WHITE BOX BUILD-OUT SUITE 33-B
|
|
- Chloe Logan
- 5 years ago
- Views:
Transcription
1 GENERAL NOTES PROJECT INFORMATION WHITE BOX BUILD-OUT DRAWING LOG 1. Construction shall conform to the requirements of all governing federal, state, and local codes. In addition to complying with current enforced ANSI guidelines, this project must also comply with the Americans with Disabilities Act (ADA). 2. All materials, hardware and fixtures will be U.L. listed. 3. The drawings illustrate general workscope requirements and do not elaborate on installation techniques. All work performed shall meet or exceed industry standards, be performed in accordance with manufacturer's recommendations, and shall conform to all provisions of state, county and city codes, building laws, ordinance rules and regulations. 4. Contractor shall obtain and pay for building permits. 5. Coordinate exact locations of conduit, ductwork, mechanical and electrical devices, and light fixtures with the Architect in the field. 6. All dimensions shown on the drawings shall be considered critical. It shall be the responsibility of the contractor to notify the Architect of any deviation in the placement of work prior to installation. 7. Drawings are furnished to show design intent for construction only and do not show every condition or aspect of construction. Contractor to inform the architect of any discrepancies prior to proceeding with any work. Do not scale drawings. Dimensions govern. 8. Contractor to remove existing soils to allow for new construction. See Civil Drawings. 9. Debris resulting from the construction shall be removed entirely from the construction site on a daily basis to a waste area provided by the contractor. 10. All work shall be done in a workmanlike manner and in accordance with accepted construction standards. All walls, ceilings, and other assemblies to be plumb, true, and square, unless otherwise noted. 11. Mechanical, electrical and plumbing scope, fixtures and locations will generally be noted on the drawings. The contractor is responsible for providing permit drawings and obtaining all MEP permits. 12. Double studs construction to be used at all cased and door openings. 13. Outlets and utilities indicated on plan are minimum requirements. Additional telephones or outlets may be required by code. General Contractor to verify all locations in field. 14. All floor and wall penetrations in rated assemblies shall be sealed with approved, current firestop assemblies appropriate for the rated wall assembly. 15. Contractor is responsible for soil testing. Contractor is responsible for any required testing of material and assemblies installed by contractor. 16. All assemblies, material to meet current Georgia Energy Code requirements. 17. Interior finishes, materials, and furnishings shall comply with and meet the smoke and fire rating requirements of all state and local codes. In particular, all interior finishes shall meet requirements set forth in the international building code. 18. Final clean-up of building and site shall be the responsibility of the general contractor. Building and site shall be turned over in a clean and new condition. 19. N/A 20. Provide portable fire extinguishers in accordance with NFPA All lumber in contact with concrete slabs, exterior masonry walls, or in conjunction with concrete slabs, exterior masonry walls, or in conjunction with gravel stops or roofing shall be preservative treated in accord with AWPA C1-77 and AWPI LP-22, CCA, Type A, non-leaching type preservative. 22. The design of this project to the best of our professional knowledge, information and belief complies with applicable provisions of the Americans with Disabilities Act (ADA), ANSI standard A , and the Georgia accessibility code requirements as they apply to this project. Because the requirements of the ADA are subject to various and possibly contradictory interpretations, we cannot and do not guarantee that this project will comply with interpretations of ADA requirements as they apply to this project. 23. The contractor shall provide a warranty for correction of the work of this project for the period of one year after substantial completion or as otherwise stipulated in the contract documents. 24. The architect is not responsible for changes made or authorized by the owner, owner's representatives, tenants, contractor or others without written consent by the architect or consultant. 25. The contractor shall be responsible for coordination of structural, mechanical, electrical, and plumbing work with the architectural drawings. All discrepancies in the documents shall be reported to the architect for resolution of any conflicts with any design elements before the work is done. 26. The contractor shall field verify construction tolerances and take field measurements of any existing conditions related to the work of this project. Conditions encountered at the site materially different from those indicated in the contract document shall be promptly reported to the architect or owner's representative before the conditions are disturbed. 27. The contractor shall be responsible for all cutting, patching and fitting necessary to achieve the scope of the work. 28 Existing utilities or other mechanical, electrical, or plumbing equipment requiring removal, capping, termination, and/or relocation shall be included in the overall scope and performance of the project by the contractor. 29. All substrate surfaces are to be prepared to receive finish materials per manufacturer's product literature and written instructions for installation, or application. Fill voids in round columns prior to applying finish materials. 30. The contractor shall verify that no conflicts exist in locations of any and all mechanical, telephone/data, electrical, lighting and plumbing equipment (to include all piping, ductwork, and conduit) and that all required clearance for installation or maintenance or above equipment is provided. 31. The contractor shall provide and install equipment and appliances specified unless otherwise noted. The contractor shall verify all plumbing and electrical requirements related to equipment and appliances in the scope of work. SHELL BUILDING PERMIT INFORMATION FOR REFERENCE: PROJECT NAME: GEORGIA AVENUE REDEVELOPMENT - LOT 19 LOCATION: 33 GEORGIA AVE PERMIT NUMBER: BB PROJECT DESCRIPTION: IS A WARM, WHITE-BOX BUILD-OUT FOR FUTURE OFFICE TENANT IN AN EXISTING BUILDING. -MECHANICAL = RTU PLACEMENT AND MAIN DUCT ROUTING -ELECTRICAL = STUMBLE LIGHTING -PLUMBING = FULL BATHROOM BUILD-OUT -FIRE SUPPRESSION = RISER AND ROUTING CODE INFORMATION OCCUPANCY: IBC: MIXED USE, NON-SEPARATED OCCUPANCY (508.3) ASSEMBLY (A-2), RESTAURANT + BUSINESS (B) + MERCANTILE (M) CLASS C PER (3), RETAIL NFPA: MIXED OCCUPANCY, NON-SEPARATED FIRST FLOOR: NEW ASSEMBLY (CH 12) SECOND FLOOR: NEW BUSINESS (CH 38) CONSTRUCTION TYPE: IBC: TYPE VB, SPRINKLERED NFPA:TYPE V(000) OCCUPANCY SEPARATION: 1 HOUR TENANT SEPARATION PER CITY OF ATLANTA MUNICODE NOT REQUIRED PER IBC OR NFPA 1 HOUR WALLS & CEILINGS WERE INSTALLED DURING BASE-BUILDING SHELL CONSTRUCTION. BUILD-OUT AREA: FIRST FLOOR + STAIRS = 445 SF SECOND FLOOR = 3,300 SF OCCUPANT LOAD: BUSINESS = 3,300 SF / 100 = 33 OCCUPANTS MAX NUMBER OF EXITS: EXIT REQUIRED = 2 EXIT PROVIDED = 2 COMMON PATH OF TRAVEL: 100' MAX, = 0' MAXIMUM TRAVEL DISTANCE TO EXIT: 300' MAX, = 110' MAXIMUM DEAD END CORRIDOR LENGTH: 50' MAX, = n/a EGRESS WIDTH PER PERSON HORIZONTAL.2"/PERSON = 6.6" STAIRS.3"/PERSON = 9.9" MIN. CORRIDOR WIDTH (7.3.4) 3'0" (2'-8" FOR EXISTING) MIN. CLEAR OPENING ( ) 2'8" MIN. STAIR WIDTH ( ) 3'8" (36" IF OCCUPANT LOAD OF ALL STORIES SERVED BY STAIR IS <50) PLUMBING: 33 OCCUPANTS / 2 = 17 (1 TOILET PER 25 OCC) = 2 WC'S REQUIRED, 2 PROVIDED CITY OF ATLANTA CONSTRUCTION CODES 1. INTERNATIONAL BUILDING CODE: 2012 EDITION, WITH GEORGIA AMENDMENTS (2014) (2015) (2017) (2018) 2. INTERNATIONAL FIRE CODE: 2012 EDITION, WITH GEORGIA AMENDMENTS (2014) 3. INTERNATIONAL PLUMBING CODE: 2012 EDITION, WITH GEORGIA AMENDMENTS (2014) (2015) 4. INTERNATIONAL MECHANICAL CODE: 2012 EDITION, WITH GEORGIA AMENDMENTS (2015) 5. INTERNATIONAL FUEL GAS CODE: 2012 EDITION, WITH GEORGIA AMENDMENTS (2014) (2015) 6. NATIONAL ELECTRICAL CODE: 2017 EDITION, WITH NO GEORGIA AMENDMENTS 7. INTERNATIONAL ENERGY CODE: 2009 EDITION, WITH GEORGIA SUPPLEMENTS & AMENDMENTS (2011) (2012) NFPA 101: LIFE SAFETY CODE, WITH STATE AMENDMENTS (2013) 9. ACCESSIBILITY CODE: 2010 ADA STANDARDS FOR ACCESSIBLE DESIGN - GA A PROJECT ADDRESS: 33 GEORGIA AVE SE, SHT# DESCRIPTION ARCHITECTURAL 33-B A-0.0 TITLE SHEET X 33-B A-0.1 SITE PLAN X 33-B A-2.0 BUILDING PLANS X 33-B A-2.1 FLOOR PLANS X 33-B A-2.2 ENLARGED FLOOR PLANS X ELECTRICAL 33-B E-0.1 ELECTRICAL LEGENDS & SPECIFICATIONS X 33-B E-1.1 ELECTRICAL FLOOR PLANS X 33-B E-1.2 ELECTRICAL ROOF PLAN X MECHANICAL 33-B M-0.1 MECHANICAL NOTES & DETAILS X 33-B M-1.1 MECHANICAL FLOOR PLAN X 33-B M-2.1 MECHANICAL SPECS X 33-B M-2.2 MECHANICAL SPECS X PLUMBING 33-B P-0.1 PLUMBING SCHEDULES X 33-B P-0.2 PLUMBING DETAILS X 33-B P-2.1 PLUMBING PLANS FIRST FLOOR X 33-B P-2.2 PLUMBING PLANS SECOND FLOOR X 33-B P-4.1 PLUMBING SPECIFICATIONS X STRUCTURAL 33-B S-1 ENGINEER'S LETTER X 33-B S-2 LOCATION OF NEW RTU X 33-B S-3 TRUSS MODIFICATION DETAIL X STRUCTURAL ENGINEER: STABILITY ENGINEERING 1376 CHURCH ST DECATUR, GA CONTACT: JAMES BREEDEN PHONE: ext jbreeden@stabilityengineering.com MEP ENGINEER: SUBSCRIPTION ENGINEERING ATLANTA, GA CONTACT: YANCEY JUSTICE PHONE: yjustice@subscriptionengineering.com CONTRACTOR: TBD PERMIT SET PROJECT DIRECTORY OWNER: CARTER USA 1440 DUTCH VALLEY SUITE 1200 ATLANTA, GA CONTACT: TOMMY WEBB PHONE: twebb@carterusa.com ARCHITECT:, LLC 368 MORELAND AVE NE, SUITE 240 ATLANTA, GA CONTACT: LAURA DANIEL PHONE: laura@revivearchitecture.com WHITE BOX BUILD-OUT PERMIT SET TITLE SHEET 33-B A-0.0
2 WHITE BOX BUILD-OUT SECOND FLOOR = 3,300 SF SUITE 39-B SECOND FLOOR = 1,400 SF PERMIT SET SITE PLAN 33-B A-0.1
3 33-A NOT IN SCOPE 33-B GEORGIA AVENUE WHITE BOX BUILD-OUT 1 BUILDING 33 - FIRST FLOOR PLAN 1/8" = 1'-0" 33-B A BUILDING 33 - SECOND FLOOR PLAN 1/8" = 1'-0" 33-B A PERMIT SET BUILDING PLANS 33-B A-2.0
4 LIGHT FIXTURE SCHEDULE - 33-B Type Mark Type Comments Count 4' LINEAR LED 1 8' LINEAR LED 8 BATHROOM RECESSED CAN / EXHAUST FAN COMBO 2 BATHROOM WALL SCONCE 2 EMERGENCY LIGHT WITH BATTERY BACK-UP 4 EXIT SIGN WITH BATTERY BACK-UP 2 EXIT SIGN - DIRECTIONAL WITH BATTERY BACK-UP 2 DOOR SCHEDULE 33-B MARK WIDTH HEIGHT DOOR TYPE FRAME TYPE HEAD TYPE JAMB TYPE SILL TYPE COUNT A 3' - 0" 7' - 0" D1 F1 H1 J1 S1 3 PARTITION TYPE LEGEND - 33-B EXISTING WALL P-1 3 5/8" METAL STUD WITH 5/8" GYP BD BOTH SIDES. WALL HEIGHT TO BOTTOM OF JOIST 6" METAL STUD WITH 5/8" GYP BD BOTH SIDES. WALL HEIGHT TO BOTTOM OF JOIST 10' - 0" 13' - 4" 14' - 0" 14' - 0" 14' - 0" 10' - 0" EQ BOTTOM OF LIGHT FIXTURE = 9'-6" BOTTOM OF JOIST = 10'-0" 2 SECOND FLOOR - REFLECTED CEILING PLAN 3/16" = 1'-0" 33-B A-2.1 EXISTING ROOF ACCESS HATCH EQ GWB Ceiling with Framing 9' - 0" A.F.F. BATHROOM WALL SCONCE CENTER CAN IN ROOM BATHROOM WALL SCONCE GWB Ceiling with Framing 9' - 0" A.F.F. NO CEILING IN UTILITY CLOSET 8' - 0" EQ EQ 8' - 0" WOOD STUD 42" HIGH TO SERVE AS GUARDRAIL 1 SECOND FLOOR PLAN 3/16" = 1'-0" 33-B A-2.1 WOOD STAIR WOOD 36" HIGH, TYP MAX TRAVEL DISTANCE = 110'-0" RELOCATE ELECTRIC PANEL TO CLOSET N FUTURE CHASE DN WOOD STUD 42" HIGH TO SERVE AS GUARDRAIL WOOD STAIR WOOD 36" HIGH, TYP A FE 33-B DN A A UTILITY CLOSET 1 33-B A-2.2 P-2 3 FIRST FLOOR PLAN 1/8" = 1'-0" 33-B A ALL GYPSUM BOARD AT BATHROOM AREA AND KITCHEN SINK AREA TO BE WATER RESISTANT. PROVIDE MOISTURE & MOLD RESISTANT GYPSUM AT ALL TILED WALLS NOT IN A SHOWER. PROVIDE CEMENT BOARD AT SHOWER LOCATIONS. 2. PROVIDE BLOCKING AT ALL BATHROOM ACCESSORIES, WALL CABINETS, AND SHELVING. 3. PROVIDE SOUND BATT INSULATION IN ALL STUD WALLS AND ABOVE BATHROOM CEILINGS. 4. PROVIDE R-13 BATT INSULATION IN ALL EXTERIOR STUD WALLS. DO NOT PROVIDE GYP BOARD. 5. DO NOT PROVIDE WALL BASE ON EXTERIOR SIDE OF WALL. UP WHITE BOX BUILD-OUT FLOOR PLANS PERMIT SET 33-B A-2.1
5 PUBLIC TOILETS ACCESSORIES SCHEDULE TO BOTTOM OF EXPOSED GLASS SURFACE FINISH FLOOR LINE 40" MAX 2'-10" MAX PROTECT ALL HOT WATER & DRAIN PIPES AGAINST CONTACT 4' - 0" MAX MT HT IN ADA STALL PARTITION TYPE LEGEND - 33-B P-1 P-2 EXISTING WALL 3 5/8" METAL STUD WITH 5/8" GYP BD BOTH SIDES. WALL HEIGHT TO BOTTOM OF JOIST 6" METAL STUD WITH 5/8" GYP BD BOTH SIDES. WALL HEIGHT TO BOTTOM OF JOIST DOOR SCHEDULE 33-B MARK WIDTH HEIGHT DOOR TYPE FRAME TYPE HEAD TYPE JAMB TYPE SILL TYPE COUNT A 3' - 0" 7' - 0" D1 F1 H1 J1 S1 3 M MIRROR HK L WALL MOUNTED LAVATORY 54" MIN WALL/DOOR MOUNTED HOOK 36" MIN 1. ALL GYPSUM BOARD AT BATHROOM AREA AND KITCHEN SINK AREA TO BE WATER RESISTANT. PROVIDE MOISTURE & MOLD RESISTANT GYPSUM AT ALL TILED WALLS NOT IN A SHOWER. PROVIDE CEMENT BOARD AT SHOWER LOCATIONS. 2. PROVIDE BLOCKING AT ALL BATHROOM ACCESSORIES, WALL CABINETS, AND SHELVING. 3. PROVIDE SOUND BATT INSULATION IN ALL STUD WALLS AND ABOVE BATHROOM CEILINGS. P-1 SN TP 3 5/8" FINISH FLOOR LINE 17" 17"- 19" TOP OF RAIL 33" - 36" 12" MAX 42" MIN 12" MIN24" MIN WC G1 G2 TP 48" MAX 12" MIN 7"-9" 15" MIN 48" MAX SN 4. PROVIDE R-13 BATT INSULATION IN ALL EXTERIOR STUD WALLS. DO NOT PROVIDE GYP BOARD. 5. DO NOT PROVIDE WALL BASE ON EXTERIOR SIDE OF WALL. P-2 G2 WC G1 7' - 3 3/4" FLOOR MOUNTED TOILET - REF PLUMB. 42" GRAB BAR 36" GRAB BAR SURFACE MTD TOILET PAPER DISPENSER SANITARY NAPKIN DISPOSAL INTERIOR DOORS 1X4 FLAT STOCK TRIM M JL INDUSTRIES MODEL # 1027 S21 ALUMINUM SATIN FINISH OBJECT PROTRUSION LIMITS L 4' - 0" 2' - 6" 4' - 7 1/2" 4" MAX 27" MIN 80" MAX 2 WOOD DOOR F1 P-1 A HK 3 5/8" REQ'D HC LAVATORY, URINAL & DRINKING FOUNTAIN CLEARANCE (PLAN VIEW) FE SEMI RECESSED F.E. CABINET METAL STUD FRAMING SEALANT; TYP 6' - 7 1/4" DOOR H1 DOOR TILE GWB EXTERIOR METAL STUD FRAMING SEALANT; TYP 1x4 FLAT STOCK TRIM S3 INTERIOR 1/2" MAX DOOR J1 GWB 1X4 FLAT STOCK TRIM STRIKE PLATE SHALL EXTEND TO PROTECT CASING ADA COMPLIANT THRESHOLD AT FLOOR MATERIAL TRANSITION LOCATIONS ONLY EXISTING PLYWOOD SUBFLOOR P-2 P-1 P-1 HK A M L G2 WC G1 SN TP P-1 A UTILITY CLOSET 1 ENLARGED BATHROOMS 1/2" = 1'-0" 33-B A-2.2 5' - 0 5/8" 3 5/8" 7' - 3 3/4" 3 5/8" 27' - 5 7/8" WHITE BOX BUILD-OUT ENLARGED FLOOR PLANS PERMIT SET 33-B A-2.2
6 GENERAL NOTES: ELEC LEGENDS & SPECIFICATIONS 33-B E-0.1 Engineering, LLC
7 UP Engineering, LLC 2 ELECTRICAL FLOOR PLAN LVL 2 33-B E-1.1 NORTH 1 ELECTRICAL FLOOR PLAN LVL 1 33-B E-1.1 NORTH ELECTRICAL FLOOR PLANS 33-B E-1.1
8 FE Engineering, LLC LIGHTING NOTES: 1 ELECTRICAL ROOF PLAN 33-B E-1.2 NORTH ELECTRICAL ROOF PLAN 33-B E-1.2
9 Engineering, LLC 3 RTU ROOF CURB DETAIL 33-B M ROOFTOP UNIT 33-B M CONDENSATE DRAIN (CD) 33-B M-0.1 MECH NOTES & DETAILS 33-B M-0.1
10 Engineering, LLC 2 MECHANICAL ROOF PLAN 33-B M MECHANICAL FLOOR PLAN 33-B M-1.1 NORTH MECHANICAL FLOOR PLAN 33-B M-1.1
11 Engineering, LLC MECHANICAL SPECS 33-B M-2.1
12 ¾ MECHANICAL SPECS 33-B M-2.2 Engineering, LLC
13 PLUMBING GENERAL NOTES PLUMBING FIXTURE SCHEDULE 1/2" 1/2" 2" 1-1/2" WATER HAMMER ARRESTER SCHEDULE DRAIN & SPECIALTY SCHEDULE ABBREVIATIONS PLUMBING LEGEND Engineering, LLC WATER HEATER SCHEDULE PLUMBING RENOVATION NOTES PLUMBING SCHEDULES 33-B P-0.1
14 Engineering, LLC 2 Domestic Water Riser Diagram 33-B P Sanitary Waste & Vent Riser Diagram 33-B P-0.2 PLUMBING DETAILS 33-B P-0.2
15 8'-0" EQ EQ UP Engineering, LLC 1 LOWER LEVEL PLUMBING PLAN - WASTE & VENT 33-B P-2.1 NORTH UPPER LEVEL PLUMBING PLAN - WASTE & VENT 33-B P-2.1 NORTH PLUMBING PLANS FIRST FLOOR 2 33-B P-2.1
16 Engineering, LLC PLUMBING SPECIFICATIONS 33-B P-4.1
17 8'-0" EQ EQ M M UP Engineering, LLC 1 LOWER LEVEL PLUMBING PLAN - SUPPLY 33-B P-2.2 NORTH UPPER LEVEL PLUMBING PLAN - SUPPLY 33-B P-2.2 NORTH PLUMBING PLANS SECOND FLOOR 2 33-B P-2.2
18 March 15, 2019 Carter USA 1440 Dutch Valley Place NE Suite 1200 Atlanta, GA RE: Engineer s Letter for 33 Georgia Avenue SE, Atlanta, GA RTU Support Se#17043 To whom it may concern, At the request of Carter USA, I provided a structural assessment of the roof structure at the aforementioned address to ensure adequacy to support two (2) new roof top units (RTU). The roof structure consists of manufactured wood trusses constructed of 2x6 top and bottom chords and 2x4 web members. The wood trusses span 47-6 between load bearing walls. I have analyzed the roof structure with a live load of 20 psf and a dead load of 15 psf. The analysis includes the additional specified maximum RTU weight of 750 lbs. To support the additional weight of the unit, the RTU platform must span between a minimum of eight (8) adjacent roof trusses. These roof trusses will also require modification as specified in the figures below. Based on my analysis, the additional weight of the new RTUs at the shown locations do not overstress the existing roof trusses given proper installation of the truss modifications shown in Figures 2 and will meet all requirements of the 2012 IBC. If you have any questions, or if I can be of any assistance, please call myself or the Stability Engineering office. Sincerely, Stability Engineering, Inc. James Breeden WARRANTY AND LIABILITY This report is based upon a visual observation of conditions as they existed at the time of the site visit only. Stability Engineering s investigation did not include a review of hidden or concealed conditions. Although an earnest effort has been made to discover and identify all visible defects, in the event of an oversight, Stability Engineering s maximum liability shall be limited to the fee paid for its services. Stability Engineering reserves the right to supplement or revise its opinions based upon changed conditions, further site visits by Stability Engineering or others, or new findings. Stability Engineering warrants that its services are performed, within the limits prescribed by the Client, with that level of care and skill ordinarily exercised by members of the same profession currently practicing in the same locality under similar conditions. No other warranties or representations are expressed or implied. This report and its conclusions are intended for the exclusive use of the Client and Stability Engineering shall have no liability arising out of their unauthorized use by others.
19 33 Georgia Avenue Se#17043 Atlanta, GA /15/2019 Figure 1: Location of new roof top units 2
20 33 Georgia Avenue Se#17043 Atlanta, GA /15/2019 Figure 2: Truss modification details 3
Tenant Fit-Out for PLCB / Waynesboro Mall
Tenant Fit-Out for PLCB / CODE REVIEW: PROJECT DESCRIPTION TENANT BUILD OUT PROPOSED USE SALE OF BEVERAGE ALCOHOL / PLCB SPRINKLERED: YES ALLOWABLE BUILDING HEIGHT & AREA: GROUP M / TYPE VB ALLOWED 1 STORY
More informationSPARTANBURG COUNTY BUILDING CODES DEPARTMENT
SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,
More informationPHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No C
PHASE I ACADEMIC BUILDING CORE RENOVATIONS RCNJ Project No. 20140101C CONSTRUCTION ESTIMATE AND PROJECT BUDGET Dated June 7. 2014 Estimated Cost HARD COSTS $ 1,560,284 Core Renovations (Toilet Rooms, Ceilings
More informationBay Bridge Cove. Clubhouse and Ammenities QUEEN ANNE'S COUNTY, MARYLAND
Structural Engineer: APEX Technology 8 N East Street Frederick, MD 21701 Mechanical Engineer: Emerald Engineering 205 North Armenia Ave. - Suite 102 Tampa, Florida 33609 Clubhouse and Ammenities QUEEN
More informationWork Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free
/ / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary
More informationBUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL Phone: (321) Fax: (321)
BUILDING DIVISION 120 Malabar Road, S.E., Palm Bay, FL 32907 Phone: (321) 953-8924 Fax: (321) 953-8925 CUSTOMER SERVICE INFORMATION ON COMMERCIAL PLAN REVIEW REQUIRED DOCUMENTS MUST BE SUBMITTED AT TIME
More informationCOMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION
COMMERCIAL TENANT IMPROVEMENT PERMIT APPLICATION OFFICIAL USE ONLY Date: Permit #: Received by: For Staff Use Only: OFD ELEC Planning SITE LOCATION Site Address: Tax Parcel Number: TYPE OF WORK Building
More informationSUBMISSION GUIDE FOR ARCHITECTS
SUBMISSION GUIDE FOR ARCHITECTS CONTENTS TAB 6 - SUBMISSION REQUIREMENTS FOR LIHTC DEVELOPMENTS NOT RECEIVING OR ASSUMING A PHFA LOAN Page Contents... 6.1 6.01 Submission Requirements... 6.2 6.02 Minimum
More informationCity of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:
City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building
More informationCity of South Pasadena COMMUNITY IMPROVEMENT
City of South Pasadena COMMUNITY IMPROVEMENT Office Address: Mailing Address: 6940 Hibiscus Ave S 7047 Sunset Dr S South Pasadena, FL 33707 South Pasadena, FL 33707 *PHONE: (727) 343-4192 * FAX: (727)
More informationSIDEWALK & RAILING REPLACEMENT BOARD OF ED BUILDING
PROJECT: 25 E 5 S SALT LAKE CITY, UTAH 84111 CODE ANALYSIS APPLICABLE CODES 675 E. 5 S. Suite 4 DFCM PROJECT NUMBER: 182782 DFCM CONTRACT NUMBER: 18793 STRUCTURAL ENGINEER: REAVELEY ENGINEERS + ASSOCIATES
More informationADA RESTROOM 79 LF EXISTING ANDERSON MAINTENANCE BUILDING (E) SNOW STORAGE AREA: 160 SF EXISTING STORAGE BUILDING (E) ELECTRICAL PAD
T ectoniccop yright07 T ectoniccop yright07 0BOBADAMSDRIVESTEAMBOATSPRINGS,COLORADO8047GENERAL NOTES SHEET INDEX. ALL RIGHTS RESERVED. THE ARRANGEMENTS, DECISIONS, DETAILS AND CONCEPTS DEPICTED HEREIN
More informationSPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)
SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in
More informationCommon Plan Review Rejection Reasons
Common Plan Review Rejection Reasons Submitted plans must contain sufficient information for plan reviewers to be able to verify that the proposed construction complies with the Virginia Uniform Statewide
More informationCommon Plan Review Rejection Reasons
(CPHD) (ISD) Common Plan Review Rejection Reasons Submitted plans must contain sufficient information for plan reviewers to be able to verify that the proposed construction complies with the Virginia Uniform
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationNOTE: For construction other than new commercial or additions (renovations), only those areas below describing the scope of work will be applicable.
Applicant s Name: New Commercial - Commercial Additions Renovations Permit Plan Submittal Check List Applicant s Phone Number (s): Project Address: Project Type: _New Commercial or Commercial Addition
More informationApplying the Building Code During Design
Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education
More informationINFORMATIONAL HANDOUT FOR FINISHING A BASEMENT
7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed
More informationCODE COMPLIANCE PLAN REVIEW PROCEDURES
CODE COMPLIANCE PLAN REVIEW PROCEDURES 1. All construction for state agencies on state-owned or state leased-purchased properties or facilities are to submit design documents for code compliance plan reviews
More informationWATER 107 TOILET 106 EXISTING TYP. EXISTING CLG. TYP. (E) RETURN REGISTER SUPPLIES 105 NEW RETURN REGISTER
GFI (E) ROOM NOW WORK REQUIRED 60x66 30x60 ISTING TYP. ISTING CLG. TYP. AURORA, LLC 1155 S. Havana St. Space 53 Aurora, CO 80012 Code Information: 2009 International Building Code Address: 1155 S. Havana
More informationWaikoloa Homesites. Kohala Coast, HI. Outline Specifications. Prepared By: 16 December 15
Waikoloa Homesites Kohala Coast, HI Prepared By: Fritz Harris-Glade, NCARB, AIA FHG Architects AIA, LLC HG Construction Management, Inc. P. O. Box 4476 Kailua Kona, HI 96745 16 December 15 TMK : (3) 0-0-000:000
More informationPLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS
PLANS REVIEW CRITERIA - COMMERCIAL BUILDINGS NOTE: Building Code compliance is the obligation of design professionals and/or contractors. Plan review and inspection guidelines are to be used to ensure
More informationALVARADO STREET SAN FRANCISCO, CA VARIANCE APPLICATION
621-23 ALVARADO STREET SAN FRANCISCO, CA 94114 VARIANCE APPLICATION PROJECT LOC. ABBREVIATIONS LEGEND EXISTING FRONT ELEVATION VICINITY MAP (NO SCALE) OWNER: 621 ALVARADO ST, LLC PHONE: 707-373-0832 400
More informationResidential Basement Finish Guide
Residential Basement Finish Guide Basement finish permits are typically issued same day, however standard review times may apply if: There is structural work (foundation, beams, etc.), or if the entire
More informationSITE / BUILDING PLAN 10/18/16 10/18/16 A+M ARCHITECTS, LLC REINF. ANGLE REQUIRED AT ALL ROOFTOP UNITS WHERE "X" EXCEEDS 8"
10'-7" 4 7/8" 30'- 20'-7 3/8" WH WH A+M ARCHITECTS, LLC TO THE BEST OF MY KNOWLEDGE AND BELIEF, ALL OCCUPANTS WITHIN THE BUILDING ARE IN COMPLIANCE WITH APPLICABLE ILLINOIS STATE PLUMBING CODES PERTAINING
More informationINFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS
INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit
More informationBonadio Residence. Renovations to Existing Dwelling: new kitchen. 23 Albert Street Waltham, MA. Addition to existing structure.
December 1, 6 Renovations to Existing Dwelling: new kitchen 3 Albert Street Waltham MA Addition to existing structure. Renovations for 3 Albert Street Waltham, MA Cover sheet First Floor Demolition D1
More informationCONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist
CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist
More informationRESIDENTIAL REMODELING AND BASEMENT FINISH
RESIDENTIAL REMODELING AND BASEMENT FINISH CITY OF HUTCHINSON BUILDING DEPARTMENT 111 Hassan Street SE, Hutchinson, MN 55350 Phone: (320) 234-4216 Web Site www.ci.hutchinson.mn.us/building.htm This handout
More informationC. Type of Selective Demolition Work: Demolition requires the selective removal and subsequent off-site disposal of:
02070 - SELECTIVE DEMOLITION PART 1 - GENERAL 1.1 STIPULATIONS A. The specifications sections " General Conditions of the Construction Contract ", "Special Conditions", and "Division 1 - General Requirements"
More information--*6 S CONSTRUCTION GROUP, INC SW 87 Avenue Miami, FL Phone:
--*6 S,.- CONSTRUCTION GROUP, INC. FLORIDA STATE CERTIFIED GENERAL CONTRACTOR CGC 1 508637 9505 SW 87 Avenue Miami, FL 33176 Phone: 305-219-6046 Email: jrossel@rosselconstruction.com PRELINIARY ESTIMATE
More informationSTANDARD PLAN RELEASE SUMMARY(SPR) Facilities Management Department
STANDARD PLAN RELEASE SUMMARY(SPR) Facilities Management Department Building Design: Nauvoo 00 Release Date: February 2001 Release Number: 1 Summarized below is a list of modifications made to the Standard
More informationUCC Permit Application Procedures
How do I apply for a permit? UCC Permit Application Procedures 1. Please complete the CodeMaster Pan Review Application 2. Please provide the scope of work description and/or construction documents/plans.
More informationPETRO S - Bedford, TX
REVISED Schematic Design Package APRIL 26 These drawings are for communication of design intent only and are not suited or intended for permitting or construction. PG of 8 CLIENT APPROVAL SIGNATURE: DATE:
More informationBASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)
BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from
More informationMinneapolis Community and Technical College T-Building Floor 2 Student Affairs Cost Estimating Form Templates - Exhibit C
2 3 4 5 6 7 8 9 0 2 3 4 5 6 7 8 9 20 2 22 23 24 25 26 27 28 29 30 3 32 33 34 35 36 37 38 39 40 4 42 43 44 45 46 DIVISION 02 EXISTING CONDITIONS Demolition; Removal & Disposal: CMU Partitions AD Quan UM
More informationUniversal Design Standards
Universal Design Standards For applications submitted and approved after April 16, 2007 Introduction to Universal Design Universal design is a building concept that incorporates products, general design
More informationPROJECT DATA USE GROUP M M TYPE OF CONSTRUCTION IIB NUMBER OF STORIES 1 HIGH RISE BUILDING COVER MALL IS BUILDING FULLY SPRINKLERED
GENERAL TES ABBREVIATION PROJECT DATA CONTACTS 1. CONTRACTOR TO VERIFY ALL FIELD CONDITIONS TED PRIOR TO COMMENCEMENT OF CONSTRUCTION. FIELD CONDITIONS T AGREEING WITH CONSTRUCTION DOCUMENTS SHALL BE BROUGHT
More informationTypical Finished Basement Details
Albemarle County, Virginia Typical Finished Basement Details Based on the 2012 Virginia Residential Code Finished basements must be constructed in conformance with these details. For requirements, details
More informationDocument G808. Project Data CONSTRUCTION DOCUMENTS DATE IDENTIFICATION DESIGN DEVELOPMENT DATE IDENTIFICATION INITIAL INFORMATION DATE IDENTIFICATION
Document G808 TM 2001 Project Data PROJECT: (Name and address) PROJECT NUMBER: CONTRACTOR: (Name and Address) ARCHITECT: (Name and Address) OWNER S APPROVALS/AGREEMENTS INITIAL INFORMATION DATE IDENTIFICATION
More informationHOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS
St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the
More informationCITY OF CALABASAS RESIDENTIAL PLAN REQUIREMENTS 1 OF 5 8/2017 PLAN INFORMATION
1 PLAN INFORMATION Residential plans must be legible and capable of digital scanning. All sheets shall be the same size and distinctly labeled with a sheet title and number. The minimum dimension of the
More informationPROCUREMENT AND CONTRACTING DOCUMENTS GROUP
PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders
More informationMECHANICAL M-1 LEGEND AND DETAILS M-2 FLOOR PLAN - DUCTWORK M-3 FLOOR PLAN - PIPING
SHEET TITLE ARCHITECTURAL A-0 COVER SHEET A-1 DEMOLITION NOTES A-2 DEMOLITION PLAN A-3 FLOOR PLAN NOTES A-4 FLOOR PLAN A-5 INTERIOR ELEVATIONS A-6 DOOR SCHEDULE A-7 DETAILS MECHANICAL M-1 LEGEND AND DETAILS
More informationAIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7
AIRWAYS CROSSING PHASE II BUILDING INFORMATION 5305 McCall Way N.E. T2E 7N7 www.airwayscrossing.ca Excellent access to Barlow Trail/McKnight Blvd. Bays starting at 4,000 sq. ft. Surface loading T5 lighting
More informationContractor/Owner initials are verification that items #1 and #2 and items (a) thru (g) above are included in the submitted plan/drawing.
FINISH BASEMENT/ADDITION/REMODEL PLAN CORRECTIONS LIST (Based on the current Editions of the International Codes and National Electrical Code) PLAN CHECKED BY: LOT/SUBDIVISION/ADDRESS: CONTRACTOR OR OWNER/BUILDER:
More information8. Whether the proposed zoning will adversely affect the existing use or usability of adjacent or nearby property; District change is not proposed
HABERSHAM COUNTY Planning Department 6257 State Hwy 115, Ste. 1, Clarkesville, GA 30523 706-839-0140 Fax: 706-754-1761 www.habershamga.com Habersham County Planning Commission Conditional Use Staff Report
More informationDelta Gamma Sorority Renovation Budget Scope 3/7/2018
Delta Gamma Sorority Renovation Budget Scope 3/7/2018 PROJECT: Barbara Cerni Delta Gamma Sorority Tallahassee, Fla. This scope is based on the 50% Construction Documents drawn by BKJ Architecture dated
More informationRESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS
RESIDENTIAL BUILDING PERMIT GUIDE FOR MULTI-FAMILY DWELLINGS New Construction, Addition, or Alteration All plans submitted must be prepared, sealed, and signed by a Registered Nebraska Design Professional
More informationCITY OF ANDERSON BUILDING AND CODES 601 South Main Street
CITY OF ANDERSON BUILDING AND CODES 601 South Main Street Plan Review Notes (STREET ADDRESS) ANDERSON, SC Plan Review Number: Building Plans prepared by: Plans Signed by: Project Name: Plans Received:
More information6'-0" G-4 ADJUSTABLE SHELVING 2'-0" 4'-5" MOP SINK STORAGE '-0" 2'-0" 26'-6" G-4 6' X 4' OPENING WITH SHUTTER BASE CABINETS 34" FOR ADA 20'-0"
2 G1 3'4" 4'0" ROOM FINISH SCHEDULE 4'0" F.F. WINDOW DETAILS GROUT CORES SOLID GROUT CORES SOLID 3 G1 #5 BARS HOLLOW METAL FRAME INSULATED GLASS 1" CLEAR INSULATED (U=0.45) CAULKING & BACKER ROD PREFORMED
More information* RESIDENTIAL PLAN REVIEW *
CITY OF DES MOINES, IOWA COMMUNITY DEVELOPMENT DEPARTMENT PERMIT AND DEVELOPMENT CENTER 602 Robert D. Ray Drive DES MOINES, IOWA 50309 Phone: 515.283.4200 Facsimile: 515.283.4270 Based on the scope of
More informationCity of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage
City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number
More informationSANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA
Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes
More informationCity of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage
City of Treasure Island FEMA Cost Breakdown Worksheet For Substantial Improvement / Damage Property Address: Company Name: Contractor Name: Contractor Address: City: State: Zip: License Number: Phone Number
More informationPulaski County, Virginia
Pulaski County, Virginia Typical Carport Enclosure Details Based on the 2009 International Residential Code CONTENTS General Requirements... 2 Emergency Escape and Rescue... 2 Foundation and Floor... 3
More informationProposal Request (attachment to AIA Form G709)
Proposal Request (attachment to AIA Form G09) PR No: PR-0 Date: January, 06 Project: Great Work Montessori School Owner: Great Work Inc. Architect: Cuningham Group Copy To: File DESCRIPTION OF WORK The
More informationBIDDING SHEET CHECKLIST--SUBCONTRACTORS AND SUPPLIERS SUBCONTRACTOR/ PHONE DATES SUPPLIER NAME: CALLED BID. Sample
BIDDING SHEET CHECKLIST--SUBCONTRACTORS AND SUPPLIERS Project Name: Address: Owner: Phone/Fax/Email: Architect / General Contractor Name: : BID DEADLINE DATE: SUBCONTRACTOR/ PHONE DATES SUPPLIER NAME:
More informationEMBASSY SUITES PARK EAST DRIVE BEACHWOOD, OH INTERIOR AND EXTERIOR RENOVATION Owner NF II Beachwood, LLC
EMBASSY SUITES 3775 PARK EAST DRIVE BEACHWOOD, OH 44122 INTERIOR AND EXTERIOR RENOVATION Owner NF II Beachwood, LLC 1100 Monarch Tower 3424 Peachtree Rd. NE Atlanta, GA 30326 Tel: 404.262.9660 Developer
More informationCommercial Remodel Permit
Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each
More informationCODE ANALYSIS REPORT SECOND FLOOR
CODE ANALYSIS REPORT SECOND FLOOR 384 DWIGHT STREET HOLYOKE, MA Prepared by Dietz & Company Architects, Inc. 17 Hampden Street Springfield, MA March 2014 INTRODUCTION The following report is a preliminary
More informationCOMMERCIAL BUILDING PLAN REVIEW CHECKLIST
Department of Urban Planning & Codes Enforcement City of Coatesville - 1 City Hall Place - Coatesville, Pennsylvania 19320 Phone: 610.384.0300 Fax: 610.384.6051 COMMERCIAL BUILDING PLAN REVIEW CHECKLIST
More informationSmokey Ridge, Christiansburg, Virginia
Smokey Ridge, Christiansburg, Virginia Outline Specifications Prepared by Community Design Studio, LLC Project # 1305, March 15, 2013 The following describes the Sections to be included in each Division
More informationFOR LEASE th & LOUISE AVENUE RETAIL LOCATION SIZE PRICE DESCRIPTION $20.00 / SF NNN 3,154 SF RAQUEL BLOUNT, SIOR 605
3511 W 57th Street Sioux Falls, SD 57108 FOR LEASE $20.00 / SF NNN 3,154 SF SIZE DESCRIPTION PRICE $20.00 / SF NNN Estimated NNN: $5.25 / SF LOCATION Co-tenant with Great Western Bank, Healing Touch, Honeybaked
More informationSANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA
Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes
More informationPENNSAFE BUILDING INSPECTION SERVICES LLC NEW COMMERCIAL BUILDING UCC PLAN REVIEW HANDOUT AND CHECKLIST
PENNSAFE BUILDING INSPECTION SERVICES LLC NEW COMMERCIAL BUILDING UCC PLAN REVIEW HANDOUT AND CHECKLIST Every item below must be checked as completed (if applicable), or marked n/a (if not applicable),
More information10155 Toilet Compartments
10155 Toilet Compartments This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or
More informationProject Manual Index of Specifications Shenandoah Schools Concession Building
INDEX OF SPECIFICATIONS Division 0..BIDDING AND CONTRACT REQUIREMENTS 00 11 13 Advertisement for Bids 00 21 13 Instructions to Bidders 00 41 00 Bid Forms 00 43 13 Bid Security Form 00 72 00 General Conditions
More information5. Project Construction Cost (Provide cost for new construction, the addition or the alteration): $ Estimated Project Budget is $125,000.
3. Please check one of the following: [ ] New construction. [ ] Addition to a building or facility. [X] Alteration to an existing building or facility. [ ] Historical preservation (addition). [ ] Historical
More informationHOUSING CONVERSION Guidelines for the conversion of a house to commercial use.
PLANNING, PROPERTY AND DEVELOPMENT DEPARTMENT HOUSING CONVERSION Guidelines for the conversion of a house to commercial use. HAIR 105 January 2017 contents General Information 3 Zoning Information 4 Building
More information9'-" DATE: 2-2-6 EP NEW WOOD RAILS TO MATCH NEW PORCH RAILS. PT AND PAINTED NEW WOOD 6X6 WOOD POSTS W/ CAP. PT AND PAINTED NEW WOOD STAIRS. PT AND PAINTED TREADS 23'-6" NEW WOOD PORCH W/ T&G PT WOOD FLOORING
More informationCity Of Mendota Construction Procedures
City Of Mendota Construction Procedures Building Permit Application: A permit shall be obtained prior to commencing work of any type. Failure to do so may result in doubling the permit fees. At the time
More informationAccessible Toilet and Bathing Rooms
Accessible Toilet and Bathing Rooms Building & Fire Safety Division Yakima County Public Services This brochure is for illustration purpose only. It is NOT a complete section of the referenced codes, nor
More informationRESIDENTIAL BASEMENT ALTERATIONS GUIDE
RESIDENTIAL BASEMENT ALTERATIONS GUIDE THIS IS A GUIDE ONLY! FOR DETAILED INFORMATION, CONTACT THE BUILDING INSPECTOR OR TOWNSHIP AS ADDITIONAL REQUIREMENTS MAY PERTAIN TO YOUR PROJECT. November 2018 WHITEHALL
More informationPROJECT INFORMATION PROJECT NUMBER 1706 SINGLE DETACHED DWELLING - RENO 4208 VARMOOR ROAD NW CALGARY ALBERTA
BERZE RESIDENCE 4208 VARMOOR ROAD, NW CALGARY ALBERTA CLIENT PROJECT INFORMATION NAME BELA & BOGLARKA BERZE PROJECT NAME BERZE RESIDENCE PERMANENT ADDRESS TEMPORARY ADDRESS PHONE NUMBER EMAIL 4208 VARMOOR
More informationSECTION GYPSUM BOARD ASSEMBLIES
SECTION 09 21 16 GYPSUM BOARD ASSEMBLIES PART 1 GENERAL 1.1 SECTION INCLUDES A. Metal stud wall and ceiling framing, 20 gauge. B. Metal channel suspended ceiling framing. C. Gypsum board. D. Gypsum sheathing.
More informationCommercial and Residential Projects (after appropriate Board approvals have been made if necessary):
Village of Lansing Office: 2405 N. Triphammer Rd. Hours: 9:00-1:00 Telephone: 257-0424 Ext. # 3 Email: codeofficer2@vlansing.org Commercial and Residential Projects (after appropriate Board approvals have
More informationTHE BARTON. CONTACT US Paul Fusz First Vice President NEW MIXED-USE DEVELOPMENT - GROUND FLOOR RETAIL SPACE
NEW MIXED-USE DEVELOPMENT - GROUND FLOOR RETAIL SPACE CONTACT US Paul Fusz First Vice President +1 314 655 6046 paul.fusz@cbre.com Josh Roedemeier Vice President +1 314 655 5942 josh.roedemeier@cbre.com
More informationArchitect and Engineer: Friar Associates inc.
Architect and Engineer: Friar Associates inc. BACKGROUND In June, after soliciting and interviewing several professional firms, Friar Associates was hired to perform an Existing Conditions Survey and Facilities
More informationFairfax County, Virginia
Fairfax County, Virginia Typical Finished Basement Details Based on the 2009 International Residential Code CONTENTS General Requirements... 2 Emergency Escape and Rescue... 2 Wall Construction... 3 Floor/ceiling
More informationEXIT CONTROL 108 SIM LAB 105 SIM LAB 106 BUSINESS 2465 SF 100 GROSS 25 OCCUPANTS CLASSROOM 104 DATA / COMM 103 SCOPE OF WORK
DN USCL NURSING OSE# H7-955 76 HUBBARD DRIVE LANCASTER, S.C. 970 DN DN DN UP UP 05 CONTROL 08 06 07 MECH 0 GOODWYN MILLS CAWOOD 0 East Washington Street, Suite 00 Greenville, SC 960 Tel 86.57.060 GMCNETWORK.COM
More informationDesign and Construction AN ISO 9001:2008 CERTIFIED ORGANIZATION
Design and Construction AN ISO 9001:2008 CERTIFIED ORGANIZATION Division of Design, 35 th Floor, Corning Tower The Governor Nelson A. Rockefeller Empire State Plaza Albany, New York 12242 Phone: (518)
More informationINSTRUCTIONS FOR COMPLETING THE BUILDING PERMIT APPLICATION FOR COMMERCIAL PROJECTS
INSTRUCTIONS FOR COMPLETING THE BUILDING PERMIT APPLICATION FOR COMMERCIAL PROJECTS The Commercial Plan Summary has been designed to give you a clear understanding of the minimum requirements for submitting
More informationADDENDUM NO. 2 Consisting of 3 pages and Attachments
10404-125 Street, Edmonton, AB. T5N 1T2 Tel: 780.455.5975 Fax: 780.454.2397 info@cdyarchitect.com ADDENDUM NO. 2 Consisting of 3 pages and Attachments PROJECT: Maina Centre Ville Phase II, Beaumont, Alberta
More informationSTAIR ELEC CLOSET francisco alvarado, architect tel: 47-545-884 email: francisco.p.alvarado@gmail.com STAIR M5 MEN'S WALK-IN COOLER M4 HOUR FIRE RATED PARTITION KITCHEN 8 53' TRAVEL DISTANCE OFFICE 7 HOUR
More informationAPPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:
COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION
More informationExhibit A Library Shell Construction
Exhibit A Library Shell Construction Library Component Building Requirements Approximately 15,000-17,000 square feet plus 900 square feet for mechanical room and additional space on roof for installation
More informationINTERIOR ENVIRONMENT
CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,
More informationMITTERSILL WARMING HUT
STATE OF NEW HAMPSHIRE DEPARTMENT OF RESOURCES AND ECONOMIC DEVELOPMENT DIVISION OF PARKS AND RECREATION PROJECT #: CAP 1786 FRANCONIA NOTCH STATE PARK FRANCONIA, NEW HAMPSHIRE DRAWING LIST: COVER SHEET
More informationCarter's Oshkosh (SIS) # The Center at Pearland Parkway - Pearland, TX Scope Of Work / Bid Qualifications
Carter's Oshkosh (SIS) #1185 - The Center at Pearland Parkway - Pearland, TX 77581 - Scope Of Work / Bid Qualifications Please fill out the blanks associated with your trade scope or work with the words
More informationTHIS APPLICATION IS FOR NEW CONSTRUCTION OR RENOVATION OF ONE AND TWO FAMILY DWELLINGS.
CITY OF DECATUR, TEAS 1601 S. State Street Phone 940-393-0250 Inspections Line 940-393-0259 * Fax 940-626-4629 Permit Application (New Construction / Remodel / Addition) Permit #: Valuation: $ Permit Fee:
More informationFRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6
PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA
More informationSECTION NON-STRUCTURAL METAL FRAMING
SECTION 09 22 16 PART 1 - GENERAL 1.1 DESCRIPTION A. This section specifies steel studs wall systems, shaft wall systems, ceiling or soffit suspended or furred framing, wall furring, fasteners, and accessories
More informationAdministrative Changes
Revised 11/29/06 Knox County Residential Building Codes Significant Changes From The 1995 CABO One And Two Family Dwelling Code To The 2006 International Residential Code All one and two family dwellings
More informationWorksheet for Commercial Building Planning
Worksheet for Commercial Building Planning Note: This checklist helps ensure that all major code items were checked BEFORE applying for permit. ADDRESS OF PROJECT: Chapter 3 Information 301-312 OCCUPANCY
More informationBUILDING PERMIT APPLICATION
TOWN OF LEICESTER 132 Main Street Post Office Box 197 Leicester, New York 14481 Phone: (585) 382-3231 FAX: (585) 382-9766 BUILDING PERMIT APPLICATION All Town of Leicester property owners are required
More informationA. Remove Table of Contents and insert new attached Table of Contents.
ADDENDUM NO. 01 PROJECT Colby Glass E.S. Window Upgrades and ADA Work PROJECT NO. 16043 DATE February 07, 2018 TO: All Prime Contract Bidders and all others to whom Drawings and Specifications have been
More informationFOR SALE OR LEASE 1924 Dana Ave. Cincinnati, OH Floor, Single user building
94 Dana Ave Cincinnati, OH 407 SINGLE TENANT OPPORTUNITY!,7 SF Building $,00,000 for Sale $9.0/SF Net for Lease Property Highlights Floor, Single user building Constructed in 9 and completely renovated
More information