1 LIMITED MOLD ASSESSMENT REPORT City of Panama City New City Hall 501 Harrison Avenue Panama City, Florida PREPARED FOR: City of Panama City, Florida 9 Harrison Avenue Panama City, Florida NOVA Project Number: May 15, 2018

2 May 15, 2018 Mr. Jared Jones, Interim City Manager City of Panama City Florida 9 Harrison Avenue Panama City, Florida Subject: Limited Mold Assessment City of Panama City New City Hall 501 Harrison Avenue Panama City, Florida NOVA Project No Dear Mr. Jones: NOVA Engineering and Environmental, LLC (NOVA) has completed the authorized Limited Mold Assessment of the building located at 501 Harrison Avenue in Panama City, Bay County, Florida. The initial assessment was performed on May 7, 2018, and included a visual inspection, and tape lift sample collection. This assessment was performed using current guidelines and protocols published by the American Society of Heating, Refrigerating and Air Conditioning Engineers (ASHRAE, 2016), the National Institute of Occupational Safety and Health (NIOSH), the American Conference of Governmental Industrial Hygienists (ACGIH), the Occupational Safety and Health Administration (OSHA) and the Environmental Protection Agency (EPA). According to project representatives, the building has been undergoing extensive renovation over the past several months, and evidence of mold growth has been detected in the process. The Owner, realizing that it had potential mold issues, contracted with NOVA for this service in order to remedy the problem. BUILDING DESCRIPTION The circa 1952 commercial building, comprised of two above-ground stories and a basement, consists of approximately 63,000 square feet of interior space. The building is constructed of concrete block and stucco, with a built-up roof. The property is currently under renovation. Renovation continued concurrently to the limited mold assessment with installation of Mechanical, Electrical, and Plumbing (MEP), exterior siding, windows, etc. VISUAL INSPECTION NOVA performed a limited visual inspection of the interior of the building at the direction of the Client s representative to document select areas of visible mold growth. NOVA s inspection was limited to the areas directed by the client. Representative photographs are provided in Attachment A. P R O F E S S I O N A L P R A C T I C A L P R O V E N 1630 Old Bainbridge Road, Suite C, Tallahassee, Florida t / f / usanova.com

3 City of Panama City New City Hall Mold Assessment/Remediation Report 501 Harrison Avenue Panama City, Florida May 15, 2018 City of Panama City NOVA Project No Evidence of obvious water intrusion was not observed in the building, although mold growth was evident on the drywall in the basement at a height of zero to approximately 12 inches from the floor, which suggests water intrusion through the wall or wall/floor intersect. Mold growth was also evident in some areas surrounding HVAC ductwork on the upper floor. Building envelope services were also being provided by NOVA at the time of the mold assessment TEMPERATURE, RELATIVE HUMIDITY, CO AND CO2 MEASUREMENTS This building is currently open to ambient conditions, therefore rather than conduct measurements throughout the building, Panama City weather conditions were obtained and used in the record. Temperature was relatively constant during the assessment at 84 degrees and humidity was approximately 37%. Carbon Monoxide and Carbon Dioxide levels were not monitored as the building was open to ambient conditions; those measurements would equal those of normal outdoor atmospheric conditions. DISCUSSION Sheila Schneider, a NOVA Professional and licensed Mold Assessor, visually inspected limited areas of the building s interior for areas with obvious mold growth. Assessment areas included an area around several HVAC ducts on the upper floor, where defects in the insulation on the ductwork caused condensation on the surrounding drywall penetrations, and a drywalled area in the basement where prior water intrusion led to mold growth on drywall near the floor. Tape lift samples were collected from both areas (4 total) and sent to a certified laboratory for analysis. The results are attached in Appendix C. Schneider s license is included in Attachment B. Subsequent to the onsite assessment, photographs were provided to Schneider of an area that was not part of the original areas indicated by the owner s representative as having visible mold. This area was in the basement along an exterior foundation wall. Apparent mold growth exists on the wall panel material (it is not confirmed whether this material is drywall or plaster) adjacent to the exterior bricking. Building envelope observations are also included here: Outside Perimeter Walls There was evidence of existing moisture intrusion witnessed by varying degrees of metal stud deterioration and some damp lower walls and wall to floor slab transitions. The primary area of moisture intrusion appears to be at the exterior wall to floor slab transition. This is generally confirmed by the majority of the observed metal framing deterioration being located at the horizontal base track and lower portions of the vertical members. Page 2

4 City of Panama City New City Hall Mold Assessment/Remediation Report 501 Harrison Avenue Panama City, Florida May 15, 2018 City of Panama City NOVA Project No Concrete Floor Slab Several areas of sand/soil were handled with all being damp to the touch. No vapor barrier was observed below the slab. General Initial Overview Based on our site visit the basement area has experienced some moisture intrusion. Although, for a 60+ year building, the effects of the moisture intrusion appear overall to be minimal, however moisture intrusion still likely exists. It is our opinion that the moisture intrusion has occurred off and on at varying times throughout the building s existence. Most likely during times of heavy lengthy rains, days of steady rainfall and tropical storms/hurricanes the water table rises as well as the soil/areas surrounding the building hold water and this water accumulates below grade against the exterior walls. These conditions put pressure/hydrostatic pressure on the floor slab and exterior walls and will typically show as moisture intrusion at the weakest location. This location is historically at the exterior wall to floor slab transition. Buildings constructed during this era typically didn t have the benefit of moisture intrusion prevention materials that current exist. After the heavy lengthy rains/days of steady rainfall/tropical storms end the water recedes to normal and the conditions dry out. RECOMMENDATIONS LIMITATIONS o A mold remediation protocol has been developed for use by the Florida licensed mold remediator, and is included as Attachment D. o The building should be dried in as soon as practical. o Once dried-in, the interior areas should be subjected to dehumidification using dehumidifiers to further dry the interior building materials. o The HVAC system should be operated 24 hours a day, 365 days a year to maintain temperature, CO, CO2 and humidity levels within recommended ASHRAE ranges. o If the source(s) of water/moisture is/are not remedied, or new source(s) develop, mold will likely return. Opinions and findings offered in the report were based upon observable conditions or features and information derived from the most recent site reconnaissance date and from other activities described within the report. This is not intended to identify de minimis conditions that do not present a material risk of harm to the public health or the environment and would not be the subject of an enforcement action if brought to the attention of appropriate governmental entities. Any type or quantity of mold may produce reactions in hypersensitive or allergic individuals. Although mold containing areas or surfaces may be cleaned or removed, mold will reoccur if the source of moisture is not remedied. Page 3

5 City of Panama City New City Hall Mold Assessment/Remediation Report 501 Harrison Avenue Panama City, Florida May 15, 2018 City of Panama City NOVA Project No The findings and opinions conveyed in this report are based upon information obtained at a specific date from a variety of sources listed within the report, and which NOVA believes are reliable. Nonetheless, NOVA cannot and does not warrant the authenticity or reliability of the information sources. The study and report was prepared on behalf of and for the exclusive use of Client solely for its use and reliance in the sampling of this site. Client is the only party to which NOVA has explained the risks involved and which has been involved in shaping the scope of services needed to satisfactorily address the Client s interests. This report may not be relied upon by any third party without the execution of an agreement between NOVA and that third party. NOVA appreciates the opportunity to provide the above services. Please call if you have questions or require additional information. Sincerely, NOVA Engineering and Environmental, LLC Sheila E. Schneider Florida Licensed Mold Assessor #MRSA2626 Larry G. Schmaltz, PE Senior Vice President Florida Environmental Services Manager Attachments Attachment A Photographs Attachment B License Attachment C Laboratory Data Attachment D - Mold Remediation Protocol Page 4

6 ATTACHMENT A Photographs APPENDIX A SUBJECT PROPERTY PHOTOGRAPHS NOVA Project Number

7 1. Broad view of apparent mold on ceiling 2. Close up view of mold near ceiling in main duct area 3. Apparent mold growth inside HVAC duct 4. Mold growth on drywall upper level near ceiling APPENDIX A SUBJECT PROPERTY PHOTOGRAPHS NOVA Project Number

8 5. Mold growth around HVAC duct penetration 6. Mold growth on drywall near floor in basement 7. Mold growth on plaster/drywall on exterior wall 8. Closer view of exterior wall/mold APPENDIX A SUBJECT PROPERTY PHOTOGRAPHS NOVA Project Number

9 ATTACHMENT B License NOVA Project Number

10 NOVA Project Number

11 ATTACHMENT C Laboratory Data NOVA Project Number

12 Attn: Proj: EMSL Analytical, Inc PARKWAY CENTER COURT Orlando, FL Phone/Fax: (407) / (407) / orlandolab@emsl.com SHEILA E. SCHNEIDER, Nova Engineering 1630C Old Bainbridge Tallahesee, FL Order ID: Customer ID: Customer PO: Project ID: Phone: (850) Fax: Collected: 05/07/2018 Received: 05/08/2018 Analyzed: 05/09/ NOVA29 Test Report: Microscopic Examination of Fungal Spores, Fungal Structures, Hyphae, and Other Particulates from Tape Samples (EMSL Method MICRO-SOP-200) Lab Sample Number: Client Sample ID: PCCH-1 Sample Location: Top Floor Inside Duct in Hall PCCH-2 Top Floor - Drywall Next to Duct PCCH-3 Top Floor Wall Opposite Duct PCCH-4 Bsmt Wallboard near Floor Main Hall Dummy Dummy Spore Types Category Category Category Category - Alternaria (Ulocladium) - - Rare Rare - Ascospores Aspergillus/Penicillium - Medium *Medium* *Low* - Basidiospores Bipolaris Chaetomium Rare - Low - - Cladosporium *High* Low *High* *High* - Curvularia Epicoccum Fusarium Ganoderma Myxomycetes Rare - - Pithomyces Rust Scopulariopsis/Microascus Stachybotrys/Memnoniella Unidentifiable Spores Zygomycetes Cheiromycella - *High* *High* - - Nigrospora - Rare Tritirachium - - *Medium* - - Tritirachium-like - *Medium* Hyphal Fragment Fibrous Particulate Insect Fragment Pollen Rare Low Rare - - Category: Count/per area analyzed - Rare: 1 to 10 Low: 11 to 100 Medium: 101 to 1000 High: > Denotes Not Detected. Bipolaris++ = Bipolaris/Dreschlera/Exserohilum Myxomycetes++ = Myxomycetes/Periconia/Smut * = Sample contains fruiting structures and/or hyphae associated with the spores. No discernable field blank was submitted with this group of samples. Yessica Martinez Seeman, Microbiology Technical Manager, Central Florida EMSL maintains liability limited to cost of analysis. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities or analytical method limitations. Interpretation of the data contained in this report is the responsibility of the client. Samples received in good condition unless otherwise noted. Samples analyzed by EMSL Analytical, Inc. Orlando, FL AIHA-LAP, LLC--EMLAP Accredited # Initial report from: 05/09/ :22:53 For Information on the fungi listed in this report please visit the Resources section at Test Report DEVER Printed: 5/09/ :22:53AM Page 1 of 1

13 OrderID: Page 1 Of 2

14 OrderID: Page 2 Of 2

15 ATTACHMENT D Protocols

16 MOLD REMEDIATION PROTOCOLS For: New City Hall Building City of Panama City 501 Harrison Avenue Panama City, Florida Prepared by: NOVA Engineering and Environmental LLC 1630 Old Bainbridge Road, Suite C Tallahassee, Florida May 15, 2018

17 Mold Remediation Protocols New City Hall - City of Panama City 501 Harrison Avenue May 15, 2018 Panama City, Florida NOVA Project #: INTRODUCTION The subject site is the New City Hall Building for the City of Panama City located at 501 Harrison Avenue in Panama City, Florida. These protocols have been developed to facilitate the safe remediation of mold and mold-contaminated materials located within the subject building. A Limited Mold Assessment was completed by NOVA on May 9, The Florida Licensed Mold Assessor identified various area of mold infestation. 2.0 OBJECTIVES OF REMEDIATION The remediation objectives will be to remove building materials that have signs or suspicions of mold growth and to clean HVAC ductwork and components, to provide a safe working and occupancy environment. 3.0 REFERENCED DOCUMENTS AND STANDARDS The following documents and standards are adopted into this protocol document by reference. The requirements and protocols in these standards and documents are to be considered the minimum guidelines for this work. 3.1 OSHA 29 CFR 1926 Construction Standard 3.2 OSHA 29 CFR Respiratory Protection Standard 3.3 OSHA 29 CFR Hazard Communication 3.4 USEPA 402-K Mold Remediation in Schools and Commercial Buildings 3.5 Florida Statute 468 Licensing 3.6 Chapter Florida Administrative Code (FAC) 3.7 ANSI/IICRC S Standard for Professional Mold Remediation 3.8 National Air Duct Cleaners Association; Assessment, Cleaning and Restoration of HVAC Systems (ACR 2013) Mold Remediation Protocols Page 1

18 Mold Remediation Protocols New City Hall - City of Panama City 501 Harrison Avenue May 15, 2018 Panama City, Florida NOVA Project #: CONTRACTOR QUALIFICATIONS The contractor performing the mold remediation activities will have an on-site project manager that is a Florida Licensed Mold Remediator pursuant to Chapter Florida Administrative Code (FAC) and Florida Statute The Licensed Mold Remediator will be the contractor s Responsible Person for all mold-related activities. The contracting company shall be able to show evidence of at one (1) year experience with mold remediation projects. The mold remediation contactor will be required to provide the following insurance coverages, as a minimum: Workers Compensation & Employers Liability Statutory limits Includes waiver of subrogation with regard to the Owner and other indemnities as required by contract Includes Employer s Liability Coverage with policy limits equal to: $1,000,000 each accident $1,000,000 disease each employee $1,000,000 disease policy limit Contractor s sub-contractors and any employee leasing company have Workers Compensation Insurance with equal or greater coverage limits. General Liability Includes Premises & Operations, Independent Contractors and Completed Operations Policy limits $1,000,000 each occurrence; $1,000,000 personal & advertising injury; $2,000,000 products & completed operations aggregate; $2,000,000 general aggregate and $5,000 medical expense Aggregate limit applies per project Occurrence policy form includes X, C, or U (explosion, collapse or underground) The owner and other indemnities as required by contract are to be named as Additional Insureds utilizing endorsement CG (also acceptable is CG plus CG extending coverage to products and completed operations). The Contractual Liability coverage contains no restrictions for assumption of the others sole negligence, nor and deletion of coverage for contractual liability. Coverage does not have punitive damages exclusion. Policy is primary and non-contributory as respects other insurance coverages carried by the owner and other indemnities as required by contract. Mold Remediation Protocols Page 2

19 Mold Remediation Protocols New City Hall - City of Panama City 501 Harrison Avenue May 15, 2018 Panama City, Florida NOVA Project #: Automobile Liability Policy limits $1,000,000 combined single limit Coverage applies to owned, hired and non-owned vehicles. The owner shall be named additional insured. Policy is primary and non-contributory as respects any other insurance coverage carried by the owner and other indemnities as required by contract. The contractual liability coverage contains no restrictions for the assumption of the others negligence, nor any deletion of coverage for contractual liability. Umbrella/Excess Liability (if applicable) Minimum policy limits $1,000,000 each occurrence $1,000,000 aggregate The owner and other indemnities are named as additional insureds as required by contract. Policy is primary and non-contributory as respects any other insurance coverage carried by the owner and other indemnities as required by contract. Contractors Pollution Liability Minimum policy limits $1,000,000 each occurrence $1,000,000 aggregate Aggregate limit applies per project Occurrence policy form The owner and other indemnities are named as additional insureds as required by contract. Policy is primary and non-contributory as respects any other insurance coverage carried by the owner and other indemnities as required by contract. All Policies A waiver of subrogation is provided in favor the owner. Policies include 30 days notice to owner of cancellation or material changes with the words endeavor to and but failure to mail such notice shall impose no obligation or liability upon the company crossed out or deleted. Policies are written with insurers rated A-, VII or better by A.M. Best Company. Coverages listed above, including the additional insured coverages, will be maintained for a period equal to or greater than the statue of repose following completion of this project. Mold Remediation Protocols Page 3

20 Mold Remediation Protocols New City Hall - City of Panama City 501 Harrison Avenue May 15, 2018 Panama City, Florida NOVA Project #: PPE REQUIREMENTS Mold disturbance work shall be performed in Level C Personal Protective Equipment (PPE), and includes, as a minimum, Tyvek-type disposal suit, eye protection, head protection and ½ face respirator (NIOSH-approved) with HEPA cartridges. 6.0 ABATEMENT Prior to any disturbance of mold, the contractor will place critical barriers at openings to other portions of the building. Further, no one other than the remediation contractor personnel and consultant will be permitted in any area undergoing mold remediation. With the building not being enclosed at this time, and with the limited scope of abatement, full negative pressure containment will not be required. However, the placement of negative pressure air filtration unit is required in each are of mold-related work and shall be operational at all times. Fungicidal coatings and mold-resistant coatings should not be used in place of proper source removal of mold contamination, moisture control, and regular cleaning and maintenance, but can protect some materials from microbial growth. Fungicidal coatings and mold-resistance coatings should not create a vapor barrier that could lead to a buildup of moisture, and possibly contribute to a future microbial or structural problem. Products should demonstrate reasonable permeability as tested under ASTM D-1653, should be water-based, low odor, and contain low VOCs (ANSI/IICRC S520). Duct work that is to remain will be thoroughly cleaned in accordance with The National Air Duct Cleaners Association (NADCA) standard, Assessment, Cleaning and Restoration of HVAC Systems. Affected drywall around the ductwork will be removed and the ductwork will be thoroughly cleaned. Further, the HVAC condensing unit and drip lines and pans will be thoroughly cleaned and treated with a disinfection solution (drain pan only). Following ductwork cleaning NOVA recommends, but does not require, a flushing of the ductwork with ozone (O3). Note that the HVAC system will be off at all times of cleaning and remediation. Drywall and plaster with evidence of mold will be removed, placed into 6 mil polyethylene bags for proper disposal. Impacted drywall will be removed at least 2 before the impacted area. Mold Remediation Protocols Page 4

21 Mold Remediation Protocols New City Hall - City of Panama City 501 Harrison Avenue May 15, 2018 Panama City, Florida NOVA Project #: POST-REMEDIATION EVALUATION Following completion of the remediation, NOVA s Licensed Mold Inspector will perform and visual inspection of all areas. The inspector may take tape lift samples at the inspector s discretion. No spore trap air samples will be collected due to the subject building being open to the ambient air. Mold Remediation Protocols Page 5

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t:

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t: Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL 35244 t: 205.986.0270 Decatur 717 Highway 67 South Suite 26 Decatur, AL 35603 t: 256.353.6222 Florence 4050 Helton Drive Suite 111 Florence, AL 35633

More information

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t:

Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL f: t: Birmingham 2080 Valleydale Road Suite 16 Birmingham, AL 35244 t: 205.986.0270 Decatur 717 Highway 67 South Suite 26 Decatur, AL 35603 t: 256.353.6222 Florence 4050 Helton Drive Suite 111 Florence, AL 35633

More information

Professional remediation of the school began on the weekend of October 5, 2013 and is due to continue until the entire building can be remediated.

Professional remediation of the school began on the weekend of October 5, 2013 and is due to continue until the entire building can be remediated. 1805 Atlantic Avenue Manasquan, New Jersey 08736 Tel: (732) 223-2225 www.brinkenv.com November 4, 2013 Mr. Robert Vogel, Facilities Manager Brick Township Public Schools 346 Chambers Bridge Road Brick,

More information

No dry drains/traps were found, eliminating a potentially concern for odors.

No dry drains/traps were found, eliminating a potentially concern for odors. January 5, 2017 Ms. Alix Zapolski Zapolski Real Estate, LLC. 501 Washington Street Durham, NC 27701 Re: Limited Indoor Air Quality Assessment Women s Restroom 137 E. Franklin Street, Chapel Hill, NC UNC

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services Lincoln School 1601 State Street Harrisburg, Pennsylvania 17103 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania 17103 February

More information

April 4, AHERA / Environmental Inspector Environmental Safety Office Old Marlboro Pike Upper Marlboro, MD 20772

April 4, AHERA / Environmental Inspector Environmental Safety Office Old Marlboro Pike Upper Marlboro, MD 20772 April 4, 2017 Mr. Alex Baylor AHERA / Environmental Inspector Environmental Safety Office 13306 Old Marlboro Pike Upper Marlboro, MD 20772 via email: alex.baylor@pgcps.org RE: Indoor Air Quality (IAQ)

More information

MOLD SCREENING REPORT

MOLD SCREENING REPORT MOLD SCREENING REPORT Mount Washington Middle School 269 Water Street Mt. Washington, KY 40047 Project # 115-7346 BCBOE PO#156081 Prepared for: Mr. Mark Mitchell Director, Buildings and Grounds Bullitt

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services 301 Hale Street Harrisburg, Pennsylvania 17104 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania 17103 February 2015 February

More information

Via . September 5, City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC

Via  . September 5, City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC Via Email September 5, 2014 City of Charlotte Engineering & Property Management 600 E. 4 th Street, 12 th Floor Charlotte, NC 28204-2844 Attention: Mr. David Wolfe, PE Re: Moisture Screening and Mold Air

More information

Limited Indoor Air Quality Assessment

Limited Indoor Air Quality Assessment Young Rainey STAR Center Areas 121 and 133 7887 Bryan Dairy Road Largo, Florida March 3, 2014 Terracon Project No. H4147022 Prepared for: Young Rainey STAR Center Pinellas County BOCC 7887 Bryan Dairy

More information

Report of Limited Indoor Air Quality Services

Report of Limited Indoor Air Quality Services Report of Limited Indoor Air Quality Services Camp Curtin School 2900 North 6th Street Harrisburg, Pennsylvania 17110 Prepared For: Harrisburg School District 1601 State Street Harrisburg, Pennsylvania

More information

INTRODUCTION. The evaluation was performed in the morning and afternoon on a weekday during normal building operations.

INTRODUCTION. The evaluation was performed in the morning and afternoon on a weekday during normal building operations. INTRODUCTION A preliminary indoor air quality (IAQ) evaluation was performed at the City of Stockton Police Department on March 23, 20. John J. Sacco, P.E., CIH of Earthshine Consulting, Inc (ECI) performed

More information

S outhwest GEOSCIENCE. Analytical Results/Chain of Custody

S outhwest GEOSCIENCE. Analytical Results/Chain of Custody S outhwest GEOSCIENCE Analytical Results/Chain of Custody Steve Moody Micro Services, LLC 2051 Valley View Lane Farmers Branch, TX 75234 Phone: (972) 241-8460 IAQ Mold Report Summary DSHS License No.:

More information

MOLD SCREENING REPORT

MOLD SCREENING REPORT MOLD SCREENING REPORT Mount Washington Middle School 269 Water Street Mt. Washington, KY 40047 Project # 115-7358 Prepared for: Mr. Mark Mitchell Director, Buildings and Grounds Bullitt County Board of

More information

Mr. Jody Davis PO Box 1475 Montgomery, TX

Mr. Jody Davis PO Box 1475 Montgomery, TX Texas Association of School Boards P.O. Box 400 Austin, TX 78767-0400 512-467-0222 Serving Texas School Boards since 1949 January 7, 2014 Mr. Jody Davis PO Box 1475 Montgomery, TX 77356-1475 Dear Mr. Davis:

More information

April 25, Mr. Simon List SITECH Consulting, P.C Breeland Way Raleigh, North Carolina 27613

April 25, Mr. Simon List SITECH Consulting, P.C Breeland Way Raleigh, North Carolina 27613 6304 Woodside Court Suite 112 Columbia, MD 21046 Tel: 410.794.1262 Fax: 410.794.1269 www.efiglobal.com April 25, 2016 Mr. Simon List SITECH Consulting, P.C. 9000 Breeland Way Raleigh, North Carolina 27613

More information

DATE: October 5, TO: Shawn Barr, Director. SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office

DATE: October 5, TO: Shawn Barr, Director. SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office DATE: October 5, 2017 TO: Shawn Barr, Director SUBJECT: Facility Services - IAQ - Air Test results - Jason Hughes' Office On Monday 10/2, Apex-Titan Air tested Jason Hughes Office. It is typically assumed

More information

Post Remediation Verification For 845 W. Center Street Pocatello, Idaho

Post Remediation Verification For 845 W. Center Street Pocatello, Idaho Post Remediation Verification For 845 W. Center Street Pocatello, Idaho Prepared for: Bank of the Cascades 1070 NW Bond Street, Suite 212 Bend, Oregon 97701 Prepared By: Summit 795 S. Orchard Street Boise,

More information

December 28, Lewisville Independent School District 340 Lake Haven Lewisville, Texas Attn: Mr. Paul Siddall

December 28, Lewisville Independent School District 340 Lake Haven Lewisville, Texas Attn: Mr. Paul Siddall December 28, 2015 Lewisville Independent School District 340 Lake Haven Lewisville, Texas 75057 Attn: Mr. Paul Siddall Re: Limited Mold Assessment Services Prairie Trail Elementary School Room 113 5555

More information

DATE: May 13, TO: Patricia Cuckler, Principal. SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206

DATE: May 13, TO: Patricia Cuckler, Principal. SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206 DATE: May 13, 2014 TO: Patricia Cuckler, Principal SUBJECT: Hedrick ES - IAQ - Air Test Results - Room 206 On Wednesday 5/7, SWG Air tested the Room 206. It is typically assumed that indoor spore levels

More information

Table of Contents. C. Recommended Remediation Firms: upon request

Table of Contents. C. Recommended Remediation Firms: upon request Table of Contents I. Job, Contact & Site Information II. Scope of Work III. Building Overview IV. Findings V. Conclusions and Recommendations VI. Expectations VII. References VIII. Limits of Liability

More information

ASBESTOS SCIENCE TECHNOLOGIES, INC.

ASBESTOS SCIENCE TECHNOLOGIES, INC. ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - astinc17@yahoo.com Report for Hoopa Valley Elementary School 11500 State Highway 96 Hoopa, Ca. 95546 Mold

More information

ASBESTOS SCIENCE TECHNOLOGIES, INC.

ASBESTOS SCIENCE TECHNOLOGIES, INC. ASBESTOS SCIENCE TECHNOLOGIES, INC. P.O. Box 505 Bangor, CA 95914 Phone (530) 518-0934 Email - astinc17@yahoo.com Report for Trinity Valley Elem. School Willow Creek, Ca. Mold Report - Rooms 12 through

More information

DATE: September 29, TO: Michael Wetchensky, Assistant Principal. SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511

DATE: September 29, TO: Michael Wetchensky, Assistant Principal. SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511 DATE: September 29, 2016 TO: Michael Wetchensky, Assistant Principal SUBJECT: Rockbrook ES - IAQ - Initial Contact - Room 511 This morning 9/29, I was following up on W.O. #334260: The room smells of mildew

More information

TN Tatem Middle School Indoor Air Quality Assessment September 2016

TN Tatem Middle School Indoor Air Quality Assessment September 2016 TN Tatem Middle School Indoor Air Quality Assessment September 2016 Completed by Island Air Quality Services P.O. Box SN139 Southampton SNBX Bermuda Table of Contents 1 Report Summary... 1 2 Introduction

More information

DATE: October 21, TO: Susan Blockley, Director

DATE: October 21, TO: Susan Blockley, Director DATE: October 21, 2013 TO: Susan Blockley, Director SUBJECT: Campus Support Services-Charles Street - IAQ - Air Test - Storage Rm- Southwest Corner Rm, Martha Fahlund's Office, Storage Rm-Northwest Corner

More information

Mold Remediation Supervisor. Course Syllabus

Mold Remediation Supervisor. Course Syllabus Mold Remediation Supervisor Course Syllabus The Mold Remediation Supervisor course is a three day introduction to mold remediation for supervisors. The course includes classroom instruction on background

More information

DATE: September 6, TO: Tim Greenwell, Principal. SUBJECT: Liberty ES - IAQ Air Test Results - Room 423

DATE: September 6, TO: Tim Greenwell, Principal. SUBJECT: Liberty ES - IAQ Air Test Results - Room 423 DATE: September 6, 2017 TO: Tim Greenwell, Principal SUBJECT: Liberty ES - IAQ Air Test Results - Room 423 On Tuesday 8/29, Apex-Titan Air tested Rooms 423. It is typically assumed that indoor spore levels

More information

INDOOR AIR QUALITY ASSESSMENT

INDOOR AIR QUALITY ASSESSMENT INDOOR AIR QUALITY ASSESSMENT Biddeford Intermediate School Biddeford Primary School JFK Memorial Kindergarten Center Biddeford High School Air Quality Management Services, Inc. PREPARED FOR Biddeford

More information

DATE: February 28, TO: Robin Fry, Principal. SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210

DATE: February 28, TO: Robin Fry, Principal. SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210 DATE: February 28, 2014 TO: Robin Fry, Principal SUBJECT: Polser ES - IAQ - Air Test - Room 200, 210 & Hallway outside 210 I received your E-mail on February 24, in regards to Room 210. When we looked

More information

DATE: December 10, TO: Jim Baker, Principal. SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222

DATE: December 10, TO: Jim Baker, Principal. SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222 DATE: December 10, 2013 TO: Jim Baker, Principal SUBJECT: DeLay MS - IAQ - Request for Air Test - Room 222 Received your E-mail this morning 12/10, and set up Work Order #172809: We had a leak in a class

More information

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance

Rowan University Department of Environmental Health and Safety. A Brief Overview for Building Maintenance Rowan University Department of Environmental Health and Safety A Brief Overview for Building Maintenance Mold Overview Wide variety of molds may be present in building materials Common ones include: Alternaria

More information

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

October 14, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment October 14, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix, Arizona

More information

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO#

November 18, Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona PO# Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment November 18, 2014 Attn: Deer Valley Unified School District Jim Migliorino 20402 North 15th Avenue Phoenix,

More information

DATE: June 4, TO: Randall Holder, Associate Principal

DATE: June 4, TO: Randall Holder, Associate Principal DATE: June 4, 2018 TO: Randall Holder, Associate Principal SUBJECT: Dale Jackson Career Center - IAQ - Air Test Results - Hallway Outside Wood Manufacturing and Tech On Thursday 5/24, Apex-Titan Air tested

More information

Limited Visual Assessment Report

Limited Visual Assessment Report Terramar School Peoria, Arizona July 27, 2015 Terracon Project No. 65157316 Prepared for: Deer Valley Unified School District Glendale, Arizona Prepared by: Terracon Consultants, Inc. Tempe, Arizona July

More information

DATE: October 30, TO: Curtis Martin, Principal. SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222

DATE: October 30, TO: Curtis Martin, Principal. SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222 DATE: October 30, 2018 TO: Curtis Martin, Principal SUBJECT: Hicks ES - IAQ - Air Test Report - Rooms E-209 & E-222 On Thursday 10/25, Apex-Titan Air tested Rooms E-209 and E-222. It is typically assumed

More information

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383

September 18, 204. Subject Property: Terramar Elementary School 7000 West Happy Valley Road Peoria, Arizona 85383 Asbestos Testing Lead Testing Microbial Testing Management Analysis Environmental Assessment September 18, 204 Attn: Valley Schools Insurance Trust and Pools Scott McCleary PO Box 41760 Phoenix, Arizona

More information

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22 Page 1 of 22 Asbestos Survey Project Summary Pursuant to your request; Environmental, Inc., has performed an Asbestos Building Survey on 8/13/2014 and limited to the above referenced location. The Interior/Exterior/Roof

More information

DATE: March 21, TO: Martha Gooding, Principal. SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5

DATE: March 21, TO: Martha Gooding, Principal. SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5 DATE: March 21, 2014 TO: Martha Gooding, Principal SUBJECT: Ethridge ES - IAQ - Initial contact - Room A-5 On Tuesday 3/18, I received W.O. #180591: In A5 the teacher has mentioned that in the morning

More information

Mold Remediation. 1. Purpose and Requirements. 2. Scope. 3. General Responsibilities HS13_IAQ_SOP_002. Occupational Safety & Health

Mold Remediation. 1. Purpose and Requirements. 2. Scope. 3. General Responsibilities HS13_IAQ_SOP_002. Occupational Safety & Health Occupational Safety & Health HS13_IAQ_SOP_002 1. Purpose and Requirements When mold growth occurs indoors, adverse health problems may be reported by some building occupants, particularly those with allergies

More information

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Bolin Administrative Center Suite W. Main Street Lewisville, Texas

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Bolin Administrative Center Suite W. Main Street Lewisville, Texas POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT Bolin Administrative Center Suite 105 1585 W. Main Street Lewisville, Texas May 30, 2017 Apex Project No. 72501027079 Prepared for: Lewisville Independent

More information

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Marcus High School ROTC Hallway 5707 Morriss Road Flower Mound, Texas

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. Marcus High School ROTC Hallway 5707 Morriss Road Flower Mound, Texas POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT Marcus High School ROTC Hallway 5707 Morriss Road Flower Mound, Texas August 17, 2015 LISD PO No. 91538989-00 Apex Project No. 7250115212 Prepared

More information

ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002)

ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002) ASSESSMENT, CLEANING & RESTORATION OF HVAC SYSTEMS (ACR-2002) C Cochrane * and T Yacobellis National Air Duct Cleaners Association ACR 2002 Committee, Washington, DC, USA ABSTRACT In the fall of 2001 NADCA

More information

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. BB Owen Elementary School Library 5640 Squires The Colony, Texas

POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT. BB Owen Elementary School Library 5640 Squires The Colony, Texas POST-REMEDIATION MOLD ASSESSMENT AND CLEARANCE REPORT BB Owen Elementary School Library 5640 Squires The Colony, Texas May 20, 2013 Project No. 0113H113 Prepared for: Lewisville Independent School District

More information

TEXAS CONSULTING SERVICES PO Box 9910 * Midland, Texas Phone: (432) * Fax: (432)

TEXAS CONSULTING SERVICES PO Box 9910 * Midland, Texas Phone: (432) * Fax: (432) TEXAS CONSULTING SERVICES PO Box 9910 * Midland, Texas 79708 Phone: (432) 687-5455 * Fax: (432) 687-5456 Email: Txcs65@yahoo.com May 28, 2015 City of Odessa Community Development PO Box 4398 Odessa, Texas

More information

DATE: September 5, TO: Chris Mattingly, Principal. SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307

DATE: September 5, TO: Chris Mattingly, Principal. SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307 DATE: September 5, 2017 TO: Chris Mattingly, Principal SUBJECT: Briarhill MS - IAQ - Air Test Results - Room 307 On Tuesday 8/29, Apex-Titan Air tested Rooms 307. It is typically assumed that indoor spore

More information

Limited Asbestos Demolition Survey

Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Former Fire Station Facility 25 to 45 S. Orlando Avenue Cocoa Beach, Florida Client: City of Cocoa Beach Public Works Department 1600

More information

Visible Mold (VM) and visible water damage under cabinet on the east wall

Visible Mold (VM) and visible water damage under cabinet on the east wall Liberty Occupational Health Management, Inc. E. 9 th St. Tulsa, Oklahoma 5 9..56 www.libertyohm.com 9..569 (fax) April 6, 0 Mr. Marty Foutch Facilities Director Bixby Public Schools 09 N. Armstrong Bixby,

More information

Mold. Guidelines for New Jersey Residents

Mold. Guidelines for New Jersey Residents Mold Guidelines for New Jersey Residents NJ Department of Health Consumer, Environmental and Occupational Health Service Environmental and Occupational Health Assessment Program P.O. Box 369 Trenton, NJ

More information

DATE: October 31, TO: Toby Maxson, Principal. SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16

DATE: October 31, TO: Toby Maxson, Principal. SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16 DATE: October 31, 2016 TO: Toby Maxson, Principal SUBJECT: Heritage ES - IAQ - Initial Contact - Room B-16 On Friday 10/28, I received Work Order #344295: Principal would like room tested: Per teacher

More information

THANK YOU WE APPRECIATE YOUR BUSINESS!

THANK YOU WE APPRECIATE YOUR BUSINESS! P.O. BOX 314 WASHBURN, ME 04786 TEL 207 455-4717 207 945-0131 800 509-5193 FAX 207 455-8090 EMAIL criterium-brown@criterium-brown.com February 26, 2015 Town of Addison Board of Selectmen Attn: John Woodward,

More information

BUILDING EXTERIOR SHELL TRAINING

BUILDING EXTERIOR SHELL TRAINING BUILDING EXTERIOR SHELL TRAINING Course Handout Part 1 Background and Insurance Issues (19min) Causes of Building Exterior Shell Problems Bad Design Poor Planning Failure to Follow Manufacturer s Recommendations

More information

SUMMARY OF OUR FINDINGS

SUMMARY OF OUR FINDINGS August 25, 2009 Mr. R.M. 12 XXXXX Shirley, NY 11967 Dear Mr. M., SUMMARY OF OUR FINDINGS A site visit was conducted on August 19, 2009 at the above address. Based on our visual inspection of the home we

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

Post Remediation Warranty

Post Remediation Warranty Post Remediation Warranty This warranty is provided by: Manufacturer: Anabec, Inc. 9393 Main Street PO Box 433 Clarence, NY 14031 716-759-1674 info@anabec.com & Qualified Contractor (Contractor): Presented

More information

2015 WSSCA Conference

2015 WSSCA Conference 2015 WSSCA Conference Patrick Finnemore, P.E. Director of Facilities Kenosha Unified School District Office: 262-359-7757 Cell: 262-945-2129 pfinnemo@kusd.edu Special thank you to Bill Freeman of EMC who

More information

DATE: May 27, TO: Sam Russell, Director. SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room

DATE: May 27, TO: Sam Russell, Director. SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room DATE: May 27, 2015 TO: Sam Russell, Director SUBJECT: Administration - IAQ - Initial Contact - Suite 225-Copy Room This morning 5/27, I received Work Order 220274: Suite 225 -The carpet in the copier room

More information

DATE: March 23, TO: Chad Russell, Principal. SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym

DATE: March 23, TO: Chad Russell, Principal. SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym DATE: March 23, 2018 TO: Chad Russell, Principal SUBJECT: Lamar MS - IAQ - Air Test Results - Main Gym On Monday 3/19, Apex-Titan Air tested the Main Gym. It is typically assumed that indoor spore levels

More information

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 4, Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 November 4, 2011 Mr. Tom Heinz 353 West Sawgrass Dakota Dunes, SD 57049 Re: Project #: 4004-050 353 West Sawgrass, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here 2847 Barnard Street San Diego California 92110 Phone 619.501.0185 Mobile 619.203.9774 Fax 619.501.9843 hoveyenv@cox.net RESIDENTIAL MOLD ASSESSMENT Final Report Your Address Here September 1, 2003 Prepared

More information

Mold Remediation. Containment guidelines: based on the size of the infected area.

Mold Remediation. Containment guidelines: based on the size of the infected area. Mold Remediation Containment guidelines: based on the size of the infected area. Level 1 (10 sq. ft. or less): e.g. ceiling tiles, small areas on walls Moldy materials that can be cleaned should be cleaned

More information

Limited Mold Sampling Investigation Report

Limited Mold Sampling Investigation Report Page 1 of 13 Limited Mold Sampling Investigation Report 9811 W. Charleston Blvd Suite 2403 Las Vegas, NV 89117 Tel: 702.255.2457 * Fax: 702.953.0286 www.msenational.com * info@msenational.com Customer

More information

TOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION Ext 395

TOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION Ext 395 TOWN OF ROTTERDAM BUILDING DEPARTMENT RESIDENTIAL ACCESSORY BUILDINGS AND STRUCTURE PERMIT APPLICATION 518-355-7575 Ext 395 Needed to Obtain a Residential Accessory Structure Building Permit: 1. Building

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785)

Dalrymple Consulting, Inc. Your Environmental Engineering Source 7841 SW 1 i b Street, Topeka, Kansas (785) FAX (785) Dalrymple Consulting, Inc. "Your Environmental Engineering Source" 7841 SW 1 i b Street, Topeka, Kansas 66615-1406 (785) 273-0345 FAX (785) 273-3071 January 10,2012 Mr. Steve Wiseman, Superintendent Atchison

More information

General Specifications for HVAC System Cleaning

General Specifications for HVAC System Cleaning General Specifications for HVAC System Cleaning Part 1 Special Provisions 1.01 Qualification of the HVAC System Cleaning Contractor (A) Membership: The HVAC system cleaning contractor shall be a member

More information

KORA_Req._for_Eng._Studies_on_Stouffer_Apts. KU Reference No

KORA_Req._for_Eng._Studies_on_Stouffer_Apts. KU Reference No 000130 1 PURPOSE: Professional Engineering Consultants, P.A. (PEC) was engaged by University of Kansas Design & Construction Management to perform an assessment of Stouffer Place Apartment Building 20

More information

Investigation Remediation Citation Drive, Suite 100 Compliance Restoration Brighton, MI 48116

Investigation Remediation Citation Drive, Suite 100 Compliance Restoration Brighton, MI 48116 Investigation Remediation 10448 Citation Drive, Suite 100 Compliance Restoration Brighton, MI 48116 Mailing Address: P.O. Box 2160 Brighton, MI 48116-2160 800 395-ASTI Fax: 810.225.3800 www.asti-env.com

More information

City of Warrenville, IL

City of Warrenville, IL CONSTRUCTION CODE SERVICES, INC. Building & Fire Protection Plan Review Training Inspections Code Consulting City of Warrenville, IL PROPOSAL FOR PLAN REVIEW, INSPECTION and ADMINISTRATIVE SERVICES SUBMITTED

More information

Table 1: Fungal Particulate Air Sample Results. ST-32 Room 17; post clean-up 5. 2 nd floor; commons area adjacent to Room 617

Table 1: Fungal Particulate Air Sample Results. ST-32 Room 17; post clean-up 5. 2 nd floor; commons area adjacent to Room 617 November 29, 2016 Chuck Doan Yakima School District #7 104 N 4th Avenue Yakima, WA 98902 Via email: Regarding: doan.chuck@yakimaschools.org Fungal Sample Results Blue Wall Room 617 Eisenhower High School

More information

Hikone. Sincerely, Enclosures

Hikone. Sincerely, Enclosures August 8, 2013 Mr. Richard Higgins Norstar Development USA, L.P. 733 Broadway Albany, New York 12207 Re: Asbestos Containing Material Survey Hikone 2702 2760 Hikone Road, Ann Arbor, Michigan ERG Project

More information

Mr. John Serraino QEP Vice President Product Management & Development 1001 Broken Sound Parkway, NW Boca Raton, FL 33487

Mr. John Serraino QEP Vice President Product Management & Development 1001 Broken Sound Parkway, NW Boca Raton, FL 33487 November 30, 2017 via email: jserraino@qep.com Mr. John Serraino QEP Vice President Product Management & Development 1001 Broken Sound Parkway, NW Boca Raton, FL 33487 Re: Respirable Dust Sampling During

More information

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049

INTRODUCTION: METHODOLOGY: November 11, Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 November 11, 2011 Mr. Tim Squier 487 Deerfield Dakota Dunes, SD 57049 Re: Project #: 4004-040 487 Deerfield, Dakota Dunes SD Microbial Clearance Testing INTRODUCTION: This report presents the findings

More information

MOLD ASSESSMENT REPORT

MOLD ASSESSMENT REPORT MOLD ASSESSMENT REPORT Project Location: Belleville Henderson CSD 8372 County Route 75 Adams, NY 13605 Prepared for: Ms. Jane Collins Superintendent Belleville/Henderson CSD 8372 County Route 75 Adams,

More information

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION INDOOR AIR QUALITY MANAGEMENT PLAN. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 018119 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION

STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION West Virginia University Environmental Health and Safety STANDARD OPERATING PROCEDURES FOR MOLD REMEDIATION Revised February 2016 West Virginia University P.O Box 6551 Morgantown WV 26506 # 304-293-3792

More information

Indoor Air Quality Report

Indoor Air Quality Report Indoor Air Quality Report Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 INDOOR AIR QUALITY SAMPLING REPORT Project Locations: Shawnee City Hall 222 N. Broadway, Shawnee, Oklahoma 74801 Prepared

More information

Post Remediation Testing Site Evaluation with Environmental Sampling

Post Remediation Testing Site Evaluation with Environmental Sampling Nationwide Locations Locally Served Corporate Headquarters: 7700 Congress Avenue Suite 1119 Boca Raton, FL 33487 Industrial Hygiene IAQ/Mold Assessments Water Loss Projects Restoration Project Mgmt Post

More information

Moisture in Buildings & Affects

Moisture in Buildings & Affects Moisture in Buildings & Affects on Occupant Health Rob Rottersman, MS, CIH rrottersman@environcorp.com 312.288.3857288 3857 Midwest Facility Masters Conference November 4, 2014 Health Risks What we know

More information

UNIVERSITY OF TOLEDO

UNIVERSITY OF TOLEDO UNIVERSITY OF TOLEDO SUBJECT: MOLD PREVENTION AND REMEDIATION Procedure No: HM-08-035 PROCEDURE STATEMENT In accordance with guidance provided by the US Environmental Protection Agency (EPA), Centers for

More information

SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE

SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE October 4, 2016 Michael Strong Vice President of Administrative Services SAN BERNARDINO COMMUNITY COLLEGE DISTRICT FOR CRAFTON HILLS COLLEGE 114 South Del Rosa Drive San Bernardino, California 92408 Re:

More information

Defining Failures in Residential Construction

Defining Failures in Residential Construction PHRC Webinar Series Tuesday, January 12, 2016 @ 1pm Defining Failures in Residential Construction Brian Wolfgang Housing Systems Specialist Pennsylvania Housing Research Center 219 Sackett Building University

More information

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY:

ANALYTICAL REPORT. Airconstruct HVAC Pty Ltd 37 Carlyle Street Mackay QLD Withheld PROPERTY: NSJ EnviroSciences Pty Ltd t/a MouldLab ABN 27 143 789 995 PO Box 306 WICKHAM NSW 2293 Phone: 02 4968 8448 Fax: 02 8004 3576 Mobile: 0410 239 848 Email: ---------------------------- ANALYTICAL REPORT CLIENT:

More information

Roseville OFFICE* 1911 Douglas Blvd, ste * Roseville, CA Phone (916) * Fax (916) *

Roseville OFFICE* 1911 Douglas Blvd, ste * Roseville, CA Phone (916) * Fax (916) * Roseville OFFICE* 1911 Douglas Blvd, ste 85-349* Roseville, CA 95661 Phone (916) 628-0050 * Fax (916) 781-6837 * www.hazmanage.com Camino Union Elementary School District Maintenance Building Demolition

More information

UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count!

UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count! Project # PRV140519 UNIVERSAL HOME & MOLD INSPECTIONS Where Quality and Details Count! Post Remediation Verification Visual Post-Remediation Verification With Non-viable Mold Sampling Client: Lauren Gash

More information

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe:

February 21, Mold Assessment. 400 East Avenue, Warwick, Rhode Island. Dear Mr. McCabe: February 21, 2014 Mr. Ken McCabe Lincoln Campus Physical Plant Director Community College of Rhode Island Knight Campus 400 East Avenue Warwick, Rhode Island 02866 Re: Mold Assessment Community College

More information

OLM Environmental, LLC PHONE: (919) LOCKWOOD FOLLY LANE; RALEIGH, NC CELLPHONE: (919)

OLM Environmental, LLC PHONE: (919) LOCKWOOD FOLLY LANE; RALEIGH, NC CELLPHONE: (919) OLM Environmental, LLC PHONE: (919) 212-3019 2317 LOCKWOOD FOLLY LANE; RALEIGH, NC 27610 CELLPHONE: (919) 931-0629 July 31, 2016 Zapolski Real Estate, LLC 501 Washington Street Durham, North Carolina 27701

More information

PRE-DEMOLITION LEAD PAINT SURVEY

PRE-DEMOLITION LEAD PAINT SURVEY PRE-DEMOLITION LEAD PAINT SURVEY Viewpoint Apartments 2518 Leon Street Austin, Florida PM Project Number 01-6219-0-002 Prepared for: Scannell Properties 800 East 96th Street, Suite 175 Indianapolis, Indiana

More information

FirstEnergy Program Overview

FirstEnergy Program Overview FirstEnergy Program Overview Builder incentives $400 per unit + $0.10/kWh in projected savings Eligibility Located in service area of a FirstEnergy Utility Certificate of Occupancy Dates: FirstEnergy Ohio

More information

ASBESTOS AND LEAD PAINT INSPECTION REPORT

ASBESTOS AND LEAD PAINT INSPECTION REPORT ASBESTOS AND LEAD PAINT INSPECTION REPORT for the former HENRY SILER SCHOOL 502 WEST THIRD STREET SILER CITY, NC March 2012 prepared by Herrick Engineering, Inc. 526 Lochness Lane Cary, NC 27511 (919)

More information

Pre-Renovation Asbestos Survey

Pre-Renovation Asbestos Survey Pre-Renovation Asbestos Survey L640 Level 2 Remodel College Complex Los Medanos College Pittsburg, California November 23, 2016 Terracon Project No. R1167D98 Prepared for: Contra Costa Community College

More information

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance

Foundations. Issue. Slab-On-Grade Liquid Water Control (See Figure 2-2) Goals. Guidance www.epa.gov/iaq/moisture Foundations Issue Building foundations are vulnerable to moisture problems for a number of reasons, including: Water from rain and from plumbing leaks is drawn by gravity to foundations,

More information

DRAFT. UNR Fungi Assessment & Remediation Program

DRAFT. UNR Fungi Assessment & Remediation Program DRAFT UNR Fungi Assessment & Remediation Program TABLE OF CONTENTS SCOPE AND APPLICATION... 3 ROLES AND RESPONSIBILITIES... 3 BUILDINGS AND GROUNDS / FACILITIES MANAGMENT... 3 ENVIRONMENTAL HEALTH AND

More information

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL

MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL MOLD REMEDIATION PROCEDURES AT A NEW JERSEY ELEMENTARY SCHOOL M McGuinness * R.K. Occupational and Environmental Analysis, Phillipsburg, NJ, USA ABSTRACT Microbiological remediation procedures at an Elementary

More information

Asbestos Abatement Standard Procedures Indoor Environment Group, Inc.

Asbestos Abatement Standard Procedures Indoor Environment Group, Inc. The following work procedures are specified on all full containment asbestos abatement projects that we design. A. Preliminary Air Sampling: Many buildings contain background fiber levels prior to, or

More information

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR:

SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD PREPARED FOR: SPORE SAMPLING REPORT FOR GLENWOOD MIDDLE SCHOOL 2680 ROUTE 97 GLENWOOD, MD 21738 PREPARED FOR: HOWARD COUNTY PUBLIC SCHOOL SYSTEM 10910 ROUTE 108 ELLICOTT CITY, MD 21043 PREPARED BY: ARIA ENVIRONMENTAL,

More information

Lead-Based Paint Inspection Summary

Lead-Based Paint Inspection Summary Lead-Based Paint Inspection Summary July 17, 2018 Montrose County Inspection Site: 61935 LaSalle Road Montrose, Colorado Inspection Date: June 20, 2018 Lead Risk Assessor: Sheila D. Sealander XRF Manufacturer:

More information

Chapter 2: Foundation

Chapter 2: Foundation Chapter 2: Foundation Crawlspace [V502.1.2] [V502.1.2] [V502.1.3] Vents. Vents in the crawlspace help keep floor insulation and floor framing dry. Crawlspace vents also reduce the potential for radon buildup

More information

Construction Indoor Air Quality (IAQ) Management Plan

Construction Indoor Air Quality (IAQ) Management Plan Denver School of Science & Technology Middle School 2000 Valentia Street Denver, CO 80238 Telephone: 303-643-5775 Main Fax: 303-673-5776 Construction Indoor Air Quality (IAQ) Management Plan Denver School

More information