NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency. August 21, 2013

Size: px
Start display at page:

Download "NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency. August 21, 2013"

Transcription

1 NEBBinar: Retro-Commissioning for Comfort and Energy Efficiency August 21,

2 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning. He has over 29 years of industry experience, is a Certified Energy Manager, and has extensive experience with BACNET, LON, MODBUS, and other building automation protocols and communication networks. He has programming, tuning, and testing experience with multiple systems and applications, as well as building systems commissioning, sound and vibration measurement, and testing and balancing. 1

3 Speaker Dave McFarlane, Principal Project Director, Atkins Dave McFarlane is a principal project director in the asset management practice and head of the Retro-Commissioning group for Atkins, one of the world s leading engineering, design, and project management consultancies. Prior to joining Atkins, Dave was the president of Technical Commissioning, Inc. (Fort Myers, FL) and McFarlane, Inc. (Grand Forks, ND). He was a member of NEBB s Commissioning Committee; he chaired the committee in and rejoined in Dave serves as an instructor for NEBB s courses in Commissioning and Retro- Commissioning. He speaks at conferences nationwide, and has written numerous articles for a variety of industry publications. 2

4 Agenda What is Retro-Commissioning Case study: Grand Forks ND County Office Question and Answers 3

5 Retro-Commissioning A systematic, documented process that identifies and implements low cost operational and maintenance improvements which improve building efficiency and allows the building to meet the current design requirements 4

6 Retro-Commissioning Ensure that the building meets the Current Facility Requirements (CFR) Reduce energy usage Improve comfort 5

7 Agenda What is Retro-Commissioning Case study: Grand Forks ND County Office Question and Answers 6

8 Grand Forks County Office Retro-Commissioning 7

9 Grand Forks Country Office Seven story - 140,000 square feet Five floors office space w/conference rooms Meeting rooms on sixth floor Mechanical room on the 7 th floor 8

10 Interior/exterior walls and conference rooms Floors 1-5 9

11 Interior/exterior walls and conference rooms Floor 6 10

12 Interior offices Perimeter offices 11

13 County Commissioners Chambers 12

14 Perimeter link Meeting room 13

15 Establish baseline Review the past 2-3 years energy bills Convert to MM BTU ft2/year Energy intensity is ~ 151,000 BTU/ft2/yr Session 21 Energy Savings 14

16 Natural Gas 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2, Premodification Gas Use 15

17 Electrical Usage KWH 330, , , ,000 Premodification KWH 130,000 80,

18 Electrical Demand KW Premodif ication KW 17

19 Compare baseline to typical For North Dakota typical energy intensity: 93,000 BTU/ft2/yr County office energy intensity: ~ 151,000 BTU/ft2/yr Projected savings achievable through retrocommissioning: $45,000 annually 18

20 Discovery phase Determine what is wrong Review documents, plans and specs Interview maintenance staff 19

21 Plans and specs showed VAV boxes with 2-way valves 4 VAV air handlers 4 boilers 20

22 AHU Quadrants Session 21 Energy Savings 21

23 Plans and specs showed HW pumps and fans with VFD s Pump and fan VFD s 22

24 Discovery and maintenance staff perspectives Building had electric baseboard supplement heat Too many occupant complaints about temperature controls Lack of understanding of Building Management System (BMS) Systems in overridden and in manual control BMS system not used to potential 23

25 Light shelves 24

26 Heating pumps VFD 60 Hz % Leaking reheat valves

27 Site investigations Fresh air dampers open on night set back Control sequence cooled building Building in occupied mode Occupied air flow: meeting/conference rooms Space stats not controlling within 1 o F Occupants had full thermostat control Mixed air control set at a constant 55 F o 26

28 Site investigations Equal occupied and unoccupied heating variable air volume (VAV) set points Min/max heating VAV set points are the same Equal unoccupied interior and exterior zones air flow 27

29 Site investigations Boilers reset to 120 during summer months Heat from dimmer switch 28

30 Site investigation Electric baseboard on whenever OA below 50 F Duct static pressure sensor set at 2 pressure Most VAV boxes call for reheat Most VAV boxes damper position 50-75% in summer 29

31 Site investigations Outdoor CO2 is 370 PPM. Indoor CO2 is 425 PPM Chiller energized at 50 F OAT Many VAV min / max set points had been occupant complaint adjusted Room registers read between.5 and 4.0 CFM / Ft2 Building positive, then negative 30

32 RA fan and SA fan not tracking 31

33 Analysis phase Computer modeling Determine if we can predict the current energy usage before changes are made 32

34 Corrective action items Recalculate new air flows based on the actual people, lights, equipment, glass walls and roof loads. Use ASHRAE 98% design Use actual people loading for fresh air 33

35 Analysis phase Actual operating data Total fan air flow Actual fan static pressures Actual fan amperage readings System type, fan wheel type and fan speed Actual run times 34

36 Analysis phase Actual data Average Min / Max set points Occupied / unoccupied set points VAV occupied unoccupied set points Fan type and fan speed Run times Actual fresh air CFM 35

37 Analysis phase Actual operating data Total fan discharge temp Hot water temps Chilled water temps Space temp Type of fin tube heat and fin tube parameters 36

38 Analysis phase: actual space data Actual people, light load, equipment load Actual occupied times Actual space temperatures Actual glass area and parameters Actual roof area, wall area and parameters 37

39 Analysis phase: actual utility cost data Gas cost per therm KWH cost KW demand cost Auxiliary fuel costs Local degree days / bin temperatures 38

40 Analysis phase DOE 2 or Super DOE Crunch the numbers and compare 39

41 Natural Gas 16,000 14,000 12,000 10,000 8,000 6,000 4,000 2, Projected Gas Use Premodification Gas Use 40

42 Annual Natural Gas Summary 150, ,000 90,000 60,000 Premodification Projected 30,000-41

43 Electrical Demand KW Projected KW Premodification KW 42

44 Annual Electrical KW Demand Summary 8,000 7,000 6,000 5,000 4,000 3,000 2,000 1,000 - Premodification Projected 43

45 Electrical Usage KWH 330, , , ,000 Projected KWH Premodif icatio n KWH 130,000 80,

46 Annual Electrical KWH Summary 2,500,000 2,000,000 1,500,000 1,000,000 Premodification Projected 500,

47 Office Energy Intensity Current Intensity is ~ 151,000 BTU/ft2/yr Area Average ~ 93,000 BTU/ft2/yr Computer modeling ~ 85,000 BTU/ft2/yr 46

48 Corrective action items Make the corrections needed to obtain the results outlined in the modeling. Rebalance air and water flows to new ASHRAE 98% requirements Session 21 Energy Savings 47

49 Repair leaky valves 48

50 49 Eliminate restrictive duct

51 Corrective action items Adjust throttling range and dead band on all VAV thermostats and AHU Controllers 50

52 Improper Control - Too tight 51

53 Improper Control - Too Loose 52

54 Proper Control 53

55 Adjust occupied/unoccupied sequence 54

56 Fixes and corrective actions Rezone for interior exterior zones Set VAV box up with different occupied/unoccupied min/max Set conference room VAV box to standby Unoccupied interior VAV set to zero air flow Set 6th floor conference room VAV s to standby mode 55

57 Fixes and corrective actions Lock thermostats between 68 and 75F Reset discharge temperature on cooling Reset hot water 140 to 180F De-energize electric fin tube above 30 F De-energize the fin tube in the unoccupied mode Rotate the fin tube usage off for 1 of 5 minutes Shut boiler off at 40F unoccupied 56

58 Acceptance phase Energy Procedures Winter temps F Summer temps F No space heaters Monitor usage for one year 57

59 58 Grand Forks County Office Retro-Cx Results

60 59

61 60

62 61

63 62

64 63

65 64

66 Yearly energy usage per square foot Pre-modification 151,000 BTU/FT² Typical 93,000 BTU/FT² Modeling 85,000 BTU/FT² Actual: 76,000 BTU/FT² 65

67 Results Gas 29.8 % $417,200 KW-hr 45.9 % $642,600 Demand 26.3 % $368,200 Total 100 % $1,400,000 Energy levels have stayed at projected levels for the past eleven years 66 \

68 Three years after RCx 67

69 68 Question and Answers

70 Contact information Jim Huber, NEBB Vice President and President of Complete Commissioning Tel: Dave McFarlane, Atkins Tel: Ext

71 Thank you for joining the webcast. To improve future NEBBinars, please take a minute to answer a brief survey that will be sent to you. 70

72 2013 NEBB. All rights reserved. 71

NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings. March 5, 2014

NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings. March 5, 2014 NEBBinar: Technical Commissioning: The most effective commissioning process for new buildings March 5, 2014 0 Moderator Jim Huber, NEBB President-Elect and President of Complete Commissioning Jim Huber

More information

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013 NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.

More information

Project Information. Measure Description

Project Information. Measure Description Project Information Project ID#: CE07M016 Measure: Multiple Electric : 452,593 kwh, 8.84 kw, 39.26 kw Facility Type School Technology: Multiple Measure Description CH-1 - Chiller Plant Optimization and

More information

Building Control Strategies That Work to Improve Your Energy Bottom Line

Building Control Strategies That Work to Improve Your Energy Bottom Line Building Control Strategies That Work to Improve Your Energy Bottom Line William D. (Skip) Milton MBA, CEM, CEA Assistant Director of Facilities Operations Texas Children s Hospital Objective: Learn how

More information

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE

Reducing Hospital Energy Use and Maintaining Savings. Glen Anderson, PE Reducing Hospital Energy Use and Maintaining Savings Glen Anderson, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute of Architects Continuing

More information

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load.

2-Pipe fan coil terminal units were selected as the parallel system to handle the remaining sensible cooling load. Redesign Introduction This report is an in depth analysis of the mechanical systems of the Outreach Innovation Building located in University Park, PA and the impact these changes had on other systems

More information

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response

Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Three Case Studies of the Application of Energy Systems Optimization Best Practices for Automatic Demand Response Yifu Shi Kelly Guiberteau Carlos Yagua, P.E. James Watt, P.E. Energy Systems Laboratory,

More information

Retro-Commissioning for Existing Facilities

Retro-Commissioning for Existing Facilities Retro-Commissioning for Existing Facilities Tom Meyer Director, Technical Programs National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 (301) 977-3698 www.nebb.org

More information

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc.

How LEED & The Retro-Commissioning Credits Produce Energy Savings. James Vallort Vice President Environmental Systems Design, Inc. How LEED & The Retro-Commissioning Credits Produce Energy Savings James Vallort Vice President Environmental Systems Design, Inc. Retro-Commissioning Today s session will focus on the following items:

More information

Retrocommissioning: A Persistence Study

Retrocommissioning: A Persistence Study Retrocommissioning: A Persistence Study Umamaheswar Krishnan and Aniruddha Duttagupta, Nexant, Inc Alan Ahrens, CenterPoint Energy ABSTRACT Retrocommissioning (RCx) projects have become more commonplace

More information

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC

Variable Frequency Drive Retrofit Opportunities. Michael Kuk CERx Solutions LLC Variable Frequency Drive Retrofit Opportunities Michael Kuk CERx Solutions LLC Speaker Introduction» Founder / owner of CERx Solutions LLC» Veteran Owned Small Business Enterprise founded in 2013» 27+

More information

Retrocommissioning Investigation Report

Retrocommissioning Investigation Report Continuous Optimization for Commercial Buildings Program Retrocommissioning Investigation Report March 22, 2013 Prepared for: Thompson Rivers University International Building BC Hydro #:COP10-353 Prism

More information

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time

Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois. Retrocommissioning Saving the Planet One Building at a Time Karl Helmink, P.E., CEM Retrocommissioning Manager University of Illinois Retrocommissioning Saving the Planet One Building at a Time AIA Quality Assurance Portland Energy Conservation, Inc is a registered

More information

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training November 18, 2015 Agenda Commissioning Monitoring Based Commissioning Building Tune up Case

More information

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS

CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS CONTINUOUS COMMISSIONING OF SALT LAKE COMMUNITY COLLEGE SOUTH CITY CAMPUS Song Deng, P.E. and Dan Turner, P.E., Ph.D., Energy Systems Laboratory, Texas A&M University System, College Station, Texas Jim

More information

Success with MEASUREMENT & VERIFICATION

Success with MEASUREMENT & VERIFICATION 2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable

More information

The energy benefits of View Dynamic Glass

The energy benefits of View Dynamic Glass Workplace demonstration Energy monitoring over a period of 12 months resulted in the commercial office room installed with View Dynamic Glass saving 39 percent of the total energy consumed compared to

More information

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Summary Major Fortune 500 Telecom Company Estimated 40% the corporate building portfolio still use pneumatic thermostats

More information

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center September 21 st, 2011 4:15pm 5:15pm Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Energy consumption (BTU/SF) in

More information

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses

SMART HVAC & LIGHTING SYSTEMS. Savings From Two Major C&I End Uses SMART HVAC & LIGHTING SYSTEMS Savings From Two Major C&I End Uses September 21, 2016 PRESENTATION OVERVIEW Why this focus? Significant savings potential Smart controls coupled with more efficient technologies

More information

Use of Building Automation Systems for (Retro)Commissioning

Use of Building Automation Systems for (Retro)Commissioning Center for Energy and Environment Use of Building Automation Systems for (Retro)Commissioning Neal Ray, Center for Energy and Environment Gustav Brändström, Center for Energy and Environment January 17,

More information

EBCx of the Connecticut Convention Center Complex

EBCx of the Connecticut Convention Center Complex EBCx of the Connecticut Convention Center Complex Presentation and Panel Discussion David Vallerie, Principal, Strategic Building Solutions May 20, 2014 AIA Quality Assurance The Building Commissioning

More information

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions

Strategies for Persistence: Measurement and Verification. Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions Strategies for Persistence: Measurement and Verification Ryan Hughes PE, CEM, LEED AP Eaton Energy Solutions AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The

More information

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario

The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario The Impact of VISIONWALL High Performance Windows on the Northern Telecom Building in Ottawa, Ontario Visionwall Technologies Inc. 14904-123 Avenue Edmonton, Alberta, Canada T5V 1B4 Tel: 403 451 4000 Fax:

More information

Recommissioning Workshop

Recommissioning Workshop Recommissioning Workshop October 2, 2013 Dave Moser, PE Senior Engineer PECI PECI 2013 1 Preview for the Day Topic Start time What is existing building commissioning (EBCx)? 8:30 Costs / benefits Case

More information

Energy Savings Audit

Energy Savings Audit Energy Savings Audit PREPARED FOR Steve Bennett Eileen Horn City of Lawrence ASSESSMENT SITE City of Lawrence Arts Center 940 new Hampshire St. Lawrence, KS 66044 ASSESSMENT PERFORMED BY P1 Group Inc 16210

More information

Wireless Pneumatic Thermostats:

Wireless Pneumatic Thermostats: Wireless Pneumatic Thermostats: Quality Commissioning is Essential Peter Pollard, P.E. Principal kw Engineering AIA Quality Assurance The Building Commissioning Association is a Registered Provider with

More information

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM

CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM CHAPTER/REGIONAL TECHNOLOGY AWARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable) Commercial Buildings New or Existing Institutional Buildings: Educational Facilities New

More information

Building Retro-Commissioning

Building Retro-Commissioning Building Retro-Commissioning Ben J. Sliwinski SEDAC Technical Director Smart Energy Presenter s Design Assistance name Professional Center (SEDAC), Title (eg. University architect/energy of Illinois specialist..)

More information

Xavier Energy Initiative

Xavier Energy Initiative Xavier Energy Initiative By Ron Perkins Report of August Site Visit To paraphrase Blaise Pascal, if I had more time I would have written a shorter report. In deference to those who do not share my enthusiasm

More information

Freetown Elementary School

Freetown Elementary School Building and Plant Energy Analysis Technical Report 2 Freetown Elementary School Glen Burnie, MD Matthew R. Buda The Pennsylvania State University Architectural Engineering Mechanical Option Advisor: Dr.

More information

Continuous Commissioning Leading Energy Project Process - An Industry Approach

Continuous Commissioning Leading Energy Project Process - An Industry Approach Continuous Commissioning Leading Energy Project Process - An Industry Approach Mingsheng Liu, Ph.D., P.E. Energy Systems Laboratory, University of Nebraska Jinrong Wang, P.E., Ken Hansen, P.E. Omaha Public

More information

NEBBinar: Building Enclosure Testing. September 25, 2013

NEBBinar: Building Enclosure Testing. September 25, 2013 NEBBinar: Building Enclosure Testing September 25, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning. He has over

More information

Retro-Commissioning in Hospitals

Retro-Commissioning in Hospitals Retro-Commissioning in Hospitals American Society of Healthcare Engineering () Introduction Elements of the Health Facility Retro-Cx Process Retro-Cx Case Studies Hospital Hospital Oklahoma Heart Hospital

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Building Operator Certification Level I

Building Operator Certification Level I Building Operator Certification Level I A Partnership of the CUNY Institute for Urban Systems Building Performance Lab, the CUNY School of Professional Studies, and the New York State Energy Research &

More information

Jim Huber, NEBB Vice President and President of Complete Commissioning

Jim Huber, NEBB Vice President and President of Complete Commissioning October 14, 2014 Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning. He has over 29 years of industry experience, is a Certified

More information

Building Retro-Commissioning

Building Retro-Commissioning Building Retro-Commissioning Greg Swiss SEDAC Building Energy Specialist Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign WHAT IS RETRO-COMMISSIONING? Commissioning

More information

Technical Retro-Commissioning of Existing Buildings

Technical Retro-Commissioning of Existing Buildings Standard S0 0 0 Technical Retro-Commissioning of Existing Buildings Review Draft (--) This draft has been recommended for public review by the responsible project committee. To submit a comment on this

More information

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1

Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Commercial Retro-Commissioning Program Manual for 2015 SECTION 1 Introduction The Commercial Retro-Commissioning Program (RCx) is designed to achieve demand and energy savings in commercial facilities.

More information

Energy Efficiency in Multi-Tenant Office Buildings

Energy Efficiency in Multi-Tenant Office Buildings Energy Efficiency in Multi-Tenant Office Buildings Presented by David Herman, PE, LEED AP Principal, EnerG Associates, LLC 3/10/2015 1 Learning Objectives 1. List the principal sources and uses of energy

More information

Steps to Making Existing Commercial Buildings Become High Performance. Jim Bochat

Steps to Making Existing Commercial Buildings Become High Performance. Jim Bochat Steps to Making Existing Commercial Buildings Become High Performance Jim Bochat Steps to Advanced Existing Building Energy Performance Presentation s Reference Documents ASHRAE s Energy Efficiency Guides

More information

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC LIBRARY ENERGY WALK- THROUGH Andy Robinson, Training and Education, SEDAC ILLINOIS ENERGY NOW University of Illinois 360 Energy Group 2 WHAT WE DO SEDAC Free Services Outreach and Training Energy Assistance

More information

University of Minnesota Duluth Civil Engineering Building

University of Minnesota Duluth Civil Engineering Building Energy Data Attachment University of Minnesota Duluth Civil Engineering Building LEED Energy Modeling The energy modeling for LEED NC 2.2 was performed against ASHRAE 9.1-24 Appendix using equest version

More information

Underf loor For Schools

Underf loor For Schools The following article was published in ASHRAE Journal, May 2008. Copyright 2008 American Society of Heating, Refrigerating and Air-Conditioning Engineers, Inc. It is presented for educational purposes

More information

NURTURING FUTURE GLOBAL CITIZENS THROUGH SUSTAINABLE FACILITIES

NURTURING FUTURE GLOBAL CITIZENS THROUGH SUSTAINABLE FACILITIES NURTURING FUTURE GLOBAL CITIZENS THROUGH SUSTAINABLE FACILITIES GONZAGA S MULTIPRONGED APPROACH TO INSTITUTING SUSTAINABILITY VIA NEW DESIGN AND ON-GOING CAMPUS OPERATIONS & MAINTENANCE AGENDA INTRODUCTIONS

More information

Technical Report Three Mechanical Systems Existing Conditions Evaluation

Technical Report Three Mechanical Systems Existing Conditions Evaluation 09 10 Technical Report Three Mechanical Systems Existing Conditions Evaluation WESTINGHOUSE ELECTRIC CO. NUCLEAR ENGINEERING HEADQUARTERS CAMPUS Pittsburgh, PA Daniel P. Aughenbaugh Mechanical Dr. Bahnfleth

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Oklahoma University Children s Medical Office Building

Oklahoma University Children s Medical Office Building Oklahoma University Children s Medical Office Building Oklahoma City, O.K., BAE Advisor: Laura Miller Presentation Outline VRF System Dedicated Outdoor Air System Evaluation VRF Indoor Units Design Criteria

More information

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne Existing Building Cx: Processes & Results A Cultural Journey Barry Abramson Senior Vice President Servidyne AIA Quality Assurance Learning Objectives 1. Define the key steps in the process of retrocommissioning

More information

Commissioning & Retro-Commissioning Meet Energy Code

Commissioning & Retro-Commissioning Meet Energy Code Commissioning & Retro-Commissioning Meet Energy Code Agenda Introductions What is Commissioning Value of Commissioning Code Required Cx Process Customize your Cx Process What documentation should be expected

More information

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA

05/14/2012 THE CRIME OF IMPROPER ENERGY MANAGEMENT AGENDA THE CRIME OF IMPROPER ENERGY MANAGEMENT COOLING MANAGEMENT SOLUTIONS Dan Mascola AGENDA Promote Background Cooling Management Solutions Case Studies Additional Energy Savings Tips How To Start on Monday

More information

CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH. William D. Turner, P.E., Ph.D. Song Deng, P.E.

CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH. William D. Turner, P.E., Ph.D. Song Deng, P.E. CONTINUOUS COMMISSIONING OF THE MATHESON COURTHOUSE IN SALT LAKE CITY, UTAH William D. Turner, P.E., Ph.D. Song Deng, P.E. Director Assistant Director Energy Systems Laboratory Texas A&M University System

More information

THE KEMPER BUILDING 1 EAST WACKER DRIVE PHIL KEUHN SIEBEN ENERGY ASSOCIATES

THE KEMPER BUILDING 1 EAST WACKER DRIVE PHIL KEUHN SIEBEN ENERGY ASSOCIATES THE KEMPER BUILDING 1 EAST WACKER DRIVE BY PHIL KEUHN OF SIEBEN ENERGY ASSOCIATES CHAPTERfREGIONAL TECHNOLOGY A WARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable).,..(!)~8(}~lnerc[~i~~ii9in:~~).,...;;().

More information

Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System

Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System Eric Baxter, Hannah Friedman, Larry Luskay, and Tudi Haasl, Portland Energy Conservation,

More information

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation

Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation Mechanical Technical Report Three Mechanical Systems Existing Conditions Evaluation 2900 Fairview Park Drive, Prepared By: Charles Haack Mechancial Option November 21, 2008 Prepared For: Dr. William P.

More information

Final Commissioning (Cx) Retro-Commissioning (RCx) Policy

Final Commissioning (Cx) Retro-Commissioning (RCx) Policy Final Commissioning (Cx) Retro-Commissioning (RCx) Policy Final Policy Strategic Plan Task 3.2.4 Deliverable 5.5 Funded by Southern California Edison Company Local Government Strategic Plan Strategies

More information

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas

You Can t Afford Discomfort. Dan Int-Hout Chief Engineer, Krueger Richardson, Texas You Can t Afford Discomfort Dan Int-Hout Chief Engineer, Krueger Richardson, Texas Where We Are Today: So You Want To Save Money? Things to consider: 1. First Cost 2. Energy cost 3. Occupant Salary costs

More information

Georgetown University New Science Center

Georgetown University New Science Center Georgetown University New Science Center Final Thesis Proposal PENN STATE UNIVERSITY Prepared For: Dr. William P. Bahnfleth Department of Architectural Engineering Prepared By: Kevin M Edstrom Mechanical

More information

Building X Retrocommissioning Final Report

Building X Retrocommissioning Final Report Building X Retrocommissioning Final Report A study done by Portland Energy Conservation, Inc. (PECI) And Partner IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC

More information

MBCx: The Next Wave of Energy Savings in Utility Incentive Programs

MBCx: The Next Wave of Energy Savings in Utility Incentive Programs AABC Commissioning Group AIA Provider Number 50111116 MBCx: The Next Wave of Energy Savings in Utility Incentive Programs Course Number: CXENERGY1716 Walid Guerfali, ComEd Ben Talbot, DLR Group Ruairi

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

Existing Building Commissioning (or Retro-Commissioning)

Existing Building Commissioning (or Retro-Commissioning) SOUTHEAST REGION Existing Building Commissioning (or Retro-Commissioning) SERBCA Annual Meeting Covington, KY December 6, 2013 Session Learning Objectives o Definition of Existing Building Cx / RetroCx

More information

BOMA s Energy Efficiency Program BEEP Course 4. No- and Low Cost Operational Adjustments to Improve Energy Performance

BOMA s Energy Efficiency Program BEEP Course 4. No- and Low Cost Operational Adjustments to Improve Energy Performance BOMA s Energy Efficiency Program BEEP Course 4 No- and Low Cost Operational Adjustments to Improve Energy Performance Agenda Review ENERGY STAR's Energy Performance Rating System Identify specific areas

More information

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel

Retrocommissioning Investigation Study of the Sheraton Chicago Hotel Retrocommissioning Investigation Study of the Sheraton Chicago Hotel & Towers Cityfront Center Tracy Phillips May 4, 2007 May 4, 2007 You can go anywhere you want, if you look serious and carry a clip

More information

Retro-Commissioning for Energy Efficiency

Retro-Commissioning for Energy Efficiency High Performance Buildings 2006 AABC Commissioning Group (ACG) April 6, 2006 Retro-Commissioning for Energy Efficiency Making buildings work. Better. Tom Poeling, P.E., CEM, LEED AP E M C Engineers, Inc.

More information

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems AIHEC VENT 2006 Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems Thomas C. Smith Exposure Control Technologies, Inc. Safety is the Primary Objective Lab Occupancy 26%

More information

EnergyPro Building Energy Analysis. Single-story School Building

EnergyPro Building Energy Analysis. Single-story School Building EnergyPro Building Energy Analysis Single-story School Building EnergyPro Building Energy Analysis for a single-story school bulding Project Scope The purpose of the EnergyPro energy model was to evaluate

More information

Introduction to Building Analytics

Introduction to Building Analytics INNOVATION INNOVATION Introduction to Building Analytics www.ecosave.com.au INNOVATION INNOVATION Lunch + Analytics = Sleep www.ecosave.com.au INNOVATION What? Why? How? www.ecosave.com.au Who is Watching?

More information

EADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel Mechanical Option

EADQUARTERS. Thesis Revised Proposal. Stephanie Kunkel  Mechanical Option EADQUARTERS 707 N. Calvert St. Mechanical System Renovation Construction Management & Lighting/Electrical Breadths Stephanie Kunkel www.engr.psu.edu/ae/thesis/portfolios/2011/slk5061 Mechanical Option

More information

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate

Characteristics of Energy Consumption by building type of a U.S. Navy Installation in Hot and Humid Climate Purdue University Purdue e-pubs International High Performance Buildings Conference School of Mechanical Engineering 216 Characteristics of Energy Consumption by building type of a U.S. Navy Installation

More information

LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS

LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS LOW CARBON HEATING FOR COMMERCIAL BUILDINGS USING GRID SUPPLIED ELECTRCITY DURING-OFF PEAK PERIODS R. Hutcheson, P.Eng. LEED AP, CxA, S. Jorens B.Eng., D. Knapp, PhD., P.Phys., LEED AP Arborus Consulting

More information

WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION

WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION 1 WHOLE BUILDING RETROFITS: A CONTRACTOR/SUPPLIER DEMONSTRATION Professor Kirk Alter Purdue University Fast Management, Inc. SESSION DESCRIPTION Whole Building Retrofits: A Contractor/Supplier Demonstration

More information

Mechanical Systems Proposal

Mechanical Systems Proposal Mechanical Systems Proposal Prepared for: Dr. William Bahnfleth, Professor The Pennsylvania State University, Department of Architectural Engineering Prepared by: Chris Nicolais Mechanical Option December

More information

Energy Treasure Hunt ESI Members Meeting. Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity

Energy Treasure Hunt ESI Members Meeting. Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity Energy Treasure Hunt 2017 ESI Members Meeting Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity Agenda What is an Energy Treasure Hunt? What value do they bring? What are the results? Who are

More information

Matt Gudorf Campus Energy Manager. Page 1

Matt Gudorf Campus Energy Manager. Page 1 Matt Gudorf Campus Energy Manager Page 1 Quick Facts About UCI 7.4 Million Square Feet of Conditioned Space District High Temp and Chilled Water Campus 12kV owned and operated grid 4.5 Million Gallon Thermal

More information

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System)

Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat Recovery VRF System) Energy Efficiency Analysis for a Multi-Story Research Office Building (LG Multi V Water IV Heat VRF System) (* Source: http://kr.lgeaircon.com/) Commercial Air-Conditioning Engineering Study ES-MultiVWaterIV_EnergyAnalysis-08-14

More information

Baffled Openings at Chain Link Fencing: Design shall consist of two end-posts set 4 feet apart, and a 10 foot wide chain-link fence panel equal in height as the adjacent fence. Chain link fence panel shall

More information

Figure 26.5 Potential fan energy savings using fan speed limiting 16.

Figure 26.5 Potential fan energy savings using fan speed limiting 16. COMMISSIONING FOR ENERGY MANAGEMENT 685 Figure 26.5 Potential fan energy savings using fan speed limiting 16. 26.4.2.2. Set Minimum Outside Air Intake Correctly Outside air intake rates are often significantly

More information

OPTION 1: PERFORMANCE RATING METHOD

OPTION 1: PERFORMANCE RATING METHOD OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2 Simulation General Requirements' in Appendix

More information

RETROCOMMISSIONING S GREATEST HITS

RETROCOMMISSIONING S GREATEST HITS RETROCOMMISSIONING S GREATEST HITS Tudi Haasl Associate Director PECI Portland, Oregon Amanda Potter Project Manager PECI Portland, Oregon Linda Irvine Program Assistant PECI Portland, Oregon Larry Luskay

More information

Management Committee December 3, Johnson County Community College Retrocommissioning Report

Management Committee December 3, Johnson County Community College Retrocommissioning Report Johnson County Community College Retrocommissioning Report Management Committee December 3, 2014 What is Retrocommissioning? Retrocommissioning is a systematic process to improve an existing building s

More information

BETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information

BETA OPTION 1: PERFORMANCE RATING METHOD. Section General Information LEED-CS 2. Certification Submittal Template OPTION 1: PERFORMANCE RATING METHOD I confirm that the energy simulation software used for this project has all capabilities described in EITHER section `G2

More information

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma

The Creative and Performing Arts High School (CAPA) Pittsburgh, PA 9/30/2002 Andrew Tech Mechanical Option Prof. S. A. Mumma LEED Green Building Certification The purpose of the LEED Green Building Rating is to provide a national standard that aims to improve environmental, health and economic performance of buildings using

More information

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Do-It-Yourself Energy Audit Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Agenda» Basic Terminology» Background» Benchmarking» Audit Types/ASHRAE Standard» Building Audit Systems

More information

Turn off fossil fuels. Turn on the power of nature. Energy Audits Hot Water Solutions. Solar Electricity Heat Pumps

Turn off fossil fuels. Turn on the power of nature. Energy Audits Hot Water Solutions. Solar Electricity Heat Pumps Turn off fossil fuels. Turn on the power of nature. Energy Audits Hot Water Solutions Solar Electricity Heat Pumps It s going to get cold outside... So let s talk about heat. Heat Pumps Ground Source Heat

More information

how to read an energy model

how to read an energy model how to read an energy model Kohler Ronan, LLC is a Registered Provider with The American Institute of Architects Continuing Education Systems. Credit earned on completion of this program will be reported

More information

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader Building Controls Strategies Conference Retro-Commissioning with BAS Overview 10 March 2015 Steve Brown, CAP ESD Controls Team Leader Kevin Caho PE, LEED AP ESD Energy Engineer Agenda BAS Overview RCx

More information

COOLING COIL (35% ETHYLENE GLYCOL)

COOLING COIL (35% ETHYLENE GLYCOL) APPENDIX Contents A1.1 Existing Mechanical Equipment Schedules A1.2 Existing Mechanical System Schematic Drawings A2. Building Design Loads, Energy Loads and Cost Data Tables A3. Standard 62n-2001 Ventilation

More information

Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E.

Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates. Jeff S. Haberl, Ph.D., P.E. Analysis of the Energy Savings Potential in K-5 Schools in Hot and Humid Climates Piljae Im Graduate Student Jeff S. Haberl, Ph.D., P.E. Professor Energy Systems Laboratory Texas Engineering Experiment

More information

University of Southern California Main Campus Plant Energy use reduction of 49% compared to previous plants and control strategies.

University of Southern California Main Campus Plant Energy use reduction of 49% compared to previous plants and control strategies. Foreword Most chiller based systems save energy when compared to packaged cooling equipment, but they waste a substantial amount of energy compared to their optimized state of operation. On an annual basis,

More information

Promulgation Details for 1 RCNY

Promulgation Details for 1 RCNY Promulgation Details for 1 RCNY 103-07 This rule became effective on October 13, 2012. Since such date, one or more amendments have been made to this rule. Each rule amendment has its own effective date

More information

Energy Reduction in Hospitals

Energy Reduction in Hospitals Energy Reduction in Hospitals OSBORN ENGINEERING DAVE CHOUINARD, CBCP, LEED AP, DIRECTOR HEALTHCARE CARL SCHULTZ, PE, DIRECTOR ENERGY AND FACILITY SYSTEMS MARK WUTZ, PE, DIRECTOR ENERGY & COMMISSIONING

More information

ILLINOIS ENERGY NOW Energy Efficiency Incentives for State Facilities. December 2016

ILLINOIS ENERGY NOW Energy Efficiency Incentives for State Facilities. December 2016 ILLINOIS ENERGY NOW Energy Efficiency Incentives for State Facilities December 2016 1 ILLINOIS OFFICE OF ENERGY & RECYCLING Business Development Community Development Illinois Department of Commerce &

More information

FirstEnergy s Pennsylvania Utilities. Energy Efficiency Programs for Business

FirstEnergy s Pennsylvania Utilities. Energy Efficiency Programs for Business FirstEnergy s Pennsylvania Utilities Energy Efficiency Programs for Business 2018 TODAY S AGENDA Introduction to Sodexo Summary of Pennsylvania Act 129 Overview of program website Overview of Application

More information

Energy Saving Calculations for Recommissioning and Design

Energy Saving Calculations for Recommissioning and Design ASHRAE December Chapter Meeting Energy Saving Calculations for Recommissioning and Design Gustav Brändström Angela Vreeland December 13, 2011 Agenda Agenda Introduction Trending and Trend Data TMY and

More information

Final Thesis Report: Mechanical Alternative Systems

Final Thesis Report: Mechanical Alternative Systems The American Swedish Institute Minneapolis, MN Final Thesis Report: Mechanical Alternative Systems Analysis Name: Option: Mechanical Advisor: Stephen Treado Date: 4.4.12 Table of Contents Abstract 5 Executive

More information

Pay Now or Pay Forever Commissioning the Design of Control System Software

Pay Now or Pay Forever Commissioning the Design of Control System Software Pay Now or Pay Forever Commissioning the Design of Control System Software Bill Gnerre Interval Data Systems May 2, 2007 The Classic Struggle Construction First cost Design it right Pay now Operations

More information

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning

Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Commercial Building Performance Evaluation System for HVAC Diagnostics and Commissioning Stuart S. Waterbury and Donald J. Frey, Architectural Energy Corporation Karl F. Johnson, Electric Power Research

More information