BEP- TR CALCULATION METHOD and REFERENCE BUILDING
|
|
- Marilyn Cobb
- 5 years ago
- Views:
Transcription
1 BEP- TR CALCULATION METHOD and REFERENCE BUILDING
2 NATIONAL CALCULATION METHOD BEP-TR The officially accepted calculation methodology is based on BEP-TR is based on simple hourly method and planned to be used to assess the energy performance of new and existing buildings in Turkey. residential, office, health care, school buildings, hotels and shopping centers.
3 FIRST CERTIFIED BUILDINGS Ministry of Environment and Urban Planning
4 FIRST CERTIFIED BUILDINGS Building of Prime Minister
5 FIRST CERTIFIED BUILDINGS Building of Prime Minister
6 NOTIONAL REFERENCE BUILDING of BEP-TR (NO SATISFACTORY DATA for BUILDING STOCK)!!! Same form, orientation and location with the real building. Insulated according to compulsory Turkish Standard - TS8. Average glazing transmission. No shading. 0% incandescent and 70% fluorescent lamps. Average surface reflectivity. Standard efficiency for mechanical systems. Central heating system with natural gas. Central cooling and ventilating systems for commercial buildings with fan-coil. Natural ventilation and cooling with split-clima for residential buildings.
7 EPBD010 Reference: Int. Seminar on EPBD, 011, E. Cabau
8 STUDIES for REFERENCE BUILDING Climatic zones of Turkey
9 Relative Humidity (%) RELATIVE HUMIDITY Temperature ( C) TEMPERATURE Solar Radiation Intensity (W/m²) Relative Humidity (%) Relative RelativeHumidity Humidity(%) (%) Temperature Temperature ( C) Temperature( C) ( C) Solar SolarRadiation RadiationIntensity Intensity(W/m²) (W/m²) STUDIES for REFERENCE BUILDING ANKARA WEATHER SOLAR RADIATION ANTALYA WEATHER TEMPERATURE RELATIVE HUMIDITY SOLAR RADIATION
10 STUDIES for REFERENCE BUILDING ERZURUM WEATHER İSTANBUL WEATHER
11 BEP-TR PARAMETRIC SENSIVITY ANALYSIS APARTMENT BUILDING OFFICE BUILDING
12 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for apartment building in Istanbul Climatic zone İstanbul, Ankara, Erzurum Muğla, Mardin Scenario Base Scenario Base Scenario Base Scenario Heat Transfer coeff. for Opaque Comp. U (W/mK) B1 0.0 B 0.0 B Heat Transfer coeff. For Trans. Comp. U (W/mK) SHGC Air change rate ach
13 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for apartment building in Istanbul
14 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for apartment building in Antalya
15 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for apartment building in Erzurum
16 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for office building in Istanbul
17 BEP-TR PARAMETRIC SENSIVITY ANALYSIS Heating and cooling energy demand for office building in Antalya
18 CONFLICT between BEP-TR and Compulsory Insulation Standard of Turkey TS-8 HEATING and COOLING NEEDS of an OFFICE BUILDING in ANTALYA 0 0 SOĞUTMA (kwh/m²_yıl) 0 ISITMA (kwh/m²_yıl) YALITIMI TS 8'E UYGUN YALITIMI TS 8'DEN FAZLA YALITIMSIZ YALITIMSIZ VE YARI SAYDAM DIŞ GÖLGELEME İLE
19 EPBD010: Cost effective energy efficiency???
20 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 COST CALCULATIONS *For cost calculations, construction costs of base building is not included as investment cost. (Office building is considered as an existing building)
21 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Conditioned Zones: Five Floor Office Building Total Floor Area: 00 m² Transparency Ratio: %0 External North Office Zone External East Office Zone External South Office Zone External West Office Zone Internal West Office Zone Core Zone Internal East Office Zone East
22 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Ankara Office ,8 Heating -Natural Gas Boiler 180 Cooling -Electricity Chiller (COP =,) End Use Consumption kwh/m²a , 1,8 10, 111,1 109,8 108,7 100,,9,9 80 7, 0,9, 1,,, 19, 19, 11, 1,, 7,1,, 1,8,9 9,, 0 Cooling- Electricity 7,8,1 10,, Oth. Mech. - Electricity 8,1 11,,8, 0 Lighting -Electricity 0,0 0, 8,9 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Lighting Control Glazing: SHGC: 0,, Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading Case studies Heating-Natural Gas
23 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Ankara Office 0,0 Heating -Natural Gas Boiler 1,8 Primary Energy kwh/m ²a 00,0 Cooling -Electricity Chiller (COP =,) 0,0 00,0 0,0 1,8 1, 17,7 17,0 1,1 197, 00,0 Lighting -Electricity Oth. Mech. - Electricity 19, 10,0 100,0 0,0 0,0 19, 1, 19, 10,7, 17,0 1,, 9,0,7 7, 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading 1, 1, Cooling- Electricity 10,8 Heating-Natural Gas 88, 11,, 1,,7 11, 8, 1,8,, 1,8,,1 9,,1 7,7,1, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, Case studies
24 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Ankara Office End Use Consumption kwh/m ²a 00,0 Heating -Natural Gas Boiler 9,7 0,0 00,0 1, 179,9 180,0 10,9,9 10,0 180,1 Cooling -Electricity Chiller (COP=1),9,9 1, 1,7, 8,1 100,0, 11, 7, 99, Lighting -Electricity 11,, Oth. Mech. - Electricity,,1 Heating-Natural Gas,9 8,,9 87,9 101,, 0,0 8, 9, 7, 0,0 8, 0, 8,9 Th Ins. = TS8 Th Ins. > TS 8,,1,, 1,8 7 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, 0,0, 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading Case studies Cooling- Electricity
25 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Ankara Office 700,0 Primary Energy kwh/m²a 00,0 Heating -Natural Gas Boiler 8 Cooling -Electricity Chiller (COP = 1) 00,0 00,0 1,8 8, 19, 00,0 1,8 19, 19, 19, 19, 19,7 10,7 00,0 100,0 0,0 9,8 17, 08, 81, 0, 07, 11, 99,,, 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading 8,7 1,, 18,0 1,8 109, 11,8 Lighting -Electricity 1,, 10, 7,7 0, 8,9 0,0,, 1,8 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, Case studies Oth. Mech. - Electricity Cooling- Electricity Heating-Natural Gas
26 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office 0,0 Heating -Natural Gas Boiler End Use Consumption kwh/m²a 19, 00,0 10,0 1, Cooling -Electricity Chiller (COP =,) 1, 17,0 17,8 10,9 100,0,1,1,1 1, 1, 0,0 0,8, 1, 0,0,8 80,, 18, 108, 11,0 1, 11, 11,,9,7,9 Lighting -Electricity 8, 11,1 9,8,1,9,0,7 1, 1,, 7, 7,1 9, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading Case studies 8, Oth. Mech. - Electricity Cooling- Electricity Heating-Natural Gas
27 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office 00,0 Heating -Natural Gas Boiler 1,8 Primary Energy kwh/m²a 00,0 Cooling -Electricity Chiller (COP =,) 00,0 1,8 9,0 97, 00,1 00,0 1,9 17, 17, 18, 8,7 8,9 0,0 0,8 11, 9, 100,0 10, Lighting -Electricity 179,9 00,0,, 17, 1,1,0,1,7 7,0 8, 79, Oth. Mech. - Electricity 1,,,0 1,0 19,,7 1, 1,, 7, 7,1 9, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading Case studies 110,7,8 Cooling- Electricity Heating-Natural Gas
28 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office End Use Consumption kwh/m ²a 00,0 0,0 00,0 7, 1,8,,1 0,0,, 0,1,1,1,8,0 00,0 10,0 Heating -Natural Gas Boiler 7, Cooling -Electricity Chiller (COP = 1) 1, 0,,, 1, 1, 7,,,9 1,9 0 11,0 0, ,1 1, 11,0 100,0 17, 11, 9,0,7 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading Heating-Natural Gas 17, 1, 1,, 7, 7,1 9, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, Case studies Oth. Mech. - Electricity Cooling- Electricity 0,0 0,0 Lighting -Electricity
29 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office Heating -Natural Gas Boiler 900,0 818, Primary Energy kwh/m²a 800,0 700,0 00,0 78,0 17,1 17,,0,1 7,7 777, 17, 17,,7, 00,0 00,0 8,, 80, 0, 00,0 8,8 Cooling -Electricity Chiller (COP = 1) 18, 11,,,8,0 9, 7,, 1, 9, 71,0 7, Heating-Natural Gas 00,7 100,0 0,0,9,7 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading 1, 1,, 7, 7,1 9, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, Case studies Oth. Mech. - Electricity Cooling- Electricity 98,0 00,0 Lighting -Electricity
30 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office End Use Consumption kwh/m ²a 0,0 Heating -Natural Gas Boiler 0, Cooling -Electricity Chiller (COP =,) 00,0 10,0 1, 10,9 10, 10,9 99, 100,0 Lighting -Electricity,,, Oth. Mech. - Electricity, 1,7 0,0 11,1 9,8 11, 11, 11,8,9 8, 9,7 7, 8, 0,7, 1, 0,9, 9, 1 -Without Th Ins. -Glazing: SHGC: 0, -Encandescent Lamp -Without -Without Shading Th Ins. = TS8 Th Ins. > TS 8 Shading 1, 0,0 8, Case studies 9,1 Cooling- Electricity Heating-Natural Gas
31 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Mechanical System Antalya Office 00,0 Primary Energy kwh/m²a 00,0 Heating -Natural Gas Boiler 78,7 Cooling -Electricity Chiller (COP =,) 00,0 00,0 1,8 1,0, Lighting -Electricity 00,0 18,,7 7, 7,8 8, 90,1 9,8 0,7, 1, 1 -Without Th Ins. -Glazing: SHGC: 0, -Encandescent Lamp -Without -Without Shading Th Ins. = TS8 1,,8 100,0 11, 0,0 Oth. Mech. - Electricity 18, 18, 1, 1,,,0,1,8 0,9, 9, Th Ins. > TS 8 Shading Case studies Cooling- Electricity Heating-Natural Gas
32 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Heating -Natural Gas Boiler 1,8 Primary Energy kwh/m²a 00,0 COST CALCULATIONS Cooling -Electricity Chiller (COP =,) 0,0 00,0 0,0 1,8 1, 17,7 17,0 1,1 197, Lighting -Electricity 00,0 Oth. Mech. - Electricity 19, 10,0 100,0 0,0 0,0 19, 1, 19, 10,7 1,, 9,0,7 7, 1, 1,,,1 9,,1 7,7,1, 0,0-100,0 1-00,0 7-00,0-00,0-00,0-700,0 7 Investment Cost Enegry Cost Saving,7 11, 8, 1,8,, 1,8 7 8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, Heating-Natural Gas Heating -Natural Gas Boiler -00,0-800,0 1, Mechanical System Ankara Office 88, 11,, Th Ins. = TS8 Case studies 100,0 Cooling- Electricity 10,8, 17,0 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading TL/m² Mechanical System Ankara Office 0,0 Net Cost Cooling -Electricity Chiller (COP =,) 1. (). () (). () (Th Ins.=TS8) (). () (Th Ins.>TS8) (). () (Glazing) (). () (Shading) () 7. () () () 8. () (Glazing) () ()
33 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 Heating -Natural Gas Boiler 1,8 Primary Energy kwh/m²a 00,0 Cooling -Electricity Chiller (COP =,) 00,0 1,8 9,0 97, 00,1 00,0 17, 17, 17, 8,7 8,9 9, 00,0, 100,0 COST CALCULATIONS 10, 0,0 0,8 1,1 1,9, 18, 11,,7 7,0 8, 79, 179,9,1 0,0 1,,0,7 1, 1,, 7, 7,1 9, 7 8 Th Ins. = TS8 Th Ins. > TS 8 Glazing: SHGC: 0, Shading Glazing: SHGC: 0, 110,7 Oth. Mech. - Electricity Cooling- Electricity Heating-Natural Gas,8 Mechanical System Antalya Office Lighting -Electricity 1, 19, Case studies,0 1,0 1 -Without Th Ins. -Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 -Encandescent Lamp -Without -Without Shading TL/m² 100,0 Mechanical System Antalya Office 00,0 Heating -Natural Gas Boiler 7 8 Cooling -Electricity Chiller (COP =,) -100,0-00,0-00,0-00, ,0-00,0 InvestmentCost Enegry Cost Saving Net Cost 1. (). () (). () (Th Ins.=TS8) (). () (Th Ins.>TS8) (). () (Glazing) (). () (Shading) () 7. ()() () 8. () (Glazing) () ()
34 COST OPTIMIZED ENERGY EFFICIENCY COST CALCULATIONS Cooling -Electricity Chiller (COP =,) 00,0 00,0 1,8 1,0, Lighting -Electricity 00,0 18, 18, 18,,7 7, 7,8 8, 90,1 9,8 0,0 0,7, 1, 1 -Without Th Ins. -Glazing: SHGC: 0, -Encandescent Lamp -Without -Without Shading Th Ins. = TS8 1, 1,,,0,1,8 0,9, 9, Th Ins. > TS 8 Shading Cooling- Electricity Heating-Natural Gas Case studies Mechanical System Heating -Natural Gas Boiler 100,0 Oth. Mech. - Electricity 1,,8 11, Heating -Natural Gas Boiler 78,7 100,0 Antalya Office 11 0,0 1 00,0 Primary Energy kwh/m²a EnergyPlus EN 19 Mechanical System Antalya Office 00,0 Cooling -Electricity Chiller (COP =,) -100,0-00,0-00,0-00,0-00,0 Investment Cost Enegry Cost Saving Net Cost 1. (: wi th effi ci ent gl a zi ng ). () (). () (Th Ins.=TS8) (). () (Th Ins.>TS8) (). () (Shading) (). () () ()
35 COST OPTIMIZED ENERGY EFFICIENCY EnergyPlus EN 19 0 Without Thermal Insulation Glazing: SHGC: 0,8 Tvis: 0,89 U =,7 Encandescent Lamp Without FOR FURTHER STUDIES Without Shading 1 0 %70 Fluorescent %0 Incandescent Lamps RESIDENTIAL OFFICE 1 Th. Ins. = TS 8 Th. Ins.> TS 8 Glazing: SHGC: 0, 7 8 Shading %100 Fluorescent Lamps Glazing: SHGC: 0,
36 THANK YOU... Prof. Dr. A. Zerrin YILMAZ
A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey
Journal of Energy and Power Engineering 8 (2014) 20452052 D DAVID PUBLISHING A Study on the Evaluation of Heating and Cooling Energy Efficiency in Residential Buildings for Climatic Zones of Turkey Suzi
More informationOptimise the Specification of a Building Envelope
Optimise the Specification of a Building Envelope Introduction The building under analysis is to be used as a relaxation and study place for the doctors of a major clinic in Santiago, Chile. The first
More informationIMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO STANDARD AND DETAILED MODELLING PROGRAMS
IMPACT OF USING DIFFERENT MODELS IN PRACTICE A CASE STUDY WITH THE SIMPLIFIED METHODS OF ISO 13790 STANDARD AND DETAILED MODELLING PROGRAMS Kokogiannakis Georgios 1, Clarke Joe 1, Strachan Paul 1 1 Energy
More informationGreen Building Parameters & Case Studies
Green Building Parameters & Case Studies 14 th March, 2015 Mumbai Abdullah Nisar Siddiqui abdullah.nisar.siddiqui@undp.org Presentation Coverage 1. Energy Scenario in the Country 2. Green / Energy Efiicient
More informationPerformance Based Window Selection Model for Residential Buildings
Performance Based Window Selection Model for Residential Buildings Aslihan Tavil, Hakan Yaman and Ikbal Cetiner Faculty of Architecture, Istanbul Technical University, Taskisla, Istanbul, 34437 Turkey
More informationEvaluating Energy Savings Retrofits for Residential Buildings in China
Proceedings of BSO 2018: 4th Building Simulation and Optimization Conference, Cambridge, UK: 11-12 September 2018 Evaluating Energy Savings Retrofits for Residential Buildings in China 1 Christopher Tsang1,
More informationEvaluation of Energy Savings of the New Chinese Commercial Building Energy Standard
Evaluation of Energy Savings of the New Chinese Commercial Building Energy Standard Wei Feng, Ke Huang, Mark Levine and Nan Zhou, Lawrence Berkeley National Laboratory Shicong Zhang, Lawrence Berkeley
More informationWindows as a low energy light source in residential buildings: Analysis of impact on electricity, cooling and heating demand
Windows as a low energy light source in residential buildings: Analysis of impact on electricity, cooling and heating demand Peter Foldbjerg 1, Nicolas Roy 1, Karsten Duer 1 and Per Arnold Andersen 1 1
More informationPortuguese Thermal Building Legislation and Strategies for the Future
Chapter 2: Policies to Low Cost Sustainable Construction Portuguese Thermal Building Legislation and Strategies for the Future H. J. P. Gonçalves, M. J. N. Oliveira Panão & S.M.L. Camelo LNEG, Lisboa,
More informationENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICEBUILDING
ENERGY PERFORMANCE MODELLING AND HEAT RECOVERY UNIT EFFICIENCY ASSESSMENT OF AN OFFICEBUILDING Norbert L. HARMATI a*, Radomir J. FOLIĆ a, Zoltán MAGYAR b a University of Novi Sad, Faculty of Technical
More informationCase study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur
Case study of an ECBC Compliant, Energy Efficient Building: Aranya Bhawan, Jaipur Prashant Bhanware (BEEP) 2 nd REGIONAL WORKSHOP ON ECBC IMPLEMENTATION IN STATES March 15 & 16, 2017 Hyatt, Ahmedabad Outline
More informationEXECUTIVE SUMMARY: Best practices and lists of technologies to refurbish buildings & Proposed packages of measures
EXECUTIVE SUMMARY: Best practices and lists of technologies to refurbish buildings & Proposed packages of measures Authors: Zoltan Magyar, Gabor Nemeth & Jeno Kontra BME RePublic_ZEB 2016 Executive summary:
More informationOPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU
OPEN COMPETITION Energy Design of High Performance Buildings Organised by EC-JRC and ESRU Target group: under-graduate, postdoc, PhD students and researchers level SUMMARY The objective is to assess for
More informationMarket size and energy consumption of Korean building sector
Market size and energy consumption of Korean building sector Weather Condition of South Korea (Seoul) Target year for Net-ZERO BUILDING by countries - HDD : 2800-2950 Seoul - CDD : 750-908 Source : Towards
More informationA SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS
Proceedings of Building Simulation 2011: 1 2 3 4 5 6 7 8 9 10 A SIMPLE USER INTERFACE FOR ENERGY RATING OF BUILDINGS Abraham Yezioro 1, Oren Shapir 1, and Guedi Capeluto 1 1 Faculty of Architecture and
More informationatspaceltd.co.uk SBEM Checklist Version 1.0 January 2017 Call us today on to speak with an adviser or visit atspaceltd.co.
Version 1.0 January 2017 SBEM Checklist Call us today on 0800 917 8922 to speak with an adviser or visit SBEM Checklist This checklist is split into four sections. Section 1 Project/Client details. Section
More informationAnalysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.
Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates Piljae Im Graduate Student Jeff S. Haberl, Ph.D., P.E. Professor Energy Systems Laboratory Texas Engineering Experiment
More informationBULGARIAN LEGISLATION IN THE FIELD OF ENERGY EFFICIENCY HEAT RETENTION AND ENERGY CERTIFICATION OF NEW AND EXISTING BUILDINGS
BULGARIAN LEGISLATION IN THE FIELD OF ENERGY EFFICIENCY HEAT RETENTION AND ENERGY CERTIFICATION OF NEW AND EXISTING BUILDINGS GOVERNMENTAL POLICY FOR HARMONIZATION of the technical rules and regulations
More informationEE2E045 A Calculation Method on the Energy Demand of Urban Districts
EE2E045 A Calculation Method on the Energy Demand of Urban Districts DILAY KESTEN 1, AYSEGUL TERECI 2, URSULA EICKER 3 1 Department of Architecture, İstanbul Technical University, İstanbul Turkey & Centre
More informationEnergy efficiency building standards in Korea
www.asiabusinesscouncil.org Energy efficiency building standards in Korea Although government-affiliated research institutes, universities, and utility companies have investigated building energy efficiency
More informationJOTUN Cool Shades. Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings. ai³ Werner Jager
JOTUN Cool Shades Impact of the TSR Value on the Users Comfort and the Energy Performance of Buildings ai³ Werner Jager Exclusion of warranty: All tables, graphical charts and results presented within
More informationBUILDINGS BASED ON BUILDING ENERGY SIMULATION. Public Doctoral Defence April 12, Wout Parys
COST OPTIMIZATION OF CELLULAR OFFICE BUILDINGS BASED ON BUILDING ENERGY SIMULATION Public Doctoral Defence April 12, 213 Wout Parys Supervisor: Prof. dr.ir. Hugo Hens Co-supervisor: Prof.dr.ir. Dirk Saelens
More informationBUILDING ENERGY SYSTEMS
BUILDING ENERGY SYSTEMS Week 6 7LYM30 Building performance and energy systems simulation Building District Regional 2 Other challenges» Real challenge: existing buildings» Building + system building =
More informationMODELLING THE ENERGY PERFORMANCE
IBPSA Nordic 203 (Lund) 20 / 09 / 203 MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION QUASI-STEADY STATE CALCULATION METHOD EN ISO 3790 Jérôme LE DRÉAU Per HEISELBERG, Rasmus JENSEN, Ayser SELMAN
More informationIntroduction Table of Contents
Table of Contents 2 3 4 5 6 9 10 14 1 Energy consumption for different purposes of use and annual and hourly energy consumption patterns of hotels Energy consumption structure of a hotel Ventilation and
More information012345 523478 94 3432 39934 94 324 ()*+,-./) 0*1,2)3-4 5263*5.7 891: ;373.> -)5?5@5*36 ;+7+,-*A.> B2.7.9+2, 37@ C52)7.6.
More informationCHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017
CHIANG MAI HEALTH CARE CENTER Energy Efficiency Study, Chiang Mai, January 19, 2017 Unexpected Co., Ltd. EGS-plan (Bangkok) Co.,Ltd. Project location, 18 45'47.2"N / 99 00'40.9 E Chiang Mai Old City Ban
More informationThe commercial units were modelled as 2 separate units, please refer figure 1.1 and 1.2 for model details.
1.0 Introduction As part of the design for Plot G, a model was created of the commercial units which are located on the ground floor of the development, to calculate the carbon emissions. This model has
More informationDTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0
DTS & ENERGY MODELLING PROTOCOL GUIDE Version 1.0 Green Star SA Multi Unit Residential v1 DTS & Energy Modelling Protocol Guide First Released: 27 th October 2011 Last Update: 27 th October 2011 Change
More informationProject name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles
http://lowenergybuildings.org.uk Project name Gentoo Retrofit Bid 1 Project summary Refurbishment of 2no. Semi Detached houses using Passivhaus principles Project Description Projected build start date
More informationIESVE Compliance for ASHRAE IES Virtual Environment
IESVE Compliance for ASHRAE 90.1 - IES Virtual Environment July 2018 IES Virtual Environment and Compliance with ASHRAE 90.1-2004, 2007, 2010 & 2013; Appendix G, Performance Rating Method and Chapter 11,
More informationAssessing the energy performance of modern glass facade systems
Assessing the energy performance of modern glass facade systems Abdelsalam Aldawoud * Architectural Engineering Department, University of Sharjah Sharjah, United Arab Emirates Abstract. The design and
More informationA survey on energy consumption status and characteristics of hotel buildings in Guangzhou
IOP Conference Series: Earth and Environmental Science PAPER OPEN ACCESS A survey on energy consumption status and characteristics of hotel buildings in Guangzhou To cite this article: Yehong Li et al
More informationRetrofit Options to Reduce Climate Change Impacts on UAE Building Cooling Demand
Int. J. of Sustainable Water & Environmental Systems Volume 8, No. 2 (2016) 71-76 Retrofit Options to Reduce Climate Change Impacts on UAE Building Cooling Demand Abstract K. Shanks* School of Energy,
More informationGreen Star Multi Unit Residential Calculator Guide
Green Star Multi Unit Residential Energy Calculator Guide 1 EXECUTIVE SUMMARY The Green Star Multi Unit Residential Energy Calculator has been developed to predict the performance of multi-unit residential
More informationEnergy Audit of two Apartment Buildings in Cagliari using Energy Simulation
Energy Audit of two Apartment Buildings in Cagliari using Energy Simulation Graduation Thesis by Carla Vargiu and Luisa Zedda, Master in Green Building and Energy Efficiency This thesis focuses on the
More informationCALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE
Green design and sustainable architecture CALCULATIONS OF COST-OPTIMAL LEVELS OF ENERGY PERFORMANCE REQUIREMENTS FOR RENOVATED BUILDINGS AND BUILDING ELEMENTS: A LATVIAN CASE Dr. phys. Staņislavs Gendelis
More informationSURNA Grow Facility: Systems Comparison - IEA
SURNA Grow Facility: Systems Comparison - IEA May 2016 SURNA Grow Facility This analysis provides the projected energy and associated cost comparison between the Surna proposed facility in comparison to
More informationLoad Calculations Heat Balance Method - Application
Load Calculations Heat Balance Method - Application Prof. Jeffrey D. Spitler School of Mechanical and Aerospace Engineering, Oklahoma State University Weather Data: Cooling Three types of design days Based
More informationAppendix E-1f: Small Building Methodology for Pre-SB2030 Projects
Appendix E-1f: Small Building Methodology for Pre-SB2030 Projects Prescriptive Bundle Option Method for Office Buildings less than 30,000 GSF This section describes energy strategy requirements for three
More informationTREES Training for Renovated Energy Efficient Social housing. Section 1 Techniques 1.2 Replacement of glazing
TREES Training for Renovated Energy Efficient Social housing Intelligent Energy -Europe programme, contract n EIE/05/110/SI2.420021 Section 1 Techniques 1.2 Replacement of glazing Bruno PEUPORTIER ARMINES
More informationSimplified methods to evaluate energy use for space cooling in the energy certification
Simplified methods to evaluate energy use for space cooling in the energy certification Alessio Gastaldello and Luigi Schibuola University IUAV of Venice, Italy Corresponding email: luigi.schibuola@iuav.it
More informationAsset Energy Calculator Guidance
Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements
More informationASHRAE 90.2 Kuwait What Can be Learned From It?
ASHRAE 90.2 Kuwait What Can be Learned From It? Prof. Walid Chakroun Kuwait University Sixth "Zayed Seminar" on Green Economy: Success Stories from the GCC May 8-9, 2013 Today s building designs mortgage
More informationLARGE-SCALE IMPLEMENTATION OF ENERGY EFFICIENCY IN BUILDINGS
LARGE-SCALE IMPLEMENTATION OF ENERGY EFFICIENCY IN BUILDINGS Policies and initiatives Implementing energy efficiency in buildings Regulatory policy instruments Energy efficiency codes & guidelines for
More informationReducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling
Reducing energy demand in non-domestic buildings: integrating smart facades, ventilation, and surface heating and cooling Phil Jones, Shan Shan Hou and XiaoJun Li Welsh School of Architecture, Cardiff
More informationComplying with the Minimum Energy Efficiency Standards (MEES)
Complying with the Minimum Energy Efficiency Standards (MEES) Advantages of using DSM software to calculate the EPC Rating Introduction The Minimum Energy Efficiency Standards (MEES) for commercially rented
More informationEnergy and Cost Analyses of Solar Photovoltaic (PV) Microgeneration Systems for Different Climate Zones of Turkey
Energy and Power Engineering, 2016, 8, 117-129 Published Online March 2016 in SciRes. http://www.scirp.org/journal/epe http://dx.doi.org/10.4236/epe.2016.83010 Energy and Cost Analyses of Solar Photovoltaic
More informationENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE
Bulletin of the Transilvania University of Braşov Vol. 3 (52) - 2010 Series I: Engineering Sciences ENERGETIC MONITORING AND OPTIMIZATION OF A SOLAR HOUSE M. MOLDOVAN 1 I. VIŞA 1 A. DUŢĂ 1 Abstract: Into
More informationInterventions for Ensuring Thermal Comfort Equality in Apartment Buildings
European Journal of Sustainable Development (2017), 6, 3, 40-50 ISSN: 2239-5938 Doi: 10.14207/ejsd.2017.v6n3p40 Interventions for Ensuring Thermal Comfort Equality in Apartment Buildings By Nese Dikmen
More informationEnergy and the Built Environment
Energy and the Built Environment Atila Novoselac Wesley Cole Energy Technology & Policy 10/23/12 Lecture Objectives How much energy is consumed in buildings How the energy is consumed How to make them
More informationProceedings of BS2015: 14th Conference of International Building Performance Simulation Association, Hyderabad, India, Dec. 7-9, 2015.
PARAMETRIC ANALYSIS USING DYNAMIC ENERGY SIMULATION TOOLS TO EVALUATE THE PERFORMANCE OF BUILDING ENVELOPE IN THE RESIDENTIAL BUILDINGS OF COMPOSITE CLIMATIC REGION OF INDIA Pierre Jaboyedoff 1, Kira Cusack
More informationCOOLING LOAD ESTIMATION OF A ROOM
COOLING LOAD ESTIMATION OF A ROOM Prof. Deepak Kumar Yadav 1, Aviral Srivastava 2, Ayush Chauhan 3, Gaurang Tripathi 4, Ankur Kumar 5 1Assistant Professor, Mechanical Engineering, IMS Engineering College,
More informationTheory versus practice of energy and comfort in 4 low energy houses in Belgium
Theory versus practice of energy and comfort in 4 low energy houses in Belgium Griet Verbeeck 1,*, Werner Carmans 1, Veerle Martens 1 1 PHL University College, Diepenbeek, Belgium * Tel: +32 11249207,
More informationSUCCESSFUL RETROFIT OF NON- RESIDENTIAL BUILDINGS: HEATING AND COOLING CONCEPTS
SUCCESSFUL RETROFIT OF NON- RESIDENTIAL BUILDINGS: HEATING AND COOLING CONCEPTS Dr.-Ing. Doreen Kalz Fraunhofer-Institute for Solar Energy Systems ISE Symposium IEA SHC Task 47 Frankfurt, 3. April 2014
More informationChapter 4. Analysis of Building Energy Performance
Chapter 4 Analysis of Building Energy Performance 128 4.1 Introduction This chapter deals with energy modeling and simulation of the baseline models for the buildings to assess energy performance of the
More informationDeliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006
Contract No. EIE-2003-RURASU-223 Deliverable D.3.3 Common computer tool for building simulations -Manual- English version July 2006 Prepared by: Kostas Pavlou University of Athens, Physics Department (IASA
More informationZEM ds : Case studies
ZEMedS: Case studies Case study: Salamanque Group school, Montpellier, France The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect the opinion
More informationWindow Labelling Program for India
Window Labelling Program for India Stakeholder consultation meeting : October 13, 2012, New Delhi Centre for Advanced Research in Building Science and Energy, CEPT University, Ahmedabad INDIA Rajan Rawal,
More informationEnergy Simulation Study of Efficient Construction Materials for Cold Climate Homes
Energy Simulation Study of Efficient Construction Materials for Cold Climate Homes Gül Nihal Güğül [0000-0002-5927-3308] Selcuk University, Faculty of Technology, Department of Computer Engineering,, 42075,
More informationGLAZING STUDIES FOR THE NATIONAL CONSTRUCTION CODE 2019
GLAZING STUDIES FOR THE NATIONAL CONSTRUCTION CODE 2019 DANIEL JOHNSTON Graduate Consultant, Projects & Advisory Services Division Energy Action Unit H, 58-69 Lathlain St Belconnen ACT 2617 daniel.johnston@energyaction.com.au
More informationUnderstanding "Heat Load & Psychometric. by Djunaidi HS
Understanding "Heat Load & Psychometric by Djunaidi HS Welcome To The Heat Load Calculation Course 2 3 Understanding Of Heat Load (Human Comfort) 1) Heat Load - Classified into 2 main types : 1. Sensible
More informationnzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing.
BBR Bonn 2011 nzeb Germany - Strategy to improve energy efficiency in the German building sector and the leading role of public buildings Dr.-Ing. Olaf Böttcher - Commissioner for Energy in Federal Buildings
More informationBUILDING PERFORMANCE IMPROVEMENTS FROM NCC2019
BUILDING PERFORMANCE IMPROVEMENTS FROM NCC2019 DR PAUL BANNISTER, F.AIRAH FIEAUST Director, Innovation and Sustainability Energy Action (Australia) Pty Ltd PO Box 546 Belconnen ACT 2617 paul.bannister@energyaction.com.au
More informationTechnology and Techniques
Technology and Techniques in glass facades SEE MORE Building follows Trend : Conventional Green Buildings: E.P.I = 140 kwh/m²-yr Cost / m² =Rs.1100 /- Modern Buildings : Air Conditioned E.P.I = 200 kwh/m²-yr
More informationLow energy buildings
Low energy buildings the basis for realizing the strategy for independency of fossil fuels in 2050 NSB 2011 Tampere 2011-05-31 Professor Svend Svendsen Department of Civil Engineering Technical University
More informationResults from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments
Results from the Application of the Maltese Energy Performance Rating of Dwellings in Malta EPRDM Software to a New Block of Apartments Charles Yousif Institute for University of Malta with Celia Pérez
More informationBuilding Regulations and the Future of Energy Efficient Buildings. Chris Hughes Programme Manager Energy Performance of Buildings Directive
Building Regulations and the Future of Energy Efficient Buildings Chris Hughes Programme Manager Energy Performance of Buildings Directive Overview SEAI Energy Efficiency Building Regulations Part L Conservation
More informationMinisterio Público Fiscal de la Ciudad de Buenos Aires Fiscalía General Departamento de Infraestructura y Apoyo Operativo
Air System Design Load Summary for Zona 1 Project Name: Av. Cabildo 3076, 4 piso 04/05/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8
More informationUrban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK
Urban Greening and the UHI: Seasonal Trade-offs in Heating and Cooling Energy Consumption in Manchester, UK T H E R E S E A R C H E R S C y n t h i a S k e l h o r n PhD Physical Geography Post-Doctoral
More informationTHE ROAD TO NEARLY ZERO-ENERGY BUILDINGS
Int. Journal for Housing Science, Vol.38, No.4 pp. 239-250, 2014 Published in the United States THE ROAD TO NEARLY ZERO-ENERGY BUILDINGS Z. Szalay Department of Architectural Engineering Budapest University
More informationCost Benefits of SunGuard SN 54
Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building
More informationTwo-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings
Downloaded from vbn.aau.dk on: March 30, 2019 Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings Afshari, Alireza; Gordnorouzi, Rouzbeh; Hultmark, Göran;
More informationAvailable online at ScienceDirect. Energy Procedia 111 (2017 )
Available online at www.sciencedirect.com ScienceDirect Energy Procedia 111 (2017 ) 308 317 8th International Conference on Sustainability in Energy and Buildings, SEB-16, 11-13 September 2016, Turin,
More informationDemonstration of modeling of radiant cooling system in design builder. Prashant Bhanware & Bharath Reddy
Demonstration of modeling of radiant cooling system in design builder Prashant Bhanware & Bharath Reddy CONTENTS Introduction to Design Builder Building Energy Simulation Modeling procedure Making a model
More informationAalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings General rights Take down policy
Aalborg Universitet Two-Pipe Chilled Beam System for Both Cooling and Heating of Office Buildings Afshari, Alireza; Gordnorouzi, Rouzbeh; Hultmark, Göran; Bergsøe, Niels Christian Published in: Proceedings
More informationADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING
ADVANCED FAÇADES AND HVAC SYSTEMS: PRELIMINARY RESULTS OF FULL-SCALE MONITORING M. Kragh, M. Colombari and M. Zobec Permasteelisa Group, Research & Engineering, 31020 San Vendemiano (TV), Italy www.permasteelisa.com,
More informationBenchmarking Regulations on Energy Efficiency of Buildings
Benchmarking Regulations on Energy Efficiency of Buildings Federation of European Heating, Ventilation and Air-conditioning Associations REHVA May 8, 2010 This summary and conclusions are based on the
More informationHigh-efficiency Appliance Certification Program in
High-efficiency Appliance Certification Program in High-efficiency Appliance Certification Program Promotion of High-efficiency Appliances High-efficiency Appliance Certification Program 1. The Propose
More informationPassivhaus Projects and Benefits
Passivhaus Projects and Benefits Andrew T. Arthur MPH CMCIEH Arthur Associates Passivhaus not Passive House Need to make distinction between: this and this Passivhaus Standard which was developed in Germany
More informationPlanned energy-efficient retrofitting of a residential building in Italy
Zanchini et al. Future Cities and Environment (2015) 1:3 DOI 10.1186/s40984-015-0004-9 TECHNICAL ARTICLE Planned energy-efficient retrofitting of a residential building in Italy Enzo Zanchini 1*, Claudia
More informationNearly Zero Energy Buildings (NZEB) Seán Armstrong, Housing/Building Standards Section, DHPCLG
Nearly Zero Energy Buildings (NZEB) Seán Armstrong, Housing/Building Standards Section, DHPCLG Outline Current Part L Requirements Implementing the Energy Performance of Buildings Directive and NZEB Dwellings
More informationThermal Characteristics of a Vernacular Building Envelope
Thermal Characteristics of a Vernacular Building Envelope Priyanka Dhar, M.Tech. Department of Energy, Tezpur University, Tezpur, 784028, Assam, India Pallavi Borah, M.Tech. Department of Energy, Tezpur
More informationATS Le Grandiose, Sector 150 Noida. Energy Conservation Building Code (ECBC) Compliance Report
Energy Conservation Building Code (ECBC) Compliance Report ATS Le Grandiose, Sector 150 Noida Energy Conservation Building Code (ECBC) Compliance Report For M/s. Nobility Estates Pvt. Ltd. ECBC CONTENTS
More informationSIMULATION AS A TOOL TO DEVELOP GUIDELINES FOR THE DESIGN OF SCHOOL SCHEMES FOR FOUR CLIMATIC REGIONS OF TURKIYE
SIMULATION AS A TOOL TO DEVELOP GUIDELINES FOR THE DESIGN OF SCHOOL SCHEMES FOR FOUR CLIMATIC REGIONS OF TURKIYE Gülsu Ulukavak Harputlugil 1, Jan L.M. Hensen 2 and Pieter de Wilde 3 1 Department of Architecture,
More informationNC ECC Commercial Training June 2011
Mathis Consulting Company North Carolina Energy Conservation Code: Commercial Prescriptive Provisions Mathis Consulting Company Building Solutions Chris Mathis 100+ Years of Experience as Building Scientists,
More informationA method for economic optimization of energy performance and indoor environment in the design of sustainable buildings
A method for economic optimization of energy performance and indoor environment in the design of sustainable buildings Sanne Hansen 1 and Lies Vanhoutteghem 1 1 Department of Civil Engineering, Technical
More informationZEMedS: Case studies
ZEMedS: Case studies Case study: ANTONIO SALVETTI Primary School, Colle di Val d'elsa, Italy The sole responsibility for the content of this publication lies with the authors. It does not necessarily reflect
More informationSt Loyes Extra Care Facility PHPP Pre-Assessment Report
St Loyes Extra Care Facility PHPP Pre-Assessment Report Gale & Snowden Architects & Engineers July 2011 Gale & Snowden Architects St Loyes Extra Care Facility PHPP Pre-Assessment Report Page 2 of 10 St
More informationA STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE
Int. Journal for Housing Science, Vol.37, No.1 pp.23-31, 2013 Published in the United States A STUDY ON DESIGN OPTIMIZATION OF A NEAR NET-ZERO ENERGY HOUSE Narghes Doust, Gabriele Masera and Marco Imperadori
More informationctbuh.org/papers Effects of Vertical Meteorological Changes on Heating and Cooling Loads of Super Tall Buildings Title:
ctbuh.org/papers Title: Authors: Subjects: Keywords: Effects of Vertical Meteorological Changes on Heating and Cooling Loads of Super Tall Buildings Doosam Song, Sungkyunkwan University Yang Su Kim, Samsung
More informationPart L of Building Regulations 2017-Buildings other than Dwellings. Seán Armstrong, Housing/Building Standards Section, DHPCLG
Part L of Building Regulations 2017-Buildings other than Dwellings Seán Armstrong, Housing/Building Standards Section, DHPCLG Outline Implementing the Energy Performance of Buildings Directive and NZEB
More informationABUD Engineering Ltd., Budapest, Hungary. The Building Performance Team Inc, Grand Rapids, Michigan
2018 Building Performance Analysis Conference and SimBuild co-organized by ASHRAE and IBPSA-USA Chicago, IL September 26-28, 2018 IMPLICATIONS OF EPBD COMPLIANT FACADE ON PRIMARY COOLING ENERGY DEMAND
More informationENERGY STAR Qualified Homes National Program Requirements, Version 3.0
Qualifying Homes The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or less; Units in multi-family buildings that are
More informationPrinciples of Ventilation and Air Conditioning Design & Installation
Unit 10: Unit code Principles of Ventilation and Air Conditioning Design & Installation D/615/1926 Unit level 4 Credit value 15 Introduction The demands of modern living as well as the potential impact
More informationCalculation of Annual Consumption of Lighting Energy for Five Different Cities and Building Types and a Control System Proposal
Calculation of Annual Consumption of Lighting Energy for Five Different Cities and Building Types and a Control System Proposal Ahmet Can Cevahir 1, Nurettin Çetinkaya 2 1,2 Department of Electrical &
More informationEnergy savings certificates in France Selection of calculation sheets. IEA-DSM Task XXI: Standardisation of Energy Savings Calculation
Energy savings certificates in France Selection of calculation sheets IEA-DSM Task XXI: Standardisation of Energy Savings Calculation March 2010 Household sector Insulation building envelope Internal wall
More informationThermal rehabilitation of buildings facades with exterior insulation systems
Thermal rehabilitation of buildings facades with exterior insulation systems Bruno André Pirão Freire Supervisor: Prof. António Heleno Domingues Moret Rodrigues June 2015 Thermal rehabilitation of buildings
More informationXiaofen Xu, Liang Zhang, Huajing Sha, Ying Ji, Peng Xu. Tongji University, Shanghai, China
Establishment of Typical Building Models in Each Climate Regions in China and Research of Adaptability of Energy Saving Research of Adaptability of Energy- Technologies in the Standard of 65% Energy Saving
More information