Achieving ASHRAE 90.1 and with Armstrong Design Envelope Green Building Solutions

Size: px
Start display at page:

Download "Achieving ASHRAE 90.1 and with Armstrong Design Envelope Green Building Solutions"

Transcription

1 Armstrong Fluid Technology ASHRAE QATAR ORYX CHAPTER - Seminar 2014 Achieving ASHRAE 90.1 and with Armstrong Design Envelope Green Building Solutions

2

3 Armstrong Core Competencies Heat Transfer Fluid Flow Variable Speed Demand Based Control Integrated Solutions Pumping Units Integrated Fluid Management Integrated Plant Packages Re-Commissioning and Service Optimum Life-Cycle Building Performance

4 Agenda Peter Wolff: Exceeding ASHRAE 90.1 Best-practices in Pump Applications Demand-based Pump Controls Rajmohan Govindraj: Exceeding ASHRAE Demand-based Plant Controls

5 Design Envelope selection method HVAC is a global part-load industry London Heathrow Los Angeles Qatar 10%-60% of design load 90% of the time Toronto Canada Berlin Germany Worldwide

6 ASHRAE Standard ASHRAE 90.1 is an energy standard for buildings It provides the minimum requirements for the energyefficient design of buildings Most North American building codes have adopted ASHRAE 90.1 standards The 2010 version is expected to be adopted by North American building codes on October 18, 2013

7 ASHRAE Hydronic system design and control Hydronic variable flow systems Individual chilled water pumps serving variable flow systems having motors exceeding 5hp (3.7kW) shall have controls and / or devices (Such as variable speed control) that will result in pump motor demand of no more than 30% of design wattage at 50% of design water flow Note that the ASHRAE requirement starts at 5hp (3.7kW) motors. Compare this to the 2007 version which started at 50hp (37kW) Progress to all pumps 1hp (0.75kW) and over having integrated controls

8 Building load profile Pumps should be designed for BEST EFFICIENCY operation here. Traditional pumps are designed for best efficiency operation here.

9 ASHRAE System balancing Hydronic systems shall be proportionately balanced in a manner to first minimize throttling losses; then the pump impeller shall be trimmed or speed adjusted to meet design flow conditions

10 Why have throttling ability in variable flow system? Head/Pressure Spee d 2 Spee d 1 D C A = Design Point B = Actual Site Duty Point C = Reduced Speed without throttling D = Reduced Speed with Throttling A System Resista nce B Flow Triple duty valves Isolates pump Check feature Throttle AVAILABLE if system is outside pump operation Reducing speed will not achieve this Use on all pumps 90 elbow when needed

11 ASHRAE Pipe sizing All chilled water and condenser water piping shall be designed such that the flow rate shall not exceed the values listed in table for the appropriate total annual hours of operation. Separated into 2 categories 1. Variable flow/variable speed systems 2. All other (constant flow) systems

12 ASHRAE Table Pipe sizing

13 ASHRAE Pipe sizing Example: 1400 USgpm 90.1 Standard Pipe Variable Constant 12 Another example of cost savings from variable speed, Design Envelope pumps: 10" pipe x 100 ft long = $4,640 pipe cost 12" pipe x 100 ft long = $5,260 pipe cost A $620 (or 12%) savings can be found with using smaller pipe - another reason that all pumps over 1 hp (.75 kw) should have integrated controls.

14 HVAC pump requirements in ASHRAE 90.1 Energy savings through: Flow control Balancing Pipe sizing

15 3 Basic pump configurations Horizontal split case End suction Vertical in-line

16 Horizontal split case Coupling Outlet Inlet Bedplate

17 Horizontal split case vertically mounted Coupling Outlet Inlet Bedplate

18 Horizontal Split Case - top suction and discharge Inlet Outlet Bedplate Coupling

19 End suction pump Outlet Coupling Inlet Bedplate

20 Split coupled Vertical in-line No Bedplate Coupling Outlet Inlet

21 Vertical in-line Armstrong recommends this configuration be used up to 7.5 hp only (Design Envelope 5 hp only) due to weight and handling of motors during seal changes.

22 Which is the best configuration for the application?

23 Consider six major criteria A. Floor space B. Ease of installation C. Maintainability D. Reliability E. Energy costs F. Sustainability Product Life Cycle

24 Floor space End Suction / Horizontal Split Case and variations Inertia base typically extends 6 or more around the pump bedplate

25 Floor space Vertical Inline Can be suspended in ceiling requiring no floor space Supports No supports Can be installed with or without supports Space under pumps always accessible for cleaning or maintenance Use long radius elbow if space extra tight

26 Floor space (500 USgpm/90ft) VIL 50% less floor space than end Suction 3 pump system: Savings 14.1 ft $150/ft 2 is $2,115 End suction (28.5 ft 2 ) Vertical In-line (14.4 ft 2 )

27 Floor space (500 USgpm/90ft) VIL 78% less floor space than HSC 3 pump system: Savings 51.9 ft $150/ft 2 is $7,785 Horizontal split case (66.0 ft 2 ) Vertical In-line (14.4 ft 2 )

28 VIL replacing HSC

29 Floor space (500 USgpm/90ft) VIL 66% less floor space than HSC turned Vertically 3 pump system: Savings 27.6 ft $150/ft 2 is $4,140 Horizontal split case (42.0 ft 2 vertically mounted) Vertical In-line (14.4 ft 2 )

30 Floor space (500 USgpm/90ft) VIL 60% less floor space than HSC (top suction top discharge) 3 pump system: Savings 21.6 ft $150/ft 2 is $3,240 Horizontal split case (36.0 ft 2 top suction and discharge) Vertical In- Line Vertical In-line (14.4 ft 2 )

31 Floor space Vertical In-Line pumps typically use 1/4 floor space of equivalent HSC design units Consultant Flack + Kurtz inc. Battery Park, New York City Installed in the 80 s

32 Floor space 1/4 floor space HICSA Mexico Design Built Contractor Ford Plant, Mexico

33 Floor space Southern Air Design Build Contractor

34 Floor space Enwave, Toronto 16x16x15 350hp ( kW) TMP Toronto

35 Floor space Allows for direct connection to equipment: To chiller To heat exchanger

36 Consider six major criteria A. Floor space - Vertical 50 to 78% less B. Ease of installation C. Maintainability D. Reliability E. Energy costs F. Sustainability Product Life Cycle

37 Ease of installation Coupling re-alignment Grouting Inertia pad Concrete base Flex connectors

38 Ease of installation: Base mounted end suction pump Typical cost required 8 Pump Inertia base spring mounts $3660 Flex connectors $ 500 Grout and alignment $1600 Extra cost to install $5,760

39 Ease of installation: Base mounted split case pump Typical cost required 8 Pump Inertia base spring mounts $5,740 Flex connectors $500 Grout and alignment $2,100 Extra cost to install $8,340

40 Ease of installation: Vertical In-Line pump Typical cost required 8 Pump No Inertia Base 0 No Spring Mounts 0 (Base snubbers only for seismic applications) No flex connectors 0 No grout or alignment 0 Extra cost to install 0

41 Ease of installation

42 Ease of installation Piping cost Length of pipe $225,975 $128, ft (2751/100=27.51x 3 tdh=82.53 tdh) 1723 ft (1723/100=17.23x 3 tdh=51.69 tdh) Savings $97,015 (= 43%) 1028 ft

43 Ease of installation Economical VIL Seismic Mounting

44 Consider six major criteria A. Floor space - Vertical B. Ease of installation - Vertical save > $5,760 C. Maintainability D. Reliability E. Energy costs F. Sustainability cradle to grave

45 Maintainability Split coupled Vertical In-Line Features: Critical item is the mechanical seal Seal can be replaced in 20 minutes to 1 Hour for an 8 pump Rabbet motor fit means no alignment necessary

46 Maintainability: Savings (Edmonton Airport) Particularly important with Design Envelope pumps $8200 annual savings due to faster mechanical seal changes

47 Maintainability: Base mounted Impeller must be removed and reinstalled to change seal Realignment always necessary Seal can be replaced in 8 hours (estimated) in 8 pump An extra 7 hours or $700

48 Maintainability: Split case horizontal Features: 2 seals to maintain and 2 bearings to remove and replace Realignment always Necessary Inboard seal can be replaced in an estimated 6 hours in an 8 pump An extra 5 hours required per seal or $500

49 Maintainability: HSC vertically mounted Features: 2 seals to maintain and 2 bearings to remove and replace Water leakage problems persist with bottom bearing housing Top of casing weighs 225 lbs. in a 8 pump Seal can be replaced in an estimated 16 hours in 8 Pump An extra 15 hours or $1,500 per seal required

50 Maintainability: HSC top suction, top discharge 2 seals to maintain and 2 bearings to remove and replace Realignment always necessary Inboard seal can be replaced in an estimated 6 hours in 8 pump An extra 5 hours required per seal or $500

51 Consider six major criteria A. Floor space - Vertical B. Ease of installation Vertical C. Maintainability - Vertical - $500 - $1500 less D. Reliability E. Energy costs F. Sustainability cradle to grave

52 Reliability The vertical configuration has been proven in thousands of installations for over 50 years Horsepower is available up to 1250 hp and discharge sizes available larger than 20

53 Reliability: Armstrong VIL 1960 / 70 s All major competitors have now copied the Armstrong VIL concept for HVAC pumping 2180 Yonge installation see pumps circa Still relevant for present day Add Sustainability concerns Vertical In-Line (VIL) Pump. Circa: 1970

54 Reliability Vertical Pump runs vibration free End Suction Vertical HSC 10 hp hp in/sec rms unfiltered hsc highest vibration Source - Hydraulic Institute

55 Reliability Pump runs vibration free VIL maximum above pipe, reduces down to casing and then any residual attenuated by piping system Horizontal maximum hard mounted to baseplate Requires inertia base and springs Source - Hydraulic Institute

56 Reliability Pump runs vibration free Rotating motor is above the pump Makes Hydraulic Institute vibration requirement Flat edge coin will stand on end while pump is operating

57 Reliability Atlantic Station, Atlanta 14 (350mm) pumps 450hp (335kW) Engineer: Barrett, Woodyard & Associates, Inc. (BWA) Design/Build Contractor: Mallory & Evans Inc.

58 Reliability University of Miami, Miller School of Medicine 20x20x19 600hp 6P Engineering Firm: Newcomb & Boyd Atlanta Contractor: John J Kirlin Ft. Lauderdale

59 Reliability Centrifugal Pumps Failure Rate Versus Pump Type Shell Limited 150 Vertical In-Line 58% more reliable than Base Mounted Drive Others Drive Bearings Pump Others Pump Closure Pump Bearings Horizontal Vertical

60 Consider six major criteria A. Floor space - Vertical B. Ease of installation - Vertical C. Maintainability - Vertical D. Reliability - Vertical 58% more reliable E. Energy costs F. Sustainability cradle to grave

61 Efficiency End suction pumps uses single suction impellers, HSC uses double suction impeller VIL uses the same impellers Single suction to 10, double suction, double volute12 to 20 Efficiency varies by 0.1 percentage point depending on casing hydraulic turns Efficiency of the pump types are basically the same

62 Energy costs Pipe Length reduction Less pipe = less friction loss resulting in operating cost savings: $6,600 (est. from TDH reduction) Pipe energy loss Savings 37% Length of pipe 2751 ft (2751/100=27.51x 3 tdh=82.53 tdh) 1723 ft (1723/100=17.23x 3 tdh=51.69 tdh) 1028 ft

63 Consider six major criteria A. Floor space - Vertical B. Ease of installation - Vertical C. Maintainability - Vertical D. Reliability - Vertical E. Energy costs - Vertical 37% less pipe loss F. Sustainability cradle to grave

64 Sustainability Product Life cycle: Carbon footprint VIL no house keeping pad No inertia base Required for both end suction and horizontal split case

65 Sustainability Product Life Cycle: Carbon footprint Carbon footprint of concrete For typical 8 HSC pump 2 metric tons is used 160 kgs of CO2 All the concrete then goes into landfill when the building is demolished

66 Consider six major criteria A. Floor space - Vertical B. Ease of installation - Vertical C. Maintainability - Vertical D. Reliability - Vertical E. Energy costs - Vertical F. Sustainability Product Life cycle - Vertical

67 Consider six major criteria A. Floor space B. Ease of installation C. Maintainability D. Reliability E. Energy costs F. Sustainability Vertical Values escalate exponentially with integrated controls

68 Design Envelope Vertical Inline Pumping

69 The three fundamental Design Envelope elements Enabling Technologies Digital Integrated controls On-board intelligence Economical variablespeed inverters Factory configuration Modeling Selection software In-house 3D design Economical control logic

70 The three fundamental Design Envelope elements Design Envelope Capabilities Enabling Technologies Demand-based control All variable load/speed Plug and play BMSready/-independent Sensorless / Sensoring Commissioning by controls, selfregulating / continuous commissioning Automatic data/metering Internal diagnostics (incl. data storage) Increased sweet spot Digital Integrated controls On-board intelligence Economical variablespeed inverters Factory configuration Modeling Selection software In-house 3D design Economical control logic

71 The three fundamental Design Envelope elements Design Envelope Capabilities Design Envelope equipment Enabling Technologies Demand-based control All variable load/speed Plug and play BMSready/-independent Sensorless / Sensoring Commissioning by controls, selfregulating/ continuous commissioning Automatic data/metering Internal diagnostics (incl. data storage) Increased sweet spot Pumps Domestic Water Boosters Integrated Plant Package Modular Boiler System Intelligent Fluid Management Systems Circulators Digital Integrated controls On-board intelligence Economical variablespeed inverters Factory configuration Modeling Selection software In-house 3D design Economical control logic

72 Design Envelope selection method HVAC is a global part-load industry London Heathrow Los Angeles Bahrain 10%-60% of design load 90% of the time Toronto Canada Berlin Germany Worldwide

73 Design Envelope solution Selections save energy and cost Traditional Variable Speed Design Envelope 100 mm pump 80 mm pump η% η % Traditional pump with design point to the left of BEP Design Envelope pump with design point to the right of BEP Design point 72% 68% Average load 68% 74% Design Envelope selection is often smaller and in a typical example saves 7% in pump cost and 9% in energy costs

74 Design Envelope Ease of selection Preferred Envelope Equipment design envelopes

75 Take the Load Off

76 Design Envelope Sensorless Control

77 Sensorless control - Detailed Head Power S2 System Curve 2 S1 System Curve Traditional Sensorless Control P2 1 P1 Original System Curve S2 S1 Flow Operating point is wherever pump pump performance, curve system intersects resistance system and control resistance curves curve converge How do we get from 1 to 2? 1 Satisfied Flow & Head Operating Point (S1 System Curve) S1 Operating Speed pump curve P1 Power at current flow & head 2 Satisfied Flow & Head Operating Point (S2 System Curve) S2 Operating Speed pump curve P2 Power at current flow & head

78 Sensorless control - Detailed Sensorless data Original System Curve Flow (gpm) Head (ft) Power (bhp) Freq. (Hz) S2 System Curve 1 Constant speed S2 System Curve How we get from 1 to 2 2 S1 System Curve S1 Speed is stable at 1 until system control valves (CV) modulate. System has CV modulating closed resulting in a steeper S2 system curve Reverses as CVs open S2

79 Integrated Sensorless control Values and benefits: Operating cost saving opportunities Based on 6 40hp unit Power Energy Savings A Constant speed throttled Incremental Cumulative B Reduced speed unthrottled constant flow % 15% C Reduced constant speed variable flow % 40% D Variable speed variable flow Mech. Room Sensor % 55% E Integrated Control Sensorless % 77% Exceeds ASHRAE 90.1 requirements

80 Integrated Pump Systems Design Envelope Pumps For Every Application ARMSTRONG Integrated Pump System controller IPS4000 Integrated Plant Control IPC9511 IPC9521

81 Integrated Pump Systems Some Key Definitions Primary Only Systems (CPF & VPF) Primary Secondary Systems (CPVS, VPVS)

82 Integrated Pump Systems Objectives Occupant Comfort 2 way or 3 way valves Pumps provide a head pressure for valve authority on flow control Energy Savings During part load operation Reduce pump energy with variable flow and pump speed Improve system delta T for performance of other equipment

83 Integrated Pump Systems Converting 3-Way Valve Constant Flow Systems An Easier Implementation IPS4000 pump control can adjust based on return temperature zones to regulate pump speed. Pumps can be made variable flow based on return temperature signal Flow and system dp received from Design Envelope pumps NOC received from BMS

84 Integrated Pump Systems Converting 3-Way Valve Constant Flow Systems CHW reset Implementation IPS4000 pump control can adjust based on temperature difference of zones to regulate pump speed control. Flow and system dp received from Design Envelope pumps NOC received from BMS

85 Integrated Pump Systems IPS way Valve Conversion Economics Design Day Load 450 ton design day % ann avg load 45 % % delta T maintained 80% % INR / kw-hr 7 INR system head 80 ft design delta T 6.67 deg C design flow 900 usgpm Annual hours 7000 HR/YEAR # duty chillers 3 # of duty pumps 3

86 Integrated Pump Systems IPS way Valve Conversion Economics Pump Power Draw (kw) at % Load Operating point

87 Integrated Pump Systems IPS way Valve Conversion Economics Annual Energy Consumed (kw-hr) at % Load Operating point Pump speeds are lower Valve position are giving better authority and less resistance Pumps operate at a more efficient point on their curves

88 Integrated Pump Systems IPS way Valve Conversion Economics Pump Energy Analysis base case IPS4000 Savings Savings 3-way valve Temp Control Percent CS pump VS pump kw-hrs % INR INR 674,131 INR 326,257 INR 347,874 Chiller Savings at 0.9 kw/ton base case IPS4000 Savings Savings 3-way valve Temp Control CS pump VS pump kw-hrs % INR INR 172,559 INR 83,513 INR 89,046 TOTAL PLANT SAVINGS base case IPS4000 Savings Savings 3-way valve Temp Control CS pump VS pump kw-hrs % INR INR 846,690 INR 409,770 INR 436,921 Retrofit Project INR 800,000 Payback Period on 450 ton plant <24 months

89 Integrated Pump Systems Two Way Variable Flow with dp Zone Sensors Differential Pressure (dp) sensors placed at greater than 2/3 rd, or at end of distribution After balancing of the system, dp zone setpoint(s) set for design day load What if the contractor installs at the mechanical room pump discharge dp dp

90 Parallel Pump Staging Best Efficiency Staging versus Speed Based Staging 1P EFFY 2P EFFY 3P EFFY 100% 80% HEAD ARMSTRONG BEST EFFICIENCY STAGING EFFICIENCY 60% 40% 20% 0% POWER FLOW 1P EFFY 2P EFFY 3P EFFY 100% 80% HEAD EFFICIENCY 60% 40% POWER SPEED BASED STAGING FLOW 20% 0%

91 Parallel Pump Staging Energy Performance Implications of Speed Based Staging 1P EFFY 2P EFFY 3P EFFY = Areas of highest inefficiency Energy Savings: 3 x 30kW Pumps Operating Cost* Speed Based Staging ~ $30,371 SPEED BASED STAGING Best Efficiency Staging ~ $20,092 34% Saving *Based on $0.10/kWh 12 months operation 40% design head min pressure

92 Armstrong Design Envelope Parallel Sensorless Pump Control* (PSPC) For customers requiring parallel pump control [Up to 4 motors] No control panel or building automation control fees required Parallel Sensorless Pump Controller integrated on one unit only. (Interchangeable) dualarm units (Illustrated) are wired at factory. Single pumps will be daisy-chain wired on site * Patent Pending

93 Integrated Pump Systems Two Way Variable Flow with dp Zone Sensors What if the contractor installs at the mechanical room pump discharge IPS4000 controller can apply a quadratic control curve to emulate the remote sensor, and get the extra energy savings at part load operation to comply with 90.1 dp

94 Head (ft) Integrated Pump Systems Two Way Variable Flow with dp Zone Sensors IPS4000 controller quadratic control curve, exceeding 90.1 dp setpoint at exit of mechanical room IPS4000 Quadratic Control Curve with MR Sensor Flow (000s) gpm

95 Integrated Pump Systems IPS4000

96 Integrated Pump Systems Sensorless Speed Control with IPS4000 Simple on screen setup to adjust as built design flow and head parameters Parallel Sensorless Pump Control staging points automatically recalculated for the as built entered condition (no modifications at the pump)

97 Floor Space Qty x10x19 c/w 125 hp integrated controls ft head Qty x14x15-60 hp ft Qty x14x hp Foot print Vertical inline = 830 sq ft HSC = 2600 sq ft

98 Ease of Installation No base 148 metric tons of concrete No flex connector No support under the

99 Energy Costs and Sustainability Integrated approach for pump balancing Controller used for soft start vs across the line on 600 hp

100 Enwave Case Study Summary A. Floor space - Vertical 68% less B. Ease of installation - Vertical save > $150,000 C. Maintainability - Vertical $5,200/year less D. Reliability - Vertical more reliable E. Energy costs - Vertical less pipe loss F. Sustainability Product Life Cycle - Vertical 26,640 lbs of CO2 less

101 Achieving Through Integrated Plant Control

102 Agenda 1. Overview of Standard Long term objectives 3. A Net Zero road map for chilled water plant solutions 4. Demand based Integrated Plant Controls and 189.1

103 Standard What is it About? Standard for the design of high performance green buildings A compliance option of the international green construction code Minimum for high-performance, green buildings Applies as per ASHRAE/IES Standard 90.1 Optional compliance path to the International Green Construction Code Not a design guide or a rating system

104 189.1 Standard for High-Performance Green Buildings Purpose Environmental Responsibility Occupant Comfort Balance Resource Efficiency Community Sensitivity Today While meeting the needs Of the present, without Compromising the ability Of future generations Tomorrow

105 189.1 Application Is Voluntary Can be adopted as law Draws from ASHRAE 62.1 and 90.1 Applies to the building design, construction and life prescriptive or performance based

106 189.1 Standard Topic Areas Sustainable Sites Water Use Efficiency Energy Efficiency Indoor Environmental Quality Building s Impact on the Atmosphere, Materials & Resources Construction and Operations Plans

107 189.1 Relative to Existing Standards Original Standard goal 30% lower than Standard INCLUDING PROCESS Standard goal 5-15% lower than Standard Appendix G from Standard 90.1 is incorporated as a Normative Appendix

108 189.1 Where Integrated Plant Control Contributes Sustainable Sites Water Use Efficiency Energy Efficiency Indoor Environmental Quality Building s Impact on the Atmosphere, Materials & Resources Construction and Operations Plans

109 More Aggressive Net Zero Agenda Energy Reduction Proposal Standard 90.1 Energy Density High Performance

110 189.1 Not All Buildings can reach net Zero ZEB Floorspace % By Segment Percent Of Floorspace able to meet Net Zero Warehouse Religious Worship Retail (non mall) Education Service Public Assembly Average Health Care (outpatient) Office High Percentages Low Percentages Lodging Food Sales Laboratory

111 Achieving Through Integrated Plant Control Where we can go with HVAC chilled water systems and how that compares to our net zero building goals Energy use Energy consumption Renewable energy source sufficient to meet building energy demand Renewable energy Time

112 Net Zero CHW Solution Roadmap Starting Point Variable secondary flow plants (30% today, and 90% installed base) HVAC system Chiller plant Variable flow design Efficiency kw/ton

113 Net Zero CHW Solution Roadmap Variable Primary Chiller Plants with Variable Speed Chillers HVAC system Chiller plant Variable flow design Variable primary Efficiency kw/ton

114 Net Zero CHW Solution Roadmap Demand Based All-Variable Chiller Plants HVAC system Chiller plant Variable flow design Efficiency kw/ton Variable primary Demand Based Allvariable Control (IPC)

115 Net Zero CHW Solution Roadmap Intelligent Devices HVAC system Chiller plant Variable flow design Efficiency kw/ton Variable primary Demand based all variable Intelligent devices

116 Net Zero CHW Solution Roadmap Ground Source Solutions HVAC system Chiller plant Variable flow design Efficiency kw/ton Variable primary Demand based all variable Intelligent devices Ground sourced

117 Net Zero CHW Solution Roadmap Chilled Beams HVAC system Chiller plant Variable flow design Efficiency kw/ton Variable primary Demand based all variable Intelligent devices Ground sourced Chilled beams

118 Net Zero CHW Solution Roadmap Low Loss Distribution HVAC system Chiller plant Variable flow design Variable primary Efficiency kw/ton Demand based all variable Intelligent devices Ground sourced Chilled beams Low loss distribution

119 Net Zero CHW Solution Roadmap Demand based all-variable chiller plant automation HVAC system Chiller plant Variable flow design Energy Efficiency Variable primary Efficiency kw/ton Demand based all variable Intelligent devices Ground sourced Chilled beams Low loss distribution Renewables 0.0

120 Net Zero CHW Solution Roadmap Demand based all-variable chiller plant automation HVAC system Chiller plant Variable flow design Energy Efficiency Variable primary Efficiency kw/ton Demand based all variable plant automation Intelligent devices Ground sourced Chilled beams 25-50% Low loss distribution Renewables 0.0

121 Design Envelope Integrated Plant Control The Benefits of Optimization Plant Annual energy Savings of 30-60% kw-hr H2O Life ROI Annual Water Savings on the Cooling Tower of 4-7% Longer Plant Equipment Life, 30-60% 4-7% 20-30% 5-20% 20-30% Protect your ROI with ECO*PULSE On-board Diagnostic Service $ $ $ $ saving 5-20% annual energy costs

122 Armstrong s Chiller Plant Optimization New Variable Speed Chiller Plants Plant efficien cy Modera te Humid Arid Existing practice (CPVS) Analog era Feedback loop (PID) Silo sub-system control VS chillers, variable secondary CW reset 0.76 kw/ton Existing best in class Analog era Feedback loop (PID) Silo sub-system control Variable primary flow (VPF) with CHW & CW reset 0.72 kw/ton Design Envelope integrated demand based Digital era Demand based relational Integrated plant solution All-variable chiller plant 0.50 kw/ton (COP 4.7) 0.78 >.76 kw/ton kw/ton (COP 0.72 kw/ton 4.6) (COP 4.9) (COP 4.9) 0.75 >.72 kw/ton (COP 0.68 kw/ton 4.7) (COP 5.2) (COP 7.1) 0.56 <.50 kw/ton (COP 0.48 kw/ton 6.3) (COP 7.4)

123 Comfort Cooling Is A Part Load Application More Than 90% of Time Spent at Part load

124 Design Envelope Equipment Operation In A Part Load Application Design Envelope Solutions are designed for BEST EFFICIENCY operation here Traditional Designs were optimized for operation at full load

125 Variable Speed Devices Are More Efficient At Part Load By Design New Performance Curves: Variable flow cooling towers Variable speed pumps Variable speed air handlers Variable flow chillers Different Performance Curves Different Method Of Control

126 Traditional chiller plant control process set-point based BMS Automation Sequence Parallel equipment staging (up/down) Equipment speed control Silo sub-system control Traditional Logic Capacity based sequencing PID feedback control loops Ambient reset

127 Armstrong Design Envelope Integrated Plant Control View Equipment As Performance Maps: Tons of cooling (kwc), and Electrical Power Performance Curve Based IPC Heat Transfer and Power Consumed demand with power relationships

128 Two different system philosophies Component based System based BMS IPC

129 Building Cooling Demand (tons kwc), for Power In with target delta T

130 Natural curve sequencing vs traditional capacity based Natural Curve Sequencing IPC Capacity Based Overall System COP % 10% 20% 30% 40% 50% 60% 70% 80% 90% 100% % Chiller Load VS ECWT 13 C VS ECWT 18 C VS ECWT 24 C VS ECWT 29 C 55F 65F 75F 85F

131 Natural curve sequencing vs traditional capacity based 100 % 80% 60% 40% Chiller 1 (lead) - 40% Chiller 2 (lag 1) - 40% Chiller 3 (lag 2) 40% 20% 0% Chiller 1 Chiller 2 Chiller 3

132 Natural curve tower sequencing approach temperature effects ETW Approach Temperatures (deg F) at Identical Fan and Pump Power Natural Curve Sequence Of Towers Capacity Sequence Natural Curve 33% at 56F, 13C 66% at 65F, 18C 100% at 77F, 25C Lower the leaving tower water temperature with: - Natural curve sequencing, - Variable flow towers, and - the same or less power % 66% 100% deg C

133 Speed control Demand based power relationships (not set-point PID feedback loops) IPC

134 Design Envelope Integrated Plant Control Patented Control Technology Automation element Traditional Demand based Parallel equipment staging (up/down) Capacity based sequencing Natural curve sequencing Equipment speed control Silo sub-system control PID feedback control loops Ambient reset Equal marginal performance principle Demand based control

135 Armstrong solutions: two configurations Integrated Plant Control For New Projects Optimization Modules For Retrofit Projects

136 Design Envelope Integrated Plant Control System Full plant automation Remote Access BMS Read/Write alarms Equipment Data User Friendly Interface 10 Year Data Capacity Factory Built & Tested

137 Design Envelope Integrated Plant Control System Sequences for: All variable flow (VPF & VPVS) Water Side Economizers Thermal Energy Storage Ground Source (Geothermal) Dry Air Coolers (Evaporative mist) Compressor Sequencing (large 11 kv dual compressor CS) Demand Limiting for Demand Response Emergency Power Transfer Switch

138 Integrated Plant Controller IPC11550HMI 0.55 kw/ton At a glance display Intuitive touch-screen interface System performance (operating status, setpoints, hardware data, etc.) Integrated I&O Files Trending Data logs Alarm history Setup and troubleshooting Remote monitoring

139 Retrofit Impact: Payback Periods as Short as 6 months 25 30% SAVINGS Installed on Variable Primary Systems, upgrad ing to All-variable OPTI-VISOR

140 Health Management Service Real time diagnostics of plant equipment and operating status Assess equipment based on trended performance ratios Able to alert to issues before they become a problem or alarm (low refrigerant, clogged strainers, failing motors, vibration, incorrect service calls) Provides assessment of predicted, base case and actual performance Viewable web site, device views, and quarterly reports IPC System OPTI-VISOR TM

141 Health Management Service Staff monitoring of trends, alerts, and assessments Phone notification of issues and recommended site investigation Assessment of energy impact through non-response Real time: assessment for actual conditions (WBT, load, and combination of operating equipment) Water cooled New Projects Water cooled Retrofit Projects Air cooled New Projects Air cooled Retrofit Projects

142 DESIGN ENVELOPE Integrated Plant Control Part of the Net Zero CHW Solution Roadmap HVAC system Chiller plant Efficiency kw/ton Variable flow design Energy Efficiency Variable primary Design Envelope Integrated Plant Control Demand based all variable plant automation Intelligent devices Ground sourced Chilled beams Renewables 25-50% Low loss distribution 0.0

143 Design Envelope Integrated Plant Control HELPING YOU ACHIEVE TODAY ENABLING YOUR CUSTOMERS TO TAKE THEIR SITE TO IN THE FUTURE, OR ACHIEVE LEED RATINGS TODAY BRINGING BENEFITS AT NO EXTRA COST

144 Design Envelope IPC New Construction Sidra Village, Doha, Qatar IPC Delivers: On an annual basis 25% energy cost savings Confirmed by an Independent utility ** 7250 TR, York Chillers

145 Design Envelope OPTI-VISOR Retrofit Dalma Mall, Abu Dhabi, UAE Integrated plant controls deliver: On an annual basis 28% energy cost savings **10,000TR York Chillers

146 Design Envelope IPC New Construction Mixed Use Building, Dubai, UAE IPC Delivers: On an annual basis 23% energy cost savings ** 1150 TR, Clivet Chillers

147 Design Envelope OPTI-VISOR Retrofit Jumeirah Group, Dubai, UAE Delivers: On an annual basis 21% energy cost savings ** 3000 TR, York, Trane & Carrier Chillers

148 Design Envelope IPC New Construction Markhiya Mall, Doha, Qatar IPC Delivers: On an annual basis 27% energy cost savings ** 6250 TR, Carrier Chillers

149 Design Envelope IPC New Construction Convention Centre, Muscat, Oman VPVS with Variable Condenser Flow 10,000 TR Phase 1 Expansion to 25,000 TR LEED Gold Certification Energy & Water Conservation IPC Delivers: On an annual basis 29% energy cost savings ** TR, Carrier Chillers

150 Armstrong Fluid Technology Thank You For Your Attention Questions?

2

2 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 24 This presentation will explain how the new Armstrong Design Envelope pump range delivers benefits to all stakeholders in a building through its

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Ben Erpelding and Annika Moman, San Diego Regional Energy Office ABSTRACT According the U.S. Department

More information

Central Chiller Plants

Central Chiller Plants Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland

More information

Large University Central Chiller Plant Design Considerations

Large University Central Chiller Plant Design Considerations Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful

More information

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering 2016 District Cooling Presented by George Berbari CEO of DC PRO Engineering District Cooling Brief History & Future Central Chilled Water plants existed in the Middle East as early as the 1960 s. Few examples

More information

Condenser Water Heat Recovery"

Condenser Water Heat Recovery PLEASE MUTE CELL PHONES Condenser Water Heat Recovery" Julian de Bullet ASHRAE Distinguished Lecturer Director of Industry Relations McQuay International 703-395-5054 1 What Is Sustainability? sustainable

More information

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013

Pressure Independent Valve Systems. ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013 Pressure Independent Valve Systems ASHRAE Seminar College of the North Atlantic, Doha, Qatar 20 th April 2013 1 Agenda Introduction Pressure independent Valves - mechanical PICCV Pressure independent Valves

More information

Chilled Water System Optimization

Chilled Water System Optimization Advanced HVAC Diagnostics and Control Strategies Chilled Water System Optimization Brian Leduc Carrier Corporation August 16, 2017 Contents of this presentation 2017 Carrier Corporation Tampa Convention

More information

Series Sump and Sewage Systems

Series Sump and Sewage Systems Series 000 Sump and Sewage Systems file no: 0. date: may 17, 13 supersedes: 0. date: march 29, 13 Series 000 Sump Series 0 & 2 Armstrong offers a complete range of high performance, easily maintained Column

More information

SECTION COOLING TOWER

SECTION COOLING TOWER PART 1 GENERAL 1.1 SECTION INCLUDES A. Mechanical induced draft Cooling Tower B. Controls C. Ladder and handrails 1.2 REFERENCES SECTION 23 65 00 COOLING TOWER A. ANSI/AFBMA 9 - Load Rating and Fatigue

More information

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader Building Controls Strategies Conference Retro-Commissioning with BAS Overview 10 March 2015 Steve Brown, CAP ESD Controls Team Leader Kevin Caho PE, LEED AP ESD Energy Engineer Agenda BAS Overview RCx

More information

Flygt N-Pumps 3085, 3102 & For reliable and efficient wastewater handling

Flygt N-Pumps 3085, 3102 & For reliable and efficient wastewater handling Flygt N-Pumps 3085, 3102 & 3127 For reliable and efficient wastewater handling The Concept Flygt N-Pump series Reduced pumping efficiency, high energy and maintenance costs shouldn t be a fact of life

More information

FlowSet. Balancing Procedure

FlowSet. Balancing Procedure FlowSet Balancing Procedure Select the flow tolerance required As per the attached chart (ASHRAE Systems Guide, 1984), ± 10% is generally accepted as a reasonably cost effective flow tolerance, but special

More information

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of

More information

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40

NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40 NEW FEATURES IN THE CARRIER HOURLY ANALYSIS PROGRAM v4.40 By: Carrier Software Systems Carrier Corporation Syracuse, New York rev August 11, 2008 Copyright 2008 Carrier Corporation, All Rights Reserved

More information

WHITE PAPER. Chiller Plant Optimization - A Practitioner s Perspective. Abstract

WHITE PAPER. Chiller Plant Optimization - A Practitioner s Perspective. Abstract WHITE PAPER Chiller Plant Optimization - A Practitioner s Perspective Sridhar Chidambaram Advanced Engineering Group, Engineering Services, Infosys Limited Bangalore, India Abstract Maintaining optimal

More information

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF) Roy Hubbard Agenda Understanding the three basic piping systems Design and Off-design operation Advantages and Disadvantages Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Chiller Optimiser Technical Specification

Chiller Optimiser Technical Specification Chiller Optimiser Technical Specification 1. System Description The Chiller Optimiser Millennium Series is a self contained solid state dedicated microprocessor system. It has been specifically designed

More information

CHILLED WATER SYSTEM OPTIMIZER

CHILLED WATER SYSTEM OPTIMIZER CHILLED WATER SYSTEM OPTIMIZER A White Paper by Steve Tom, P.E., Phd. Carrier Corporation Farmington, Connecticut July, 2017 INTRODUCTION When it comes to measuring HVAC energy use in buildings, it s

More information

Persistence Tracking in a Retro-commissioning Program

Persistence Tracking in a Retro-commissioning Program Persistence Tracking in a Retro-commissioning Program Mike Eardley Architectural Energy Corporation Synopsis The persistence of energy savings and electrical demand reductions created by retrocommissioning

More information

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m. Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial

More information

Daikin LXE10E Reefer Machine

Daikin LXE10E Reefer Machine Daikin LXE10E Reefer Machine Carry your temperature-controlled container cargo confident in the knowledge it is receiving the ultimate care and attention from a Daikin machine. Quality Performance Reliability

More information

Surface pumping SyStemS

Surface pumping SyStemS wood group SPS surface pumping systems bringing our downhole pump experience to the surface Surface pumping SyStemS surface pumping systems corporate structure wood group is a leading international energy

More information

Caribbean Hotel Energy Efficiency Action (CHENACT)

Caribbean Hotel Energy Efficiency Action (CHENACT) Caribbean Hotel Energy Efficiency Action (CHENACT) Energy Efficiency Opportunities for Caribbean Hotels 31 st March 2010 Presented by: Andre Escalante Agenda Air Conditioning Energy Efficient Lighting

More information

Chilled Water Plant Redesign

Chilled Water Plant Redesign 17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

AR No. # Efficient Irrigation

AR No. # Efficient Irrigation AR No. # Efficient Irrigation Recommendation Optimize the facilities irrigation pumping system by ensuring pumps are operating at their Best Efficiency Point (BEP). We estimate the system pumping efficiency

More information

Booster Pump Fundamentals. By: Bill Baglot

Booster Pump Fundamentals. By: Bill Baglot Booster Pump Fundamentals By: Bill Baglot March 22, 2010 1 Booster Pumps Presentation Topics What are Booster Pumps and when do we need them Accurately sizing boosters and drawdown tanks Maximizing Energy

More information

Modal Analysis as a Tool to Resolve Pump Vibration Issues

Modal Analysis as a Tool to Resolve Pump Vibration Issues Modal Analysis as a Tool to Resolve Pump Vibration Issues John Koch HDR, Bellevue, WA jkoch@hdrinc.com ABSTRACT Vibration spectrum analysis and modal analysis are tools designers and plant staff can use

More information

Improved efficiency and lifetime reliability with new hydraulic energy recovery design for CO2 removal in ammonia plants

Improved efficiency and lifetime reliability with new hydraulic energy recovery design for CO2 removal in ammonia plants Improved efficiency and lifetime reliability with new hydraulic energy recovery design for CO2 removal in ammonia plants PREM KRISH, JEREMY MARTIN, JOHN SIENKIEWICZ, ANDREA GAINS-GERMAIN Energy Recovery

More information

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors

An Integrated Solution for Commercial AC Chillers Using Variable Speed Scroll Compressors Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2016 An Integrated Solution for Commercial AC Chillers Using Variable Speed

More information

WATER CHILLER / HEAT PUMP. The high performance packaged solutions for all your needs

WATER CHILLER / HEAT PUMP. The high performance packaged solutions for all your needs WATER CHILLER / HEAT PUMP Aquaciat / Aquaciat Power The high performance packaged solutions for all your needs The Aquaciat Range: the versatile way to sustainable comfort Available in air-cooled chiller

More information

CHILLED WATER DISTRIBUTION SYSTEM

CHILLED WATER DISTRIBUTION SYSTEM Campus-Wide System: A campus-wide central chilled water system has been developed in recent years and is being expanded to serve additional cooling loads as need arises and opportunity affords. This system

More information

Centrifugal Air Compressors. Centac C m 3 /min

Centrifugal Air Compressors. Centac C m 3 /min Centrifugal Air Compressors Centac C1000 135-220 m 3 /min More Than Air, Peace of Mi Ingersoll Rand is now well into our second century of providing industries throughout the world with innovative solutions

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

e-hmseries STAINLESS STEEL HORIZONTAL MULTI-STAGE PUMPS BROeHM R2

e-hmseries STAINLESS STEEL HORIZONTAL MULTI-STAGE PUMPS BROeHM R2 e-hmseries STAINLESS STEEL HORIZONTAL MULTI-STAGE PUMPS BROeHM R2 Let s solve your water needs. e-hm is customizable to your applications e-hm bare pump e-hm residential boosters Variable speed systems

More information

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series

TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Absorption Chillers TGG, TBG, TEG, TUG, 3.9 TBS, Gene-Link series Stable Chilled Water Outlet Temperature PID control is applied to maintain constant chilled water outlet temperature. When the cooling

More information

Innotech is a registered Trademark of Mass Electronics Pty Ltd Copyright 2013 Mass Electronics Pty Ltd

Innotech is a registered Trademark of Mass Electronics Pty Ltd Copyright 2013 Mass Electronics Pty Ltd CHILLED WATER PRIMARY SECONDARY & THERMAL ENERGY STORAGE DIGITAL CONTROL SYSTEM FUNDAMENTALS Presented by : Ben Macdonald QLD Sales Manager Innotech Control Systems Australia www.innotech.com.au Innotech

More information

6. PUMPS AND PUMPING SYSTEM

6. PUMPS AND PUMPING SYSTEM 6. PUMPS AND PUMPING SYSTEM Syllabus Pumps and Pumping System: Types, Performance evaluation, Efficient system operation, Flow control strategies and energy conservation opportunities 6.1 Pump Types Pumps

More information

CT425 Optimize Your Process to Make Profits

CT425 Optimize Your Process to Make Profits - 5058-CO900H 1 CT425 Optimize Your Process to Make Profits Rockwell s Model Predictive Control Technology Aaron Dodgson Pavilion Business Development Western Region aadodgson@ra.rockwell.com PUBLIC 2

More information

Italcementi Center for Research and Innovation

Italcementi Center for Research and Innovation Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located

More information

Planning for Biomed Facility Puts Energy Efficiency Under Microscope

Planning for Biomed Facility Puts Energy Efficiency Under Microscope Planning for Biomed Facility Puts Energy Efficiency Under Microscope Chilled beams, runaround-loop ERV system included May 19, 2014 By DAN VASTYAN, Common Ground, Manheim, Pa. HPAC Engineering Constructing

More information

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012

Cogeneration. Thermal Chillers. and. .. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012 Cogeneration and Thermal Chillers.. ASHRAE National Capital Chapter. Arlington, VA 10/10/2012 Agenda Cogeneration Interest and Application Basics Equipment Matching Thermal Chiller Overview Steam Components

More information

New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems

New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems New Approaches in Automating and Optimizing Demand Response to Solve Peak Load Management Problems WHITE PAPER Abstract Grid power demand peaks and increasing supply/ demand inbalances create management

More information

Eco-Flow - C VARIABLE FREQUENCY DRIVE PRODUCT BROCHURE. for Commercial Swimming Pools & Water Feature Pumps. H flow 2. Pool & Spa Products Division

Eco-Flow - C VARIABLE FREQUENCY DRIVE PRODUCT BROCHURE. for Commercial Swimming Pools & Water Feature Pumps. H flow 2. Pool & Spa Products Division H flow 2 Pool & Spa Products Division Eco-Flow - C VARIABLE FREQUENCY DRIVE for Commercial Swimming Pools & Water Feature Pumps PRODUCT BROCHURE Tel: 888 635 0296 www.h2flow.net We don t make Pool Pumps,

More information

The H-25/H-15 Gas Turbine A Product of Hitachi Quality

The H-25/H-15 Gas Turbine A Product of Hitachi Quality DMLieferant www.dmliefer.ru The H-25/H-15 Gas Turbine A Product of Hitachi Quality The H-25 s fuel savings will repay your investment within a few years while allowing you a range of fuels from distillate

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

Chilled Water Distribution Systems. APPA Institute for Facilities Management New Orleans, LA January 19, 2016

Chilled Water Distribution Systems. APPA Institute for Facilities Management New Orleans, LA January 19, 2016 Chilled Water Distribution Systems APPA Institute for Facilities Management New Orleans, LA January 19, 2016 1 Purpose of Today s Presentation To provide a broad understanding of chilled water distribution

More information

Nilan VPL Active heat recovery and cooling (air/air)

Nilan VPL Active heat recovery and cooling (air/air) M a r k e t l e a d i n g c o m m e r c i a l a n d d o m e s t i c v e n t i l at i o n w i t h h e at r e c o v e r y Nilan 31-125 Active heat recovery and cooling (air/air) Nilan 31-125 Commercial ventilation

More information

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Summary Major Fortune 500 Telecom Company Estimated 40% the corporate building portfolio still use pneumatic thermostats

More information

GRUNDFOS INDUSTRIAL SOLUTIONS. Grundfos CM CM/CME COMPACT PUMPS FOR DEMANDING APPLICATIONS

GRUNDFOS INDUSTRIAL SOLUTIONS. Grundfos CM CM/CME COMPACT PUMPS FOR DEMANDING APPLICATIONS CM/CME COMPACT PUMPS FOR DEMANDING APPLICATIONS GRUNDFOS INDUSTRIAL SOLUTIONS Grundfos CM COMPACT, FLEXIBLE, RELIABLE SOLUTIONS FOR TIGHT SPACES CM stainless steel Grundfos Centrifugal Modular (CM) pumps

More information

Modular Chiller Plants A GLOBAL LEADER IN ENERGY SOLUTIONS

Modular Chiller Plants A GLOBAL LEADER IN ENERGY SOLUTIONS Modular Chiller Plants A GLOBAL LEADER IN ENERGY SOLUTIONS A B O U T S tellar Energy is a global leader in the design, construction, fabrication, installation, and servicing of a range of energy systems,

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Fiberglass Cooling Towers

Fiberglass Cooling Towers Fiberglass Cooling Towers Available in sizes from 100 to 240 tons. FC Series 700 Fiberglass Cooling Tower Available in sizes from 170 to 240 tons. No other fiberglass cooling tower comes with as many high-quality

More information

High Efficiency Liquid-Solid Separators

High Efficiency Liquid-Solid Separators High Efficiency Liquid-Solid Separators Continuous Filtration with Zero Maintenance ehtx Features and Benefits: Filter performance rated to remove 98% of all solids 44 micron (325 mesh), 2.6 specific gravity,

More information

SECTION ROTARY SCREW WATER CHILLERS

SECTION ROTARY SCREW WATER CHILLERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Energy Reduction Strategy Through 2020

Energy Reduction Strategy Through 2020 Through 2020 Revised: August 2017 Executive Summary Auburn University is a land, sea and space grant university established in 1856. The university consists of 11,629,000 square feet on 1,840 acres and

More information

Global Warming and Geothermal Heat Pumps

Global Warming and Geothermal Heat Pumps Global Warming and Geothermal Heat Pumps John D. Manning, PE LEED TM Accredited Professional Earth Sensitive Solutions, LLC 9th Annual NYS Green Building Conference Friday, March 25 th, 2011 The U.S. Green

More information

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering

LEED Commissioning and Actual Energy Use. John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering LEED Commissioning and Actual Energy Use John Kokko, P.Eng. LEED A.P. Vice President Enermodal Engineering AIA Quality Assurance Learning Objectives 1. Why Best Practice and Fundamental Commissioning are

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps...

PUMPS FOR INDUSTRY. The Vertical Pump Specialists CONTENTS: Introduction & User List. Product Overview. Vertical Process Pumps... PUMPS FOR INDUSTRY CONTENTS: The Vertical Pump Specialists Introduction & User List Product Overview Vertical Process Pumps... Series 600 Vertical Sewage Pumps... Series 700 Vertical Sump Pumps... Vertical

More information

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study North Orange County Community College District Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study Fullerton College Final September 8, 2017 Table of

More information

Permanent Load Shifting Program

Permanent Load Shifting Program 1. Program Description Permanent Load Shifting (PLS) can help reduce system peak load by storing energy produced during off-peak period and shifting electricity use from on-peak to off-peak periods on

More information

Flooded Type Water-Cooled Chillers. R134a

Flooded Type Water-Cooled Chillers. R134a Flooded Type WaterCooled Chillers The HighEfficiency WaterCooled Flooded Chillers The New WaterCooled Flooded chiller with improved efficiency and functionality by incorporating several advanced technology

More information

Engineered Hot Water Systems. For your specific requirements

Engineered Hot Water Systems. For your specific requirements Engineered Hot Water Systems For your specific requirements Experience is Central to Every Solution Armstrong is a global leader in providing integrated, intelligent hot water generation and water temperature

More information

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis Lee Willmon, Head of Health, Safety and Environment Vaccines and Diagnostics Holly Springs, NC 16 Sept 10 Agenda Holly

More information

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers.

C. ASSE 1013 Performance Requirements for Reduced Pressure Principle Backflow Preventers. PART 1: GENERAL 1.01 Purpose: A. This standard is intended to provide useful information to the Professional Service Provider (PSP) to establish a basis of design. The responsibility of the engineer is

More information

Condenser Water System Retrofit Opportunities. Figure 1. Condenser water system schematic. isolation valve. cooling tower

Condenser Water System Retrofit Opportunities. Figure 1. Condenser water system schematic. isolation valve. cooling tower providing insights for today s hvac system designer Engineers Newsletter volume 45 1 Condenser Water System Retrofit Opportunities Although there are many publications dedicated to the topic of retrofitting

More information

Commercialization of Energy Harvesting Wireless Technology. March 2013 Troy Davis

Commercialization of Energy Harvesting Wireless Technology. March 2013 Troy Davis Commercialization of Energy Harvesting Wireless Technology March 2013 Troy Davis EnOcean - No Limits Agenda Overview of the Energy Harvesting Solutions Examples of Energy Harvester modules Energy Harvesting

More information

CO2 in Vending Machine

CO2 in Vending Machine CO2 in Vending Machine CO2 SANYO Electric Co., Ltd. Commercial Solutions Company Daiki Shiomi Outline Contents 1. Company Profile 2. CO2 Compressor / Refrigeration System 3. CO2 System Performance 4. VM

More information

Altivar AC Drives. Advanced energy management and performance in motor control. altivardrives.com

Altivar AC Drives. Advanced energy management and performance in motor control. altivardrives.com Altivar AC Drives Advanced energy management and performance in motor control altivardrives.com 988-19614608_US_A.indd 1 2 altivardrives.com Schneider Electric Segment focused. Customer centric. Schneider

More information

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer

NEWMOA June 30, Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer NEWMOA June 30, 2009 Fran Boucher LEED AP, Certified Energy Manager Senior Energy Engineer Utility Incentives MA, RI, NH, VT, ME, CT, Long Island NY, Gas in NYC New construction and gas in Upstate NY.

More information

The Charles Machine Works Perry, OK

The Charles Machine Works Perry, OK said. Beginning with our early days as leaders in the supply of modular chillers to the U.S. market, ClimaCool has built on this legacy to become a premier manufacturer of ultimate comfort solutions like

More information

Pump selection: a real example

Pump selection: a real example 28 Feature WORLD PUMPS March 2010 Centrifugal pumps Pump selection: a real example Choosing the most appropriate and cost-effective centrifugal pump for a given duty requires strict adherence to a thorough

More information

Cutting-Edge Pumping Solutions for the Concentrated Solar Power Generation

Cutting-Edge Pumping Solutions for the Concentrated Solar Power Generation Cutting-Edge Pumping Solutions for the Concentrated Solar Power Generation The Sulzer Advantage Taking on new challenges Around the world, the power industry is taking on the challenge to produce clean,

More information

Transform your HVAC performance. Good for your comfort, for the environment and for your bottom line

Transform your HVAC performance. Good for your comfort, for the environment and for your bottom line Transform your HVAC performance Good for your comfort, for the environment and for your bottom line TRANSFORMING YOUR HVAC SYSTEM IMPULS-e is a portfolio of solutions from Trane which uses advanced technology

More information

Mission Critical Commissioning for Healthcare Facilities

Mission Critical Commissioning for Healthcare Facilities Mission Critical Commissioning for Healthcare Facilities Steven R. Rusty Ross SSRCx, LLC Synopsis Healthcare Facilities serve a critical and unique mission. Few facilities delivered by the construction

More information

Knowledge is Power. Belimo Energy Valve

Knowledge is Power. Belimo Energy Valve Knowledge is Power Belimo Energy Valve 1 Product Presentation Agenda The Evolution of BELIMO Control Valves Coil Performance Influences BELIMO Energy Valve Overview BELIMO Energy Valve Tools BELIMO Energy

More information

In-line Twin Pump. Type Series Booklet. Omega DSL

In-line Twin Pump. Type Series Booklet. Omega DSL In-line Twin Pump Type Series Booklet Legal information/copyright Type Series Booklet All rights reserved. The contents provided herein must neither be distributed, copied, reproduced, edited or processed

More information

SUGGESTED SPECIFICATIONS Pump Frames through 64132

SUGGESTED SPECIFICATIONS Pump Frames through 64132 TYPE HBB - HORIZONTAL SOLIDS-HANDLING WASTEWATER PUMPS Pump Frames 44081 through 64132 GENERAL Furnish and install Horizontal Flexible Coupled Dry Pit Pumping Units complete with all accessories and appurtenances

More information

Thermal Storage Vessel Sizing

Thermal Storage Vessel Sizing This is a free article provided by www.homemicro.co.uk Thermal Storage Vessel Sizing www.homemicro.co.uk LZC Articles on LZC technologies, HVAC, Computers & CAD too! Page 1 of 18 Summary This article provides

More information

SINGLE STAGE END SUCTION PUMPS AURORA Series. Distributed By: Model 3804

SINGLE STAGE END SUCTION PUMPS AURORA Series.  Distributed By: Model 3804 Model 3804 AURORA 3800 Series SINGLE STAGE END SUCTION PUMPS Distributed By: Flow-Tech Industries 4601 South Pinemont, Suite 100 Houston, Texas 77041 Phone: 713.690.7474 Fax: 409.882.0254 sales@flow-tech.com

More information

Organic Rankine Cycle Technology

Organic Rankine Cycle Technology Power Systems Pratt & Whitney Power Systems Organic Rankine Cycle Technology TM It s in our power. Pratt & Whitney Organic Rankine Cycle Technology Quality High-volume components produced to strict tolerances

More information

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT

SECTION VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT SECTION 220550 - VIBRATION ISOLATION FOR PLUMBING PIPING AND EQUIPMENT PART 1 - GENERAL REQUIREMENTS 1.1 SUMMARY A. It is the intent of this specification to provide vibration isolation supports for Plumbing

More information

trusted innovative expertise

trusted innovative expertise Ingersoll Rand is well into its second century of building our legacy as a trusted global leader by delivering the innovative solutions and expertise our customers require. We continue to advance compressed

More information

Intelligent Well Management System

Intelligent Well Management System Intelligent Well Management System By combining our vast years of experience in the Oil/Gas market with the versatility of the Schneider Electric Altivar 930 variable frequency drive (VFD), the Well iknow

More information

Industrial Refrigeration. Highly flexible and reliable solutions that save energy and increase your coefficient of performance

Industrial Refrigeration. Highly flexible and reliable solutions that save energy and increase your coefficient of performance Industrial Refrigeration Highly flexible and reliable solutions that save energy and increase your coefficient of performance Industrial Refrigeration Key to a sustainable planet For around 200 years,

More information

Pump Vibration. Related Considerations and How Much is Too Much? MWEA Collection Systems Seminar. Steve Fehniger, P.E.

Pump Vibration. Related Considerations and How Much is Too Much? MWEA Collection Systems Seminar. Steve Fehniger, P.E. Pump Vibration Related Considerations and How Much is Too Much? MWEA Collection Systems Seminar Steve Fehniger, P.E. October 12, 2017 Agenda Presentation Focus Areas Pump Vibration Considerations Operating

More information

technical bulletin Subcooler Control

technical bulletin Subcooler Control Overview technical bulletin The E2 now has support for controlling a Subcooler. Incorporating Subcooler control in the E2 eliminates the need for standalone Subcoolers that do not have network communication

More information

Thermal Energy Storage

Thermal Energy Storage This article was published in ASHRAE Journal, June 2013. Copyright 2013 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Delivering What Matters Most

Delivering What Matters Most Delivering What Matters Most The question isn t Which compressor can do the job? Many can perform that basic function. More important is knowing which compressor works reliably longer, even in the most

More information

SECTION PACKAGE BOOSTER PUMP STATIONS

SECTION PACKAGE BOOSTER PUMP STATIONS SECTION 331223 PACKAGE BOOSTER PUMP STATIONS Scope: The Contractor shall install a pump station at two locations to be determined by the Owner. These pump stations shall be designed to deliver flow to

More information

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating

The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating The Potential and Challenges of Solar Boosted Heat Pumps for Domestic Hot Water Heating Stephen Harrison Ph.D., P. Eng., Solar Calorimetry, Dept. of Mechanical and Materials Engineering, Queen s University,

More information

REPORT DOCUMENTATION PAGE

REPORT DOCUMENTATION PAGE REPORT DOCUMENTATION PAGE Form Approved OMBNo.0704-018 Public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions,

More information

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372.

W ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS. Certified to NSF/ANSI 372. W ST IND TRY FIR US ARR A NTY FAIRBANKS NIJHUIS 1600 SERIES SINGLE STAGE END SUCTION PUMPS Certified to NSF/ANSI 372 www.fairbanksnijhuis.com FAIRBANKS NIJHUIS 1600 SERIES Single Stage End Suction Pumps

More information

TYP. SINGLE PLY ROOFING ROOF SHEETING BROAN VENT CAP #10 x 1" GASKETED SMS TYP. 4 SIDES 8" FRAMED CURB HVAC SYSTEMS "BASIS OF DESIGN" ROOF INSULATION R-19 WALL INSULATION R-13 LIGHTING EFFIECNCY PER STANDARDS

More information

V entilation control using carbon dioxide

V entilation control using carbon dioxide REAL-TIME VENTILATION Operational control of ventilation systems using sensors that measure concentrations Editors Note: A longer version of this article is available at no cost on HPAC Engineering s Website

More information

IECC Commercial Significant Changes Summary Tier I

IECC Commercial Significant Changes Summary Tier I 2009-2015 IECC Commercial Significant Changes Summary Tier I The first change is in the layout of the book. Instead of having Chapters 1-3 that applied to all projects and then having Chapter 4 Residential

More information