Measurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276)

Size: px
Start display at page:

Download "Measurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276)"

Transcription

1 University of Nebraska - Lincoln From the SelectedWorks of David Yuill Spring May, 2008 Measurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276) David P Yuill, University of Nebraska-Lincoln Grenville K Yuill Andrew H Coward Available at:

2 2008, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. ( For personal use only. Additional reproduction, distribution, or transmission in either print or digital form is not permitted without ASHRAE s prior written permission. VOLUME 14, NUMBER 3 HVAC&R RESEARCH MAY 2008 Measurement and Analysis of Vitiation of Secondary Air in Air Distribution Systems (RP-1276) David P. Yuill Grenville K. Yuill, PhD Andrew H. Coward Member ASHRAE Fellow and Life Member ASHRAE Received July 23, 2007; accepted February 6, 2008 This paper is based on findings resulting from ASHRAE Research Project RP Appendix A of ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality, describes the recycling of unvitiated ventilation air in a recirculating air-handling system. Equation A-2 considers air delivered through the primary air path (central air distribution system) and secondary air paths, such as fan-powered boxes or transfer-air fans. It contains a variable,, that describes the extent to which the secondary air comes from the zone in question, as opposed to coming from average system return air. This paper describes the development of an equation that can be used to quantify, and shows the results of the first experimental measurements of. For these measurements, tracer gas experiments were carried out on an office building in Omaha, Nebraska. The study showed that the theoretical range of is from zero to infinity. Its range in the test building is from 0.74 to 1.01 as built, but could range from 0.14 to 1.13 if the fan-powered boxes had been located in different, but realistic, locations. These findings contradict the standard, which defines as ranging from 0 to 1. INTRODUCTION ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality, (ASHRAE 2007) specifies minimum ventilation rates and other measures intended to provide indoor air quality conditions that will be acceptable to occupants of buildings and that minimize the potential for adverse health effects. Standard 62 was first published in 1973 and has undergone many revisions, including substantial changes to the amount of outdoor air that must be provided to occupied areas, and to the procedure for calculating these amounts. One of these revisions was the introduction of the multiple spaces equation (MSE). The MSE can be applied to buildings that use a recirculating system one that recirculates some portion of air returned from the occupied zones in its supply air. The MSE is based on a mass balance. It accounts for the fact that only the critical zone a zone that requires the highest fraction of ventilation air in its supply air will produce fully vitiated air (where fully vitiated air is air from zones that receive exactly the minimum ventilation rate required by the standard, and ventilation air is a combination of outdoor air and recirculated return air that is not fully vitiated). All other zones receive more outdoor air than the minimum required, so that the return air from those zones contains some unvitiated air. This unvitiated air is recirculated, so the amount of new ventilation air that must be introduced is lower than if this effect were ignored. David P. Yuill is president and Andrew H. Coward is a research scientist at Building Solutions, Inc., Omaha, NE. Grenville K. Yuill is director of the Charles W. Durham School of Architectural Engineering and Construction, University of Nebraska, Lincoln, NE. 345

3 346 HVAC&R RESEARCH Originally, the MSE accounted only for single-path air distribution systems. Warden (1995) pointed out that a secondary path one that does not pass through the central air handler could also be used to help ventilate the critical zone. He presented a general case of the MSE that accounted not only for the primary path, as the earlier MSE does, but also for secondary paths, such as dual-fan dual-duct systems, fan-powered terminal units, and transfer fans. Ke (1997) also developed a generalized MSE with a different form, but consistent with Warden s derivation. The general case of the MSE was included as Equation A-2 in the 2004 version of ASHRAE Standard To use the general case of the MSE for ventilation calculations requires knowledge of two additional variables not previously considered. In the nomenclature of the standard, these are E p (the primary air fraction to the zone, i.e., the ratio of primary airflow to total discharge flow) and. The first of these variables is straightforward, a fraction of two quantities typically known by a designer. The variable,, however, is more complex and is the subject of this paper. DEFINITION OF ASHRAE Standard defines as the fraction of secondary recirculated air to the zone that is representative of average system return air rather than air directly recirculated from the zone. No quantitative definition is provided, but guidance in selecting a value is given in a note: For plenum return systems with local secondary recirculation (e.g., fan-powered VAV with plenum return), 1.0. For ducted return systems with local secondary recirculation (e.g., fan-powered VAV with ducted return), typically = 0.0. The general case of the MSE (Equation A-2 in the standard) is shown in expanded form in Equation 1. ( E p + ( 1 E p ) ) + X s E p Z d [ 1 ( 1 E z ) ( 1 ) ( 1 E p )] E vz = E p + ( 1 E p ) (1) where E p = V pz / V dz E vz = the ventilation efficiency of the zone in question E z = the effectiveness of the zone air distribution system in delivering ventilation air to the breathing zone (zone air distribution effectiveness) V dz = discharge flow rate to the zone V ou = uncorrected outdoor air intake; required intake if system ventilation efficiency were 1.0 V oz = outdoor airflow rate to the zone V ps = primary airflow rate to all zones served by the system V pz = primary airflow rate to the zone X s = V ou / V ps Z d = V oz / V dz Most of these quantities are depicted in a schematic shown in Figure 1. With the exception of, all of the variables used in Equation 1 can be calculated from values known or defined in the system design process. Quantifying requires some assumptions to be drawn about the exact meaning of the qualitative definition given in the standard, as well as knowledge about the mixing and airflows in the region that the secondary air is drawn from. If the secondary air is a proportionate mix of return air from all zones in the system, then = 1.0. Note that vitiation, as discussed in this paper, does not relate to concentrations of pollutants. Rather, it refers to the amount of ventilation air in a sample that exceeds or falls short of the ventilation rate prescribed by the standard.

4 VOLUME 14, NUMBER 3, MAY Figure 1. Schematic of airflows used in the multiple spaces equation. To develop a quantitative definition of, let U represent the fraction of unvitiated air in a given sample. Consider the fraction of unvitiated air in the secondary air for the critical zone, U sz, and in the system return air, U rs. U sz can be evaluated by taking a weighted average of unvitiated outdoor air fractions in all of the constituents of the secondary air. i = 0m i U U i sz = n m sz (2) If the air density is assumed to be constant for each airstream, then volumetric flow rates can be used in place of mass flow rates, and the secondary airflow rate can be expressed using terms from ASHRAE Standard for a system with n zones contributing to the secondary air. n V U i = 0 iu i sz = = V sz n i = 0V iu i ( 1 E p )V dz (3) is defined by dividing the unused outdoor air fraction in the secondary air by the unused outdoor air fraction in the system s return air. U sz = U rs (4) The term U rs, the fraction of unused outdoor air in the system return air, can be expressed using the ventilation efficiency term, E v, from ASHRAE Standard Since E v is a function of, this is an iterative calculation. U rs = 1 E v (5)

5 348 HVAC&R RESEARCH The study described in this paper included field measurements of. To determine, an alternate equation was derived for use with tracer gas measurements. This derivation is based on a tracer gas mass balance at the inlet to the fan-powered box. The concentration at the inlet is denoted C fpb, the return air concentration is C ret, and the zone concentration is. C fpb ( 1 E p )V dz = ( 1 )( 1 E p )V dz + C ret ( 1 E p )V dz (6) This is simplified to C fpb = ( 1 ) + C ret. (7) Solving for gives C fpb = C ret (8) During this test the building was treated as a laboratory assumptions about occupancy and space usage could be made arbitrarily. Therefore, we assumed that all non-critical zones were equally vitiated. Note that this gives an identical outcome to a well-mixed return plenum with zones that are not equally vitiated. A less obvious but important fact is that the magnitude of the concentration of the other zones does not affect the result. This is shown in the discussion of validity, below. RANGE OF If we assume that representative of average system return air means having the same vitiation as average system return air, then can be greater than one. A value of greater than one occurs when secondary air is less vitiated than average system return air. If half of the zones in a building are less vitiated than the average and half are more vitiated, it is not unrealistic to draw return air from a location where it is less vitiated than the average system return air. In a small system, values much greater than one are possible. The following example illustrates a calculation of using Equation 8. In this example, is greater than one. Consider a three-zone building with a common return duct. If the air from all three zones is well-mixed at some point in the return duct, that air can be assumed to be representative of average system return air, so is 1.0 if the secondary air is drawn from this point. However, consider the case in which the secondary air is drawn from a location that has air less vitiated than the fully mixed return air, as in Figure 2. Assume the flow rates and zone vitiation percentages as shown in Figure 2. The total return flow is 3000 cfm (1416 L/s), of which 2000 cfm (944 L/s) comes from the critical zone. Weighted averages are calculated to determine the vitiated fraction of the secondary air (65%) the unvitiated fraction (U sz = 35%), and the system return air (88.3% vitiated), so U rs = 11.7%. Then is calculated with Equation 4 as follows: U sz = = = U rs (9) Using the tracer gas formulation for (Equation 8) gives the same result. C fpb = = = C ret (10)

6 VOLUME 14, NUMBER 3, MAY Figure 2. Schematic of flow paths for example calculation. This example shows that can be greater than one. In fact, the upper limit of is unbounded. The extreme case, where all of the return air from the other zones is used as secondary air in the critical zone gives an infinite value of. Quantitatively, this is because there is no unvitiated air in the return air (U rs = 0). Qualitatively, this is because if the secondary air has some quantity of unvitiated air, it is infinitely cleaner than the fully vitiated return air. (If the return air from the other zones has no unvitiated air, then all zones are critical zones, and is undefined.) A final observation about is that it is defined only for the fully vitiated critical zone; thus, its lower bound is zero. If were applied to a noncritical zone, it is possible that the secondary air could be more vitiated than the zone, in which case would be negative. EXPERIMENTAL SETUP The variable was measured with the use of tracer gas tests in a five-story office building located in Omaha, Nebraska. This building is 130,000 ft² (12,100 m²) and is served by two large, single-duct, variable-air-volume air handlers with a design capacity of 65,000 cfm (30,700 L/s) each. The air handlers serve 134 pressure-independent air terminal units (ATUs), of which 87 are parallel fan-powered boxes (FPB). The zones have a shared ceiling-plenum return path (i.e., unducted on each floor). This building was built in Four zones in the building were selected to serve as nominal critical zones. Each of these zones is an enclosed office or conference room, and is served by an FPB. Sulfur hexafluoride (SF 6 ) tracer gas was released into the test zone through a mixing and dispersal system. To eliminate the confounding variable of stratification due to room air distribution imperfections, the test zone was fully mixed with several large mixing fans (the mixing was confirmed experimentally). Measurements were made periodically over several hours as the concentration rose and while it was at steady state. The variable was calculated by evaluating Equation 8 using arithmetic averages of seven concentration measurements at steady state. During the tests the air handlers were configured to use 100% outdoor air. This prevented another confounding variable: imperfect mixing of all of the non-test zones. Since the essence of the experiment is to determine how much of the air drawn into the FPB comes from the critical

7 350 HVAC&R RESEARCH zone, it is necessary that there be only two zonal concentrations: the critical zone concentration and the other zones concentration. During the test the other zones concentrations were zero, as confirmed by measurements. Three test conditions were studied. 1. All adjacent zones at minimum flow. Zones that are served by FPB have the fans running. 2. All adjacent zones at design flow with no FPB fans running. The critical zone is at minimum flow with its FPB fan running. 3. Identical to (1) except that no FPB fans are running except the critical zone s. This condition was only tested for one zone. Conditions 1 and 2 were tested for each of the four test zones. Some of these tests were repeated once or twice to evaluate experimental repeatability. A total of 13 tests were conducted. During this experiment several additional parameters were measured. These data were intended to allow other analyses, to detect or troubleshoot experimental problems, and to provide redundant, but less certain, results. They include airflow measurements, pressure differentials across each test zone s walls and partitions, temperature and humidity of indoor and outdoor air, wind direction and speed, and tracer concentrations in several other locations. Since these data are not used to calculate the results in this paper, they are not reported here. EXPERIMENTAL RESULTS AND DISCUSSION An example of the raw data from one test is shown in Figure 3. In this figure the concentration in the test zone reaches steady state after about one hour. Error bars represent the uncertainty associated with tracer gas measurements (3%), as stated by the manufacturer of the analyzer. Concentration measurements were made in the breathing zone (a location four feet [1.2 m] above the floor near the center of the room) in the return grille, which should be similar to the breathing zone if the room is well-mixed, and in the secondary air inlet, where the FPB draws air from the ceiling plenum. Figure 3. Example of SF 6 measurements.

8 VOLUME 14, NUMBER 3, MAY The return concentration, C ret, is absent from this list. The return concentration was calculated, rather than being measured, for two reasons. The first is that the clean return air from the dozens of other zones diluted the tracer gas to a very low concentration in the system return air. The concentration is below the accurate range of the gas chromatograph that was used to measure the concentration. The second reason is that the return air is highly stratified, even after passing through the return fan, so a measurement would be meaningless. This was confirmed by experimentation. Any attempt to mix the return air would interfere with the normal return path, damaging the validity of the experiment. Instead of measuring the return concentration, it was calculated by multiplying the concentration in the test zone,, by the portion of the total discharge air that comes from the test zone. C ret = V dz,test V dz (11) The discharge airflow rates to all zones were set to constant values during testing. The research team recalibrated the flow stations on all ATUs prior to conducting the experiment. Since C ret is very low, the result is very insensitive to C ret, so that any error associated with this approach has no significant effect. The results of the tests are shown in Table 1. These results reference the four test zones that are located as shown in Figure 4. The variable ranges from 0.74 to One question that was considered is: does the status of the other ATU (for example, whether they are on maximum or minimum flow, and whether FPB fans are running) affect the results? Table 2 has the results of similar tests grouped together for easier comparison. Although the data set is too small for definitive conclusions, there appears to be no correlation between adjacent zones ATU status and. In Zone A, is higher when the adjacent zones are on design flow, but the opposite is true for Zone C. In Zones B and D, is essentially unaffected by ATU status. These results are not surprising because depends on the airflow patterns in the ceiling plenum, which vary depending on the physical layout of each zone. For a Table 1. Test Results Test ID Zone Adjacent Zones Er 1 C Minimum a 0.85 Er 2 C Minimum 0.94 Er 3 C Minimum 0.82 Er 4 C Design 0.94 Er 5 D Minimum 0.92 Er 6 D Design 1.01 Er 7 B Minimum 0.74 Er 8 B Design 0.84 Er 9 A Minimum 0.74 Er 10 A Design 0.91 Er 11 A Minimum 0.75 Er 12 A Design 0.99 Er 13 A Minimum 0.79 a Adjacent zone FPB fans were off for Test 1. In all other minimum flow cases, they were on.

9 352 HVAC&R RESEARCH Figure 4. Test zone locations. Table 2. Grouped Results of Similar Tests Test ID Zone Adjacent Er 10 A Design 0.91 Er 12 A Design 0.99 Mean 0.95 Er 9 A Minimum 0.74 Er 11 A Minimum 0.75 Er 13 A Minimum 0.79 Mean 0.76 Er 8 B Design 0.84 Er 7 B Minimum 0.74 Er 4 C Design 0.94 Er 2 C Minimum 0.94 Er 3 C Minimum 0.82 Mean 0.88 Er 6 D Design 1.01 Er 5 D Minimum 0.92

10 VOLUME 14, NUMBER 3, MAY Table 3. Standard Deviation of Data Test ID Zone Adjacent Er 10 A Design 0.91 Er 12 A Design 0.99 Mean 0.95 Std. Dev % Er 9 A Minimum 0.74 Er 11 A Minimum 0.75 Er 13 A Minimum 0.79 Mean 0.76 Std. Dev % Er 2 C Minimum 0.94 Er 3 C Minimum 0.82 Mean 0.88 Std. Dev % given zone, therefore, we can conclude that may or may not vary with adjacent ATU status, and, if it varies, it may increase or decrease. In Table 3 the standard deviation is calculated for each set of data from tests that were made under identical conditions. This gives an indication of the repeatability of the testing. The standard deviation is also presented as a percentage of the average value. The most meaningful repeatability data come from tests 9, 11, and 13 because there are three data. In this case the standard deviation is 4% of the average value. To extend the results of this study, a second kind of test was developed. In this test, referred to as a grid map test, tracer gas was released in one test zone, as in previous tests, but tracer gas samples were taken from approximately 100 locations in the nearby ceiling plenum that are potential locations of an FPB. The locations are laid out in a 4 ft (1.2 m) grid pattern in the region near the test zone, and in an 8 ft (2.4 m) grid in further regions.the values of were calculated for each of these sets of concentration measurements, and then bi-linearly interpolated to create the grid maps shown in Figures 5 and 6. Figure 5 shows the results of a test with adjacent ATU at minimum and all FPB fans on, superimposed on a mechanical system plan. Figure 6 shows the results of a test with adjacent ATU at design flow. In these figures solid black regions indicate barriers to flow that are present in the ceiling plenum. In Figure 5, an FPB placed in a region near the test zone would have values as low as A beam runs from the top of the drawing downward, starting at the column located between the test zone and the adjacent office. This beam appears to cause return air from the test zone to collect before dissipating downstream toward the return air duct inlet. In this test, the repositioning of an FPB by only 10 ft (3 m) could cause to increase from 0.1 to 0.9 in some areas.

11 354 HVAC&R RESEARCH Figure 5. grid map with adjacent zones ATU on minimum flow and FPB fans on.

12 VOLUME 14, NUMBER 3, MAY Figure 6. grid map with adjacent zones ATU on maximum flow and FPB fans off.

13 356 HVAC&R RESEARCH Figure 6 shows that a very different flow pattern exists when the adjacent zones are at maximum flow. These tests give a general sense as to the size of the mixing plume downstream of a particular zone in a ceiling plenum. Most importantly, they show that carefully locating the FPB is critical to achieving an efficient ventilation design. One might conclude from an examination of the grid map results that the practical minimum value of is 0.1. However, if the flow of return air from the critical zone passed through a constriction, such as a transfer boot, a plume of concentrated return air could likely cause values much lower than 0.1 if the FPB were located in this plume. VALIDITY Vitiation of Other Zones Since the building was unoccupied during experimental testing, any assumption about occupancy could be made. We assumed that occupants, or other sources of vitiation, were distributed such that the return air from all zones except the critical zone was equally vitiated. This assumption allowed the experiment to be conducted using a single tracer gas. It also allows airflow rates to be used to determine concentrations and vice versa. It seems that tracer gas in the test zone and concentrations of zero in adjacent zones could not accurately represent a real building in which there are concentrations of pollutant everywhere. The following example shows that this experiment gives the same result as if there were tracer gas sources (emulating pollutants) evenly distributed throughout the building. Assume 1000 cfm (472 L/s) of primary air is delivered to the critical zone, and 9000 cfm (4250 L/s) is delivered to all other zones. The critical zone s FPB draws 1000 cfm (472 L/s) of secondary air, of which 30% is from the critical zone. The critical zone is 100% vitiated, and the other zones are 0%. Therefore, C fpb is 30%, and C ret is 20%. Evaluating Equation 8 for this scenario gives C fpb = = = C ret (12) Now assume the other zones are 90% vitiated instead of 0%. This means that C fpb is 93%, and C ret is 92%. Evaluating Equation 8 for this scenario gives C fpb = = = C ret (13) The result, 0.875, is unaffected by the concentration in the other zones because in a two-concentration system, a ratio of airflows is a perfect proxy for concentrations. Unless the airflows change, remains constant. The general case of, in Equation 4, gives identical results in this example. SUMMARY AND CONCLUSIONS Two equations for have been derived. The first is based on a mass balance of unvitiated air in the critical zone; the second is based on a mass balance of tracer gas at the inlet to an FPB. The theoretical range of for a critical zone has been shown to be from zero to infinity. Experiments on an existing building have been conducted, and the resulting values of ranged from 0.74 to 1.01 as built, but could have ranged from 0.14 to 1.13 if the FPB had been located in different, but feasible, locations. The findings of this study contradict ASHRAE Standard , which defines as ranging between 0 and 1. It is now clear that

14 VOLUME 14, NUMBER 3, MAY values greater than one are possible, since locally recirculated air can be less vitiated than average return air. ACKNOWLEDGMENTS The authors would like to acknowledge the great efforts and insight of the monitoring subcommittee for this project: Steve Taylor, Craig Wray, Iain Walker, and Jim Reardon. We are also grateful to Dennis Stanke for his careful review of the results. REFERENCES ASHRAE ANSI/ASHRAE Standard , Ventilation for Acceptable Indoor Air Quality. Atlanta: American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Ke, Y.P Optimum ventilation control for variable-air-volume systems. PhD thesis, Department of Mechanical Engineering, Pennsylvania State University, State College, PA. Warden, D Outdoor air Calculation and delivery. ASHRAE Journal 37(6):54 63.

TO Stanley A. Mumma, Ph.D., P.E.

TO Stanley A. Mumma, Ph.D., P.E. TO-98-21-3 Extension of the Multiple Spaces Concept of ASHRAE Standard 62 to Include Infiltration, Exhaust/Exfiltration, Interzonal Transfer, and Additional Short-Circuit Paths Stanley A. Mumma, Ph.D.,

More information

Dynamic Reset for Multiple-Zone Systems

Dynamic Reset for Multiple-Zone Systems This article was published in ASHRAE Journal, March 2010. Copyright 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Posted at www.ashrae.org. This article may not be

More information

Technical Assignment #1. ASHRAE Standard Ventilation Compliance Evaluation Report

Technical Assignment #1. ASHRAE Standard Ventilation Compliance Evaluation Report Technical Assignment #1 ASHRAE Standard 62.1-2004 Ventilation Compliance Evaluation Report Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical

More information

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based

Ventilation. Demand-controlled ventilation (DCV) Demand-Controlled. With ASHRAE Standard Based CO Demand-Controlled 2 -Based Ventilation With ASHRAE Standard 62.1 Though not as straightforward as it once was, remains a practical way to reduce costs Editor s note: Following is an update of the November

More information

newsletter The significance of 62n

newsletter The significance of 62n engineers volume 33 1 newsletter providing insights for today s hvac system designer Addendum 62n breathes new life into ASHRAE Standard 62 PRECIS Addendum 62n revises the entire Ventilation Rate Procedure,

More information

ASHRAE Standard : Ventilation Rate Procedure

ASHRAE Standard : Ventilation Rate Procedure engineers newsletter live Course Outline ASHE Standard 62.1-2004: Ventilation Rate Procedure This presentation covers the Ventilation Rate Procedure for calculating zone and system ventilation airflow,

More information

ASHRAE Standard 62.1 Ventilation Report

ASHRAE Standard 62.1 Ventilation Report Mechanical Technical Report 1 ASHRAE Standard 62.1 Ventilation Report The nue New York, NY 10022 Faculty Advisor: Dr. Jelena Srebric October 5, 2005-1 - Table of Contents 1.0 Executive Summary 2.0 Building

More information

Compliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality

Compliance Evaluation: ASHRAE Standard Ventilation for Acceptable Indoor Air Quality Compliance Evaluation: ASHRAE Standard 62.1-2001 Ventilation for Acceptable Indoor Air Quality Photo rendering courtesy of Hooper Shiles Architects Philadelphia School District Administration Headquarters

More information

Terminal. 3 Las Vegas, NV. Technical

Terminal. 3 Las Vegas, NV. Technical McCarran International port Terminal 3 Technical Assignment 1 ASHRAE Standard 62.1 2007 Compliance Evaluation October 5, 2007 Prepared By: Jason A. Witterman Faculty Advisor: Dr. William Bahnfleth, Ph.D.,

More information

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality

Proposed Addendum L to Standard , Ventilation for Acceptable Indoor Air Quality BSR/ASHRAE Addendum L to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum L to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality Second Public Review (August 2018) (Draft

More information

Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation

Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation Mechanical Option Technical Report #1 Technical Report #1 ASHRAE Standard 62: Ventilation Compliance Evaluation Instructor: Dr. Srebric 10.06.04 Building Sponsors: CCG Facilities Integration Table of Contents

More information

ASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality

ASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality ANSI/ASHRAE Addenda g, r, and t to ANSI/ASHRAE Standard 62.1-2007 ASHRAE STANDARD Ventilation for Acceptable Indoor Air Quality Approved by the ASHRAE Standards Committee on January 23, 2010; by the ASHRAE

More information

CO 2 -Based DCV Using

CO 2 -Based DCV Using 2006 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Journal (Vol. 48, May 2006). For personal use only. Additional distribution in

More information

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation

Mechanical Technical Assignment One ASHRAE Standard Compliance Evaluation Mechanical Technical Assignment One ASHRAE Standard 62.1-2007 Compliance Evaluation The Prepared By: Maxwell S. Chien October 5 th, 2007 Prepared For: Dr. William P. Bahnfleth, Ph.D., P.E., Professor Department

More information

The Palestra Building London, England

The Palestra Building London, England Architectural Renderings compliments of Alsop Architects Ventilation Report Becca Allen The Pennsylvania State University Architectural Engineering AE 481W, Fall 2005 Table of Contents I. Executive Summary

More information

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory

Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Lawrence Berkeley National Laboratory Title Real-Time Measurement of Rates of Outdoor Airflow into HVAC Systems: A Field Study of Three Technologies Permalink https://escholarship.org/uc/item/3rf221fw

More information

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT

HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT HVAC SYSTEM CONFIGURATIONS, AN ENERGY ASPECT Y Zhang 1,*, JA Wright 2 and VI Hanby 1 1 Institute of Energy and Sustainable Development, De Montfort University, Leicester, LE1 9BH, UK 2 Department of Civil

More information

DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA

DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA Student: David M. Potchak Mechanical Option Faculty Consultant: Jae-Weon Jeong October 5, 2006 DEA Clandestine Laboratory Training Center Quantico Marine Corps Base, Quantico, VA Mechanical Technical Report

More information

Ventilation for Changeover-Bypass VAV Systems

Ventilation for Changeover-Bypass VAV Systems Copyright 2004, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. This posting is by permission of ASHRAE Journal. This article may not be copied nor distributed in either

More information

in UFAD Systems The control of room-air stratification is Design Guidelines for Stratification

in UFAD Systems The control of room-air stratification is Design Guidelines for Stratification Design Guidelines for Stratification in UFAD Systems Guidance for sizing interior and perimeter zones of underfloor-air-distribution systems Editor s note: This is the first of two articles based largely

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

LESSONS LEARNED IN MODELING UNDERFLOOR AIR DISTRIBUTION SYSTEM

LESSONS LEARNED IN MODELING UNDERFLOOR AIR DISTRIBUTION SYSTEM LESSONS LEARNED IN MODELING UNDERFLOOR AIR DISTRIBUTION SYSTEM Kwang Ho Lee 1, 2, Stefano Schiavon 1, Tom Webster 1, Fred Bauman 1, Jingjuan Feng 1, Tyler Hoyt 1 1 Center for the Built Environment, University

More information

What s My Baseline? ASHRAE

What s My Baseline? ASHRAE 2010 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions (2010, vol 116,part 2). For personal use only. Additional reproduction,

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION DISPLACEMENT VENTILATION D3 OVERVIEW The fundamental approach to displacement ventilation utilizes the natural buoyancy forces created by the convective flows from heat sources in the space. As supply

More information

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation 2900 Fairview Park Drive, Prepared By: Charles Haack Mechancial Option November 21, 2008 Prepared For: Dr. William P.

More information

David S. Dougan, President Leonard A. Damiano, V.P. Sales & Marketing. EBTRON, Inc.

David S. Dougan, President Leonard A. Damiano, V.P. Sales & Marketing. EBTRON, Inc. David S. Dougan, President Leonard A. Damiano, V.P. Sales & Marketing EBTRON, Inc. It should be clear to the design professional that the dynamic nature of mechanical ventilation requires dynamic control.

More information

ASHRAE Standard Ventilation Compliance Evaluation Mechanical Technical Report #1. Bronx School for Law, Government, & Justice Bronx, NY

ASHRAE Standard Ventilation Compliance Evaluation Mechanical Technical Report #1. Bronx School for Law, Government, & Justice Bronx, NY ASHRAE Standard 62.1 2004 Ventilation Compliance Evaluation Mechanical Technical Report #1 Bronx, NY Prepared By: Yulien Wong Faculty Advisor: Dr. Jelena Srebric October 4, 2005 TABLE OF CONTENTS 1.0 EXECUTIVE

More information

Canada Published online: 28 Feb 2011.

Canada Published online: 28 Feb 2011. This article was downloaded by: [Bibliothèque ÉTS] On: 21 July 2015, At: 04:30 Publisher: Taylor & Francis Informa Ltd Registered in England and Wales Registered Number: 1072954 Registered office: 5 Howick

More information

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR

Chilled Beams Selection BY DAN INT-HOUT, FELLOW ASHRAE; AND LILLI WILBAR This article was published in ASHRAE Journal, November 2014. Copyright 2014 ASHRAE. Reprinted here by permission from ASHRAE at www.krueger-hvac.com This article may not be copied nor distributed in either

More information

Engineering Update JANUARY VOLUME 9 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 9 OF THE JANUARY 2013 ENGINEERING UPDATE.

Engineering Update JANUARY VOLUME 9 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 9 OF THE JANUARY 2013 ENGINEERING UPDATE. Engineering Update JANUARY 2013 - VOLUME 9 THIS PACKAGE INCLUDES A COLLECTION OF ARTICLES FROM VOLUME 9 OF THE JANUARY 2013 ENGINEERING UPDATE. TABLE OF CONTENTS: Two Sides to Every Noise... 1 Product

More information

Index of Addenda to ANSI/ASHRAE Standard 62.1

Index of Addenda to ANSI/ASHRAE Standard 62.1 a b in 62-1989 Published in 1990. The committee withdrew this addendum from consideration, and the issue of existing buildings was addressed by Addenda 62k and 62af. Withdrawn in September 2000. The addendum

More information

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics

Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Achieving acoustical standards in the classroom Study of HVAC systems and classroom acoustics Trane believes the facts and suggestions presented here to be accurate. However, final design and application

More information

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON

Outdoor Airflow Control Fixed point and DCV. Presented by: David S. Dougan, President EBTRON Outdoor Airflow Control Fixed point and DCV Presented by: David S. Dougan, President EBTRON OUTSIDE AIR Pressure Changes Damper Issues Intake Flow Rates (Fixed Min or DCV) OUTSIDE AIR Intake Flow Rate

More information

Depth: Mechanical Redesign

Depth: Mechanical Redesign Depth: Mechanical Redesign Redesign Objectives The most important objective of the mechanical redesign is to provide Greenbriar East with ventilation that meets the requirements of ASHRAE Standard 62-2001.

More information

Proposal: Mechanical System Redesign

Proposal: Mechanical System Redesign Proposal: Mechanical System Redesign The 959 Eighth Avenue 10019 Faculty Advisor: Dr. James Freihaut December 12, 2005 Table of Contents 1.0 Executive Summary 2.0 3.0 Proposal Obectives 4.0 Preliminary

More information

Contaminant Transport and Filtration Issues with DOAS

Contaminant Transport and Filtration Issues with DOAS 2009. American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. (www.ashrae.org). Published in ASHRAE Transactions 2009, Vol 115, Part 2. For personal use only. Additional reproduction,

More information

Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign

Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign Topic B14: Policy, standards, and regulations ASHRAE STANDARD 62.2: WHAT S NEW AND WHY Paul W FRANCISCO,* Illinois Sustainable Technology Center, University of Illinois at Urbana-Champaign *Corresponding

More information

PROPOSAL OF JAPANESE STANDARD OF THE MEASURING METHOD OF AIRFLOW RATES OF BUILDING EQUIPMENTS

PROPOSAL OF JAPANESE STANDARD OF THE MEASURING METHOD OF AIRFLOW RATES OF BUILDING EQUIPMENTS PROPOSAL OF JAPANESE STANDARD OF THE MEASURING METHOD OF AIRFLOW RATES OF BUILDING EQUIPMENTS Y. Utsumi 1, S. Hayakawa 2, T. Kurabuchi 3, and H. Yoshino 4 1 Department of Architecture, Miyagi National

More information

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins

Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Ins Numerical simulation of inter-flat pollutant dispersion routes and cross-contamination risk in high-rise residential buildings Di Mu, Naiping Gao* Institute of Thermal and Environment Engineering, School

More information

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations

Validation of a Coupled Multizone and CFD Program for Building Airflow and Contaminant Transport Simulations Wang, L. and Chen, Q. 2007. Validation of a coupled multizone and CFD program for building airflow and contaminant transport simulations, HVAC&R Research, 13(2), 267-281. Validation of a Coupled Multizone

More information

ASHRAE STANDARD 62.1 VENTILATION COMPLIANCE

ASHRAE STANDARD 62.1 VENTILATION COMPLIANCE HEALTHCARE CENTER VERONA, PENNSYLVANIA TECHNICAL ASSIGNMENT I ASHRAE STANDARD 62.1 VENTILATION COMPLIANCE Prepared by Tyler Lobb October 2, 2007 The Pennsylvania State University Department of Architectural

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs

More information

Evaluation of Underfloor Air Distribution

Evaluation of Underfloor Air Distribution McCarran International Airport Terminal 3 L as Vegas, NV Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems The Pennsylvania State University AESenior ThesisPresentation, Spring

More information

Accuracy of Flow Hoods in Residential Applications

Accuracy of Flow Hoods in Residential Applications Accuracy of Flow Hoods in Residential Applications Craig Wray, Lawrence Berkeley National Laboratory Iain Walker, Lawrence Berkeley National Laboratory Max Sherman, Lawrence Berkeley National Laboratory

More information

Estimating a Building Airflow Network using CO2 Measurements from a Distributed Sensor Network

Estimating a Building Airflow Network using CO2 Measurements from a Distributed Sensor Network Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 2010 Estimating a Building Airflow Network using CO2 Measurements from a Distributed

More information

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS

A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS A STUDY OF CROSS CONTAMINATION OF IN-SUITE VENTILATION SYSTEMS USED IN MULTI-UNIT RESIDENTIAL BUILDINGS C.A. Parker, K.D. Pressnail, M.F. Touchie, D. DeRose, and S. Dedesko ABSTRACT Complaints of cross

More information

Sound & Vibration Commissioning STUART MCGREGOR, PE ENGINEERING DYNAMICS, INC.

Sound & Vibration Commissioning STUART MCGREGOR, PE ENGINEERING DYNAMICS, INC. Sound & Vibration Commissioning 1 STUART MCGREGOR, PE ENGINEERING DYNAMICS, INC. 2 Sound and Vibration: Maintaining Tenants Spaces and Building Mechanical Systems 22 August 2018 Speaker 3 Stuart McGregor,

More information

A Method for Modifying Ventilation Airflow Rates to Achieve Equivalent Occupant Exposure

A Method for Modifying Ventilation Airflow Rates to Achieve Equivalent Occupant Exposure building science.com 2009 Building Science Press All rights of reproduction in any form reserved. A Method for Modifying Ventilation Airflow Rates to Achieve Equivalent Occupant Exposure Conference Paper

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

OPTIMAL OPERATION OF VAV AIR-CONDITIONING SYSTEM

OPTIMAL OPERATION OF VAV AIR-CONDITIONING SYSTEM Nabil NASSIF *, Stanislaw KAJ *, Robert SABOURIN * Key words: VAV system, controller set point, optimization, genetic algorithm OPTIMAL OPERATION OF VAV AIR-CONDITIONING SYSTEM The detailed and simplified

More information

ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering

ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals. Steven T. Taylor, PE Principal Taylor Engineering ASHRAE Region VI CRC Track III: Session 1 Ventilation & IAQ Fundamentals Steven T. Taylor, PE Principal Taylor Engineering This program is registered with the AIA/CES for continuing professional education.

More information

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard. 19 SECTION 3 NATURAL VENTILATION 3.1 SCOPE OF SECTION This Section specifies the means of achieving the quantity of outdoor air required in a naturally ventilated enclosure. The provisions described include

More information

Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents. Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri

Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents. Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri Spending Through the Roof: Tall Building Energy Wasted Through Passive Vents Building Energy 2017 A presentation by: Jamie Kleinberg & Robin Neri Project Objective: Develop and test methods for estimating

More information

Saving Energy in Lab Exhaust Systems

Saving Energy in Lab Exhaust Systems This article was published in ASHRAE Journal, June 211. Copyright 211 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. Reprinted here by permission from ASHRAE at www.cppwind.com.

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc (wwwashraeorg) Published in ASHE Journal Vol 48, Oct 2006 For personal use only Additional reproduction, distribution,

More information

Cooling Tower Noise Control

Cooling Tower Noise Control Providence, Rhode Island Acoustical Society of America 5-9 June 2006 Cooling Tower Noise Control Tom Paige, P.Eng. Products Application Engineer Kinetics Noise Control, Inc. Vibron Products Group Mississauga,

More information

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5)

Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Indoor Air Quality and Mechanical Ventilation (Page 1 of 5) Title 24, Part 6, Section 150.0(o) Ventilation for Indoor Air Quality. All dwelling units shall meet the requirements of ANSI/ASHRAE Standard62.2.

More information

McCarran International Airport Terminal 3

McCarran International Airport Terminal 3 McCarran International Airport Terminal 3 The Pennsylvania State University Architectural Engineering Senior Thesis Final Report Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems

More information

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Stuart S. Waterbury and Donald J. Frey, Architectural Energy Corporation Karl F. Johnson, Electric Power Research

More information

Sample Reports. for. HAP v4.90 Example Problem

Sample Reports. for. HAP v4.90 Example Problem Sample Reports for HAP v4.90 Example Problem December, 2014 Carrier Software Systems Copyright 2014 Carrier Corporation, All Rights Reserved Introduction This document contains reports generated using

More information

IAQ & Energy Impact of Exhaust Air Transfer Ratio

IAQ & Energy Impact of Exhaust Air Transfer Ratio This article was published in ASHRAE Journal, November 207. Copyright 207 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM

Implementing Demand Controlled Ventilation to Meet ASHRAE Standard By KlasC. Haglid, P.E., R.A., CEM Implementing Demand Controlled Ventilation to Meet ASHRAE Standard 62.1-2010 By KlasC. Haglid, P.E., R.A., CEM 1 Klas C. Haglid, P.E., R.A., CEM - Bio ASHRAE Distinguished Service Award 2011 ASHRAE Handbook,

More information

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings

A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings A Field Study of Airflow in Mid to High-Rise Multi-Unit Residential Buildings Lorne Ricketts, MASc, EIT John Straube, PhD, P.Eng. ABSTRACT Airflow into, out of, and within buildings is a fundamental factor

More information

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia

WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia TECHNICAL REPORT I ASHRAE STANDARDS 62.1 AND 90.1 COMPLIANCE EVALUATION 8/29/08 WEST VIRGINIA UNIVERSITY ALUMNI CENTER Morgantown, West Virginia GREGORY SMITHMYER PENN STATE UNIVERSITY ARCHITECTURAL ENGINEERING

More information

Ceiling Radiant Cooling Panels

Ceiling Radiant Cooling Panels Copyright 2006, American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc This posting is by permission from ASHE Journal This article may not be copied nor distributed in either paper

More information

UC Berkeley HVAC Systems

UC Berkeley HVAC Systems UC Berkeley HVAC Systems Title Outlook for underfloor air distribution Permalink https://escholarship.org/uc/item/5v60x57q Authors Bauman, Fred Webster, T. Publication Date 2001-06-01 Peer reviewed escholarship.org

More information

Energy aspects of HVAC system configurations problem definition and test cases

Energy aspects of HVAC system configurations problem definition and test cases Loughborough University Institutional Repository Energy aspects of HVAC system configurations problem definition and test cases This item was submitted to Loughborough University's Institutional Repository

More information

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES

Holistic Design Approach For Energy Efficiency ASHRAE TECHNOLOGY AWARD CASE STUDIES ASHRAE TECHNOLOGY AWARD CASE STUDIES This article was published in ASHRAE Journal, June 2018. Copyright 2018 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically

More information

HVAC SYSTEM SCHEMATIC DESIGN

HVAC SYSTEM SCHEMATIC DESIGN HVAC SYSTEM SCHEMATIC DESIGN Ball State Architecture ENVIRONMENTAL SYSTEMS 2 Grondzik 1 HVAC System Design Process Establish HVAC-related owner s project requirements (OPR: design issues/intents/criteria;

More information

Designing Air-Distribution Systems To Maximize Comfort

Designing Air-Distribution Systems To Maximize Comfort Designing Air-Distribution Systems To Maximize Comfort By David A. John, P.E., Member ASHRAE An air-distribution system that provides occupant thermal comfort can be a complicated system to predict and

More information

Fundamentals of Acoustics

Fundamentals of Acoustics providing insights for today s hvac system designer Engineers Newsletter volume 47 4 Understanding VAV Sound Standards Acoustics are an important and often overlooked topic in HVAC&R. Many pieces of equipment

More information

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA

IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA IDENTIFICATION OF VENTILATION PROBLEMS IN AN UNDERGROUND BUS TERMINAL IN KOREA H Han 1* and Y-I Kwon 2 1 Dept. Of Mechanical Engineering, Kookmin University, Korea 2 Dept. Of Building Mechanical Engineering,

More information

LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS

LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS R. Hutcheson, P.Eng. LEED AP, CxA, S. Jorens B.Eng., D. Knapp, PhD., P.Phys., LEED AP Arborus Consulting

More information

INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000

INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, SEPTEMBER 2000 INNOVATIONS IN VENTILATION TECHNOLOGY 21ST ANNUAL INTERNATIONAL AIVC CONFERENCE THE HAGUE, NETHERLANDS, 26-29 SEPTEMBER 2000 Impact of Ventilator Parameters on System Energy Consumption Dipak J. Shah Senior

More information

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM

COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM COMPUTER MODELING OF UNDERFLOOR AIR SUPPLY SYSTEM JJ Kim, JD Chang, and JC Park Taubman College of Architecture and Urban Planning, University of Michigan, Ann Arbor, MI, USA ABSTRACT An underfloor air

More information

While underfloor air. Learning objectives

While underfloor air. Learning objectives Displacement ventilation best practices Displacement ventilation (DV) is a low-velocity, non-turbulent cooling system for commercial buildings that is not always fully understood. Learn when and where

More information

REDUCED-ORDER ENERGY MODELING IN RETRO-COMMISSIONING: A CASE STUDY OF AN ACADEMIC BUILDING

REDUCED-ORDER ENERGY MODELING IN RETRO-COMMISSIONING: A CASE STUDY OF AN ACADEMIC BUILDING 2018 Building Performance Analysis Conference and SimBuild co-organized by ASHRAE and IBPSA-USA Chicago, IL September 26-28, 2018 REDUCED-ORDER ENERGY MODELING IN RETRO-COMMISSIONING: A CASE STUDY OF AN

More information

Project Proposal Proposal for Investigation of Alternative Systems

Project Proposal Proposal for Investigation of Alternative Systems Project Proposal Proposal for Investigation of Alternative Systems 01.15.2010 Defense Media Activity Building Fort George G. Meade Penn State University Architectural Engineering Faculty Advisor: Dr. Treado

More information

LAHU Heat Recovery System Optimal Operation and Control Schedules

LAHU Heat Recovery System Optimal Operation and Control Schedules Yujie Cui Nexant, Inc., 44 South Broadway, 5th Floor, White Plains, NY 10601 e-mail: ycui@nexant.com Mingsheng Liu Architectural Engineering, University of Nebraska Lincoln, 206C, PKI, 1110 S. 67th St.,

More information

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance

SMART LABS. Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance SMART LABS Reduce Energy Consumption, Improve Lab Safety, and Lower Deferred Maintenance From 1999 to 2016 The Georgia Institute of Technology constructed six laboratory buildings in its Bio- Quad region

More information

Terminal. 3 Las Vegas, NV

Terminal. 3 Las Vegas, NV McCarran International Airport Terminal 3 Thesiss Proposal Mechanical Systems Project Proposal December 18, 2007 Prepared By: Jason A. Witterman Faculty Advisor: Dr. William Bahnfleth, Ph.D., P..E. Table

More information

Proposed Addendum t to Standard , Ventilation for Acceptable Indoor Air Quality

Proposed Addendum t to Standard , Ventilation for Acceptable Indoor Air Quality BSR/ASHRAE Addendum t to ANSI/ASHRAE Standard 62.1-2016 Public Review Draft Proposed Addendum t to Standard 62.1-2016, Ventilation for Acceptable Indoor Air Quality Second Public Review (August 2018) (Draft

More information

Effect of room air recirculation delay on the decay rate of tracer gas concentration

Effect of room air recirculation delay on the decay rate of tracer gas concentration Effect of room air recirculation delay on the decay rate of tracer gas concentration A.R. Kristoffersen, A.J. Gadgil, D.M. Lorenzetti. Indoor Environment Department, Lawrence Berkeley National Laboratory,

More information

The influence of opening windows and doors on the natural ventilation rate of a residential building

The influence of opening windows and doors on the natural ventilation rate of a residential building The influence of opening windows and doors on the natural ventilation rate of a residential building David Marr *, Mark Mason, Ron Mosley, Xiaoyu Liu U.S. EPA, RTP, NC, USA * Corresponding email: marr.david@epa.gov

More information

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619

Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 AABC Commissioning Group AIA Provider Number 50111116 Fundamentals of Test & Balance for Engineers, Cx & Energy Providers Course Number: CXENERGY1619 Jim Hall, PE, TBE, CxA Systems Management & Balancing,

More information

DUCT SYSTEM DESIGN CONSIDERATIONS Part 2

DUCT SYSTEM DESIGN CONSIDERATIONS Part 2 Refrigeration Service Engineers Society 1666 Rand Road Des Plaines, Illinois 60016 DUCT SYSTEM DESIGN CONSIDERATIONS Part 2 by Roger M Hensley, CMS INTRODUCTION One of the most important components of

More information

DISPLACEMENT VENTILATION

DISPLACEMENT VENTILATION clever creative comfort DISPLACEMENT VENTILATION A p p l i c a t i o n G u i d e Application Guide3 Introduction to 3 Air Change Effectiveness3 Typical Applications4 Contaminant Removal4 Benefits & Limitations4

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

Mechanical Systems Project Proposal

Mechanical Systems Project Proposal Mechanical Systems Project Proposal December 15, 2006 Table of Contents 1.0 Executive Summary... 2 2.0 Building Background... 3 3.0 Proposal Objectives... 5 4.0 Initial Considerations... 6 5.0 Proposed

More information

VALIDATED CFD STUDY OF INDOOR ENVIRONMENTAL CONDITIONS IN A HIGHLY GLAZED, CROSS-VENTILATED MEETING ROOM

VALIDATED CFD STUDY OF INDOOR ENVIRONMENTAL CONDITIONS IN A HIGHLY GLAZED, CROSS-VENTILATED MEETING ROOM VALIDATED CFD STUDY OF INDOOR ENVIRONMENTAL CONDITIONS IN A HIGHLY GLAZED, CROSS-VENTILATED MEETING ROOM Magdalena Hajdukiewicz 1, 2, 3, Marco Geron 1, 2, 3 1, 2, 3, and Marcus M. Keane 1 Civil Engineering,

More information

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA

Update to ASHRAE Ventilation Standards. William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA Update to ASHRAE Ventilation Standards William P. Bahnfleth, PhD, PE, FASHRAE, FASME The Pennsylvania State University University Park, PA, USA REHVA Annual Conference Riga, Latvia May 8 9, 2015 Acknowledgements

More information

Standards for Ventilation and Indoor Air Quality in relation to the EPBD

Standards for Ventilation and Indoor Air Quality in relation to the EPBD Standards for Ventilation and Indoor Air Quality in relation to the EPBD Bjarne W. Olesen International Center for Indoor Environment and Energy Technical University of Denmark, Denmark bwo@byg.dtu.dk

More information

Mechanical Project Proposal. Indoor Multi-Sport Facility. At Pennsylvania State University

Mechanical Project Proposal. Indoor Multi-Sport Facility. At Pennsylvania State University At Pennsylvania State University Christopher Van Campen December 05, 2002 Executive summary The proposed thesis is to alleviate the of its only major problem, not enough seating capacity for the spectators

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS

ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS ENERGY EFFICIENT AIR QUALITY CONTROL IN LABORATORIES USING BENCH EXHAUSTS Farhad Memarzadeh 1, Jane Jiang 2, and Andy Manning 2 1 PhD, PE, National Institutes of Health, Bethesda, MD, USA 2 PhD, Flomerics,

More information

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal

David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option. Proposal 0 David H. Koch Institute for Integrative Cancer Research Senior Capstone Mechanical Option Proposal David H. Koch Institute for Integrative Cancer Research Massachusetts Institute of Technology Cambridge,

More information

Technology and Engineering Development (TED) Building. ASHRAE Std and Std Compliance Report

Technology and Engineering Development (TED) Building. ASHRAE Std and Std Compliance Report Technology and Engineering Development (TED) Building Thomas Jefferson National Accelerator Facility Newport News, VA Tech Report I ASHRAE Std. 62.1-2007 and Std. 90.1-2007 Compliance Report 10/4/2010

More information

ADVANCES in NATURAL and APPLIED SCIENCES

ADVANCES in NATURAL and APPLIED SCIENCES ADVANCES in NATURAL and APPLIED SCIENCES ISSN: 1995-0772 Published BYAENSI Publication EISSN: 1998-1090 http://www.aensiweb.com/anas 2017 May 11(7): pages 910-918 Open Access Journal Analysis Of Ventilation

More information

Development and Evaluation of Applicable Optimal Terminal Box Control Algorithms for Energy Management Control Systems

Development and Evaluation of Applicable Optimal Terminal Box Control Algorithms for Energy Management Control Systems sustainability Article Development and Evaluation of Applicable Optimal Terminal Box Control Algorithms for Energy Management Control Systems Yoon-Bok Seong 1 and Young-Hum Cho 2, * 1 Senior Research Engineer,

More information