Tubman African American Museum. Christopher Champagne Mechanical Option 2003 Senior Thesis

Size: px
Start display at page:

Download "Tubman African American Museum. Christopher Champagne Mechanical Option 2003 Senior Thesis"

Transcription

1 Tubman African American Museum 2003 Senior Thesis

2 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

3 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

4 Presentation Goals Investigation of the air-cooled water chillers: Museums have low load profiles during the evenings when only the exhibit spaces or anywhere artwork is stored needs to be cooled. A smaller chiller for off-hours cooling and a larger one for occupied mode. Staging of the chillers to see if an energy savings could be realized. Investigation of switching from constant speed pumping to variable speed pumping: Advantages of primary-only, variable speed pumping. Possibility of switching the chilled water pumps in this case. Should the switch be made? Investigation of current lighting system in gallery space

5 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

6 Existing Conditions Location: Atlanta, GA Use: Museum Size: 45,000 ft 2 Two stories Construction Started: October 2001 Planned Completion: Spring 2004 Construction Cost: $15.5 million

7 Design Team Architect CM/GC M/E/P Structural Exhibit Designer E. Verner Johnson and Associates, Inc. Harmon-Piedmont Construction, LLC Vanderweil Engineers Souza, True and Partners, Inc. The PRD Group, Ltd

8 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

9 Existing Mechanical System (2) ton HCFC-22 air-cooled water chillers (3) 290 GPM chilled water pumps (2) 25,000 CFM constant volume and (1) 18,000 CFM variable volume custom air handling unit.

10 Chilled Water Equipment (2) Trane Air-Cooled Water Chillers tons 290 GPM EWT = 55 F LWT = 45 F HCFC-22 Refrigerant Screw compressor (3) Bell & Gossett ½ BB Pumps 290 GPM 65 ft. head 1750 RPM 10.0 motor HP (1) Pump Standby

11 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

12 Chiller Optimization Technique The maximum cooling load is tons on July 15th at 2 pm using Atlanta Bin Data and Carrier s Hourly Analysis Program (HAP). Engineering Equation Solver (EES) was used to simulate two equal size air-cooled chillers 1. Trane Air-Cooled Series R Rotary Liquid Chillers Model RTAA 125 (Design Capacity = ton) 2. Trane RTAA 110 (Design Capacity = ton) 3. Trane RTAA 100 (Design Capacity = ton). Upper capacity that one chiller would run before the second chiller was run was varied from 85% to 100% of capacity to see which is the most efficient. The lower capacity at which the second chiller would turn off was set to 40%.

13 Chiller Optimization Equations The optimization equations used in the EES simulation are from the California Energy Commission s 2001 Non-Residential Alternative Calculation Methods (ACMs) document, specifically Chapter 2 entitled Reference Method and Required Modeling Capabilities for Alternative Calculation Methods (ACMs). The following three terms are functions of chilled water supply temperature (T chws ) and the outdoor dry-bulb temperature (T oa ). They are used to establish the efficiency of the chiller operation. CAP_FT is the full load capacity as a fraction of rated capacity. It is a capacity correction that is a function of those terms. EIR_FT is the full load efficiency (kw/ton) as fraction of rated capacity. It is an efficiency correction factor. EIR_FPLR is the fraction of full load power as a function of fraction of full load output.

14 EES Model Cases Case Model Ton kw Lower Upper Cap. (%) Cap. (%) A B C D E F G H I J K L

15 Electrical Utility Rates The electricity would be provided by Georgia Power (a subsidiary of Southern Company). PLM-3 rate which is for small to medium building size. Not less than 30 kw but less than 500 kw. Base Charge (includes first 25 kwh or less $14.00 All consumption (kwh) not greater than 200 hours 200 hours times the billing demand. First 3,000 kwh Next 7,000 kwh Next 190,000 kwh per kwh per kwh per kwh

16 Annual Operating Cost and Time Case AEC Operating Cost Operating Time Cost Operating Time (kwh) ($) (hrs) Rankings Rankings A 1,033,188 88,572 13, B 1,043,601 89,291 14, C 1,038,866 88,964 15, D 1,096,997 92,981 14, E 1,108,762 93,794 14, F 1,104,441 93,495 15, G 977,400 84,717 13, H 985,828 85,299 13, I 1,038,866 88,964 14, J 927,718 81,284 12, K 934,654 81,763 13, L 929,304 81,393 14,

17 Annual Operating Cost Annual Energy Cost 95,000 90,000 Cost ($) 85,000 80,000 75,000 A B C D E 1F G H I J K L

18 Life Cycle Cost of Chillers The following formula from CoolTools was used in the calculation of the LCC. Where: FC = first cost of plant UCj = plant utility cost for year j MCj = relative maintenance cost for year j d = discount rate N = number of years of analysis MCj = $500 d = 12 % N = 20 LCC = FC + N ( UC j + MC j ) ( 1+ d ) j= 1 Case A B C j ( ) Model Ton First Cost (FC) $96,000 $84,000 $75,000

19 Life Cycle Cost of Chillers LCC of Different Size Chillers Trane Model Number RTAA 100 RTAA 110 RTAA 125 $686, $698, $706, , , , , , , Cost ($)

20 Chiller Optimization Recommendation The RTAA 100 has the smallest life cycle cost based on the assumptions stated above. However given its tonnage being only slightly above the design cooling load, this might not be a wise selection. The RTAA 110 would still provide cost savings over the RTAA 125 (LCC savings = $10,422.14), along with some added safety to the designer. The staging should be set to 100% of capacity of the first chiller before the second chiller is turned on.

21 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

22 Chilled Water Pumping One method of saving energy used by a building is changing the primary pumps of a primary-only, chilled water system from constant speed to variable speed. Important Considerations: Does the chilled water system meets the requirements for being switched from constant speed to variable speed pumps? What is the overall economic benefit along with benefits that are not quantifiable?

23 Advantages of Variable Speed Pumps Improved efficiency (motor and pump) and consequently energy savings. Reduced system noise. Improved control of system flow to respond to flow and pressure requirements of the system. Extended motor life due to soft stops & starts which puts less wear and tear on the parts of the pump. Lower installation cost. The control valve in the bypass ensures that neither of the chillers would become starved during a low load situation, as flow is diverted directly from the supply back to the chillers.

24 Possibility of Switching Pumps Trane mentions four situations where variable primary flow should not be used (Trane, 1999). They are for system where: System chilled-water temperature is critical. Examples are a clean room or computer chip making plants. Although there are specific temperature and humidity guidelines for a museum, they are not critical. Slight temporary fluctuations will not cause permanent damage to the artifacts. The system flow rate, and consequently the load, does not vary. The load does vary in the Tubman Museum, between the occupied hours and the unoccupied hours. Also, due to the large transient load of occupants, the location of the load varies frequently within the inside of the building during the occupied hours. It is unlikely that the owner/operator will run the plant as designed. This is a slight area of concern, but something that doesn t eliminate the use of variable speed pumps for the system. Existing chiller controls are old and inaccurate. This is a new construction project, so this also is not a concern.

25 Current Piping Schematic BEFORE CHILLER: EWT = 55 F 290 GPM BEFORE CHILLER: EWT = 55 F 290 GPM CHILLER 1 (CH-1): CAPACITY = TONS HCFC-22 REFRIGERANT (2) SCREW COMPRESSORS (10) CONDENSER FANS 1.0 HP EACH 850 RPM AMBIENT MAX = 95 F AMBIENT MIN = 23 F CHILLER 2 (CH-2): CAPACITY = TONS HCFC-22 REFRIGERANT (2) SCREW COMPRESSORS (10) CONDENSER FANS 1.0 HP EACH 850 RPM AMBIENT MAX = 95 F AMBIENT MIN = 23 F AFTER CHILLER: LWT = 45 F 290 GPM CHWR AFTER CHILLER: LWT = 45 F 290 GPM CHWS AHU-1A&1B (LOAD) CHWS AHU-2 (LOAD) FOR ALL PUMPS: 290 GPM WATER TEMP. = 55 F NPSHR = 8.4 FT HEAD = 65 FT PUMP RPM = 1750 BHP = 7.25 MOTOR HP = 10 SHOT CHEMICAL FEEDER AIR SEPARATOR PRESSURE RELIEF VALVE CHWR CSPUMP (P-6): (STAND BY) CS PUMP (P-3): EXPANSION TANK LEGEND: BALL VALVE BUTTERFLY VALVE BUTTERFLY VALVE WITH MEMORY STOP (BALANCING VALVE) CHECK VALVE STRAINER W/BALL VALVE, HOSE BIBB & CAP AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE (CIRCUIT SETTER) CS PUMP (P-4): UNION OR FLANGE

26 Proposed Piping Schematic BEFORE CHILLER: EWT = 55 F 290 GPM BEFORE CHILLER: EWT = 55 F 290 GPM CHILLER 2 (CH-2): CAPACITY = TONS HCFC-22 REFRIGERANT (2) SCREW COMPRESSORS (10) CONDENSER FANS 1.0 HP EACH 850 RPM AMBIENT MAX = 95 F AMBIENT MIN = 23 F CHILLER 2 (CH-2): CAPACITY = TONS HCFC-22 REFRIGERANT (2) SCREW COMPRESSORS (10) CONDENSER FANS 1.0 HP EACH 850 RPM AMBIENT MAX = 95 F AMBIENT MIN = 23 F AFTER CHILLER: LWT = 45 F 290 GPM CHWR AFTER CHILLER: LWT = 45 F 290 GPM CHWS AHU-1A&1B (LOAD) CHWS AHU-2 (LOAD) FOR ALL PUMPS: 290 GPM WATER TEMP. = 55 F NPSHR = 8.4 FT HEAD = 65 FT SHOT CHEMICAL FEEDER AIR SEPARATOR PRESSURE RELIEF VALVE CHWR VSPUMP (P-6): (STAND BY) VS PUMP (P-3): EXPANSION TANK LEGEND: BALL VALVE BUTTERFLY VALVE BUTTERFLY VALVE WITH MEMORY STOP (BALANCING VALVE) CHECK VALVE STRAINER W/BALL VALVE, HOSE BIBB & CAP AUTOMATIC CONTROL VALVE, MODULATING ACTUATOR COMBINATION FLOWMETER/SHUT OFF/BALANCING VALVE (CIRCUIT SETTER) VS PUMP (P-4): UNION OR FLANGE

27 Chilled Water Bypass Control Normally closed control valve. Permits the operation of a single chiller below its low flow limit. Programmed to maintain only the minimum flow for each chiller that is on as opposed to constant flow, which would waste energy. Located near to the chillers so that the pressure drop throughout the system can drop as the coil loads drop.

28 Additional Costs Savings: The three-way valves are replaced with two-way valves at the AHU s. Less piping needs to be around the load with the elimination of the three-way valves. Steel schedule 40 piping, which costs $97 per linear foot for 6 piping for 100 feet of piping, meaning a savings of $9,700. Costs: A control valve in the bypass has to be added in the bypass line, which would typically cost $1950. Three variable frequency drives must be purchased each costing $5,800. Additional cost = $9,650.

29 Cost Savings Energy There are several different techniques available for calculating the energy savings (kwh) for variable speed pumps. Carrier s Hourly Analysis Program (HAP) Bell & Gossett ESP-Plus Online Program Engineering Equation Solver (EES) The results from EES will be presented further.

30 Engineering Equations Solver (EES) The following terms were created using lookup tables: Flow Rate vs. Head Flow Rate vs. Pump Efficiency Percent of Nameplate Load vs. Motor Efficiency Percent of Design Speed vs. Drive Efficiency (for the Variable speed pumps only) Individual functions were created for: Total Power Pump Efficiency Pump Model Curve Percent of Nameplate Load Deciding Number of Pumps Operating Based on the Load Speed the Variable Speed Pumps Operate At

31 Engineering Equations Solver (EES)

32 Engineering Equations Solver (EES)

33 Life Cycle Cost of Pumps The following formula from CoolTools was used in the calculation of the LCC. LCC = FC + j ( ) N ( UC j + MC j ) ( 1+ d ) j= 1 Where: FC = first cost of equipment UCj = utility cost for year j MCj = relative maintenance cost for year j d = discount rate N = number of years of analysis In this example: FCconstant = $0 FCvariable = $9,650 MCj = $500 d = 12% N = 20 years UCj constant speed = $4,092 UCj variable speed = $2,369

34 Payback Period of Pumps Initial Additional Cost for Variable Speed Pumps = $9,650 Yearly Savings = $1, Payback Period = $9,650 / $1, = 5.6 years

35 Chilled Water Pumping Conclusion Based solely on cost, it makes sense to switch from constant speed pumps to variable-speed pumps. The LLC is $3, less for variable speed. The payback period is slightly lengthy, but realistic.

36 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

37 Lighting of Gallery Space The lighting system for a gallery space in the museum (Collection Gallery 255) was designed using industry guidelines. The IESNA Lighting Handbook Ninth Edition (2000)

38 Placement of Luminaries X = (Ceiling height eye level) * = ( ) * = 66 = 5-6

39 Lightscape Renderings Southeast corner of room from above South of the room from above

40 Target Illuminance The IESNA Lighting Handbook target illuminance for: Flat displays and 3-dimensional objects is 300 lx (30 fc) Lobbies, general gallery areas and corridors is 100 lx (10 fc).

41 Photometric Data Southeast corner of room from above

42 Photometric Data South of the room from above

43 Lighting of Gallery Space Conclusion The new lighting design is compliant with the lighting requirements stated in the IESNA Lighting Handbook for illuminance. Artwork and artifacts are accentuated.

44 Presentation Outline Presentation Goals Existing Conditions Existing Mechanical System Chiller Optimization Chilled Water Pumping Lighting of Gallery Space Conclusions and Recommendations

45 Conclusions and Recommendations The RTAA 110 would still provide cost savings (LCC savings = $10,422.14) over the RTAA 125, along with some added safety to the designer and should be selected. The staging should be set to 100% of capacity of the first chiller before the second chiller is turned on. The primary-only, chilled water pumps should be switched from constant speed pumps to variable-speed pumps. The LCC is $3, less for variable speed. Variable speed control also has some advantages that are not quantifiable in economic terms. The new lighting design is compliant with the lighting requirements stated in the IESNA Lighting Handbook.

46 Acknowledgements I would like to thank the following people who have made my thesis possible: The Pennsylvania State University Department of Architectural Engineering faculty including: My advisor, Dr. James Freihaut Dr. William Bahnfleth and Dr. Stanley Mumma Jonathan Dougherty, Moses Ling, M. Kevin Parfitt and Kenneth Davidson Vanderweil Engineers, especially Heather Tsatsarones and Ron Edwards Fellow architectural engineering students who have lent their knowledge and expertise Mom, Dad and Jen who are always there for me My friends who have been understanding and helpful

47 Questions Thank you for your time Any questions???

Tubman African American Museum Atlanta, Georgia

Tubman African American Museum Atlanta, Georgia Tubman African American Museum Atlanta, Georgia Christopher Champagne The Pennsylvania State University Spring 2003 Project Info: - - 45,000 Sq. Ft. - Two stories - Museum Construction: Started: October

More information

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option

The Milton S. Hershey Medical Center Academic Support Building. AE Senior Thesis Kari Anne Donovan Mechanical Option The Milton S. Hershey Medical Center Academic Support Building AE Senior Thesis Kari Anne Donovan Mechanical Option Presentation Outline Existing Conditions Distributed Chilled Water Feasibility Study

More information

Mechanical Project Proposal

Mechanical Project Proposal Mechanical Project Proposal Miller Children s Hospital Prepared for: Dr. James Freihaut Department of Architectural Engineering The Pennsylvania State University Prepared by: Stephen Haines December 18

More information

Chilled Water Plant Design American Standard Inc.

Chilled Water Plant Design American Standard Inc. Chilled Water Plant Design 2003 American Standard Inc. Agenda Earthwise System Variable Primary Flow Series Configuration Case Study 20,000RT Project Parallel, primary/secondary, low temp, YK Series-counter,

More information

Technical Report Two: Building and Plant Energy Analysis Report

Technical Report Two: Building and Plant Energy Analysis Report The American Swedish Institute Minneapolis, MN Technical Report Two: Building and Plant Energy Analysis Report Name: Option: Mechanical Advisor: Stephen Treado Date: 10.19.11 Table of Contents Executive

More information

Proposal: Mechanical System Redesign

Proposal: Mechanical System Redesign Proposal: Mechanical System Redesign The 959 Eighth Avenue 10019 Faculty Advisor: Dr. James Freihaut December 12, 2005 Table of Contents 1.0 Executive Summary 2.0 3.0 Proposal Obectives 4.0 Preliminary

More information

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load. Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems

More information

Project Proposal Proposal for Investigation of Alternative Systems

Project Proposal Proposal for Investigation of Alternative Systems Project Proposal Proposal for Investigation of Alternative Systems 01.15.2010 Defense Media Activity Building Fort George G. Meade Penn State University Architectural Engineering Faculty Advisor: Dr. Treado

More information

Comparison of Air Distribution Systems

Comparison of Air Distribution Systems of Air Distribution s vs. s & s Presentation Outline & s Distribution Conclusion & s & s Project Team Owner - Capital One Financial Corporation Owner s Rep - Jones Lang LaSalle Architect - Ai Architecture

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by:

FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC MANGUM ROAD HOUSTON, TEXAS. performed by: FRIGI-TECH OIL SUPPLEMENT TEST GAMMA BIOLOGICALS, INC. 3700 MANGUM ROAD HOUSTON, TEXAS performed by: ADAMS MECHANICAL SERVICES, INC. 235 CORTLANDT HOUSTON, TEXAS TEST DATES: JUNE 16, 1989 - SEPTEMBER 10,

More information

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne Existing Building Cx: Processes & Results A Cultural Journey Barry Abramson Senior Vice President Servidyne AIA Quality Assurance Learning Objectives 1. Define the key steps in the process of retrocommissioning

More information

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin

Thesis Proposal. Clemson University Advanced Material Research Laboratory Anderson, SC. David Anderson Mechanical Option. Photo by Fred Martin Thesis Proposal Photo by Fred Martin Clemson University Advanced Material Research Laboratory Anderson, SC David Anderson Mechanical Option Friday, December 15, 2006 Table of Contents 1. Executive Summary

More information

Table of Contents. The Creative and Performing Arts High School (CAPA) Pittsburgh, PA

Table of Contents. The Creative and Performing Arts High School (CAPA) Pittsburgh, PA Table of Contents Cover Sheet i Acknowledgements ii Building Abstract iii Table of Contents iv-v Introduction 1 Background 2 Site & General Architecture 3 Mechanical Analysis 4 Goal / Introduction 5 Existing

More information

Chilled Water Plant Redesign

Chilled Water Plant Redesign 17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by

More information

Technical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis

Technical Report 2. Bellevue Ambulatory Care Pavilion New York, NY. Building and Plant Energy Analysis Technical Report 2 Building and Plant Energy Analysis Bellevue Ambulatory Care Pavilion New York, NY Prepared for: Dr. Jelena Srebric, PhD Department of Architectural Engineering The Pennsylvania State

More information

Glen Burnie High School Glen Burnie, MD. Wade Myers Mechanical Option

Glen Burnie High School Glen Burnie, MD. Wade Myers Mechanical Option I. I n t r o d u c t i o n II. Existing Mechanical System III. Proposed System Alterations IV. CM Breadth V. Conclusion School Background 6 building; campus style high school Located in Construction of

More information

Water Bottling Facility

Water Bottling Facility TECHNICAL REPORT 2 Water Bottling Facility Mid-Atlantic, US Building and Plant Energy Analysis Report The Pennsylvania State University Author: Justyne Neborak Architectural Engineering Advisor: Dr. William

More information

Chilled Water Energy Savings Study

Chilled Water Energy Savings Study 1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting

More information

Technical Assignment 2 Building and Plant Energy Analysis

Technical Assignment 2 Building and Plant Energy Analysis Technical Assignment 2 Building and Plant Energy Analysis Des Places Residence Hall Duquesne University Pittsburgh, PA Peter Edwards Advisor: James Freihaut October 4, 2010 Table of Contents Executive

More information

Chilled Water Loop Optimization. Kazimir Gasljevic Richard Dewey Sandro Sanchez

Chilled Water Loop Optimization. Kazimir Gasljevic Richard Dewey Sandro Sanchez Chilled Water Loop Optimization Kazimir Gasljevic Richard Dewey Sandro Sanchez WHAT WE STARTED WITH: LOOP OUTLINE: WHAT WE STARTED WITH: LOOP OUTLINE: - Justification for the loop WHAT WE STARTED WITH:

More information

Large University Central Chiller Plant Design Considerations

Large University Central Chiller Plant Design Considerations Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful

More information

Freetown Elementary School

Freetown Elementary School Building and Plant Energy Analysis Technical Report 2 Freetown Elementary School Glen Burnie, MD Matthew R. Buda The Pennsylvania State University Architectural Engineering Mechanical Option Advisor: Dr.

More information

Project Information. Measure Description

Project Information. Measure Description Project Information Project ID#: CE07M016 Measure: Multiple Electric : 452,593 kwh, 8.84 kw, 39.26 kw Facility Type School Technology: Multiple Measure Description CH-1 - Chiller Plant Optimization and

More information

September 22, Roy Hubbard HVAC Systems Technology

September 22, Roy Hubbard HVAC Systems Technology September 22, 2011 Roy Hubbard HVAC Systems Technology Lesson Objectives (YC-3) At the end of this session, you will understand: Understanding Chiller Energy Fundamentals Impact of VSDs (maintenance and

More information

South Jefferson High School Huyett Road Charles Town, WV 25414

South Jefferson High School Huyett Road Charles Town, WV 25414 Thesis Proposal Mechanical System Redesign Report Charles Town, WV 25414 Prepared for Dr. Jelena Srebric The Pennsylvania State University By Jonathon Gridley Friday, December 15, 2006 1.0 Table of Contents

More information

Central Chiller Plants

Central Chiller Plants Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland

More information

The Montgomery County Conference Center and Hotel. The Montgomery County. Conference Center and Hotel

The Montgomery County Conference Center and Hotel. The Montgomery County. Conference Center and Hotel The Montgomery County 5701 Marinelli Road, Rockville, MD Senior Thesis Presentations 2005 Presentation Outline Building Overview Mechanical System Existing Conditions Mechanical System Redesign Goals /

More information

Free Cooling Technology

Free Cooling Technology Free Technology Utilise low ambient temperatures to save energy and reduce your cooling costs by up to 70% Free for industrial process and air conditioning How Free can save you money Free is a fast and

More information

Utilities Infrastructure Cooling Distribution. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc.

Utilities Infrastructure Cooling Distribution. Purpose of Today s Presentation. Agenda. GLHN Architects & Engineers, Inc. Utilities Infrastructure Cooling Distribution APPA Institute for Facilities Management Dallas Jan 2017 Bill Nelson PE 1 Purpose of Today s Presentation To provide a broad understanding of Chilled water

More information

COOLING COIL (35% ETHYLENE GLYCOL)

COOLING COIL (35% ETHYLENE GLYCOL) APPENDIX Contents A1.1 Existing Mechanical Equipment Schedules A1.2 Existing Mechanical System Schematic Drawings A2. Building Design Loads, Energy Loads and Cost Data Tables A3. Standard 62n-2001 Ventilation

More information

Oklahoma University Children s Medical Office Building

Oklahoma University Children s Medical Office Building Oklahoma University Children s Medical Office Building Oklahoma City, O.K., BAE Advisor: Laura Miller Presentation Outline VRF System Dedicated Outdoor Air System Evaluation VRF Indoor Units Design Criteria

More information

Coppin State University Physical Education Complex - Technical Report 2

Coppin State University Physical Education Complex - Technical Report 2 Coppin State University Physical Education Complex - Technical Report 2 Building and Plant Energy Analysis Report Kaylee M Damico Advisor: Dr. Jelena Srebric Location: Baltimore, MD Table of Contents Contents

More information

Optimizing Central Chilled Water Systems

Optimizing Central Chilled Water Systems Optimizing Central Chilled Water Systems OPTIMIZING CENTRAL CHILLED WATER SYSTEMS kent.peterson@p2seng.com 1 O P T I M I Z I N G C E N T R A L C H I L L E D W A T E R S Y S T E M S Kent W. Peterson, PE,

More information

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC Variable Frequency Drive Retrofit Opportunities Michael Kuk CERx Solutions LLC Speaker Introduction» Founder / owner of CERx Solutions LLC» Veteran Owned Small Business Enterprise founded in 2013» 27+

More information

The Ed Roberts Campus

The Ed Roberts Campus The Ed Roberts Campus Proposal Anderson Clemenceau Mechanical Option Advisor: Donghyun Rim December 12, 2014 2 Contents Executive Summary... 3 Building Overview... 4 Existing Mechanical System... 5 Airside

More information

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary

Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary Improved Chilled Water Plant Performance with New Energy Valve (EV) Outline Chilled Water T Study AHU Coil Overview Cooling Overview Test Setup Data Analysis Findings Summary 6 December 2012 Boston Hotels

More information

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of

More information

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE Reducing Hospital Energy Use and Maintaining Savings Glen Anderson, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing

More information

Fifteen Year Plan for Energy Efficiency and Conservation Projects

Fifteen Year Plan for Energy Efficiency and Conservation Projects Fifteen Year Plan for Energy Efficiency and Conservation Projects Presented to the Board of Trustees of the Northeastern Ohio Universities Colleges of Medicine and Pharmacy, December, 2008, in accordance

More information

AE 481-COMPREHENSIVE SENIOR PROJECT I Building Mechanical & Energy Systems Option

AE 481-COMPREHENSIVE SENIOR PROJECT I Building Mechanical & Energy Systems Option Senior Thesis Program The Department of Architectural Engineering The Pennsylvania State University University Park, PA 2016-2017 AE 481-COMPREHENSIVE SENIOR PROJECT I Building Mechanical & Energy Systems

More information

Appendix D Example M&V Plans

Appendix D Example M&V Plans Appendix D: Example M&V Plans Appendix D Example M&V Plans 1 California s 2000 LNSPC Program Procedures Manual Example M&V Plans Several example M&V Plans are included in this Appendix for further guidance.

More information

Final Thesis Report Mechanical System Alternatives Analysis

Final Thesis Report Mechanical System Alternatives Analysis [Type text] Nassau Community College Life Sciences Building Garden City, NY Final Thesis Report Mechanical System Alternatives Analysis Prepared By: Prepared For: James D. Freihaut, PhD Dustin Eplee Date:

More information

THERMAL STORAGE FEASIBILITY STUDY

THERMAL STORAGE FEASIBILITY STUDY THERMAL STORAGE FEASIBILITY STUDY SPRING 2005 NEW HOUSE RESIDENCE HALL PRESENTATION OUTLINE GENERAL PROJECT DATA PROJECT TEAM MECHANICAL REDESIGN ELECTRICAL ANALYSIS ACOUSTICAL ANALYSIS CONCLUSIONS GENERAL

More information

Table of Contents. Page 1

Table of Contents. Page 1 Table of Contents Acknowledgments...2 Executive Summary...4 Project Background...5 Existing Mechanical System...8 Proposed Mechanical Redesign...13 Impact of Proposed Mechanical System on Structure...36

More information

Acknowledgements 4. Executive Summary 5

Acknowledgements 4. Executive Summary 5 Table of Contents Acknowledgements 4 Executive Summary 5 Building Overview.. 6 Building Summary.. 6 Site. 6 Evaluation of Existing Mechanical System. 7 Mechanical System Overview 7 Design Objective 7 Outdoor

More information

Central Chilled Water Plant Sustainable Design. By : George Berbari, CEO DC PRO Engineering

Central Chilled Water Plant Sustainable Design. By : George Berbari, CEO DC PRO Engineering . By : George Berbari, CEO DC PRO Engineering Design Broad Objectives: Most Design Point Energy Efficient. Cost effective. Smallest foot print. Most Energy Efficient based on Year Round Operational. High

More information

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Technical Report Three Mechanical Systems Existing Conditions Evaluation 09 10 Technical Report Three Mechanical Systems Existing Conditions Evaluation WESTINGHOUSE ELECTRIC CO. NUCLEAR ENGINEERING HEADQUARTERS CAMPUS Pittsburgh, PA Daniel P. Aughenbaugh Mechanical Dr. Bahnfleth

More information

Thesis Final Presentation

Thesis Final Presentation Acoustical lanalysis Thesis Final Presentation Facility Information Mechanical Information Goals Facility Information Location: Total Cost: $56,000,000 Occupancy: Office, Media Center Delivery Method:

More information

Chiller plant optimization

Chiller plant optimization Chiller plant optimization CLEANROOM Terrence Morris & Steve Blaine PE, CH2M HILL, Oregon, USA ABSTRACT Outside of the process tools themselves, the chilled water plant is typically the single largest

More information

Mechanical Systems Project Proposal

Mechanical Systems Project Proposal Mechanical Systems Project Proposal December 15, 2006 Table of Contents 1.0 Executive Summary... 2 2.0 Building Background... 3 3.0 Proposal Objectives... 5 4.0 Initial Considerations... 6 5.0 Proposed

More information

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories

> HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION. Available range. Unit description. Options. Accessories > HGW WATER - WATER AND BRINE - WATER HEAT PUMPS FOR INDOOR INSTALLATION Available range Unit type IH Heat pump IP Reversible heat pump (reversible on the refrigerant side) ECO-FRIENDLY REFRIGERANT GAS

More information

Due Date: January 18, 2011

Due Date: January 18, 2011 prepared by: Zachary Heilman MECHANICAL OPTION prepared for: James Freihaut, PhD THESIS PROPOSAL [REVISED] Due Date: January 18, 2011 The Mirenda Center for Sports, Spirituality, and Character Development

More information

CNBC GLOBAL HEADQUARTERS. Englewood Cliffs, NJ

CNBC GLOBAL HEADQUARTERS. Englewood Cliffs, NJ CNBC GLOBAL HEADQUARTERS Englewood Cliffs, NJ Christine Cajilig Lighting/Electrical Thesis 2005 Presentation Outline Items Covered Building Background Lighting Depth: Cafeteria Dining Electrical Depth:

More information

Energy Efficiency in Building Active Design Part II

Energy Efficiency in Building Active Design Part II Energy Efficiency in Building Active Design Part II Presented by: CK Tang BSEEP Component 4 Manager Veritas Enviornment Sdn Bhd ck.tang@veritas.com.my Air Conditioning System System Sizing 1 Current Industry

More information

A building controls strategy based on fundamental engineering principles

A building controls strategy based on fundamental engineering principles How is a healthcare facility like a chemical plant? Lessons from chemical engineering for HVAC optimization Edward George & Associates Leslie R. Schulte, PhD Valerie Coulter Eddie McLaughlin A better way

More information

Building Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital

Building Load and Energy Estimates Analysis. Instructor: Dr. Mumma. October 28, Thesis Building Sponsor s: INOVA Fairfax Hospital David Peterson Penn State AE, Mechanical INOVA Fairfax Hospital The INOVA Heart Institute David J. Peterson Mechanical Option Mechanical Technical Report #2b The INOVA HEART INSTITUTE AT INOVA Fairfax

More information

Cost Benefits of SunGuard SN 54

Cost Benefits of SunGuard SN 54 Cost Benefits of SunGuard SN 54 Guardian Industries recently introduced SunGuard SN 54 low-e glass. This new low-e glass is clear in appearance and has optimal energy performance for commercial building

More information

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort

Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort AABC Commissioning Group AIA Provider Number 50111116 Optimizing Chilled Water Systems for Energy Efficiency and Occupant Comfort Course Number: CXENERGY1709 Mark Benevides Siemens April 26, 2017 Page

More information

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017

Optimized System for Your Bottom Line. Trane Training Class 1 Dec, 2017 Optimized System for Your Bottom Line Trane Training Class 1 Dec, 2017 Total Cost of Ownership Setting your system for great payback Where is money spent over a 30 year lifetime? First Cost 4.9% Service

More information

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Yifu Shi Kelly Guiberteau Carlos Yagua, P.E. James Watt, P.E. Energy Systems Laboratory,

More information

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels

Air-Water Systems. Chilled Ceilings and Beams TROX USA. Principle of Operation. Radiant Effect on Occupants. Early 1980 s. Chilled Ceiling Panels Air-Water Systems and Beams Early 1980 s 1980 1990 2005 Buildings well insulated for heating Advent of personal computers Need to remove heat from space Limited space available TROX USA 1 2 Principle of

More information

Walter Reed National Military Medical Center Bethesda, MD

Walter Reed National Military Medical Center Bethesda, MD Walter Reed National Military Medical Center Bethesda, MD Technical Report Two: Building and Central Plant Energy Analysis Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date: 10/28/09

More information

Mechanical Depth. Redesign and Analysis

Mechanical Depth. Redesign and Analysis Depth Redesign and Analysis 14 Analysis Scope The scope of my mechanical redesign will include the 2 nd and 3 rd floors of the SW hospital wing which includes Semi-Private, Private and Isolations rooms.

More information

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Ben Erpelding and Annika Moman, San Diego Regional Energy Office ABSTRACT According the U.S. Department

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE

THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE T13-O-15: Air conditioning components Proceedings: EERB-BEPH 2009 THE USE OF HEAT RECOVERY DEVICES FOR REDUCING ENERGY CONSUMPTION OF TREATING VENTILATION AIR IN A TROPICAL OPERATING THEATRE Y.H. Yau *

More information

Final Thesis Report: Mechanical Alternative Systems

Final Thesis Report: Mechanical Alternative Systems The American Swedish Institute Minneapolis, MN Final Thesis Report: Mechanical Alternative Systems Analysis Name: Option: Mechanical Advisor: Stephen Treado Date: 4.4.12 Table of Contents Abstract 5 Executive

More information

Building Control Strategies That Work to Improve Your Energy Bottom Line

Building Control Strategies That Work to Improve Your Energy Bottom Line Building Control Strategies That Work to Improve Your Energy Bottom Line William D. (Skip) Milton MBA, CEM, CEA Assistant Director of Facilities Operations Texas Children s Hospital Objective: Learn how

More information

5.0 Mechanical Depth:

5.0 Mechanical Depth: 5.0 Mechanical Depth: Air-Side Systems The airside mechanical system for the Montgomery County Conference Center and Hotel consists of a combination of variable air volume and constant volume systems served

More information

percent hours of the year heat rejected to loop percent hour building load on loop, Btuh percent hour building load on loop, Btuh

percent hours of the year heat rejected to loop percent hour building load on loop, Btuh percent hour building load on loop, Btuh HOBOKEN RESIDENTIAL C- Ground Loop Pump Calculations Central Geothermal System building load on loop, Btuh Bin - 5 5 25 35 45 55 hours of the year Count 3 35 48 64 79 89 96 96 3 32 3 6 5 7 274 292 86 46

More information

Evaluation of Underfloor Air Distribution

Evaluation of Underfloor Air Distribution McCarran International Airport Terminal 3 L as Vegas, NV Evaluation of Underfloor Air Distribution and Displacement Ventilation Systems The Pennsylvania State University AESenior ThesisPresentation, Spring

More information

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc.

Gregory W. Stevens and Ronald K. Ishii, Alternative Energy Systems Consulting, Inc. A Study of Optimizing the System Integration of Combined Heat and Power (CHP) with Absorption Cooling for Cold Storage Applications: Design Considerations, Modeling and Life Cycle Costing Gregory W. Stevens

More information

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering

District Cooling Sustainable Design. Presented by George Berbari CEO of DC PRO Engineering 2016 District Cooling Presented by George Berbari CEO of DC PRO Engineering District Cooling Brief History & Future Central Chilled Water plants existed in the Middle East as early as the 1960 s. Few examples

More information

AE 481W Thesis Proposal

AE 481W Thesis Proposal AE 481W Thesis Proposal I I Advisor: Dr. Treado UNIVERSITY OF CALIFORNIA SAN DIEGO RADY SCHOOL OF MANAGEMENT LA JOLLA, CA TABLE OF CONTENTS Executive Summary.3 Mechanical System Overview..4 Design Objectives,

More information

Verification of Chiller Performance Promotion and Energy Saving

Verification of Chiller Performance Promotion and Energy Saving Engineering, 2013, 5, 141-145 http://dx.doi.org/10.4236/eng.2013.51a020 Published Online January 2013 (http://www.scirp.org/journal/eng) Verification of Chiller Performance Promotion and Energy Saving

More information

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF)

Agenda. Understanding the three basic piping systems. Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations (VPF) Roy Hubbard Agenda Understanding the three basic piping systems Design and Off-design operation Advantages and Disadvantages Low DeltaT Syndrome causes, effects, and solutions Design & Control Considerations

More information

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance

Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance Proceedings: ISHVAC 007 Using Annual Building Energy Analysis for the Sizing of Cooling Tower for Optimal Chiller-Cooling Tower Energy Performance Chia-Wei Liu, Yew-Khoy Chuah Institute of Mechanical and

More information

Thesis Proposal. Freetown Elementary School

Thesis Proposal. Freetown Elementary School Thesis Proposal Freetown Elementary School Glen Burnie, MD Matthew R. Buda The Pennsylvania State University Architectural Engineering Mechanical Option Advisor: Dr. Treado Table of Contents Executive

More information

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS University of Dayton, Dayton, Ohio Vijay Gopalakrishnan, Lead Engineer Alexandra Brogan,

More information

Mechanical Systems Proposal

Mechanical Systems Proposal Mechanical Systems Proposal Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option December

More information

Xavier University of Louisiana

Xavier University of Louisiana Annual Savings Report Year 2 May 1, 2012 to April 30, 2013 July 2013 For Marion Bracy Vice President Xavier University Facilities Planning 1 Drexel Drive New Orleans LA 70125 (504) 520 1056 Submitted By

More information

Integration of Mechanical System Redesign. The New Learning Center Lutheran Theological Seminary at Philadelphia

Integration of Mechanical System Redesign. The New Learning Center Lutheran Theological Seminary at Philadelphia Integration of Mechanical System Redesign Geothermal Heat Pump Redesign The New Learning Center Lutheran Theological Seminary at Philadelphia Wesley S. Lawson Architectural Engineering Mechanical Option

More information

Mechanical Tech Report 2

Mechanical Tech Report 2 Mechanical Tech Report 2 Design Load Estimation and Energy Analysis M Resort Spa and Casino Tom M. Chirdon Faculty Advisor; William P. Bahnfleth October 24, 2008 Table of Contents 1.0 Executive summary

More information

Darren Bruce Mechanical Option 1919 M St, Washington DC Primary Faculty Advisor: Prof. Bahnfleth December 5, Mechanical Systems Proposal:

Darren Bruce Mechanical Option 1919 M St, Washington DC Primary Faculty Advisor: Prof. Bahnfleth December 5, Mechanical Systems Proposal: Primary Faculty Advisor: Prof. Bahnfleth December 5, 2003 Mechanical Systems Proposal: Executive Summary: My senior thesis redesign will focus on the mechanical aspects of1919 M St. 1919 is an 8-story,

More information

- Operating hours. - Average kw/ton.

- Operating hours. - Average kw/ton. OPTIMIZATION OF CHILLED WATER SYSTEMS 8. N. Gidwani, P.E. Project Director Roy F. Weston, Inc. West Chester. Pennsylvania 19380 ABSTRACT Chilled water systems are one of the major energy consumers in industrial,

More information

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya

HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya HVAC INTEGRATED CONTROL FOR ENERGY SAVING AND COMFORT ENHANCEMENT vahid Vakiloroaya (vahid.vakiloroaya@engineer.com) ABSTRACT: The overall attainable reduction in energy consumption and enhancement of

More information

center for the arts towson university Architectural Engineering Lighting/Electrical Benjamin Mitten Spring 2005

center for the arts towson university Architectural Engineering Lighting/Electrical Benjamin Mitten Spring 2005 Architectural Engineering Lighting/Electrical Presentation Outline duction To The Building Lighting Depth - Paint Studio - Lobby Controls Depth Mechanical Breadth Presentation Outline duction To The Building

More information

Jesse A. Fisher Mechanical Option Riverpark I Salt Lake City, UT Spring 2005 Advisor: Jae-Weon Jeong

Jesse A. Fisher Mechanical Option Riverpark I Salt Lake City, UT Spring 2005 Advisor: Jae-Weon Jeong Mechanical Option Riverpark I Salt Lake City, UT Spring 2005 Advisor: Jae-Weon Jeong Riverpark Corporate Center, Phase 1 South Jordan, Utah www.arche.psu.edu/thesis/2005/jaf327 Jesse A. Fisher Mechanical

More information

ADDENDUM NO. 01. Include this signed and dated addendum to your proposal.

ADDENDUM NO. 01. Include this signed and dated addendum to your proposal. ADDENDUM NO. 01 To City of College Park RFP FIN 012716 - LEASE ADVERTISEMENT for LEASE for TAX-EXEMPT FINANCING Please note the following additions/changes to this bid. Include this signed and dated addendum

More information

Intelligent. Powerful. Proven. usa.siemens.com/demandflow

Intelligent. Powerful. Proven. usa.siemens.com/demandflow Demand Flow Chilled Water System Optimization Intelligent. Powerful. Proven. usa.siemens.com/demandflow Demand Flow CHW Building Technologies A powerful solution to reduce energy consumption and improve

More information

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation 2900 Fairview Park Drive, Prepared By: Charles Haack Mechancial Option November 21, 2008 Prepared For: Dr. William P.

More information

DOE Best Practice Software Tools. Joseph Chappell Adam Roget

DOE Best Practice Software Tools. Joseph Chappell Adam Roget DOE Best Practice Software Tools Joseph Chappell Adam Roget DOE Software Tool Use Over the past year 12 regular IAC assessments 3 large energy user assessments 1 SEN type assessment for a local hospital

More information

Intelligent System Design

Intelligent System Design Intelligent System Design Justin Wieman Chiller Systems Engineer Trane, A Division of Ingersoll-Rand Member AHRI Systems Committes ASHRAE Member since 2000 When you buy a HVAC System would you rather buy:

More information

Walter Reed National Military Medical Center Bethesda, MD

Walter Reed National Military Medical Center Bethesda, MD Walter Reed National Military Medical Center Bethesda, MD Technical Report Three: Mechanical Systems Existing Conditions Evaluation Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date:

More information

Mechanical Project Proposal. Indoor Multi-Sport Facility. At Pennsylvania State University

Mechanical Project Proposal. Indoor Multi-Sport Facility. At Pennsylvania State University At Pennsylvania State University Christopher Van Campen December 05, 2002 Executive summary The proposed thesis is to alleviate the of its only major problem, not enough seating capacity for the spectators

More information

Dresden, Germany 2 Thermodynamics Laboratory, University of Liège, Belgium 3 Vabi Software bv, Delft, The Netherlands ABSTRACT INTRODUCTION

Dresden, Germany 2 Thermodynamics Laboratory, University of Liège, Belgium 3 Vabi Software bv, Delft, The Netherlands ABSTRACT INTRODUCTION Eleventh International IBPSA Conference Glasgow, Scotland July 27-30, 2009 TESTING AND VALIDATION OF SIMULATION TOOLS OF HVAC MECHANICAL EQUIPMENT INCLUDING THEIR CONTROL STRATEGIES. PART I: DESCRIPTION

More information

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL

ABSTRACT I. INTRODUCTION II. METHODS AND MATERIAL 2017 IJSRSET Volume 3 Issue 2 Print ISSN: 2395-1990 Online ISSN : 2394-4099 Themed Section: Engineering and Technology Chiller and AHU Design for A commercial Usage S M Azfar Hashmi, Mirza Muneer Baig,

More information

Trane Engineering News Multi-pipe unit for heating and cooling buildings

Trane Engineering News Multi-pipe unit for heating and cooling buildings Trane Engineering News Multi-pipe unit for heating and cooling buildings Today, it is common to find buildings with traditional heating and cooling systems working simultaneously to satisfy the comfort

More information

Prepared. r William. 10 th, Mechanical. Option. Architectural Engineering. Bachelor of. The

Prepared. r William. 10 th, Mechanical. Option. Architectural Engineering. Bachelor of. The Architectural Engineering Mechanical Option 2011 Thesiss Proposal Prepared for: Professor r William Bahnfleth, PhD, PE Date: December 10 th, 20100 Mechanical Option Senior Thesis 2010-2011 The Pennsylvania

More information