1 CASCADING BENEFITS: OPTIMIZING DISINFECTION FOR CHEMICAL SAVINGS, CONTROL NITRIFICATION AND DISINFECTION BY-PRODUCTS. ABSTRACT Ignacio Cadena, P.E., Project Manager Freese and Nichols, Inc. Bobbie Kidd, General Manager, Greenbelt Municipal and Industrial Water Authority KEYWORDS Loss of Chlorine Residual, Nitrification, Disinfection By-Products, Disinfection Strategy, Chemical Optimization INTRODUCTION The Greenbelt Municipal and Industrial Water Authority (GMIWA) operate an 8.0 MGD conventional Water Treatment Plant and a 120 mile linear system that supplies water to five primary customers and 23 small systems across 5 counties in northwestern Texas. The GMIWA operated a free chlorine system until high occurrences of disinfection by-products (DBP s) force them to evaluate disinfection alternatives. TCEQ approved the Greenbelt Municipal and Industrial Water Authority s (GMIWA) request to use chloramines as a disinfectant on November 3, 2003 to reduce formation of DBPs in the distribution system. The three year case study analyzed the loss of chlorine residual and nitrification in the distribution system; unusual DPS s issues; and evaluated the disinfection strategy at the Water Treatment Plant (WTP) to optimize the use of chemicals. LOSS OF CHLORINE RESIDUAL/ NITRIFICATION After two years of trouble free operation, during the fall of 2005 the GMIWA experienced difficulties maintaining chloramine residual at the end of the system. The total chlorine (chloramine) residual concentration recorded at the farthest point in the system at the time was 0.7 mg/l, with reports by the City of Crowell (farthest customer) of even lower concentrations in their distribution system. The loss of chlorine residual was attributed to a possible growth of nitrifying bacteria in the system. Additional sampling was conducted for HPC (heterotrophic plate count), free and total chlorine, free ammonia, nitrite and nitrate at the following sites: Childress (Site 3), Quanah (Site 4), Medicine Mound (Site 5), and Crowell (Site 6). The results showed an increase in the HPC, nitrates and nitrites in the last segment of the system from Site 5 to Site 6. Figure 1 shows a map of the Water system and the Site Locations. The Authority was advised that one effective means of controlling bacterial growth in the system was to periodically shock it by temporarily reverting from chloramines to a free chlorine residual. The Authority shut off the ammonia feed at the WTP on November 18, 2005 and reverted to free chlorine residual for approximately 6 weeks (until January 2, 2006). No taste and odor complaints were received during this period. The response after shocking the distribution system was sustained chlorine residual throughout the system. An annual free chlorine shock has been recommended as a result of the study to keep nitrifying bacteria from growing in the distribution system.

2 DISINFECTION BY-PRODUCTS - THM VIOLATIONS TCEQ performed the fourth quarter DBP sampling the first week in December At the time of the sampling, the Authority was implementing the action plan to address the nitrification outbreak and all GMIWA customers were receiving water with free chlorine. As a result of the action plan, the Authority s customers experienced unusually high TTHM s in the samples collected for this period. As a result, the Running Annual Average (RAA) was skewed to exceed the Total Trihalomethane (TTHM) limit of 80 ug/l for the next four quarters. This resulted in GMIWA wholesale customers having to notify their customers in writing of the water quality violations and provide a copy to TCEQ. The mandatory public notification was done on a quarterly basis for the duration of the violations. Recent records show that THMs were exceeding the MCL of mg/l on multiple occasions between 2005 and However, efforts from the Authority have shown dramatic improvement in the THM and HAA s samples collected since the fourth quarter of 2007, with levels below the MCL for all customers. Table 1 shows the TTHM concentrations for the GMIWA customers from the 1 st quarter of 2006 to the fourth quarter of Table 1. TTHM Quarterly Concentrations for the GMIWA Customer Cities. GMIWA WTP TTHM City of Clarendon TTHM City of Hedley TTHM 1st Quarter 06 1st Quarter st Quarter 06 2nd Quarter 06 2nd Quarter nd Quarter 06 3rd Quarter rd Quarter rd Quarter th Quarter th Quarter th Quarter st Quarter st Quarter st Quarter nd Quarter nd Quarter nd Quarter rd Quarter rd Quarter rd Quarter th Quarter th Quarter th Quarter st Quarter st Quarter st Quarter nd Quarter nd Quarter nd Quarter rd Quarter rd Quarter rd Quarter th Quarter th Quarter th Quarter City of Childress TTHM City of Quanah TTHM City of Crowell TTHM 1st Quarter st Quarter st Quarter nd Quarter nd Quarter nd Quarter rd Quarter rd Quarter rd Quarter th Quarter th Quarter th Quarter st Quarter st Quarter st Quarter nd Quarter nd Quarter nd Quarter rd Quarter rd Quarter rd Quarter th Quarter 07 NA 4th Quarter th Quarter st Quarter st Quarter st Quarter nd Quarter nd Quarter nd Quarter rd Quarter rd Quarter rd Quarter th Quarter th Quarter th Quarter

3 CHEMMICAL OPTIMIZATION The Greenbelt Water Authority disinfection strategy relies on free chlorine through the first two disinfection zones D1 and D2 (flocculators and clarifiers) and uses chloramines in disinfection zones D3 and D4 (filters and clearwell). The disinfection strategy was modeled to optimize the disinfectant residual needed to meet CT requirements. The model analyzed the optimum use of free chlorine and chloramines to meet a conservative inactivation ratio of 2. TCEQ s minimum inactivation ratio criteria is 1. Figure 2. Disinfection Strategy Schematic Rapid Mix + Flocculators Clarifiers D1 D2 Filters D3 Clearwell D4 Flocculator No. 1 Clarifier Cl 2 No. 1 Cl 2 NH 3 Cl Filter No. 1 2 RM Filter No. 2 Filter No. 3 Clearwell Flocculator No. 2 Clarifier No. 2 Filter No. 4 D1, D2, D3 & D4: Disinfection Zones Excess Ammonia Feed / Nitrification During the summer of 2006, the Greenbelt Water Authority continued to experience difficulties maintaining chloramine residual at Quanah (Site 4), Medicine Mound (Site 5) and Crowell (Site 6). The cause of the nitrifying bacteria growth coupled with chlorine residual loss was assessed, including an ammonia feed rate evaluation. Sampling similar to that done in the fall of 2005 was conducted again. The results showed a decrease of the total ammonia concentration from Site 2 to Site 3 and a total depletion of ammonia from Site 3 to Site 4. The results also showed a rapid increase in the nitrite/ nitrate concentration at Site 3, and a rapid increase in the HPC count from Site 3 to Site 4. An assessment of the chlorine and ammonia feed rate at the Water Treatment Plant (WTP) showed that between 60% and 80% of the chlorine fed at the rapid mix was depleted by the time the ammonia was fed following sedimentation. At the time, the chlorine:ammonia feed ratio was calculated based on the total pounds of chlorine and ammonia fed, a common practice. While the calculated (applied) ratio was targeted at 4.5:1, the actual ratio at the point of ammonia addition was approximately 2:1, resulting in a large excess of ammonia. An analysis of the operation from August 14, 2006 showed that the WTP flow was MGD, the chlorine feed was a total of 262 lbs of Cl 2 and the Ammonia feed was a total of 55 lbs of NH 3 -N. From the MOR, the free chlorine residual reading at the second stage (D2) for that same day was 1.5 mg /L or a total of 59.9 lbs Cl 2 /day. The free chlorine concentration is the amount that will react with ammonia to form chloramines. The total chlorine concentration leaving the plant (D4) is 2.0 mg/l, meaning the chlorine: ammonia ratio is approximately 1.45:1 or lbs Cl 2 : 55lbs NH 3 -N. An example of the ammonia feed rate calculation for a flow of MGD is as follows: ( D2 free Cl 2 Residual + 2 nd Stage Cl 2 Dose) X 0.25 = NH 3 -N dose 1.5 mg/l 0.5 mg/l X 0.25 = 0.50 mg NH 3 -N/L lbs Cl 2 /day lbs Cl 2 /day X 0.25 = lbs. NH 3 -N/day

4 It was recommended adjusting the ammonia feed rate to meet a 4.5:1 chlorine:ammonia ratio leaving the plant calculating the ration based on chlorine residual through the treatment process. It was also recommended sampling the parameters stated above at the same locations one week after the ammonia feed rate modification were made and one month after the changes. This will help us monitor the effect of the ammonia feed rate reduction with the growth of nitrifying bacteria in the distribution system. The adjustment to the ammonia feed rate reflect an approximate 50% reduction to accomplish a 4.5:1 chlorine:ammonia ratio based on the available chlorine left after the first disinfection zone. The ammonia feed rate reduction has helped the Authority prevent the growth of nitrifying bacteria in the distribution system to date. Approximately 800 lbs of ammonia are saved on average per month or $550 per month in cost savings. Disinfection Strategy Evaluation Plant records were reviewed to determine conditions likely responsible for the formation of excessive THMs. Although the disinfection strategy in place is appropriate, free chlorine residuals observed in zones D1 and D2 are significantly higher than required, and may be reduced to control THM formation without jeopardizing the disinfection performance. The existing disinfection strategy was modeled to optimize the disinfectant residual needed to meet CT requirements. The model analyzed the optimum use of free chlorine at disinfection zones D1/ D2, and chloramines at disinfection zones D3 and D4 to meet TCEQ s disinfection criteria. The plant parameters used for this evaluation are conservative values that will provide a significant safety factor for the resulting recommendations. Two temperatures were used to model summer and winter conditions. Summer conditions were modeled using a temperature of 20 ºC. For the winter conditions, a temperature of 5 ºC was used to model the effect of temperature in the inactivation ratio. The average flow used for this evaluation was 8 MGD with a ph of 8. A review of the monthly operating reports (MOR) from January 2004 through September 2007 showed an average flow of 3.2 MGD and an average temperature of 18.7 ºC during this three year period. The purpose of this analysis is to determine the preferred free chlorine residual concentration entering disinfection zone D3 (filter influent) given the Authority s desire to maintain 2.5 mg/l chloramine residual leaving the plant (D4). The results from the disinfection strategy analysis are shown on Table 1. Operating experience has indicated this 2.5 mg/l chloramine residual at disinfection zone D4 may not always satisfy TCEQ s minimum chlorine residual concentration criteria throughout the system without additional chemical boosting. The minimum disinfection inactivation ratio used in this evaluation was 2. TCEQ s criteria for minimum inactivation ratio is 1. In order for the Greenbelt Water Authority to meet the Stage 1 D/DBPR and TCEQ s disinfection criteria, the Authority will have to adjust the free chlorine feed rate to control the chlorine residual at disinfection zones D1/ D2. The target residual will require adjustment at least twice a year to accommodate flow and temperature seasonal variations.

5 Table 1. Disinfectant Optimization Table. DISINFECTION PROCESS DATA C Flow Temp Giardia Virus Inact. Date Disinfectant (mg/l) (MGD) ( o C) ph Log Log Ratio Time= FCL D FCL D2A FCL D2B CLA D (G) CLA D FCL D FCL D2A FCL D2B CLA D (V) CLA D FCL D FCL D2A FCL D2B CLA D (G) CLA D Winter Time Recommended Strategy 4 FCL D FCL D2A FCL D2B CLA D (G) CLA D Summer Time Recommended Strategy 5 FCL D FCL D2A FCL D2B CLA D (G) CLA D

6 FINDINGS / RECOMMENDATIONS The recommendation was to continue with the same disinfection strategy. This strategy feeds free chlorine through disinfection zones D1/ D2 and chloramines through disinfection zone D3 and D4. It was recommended to adjust the free chlorine dose at the raw water meter vault (D1) feed point twice a year to accommodate the flow and temperature seasonal variations. A chart was developed (see Figure 3) to help the Greenbelt Water Authority determine the target chlorine residual concentration through disinfection zones D1/ D2 depending on the flow and the temperature in degrees Celsius (ºC). The plant flow range used to develop this chart is from 2 MGD to 8 MGD in 2 MGD increments. The temperature range used to develop this chart is from 6 ºC to 20 ºC in 2 ºC increments. How to use the Chlorine Residual Concentration Chart: Example: Daily average flow 5.0 MGD Water temperature at the Clearwell 15 ºC Approximate target free chlorine residual conc mg/l * Figure 3. Chlorine Residual Concentration Chart Example. Disinfection Zone D1/ D2 Free Chlorine Residual Concentration Chart Temperature Analysis at a Fixed Inactivation Ratio of 2 Water Flow Analysis at 2 MGD,4MGD, 6 MGD and 8 MGD 0.80 Free Chlorine Residual Concentration (mg/l) mg/l 4 MGD 2 MGD 6 MGD 8 MGD 5.0 MGD ºC Temperature in C * The values from this Chart are conditioned to a 2.5 mg/l chlorine residual (chloramines) concentration through disinfection zones D3 and D4. In order for the GMIWA to meet the Stage 1 D/DBPR and TCEQ s disinfection criteria, the Authority adjusted the free chlorine feed rate to sustain a lower free chlorine residual concentration (between 0.3 to 0.6 mg/l) entering disinfection zone D2 (clarifiers). This adjustment not only provided a reduction in the formation of DBPs through the treatment process, but also a significant chemical savings. The optimization of the chemical disinfection strategy is saving the GMIWA approximately $20,000 per year in chlorine and ammonia chemicals since the changes were implemented (approximately a 50% reduction). Approximately 40,000 lbs of chlorine and 5,500 pounds of ammonia were saved in 2008.

7 Disinfection Zone D1/ D2 Free Chlorine Residual Concentration Chart Temperature Analysis at a Fixed Inactivation Ratio of 2 Water Flow Analysis at 2 MGD,4MGD, 6 MGD and 8 MGD 0.80 Free Chlorine Residual Concentration (mg/l) Dis Zone 2 Cl2 Residual Conc at 2 MGD Dis Zone 2 Cl2 Residual Conc at 4 MGD 6 MGD 4 MGD 2 MGD Dis Zone 2 Cl2 Residual Conc at 6 MGD Dis Zone 2 Cl2 Residual Conc at 8 MGD 8 MGD Temperature in C * The values from this Chart are conditioned to a 2.5 mg/l chlorine residual (chloramines) concentration through disinfection zones D3 and D4.

Granular Activated Carbon System

Granular Activated Carbon System Granular Activated Carbon System Eliminating Use of Chloramines March 22, 2017 www.jacobs.com worldwide The Jacobs Team Mike McCarty, PE Project Manager Tobin Lichti, PE Water Treatment Engineer Russ Dahmer,

More information

LT1ESWTR Disinfection Profiling and Benchmarking

LT1ESWTR Disinfection Profiling and Benchmarking LT1ESWTR Disinfection Profiling and Benchmarking Technical Guidance Manual Log Inactivation 1.400 1.200 1.000 0.800 0.600 0.400 0.200 0.000 Log Inactivation 0 4 8 12 16 20 24 28 32 36 40 44 48 52 Week

More information

Side by Side Piloting of Process Alternatives Yields Direct Performance Comparison

Side by Side Piloting of Process Alternatives Yields Direct Performance Comparison OBG PRESENTS: OBG PRESENTS: Side by Side Piloting of Process Alternatives Yields Direct Performance Comparison LORI W. REID, P.E. New York State AWWA Spring Meeting, April 26, 2017 Outline Background Project

More information

Reducing THM via Aeration: A Case Study August 28, 2014

Reducing THM via Aeration: A Case Study August 28, 2014 1 Reducing THM via Aeration: A Case Study August 28, 2014 by Gary Williams, P.E. Jones & Henry Engineers WEA-AWWA 2014 Technical Conference & Expo Agenda 2 Location History Pilot Implementation Take Away

More information

Development of an Algorithm for Dosing PAC to Remove NOM and Control DBP Formation

Development of an Algorithm for Dosing PAC to Remove NOM and Control DBP Formation Development of an Algorithm for Dosing PAC to Remove NOM and Control DBP Formation Adam Eyring, Linda Kramer, Kate Guest Philadelphia Water Department PA-AWWA Annual Conference 2014 Bethlehem, PA Topics

More information

ACHIEVING STAGE 2 DBPR COMPLIANCE THROUGH SYSTEM OPTIMIZATION AND EFFICIENT USE OF POST-FILTRATION GAC: A 5 YEAR CASE STUDY

ACHIEVING STAGE 2 DBPR COMPLIANCE THROUGH SYSTEM OPTIMIZATION AND EFFICIENT USE OF POST-FILTRATION GAC: A 5 YEAR CASE STUDY ACHIEVING STAGE 2 DBPR COMPLIANCE THROUGH SYSTEM OPTIMIZATION AND EFFICIENT USE OF POST-FILTRATION GAC: A 5 YEAR CASE STUDY AMANDA WILLIAMS (CO-WRITER: PETER THOMPSON JR.) WATER QUALITY SUPERVISOR PALMDALE

More information

MONITORING PLAN FOR THE DISINFECTANTS/DISINFECTION BYPRODUCTS RULES

MONITORING PLAN FOR THE DISINFECTANTS/DISINFECTION BYPRODUCTS RULES MONITORING PLAN FOR THE DISINFECTANTS/DISINFECTION BYPRODUCTS RULES COMMONWEALTH OF PENNSYLVANIA DEPARTMENT OF ENVIRONMENTAL PROTECTION BUREAU OF SAFE DRINKING WATER PART 1: GENERAL SYSTEM INFORMATION

More information

Module 20: Trickling Filters Answer Key

Module 20: Trickling Filters Answer Key Module 20: Trickling Filters Answer Key Calculation Capital City WWTF, which processes 2.0 MGD, is required to nitrify to meet the 2.0 mg/l ammonia discharge limit stated in their NPDES permit. A table

More information

Example Plan Small PWS

Example Plan Small PWS PA Department of Environmental Protection Bureau of Water Supply and Wastewater Management Disinfectants and Disinfection Byproducts Rule (DBPR) Monitoring Plan Template Example Plan Small PWS Monitoring

More information

Pittsburgh Water Treatment Plant Projects. by Jay R. Lucas, P.E. Senior Project Manager

Pittsburgh Water Treatment Plant Projects. by Jay R. Lucas, P.E. Senior Project Manager Pittsburgh Water Treatment Plant Projects by Jay R. Lucas, P.E. Senior Project Manager Who Is American Water We are the largest publicly traded water and wastewater utility in the United States Broad national

More information

Integrating Ozone and Ion Exchange into a 40 Year Old Lime Softening Plant

Integrating Ozone and Ion Exchange into a 40 Year Old Lime Softening Plant Integrating Ozone and Ion Exchange into a 40 Year Old Lime Softening Plant City of Columbus Division of Water: Matt Steele CH2M HILL: Enoch Nicholson DRWP Source Water and Treatment DRWP Overview Current

More information

Triplepoint Environmental

Triplepoint Environmental Agenda 1. Brief Introduction 2. Overview of the Lagoon Ammonia Problem Causes and Effects of Ammonia Pollution Basics of Ammonia Removal 3. Review Conventional Wisdom 4. Compare Ammonal Treatment Options

More information

Treatment techniques for control of disinfection byproduct (DBP) precursors.

Treatment techniques for control of disinfection byproduct (DBP) precursors. 3745-81-77 Treatment techniques for control of disinfection byproduct (DBP) precursors. (A) (B) Surface water community and nontransient noncommunity public water systems using conventional filtration

More information

Drinking Water Treatment Optimization Tools

Drinking Water Treatment Optimization Tools Drinking Water Treatment Optimization Tools Introduction Treating water to meet today s potable drinking water regulations requires a delicate balance between seemingly conflicting or competing regulations,

More information

Performance of GAC Filter-Adsorbers for Herbicide and DBP Control at Higginsville,, MO

Performance of GAC Filter-Adsorbers for Herbicide and DBP Control at Higginsville,, MO Performance of GAC Filter-Adsorbers for Herbicide and DBP Control at Higginsville,, MO Robert L. Segar Jr., Ph.D., P.E. Department of Civil and Environmental Engineering University of Missouri-Columbia

More information

REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS

REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS REAL WORLD APPLICATIONS OF USING DYNAMIC SIMULATION SOFTWARE TO OPTIMIZE WATER TREATMENT PLANT PROCESS OPERATIONS (FRIT05) OCTOBER 30, 2015 Authors: Matt Ridens/CH2M, Jason Curl/CH2M Overview Drivers for

More information

Nitrification Action Plans (NAPs)

Nitrification Action Plans (NAPs) Directed Assistance Module (DAM) 8: Nitrification Action Plans (NAPs) Developed by the TCEQ Water Supply Division (WSD) Texas Optimization Program (TOP) Presented by the WSD Financial, Managerial, and

More information

A Method to Determine Biodegradable Dissolved Organic Nitrogen in Water ND 58108, USA

A Method to Determine Biodegradable Dissolved Organic Nitrogen in Water ND 58108, USA A Method to Determine Biodegradable Dissolved Organic Nitrogen in Water Tanush Wadhawan a, Halis Simsek a, Murthy Kasi a, Kristofer Knutson b, John McEvoy c, Birgit Pruess c and Eakalak Khan a* a Department

More information

THMs Control in Wastewater Treatment Plant Effluent Jurek Patoczka 1, Peter Tyrrell 2 and Michael Wynne 2

THMs Control in Wastewater Treatment Plant Effluent Jurek Patoczka 1, Peter Tyrrell 2 and Michael Wynne 2 THMs Control in Wastewater Treatment Plant Effluent Jurek Patoczka 1, Peter Tyrrell 2 and Michael Wynne 2 1 Hatch Mott MacDonald, 27 Bleeker St., Millburn, NJ 07041, jurek.patoczka@hatchmott.com 2 Hanover

More information

Water Quality Changes in the Distribution System. Module 6

Water Quality Changes in the Distribution System. Module 6 Water Quality Changes in the Distribution System Module 6 Learning Objectives Be able to describe what different water quality parameters tell us about distribution system health Be able to describe and

More information

Control of Trihalomethanes (THM s) In Wastewater. Philip S. Bober, Operations Superintendent, Wayne Township

Control of Trihalomethanes (THM s) In Wastewater. Philip S. Bober, Operations Superintendent, Wayne Township Control of Trihalomethanes (THM s) In Wastewater By Philip S. Bober, Operations Superintendent, Wayne Township A viable solution exists for wastewater treatment plants using sodium hypochlorite to decrease

More information

City of Paso Robles Uses Online Monitor to Detect Low-Level of THMs in Treated Wastewater

City of Paso Robles Uses Online Monitor to Detect Low-Level of THMs in Treated Wastewater City of Paso Robles Uses Online Monitor to Detect Low-Level of THMs in Treated Wastewater The City of Paso Robles, California used an online water quality instrument to characterize and monitor low-levels

More information

Lignite versus. bituminous GAC for biofiltration a case study

Lignite versus. bituminous GAC for biofiltration a case study The city of Wilmington, N.C., initiated a study to compare lignite granular activated carbon (GAC) to bituminous GAC for biofiltration at the city s surface water treatment plant. The plant uses conventional

More information

Chlorate Working Group

Chlorate Working Group Chlorate Working Group Drinking Water Treatment V0 1 May 2016 Why Our journey Jan 2015: 23,000 people on a BWN 121 WSZs on RAL The Challenge 49% UFW Over 33% of our WTPs do not have 15% headroom What brought

More information

2012 Water Research Foundation. ALL RIGHTS RESERVED.

2012 Water Research Foundation. ALL RIGHTS RESERVED. 2012 Water Research Foundation. ALL RIGHTS RESERVED. 2012 Water Research Foundation. ALL RIGHTS RESERVED. No part of this presentation may be copied, reproduced, or otherwise utilized without permission.

More information

Innovative Approach to Expanding the Olentangy WTP

Innovative Approach to Expanding the Olentangy WTP Innovative Approach to Expanding the Olentangy WTP September 28, 2017 Spencer Sheldon, WTP Superintendent Bret M. Casey, P.E., BCEE Who is Del-Co Water? Member owned 501-(c) Non-Profit Corporation Governed

More information

ONLINE MONITORING PRACTICES FOR MANGANESE CONTROL IN DRINKING WATER TREATMENT

ONLINE MONITORING PRACTICES FOR MANGANESE CONTROL IN DRINKING WATER TREATMENT ONLINE MONITORING PRACTICES FOR MANGANESE CONTROL IN DRINKING WATER TREATMENT Vadim B. Malkov, Hach Company Water Systems Optimization, 10/30/2015 INTRODUCTION Manganese in US source water why is it a

More information

Matt Leach, P.E. CH2M. Mark Eppich, P.E. City of Columbus Division of Water. S. Dean Ramsey, P.E. CH2M

Matt Leach, P.E. CH2M. Mark Eppich, P.E. City of Columbus Division of Water. S. Dean Ramsey, P.E. CH2M Matt Leach, P.E. CH2M Mark Eppich, P.E. City of Columbus Division of Water S. Dean Ramsey, P.E. CH2M 1 Presentation Topics Project Background Project Team Unique Challenges and Opportunities Risk Assessment

More information

DISTRIBUTION SYSTEM OPTIMIZATION THE PARTNERHSIP FOR SAFE WATER APPROACH

DISTRIBUTION SYSTEM OPTIMIZATION THE PARTNERHSIP FOR SAFE WATER APPROACH No part of this presentation may be copied, reproduced, or otherwise utilized without permission. DISTRIBUTION SYSTEM OPTIMIZATION THE PARTNERHSIP FOR SAFE WATER APPROACH Southwest Section AWWA Annual

More information

Partnership for Safe Water Distribution System Optimization Program. Barbara Martin, AWWA

Partnership for Safe Water Distribution System Optimization Program. Barbara Martin, AWWA Partnership for Safe Water Distribution System Optimization Program Barbara Martin, AWWA Why Optimize? Assessment benefits: System-specific learning opportunity Prepare for future regulations Water quality

More information

CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2012

CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2012 CITY OF OXFORD WASTEWATER TREATMENT FACILITY ANNUAL PERFORMANCE REPORT FOR THE CALENDAR YEAR OF 2012 PREPARED: January 2013 2012 ANNUAL PERFORMANCE REPORT FOR THE CITY OF OXFORD WASTEWATER TREATMENT FICILITY

More information

NPDES COMPLIANCE OF COOLING TOWERS BLOWDOWN AT POWER PLANTS WITH RECLAIMED WATER AS SOURCE WATER

NPDES COMPLIANCE OF COOLING TOWERS BLOWDOWN AT POWER PLANTS WITH RECLAIMED WATER AS SOURCE WATER NPDES COMPLIANCE OF COOLING TOWERS BLOWDOWN AT POWER PLANTS WITH RECLAIMED WATER AS SOURCE WATER Nathan Schmaus, P.E. *, Joseph Viciere, P.E., BCEE, CDM Smith CDM Smith, 1715 North Westshore Boulevard,

More information

Chlorine Residual Boosting

Chlorine Residual Boosting Chlorine Residual Boosting in Distribution Water There is no shortage to the available information in regard to disinfection methods from principle to application. Two common disinfection methods are to

More information

Online THM Analyzer Integral to City of Benicia s Stage 2 DBPR Compliance Strategy

Online THM Analyzer Integral to City of Benicia s Stage 2 DBPR Compliance Strategy Online THM Analyzer Integral to City of Benicia s Stage 2 DBPR Compliance Strategy Author: Scott Rovanpera, Superintendent, City of Benicia Water Treatment Plant, srovanpera@ci.benicia.ca.us or Tel: +1

More information

ATTACHMENT A TO THE AGREEMENT FOR ENGINEERING SERVICES. Project: Chloramine Replacement Alternative Evaluation

ATTACHMENT A TO THE AGREEMENT FOR ENGINEERING SERVICES. Project: Chloramine Replacement Alternative Evaluation ATTACHMENT A TO THE AGREEMENT FOR ENGINEERING SERVICES Owner: Board of Public Works, City of Hannibal, Missouri Project: Chloramine Replacement Alternative Evaluation DESCRIPTION OF SCOPE OF SERVICES On

More information

Water Quality Permitting Program Monitoring Matrix 1,2,3

Water Quality Permitting Program Monitoring Matrix 1,2,3 State of Oregon Department of Environmental Quality Water Quality Permitting Program Monitoring Matrix 1,2,3 ITEM OR PARAMETER Total Flow (influent and/or effluent) 4 Flow Meter Calibration 5 (influent

More information

NOVEL APPROACHES TO TRIHALOMETHANE MANAGEMENT. Dr Rino Trolio. Water Corporation (WA)

NOVEL APPROACHES TO TRIHALOMETHANE MANAGEMENT. Dr Rino Trolio. Water Corporation (WA) NOVEL APPROACHES TO TRIHALOMETHANE MANAGEMENT Paper Presented by : Dr Rino Trolio Authors: Rino Trolio, Manager Operations Suppor, Richard Walker, Manager Drinking Water Quality, Sharon McNeil, Chemistry

More information

Proposed Revised Total Coliform Rule (RTCR)

Proposed Revised Total Coliform Rule (RTCR) Proposed Revised Total Coliform Rule (RTCR) Technical Advisory Committee for Small Water Systems Meeting June 18, 2014 1 Meeting Objectives Review key provisions of the pre-proposed Revised Total Coliform

More information

Breakpoint. Do you Really Have a Free Chlorine Residual? Chloramination. Bob Spon, chemist Spon Water Consulting. Nitrification

Breakpoint. Do you Really Have a Free Chlorine Residual? Chloramination. Bob Spon, chemist Spon Water Consulting. Nitrification Breakpoint Chlorination Do you Really Have a Free Chlorine Residual? Chloramination Nitrification Disinfection Byproducts Bob Spon, chemist Spon Water Consulting 1 Water Quality Problems in Distribution

More information

Nature. Technology. Innovation. PAX Water Mixers.

Nature. Technology. Innovation. PAX Water Mixers. Nature. Technology. Innovation. PAX Water Mixers www.paxwater.com Innovative Water Quality Solutions Inspired by Nature PAX Water Technologies is the leading manufacturer of technologies that improve water

More information

Pilot Testing El Paso s Advanced Water Purification Facility

Pilot Testing El Paso s Advanced Water Purification Facility Pilot Testing El Paso s Advanced Water Purification Facility Caroline Russell, Dan Olson, Sanaan Villalobos, Gilbert Trejo Imagine the result July 17, 2015 Acknowledgements El Paso Water Utilities: John

More information

American Water College 2010

American Water College 2010 Vocabulary Trickling Filters Biomass A mass or clump of organic material consisting of living organisms feeding on the wastes in wastewater, dead organisms and other debris. Colloids Very small, finely

More information

Choices to Address Filamentous Growth

Choices to Address Filamentous Growth Michigan Water Environment Association Process Seminar November 12, 2015 Choices to Address Filamentous Growth Richard Beardslee City of Battle Creek Nathan Cassity Donohue & Associates Outline Battle

More information

Analysis of Residential Subsurface. SF constructed wetlands. Performance in Northern Alabama

Analysis of Residential Subsurface. SF constructed wetlands. Performance in Northern Alabama Analysis of Residential Subsurface Flow Constructed Wetlands Performance in Northern Alabama CONTRIBUTING WRITER Kathleen M. Leonard Ph.D., P.E. ABSTRACT Constructed wetlands are becoming increasingly

More information

Improved Membrane Design Addresses Integrity Issues for the City of Yuba City Water Treatment Plant

Improved Membrane Design Addresses Integrity Issues for the City of Yuba City Water Treatment Plant Improved Membrane Design Addresses Integrity Issues for the City of Yuba City Water Treatment Plant Richard Stratton, PE HDR Engineering Acknowledgements City of Yuba City - John Westhouse, Plant Supervisor

More information

WEFTEC.06. **Cobb County Water System, Marietta, Georgia

WEFTEC.06. **Cobb County Water System, Marietta, Georgia CHEMICALLY ENHANCED PRIMARY TREATMENT FOR A LARGE WATER RECLAMATION FACILITY ON A CONSTRICTED SITE - CONSIDERATIONS FOR DESIGN, START-UP, AND OPERATION ABSTRACT Jeffrey A. Mills, P.E., BCEE,* Roderick

More information

Should we use a residual in our drinking water distribution systems?

Should we use a residual in our drinking water distribution systems? Should we use a residual in our drinking water distribution systems? R. Rhodes Trussell Trussell Technologies, Inc. Pasadena, CA Vernon L Snoeyink Lecture University of Illinois 10 March 2005 How did the

More information

Removal of High Ammonia Levels from Municipal Wastewater Using Humic Acid and Selective Bio-Augmentation

Removal of High Ammonia Levels from Municipal Wastewater Using Humic Acid and Selective Bio-Augmentation Removal of High Ammonia Levels from Municipal Wastewater Using Humic Acid and Selective Bio-Augmentation Prepared by: Brent W. Cowan, P.E. Coatesville, PA 19320 Steven M. Cawley Cawley Environmental Services,

More information

Nutrients and Water Quality A Region 8 Collaborative Workshop February 15-17, 2011 By Bob Clement, Environmental Engineer M.S.

Nutrients and Water Quality A Region 8 Collaborative Workshop February 15-17, 2011 By Bob Clement, Environmental Engineer M.S. Nutrients and Water Quality A Region 8 Collaborative Workshop February 15-17, 2011 By Bob Clement, Environmental Engineer M.S./Microbiologist Goals: Nutrients have a huge impact on drinking water treatment

More information

FORT JACKSON WATER SYSTEM 2014 WATER QUALITY REPORT. Delivering Excellence, One Drop at a Time. PSUS s Water Philosophy

FORT JACKSON WATER SYSTEM 2014 WATER QUALITY REPORT. Delivering Excellence, One Drop at a Time. PSUS s Water Philosophy PSUS s Water Philosophy Protect Palmetto State Utility Services, Inc. (PSUS) understands that protecting your water supply is of the utmost importance. The source of your water supply is monitored on a

More information

Treatment Processes for Potable Water

Treatment Processes for Potable Water Treatment Processes for Potable Water Drinking Water Potable water is water that is free of harmful chemicals, microorganisms, and other contaminants and is safe to drink Drinking water also should be

More information

Annual Drinking Water Quality Report for 2013 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY )

Annual Drinking Water Quality Report for 2013 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY ) INTRODUCTION Annual Drinking Water Quality Report for 2013 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY3100567) To comply with State regulations, the Niagara

More information

Water Treatment Overview. Gabe Sasser December 2016

Water Treatment Overview. Gabe Sasser December 2016 Water Treatment Overview Gabe Sasser December 2016 Topics of Discussion Source Water Information Treatment Plants (History and Capacity) Water Quality Water Treatment Process Distribution System Conservation

More information

Localized Treatment for DBP s using Spray Aeration and Online Monitoring

Localized Treatment for DBP s using Spray Aeration and Online Monitoring Localized Treatment for DBP s using Spray Aeration and Online Monitoring Tom Williams +1 408 476 7768 twilliams@aquametrologysystems.com Tom.Williams@enebio.com Who are we? Worked in DBP s since 2008 AMS

More information

Chloramine Optimization through Proper Mixing and a Unique Chloramine Management System. John Kiernan

Chloramine Optimization through Proper Mixing and a Unique Chloramine Management System. John Kiernan Chloramine Optimization through Proper Mixing and a Unique Chloramine Management System John Kiernan EPA has set a compliance date of April 1, 2016 but some states are accelerating their compliance To

More information

Introduction and Water Resources Source Water Assessment Additional Health Information

Introduction and Water Resources Source Water Assessment Additional Health Information Introduction and Water Resources As required by the US Environmental Protection Agency (EPA), the City of Naples Utilities Department is providing this annual report on the quality of its drinking water

More information

THM Removal by Water Spray Aeration- Tank Top Results. Thomas F. Clark, P.E. Production Engineer Monroe County Water Authority Rochester, New York

THM Removal by Water Spray Aeration- Tank Top Results. Thomas F. Clark, P.E. Production Engineer Monroe County Water Authority Rochester, New York THM Removal by Water Spray Aeration- Tank Top Results Thomas F. Clark, P.E. Production Engineer Monroe County Water Authority Rochester, New York Monroe County s Primary Water Supply Lake Ontario Treatment

More information

2017 Water Quality Report

2017 Water Quality Report 2017 Water Quality Report We are pleased to present to you the water quality / consumer confidence report for the 2016 calendar year. Castle Rock Water is committed to providing you with a safe and reliable

More information

The Aquaponics Calculator

The Aquaponics Calculator The Aquaponics Calculator This tool is designed to enable the operators of an aquaponics system a virtual view of the operating environment of their system. Following input of the users values the AC will

More information

Risk Assessment of Total Coliform in X WTP s Water Production Using Failure Mode And Effect Analysis Method

Risk Assessment of Total Coliform in X WTP s Water Production Using Failure Mode And Effect Analysis Method 183 Simposium I Jaringan Perguruan Tinggi untuk Pembangunan Infrastruktur Indonesia, 2016 Risk Assessment of Total Coliform in X WTP s Water Production Using Failure Mode And Effect Analysis Method Bella

More information

Annual Drinking Water Quality Report. Sources of Drinking Water

Annual Drinking Water Quality Report. Sources of Drinking Water ThedkdkdkdkdkThe Annual Drinking Water Quality Report TX2270207 TRAVIS COUNTY WCID 19 Annual Water Quality Report for the period of January 1 to December 31, 2016. For more information regarding this report

More information

VILLAGE OF NORTH BALTIMORE WTP CLEARWELL THM REMOVAL SYSTEM

VILLAGE OF NORTH BALTIMORE WTP CLEARWELL THM REMOVAL SYSTEM VILLAGE OF NORTH BALTIMORE WTP CLEARWELL THM REMOVAL SYSTEM Two 15 HP Spray Units Operational Spray Unit Two 2 HP Ventilation Fans SAMPLE DATE WATER TEMP (degc) WTP Production (MG) Village of North Baltimore

More information

Drinking-Water Systems Regulation O. Reg. 170/03

Drinking-Water Systems Regulation O. Reg. 170/03 SECTION 11 ANNUAL REPORT Drinking-Water System Number: 210000194 Drinking-Water System Name: Minden Hills DWS Drinking-Water System Owner: Township of Minden Hills Drinking-Water System Category: Large

More information

Impact of Chlorine Dioxide on TTHMs Reduction in Drinking Water By Douglas D. Rittmann, Ph.D., P.E. Water/Wastewater Consultant

Impact of Chlorine Dioxide on TTHMs Reduction in Drinking Water By Douglas D. Rittmann, Ph.D., P.E. Water/Wastewater Consultant Impact of Chlorine Dioxide on TTHMs Reduction in Drinking Water By Douglas D. Rittmann, Ph.D., P.E. Water/Wastewater Consultant Introduction In 1974, chloroform, a trihalomethane (THM) species, was identified

More information

Preparing for Nutrient Removal at Your Treatment Plant

Preparing for Nutrient Removal at Your Treatment Plant Summer Seminar Emerging Issues in the Water/Wastewater Industry Preparing for Nutrient Removal at Your Treatment Plant Rajendra P. Bhattarai, P.E., BCEE Austin Water Utility Ana J. Peña-Tijerina, Ph.D.,

More information

Coupling Trickling Filter or RBC s with Activated Sludge

Coupling Trickling Filter or RBC s with Activated Sludge Coupling Trickling Filter or RBC s with Activated Sludge By John R. Harrison, P.E. Kennedy/Jenks Consultants 503-295-4911 or JohnHarrison@KennedyJenks.com 1. What are Combined or Coupled Plants? Most coupled

More information

Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448]

Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448] Optimizing Filter Conditions for Improved Manganese Control During Conversion To Biofiltration [Project #4448] ORDER NUMBER: 4448 DATE AVAILABLE: May 2016 PRINCIPAL INVESTIGATORS: Chance V. Lauderdale,

More information

Ammonia Removal and ph Adjustment in Aerated Lagoons

Ammonia Removal and ph Adjustment in Aerated Lagoons Ammonia Removal and ph Adjustment in Aerated Lagoons WWOA 45 th Annual Conference Thursday, October 6 th, 2011, 8:50 AM Presented by: Jeremiah Wendt, PE SEH Overview Ammonia Background Chemistry Toxicity

More information

General Information on Nitrogen

General Information on Nitrogen General Information on Nitrogen What is nitrogen? Nitrogen was discovered in 1772 by Daniel Rutherford in Scotland Nitrogen gas makes up nearly 80% of the air we breathe Nitrogen gas is not toxic Nitrogen

More information

NEW BIOLOGICAL PHOSPHORUS REMOVAL CONCEPT SUCCESSFULLY APPLIED IN A T-DITCH PROCESS WASTEWATER TREATMENT PLANT

NEW BIOLOGICAL PHOSPHORUS REMOVAL CONCEPT SUCCESSFULLY APPLIED IN A T-DITCH PROCESS WASTEWATER TREATMENT PLANT NEW BIOLOGICAL PHOSPHORUS REMOVAL CONCEPT SUCCESSFULLY APPLIED IN A T-DITCH PROCESS WASTEWATER TREATMENT PLANT ABSTRACT C. Yang*, L. Zhou**, W. Luo***, and L. Johnson**** *Corstar International Corp. 111

More information

Optimization of an Advanced Water Treatment Plant: Bromate Control and Biofiltration Improvement

Optimization of an Advanced Water Treatment Plant: Bromate Control and Biofiltration Improvement University of South Florida Scholar Commons Graduate Theses and Dissertations Graduate School January 202 Optimization of an Advanced Water Treatment Plant: Bromate Control and Biofiltration Improvement

More information

TROUBLESHOOTING OF NITRIFICATION UPSETS AT PHARMACEUTICAL WASTEWATER TREATMENT PLANT

TROUBLESHOOTING OF NITRIFICATION UPSETS AT PHARMACEUTICAL WASTEWATER TREATMENT PLANT TROUBLESHOOTING OF NITRIFICATION UPSETS AT PHARMACEUTICAL WASTEWATER TREATMENT PLANT ABSTRACT Jurek Patoczka, PhD, PE, Hatch Mott MacDonald 27 Bleeker Str., Millburn, NJ 07041 jurek.patoczka@hatchmott.com

More information

A Monitoring and Control Toolbox for Biological Filtration. Water Research Foundation Project 4231

A Monitoring and Control Toolbox for Biological Filtration. Water Research Foundation Project 4231 A Monitoring and Control Toolbox for Biological Filtration Water Research Foundation Project 4231 2013 Water Research Foundation. ALL RIGHTS RESERVED. 2013 Water Research Foundation. ALL RIGHTS RESERVED.

More information

Basic Steps in DW Treatment Process. Water Treatment. EPA and DBP s. Scottsdale Chaparral DW Plant

Basic Steps in DW Treatment Process. Water Treatment. EPA and DBP s. Scottsdale Chaparral DW Plant Basic Steps in DW Treatment Process Water Treatment DW: Drinking Water (pre use) Vs. WW: Waste Water (post use) Natural Sedimentation Coagulation lime ++ & clay => floc Flocculation time and mixing to

More information

Kamloops Centre for Water Quality: Membrane Technology Ensures Water Safety

Kamloops Centre for Water Quality: Membrane Technology Ensures Water Safety Kamloops Centre for Water Quality: Membrane Technology Ensures Water Safety History of Water Treatment in Kamloops The waters of the North and South Thompson Rivers that meet in Kamloops, British Columbia,

More information

Riverbend Water Resources District Phase 3 Report on Water Treatment Plant and Raw Water Intake Site Selection

Riverbend Water Resources District Phase 3 Report on Water Treatment Plant and Raw Water Intake Site Selection Riverbend Water Resources District Phase 3 Report on Water Treatment Plant and Raw Water Intake Site Selection Submitted To Riverbend Water Resources District By CH2M HILL and MTG Engineers and Suveyors

More information

2009 Water Quality Report

2009 Water Quality Report 2009 Water Quality Report A Message from the Director side this issue: Definitions 2 Lead and Copper 2 Abel Lake WTF Table of Detected Contaminants Smith Lake WTF Table of Detected Contaminants Potential

More information

Regulatory & Research Aspects of the San Gabriel Valley Indirect Reuse Replenishment Project (IRRP)

Regulatory & Research Aspects of the San Gabriel Valley Indirect Reuse Replenishment Project (IRRP) Regulatory & Research Aspects of the San Gabriel Valley Indirect Reuse Replenishment Project (IRRP) CA-NV AWWA AFC15 Session 12A Research 10:00 am October 28, 2015 Outline Background Project Description

More information

OPERATION OF AN STP FOR RECYCLED WATER PRODUCTION PLANT. Iain Fairbairn. Iain Fairbairn, Plant Manager, Sydney Water

OPERATION OF AN STP FOR RECYCLED WATER PRODUCTION PLANT. Iain Fairbairn. Iain Fairbairn, Plant Manager, Sydney Water Winner of the Actizyme Prize for Best Paper at the NSW Operators Conference held in October 2005 OPERATION OF AN STP FOR RECYCLED WATER PRODUCTION PLANT Paper Presented by : Iain Fairbairn Author: Iain

More information

Drinking-Water Systems Regulation O. Reg. 170/03

Drinking-Water Systems Regulation O. Reg. 170/03 SECTION 11 ANNUAL REPORT Drinking-Water System Number: 210000194 Drinking-Water System Name: Minden Hills DWS Drinking-Water System Owner: Township of Minden Hills Drinking-Water System Category: Large

More information

North American Biofiltration Knowledge Base. Appendices A and B. Project #4459

North American Biofiltration Knowledge Base. Appendices A and B. Project #4459 rth American Biofiltration Knowledge Base Appendices A and B Project #4459 rth American Biofiltration Knowledge Base Appendices A and B Prepared by: Jess Brown and Giridhar Upadhyaya Carollo Engineers,

More information

ANNUAL DRINKING WATER QUALITY REPORT FOR 2016

ANNUAL DRINKING WATER QUALITY REPORT FOR 2016 ANNUAL DRINKING WATER QUALITY REPORT FOR 2016 Village of Monroe Water Department 76 Woodcock Road Monroe, New York 10950 Public Water Supply ID# 3503535 INTRODUCTION To comply with State and Federal regulations

More information

FAYOUM CITY SEWAGE TREATMENT PLANT, DEVELOPMENT STAGES, CASE STUDY

FAYOUM CITY SEWAGE TREATMENT PLANT, DEVELOPMENT STAGES, CASE STUDY FAYOUM CITY SEWAGE TREATMENT PLANT, DEVELOPMENT STAGES, CASE STUDY Ahmed El-Zayat, Environmental Engineering Group, Egypt Emaill: ahmed_el_zayat@yahoo.com Introduction This case study focuses on three

More information

Copies: Mark Hildebrand (NCA) ARCADIS Project No.: April 10, Task A 3100

Copies: Mark Hildebrand (NCA) ARCADIS Project No.: April 10, Task A 3100 MEMO To: Jeff Pelz (West Yost) Kathryn Gies (West Yost) Copies: Mark Hildebrand (NCA) ARCADIS U.S., Inc. 200 Harvard Mills Square Suite 430 Wakefield Massachusetts 01880 Tel 781 224 4488 Fax 781 224 3033

More information

Operation of a small scale MBR system for wastewater reuse

Operation of a small scale MBR system for wastewater reuse Operation of a small scale MBR system for wastewater reuse K. Azis, Ch. Vardalachakis, P. Melidis and S. Ntougias Laboratory of Wastewater Management and Treatment Technologies, Department of Environmental

More information

Module 1: General Overview

Module 1: General Overview Module 1: General Overview Revised January 2006 This course includes content developed by the Pennsylvania Department of Environmental Protection (Pa. DEP) in cooperation with the following contractors,

More information

Integrated Fixed Film Activated Sludge (IFAS) System for Additional Nitrification at the Coldwater WWTP

Integrated Fixed Film Activated Sludge (IFAS) System for Additional Nitrification at the Coldwater WWTP Fishbeck, Thompson, Carr & Huber, Inc. Integrated Fixed Film Activated Sludge (IFAS) System for Additional Nitrification at the Coldwater WWTP Jim Flamming, P.E., Senior Process Engineer, FTC&H Dave Woodman,

More information

KIMBERLEY-AMIK-TALISMAN WATER SYSTEM

KIMBERLEY-AMIK-TALISMAN WATER SYSTEM KIMBERLEY-AMIK-TALISMAN WATER SYSTEM 2015 OPERATION AND MAINTENANCE ANNUAL REPORT Municipality of Grey Highlands Project No: OS-02-702-14-OS Date: February 2016 Prepared for: Municipality of Grey Highlands

More information

Drinking-Water Systems Regulation O. Reg. 170/03

Drinking-Water Systems Regulation O. Reg. 170/03 2011 ANNUAL REPORT Drinking-Water System Number: 210002263 Drinking-Water System Name: Vars Well System Drinking-Water System Owner: City of Ottawa Drinking-Water System Category: Large Municipal Residential

More information

Water. Greater Vancouver Water District 2016 Quality Control Annual Report. Volume 1

Water. Greater Vancouver Water District 2016 Quality Control Annual Report. Volume 1 Water Greater Vancouver Water District 216 Quality Control Annual Report Volume 1 Foreword This report has been produced to meet the requirement for water suppliers to produce an annual report on water

More information

Startup and Performance of the World s first Large Scale Primary Dissolved Air Floatation Clarifier ABSTRACT KEYWORDS INTRODUCTION

Startup and Performance of the World s first Large Scale Primary Dissolved Air Floatation Clarifier ABSTRACT KEYWORDS INTRODUCTION Startup and Performance of the World s first Large Scale Primary Dissolved Air Floatation Clarifier Bruce R. Johnson 1 *, Jennifer Phillips 2, Tim Bauer 3, Greg Smith 4, George Smith 5, John Sherlock 6

More information

Water Treatment Plant Improvements For Disinfection Byproduct, Iron/Manganese and Turbidity Removal

Water Treatment Plant Improvements For Disinfection Byproduct, Iron/Manganese and Turbidity Removal For Disinfection Byproduct, Iron/Manganese and Turbidity Removal September 9, 2010 Prepared for: Prepared by: Provost & Pritchard Consulting Group Clovis, California COPYRIGHT 2008 by PROVOST & PRITCHARD

More information

CHAPTER DRINKING WATER STANDARDS, MONITORING, AND REPORTING

CHAPTER DRINKING WATER STANDARDS, MONITORING, AND REPORTING CHAPTER 62-550 DRINKING WATER STANDARDS,, AND REPORTING 62-550.102 Intent and Scope 62-550.200 Definitions for Public Water Systems 62-550.300 Application of Quality Standards to Public Water Systems 62-550.310

More information

Annual Drinking Water Quality Report for 2015 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY )

Annual Drinking Water Quality Report for 2015 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY ) Annual Drinking Water Quality Report for 2015 Niagara County Water District 5450 Ernest Road, Lockport, NY (Public Water Supply ID# NY3100567) INTRODUCTION To comply with State regulations, the Niagara

More information

WHERE DOES OUR WATER COME FROM?

WHERE DOES OUR WATER COME FROM? Annual Drinking Water Quality Report for 2015 Town of Cambria Water District 4160 Upper Mountain Rd. Sanborn, NY 14132 (Public Water Supply ID# NY3100557) INTRODUCTION To comply with State regulations,

More information

DEP 2003 DRINKING WATER STANDARDS, MONITORING AND REPORTING CHAPTER DRINKING WATER STANDARDS, MONITORING, AND REPORTING

DEP 2003 DRINKING WATER STANDARDS, MONITORING AND REPORTING CHAPTER DRINKING WATER STANDARDS, MONITORING, AND REPORTING CHAPTER 62-550 DRINKING WATER STANDARDS, MONITORING, TABLE OF CONTENTS PAGE 62-550.101 Authority, Intent, and Policy. (Repealed) 3 62-550.102 Intent and Scope. 3 62-550.103 Effective Date. (Repealed) 4

More information

Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado

Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado JUST ADD WATER Renovation of the Filters at the Soldier Canyon Filter Plant in Fort Collins, Colorado Thomas M. Getting, P.E., DEE, Filtration Product Manager John Geibel, P.E., Chief Engineer Michael

More information

DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Standards and Facility Regulation. Guidance for Filter Plant Performance Evaluations

DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Standards and Facility Regulation. Guidance for Filter Plant Performance Evaluations DEPARTMENT OF ENVIRONMENTAL PROTECTION Bureau of Water Standards and Facility Regulation DOCUMENT NUMBER: 383-3120-106 TITLE: EFFECTIVE DATE: AUTHORITY: POLICY: PURPOSE: APPLICABILITY: DISCLAIMER: Guidance

More information

EVENT-BASED PATHOGEN ASSESSMENT IN A DEGRADED CATCHMENT. Heidi Josipovic. North East Water

EVENT-BASED PATHOGEN ASSESSMENT IN A DEGRADED CATCHMENT. Heidi Josipovic. North East Water EVENT-BASED PATHOGEN ASSESSMENT IN A DEGRADED CATCHMENT Paper Presented by: Heidi Josipovic Author: Heidi Josipovic, Systems Optimisation Project Officer, North East Water 77 th Annual WIOA Victorian Water

More information

THM Monitoring in Consecutive Drinking Water Systems

THM Monitoring in Consecutive Drinking Water Systems THM Monitoring in Consecutive Drinking Water Systems Rick Bacon rbacon@aquametrologysystems.com Rudy Mui rudy@aquametrologysystems.com Systems that Enable the Optimization of THM Control www.aquametrologysystems.com

More information