ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14

Size: px
Start display at page:

Download "ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14"

Transcription

1 September 24, 2014 ADDENDUM #4 Lanier Filter Plant Ozone System Safety Improvements BL Q1. Please clarify how many submarine doors the perimeter gaskets and gasket hardware must be replaced on. A1. The number of submarine doors opened shall be at the Contractor s discretion based on their means and methods for demolishing the existing dissolved ozone sample piping inside the Ozone Contactors, installing new piping, and providing for a safe work environment per state and Federal guidelines while working inside the ozone contactors. Any and all submarine doors which are opened by the Contractor shall have their gaskets replaced. Existing hardware may be reused unless it is worn or otherwise degraded such that a gastight seal cannot be achieved with the existing hardware and/or the hardware will not allow for future disassembly and access. Hardware replacements shall match existing. The submarine doors referred to are located in the lower level pipe galleries of the Ozone Building. There are three (3) submarine doors installed per ozone contactor and four (4) contactors. Twelve (12) total submarine doors are available for the Contractor to perform the work and may be accessed at the Contractor s discretion. Q2. Also, please confirm there are only 4 checkered plates that must be resealed. If not, how many checkered plates are present? A2. To clarify, the checker plates are located in the Ozone Generator Room, upper level of the Ozone Building. Each ozone contactor has one (1) approximately 65-inch square checker plate (a total of four (4)). Below, each of the checker plates is a secondary gastight hatch. There are four (4) of these and they have their own hardware and gasketing separate from the checker plates above them. Thus, if the Contractor desires to access the ozone contactor from above in the Generator Room, for each contactor accessed, the Contractor shall be responsible for replacing the gaskets for the checker plate AND it s underlying gastight hatch. Existing hardware may be reused unless it is worn or otherwise degraded such that a gastight seal cannot be achieved with the existing hardware and/or the hardware will not allow for future disassembly and access. Hardware replacements shall match existing. The number of checker plates and gastight hatches opened shall be at the Contractor s discretion based on their means and methods for demolishing the existing dissolved ozone sample piping inside the Ozone Contactors, installing new piping, and providing for a safe work environment per state and Federal guidelines while working inside the ozone contactors.

2 Additional Clarifications: 1. In Addendum #1 (dated September 12, 2014), delete clarification 2 in its entirety. The Bid form shall not include the Part 3 - Additive Alternate section as previously directed. Deleted requirements are shown below. Part 3 Additive Alternate The Bidder shall include within their lump Total Bid (lump sum) an allowance for the following items: Demolition of the four (4) stainless steel sample sinks located in the basement of the Ozone Building. Core drilling twelve (12) new holes into the existing 1-6 reinforced concrete vertical walls of the Ozone Contactors to accommodate the new ¾ dissolved ozone sample piping as described in the Bid Documents. The utilization of this task would be in lieu of enlarging the existing penetrations, if based on Engineer s evaluation of the of existing piping, it is found to be advantageous or required to do so. All such Work shall be at the direction of the Engineer. This Work shall only be performed only if directed by the Engineer. The Contractor submits the following deduct for all Work, labor, materials, and disposal costs associated with this Additive Alternate should the activity not be required. The deduct shall be utilized to adjust the final project cost upon completion and acceptance of the Work. Additive Alternate Demolition and disposal of the four (4) stainless steel sample sinks located in the basement of the Ozone Building. Core drilling twelve (12) new holes into the existing 1-6 reinforced concrete vertical walls of the Ozone Contactors. Deduct from Total Bid (Lump Sum) $ $ 2. Figures of Section are revised and reissued in the attachment to this addendum.

3 3. The bid opening date has been extended as follows: Sealed bids will be received by the Gwinnett County Department of Financial Services Purchasing Division-2 nd Floor, 75 Langley Drive, Lawrenceville, Georgia until 2:50 P.M. local time on October 1, 2014 and then publicly opened and read aloud at 3:00 P.M. Any bid received after 2:50 P.M. will not be accepted. Bid envelope must be marked on the outside with Bid Number, name of Bidder, date and time of opening. Contractor providing the utility work must have a current valid Utility Contractors License. This addendum should be signed in the space provided below and returned with your bid. Failure to do so may result in your bid being deemed non-responsive. Company Name Authorized Representative Thank you. Holly Cafferata, CPPB Purchasing Associate III

4 ADDENDUM #4 Lanier Filter Plant Ozone System Safety Improvements BL Attachments The following attachments are provided on the pages that follow. Specification Section Figure 24-26

5 There are three (3) submarine doors installed for each ozone contactor, on the vertical walls in lower level pipe galleries of the Ozone Building. There are twelve (12) total. For all submarine doors opened by the Contractor during the course of the Work, Contractor shall replace gasket materials, replace hardware as required, and perform and provide all other requirements as noted or specified. DETAIL BELOW PROVIDED FOR INFORMATIONAL PURPOSES ONLY, CONTRACTOR SHALL FIELD VERIFY ACTUAL DIMENSIONS. NOTES: 1. Contractor shall provide replacement gaskets for submarine doors opened during the Work. 2. The number of submarine doors opened shall be at the Contractor s discretion based on their means and methods for demolishing the existing dissolved ozone sample piping inside the Ozone Contactors, installing new piping, and providing for a safe work environment per state and federal requirements while working inside the ozone contactors. 3. Gasket materials shall be ozone compatible. 4. If submarine doors in the Generator Pipe Galleries are to be opened by the Contractor, the following submittals shall be provided for Engineer review and approval prior to gasket fabrication: a. Summary of submarine doors, including: make, model, dimensions, and hardware summary (hardware quantity, type, size, spacing, and material). b. Photographs of the existing installation before and after opening. c. Photographs and summary of existing gaskets, including dimensions, bolt patterns, materials, and thickness. d. Documentation from the submarine door manufacturer including recommendations for gasket materials and thickness. e. Submit gasket fabrication drawings and quantities for gaskets to be replaced. Include material types and replacement hardware to be provided. 5. Existing hardware may be reused unless it is worn or otherwise degraded such that a gastight/watertight seal cannot be achieved with the existing hardware and/or the hardware will not allow for future disassembly and access. Hardware replacements shall match existing. 6. Replacement gaskets shall be of the following materials: a. Each gasket shall be one piece and fully molded solely of 1/4 thick PTFE (GARLOK GYLON Style 3505, or equal). Figure 24. Gastight/Watertight Door Resealing Requirments GWINNETT COUNTY DWR LFP Ozone System Safety Improvements -25- BV September 2014

6 Existing checker plate access hatches on the Generator Room floor are shown in this photo. There are four (4) total (one per ozone contactor). Below, each of the checker plates (in the same slab opening) is a secondary gastight hatch which provides access to the interior of the ozone contactors. There are four (4) total gastight hatches. For all checker plate/gastight hatch pairs opened by the Contractor during the course of the Work, Contractor shall replace gasket materials, replace hardware as required, and perform and provide all other requirements as noted or specified. NOTES: 1. Contractor shall provide replacement gaskets for checker plate covers and gastight hatches opened during the Work. 2. The number of checker plates and gastight hatches opened shall be at the Contractor s discretion based on their means and methods for demolishing the existing dissolved ozone sample piping inside the Ozone Contactors, installing new piping, and providing for a safe work environment per state and federal guidelines while working inside the ozone contactors. 3. Gasket materials shall be ozone compatible. 4. If plates and hatches in the Generator Room are to be opened by the Contractor, the following submittals shall be provided for Engineer review and approval prior to gasket fabrication: a. Summary of existing checker plates and gastight hatches, including: make, model, dimensions, and hardware summary ( hardware quantity, type, size, spacing, and material). b. Photographs of the existing installation for both checker plates and gastight hatches before and after opening. c. Photographs and summary of existing gaskets (for checker plate and gastight hatch), including dimensions, bolt patterns, materials, and thickness. d. Documentation from the gastight hatch manufacturer including recommendations for gasket materials and thickness. e. Submit gasket fabrication drawings and quantities for gaskets to be replaced. Include material types and replacement hardware to be provided. 5. Existing hardware may be reused unless it is worn or otherwise degraded such that a gastight seal cannot be achieved with the existing hardware and/or the hardware will not allow for future disassembly and access. Hardware replacements shall match existing. 6. Replacement gaskets and sealant shall be of the following materials: a. Replacement gaskets for the checker plates on the generator slab shall be one piece and fully molded solely of 1/8 thick Viton with bolt patterns to match existing. Viton gasket strips shall also be provided between the checker plates and the cast-in frame, cut to fill the void space between the checker plates and the cast-in frame, and flush with the operating floor to eliminate potential trip hazards. Apply silicone caulk around the perimeter and atop mounting bolts. Typical of four checker plate hatches. b. Replacement of gastight hatch gaskets located below the checker plates in the Ozone Generator Room, each one piece and fully molded solely of 1/4 thick PTFE (GARLOK GYLON Style 3505, or equal). No photo or detail of the hatch are available. Figure 25. Gastight/Watertight Door Resealing Requirments GWINNETT COUNTY DWR LFP Ozone System Safety Improvements -26- BV September 2014

7 Valve shall be closed. Temporary connections for compressed air. Contaminant and oil-free, filtered compressed air shall be introduced to the headspace of the Ozone Contactors to achieve positive pressure. The Ozone Contactors shall be pressurized to achieve positive 5 inches of water column during the duration of the test. Compressed air shall be introduced via temporary connections to the Ozone Contactors off-gas piping. Figure 26. Gastight Testing END OF SECTION GWINNETT COUNTY DWR LFP Ozone System Safety Improvements -27- BV September 2014

Specifications and Documents

Specifications and Documents Specifications and Documents City of West Haven, Connecticut Water Pollution Control Facility Secondary Sludge Building Pump Station Upgrade Bid No. 207-03 ADDENDUM NO. A. SCOPE. This Addendum No. consists

More information

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION

SECTION COMMON WORK RESULTS FOR FIRE SUPPRESSION Page 210500-1 SECTION 210500 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

CITY OF PANAMA CITY BEACH WWTF INFLUENT SCREENS REPLACEMENT April 14, 2017

CITY OF PANAMA CITY BEACH WWTF INFLUENT SCREENS REPLACEMENT April 14, 2017 CITY OF PANAMA CITY BEACH WWTF INFLUENT SCREENS REPLACEMENT April 14, 2017 ADDENDUM NO. 1 (This Form Must Be Signed and Submitted With Bid Form) Addendum No. 1 addresses the following issues: QUESTIONS

More information

CHARLES COUNTY GOVERNMENT ITB NO MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY CLARIFIER NO. 1 IMPROVEMENTS

CHARLES COUNTY GOVERNMENT ITB NO MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY CLARIFIER NO. 1 IMPROVEMENTS CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 February 07, 2017 ITB NO. 17-17 MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY

More information

ADDENDUM NUMBER TWO (2) DATE: May 1, 2015

ADDENDUM NUMBER TWO (2) DATE: May 1, 2015 ADDENDUM NUMBER TWO (2) DATE: May 1, 2015 PROJECT: FROM: TO: Tenant Improvements for: RELOCATION OF TIME INC. LIFESTYLE GROUP KPS GROUP, INC. 2101 First Avenue North Birmingham, Alabama 35203 All Bidders

More information

RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number:

RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number: RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number: 13-146 A D D E N D U M NO. 1 The following shall form part of the tender documents

More information

IN2 Sleeves and Sleeve Seals for Communications Pathways and Cabling

IN2 Sleeves and Sleeve Seals for Communications Pathways and Cabling Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Sleeves and Sleeve Seals for Communications Pathways and Cabling Illinois Mathematics and Science Academy Follow this

More information

Rytec Corporation One Cedar Parkway Jackson, WI GO-RYTEC (262)

Rytec Corporation One Cedar Parkway Jackson, WI GO-RYTEC (262) Rytec Corporation One Cedar Parkway Jackson, WI 53037 1-888-GO-RYTEC (262) 677-9046 WWW.Rytecdoors.com Pharma-Swing Model Number PSW12002 SECTION 08300 HIGH PERFORMANCE FIBERGLASS SWING DOOR PAIR PART

More information

Success with 2009 IECC in Georgia: Tech Tips for Builders. Insulation. Copyright 2014 Advanced Energy. All Rights Reserved

Success with 2009 IECC in Georgia: Tech Tips for Builders. Insulation. Copyright 2014 Advanced Energy. All Rights Reserved Success with 2009 IECC in Georgia: Tech Tips for Builders Copyright 2014 Advanced Energy. All Rights Reserved 1. For vented attics, install wind baffles on top of all exterior walls, leaving room for at

More information

TOWN OF EAST HADDAM INVITATION TO BID EAST HADDAM COMPANY #1 FIREHOUSE INTERIOR RENOVATIONS ADDENDUM NO. 1 TO CONTRACT DOCUMENTS

TOWN OF EAST HADDAM INVITATION TO BID EAST HADDAM COMPANY #1 FIREHOUSE INTERIOR RENOVATIONS ADDENDUM NO. 1 TO CONTRACT DOCUMENTS TOWN OF EAST HADDAM INVITATION TO BID EAST HADDAM COMPANY #1 FIREHOUSE INTERIOR RENOVATIONS ADDENDUM NO. 1 TO CONTRACT DOCUMENTS The Town of East Haddam is seeking bids from qualified contractors who will

More information

CITY OF PUNTA GORDA, FLORIDA

CITY OF PUNTA GORDA, FLORIDA CITY OF PUNTA GORDA, FLORIDA PHONE: (941) 575-3351 FAX: (941) 575-3340 EMAIL: pgpurch@pgorda.us PROCUREMENT DIVISION 326 West Marion Avenue Punta Gorda, Florida, 33950 October 9, 2014 SOLICITATION #F2013124/CONS-PIPEREPL/WWTP

More information

IN2 Sleeves and Sleeve Seals for Electrical Raceways and Cabling

IN2 Sleeves and Sleeve Seals for Electrical Raceways and Cabling Illinois Math and Science Academy DigitalCommons@IMSA Project Manuals IN2 2015 IN2 Sleeves and Sleeve Seals for Electrical Raceways and Cabling Illinois Mathematics and Science Academy Follow this and

More information

RFB # ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION

RFB # ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION RFB # 18-0197 ADDENDUM NO. 1 ISSUED APRIL 23, 2018 PRE-BID MEETING MINUTES NEW HANOVER COUNTY LANDFILL GAS COLLECTION AND CONTROL SYSTEM CONSTRUCTION The following information was conveyed and discussed

More information

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport RESPONSES TO QUESTIONS and/or RFI s Date: 6/1/2018 The attention of Contractors submitting Filed Sub-Bids

More information

Addendum No. 1. City of Chicago Department of Water Management Bureau of Engineering Services

Addendum No. 1. City of Chicago Department of Water Management Bureau of Engineering Services Addendum No. 1 City of Chicago Department of Water Management Bureau of Engineering Services South Water Purification Plant Filter Backwash Controls Replacement DWM PROJECT NO. 13-202 SPECIFICATION NO.

More information

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications.

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications. ADDENDUM NO. 5 ITB-CD-CME-16-10 Southern Well Field Expansion: Equip 5 Wells and New Raw Water Main Phase 2 ISSUE DATE: August 22, 2016 DUE DATE: August 25, 2016 @ 2:00 p.m. SUBJECT: Addendum No. 5 INTENT:

More information

Cattaraugus County Little Valley County Center Court Renovations Second Floor Little Valley, NY

Cattaraugus County Little Valley County Center Court Renovations Second Floor Little Valley, NY 140 John James Audubon Parkway, Suite 201, Amherst, New York 14228 P 716.688.0766 F 716.625.6825 ADDENDUM NO. 1 Cattaraugus County Little Valley County Center Court Renovations Second Floor Little Valley,

More information

Expansion Joint Covers (079513)

Expansion Joint Covers (079513) Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1

More information

APPENDIX 1 PROJECT REQUIREMENTS

APPENDIX 1 PROJECT REQUIREMENTS APPENDIX 1 PROJECT REQUIREMENTS I) Scope of Work This section contains a general summary of the work the Contractor shall perform under this contract. If any conflict exists between the work described

More information

CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1

CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1 Addendum No. 1 September 26, 2016 Page 1 of 8 CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1 This Addendum forms part of the original contract drawings and specifications

More information

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows:

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows: ADDENDUM NO. 1 TO THE DRAWINGS AND SPECIFICATIONS FOR THE New Dishman-McGinnis Elementary School Bowling Green Independent Schools Bowling Green, Kentucky BG 12-256 RTA 1209 March 11, 2013 To All Plan

More information

Special Applications. Dorn Equipment, Corporation 27 Upham Street Melrose, MA Phone: Fax:

Special Applications. Dorn Equipment, Corporation 27 Upham Street Melrose, MA Phone: Fax: Special Applications Outdoor Protection When using the FIRSTO units outdoors, or wherever vapor or moisture barrier is needed, an application of FIWA sealant is used. The sealant should be applied to any

More information

ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION THE TOWN OF MALTA AND A PORTION OF THE 115KV

ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION THE TOWN OF MALTA AND A PORTION OF THE 115KV ADDENDUM #1 TO THE SPECIFICATION FOR THE CONSTRUCTION OF THE 115KV STONEBREAK RD. TRANSITION STATION IN THE TOWN OF MALTA AND A PORTION OF THE 115KV LUTHER FOREST STATION IN THE TOWN OF STILLWATER SARATOGA

More information

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School A D D E N D U M # 1 DATE: TO: FROM: PROJECT: All Bidders Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School CBI JOB NO.: 11063 The following items shall modify

More information

TITLE: Construction Services for the US-1 South Re-Pump and Booster Pump Station Project

TITLE: Construction Services for the US-1 South Re-Pump and Booster Pump Station Project Procurement Department Bid Office Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 June 06, 2018 ADDENDUM NUMBER: One (1) TITLE: Construction Services for the US-1 South

More information

RPQ ADDENDUM. Project Manager Frank Ramirez

RPQ ADDENDUM. Project Manager Frank Ramirez Port of Miami Contracts, Procurement & Materials Management 1007 N. America Way, Suite 311 Miami Fl 33132 MIAMI-DADE COUNTY, FLORIDA REQUEST FOR PRICE QUOTATION (RPQ) Contract No: MCC 7360 Plan - CICC

More information

Effective Date: Revision #: 1. Section I: Castings and Aluminum Covers. Valve Boxes. Service Clean-out Box and Lid

Effective Date: Revision #: 1. Section I: Castings and Aluminum Covers. Valve Boxes. Service Clean-out Box and Lid Section I: Castings and Aluminum Covers I 1 I 2 I 3 I 4 Valve Boxes Service Clean-out Box and Lid Manhole Casting/ Standard Ring and Cover Access Covers/ Aluminum 1 I 1 VALVE BOXES: Valve boxes shall meet

More information

ATTACHMENT A. Bid # 6793

ATTACHMENT A. Bid # 6793 ATTACHMENT A SCOPE OF WORK TECHNICAL SPECIFICATIONS AND CONTRACT DRAWINGS STORAGE SHED INSTALLATION AT THE SAN JOAQUIN COUNTY HOUSEHOLD HAZARDOUS WASTE FACILITY Bid # 6793 Department of Public Works Solid

More information

INSULATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings

INSULATION SUCCESS WITH 2012 IECC DELAWARE. for Builders & Trades. Recommended Practices for Optimized Energy Savings SUCCESS WITH 2012 IECC DELAWARE Recommended Practices for Optimized Energy Savings for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 DELAWARE For vented attics,

More information

SECTION MISCELLANEOUS METALS

SECTION MISCELLANEOUS METALS PART 1 GENERAL 1.1 WORK OF THIS SECTION A. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to furnish and install all miscellaneous metal fabrications

More information

ADDENDUM NO. 1. Kapuskasing District High School Interior Upgrades. ADDENDUM NO. 1 November 9, 2018

ADDENDUM NO. 1. Kapuskasing District High School Interior Upgrades. ADDENDUM NO. 1 November 9, 2018 Kapuskasing District High School Kapuskasing District High School JLR No.: 27729-032 Owner No.: 7587 Page 1 of 4 This Addendum forms part of the Contract Documents and amends the original drawings and

More information

Pre-Bid Meeting Minutes November 5, Dos Rios WRC First Stage Diffuser Replacement. S&GE, LLC (formerly Sherfey Engineering SA, LLC)

Pre-Bid Meeting Minutes November 5, Dos Rios WRC First Stage Diffuser Replacement. S&GE, LLC (formerly Sherfey Engineering SA, LLC) Pre-Bid Meeting Minutes November 5, 2013 Dos Rios WRC First Stage Diffuser Replacement PREPARED BY: SUBJECT: MEETING DATE: MEETING PLACE / ROOM ISSUE DATE: MEETING ATTENDEES: S&GE, LLC (formerly Sherfey

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES Section SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL... 39-1 39-2 PRECAST CONCRETE MANHOLES... 39-1 39-2.01 Precast Concrete Storm Drain Manholes... 39-1 39-3 SADDLE MANHOLES... 39-2 39-3.01 Saddle

More information

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS

SECTION PATHWAYS FOR COMMUNICATIONS SYSTEMS SECTION 270528 PATHWAYS FOR COMMUNICATIONS SYSTEMS PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Communications equipment coordination and installation. 2. Sleeves for pathways and cables. 3. Raceway

More information

SECTION FLAT WALK-ON TYPE ALGAE CONTROL/LAUNDER COVERS

SECTION FLAT WALK-ON TYPE ALGAE CONTROL/LAUNDER COVERS PART 1 GENERAL 1.01 THE REQUIREMENT SECTION 11301 FLAT WALK-ON TYPE ALGAE CONTROL/LAUNDER COVERS A. The contractor shall furnish and install complete Flat Walk-On Algae Control/Launder Covers as shown

More information

BID # College Center EXTERIOR DOOR REPLACEMENT SECTION "C" TECHNICAL SPECIFICATIONS OWNER

BID # College Center EXTERIOR DOOR REPLACEMENT SECTION C TECHNICAL SPECIFICATIONS OWNER BID # 16-15 College Center EXTERIOR DOOR REPLACEMENT SECTION "C" TECHNICAL SPECIFICATIONS OWNER Board of Trustees Middlesex County College 2600 Woodbridge Avenue P.O. Box 3050 Edison, New Jersey 08818-3050

More information

Expansion Joint Covers

Expansion Joint Covers Expansion Joint Covers 07 95 00 (079513) PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General Conditions, Supplementary Conditions and Division-1

More information

ADDENDUM No. 2 July 6, WWTP IMPROVEMENTS SLUDGE HANDLING UPGRADES Village of Dexter

ADDENDUM No. 2 July 6, WWTP IMPROVEMENTS SLUDGE HANDLING UPGRADES Village of Dexter ADDENDUM No. 2 July 6, 2012 WWTP IMPROVEMENTS SLUDGE HANDLING UPGRADES Village of Dexter 0130-11-0071 The following changes, additions, and/or clarifications to the Contract Documents shall be incorporated

More information

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement DATE: July 15, 2011 ADDENDUM NUMBER: 2 MODIFYING: Specifications No. 1698 PROJECT: Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement BID TIME AND DATE: 2:00 p.m., July 19, 2011

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS Section SECTION 39 - MANHOLES TABLE OF CONTENTS Page 39-1 GENERAL... 39.1 39-2 CONCRETE MANHOLES... 39.1 39-2.01 NOT USED... 39.1 39-2.02 Concrete Storm Drain Manholes... 39.1 39-3 SADDLE SEWER MANHOLES...

More information

Replace Roof Henderson Beach State Park Project #61012

Replace Roof Henderson Beach State Park Project #61012 Replace Roof Henderson Beach State Park Project #61012 Restrooms E & F Scope Of Work Base Bid Scope of Work: The contractor shall provide all labor, materials, equipment, supervision and permitting to

More information

SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION

SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION 820-1 SCOPE OF WORK: SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION a. Furnish all labor, materials, equipment, and incidentals required for demolition and/or removal and disposal of existing

More information

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 QUESTIONS & ANSWERS FOR B1900051 SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 Answers to questions: 1) Question: Is the existing slab post tensioned? Answer: No. Existing slab is 4 thick with welded

More information

Peralta Community College District th Avenue Oakland, California Phone (510) Fax (510) Purchasing Department

Peralta Community College District th Avenue Oakland, California Phone (510) Fax (510) Purchasing Department Peralta Community College District 501 5 th Avenue Oakland, California 94606 Phone (510) 466-7225 Fax (510) 587-7873 Purchasing Department ADDENDUM No. 2 DATED JULY 2, 2013 TO THE PROJECT MANUAL and PLANS

More information

All proposals will be evaluated by a district committee. The following criteria/weighting will be used to evaluate each proposal:

All proposals will be evaluated by a district committee. The following criteria/weighting will be used to evaluate each proposal: The School District of Newberry County Request for Proposals Newberry High School Countertop/Toilet Partitions Replacement The School District of Newberry County is accepting proposals for Boys and Girls

More information

Addendum No. 2. Pre-Bid Meeting Notes and Scope of Work Clarifications

Addendum No. 2. Pre-Bid Meeting Notes and Scope of Work Clarifications Addendum No. 2 Project No. 2016-01EL West Barbour Street 12kV Underground Reconductoring Revisions to Drawings and Specifications Pre-Bid Meeting Notes and Scope of Work Clarifications Replace Section

More information

COUNCIL ROCK SCHOOL DISTRICT ADMINISTRATION & BUSINESS OFFICES The Chancellor Center 30 North Chancellor Street Newtown, PA ADDENDA No.

COUNCIL ROCK SCHOOL DISTRICT ADMINISTRATION & BUSINESS OFFICES The Chancellor Center 30 North Chancellor Street Newtown, PA ADDENDA No. COUNCIL ROCK SCHOOL DISTRICT ADMINISTRATION & BUSINESS OFFICES The Chancellor Center 30 North Chancellor Street Newtown, PA 18940 Doug Taylor, Assoc. AIA, AVS TELEPHONE (215) 944-1015 Supervisor of Operational

More information

Infinity - Century Combination Installation Instructions Gelcoat & Solid Surface Bathware

Infinity - Century Combination Installation Instructions Gelcoat & Solid Surface Bathware Tools and materials you might need for proper installation: Level Caulking gun Drill Scissors Jig saw or router Wood file or 180 grid sand paper 100% silicone caulking Clamps Galvanized screws (8) 1 bolts

More information

September 23, 2016 ADDENDUM #2

September 23, 2016 ADDENDUM #2 September 23, 2016 ADDENDUM #2 To: From: Subject: Prospective Bidders St. Johns County Purchasing Department Bid No. 16-55 St. Johns County Building Services Renovation & Remodeling. This Addendum #2 is

More information

CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE

CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO. 1124 REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE 1 4/13/2016 Questions below pertain to note 4 per drawing, which

More information

MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project

MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project MUSC Psychiatric Hospital CRI Air-Cooled Chiller Replacement Project H51-9832-FW-A ADDENDUM NO. 01 The following items shall take precedence over the drawings and specifications for the above named project

More information

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO. 2017-26R Stone Group Architects Project No. 1731 ADDENDUM DATE: September 14, 2017 BID DATE: September 18, 2017 2:00 P.M. C.S.T. SCOPE OF THIS ADDENDUM:

More information

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM

SECTION LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM Page 1 of 6 SECTION 08 32 20 LAGUNA SERIES TOP HUNG SLIDING DOOR SYSTEM USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS SLIDING DOORS. SECTION INCLUDES OVERHEAD SLIDING TUBE ASSEMBLY, MOUNTING

More information

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS

Central Dartmouth Section Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Dartmouth, NS Exterior Envelope Renovations METAL-CLAD WOOD DOORS Page 1 of 5 Part 1 General 1. RELATED SECTIONS 1. Section 07 92 10 Joint Sealing 2. Section 08 71 00 Door Hardware 2. REFERENCES 1. American Society

More information

INSULATION. Success with 2015 IECC Northeast & Mid-Atlantic. Techtips for Builders & Trades

INSULATION. Success with 2015 IECC Northeast & Mid-Atlantic. Techtips for Builders & Trades Success with 2015 IECC Northeast & Mid-Atlantic Techtips for Builders & Trades COPYRIGHT 2015 ADVANCED ENERGY. ALL RIGHTS RESERVED TEMPLATE 2015.1.0 PAGE 1 NORTHEAST For vented attics, install wind baffles

More information

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON ADDENDUM NUMBER FROM: MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 0 / 533 WEST MAIN STREET TUPELO, MS 3880 / 3880 FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON PHONE: -8-00 PROJECT: ACADEMIC STUDENT

More information

THE CITY OF WALTHAM MASSACHUSETTS PURCHASING DEPARTMENT PHASE III RENOVATIONS TO THE FORMER BANKS SCHOOL ELDERLY HOUSING CONDOMINIUMS AND CONDOMINIUMS

THE CITY OF WALTHAM MASSACHUSETTS PURCHASING DEPARTMENT PHASE III RENOVATIONS TO THE FORMER BANKS SCHOOL ELDERLY HOUSING CONDOMINIUMS AND CONDOMINIUMS THE CITY OF WALTHAM MASSACHUSETTS PURCHASING DEPARTMENT PHASE II RENOVATIONS TO THE FORMER BANKS SCHOOL ELDERLY HOUSING CONDOMINIUMS AND PHASE III RENOVATIONS TO THE FORMER BANKS SCHOOL ELDERLY HOUSING

More information

The addendum consists of six (6) pages of 8½ x 11 text and three (3) 30 x 42 drawings*. End of Addendum 1

The addendum consists of six (6) pages of 8½ x 11 text and three (3) 30 x 42 drawings*. End of Addendum 1 ADDENDUM # ENTRYWAY UPGRADES KILLINGLY INTERMEDIATE SCHOOL 99 UPPER MAPLE STREET DAYVILLE, CT 0 S/P+A PROJECT NO. 8.8 DATE: July, 08 The following changes to the Drawings and Project Specifications shall

More information

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date

ORDINANCE. APPROVED EMERGENCY: (Yes) (No) VETOED: Date ORDINANCE AN ORDINANCE OF THE COMMISSION OF KNOX COUNTY, TENNESSEE RESCINDING ARTICLE III. CABO ONE- AND TWO-FAMILY DWELLING CODE, SEC. 10-56, SEC. 10-57 AND SEC. 10-58 AND ADOPTING THE 2006 INTERNATIONAL

More information

SECTION WATERTIGHTNESS TEST FOR PLANT TANKAGE STRUCTURES

SECTION WATERTIGHTNESS TEST FOR PLANT TANKAGE STRUCTURES SECTION 01 48 00 - WATERTIGHTNESS TEST FOR PLANT TANKAGE STRUCTURES PART 1 - GENERAL 1.1 SCOPE OF WORK A. Furnish all labor, materials and incidentals required and perform tightness testing of water-containing

More information

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17

Division 07 Thermal and Moisture Protection Thermal Protection Blanket Insulation Page 1 of 17 07 21 16 Blanket Insulation Page 1 of 17 Design Number UNI/BI 120-03 FIRE RESISTANT GREASE DUCT Unifrax I LLC FyreWrap Elite 1.5 Duct Insulation CAN/ULC S144 Fire Resistance Rating 2 hours Fire Inside

More information

SECTION FIRE HYDRANTS

SECTION FIRE HYDRANTS SECTION 21 11 10 PART 1. GENERAL 1.1 SUMMARY: A. Work consists of furnishing and installing new fire hydrants, (boot with ductile iron retainer gland, standpipe and hydrant complete) plus constructing

More information

ADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs

ADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs ADDENDUM NUMBER 3 AUGUST 18, 2016 Jackson County Utility Authority Project No. 20150619124 Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs FROM: BURK-KLEINPETER, INC. ENGINEERS, ARCHITECTS, PLANNERS,

More information

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:

SECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows: SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.

More information

Success with Louisiana Energy Code. Techtips for Builders/Trades & Code Officials INSULATION

Success with Louisiana Energy Code. Techtips for Builders/Trades & Code Officials INSULATION Success with Louisiana Energy Code Techtips for Builders/Trades & Code Officials COPYRIGHT 2017 ADVANCED ENERGY. ALL RIGHTS RESERVED VERSION 2015.1.0 PAGE 1 For vented attics, install eave baffles on top

More information

SECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete.

SECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete. SECTION 02720 STORM DRAINAGE SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02221 - Excavating, Backfilling, and Compaction for Utilities. 2. 03300 - Cast-in-place Concrete. 1.02 REFERENCES

More information

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS

SECTION EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS Page 1 of 6 SECTION 08 32 20 EZ-SLIDE 80 AND 180 HEAVY GLASS TOP HUNG SLIDING DOOR SYSTEMS USE THIS SECTION WHEN SPECIFYING OVERHEAD SUPPORTED GLASS PANEL PARTITIONS. SECTION INCLUDES OVERHEAD TRACK ASSEMBLY,

More information

REBECCA LG BOSTICK, ARCHITECTS, INC

REBECCA LG BOSTICK, ARCHITECTS, INC REBECCA LG BOSTICK, ARCHITECTS, INC 703-768-2250 ADDENDUM NO. 3 Page 1 of 4 (plus attachments -2 pages) SILVERBROOK ELEMENTARY SCHOOL RENOVATION Fairfax County Public Schools 9350 Crosspointe Drive, Fairfax

More information

Aluminum Storefront Systems SERIES 200, 300 and 500 DOORS GUIDE SPECIFICATIONS

Aluminum Storefront Systems SERIES 200, 300 and 500 DOORS GUIDE SPECIFICATIONS Aluminum Storefront Systems SERIES 200, 300 and 500 DOORS GUIDE SPECIFICATIONS SECTION 08410 ALUMINUM ENTRANCES AND STOREFRONTS This suggested guide specification has been developed using the current edition

More information

SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida Telephone Fax

SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida Telephone Fax SARASOTA COUNTY GOVERNMENT PROCUREMENT 1660 Ringling Blvd., 3 rd Floor Sarasota, Florida 34236 Telephone 941-861-5266 Fax 941-861-5129 ADDENDUM NO.1 BID # : #153025CS CCSWDC Leachate Lift Station Rehabilitation

More information

Addendum # 1 Perdue Stadium Seating Bowl Improvements Date of Addendum: 09/07/16

Addendum # 1 Perdue Stadium Seating Bowl Improvements Date of Addendum: 09/07/16 Wicomico County Purchasing 125 N. Division St. Room B-3 Salisbury, MD 21801 Ph. 410-548-4805 Fax 410-334-3130 Email: purchasing@wicomicocounty.org Addendum # 1 Perdue Stadium Seating Bowl Improvements

More information

ADDENDUM NO. 2 Consisting of 3 pages and Attachments

ADDENDUM NO. 2 Consisting of 3 pages and Attachments 10404-125 Street, Edmonton, AB. T5N 1T2 Tel: 780.455.5975 Fax: 780.454.2397 info@cdyarchitect.com ADDENDUM NO. 2 Consisting of 3 pages and Attachments PROJECT: Maina Centre Ville Phase II, Beaumont, Alberta

More information

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX BID PACKAGE #1 SITE WORK

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX BID PACKAGE #1 SITE WORK HOSKINS ARCHITECTURE, LLC 1827 1 ST AVENUE NORTH, SUITE 104 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 1 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX BID PACKAGE #1 SITE WORK

More information

REQUEST FOR BIDS FOR REPAIRS SOUTH FEATHER WATER AND POWER AGENCY S MINERS RANCH CONDUIT

REQUEST FOR BIDS FOR REPAIRS SOUTH FEATHER WATER AND POWER AGENCY S MINERS RANCH CONDUIT REQUEST FOR BIDS FOR REPAIRS OF SOUTH FEATHER WATER AND POWER AGENCY S MINERS RANCH CONDUIT Issue date: July 2, Bid Due Date: August 8, 2012 Prepared by: Shawn Hayse, Special Projects Manager Shayse@southfeather.com

More information

City of Tacoma Tacoma Public Utilities Tacoma Power. REQUEST FOR BIDS PG F Alder Lake Park Sewage Treatment Expansion

City of Tacoma Tacoma Public Utilities Tacoma Power. REQUEST FOR BIDS PG F Alder Lake Park Sewage Treatment Expansion City of Tacoma Tacoma Public Utilities Tacoma Power REQUEST FOR BIDS PG14-0667F Alder Lake Park Sewage Treatment Expansion Submittal Deadline: 11:00 a.m., Pacific Time, Tuesday, April 14, 2015 Submittal

More information

Specification Section Storefront Systems has been revised. Omit previously issued Storefront section.

Specification Section Storefront Systems has been revised. Omit previously issued Storefront section. December 28, 2018 ADDENDUM NO. 2 To: Re: Bidders Corey Pitts, NewQuest Properties This Addendum forms a part of the contract documents identified above. Acknowledge the receipt of this Addendum on the

More information

***************************************************************************************************************

*************************************************************************************************************** 02720 STORM DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 40 00. ***************************************************************************************************************

More information

ADDENDUM NUMBER TWO. for SWIM TEAM LOCKER ROOM RENOVATIONS REBID UNIVERSITY OF SOUTH CAROLINA COLUMBIA, SOUTH CAROLINA. DATE OF ISSUE: June 19, 2014

ADDENDUM NUMBER TWO. for SWIM TEAM LOCKER ROOM RENOVATIONS REBID UNIVERSITY OF SOUTH CAROLINA COLUMBIA, SOUTH CAROLINA. DATE OF ISSUE: June 19, 2014 ADDENDUM NUMBER TWO for SWIM TEAM LOCKER ROOM RENOVATIONS REBID UNIVERSITY OF SOUTH CAROLINA COLUMBIA, SOUTH CAROLINA DATE OF ISSUE: June 19, 2014 TO: ALL BIDDERS OF RECORD This Addendum is issued pursuant

More information

SECTION STAINLESS STEEL WALL PANELS

SECTION STAINLESS STEEL WALL PANELS SECTION 07400 PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Dry joint, Rainscreen stainless steel wall panel system. 2. Accessories including attachments, clips, sub girts, shims, and fasteners 3.

More information

ADDENDUM #1 AUGUST 25, INTERSECTION IMPROVEMENTS AT SR 434 AND TUSCORA DRIVE Bid # ITB-06/16/BF

ADDENDUM #1 AUGUST 25, INTERSECTION IMPROVEMENTS AT SR 434 AND TUSCORA DRIVE Bid # ITB-06/16/BF ADDENDUM #1 AUGUST 25, 2016 INTERSECTION IMPROVEMENTS AT SR 434 AND TUSCORA DRIVE Bid # ITB-06/16/BF TO: ALL PLAN HOLDERS This Addendum No. 1 to the Contract Documents for City of Winter Springs project

More information

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications:

The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general specifications: Query No.1 ; we need more specs. about fire resistant doors Answer to Query No. 1: The fire resistance required for doors in this building is 1 (one) hour resistance in compliance with the below general

More information

SECTION SLUICE GATES

SECTION SLUICE GATES SECTION 11100 SLUICE GATES PART 1--GENERAL Fill in the blank with a short description of sluice gate usage, i.e., for isolation of wastewater, or for tank drainage, or for control of water surface. 1.01

More information

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen:

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen: March 6, 2018 Subject: Addendum No. 2 Toyota Park Transit Center Phase II Ladies and Gentlemen: This Addendum No. 2 is being issued to provide responses to questions submitted by potential bidders and

More information

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336) Ricky L. Loman, AIA Architect 603 Summit Avenue, Suite 102 Greensboro, N.C. 27405-7700 Voice/FAX (336) 273-7999 ADDENDUM: Number 1 ISSUED: March 14, 2017 SUBJECT: New Agriculture & Equipment Storage Barn

More information

Installation Instructions

Installation Instructions 20 Minute Positive Pressure Fire Door WH = PP Cat A 1. Doors must be installed in a Listed and Labeled Minimum 22 gauge K-D or welded steel frame, or fire-rated aluminum frame, or fire-rated wood frames.

More information

SECTION RESILIENT SHEET FLOORING

SECTION RESILIENT SHEET FLOORING SECTION 09 65 16 RESILIENT SHEET FLOORING SPEC WRITER NOTE: Delete text between // // not applicable to project. Edit remaining text to suit project. PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1.

More information

Job Order Sewer Repair Services

Job Order Sewer Repair Services Job Order Sewer Repair Services Bid Addendum No. 1 October 10, 2018 All Contractual Requirements as defined within the Contract Documents shall remain in full force to the extent that they are not modified

More information

Baysinger Design Group, Inc West DeYoung Street, Suite 100B Marion, Illinois Ph Fax

Baysinger Design Group, Inc West DeYoung Street, Suite 100B Marion, Illinois Ph Fax 4501 West DeYoung Street, Suite 100B Marion, Illinois 62959 Ph. 618-998-8015 Fax 618-998-8032 Addendum No. 1 to the Bidding Documents For: Toilet Partition Replacement Massac County High School Massac

More information

Addendum No. 1 November 03, 2016

Addendum No. 1 November 03, 2016 Addendum No. 1 November 03, 2016 Project: Location: Bid Date: Liberal Arts Building Entry & Basement Remodel University of Montana University of Montana Campus Liberal Arts Building 136, 32 Campus Drive,

More information

2013 ANNUAL AIRFIELD PAVEMENT REHABILITATION CONTRACT NO ADDENDUM NUMBER TWO. Scope of this Addendum

2013 ANNUAL AIRFIELD PAVEMENT REHABILITATION CONTRACT NO ADDENDUM NUMBER TWO. Scope of this Addendum D E N V E R I N T E R N A T I O N A L A I R P O R T CONTRACT NO. 201208796 ADDENDUM NUMBER TWO Scope of this Addendum Addendum Number Two includes modifications to the following Contract Documents issued

More information

B. Polyethylene samples shall be submitted for Owner approval of color and quality.

B. Polyethylene samples shall be submitted for Owner approval of color and quality. Glass Rail ENGINEERED DASHERBOARD SPECIFICATIONS PART 1 - GENERAL 1.01 PROJECT SCOPE A. Contractor shall furnish and install one complete set of steel framed dasherboards as indicated on the drawings and

More information

DALLAS-FORT WORTH INTERNATIONAL AIRPORT

DALLAS-FORT WORTH INTERNATIONAL AIRPORT DALLAS-FORT WORTH INTERNATIONAL AIRPORT ADDENDUM NO. 2 TO THE REQUEST FOR BIDS Contract No. 9500445 Restroom Rehabilitation at Terminal B (Phase 3 & 4) December 20, 2010 THE REQUEST FOR BIDS (RFB) FOR

More information

SECTION ALL GLASS ENTRANCES. 1. Lock cylinders for tempered glass entrance doors are specified in Division 8 section Finished Hardware.

SECTION ALL GLASS ENTRANCES. 1. Lock cylinders for tempered glass entrance doors are specified in Division 8 section Finished Hardware. 1 SECTION 08 4210 ALL GLASS ENTRANCES PART 1 - GENERAL 1.01 SUMMARY A. This section includes: 1. Vestibule doors matching entrance doors. 2. Sidelites. B. Related work in other sections: 1. Lock cylinders

More information

REVISED MT. SAN ANTONIO COMMUNITY COLLEGE DISTRICT. Addendum No. 1. May 9, 2018 HUMANITIES SOCIAL SCIENCES BUILDING 26 RESTROOM REMODEL Bid No.

REVISED MT. SAN ANTONIO COMMUNITY COLLEGE DISTRICT. Addendum No. 1. May 9, 2018 HUMANITIES SOCIAL SCIENCES BUILDING 26 RESTROOM REMODEL Bid No. REVISED MT. SAN ANTONIO COMMUNITY COLLEGE DISTRICT May 9, 2018 HUMANITIES SOCIAL SCIENCES BUILDING 26 RESTROOM REMODEL To All Bidders: All bidders shall acknowledge receipt of this Addendum on the bid

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011.

K. ASTM F436- Standard Specification for Hardened Steel Washers; 2011. DIVISION 05 METALS 05 12 00 STRUCTURAL STEEL FRAMING PART 1 GENERAL 1.1 SECTION INCLUDES A. Structural steel framing members, support members. 1.2 RELATED REQUIREMENTS A. Section 05 50 00 - Metal Fabrications:

More information

Laney College Childcare Center Renovation 900 Fallon Street Oakland, CA 94607

Laney College Childcare Center Renovation 900 Fallon Street Oakland, CA 94607 LANEY COLLEGE CHILDCARE CENTER RENOVATION DOCUMENT 00 9113 ADDENDA BID NO. 18-19/09 Peralta Community College District Laney College Childcare Center Renovation 900 Fallon Street Oakland, CA 94607 October

More information

RFP/GRC/LSV/ : RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE. Annex A - BILL OF QUANTITIES 1/9

RFP/GRC/LSV/ : RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE. Annex A - BILL OF QUANTITIES 1/9 RFP/GRC/LSV/2017-005: RENOVATION (CIVIL WORKS) OF THR 8th PRIMARY SCHOOL TOILETS IN MYTILENE Annex A - BILL OF QUANTITIES 1/9 The Contractor shall consider in his price all costs or expenses of all requirements

More information

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications Mar/2008 v1.0 SECTION 02255 HYDRAULICLY DRIVEN STEEL UNDERPINNING PILES PART 1 GENERAL 1.01 SCOPE OF WORK The work shall

More information

RIVERSIDE CHURCH OF CHRIST. Lafayette, LA

RIVERSIDE CHURCH OF CHRIST. Lafayette, LA SECTION 000010 INVITATION FOR BIDS Bids for will be received in the office of Church Development Construction Services, 708 S. Rosemont Road, Suite #101,, until 12:00 noon Local Prevailing Time on Friday,

More information