1 CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: February 27, 2014 ITB NO WAKEFIELD PUMPING STATION UPGRADE ADDENDUM NUMBER TWO TO: All Offerors Please be advised of the following modification(s) & information related to Invitation to Bid (ITB) to These modifications, comments, and attachments are hereby made a part of the bid documents to the same extent as if bound therein. The due dates for questions and bids remain the same. I. Changes, Additions, and Modifications to the ITB A. Changes 1. Addendum 1 Questions 23, 24, 25, 26 Clarification Delete references to estimate and $600,000. The budget for this project is between $700,000 - $900, Appendix 1 Specifications and Drawings (Page APP-1) a) Drawing S-002, C-001 Delete Drawings S-002 and C-001 in their entirety and replace with Revised Drawings S- 002 and C-001 in the file named ITB Revised Drawings S002 C001 Addendum pdf available on the County s Bid Board. b) Specifications Section Geotextiles Add Specifications Section Geotextiles (Attachment A) in its entirety to the ITB Wakefield Pumping Station - SPECIFICATIONS pdf. c) Specifications Section 13120, Article 2.04.B (Page ) Add the bold, italicized text below: 8. Reference Electrical Drawings for voltage and kw capacity. 1
2 d) Specifications Section 13120, Article 2.04.C (Page ) Add the bold, italicized text below: 11. Fans shall be sized for ¼ water column pressure drop. The fan shall be a wall fan, propeller type. Motor shall be inside of building. 12. Reference Electrical Drawings for voltage and kw capacities. 13. Intake and exhaust louvers shall be a minimum of 16 x Louvers shall be combination fixed-operate type 15. Louver Manufacturers a. Greenheck Model EAC-401 or approved equal e) Specifications Section 15870, Article 2.01.A.2 (Page ) Delete the following strikethrough text and replace with the bold, italicized text below: f. Performance Variable to 550 cfm at inches water column B. Attachments 1. Attachment A Specifications Section Geotextiles IV. Written Questions Received through 2/13/2014 Question 1 Question: Are there easement issues related to the electrical 4 PVC installed by the Contractor? Response: There is a 60 Right of Way centered on Wakefield Circle. Question 2 Question: Should the bidder assume the existing force main is ductal iron? Response: Existing force main is ductile iron pipe. Question 3 Question: Should the bidder assume the existing force main is at a depth of 4 feet? Response: Existing force main is at a depth of 7 to 8 feet. Question 4 Question: Regarding drawing C-001, will the LOD change to include the installation of the SMECO Primary Feed? Response: Refer to the attached Drawing C-001. Question 5 Question: Can the Contractor leave sheeting in place and cut to a certain depth? Response: The County will allow sheeting to remain in place. Question 6 Question: Can the LOD be moved to allow more room near the force main tie in? Response: Refer to the attached Drawing C
3 Question 7 Question: Will the electrical line need to be moved prior to sheeting? Will the County provide an allowance for moving the electrical line? Response: The Contractor shall anticipate relocating existing electrical service equipment (meter box, panel, etc.) to facilitate construction if deemed necessary to maintain the existing pump stations operations required per the Contract. Any work associated with relocating the existing service, excavating around the existing service, etc. shall be coordinated with SMECO. No allowance will be provided. Question 8 Question: Where are the easements located around the property next door to the pumping site? Response: Neighboring property 2382 Paddington Court has a 10 utility easement along the northern property line shared with Wakefield Pumping Station. There is a 10 utility easement on the shared property line for both 2382 and 2384 Paddington Court. Also, there is a 60 Right of Way centered on Wakefield Circle. Question 9 Question: It appears from Drawing S-002 that the excavation for the Wet Well can be laid back. Will this be permitted? Response: A lay back area will be permitted if needed to facilitate construction of the wet well. Question 10 Question: Are there any Manholes in the incoming Sanitary Sewer? There is a circle in the 8 Sewer line along the property line; is it a Manhole? Response: The closest upstream manhole to the existing wet well is on Wakefield Circle, labeled with an S on Drawing C-001. Question 11 Question: What is the length of the existing FM to Paddington Court? Response: See Specifications Section Question 12 Question: Spec Section & Addendix II; Dewatering will be required to excavate for wet well has the County applied for dewatering permit. Response: Yes. Question 13 Question: GP-13, Permits; If Contractor has to obtain a dewatering permit the contract duration of 330 days may not allow enough time for project completion. Response: The dewatering permit will be provided by the County. Question 14 Question: Addendix II; Geotechnical Report states the use of shoring systems requiring dynamic installation are not recommended for use. Please advise if driven or vibrated steel sheet pile will be allowed? Response: Driven or vibrated sheet piling will not be allowed. The Contractor shall use augered soldier piles with lagging or similar non-dynamic installation. 3
4 Question 15 Question: Spec Section B.1; Sheeting can be left in place if approved by owner. Please advise if owner is going allow the sheeting to be left in place? Response: The County will allow sheeting to remain in place. Question 16 Question: Spec Section 13120; Requires precast building to include HVAC ventilation system consisting of fans louvers and MODs. Please provide louver and damper schedule indicating size of each. Additionally please provide spec for louvers and MOD's. Response: HVAC requirements are listed in Specification Precast Concrete Building. The bottom of a fan or louver shall not be less than 3 feet above finished floor elevation and the top not less than 3 feet from the roof. Both shall be a minimum 16 x16 size. Alternate sizes are an option for possible location above doors, as long as the free area is maintained. Panelboard GP has voltage listed for LV 1 & 2. Louvers shall be combination fixed-operate type. The louvers shall be Greenheck Model EAC-401, or equal. Question 17 Question: Sheet C-001; Shored excavation for wet well will encroach the LOD and on opposite the electric line will be in the way. Can an allowance be added in the bid sheet for relocation of the existing site electric. Response: The Contractor shall anticipate relocating existing electrical service equipment (meter box, panel, etc.) to facilitate construction if deemed necessary to maintain the existing pump stations operations required per the Contract. Any work associated with relocating the existing service, excavating around the existing service, etc. shall be coordinated with SMECO. No allowance will be provided. Question 18 Question: Sheet M-001; Indicates Bubbler conduit through the wall of the wet well. Sheet M-002 shows it turning out the ground and through the top slab. Please advise. Response: The bubbler piping is intended to proceed through the top slab and back down as per the Bubbler Guide Well Detail provided on Drawing M002. Question 19 Question: Sheet C-001; Proposed force main connection to existing is to close to the LOD. Response: The LOD has been modified. Refer to the attached Drawing C001. Question 20 Question: Sheet C-001; Note 7- is contractor to assume a depth of 4 feet as basis of bid? Response: Existing force main is at a depth of 7 to 8 feet. Question 21 Question: Sheet C-001; Please identify existing force main materials of construction; ductile, PVC or transite asbestos. Response: Existing force main is ductile iron pipe. 4
5 Question 22 Question: Sheet C-001; Proposed force main connection to existing force main note states restrained coupling with concrete thrust blocks. Please provide detail of the connection. Response: The Contractor shall provide a restrained wye connection to the existing force main. Thrust block at the wye shall be per the Charles County standard detail B.101. Question 23 Question: Is a engineers trailer required and if required where will it be located. Response: An engineer s trailer is not required. Question 24 Question: Sheet E-002; Has the proposed primary electric service to the site been coordinated with SMECO? Response: The Engineer has made initial contact with the utility on behalf of the Owner regarding service at this facility including proposed routing of the primary feeder to the utility transformer as shown on the contract drawings. The Contractor is still required to coordinate final installation including final primary feeder routing and hold a pre-installation conference with utility prior to work as specified in Contract Specifications Question 25 Question: Spec. Section 01540, 1.05.C; States pump around discharge Manhole is 300 feet away; please advise can the by-pass pump piping be installed within the existing force main easement or does it have to be installed along sidewalk along Wakefield Circle and Paddington Court. Response: For bidding purposes, the Contractor shall assume along the sidewalk along Wakefield Circle and Paddington Court. Question 26 Question: Sheet C-001; The LOD shown does not encompass by-pass pump piping installation and proposed primary site electrical feeder. New LOD's need to be established to encompass all proposed work. Response: Refer to the attached Drawing C001. Question 27 Question: Sheet C-001; Does Note 3 apply to proposed primary electrical service installed along Wakefield Circle Response: Note 3 applies to the verification of all existing underground utility locations as applicable to facilitate construction. Question 28 Question: Sheet C-001; Is the buried water meter assembly proposed or existing? Response: Proposed. Question 29 Question: Site Visit; Existing Sidewalk at driveway to pump station is broken will the sidewalk be replaced. Response: No. Existing sidewalk to remain as-is unless impacted by construction activities. 5
6 Question 30 Question: Site Visit; Existing Dirt/Gravel Driveway to pump station is it to be improved with new gravel/stone after completion of the proposed pump station work? Response: No. Question 31 Question: Sheet C-001; Please provide invert of pipe exiting interceptor manhole upstream of existing Wet Well? Response: Per Record Drawings, the invert of the 8 pipe exiting the manhole on Wakefield Circle upstream of the existing wet well is FT. Question 32 Question: Sheet M-001; 10" Gate Valve end connection MJ or Flanged? Response: The 10-inch gate valve located in the wet well is a flanged connection. Question 33 Question: Sheet M-001; 2" Air release piping at wet well indicates a flapper valve please provide spec. Response: Apco 100 Series Rubber Flapper Swing Check Valve or equal. The valve requires a flanged connection on the PVC pipe. Question 34 Question: Sheet M-001; Please provide spec/detail/make/manufacturer of the portable fall arrest post with SS base plate. Response: Refer to Specifications Section Article Question 35 Question: Sheet E-002; Please provide section of duct bank from handhold to intersection of DB/LTG and DB/BOW. Response: Ductbank shall consist of (3)-2 conduits in 3x1 arrangement (3 row by 1 column) with plan west end conduit supplying Wet Well Blower, spare middle conduit stubbing up adjacent to Wet Well Blower DS, and east end conduit supplying the A1 lighting fixture. Question 36 Question: Sheet E-002; Please clarify "conduits routed in equipment pads" for the conduits from Wet Well junction boxes to the interior of the wet well. Response: The type E-1 conduits from the wet well shall be routed below grade under the wet well concrete top slab and equipment pad and they shall stub up at the corresponding pump station wet well junction boxes. Question 37 Question: Sheet M-002; Bubbler detail are pipe clamps 4 ft on center or 6 ft? Response: Pipe clamp spacing shall be a minimum of 4 feet and maximum of 6 feet as per the Bubbler Guide Well Detail on Drawing M-002. Question 38 Question: Sheet C-003; Will the County supply the water meter? Response: Yes. 6
7 Question 39 Question: Sheet C001; 10" C900 PVC sewer with restraint system; spec A.6 call for a split serrated ring behind bell; restraint is shown in 3 places. Are 3 bell restraint joints required on the 22 foot run? Are wall sleeves and link seals required at structures to restrain pipe at structure walls? Response: The full length between structures shall be restrained joint pipe. The drawings show 3 joints given distance and differential settlement potential. Wall sleeves and link seals will not be required on the 10 C900 PVC sewer system. Question 40 Question: Can some specs be provided for the door hardware? Response: Refer to Section Precast Concrete Building for the door hardware specifications. Question 41 Question: Can Landia be added as a named manufacture under Bid Item No. 2, Submersible Chopper Pumps? Response: No. However, the Contractor may specify Landia as an or equal alternative along with price savings to be reviewed by the County. The County reserves the right to accept or reject the use of any or all or equal equipment/material. 7
8 ATTACHMENT A 8
9 9
10 10
11 11
12 * * * * * * END OF ADDENDUM * * * * * * 12
A/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
More informationBUREAU Joe Iuviene, AIA January 20, 2017
architectural BUREAU Joe Iuviene, AIA January 20, 2017 Alterations & Additions NEW TOWN HALL for TOWN OF AUSTERLITZ 816 State Route 203, Spencertown, New York 12165 ADDENDUM NO. 1 This addendum amends
More informationA/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
More informationEngineering Design Center. Standard Drawings. 1st Edition -January 2016
Engineering Design Center Standard Drawings 1st Edition -January 2016 Golden State Water Company Standard Drawings 1/11/2016 Table of Contents PART A STANDARD DRAWINGS Section I Pipeline Construction P-1
More informationElectric Service Standards
V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are
More informationBIDDING SCHEDULE SEWER LIFT STATION NO. 2 REPLACEMENT PROJECT CITY OF ALHAMBRA City s Project No. N2M17-83
Item No. BIDDING SCHEDULE SEWER LIFT STATION NO. 2 REPLACEMENT PROJECT CITY OF ALHAMBRA City s Project No. N2M17-83 DESCRIPTION EST. QTY. UNIT UNIT PRICE TOTAL PRICE GENERAL BID ITEMS 1 Per Plans and Specifications
More informationSECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION
820-1 SCOPE OF WORK: SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION a. Furnish all labor, materials, equipment, and incidentals required for demolition and/or removal and disposal of existing
More informationDIVISION 3: SEWER. Improvement Design Standards City of Dundee Oregon. Division 3 : Sewer Page 1
DIVISION 3: SEWER 3.1 DESIGN CRITERIA A. APPLICABILITY 1. These Design Standards shall govern all construction and upgrading of public sanitary sewer facilities in the City of Dundee and applicable work
More informationThis is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.
COACHELLA VALLEY WATER DISTRICT DOMESTIC WATER CHECKLIST Tract/Parcel No: Project Common Name: Developer: Engineer: Engineer Signature: Date: Phone: Phone: Print: This is only a general checklist; please
More informationThe designer shall also submit additional information required by the University as described and underlined below.
I. Structural Engineering Submissions The designer shall submit all information required by the State Construction Office (SCO) as described in the State Construction Manual Chapter 300 - Project Design
More informationGV 001 Equipment Bases and Enclosures General Information
Eq u ip me n tba s e s a n d En c lo s u re s Ge n e ra lin fo rma tio n E n g in e e r :R.An th o n GV0 0 1 Ap p r o v e r :Jo s h u a Jo n e s Ap r 1 7 2 0 Ap r1 7 GV 001 Equipment Bases and Enclosures
More informationCITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT
CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT Adopted by City Council: May 21, 2007 X:\General Eng\DESIGN STANDARDS\Engineering Design Standards
More informationSEWER SYSTEM DESIGN GUIDELINES
SEWER SYSTEM DESIGN GUIDELINES PART 1 GENERAL 1.1 GENERAL GUIDELINES A. The following sewer system design guidelines are based on Federal, State and Local health requirements, and the Berkeley County Water
More informationDOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES
Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating
More informationSECTION PIPE & PIPE FITTINGS PART 1 GENERAL
SECTION 02610 PIPE & PIPE FITTINGS PART 1 GENERAL 1.01 DESCRIPTION A. This Section includes the material and bedding requirements for all pipe and pipe fittings for underground pressure and non-pressure
More informationContact Clark Public Utilities Construction Services department at (360) to initiate a request for service.
CHAPTER3 Clark Public Utilities Commercial Electric Service Handbook Commercial Underground Services Preparing for the installation The following checklist will assist in preparing a project for the installation
More information3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES
3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES All sanitary sewers shall be designed in accordance with these Design Standards, LBWD Rules and Regulations, and to accepted engineering principles. In
More information2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.
General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting
More informationSanitary Sewer Extensions, Lift Stations, and Force Mains Engineering Report Form. I. General Information. 1. Name of Facility:
Oklahoma Department of Environmental Quality Water Quality Division Phone: 405-702-8100 Construction Permitting Section 707 N. Robinson, OKC, OK 73102-6010 P.O. Box 1677, OKC, OK 73101-1677 Sanitary Sewer
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationHITT STREET UNIVERSITY PROJECT #: CP REFER TO CP PLANS FOR ELECTRICAL DUCTBANK IN HITT STREET INSTALL:
N 1133521.33 E 1689742.43 STA: 10+53.07 INSTALL: 2-10" 90 BENDS CONNECT TO MIDDLEBUSH HALL INTERIOR PLANT PLUMBING MIDDLEBUSH HALL HW1 HWS HWR 10+00 FREDRICK APARTMENTS FINE ARTS INSTALL 422 LF 10" HWS
More informationITEM L-119 AIRPORT OBSTRUCTION LIGHTS DESCRIPTION
SECTION 74 AIRPORT OBSTRUCTION LIGHTS (FAA L-119) 74-1 GENERAL The Contractor shall perform all work required by the plans and specifications for construction of obstruction lights in accordance with the
More informationCURRENT NORTH LAS VEGAS ADDENDA
SECTION 1 Section 1.01.73 Fire Service Meter ADD: Type I is not approved for installation in the City of North Las Vegas service area. Section 1.01.107 Pressure Reducing Valve (PRV) or Pressure Regulator
More informationCity of Wentzville. Standard Specifications and Construction Details Amendment List
Amendment No. 1 Standard Specifications and Construction Details Amendment List Date: September 21, 2009 Subject: SCD 700.23 - Residential Entrance Layout and drawing revised to more clearly show the location
More informationSECTION FOUNDATION DRAINAGE
SECTION 33 41 13 SPEC WRITER NOTES: Use this section only for NCA projects. Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section
More informationTRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING)
PART 1 - GENERAL TRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING) 1.01 SECTION INCLUDES A. Trenchless Installation of Carrier Pipe with Casing Pipe B. Trenchless Installation of Carrier Pipe without
More informationCONSTRUCTION SURVEY. Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following:
CONSTRUCTION SURVEY PART 1 - GENERAL 1.01 SECTION INCLUDES Construction survey includes personnel, equipment, and supplies required for, but not limited to, the following: A. Construction Survey: 1. Project
More informationSEMINOLE TRIBE OF FLORIDA
SEMINOLE TRIBE OF FLORIDA Denise DeCarolis Carpenter Purchasing Department Director 6300 STIRLING ROAD HOLLYWOOD, FLORIDA 33024 PHONE (954) 966-6300 x11170 FAX (954) 967-3478 E-MAIL: dcarpenter@semtribe.com
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 22 1316 - SANITARY WASTE AND VENT PIPING PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01
More informationLI STATIONS N-03 & N-06 PLACEMENT BID # B May 18, 2016 Addendum 2
revard Central Services Florida's Coast CENTRAL SERVICES GROUP Telephone (321) 617 7390 PURCHASING SERVICES Fax (321) 617-7391 Brevard County Government Center 2725 Judge Fran Jamieson Way, Bldg. C, Suite
More informationSECTION TRENCHING & BACKFILLING
SECTION 02225 - TRENCHING & BACKFILLING 1.0 GENERAL 1.1 Work included in this Section includes trenching and backfilling for underground pipelines and related structures only. 1.2 Reference Specifications
More informationEngineer s Packet. Water and Sewer
Engineer s Packet Water and Sewer The White House Utility District engineer s packet has been created to help streamline the plan review and plan approval of projects within the White House Utility District
More informationVillage of Arlington Heights. Sewer Back-up Rebate Program
Village of Arlington Heights Sewer Back-up Rebate Program (Including Enhanced Program Information) Updated: October 1, 2017 Village of Arlington Heights Building & Life Safety Department 33 S. Arlington
More informationCITY OF TAMPA WASTEWATER DEPARTMENT TECHNICAL STANDARDS GUIDELINE. FOR CONSTRUCTION OF WASTEWATER FACILITIES July 2014 Version 6
CITY OF TAMPA WASTEWATER DEPARTMENT TECHNICAL STANDARDS GUIDELINE FOR CONSTRUCTION OF WASTEWATER FACILITIES July 2014 Version 6 2545 Guy N Verger Boulevard, Tampa, FL 33605 www.tampagov.net TECHNICAL STANDARDS
More informationSECTION CONSTRUCTION SERVICES
SECTION 01100 CONSTRUCTION SERVICES PART 1 GENERAL 1.01 - Section Includes A. Mobilization. B. Construction Surveys. C. Record Documents. 1.02 Description Of Work A. Mobilization: includes the preparatory
More informationSANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.
SANITARY SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sanitary Sewer Gravity Mains B. Sanitary Sewer Force Mains C. Sanitary Sewer Services 1.02 DESCRIPTION OF WORK A. Construct sanitary sewer gravity
More informationBUILDING CODES & DESIGN CRITERIA
BUILDING CODES & DESIGN CRITERIA Adopted Building Codes: 2006 International Building Code (IBC) 2006 International Residential Code (IRC) 2006 International Mechanical Code (IMC) 2006 International Plumbing
More information(a) If this solicitation is amended, then all terms and conditions which are not modified remain unchanged.
Inspiration Water & Sewer Adjustments Bid No. 16-217-05-17 Page 3 of 26 Addendum #1, RFB 16-217-05-17, May 13, 2016 be furnished to all bidders as an amendment to the solicitation, if such information
More informationSECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS
SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS Section Page 19-1 TRENCH EXCAVATION...19.1 19-1.01 Exploratory Excavation...19.1 19-1.02 Trench Width...19.1 19-1.02.A Storm Drain
More informationNatural Gas Service Installation and Meter Clearance Requirements
Natural Gas Service Installation and Meter Clearance Requirements Call SJG s new construction line at 1-844-611-5605 for more information. Builder/Owner/Developer Requirements The clearances in this handout
More informationCustomer Requirements Customer-owned Transformer Vault Room
Scope This standard documents the requirements for customer-owned vault rooms containing transformers and switches that are owned, operated, and maintained by Tacoma Power. It does not address transformer
More informationSECTION DUCTILE IRON FITTINGS. A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller.
PART 1 - GENERAL 1.1 DESCRIPTION A. This section includes materials, installation, and testing of ductile iron fittings 48 inches and smaller. 1.2 RELATED WORK SPECIFIED ELSEWHERE A. Section 01300 Record
More informationSECTION WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA
SECTION 6900 - WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA 6901 DESIGN CRITERIA A. General 1. The design standards presented in the City of Lee's Summit Design Criteria are the minimum standards
More informationContact the Jurisdictional Engineer for materials allowed by each jurisdiction.
Design Manual Chapter 3 - Sanitary Sewers 3C - Facility Design 3C-1 Facility Design A. Capacity of Pipe Pipe sizes 15 inches and smaller should carry the peak flow at a depth of no more than 0.67 of the
More informationA. Codes and Standards that are standard at the University. C. Coordinate cleanout locations with Architect.
PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationSECTION HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE)
SECTION 02623 HIGH DENSITY POLYETHYLENE PIPE AND FITTINGS (PRESSURE PIPE) PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials, equipment and incidentals required and install high density
More informationINFORMATIONAL PACKAGE ACCESSORY RESIDENTIAL BUILDINGS (INCLUDING DETACHED GARAGES, STORAGE BUILDINGS & WORKSHOPS)
1102 4 th Street Telephone: 306-634-1819 Estevan, Saskatchewan, Canada Fax: 306-636-2199 S4A 0W7 INFORMATIONAL PACKAGE ACCESSORY RESIDENTIAL BUILDINGS (INCLUDING DETACHED GARAGES, STORAGE BUILDINGS & WORKSHOPS)
More informationSECTION FACILITY SANITARY SEWERS
SECTION 22 13 13 FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationVoigt 1. Russell Voigt Construction Option Advisor Ed Gannon Louis at 14 th Washington, D.C. 16 September 2013 Technical Report #1.
Voigt 1 Russell Voigt Construction Option Advisor Ed Gannon Louis at 14 th Washington, D.C. 16 September 2013 Technical Report #1 Executive Summary Located in northwest Washington, D.C. at the corner of
More informationADDENDUM No. 6. ITB No. 4424: W.R. Wheeler (Swift Run) Service Center PUD Non-motorized Improvements Phase 1
ADDENDUM No. 6 ITB No. 4424: W.R. Wheeler (Swift Run) Service Center PUD Non-motorized Improvements Phase 1 Due: June 9, 2016 at 2:00 p.m. (local time) The following changes, additions, and/or deletions
More informationResidential Engineering P.O. Box 430 Memphis, TN (Deliveries at 5791 Summer Trees Memphis, TN 38134) (901) / (901) Fax
MEMPHIS LIGHT, GAS, AND WATER DIVISION Application for Utility Services for Residential Subdivisions Residential Engineering P.O. Box 430 Memphis, TN 38101-0430 (Deliveries at 5791 Summer Trees Memphis,
More informationTCC/SHORE TRANSIT BUS MAINTENANCE FACILITY - PHASE II
SECTION 221313 - FACILITY SANITARY SEWERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification
More informationMANHOLES, VAULTS AND CATCH BASINS SECTION A. Section Soil and Aggregate Materials. C. Section Storm Drainage Systems
SECTION 02607-1 1.0 GENERAL 1.1 SCOPE: A. This section covers the work necessary for the construction of sanitary and storm system manholes, catch basins, and miscellaneous concrete structures complete.
More informationHANDHOLES, PULLING VAULTS AND JUNCTION BOXES
Handholes and pulling vaults perform several important functions: Provide drainage for the conduit system so that freezing water does not damage the conduit or wires. Provide a location for bending the
More informationALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL
ADDENDUM NO. 2 To all holders of Contract Documents for the construction of: ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL Please note this Addendum forms a part of the Contract
More informationTOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK
TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK COST EVALUATION FOR ROLLING HILLS AREA WATER MAIN EXTENSION PROFESSIONAL CONSULTING, LLC. Octagon 10, Office Center 1719 Route 10, Suite 225 Parsippany,
More informationSECTION PACKAGE BOOSTER PUMP STATIONS
SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to
More informationBASED ON DFD MASTER SPECIFICATION DATED 2/24/2014
1 0 1 0 1 0 1 SECTION 1. TRENCHING BASED ON DFD MASTER SPECIFICATION DATED // P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of providing all work, materials, labor, equipment,
More informationThe following is required for a complete permit submittal for each unit.
P: (847)810-3502 OR (847)810-3503/3521, F: (847)615-4383 MULTI-FAMILY OR COMMERCIAL ADDITION OR ALTERATION PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. MULTI-FAMILY
More information16. Design of Pipeline Structures.
16. Design of Pipeline Structures. a. General. 1) The following guidelines are for the design of structures for water and sewer pipelines including structural concrete and miscellaneous metals design.
More informationA NEW GYMNASIUM AND RENOVATED FINE ARTS FOR MONTGOMERY CATHOLIC PREPARATORY SCHOOL MONTGOMERY, ALABAMA
McKee and Associates Architecture and Interior Design Addendum No. SEVEN Date: 07.11.17 Project: A NEW GYMNASIUM AND RENOVATED FINE ARTS FOR MONTGOMERY CATHOLIC PREPARATORY SCHOOL MONTGOMERY, ALABAMA A7.1
More informationC. Foundation stabilization for pipe and utility structures.
PART 1 - GENERAL 1.1 SECTION INCLUDES A. Excavating, backfilling, and compacting for utilities, including pipe, structures, and appurtenances. B. Control of water in trenches. C. Foundation stabilization
More informationUnderground Piping for Private Hydrants & Sprinkler Supply Line
City of Brea Brea Fire Department Fire Prevention 1 Civic Center Circle Phone: (714) 990-7655 Underground Piping for Private Hydrants & Sprinkler Supply Line PURPOSE The provision of adequate water supplies
More informationSECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL
SECTION C1 DUCTILE IRON PIPE AND FITTINGS GENERAL This section covers the furnishing and installation of ductile iron water pipe, fittings, thrust restraint and pipe disinfection. Ductile Iron Pipe MATERIALS
More informationDGR PROJECT NUMBER:
P:\08\010\25\DWG\PIPELINE\TITLE.DWG Plot Date: 8/18/2014 1:52 PM 220TH ST. 210TH ST. 200TH ST. 190TH ST. IRONWOOD AVE. JACKSON AVE. 180TH ST. HWY 75 170TH ST. STANDPIPE "S" ROCK RAPIDS CITY OF HWY 9 DRAWINGS
More informationUNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-13 48 00.00 10 (October 2007) ---------------------------------- Preparing Activity: USACE Superseding UFGS-13 48 00.00 10 (April 2006) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationCOUNTY OF ALAMEDA. ADDENDUM No. 5. RFP No for. Cherryland Fire Station
COUNTY OF ALAMEDA ADDENDUM No. 5 to RFP No. 13024 for Cherryland Fire Station This County of Alameda, General Services Agency (GSA), RFP/Q Addendum has been electronically issued to potential bidders via
More informationADDENDUM ADDENDUM NUMBER: One DATE: 30 October 2012
ADDENDUM ADDENDUM NUMBER: One DATE: 30 October 2012 RE: Putnam County Emergency Services Disaster Response and Logistical Storage 410 S. State Road 19 Palatka, Florida Architect s Project No. 1132 FROM:
More information1. B16.1 Cast Iron Pipe Flanges and Flanged Fittings, Class C 111 Rubber Gasket Joints for Ductile Iron Pressure Pipe and Fittings
SECTION 33 34 00 SANITARY FORCE MAIN PART 1 GENERAL 1.1 SCOPE OF WORK A. This section specifies the requirements for furnishing and installing sanitary force main and appurtenances. The pipe shall be of
More informationSWIMMING POOL PERMIT AND INSPECTION REQUIREMENTS
Building Inspections SWIMMING POOL PERMIT AND INSPECTION REQUIREMENTS Permit Applications Pool permit applications are now being accepted online at http://etrakit.flower-mound.com/. Starting November 1,
More informationThe following is required for a complete permit submittal for each unit.
P: (847)810-3503 OR (847)810-3503/3521, F: (847)615-4383 NEW MULTI-FAMILY DWELLING OR COMMERCIAL PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. NEW MULTI-FAMILY
More informationSection 2: Underground
Section 2: Underground GENERAL INSTALLATION REQUIREMENTS FOR UNDERGROUND FACILITIES Underground electric service and meter location will be established by NHEC upon site visit. In some instances the type,
More informationWASTEWATER SYSTEM STANDARDS
8.1 SCOPE Wastewater pipelines and appurtenances shall be provided as shown on the plans and as specified herein. Clearing, grubbing, trench excavation and backfill, pipe material, valves, cutting and
More informationSpecifications for Electrical Underground Residential Distribution Systems
Specifications for Electrical Underground Residential Distribution Systems Specification DDS-2 Revision 13, February 2010 ONCOR ELECTRIC DELIVERY COMPANY SPECIFICATIONS FOR ELECTRICAL UNDERGROUND RESIDENTIAL
More informationSECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES
SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES 4.1 GENERAL REQUIREMENTS 4.1.1 Water and fire protection distribution facilities are to be provided solely for the purpose of supplying potable
More informationUTILITIES COMMISSION CITY OF NEW SMYRNA BEACH, FLORIDA 200 CANAL STREET P.O. BOX 100 NEW SMYRNA BEACH, FL
DATE: January 5, 2018 UTILITIES COMMISSION CITY OF NEW SMYRNA BEACH, FLORIDA 200 CANAL STREET P.O. BOX 100 NEW SMYRNA BEACH, FL 32170-010 ITB# 04-18 REPLACE 12 WATER MAIN AT TURNBULL BAY (DAMAGED DURING
More information***************************************************************************************************************
02735 WASTE WATER DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 22 14 00 ***************************************************************************************************************
More informationINSPECTION AND ACCEPTANCE FOR MAINTENANCE
Inspection and Acceptance For Maintenance Page 1 (Last revised 6/29/10) INSPECTION AND ACCEPTANCE FOR MAINTENANCE SELECTED LINKS TO SECTIONS WITHIN THIS SPECIFICATION Acceptance Sewer As Built Drwg Example
More informationDESIGN DEVELOPMENT PHASE
UNIVERSITY OF MICHIGAN DESIGN DELIVERABLES FEBRUARY 2012 As part of the deliverables for formal UM review at each of the major phases of design listed below, the Design Professional shall submit this "Design
More informationResidential Sewer Backup Prevention Program
City of Wheaton Residential Sewer Backup Prevention Program Please Note: The City reserves the right to modify the policies, procedures and rules of this program or discontinue the program in its entirety
More informationDARTMOUTH COLLEGE DESIGN January 3, 2012 & CONSTRUCTION GUIDELINES
SECTION 15420 DRAINAGE AND VENT SYSTEMS PART 1 DESIGN DIRECTIVES 1.1 DESIGN CRITERIA A. All cleanouts above finished (accessible and non-accessible) ceilings shall be extended to the floor above. B. Do
More informationWelcome to Douglas County PUD
Welcome to Douglas County PUD We are committed to providing the best possible utility services at the lowest possible cost consistent with sound business principles. To better serve you, please fill out
More informationM I N N E S O T A D O T BID TABULATION SUMMARY JOB PAGE 1 ON 03/16/94 MINNESOTA PROJECT NO.S: STP 5822(002)
BID TABULATION SUMMARY JOB 940094 PAGE 1 STATE PROJECT NO. 162-080-04 BIDS RECEIVED UNTIL 11:00 A.M. ON 03/16/94 MINNESOTA PROJECT NO.S: STP 5822(002) BETWEEN 2ND STREET NORTH AND 15 STREET NORTH IN ST.
More informationREAD ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X
CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 9 - VENTS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building application.)
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationPLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL
FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors
More informationWelcome! Thank you for your interest in upgrading your service with Great Lakes Energy Cooperative (GLE).
Welcome! Thank you for your interest in upgrading your service with Great Lakes Energy Cooperative (GLE). Enclosed is the information needed to upgrade your service with GLE. Please read the documents
More informationADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities
ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road,
More informationMATERIAL ALLOWANCES AND UNIT PRICES
PART 1 - GENERAL 1.1 SECTION INCLUDES ADDITIONS AND RENOVATIONS TO WEST YORK AREA HIGH SCHOOL - #1231 SECTION 012200 MATERIAL ALLOWANCES AND UNIT PRICES A. Measurement and payment criteria applicable to
More informationA. Codes and Standards that are Standards at the University. A. Provide floor drains in all toilet rooms, janitor closets, and mechanical rooms.
PART 1: GENERAL 1.01 Purpose A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is
More informationJune 15, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA ADDENDUM NO. 3 / IFB NO. Y PH
June 15, 2017 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA ADDENDUM NO. 3 / IFB NO. Y17-763-PH NORTHWEST WATER RECLAMATION FACILITY REUSE WATER STORAGE IMPROVEMENTS REVISED BID OPENING DATE: June
More information3.1 Introduction: Design Responsibility and Applicability of Requirements
SECTION 3 Sewer Design and Construction 3.1 Introduction: Design Responsibility and Applicability of Requirements The design and construction requirements for sewer collection systems included in this
More informationSECTION UTILITY MANHOLES AND STRUCTURES
SECTION 33 05 14 UTILITY MANHOLES AND STRUCTURES PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Precast reinforced concrete manholes and structures with tongue-and-groove joints with masonry transition
More informationNASHVILLE ELECTRIC SERVICE NON NETWORK VAULT DESIGN GUIDE
NASHVILLE ELECTRIC SERVICE NON NETWORK VAULT DESIGN GUIDE EFFECTIVE JULY 2, 2015 1. PURPOSE...1 2. CUSTOMER RESPONSIBILITY...2 3. DRAWINGS...2 3.1. PRELIMINARY DESIGN DRAWINGS...2 3.2. CONSTRUCTION/APPROVAL
More informationConstruction Documents (CDs) Required Signature Blocks and Standard Notes
Development Services Department 100 N. Wilcox Street, Castle Rock CO 80104 Project Manager 720-733-3582 Construction Documents (CDs) Required Signature Blocks and Standard Notes Revised July 17, 2017 INDEMNIFICATION
More informationSDR26 material is to be used as a minimum on all U-M projects.
BuildingName The Description of the Project P00000000 0000 DOCUMENTS SPECIFICATION DIVISION 33 NUMBER SECTION DESCRIPTION DIVISION 33 SANITARY SEWER UTILITIES SECTION 333100 - SANITARY SEWER END OF CONTENTS
More informationTask Order Authorization
Task Order Authorization Task Order Number: 6 Task Order Name: 2017 Small Drainage Program Hourly Rate: See attached Exhibit B Budget Not To Exceed: $79,795.00 This Task Order pertains to the On-Call Agreement
More informationADDENDUM NO. TWO TO THE REQUEST FOR PROPOSAL (RFP) DOCUMENTS April 25, 2016
ADDENDUM NO. TWO TO THE REQUEST FOR PROPOSAL (RFP) DOCUMENTS April 25, 2016 General: The following changes, additions, or deletions shall be made to the following documents; all other conditions shall
More informationPipe Jacking/Microtunnelling. Dr. Mark Knight. Centre for Advancement of Trenchless Technologies (CATT) University of Waterloo.
Pipe Jacking/Microtunnelling Dr. Mark Knight Centre for Advancement of Trenchless Technologies (CATT) University of Waterloo 1 New Installations New Installations Non-Steering Methods Steering Methods
More informationSITE SERVICES GUELPH TRANSIT OPERATIONS & MAINTENANCE SECTION WATSON ROAD FACILITY PAGE 1 OF 6 WATER RECLAMATION PROJECT JUNE 2013
WATSON ROAD FACILITY PAGE 1 OF 6 PART 1 GENERAL 1.1 Description The work covered by this Section includes all labour, materials, equipment, and supervision necessary to complete the site services as shown
More information