HILTI FIRESTOP MORTAR CFS-M RG. European Technical Assessment ETA N o 12 / 0101

Size: px
Start display at page:

Download "HILTI FIRESTOP MORTAR CFS-M RG. European Technical Assessment ETA N o 12 / 0101"

Transcription

1 HILTI FIRSTOP MORTAR FS-M RG uropean Technical Assessment TA N o 12 / 0101

2 HILTI FIRSTOP MORTAR FS-M RG APPLIATIONS Mixed penetrations in rigid walls and floors from 150 mm ables, cable bundles, cable trays and cable conduits Non-combustible (metal) pipes with non-combustible insulation Non-combustible (metal) and composite pipes with combustible insulation in combination with firestop bandage FS-B ombustible (PV-U and P) pipes in combination with firestop collar FS-, firestop collar FS- P or firestop wrap FS-W Technical ata Mix ratio (Mortar to Water by Weight) Max. compressive strength after 28 days Working time Shelf life (@73 F / 23 and 50% relative humidity) Application temperature range Application temperature range (Imperial) 2.5:1 2.9 N / mm² 45 min 12 month(s) F 176 F AVANTAGS asy to install with trowel or commercially available pumps thanks to adjustable consistency xcellent thermal insulating properties No shrinkage during curing or in the event of fire Paintable Assessments T2 / 0101 Base materials oncrete, aerated concrete and masonry Reaction to fire class lass A1 according to N The uropean Technical Assessment (TA) and the technical data sheet can be obtained via your local Hilti contact. Order designation Sales quantity Item number Firestop mortar FS-M RG 1 P

3 INSTALLATION INSTRUTIONS 1 lean and pre-moisten surfaces. ables and supporting structures must be dry and clean of dust, grease or oil and installed in compliance with local building and electrical standards. 2 Add Hilti Firestop Mortar FS-M RG to water in a ratio of approximately 2.5 : 1 (mortar to water by weight). The mix ratio of Hilti Firestop Mortar to water determines the desired consistency (stiffness) Stir the mixture thoroughly with, for example, a Hilti T-MP paddle. Large volumes of Hilti Firestop Mortar may be mixed using commercially available mixing or plastering machines. o not use any other binders or additives. 4 Place forms on one or both sides of large openings. Floor openings must have formwork underneath. Apply mixed mortar in the opening using a trowel or pump and compact it. nsure that all gaps and spaces are completely filled and closed. Smooth the surface as with standard concrete. 5 Ausführungsschild epending on the application and fire rating to be achieved, additional protection (e.g. mineral wool mat) may be required (see TA for details). For installation of additional components (e.g. Hilti Firestop ollar FS- P and Hilti Firestop Bandage FS-B) see TA. If required by national prescriptions mark the penetration seal with an identification plate containing the required information. In such a case fasten the identification plate in a visible position next to the seal. 03

4 ABL PNTRATION, PIP PNTRATION RIGI WALL The intended use of Hilti firestop mortar FS-M RG is to reinstate the fire resistance of: Rigid walls (), minimum thickness 150 or 175 mm (t ), concrete, aerated concrete or masonry, minimum density of 550 or 1100 kg / m 3. All penetrating items (cables, cable trays, conduits, metal pipes and plastic pipes) can be installed as a single, multiple or mixed configuration. Maximum seal size (width height) 1200 mm 2000 mm respectively 1000 mm 1500 mm depending on wall thickness. Minimum distances between penetrants and seal edges to be considered. ABLS, ABL BUNLS, ABL TRAYS AN ONUITS Additional protection epending on the required fire resistance, additional protection (AP) may be required. AP: mineral wool mat, wrapped around cables / cable support (trays, ladders), Al-faced side outside, fixed with wire, width (length along the cables LAP) 200 mm, thickness (tap) 30 mm. Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity Without additional protection (AP) With additional protection (AP) All sheathed cables up to 21 mm diameter I 120 I 120 All sheathed cables up to 80 mm diameter I 90 I 120 All non-sheathed cables max. diameter 24 mm I 30 I 120 Tied cable bundle max. diameter 100 mm with max. diameter of single cable 21 mm Plastic conduits and tubes 16 mm with or without cables or cable supports Steel conduits and tubes 16 mm with or without cables or cable supports Rigid Wall 150 mm minimum density of 550 kg / m 3 I 120 I 120 I 180-U / I 180- / U In case a conduit is installed with open ends on both sides (U / U), conduit must be closed with e.g. Hilti Firestop Acrylic Sealant FS-S AR. able penetrations without add. protection able penetrations with additional protection (AP) t t w A1 3 A1 AP 3 AP h tap ta1 LAP LAP A 1 ta1 t t w 2 AP 2 AP h t AP A 1 1 L AP L AP 1 04

5 MTAL PIPS WITH MINRAL WOOL INSULATION Penetration seal (A) / services () Wall type and thickness (t ) Insulation thickness (t ) lassification = Integrity Steel pipes mm diameter, pipe wall thickness 2.2 / mm Steel pipes mm diameter, pipe wall thickness 2.9 / mm 20 mm 40mm I 120- / U With continued insulation (), sustained Steel pipes mm diameter, pipe wall thickness 2.2 / mm Steel pipes 76.0 mm diameter, pipe wall thickness mm 20 mm 40 mm I 120- / U L 500 mm, sustained Steel pipes mm diameter, pipe wall thickness 2.9 / mm 40 mm I 90- / U Steel pipes mm diameter, pipe wall thickness mm Steel pipes mm diameter, pipe wall thickness mm Rigid Wall 150 mm minimum density of 550 kg / m 3 40 mm I 120- / U 40 mm I 120- / U With continued insulation (), interrupted L 800 mm, interrupted opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes mm diameter, pipe wall thickness 1.5 / mm 20mm 40 mm I 120- / U With continued insulation (), sustained opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes 54 mm diameter, pipe wall thickness mm 20 mm 40 mm I 120- / U L 500 mm, sustained opper pipes mm diameter, pipe wall thickness 1.5 / mm 40 mm L 800 mm, sustained ontinued insulation, sustained Local insulation, sustained t t t A1 t t A1 t d d ta1 L ta1 ontinued insulation, interrupted Local insulation, interrupted t t t A1 t t A1 t d d ta1 L ta1 05

6 MTAL PIPS WITH ARMAFLX AF INSULATION Steel, cast iron, stainless steel, Ni alloys (Niu, Nrr, NiMO alloys), copper pipes. With Hilti firestop bandage FS-B (A2), two layers wrapped around pipe insulation on each side of the seal. Penetration seal (A) / services () Wall type and thickness (t ) Insulation thickness (t ) lassification = Integrity Metal pipes, mm diameter, pipe wall thickness 2.2 / mm Metal pipes, mm diameter, pipe wall thickness 2.9 / mm 19 / mm 41 mm I 120- / U With continued insulation (), sustained Metal pipes, mm diameter, pipe wall thickness 2.2 / mm Metal pipes, mm diameter, pipe wall thickness 2.9 / mm opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes mm diameter, pipe wall thickness 1.5 / mm Rigid Wall 150 mm minimum density of 550 kg / m 3 19 / mm I 120- / U 41 mm I 60- / U mm I 120- / U 41 mm L 500 mm, sustained With continued insulation (), sustained opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes mm diameter, pipe wall thickness 1.5 / mm 19 / mm L 500 mm, sustained I 120- / U 41 mm L 800 mm, sustained ontinued insulation, sustained Local insulation, sustained t t t t t t d d A 2 L A 2 06

7 MTAL PIPS WITH ARMAFLX AF INSULATION Steel, cast iron, stainless steel, Ni alloys (Niu, Nrr, NiMO alloys), copper pipes. Additional protection: Armaflex AF, thickness 25 mm over a length of 200 mm from the seal on both sides. Penetration seal (A) / services () Wall type and thickness (t ) Insulation thickness (t ) lassification = Integrity Metal pipes, mm diameter, pipe wall thickness mm Metal pipes, mm diameter, pipe wall thickness mm Rigid Wall 150 mm minimum density of 550 kg / m 3 25 mm With continued insulation (), interrupted I 120- / U 25 mm L 780 mm, interrupted ontinued insulation, interrupted Local insulation, interrupted t t AP AP t t AP t t t AP t d d L AP L AP L L AP L AP 07

8 PLASTI PIPS With Hilti firestop collar FS- P PV-U pipes according to N ISO 1452, N ISO and IN 8061 / 8062 Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness mm I 120-U / U 63 mm, pipe wall thickness mm I 120-U / U 75 mm, pipe wall thickness mm I 180-U / U 90 mm, pipe wall thickness mm I 120-U / U 110 mm, pipe wall thickness mm Rigid Wall 150 mm minimum density of 550 kg / m 3 I 120-U / U 110 mm, pipe wall thickness 8.1 mm I 180-U / U 125 mm, pipe wall thickness mm I 120-U / U With Hilti firestop collar FS- P (A 3 ) on both sides of the seal, fixed together by M8 threaded rods, washers and nuts. Always use the appropriate collar size and number of hooks for the different pipe diameters. 160 mm, pipe wall thickness mm I 120-U / U 160 mm, pipe wall thickness 11.8 mm I 180-U / U P pipes according to N ISO 15494, IN 8074 / 8075 Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 2.9 mm I 180-U / U 50 mm, pipe wall thickness mm I 120-U / U 63 mm, pipe wall thickness mm I 90-U / U 63 mm, pipe wall thickness mm I 120-U / U 75 mm, pipe wall thickness mm 90 mm, pipe wall thickness mm Rigid Wall 150 mm minimum density of 550 kg / m 3 I 120-U / U I 120-U / U 110 mm, pipe wall thickness mm I 120-U / U With Hilti firestop collar FS- P (A 3 ) on both sides of the seal, fixed together by M8 threaded rods, washers and nuts. Always use the appropriate collar size and number of hooks for the different pipe diameters. 125 mm, pipe wall thickness mm I 120-U / U 160 mm, pipe wall thickness mm I 120-U / U 160 mm, pipe wall thickness 9.1 mm I 180-U / U P pipes according to N ISO Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 3.0 mm I 120-U / U 63 mm, pipe wall thickness 3.0 mm I 180-U / U 75 mm, pipe wall thickness 3.0 mm I 120-U / U 90 mm, pipe wall thickness 3.5 mm Rigid Wall 150 mm minimum density of 550 kg / m 3 I 180-U / U 110 mm, pipe wall thickness 4.2 mm I 120-U / U 125 mm, pipe wall thickness 4.8 mm I 120-U / U With Hilti firestop collar FS- P (A 3 ) on both sides of the seal, fixed together by M8 threaded rods, washers and nuts. Always use the appropriate collar size and number of hooks for the different pipe diameters. 160 mm, pipe wall thickness 6.2 mm I 120-U / U 08

9 PLASTI PIPS With Hilti firestop collar FS- PV-U pipes according to N ISO 1452, N ISO 15493, IN 8061 / 8062 Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 2.2 mm 110 mm, pipe wall thickness mm Rigid Wall 150 mm minimum density of 550 kg / m 3 I 180-U / With Hilti firestop collar FS- (A 3 ) on both sides of the seal, fixed together by M8 threaded rods, washers and nuts. Always use the appropriate collar size and number of hooks for the different pipe diameters. Plastic pipes t t d A 3 09

10 PLASTI PIPS With Hilti firestop wrap FS-W Hilti firestop wrap FS-W (A 4 ) on both sides of the mortar seal, flush with the surface of the seal. PV pipes according to N ISO 1452, N ISO 15493, IN 8061 / 8062 Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 32 mm, pipe wall thickness 1.8 mm FS-W L 1 layer 90 mm, pipe wall thickness 3.2 mm FS-W SG 110 mm, pipe wall thickness 3.2 mm FS-W SG Rigid Wall 175 mm, minimum I 240-U / density of 1100 kg / m 3 > mm, pipe wall thickness 3.2 mm FS-W L 2 layers 160 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 3 layers P pipes according to N ISO 15494, IN 8074 / 8075 Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 32 mm, pipe wall thickness 1.8 mm FS-W L 1 layer 90 mm, pipe wall thickness 2.7 mm FS-W SG 110 mm, pipe wall thickness 2.7 mm FS-W SG Rigid Wall 175 mm, minimum I 240-U / density of 1100 kg / m 3 > mm, pipe wall thickness 2.7mm FS-W L 2 layers 160 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 3 layers P pipes according to N Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity 160 mm, pipe wall thickness 6.2 mm FS-W SG Rigid Wall 175 mm, minimum I 180-U / density of 1100 kg / m 3 > mm, pipe wall thickness 6.2 mm FS-W L 3 layers Plastic pipes t A1 A 4 t d 10

11 ABL PNTRATION, PIP PNTRATION Rigid floors The intended use of the Hilti firestop mortar FS-M RG is to reinstate the fire resistance of: Rigid floors (), minimum thickness 150 or 175 mm (t ), concrete or aerated concrete, minimum density of 550 or 2400 kg / m 3. All penetrating items (cables, cable trays, conduits, metal pipes and plastic pipes) can be installed as a single, multiple or mixed configuration. Maximum opening sizes as well as minimum distances between penetrants and seal edges to be considered. ABLS, ABL BUNLS, ABL TRAYS AN ONUITS Additional protection epending on the required fire resistance, additional protection (AP) may be required. AP: mineral wool mat, wrapped around cables / cable support (trays, ladders), Al-faced side outside, fixed with wire, width (length along the cables) 200 mm, thickness 30 mm. Penetration seal (A) / services () Wall type and thickness (t ) lassification = Integrity Other criteria, description Without additional protection (AP) Without additional protection (AP) With additional protection (AP) 200 mm seal thickness 150 mm seal thickness All sheathed cables up to 21 mm diameter I 90 I 90 I 90 All sheathed cables up to 80 mm diameter I 90 I 60 I 90 All non-sheathed cables up to 17 mm diameter I 90 I 45 I 90 All non-sheathed cables up to 24 mm diameter Rigid Floor I 45 I 45 I 60 Tied cable bundle max. diameter 100 mm 150 mm with max. diameter of single cable 21 mm minimum density of 550 kg / m 3 I 90 I 90 I 90 Plastic conduits and tubes 16 mm with or without cables or cable supports Steel conduits and tubes 16 mm with or without cables or cable supports I 120-U / I 90-U / I 90-U / I 120- / U I 90- / U I 90- / U In case a conduit is installed with open ends on both sides (U / U), conduit must be closed with e.g. Hilti Firestop Acrylic Sealant FS-S AR. 11

12 able penetrations without add. protection able penetrations with additional protection (AP) t AP w L AP AP AP t t l 3 3 A 1 L AP t AP AP w t t AP l A 1 Seal type with 200 mm seal thickness d d ta1 d d t t

13 MTAL PIPS WITH MINRAL WOOL INSULATION Steel, cast iron, stainless steel, Ni alloys (Niu, Nrr, NiMO alloys), copper pipes. No additional protection (AP). Penetration seal (A) / services () Floor type and thickness (t ) Insulation thickness (t ) lassification = Integrity Steel pipes mm diameter, pipe wall thickness 2.2 / mm Steel pipes mm diameter, pipe wall thickness 2.9 / mm 20 mm 40 mm I 120- / U With continued insulation (), sustained Steel pipes mm diameter, pipe wall thickness 2.2 / mm Steel pipes 76.0 mm diameter, pipe wall thickness mm 20 mm 40 mm I 120- / U L 500 mm, sustained Steel pipes mm diameter, pipe wall thickness 2.9 / mm opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes mm diameter, pipe wall thickness 1.5 / mm Rigid Floor 150 mm minimum density of 550 kg / m 3 40 mm 20 mm 40 mm I 120- / U L 700 mm, sustained With continued insulation (), sustained opper pipes mm diameter, pipe wall thickness 1.0 / mm opper pipes 54 mm diameter, pipe wall thickness mm 20 mm 40 mm I 120- / U L 500 mm, sustained opper pipes mm diameter, pipe wall thickness 1.5 / mm 40 mm L 800 mm, sustained Metal pipes, mm diameter, pipe wall thickness mm Metal pipes, mm diameter, pipe wall thickness mm Rigid Floor 150 mm, minimum density of 2400 kg / m 3 40 mm 40 mm I 120- / U With continued insulation (), interrupted L 800 mm, interrupted ontinued insulation, sustained Local insulation, sustained t t L t t t t d d ontinued insulation, sustained Local insulation, interrupted t t L t t t t d d 13

14 MTAL PIPS WITH ARMAFLX AF INSULATION Steel, cast iron, stainless steel, Ni alloys (Niu, Nrr, NiMO alloys), copper pipes. With Hilti firestop bandage FS-B (A2), two layers wrapped around pipe insulation on each side of the seal. Penetration seal (A) / services () Floor type and thickness (t ) Insulation thickness (t ) lassification = Integrity Metal pipes, 26.7 mm diameter, pipe wall thickness mm 19 mm I 120- / U Metal pipes, mm diameter, pipe wall thickness 2.2 / mm Metal pipes, 76.0 mm diameter, pipe wall thickness mm mm I 90- / U 41 mm I 120- / U With continued insulation (), sustained Metal pipes, mm diameter, pipe wall thickness 2.9 / mm 41 mm I 90- / U Metal pipes, 26.7 mm diameter, pipe wall thickness mm 19 mm I 120- / U Metal pipes, mm diameter, pipe wall thickness 2.2 / mm mm I 90- / U L 500 mm, sustained Metal pipes, 76.0 mm diameter, pipe wall thickness mm 41 mm I 120- / U Metal pipes, mm diameter, pipe wall thickness 2.9 / mm Rigid Floor 150 mm minimum density of 550 kg / m 3 41 mm I 90- / U L 700 mm, sustained opper pipes 28 mm diameter, pipe wall thickness mm 19 mm I 120- / U opper pipes mm diameter, pipe wall thickness 1.0 / mm mm I 90- / U With continued insulation (), sustained opper pipes mm diameter, pipe wall thickness 1.5 / mm 41 mm I 120- / U opper pipes 28 mm diameter, pipe wall thickness mm 19 mm I 120- / U opper pipes mm diameter, pipe wall thickness 1.0 / mm mm I 90- / U L 500 mm, sustained opper pipes 54 mm diameter, pipe wall thickness mm opper pipes mm diameter, pipe wall thickness 1.5 / mm 41 mm 41 mm I 120- / U L 800 mm, sustained ontinued insulation, sustained Local insulation, sustained t t A 2 L A 2 A1 t t t t d d 14

15 MTAL PIPS WITH ARMAFLX AF INSULATION Steel, cast iron, stainless steel, Ni alloys (Niu, Nrr, NiMO alloys), copper pipes. Additional protection: Armaflex AF, thickness 25 mm over a length of 200 mm from the seal on the top side of the floor. Penetration seal (A) / services () Floor type and thickness (t ) Insulation thickness (t ) lassification = Integrity Metal pipes, mm diameter, pipe wall thickness mm Metal pipes, mm diameter, pipe wall thickness mm Rigid Floor 150 mm, minimum density of 2400 kg / m 3 25 mm 25 mm I 180-U / With continued insulation (), interrupted L 800 mm, interrupted ontinued insulation, interrupted Local insulation, interrupted t t t AP t AP AP L AP L AP L AP t t t t d d 15

16 PLASTI PIPS With Hilti FS- P firestop collar PV-U pipes according to N ISO 1452, N ISO and IN 8061 / 8062 Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness mm 63 mm, pipe wall thickness mm 75 mm, pipe wall thickness mm 90 mm, pipe wall thickness mm 110 mm, pipe wall thickness mm Rigid Floor 150 mm minimum density of 550 kg / m 3 I 120-U / U With Hilti firestop collar FS- P (A 3 ) fixed on the underside of the seal. Always use the appropriate collar size and number of hooks for the different pipe diameters. 125 mm, pipe wall thickness mm 160 mm, pipe wall thickness mm P pipes according to N ISO 15494, IN 8074 / 8075 Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness mm 63 mm, pipe wall thickness mm 75 mm, pipe wall thickness mm 90 mm, pipe wall thickness mm 110 mm, pipe wall thickness mm Rigid Floor 150 mm minimum density of 550 kg / m 3 I 120-U / U With Hilti firestop collar FS- P (A 3 ) fixed on the underside of the seal. Always use the appropriate collar size and number of hooks for the different pipe diameters. 125 mm, pipe wall thickness mm 160 mm, pipe wall thickness mm P pipes according to N ISO Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 3.0 mm 63 mm, pipe wall thickness 3.0 mm 75 mm, pipe wall thickness 3.0 mm 90 mm, pipe wall thickness 3.5 mm 110 mm, pipe wall thickness 4.2 mm Rigid Floor 150 mm minimum density of 550 kg / m 3 I 120-U / U With Hilti firestop collar FS- P (A 3 ) fixed on the underside of the seal. Always use the appropriate collar size and number of hooks for the different pipe diameters. 125 mm, pipe wall thickness 4.8 mm 160 mm, pipe wall thickness 6.2 mm 16

17 PLASTI PIPS With Hilti firestop collar FS- PV-U or PV- pipes according to N ISO 15493, N ISO 1452, IN 8061 / 8062, N , N and N Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 2.0 mm 110 mm, pipe wall thickness mm Rigid Floor 150 mm, minimum density of 2400 kg / m 3 I 180-U / With Hilti firestop collar FS- (A 3 ) fixed on the underside of the seal. Always use the appropriate collar size and number of hooks for the different pipe diameters. Plastic pipes t A 3 t d 17

18 PLASTI PIPS With Hilti firestop wrap FS-W Hilti firestop wrap FS-W (A 4 ) on the underside of the mortar seal flush with the lower surface of the mortar seal. PV-U pipes according to N ISO 1452, N ISO 15493, IN 8061 / 8062 Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 32 mm, pipe wall thickness 1.8 mm FS-W L 1 layer 50 mm, pipe wall thickness mm FS-W SG 63 mm, pipe wall thickness mm FS-W SG 75 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 1 layer I 120-U / 90 mm, pipe wall thickness mm FS-W SG 110 mm, pipe wall thickness mm > mm, pipe wall thickness mm Rigid Floor 175 mm, minimum density of 2400 kg / m 3 FS-W SG FS-W L 2 layers 125 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 2 layers 160 mm, pipe wall thickness mm FS-W SG I 60-U / > mm, pipe wall thickness mm FS-W L 3 layers 160 mm, pipe wall thickness mm FS-W SG I 120-U / > mm, pipe wall thickness mm FS-W L 3 layers P pipes according to N ISO 15494, IN 8074 / 8075 Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 32 mm, pipe wall thickness 1.8 mm FS-W L 1 layer 50 mm, pipe wall thickness mm FS-W SG 63 mm, pipe wall thickness mm FS-W SG 75 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 1 layer 90 mm, pipe wall thickness mm FS-W SG Rigid Floor 175 mm, minimum I 120-U / density of 2400 kg / m mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 2 layers 125 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 2 layers 160 mm, pipe wall thickness mm FS-W SG > mm, pipe wall thickness mm FS-W L 3 layers 18

19 P pipes according to N Penetration seal (A) / services () Floor type and thickness (t ) lassification = Integrity 50 mm, pipe wall thickness 3.0 mm FS-W SG 63 mm, pipe wall thickness 3.0 mm FS-W SG 75 mm, pipe wall thickness 3.0 mm FS-W SG 75 mm, pipe wall thickness 3.0 mm FS-W L 1 layer 90 mm, pipe wall thickness 4.8 mm FS-W SG Rigid Floor 175 mm, minimum I 120-U / density of 2400 kg / m mm, pipe wall thickness 4.8 mm FS-W SG 125 mm, pipe wall thickness 4.8 mm FS-W SG > mm, pipe wall thickness 4.8 mm FS-W L 2 layers 160 mm, pipe wall thickness 6.2 mm FS-W SG > mm, pipe wall thickness 6.2 mm FS-W L 3 layers Plastic pipes t A 4 t d 19

20 Specification for mineral wool products suitable for being used as additional protection (AP) for cables / cable supports: Stone wool according to N 14303, reaction to fire class according to N A1 or A2, thermal conductivity at W / (mk), density kg / m 3, surface faced with aluminum foil on one side. The following list contains suitable products but may not be exhaustive: Isover Ultimate U TFA 34 Knauf Lamella Forte LLMF AluR Paroc Lamella Mat 35 Alu oat Rockwool Klimafix, Klimarock or 133 (Lamella mat) Specification for mineral wool products suitable for being used as pipe insulation: Sustained insulation: Isover oquilla AT-LR, Protect 1000 S alu, Protect BSR 90 alu. Paroc Section Aluoat T Rockwool onlit Pipe sections, Klimarock, RS 800 pipe sections Interrupted insulation: Stone wool acc. to N 14303, class A2 or A1 acc. to N , Al-faced Specification for flexible elastomeric foam (FF) products suitable for being used as pipe insulation: Armacell International GmbH Armaflex AF ( marked acc. to N 14304) 20

21 HARATRISTIS OF FS-M RG Additional Attributes Hilti firestop products are comprehensively tested and individually matched to the technical requirements of a building s mechanical and electrical installations. In addition to their superior passive fire protection behavior, Hilti firestop products also meet increasingly significant requirements in building technology and also help designers and installers to meet these additional requirements. The assessment of fitness for use has been made in accordance with OTA TAG No 026 Part 2. haracteristics Assessment of characteristics Norm, standard, test Health and the environment Air and gas permeability (gas tightness) angerous substances Protection against noise (air-borne sound insulation) Safety in use Mechanical resistance and stability Resistance to impact / movement / adhesion nergy, economy and heat retention Thermal properties lectrical properties urability and serviceability Gas permeability with the gases air, nitrogen (N 2 ), carbon dioxide (O 2 ) and H 4 (methane) with specific flow rates. See TA for detailed results. oes not contain dangerous substances from the list of the uropean ommission above the acceptable limits. Weighted element-normalized level difference: n,w = 59dB Weighted sound reduction index R w = 52dB Safety in use: Internal walls: Highest risk zone type has been fulfilled (Type IV). For floors: soft body impact energy 600 Nm, hard body impact energy 10 Nm Serviceability: soft body impact energy 120 Nm, hard body impact energy 6 Nm Heat conductivity (λ 10, calculated): W / mk. Volume resistivity: ± 50+10Ωcm. Surface resistivity: ± 80+08Ω. ategory Y 1,( 5 / +70) (suitable for pe netration seals intended for use at temperatures between 5 and +70 with no exposure to rain. N 1026 Material safety data sheet N ISO N ISO OTA Technical Report TR001 A.1 and A.4 N IN I 93 (V 0303 Part 30): OTA Technical Report TR 024 TAG Reaction to fire lass A1 N SRVI With more than 20 years of experience worldwide, Hilti is one of the world s leading suppliers of firestop systems. We actively help you manage your firestop projects better by providing: Quick engineering judgments xtensive technical literature On-site training and demonstrations Sophisticated jobsite logistics Assurance of conformity with specific application requirements International network of Hilti firestop specialists Our network of experienced sales representatives, field engineers, firestop specialists and customer service representatives is just a phone call away (use the local toll-free Hilti number). 21

22 22

23 23

24 Hilti orporation 9494 Schaan, Liechtenstein P / hiltigroup Hilti = registered trademark of Hilti orp., Schaan W en 2 Printed in Liechtenstein 2017 Right of technical and programme changes reserved S.. & O.

European Technical Assessment. ETA-12/0101 of Member of. General part

European Technical Assessment. ETA-12/0101 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (U) No 305/2011 Member of www.eota.eu

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the ouncil Directive 89/ 106/ of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to

More information

Technical Data Sheet. Hilti Firestop cable collar CFS-CC. European technical approval ETA N o 13 / Issue 10 / 2013

Technical Data Sheet. Hilti Firestop cable collar CFS-CC. European technical approval ETA N o 13 / Issue 10 / 2013 Technical Data Sheet Hilti Firestop cable collar CFS-CC Hilti Firestop cable collar CFS-CC European technical approval ETA N o 13 / 0704 Issue 10 / 2013 Hilti Firestop cable collar CFS-CC Issue 10 / 2013

More information

Technical Data Sheet. Hilti Firestop Foam CP 660. Firestop Solutions in Accordance with AS & AS BWA Report No

Technical Data Sheet. Hilti Firestop Foam CP 660. Firestop Solutions in Accordance with AS & AS BWA Report No Technical Data Sheet Hilti Firestop Foam CP 660 New Zealand Hilti Firestop Foam CP 660 Firestop Solutions in Accordance with AS 15.4-2005 & AS 4072.1-2005 BWA Report No. 2244100.1 Validity Extension EWFA

More information

European technical approval

European technical approval Page 1 of uropean technical approval TA-10/0404, uropean technical approval (nglish language translation, the original version is in German language) TA-10/0404 Handelsbezeichnung: Trade name: Hilti irestop

More information

DECLARATION OF PERFORMANCE

DECLARATION OF PERFORMANCE EN DECLARATION OF PERFORMANCE according to Annex III of the Regulation (EU) Nr. 35/211 (Construction Products Regulation) Hilti Firestop Intumescent Sealant CFS-IS No. Hilti CFS 761-CPD-173 1. Unique identification

More information

Technical Data Sheet. Astro HPE Sealant. UIC of product-type: AFHPE

Technical Data Sheet. Astro HPE Sealant. UIC of product-type: AFHPE Technical Data Sheet Astro HPE Sealant UIC of product-type: AFHPE Revision 2 - July 2016 Astroflame (Fireseals) LTD : Unit 8, I.O Centre Stephenson Road : Segensworth : Fareham : PO15 5RU Tel - 01329 844500

More information

Hilti Firestop Coating CFS-CT. Hilti AG Feldkircherstrasse Schaan Liechtenstein

Hilti Firestop Coating CFS-CT. Hilti AG Feldkircherstrasse Schaan Liechtenstein SITAC Box 553 SE 371 23 Karlskrona SWEDEN MEMBER OF EOTA Tfn.: +46-(0)10-516 63 00 Fax: +46-(0)455-206 88 E-mail: info@sitac.se European Technical Approval ETA-11/0429 This ETA replaces the previous ETA

More information

European Technical Assessment ETA-16/0952 of 06/01/2017

European Technical Assessment ETA-16/0952 of 06/01/2017 ETA-Danmark A/S Göteborg Plads 1 DK-2150 Nordhavn Tel. +45 72 24 59 00 Fax +45 72 24 59 04 Internet www.etadanmark.dk Authorised and notified according to Article 29 of the Regulation (EU) No 305/2011

More information

ÖSTERREICHISCHES INSTITUT FÜR BAUTECHNIK

ÖSTERREICHISCHES INSTITUT FÜR BAUTECHNIK ÖSTRRICHISCHS INSTITUT FÜR AUTCHNIK A-1010 Vienna, Schenkenstrasse 4 Tel.: + 4 3 ( 0 ) 1-5 3 3 6 5 5 0 Fax: + 4 3 ( 0 ) 1-5 3 3 6 4 2 3 relating to construction products -mail: mail@oib.or.at Authorised

More information

Hilti Firestop Single Board Seal Hilti Firestop Single Board Seal. Hilti AG Feldkircherstrasse Schaan Liechtenstein

Hilti Firestop Single Board Seal Hilti Firestop Single Board Seal. Hilti AG Feldkircherstrasse Schaan Liechtenstein SITAC Box 553 SE 371 23 Karlskrona SWEDEN MEMBER OF EOTA Tfn.: +46-(0)10-516 63 00 Fax: +46-(0)455-206 88 E-mail: info@sitac.se European Technical Approval ETA -11/0428 Handelsnamn Trade name Hilti Firestop

More information

FIRESTOP AND FIRE PROTECTION

FIRESTOP AND FIRE PROTECTION FIRESTOP AND FIRE PROTECTION 170 Firestop Sealants, Sprays High-performance intumescent firestop sealant FS-ONE MAX Page 172 Flexible firestop sealant CP 606 Page 172 Elastomeric silicone sealant CP 601S

More information

European Technical Assessment. ETA-16/0320 of Member of. General part

European Technical Assessment. ETA-16/0320 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

Firestop and Fire Protection Systems

Firestop and Fire Protection Systems Firestop and Fire Protection Systems Leading-edge Technology. Outstanding Service. 156 Firestop sealants and sprays Elastomeric silicon sealant CP 601S Flexible firestop sealant CP 606 Firestop sealant

More information

U L - E U C E R T I F I C A T E

U L - E U C E R T I F I C A T E U L - U C R T I F I C A T Page 1/8 Date of Issue 15-07-02 Certificate Holder Manufacturer Certified Product Type Product Trade Name Trademark Rating/Classification ASTROFLAM FIRSALS LIMITD UNIT 8 TH IO

More information

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the ÖSTRRICHISCHS I N S T I T U T F Ü R B A U T C H N I K A-1010 Vienna, Schenkenstrasse 4 Tel.: + 4 3 ( 0 ) 1-5 3 3 6 5 5 0 Fax: + 4 3 ( 0 ) 1-5 3 3 6 4 2 3 relating to construction products - m a i l : m

More information

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING

DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION PENETRATION FIRESTOPPING DIVISION 7 THERMAL AND MOISTURE PROTECTION SECTION 07 84 13 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

HILTI CP 606 Flexible Firestop Sealant

HILTI CP 606 Flexible Firestop Sealant Data Sheet HILTI CP 606 Flexible Firestop Sealant The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety data

More information

European Technical Assessment. ETA-11/0372 of Member of. General part

European Technical Assessment. ETA-11/0372 of Member of. General part INSTITU Schenkenstrasse 4 T +43 1 533 65 50 1010 Vienna Ι Austria F +43 1 533 64 23 www.oib.or.at Ι mail@oib.or.at Designated according to Article 29 of Regulation (EU) No 305/2011 Member of www.eota.eu

More information

HILTI CP 601S Elastomeric Firestop Sealant

HILTI CP 601S Elastomeric Firestop Sealant Data Sheet HILTI CP 601S Elastomeric Firestop Sealant The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety

More information

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS SECTION 07841 - THROUGH-PENETRATION FIRESTOP SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2

Tehnical Data Sheet Astro HS FM Compound. UIC of product-type: HSFMC CPR-JA5013 ETA-14/0047. ETAG 026-Part 1 ETAG 026-Part 2 1121 Astroflame Fireseals Ltd Unit 8 The I O Centre 14 1121-CPR-JA5013 ETA-14/0047 ETAG 026-Part 1 ETAG 026-Part 2 FM Compound see ETA-14/0047 for relevant characteristics APPROVED CF613 EN13501-2 EN1366-3:2009

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notiied according to Article 10 of the Council Directive 89/ 106/C of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating to

More information

K-FLEX K-FLEX K-FIRE. firestopping solutions

K-FLEX K-FLEX K-FIRE. firestopping solutions K-FLEX NAME Edition PRODUCT 2018 K-FLEX K-FLEX K-FIRE firestopping solutions K-FLEX K-FIRE K-FLEX K-FIRE K-FIRE SEALANT K-FIRE WRAP K-FIRE BOARD/BATT K-FIRE COLLAR K-FIRE BOARD/BATT K-FIRE COLLAR INDEX

More information

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd

Technical Assessment Body issuing the ETA and designated according to Article 29 of the Regulation (EU) No 305/2011: UL International (UK) Ltd Member of www.eota.eu UL INTERNATIONAL (UK) LTD Wonersh House, Building C, The Guildway, Old Portsmouth Road, Guildford. GU3 1LR. United Kingdom. designated according to Article 29 of the Regulation (EU)

More information

Assembly Instruction. FLAMRO Variant N II A / N II KS

Assembly Instruction. FLAMRO Variant N II A / N II KS Assembly Instruction / N II KS Please respect the permit specifications. All documents may be downloaded from www.flamro.com/services/downloads. It is assumed that - any damage to the seal will be repaired

More information

Installation in ceilings

Installation in ceilings Installation instructions EI90 BET Cable Boxes "System Wichmann" ceiling 350 mm depth, rectangular ETA 13/0902 BET Cable Box to be poured in the concrete» Technical datasheet - page 4-7 Installation in

More information

HILTI CP 657 Firestop Brick

HILTI CP 657 Firestop Brick Data Sheet HILTI CP 657 Firestop Brick The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety data sheets visit

More information

3M Fire Barrier Sealant IC 15WB+

3M Fire Barrier Sealant IC 15WB+ 3M Technical Data Sheet 3M Fire Barrier Sealant IC 15WB+ The 3M Fire Barrier Sealant IC 15WB+ is a latex sealant designed for use as a one-part fire, smoke, noxious gas and water resistant sealant. In

More information

Tehnical Data Sheet Astro Intu Mastic. UIC of product-type: INTUM CPR-JA5015

Tehnical Data Sheet Astro Intu Mastic. UIC of product-type: INTUM CPR-JA5015 1121 Astroflame Fireseals Ltd Unit 8 The I O Centre 14 1121-CPR-JA5015 ETA-14/0049 ETA-14/0050 ETAG 026-Part 1 ETAG 026-Part 2 ETAG 026-Part 3 MASTIC see ETA-14/0049 & ETA- 14/0050 for relevant characteristics

More information

FIRESTOP SUBMITTAL PACKAGE

FIRESTOP SUBMITTAL PACKAGE FIRESTOP SUBMITTAL PACKAGE HVAC Materials FS-ONE Intumesent Caulk CP 606 Acrylic Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Concrete Assemblies

More information

HILTI CP 643N Firestop collar

HILTI CP 643N Firestop collar Data Sheet HILTI CP 643N Firestop collar The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details For Material Safety data sheets

More information

St. Monica Food Pantry

St. Monica Food Pantry St. Monica Food Pantry 07 8400-1 SECTION 07 8400 - FIRESTOPPING PART 1 - GENERAL 1.1 SUMMARY: A. Related work: 1. Concrete. 2. Mortar and grout. 3. Brick masonry. 4. Concrete unit masonry. 5. Structural

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

CERTIFICATE OF APPROVAL No CF 517 FSI LIMITED

CERTIFICATE OF APPROVAL No CF 517 FSI LIMITED CERTIFICATE OF APPROVAL No CF 517 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Westminster Industrial

More information

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F

Österreichisches Institut für Bautechnik Schenkenstrasse Vienna Austria T F Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

Fire Barrier Duct Wrap 615+

Fire Barrier Duct Wrap 615+ Fire Barrier Duct Wrap 615+ Duct Wrap Fire Protection System for Commercial Kitchen Grease and Ventilation Air Ducts Product Data Batts and blankets for use in fire resistive duct assemblies see UL fire

More information

Intumescent Pipewrap Roll

Intumescent Pipewrap Roll FIRESTOPPING December 2016 Intumescent Pipewrap Roll ROCKWOOL FirePro Intumescent Pipewrap Roll offers a simple and more economical alternative to Firestop Collars and avoids the need to carry a wide range

More information

European technical approval

European technical approval Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

The budget Security expert!

The budget Security expert! The budget Security expert! Passive Fire Protection systems Intelligent technology, which protects you when the going gets tough. The innovative technology reacts immediately when it comes into contact

More information

CERTIFICATE OF APPROVAL No CF 513 FSI LIMITED

CERTIFICATE OF APPROVAL No CF 513 FSI LIMITED CERTIFICATE OF APPROVAL No CF 513 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Westminster Industrial

More information

D Side lap. Side lap screw spacing < 500mm factory-installed seals on side lap. Decoupling tape > 60mm

D Side lap. Side lap screw spacing < 500mm factory-installed seals on side lap. Decoupling tape > 60mm 25 Side lap screw spacing < 500mm 333.3 15 42 Decoupling tape > 60mm 3 factory-installed seals on side lap Side lap D 201.1 SECTION VIEWS Type L Ridge profile Type R Ridge flashing FLOOR PLAN > 200 overlap

More information

CERTIFICATE OF APPROVAL No CF 816 BIP GMBH

CERTIFICATE OF APPROVAL No CF 816 BIP GMBH CERTIFICATE OF APPROVAL No CF 816 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of St Peter Straβe 25 (Chemiepark

More information

Product Information High Performance Building Dow Corning Firestop 700 Silicone Sealant

Product Information High Performance Building Dow Corning Firestop 700 Silicone Sealant Product Information High Performance Building Dow Corning Firestop 700 Silicone Sealant FEATURES & BENEFITS Meets BS 476 Part 22 Excellent unprimed adhesion to most porous and non-porous construction substrates

More information

This European technical approval

This European technical approval Authorised and notified according to Article 10 of the Council Directive 89/ 106/EEC of 21 December 1988 on the approximation of laws, regulations and administrative provisions of Member States relating

More information

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems

HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems Data Sheet HILTI CP 674 Cavity Closure For Rainscreen / Cladding Systems The enclosed pages are taken from the Hilti Firestop Systems Manual Edition April 2011 Supported by additional standard details

More information

BICSI March 19 th, 2009 Canadian Regional Meeting NBCC Moncton, New Brunswick. Firestop, it s not Magic It s understanding!

BICSI March 19 th, 2009 Canadian Regional Meeting NBCC Moncton, New Brunswick. Firestop, it s not Magic It s understanding! BICSI March 19 th, 2009 Canadian Regional Meeting NBCC Moncton, New Brunswick Firestop, it s not Magic It s understanding! Presenter: Illya Kornobis Discussion Topic: Firestop and Re-enterable Firestop

More information

3M CS-195+ Composite Sheet Product Description

3M CS-195+ Composite Sheet Product Description Product Data Sheet 3M Product Description 3M Fire Barrier is a one-part composite system comprised of four components. The heart of the system is an organic/ inorganic, fire-resistive elastomeric sheet.

More information

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts.

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIRE DUCT SYSTEMS Rectangular and circular, single layer fire protection for steel ductwork. As part of

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: MINERAL FIBER FIREPROOFING REPORT HOLDER: UNIFRAX I LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2224 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

FIREPRO FIRESTOP PIPE COLLARS. Firestop solution for plastic pipework penetrations

FIREPRO FIRESTOP PIPE COLLARS. Firestop solution for plastic pipework penetrations FIREPRO FIRESTOP PIPE COLLARS Firestop solution for plastic pipework penetrations FIREPRO FIRESTOP PIPE COLLARS Firestop solution for plastic pipework penetrations. ROCKWOOL Firestop Pipe s provide a simple

More information

Fireban One FIRE RATED SEALANT UP TO 4 HOURS FIRE PROTECTION TO AS ONE PART POLYURETHANE

Fireban One FIRE RATED SEALANT UP TO 4 HOURS FIRE PROTECTION TO AS ONE PART POLYURETHANE Fireban One FIRE RATED SEALANT UP TO 4 HOURS FIRE PROTECTION TO AS 1530.4 ONE PART POLYURETHANE Bostik Fireban One Fire Rated Sealant 1 FIREBAN ONE - FIRE RATED SEALANT DESCRIPTION Fireban One is a one-part

More information

PASSIVE FIRE PROTECTION PRODUCTS

PASSIVE FIRE PROTECTION PRODUCTS OCTOBER 2016 PASSIVE FIRE PROTECTION PRODUCTS www.allproof.com CONTENTS FIRE TESTING 1 ADVANCED INTUMESCENT 2 ALLPROOF INTUMESCENT TECHNOLOGY: 2 LOW PROFILE S 3 CONCRETE SLAB TEST RESULTS: 4 FLOOR WASTE

More information

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers.

B. American Society for Testing and Materials: 1. ASTM F708 - Standard Practice for Design and Installation of Rigid Pipe Hangers. SECTION 230529 - HANGERS AND SUPPORTS PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Pipe hangers and supports. 2. Hanger rods. 3. Inserts. 4. Flashing. 5. Sleeves. 6. Mechanical sleeve seals. 7. Firestopping

More information

1. Any modification to these details could result in an application/system not meeting the

1. Any modification to these details could result in an application/system not meeting the . Refer to the following a. 07 8 00 Firestopping b. 07 8 Penetration Firestopping c. 07 8 Joints Firestopping d. 00 00 Plumbing e. 00 00 HV f. 6 00 00 Electrical g. 7 05 7 ommunication s For Quality ontrol

More information

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED

CERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED CERTIFICATE OF APPROVAL No CF 563 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Forge Industrial Estate,

More information

Assembly Instruction. FLAMRO KSL Combi seal according to ETA-16/0320. Content

Assembly Instruction. FLAMRO KSL Combi seal according to ETA-16/0320. Content Content Target audience, usage of assembly instruction, safety information Components Application field (Component strength, insulation strength and distances) Approved assignments and classifications

More information

REGULATORY INFORMATION REPORT

REGULATORY INFORMATION REPORT REGULATORY INFORMATION REPORT The fire resistance performance of Hilti Flexible Firestop Foam CFS-F FX / CP 660 protecting cable and cable conduit penetrations in walls and concrete floors if tested in

More information

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the ÖSTERREICHISCHES I N S T I T U T F Ü R B A U T E C H N I K A-1010 Vienna, Schenkenstrasse 4 Tel.: + 4 3 ( 0 ) 1-5 3 3 6 5 5 0 Fax: + 4 3 ( 0 ) 1-5 3 3 6 4 2 3 relating to construction products E - m a

More information

Product Catalogue 2017

Product Catalogue 2017 T M Product Catalogue 2017 Second Edition Distributed by PASSIVE FIRE-STOPPING FLOWCHART (Basic Service Penetrations) Plan Identify what is required. Is the wall fire rated? If so, what is the fire rating?

More information

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS

SEALING & BONDING SIKA FIRE PROTECTION SOLUTIONS SIKA FIRE PROTECTION SOLUTIONS APPROVED AND RELIABLE: FOR JOINTS AND PENETRATIONS BENEFIT OF OUR SOLUTION Sika provides comprehensive solutions for fire resistant constructions such as tunnels, commercial

More information

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the

Authorised and notified according to Article 10 of the Council Directive 89/106/EEC of 21 December 1988 on the ÖSTERREICHISCHES I N S T I T U T F Ü R B A U T E C H N I K A-1010 Vienna, Schenkenstrasse 4 Tel.: + 4 3 ( 0 ) 1-5 3 3 6 5 5 0 Fax: + 4 3 ( 0 ) 1-5 3 3 6 4 2 3 relating to construction products E - m a

More information

Rail anchoring systems Introduction Bottom-up post-installed method Top-down cast-in method. Rail anchoring systems

Rail anchoring systems Introduction Bottom-up post-installed method Top-down cast-in method. Rail anchoring systems Rail anchoring systems Rail anchoring systems Introduction Bottom-up post-installed method Top-down cast-in method 09 / 2014 These pages are part of the Anchor Fastening Technology Manual issue September

More information

CERTIFICATE OF APPROVAL No CF 663 HILTI AG

CERTIFICATE OF APPROVAL No CF 663 HILTI AG CERTIFICATE OF APPROVAL No CF 663 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of BU Chemicals, Feldkircherstrasse

More information

Fire Protection Products. Firestop Submittal Package FIP 1-Step Firestop Foam. Electrical Trade

Fire Protection Products. Firestop Submittal Package FIP 1-Step Firestop Foam. Electrical Trade Fire Protection Products Firestop Submittal Package FIP 1-Step Firestop Foam Electrical Trade Manufacturer: Fire Protection Products Ryan Fenstermaker 732.921.1503 rfenstermaker@mmm.com Electrical Products

More information

FIRE STOP PRODUCTS. As innovative manufacturers, we are continuously adding to our range, meeting the needs of a highly demanding market.

FIRE STOP PRODUCTS. As innovative manufacturers, we are continuously adding to our range, meeting the needs of a highly demanding market. FIRE STOP PRODUCTS For over 50 years has led the way in passive fire protection. Our products help maintain the safety of public, private, commercial and historical buildings worldwide. Today, continues

More information

Promat PROMASEAL Fire Barrier

Promat PROMASEAL Fire Barrier Promat PROMASEAL Fire Barrier PRODUCT DESCRIPTION Promat PROMASEAL Fire Barriers are slabs of high density rock wool with a white endothermic, ablative coating. APPLICATION Promat PROMASEAL Fire Barriers

More information

The following excerpt are pages from the Firestop Systems Specifiers Guide U.S. Volume 14.

The following excerpt are pages from the Firestop Systems Specifiers Guide U.S. Volume 14. The following excerpt are pages from the Firestop Systems Specifiers Guide U.S. Volume 14. Please refer to the publication in its entirety for complete details on this topic or system including data development,

More information

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp.

Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp. Cable Management Firestop Jean Vaillancourt Fire Protection Specialist Hilti (Canada) Corp. FIRESTOPPING KNOWLEDGE FOR BETTER SPECIFICATION AND DESIGN OF FIRE-RATED CONSTRUCTION Presentation Topics and

More information

Innovative Fire Protection Systems ETA CATALOG

Innovative Fire Protection Systems ETA CATALOG Innovative Fire Protection Systems ETA CATALOG Overview / Introduction / Credentials / Certified safety / Approval overview / EOTA Member States 3-8 3 4 5 6 8 New applications and / firestop systems /

More information

Pyroscat Duct Wrap XL

Pyroscat Duct Wrap XL Datasheet Code US: - 0 Thermal Ceramics is a business of Morgan Advanced Materials * Commonly referred to test method CA Section 00 is CDPH Standard Method for the Testing and Evaluation of Volatile Organic

More information

Insulation in decks and bulkheads PYROLIQ sealing compound system

Insulation in decks and bulkheads PYROLIQ sealing compound system Insulation in decks and bulkheads PYROLIQ sealing compound system PYROLIQ casting compound In industry, ship construction and offshore areas, very high requirements are placed on cable and pipe penetrations

More information

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone:

Cardok Sàrl CP37 CH-1295 Tannay Switzerland Phone: CARDOK CARLIFT with Rigid chains technology Very fast access to underground garages Fast, Silent, Discreet, Design, High-Tech Installation to replace an access ramp on private property Dimensions: (Built

More information

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade)

Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) CERTIFICATE NO. 03/0183 DETAIL SHEET 1 Xtratherm Thin-R Partial Fill Cavity Wall Board (XT/CW Grade) PRODUCT DESCRIPTION This Detail Sheet relates to Xtratherm Thin-R Partial Fill Cavity Wall Board, as

More information

DECEMBER Phone: Fax:

DECEMBER Phone: Fax: DECEMBER 007 TM system components www.nsiindustries.com Phone: 800.1.587 Fax: 800.81.5566 Table of Contents FireStop System Components Intumescent Caulk...1 Silicone...1 Silicone SL... FireStop81.... FireBlock16...

More information

Assembly Instruction. Fire protection collars

Assembly Instruction. Fire protection collars Assembly Instruction Fire protection collars Please respect the permit specifications. All documents may be downloaded from www.flamro.com/services/downloads. It is assumed that - Any damage to the seal

More information

ROOF MOUNT KIT OWNERS MANUAL

ROOF MOUNT KIT OWNERS MANUAL ROOF MOUNT KIT OWNERS MANUAL Made in the USA by: Primus Wind Power, Inc. 938 Quail St. Lakewood, CO 80215 Phone: (303) 242-5820 www.primuswindpower.com AIR is a trademark of Primus Wind Power, Inc. ROOF

More information

BROADCAST: M BLOCKS, PLUGS, PLANKS NEW PRODUCT LAUNCH Date: June 16, 2016 Issued by: George Yoshida, Ted Colwell

BROADCAST: M BLOCKS, PLUGS, PLANKS NEW PRODUCT LAUNCH Date: June 16, 2016 Issued by: George Yoshida, Ted Colwell BROADCAST: M16-001 BLOCKS, PLUGS, PLANKS NEW PRODUCT LAUNCH Date: June 16, 2016 Issued by: George Yoshida, Ted Colwell TITLE: DESCRIPTION: NEW PRODUCT LAUNCH 3M FIRE BARRIER BLOCKS, PLUGS AND PLANKS 3M

More information

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years.

ICC-ES Evaluation Report Reissued May 1, 2010 This report is subject to re-examination in two years. ICC-ES Evaluation Report ESR-1255 Reissued May 1, 2010 This report is subject to re-examination in two years. www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council

More information

FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct

FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct FastWrap+ 1 1 /2 Commercial Kitchen Grease Duct Air Ventilation Duct Fire Protection Systems Product Data and Installation Guide NFPA 96 IMC 1. Product Description - New and Improved FastWrap+ Thermal

More information

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution

B-LINE SERIES. DURA-BLOK rooftop supports BRTS-17 DURA-BLOK. A complete rooftop support solution DURA-BLOK rooftop supports BRTS-17 B-LINE SERIES DURA-BLOK A complete rooftop support solution DURA-BLOK rooftop solutions support DURA-BLOK supports are made of 100% recycled rubber and are designed to

More information

1. Division 23 Section "Hangers and Supports for HVAC Piping and Equipment" for pipe insulation shields and protection saddles.

1. Division 23 Section Hangers and Supports for HVAC Piping and Equipment for pipe insulation shields and protection saddles. SECTION 23 07 19 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS

SPECIFICATION DIVISION 7 NUMBER SECTION DESCRIPTION DIVISION 07 THERMAL AND MOISTURE PROTECTION SECTION THROUGH-PENETRATION FIRESTOP SYSTEMS BuildingName The Description of the Project P00000000 0000 DOCUMENTS Title Page Table of Contents Instruction to Bidders Form of Proposal Equal Opportunity Statement Form of Guarantee Supplemental General

More information

FIRESTOPPING. The Hidden Solution that Compartmentalizes. Vic Wootton A/T Firestop and Fireproofing Solutions

FIRESTOPPING. The Hidden Solution that Compartmentalizes. Vic Wootton A/T Firestop and Fireproofing Solutions FIRESTOPPING The Hidden Solution that Compartmentalizes Vic Wootton A/T Firestop and Fireproofing Solutions Firestop What is Firestop Where Required Why Important Who Installs Type of Products How to Install

More information

Pipe Supports Comparison

Pipe Supports Comparison PIPE SUPPORTS: Comparison of the installation costs for various systems ARMAFIX The easy to install and cost effective solution to prevent thermal bridging at the pipe bracket in low-temperature applications.

More information

Technical Data Sheet StoLevell Duo plus

Technical Data Sheet StoLevell Duo plus Mineral bonding and reinforcing mortar Characteristics Areas of application Properties Exterior and interior For all mineral substrates For bonding insulation boards onto mineral substrates For producing

More information

BlazeBrake. Fire Protection Systems. Retrofit Fire Rated Devices for Cable & Pipe Services

BlazeBrake. Fire Protection Systems. Retrofit Fire Rated Devices for Cable & Pipe Services BlazeBrake Systems Retrofit Fire Rated Devices for Cable & Pipe Services Retrofit Fire Pillows For Cables & Metal Pipes Up to 4 Hour Fire Rating in Floors & Walls Description Blazebrake Fire Rated Pillows

More information

Protecting Penetrations in Fire Rated Construction

Protecting Penetrations in Fire Rated Construction Protecting Penetrations in Fire Rated Construction NY State Fire Marshals and Inspectors Conference September 7 th Bruce E. Johnson UL Codes and Advisory Services UL and the UL logo are Trademarks of UL

More information

3-part thixotropic epoxy patching mortar

3-part thixotropic epoxy patching mortar Product Data Sheet Edition 28/08/2006 Identification no: 02 04 02 03 001 0 000044 3-part thixotropic epoxy patching mortar Construction Product Description Uses Characteristics / Advantages Sikadur -41

More information

Hoesch isodach integral Technical information

Hoesch isodach integral Technical information Technical information A company of ThyssenKrupp Steel tk Contents Page General 3 Main dimensions and properties 4 Corrosion protection 5 Thermal protection / Insulating core 5 Fire protection 5 Information

More information

FIRESTOP SUBMITTAL PACKAGE

FIRESTOP SUBMITTAL PACKAGE FIRESTOP SUBMITTAL PACKAGE PLUMBING Materials FS-ONE Intumesent Caulk Includes: Technical and Installation Data UL Certificate of Compliance LEED information MSDS UL Details Gypsum Wall Assemblies W-L-1054

More information

Product Data Sheet Sikadur -31 CF Normal Product Description Uses ruction Const Characteristics / Advantages

Product Data Sheet Sikadur -31 CF Normal Product Description Uses ruction Const Characteristics / Advantages Construction Product Data Sheet Edition 02/12/2013 Identification no: 02 04 02 03 001 0 000039 Sikadur -31 CF Normal 2-part thixotropic epoxy adhesive Product Description Uses Characteristics / Advantages

More information

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE.

FEATURES APPLICATIONS. Technical data sheet SSW - STEEL STRONG-WALL FOR TIMBER FRAME RACKING RESISTANCE. The Steel Strong-Wall is a corrugated steel panel which is designed to be fixed directly to the concrete foundations of a building, within the external or internal wall, via a bolted connection. FEATURES

More information

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5

FIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079) WET FILM ± 7.5 ± 5 Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a

More information

Quieting New Zealand one space at a time

Quieting New Zealand one space at a time Quieting one space at a time Inventory Catalogue Correct as of JUNE 2016 Quantity and Trade Discounts available. Contact us to find out more! Acoustiblok 3mm and 6mm A revolutionary 3mm stiff, flexible

More information

FireMaster FastWrap XL

FireMaster FastWrap XL Datasheet Code US: 7-14-36 MSDS Code US: 406 009 Morgan Thermal Ceramics, a business within the Morgan Ceramics Division of The Morgan Crucible Company plc * Commonly referred to test method CA Section

More information

3M Fire Barrier Duct Wrap 615+ Product Data Sheet and Installation Guide (Condensed Version)

3M Fire Barrier Duct Wrap 615+ Product Data Sheet and Installation Guide (Condensed Version) M Fire Barrier Duct Wrap + Product Data Sheet and Installation Guide (Condensed Version) FIRE BARRIER UP TO Fire Protection HOUR FLEXIBLE WRAP GREASE & AIR DUCT Fire Protection. Product Description M Fire

More information

Sormat ITH-Pe PRODUCT DATA SHEET. ITH-Pe - POLYESTER BASED RESIN STYRENE FREE. Polyester based injection resin, styrene free. ITH 165 Pe art.

Sormat ITH-Pe PRODUCT DATA SHEET. ITH-Pe - POLYESTER BASED RESIN STYRENE FREE. Polyester based injection resin, styrene free. ITH 165 Pe art. ITH 165 Pe art. 72900 Application in noncracked concrete ITH 300 Pe art. 72940 ITH 410 Pe art. 72941 Content Page Product description 2 Properties and benefits 2 Sample applications 2 Applications and

More information