evaporators, solvent purification systems, and high-throughput samplers. Understandably, researchers with a voice in laboratory design are increasingly requesting the widest fume hoods possible, abandoning the once-standard four-foot-wide fume hoods in favor of eight-foot or larger models that can accommodate equipment and provide adequate preparation and work-up space. With 160 eight-foot chemical fume hoods as well as 74 point exhaust systems, 74 vented chemical storage cabinets, and 37 equipment exhaust locations in addition to a once-through air system, Yale University s Chemistry Research Building promised to be a severe energy guzzler unless measures were taken to reduce energy costs. To address this problem, the design team focused on rethinking several aspects of fume hood design and reducing overall ventilation to laboratory spaces, as well as implementing other energy-saving strategies such as daylighting. ways to save millions of dollars in energy costs over the building s life cycle. The real success of the project wasn t just saving energy, says Schofer. It was the fact that we were able to save energy with the buy-in of the users, the maintenance staff, and the University s environmental health and safety officers, as well as the local code authority. We went to a great deal of effort and expense to make this a truly collaborative endeavor. Fume Hood Design Innovations Most of the time, researchers aren t going to be that excited about saving energy, says Schofer. They just want to do their work safely and efficiently. The researchers natural desire for an unencumbered workspace which in the lab would translate to the widest possible chemical fume hood, with a wide-open sash clearly was not an option from an energy standpoint. However, it was also true that no individual Throughout the project, the team concentrated on implementing as many energy-saving measures as possible, while ensuring adequate health and safety protections for students and faculty. From the very beginning, we did life cycle cost analyses on some of these measures to see how much they would benefit the University and the users, says Lee Schofer, senior associate and project manager at Vanderweil Engineers. Two of those analyses of constant versus variable air volume fume hoods, and of two different types of fume hood sashes revealed Fume Hood Preoccupancy - Chemical fume hoods in Yale s Chemistry Research Building are equipped with numerous energy-saving features, including combination vertical/horizontal sliding sashes, zone presence sensors, room occupancy sensors, fume hood monitors and under-hood storage cabinets.

3 researcher would need to use the entire eight-foot width of the hood at one time. An effective compromise was struck in the implementation of a combination sash, with a custom-designed aerodynamic airfoil. In addition to sliding up and down like a normal fume hood sash, the combination sash contains glass panels that slide horizontally within it. With a maximum 28" x 34" horizontal sash opening, the combination sash provided openings sufficient to accommodate the full spectrum of research activities conducted at the Chemistry Research Building. The combination sash was shown in a life cycle cost analysis to yield a 25 percent energy savings compared to a standard sash with a vertical opening of 14". Additionally, as it turned out, the researchers actually preferred the combination sash to the conventional model. This is the first instance on campus where we have used a large number of these types of sash configurations, says Rob Klein, associate director at Yale s Office of Environmental Health and Safety, and we were worried that individuals would find them too confining. Instead, people have indicated that they do like them. They found they could have a higher opening in the hood, says Schofer. The researchers especially appreciated the added safety they could achieve by using a horizontal sliding panel as a body shield, reaching around the sides of the panel to perform particularly hazardous work. Another significant savings was achieved by employing variable-air-volume (VAV) chemical fume hoods equipped with zone presence sensors. A life cycle cost study of the devices showed that they could reduce energy use by an additional 40 percent by reducing exhaust Another significant savings was achieved by employing variable-air-volume (VAV) chemical fume hoods equipped with zone presence sensors. A life cycle cost study of the devices showed that they could reduce energy use by an additional 40 percent by reducing exhaust through the hood when the floor area in front of the hood was unoccupied. through the hood when the floor area in front of the hood was unoccupied. This exhaust-rate reduction enabled by the zone presence sensors combined with the 25 percent reduction provided by the combination sash resulted in a total exhaust-rate reduction that exceeded that permitted by NFPA guidelines. To justify this reduction, Klein and several of his safety colleagues spearheaded an investigation into the efficacy of various fume-hood exhaust rates in mitigating explosive environments caused by chemical spills within hoods. The team purposely spilled various common solvents within fume hoods and measured the evaporation and resulting solvent concentrations in exhaust air under different hood operating conditions. Klein s findings, which were published in the American Chemical Society journal Chemical Health and Safety (March/April 2004), were very clear and extremely advantageous to the project. What we confirmed, says Klein, is that solvent evaporation is a function of chemical vapor pressure and exhaust flow rates. With all other fume hood variables held the same, less total exhaust air does increase chemical concentrations, but you can significantly lower flow without creating an explosive atmosphere. In fact, we found that for common lab chemicals, we could lower flows nearly fivefold during non-use times and still maintain a safe fume hood environment for a net exhaust-rate reduction of 80 percent. Armed with these results, the design team appealed to the local and state code authorities for an exception to the NFPA requirements an exception that was granted.

4 Room Ventilation Innovations In addition to making fume hoods more efficient, the project team also sought to optimize ventilation airflow into laboratory areas. The first step was finding out when researchers did their work. When we looked at the use patterns of Yale s graduate-level chemistry research facilities, says Blount, we found that they were virtually unoccupied from about 2 a.m. to about 10 a.m. We wanted to develop systems that would respond to these large windows of unoccupied time. Laboratories are equipped with dual technology (ultrasonic/infrared) occupancy sensors, and airflow rates as well as lighting switches are keyed to the sensors. To ensure that the sensors could see all parts of the room including the shadow areas cast by island benches and other obstacles laboratories are equipped with three occupancy sensors apiece. In addition, the zone presence sensors on the fume hoods, which raised or lowered varied fume hood exhaust rates depending on whether a user was nearby, are also keyed to room ventilation controls to ensure a sufficient volume of air for the fume hoods to exhaust. With the three occupancy sensors, and the zone presence sensors for the fume hoods, says Schofer, we were pretty heavily instrumented. How much could airflow be reduced when labs were unoccupied? Best-practices standards of the day dictated 12 air changes per hour for all lab spaces, occupied or not. The team, however, proposed reducing the airflow in unoccupied lab spaces from 12 air changes per hour to six. At the time, this was almost heresy, says Schofer. Everyone assumed that you had to have at least 12 air changes per hour in a lab, especially a chemistry lab. Yale s Office of Environmental Health and Safety, reluctant at first, eventually warmed to the idea. As we got more into the design and they could see that we were providing adequate chemical storage and room pressurization, they were willing to try it, he says. The measure, says Schofer, has resulted in big-time energy savings, with no reduction whatsoever in air quality. Building Design and Layout Natural Light - Daylighting abounds in Yale s Chemistry Research Building, enhancing the work environment for researchers and achieving significant energy savings. Light sensors in laboratories enable shutoff of lights when daylight levels exceed set thresholds. The Chemistry Research Building (CRB) is Yale University s third building on Science Hill, joining the Sterling Chemistry Building and the Kline Chemistry Building. The 100,000-sf new building is dedicated to organic chemistry, with space for 12 PIs and 148 graduate students.

5 This building really is based around academic research in the lab, says Klein. The building layout consists of a simple and modular rectangle with technical program on one side and non-technical program on the other. Faculty offices are co-located to encourage collaboration among the groups. Graduate student offices are located directly across from the main labs. The 37 lab modules are each configured for four investigators, with four chemical fume hoods, four bench spaces, one central island bench, four sinks, and an equipment zone. Write-up spaces and lab support spaces are accessible via a corridor within the lab. Breakout and collaboration spaces are situated along the main circulation spine and in central locations. laboratory, says Schofer. But we were able to work within the LEED regulations and get the certification. Reprinted with Permission February 2007 from TradelineInc.com, a registered product of Tradeline Inc., a provider of leading-edge resources to facilities planning and management through conferences, publications, and the Internet community. Visit for more information. Daylighting is a simple yet powerful design strategy that the design team employed in abundance throughout the Chemistry Research Building. Besides enabling significant energy savings on electric lighting, the sunlight streaming through the laboratory windows creates a pleasant, vibrant environment in which researchers can do their best work. Project Successes Despite the myriad reductions in ventilation and fume hood exhaust rates, users express high levels of satisfaction with the new facility. Over the first year of operation, says Klein, the volume of complaints related to odors, spills, and smells was 50 percent less than at Yale s older laboratory buildings. On a daily basis that classic organic chemical odor is essentially imperceptible in the rooms. The big success of this project, says Schofer, is that in all aspects, whether it s fighting fires, paying for energy, health and safety, efficiency of use, everybody just seems satisfied with it. In a major triumph, however, the building has achieved LEED certification thought by many to be impossible for a building of this type. I had many a heated debate as to whether we could end up with a LEED-certified

6 Biographies: James V. Blount, AIA, LEED AP, formerly with Cannon Design (architect of the Chemistry Research Building), now associate principal at Perkins+Will, has dedicated his career to sustainable architecture for science and technology. He has been involved in the management, planning, and design of more than 1 million square feet of research laboratory space. Robert Klein, CIH, is associate director of Yale University s Office of Environmental Health and Safety. Over more than 20 years of practice, he has also worked at a national laboratory, a consulting engineering firm, and a biomedical laboratory and published numerous articles on applied environmental, health, and safety issues. E. Lee Schofer, PE, is senior associate and project manager for Vanderweil Engineers. With 37 years of experience in HVAC and architectural engineering, primarily of laboratories and vivariums, he has been involved in the designs of numerous buildings on Yale s Science Hill for the past 11 years. For more information: James Blount, AIA, LEED AP Associate Principal Perkins+Will Inc. 55 Court Street Boston, MA (617) james.blount@perkinswill.com Robert Klein, CIH Associate Director, Office of Environmental Health and Safety Yale University 135 College Street, 1st Floor New Haven, CT (203) rob.klein@yale.edu E. Lee Schofer, PE Senior Project Manager Vanderweil Engineers Inc. 101 Grovers Mill Road Lawrenceville, NJ (609) lschofer@vanderweil.com Project Team: Architect of Record: Cannon Design, Boston, MA Civil Engineer: Purcell Associates, Glastonbury, CT Design Architect: Bohlin Cywinski Jackson, Pittsburgh, PA Fume Hoods: Fisher Hamilton, Two Rivers, WI Lab Planner: Research Facilities Design, San Diego, CA Laboratory Controls: Phoenix Controls Corporation, Boston, MA Landscape Architect: Carol R. Johnson Associates, Cambridge, MA LEED Consultant: The RETEC Group Inc., New Haven, CT MEP Engineer: R. G. Vanderweil Engineers, LLP, Lawrenceville, NJ Structural Engineer: Cannon Design, Grand Island, NY Yale University, New Haven, CT Facilities Project Manager: Rich Vollaro Office of Health and Safety: Rob Klein, Paula Labbie, Cathleen King Chemistry Department Building Manager: Joanne Bentley Printed in U.S.A. MKT-0219 MPC /07

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation

Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation Evaluating Alternative Fume Hood System Technologies Using Advanced Building Simulation William J. Kosik, P.E., C.E.M. 1 Karl Aveard, AIA Associate 2 Heather R. Beaudoin, P.E., C.E.M. 3 Erik L. Olsen 3

More information

Better airflow, less energy, lower costs

Better airflow, less energy, lower costs Better airflow, less energy, lower costs Fume hood retrofits yield big benefits for National Research Council Canada Building M-12 Laboratories and research facilities can consume up to eight times the

More information

It s all part of a cyclic process, perhaps best described as outcome-based design, Blakey adds.

It s all part of a cyclic process, perhaps best described as outcome-based design, Blakey adds. Using Outcome-Based Design to Right-Size the Project Budget Standard Financial Analysis and Productivity Data Help Align New Building Plans with Critical Goals What determines how much a new project should

More information

43% reduction in water use below code maximum 100% 100% 14% reduction in lighting power density. 56% of offices have thermal comfort controls 100%

43% reduction in water use below code maximum 100% 100% 14% reduction in lighting power density. 56% of offices have thermal comfort controls 100% Insert school or unit logo Nocera Lab LEED CI v3.0 12 Oxford Street, Cambridge, MA GOLD Project Profile Laboratories are typically regarded as an energy intensive building typology. Many of these buildings

More information

2010 CA Higher Education Sustainability Conference

2010 CA Higher Education Sustainability Conference 2010 CA Higher Education Sustainability Conference Energy Efficiency Partnership Program Best Practice Awards Application Project Category 11 Rendering Used Courtesy of Cannon Design I. Contact Information

More information

Beyond LEED, Sustainable Laboratory Design

Beyond LEED, Sustainable Laboratory Design Beyond LEED, Sustainable Laboratory Design Beyond LEED, Sustainable Laboratory Design The U.S. Green Building Council s LEED (Leadership in Energy and Environmental Design ) Green Building Rating System

More information

Achieving Near Net-Zero Energy Usage in Laboratory

Achieving Near Net-Zero Energy Usage in Laboratory Page 1 of 8 Published on www.tradelineinc.com (http://www.tradelineinc.com) Home > Achieving Near Net-Zero Energy Usage in Laboratory Facilities Achieving Near Net-Zero Energy Usage in Laboratory Facilities

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract.

Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. SECTION 11 00 00 - EQUIPMENT GENERAL INFORMATION Fixed equipment shall generally be furnished and installed by the General Contractor as part of the construction contract. Movable equipment shall, as a

More information

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois Retrocommissioning Saving the Planet One Building at a Time AIA Quality Assurance Portland Energy Conservation, Inc is a registered

More information

What s Possible? Extreme repurposing of non-lab spaces in to state-of-the-art research facilities: Tradeline Research Facilities May 9-10, 2013

What s Possible? Extreme repurposing of non-lab spaces in to state-of-the-art research facilities: Tradeline Research Facilities May 9-10, 2013 Extreme repurposing of non-lab spaces in to state-of-the-art research facilities: What s Possible? Tradeline Research Facilities May 9-10, 2013 Jeff Goldberg/Esto Presenters STEVE FREI, PE, LEED AP Principal

More information

15020 LABORATORIES. C. Section Building Automation and Control System Guidelines

15020 LABORATORIES. C. Section Building Automation and Control System Guidelines 15020 LABORATORIES PART 1: GENERAL 1.01 RELATED SECTIONS A. Section 01004 Energy Guidelines B. Section 01008 Energy Modeling Guidelines C. Section 15955 Building Automation and Control System Guidelines

More information

Using CFD to Wring Out Energy Efficiency in Laboratory Settings

Using CFD to Wring Out Energy Efficiency in Laboratory Settings Using CFD to Wring Out Energy Efficiency in Laboratory Settings Energy Conservation Strategies for Cornell University Laboratories Primary focus is on controls to reduce outside air use Occupancy sensors

More information

PART 30: LABORATORIES

PART 30: LABORATORIES PART 30: LABORATORIES GENERAL REQUIREMENTS Definitions 30.7.1 In sections 30.8 to 30.11: laboratory fume hood operational face opening sash Laboratory fume hoods means an enclosed and mechanically ventilated

More information

In the last few years, the concerns about global

In the last few years, the concerns about global Gordon P. Sharp March 2009 A Comprehensive Review of the IEQ and Energy Savings Impact of Dynamically Varying Air Change Rates in Labs and Vivariums The greatest single approach for reducing energy use

More information

Demand-Based Control of Laboratory Air Change Rates

Demand-Based Control of Laboratory Air Change Rates Demand-Based Control of Laboratory Air Change Rates Gordon P. Sharp Chairman Aircuity,, Inc. Aircuity Project: Bank of America Tower, NYC Research Laboratory Energy: Why Do We Care? Lab Energy Usage: 5

More information

LABORATORIES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. A. Section Accessibility for People with Disabilities

LABORATORIES 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS. A. Section Accessibility for People with Disabilities 230540 LABORATORIES PART 1 GENERAL 1.01 RELATED CORNELL DESIGN AND CONSTRUCTION STANDARDS A. Section 013010 Accessibility for People with Disabilities B. Section 018120 Energy Guidelines C. Section 018130

More information

Cleveland State University Office of Environmental Health & Safety. Standard Operating Procedures For Chemical Fume Hoods

Cleveland State University Office of Environmental Health & Safety. Standard Operating Procedures For Chemical Fume Hoods Cleveland State University Office of Environmental Health & Safety Standard Operating Procedures For Chemical Fume Hoods Cleveland State University, in its efforts to provide for the health and safety

More information

Blue Ridge Parkway Destination Center Earns a Rare 11 of 10 Points for Optimized Energy Performance

Blue Ridge Parkway Destination Center Earns a Rare 11 of 10 Points for Optimized Energy Performance FOR IMMEDIATE RELEASE News Release Contact: Anne Taylor Lord, Aeck & Sargent 404-253-6710 ataylor@lasarchitect.com or Ann Kohut Kohut Communications Consulting 770-913-9747 annielk@bellsouth.net Blue Ridge

More information

GATES-HILLMAN CENTERS

GATES-HILLMAN CENTERS GATES-HILLMAN CENTERS CARNEGIE MELLON UNIVERSITY CASE STUDY ENERGY EFFICIENCY CARNEGIE MELLON UNIVERSITY Carnegie Mellon University looked to SEMCO to provide solutions for their energy efficiency goals.

More information

Variable Air Volume (VAV) For Laboratories

Variable Air Volume (VAV) For Laboratories Variable Air Volume (VAV) For Laboratories by Steven G. Liescheidt, PE, CCS, CCPR Overview: Variable Air Volume (VAV) systems have been used for many years in commercial HVAC systems for a variety of reasons.

More information

Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance

Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Forum M: Top 10 Cost Reduction Strategies for Science Facility Operations and Maintenance Presentation Outline

More information

MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN

MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN MODULE 5 HVAC FUNDAMENTALS OF MODERN LABORATORY DESIGN Module 5 PG1 MODULE 5 GOAL Provide a fundamental understanding of Laboratory Heating, Ventilating and Air Conditioning Concepts and Systems Module

More information

DESIGNER'S GUIDE. Section IV Close Out Procedures (Revised May 22, 2013) Yale University Facilities Planning & Construction

DESIGNER'S GUIDE. Section IV Close Out Procedures (Revised May 22, 2013) Yale University Facilities Planning & Construction DESIGNER'S GUIDE Section IV Close Out Procedures (Revised May 22, 2013) Yale University Facilities Planning & Construction TO ACCESS SECTION CLICK ON TITLE IN INDEX IV. Table of Contents IV. CLOSE OUT

More information

Fume Hoods The Next Generation

Fume Hoods The Next Generation Fume Hoods The Next Generation CETA/SEFA Spring Meeting Tampa-St. Petersburg, FL Karl Aveard, AIA Associate Director of Business Development Earl Walls Associates The Evolution of Fume Hoods Conventional

More information

Grunenwald Science and Technology Building

Grunenwald Science and Technology Building Grunenwald Science and Technology Building Clarion University- Clarion, PA AE 482 Mechanical Project Proposal: Proposal for Alternative Designs Shane Helm The Pennsylvania State University Architectural

More information

ARE YOU READY TO OPERATE? Designing ORs to meet new technological advancements

ARE YOU READY TO OPERATE? Designing ORs to meet new technological advancements ARE YOU READY TO OPERATE? Designing ORs to meet new technological advancements Gary Hamilton PE, SASHE, LEED AP BD+C, CxA, EDAC Ionel Petrus PE, LEED AP BD+C, CEM 2016 SmithGroupJJR 1 Objectives The audience

More information

PHONE FAX WEB Mitchell Road Newbury Park, CA 91320

PHONE FAX WEB Mitchell Road Newbury Park, CA 91320 PHONE 805-498-3121 FAX 805-498-1855 EMAIL info@hansonlab.com WEB www.hansonlab.com 814 Mitchell Road Newbury Park, CA 91320 About HLF Building Great Labs Since 1973 Since 1973, Hanson Lab Furniture (HLF)

More information

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations

DIVISION 11 - EQUIPMENT FOOD SERVICE EQUIPMENT LABORATORY FUME HOODS. A. Design Considerations DIVISION 11 - EQUIPMENT 11400 FOOD SERVICE EQUIPMENT A. Design Considerations 1. The A/E shall use the services of a food service equipment specialist in preparation of kitchen areas and other food preparation

More information

Lab Energy Management Big Ten Mechanical & Energy Conference October The Approach

Lab Energy Management Big Ten Mechanical & Energy Conference October The Approach Lab Energy Management Big Ten Mechanical & Energy Conference October 2014 1 The Approach Promotion and awareness of Campus Energy Transition Plan Goals Be Spartan Green, Face It: Green Looks Good on You,

More information

Energy at Tufts Health Sciences Campus, Boston January 15, 2014

Energy at Tufts Health Sciences Campus, Boston January 15, 2014 Energy at Tufts Health Sciences Campus, Boston January 15, 2014 Utilities: Boston Campus Purchased steam from Veolia s Kneeland Street facility and cogenerated steam from Kendall Station in Cambridge Nstar

More information

DESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards

DESIGN AND CONSTRUCTION STANDARDS. Section 2: Standards for Specific Categories of Work. Laboratory Standards Laboratory Standards These criteria include general planning guidelines. They are intended for use of Designers during the design phases of the project. Planning Assumptions Overview In order to maximize

More information

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM

Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Shannon Horn P.E., AHJ, LEED A.P. Timothy Lockhart CIH, CHMM Participants will be able to: 1. Provide a convincing argument to Authorities Having Jurisdiction (AHJ) and Environmental Health and Safety

More information

Section Gas, Chemical, Hazardous Material Storage

Section Gas, Chemical, Hazardous Material Storage 1 2 Gas, Chemical, Hazardous Material Storage 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24 25 26 27 28 29 30 31 32 33 34 35 36 37 4.4.1 General Comply with the design and safety guidelines

More information

LABORATORY CONTROL SOLUTIONS FROM TSI

LABORATORY CONTROL SOLUTIONS FROM TSI LABORATORY CONTROL SOLUTIONS FROM TSI UNDERSTANDING, ACCELERATED SAFE, FLEXIBLE CONTROL SOLUTIONS SAFETY Research in laboratories helps advance science in many different disciplines. Professionals working

More information

Sustainable Laboratory Design: Challenges and Solutions

Sustainable Laboratory Design: Challenges and Solutions Sustainable Laboratory Design: Challenges and Solutions Stephen P. Mead Ph.D. College of Engineering Northern Arizona University U.S.A. Abstract: This paper provides a case study analysis of a biohazard

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

The Safety and Sustainability Factors of FILTERED FUME HOODS, DUCTLESS FUME HOODS, AND DUCTED FUME HOODS. By Kenneth Crooks

The Safety and Sustainability Factors of FILTERED FUME HOODS, DUCTLESS FUME HOODS, AND DUCTED FUME HOODS. By Kenneth Crooks The Safety and Sustainability Factors of FILTERED FUME HOODS, DUCTLESS FUME HOODS, AND DUCTED FUME HOODS By Kenneth Crooks Fume hoods are a central component in most laboratories. Whether you are designing

More information

88.2% 32% 23% WEITZ LABORATORY GOLD. PROJECT HIGHLIGHTS LEED Facts. of on-site generated construction waste was diverted from landfills.

88.2% 32% 23% WEITZ LABORATORY GOLD. PROJECT HIGHLIGHTS LEED Facts. of on-site generated construction waste was diverted from landfills. WEITZ LABORATORY GORDON MCKAY LABS BUILDING, 9 OXFORD STREET, CAMBRIDGE, MA 02138 LEED-CIV3.0 GOLD The Gordon McKay Laboratory of Applied Science (McKay) building, occupied and operated by the School of

More information

IFMA's How-To Guide Highlight: Getting Started on the Path to Sustainable Facility Management. Facility Engineering Associates

IFMA's How-To Guide Highlight: Getting Started on the Path to Sustainable Facility Management. Facility Engineering Associates IFMA's How-To Guide Highlight: g Getting Started on the Path to Sustainable Facility Management Christopher P. Hodges, P.E., CFM, LEED-AP, IFMA Fellow Christopher P. Hodges, P.E., CFM, LEED AP, IFMA Fellow

More information

Taylor Institute. LEED Certification : GOLD

Taylor Institute. LEED Certification : GOLD Taylor Institute LEED Certification : GOLD Native Landscaping Vegetation surrounding the Taylor Institute for Teaching and Learning is naturally suited to the Calgary climate. Native and adaptive plant

More information

UNIVERSITY OF NORTH DAKOTA

UNIVERSITY OF NORTH DAKOTA UNIVERSITY OF NORTH DAKOTA Safety & Environmental Health Office Standard Practice RSP 7 Testing and Maintenance of Radioisotope Fume Hoods Effective Date January 31, 1999 I. PURPOSE The purpose of this

More information

Broad Institute Expansion: Cambridge, Massachusetts. Mechanical Thesis Proposal

Broad Institute Expansion: Cambridge, Massachusetts. Mechanical Thesis Proposal Broad Institute Expansion: Cambridge, Massachusetts Mechanical Thesis Proposal Table of Contents Executive Summary... 2 Building Overview... 3 Mechanical System Overview... 4 Mechanical System Design Objectives...

More information

Report Contents. List of Figures Figure 1: Thesis Building Abstract... 3 Figure 2: Geothermal Well Detail... 6

Report Contents. List of Figures Figure 1: Thesis Building Abstract... 3 Figure 2: Geothermal Well Detail... 6 Report Contents Table of Contents Executive Summary... 2 Project Background... 3 Analysis One Impact of LEED on a Project... 5 Analysis Two Geothermal Well Evaluation... 6 Analysis Three Rainwater Collection

More information

Lab Sketchbook 2nd Floor Biology Science Building Saddleback College 2011 December 08

Lab Sketchbook 2nd Floor Biology Science Building Saddleback College 2011 December 08 Lab Sketchbook 2nd Floor Biology Science Building Saddleback College 2011 December 08 CONTENTS LABS ARE ORDERED WEST TO EAST Summary..... 3 Composite 2rd Floor Plan.... 4 Microbiology Laboratory 228...

More information

SECTION LABORATORY FUME HOODS

SECTION LABORATORY FUME HOODS PART 1 - GENERAL 1.1 DESCRIPTION: SECTION 11 53 13 LABORATORY FUME HOODS SPEC WRITER NOTE: Delete between // // if not applicable to project. Delete other items or paragraphs in the section that are not

More information

UBC Technical Guidelines Section Edition Fume Hoods Page 1 of 5

UBC Technical Guidelines Section Edition Fume Hoods Page 1 of 5 Page 1 of 5 1.0 GENERAL 1.1 Related UBC Guidelines.1 Section 12 35 53 Laboratory Casework.2 Section 23 38 16 Fume Hood Exhaust Systems.3 Section 20 00 08 Mechanical Identification for the details for fume

More information

The ASHRAE GreenGuide: One Means of Establishing a Link between Sustainable Design Practitioners

The ASHRAE GreenGuide: One Means of Establishing a Link between Sustainable Design Practitioners The ASHRAE GreenGuide: One Means of Establishing a Link between Sustainable Design Practitioners John Swift 1, Thomas M. Lawrence 2 1 Cannon Design, Boston, MA USA 2 University of Georgia, Athens, GA USA

More information

2012 USGBC Central Florida Chapter LEEDership Awards Outstanding Green Building of the Year: Valencia College, Lake Nona Campus Valencia College s

2012 USGBC Central Florida Chapter LEEDership Awards Outstanding Green Building of the Year: Valencia College, Lake Nona Campus Valencia College s 2012 USGBC Central Florida Chapter LEEDership Awards Outstanding Green Building of the Year: Valencia College, Lake Nona Campus Valencia College s fifth campus the first new campus in 15 years is in Southeast

More information

Analysis 1. LEED Analysis of Laboratory Buildings. Penn State School of Forest Resources University Park, PA

Analysis 1. LEED Analysis of Laboratory Buildings. Penn State School of Forest Resources University Park, PA Analysis 1 LEED Analysis of Laboratory Buildings Background The LEED program (Leadership in Energy and Environmental Design) established by the U.S. Green Building Council is becoming the standard by which

More information

How to Reduce Energy Use in Your Labs by Up to 50%

How to Reduce Energy Use in Your Labs by Up to 50% How to Reduce Energy Use in Your Labs by Up to 50% Illinois Chapter of ASHRAE April 11, 2017 Dan Doyle, Chairman Grumman/Butkus Associates 1 Course Description Labs have high exhaust requirements and large

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

PROPOSAL FOR ARCHITECTURAL SERVICES. June 22, 2015

PROPOSAL FOR ARCHITECTURAL SERVICES. June 22, 2015 PROPOSAL FOR ARCHITECTURAL SERVICES June 22, 2015 FIRM BACKGROUND Dimension IV Madison Design Group is built on a vision of architecture and professional services that puts the client and users, the building

More information

MODULE #5 MECHANICAL, ELECTRICAL, PLUMBING II

MODULE #5 MECHANICAL, ELECTRICAL, PLUMBING II MODULE #5 MECHANICAL, ELECTRICAL, PLUMBING II MICHAEL WALSH PRINCIPAL, R.G. VANDERWEIL ENGINEERS, LLP 274 Summer Street, Boston, MA 02210 (T) 617-423-7423 (F) 617-423-7401 mwalsh@vanderweil.com Module

More information

PRODUCTS SOLAR PLEXICON PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone.

PRODUCTS SOLAR PLEXICON PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION. Redefine your comfort zone. A I R D I S T R I B U T I O N PRODUCTS PRODUCT: SOLAR PLEXICON F O C U S 05 ADVANCING THE SCIENCE OF AIR DISTRIBUTION Redefine your comfort zone. www.titus-hvac.com Rethink what air management systems

More information

Laboratory Centralized Demand Controlled Ventilation System Increases Energy Efficiency in Pilot Study

Laboratory Centralized Demand Controlled Ventilation System Increases Energy Efficiency in Pilot Study Laboratories for the 21 st Century Technical Bulletin Laboratory Centralized Demand Controlled Ventilation System Increases Energy Efficiency in Pilot Study Laboratory ventilation rate guidelines are usually

More information

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,

More information

Background. LEED Design. VAV Systems. VRML Models. Conclusion. Background. LEED Design. VAV Systems. VRML Models. Conclusion. Background.

Background. LEED Design. VAV Systems. VRML Models. Conclusion. Background. LEED Design. VAV Systems. VRML Models. Conclusion. Background. SCHOOL OF FOREST RESOURCES BUILDING Penn State University University Park, PA Project s and Recommendations 3 April 200 PROJECT BACKGROUND PROJECT OVERVIEW Size: 92,000 SF Project Laboratory Space: 28,000

More information

Broad Institute Expansion: Cambridge, Massachusetts. Mechanical Thesis Proposal : REVISION I

Broad Institute Expansion: Cambridge, Massachusetts. Mechanical Thesis Proposal : REVISION I Broad Institute Expansion: Cambridge, Massachusetts Mechanical Thesis Proposal : REVISION I Table of Contents Executive Summary... 2 Building Overview... 3 Mechanical System Overview... 4 Mechanical System

More information

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal 0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Proposal David H. Koch Institute for Integrative Cancer Research Massachusetts Institute of Technology Cambridge,

More information

Basic Design Considerations for a Laboratory. The Ministry of Health & Family Welfare, under the Drugs & Cosmetics Act, laid down

Basic Design Considerations for a Laboratory. The Ministry of Health & Family Welfare, under the Drugs & Cosmetics Act, laid down Basic Design Considerations for a Laboratory Archana Salil, Director and Principal Architect- Arena Consultants The Ministry of Health & Family Welfare, under the Drugs & Cosmetics Act, laid down Good

More information

Fume Hood Equipment Service and Maintenance Policy

Fume Hood Equipment Service and Maintenance Policy Fume Hood Equipment Service and Maintenance Policy Objective: The objective of this policy is to establish fume hood equipment inspection, testing, and maintenance procedures to: Ensure the safety of students,

More information

Student Sustainability Committee Proposal Shut the Sash Model Program Development

Student Sustainability Committee Proposal Shut the Sash Model Program Development Project Lead Contact Information Name: Jeremy Neighbors Phone: 265-6084 Email: jneighbo@illinois.edu Address: 1501 S. Oak Street Title: Occupational Safety & Health Engineer PPSB, MC-821 Organization/Department:

More information

DISCOVERIES AT NET ZERO. Michael Leckman Diamond Schmitt Architects Chris Piche Integral Group

DISCOVERIES AT NET ZERO. Michael Leckman Diamond Schmitt Architects Chris Piche Integral Group DISCOVERIES AT NET ZERO Michael Leckman Diamond Schmitt Architects Chris Piche Integral Group DISCOVERIES AT NET ZERO So, what is a Net Zero Energy building? A building achieves Net Zero Energy when it

More information

OSU Cascades Net Zero Campus. Recommendations

OSU Cascades Net Zero Campus. Recommendations OSU Cascades Net Zero Campus Recommendations February 20, 2017 Viable Net Zero Options Building Energy Efficiency Better 30% better than code Best 50% better than code Electrical energy Photovoltaic energy

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Ventilation and Cooling

Ventilation and Cooling Natural vs. mechanical Ventilation and Cooling Weighing the benefits and the drawbacks of each type of ventilation system helps the building occupants, owners, and the technicians integrating and monitoring

More information

Filtered fume hoods. Experts in air filtration for the protection of laboratory personnel since

Filtered fume hoods. Experts in air filtration for the protection of laboratory personnel since Experts in air filtration for the protection of laboratory personnel since 1968 A Global Solution For Green Buildings Filtered fume hoods www.erlab.com Not any more! FAQ Some of the most frequently asked

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Stuart S. Waterbury and Donald J. Frey, Architectural Energy Corporation Karl F. Johnson, Electric Power Research

More information

University of Illinois Business Instructional Facility LEED Gold Design. University of Illinois. University of Illinois

University of Illinois Business Instructional Facility LEED Gold Design. University of Illinois. University of Illinois Keys to success: Sustainable design strategies included early. Clear and early benchmarking choice. Integrated design process. Consensus building. Keys to success: Sustainable design strategies considered

More information

Lab Ventilation Safety & Energy Efficiency. Agenda & Objectives

Lab Ventilation Safety & Energy Efficiency. Agenda & Objectives Lab Ventilation Safety & Energy Efficiency Methods to Achieve Safe and Energy Efficient Laboratory Ventilation Systems Thomas C. Smith tcsmith@labhoodpro.com Agenda & Objectives Introduction Laboratory

More information

Overview of Dynamic Control of Lab ACH s

Overview of Dynamic Control of Lab ACH s A Comprehensive Review of the Indoor Environmental Quality and Energy Impacts of Dynamically Varying Air Change Rates at Multiple Laboratory Facilities Overview of Dynamic Control of Lab ACH s Background

More information

Fume Cupboard Management Policy

Fume Cupboard Management Policy Fume Cupboard Management Policy 1.0 Purpose & Scope This policy serves to provide procurement, installation, maintenance, and management guidance for ducted fume cupboards either maintained by KCL estates

More information

COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233

COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233 COMMUNITY COLLEGE OF ALLEGHENY COUNTY PURCHASING DEPARTMENT 800 ALLEGHENY AVENUE, PITTSBURGH, PA 15233 ADDENDUM NO. 1 BID PROPOSAL NO. 979 MODIFICATIONS TO CHEMISTRY LAB SOUTH CAMPUS JUNE 29, 2016 The

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

30% 85% 37% PROJECT HIGHLIGHTS LEED Facts. Lecture Hall BioLabs Building

30% 85% 37% PROJECT HIGHLIGHTS LEED Facts. Lecture Hall BioLabs Building LECTURE HALL BIOLOGICAL LABORATORIES BUILDING 16 Divinity Avenue, Cambridge, MA 02138 LEED-CI V3 GOLD The Biological Laboratories (BioLabs) Building Lecture Hall, located on the first floor of 16 Divinity

More information

Energy Research Facilities A Whole New Game!

Energy Research Facilities A Whole New Game! Energy Research Facilities A Whole New Game! Presented by: Advanced Energy 2010 Jerry Polly, PE, Principal Flad Architects Unique Characteristics of Energy Research Facilities SCIENCE External communications

More information

PRODUCTS. eos EOS PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION THE SMART DIFFUSER. Redefine your comfort zone.

PRODUCTS. eos EOS PRODUCT: ADVANCING THE SCIENCE OF AIR DISTRIBUTION THE SMART DIFFUSER. Redefine your comfort zone. A I R D I S T R I B U T I O N PRODUCTS PRODUCT: EOS eos THE SMART DIFFUSER F O C U S 01 ADVANCING THE SCIENCE OF AIR DISTRIBUTION Redefine your comfort zone. www.titus-hvac.com Rethink what air management

More information

Aircuity Installation

Aircuity Installation Aircuity Installation Project Team Project Services Allen Shiroma Asst. Director Renovations Matt Gudorf Campus Energy Manager Adam Feuerstein Project Manager EH&S Lisa Mahar - Senior Mgr, Occupational

More information

Applying Geothermal Technology for Large Scale Projects

Applying Geothermal Technology for Large Scale Projects Jeff Urlaub, PE MEP Associates, LLC jeffu@mepassociats.com 715.832.5680 Engineering Future Focused Solutions Applying Geothermal Technology for Large Scale Projects Breakout Session Category (e.g. Residential)

More information

Fume Cupboard Management Policy

Fume Cupboard Management Policy Fume Cupboard Management Policy 1.0 Purpose & Scope This policy serves to provide procurement, installation, maintenance, and management guidance for ducted fume cupboards either maintained by KCL estates

More information

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT Adam Renzi, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute

More information

SUSTAINABILITY FOR LABS

SUSTAINABILITY FOR LABS SUSTAINABILITY FOR LABS COLORADO STATE UNIVERSITY CHEMISTRY BUILDING ASHRAE 2017 TECHNICAL CONFERENCE April 28 th, 2017 PRESENTERS SEAN CONVERY, PE PRINCIPAL MECHANICAL ENGINEER ERIC RINGOLD BUILDING PERFORMANCE

More information

Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities

Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities October 4, 2007 Charleston, SC Designing for Actual Not Theoretical HVAC Requirements in Laboratory Facilities J. Patrick Carpenter, PE Principal V a n d e r w e i l E n g i n e e r s What Are Laboratory

More information

Demand-Controlled Ventilation: A Design Guide

Demand-Controlled Ventilation: A Design Guide Demand-Controlled Ventilation: A Design Guide June 2003 This guide is intended to assist those implementing demand-controlled ventilation (DCV) systems. It was written by Marty Stipe, P.E. with the Oregon

More information

Ensure Your Campus Labs are Safe LABS AND RESEARCH FACILITIES. Fume Hoods and Biological Safety Cabinets

Ensure Your Campus Labs are Safe LABS AND RESEARCH FACILITIES. Fume Hoods and Biological Safety Cabinets Photo courtesy Erlab LABS AND RESEARCH FACILITIES by Kelly Williams Ensure Your Campus Labs are Safe Headlines involving laboratory safety issues are not making the national news agencies, so the general

More information

LEED Best Practices Save $$$

LEED Best Practices Save $$$ 16 Savings result where LEED has been applied to improve IAQ! LEED Best Practices Save $$$ A growing body of green building case studies document the benefits of healthy IAQ in the workplace Learn More

More information

Science Education Facilities

Science Education Facilities Science Education Facilities Considerations for Safety Roger W. Ballard, Consulting Architect N.C. Dept. of Public Instruction School Planning Section NCDPI School Planning Section N.C. General Statute

More information

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report

Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Cornell University Chilled Water Best Management Practices Program 2015 Annual Report Prepared by: Cornell University Facilities Services Energy and Sustainability Utilities Report Date: 26 January 2016

More information

Maintaining quality and reducing energy in research animal facilities

Maintaining quality and reducing energy in research animal facilities August 2011 Animal Technology and Welfare Maintaining quality and reducing energy in research animal facilities STEVEN CUBITT 1 and GORDON SHARP 2 1 The Cube, St Johns Innovation Centre, Cambridge, Cambridgeshire

More information

23-28 = -5. Zero Net Energy Case Study WEST BERKELEY PUBLIC LIBRARY OVERVIEW. Planning & Design Approach. Measured Energy Stats

23-28 = -5. Zero Net Energy Case Study WEST BERKELEY PUBLIC LIBRARY OVERVIEW. Planning & Design Approach. Measured Energy Stats Zero Net Energy Case Study Photos Mark Luthringer Photography OVERVIEW Building Size: 9,400 SF Location: Berkeley, CA Construction Type: New Construction Completion Date: December 2013 Building Type: Public

More information

/ How to Select Your Next Workplace /

/ How to Select Your Next Workplace / / How to Select Your Next Workplace / / Introduction / The modern workplace is a strategic, competitive advantage. Now more than ever, the way we work contributes to the success of businesses and individuals.

More information

Therma-Fuser Energy Analysis Report 2016

Therma-Fuser Energy Analysis Report 2016 Therma-Fuser Energy Analysis Report 2016 Executive Summary This study compares the annual HVAC energy use of a Therma-Fuser VAV system to that of a conventional VAV box system. A typical 68,800 square

More information

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer NEWMOA June 30, 2009 Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer Utility Incentives MA, RI, NH, VT, ME, CT, Long Island NY, Gas in NYC New construction and gas in Upstate NY.

More information

Designed for Storage of Noxious and Odorous Evidence

Designed for Storage of Noxious and Odorous Evidence Designed for Storage of Noxious and Odorous Evidence Storage cabinets for storage of hazardous chemicals and other substances. Mini Safestore Provides Environmentally Safe Processing and Storage of Evidence

More information

Hotels: Water and Energy

Hotels: Water and Energy Hotels: Water and Energy Agenda 01 Introduction 05 Hotel System Options 02 Company Overview 06 Hotel Energy Conservation 03 Hotel Energy & Water Use 07 Hotel Project Examples 04 Design Philosophy Introduction

More information

TEXAS A&M ENGINEERING

TEXAS A&M ENGINEERING TEXAS A&M ENGINEERING 312 Jack K. Williams Administration Building I 3126 TAMU I College Station, Texas 77843-3126 M. Katherine Banks, Ph.D., P.E. Vice Chancellor and Dean of Engineering Director, Texas

More information

They are also responsible for 12% of water used and 36% of non-industrial waste generated.

They are also responsible for 12% of water used and 36% of non-industrial waste generated. Good Morning, everyone, and thank you, Jack. Thank you, Nora, for inviting me to the launch of your website. EPA Region 2 is delighted to have been able to support the work of the Newman Real Estate Institute

More information

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES ASHRAE TECHNOLOGY AWARD CASE STUDIES This article was published in ASHRAE Journal, June 2018. Copyright 2018 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information