1 - Residential Inspection Specialists - Date of Inspection: 24th February 2016 Time of Inspection: 2:00 PM Weather: Sunny-Hot Inspection Type: Pre-Sale Inspection Report Type: Full Infrared Inspection Report Address: 335B Glenfield Road Glenfield Auckland Client: Petrice Cancare Inspector: Tim Smith Report Written by : LB Reference Number: of 25

2 - TABLE OF CONTENTS Page # COVER PAGE...1 TABLE OF CONTENTS...2 Inspection Equipment...3 Weather-Tightness Observations (CLADDING)...5 Weather-Tightness Observations (ROOFING)...7 Weather-Tightness Observations (MISC)...9 Maintenance Observations...11 Areas of Concern...15 Infrared Inspection...16 General Observations...18 Report Summary...20 General Information...21 Certification:...22 Cladding Maintenance Guide...23 Terms and Conditions...24 Instructions: Thermo Pro Inspections was commissioned by the property owners to carry out a Pre-Sale Inspection and prepare a builders report on the property. An Infrared Inspection was commissioned as part of the builders report. Thermo Pro Inspectors are fully trained ISO Qualified Thermographers and were qualified to perform this inspection. The Thermo Pro Inspector may have taken the liberty to move items of furniture or personal items that we deemed necessary to carry out a comprehensive inspection of the property. The Thermo Pro Inspector may have lifted carpet in corners of rooms, on thresholds of doors, under windows and anywhere he felt was necessary to inspect the flooring. NOTE: 2 of 25

3 Inspection Equipment Normal moisture reading on window frame. Normal moisture reading on tiles over Gib For non invasive moisture testing, Thermo Pro Inspections use the Trotec T650 material moisture meter, which has a material moisture measurement of up to 40mm. The Trotec T650 material moisture meter is a Dielectric Moisture Meter. The reading for moisture is 80. Various materials give different readings and the proximity of metals, concrete and other dense materials will vary the reading from normal. Because of this, high dielectric moisture readings only indicate the possible presence of moisture. Where there is a reading indicating moisture the Thermo Pro Inspector will verify this with the Trotec T500 moisture meter or FLIR Infra-red Camera. Moisture reading at base of door frame. Reading in framing of bay window seat. For invasive and moderately invasive moisture readings the Trotec T500 moisture meter is used. The Trotec T500 moisture meter gives a percentage reading of moisture in wood or plaster board using the resistance method. It is suitable for testing in areas where the pin holes it makes are not a concern. The Trotec T500 moisture meter is the best device for verifying moisture readings detected by non invasive means. 3 of 25

4 Inspection Equipment.. Cont'd For infra-red inspections Thermo Pro Inspections use the FLIR T 200 Infra-red Camera. Thermo Pro Inspectors are ISO certified thermographers. What looks like a normal ceiling with good paint finish. Infra-red shows moisture from an upstairs terrace with a leaky door threshold. Infrared camera will help locate or verify moisture presence in many areas. All thermal anomalies are verified with non invasive moisture meters. 4 of 25

5 Weather-Tightness Observations (CLADDING) The property inspected is clad with EIFS insulated The cladding system is in mostly good condition. plaster (Insulclad) on timber framing. See maintenance for exceptions. The aluminium joinery is in good condition, all windows and doors opened and closed freely. Joinery has typical weather details for the early type Insulclad. It incorporates an over lap rather than flashings. The windows rely on sealant to keep the building waterproof. Moisture readings taken internally were mostly normal at time of inspection. Cladding penetrations are well sealed. Cladding to ground clearances are minimal. Refer to maintenance for further details. 5 of 25

6 Weather-Tightness Observations (CLADDING) There are some cedar weather-board feature walls. Boards are are stained/painted, corner mouldings appear in good condition. Ground clearance is minimal. 6 of 25

7 Weather-Tightness Observations (ROOFING) The roof is clad with Coloursteel tiles. Roof pitch appears to be adequate for the roofing material. The Coloursteel tile roof is in average weathered condition. The roof penetrations are correctly flashed and well sealed. Flashings are correct type for roof profile and in mostly good condition. Refer to maintenance for further details. The ridge flashings are correct type and well formed. The Coloursteel gutters were in good condition at time of inspection. 7 of 25

8 Weather-Tightness Observations (ROOFING) Apron flashings must be well sealed, but no kick- The PVC downpipes are secure and in mostly out flashings are installed. good condition. Refer to maintenance for further details. Low pitched carport roof section is clad with tray-type Coloursteel sheets, in good condition. There is a brand new flashing at the roof junction which is the correct type for roof profile. 8 of 25

9 Weather-Tightness Observations (MISC) The garage entry has no cover and adequate drip Surface storm-water drain installed at edge of edge. paving. There is inadequate gap between decking and Moisture can be trapped between the cladding cladding. Min. clearance of 12mm recommended. and deck causing moisture ingress. The upper level deck surface is clad with open draining timber decking. The deck parapets are well plastered with timber capping. No saddle flashings installed. Refer to maintenance for further details. 9 of 25

10 Weather-Tightness Observations (MISC) Ensure the bottom door channels are kept clean and drain holes open to avoid risk of moisture ingress. The timber garden retaining walls are in mostly good condition. 10 of 25

11 Maintenance Observations Kitchen cabinet door hinges need adjustment. Door hardware is in need of maintenance, loose hinges on master bedroom french doors are causing door to bind. Tighten screws to secure. Infrared inspection of the bathroom ceiling found thermal anomalies indicating moisture ingress. Dampness conformed with dielectric moisture meter. It is unclear whether this is from before roof flashings were replaced. No visible damage or water ingress. Probably an intermittent leak. Recommend re-check in two weeks. Recommended minimum cladding to paving clearance is 150mm. Inadequate clearance can be a risk to moisture ingress. This building was constructed before ground clearance was required for plaster cladding. 11 of 25

12 Maintenance Observations Cracks in the plaster cladding beside and over garage door need maintenance, refer to Cladding Maintenance Guide at end of this report. Other cracks in plaster cladding require maintenance. Concrete haunching around gully trap is broken. Timber decking requires maintenance, split decking, nails are popping, and stain needs renewing. 12 of 25

13 Maintenance Observations Flashing tap has been applied to junction of There is cracking and isolated decay in some of Coloursteel tiles and barge flashings. This is a barge boards. temporary fix. But should last a number of years. Junction of timber parapet capping and cladding needs to be well sealed. Timber capping is cracking with soft spots indicating rot. Timber needs repair and re-painting. Paint surface on Coloursteel tiles is faded and needs re-painting. Lead edges to this apron flashing are broken. This is a risk to moisture ingress. Consult qualified roofer to replace or repair. 13 of 25

14 Maintenance Observations Drainpipe from upper level roof should not discharge directly on apron flashings. This can be a risk to moisture ingress. Install a diverter or spreader. 14 of 25

15 Areas of Concern Inspection of the lounge found high moisture readings and localised rot in the bottom plate. This is the corner close to the front entrance. Further investigation found the likely source is the window sill in the bedroom above. There is old silicone which has deteriorated and a bonded flashing over the front door area. Will need further investigation to confirm source of leak and extent of timber decay. Inspection of the laundry found high moisture readings in back wall under the tub and in skirting boards adjacent to the tub. Skirting boards are swollen. This needs further investigation to determine the source of moisture ingress or plumbing leak. 15 of 25

16 Infrared Inspection Digital image of kitchen ceiling. No thermal anomalies in the infrared image. Digital image of lounge ceiling. No thermal anomalies in the infrared image. Digital image of hallway ceiling. No thermal anomalies in the infrared image. 16 of 25

17 Infrared Inspection Digital image of laundry ceiling. No thermal anomalies in the infrared image. Digital image of study ceiling. No thermal anomalies in the infrared image. Digital image of garage wall/doorway. No thermal anomalies in the infrared image. Infrared inspection of all exterior walls and ceilings taken internally, found one moisture related thermal anomaly at time of inspection. See maintenance for further comment. NOTE: Images used are a representative sample of a full scan of the property. 17 of 25

18 General Observations Kitchen Inspected, cupboards and drawers checked, Refer to maintenance details. Laundry inspected, moisture readings were mostly normal at time of inspection, Refer to maintenance details. Main bathroom inspected, moisture readings were mostly normal at time of inspection. See maintenance for further comment. Upstairs bathroom inspected, moisture readings were normal at time of inspection. All bedrooms inspected, moisture readings were normal at time of inspection. Living areas inspected, most moisture readings were normal at time of inspection, Refer to maintenance details. Hot water cylinder inspected. Dated: September 2010 Hot water cylinder pipes & valves checked for leaks. OK The garage door was tested, garage moisture readings were normal at time of inspection. The roof space was inspected insulation present. There was no sign of moisture ingress or damage at time of inspection. Electrical distribution board has modern circuit breakers and RCD installed. 18 of 25

19 General Observations Heat pump not tested. Normal servicing & cleaning is required to maintain effective performance. This property was constructed Garden shed located at rear, not before untreated timber was inspected. used in residential construction. Timber appears to be marked as treated but writing was not clear. 19 of 25

20 Report Summary Cladding & Joinery: The EIFS insulated plaster on timber framing is in average condition. The aluminium joinery is in good condition. Joinery has correct flashings and weather details, all windows and doors opened and closed freely. Roofing: The Coloursteel tile roof is in average weathered condition. The Coloursteel gutters are in good condition. Roof pitch appears to be adequate for the roofing material. Flashings are correct type for roof profile and in good condition. Roof Space: The roof space was inspected & insulation present over all areas. There was no sign of moisture ingress or damage at time of inspection. Foundation/slab: The foundation is concrete footings and slab. The floor is concrete with no obvious signs of failure at time of inspection. Non Invasive Moisture Readings: Non invasive moisture meter readings taken internally around all windows, exterior doors, and around utilities, were mostly normal at time of inspection, Refer to maintenance for details. Infrared Inspection: Infrared inspection of all exterior walls and ceilings taken internally, found one moisture related thermal anomaly at time of inspection. General comments: The property is in average overall condition. It has some outstanding maintenance issues and two obvious areas of concern. General wear and tear is consistent with the age of the property. Note: This property was constructed before untreated timber was used in residential construction. It is likely to be H1 Boric Treated timber. Timber appears to be marked as treated but writing was not clear. Our Service Commitment Thermo Pro's services to you are in the delivery of quality house inspections. Our inspectors have a range of building related experience. With this industry knowledge we are better equipped to identify good building practices from bad and find any problems or potential problems. Our use of infrared and moisture detection technologies increases our level of accuracy and certainty in identifying weather-tightness issues and structural anomalies. We strive for a high standard in what we do, thorough pre-sale and pre-purchase house inspections. We are not experts in any single building discipline (plastering, plumbing, electrical, roofing etc.) We endeavour to clarify wherever possible the limitations of our advice, conclusions or recommendations. Our professional opinion is not a guarantee against future failure in any product or service. Any conclusions drawn in our report should be verified or qualified by a trade expert in the area concerned. Definition of Terms Very Good As new condition. No maintenance issues. Good Some expected wear for age of property, some standard/minor maintenance issues. Reasonably Good More areas that need attention than reasonable for age of property but not of major concern. Average Average condition for the age of property, expected no. of maintenance issues and wear present. Poor Low maintenance levels, neglected upkeep requiring significant repairs. Very Poor Major areas of concern and significant maintenance issues, failure of materials. Areas of Concern Significant number and/or severity of maintenance issues, or product failures, requiring urgency. 20 of 25

21 General Information Scope of inspection: Under the Standards NZS 4306, the scope of the Inspection is limited to a visual inspection of the components of the building, which the inspector has reasonable access to and being in their clear line of sight. The report shall include grounds, retaining walls, house exterior, structure, foundations and sub-floor area, roofs ceiling space, security, plumbing summary, electrical summary, heating summary, interior summary of rooms, checking for the operation of all doors and windows is also included. The purpose of the property inspection is to identify significant defects visible at the time of the inspection, the report shall reflect conditions as found on the day of inspection only. Minor fault or defect as described in the NZS 4306: a matter which in the view of the age, type or condition of the residential building, does not require substantial repairs or urgent attention and rectification and which could be attended to during normal maintenance. Note- minor defects are common to most properties and may include minor blemishes, corrosion, cracking, weathering, general deterioration, unevenness, and physical damage to materials and finishes. The inspector shall consider when making the assessment, matters such as instability, weather tightness risk and the standard of workmanship. Limitations: Any areas that are concealed, contained, inaccessible, or cannot be sighted, due to walls, wall linings, ceiling linings, floors, paths, soils, gardens, insulation, furniture, stored items, systems, vehicles, personal items, or any other object will not be inspected or included in the report. The client shall assume all risk, for any condition or problems that may be concealed at the time of the inspection. No item shall be dismantled, moved, or dislodged during the inspection, and there will be no destructive testing undertaken. Reasonable access: Areas where safe, unobstructed access is provided and the minimum clearances specified in Table 1 are available; or where these clearances are not available, areas within the inspectors unobstructed line of sight. Note- It shall be clearly stated if no access was available, or access to limited areas only was available at the time inspection was carried out. Table-1 Area Access manhole mm Crawl Space mm Height Roof Space 450mm x 400mm 600mm x 600mm Accessible from a 3.6m Ladder Sub-floor 500mm x 400mm Vertical Clearance Timber Floor; 400mm* Concrete Floor; 500mm Roof Exterior Accessible from a 3.6m Ladder *From underside of bearer 21 of 25

22 Certification: ThermoPro Certificate We hereby certify that I have carried out the inspection of the property at: 335B Glenfield Road Glenfield Auckland Ref: 5748 In accordance with NZS4306:2005 Residential Property Inspection and we are competent to undertake this inspection. Signature: Tim Smith Date: 24th February 2016 Director Member Building Officials Institute of NZ Limitations: The client shall assume all risk, for any condition or problems that may be concealed at the time of inspection. No item shall be dismantled, moved, or dislodged during the inspection, and there will be no destructive testing undertaken. An investigation of the condition and location of underground drainage and services and of hidden electrical, gas and plumbing is not included. No invasive or destructive inspection methods have been used in the assessment and concealed work not inspected, therefore no opinion or warranty can be offered in respect of the said concealed work. An inspection carried out in accordance with NZS4306:2005 is not a statement that a property complies with the requirements of any Act, regulation or by-law. 22 of 25

23 Cladding Maintenance Guide All Cladding Systems: Regular maintenance - is essential in maintaining the water tightness and longevity of all cladding systems. Regular cleaning - (at least annually) of the paint coating is required to remove grime, dirt and organic growth and to maximize the life and appearance of the coating. Grime may be removed by brushing with a soft brush, warm water and detergent. Plaster Cladding Systems Repair/Maintenance: Re-painting - Paint system must be re coated at approximately 5-7 year intervals in accordance with Plaster system manufacturers instructions. Annual inspections - must be made to ensure that all aspects of the cladding system, including the coating system, plaster, flashings and any control joins, cladding to ground clearances remain in a waterproof condition. Any cracks, damaged areas or areas showing signs of deterioration, build-up of gardens next to cladding which would allow moisture ingress, must be repaired/corrected immediately. Repair and Maintenance of cracks: What to look for; Places where water can get into the framing, and Some signs that water has already got in are: holes, cracks, loose plaster, loose fixings, joints that have separated, around joinery, anywhere where the sealing has failed, or any area where water can pool against or soak into cladding. Moisture staining and other visible water damage. Musty smells. Efflorescence (white chalky substance) at junctions or cracks. Mould, moss or colour degradation. Blistering or fading of paintwork, or bubbling or peeling of wallpaper. Levels of damage: Cracks under 1mm wide can be painted over using an Elastomeric Paint after correct preparation and cleaning of the affected area. Cracks over 1mm require filling with an MS type paintable Elastomeric Sealant and then repainted with elastomeric paint. Significant cracks or damage require the plaster system to be ground off and reinforcing fibreglass mesh fixed and plastered over. Want more information on monolithic cladding (plaster cladding) go to our website page: 23 of 25

24 Terms and Conditions ThermoPro Terms and Conditions 1. Pricing As per Services and prices page on our website. 2. Terms of payment Payment of our fee is payable upon provision of the report and invoice. Payment should be made direct as per instructions on our invoice. 3. Standard of inspections Our inspections are intended to be carried out in accordance with New Zealand Standard NZS 4306:2005. A copy of the standard can be obtained from Standards New Zealand. A property report is intended to report on the following matters which may be identified using the external inspection methods employed by Thermopro Inspections Ltd. (a) Significant defects; (b) Particular attributes; (c) Gradual deterioration; and (d) Significant maintenance required. A property report is not a destructive test, a Code Compliance Certificate, a Certificate of Acceptance under the Building Act, nor a statement that the property complies with the requirements of the Building Act or any other Act, regulation, or by-law. A property report is not a warranty against problems developing with the building after the date of the report. Estimating the cost of remedying defects is also not part of the report. 4. Ongoing maintenance All buildings will deteriorate without proper maintenance. A copy of some tips in relation to proper maintenance is available in this report and on our website. 5. Limitations of liability and unavailability of professional indemnity insurance Although our inspections are intended to give a reasonable assessment of the condition of the property, and are intended to be carried out in accordance with the applicable New Zealand Standard, without destructive testing it is not possible to be 100% certain that all potential defects have been discovered. There is also the possibility that the owner of the property may have intentionally disguised defects in the property. Our inspection in confined to the limitations specified by New Zealand Standard NZS 4306:2005 for property inspections. Due to these factors it is not possible for us to guarantee that all potential defects have been discovered. Due to the number of leaky building claims in New Zealand it is no longer practical to obtain professional indemnity insurance. Continued of 25

25 Notwithstanding anything in this or any other agreement with Thermopro Inspections Ltd, the liability of Thermopro Inspections Ltd, the person carrying out the inspection, and all of Thermopro Inspections Ltd s employees, contractors, directors and shareholders ( the protected parties ), for any loss, damage or delay arising from any act, default or omission (whether negligent or otherwise) in relation to the inspection, the report, or any service provided by, or statement made by, or act of, any of the protected parties ( the defects ): (a) Is restricted to any bad faith defects; (b) Is excluded in the case of all other defects made in good faith, including mistakes, misdescriptions and omissions whether made negligently or recklessly, and whether they occurred during the course of the inspection, were made orally, in the written report, or otherwise howsoever; (c) Shall be limited to physical damage or injury to any person or property which in any case is the foreseeable result of the defect; (d) Shall be excluded in the case of economic and consequential loss (including loss of rent or enjoyment of the property) (e) In any event is limited to the fee paid to Thermopro Inspections Ltd. The above limitations are severable with the intention that if any one of them is unenforceable then the other limitations will still be enforceable. This limitation of liability binds the person who requested the report, and any other person to who the report is provided to, together with their successors and assigns. The report generated by Thermopro Inspections Ltd is not to be relied upon by any person other than the person to whom the report is addressed to. 25 of 25

ThermoPro Inspections Ltd - Residential Inspection Specialists -

ThermoPro Inspections Ltd - Residential Inspection Specialists - - Residential Inspection Specialists - Date of Inspection: 10th March 2015 Time of Inspection: 9:30 AM Weather: Sunny-Fine Inspection Type: Pre-Sale Inspection Report Type: Full Infrared Inspection Report

More information

BUILDING REPORT. 123 Anywhere Street Suburb City. Prepared for: Client NON INVASIVE

BUILDING REPORT. 123 Anywhere Street Suburb City. Prepared for: Client NON INVASIVE 0 NON INVASIVE BUILDING REPORT 123 Anywhere Street Suburb City Prepared for: Client 1 Following your instructions we visited the above property on the 11/06/12 to carry out a non-invasive building inspection

More information

DryScan Limited was engaged to complete a Pre-Purchase Scan only moisture ingress thermal imaging inspection for Joe Blogs at 8 Anywhere, Auckland.

DryScan Limited was engaged to complete a Pre-Purchase Scan only moisture ingress thermal imaging inspection for Joe Blogs at 8 Anywhere, Auckland. Infrared Inspections DryScan Limited PO Box 869, Whangaparoa, Auckland 0943 Free phone: 0800-DRYSCAN ~ Mobile: 021 892 056 ~ Fax: 0064 9 421 1792 Email: bryce@dryscan.co.nz 6 th March 2012 Joe Blogs 8

More information

Po Box Chartwell 3248 Hamilton Free Ph

Po Box Chartwell 3248 Hamilton Free Ph Po Box 12660 Chartwell 3248 Hamilton Free Ph 0800 223 556 Email tony@kiwiinspections.co.nz INTRODUCTION Independent building inspection report on 12 Holly Place, Rototuna North, Hamilton This report has

More information

Sample Report, Auckland

Sample Report, Auckland Building and Infrared Inspections Sample Report, Auckland REPORT TYPE: DATE OF INSPECTION: 11th April 2015 DRYSCAN LIMITED PO Box 869, Whangaparaoa, Auckland 0932 Free phone: 0800-DRYSCAN Mobile: 021 892

More information

Determination 2012/010

Determination 2012/010 Determination 2012/010 Regarding the refusal of code compliance certificates for a 12-year-old house with monolithic cladding and a 7-year-old pergola addition at 12 Diana Avenue, Gisborne 1. The matter

More information

Determination 2010/052 Refusal to issue a code compliance certificate for a 6-year old house at 103 Karewa Parade, Papamoa

Determination 2010/052 Refusal to issue a code compliance certificate for a 6-year old house at 103 Karewa Parade, Papamoa Determination 2010/052 Refusal to issue a code compliance certificate for a 6-year old house at 103 Karewa Parade, Papamoa 1. The matters to be determined 1.1 This is a determination under Part 3 Subpart

More information

Owner Builder Inspection Report

Owner Builder Inspection Report www.sherspec.com Owner Builder Inspection Report PREPARED FOR USE IN ASSESSING A PROPOSAL FOR WARRANTY INSURANCE TO BE ISSUED UNDER SECTION 137B (2)(a) OF THE BUILDING ACT 1993 INSPECTION DETAILS Registered

More information

INSPECT DIRECT Pty Ltd

INSPECT DIRECT Pty Ltd Web Page: www.inspectdirect.com.au INSPECT DIRECT Pty Ltd Property Address: Sample.Dilapidation.Report Victoria Building Status / Dilapidation Report This is not a Pest Inspection The Building Status /

More information

WEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT

WEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT WEATHERTIGHTNESS (INVASIVE MOISTURE TESTING) ASSESSMENT 1 INTRODUCTION Inspection Date: 24 TH August 2016 Job No:47126 Property Inspected: 1-51 Watford Street Christchurch Weather Conditions: Fine Prepared

More information

HANDOVER INSPECTION PRE-PURCHASE BUILDING INSPECTION REPORT

HANDOVER INSPECTION PRE-PURCHASE BUILDING INSPECTION REPORT PPDoesn t Apply HANDOVER INSPECTION PRE-PURCHASE BUILDING INSPECTION REPORT This Report» Building Inspection Report» House ONLY» House AND Unit» All inspections are standard visual reports in accordance

More information

Regarding the refusal to issue a code compliance certificate for a 13-year-old house at 14 Patsy O Hara Place, Swanson, Auckland

Regarding the refusal to issue a code compliance certificate for a 13-year-old house at 14 Patsy O Hara Place, Swanson, Auckland Determination 2011/077 Regarding the refusal to issue a code compliance certificate for a 13-year-old house at 14 Patsy O Hara Place, Swanson, Auckland 1. The matter to be determined 1.1 This is a determination

More information

Inspection details. Subfloor. Subfloor. Before You Buy property inspection

Inspection details. Subfloor. Subfloor. Before You Buy property inspection Before You Buy 254 Richmond Rd, Auckland, 1011, Auckland info@beforeyoubuy.co.nz www.beforeyoubuy.co.nz 29th Sep, 2015 Inspection details Property owner Joe Bloggs Address 36 Bloggs st Date 03 Jul 2015

More information

Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland

Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland Determination 2011/095 Regarding the code-compliance of a channel drain around the foundation of a house and garage at 533 Waitoki Road, Wainui, Auckland 1. The matter to be determined 1.1 This is a determination

More information

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002

Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Storm Damage Assessment Report For: 1234 Example Street., Houston, TX 77002 Prepared For: Miriam Saliba nspection Date: 9/6/2017 Prepared By: Adam Wells TREC License # 21140 105 E Spreading Oaks Ave, Friendswood,

More information

Date of inspection 19/2/2015. House inspection. Geraldine Wong. Address:

Date of inspection 19/2/2015. House inspection. Geraldine Wong. Address: House Inspection Specialists Member of NZ Institute of Building Inspectors Sum Insured Home Rebuild Cost Appraisals Pre Purchase Inspections Mobile: 0274 522 159 Work: 09 5334521 www.fchi.co.nz NZS 4306-2005

More information

KEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822

KEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822 KEVIN BURNS BUILDING INSPECTIONS REGISTERED BUILDER 6163 PRE-PURCHASE VISUAL STRUCTURAL INSPECTION REPORT No. 822 CLIENT: Talavera PROPERTY ADDRESS: Mindarie DATE: 20 April 2017 TIME: 9.00am WEATHER: Fine

More information

INSPECTOR GROUP PTY LTD

INSPECTOR GROUP PTY LTD Website: http://www.inspectorgroup.com.au Inspector's email: peter@inspectorgroup.com.au Inspector: Peter Hopfinger Building Surveyor & Timber Pest Inspector Registration Number: 2194 Mob: 0414 607 240

More information

Home Inspection Report. Home Inspection Report DRAFT ONLY

Home Inspection Report. Home Inspection Report DRAFT ONLY Cover Page Home Inspection Report Home Inspection Report Inspection prepared for: Date of Inspection: 26/1/2017 Time: 10.00am-12.01pm Age of Home: 1980's Size: Approx 90sqm Inspector: Phone: 021 064 8604

More information

SAMPLE REPORT Location:

SAMPLE REPORT Location: Stucco Check Inspections, LLC Invasive Stucco Inspection Prepared for: SAMPLE REPORT Location: Sample Houston, TX PHONE: 713.319.5751 EMAIL: Info@stuccocheck.com I. INTRODUCTION 1.1 PURPOSE: Enclosed is

More information

SHS Building Consultants. Ph Job Details. Photograph shows the front elevation of the residence.

SHS Building Consultants. Ph Job Details. Photograph shows the front elevation of the residence. Practical Completion Report Inspection date 1 st January Client Mohit Vir Job Details Address Lot 3349 Limone street Aveley. W.A. Photograph shows the front elevation of the residence. DESCRIPTION OF THE

More information

Cascade Thermal Imaging, Inc. ~ Infrared Imaging The Non-Invasive Truth ~ Thermography Report

Cascade Thermal Imaging, Inc. ~ Infrared Imaging The Non-Invasive Truth ~ Thermography Report TM Thermography Report Completed for: Mr. John Smith 2242 Greenwood Ave - Seattle, WA 98102 Thermography date: 1-26 & 1-29-16 Outdoor temperature: 54 F Indoor temperature: 68 F Temp diff In-Out Δ T : 14

More information

Determination 2007/10

Determination 2007/10 Determination 2007/10 Refusal of a code compliance certificate for additions to a building with timber weatherboards, profiled metal and monolithic cladding systems at 283 Maitai Valley Road, Nelson 1.

More information

Infrared Inspection Report

Infrared Inspection Report Infrared Inspection Report 1234 Sample St, Anywhere Inspection Date/Time: 3/12/2007-11:00 AM Prepared For: Dave Smith Prepared By: Norton Inspection Co. 6632 Telegraph Rd, #346 Bloomfield Hills, MI 48301

More information

Property Inspection Report

Property Inspection Report - Habit New Zealand Limited Sample Report. 1945 Direct Fixed Cladding With Issues This report is for the sole benefit of: Sample Report Only Page 1 of 88 Terms and Conditions Payment Terms and Conditions

More information

Refusal of a code compliance certificate for a building with a monolithic cladding system: House 9

Refusal of a code compliance certificate for a building with a monolithic cladding system: House 9 Refusal of a code compliance certificate for a building with a monolithic cladding system: House 9 1 THE DISPUTE TO BE DETERMINED 1.1 This is a determination of a dispute referred to the Chief Executive

More information

Refusal of a code compliance certificate for a building with a monolithic cladding system at 1758 Cust Road, Canterbury

Refusal of a code compliance certificate for a building with a monolithic cladding system at 1758 Cust Road, Canterbury Determination 2007/9 Refusal of a code compliance certificate for a building with a monolithic cladding system at 1758 Cust Road, Canterbury 1. The matter to be determined 1.1 This is a determination under

More information

PRACTICAL COMPLETION REPORT

PRACTICAL COMPLETION REPORT PRACTICAL COMPLETION REPORT Report Commissioned By: Sample Practical Completion Report PO Box 355 HELENSVALE QLD 4212 Property Address: Sample Street SAMPLE REPORT QLD 0000 Date of Inspection: 8th July

More information

160.F1 PROPERTY INSPECTION REPORT 6 Vitoria St, Sebastopol, 3356 INSPECTION DETAILS Registered Practitioners Signature:

160.F1 PROPERTY INSPECTION REPORT 6 Vitoria St, Sebastopol, 3356 INSPECTION DETAILS Registered Practitioners Signature: www.sherspec.com 6 Vitoria St, Sebastopol, 3356 160.F1 PROPERTY INSPECTION REPORT INSPECTION DETAILS Registered Practitioners Name: Rudolf Venema Registered Practitioners Signature: Practitioners Registration

More information

Determination 2015/047

Determination 2015/047 Determination 2015/047 Regarding the refusal to issue a code compliance certificate for a 14-year-old house with stucco wall cladding at 2130 Riverton Wallacetown Highway, Riverton 1. The matter to be

More information

TOP 10 RED FLAGS #10 - SITE GRADING AND DRAINAGE PROBLEMS. Understand what issues your homebuyers are on the lookout for and how to offer solutions.

TOP 10 RED FLAGS #10 - SITE GRADING AND DRAINAGE PROBLEMS. Understand what issues your homebuyers are on the lookout for and how to offer solutions. TOP 10 RED FLAGS Understand what issues your homebuyers are on the lookout for and how to offer solutions. #10 - SITE GRADING AND DRAINAGE PROBLEMS Right. Wrong. High grading around the foundation is one

More information

25 Cherie Close, Rototuna Hamilton. Clear skies, no rain present at the time of inspection. Monday 22 nd October 2018 at 9:30am

25 Cherie Close, Rototuna Hamilton. Clear skies, no rain present at the time of inspection. Monday 22 nd October 2018 at 9:30am ADDRESS OF PROPERTY: 25 Cherie Close, Rototuna Hamilton WEATHER CONDITIONS: Clear skies, no rain present at the time of inspection. DATE & TIME OF INSPECTION: Monday 22 nd October 2018 at 9:30am REPORT

More information

SITE AND BUILDING INSPECTION CHECKLIST

SITE AND BUILDING INSPECTION CHECKLIST PARISH BUILDING Page 1 of 6 SITE AND GROUNDS DATE INIT COMMENTS DATE INIT COMMENTS Ramps & Provisions for Handicap Designated parking spaces for Handicap Has soil dropped or heaved Is there standing water

More information

Residential Commercial Minor Works Owners Abroad. yes. Inspection Date Inspector

Residential Commercial Minor Works Owners Abroad. yes. Inspection Date Inspector Residential Commercial Minor Works Owners Abroad yes Inspection Date 01.04.2005 Inspector MJM Client Name Mr M Property Address Development Name Developer/Builder Warranty type NHBC SNAGGING REPORT Terms

More information

MLC MASONRY AND BRICK PLASTER SYSTEM. Product. Scope. Appraisal No. 839 [2013] Appraisal No. 839 (2013) BRANZ Appraisals

MLC MASONRY AND BRICK PLASTER SYSTEM. Product. Scope. Appraisal No. 839 [2013] Appraisal No. 839 (2013) BRANZ Appraisals MLC MASONRY AND BRICK PLASTER SYSTEM BRANZ Appraisals Technical Assessments of products for building and construction. Specialized Construction Products Ltd PO Box 101 127 North Shore Mail Centre Auckland

More information

Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson

Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson Refusal of a code compliance certificate for a building with a brick veneer and monolithic cladding system at 47 San Bernadino Drive, Henderson 1. The dispute to be determined 1.1 This is a determination

More information

KEVIN BURNS HOMES PRACTICAL COMPLETION REPORT VISUAL BUILDING INSPECTION REPORT

KEVIN BURNS HOMES PRACTICAL COMPLETION REPORT VISUAL BUILDING INSPECTION REPORT KEVIN BURNS HOMES PRACTICAL COMPLETION REPORT VISUAL BUILDING INSPECTION REPORT No. 764 CLIENT: PROPERTY ADDRESS: Jindalee DATE: 25 November 2016 WEATHER: Fine ARRIVAL TIME: 8.15am DEPARTURE TIME: 10.30am

More information

Pink Inspection Services B&R A Division of B&R Constructions Pty. Ltd. ABN

Pink Inspection Services B&R A Division of B&R Constructions Pty. Ltd. ABN Pink Inspection Services B&R A Division of B&R Constructions Pty. Ltd. ABN 11 001 564 718 Visual Building Inspection Report Commissioned By: XX Purchaser: Property Inspected: XX This Report is provided

More information

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM

SUMMARY 1234 Main St.Loudon TN Buyer Name 08/28/2018 9:00AM SUMMARY 1234 Main St.Loudon TN 37774 Buyer Name 08/28/2018 9:00AM Dusty Jameson TN Home Inspector License #00123, TN WDI License #104158 Inspector Cluseau's Home Inspection Service 865-691-6158 dustyjameson@gmail.com

More information

Building Dilapidations International

Building Dilapidations International Building Dilapidations International As trustee for Syranah Solutions Trust ACN: 189 305 382 ABN: 32 754 005 187 9a Sylvan Street, Galston, NSW 2159 Telephone: 1800 134527 Mobile Phone: 042 476 9006 Web:

More information

RSH ENGINEERING, INC. END OF BUILDERS WARRANTY INSPECTION REPORT INSP#: K00001 DATE: 00/00/11 PAGE #: 1

RSH ENGINEERING, INC. END OF BUILDERS WARRANTY INSPECTION REPORT INSP#: K00001 DATE: 00/00/11 PAGE #: 1 PAGE : 1 1 2 3 4 LEFT SIDE OF HOUSE: SEE. 3 TO. 10 FOR DETAILS. LEF T SIDE OF HOUSE: GENERAL NOTE: SOFFIT VENTS ARE MISSING AND/OR IS INADEQUATE ADD SOFFIT VENTS. PROVIDE ADEQUATE OF SOFFIT VENTS TO MEET

More information

SNAGGING REPORT. Plot 19 Snag Close Unfinished Avenue Oxford OX90 1AB. for. Mr T & Mrs N Sample

SNAGGING REPORT. Plot 19 Snag Close Unfinished Avenue Oxford OX90 1AB. for. Mr T & Mrs N Sample SNAGGING REPORT on Plot 19 Snag Close Unfinished Avenue Oxford OX90 1AB for Mr T & Mrs N Sample Prepared By: Marshalls Chartered Surveyors Rochester House The Grange Farm Eynsham Road Oxford OX2 9NH Tel:

More information

FINEGAN INSPECTION SERVICES, INC.

FINEGAN INSPECTION SERVICES, INC. FINEGAN INSPECTION SERVICES, INC. TERRY FINEGAN 76 WEST FOSTER MAINEVILLE ROAD MAINEVILLE, OHIO 45039 683-0733-PHONE 697-0163-FAX Email- finegan @ fuse.net CLIENT: 1/14/08 Mr. BUILDING LOCATION As in all

More information

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011 Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT

More information

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011 Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &

More information

Example Building Condition Survey & Summary Report Address Address Address London

Example Building Condition Survey & Summary Report Address Address Address London Example Building Condition Survey & Summary Report on Address Address Address London Date 2016 Ref. no. London Building Surveyors Ltd, 20 Stanmore Road, London. E11 3BU Tel: 020 8257 5766 Mob: 07854 755

More information

Inspection Report. Property Address:

Inspection Report. Property Address: Inspection Report provided by: Safe Side Home Inspection Inspector: Corey Stuart TN License # 778 434 Margaret Circle McMinnville, TN 37110 safesideinspection@blomand.net Property Address: 1234 Anywhere

More information

Property and Earthquake Assessment

Property and Earthquake Assessment Property and Earthquake Assessment Report by: Vendors: Iain Whyte Kyla Hurley & Philip Tubby Contact Number: 03 3134939 Address: 14 Taiwhenua Street Site was visited for inspection on 11.06.2015 to undertake

More information

MAINTENANCE PLAN Wing Village Hall, Morcott Road, Wing, Oakham LE15 8SA

MAINTENANCE PLAN Wing Village Hall, Morcott Road, Wing, Oakham LE15 8SA MAINTENANCE PLAN Roof Covering Roof slates Yearly Maintenance & Finishes 1 1, 8 & 13 Timber fascia and soffit boards Slates in good condition, some have been replaced during routine maintenance of roof.

More information

Bituminous Sheet Flat Roofs: Their repair and maintenance

Bituminous Sheet Flat Roofs: Their repair and maintenance Bituminous Sheet Flat Roofs: Their repair and maintenance Flat roof covered in sheets of bituminous felt Introduction Whilst flat roofs are often regarded as inferior to their pitched counterparts and

More information

BUILDING INSPECTION. Mar 16, 2015 PROPERTY ADDRESS Killymoon Drive Hope Island, QLD 4212, Australia. 1 of 44

BUILDING INSPECTION. Mar 16, 2015 PROPERTY ADDRESS Killymoon Drive Hope Island, QLD 4212, Australia. 1 of 44 BUILDING INSPECTION Complies with Australian Standard AS 4349.1-2007 Inspection of Buildings Part 1: Pre-Purchase Inspections of Residential Buildings - Appendix C Mar 16, 2015 PROPERTY ADDRESS 1075 Killymoon

More information

Property Inspection Report

Property Inspection Report - Habit New Zealand Limited Sample Report 1986 Weatherboard This report is for the sole benefit of: Sample Report Only Page 1 of 67 Terms and Conditions Payment Terms and Conditions Upon booking an inspection

More information

ROCKCOTE RESENE MONOTEK SYSTEMS

ROCKCOTE RESENE MONOTEK SYSTEMS Product Appraisal No.500 [2007] BRANZ Appraisals Technical Assessments of products for building and construction 1.1 The Rockcote Resene Monotek Systems consists of the Rockcote Resene Monotek Texture

More information

BUILDING INSPECTIONS

BUILDING INSPECTIONS PO Box 5166 HUGHESDALE Australia 3166 Ph 1300-693-583 Fax 1300-692-823 scott@homefirstinspections.com.au As part of our undertaking to comply with Australian Standard AS4349.1 2007 Inspection of buildings

More information

Regarding the refusal to issue a code compliance certificate due to a lack of inspections for an office/studio building at 16A Rotoiti Street, Dunedin

Regarding the refusal to issue a code compliance certificate due to a lack of inspections for an office/studio building at 16A Rotoiti Street, Dunedin Determination 2011/074 Regarding the refusal to issue a code compliance certificate due to a lack of inspections for an office/studio building at 16A Rotoiti Street, Dunedin 1. The matter to be determined

More information

Home Buyer Inspection Checklist

Home Buyer Inspection Checklist Please note that this is a simplified checklist of items and tips and is not proposed to take the place of a professional pre purchase building inspection. If you require an independent pre purchase building

More information

House Inspection Specialists

House Inspection Specialists House Inspection Specialists Member of the Institute of Building Inspectors Sum Insured Home Rebuild Cost Appraisals Pre Purchase Inspections Mobile: 0274 522 159 Work: 09 5334521 www.fchi.co.nz NZS 4306-2005

More information

Home Inspection Report

Home Inspection Report Home Inspection Report Example Home Inspection Report. Page 1 of 17 Table of Contents Definitions 2 Company Information 2 General Information 2 Lots and Grounds 3 Exteriors 3 Garage/Carport 4 Roof 5 Attic

More information

Determination 2007/60

Determination 2007/60 Determination 2007/60 Determination regarding a code compliance certificate for a house with monolithic and weatherboard wall cladding systems at 11A Blease Street, New Lynn, Auckland 1 The matter to be

More information

Builders Report. 123 Somewhere St Hamilton Hamilton

Builders Report. 123 Somewhere St Hamilton Hamilton Builders Report Hamilton Prepared for: Prepared by: 46 Naylor Street 021 786 246 Summary Landscaping and Gardens 1. Garden Sheds Large garden shed - Broken window Structure and Cladding 2. Fascia Painted

More information

Residential Handover Inspection Report

Residential Handover Inspection Report , trading as Melbourne Property Inspections P/L 356 Collins Street MELBOURNE VIC 3000 Phone: (13)0088-6525 Mobile: 0414-184-686 Email: info@melbournepropertyinspections.com.au ABN: 95 477 052 614 Residential

More information

MAJOR DEFECTS BUILDING SURVEY REPORT

MAJOR DEFECTS BUILDING SURVEY REPORT MAJOR DEFECTS BUILDING SURVEY REPORT XXXXXX Road Bedminster Bristol BS3 XXX Prepared for Mr XXXXXXX July 2017 T J Maggs MRICS MAGGS AND ALLEN 22 Richmond Hill Clifton Bristol BS8 1BA 0117 973 4049 survey@maggsandallen.co.uk

More information

Stucco Moisture Inspection Report

Stucco Moisture Inspection Report Website:www.ibgoodinspector.com E-Mail:support@ibgoodinspector.com January 11, 2006 Stucco Moisture Inspection Report Property Address 123 Our Street OurTown, USA 12345 Report Ordered By: Mr. & Mrs. Client

More information

Refusal of a code compliance certificate for alterations to a house at 72 Owhiro Bay Parade, Owhiro Bay, Wellington

Refusal of a code compliance certificate for alterations to a house at 72 Owhiro Bay Parade, Owhiro Bay, Wellington Determination 2008/26 Refusal of a code compliance certificate for alterations to a house at 72 Owhiro Bay Parade, Owhiro Bay, Wellington 1. The matter to be determined 1.1 This is a determination under

More information

Welcome to your MOT Checklist

Welcome to your MOT Checklist MOT Checklist 2 Welcome to your MOT Checklist Your church buildings can be one of your greatest assets or a major drain on resources. Often the problems come because we haven t done regular checks around

More information

RSH ENGINEERING, INC. FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 1 Address: 1234 Anywhere St, Anywhere, TX

RSH ENGINEERING, INC. FINAL WALK THROUGH INSPECTION REPORT INSP#: S05092 DATE:08/27/06 PAGE #: 1 Address: 1234 Anywhere St, Anywhere, TX PAGE #: 1 1 2 3 4 FRONT VIEW OF HOUSE INSPECTED SEE PIC. # 3 TO PIC. # 15 FOR DETAILS THE SPRINKLER HEAD IS BROKEN OFF AND SOIL HAS WASHED OUT FROM BASE OF SLAB. REPAIR SPRINKLER AND REPLACE THE SOIL.

More information

CONDITION SURVEY Punch Taverns Angel Inn North Street Scarborough CONDITION SURVEY

CONDITION SURVEY Punch Taverns Angel Inn North Street Scarborough CONDITION SURVEY CONDITION SURVEY 200090 Angel Inn 44-46 North Street Scarborough UK CONDITION SURVEY 25 June 2018 Gleeds Wilford House 1 Clifton Lane Wilford Nottingham NG11 7AT CONTENTS 1. Property Overview... 3 2. Element

More information

Determination 2013/061

Determination 2013/061 Determination 2013/061 Regarding the issuing of two notices to fix in respect of the code-compliance of a two-coat plaster cladding system to an 11-year-old motel complex at 23/25 Havelock Road, Havelock

More information

Property Address: Sample.Prehandover.report

Property Address: Sample.Prehandover.report Web Page: www.inspectdirect.com.au INSPECT DIRECT Pty Ltd Property Address: Sample.Prehandover.report Building Construction Advice Inspection Report This is not a Pest Inspection Stage of construction:

More information

Eidem Farm Brooklyn Park, MN

Eidem Farm Brooklyn Park, MN Eidem Farm Brooklyn Park, MN East Farm House Structural Condition Assessment Prepared By 1 0 0 P O R T L A N D A V E N U E S O U T H, S U I T E 1 0 0 M I N N E A P O L I S, M I N N E S O T A 5 5 4 0 1

More information

11/09/2018 LBP licence classes

11/09/2018 LBP licence classes LBP licence classes Occupational Licensing aims to ensure that people in the building industry are competent and accountable so that homes and buildings are designed and built right first time. Summary

More information

Residential Pre-handover Inspection Report

Residential Pre-handover Inspection Report , trading as Melbourne Property Inspections P/L 356 Collins Street MELBOURNE VIC 3000 Phone: (13)0088-6525 Mobile: 0414-184-686 Email: info@melbournepropertyinspectionscomau ABN: 95 477 052 614 Residential

More information

Property Inspection Report. - Habit Whakatane Sample Report Single Storey

Property Inspection Report. - Habit Whakatane Sample Report Single Storey - Habit Whakatane Sample Report Single Storey Prepared for: HABiT Page 1 of 51 Mission Statement It is our mission to provide a service that is solution based. We will ensure that our service to you: Is

More information

The Home Doctor, Inc.

The Home Doctor, Inc. February 7, 2013 The Home Doctor, Inc. Property: 26147 HUNTER GATES RD. LESTER, AL 35647 Client: JOHN DOE HOME INSPECTIONS With over 10,000 since 1994 1-800-246-4362 SUMMARY PAGE CLIENT(S): JOHN DOE ADDRESS:

More information

Regarding the refusal to issue a code compliance certificate for a 6-year-old house at 4 Korotaha Terrace, Rothesay Bay, Auckland

Regarding the refusal to issue a code compliance certificate for a 6-year-old house at 4 Korotaha Terrace, Rothesay Bay, Auckland Determination 2016/051 Regarding the refusal to issue a code compliance certificate for a 6-year-old house at 4 Korotaha Terrace, Rothesay Bay, Auckland Summary This determination is concerned with the

More information

VISUAL BUILDING INSPECTION REPORT Complies with Australian Standard J Citizen. Inspected Property: 4 John Street, Johnson

VISUAL BUILDING INSPECTION REPORT Complies with Australian Standard J Citizen. Inspected Property: 4 John Street, Johnson www.scottbuildingsolutions.com.au VISUAL BUILDING INSPECTION REPORT Complies with Australian Standard 4349.1 J Citizen. Inspected Property: 4 John Street, Johnson 4 John Street, Johnson Page 1 of 23 Report

More information

Example Schedule of Condition Report

Example Schedule of Condition Report 1 INTERIOR Ground Garage Ceiling Timber members. Members appear to be in a fair and reasonable condition with no signs of any penetration marks noted. Walls Flank wall Brickwork. Part solid construction,

More information

INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings

INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings FINEGAN INSPECTION SERVICES, INC. 27 Laurelwood Drive Milford Ohio, 45150 513 683-0733 RESIDENCE LOCATION INSPECTION TYPE EIFS system, Visual, Tramex & Delmhorst probe moisture readings OVERVIEW The report

More information

PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX HOUSTON, TEXAS (713)

PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX HOUSTON, TEXAS (713) PROFESSIONAL ENGINEERING INSPECTIONS, INC. P. O. BOX 271492 HOUSTON, TEXAS 77277 http://www.profengineering.com (713) 664-1264 June 19, 2000 Mr. Samuel Underdog 329 Castle Dr. Houston TX 77018 Dear Mr.

More information

V 2.4. Hardwood Decking Installation Manual

V 2.4. Hardwood Decking Installation Manual V 2.4 Hardwood Decking Installation Manual TABLE OF CONTENTS 1. Scope... 2 2. Health and Safety... 3 3. Site Preparation... 4 4. Pre-Installation... 4 5. Fixings... 5 6. Fixing Details for Decking... 6

More information

(Address removed for privacy)

(Address removed for privacy) 10 Boat creek Road Ventnor, Vic, 3922 042-222-8716 support@islandbuildinginspections.com.au Report: 0003545 Pre Purchase Building & Timber Pest Inspection Report (Address removed for privacy) Prepared

More information

STANDARD VISUAL PRE-PURCHASE BUILDING AND PEST INSPECTION REPORT

STANDARD VISUAL PRE-PURCHASE BUILDING AND PEST INSPECTION REPORT PPDoesn t Apply VISUAL PRE-PURCHASE BUILDING AND PEST INSPECTION REPORT This Report» Building Inspection Report» Pest Inspection Report» Building Compliance» Electrical Safety Inspection» Plumbing/Drainage/Stormwater

More information

Building Report. Report Commissioned By: The Purchaser. Property Address: Sample Street Tempe. Report Number:11121

Building Report. Report Commissioned By: The Purchaser. Property Address: Sample Street Tempe. Report Number:11121 Phone: 0417 696 277 Fax: 1300 726 643 Email: restwell67@bigpond.com Web: www.restwellpropertyinspections.com.au Building Consultancy License BC 1219 ABN 121 350 801 A Division of Restwell Building Services

More information

Visual Property Inspection Report Complies with Australian Standard AS

Visual Property Inspection Report Complies with Australian Standard AS Visual Property Inspection Report Complies with Australian Standard AS 4349.1-2007 Solicitor/Company Sample Street Mr & Mrs Purchaser Alpha Building Services Pty Ltd Trading As Inspect It >> ABN 47 103

More information

AS The External Waterproofing Membranes Standard

AS The External Waterproofing Membranes Standard AS 4654-2 The External Waterproofing Membranes Standard NOTE This external waterproofing standard contains solutions for problems which have not been addressed in other countries. CONFORMANCE CONDITIONS

More information

LV= s Home MOT checklist

LV= s Home MOT checklist LV= s Home MOT checklist While you can take your car for its annual MOT, there s no such service for your property. Three quarters (77%) of homeowners have experienced maintenance issues, and people spend

More information

The Pattison. At a Glance m Study m. 17.

The Pattison. At a Glance m Study m. 17. The Pattison At a Glance... 321.8m 2 4 + Study 2.0 2 21.566 m Please Note: The floor plan provided is for illustrative purposes only and is not drawn precisely to scale. However, the overall length and

More information

The Banksia. At a Glance m Study m. 18.

The Banksia. At a Glance m Study m. 18. The Banksia At a Glance... 350.1m 2 4 + Study 2.0 20.870 m Please Note: The floor plan provided is for illustrative purposes only and is not drawn precisely to scale. However, the overall length and width

More information

County of Santa Barbara, California Facility Condition Assessment 2014

County of Santa Barbara, California Facility Condition Assessment 2014 Project No.: P05000.001 Building Number: P05000 Lompoc VMB Grounds Project Description: Overlay, Seal Coat and Restripe Parking Lots Background: The asphalt paving comprises approximately 135,600 square

More information

Residential Structural Inspection Report

Residential Structural Inspection Report , trading as Melbourne Property Inspections P/L 356 Collins Street MELBOURNE VIC 3000 Phone: (13)0088-6525 Mobile: 0414-184-686 Email: info@melbournepropertyinspections.com.au ABN: 95 477 052 614 Residential

More information

TML Home Inspectors, Inc.

TML Home Inspectors, Inc. TML Home Inspectors, Inc. CallHomeInspector.com Email: tmlhomeinspectors@gmail.com Ph. (630) 841 7333 Inspector: Jerry Zieleziecki License # 450.00xxxx Expiration Date: 11/30/2014 Date: Time: Property

More information

Prepared for Sample Page 2 of 28 Report Reference: 4960 PROPERTY DETAILS: Building Type: Residential House Description: Single Storey, Split level, 30

Prepared for Sample Page 2 of 28 Report Reference: 4960 PROPERTY DETAILS: Building Type: Residential House Description: Single Storey, Split level, 30 Prepared for Sample Page 1 of 28 Report Reference: 4960 Buy-Wise Pre Purchase Building & Pest Inspections P/L MAJOR STRUCTURAL BUILDING REPORT Inspected Property Address: 5 Parkland Close Frankston Client

More information

Bathrooms. Custom cabinetry INCLUDED

Bathrooms. Custom cabinetry INCLUDED Designer Inclusions Kitchen Stone bench tops INCLUDED 20mm Caesarstone kitchen bench tops A large choice of colours Bathrooms Custom cabinetry INCLUDED Note: wall hung vanity and stone bench top not included

More information

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012

Inspection Report. Prepared for: Tonia Mann. Property Address: 2557 Briar Valley Way Dacula, GA Date: March 01, 2012 Inspection Report Prepared for: Tonia Mann Property Address: Dacula, GA 30019 Date: March 01, 2012 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT

More information

Property Inspection Report

Property Inspection Report DAVID A. MEACHAM Professional Inspection & Construction Services Property Inspection Report Prepared for David Smith Property Address 1154 Gulf View Drive Tampa Bay, Florida Inspection Date Friday, October

More information

Inspect Hawaii. Property Inspection Report

Inspect Hawaii. Property Inspection Report Cover Page Property Inspection Report 96744 Inspection prepared for: John Doe Date of Inspection: 11/6/2014 Inspector: Oscar Libed ASHI License #257117 Honolulu, HI 96825 Email: oscar@inspecthawaii.com

More information

SOPREMA JARDIN Double Layer Torch-on membrane For water proofing roof gardens and planters

SOPREMA JARDIN Double Layer Torch-on membrane For water proofing roof gardens and planters TECHNICAL DATA Technical data may be updated at any time. It is the users responsibility to check data validity by reference to the website or Nuplex Construction Products MANUAL SECTION ISSUE DATE AUTHORISED

More information

100 Good Street, Best Suberb Auckland

100 Good Street, Best Suberb Auckland Inspection Report provided by: Builders Report ltd ABN: Liming Du 0800 533 646 info@buildersreport.co.nz www.buildersreport.co.nz Property Address: 100 Good Street, Best Suberb Auckland Report Information

More information

A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau

A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau Determination 2007/37 A dispute in relation to the code compliance of a liquid-applied membrane at 22 Moana Crescent, Te Anau 1. The matter to be determined 1.1 This is a determination under Part 3 Subpart

More information

Exterior structures (fences, sheds, decks, retaining walls, detached garages) in good condition, no evidence of termite damage or rotted wood

Exterior structures (fences, sheds, decks, retaining walls, detached garages) in good condition, no evidence of termite damage or rotted wood Please Note: This checklist should not be relied upon as a home inspection report, nor should it be considered a substitute for a home inspection. This list is representative, but NOT exhaustive. If you

More information