THE VALUE OF VENTILATION FROM THE WEBER-FECHNER LAW

Size: px
Start display at page:

Download "THE VALUE OF VENTILATION FROM THE WEBER-FECHNER LAW"

Transcription

1 Topic B12: Productivity and economics THE VALUE OF VENTILATION FROM THE WEBER-FECHNER LAW Arne JÖNSSON * Secondary Vocational Training, Härnösand, Sweden * Corresponding arne.jonsson@harnosand.se Keywords: Weber-Fechner, value, ventilation, economics SUMMARY If the value of ventilation or the relation between outdoor air rates and loss of production is known then the air rate can be optimized. If the loss of production can be related directly to different odors like body, building and cigarette odor then the removal of odor sources can be optimized. There are two methods to find the value of ventilation. One method is studies where the work rate is measured in an experiment at determined outdoor air rates and source strength of pollution. The other method is to calculate the marginal cost of outdoor air and assume that the marginal cost equals the marginal loss. The assumption of optimality is based on that the long time use of ventilation has taught us what the optimal outdoor air rate is. The marginal cost method, with costs from a Swedish office with constant 100 % outdoor air ventilation, gives the loss of production at 60 % dissatisfied. This was measured in a work rate study from Sweden. The value of ventilation in offices determined with indirect or marginal cost methods and direct measurements in work rate studies are showing the same result. INTRODUCTION The function for percentage dissatisfied in body odor gives the percentage at an outdoor air rate. With the odor threshold c*1 = 50 ppm CO 2 for the most sensible person (1.3 %) and a generation rate of 16 l/h pers CO 2 then a relation between percentage dissatisfied PD and the number of dilutions x1 to the odor threshold for body odor can be calculated. The relation is assumed to be valid for building odor and cigarette smoke odor too. So if body odor, building odor and cigarette odor separately give the same loss of production then they have the same x1. According to Fechner (1860) the strength of the feeling is proportional to the logarithm of the relation between the concentration and the odor threshold. The relation between the concentration and the odor threshold is the number of dilutions to the odor threshold. The constant of proportionality a can be determined in both dimensions, against the measured loss and against the marginal cost. 1 = 9 SEK.

2 METHODOLOGIES The loss of production for a collective The individuals in a collective have a distribution of odor thresholds. Here the distribution of dissatisfied PD(i) is used instead. For an odor that has normally distributed odor thresholds, lognormal N(ln(x1), 4, 1.8) the function in equation 1 from Fanger (2004) approximates the normal distribution. Frequency distribution of dissatisfied pd(i) equation 2 is the differential of PD(i) with regard to i. The individuals in interval 1 between 50*(1 ± 0.5) ppm are 0.02 of the population according to equation 2 and their thresholds for body odor are approximated to 50 ppm. In interval 2 between 50*(2 ± 0.5) ppm there are also 0.02 of the population and their threshold is approximated to 100 ppm CO 2 above outdoors. The demand and the loss over the intervals are added in equation 3 and equation 4. 1 < i < x 1. (1) (2) The Dem(x1) equation 3 is the function for demand of improvement for a collective. The Loss(x1) equation 4 is the function for loss of production for the collective in an air with the numbers of dilutions for the most sensible x1. The functions are calculated numerically and the result is given in Table 1. (3) (4) Addition of odors The x1 for a mixture of odors is equation 5. q* b outdoor air rate necessary to dilute body odor, from one person to the threshold for the most sensible person and q* bu outdoor air rate necessary to dilute the odor from the building surrounding one person to the threshold for the most sensible person, l/s pers. q is the outdoor air rate l/s pers. This corresponds to the calculation of pol according to Fanger (2004) where the olf is the q*. (5)

3 Table 1. Distribution of dissatesfied, diss at x1 = c/c*1, c*1 = 50 ppm CO 2 above outdoor air. Demand of improvement, Dem and Loss of production, Loss at x1. Outdoor air rate q l/s pers to make diss % dissatiesfied with body odor from one person Jönssson (2013). Optimal outdoor air rate x1 diss Dem Loss q x1 diss Dem Loss q % l/s pers % l/s pers The outdoor air rate that minimizes the sum of cost for outdoor air and loss equation 6 is the optimal outdoor air rate. It has an optimal dilution x1 from equation 5. l is the fixed cost and m is the marginal cost of outdoor air at the design of the building, SEK/ l/s yr. n is the number of persons present in office. p wh is the price of a work hour, SEK/h pers and τ is the time of operation of the office, h/yr. Equation 5 is inserted in equation 6. Equation 7 is differentiated and put equal to zero in equation 8. The optimal x1 can be solved from equation 8. (6) (7) (8) Cost of ventilation in an office The cost of ventilation SEK/yr is the sum of cost for the investment and the cost of operation in a Swedish office with constant, 100 % outdoor air ventilation during the time of operation 2000 h/yr. A linear relation between concentration and loss gave the loss at 10 l/s person Jönsson (1995). Investments An air heater for 1.25 m 3 /s including heat capacity from district heating costs phc = 2000 SEK/kW and if the design outdoor temperature is -20 C then the investment is SEK.

4 The cooling capacity for air conditioning depends on the outdoor air rate. The cooling capacity costs pcc = SEK/kW including the cooling coil. With an indoor design temperature of 27 C and a latent/ sensible relation of 1.5 the investment for 1.25 m 3 /s is SEK. The investments are added in Table 2. Half of the investment from Table 2 depends on the air rate at the design of the system. The annuity is with 4 % interest and 20 years service life. Marginal cost of outdoor air Table 2. Investments in the ventilation system, ksek. Office Investment Heat recovery No heat rec ksek ksek Heater Cooling Heat recovery Rest Ducts, inletts Sum The ventilation system with heat recovery has an investment that depends on the air rate of SEK / 1250 l/s = 460 SEK/ l/s. The annuity gives a marginal cost of 34 SEK/ l/s yr. To include the cost of the space in the building 50 % is added. The no heat recovery system has an investment per l/s of SEK/ 1250 l/s = 350 SEK/ l/s yr. The annuity gives the marginal cost 26 SEK/ l/s yr plus 50 % for space. The cost for the investment and the cost of operation are added in Table 3. Cost of operation for heat in a Swedish climate with degree hours/yr, heat price ph = 0,5 SEK/kWh and time of operation during work hours τ = 2000 h/yr gives the marginal cost of operation 16 SEK / l/s yr. Heat recovery with 75 % efficiency η = 75 % reduces the marginal cost of operation to 16 * (1-0.75) = 4 SEK/ l/s yr. Cost of electricity for two fans at the design pressure drop of 700 Pa. The price of electricity is pe = 1 SEK/kWh. The fan and electric motor efficiency is η = 0.6 which gives the marginal cost of operation to 5 SEK/ l/s yr. Table 3. Marginal cost of outdoor air rate SEK/ l/s yr. Marg. cost Heat recover No heat rec SEK/ l/s yr SEK/ l/s yr Operation Heat 4 16 Electricity 5 4 Investment Sum 60 59

5 The marginal cost of outdoor air or the cost to increase the outdoor air rate 1 l/s at the design of the building will be 60 SEK/ l/s yr with heat recovery. Determination of a If the used air rate is optimal, then the marginal cost equals the marginal loss and a can be solved from equation 8. If the optimal outdoor air rate is 12 l/s pers with q*b = 90, q*bu = 90 l/s pers, then x1 = 180/12 = 15, τ = 2000 h/yr gives Dem(15) = 0.1 from Table 1. m/pwh = 60 SEK/ l/s yr / 250 SEK/h = 0.24 h/ l/s yr in equation 8 gives a = If the optimum is 15 l/s pers then a = The air rates l/s pers for use during 2000 h/yr are high compared to the ASHRAE recommendations 8 l/s pers but the recommended air rate is used during a shorter period. Calculated loss The loss in decimals Lossd(x1) is calculated as function of x1 with equation 9. The curve in Figure 1 shows the Lossd(x1) as function of the PD. The relation between x1 and PD from Table 1. The PD is what can be determined about mixtures of odors. Loss from work rate studies (9) The calculated loss is compared with the measured loss from two work rate studies that used the same carpet as pollutant. Wargocki et al (2000), W and Lagercrantz et al (2000), L used an ordinary office with furniture s as test room. A carpet with a history of sick building syndromes was used as pollutant in both tests. Results from W in Table 4. The percentage dissatisfied, PD at first entrance with carpet is for building, bu and carpet, ca odor. The PD for body, b building, bu and carpet, ca is at reentrance. The study made in Copenhagen had 30 test persons in 5 groups Table 4. Percentage dissatisfied PD, production and loss at different outdoor air rates, W. Outdoor Dissatisfied Speed, norm. b+bu+ca air rate bu+ca, first b+bu+ca, ree Typing Add Pro read l/s pers % % : loss : loss : loss : : : : : : The PD was the same at both 10 and 30 l/s pers this gives the same number of dilutions x1 at 10 and at 30 l/s witch is unlikely.

6 The test room in L was built in an office space from 1984 with ordinary furniture s. The floor was linoleum and the walls of gypsum board. The test room was in Östersund, Sweden. The Result from the tests is in Table 5. The study had 30 test persons. Table 5. Percentage dissatisfied, production and loss at 10 l/s pers outdoor air rate and mixtures of different pollutants, L. Air rate Dissatisfied Productivity 10 l/s pers first ree Typing Add Pollutant Speed correct bu 36 : loss : loss b+bu bu+ca 60 b+bu+ca : :0.012 L got a higher percentage dissatisfied but a lower loss of production than W. b+bu+ca with 10 l/s pers in L and b+bu+ca with 3/s pers in W both gives 60 % dissatisfied. 60 % dissatisfied gave loss in W but only loss in L. "As all surface materials are 15 years old it was assumed that the primary emission of pollutants in the office was at a very low level." The office chamber may explain the high percentage dissatisfied without carpet in Table 5. Comparison between the calculated loss and loss from work rate studies The measured loss, dots from Wargocki et al. (2000) W and Lagercrantz et al. (2000) L as function of percentage dissatisfied PD % and the calculated Lossd curve if optimum is 12 l/s pers a = If the optimum is 15 l/s pers then a = Figure 1. Calculated Lossd (loss in decimals) as function of the percentage dissatisfied, PD %, curve. The measured loss from work rate studies, dots.

7 The calculated Lossd is at 60 % dissatisfied. The measured loss at 62 % dissatisfied is in L and the loss at 58 % dissatisfied is in W. Jönsson (1995) used a linear relation between concentration and loss. He calculated the loss at the optimal outdoor air rate 10 l/s pers to The calculated Lossd in Figure 1 shows that it is not profitable to reduce the PD to zero, because the Lossd goes to zero at PD = 0. The calculated Lossd at 24 % and 33 % dissatisfied is resp The Lossd = has the value of 4 work hours per pers and year. (1000 SEK/yr) If pollutants can be removed so that 20 % is dissatisfied then the Lossd is reduced to Then 3 more work hours per pers and year will be available and = or 750 SEK/pers yr will be gained. The loss curve is convex since both the loss per person and the percentage dissatisfied are reduced at a low concentration. The convex curve for the loss per person shows that the marginal loss increases at higher x1. This is realistic since at x1 = 600 or 3 % CO2 a person will faint. There are contradictions in the measured percentage dissatisfied. L measured a higher percentage dissatisfied but measured a lower loss of production than W. RESULTS AND DISCUSSION If the used outdoor air rates is optimal then the marginal cost of the outdoor air rate is put equal to the marginal loss at normally used outdoor air rates l/s pers then a constant can be solved. The constant makes it possible to calculate the loss of production with the integrated Weber-Fechner Law. The marginal cost from a Swedish office with constant, 100 % outdoor air ventilation, during an operation of 2000 h/yr gives the calculated loss of production at 60 % dissatisfied. The loss was measured in a work rate study from Sweden, Lagercrantz et al. (2000). The assumption of optimality is based on that the long time use of ventilation and the long time research about ventilation has taught us what the optimal outdoor air rate is. The measured losses have a higher variation at 60 % dissatisfied than the variation in the calculated loss at 60 % dissatisfied from different assumptions about the optimal outdoor air rate 12 or 15 l/s pers. There are contradictions in the measurements of the percentage dissatisfied. CONCLUSIONS The value of ventilation in offices determined with indirect or marginal cost methods and direct measurements in work rate studies are showing the same result. The calculated loss of production at 60 % dissatisfied and the measured loss of production at 60 % dissatisfied are the same. There is however other studies with the same pollutant showing up to loss at 60 % dissatisfied.

8 The value of ventilation in offices determined with indirect or marginal cost methods and direct measurements in work rate studies are showing the same result. REFERENCES Fanger PO (2004) Perceived air quality and ventilation requirements, Ch. 22 Indoor air quality handbook, McGraw-Hill, (2004) ( Fechner GT (1860) Elemente der Psychophysik, zweiter teil, Breitkopf und Härtel, Leipzig 1860, p Google Books (German) Jönsson A (1995) Economic analysis of ventilation in an Office Building, Indoor air quality in practice, Oslo, Norway, p Jönsson A (2012) Odour nuisance and the loss of work hours according to the Weber-Fechners Law, Ventilation 2012, Paris, France Jönsson A (2013) Improvement of the Integrated Weber-Fechner Law for Odors, Clima 2013, Prague, Czech Republic Lagercrantz L, Wistrand M, Willen U, Wargocki P, Witterseh T, Sundell J (2000) Negative impact of air pollution on productivity: Previous Danish findings repeated in new Swedish test room, Healthy Buildings 2000, Vol. 1 p , Esbo, Finland Wargocki P, Wyon DP, Fanger PO (2000) Productivity is affected by the air quality in offices, Healthy Buildings 2000, Vol. 1 p , Esbo, Finland

Improvement of the Integrated Weber-Fechner Law for Odors

Improvement of the Integrated Weber-Fechner Law for Odors Improvement of the Integrated Weber-Fechner Law for Odors Arne Jönsson Secondary Vocational Training Härnösand, Sweden arne.jonsson@harnosand.se Abstract The Weber-Fechner law gives the odor nuisance as

More information

THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS

THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS THE EFFECT OF USING LOW-POLLUTING BUILDING MATERIALS ON VENTILATION REQUIREMENTS AND ENERGY USE IN BUILDINGS Pawel Wargocki, Henrik N. Knudsen 2, and Monika Frontczak International Centre for Indoor Environment

More information

SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY

SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY SICK BUILDING SYNDROME SYMPTOMS AND PERFORMANCE IN A FIELD LABORATORY STUDY AT DIFFERENT LEVELS OF TEMPERATURE AND HUMIDITY L Fang, DP Wyon, G Clausen and PO Fanger International Centre for Indoor Environment

More information

PERCEIVED AIR QUALITY, THERMAL COMFORT, AND SBS SYMPTOMS AT LOW AIR TEMPERATURE AND INCREASED RADIANT TEMPERATURE

PERCEIVED AIR QUALITY, THERMAL COMFORT, AND SBS SYMPTOMS AT LOW AIR TEMPERATURE AND INCREASED RADIANT TEMPERATURE PERCEIVED AIR QUALITY, THERMAL COMFORT, AND SBS SYMPTOMS AT LOW AIR TEMPERATURE AND INCREASED RADIANT TEMPERATURE J Toftum *, G Reimann, P Foldbjerg, G Clausen and PO Fanger International Centre for Indoor

More information

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA Update to ASHRAE Ventilation Standards William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA REHVA Annual Conference Riga, Latvia May 8 9, 2015 Acknowledgements

More information

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D.

Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Ventilation standards EN15251 and ANSI/ASHRAE 62.1 Professor Bjarne W. Olesen, Ph.D. Technical University of Denmark Energy consumption for ventilation Exhaust Ventilation air Up to 30% of the total energy

More information

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms

Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Indoor Climate and Ventilation in Finnish Schools Air Distribution and Temperature Control in Classrooms Abstract Finland is a country without a debate on natural ventilation. In such a cold climate, it

More information

PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES

PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES PERSONAL COMPUTERS POLLUTE INDOOR AIR: EFFECTS ON PERCEIVED AIR QUALITY, SBS SYMPTOMS AND PRODUCTIVITY IN OFFICES Zs Bakó-Biró 1,2, P Wargocki 1, C. Weschler 1,3 and P. Ole Fanger 1 1 International Centre

More information

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS

INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS INTEGRATING INDOOR AIR QUALITY AND ENERGY EFFICIENCY IN BUILDINGS William P. Bahnfleth, Ph.D., P.E., FASHRAE, FASME Indoor Environment Center, The Pennsylvania State University Outline Connection between

More information

ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK

IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK IMPROVING INDOOR AIR QUALITY IMPROVES THE PERFORMANCE OF OFFICE WORK AND SCHOOLWORK Pawel Wargocki International Centre for Indoor Environment and Energy, Department of Mechanical Engineering, Technical

More information

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized.

After refurbishment, heat recovery and demand control of the air flow were installed and the use of the systems were optimized. Property name: Nordstan Nordstan Objekt 6 Property owner: Vasakronan AB Consultants: GICON Total Concept method Step 1. Creating the action package Building and its use Year built: 1968 Area: 48 600 m²

More information

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2

PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS. T Karimipanah 1 and H B Awbi 2 PERFORMANCE EVALUATION OF TWO AIR DISTRIBUTION SYSTEMS T Karimipanah 1 and H B Awbi 2 1 Air Innovation AB, Sweden 2 University of Reading, UK ABSTRACT This paper focuses on evaluating the performance of

More information

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS

DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS DEMAND CONTROLLED VENTILATION (DCV) SYSTEMS Mari-Liis Maripuu, PhD CIT Energy mari-liis.maripuu@cit.chalmers.se Swegon Air Academy, Portugal, 27 May 211 Outline Introduction Concept of a DCV system Adapting

More information

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD

MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD MODELLING THE ENERGY PERFORMANCE OF NIGHT-TIME VENTILATION USING THE QUASI-STEADY STATE CALCULATION METHOD Jérôme Le Dréau, Per Heiselberg, Rasmus L. Jensen and Ayser D. Selman Department of Civil Engineering,

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 11 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible

More information

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS

COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Kazderko Mikhail COMPARISON OF THE STANDARDIZED REQUIREMENTS FOR INDOOR CLIMATE IN OFFICE BUILDINGS Bachelor s Thesis Building Services Engineering December 2012 DESCRIPTION Date of the bachelor's thesis

More information

Energy Efficient Control of Fans in Ventilation Systems

Energy Efficient Control of Fans in Ventilation Systems Chapter 6 Energy Efficient Control of Fans in Ventilation Systems Bjørn R. Sørensen Additional information is available at the end of the chapter http://dx.doi.org/10.5772/48597 1. Introduction Ventilation

More information

ENERGY RECOVERY, CALCULATION METHODS

ENERGY RECOVERY, CALCULATION METHODS ENERGY RECOVERY ENERGY RECOVERY, CALCULATION METHODS 19/10/2016 DOCUMENT PETER SUNDELIN Efficiency of a recovery system? 1. 2. 3. 4. 5. 6. 7. 8. 9. 10. 11. 12. 13. 14. 15. Supply air temp. efficiency,

More information

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY

ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY , Volume 2, Number 4, p.113-117, 2001 ANALYSIS OF EXERGY OF MOIST AIR AND ENERGY SAVING POTENTIAL IN HVAC BY EVAPORATIVE COOLING OR ENERGY RECOVERY C.Q. Ren, G.F. Tang, N.P. Li, G.F. Zhang and J. Yang

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

ON THE OPTIMIZATION OF REFRIGERATION MACHINERY

ON THE OPTIMIZATION OF REFRIGERATION MACHINERY GÖRAN WALL Exergy Studies, Solhemsgatan 46, SE-431 44, Mölndal, Sweden, Email: Goran.Wall@exergy.se published in International Journal of Refrigeration Vol. 14., pp. 336-340. 1991. Abstract. We present

More information

Value of Lost Load some issues and reflections

Value of Lost Load some issues and reflections Value of Lost Load some issues and reflections Runar Brännlund Centre for Environmental and Resource Economics Umeå School of Business and Economics Outline What s the problem and challenges? How secure

More information

Canada Published online: 28 Feb 2011.

Canada Published online: 28 Feb 2011. This article was downloaded by: [Bibliothèque ÉTS] On: 21 July 2015, At: 04:30 Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: 1072954 Registered office: 5 Howick

More information

EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE

EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE Topic A8: IAQ and perceived indoor air quality EVALUATION OF THE INDOOR AIR QUALITY IN A SINGLE FAMILY ACTIVE HOUSE Christoffer PLESNER * and Karsten DUER VELUX A/S, Daylight Energy and Indoor climate,

More information

HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY

HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY HEAT RECUPERATION IN VENTILATION SYSTEM OF BASEMENT LABORATORY Alena Krofova, Pavel Kic Czech University of Life Sciences Prague krofovaa@tf.czu.cz, kic@tf.czu.cz Abstract. Basement spaces in many university

More information

Ventilation of Apartment Buildings and Nursing Homes

Ventilation of Apartment Buildings and Nursing Homes Smart Grid and Renewable Energy, 2014, 5, 107-119 Published Online May 2014 in SciRes. http://www.scirp.org/journal/sgre http://dx.doi.org/10.4236/sgre.2014.55010 Ventilation of Apartment Buildings and

More information

MODELLING THE COST EFFECTS OF THE INDOOR ENVIRONMENT

MODELLING THE COST EFFECTS OF THE INDOOR ENVIRONMENT MODELLING THE COST EFFECTS OF THE INDOOR ENVIRONMENT M Tuomainen 1, J Smolander 1, J Kurnitski 1, J Palonen 1 and O Seppänen 1 1 HVAC laboratory, Helsinki University of Technology, Espoo, Finland ABSTRACT

More information

INDOOR AIR QUALITY IN CLASSROOMS: FIELD CAMPAIGN BY QUESTIONNAIRES AND MEASUREMENTS S. P. Corgnati and S. Viazzo

INDOOR AIR QUALITY IN CLASSROOMS: FIELD CAMPAIGN BY QUESTIONNAIRES AND MEASUREMENTS S. P. Corgnati and S. Viazzo ABSTRACT INDOOR AIR QUALITY IN CLASSROOMS: FIELD CAMPAIGN BY QUESTIONNAIRES AND MEASUREMENTS S. P. Corgnati and S. Viazzo Department of Energy Technologies, Polytechnic of Torino, Corso Duca degli Abruzzi

More information

Articles. Figure 2. Typical set-up of personalized ventilation system.

Articles. Figure 2. Typical set-up of personalized ventilation system. Revision of 15251: ndoor Environmental Criteria Abstract: 15251 specifies indoor environmental input parameters for design and assessment of energy performance of buildings addressing indoor air quality,

More information

Energy Effort of Air Distribution Systems

Energy Effort of Air Distribution Systems Energy Effort of Air Distribution Systems F. Kolarik Content Introduction Energy effort of air distribution systems Method of calculation Example Further investigations Introduction Increasing requirements

More information

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies.

Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs. Valent is a business of Unison Comfort Technologies. Valent Packaged Rooftop Units A Fresh Choice for High-Percentage Outdoor Air Designs Valent is a business of Unison Comfort Technologies. When your HVAC system design calls for high-percentage or 100%

More information

Indoor Air Quality and Thermal Environment in Classrooms with Different Ventilation Systems

Indoor Air Quality and Thermal Environment in Classrooms with Different Ventilation Systems Indoor Air Quality and Thermal Environment in Classrooms with Different Ventilation Systems a International Centre for Indoor Environment and Energy, Department of Civil Engineering, Technical University

More information

Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course

Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course Use of MathCad and Excel to Enhance the Study of Psychrometric Processes for Buildings in an Air Conditioning Course Rogelio Luck 1 and Pedro J. Mago 2 Abstract The use of computational tools such as Mathcad

More information

INDOOR CLIMATE AND PRODUCTIVITY

INDOOR CLIMATE AND PRODUCTIVITY INDOOR CLIMATE AND PRODUCTIVITY Olli Seppänen Professor at Helsinki University of Technology, Finland President of Federation of European Heating and Air-conditioning Associations INTRODUCTION There is

More information

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2

Published in: Proceedings of the 7th International Conference on Healthy Buildings 2003, Singapore, December 2003, Vol. 2 Aalborg Universitet Design Methods for Air Distribution Systems and Comparison Between Mixing Ventilation and Displacement Ventilation Nielsen, Peter Vilhelm; Larsen, Tine Steen; Topp, Claus Published

More information

Indoor Air Quality Improvement in a School Building in Delhi

Indoor Air Quality Improvement in a School Building in Delhi Indoor Air Quality Improvement in a School Building in Delhi Maija Virta #1, Suhaas Mathur #1 # Santrupti engineers Private Limited 1083, 35 th D Cross, 4 th T Block, Jayanagar, Bangalore 560041, India

More information

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,

More information

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2

CASE STUDY. Two Dogs and Two Cats Insufficient Air Exchange with High CO2 FOR MORE INFORMATION, VISIT: HTTP://BUILDEQUINOX.COM/BLACKBOX/ CASE STUDY Two Dogs and Two Cats Insufficient Exchange with High CO2 A Black Box IAQ was placed in the main living area of a pre-1900 home.

More information

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017

Zero Carbon Building Energy Modelling Guidelines. October 31, 2017 Zero Carbon Building Energy Modelling Guidelines October 31, 2017 Contents 1. INTRODUCTION... 3 1.1 DEFINITIONS... 4 2. CALCULATING TEDI... 5 2.1 INTERNAL HEAT GAINS... 6 2.2 CALCULATING BUILDING ENVELOPE

More information

An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode

An energy-saving control strategy for VRF and VAV combined air conditioning system in heating mode Purdue University Purdue e-pubs International Refrigeration and Air Conditioning Conference School of Mechanical Engineering 2014 An energy-saving control strategy for VRF and VAV combined air conditioning

More information

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based CO Demand-Controlled 2 -Based Ventilation With ASHRAE Standard 62.1 Though not as straightforward as it once was, remains a practical way to reduce costs Editor s note: Following is an update of the November

More information

ASHRAE and Indoor Air Quality

ASHRAE and Indoor Air Quality ASHRAE 62.2-2013 and Indoor Air Quality Weatherize Ohio Conference October 27 29, 2015 The State of Ohio is an Equal Opportunity Employer and Provider of ADA Services Introduction ASHRAE: Why is it needed?

More information

The indoor climate and energy consumption of educational buildings

The indoor climate and energy consumption of educational buildings The indoor climate and energy consumption of educational buildings Department of Environmental Engineering Tallinn Technical University Ehitajate tee 5, 1986 Tallinn ESTONIA Teet.koiv@ttu.ee http://www.ttu.ee

More information

IAQ & Energy Impact of Exhaust Air Transfer Ratio

IAQ & Energy Impact of Exhaust Air Transfer Ratio This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Nilan VPL Active heat recovery and cooling (air/air)

Nilan VPL Active heat recovery and cooling (air/air) M a r k e t l e a d i n g c o m m e r c i a l a n d d o m e s t i c v e n t i l at i o n w i t h h e at r e c o v e r y Nilan 31-125 Active heat recovery and cooling (air/air) Nilan 31-125 Commercial ventilation

More information

NatVent. Overcoming technical barriers to low-energy natural ventilation in office type buildings in moderate and cold climates

NatVent. Overcoming technical barriers to low-energy natural ventilation in office type buildings in moderate and cold climates NatVent Overcoming technical barriers to low-energy natural ventilation in office type buildings in moderate and cold climates EC CONTRACT: JOR3-CT95-0022 (DGXII) Barriers to Natural Ventilation Design

More information

Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality

Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality Green Schools Track Ensuring Proper Installation and Commissioning of HVAC Systems for Energy Efficiency and Indoor Air Quality April 10, 2018 Agenda The Importance of Ventilation in Classrooms Ensuring

More information

The indoor climate and students learning performance in schools

The indoor climate and students learning performance in schools Ravage of the Planet IV 287 The indoor climate and students learning performance in schools T.-A. Koiv, A. Mikola, A. Saar & G. Silm Department of Environmental Engineering, Tallinn University of Technology,

More information

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models

Optimization of air tightness and night ventilation for Passive houses in Italian climates under Fanger and Adaptive comfort models L. Pagliano et al, I: Optimization of air tightness and night ventilation for Passive houses in Italian climates... 1 Optimization of air tightness and night ventilation for Passive houses in Italian climates

More information

Sustainable Chilled Beam Design

Sustainable Chilled Beam Design MAIJA VIRTA HARRI ITKONEN PANU MUSTAKALLIO MIKA RUPONEN RISTO KOSONEN 1 - Halton Oy ABSTRACT Chilled beam technology is seen as a very sustainable technology providing both excellent indoor conditions

More information

A CASE STUDY OF VENTILATION IMPACTS ON PARTICLE CONCENTRATION IN AIR-CONDITIONED SPACE LOCATED IN DESERT CLIMATE

A CASE STUDY OF VENTILATION IMPACTS ON PARTICLE CONCENTRATION IN AIR-CONDITIONED SPACE LOCATED IN DESERT CLIMATE A CASE STUDY OF VENTILATION IMPACTS ON PARTICLE CONCENTRATION IN AIR-CONDITIONED SPACE LOCATED IN DESERT CLIMATE Moshood Olawale Fadeyi, Assistant Professor, fadeyi.olawale@buid.ac.ae Faculty of Engineering

More information

Effect of room air recirculation delay on the decay rate of tracer gas concentration

Effect of room air recirculation delay on the decay rate of tracer gas concentration Effect of room air recirculation delay on the decay rate of tracer gas concentration A.R. Kristoffersen, A.J. Gadgil, D.M. Lorenzetti. Indoor Environment Department, Lawrence Berkeley National Laboratory,

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

ctbuh.org/papers The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Title:

ctbuh.org/papers The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Title: ctbuh.org/papers Title: Authors: Subject: Keywords: The Evaluation of Performance for the Application of a Heat Recovery Ventilator to High-rise Apartments Sang-Min Kim, Principal Research Engineer, Hyundai

More information

Energy Recovery Ventilation Equipment

Energy Recovery Ventilation Equipment ANSI/AHRI Standard 1060 (I-P) 2014 Standard for Performance Rating of Airto-Air Exchangers for Energy Recovery Ventilation Equipment Approved by ANSI on May 15, 2015 IMPORTANT SAFETY DISCLAIMER AHRI does

More information

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS

LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS LOCAL VENTILATION SYSTEMS: SOME INVESTIGATIONS ABOUT COMFORT LEVELS AND ENERGY DEMANDS Elena Buchberger - ebuch@iuav.it Luca Porciani, porciani@iuav.it Fabio Peron, fperon@iuav.it Universita IUAV di Venezia,

More information

BSRIA Heating. Worldwide Market Intelligence

BSRIA Heating. Worldwide Market Intelligence 2014 BSRIA Heating Worldwide Market Intelligence Over 25 years experience researching key markets worldwide market intelligence in 94 Countries integrated technical and market expertise management consultancy

More information

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering

Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Do European standards for indoor air quality take into account outdoor air quality? Professor Bjarne W. Olesen, PhD, Department of Civil Engineering Technical University of Denmark Global impact on people

More information

I. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE.

I. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE. Duct Loops and VAV Modelling and Control I. Khoo, BEng(Hons), G.J. Levermore, BSc, ARCS, PhD, DIC, CEng, FCIBSE, MASHRAE, MInstE, K.M. Letherman, BSc, MSc, PhD, CEng, FIEE, FCIBSE. Abstracts This paper

More information

UC Berkeley HVAC Systems

UC Berkeley HVAC Systems UC Berkeley HVAC Systems Title Energy saving strategies with personalized ventilation in tropics Permalink https://escholarship.org/uc/item/6mf6n9v9 Authors Schiavon, Stefano Melikov, Arsen Chandra Sekhar,

More information

Verification of Chiller Performance Promotion and Energy Saving

Verification of Chiller Performance Promotion and Energy Saving Engineering, 2013, 5, 141-145 http://dx.doi.org/10.4236/eng.2013.51a020 Published Online January 2013 (http://www.scirp.org/journal/eng) Verification of Chiller Performance Promotion and Energy Saving

More information

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS

ANSI/ASHRAE STANDARD , METHODS OF TESTING CHILLED BEAMS ANSI/ASHRAE STANDARD 200-2015, METHODS OF TESTING CHILLED BEAMS NEMIC 2017 Agenda 1. Foreword 2. Purpose & Scope 3. Definitions 4. Instrumentation & Facilities 5. Test Methods 6. Reporting 7. Normative

More information

Passive Houses Worlswide: International Developments

Passive Houses Worlswide: International Developments Passive Houses Worlswide: International Developments Henk Kaan, ECN Energy Research Centre of the Netherlands, P.O. Box 1, 1755 ZG Petten, The Netherlands, Isolda Strom, DHV Building and Industry, P.O.

More information

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings

Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators in High-Rise Residential Buildings Original Paper Indoor and Built Indoor Built Environ 212;21;4:486 52 Accepted: October 17, 211 Environment Improvement of Indoor Living Environment by Occupants Preferences for Heat Recovery Ventilators

More information

External Environment and Indoor Microclimate

External Environment and Indoor Microclimate External Environment and Indoor Microclimate Michal Kabrhel 1, Hana Dolezilkova 1 1 Department of Microenvironmental and Building Services Engineering, Faculty of Civil Engineering, Czech Technical University

More information

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France

Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Using passive solutions to improve thermal summer comfort in timber framed houses in South-west France Sylvain Boulet 1, Stéphanie Armand-Decker 2, FCBA Technological Institute I2M-TREFLE laboratory -

More information

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment

A Comparison of Calculated and Subjective Thermal Comfort Sensation in Home and Office Environment Proceedings of Conference: People and Buildings held at the offices of Arup UK, 23rd September 2011. London: Network for Comfort and Energy Use in Buildings, http://nceub.org.uk A Comparison of Calculated

More information

Passive house optimization for Southern Italy based on the New Passivhaus Standard

Passive house optimization for Southern Italy based on the New Passivhaus Standard Passive house optimization for Southern Italy based on the New Passivhaus Standard Paolo Zangheri end-use Effi ciency Research Group, Dipartimento di Energia Politecnico di Milano, Italy paolo.zangheri@polimi.it

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort

Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Energy-Efficient Passive House using thermal mass to achieve high thermal comfort Loa Andersson Managing Director RLI Byggdata AB rli@termodeck.com Alexander Engström Technical Director RLI Byggdata AB

More information

Coppin State University Physical Education Complex - Technical Report 2

Coppin State University Physical Education Complex - Technical Report 2 Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents

More information

UC Berkeley Indoor Environmental Quality (IEQ)

UC Berkeley Indoor Environmental Quality (IEQ) UC Berkeley Indoor Environmental Quality (IEQ) Title Energy-saving strategies with personalized ventilation in cold climates Permalink https://escholarship.org/uc/item/09q0q1rb Authors Schiavon, Stefano

More information

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS

ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS DOI: 10.2478/ace-2014-0005 ARCHIVES OF CIVIL ENGINEERING, LX, 1, 2014 NUMERICAL INVESTIGATIONS OF EFFECT OF INDOOR AIR QUALITY ON THERMAL COMFORT IN RESIDENTIAL BUILDINGS M. KRZACZEK 1, J. TEJCHMAN 2 The

More information

Scope of application. Definitions. Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health

Scope of application. Definitions. Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health Translation from Finnish Legally binding only in Finnish and Swedish Ministry of Social Affairs and Health Decree of the Ministry of Social Affairs and Health on Health-related Conditions of Housing and

More information

Air-tightness, Carbon Emissions & Health The case for a balanced approach

Air-tightness, Carbon Emissions & Health The case for a balanced approach Air-tightness, Carbon Emissions & Health The case for a balanced approach Partner Nick Research Cullen hoare & lea Development consulting engineers Hoare Lea & Partners Consulting Engineers Definitions

More information

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES

MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES MODELLING AND SIMULATION OF BUILDING ENERGY SYSTEMS USING INTELLIGENT TECHNIQUES Ph.D. THESIS by V. S. K. V. HARISH ALTERNATE HYDRO ENERGY CENTRE INDIAN INSTITUTE OF TECHNOLOGY ROORKEE ROORKEE-247667 (INDIA)

More information

Comparison of emission specifications in the US and in Europe

Comparison of emission specifications in the US and in Europe Indoor Air 2008, 17-22 August 2008, Copenhagen, Denmark - Paper ID: 954 Comparison of emission specifications in the US and in Europe Thomas Neuhaus * and Reinhard Oppl Eurofins Product Testing A/S, Denmark

More information

AIR FILTRATION in HVAC Systems

AIR FILTRATION in HVAC Systems 11.as Jornadas de Climatização 2011 October 13 th AIR FILTRATION in HVAC Systems REHVA GUIDEBOOK NO 11 Jan Gustavsson Sweden Copyright/jg 2011-10-09 1 Filtration Guidebook Aimed for designers, manufacturers,

More information

Where,h(t)the indicial response of thermal flow rate, B 0 the

Where,h(t)the indicial response of thermal flow rate, B 0 the This paper presents the results of investigations that were made on a simulation program, which calculates the temperature, the heat loads, the ventilation rates and the indoor air quality considering

More information

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Influence of Intermittent Exposure of Odor on Odor Intensity and Olfactory Adaptation

Healthy Buildings 2017 Europe July 2-5, 2017, Lublin, Poland. Influence of Intermittent Exposure of Odor on Odor Intensity and Olfactory Adaptation Healthy Buildings 07 Europe July -5, 07, Lublin, Poland Paper ID 098 ISBN: 978-8-797-- Influence of Intermittent Exposure of Odor on Odor Intensity and Olfactory Adaptation Hiromi Yamada,*, Shin-ichi Tanabe,

More information

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016

Aalborg Universitet. CLIMA proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols. Publication date: 2016 Aalborg Universitet CLIMA 2016 - proceedings of the 12th REHVA World Congress Heiselberg, Per Kvols Publication date: 2016 Document Version Publisher's PDF, also known as Version of record Link to publication

More information

http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se http://www.sis.se SVENSK STANDARD SS-EN 15316-2-1:2007 Fastställd 2007-08-03 Utgåva 1 Värmesystem i byggnader Metod för beräkning

More information

Calculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems

Calculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems AHRI Guideline V (I-P) 20 Guideline for Calculating the Efficiency of Energy Recovery Ventilation and its Effect on Efficiency and Sizing of Building HVAC Systems IMPORTANT SAFETY DISCLAIMER AHRI does

More information

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE

IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE IMPLICATIONS OF CLIMATE CHANGE AND OCCUPANT BEHAVIOUR ON FUTURE ENERGY DEMAND IN A ZERO CARBON HOUSE Halla Huws and Ljubomir Jankovic Birmingham School of Architecture Birmingham Institute of Art and Design,

More information

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features

ACTIVA Rooftop. YKN2open. ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw. Nomenclature A R C 045 B B. Features ACTIVA Rooftop ARC-ARG-ARH-ARD A complete range from 48 kw up to 84 kw YKN2open Features High efficiency EER and COP Low noise level All configurations: Cooling only, Cooling + gas, Heating, Heating +

More information

INDOOR CLIMATE IMPACT ON RETAIL SALES:A LITERATURE REVIEW

INDOOR CLIMATE IMPACT ON RETAIL SALES:A LITERATURE REVIEW INDOOR CLIMATE IMPACT ON RETAIL SALES:A LITERATURE REVIEW AC Boerstra *, JL Leyten BBA Indoor Environmental Consultancy,P.O. Box 774, 3000 AT Rotterdam, the Netherlands ABSTRACT Studies in other IEQ (Indoor

More information

Do Risks Outweigh Potential Rewards?

Do Risks Outweigh Potential Rewards? The following article was published in ASHRAE Journal, October 2004. Copyright 2004 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

Lesson 29 Inside And Outside Design Conditions. Version 1 ME, IIT Kharagpur 1

Lesson 29 Inside And Outside Design Conditions. Version 1 ME, IIT Kharagpur 1 Lesson 29 Inside And Outside Design Conditions Version 1 ME, IIT Kharagpur 1 The specific objectives of this lecture are to: 1. Describe a typical air conditioning system and discuss the need for fixing

More information

Asset Energy Calculator Guidance

Asset Energy Calculator Guidance Asset Energy Calculator Guidance Introduction This section has been produced to give BREEAM In-Use assessors further guidance on the workings of the asset energy calculator so it is clear how any improvements

More information

Trends and drivers in the Finnish ventilation and AC market

Trends and drivers in the Finnish ventilation and AC market Trends and drivers in the Finnish ventilation and AC market Jarek Kurnitski, D.Sc. Docent Helsinki University of Technology Finnish Society of Indoor Air Quality and Climate, FiSIAQ 1 Contents Indoor climate

More information

Whole Building Energy Performance Evaluation through. Similar Control Strategies

Whole Building Energy Performance Evaluation through. Similar Control Strategies Whole Building Energy Performance Evaluation through Similar Control Strategies S.H. Cheon 1, Y.H. Kwak 1, C.Y. Jang 2, and J.H. Huh 1* 1 Department of Architectural Engineering, University of Seoul, Seoul

More information

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions

Ventilation Solutions in Renovated Apartment Buildings in Cold Climate Conditions Engineering, 2015, 7, 129-139 Published Online March 2015 in SciRes. http://www.scirp.org/journal/eng http://dx.doi.org/10.4236/eng.2015.73011 Ventilation Solutions in Renovated Apartment Buildings in

More information

APPLICATION OF OPTIMIZATION METHOD TO ACTUAL CENTRAL AIR CONDITIONING SYSTEMS

APPLICATION OF OPTIMIZATION METHOD TO ACTUAL CENTRAL AIR CONDITIONING SYSTEMS Proceedings of Building Simulation : th Conference of International Building Performance Simulation Association, Sydney, -6 November. APPLICATION OF OPTIMIZATION METHOD TO ACTUAL CENTRAL AIR CONDITIONING

More information

The Heating Curve Adjustment Method

The Heating Curve Adjustment Method The Heating Curve Adjustment Method Clima 2000 paper P343 topic 10 "Software" W. Kornaat and H.C. Peitsman TNO Building and Construction Research The Netherlands The Heating Curve Adjustment Method by

More information

Air Conditioning Inspections for Buildings Assessing Equipment Sizing

Air Conditioning Inspections for Buildings Assessing Equipment Sizing Air Conditioning Inspections for Buildings Assessing Equipment Sizing PRESENTED BY NIRAJ MISTRY aircon@stroma.com Size V s Load Regulation 22 of EPB Regulations The inspection report must include an assessment

More information

Indoor Air Quality Program

Indoor Air Quality Program Environmental Health and Safety Office Indoor Air Quality Program The purpose of this program is to inform the University community about indoor air quality (IAQ). Adopted: May 28, 2008 Revised: April

More information

Application of a cooling tower model for optimizing energy use

Application of a cooling tower model for optimizing energy use Advances in Fluid Mechanics X 305 Application of a cooling tower model for optimizing energy use G. C. O Mary & D. F. Dyer Department of Mechanical Engineering, Auburn University, USA Abstract The overall

More information