COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and
|
|
- Marcia Goodman
- 6 years ago
- Views:
Transcription
1 Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Epsilon Midsun 579 RTV Anti-Corrosion Coating In COASTAL INDIA Supply & Application of 8,000kg of Epsilon Midsun HVIC by Epsilon Asia Group: 2011
2 Epsilon: Key Partners in India Epsilon an engineering company and is exclusive national partners with: Dongfang India for Minimal-Oil Boiler Combustion Systems Dongfang-Hitachi VFDs, PV Inverters SYCG/Nexans XLPE Cable Epsilon Midsun HVIC & Silicones
3 Switchyard Overview Insulators prone to severe contamination due to: Coastal Location Cooling Tower Drift as Seawater is used for cooling No Drift Eliminator Installed at the Cooling Towers at the time Extreme Leakage Current & Corona observed Frequency of unplanned outages due to flashovers was increasing rapidly Extreme Corrosion on JBs and metal infrastructure observed epsilon
4 Contaminated Insulator Surfaces Despite Extremely frequent Washing Cycles, pollution deposits were unavoidable The salt deposit in this image is within 7 days of the previous wash
5 Extreme Corrosion to Ferrous Infrastructure Metal Infrastructure Corroding within 18 months Such Corrosion Results in degrading IP54/IPxx ratings which pose a safety risk Changing JBs requires recommissioning of equipment After coating with EM 579, Resistance to Corrosion Fortified epsilon
6 Corona Visible with the naked eye epsilon
7 Corona Visible through UV Corona-Cam Watch the Full Video at:
8 HVIC of Choice: Epsilon Midsun 570 Gen-4 RTV Ultra-Hydrophobic RTV High Voltage Insulator Coating (HVIC) Targets: Mitigate Risks of Leakage Current Reduce the need for Insulator Washing Mitigate Risks of Flashovers
9 Conductive Tracking Path Cannot be Formed (All drops of water are discrete)
10 IEEE Evaluation of RTV Coating in Coastal Conditions IEEE Evaluation of RTV Coating for Station Insulators subjected to Coastal Pollution H.M Schneider, Senior Member, EPRI High Voltage Research Centre) Performance of Breaker Support Insulators (BSIs) tested before and after application of RTV Coating Resistance to Flashovers tested in field tests to check for additional equivalent creepage imparted by the coating
11 The results Measurements are given in ESDD as: Quantity of NaCl per unit area (mg/cm 2 ) Test Reports showed ESDD as high as mg/cm 2 several months after wind storms, natural and manual washing Uncoated BSIs flashed over at 209kV RTV coated BSIs flashed over at 300kV Improvement of performance of: 43.5% withstand voltage
12 Hydrophobicity Recovery (CPRI labs Test) It is essential for the silicone material to recover its hydrophobicity for long-term effective performance Epsilon HVIC Test Results of Hydrophobicity recovery at CPRI Hydrophobicity Tested (CPRI Labs) Virgin Sample HC 1 After 100-hours continuous exposure to Corona Epsilon Midsun Hydrophobicity Recovery within 48 hours of Corona Destruction HC 6 HC2 Hydrophobicity Classification (HC level as per STRI) epsilon
13 Hydrophobicity (Water-Repellency) Classification Hydrophobicity Classification (HC) goes from HC1 to HC7 HC1: Completely Hydrophobic HC7: Completely Hydrophilic HC Description HC1 HC2 HC3 Only discrete droplets formed. θ r 80 (or larger) for majority of droplets Only discrete droplets formed. 50 <θ r < 80 for the majority of droplets. Only discrete droplets formed. 20 < θ r <50 for majority of droplets. Usually they are no longer circular HC6 Wetted areas cover > 90% small un-wetted areas still observed HC7 Continuous water film Typical Examples from HC1 to HC6 epsilon
14 Application Procedure
15 Surface Preparation epsilon
16 Gentle Scraping of Salt Deposits epsilon
17 Application of Epsilon HVIC Airless Spray Application epsilon
18 Application of Epsilon HVIC epsilon
19 Corona Eliminated on Coated Insulators
20 Epsilon HVIC Team Safety Training + Documentation SEP 2011 Scheduled Start: 01 OCT 2011 Actual Site Mobilization: 01 OCT 2011 Scheduled End: 31 OCT 2011 Actual End: 98.5% job completed by 31 OCT 2011 At least 9 working days were lost due to UPCL not being given shutdown permission by Karnataka Government epsilon
21 Thank you Epsilon Asia Group X29 Hauz Khas, New Delhi, India Level 29, Offices at CentralWorld, Bangkok, Thailand ;
EPSILON EM-SILPROCOAT RTV ANTI-CORROSION RUBBER COATING TECHNICAL DATASHEET & SPECIFICATIONS
EPSILON EM-SILPROCOAT RTV ANTI-CORROSION RUBBER COATING TECHNICAL DATASHEET & SPECIFICATIONS Version 3.0; January 2015 TABLE OF CONTENTS Contents Introduction 1 Technical Specifications 3 Storage, Handling,
More informationSi-COAT 570 RTV Silicone HVIC. Reliability & Beyond. Seminar Presentation
Si-COAT 570 RTV Silicone HVIC Reliability & Beyond Seminar Presentation Overview Background & industry pressures Early validation of Si-COAT HVIC The science of Si-COAT Q&A Si-COAT HVIC : The Background
More informationCigré WG C Topics: The selection of insulators with respect to polluted conditions
Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise
More informationfire Charcoat Charcoat IC Passive Protection
Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a
More informationMidsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.
Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot
More informationMidsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing.
Midsun 570 Midsun HVIC silicone is not affected by UV light, temperature, corrosive environments, or ATH pitting from dry band arcing. Because the coating is highly water repellent, contaminant s cannot
More informationPERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS
International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10
More informationEXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION
EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani
More informationPolluted Outdoor Insulators Maintenance and Washing
Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان
More informationEffect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators
IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and
More informationPOLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES
Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216
More informationDevelopment of Composite Line Spacers for Distribution Lines
Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax
More informationDiagnostic Techniques of Composite Insulators
Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI
More informationPredicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations
Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area
More informationVijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1
Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate
More informationILMOS Insulator Leakage Current Monitor
ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable
More informationData Sheet 110kV TD123II dry type outdoor termination
3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,
More informationA-PDF PPT TO PDF DEMO: Purchase from to remove the watermark
EMERGING TECHNOLOGIES SILIDRIL - Polymeric Coating & SHRIJI - CONDUCTIVE SILICON GEL By: Surat Prestech Pvt. Limited Prepared By Mr. Nitin Oza, M.E. & Dr. Rafael Mier, PhD. A-PDF PPT TO PDF DEMO: Purchase
More informationAgeing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test
Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test J. Grasaesom, S. Thong-om, W. Payakcho and B. Marungsri* Abstract This paper presents the experimental results
More informationPerformance investigation of composite and RTV SIR coated insulators at a coastal test station
Performance investigation of composite and RTV SIR coated insulators at a coastal test station K. Siderakis High Voltage Laboratory, Technological and Educational Institute of Crete D. Pylarinos High Voltage
More informationPins Insulator. Composite/Polymers Insulators
Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make
More informationArtificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester
Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results
More informationINSULATOR REQUERIMENTS:
2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL
More informationPerformance of Thermoplastic Elastomeric and Thermoset Insulators under Accelerated Acid Rain Multistress Conditions
Performance of Thermoplastic Elastomeric and Thermoset Insulators under Accelerated Acid Rain Multistress Conditions Raji Sundararajan, Victor Godinez and Muhammad Amin Abstract Polymers are becoming the
More informationSANERGRID, représentant exclusif France
MIDSUN GROUP SILPROCOAT CORROSION PROTECTION Midsun Silprocoat RTV Coating Corrosion Protection Silicone Coating Why? Midsun Silprocoat is a one part silicone elastomer coating. Silicone elastomer coatings
More informationDifferent Characteristics of Artificially Polluted High Voltage Composite Insulators
Different Characteristics of Artificially Polluted High Voltage Composite Insulators Farhad Shahnia 1 and Ghasem Ahrabian 2 1 Eastern Azarbayjan Electric Power Distribution Company, Tabriz, Iran 2 Faculty
More informationComposite Insulator Components
Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the
More informationPerformance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions
Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various
More informationESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled
ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS by Abdelrahman Khaled A Thesis Presented to the Faculty of the American University of Sharjah College of Engineering in Partial Fulfillment of the Requirements
More informationESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE
ESDD MEASUREMENTS IN THE POWER SYSTEM OF CRETE Dionisios PYLARINOS Consultant, Hellenic Electricity Distribution Network Operator S.A., Greece dpylarinos@yahoo.com Kiriakos SIDERAKIS Assistant Professor,
More informationEvaluation of Silicone Rubber Insulators used in High-Voltage Transmission Lines Anwar Ul-Hamid, Khaled Y. Soufi, and Ibrahim AI-Hamoudi
JMEPEG (2008) 17280-286 DOl: 10.1007/s11665-007-9142-z Evaluation of Silicone Rubber Insulators used in High-Voltage Transmission Lines Anwar Ul-Hamid, Khaled Y. Soufi, and Ibrahim AI-Hamoudi (Submitted
More informationINCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS
INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS M N R Baharom 1*, Ian Cotton 1 1 School of Electrical & Electronic Engineering, The University of Manchester,
More informationMitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan
Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan Substation Insulator Pollution Contamination Management PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION
More informationLaboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators
Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis
More informationNatural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment
energies Article Natural Contamination and Surface Flashover on Silicone Rubber Surface under Haze Fog Environment Ang Ren 1,2 ID, Hongshun Liu 1,2, *, Jianchun Wei 1,2 and Qingquan Li 1,2 1 Department
More informationExperimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions
International Journal of Physical Sciences Vol. 7(47), pp. 6162-6168, 16 December, 2012 Available online at http://www.academicjournals.org/ijps DOI: 10.5897/IJPS12.508 ISSN 1992-1950 2012 Academic Journals
More informationPrediction of flashover voltage of non-ceramic insulators under contaminated conditions
Prediction of flashover voltage of non-ceramic insulators under contaminated conditions S. Venkataraman and R. S. Gorur Department of Electrical Engineering Arizona State University Tempe, AZ, USA ABSTRACT
More informationIndustrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC. (White Paper) NeverWet LLC
Industrial Coatings: HIGHLY DURABLE, SUPERHYDROPHOBIC AND OLEOPHOBIC (White Paper) NeverWet LLC Background: Metal surfaces have high surface energy, are negatively charged, and hydrophilic as shown by
More informationHIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators
HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium
More informationComparison of effects of Various Contaminations on SiR insulators
Volume 120 No. 6 2018, 609-620 ISSN: 1314-3395 (on-line version) url: http://www.acadpubl.eu/hub/ http://www.acadpubl.eu/hub/ Comparison of effects of Various Contaminations on SiR insulators Satheesh
More informationEffect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator
Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering
More informationEvaluation of Actual Field Ageing on Room Temperature Vulcanized Silicone Rubber Coating of Ceramic Insulators on 230/63 Substation
Evaluation of Actual Field Ageing on Room Temperature Vulcanized Silicone Rubber Coating of Ceramic Insulators on 230/63 Substation Iman Ahmadi-Joneidi 1*, Majid Rezaei 1, Hasan Kahuri 2, Jalil Sahragard
More information15 O&M Issues in Solar Farms
15 O&M Issues in Solar Farms Perimeter Fence Damage Damage caused to the perimeter fence can immediately have a negative effect on facility operations. Whether the damage was due to vandals, a storm or
More informationCO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment
CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment Abstract This paper provides an overview of how CO 2 cleaning works on energized electrical equipment. It also presents
More informationEnergy Division Insulators
Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products
More informationTROPICAL CLIMATE EFFECT OF HYDROPHOBICITY AND SURFACE LEAKAGE CURRENT ON ELECTRICAL INSULATION MATERIALS (SILICONE RUBBER AND FLY ASH)
TROPICAL CLIMATE EFFECT OF HYDROPHOBICITY AND SURFACE LEAKAGE CURRENT ON ELECTRICAL INSULATION MATERIALS (SILICONE RUBBER AND FLY ASH) Salama Manjang, Ikhlas Kitta, Gassing, Stephie Walukow Christiono
More informationPolymer Suspension Insulators 69kV to 765kV
CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition
More informationCOMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS
COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS BY ADNAN SALAMA KRZMA B.SC., M.SC., ELECTRICAL ENGINEERING Thesis submitted to Cardiff University In candidature
More informationINSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development
INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development MARKET FORCES THAT INFLUENCE RAYCHEM SALES PUBLIC UTILITY COMMISSIONS (System Reliability) SALES US FISH & WILDLIFE (Avian Electrocutions)
More informationComposite Outdoor High Voltage Insulators in Crete - 37 Years of Experience
Trivent Publishing The Authors, 2016 Available online at http://trivent-publishing.eu/ Engineering and Industry Series Volume Power Systems, Energy Markets and Renewable Energy Sources in South-Eastern
More informationCHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS
CHAPTER 6 HIGH VOLTAGE ELECTRICAL TESTING RESULTS 6.1 Introduction An electrical porcelain insulator plays an eminent role in electrical power system. As the insulators have high resistance path so it
More informationMeasurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments
F E A T U R E A R T I C L E Measurement of Leakage Current for Monitoring the Performance of Outdoor Insulators in Polluted Environments Key words: insulators, pollution, leakage current, diagnostic techniques,
More informationSelection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN
21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an
More informationGROUP A. Polymeric Insulators.
GROUP A Polymeric Insulators PYUNGIL Bldg., 1475-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-6650~3 FAX : 82-31-424-7300 www.pyungil.com Silicone Railway
More informationCS type composite silicone insulators up to 750 kv overhead lines for all pollution of the atmosphere levels
Climate test equipment. Allows to perform test in various temperature and humidity conditions. CS type composite silicone insulators up to overhead lines for all pollution of the atmosphere levels Insulators
More informationA Study of Critical Positive Impulse Flashover of 24 kv Contaminated Insulators
The 5 th PSU-UNS International Conference on Engineering and 467 Technology (ICET-2011), Phuket, May 2-3, 2011 Prince of Songkla University, Faculty of Engineering Hat Yai, Songkhla, Thailand 90112 Study
More informationMapping HV Insulators Pollution in the Mediterranean Island of Crete
1 Mapping HV Insulators Pollution in the Mediterranean Island of Crete D. Pylarinos, K. Siderakis, N. Mavrikakis, E. Thalassinakis Abstract The reliability of High Voltage insulators is rather important
More informationSYLGARD High Voltage Insulator Coating. A guide to proper application
SYLGARD High Voltage Insulator Coating A guide to proper application A Ready-to-Use Coating SYLGARD High Voltage Insulator Coating (HVIC) is a one-component, ready to use silicone elastomer dispersion
More informationComparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators
DOI: 10.2478/achi-2013-0009 ACTA CHEMICA IASI, 21_2, 93-106 (2013) Comparative study on field collected samples of aged silicon rubber composite coatings for high voltage insulators I.V. Tudose, 1,4 M.
More informationResearch methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications
16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,
More informationPorcelain versus Polymer Insulator- A Changing Era in Transmission Lines
Porcelain versus Polymer Insulator- A Changing Era in Transmission Lines K. R. Suri a, A. Gupta b, Y. Anand b, S. Anand b General Manager (Retd.), Power Grid Corporation of India Limited School of Energy
More informationMeasurement of surface resistance of silicone rubber sheets under polluted and dry band conditions
Electr Eng (2018) 100:1729 1738 https://doi.org/10.1007/s00202-017-0652-x ORIGINAL PAPER Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions Arshad 1 A. Nekahi
More informationElectric field analysis of 132kV EPDM insulator and correlation with ageing features
2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Electric field analysis of 132kV EPDM insulator and correlation with ageing features Antonios Tzimas, Christos Zachariades
More informationThe Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions
1 The Reliability Study of the Statistical Method on Insulator Dimensioning of (U)HVDC Lines with Regard to Pollution Conditions Ying Long 1, Yan Xiao 1, Zhiyi Su 2, Dong Wu 3, Urban Astrom 3 Abstract--The
More informationSILICONE RUBBER INSULATORS WITH NOTCHED SURFACE
SILICONE RUBBER INSULATORS WITH NOTCHED SURFACE K. L. Chrzan Wroclaw University of Technology, Institute I 7, 5-37 Wroclaw, Poland Email: krystian.chrzan@pwr.wroc.pl Abstract: A modification of an insulator
More informationPS2: Lifetime management, deterioration and ageing of substation equipment
PS2: Lifetime management, deterioration and ageing of substation equipment Ageing and deterioration of composite post insulators exposed to high electric field in 220 kv and 400 kv switchyards in Swedish
More information6C-001 High-Voltage Pin-Type Insulator
DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between
More informationInsulators pollution problem: Experience from the coastal transmission system of Crete
Insulators pollution problem: Experience from the coastal transmission system of Crete N.C. Mavrikakis, and E. Koudoumas Electrical Engineering Department, Technological Educational Institute of Crete,
More informationCONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER
The 19 th International Symposium on High Voltage Engineering, Pilsen, Czech Republic, August, 23 28, 2015 CONDITION ASSESSMENT OF A FIELD-AGED 150 kv HTV SIR SUSPENSION INSULATOR FOLLOWING FLASHOVER N.
More informationDurability of Cement Based Building Materials
Page 1 of 6 Durability of Cement Based Building Materials Ajay Ranka and Prakash Mehta Zydex Industries ABSRACT Cement based building materials undergo destructive chemical reactions. Some of the reactions
More informationINSULATORS NEW. See page J-4 for more information.
INSULATORS INSULATORS NEW Improved 23613 Dead End/Suspension Insulator Salisbury s Improved 23613 Dead End/Suspension Insulator has aluminum end fittings. These new end fittings create a lightweight product
More informationArtificial intelligence assessment of sea salt contamination of medium voltage insulators
Artificial intelligence assessment of sea salt contamination of medium voltage insulators D.S. OIKONOMOU 1 T.I. MARIS 2 L. EKONOMOU 3 oikonomoudim@gmail.com maris@teihal.gr lekonomou@hau.gr 1 Agricultural
More informationLaboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions
International Journal of Electrical & Computer Sciences IJECS-IJENS Vol: 12 No: 03 1 Laboratory Investigation on Hydrophobicity of New Silicon Rubber Insulator under Different Environmental Conditions
More informationPolymer Cutout Testing Recommendations
1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)
More informationPorcelain Insulator Performance under Different Condition of Installation around Aligarh
Porcelain Insulator Performance under Different Condition of Installation around Aligarh Asfar Ali Khan and Ekram Husain Abstract Modern Society is strongly dependent on a reliable power supply. The availability
More informationAn Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa
> REPLACE THIS LINE WITH YOUR PAPER IDENTIFICATION NUMBER (DOUBLE-CLICK HERE TO EDIT) < 1 An Investigation Into The Methodology To Develop An Insulator Pollution Severity Application Map For South Africa
More informationHeight Pole Care and Maintenance
Height Pole Care and Maintenance Updated 9/1/2016 Page 1 9 TABLE OF CONTENTS INTRODUCTION...3 NEW HEIGHT POLE TESTING...3 FIELD CARE OF HEIGHT POLE...3 FIELD CLEANING...3 COMPLETE CLEANING OF HEIGHT POLE...
More informationBELTRAN TECHNOLOGIES, INC. Process gas cleanup from Coal and Municipal Gasification. By Duane S Abbott Beltran Technologies, Inc.
Process gas cleanup from Coal and Municipal Gasification By Duane S Abbott Beltran Technologies, Inc. April 28 th, 2011 Beltran Technologies, Inc. 1133 East 35 Street Brooklyn, N.Y. 11210 Founded in 1946
More informationQ30 SUPER PROTECTIVE FILM
Product Size 400ml Gross Weight 370g Net Weight 276g UN Number 1950 Custom Code 3403.19.00 Country of Manufacture RSA Barcode 6001690300757 Article Number 030061 CHARACTERISTICS Colour Texture Odour Temp
More informationSV-ACFC Aluminum Conductor Composite Core (ACCC)
SV-ACFC Aluminum Conductor Composite Core (ACCC) SV-ACFC ACCC is a high and new technological product that is jointly developed by North China Electric Power Research Institute, Shandong University and
More informationINSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.
Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Human photo. Can be environmental/ documentaty style or portrait of engineer. industry photo.
More informationTechnical Specification for LV ABC Fuse Switch Disconnectors
Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and
More information15~35KV Termination Kit
15~35KV Termination Kit Luyon Corporation 21221 Western Ave., #210 Torrance, CA 90501, U.S.A. Advantages of Silicone Rubber Power Cable Accessories Feature of silicone rubber: Silicone rubber is a unique
More informationEffect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators
Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators By Abdelbaset Shaban Nekeb Thesis submitted to Cardiff University in candidature for the degree of DOCTOR
More informationPolymer Station Post Insulators for 69 to 345 kv Applications
CATALOG 143 Polymer for 69 to 34 kv Applications NGK-Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Polymer... 1 Application Guidelines for Polymer Station Posts (SP)...
More informationLow Fouling and Energy Consumption two-stage Forward and Reverse Osmosis desalination Process
Low Fouling and Energy Consumption two-stage Forward and Reverse Osmosis desalination Process Malak Hamdan Energy and Water Security Workshop, 15-17 February 2015, (Doha) Qatar 1 Overview of Presentation
More informationChallenges caused by cold climate when designing, constructing and operating overhead lines Sonja Berlijn and Bergit Svenning Statnett
Challenges caused by cold climate when designing, constructing and operating overhead lines Sonja Berlijn and Bergit Svenning Statnett Next Generation Grid The need for the next generation grid is increasing:
More informationReprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.
Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.
More informationSpecification for Polymer Disc Insulator
Specification for Polymer Disc Insulator Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, storage of 11 KV & 33 KV Polymer Disc
More informationTransmission Silicone Insulators Line Post 69 kv to 230 kv
K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines
More informationSolving Corrosion Under Insulation Utilizing FOAMGLAS Cellular Glass Insulation Systems
Solving Corrosion Under Insulation Utilizing FOAMGLAS Cellular Glass Insulation Systems NACE International Jubail, Kingdom of Saudi Arabia November 30, 2010 Steven T. Oslica Director of Marketing FOAMGLAS
More informationSPECIFICATION FOR POLYMER DISC INSULATOR
SPECIFICATION FOR POLYMER DISC INSULATOR Scope : This specification cover the design, manufacturing, testing at manufacturers works, transport to site, insurance, unloading & storage of 11 KV & 33 KV Polymer
More informationTechnical Specification for Insulated Low Voltage Single Core Copper Cable
Ergon Energy Corporation Limited Technical Specification for Insulated Low Voltage Single Core Copper Cable ETS03-01-03 Specification ETS03-01-03 Ver 3 Contents 1. Purpose and Scope... 1 2. References...
More informationECONOMIC ANALYSIS OF 400 KV TRANSMISSION TOWERS WITH CROSS ARMS INSULATORS
ECONOMIC ANALYSIS OF 400 KV TRANSMISSION TOWERS WITH CROSS ARMS INSULATORS Kumissay Saudeger Yildiz Technical University TURKEY Altug Bozkurt Yildiz Technical University TURKEY ABSTRACT For economic and
More informationPolymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case
Polymer Insulators and Coatings in the Cretan Power System. The Transmission Line Case D. Pylarinos Hellenic Electricity Distribution Network Operator dpylarinos@yahoo.com K. Siderakis Technological Educational
More informationInvestigation of leakage current flow through wooden poles structures on overhead distribution system
Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution
More informationWhat Forges High Reliability
What Forges High Reliability ----Endurance Tests of Huawei Inverters PV system is normally installed outdoor,exposed to hash environment, like extreme high or low temperature, high humidity, strong wind,
More informationSurface Roughness Effect on the Hydrophobicity Characteristic of Operating Composite Insulators
3rd International Conference on Electric and Electronics (EEIC 2013) Surface Roughness Effect on the Hydrophobicity Characteristic of Operating Composite Insulators Song Wang State Grid Beijing Electric
More informationCERTS Microgrids. Tom Jahns Professor, University of Wisconsin-Madison. LPPC Rates Roundtable May 21, 2013
CERTS Microgrids Tom Jahns Professor, University of Wisconsin-Madison LPPC Rates Roundtable May 21, 2013 Wisconsin Energy Institute WEI WEI provides linkage among all organizations associated with energy
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 220, 132 & 66 COMPOSITE SOLIDCORE STATION POST INSULATORS GETCO/E/2,1,6
More information