1 Woodbury - Aurora Metro Station Master Utility Report Aurora, Colorado E. Centrepoint Dr. and E. Alameda Dr. Prepared By: Galloway 6162 S. Willow Drive, Suite 32 Greenwood Village, CO POC: Randy Smith RandySmith@GallowayUS.com Job no. WOC2.1 Date: February 19, 216
2 2/19/16 Page 3 of 16 Project Location and Description Water Design Criteria Water Demand Calculations Sanitary Sewer Design Criteria Sanitary Sewer Flow Calculations Conclusion Appendix 1 Water & Sanitary Demand Calculations Appendix 2 Water Model Output Appendix 3 Utility Maps
3 2/19/16 Page 4 of 16 Project Location and Description The proposed Aurora Metro Station development consists of approximately 69-acres of the overall 8 acres of the master Centrepoint development and located in the Northwest Quarter of Section 18, Township 4 South, Range 66 West of the 6 th P.M., in the City of Aurora, Arapahoe County, State of Colorado. The site is bound by East Alameda Parkway on the north, East Center Avenue on the south, South Sable Boulevard on the west and South Chambers Road on the east. The property to be developed is vacant and covered by native grasses. There are four existing developments located within the overall master development. The existing Kaiser Hospital and Village at City Center are adjacent to the site along the south side of East Center Avenue. Arapahoe County site is located at the southeast corner of Alameda Parkway and Alameda Drive. Finally, the RTD Park-n-Ride is located at the northeast corner of South Sable Boulevard and East Centrepointe Drive. Other onsite existing improvements includes a utility corridor in the northwest corner of the site. The utility corridor contains the Sable City Center storm sewer system which is a 96 /18 RCP that crosses under Alameda Pkwy and discharges into City Center Park Detention Pond. There is also an additional 96 CMP that parallels the 96 /18 RCP that conveys on and offsite flows to the City Center Park water quality pond. The utility corridor also contains a 15 sanitary sewer and a 36 waterline. The proposed site is approximately 69 acres in size. Approximately 33-acres of the development will be commercial. Approximately 18-acres will be high density residential and the remainder roadway and landscape tracts.
4 2/19/16 Page 5 of 16 Figure 1 - VICINITY MAP Water Design Criteria All water lines were designed according to City of Aurora and Aurora Water Water, Sanitary Sewer and Storm Drainage Infrastructure as noted below: 1. Water mains will be located a minimum of 1 feet from sanitary and storm sewer pipes. 2. Water lines will be kept a minimum of four feet from the lip of curb except for short distances. 3. Where the road is too narrow for the water line to be 1 feet from the sewer line and 4 feet from the curb, the water line will be located 5 feet east or north of the road center line. The road may be too narrow only at bump outs or similar traffic control devices. 4. The pipe velocity will be between 2 and 1 feet per second during max day demand plus fire flow for 12 mains. 5. The pipe velocity will be between 2 and 15 feet per second during max day demand plus fire flow for 8 mains.
5 2/19/16 Page 6 of Water valves will be located in the main on L-1 of the legs at any tee or cross except fire hydrant laterals. 7. Water valves will be located a minimum of every 75 feet. 8. The maximum day demand plus fire flow results in a residual pressure is greater or equal to 2 psi. 9. The maximum demand residual pressure is greater or equal to 5 psi. 1. Final locations of main line and service stubs, fire hydrants, valves will be determined with the final development plan for each parcel. Water flow peaking factors and infiltration calculations were determined from section 5 of the City of Aurora and Aurora Water Water, Sanitary Sewer and Storm Drainage Infrastructure. Water Demand Calculations Water demand is based off of City of Aurora Standards and Specifications section 1734 Water, Sanitary and Storm Drainage Infrastructure paragraph 5.2. Average Daily Flow was determined using the demand rate table in Paragraph Residential based on 16 Gallons per capita per day Zoning Average Day (gpm/acre) Max Day (gpm/acre) Max Hour (gpm/acre) People per Unit Units Per Acre MH Table 1 RESIDENTIAL WATER DEMAND The above residential table was used Multi-family and Senior Living. The maximum number of units was used when a range of the number of units was provided. Then the number of units was converted to acres based on 4 DU per acre to calculate the specific load. I.e. If a parcel is zoned for 2 to 35 Sr. Units. We used 35 units divided for 4 du / acre to get 8.75 acres. Then 8.75 acres was multiplied by the factors in the above table to calculate the water load. Hotel Water demand was based on the number of rooms times a 1.5 person per room occupancy rate times 16 gal / day / capita. I.e. 112 room hotel times 1.5 person per room 16 gal / day / capita equals and average day flow of 26,88 gal per day.. Commercial Zoning Average Day (gpm/acre-building) Max Day (gpm/acre-building) Max Hour (gpm/acre-building) A/B-* (office / retail) Table 2 COMMERCIAL WATER DEMAND
6 2/19/16 Page 7 of 16 The above commercial table was used for retail and office demand calculations. The office and retail square footages were converted to acres to use the table. Restaurant Restaurant service water demand is based on a conservative estimate of 7 gallons water per seat per day. It was assumed that in a restaurant that there would be one seat per 25 SF of restaurant. This results in a restaurant service water demand rate of 2.8 gallon per SF per day. Peak flow will be based off of 4.5 times the average daily flow. At the time of this report the estimated uses for the development are: Multi Family Senior Living Parcel Retail Office Restaurant Hotel Units Area land Units Area land SF SF SF Rooms AC AC 1 8, 24, , , 18, , 45, 5, , 7 175, 15, Table 3 RESTAURANT WATER DEMAND The resultant domestic flows for each parcel are as follows; Total Water Demand Parcel Avg Max Load Hr gpm gpm Table 4 DOMESTIC WATER DEMAND PER PARCEL
7 2/19/16 Page 8 of 16 Fire Flow Fire flow was calculated based current IFC flow rates. The square footages of each use for each parcel were used to calculate the fire flow required for each parcel. It was assumed all buildings are Type IV or better. We assumed we would only fight one fire at a time. We assumed that each parcel would contain one building with all the uses for the parcel in that one building. This is conservative. When more detailed plans are available some uses may be more decentralized creating more building that in turn could have less fire flow demand. The calculations are included in the two tables below. Restaurant Retail Office Hotel 1 Multifamily 2 Sr. Living 3 Parcel SF SF SF Rooms SF Units SF Units SF 1 8, 24, ,6 2 1, 6 72, 3 11, 18, 25 3, 4 5, 45, 5, 17 24, , , 6 5, 7 175, 15, Total 29, 128, 29, , ,26, , Average Sq. footage Table 5 SQUARE FOOTAGE PER USE PER PARCEL Notes 1. Hotel square footage was estimated at 8 sf per room 2. Multifamily square footage was estimated at 12 sf per room 3. Sr. Living square footage was estimated at 9 sf per room
8 2/19/16 Page 9 of 16 Total Fire Flow Parcel SF Required⁴ w/ Sprinkler Required⁵ 1 122, , , , , , , Total 1,483,717 Table 6 FIRE FLOW PER PARCEL Notes 4. Fire Flows were estimated for Type IV buildings 5. It is assumed that each building will have automatic sprinklers, based on sprinklers the fire flow was reduced to 25% The domestic and fire flows were entered into a Bentley water cad v8i model. For each run of the model one fire flow was activated for each parcel. The resultant flows, velocities and pressures resulted in the pipe sizes indicated in the table below and on the provided utility sheets in appendix 3. Parcel Spine Road Water Pipe Dia (") Table 7 WATER MAIN SIZE Additional water model output is available in appendix 2.
9 2/19/16 Page 1 of 16 Sanitary Sewer Design Criteria All sanitary sewer lines were designed according to City of Aurora and Aurora Water Water, Sanitary Sewer and Storm Drainage Infrastructure as noted below: 1. There are no horizontal or vertical curves on sanitary sewers. 2. Sanitary sewer lines will be located along the road center line. 3. It there is a median the sewer line will be located in the center of the lane closest to the median on the south or west side of the median. 4. Where the road is too narrow for the water line to be 1 feet from the sewer line and 4 feet from the curb, the sewer line will be located 5 feet west or south of the road center line. The road may be too narrow only at bump outs or similar traffic control devices. 5. A Manning s n value of.11 was used for new PVC pipe per Water, Sanitary Sewer and Storm Drainage Infrastructure. 6. A minimum slope of.4% was observed in the design. 7. Minimum slopes were also determined as the greater of.4% or the slope required to achieve a minimum velocity of 2. feet per second. 8. The flow velocity does not exceed 1. feet per second for the full-pipe and halffull-pipe conditions. 9. A minimum of.2 feet drop through the manhole for straight-trough and near straight-through manholes. 1. A minimum of.3 feet drop through the manhole for 45 degree bend or greater manholes. 11. The depth of flow in pipes does not exceed 75% of capacity pipes 12 and smaller and does not exceed 9% for pipes larger than All service line taps will be a minimum of 5 from the outside of the nearest manhole and not in the manholes. 13. Direct service line taps will not be allowed on sewer mains 24 in diameter and larger. 14. Sanitary sewer loading rates are based on the type and density of development. 15. Final locations of main line and service stubs, manholes will be determined with the final development plan for each parcel. Sanitary Sewer flow peaking factors and infiltration calculations were determined from section 5 of the City of Aurora and Aurora Water Water, Sanitary Sewer and Storm Drainage Infrastructure.
10 2/19/16 Page 11 of 16 Sanitary Sewer Design Calculations Sanitary sewer flows are calculated at 5% of water demand flows. Peak flow will be based off of 4.5 times the average daily flow. Based off the water demand calculations the sewer flows for each parcel will be; Total Sanitary Sewer Flow Parcel Avg Max Load Hr gpm gpm Table 8 SANITARY SEWER FLOWS PER PARCEL Pipes were modeled using Bentley stand-alone sewer cad v8i. The max hour flow rate was entered into the pipe model as appropriate. Each flow was increased by 1% for I & I. Parcel 2 and 3 were entered into one outfall together. Parcel 6 and 7 were also entered into one outfall. Because Parcel 5 has two outfalls the flow was increased by 25% and divided into two halves. The resultant flow was entered into each outfall. All pipes were sized to 8 for the initial calculation. All pipes had velocities less than 1 FPS at the 8 diameter. The maximum velocity is 5.1 FPS. The maximum depth of flow is.32 feet. The maximum percent flow capacity is 35.1%. Detailed results are available in the appendix. Conclusion The water and sanitary sewer system design will meet the City of Aurora design standards.
11 2/19/16 Page 12 of 16 Appendix 1 - Water & Sanitary Demand Calculations Retail Water Demand Parcel SF Demand Avg Load Peak Day Max Hr Avg Day gpm/sf gpm gpm gpm gpd 1 8, 4.13E , 4.13E , 4.13E , 4.13E E E , 4.13E ,413 Total 29, 4.13E-5 Based on SF Office Water Demand Parcel SF Demand Avg Load Peak Day Max Hr Avg Day gpm/sf gpm gpm gpm gpd E E , 4.13E , , 4.13E , E , 4.13E , , 4.13E Total 128, 4.13E-5 Based on SF Restaurant Service Water Demand Parcel SF Demand Avg Load Peak Day Max Hr Avg Day gpm/sf gpm gpm gpm gpd 1 24,8 1.94E , E E , 1.94E , E E E Total 29,8.194 Based on SF
12 2/19/16 Page 13 of 16 Hotel Water Demand Parcel Rooms Demand Avg Load Peak Day Max Hr Avg Day gpm/sf gpm gpm gpm gpd , Total Based on Rooms Multi Family Parcel units Demand Avg Load Peak Day Max Hr Avg Day gpm/ac gpm gpm gpm gpd , , , , Total Based on area Sr Living Parcel Units Demand Avg Load Peak Day Max Hr Avg Day gpm/ac gpm gpm gpm gpd , Total Based on area
13 2/19/16 Page 14 of 16 Parcel Total Water Demand Parcel Total Sanitary demand Parcel Avg Load Peak Day Max Hr Avg Day Avg Load Peak Day Max Hr Avg Day gpm gpm gpm gpd gpm gpm gpm gpd , , , , , , , , , , , , , ,653 Total 466, ,329
14 2/19/16 Page 15 of 16 Appendix 2 - Water Model Output
15 ALAMEDA AVE SABLE BLVD ALAMEDA AVE CHAMBERS RD CENTREPOINT DR CENTER AVE Aurora Metro Station 216. Galloway & Company, Inc. All rights reserved. SCALE : 1" = 5'-"
16 Fire Flow Node FlexTable: Fire Flow Report J-11 J4 J2&3 J5 J6 J7 Label Fire Flow (Needed) (gpm) 2, 3,313 2, 1, 1,938 Flow (Total Needed) (gpm) 2,198 3,651 2,617 1,9 1,973 Flow (Total Available) (gpm) 3,5 3,698 3,839 4,117 3,59 3,535 Pressure (Calculated Residual) (psi) Pressure (Calculated System Lower Limit) (psi) Junction w/ Minimum Pressure (System) J5 J5 J5 J6 J5 J5 Velocity of Maximum Pipe (ft/s) Pipe w/ Maximum Velocity P-11 P-14 P-22 P-33 P-35 P-38 WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 1 of 1
17 FlexTable: Junction Table J-11 J4 J2&3 J5 J6 J7 Label Elevation (ft) 5, , , , ,51.5 5,481.9 Demand (gpm) Hydraulic Grade (ft) 5, , , , , , Pressure (psi) Pressure (Calculated Total Flow Needed) (psi) Velocity of Maximum Pipe (ft/s) WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 1 of 1
18 FlexTable: Pipe Table P-11 P-13 P-14 P-21 P-22 P-33 P-34 P-35 P-36 P-37 P-38 Label Length (Scaled) (ft) Diameter (in) PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC PVC Material Start Node R-1 J-11 J4 J-11 J2&3 R-2 J5 R-3 J6 R-5 J7 Stop Node J-11 J4 R-7 J2&3 R-2 J5 R-3 J6 R-4 J7 R-6 Flow (gpm) Velocity (Maximum) (ft/s) Headloss (ft) WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 1 of 1
19 Project Inventory: WOC2.1_P_UTIL WaterCAD Water.wtg Title Engineer Company Date Notes Scenario Summary ID Label Notes Active Topology Physical Demand Initial Settings Operational Age Constituent Trace Fire Flow Energy Cost Transient Pressure Dependent Demand Failure History SCADA User Data Extensions Calculation Options Label Calculation Options Label 2/17/ Fire Flow Base Active Topology Base Physical Base Demand Base Initial Settings Base Operational Base Age Base Constituent Base Trace Base Fire Flow Base Energy Cost Base Transient Base Pressure Dependent Demand Base Failure History Base SCADA Base User Data Extensions New Steady State/EPS Solver - 1 Base Calculation Options Network Inventory Pipes 11 Variable Speed Pump Batteries Junctions 6 PRV's Hydrants PSV's Tanks PBV's Reservoirs 7 FCV's WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 1 of 2
20 Project Inventory: WOC2.1_P_UTIL WaterCAD Water.wtg Network Inventory Customer Meters 6 TCV's SCADA Elements GPV's Pumps Isolation Valves Pump Stations Spot Elevations Transient Network Inventory Turbines Rupture Disks Periodic Head-Flows Discharges to Atmosphere Air Valves Orifices Between Pipes Hydropneumatic Tanks Valves With Linear Area Change Surge Valves Surge Tanks Check Valves Pressure Pipes Inventory 8. (in) 1,524 ft All Diameters 4,523 ft 12. (in) 2,999 ft WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 2 of 2
21 FlexTable: Reservoir Table R-1 R-2 R-3 R-4 R-5 R-6 R-7 Label Flow (Out net) (gpm) Hydraulic Grade (ft) 5, , , , , , ,712.4 WOC2.1_P_UTIL WaterCAD Water.wtg 2/19/216 Bentley Systems, Inc. Haestad Methods Solution Center 27 Siemon Company Drive Suite 2 W Watertown, CT 6795 USA Bentley WaterCAD V8i (SELECTseries 5) [ ] Page 1 of 1
22 2/19/16 Page 16 of 16 Appendix 3 Utility Maps
23 W WM WM C 214. Galloway & Company, Inc. All Rights Reserved PARCEL SCALE: 1"=1' UT-1 PARCEL 4 NOT FOR CONSTRUCTION PARCEL 2 PARCEL 3 COPYRIGHT THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF THE ARCHITECT, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED. UT-2 12" DIP PARCEL 7A PARCEL 7B UT-4 SA PARCEL 5A UT-3 PARCEL 7C # PARCEL 6 PARCEL 5B
24 C 214. Galloway & Company, Inc. All Rights Reserved SCALE: 1"=4' PROPOSED 12" COPYRIGHT NOT FOR CONSTRUCTION THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF THE ARCHITECT, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED MATCHLINE STA SEE SHEET UT-2 PROPOSED 12" #
25 C 214. Galloway & Company, Inc. All Rights Reserved W SEE SHEET UT-1 MATCHLINE STA MATCHLINE SEE SHEET UT-3 PROPOSED 12" PROPOSED 12" " DIP SCALE: 1"=4' COPYRIGHT # NOT FOR CONSTRUCTION THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF THE ARCHITECT, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED.
26 SEE SHEET UT-2 MATCHLINE PROPOSED 12" PROPOSED 12" SEE SHEET UT-4 MATCHLINE STA SCALE: 1"=4' 196+ C 214. Galloway & Company, Inc. All Rights Reserved COPYRIGHT NOT FOR CONSTRUCTION THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF THE ARCHITECT, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED. #
27 C 214. Galloway & Company, Inc. All Rights Reserved SCALE: 1"=4' NOT FOR CONSTRUCTION COPYRIGHT THESE PLANS ARE AN INSTRUMENT OF SERVICE AND ARE THE PROPERTY OF THE ARCHITECT, AND MAY NOT BE DUPLICATED, DISCLOSED, OR REPRODUCED WITHOUT THE WRITTEN CONSENT OF THE ARCHITECT. COPYRIGHTS AND INFRINGEMENTS WILL BE ENFORCED AND PROSECUTED MATCHLINE STA SEE SHEET UT # 193+
KUM & GO 300 SUBDIVISION THORNTON, COLORADO
FINAL UTILITY STUDY KUM & GO 300 SUBDIVISION THORNTON, COLORADO PREPARED FOR: KUM & GO, L.C. 6400 WESTOWN PARKWAY WEST DES MOINES, IOWA 50266 PH: (515) 457-6232 CONTACT: RYAN J. HALDER PREPARED BY: OLSSON
More informationPlaza Mexico Residences 3000 E Imperial Highway Lynwood, CA KPFF Job #
WATER AND SANITARY SEWER STUDY Plaza Mexico Residences 3000 E Imperial Highway Lynwood, CA KPFF Job # 1600800 October 16, 2017 PREPARED BY: KPFF Consulting Engineers 700 S Flower Street, Suite 2100 Los
More informationPRELIMINARY DRAINAGE STUDY REPORT ARBOR VILLAS
PRELIMINARY DRAINAGE STUDY REPORT FOR CARSON CITY, NEVADA Prepared for: Capstone Communities 9441 Double Diamond Pkwy #14 Reno, Nevada 89521 Prepared by: Manhard Consulting Ltd. 985 Double R Boulevard
More informationDR DRAINAGEWAY THORNTON VALLEY SUBDIVISION OVERALL DEVELOPMENT PLAN & CONCEPTUAL SITE PLAN SWC OF COLO BLVD & THORNTON PKWY THORNTON, CO
/CONCEPTUAL SITE PLAN TRACT A, THORNTON VALLEY FILING NO. 1 LOCATED IN THE NE 1/4 OF SEC. 24, T. 2 S., R. 68 W., OF THE 6TH P.M., CITY OF UNTY OF ADAMS, STATE OF COLORADO Planning. Architecture. Engineering.
More informationRE: Final Drainage Letter: Northwest Aurora Alley Improvements 2016
April 12, 2016 Mr. Craig Perl, P.E. Senior Engineer City of Aurora Public Works Department 15151 E. Alameda Parkway Aurora, CO 80012 RE: Final Drainage Letter: Northwest Aurora Alley Improvements 2016
More information100-yr Design Runoff (cfs) Basin ID 103b A a B B C Totals
PROPOSED DEVELOPMENT The drainage for this site has been designed to be less than the maximum allowable runoff from each basin as stated in the Overall Rigden Farm drainage plan. Table 1 compares the actual
More informationENGINEERING REVIEW CHECKLIST City of Mount Clemens
(To be completed by the Developer s & Submitted with ing Plans) DATE: PROJECT NAME: Site Plan Approved: Date DESIGN ENGINEERING COMPANY: ing Company Contact Information: Name: Phone: Email: Owner Contact
More informationSection 7 Hydraulic Model Development and Evaluation Criteria
Section 7 Hydraulic Model Development and Evaluation Criteria The hydraulic evaluation conducted to develop this master plan was performed using a computer model of the reclaimed water distribution system.
More informationJanuary 20, Nate Hatleback Project Manager, City of Thornton Development Engineering 9500 Civic Center Drive Thornton, CO (303)
January 20, 2017 Nate Hatleback Project Manager, City of Thornton Development Engineering 9500 Civic Center Drive Thornton, CO 80229 (303) 538-7694 RE: Riverdale Five Retail Drainage Conformance Letter
More informationCity of Fort Collins. Spring Creek Place (2105 South College Avenue) Preliminary Drainage Report
City of Fort Collins Spring Creek Place (2105 South College Avenue) Preliminary Drainage Report OCTOBER 2016 VERSION 3 Prepared By: 4582 South Ulster Street, Suite 1500 Denver, CO 80237 Daniel L. Skeehan,
More informationCITY OF ANAHEIM SEWER DESIGN MANUAL
CITY OF ANAHEIM CITY OF ANAHEIM DEPARTMENT OF PUBLIC WORKS SUBDIVISION SECTION SEWER DESIGN MANUAL TABLE OF CONTENTS 1. SIZING... 2 Design flows:... 2 Roughness coefficient (n):... 2 Velocity (Average
More informationMENIFEE VALLEY CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO COMMUNITY COLLEGE DISTRICT. Appendices
MENIFEE VALLEY CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO COMMUNITY COLLEGE DISTRICT Appendices Appendix J Utility Systems Data February 2017 MENIFEE VALLEY CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO
More informationSection 9 Distribution System Analysis
Section 9 Distribution System Analysis This section presents the analysis of the City of Sunnyside s (City) distribution system. Hydraulic modeling was performed to evaluate the adequacy of existing facilities
More informationContact the Jurisdictional Engineer for materials allowed by each jurisdiction.
Design Manual Chapter 3 - Sanitary Sewers 3C - Facility Design 3C-1 Facility Design A. Capacity of Pipe Pipe sizes 15 inches and smaller should carry the peak flow at a depth of no more than 0.67 of the
More informationAPPENDIX P WATER SUPPLY CONCEPT REPORT
APPENDIX P WATER SUPPLY CONCEPT REPORT Engineer s Report Sewage Water Supply Collection Concept & Treatment Report Blue Point Overlay Conservation District 191-0 Blue Point Road Development District Town
More informationProject: Developer/Designer: Reviewer:
City of Charlottesville, Virginia Engineering Plan Review Checklist (Site Plans, Site Plan Amendments, and Major Subdivisions) 610 East Market Street, Charlottesville, VA 22902 Telephone 434-970-3182;
More informationPermit for Construction of an Extension to a JEA Drinking Water Distribution System and/or JEA Wastewater Collection/Transmission System
Permit for Construction of an Extension to a JEA Drinking Water Distribution System and/or JEA Wastewater Collection/Transmission System INSTRUCTIONS: This form shall be completed and submitted (in duplicate)
More informationUNIFORM DESIGN AND CONSTRUCTION STANDARDS FOR EXTENDING WATER DISTRIBUTION SYSTEMS SECTION 2 DESIGN STANDARDS
UNIFORM DESIGN AND CONSTRUCTION STANDARDS FOR EXTENDING WATER DISTRIBUTION SYSTEMS SECTION 2 DESIGN STANDARDS DESIGN STANDARDS SECTION 2 INDEX ITEM DESCRIPTION 2.00 GENERAL STATEMENT 2.01 WATER DISTRIBUTION
More informationAPPENDIX B. WSSC Design Criteria for Water Distribution Systems
a. System Requirements ) Pressure Requirements APPENDIX B WSSC Design Criteria for Water Distribution Systems a) The water distribution system shall have adequate capacity to supply domestic demand to
More informationContents. Drainage Analysis: Hunters Trace, Westpointe, and Hunters Creek
Drainage Analysis: Hunters Trace, Westpointe, and Hunters Creek Contents SITE LOCATION / DESCRIPTION... 3 WESTPOINTE STORMWATER MANAGEMENT PLAN... 3 THE ENCLAVE AT WESTPOINTE DETENTION POND... 3 Table
More informationADDENDUM # 3 DATE: February 16, 2018
ADDENDUM # 3 DATE: February 16, 2018 REFERENCE: Invitation for Bid No.: S-LB-18607 IFB Issue Date: January 25, 2018 Title: Stonewall Middle School Addition and Renovations Architect/Engineer: Architecture
More informationThis is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.
COACHELLA VALLEY WATER DISTRICT DOMESTIC WATER CHECKLIST Tract/Parcel No: Project Common Name: Developer: Engineer: Engineer Signature: Date: Phone: Phone: Print: This is only a general checklist; please
More informationCOMPUTER APPLICATIONS HYDRAULIC ENGINEERING
- 7535 COMPUTER APPLICATIONS IN HYDRAULIC ENGINEERING Connecting Theory to Practice Fifth Edition HAESTAD PRESS Table of Contents Revision History Foreword CHAPTER 1 BASIC HYDRAULIC PRINCIPLES 1 1.1 General
More informationThe site slopes generally from the southwest to northeast at approximately 3.7 percent.
March 3, 2017 Nate Hatleback Project Manager, City of Thornton Development Engineering 9500 Civic Center Drive Thornton, CO 80229 (303) 538-7694 RE: Riverdale Five Retail Drainage Conformance Letter Dear
More informationPRELIMINARY WASTEWATER CAPACITY STUDY
PRELIMINARY WASTEWATER CAPACITY STUDY Tentative Tract Map No. 18955 CITY OF HESPERIA Prepared for: HESPERIA VENTURES I, LLC 10410 Roberts Road Calimesa, CA 92320 Tel (714) 785 2381 Mr. John Ohanian Prepared
More informationAPPENDIX M VANDEN MEADOWS PROJECT WATER MODELING STUDY AND TECHNICAL MEMORANDUM
APPENDIX M VANDEN MEADOWS PROJECT WATER MODELING STUDY AND TECHNICAL MEMORANDUM TECHNICAL MEMORANDUM Date: March 16, 2011 FROM: Victor M. Alaniz, P.E. Nolte Associates, Inc. 2495 Natomas Park Drive, Fourth
More informationFREELAND WATER & SEWER DISTRICT BERCOT ROAD INTERTIE STUDY
FREELAND WATER & SEWER DISTRICT ISLAND COUNTY WASHINGTON BERCOT ROAD INTERTIE STUDY G&O #13507 NOVEMBER 2013 FREELAND WATER & SEWER DISTRICT ISLAND COUNTY WASHINGTON BERCOT ROAD INTERTIE STUDY G&O #13507
More informationEPANET. Ivan Solinas
EPANET Ivan Solinas agronomi@gmail.com The Irrigation Questions How to irrigate How much to irrigate When to Irrigate Pressurized pipe network What is EPANET EPANET is a computer program that performs
More informationCHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN
CHECKLIST FOR STREETS, INLETS, I. STREET CLASSIFICATION AND DESIGN CRITERIA A. Determine drainage classification for the roadway section using Table 7-1 or Table 7-2. B. Determine the allowable flow depth
More informationM E M O R A N D U M. Date: January 31, Bjorn Schrader, Abramson Teiger Architects. Kimley-Horn and Associates, Inc.
M E M O R A N D U M Date: January 31, 2017 To: From: Subject: Bjorn Schrader, Abramson Teiger Architects Kimley-Horn and Associates, Inc. 8888 Washington - Utility Memorandum Introduction Kimley-Horn and
More informationSECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES
SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES 4.1 GENERAL REQUIREMENTS 4.1.1 Water and fire protection distribution facilities are to be provided solely for the purpose of supplying potable
More informationI - 15 CORRIDOR CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO COMMUNITY COLLEGE DISTRICT. Appendices
I - 15 CORRIDOR CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO COMMUNITY COLLEGE DISTRICT Appendices Appendix J Utility Systems Data August 2017 I - 15 CORRIDOR CAMPUS MASTER PLAN DRAFT EIR MT. SAN JACINTO
More informationSection V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES
Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES A. GENERAL 1. The following water system design guidelines are based on Federal, State and local health requirements and the Hilton Head No. 1 Public
More informationOVERALL UTILITY PLANS 1. Provide a typical section depicting the roadway (proposed/future), utility locations, and separation for
OVERALL UTILITY PLANS 1. Provide a typical section depicting the roadway (proposed/future), utility locations, and separation for all roadways. Identify utility locations/separations from gutter lip and
More information1.1 Purpose of Study Project Description Related Studies Sewage Flows Gravity Sewers...
Preliminary Wastewater Facilities Plan for Alberhill Villages April 2015 TABLE OF CONTENTS Section Name Page Number Section 1 - Introduction 1.1 Purpose of Study... 1-1 1.2 Project Description... 1-1 1.3
More informationTable of Contents. 3.1 Source Capacity Analysis
Table of Contents 3.1 Source Capacity Analysis... 3-1 3.1.1. Design Criteria... 3-1 3.1.2. Source Capacity Evaluation... 3-1 3.1.2.1 Plateau Zone... 3-1 3.1.2.2 Cascade View Zone... 3-4 3.2 Storage Capacity
More informationSUBDIVISION IMPROVEMENT PLANS FORM
Page 1 of 9 CITY OF CONROE SUBDIVISION IMPROVEMENT PLANS CHECKLIST SUBMIT THREE FINAL SETS OF PLANS (maximum size 24 X36 ), OTHER ITEMS LISTED, AND THIS COMPLETED, CERTIFIED CHECKLIST TO THE ENGINEERING
More informationENGINEERING REPORT WATER SUPPLY
PROPOSED RESIDENTIAL DEVELOPMENT, CORAL SPRINGS TRELAWNY FCS #: 1124/76/C ENGINEERING REPORT WATER SUPPLY PREPARED FOR Gore Developments Limited 2c Braemar Ave, Kingston 10 FEBRUARY 2012 1 TABLE OF CONTENTS
More informationIntroduction to Storm Sewer Design
A SunCam online continuing education course Introduction to Storm Sewer Design by David F. Carter Introduction Storm sewer systems are vital in collection and conveyance of stormwater from the upstream
More informationSITE SERVICING PRELIMINARY DESIGN BRIEF
855 Carling Avenue Proposed Redevelopment SITE SERVICING PRELIMINARY DESIGN BRIEF March 2010 March 23, 2010 RVA 081785 Arnon Corporation 1801 Woodward Dr. Ottawa, ON K2C 0R3 Attention: Mike Casey Re: 855
More informationCITY OF MELISSA MANUAL FOR THE DESIGN OF WATER AND SANITARY SEWER LINES
CITY OF MELISSA MANUAL FOR THE DESIGN OF WATER AND SANITARY SEWER LINES SECTION A NOTES TO ENGINEERS This manual is intended to aid and assist private engineers in the layout and design of sanitary sewers
More informationCHAPTER 4 HYDRAULIC ANALYSIS
CHAPTER 4 HYDRAULIC ANALYSIS This chapter presents information on the computer hydraulic model of the City s water system and the results of hydraulic analyses. The purpose of the hydraulic analysis is
More informationSYSTEM ID: KY 10 NARRATIVE DESCRIPTION
SYSTEM ID: KY 10 NARRATIVE DESCRIPTION KY 10 is primarily a branched system in Kentucky with the following assets: 13 Tanks, 13 Pumps, 1 Water Treatment Plant, and approximately 1353879 feet of pipe. KY
More informationChapter 9 Sanitary Sewers
Chapter 9 Sanitary Sewers I:\AD\030\U30\U30009.docx 4-8-16 Section 9.1 Topic General Requirements Chapter 9 Sanitary Sewers Page 9-1 9.2 Plan Submittals 9-1 9.3 Determination of Flow 9-1 9.4 Facility Design
More informationKEYSTONE EMPLOYMENT AND ECONOMIC PLAN STUDY
SUPPLEMENTAL NARRATIVE For the KEYSTONE EMPLOYMENT AND ECONOMIC PLAN STUDY Borough of Pottstown & West Pottsgrove Township Montgomery County, PA Prepared for: Pottstown Area Industrial Authority 152 East
More informationTOWN OF MANCHESTER PLANNING AND ZONING COMMISSION Subdivision Application Minimum Submission Requirements
TOWN OF MANCHESTER PLANNING AND ZONING COMMISSION Subdivision Application Minimum Submission Requirements This checklist is to be completed and submitted with all Subdivision Applications. The Town reserves
More informationSYSTEM ID: KY 3 NARRATIVE DESCRIPTION
SYSTEM ID: KY 3 NARRATIVE DESCRIPTION KY 3 is primarily a grid system in Kentucky with the following assets: 3 Tanks, 5 Pumps, 1 Water Treatment Plant, and approximately 277,022 feet of pipe. KY 3 provides
More informationINSTRUCTIONS FOR FILLING OUT APPLICATION FOR CONCURRENCY ANALYSIS, POTABLE WATER, RECLAIMED WATER AND / OR WASTEWATER SERVICE
INSTRUCTIONS FOR FILLING OUT APPLICATION FOR CONCURRENCY ANALYSIS, POTABLE WATER, RECLAIMED WATER AND / OR WASTEWATER SERVICE APPLICATION MUST BE TYPED OR HAND LETTERED IN INK AND SUBMITTED WITH A REVIEW
More informationSEWER SYSTEM DESIGN GUIDELINES
SEWER SYSTEM DESIGN GUIDELINES PART 1 GENERAL 1.1 GENERAL GUIDELINES A. The following sewer system design guidelines are based on Federal, State and Local health requirements, and the Berkeley County Water
More informationHaestad Solutions. Bentley Systems Incorporated Haestad Solution Center Watertown, CT Toll-free: Fax:
1 Haestad Solutions Bentley Systems Incorporated Haestad Solution Center Watertown, CT 06795 Toll-free: 1-800-727-6555 Fax: 203-597-1488 www.bentley.com/www.haestad.com Who was Haestad Methods? World Leader
More informationMontara Water and Sanitary District 2011 New Customer CIP and Water Capacity Charge. Presentation to Board April 21, 2011
Montara Water and Sanitary District 2011 New Customer CIP and Water Capacity Charge Presentation to Board April 21, 2011 PRESENTATION OUTLINE Master Plan Overview Purpose and Approach Supply and Demand
More informationTABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 115 WATER DISTRIBUTION SYSTEM GENERAL SIZING LINES 115.
TABLE OF CONTENTS PART III MINIMUM DESIGN STANDARDS Section 115 WATER DISTRIBUTION SYSTEM SECTION TITLE PAGE 115.1 GENERAL 115.1 115.2 SIZING LINES 115.1 115.3 DISTRIBUTION SYSTEM 115.2 115.3.1 Layout
More informationDecember 6, Nate Hatleback Project Manager City of Thornton 9500 Civic Center Drive Thornton, CO 80229
December 6, 2016 Nate Hatleback Project Manager City of Thornton 9500 Civic Center Drive Thornton, CO 80229 RE: Drainage Conformance Letter Hilton Garden Inn @ The Grove The Grove Filing No 1, lot 5E Thornton,
More informationPRELIMINARY MUNICIPAL SERVICING REPORT NORTHWOODS SUBDIVISION. Prepared for: North Grassie Properties Inc.
PRELIMINARY MUNICIPAL SERVICING REPORT SUBDIVISION Prepared for: North Grassie Properties Inc. Prepared by: Stantec Consulting Ltd. 905 Waverley St. Winnipeg, MB R3T 5P4 July 2012 File: 116808030 SUBDIVISION
More informationPROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M BANK STREET CITY OF OTTAWA SERVICEABILITY REPORT
PROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M 62 667 BANK STREET CITY OF OTTAWA SERVICEABILITY REPORT REPORT R 816 41A (Rev. 2) MARCH 2017 T.L. MAK ENGINEERING CONSULTANTS LTD.
More informationPROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT SHOPPERS DRUG MART. January 2016
The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG
More informationUTILITIES CHECKLIST CITY OF CHESAPEAKE DEPARTMENT OF PUBLIC WORKS SUBDIVISION NAME: A/C & TAX MAP PARCEL NOS (13 DIGITS) DEVELOPER:
UTILITIES CHECKLIST CITY OF CHESAPEAKE DEPARTMENT OF PUBLIC WORKS SUBDIVISION NAME: A/C & TAX MAP PARCEL NOS (13 DIGITS) DEVELOPER: REVIEWING ENGINEER: WATERSHED (INCLUDE SUBSCRIPT) I. PRELIMINARY ITEMS
More informationTOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK
TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK COST EVALUATION FOR ROLLING HILLS AREA WATER MAIN EXTENSION PROFESSIONAL CONSULTING, LLC. Octagon 10, Office Center 1719 Route 10, Suite 225 Parsippany,
More informationSummary of Detention Pond Calculation Canyon Estates American Canyon, California
July 15, 2015 Bellecci & Associates, Inc Summary of Detention Pond Calculation Canyon Estates American Canyon, California 1. Methodology: Method: Unit Hydrograph Software: Bentley Pond Pack Version 8i
More informationAppendix 13. Haymeadow Raw Water irrigation System Basis of Design
Appendix 13 Haymeadow Raw Water irrigation System Basis of Design 28 MEMORANDUM TO: FROM: Brandon Cohen, Scott Schlosser Brendon Langenhuizen, PE & David M. Kotz, PE DATE: September 13, 2018 RE: Haymeadow
More informationAppendix J Conceptual Design of Watermain and Sanitary Sewer
City of Barrie - Hewitt's Secondary Plan Class Environmental Assessment (Phase 3 and 4) Study Environmental Study Report Appendix J Conceptual Design of Watermain and Sanitary Sewer Hatch 2017 All rights
More informationCHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL
CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL INTRODUCTION The District developed a hydraulic model of the sanitary sewer system as part the 2000 Wastewater Comprehensive Plan. The output from this model
More informationIn general, the City will not approve a development which cannot be served by extensions to the City s wastewater collection system.
6. WASTEWATER SYSTEM 6.1 General: The design and construction of the wastewater collection system to serve the development shall be in accordance with good engineering principles, these Standards of Design,
More informationCONSTRUCTION PLANS FOR ENTERPRISE RENTAL CAR
CONSTRUCTION PLANS FOR VICINITY MAP (NOT TO SCALE) DEVELOPER/OWNER: CHRISTOPHER SLOVAN ENTERPRISE HOLDINGS, INC. 284 MALLORY STATION RD, SUITE 120 FRANKLIN, TN 37067 PH: 615-309-9621 DAVIDSON CO., TENNESSSEE
More informationReport. Lake Water Supply Hydraulic Modeling. Village of. Lindenhurst, IL. April 2012
Lake Water Supply Hydraulic Modeling Report Village of Lindenhurst, IL April 2012 R:\MAD\Documents\Reports\Archive\2012\Lindenhurst, IL\Lake Water Supply.HM.1290.039.mjf.jan\Report\!Front Cover (Blue=Water)
More informationPRESSURIZED IRRIGATION SYSTEM MASTER PLAN
PRESSURIZED IRRIGATION SYSTEM MASTER PLAN (HAL Project No.: 314.04.100) FINAL REPORT January 2009 ACKNOWLEDGMENTS Successful completion of this study was made possible by the cooperation and assistance
More informationNovember 21, City of Thornton 9500 Civic Center Drive Thornton, CO (303) RE: Maverik Thornton, CO - Drainage Report
November 21, 2016 City of Thornton 9500 Civic Center Drive Thornton, CO 80229 (303) 538-7295 RE: Maverik Thornton, CO - Drainage Report As per your request, we are submitting to you the drainage report
More informationRETAIL UNITS GUELPH. November Prepared For: File No Engineering Report.docx F: (905) P: (905) BURLINGTON, ONTARIO
The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED COMMERCIAL RETAIL UNITS GUELPH LINE AND UPPER MIDDLE
More informationDESIGN CRITERIA AND STANDARD DRAWINGS FOR WATER AND SEWER FACILITIES
SANTA MARGARITA WATER DISTRICT DESIGN CRITERIA AND STANDARD DRAWINGS FOR WATER AND SEWER FACILITIES SANTA MARGARITA WATER DISTRICT 26111 Antonio Parkway Rancho Santa Margarita, California 92688 (949) 459-6655
More information3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES
3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES All sanitary sewers shall be designed in accordance with these Design Standards, LBWD Rules and Regulations, and to accepted engineering principles. In
More informationCITY OF SASKATOON DESIGN AND DEVELOPMENT STANDARDS MANUAL SECTION FOUR WATER DISTRIBUTION SYSTEM
CITY OF SASKATOON DESIGN AND DEVELOPMENT STANDARDS MANUAL SECTION FOUR WATER DISTRIBUTION SYSTEM 2018 TABLE OF CONTENTS Section Four Water Distribution System SECTION PAGE NUMBER 1. Objective...1 2. Submissions
More informationINFRASTRUCTURE FINANCING PLAN FOR THE WOODGLEN SPECIFIC PLAN
FINAL REPORT INFRASTRUCTURE FINANCING PLAN FOR THE WOODGLEN SPECIFIC PLAN Prepared for: City of Modesto Prepared by: Willdan Financial Services Approved by Modesto City Council on July 9, 2013 Resolution
More informationSection 7 Design Criteria Irrigation and Drainage Facilities
Section 7 Design Criteria Irrigation and Drainage Facilities 7.1 Background The Irrigation and Drainage system is comprised of the Coachella Branch of the All-American Canal (Coachella Canal), Protective
More informationSAWS WATER PROJECTS MODELING CRITERIA GUIDELINES
SAWS WATER PROJECTS MODELING CRITERIA GUIDELINES July 2016 2800 U.S. Highway 281 North San Antonio, Texas 78212 Modeling Criteria Guidelines, July 2016 TABLE OF CONTENTS MODELING CRITERIA GUIDELINES FOR
More informationSECTION 2 - DESIGN STANDARDS FOR GRAVITY SANITARY SEWERS
SECTION 2 - DESIGN STANDARDS FOR GRAVITY SANITARY SEWERS 2.1. General Requirements Sanitary sewers are to be provided solely for the removal of sanitary waste. Under no circumstances shall any roof drains,
More informationAppendix One MASTER DRAINAGE REPORT
Appendix Appendix One. Master Drainage Report Two. Master Utility Report Three. FAA Forecast Approval Letter Four. Study Committee Notes MASTER PLAN UPDATE REGIONAL AIRPORT Appendix One MASTER DRAINAGE
More informationPresentation Summary. What, Why, and How. Building the Model. Facility Data Acquisition. Model Calibration. Real World Applications/Case Studies
Uday Khambhammettu Randolph Rostas VA AWWA Presentation Summary What, Why, and How Building the Model Facility Data Acquisition Model Calibration Real World Applications/Case Studies Model Maintenance
More informationSECTION WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA
SECTION 6900 - WATER MAINS CITY OF LEE S SUMMIT, MISSOURI DESIGN CRITERIA 6901 DESIGN CRITERIA A. General 1. The design standards presented in the City of Lee's Summit Design Criteria are the minimum standards
More informationCOLLIER COUNTY Growth Management Department
COLLIER COUNTY Growth Management Department July 07, 2015 Josh Fruth Davidson Engineering, Inc Suite 201 4365 Radio Rd Naples, FL 34104 EMAIL - Josh@DavidsonEngineering.Com; jessica@davidsonengineering.com
More informationSewer Modeling of Near- Term Development Technical Memorandum
Sewer Modeling of Near- Term Development City of Reedley, CA March 8, 2018 Page Intentionally Blank The City of Reedley (City) is anticipating near-term developments to the north of the City s currently
More informationCONSTRUCTION PLAN REVIEW CHECKLIST FOR PRIVATE DEVELOPMENT
ADDITION NAME: City of Grapevine, Texas CONSTRUCTION PLAN REVIEW CHECKLIST FOR PRIVATE DEVELOPMENT Updated April 16, 2018 Public Works Department Engineering Division 200 South Main Street Grapevine, Texas
More informationCITY OF PANAMA CITY BEACH Utilities Administration & Engineering Offices 116 South Arnold Road Panama City Beach, FL 32413
Page: 1 of 5 CITY OF PANAMA CITY BEACH Utilities Administration & Engineering Offices 116 South Arnold Road Panama City Beach, FL 32413 COMMERCIAL/RESIDENTIAL UTILITY PLAN COMPLETENESS CHECK LIST Updated
More informationUtilities are constantly striving to
Comprehensive Approach to Increase Effectiveness & Efficiency of Flushing Programs Using Latest Hydraulic & Water Quality Monitoring Tools Kelcia D. Mazana, Edward H. Talton Jr., and C. Robert Reiss Utilities
More informationEl Margarita Development Analysis
303 Second Street, Suite 300 South San Francisco, California 94107 415-243-2150 FAX: 415-896-0999 El Margarita Development Analysis 28 January 2015 Prepared for City of Yuba City 1201 Civic Center Boulevard
More informationPART V - STORM DRAIN DESIGN CRITERIA
PART V - STORM DRAIN DESIGN CRITERIA A. Hydrology Studies and Hydraulic Analyses 1. Drainage area master plans and calculations are to be submitted with all subdivision improvement plans, permit improvement
More informationPART V - STORM DRAIN DESIGN CRITERIA
PART V - STORM DRAIN DESIGN CRITERIA A. Hydrology Studies and Hydraulic Analyses 1. Drainage area master plans and calculations are to be submitted with all subdivision improvement plans, permit improvement
More informationDRAINAGE STUDY PHASE 2 REPORT HORRY COUNTY STORMWATER DEPARTMENT HIGHWAY 9 & 57 HORRY COUNTY, SC PREPARED FOR: APRIL 07, 2016 J
DRAINAGE STUDY PHASE 2 REPORT FOR: HIGHWAY 9 & 57 HORRY COUNTY, SC PREPARED FOR: HORRY COUNTY STORMWATER DEPARTMENT APRIL 07, 2016 Prepared by: Savannah, GA Charleston, SC Myrtle Beach, SC Brunswick, GA
More informationSection 5 - Planning Criteria. Section 5
Section 5 - Planning Criteria Section 5 SECTION 5 PLANNING CRITERIA This section presents the design criteria and methodologies for analysis used to evaluate the existing distribution system and its facilities
More information10.0 Storm Sewer Systems
October 2003 Chapter 10.0, Storm Sewer Systems Page 1 10.0 Storm Sewer Systems 10.1 Introduction A storm sewer system consists of a system of inlets, pipes, manholes, junctions, cleanouts, outlets, and
More informationSite Utility Study. Prepared By: Rodolfo Ibarra, PE, PA SW 117 th Avenue Unit #3 Miami, Florida 33177
WEST BRICKELL CENTRE Major Use Special Permit 290 SW 10 th Street, 245 SW 11 th Street,240-270 SW 10 th Street, 251-253 SW 11 th Street, 255 SW 11 th Street, and 267 SW 11 th Street Site Utility Study
More informationAppendix A Stormwater Site Plan Report Short Form
Appendix A Stormwater Site Plan Report Short Form The Stormwater Site Plan Report Short Form may be used for projects that trigger only Minimum Requirements #1-#5. These projects typically fall within
More informationPage Intentionally Left Blank
Page Intentionally Left Blank Julie Avenue and Hoeschler Drive Lift Stations Evaluation City of Sparta TABLE OF CONTENTS Page CHAPTER 1 GENERAL INFORMATION... 1 1.1 Scope of Lift Station Evaluation...
More informationWater and Wastewater Impact Fee Analysis Capital Improvement Plan City of Lockhart February 2017
TABLE OF CONTENTS 1.0 INTRODUCTION... 1 2.0 ANALYSIS OF WATER & WASTEWATER SYSTEMS... 1 2.1 Present Water Demands... 1 2.2 Water Supply... 3 2.3 Water Treatment Plant... 4 2.4 Storage, High-Service Pumps,
More informationAPPENDIX G HYDRAULIC GRADE LINE
Storm Drainage 13-G-1 APPENDIX G HYDRAULIC GRADE LINE 1.0 Introduction The hydraulic grade line is used to aid the designer in determining the acceptability of a proposed or evaluation of an existing storm
More informationAppendix D Irrigation Standards
I. Irrigation Design Standards Appendix D Irrigation Standards (a) Purpose. To conserve water resources and promote the efficient use of water resources by establishing requirements for design, installation
More informationPROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M BANK STREET CITY OF OTTAWA STORM DRAINAGE REPORT
PROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M 2 7 BANK STREET CITY OF OTTAWA STORM DRAINAGE REPORT REPORT R 81 41 (REV. 2) MARCH 2017 T.L. MAK ENGINEERING CONSULTANTS LTD. JULY
More informationIntroduction. Purpose
Introduction This Master Plan update includes updating the text of the Utilities Section of the current Master Plan and adding a report concerning telecommunications. Each element examines the existing
More informationCity of Crosby, ND Municipal Infrastructure Needs Assessment September 2012
City of Crosby, ND Municipal Infrastructure Needs Assessment September 2012 Project made possible by US Dept. of HUD Regional Substantiality Planning Grant and ND Energy Development Infrastructure and
More informationHydraulic Modeling, PUDs & Managing Water System Growth
Hydraulic Modeling, PUDs & Managing Water System Growth American Water Resources Association Intermountain Section October 9, 2013 Utah Division of Drinking Water Ying-Ying Macauley Presentation Topics
More informationRiverside South Block 3/4, Richcraft Group of Companies Inc., City of Ottawa SERVICING REPORT
Riverside South Block 3/4, Richcraft Group of Companies Inc., City of Ottawa SERVICING REPORT Prepared by: Stantec Consulting Ltd. 1505 Laperriere Avenue Ottawa, ON K1Z 7T1 File: 160401004/83 January 17,
More information