ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL
|
|
- Christiana Daniel
- 6 years ago
- Views:
Transcription
1 ADDENDUM NO. 2 To all holders of Contract Documents for the construction of: ALBUQUERQUE PUBLIC SCHOOLS for MONTESSORI OF THE RIO GRANDE CHARTER SCHOOL Please note this Addendum forms a part of the Contract Documents and modifies them in the manner and extent set forth below. All other contents, terms, and conditions of the Documents remain unchanged. 1. P R O J E C T M A N U A L DIVISION 7 THERMAL AND MOISTURE PROTECTION A. Section METAL ROOF AND WALL SYSTEM 1. Revise Section as follows: 2.2 BOARD INSULATION POLYISOCYANURATE A. Type: Unfaced faced, closed cell polyisocyanurate insulation board, ASTM C591 C1289, Type II. B. Minimum compressive strength: psi. C. Board size: 48 by 96 inches by thicknesses required to provide insulation thickness indicated on Drawings. D. Maximum water absorption: percent by volume in accordance ASTM D2842 C209. E. Long term thermal resistance (LTTR), R value: per inch at 75 degrees F. F. UL listed for Class A construction. 1. Maximum flame spread: Maximum smoke development: G. Edge: Square. 2. D R A W I N G S GENERAL DRAWINGS A. Sheet G102, Code Analysis 1. Occupancy classification in spaces added per PSFA request. 2. Adopted codes clarified. 3. Parking code clarified. SITE DRAWINGS B. Sheet C101, Grading and Drainage, Base Bid Plan 1. Modifications to grading and drainage per City of Albuquerque. ADDENDUM.002 Page - 1
2 C. Sheet C102, Grading and Drainage, Bid Lot 1. Modifications to grading and drainage per City of Albuquerque. D. Sheet C103, Utilities 1. Drainage system revised, details added. ARCHITECTURAL DRAWINGS E. Sheet A203, Building Elevations 1. Note at upper left on E1 was modified to clarify cement panel installation F. Sheet A412, Interior Elevations 1. Clarification issued for location of PV Monitor in room Revision issued for required ADA access at sink in room 127. G. Sheet A506, Details 1. Clarification for details related to full closure on cement panel system added. H. Sheet A903, Millwork Details 1. Revision issued for required ADA access at sink in room 127. ELECTRICAL DRAWINGS I. Sheet ES101, Electrical Site Plan 1. Add provisions for Aiphone system. Aiphone JOS 1F Box Set provided and installed by Owner's security and access control contractor. Rough-in by GC. J. Sheet E201B, Partial Power Plan - East 1. Add power for water heaters WH-3, WH-4 and WH Add receptacle for PV Monitor. Refer to revised sheet E201B. K. Sheet E301A, Partial Special Systems Plan - West 1. Add provisions for Aiphone System 2. Add provisions for card reader on door VO1.2. L. Sheet E301B, Partial Special Systems Plan - East 1. Relocate voice/data outlet for connection to PV Monitor. Refer to revised sheet E301B. M. Sheet E402, Electrical Schedules 1. Add power for water heaters WH-3, WH-4 and WH-5. N. Sheet E601, Electrical Legend and Schedules 1. Change manufacturer of Lighting Fixture Type E. O. SK-PV-1 1. Location of PV monitor clarified. P. SK-ADD Fencing around mechanical equipment added. ADDENDUM.002 Page - 2
3 3. C L A R I F I C A T I O N S 1. See Bidder questions and answers 2. See revised drawings this addendum. 4. B I D D E R Q U E S T I O N S + A N S W E R S 1. According to the electrical drawings (E201A) the two automatic door openers located on doors V01.1/V01.2 and V03.1/V03.2 seem to operate independently from one another. Please confirm that two separate buttons will be required in each vestibule. A. Correct. Vestibules act as an air-lock. 2. At the two active card reader locations (V01.1 and V03.1) where will the 120v power be tied into? Will this need to be a dedicated circuit or can it be tied into the closest power (i.e. the automatic door operator)? A. Yes. Power is indicated for access control on the power plan, keyed note Power requirements were not seen for WH-3, WH-4 or WH-5. Please provide. A. Addressed in this addendum. Please see revised sheet E201B. 4. Card reader R.I. is called out at every exterior door. The typical Rough-In detail for Access Control says to run a ¾ conduit (typical) for power hinge. If applicable. Please confirm every exterior door should have rough-in provided for future power transfer hinges or electric strikes. A. Exterior doors that require access are indicated on the Power Plans. Typical rough-in will be for electric strike unless the door unit has a panic device. Then it gets a rough-in on the hinge side. 5. Should exterior door frames/doors be prepped for future install of power transfers? If so please clarify if doors will operate using an electric strike or an ELR. A. See answer #4. 6. Are you requiring Floor Flatness and Floor Levelness Testing? If so, who pays for this? A. Yes. Please refer to , 1.03.B.2.c/d and , 3.4 TOLERANCES. The Owner pays for testing, the GC must coordinate with testing agency and conduct this test before anything is placed on the slab. The test requires a long lead time and the GC shall be responsible for accommodating the testing agencies schedule. 7. No irrigation controllers or hotboxes were seen for the landscape. It is assumed all irrigation will tie into an existing controller. If APS on-call is going to add or update the school s controller, please confirm if new data lines and or power will be required. A. Existing controller is wired to receive changes from this scope of work. No additional wiring anticipated. 8. Please provide power requirements for the PV monitor located in Rm 127. A. Addressed in this addendum. Please see revised sheet A412, E301B, and SK-PV-1 9. Please confirm that per APS Mech. Design Standards we will need to provide Bollards around the gas meters/regulators. A. Yes. Bollards are indicated on AS101. Additional bollards were added around the fire equipment and HotBox on Addendum # Again per APS Mech. Design Standards, all the site fire protection piping is required to be ductile iron. Do we need to restrain all joints? A. Addressed in this addendum. Please see revised sheet C103. Both 4" and 6" fire lines shall be ductile iron pipe Class 50. Restrained joints will be required at all pipe-to-fitting connections except where a minimum length of 18' of pipe is provided to the nearest pipe- ADDENDUM.002 Page - 3
4 to-pipe joint. All pipe joints will be required to be restrained within 46' of a 6" valve and within 32' of a 4" valve. 11. A new 6 fireline is indicated on plan sheets P102a and P102b. This line does not show up on plan sheet C103. We understand to cap where indicated if Bid Lot 3 is not accepted. A. Please refer to Sheet C103. The 6 fireline runs along the north property line, then feeds the fire riser room Mech. 125B. From there it runs west to feed Mech. 117A. If Bid Lot is not accepted, this line will be capped. 12. It appears there are gaps in the Swiss Pearl panels. The Tyvek is not rated to withstand UV. Please provide an alternative Building Wrap. A. The system is a concealed installation. No building wrap will be exposed. This is addressed in this addendum. Please see revised A203 and A506 for details. 5. P R I O R A P P R O V A L S Substitutions: The following manufacturers have been approved for use on the project. Approval is for manufacturers only. The supplier / manufacturer shall be responsible for compliance with specified product performance criteria and compatibility with specific project design requirements. Architect will have sole discretion on determination of equivalency. Metal Soffit Panels Section McElroy Mini-Rib panel Steel Toilet Compartments - Section All American Metal Corp Privacy Curtain Section InPro Corp. Toilet Accessories - Section Bradley Corporation Lighting Equipment - Lighting Fixture Schedule, Sheet E601 Types A1, A2, A3: - Type B : HE Williams, Lithonia (w/ 3000K) Type C : HE Williams, Lithonia Type D : Philips Lightolier, Lithonia Type E : - Type F : HE Williams, Lithonia Type G : Metalumen (ok w/ drywall frame), Mark Type H : Metalumen (ok w/ T-bar), Mark Type K : Pinnacle Lighting, Mark Type L : Metalumen, Mark Type M : Metalumen, Mark Type N : Metalumen, Mark Type P : Maxlite, Newstar Type Q : HE Williams (w/ wallwasher), Lithonia Type SA : - V2 Lighting (w/ A1 finish) Type SB : - Type SC : HE Williams, Lithonia Type SD : - Type SE : HE Williams, Lithonia ADDENDUM.002 Page - 4
5 Type SF : - Type SG : - Type EM : Mule Lighting Type EM1 : Mule Lighting Type EXM : Mule Lighting, Exitronix Sincerely, G. Donald Dudley Architect, Ltd. by: Don Dudley, AIA NM License #3673 DATE: 3/14/2018 Attachments: D R A W I N G S GENERAL G102, Code Analysis SITE DRAWINGS C101, Grading and Drainage, Base Bid Plan C102, Grading and Drainage, Bid Lot C103, Utilities ARCHITECTURAL DRAWINGS A203, Building Elevations A412, Interior Elevations A506, Details A903, Millwork Details ELECTRICAL DRAWINGS ES101, Electrical Site Plan E201B, Partial Power Plan - East E301A, Partial Special Systems Plan - West E301B, Partial Special Systems Plan - East E402, Electrical Schedules E601, Electrical Legend and Schedules SKETCHES SK-PV-1 SK-ADD.002 END OF ADDENDUM ADDENDUM.002 Page - 5
CLARIFICATIONS. Item 3. Specification Sections and A. All finish wood shall have sealer coat and two coats of finish material REVISIONS
Addendum #2 Project Name: Global Campus Interior Renovation Project Address: 2 E. Center Street Fayetteville, AR 72701 Date: 06/14/17 This document is issued as a response to Clarifications. These revisions
More informationMSA MOORE & SPENCE ARCHITECTS, P.A.
MSA MOORE & SPENCE ARCHITECTS, P.A. ADDENDUM NUMBER THREE (3): October 27, 2009 to the Construction Documents dated October 9, 2009 for: HACFM, Covington Meadows Apartments Lehigh Acres, Florida The following
More informationSTANDARD PLAN RELEASE SUMMARY(SPR) Facilities Management Department
STANDARD PLAN RELEASE SUMMARY(SPR) Facilities Management Department Building Design: Nauvoo 00 Release Date: February 2001 Release Number: 1 Summarized below is a list of modifications made to the Standard
More informationMITTERSILL WARMING HUT
STATE OF NEW HAMPSHIRE DEPARTMENT OF RESOURCES AND ECONOMIC DEVELOPMENT DIVISION OF PARKS AND RECREATION PROJECT #: CAP 1786 FRANCONIA NOTCH STATE PARK FRANCONIA, NEW HAMPSHIRE DRAWING LIST: COVER SHEET
More informationTown of Milton Halton Paramedic Services Station No. 17 and Milton Fire Station No. 5 Tender No and
Town of Milton No. 17 and Milton Fire Station No. 5 Tender No. 19-500-1 and 19-500-2 BID SUBMISSION 19-500-2 Part Two In accordance with Tender No. 19-500-2, Tender Form Part Two must be submitted electronically
More informationParish of Ascension Project Management ADDENDUM #1 NOTICE TO BIDDERS/ QUOTE
Parish of Ascension Project Management ADDENDUM #1 NOTICE TO BIDDERS/ QUOTE PROJECT #/ ENG-16-085 PROJECT NAME: FRANK SOTILE PAVILION ADDITION CODE: DATE: Wednesday, June 14, 2017 OWNER: ASCENSION PARISH
More informationQUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019
QUESTIONS & ANSWERS FOR B1900051 SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 Answers to questions: 1) Question: Is the existing slab post tensioned? Answer: No. Existing slab is 4 thick with welded
More informationAddendum No Downsville Pike Hagerstown MD Please note the following changes/clarifications to Bid No.
10435 Downsville Pike Hagerstown MD 21740 301-766-2800 Addendum No. 2 August 28, 2014 TO: All Prospective Offerors FROM: Lisa Freeman, C.P.M., Supervisor of Purchasing REF: Bid No. 2015 05 Renovation of
More informationSTATE OF NEW HAMPSHIRE DEPARTMENT OF NATURAL AND CULTURAL RESOURCES DIVISION OF PARKS AND RECREATION SKI PATROL HUT PROJECT #: CAP 1804
STATE OF NEW HAMPSHIRE DEPARTMENT OF NATURAL AND CULTURAL RESOURCES DIVISION OF PARKS AND RECREATION PROJECT #: CAP 1804 FRANCONIA NOTCH STATE PARK FRANCONIA, NEW HAMPSHIRE BID SET 8/4/2017 DRAWING LIST:
More informationADDENDUM 2 - JULY 14, 2015
7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures
More informationADDENDUM NO. 2. DATE: January 19, 2017 INVITATION FOR BID: IFB J Monroe Park Renovations Project DATED: December 20, 2016
ADDENDUM NO. 2 DATE: January 19, 2017 INVITATION FOR BID: IFB J170012535 Monroe Park Renovations Project DATED: December 20, 2016 RECEIPT DATE: February 8, 2017 (CHANGED) OPENING DATE: February 9, 2017
More informationS C H A M U M A C H O W S K I G R E C O PROJECT #11526 WEST VIRGINIA NORTHERN COMMUNITY COLLEGE WHEELING CAMPUS STUDENT CENTER/BARNES & NOBLE
S C H A M U M A C H O W S K I G R E C O ADDENDUM #2 PROJECT #11526 WEST VIRGINIA NORTHERN COMMUNITY COLLEGE WHEELING CAMPUS STUDENT CENTER/BARNES & NOBLE MARYLAND 1016 MORTON ST. BALTIMORE, MD 21201 TEL
More informationADDENDUM NO. 1. PROJECT: Lowell High School DATE: January 28, Eucalyptus Drive, SF, CA 94132
SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM LOWELL HIGH SCHOOL PROJECT #11493 INTERIM HOUSING for VOLUNTARY SEISMIC STRENTHENING ADDENDUM NO. 1 PROJECT: Lowell High School DATE:
More informationBID ADDENDUM #1 September 24, 2010
BID ADDENDUM #1 September 24, 2010 To: Prospective Bidders/Planholders For: Science 1 Seismic Retrofit & Renovation California State University Stanislaus One University Circle, Turlock, CA 95382 Bid /
More informationADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows:
ADDENDUM NO. 1 TO THE DRAWINGS AND SPECIFICATIONS FOR THE New Dishman-McGinnis Elementary School Bowling Green Independent Schools Bowling Green, Kentucky BG 12-256 RTA 1209 March 11, 2013 To All Plan
More informationMarch 2018 Progress. Work Completed, Week Ending 3/23/18:
March 2018 Progress Work Completed, Week Ending 3/23/18: Continued draft curtains and liner panels. Continued running power to hangar doors. Continued installation of bath accessories in the gang bathrooms.
More informationCarter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications
Carter's Oshkosh (SIS) #1185 - The Center at Pearland Parkway - Pearland, TX 77581 - Scope Of Work / Bid Qualifications Please fill out the blanks associated with your trade scope or work with the words
More informationProject Manual Index of Specifications Shenandoah Schools Concession Building
INDEX OF SPECIFICATIONS Division 0..BIDDING AND CONTRACT REQUIREMENTS 00 11 13 Advertisement for Bids 00 21 13 Instructions to Bidders 00 41 00 Bid Forms 00 43 13 Bid Security Form 00 72 00 General Conditions
More informationSECTION ADDENDUM NUMBER ONE
Softball Field Repairs and Upgrades 03 February 2012 University of South Carolina Upstate State Project Number: H34-I350 DP3 Architects Project Number: 11124 GENERAL INFORMATION SECTION 00 09 10 ADDENDUM
More informationSAN FRANCISCO UNIFIED SCHOOL DISTRICT 2006 PROPOSITION A BOND PROGRAM 300 SENECA NEW ACADEMIC CAMPUS ADDENDUM NO. 1
SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2006 PROPOSITION A BOND PROGRAM 300 SENECA NEW ACADEMIC CAMPUS ADDENDUM NO. 1 PROJECT: 300 Seneca New Academic Campus DATE: September 23, 2013 300 Seneca Ave., S.F.,
More informationSECTION TRESPA ATHLON SOLID COMPOSITE CASEWORK
SECTION 064115 TRESPA ATHLON SOLID COMPOSITE CASEWORK PART 1 GENERAL 1.01 SECTION INCLUDES A. Solid composite casework. 1.02 RELATED SECTIONS A. Documents affecting work in this section includes but is
More informationA. Remove Table of Contents and insert new attached Table of Contents.
ADDENDUM NO. 01 PROJECT Colby Glass E.S. Window Upgrades and ADA Work PROJECT NO. 16043 DATE February 07, 2018 TO: All Prime Contract Bidders and all others to whom Drawings and Specifications have been
More informationADDENDUM NO. 2 PROJECT: Omaha Nation Food Distribution Building Macy, Nebraska Project No ARCHITECT:
ADDENDUM NO. 2 PROJECT: ARCHITECT: Omaha Nation Food Distribution Building Macy, Nebraska Project No. 7-7 PETERS AND ASSOCIATES, ARCHITECTS, P.C. 427 Dayton Circle, Suite Omaha, Nebraska 6837-5558 Date
More informationDESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST
DESIGN DEVELOPMENT REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Design Development Review Package. Provide a written explanation for any omissions. The following items,
More informationCity of Miami ADDENDUM NO. 5. January 12, 2017 INVITATION TO BID NO.: CURTIS PARK NEW SWIMMING POOL FACILITY
City of Miami ADDENDUM NO. 5 January 12, 2017 INVITATION TO BID NO.: 15-16-040 CURTIS PARK NEW SWIMMING POOL FACILITY OFFICE OF CAPITAL IMPROVEMENTS ( OCI ) PROJECT NO.: TO: ALL PROSPECTIVE BIDDERS: The
More informationAddendum No. 3 pg. 1. Project: Prolift Project No.: Subject: Addendum No. 3 Date: Monday, July 18, 2016
Addendum No. 3 pg. 1 Project: Prolift Project No.: 201613.01 Subject: Addendum No. 3 Date: Monday, July 18, 2016 This addendum is a part of the bid documents. Acknowledge receipt on the proposal form.
More informationDIVISION 22 PLUMBING SECTION INTERIOR SANITARY WASTE AND VENT PIPING SYSTEM
DIVISION 22 PLUMBING PART 1 GENERAL 1.01 DESCRIPTION A. Provide a complete system of soil, waste, and vent piping to fixtures and equipment, including traps, floor drains and cleanouts, extending to a
More informationCONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST
CONTRACT DOCUMENTS REVIEW PACKAGE CHECKLIST Check off each item that is included within the submitted Contract Documents Review Package. Provide a written explanation for any omissions. The following items,
More informationSPITZER CONFERENCE CENTER BRIEFING SUITE REFRESH Addendum #2 02/22/2018 LCCC POJECT NO. SPBSR-17 BPA PROJECT NO
SPITZER CONFERENCE CENTER BRIEFING SUITE REFRESH Addendum #2 02/22/2018 LCCC POJECT NO. SPBSR-17 BPA PROJECT NO. 16-32 ADDENDUM NO. 2 SPITZER CONFERENCE CENTER BRIEFING SUITE REFRESH LORAIN COUNTY COMMUNITY
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationPRODUCTION SPECIFICATIONS INSULATED CONCRETE FORMS
PRODUCTION SPECIFICATIONS SECTION 03135 INSULATED CONCRETE FORMS PART 1 GENERAL 1.1 SECTION INCLUDES A. Insulated panel permanent concrete form system for: 1. Exterior structural wall panels. 2. Interior
More informationSection A2 Table of Contents ALL GLASS ENTRANCES
Architectural Aluminum Entrances Storefronts Curtain Walls Impact-Resistant Systems Section A Table of Contents ALL GLASS ENTRANCES Specifications...S-S Swing Type A... - Swing Type F... - Swing Type P...
More informationADDENDUM No. 1. H.S. Thompson Elementary School Abatement Org #307
ADDENDUM No. 1 for BP# 301A H.S. Thompson Elementary School Abatement Org #307 DALLAS INDEPENDENT SCHOOL DISTRICT December 01, 2017 Any addendum issued will be listed or posted at the Bond Program website
More informationJ~e~~r Senior Director of Construction Services Facilities Design and Construction UNIVERSITY OF CALIFORNIA, SAN DIEGO.
BERKELEY DAVIS IR VINE LOS ANGELES MERCED RIVERSIDE SAN DIEGO SAN FRANCISCO SAN!' A BARBARA SANT A CRUZ OFFICE OF THE ASSIST ANT VICE CHANCELLOR CAMPUS ARCHITECT - FACILITIES DESIGN & CONSTRUCTION TEL:
More informationINFORMATIONAL HANDOUT FOR FINISHING A BASEMENT
7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed
More informationSOLICITATION ADDENDUM
CITY OF PALM BEACH GARDENS PURCHASING DEPARTMENT SOLICITATION ADDENDUM Addendum No. 7 DATE: August 22, 2018 TO: SOLICITATION NO.: TITLE: OPENING DATE: All Potential Bidders ITB2018-095RC Construction of
More informationINVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION / SLAB AND SITE WORK
ADDENDUM 3 TO: FROM: RE: Vendors Christie Hutchinson, Purchasing Director INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION
More informationADDENDUM NO. 2 Consisting of 3 pages and Attachments
10404-125 Street, Edmonton, AB. T5N 1T2 Tel: 780.455.5975 Fax: 780.454.2397 info@cdyarchitect.com ADDENDUM NO. 2 Consisting of 3 pages and Attachments PROJECT: Maina Centre Ville Phase II, Beaumont, Alberta
More informationSECTION INSULATED CONCRETE FORMS - RASTRA 1.01 SUMMARY
SECTION 03135 INSULATED CONCRETE FORMS - RASTRA PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Insulated concrete forms for: NOTE TO SPECIFIER: Edit the following list as applicable to project requirements.
More informationSECTION TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS. ADD the following sections: Commissioning Requirements...
ADDENDUM NO. 01 PULASKI COUNTY MIDDLE SCHOOL FOR THE PULASKI COUNTY PUBLIC SCHOOLS PULASKI COUNTY, VIRGINIA STATE PROJECT CODE NO. 077-30-00-100 COMM. NO. 16196-00 RRMM ARCHITECTS ROANOKE, VA AUGUST 14,
More informationSECTION ALTERNATES
SECTION 01 23 00 - ALTERNATES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 01 Specification
More informationS CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS
S CHEDULE G - D OCUMENTS S UBMITTAL R EQUIREMENTS This Attachment lists the items to be provided by the Architect in accordance with Owner/Architect Agreement. This list is not all-inclusive, nor is it
More informationRESPONSES TO QUESTIONS. March 1, 2018
MPA CONTRACT NO. H275-C1 HANSCOM AIRCRAFT RESCUE FIRE FIGHTING / UNITED STATES CUSTOMS AND BORDER PROTECTION FACILITY L.G. HANSCOM FIELD, BEDFORD, MASSACHUSETTS RESPONSES TO QUESTIONS March 1, 2018 The
More informationSTANMYRE + NOEL Architects, P.C Preston White Drive, Suite 104 Reston, VA v f
STANMYRE + NOEL Architects, P.C. 1890 Preston White Drive, Suite 104 Reston, VA 20191 v. 703.471.9350 f. 703.834.1031 info@snarchitects.com S E P T E M B E R 19, 2 0 1 6 ADDENDUM #3 PROJECT: WHITE OAKS
More informationSECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES
SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.
More informationAddendum No. 3: EAST HIGH SCHOOL AUDITORIUM RENOVATIONS
Rockford Board of Education 501 Seventh Street Rockford, IL 61104 May 30, 2014 Addendum No. 3: 14-70 EAST HIGH SCHOOL To All Bidders: Attached are modification, clarifications and/or corrections for the
More informationCITY OF FORT COLLINS BUILDING STANDARDS SPECIFICATIONS/DIV 8
CITY OF FORT COLLINS BUILDING STANDARDS SPECIFICATIONS/DIV 8 L. Division 8 - Doors and Windows 1. Windows 2. Doors a. Glazing shall be energy efficient (ie; Low-E) and have an insulated glass certification
More informationSECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION
Page 210500-1 SECTION 210500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationPROJECT # University of South Carolina, Aiken USCA Convocation Center Shed Aiken, South Carolina ADDENDUM NUMBER
University of South Carolina, Aiken PROJECT #10010.01 SECTION 00911 - ADDENDUM NUMBER 2 PARTICULARS 1.01 DATE: April 10, 2012 1.02 PROJECT: USC AIKEN CONVOCATION CENTER SHED 1.03 STATE PROJECT NUMBER:
More informationKEARNEY REGIONAL AIRPORT NEW HANGAR KEARNEY, NEBRASKA 1238
ADDENDUM # KEARNEY REGIONAL AIRPORT NEW HANGAR KEARNEY, NEBRASKA Wilkins Hinrichs Stober Architects, L.L.C. Date Issued: March, 0 908 West 9 th Street, Suite A Kearney, Nebraska 88 Bid Date: April, 0 08--8
More informationAddendum #1. January 22, 2018
Addendum #1 January 22, 2018 Building B 8500 Public Works Drive Renovation for City of Manassas Water & Sewer Department 8500 Public Works Drive Manassas, VA 20110 Job Description Renovation of the existing
More informationExpansion Joint Covers
Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationBid Package# 500 Org. 046 Fred Florence Middle School Org. 164 Anson Jones Elementary School
ADDENDUM No. 002 For Bid Package# 500 Org. 046 Fred Florence Middle School Org. 164 Anson Jones Elementary School DALLAS INDEPENDENT SCHOOL DISTRICT September 24, 2014 The following items modify the Project
More informationSouth Londonderry Township Pre-Bid Meeting Minutes. August 24, 2016
Beers + Hoffman Scott L. Shonk, R.A., AIA, LEED AP Peter D. Kerekgyarto, R.A., AIA, LEED AP Timothy M. Schwear, Assoc. AIA C. Bruce Christman Jr., AIA, LEED AP, GAC Robert P. Hoffman, R.A., AIA South Londonderry
More informationThe following addendum supersedes previous addendums and does hereby become a part of the contract documents.
1 October 2014 Addendum No. 1 Swansboro Public Safety Facility The following addendum supersedes previous addendums and does hereby become a part of the contract documents. See attached Proposal for use
More informationItem 2 - Question: Building specifications call out for Factory Mutual/FM Global. Is the school insured by FM Global and does this apply?
Addendum 2: Miami R-1 High School Gym Addition 3/22/2019: Questions - Architectural: Item 1 - Question: What depth plastic seat module is required? What is the front to back row spacing? What is the rise
More informationUniversity of Massachusetts Procurement Department 140 Hicks Way 407 Goodell Building Amherst, MA 01003
University of Massachusetts Procurement Department 140 Hicks Way 407 Goodell Building Amherst, MA 01003 May 16, 2016 Addendum #1 Contract Number: UMA16-25 Project Number: 1000730 Speedtype: 157194 Title:
More informationCOMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION
COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION OFFICIAL USE ONLY Date: Permit #: Received by: For Staff Use Only: OFD ELEC Planning SITE LOCATION Site Address: Tax Parcel Number: TYPE OF WORK Building
More informationRFP P1319, Cobb Career Academy Questions and Answers
1. Blakely Downs McKnight Do you have a Square footage on the Cobb Career Academy addition? The Cobb Career Academy is 67,648 sf as is listed on the coversheet. 2. Alphonso Henderson Integrated Office
More informationSECTION TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS. A. Solid composite phenolic toilet compartments and urinal screens.
SECTION 102113 TRESPA ATHLON SOLID COMPOSITE PHENOLIC TOILET PARTITIONS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Solid composite phenolic toilet compartments and urinal screens. 1.02 RELATED SECTIONS
More informationADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT WEST VALLEY COLLEGE
ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT AT WEST VALLEY COLLEGE Owner West Valley-Mission Community College District Saratoga, California Bid #01-1516 12-22-15 WEST VALLEY-MISSION
More informationA/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
More informationDIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT
TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation
More informationTOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT
TOWN OF MANCHESTER GENERAL SERVICES DEPARTMENT 494 MAIN STREET P.O. BOX 191 MANCHESTER, CONNECTICUT 06045-0191 138 MCKEE STREET MANCHESTER, CT BID NO. 16/17-5 ADDENDUM NO. 1 1. The bid opening has been
More informationExpansion Joint Covers (079513)
Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1
More informationNortrax Section David Manchester Road, Ottawa NON-STRUCTURAL METAL FRAMING 16 May 2014 Page 1
16 May 2014 Page 1 PART 1 GENERAL 1.1 DESCRIPTION This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationREBECCA LG BOSTICK, ARCHITECTS, INC
REBECCA LG BOSTICK, ARCHITECTS, INC 703-768-2250 ADDENDUM NO. 3 Page 1 of 4 (plus attachments -2 pages) SILVERBROOK ELEMENTARY SCHOOL RENOVATION Fairfax County Public Schools 9350 Crosspointe Drive, Fairfax
More informationDALLAS-FORT WORTH INTERNATIONAL AIRPORT
DALLAS-FORT WORTH INTERNATIONAL AIRPORT ADDENDUM NO. 2 TO THE REQUEST FOR BIDS Contract No. 9500445 Restroom Rehabilitation at Terminal B (Phase 3 & 4) December 20, 2010 THE REQUEST FOR BIDS (RFB) FOR
More informationSECTION PROJECTED SCHEDULE
Addendum No: One (1) Project: Architect s Project No: Burton Memorial Coliseum HVAC Upgrades & Improvements Bid # DB-2017-FM-138 MA1701 Date: January 10, 2018 To: All Plan Holders Introduction The following
More informationSOLICITATION ADDENDUM NO. 1 RFP THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.
Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 RFP 15-0013 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION
More informationHURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R
HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO. 2017-26R Stone Group Architects Project No. 1731 ADDENDUM DATE: September 14, 2017 BID DATE: September 18, 2017 2:00 P.M. C.S.T. SCOPE OF THIS ADDENDUM:
More informationSPECIFICATION GUIDELINE
SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification
More informationDivision 08 OPENINGS TABLE OF CONTENTS
Division 08 OPENINGS TABLE OF CONTENTS 08 1000 GENERAL... 2 A. RELATED DIVISIONS... 2 B. GENERAL... 2 08 1000 DOORS AND FRAMES... 2... 2 B. EXTERIOR DOORS AND FRAMES... 2 C. DOOR FRAMES... 2 D. HOLLOW
More informationAPPENDIX 1 PROJECT REQUIREMENTS
APPENDIX 1 PROJECT REQUIREMENTS I) Scope of Work This section contains a general summary of the work the Contractor shall perform under this contract. If any conflict exists between the work described
More informationITEM NO. 1: Section Quality Requirements. ITEM NO. 2: Section Unit Masonry. ITEM NO. 3: Section Thermal Insulation
701½ West First Street Defiance, OH 43512 Phone 419-782-6211 architects@beilharzinc.com December 8, 2017 WAUSEON EXEMPTED VILLAGE SCHOOLS New Administration Office Building Wauseon, Ohio B7-4551 ADDENDUM
More informationSECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS
SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on
More informationSECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS
SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on
More informationConsultant: Addenda # Date: No. of Pages: dysarchitecture Architectural Addendum AD # Oct. 20, Performance
260 1770 Burrard Street Vancouver, BC V6J 3G7 604 669 7710 tel 604-669-6629 fax www.dysarchitecture.com Project Name: City of Vancouver Affordable Housing SITE 6 2922 East Kent Avenue South &8588 Jellicoe
More informationPulaski County, Virginia
Pulaski County, Virginia Typical Carport Enclosure Details Based on the 2009 International Residential Code CONTENTS General Requirements... 2 Emergency Escape and Rescue... 2 Foundation and Floor... 3
More informationSPARTANBURG COUNTY BUILDING CODES DEPARTMENT
SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,
More informationTHERMAL AND MOISTURE PROTECTION
RELATED DOCUMENTS: The general provisions of the Contract, including General and Supplementary Conditions, and General Requirements, and Division 1 specifications that apply to the work specified in this
More informationDIW Office and Lab Improvements - Phase 2, Project ID Date Issued: November 5, 2014
DIW Office and Lab Improvements - Phase 2, Project ID 102005 Date Issued: November 5, 201 ADDENDUM NO. This addendum will only be distributed via e-mail, but will remain available for viewing on the MSDGC
More information1. Meeting minutes from the pre-bid conference are attached for inclusion in the Bid Documents.
PROJECT NO. 13-130.03 Splash Pad at Lakeside Park ADDENDUM #4 `` Splash Pad at Lakeside Park Pell City, AL WBA No. 13-130.03 OWNER: City of Pell City 1905 First Ave. North Pell City, AL 35125 ph. (205)338-2244
More informationTELEPHONE: (215) ADDENDUM No. 1
THE SCHOOL DISTRICT OF PHILADLPHIA SCHOOL REFORM COMMISSION Office of Capital Programs 440 North Broad Street, 3 rd Floor Suite 371 Philadelphia, PA 19130 TELEPHONE: (215) 400-4730 ADDENDUM No. 1 Subject:
More informationBASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS
BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a
More informationSECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS
SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on
More informationC o u n t y o f F a i r f a x, V i r g i n i a
001961 Page 2 C o u n t y o f F a i r f a x, V i r g i n i a A D D E N D U M DATE: August 2, 2016 ADDENDUM NO. 4 TO: REFERENCE: FOR: DUE DATE/TIME: ALL PROSPECTIVE BIDDERS Government Center Generator System
More information186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS ADDENDUM #1 PERFORMANCE WORK STATEMENT
186 TH AIR REFUELING WING KEY FIELD, MERIDIAN, MS PROJECT NUMBER MDVL092051 Renovate Vehicle Maintenance Facility Bldg 200 23 June 2017 ADDENDUM #1 PERFORMANCE WORK STATEMENT 1.0 SCOPE. This addendum to
More informationA/E Design Deliverable Checklist
A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic
More informationFlorida Army National Guard Construction Facilities Management Office. Scope of Work:
Florida Army National Guard Construction Facilities Management Office Florida Armory Revitalization Program (FARP) Design Guidelines September 2011 Scope of Work: To provide complete design for the renovation/alterations
More informationBIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D
HOSKINS ARCHITECTURE, LLC 1827 1 ST AVENUE NORTH, SUITE 104 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 3 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS
More informationMSA MOORE & SPENCE ARCHITECTS, P.A.
MSA MOORE & SPENCE ARCHITECTS, P.A. ADDENDUM NUMBER SEVEN (7): November 20, 2008 to the Construction Documents dated October 17, 2008 for: HACFM, New Administration Office Building, Fort Myers, Florida
More informationBUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321)
BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL 32907 Phone: (321) 953-8924 Fax: (321) 953-8925 CUSTOMER SERVICE INFORMATION ON COMMERCIAL PLAN REVIEW REQUIRED DOCUMENTS MUST BE SUBMITTED AT TIME
More informationThe Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits
The Compass ( 270 Lisgar Street, Brighton ) Features General Site Work 1. Construction Drawings 2. Building, Plumbing Electrical and Entrance Permits 3. Development and Septic Fees 4. Tarion New Home Warranty
More informationARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section )
8-1200. International Residential Code. ARTICLE 12 INTERNATIONAL RESIDENTIAL CODE 2012 International Residential Code Modification Summary (Statutory Authority: 1976 Code Section 6-9-40) NOTE-This article
More informationADDENDUM #9 DATE: 1/12/17 TO:
ADDENDUM #9 DATE: 1/12/17 TO: Vince O Brien (Anne Arundel County Public Schools) FROM: Andy Locke (Jacobs Engineering) RE: Arnold Elementary School Replacement, All Bid Packages ADDENDUM #9: Revisions
More informationA D D E N D U M T O B I D PRE-ENGINEERED METAL BUILDING
Guadalupe County Auditor s Office 307 W. Court, Suite 205 Seguin, Texas 78155 830-303-4188 Ext. 1328 A D D E N D U M T O B I D PRE-ENGINEERED METAL BUILDING Bid Title: PRE-ENGINEERED METAL BUILDING Bid
More informationSECTIONAL OVERHEAD DOORS SECTION SECTIONAL OVERHEAD DOORS PART 1 GENERAL
13686.00 SECTIONAL OVERHEAD DOORS 083613-1 1.1 RELATED DOCUMENTS SECTION 083613 - SECTIONAL OVERHEAD DOORS PART 1 GENERAL A. Drawings and general provisions of Contract, including General and Supplementary
More informationPortola Valley Green Building Ordinance Build It Green, GreenPoint Rating Point Requirements*
Portola Valley Green Building Ordinance Build It Green, GreenPoint Rating Point Requirements* Project Type Size Points Required New Construction > 3,000 sf 75 Additional Points 1 for every 50 sf GPR Certification
More information