INTERIM CRITERIA FOR EXTERIOR INSULATION AND FINISH SYSTEMS PREFACE

Size: px
Start display at page:

Download "INTERIM CRITERIA FOR EXTERIOR INSULATION AND FINISH SYSTEMS PREFACE"

Transcription

1 ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect INTERIM CRITERIA FOR EXTERIOR INSULATION AND FINISH SYSTEMS AC24 June 2003 (Effective July 1, 2003) Previously issued April 2001, October 1999, June 1998, January 1998 April 1997, January 1993 PREFACE Legacy evaluation reports issued by ICC Evaluation Service, Inc. (ICC-ES), are based upon performance features of the Uniform family of codes and the International family of codes. Section of the 1997 Uniform Building Code (UBC), Section of the 2000 International Building Code (IBC) and Section R of the 2000 International Residential Code (IRC) are the primary charging sections upon which evaluation reports are issued. Section of the UBC reads as follows: The provisions of this code are not intended to prevent the use of any material, alternate design or method of construction not specifically prescribed by this code, provided any alternate has been approved and its use authorized by the building official. The building official may approve any such alternate, provided the building official finds that the proposed design is satisfactory and complies with the provisions of this code and that the material, method or work offered is, for the purpose intended, at least the equivalent of that prescribed in this code in suitability, strength, effectiveness, fire resistance, durability, safety and sanitation. The building official shall require that sufficient evidence or proof be submitted to substantiate any claims that may be made regarding its use. The details of any action granting approval of an alternate shall be recorded and entered in the files of the code enforcement agency. Similar provisions are contained in Sections and R of the IBC and IRC, respectively. The attached acceptance criteria has been issued to provide all interested parties with guidelines on implementing performance features of the applicable code(s) referenced in the acceptance criteria. The criteria was developed and adopted following public hearings conducted by the ICC-ES Subcommittee on Uniform Codes and is effective on the date shown above. All reports issued or reissued on or after the effective date must comply with this criteria, while reports issued prior to this date may be in compliance with this criteria or with the previous edition. If the criteria is an updated version from a previous edition, a solid vertical line ( ) in the margin within the criteria indicates a technical change, addition, or deletion from the previous edition. A deletion indicator ( ) is provided in the margin where a paragraph has been deleted if the deletion involved a technical change. This criteria may be further revised as the need dictates. ICC-ES may consider alternate criteria, provided the proponent submits valid data demonstrating that the alternate criteria are at least equivalent to the attached criteria and otherwise meet the applicable performance requirements of the codes. Notwithstanding that a material, type or method of construction, or equipment, meets the attached acceptance criteria, or that it can be demonstrated that valid alternate criteria are equivalent and otherwise meet the applicable performance requirements of the codes, if the material, product, system or equipment is such that either unusual care with its installation or use must be exercised for satisfactory performance, or malfunctioning is apt to cause unreasonable property damage or personal injury or sickness relative to the benefits to be achieved by the use thereof, ICC-ES retains the right to refuse to issue or renew an evaluation report. Copyright 2003 Business/Regional Office P 5360 Workman Mill Road, Whittier, California P (562) Regional Office P 900 Montclair Road, Suite A, Birmingham, Alabama P (205) Regional Office P 4051 West Flossmoor Road, Country Club Hills, Illinois P (708)

2 1.0 INTRODUCTION 1.1 Scope: The purpose of this acceptance criteria is to specify the conditions under which an exterior insulation and finish system (EIFS) can be recognized in an ICC-ES evaluation report under the 1997 Uniform Building Code (UBC), the 2000 International Building Code (IBC) and the 2000 International Residential Code (IRC). Where this criteria references code sections of each of the various codes, the applicable section is the section of the code under which the system is being evaluated, unless noted otherwise. Standard editions applicable to each code are summarized in Table 1. Equivalent systems can be considered with proper justification. At a minimum, the equivalent system must include the exterior coating, insulation and nonmetallic reinforcement, and be primarily confined to the exterior wall surface. 1.2 Referenced Documents: Uniform Building Code (UBC), International Conference of Building Officials International Building Code (IBC), International Code Council International Residential Code (IRC), International Code Council ICC-ES Interim Criteria for Test Reports and Product Sampling (AC85) ICC-ES Interim Criteria for Laboratory Accreditation (AC89) ICC-ES Interim Criteria for Quality Control Manuals (AC10) UBC Standard 7-1, Fire Tests of Building Construction and Materials, International Conference of Building Officials UBC Standard 8-1, Test Method for Surfaceburning Characteristics of Building Materials, International Conference of Building Officials UBC Standard 14-1, Kraft Waterproof Building Paper, International Conference of Building Officials UBC Standard 23-2, Construction and Industrial Plywood, International Conference of Building Officials UBC Standard 23-3, Performance Standard for Wood-based Structural-use Panels, International Conference of Building Officials UBC Standard 26-3, Room Fire Test Standard for Interior of Foam Plastic Systems, International Conference of Building Officials UBC Standard 26-4, Method of Test for the Evaluation of Flammability Characteristics of Exterior, Nonload-bearing Wall Panel Assemblies Using Foam Plastic Insulation, International Conference of Building Officials UBC Standard 26-9, Method of Test for the Evaluation of Flammability Characteristics of Exterior, Nonload-bearing Wall Assemblies Containing Combustible Components Using the Intermediate-scale, Multistory Test Apparatus, International Conference of Building Officials ASTM B , Practice for Operating Salt-spray (Fog) Apparatus, American Society for Testing and Materials ASTM C 79, Standard Specification for Treated Core and Nontreated Core Gypsum Sheathing Board, ASTM C 150, Standard Specification for Portland Cement, ASTM C , Standard Test Method for Flatwise Tensile Strength of Sandwich Constructions, ASTM C (1993), Standard Specification for Aggregate for Job-Mixed Portland Cement-Based Plasters, ASTM C , Standard Specification for Elastomeric Joint Sealants, American Society for Testing and Materials ASTM C , Standard Specification for Glass Mat Gypsum Substrate for Use as Sheathing, ASTM D a, Standard Specification for Asphalt-Saturated Organic Felt Used in Roofing and Waterproofing, ASTM D , Standard Practice for Testing Water Resistance of Coatings in 100% Relative Humidity, ASTM E , Standard Test Method for Surface Burning Characteristics of Building Materials, ASTM E 96-95, Standard Test Method for Water Vapor Transmission of Materials, American Society for Testing and Materials ASTM E , Standard Test Method for Fire Tests of Building Construction and Materials, American Society for Testing and Materials ASTM E , Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Uniform Static Air Pressure Difference, ASTM E , Standard Test Method for Water Penetration of Exterior Windows, Skylight, Doors and Curtain Walls by Uniform Static Air Pressure Difference, ASTM E , Standard Test Method for Structural Performance of Exterior Windows, Curtain Walls and Doors by Cyclic Static Air Pressure Differential, ASTM G 23-81, Standard Practice for Operating Light-Exposure Apparatus (Carbon-Arc Type) With and Without Water for Exposure of Nonmetallic Materials, ASTM G 26-96, Standard Practice for Operating Light-Exposure Apparatus (Xenon-Arc Type) With and Without Water for Exposure of Nonmetallic Materials, ANSI A , Test Methods and Specifications for Cementitious Backer Units. 2

3 EIMA 200.2, Standard Test Method for Determining the Drainage Performance of Exterior Insulation and Finish Systems (EIFS), Class PB, EIFS Industry Members Association Federal Specification UU-B-790a-1968, Building Paper, Vegetable Fiber: (Kraft, Waterproofed, Water Repellent and Fire Resistant), General Services Administration NFPA , Standard Test Method for Determining Ignitability of Exterior Wall Assemblies Using a Radiant Heat Energy Source, National Fire Protection Association NFPA , Standard Method of Test for the Evaluation of Flammability Characteristics of Exterior, Nonload-bearing Wall Assemblies Containing Combustible Components Using the Intermediate-scale, Multistory Test Apparatus, National Fire Protection Association UL , Fire Test of Interior Finish Material, Underwriters Laboratories Inc US DOC PS-1-95, Construction and Industrial Plywood, United States Department of Commerce US DOC PS-2-92, Performance Standard for Wood-based Structural-use Panels, United States Department of Commerce. 2.0 DEFINITIONS 2.1 EIFS: EIFS is a nonbearing exterior wall covering system, applied to a solid substrate or framing. It includes a fastening system, insulation board, base coat, nonmetallic reinforcing fabric and a finish coat. The system may also include primers, sealers, and accessories such as trim, corner beads and stops The fastening system is the method used to attach the insulation board to the substrate or framing. It may be an adhesive, a mechanical fastener or a combination thereof. For combination systems, either the mechanical or adhesive portion itself must be capable of resisting required forces when justification is other than results of full-scale structural performance tests. See Section EIFS Wall Covering Assembly With Drainage: An EIFS wall covering assembly with drainage is a nonbearing exterior wall covering assembly applied to a solid substrate. It includes a water-resistive coating that may be trowel-, spray- or roller-applied over the surface of a sheathing substrate, or a weather-resistive barrier as defined in Sections 1402 and of the UBC or a waterresistive barrier as defined in Sections and of the IBC or weather-resistant sheathing paper as defined in Section R703.2 of the IRC; a drainage medium or other means of drainage; a fastening system; insulation board; a base coat; nonmetallic reinforcing fabric; and a finish coat. The system may also include primers, sealers, and accessories such as trim, corner beads and stops The fastening system is the method used to attach the insulation board to the substrate. It may be adhesive, a mechanical fastener or a combination thereof. For combination systems, either the mechanical or adhesive portion itself must be capable of resisting the required forces when justification is other than full-scale structural performance tests. See Section The proponent is the applicant for an evaluation report on an EIFS. 3.0 MATERIAL SPECIFICATIONS 3.1 Water-resistive Coating Components (if applicable): Field Blended: Cement: Type and description must comply with ASTM C Sand: Must be clean and free from deleterious amounts of loam, clay, silt, soluble salts and organic matter. Sampling and testing must comply with ASTM C 897. Limits for grading sand must be specified when added in the field Admixtures: Description and purpose are needed for each product Preparation: Mixing instructions are needed Factory Blended: A description of the factoryblended materials is needed. 3.2 Adhesive Components: Field-blended: Cement: Type and description must comply with ASTM C Sand: Must be clean and free from deleterious amounts of loam, clay, silt, soluble salts and organic matter. Sampling and testing must comply with ASTM C 897. Limits for grading sand must be specified when added in the field Admixtures: Description and purpose are needed for each product Preparation: Mixing instructions are needed Factory-blended: A description of the factoryblended materials is needed. 3.3 Base Coat Components: Field-blended: Cement: Type and description must comply with ASTM C Sand: Must be clean and free from deleterious amounts of loam, clay, silt, soluble salts and organic matter. Sampling and testing must comply with ASTM C 897. Limits for grading sand must be specified when added in the field Admixtures: Description and purpose are needed for each product Factory-blended: A description of the factoryblended materials is needed. 3.4 Finish Coat: Specific description is needed, including any field mixing instructions. 3.5 Nonmetallic Reinforcing Fabric: Description must include such items as type, weight, thread count, strength, weave, and treatments for compatibility with coating. 3.6 Substrates: The EIFS must be applied to a rigid, solid substrate such as concrete, concrete masonry, Exterior or Exposure 1 wood-based panel sheathing complying with UBC Standard 23-2 or 23-3 (UBC) or US DOC PS-1 or PS-2 (IBC/IRC), water-resistant core gypsum sheathing complying with ASTM C 79 or C 1177, cementitious backer units 3

4 complying with ANSI A118.9, or equivalent material. In lieu of substrates, the EIFS may be applied to framing using an approved fastening system and a weather-resistive barrier complying with Section of the UBC, a water-resistive barrier complying with Section of the IBC, weatherresistant sheathing paper complying with Section R703.2 of the IRC or a weather-resistive barrier complying with the ICC-ES Interim Criteria for Weather-resistive Barriers (AC38). 3.7 Foam Plastic Insulation: Description of insulation must include type, density, flame spread, smoke density, conditioning requirements, dimensional tolerances, flexural strength, maximum water absorption, and other requirements necessary to show compliance with Section 2602 of the UBC, Section 2603 of the IBC or Section R318 of the IRC, the ICC-ES Interim Criteria for Foam Plastic Insulation (AC12), and special requirements unique to the EIFS. When used on walls required to be of noncombustible construction, the foam plastic must be identified in accordance with Section , Item 6, of the UBC or Section of the IBC. 3.8 Other Insulation Boards: Other insulation boards must comply with applicable UBC, IBC or IRC reference standards or, if not available, a recognized national standard, with the concurrence of ICC-ES. 3.9 Fastening Systems: 1. Mechanical fasteners must be specifically described, including type, shank diameter, length, head diameter, corrosion-resistance treatment and material specifications. 2. Adhesives for attachment of insulation to framing members must be qualified under the ICC-ES Interim Criteria for Sandwich Panel Adhesives (AC05). Attachment of an EIFS to framing members must be qualified in accordance with Section 5.5. Alternative adhesives and/or substrates may be qualified as described in Section Accessories: Expansion joints, weep screeds, corner reinforcement and similar items, when required by the proponent, must be installed in accordance with the proponents recommendations and as specified in the project design specifications (documents). Accessories must be described as to type of material, dimensions, thickness and corrosion-resistant treatment Primers and Adhesion Intermediaries: Specific description is necessary, including type, use, specification and location Surface Sealers: Specific description is necessary, including type, use, specification and limitations Labeling: Labeling for field identification must include the following: 1. Name and address of manufacturer and appropriate evaluation report number. 2. Identification of components. 3. Lot or batch number. 4. Quantity of material in packaged mix. 5. Storage instructions. 6. Specific mixing instructions. 7. Curing instructions. 8. Expiration date (when applicable). 9. ICC-ES evaluation report number (ICC-ES ER-xxxx). 4.0 SEALANTS Sealants used at control joints, intersections or terminations of the EIFS at dissimilar materials, wall/eave interfaces, penetrations and openings must be Type S or M, minimum Grade NS, minimum Class 25, and Use O, in compliance with ASTM C 920, and be compatible with the applicant s EIFS. Under the Use O classification, the sealant needs to be qualified for each of the materials to which the sealant will be applied, such as the EIFS material, copper piping, galvanized steel and vinyl window frames, by the adhesion and cohesion under cyclic movement test and adhesion-in-peel tests of Sections 8.8 and 8.9 of ASTM C 920. The details for sealant installation, including the width and thickness of the sealant, shall be designed by the registered design professional, designer, builder, or EIFS evaluation report applicant, in that order, to the satisfaction of the building official. An installation card, in the format shown in Exhibit A, completed by the sealant installer, must be presented to the building official, with the EIFS contractor declaration, at the completion of each project. The sealant declaration states that the sealant installation conforms to the EIFS evaluation report and the sealant manufacturers installation methods and procedures. 5.0 EXTERIOR WALL CONSTRUCTION 5.1 An EIFS can be recognized for application to walls required to be of noncombustible construction provided the EIFS is in compliance with Section of this criteria; and Section of the UBC or Section of the IBC. 5.2 Performance Requirements: Water-resistive Coating (if applicable): 1. Tensile bond tests as set forth in Section Freeze-thaw tests as set forth in Section Water-resistance tests as set forth in Section Water-vapor transmission of materials tests as set forth in Section Water-penetration tests as set forth in Section EIFS (Section 2.1): 1. Salt-spray-resistance tests as set forth in Section Tensile-bond tests as set forth in Section Freeze-thaw tests as set forth in Section Water-resistance tests as set forth in Section Optional fire tests as set forth in Section Structural testing as set forth in Section Water-penetration tests as set forth in Section (UBC) or Section (IBC/IRC) Accelerated-weathering tests as set forth in Section EIFS Wall Covering Assemblies with Drainage (Section 2.2): 4

5 1. Salt-spray-resistance tests as set forth in Section Tensile-bond tests as set forth in Section Freeze-thaw tests as set forth in Section Water-resistance tests as set forth in Section Optional fire tests as set forth in Section Structural testing as set forth in Section Water-penetration tests as set forth in Section Accelerated-weathering tests as set forth in Section Drainage-performance tests as set forth in Section The need for and locations of expansion and control joints must be determined and specified by the registered design professional, designer, builder, or exterior coating manufacturer, in that order. All expansion and control joint materials must be corrosion resistant. If used, expansion and control joints must be a part of test specimens for durability and structural tests. When the EIFS is placed over platform-frame construction with dimensional lumber, control joints are required at each floor level. 5.4 An EIFS is a nonbearing system. 5.5 Structural Considerations: Structural tests are required to determine allowable positive and negative wind loads that may be imposed on the EIFS. The test program should incorporate the following: EIFS test specimens must represent minimum conditions of installation, including such items as material thickness, density and connections. See Section Maximum allowable deflection of structural wall components must be specified and must be limited to a maximum 1 / 180 of span, except where more restrictive requirements prevail Lateral-resistance tests of mechanical connections (such as nails and screws) are required if connectors support heavy exterior wall coatings through foam plastic, or other nonstructural insulations, that are more than 1 1 / 2 inches (38 mm) thick. Where standard specifications are available on minimum structural qualities of the materials involved, calculations may be substituted for tests. 5.6 Weather-resistive Consideration: UBC Type V, Group R, Division 1 and Division 3 Occupancies: Systems shall comply with Section as EIFS wall covering assemblies with drainage. Weatherresistive barriers complying with Section of the UBC are required for Type V, Group R, Division 1 and Division 3 Occupancies having framed walls. Section , Section , and the third paragraph of Section of the UBC must be considered in establishing the required weather protection. As an alternative to using two layers of Grade D building paper as specified in Section of the UBC for construction utilizing wood-based sheathing, a single layer of Grade D building paper having a waterresistance rating of 60 minutes may be used. To qualify a water-resistive coating applied over solid substrates as an alternate to the weather-resistive barrier, testing of the coating as outlined in Section is required Occupancies Other than Type V, Group R, Division 1 and Division 3, with Framed Walls under the UBC: Compliance with Section 1402 of the UBC, without the mandatory weather-resistive barriers, is permitted with proper justification. For Type V Construction, as an alternative to using two layers of Grade D building paper as specified in Section of the UBC for construction utilizing wood-based sheathing, a single layer of Grade D building paper having a water resistance rating of 60 minutes may be used. This justification requires testing under Section of this criteria IBC Type V, Group R1, R2, R3 and R4 Occupancies: Systems shall comply with Section as EIFS wall covering assemblies with drainage. Weatherprotection items complying with Sections , , , , and of the IBC must be considered in establishing the required weather protection. For Type V, Group R Occupancies, Exception 2 of Section of the IBC shall apply to R1 and R2 Occupancies only. As an alternative to steel described in Section of the IBC, materials complying with ASTM C 1063 may be used in weep screeds. As an alternative to using two layers of Grade D building paper as specified in Section of the IBC, for construction utilizing wood-based sheathing, a single layer of Grade D building paper having a water-resistance rating of 60 minutes may be used. To qualify a water-resistive coating applied over solid substrates as an alternate to the water-resistive barrier, testing of the coating as outlined in Section is required Occupancies other than Type V, Group R1, R2, R3 and R4 with Framed Walls under the IBC: Compliance with Section of the IBC, without the mandatory waterresistive barriers is permitted with proper justification. For Type V Construction, as an alternative to using two layers of Grade D building paper as specified in Section of the IBC, for construction utilizing wood-based sheathing, a single layer of Grade D building paper having a waterresistance rating of 60 minutes may be used. This justification requires testing under Section of this criteria. Weather protection items complying with Sections , , , , and of the IBC must be considered in establishing the required weather protection and the configuration of the test assemblies required under Section IRC: Weather-resistive barriers, complying with Section R , and flashing, complying with Section R , are required for framed-wall construction over water-sensitive building components. Systems shall be EIFS wall covering assemblies with drainage and comply with Section Plans, details and specifications, concerning proper installation of the EIFS, that are applicable to the specific building under consideration, must be a part of documents submitted to the building official for approval. When installed on framed walls of Type V, Group R, Division 1 or Division 3 Occupancies (UBC), Type V, Group R1, R2, R3 or R4 Occupancies (IBC), or building under the IRC, EIFS wall covering assemblies with drainage, defined in Section 2.2, are required. 5

6 5.8 Off-site fabrication of EIFS must be done in the shop of an approved fabricator under special inspection in conformance with Section of the UBC or Section of the IBC. 5.9 Required installation details of the EIFS at typical areas of termination, such as parapets, wall openings, intersections with other materials, expansion and control joints, foundations, projections and wood-based panel sheathing are necessary. Details must be of camera-ready quality, for inclusion in evaluation reports, and must be consistent with required application instructions. See Section Impact Resistance: Impact resistance is beyond the scope of this criteria EIF systems must be separated from the interior of the building with a thermal barrier having a minimum thermal-barrier index of 15, unless specific recognition is granted based on Section or Section of the UBC or Section or of the IBC, or Section R of the IRC Vertical joints of insulation boards must be staggered from edges of wall openings. 6.0 TESTING 6.1 Testing Laboratories: Testing laboratories must comply with the ICBO ES Acceptance Criteria for Laboratory Accreditation (AC89). 6.2 Test Reports and Product Sampling: Test reports and test specimen sampling must comply with the ICBO ES Acceptance Criteria for Test Reports and Product Sampling (AC85). 6.3 Salt Spray Resistance: Testing must comply with ASTM B 117. Three samples, 4 inches by 6 inches (102 mm by 152 mm) by the minimum thickness of the EIFS as specified by the manufacturer, are mounted to minimum 1 / 2 -inch-thick (12.7 mm) gypsum sheathing or equivalent and cured in accordance with the manufacturers instructions. The testing period is 300 hours Condition of Acceptance: The absence of deleterious effects from salt spray after 300-hour exposure. 6.4 Tensile Bond: Water-resistive Coating: Testing must comply with ASTM C 297. For each substrate for which recognition is sought, five samples are prepared by applying the water-resistive coating to the substrate Condition of Acceptance: A minimum flatwise tensile strength of 15 psi (105 kpa) is required System Testing (adhesive attachment): Testing must comply with ASTM C 297. For each substrate for which recognition is sought, five samples are prepared by applying the water-resistive coating (if applicable) to the substrate, then adhering insulation board to the water-resistive coating or adhering insulation board directly to the substrate Conditions of Acceptance: Insulation board must fail cohesively. Exceptions: 1. Maximum 25 percent adhesive failure is acceptable. 2. Where flatwise tensile strength test values are 15 psi (105 kpa) or greater, adhesive failure up to 100 percent is acceptable. 6.5 Freeze-thaw Tests: Water-resistive Coatings: For each substrate for which recognition is sought, five 6-inch-square ( mm 2 ) samples are prepared by applying the water-resistive coating to the substrate. To prepare samples, the substrate is cut in half and the water-resistive coating is applied to the substrate surface in accordance with the manufacturers recommended application instructions. The back and sides of the samples must be sealed with an impervious material that need not be the coating. Specimens must be representative of those used in actual construction Samples are subjected to 10 freeze-thaw cycles. Each cycle consists of air-drying at a temperature of 120 F (49 C) for a minimum of eight hours, followed by total immersion in water at 70 F to 80 F (21.1 C to 26.7 C) for eight hours, and exposure to a temperature of -20 F ( C) for 16 hours Condition of Acceptance: Failure is defined as surface changes, as viewed by minimum 5 magnification, such as cracking, checking, crazing, erosion or other characteristics that may affect performance as a wall covering. Failure is also defined as delamination, or indications of delamination between components EIFS Testing: Five 6-inch-square ( mm 2 ) samples are prepared by applying the weather-resistive coating (if applicable) to the substrate, then applying the insulation board and exterior coatings to the front face and edges of the insulation board. The back of the sample must be sealed with an impervious material that need not be the coating. Specimens must contain coating and insulation accessories that are representative of those used in actual construction Samples are subjected to 10 freeze-thaw cycles. Each cycle consists of air-drying at a temperature of 120 F (49 C) for a minimum of eight hours, followed by total immersion in water at 70 F to 80 F (21.1 C to 26.7 C) for eight hours, and exposure to a temperature of -20 F ( C) for 16 hours Condition of Acceptance: Failure is defined as surface changes, as viewed by minimum 5 magnification, such as cracking, checking, crazing, erosion, or other characteristics that may affect performance as a wall cladding. Failure is also defined as delamination, or indications of delamination between components. 6.6 Water Resistance Tests: Water-resistive Coatings: For each substrate for which recognition is sought, three samples, a minimum of 4 inches by 6 inches (102 mm by 152 mm) in size, are prepared by applying the water-resistive coating to the substrate. The substrate is cut 6

7 in half, and the water-resistive coating is applied to the substrate surface in accordance with the manufacturers recommended application instructions. The back and sides of the samples must be sealed with an impervious material that need not be the coating. Specimens must be representative of those used in actual construction Testing must be in accordance with ASTM D Periodic inspections must be conducted. Testing may be concluded after 14 days, or after deleterious effects of exposure to water are observed Condition of Acceptance: The absence of deleterious effects from 14 days of exposure to water EIF System: General: Testing must comply with ASTM D Three samples, a minimum of 4 inches by 6 inches (102 mm by 152 mm) in size, must be used. Periodic inspections must be conducted. Testing may be concluded after 14 days, or after deleterious effects of exposure to water are observed Condition of Acceptance: The absence of deleterious effects from 14 days of exposure to water. 6.7 Fire Tests: Fire-resistive Construction UBC Standard 7-1 (UBC) or ASTM E 119 (IBC/IRC) (optional): This optional test is for recognition for fire-resistive construction. Unless a report of successful testing of an assembly in accordance with UBC Standard 7-1 or ASTM E 119 is submitted, EIFS is limited to nonfire-resistive construction. In this regard, the application of the EIFS to a recognized noncombustible fireresistive assembly negates the assemblys fire-resistive rating, unless: 1) the assembly is tested in accordance with the specified standard; or 2) an analysis of the effect of installation of the EIFS on the fire-resistance of the fireresistive assembly is submitted. The data comprising the analysis should include reports of fire-resistance tests on wall assemblies with and without EIFS installed, and an analysis of the effect of the EIFS on fire resistance. Recognition of EIFS in fire-resistive assemblies must consider type of assembly, whether bearing or nonbearing, and foam plastic thickness Noncombustible Construction under the UBC: UBC Standard 26-4 or UBC Standard 26-9 (optional): This optional test is for recognition of EIFS for application to walls required to be of noncombustible construction. Other related requirements are addressed in Section of the UBC. Without compliance, EIFS is limited to combustible construction UBC Standard 8-1 (based on ASTM E 84-84) (optional): This optional test is for recognition of EIFS as an interior finish, provided thermal-barrier requirements for foam insulation are resolved in accordance with Section 2602 of the UBC. Without successful testing, the EIFS is considered an exterior wall covering only. The EIFS must be tested with the face of the assembly exposed to the fire source during testing in accordance with UBC Standard For recognition on noncombustible construction, the system components must be tested separately in accordance with Item 4 of Section of the UBC Noncombustible Construction under the IBC: NFPA 285 (optional): This optional test is for recognition of EIFS for application to walls required to be of noncombustible construction. Other related requirements are addressed in Section of the IBC. Without compliance, EIFS is limited to combustible construction ASTM E 84 under the IBC or IRC (optional): This optional test is for recognition of EIFS as an interior finish, provided thermal-barrier requirements for foam insulation are resolved in accordance with Section of the IBC or R of the IRC. Without successful testing, the EIFS is considered an exterior wall covering only. The EIFS must be tested with the face of the assembly exposed to the fire source during testing in accordance with UL1715. For recognition on noncombustible construction, the system components must be tested separately in accordance with Section of the IBC Ignition NFPA 268 under the IBC: This test is required for exterior wall coverings in accordance with Section of the IBC. For installation on walls required to be noncombustible construction, Section of the IBC applies. 6.8 Water Vapor Transmission: Water-resistive Coatings: Three specimens of the water-resistive coating are prepared by applying the coating, at the recommended thickness, to a nonadhesive surface. After curing, the films are removed from the surface; the average thickness is determined from material density, area, and weight. The films are used to set up three wet cups in accordance with ASTM E 96, Water Method. Specimens are conditioned at 75 F ± 5 F (24 C ± 3 C) and 50 percent relative humidity for 40 hours before testing. Each cup is placed in a room with controlled conditions of 75 F ± 5 F (24 C ± 3 C) and 50 percent relative humidity. Reduction in weight is recorded daily. Water vapor transmission is calculated in accordance with Section 13 of ASTM E 96, and reported in grams per square meter per 24 hours Conditions of Acceptance: Water vapor transmission must satisfy one of the grade requirements in Table 14-1-A of UBC Standard 14-1 or Table 1 of the ICC- ES Interim Criteria for Weather-resistive Barriers (AC38). 6.9 Structural Performance Tests: Testing must be in accordance with ASTM E 330, Procedure B. At least three positive and three negative load tests must be conducted on three specimens, with the coating, insulation board, and sheathing prepared and installed in accordance with the proponents published instructions. Test-specimen fabrication must be done with verification by the testing agency or its authorized representative. Specimens must be a minimum of 4 feet by 8 feet (1219 mm by 2438 mm) in size, and must include vertical-control joints, scored joints and any other architectural features located midway between the stud framing, if these features are to be recognized in the evaluation report. Application of load to ultimate must consist of at least six increments, with a 10-second load duration for each increment Specimens must be mounted in accordance with ASTM E 330. Framing supporting the panel must be located at the maximum spacing for which recognition is sought. In most instances, this will result in triple 16-inch (406 mm) spans or double 24-inch (610 mm) spans. ICC-ES staff must be contacted by the report applicant in the event that spans vary from those required herein. For mechanically fastened systems, connections to framing members must be based 7

8 on minimum conditions (since test specimens establish a basis of acceptance), including the steel thickness (where steel framing is involved) In addition to data specified in Section 6.2, loaddeflection readings at panel midpoint must be reported Conditions of Acceptance: Allowable loading will be based on a minimum factor of safety of 3.0 applied to the ultimate load, if all of the following are satisfied: No single test result varies by more than 15 per cent from the average of three tests. Variations exceeding this limit require larger safety factors Allowable load does not exceed established values for mechanical connectors such as nails, screws and staples To qualify the adequacy of fasteners in concrete or masonry substrates, a tension-load test program, consisting of fastener withdrawal from the applicable wall(s) of the building(s) at the location in question, must be implemented. The testing must be conducted by an independent testing laboratory. The average withdrawal strength, in pounds, must be six times the design wind pressure for the location in question. A minimum of five tests per program is required, with results varying no more than 15 percent from the average. If a minimum of 10 tests per program is conducted, variation from the average may be disregarded. For masonry substrates, minimum 40 percent of the tests must be run in masonry joints. Prior to installation of EIFS fasteners, a certificate of compliance, concerning test results relating to load requirements in the evaluation report, must be submitted to and approved by the building official Results of tests conducted over gypsum sheathing as specified in Sections through can be extended to EIFS adhered to wood-based sheathing, cementitious backer units and glass-mat gypsum board, under the following conditions: The EIFS is adhered to all sheathing in question (e.g., plywood, particleboard, waferboard and oriented strand board, gypsum panels, and cementitious backer units) Tensile bond tests are conducted in accordance with ASTM C Tensile bond test results average a minimum of 15 psi (103 kpa) Water Penetration Tests: Water-resistive Coatings: Three samples are prepared by applying the water-resistive coating to the substrate. The substrate must be attached to the framing members as required by the substrate manufacturer. The test samples must be a minimum of 4 feet by 8 feet (1219 mm by 2438 mm) in size, and must include a minimum of two vertical joints and one horizontal joint within the sheathing substrate. Joints within the substrate must be 1 / 8 inch (3.2 mm) wide. The water-resistive coating is applied to the substrate surface in accordance with the manufacturers recommended application instructions. Each sample must be tested in accordance with ASTM E 1233, Procedure A, with 80 percent positive design load (design load is defined as ultimate load with a safety factor of 3.0 imposed) as the maximum test load. The samples must be cycled for a minimum of 10 cycles. Each sample must then be tested in accordance with ASTM E 331. A 6.24-psf (298 Pa) airpressure differential must be maintained, across the test specimens, for 75 minutes Conditions of Acceptance: There must be no water penetration on the plane of the exterior-facing side of the substrate. The substrate must be removed after the test to make this determination EIFS Testing: Three samples are prepared by applying the EIF system to the substrate. The substrate must be attached to the supporting framework as required by the substrate manufacturer. The test samples must be a minimum of 4 feet by 8 feet (1219 mm by 2438 mm) in size, and must include a minimum of two vertical joints and one horizontal joint within the sheathing substrate and insulation board. Each sample must be tested in accordance with ASTM E 331. A 2.86-psf (136.9 Pa) air-pressure differential must be maintained, across the test specimens, for 15 minutes Conditions of Acceptance: For specimens with insulation fully adhered to the substrate, no water penetration is permitted on the unexposed substrate face (i.e., the face of the test specimen that is not exposed to the test conditions). For specimens with insulation mechanically fastened to the substrate, no water penetration is permitted on the plane of the exterior-facing side of the substrate. The substrate must be removed after the test to make this determination EIFS Testing (IBC/IRC): Tests for EIFS are conducted in accordance with Section , Exception 2, of the IBC. At least one sample for each wall envelope assembly configuration is needed. The configuration is determined by the sheathing, insulation, insulation attachment, lamina, openings, joints, penetrations and wall sill joint configuration used in the test samples. Control joints, intersections or terminations of the EIFS at dissimilar materials, wall/eave interface, configuration and methods of making the EIFS at penetrations and openings waterproof (including the EIFS interface at doors and windows), as used in the tests, will be the basis for the evaluation report. Sealants used in the test assembly shall comply with Section 4.0. For windows and doors, the test assembly shall be in accordance with Figure 1 and include the intended flashing system, or the evaluation report will need to include dimensioned drawings of the type of window and door frame used in the tests Conditions of Acceptance: Conditions of acceptance are as set forth in IBC Section , Exception Drainage Test-Drainage-type EIFS: Testing must be performed in accordance with EIMA Standard Standard Test Method for Determining the Drainage Performance of Exterior Insulation and Finish Systems (EIFS), Class PB (described in Annex 1). Three samples are required. Each sample panel must be a minimum of 4 feet by 8 feet (1219 mm by 2438 mm) in size, with a slot fault measuring 2 inches by 24 inches (50 8

9 mm by 610 mm) positioned 12 inches (305 mm) from the top of the panel, exposing the weather-resistive barrier. The sample must be tested for 75 minutes Conditions of Acceptance: The assemblies must be capable of draining water, and the assemblies must have an average minimum true drainage efficiency of 90 percent, except that a minimum of 75 percent may be accepted, with proper justification, for wall assemblies having cementitious backer units complying with Section 3.6, used as a sheathing to the exterior of the weather-resistive barriers Accelerated Weathering Test (Weatherometer): Test Specimens: Five samples are prepared as for the freeze-thaw test (Section 6.5.2), except that sample size is as necessary to fit the chamber. The back and sides of the sample must be sealed with the appropriate impervious seal Apparatus: Either Section or Section is permitted ASTM G 23, Operating Light and Water Exposure Apparatus (Carbon-Arc Type) for Exposure of Nonmetallic Materials must be used. Model D or DH, with the operating schedule set forth under Method 1, Section 5, of the referenced ASTM procedure, must be used ASTM G 26, Practice for Operating Light- Exposure Apparatus (Xenon Arc-Type) With and Without Water for Exposure of Nonmetallic Materials, Test Method A, must be used. The exposure apparatus must be Type B or BH as specified in ASTM G 26, Method A, with a 6,000- or 6,500-watt xenon burner tube. Exposure must be for 2,000 hours, with each cycle consisting of 102 minutes of light-only exposure and 18 minutes of water-spray and light exposure. The water spray must be deionized water. The spray nozzle must be Type F-80. The apparatus must be operated with a light exposure of 0.35 W/m 2 at 340 nm. The test must be performed using a daylight filter system. The relative humidity for the Type BG exposure apparatus must be 30 ± 5 percent. Black panel temperature must be 145 F ± 5 F (62.7 C ± 2.3 C) during the light-only portion of the cycle Duration: The test must be for 2,000 hours Conditions of Acceptance: Failure is defined as surface changes, as viewed by minimum 5 magnification, such as cracking, checking, crazing, erosion, or other characteristics that might affect performance as a wall cladding. 7.0 APPLICATION Application instructions bearing the date of publication must be submitted. Instructions must include the information noted in Sections 7.1 through 7.6. Installation details need to be consistent with assemblies tested under Section , as applicable. 7.1 Illustrated details, with the following as a minimum: Flashing and/or sealing around heads, sills and jambs of windows and doors, and at the top of exposed walls Closures and flashing at other terminations, such as eaves and sills, and at other dissimilar exterior wall coverings Typical conditions within the field of the wall covering, showing substrates and control joints Parapet at top and termination on backside Flashing and/or sealing at wall penetrations Provisions to prevent retention of free water behind all portions of the EIFS Installation over wood-based sheathing Other details deemed necessary as conditions of an evaluation report. 7.2 Information on any variation from recognized proportions or content of field-mixed components. See Sections 3.1 through Curing instructions. 7.4 Limitations, such as angle of installation and installation in interior locations, must be specified. Architectural treatments that can reduce resistance to water penetration are prohibited. 7.5 Exposure: For water-resistive coatings and insulation board, the proponent must specify conditions and duration of exposure before covering. 7.6 IRC: For recognition under the IRC, instructions must include requirements described in Section R703.9 of the IRC. 8.0 QUALITY CONTROL 8.1 All foam plastic boards must be listed and labeled as set forth in Section of the UBC or of the IBC. Compliance of foam plastic is based on a current applicable evaluation report, on the foam plastic; if no such report exists, foam plastic must comply with the ICC-ES Interim Criteria for Foam Plastic Insulation (AC12). The quality control procedures must also include special requirements of the EIFS, such as conditioning, dimensional tolerances, and strength. See Section EIFS Manufacturer: The EIFS manufacturer must provide to ICC-ES a quality control manual that describes the in-house testing performed on all incoming raw materials, and on the base coat, finish coat, adhesive, and waterproof coating. At a minimum, viscosity, ph level, and specific gravity must be tested. Two quality control systems are acceptable: 1. An in-house quality control system documented in a manual addressing requirements in this section and Section 2.2 of the ICC-ES Interim Criteria for Quality Control Manuals (AC10); or 2. A quality control system with inspections by an ICBO ES accredited quality control agency, documented in a manual addressing requirements in this section and the ICC-ES Interim Criteria for Quality Control Manuals (AC10). 8.3 Field Inspections and Reporting: Installation must be by a contractor recognized by the proponent as being trained to perform such installations. A list of the names and addresses of recognized contractors must be maintained by the proponent, and must be available to the building official or ICC-ES upon request. 9

10 8.3.2 An installation card, having the format shown in Exhibit A, must be completed by the EIFS contractor and must be presented to the building official, with the sealant installer declaration (such as shown in Exhibit B), at the completion of each project IBC: For recognition under the IBC, special inspections are required in accordance with Section and of the IBC. Duties of the inspector include verifying field preparation of materials, expiration dates, installation of components, curing of components, installation of joints and sealants.# TABLE 1 CROSS REFERENCE OF STANDARDS EDITIONS STANDARD 1997 Uniform Building Code 2000 International Building Code 2000 International Residential Code ASTM C ASTM C a FIGURE 1 CONFIGURATION FOR TESTING WATER PENETRATION RESISTANCE OF OPENING FLASHING SYSTEM 10

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE

ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR METAL PLASTER BASES (LATH) AC191 Approved May 2008 Effective June 1, 2008 Previously approved February 2008, October 2007,

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER PREFACE ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 Previously approved October 2007, January 2001,

More information

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria.

The purpose of this memo is to respond to the comments received in response to the May 1, 2007, staff letter and the revised criteria. ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect #19 To: From: ICC-ES Evaluation Committee Brian Gerber, S.E., and Irni Yani Date: June 1, 2007 Subject: Revisions to the Proposed Acceptance Criteria

More information

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE

ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) PREFACE www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR METAL COMPOSITE MATERIAL (MCM) AC25 Approved October 2010 (Editorially revised August

More information

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER

ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER www.icc-es.org (800) 423-6587 (562) 699-0543 A Subsidiary of the International Code Council ACCEPTANCE CRITERIA FOR PRECAST STONE VENEER AC51 Approved February 2008 Effective March 1, 2008 (Editorially

More information

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC CALIFORNIA AVENUE CORONA, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-2064 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

SPECIFICATION GUIDELINE

SPECIFICATION GUIDELINE SPECIFICATION GUIDELINE Environmental Stoneworks Corporate Office 6300 East Stapleton Drive South Denver, CO 80216 Phone (303) 309-3040 Fax (303) 309-3059 www.estoneworks.com Environmental Stoneworks specification

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: PROWALL BUILDING PRODUCTS, INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: PROWALL BUILDING PRODUCTS, INC. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-3720 Reissued 09/2016 This report is subject to renewal 09/2018. DIVISION: 09 00 00 FINISHES

More information

ESR ICC Evaluation Service, Inc. Issued November 1, 2003 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Issued November 1, 2003 This report is subject to re-examination in one year. ESR-1015 Issued November 1, 2003 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: PAREX USA, INC EAST LA PALMA AVENUE, SUITE 250 ANAHEIM, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 689 Reissued 07/206 This report is subject to renewal 07/208. DIVISION: 07 00 00

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SUPERWALL MANUFACTURING, INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SUPERWALL MANUFACTURING, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2214 Reissued 08/2017 This report is subject to renewal 07/2019. DIVISION: 09 00

More information

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee

October 12, Yours very truly, Gary G. Nichols, P.E., SECB Vice President. GGN/md Enclosure Evaluation Committee October 12, 2010 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON STAY-IN-PLACE, FOAM PLASTIC INSULATING CONCRETE FORM (ICF) SYSTEMS FOR SOLID CONCRETE WALLS Revisions to the Acceptance Criteria

More information

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: COREV AMERICA BRITTMOORE PARK DRIVE HOUSTON, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2000 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 07 00 00 THERMAL

More information

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION

July 23, 2010 PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION July 23, 2010 TO: SUBJECT: PARTIES INTERESTED IN REFLECTIVE FOIL INSULATION Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB) Dear Madam or Sir: In June

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS REPORT HOLDER: PAREX USA, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2045 Reissued 01/2017 This report is subject to renewal 01/2019. DIVISION: 07 00

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SOMAR INDUSTRIES LTD LUCKETT COURT EL PASO, TEXAS 79932

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: SOMAR INDUSTRIES LTD LUCKETT COURT EL PASO, TEXAS 79932 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2732 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 09 00

More information

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED

REPORT HOLDER: GREENMAKER INDUSTRIES, LLC 697 OAKWOOD AVENUE WEST HARTFORD, CONNECTICUT EVALUATION SUBJECT: DECOPLAST DDARS NOTCHED 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3428 Reissued 07/2017 This report is subject to renewal 07/2019. DIVISION: 07 00

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code. *Revised July 2006

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code. *Revised July 2006 LEGACY REPORT * Reissued April 1, 2001 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES

June 7, 2012 PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES June 7, 2012 TO: PARTIES INTERESTED IN HVAC DUCT ENCLOSURE ASSEMBLIES SUBJECT: Revisions to the Acceptance Criteria for Metallic HVAC Duct Enclosure Assemblies, Subject AC179-0612-R1 (MB/CA) Dear Colleague:

More information

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS

SECTION EXTERIOR INSULATION AND FINISH SYSTEMS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 07 24 00 1. Use this section only for NCA projects. 2. Detail wall section, base edge, expansion and control joint conditions for each system. Show locations of

More information

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS

February 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS February 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON ROOF UNDERLAYMENTS FOR USE IN SEVERE CLIMATE AREAS SUBJECT: Proposed Revisions to the Acceptance Criteria for Roof Underlayments for Use

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: WATER-RESISTIVE BARRIERS/WEATHER BARRIERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1504 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 07 00

More information

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA).

October 1, SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC R1 (WU/CA). October 1, 2012 TO: PARTIES INTERESTED IN WALKING DECKS SUBJECT: Proposed Revisions to the Acceptance Criteria for Walking Decks, Subject AC39-1012-R1 (WU/CA). Dear Colleague: We are seeking your comments

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: ROOFING AND SIDING PANELS REPORT HOLDER: KINGSPAN INSULATED PANELS, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1143 Reissued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: DIRECT-APPLIED FINISH SYSTEMS REPORT HOLDER: STO CORP.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: DIRECT-APPLIED FINISH SYSTEMS REPORT HOLDER: STO CORP. 0 ICC-ES Report ICC-ES (800) 423-6587 (562) 699-0543 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-2536 Reissued 08/2016 This report is subject to renewal 08/2018. DIVISION: 07 00 00 THERMAL

More information

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed.

October 3, Section 1.2 Scope and Section 6.6 were revised to clarify interior and exterior construction types allowed. October 3, 2016 TO: PARTIES INTERESTED IN EVALAUTION REPORTS ON FIBER- REINFORCED POLYMER (FRP) COMPOSITE COLUMNS USED AS AXIAL LOAD-BEARING AND NONLOAD-BEARING ARCHITECTURAL AND DECORATIVE COLUMNS SUBJECT:

More information

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS

June 9, 2008 PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect June 9, 2008 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON TERMITE- RESISTANT FOAM PLASTICS SUBJECT: Acceptance Criteria for Termite-resistant

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC.

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: ENERCEPT, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1780 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 6587 (562) 699 0543 www.icc es.org ESR 3152 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2375 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board

DRAFT - MOCA STANDARD for Fiber-Reinforced Magnesium Cement Board 1. Scope 1.1 This standard defines the minimum prescriptive quality and performance requirements for Fiberreinforced Magnesium Cement Board products intended for use in buildings in North America. For

More information

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016.

ESR-2894 Reissued April 2014 This report is subject to renewal April 1, 2016. ICC-ES Evaluation Report ESR-894 Reissued April 04 This report is subject to renewal April, 0. www.icc-es.org (800) 4-87 () 99-04 A Subsidiary of the International Code Council DIVISION: 07 00 00 THERMAL

More information

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS

December 1, 2014 PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS December 1, 2014 TO: PARTIES INTERESTED IN WATER-RESISTIVE BARRIERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Water-resistive Barriers, Subject AC38-1214-R1 (ST/GH) Dear Colleague: You

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: ULTRAKOTE PRODUCTS, LLC

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: ULTRAKOTE PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1471 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 09 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: FUNDERMAX GMBH 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3340 Reissued 05/2017 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

Gold Bond BRAND Gypsum Sheathing

Gold Bond BRAND Gypsum Sheathing BRAND 09 06 29 16 00/NGC 43/NGC brand is a moisture-resistant sheathing installed on the outside of exterior framing as a substrate for exterior claddings. It is manufactured with a treated water-resistant

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: PARKLEX USA 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3462 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION

June 1, 2010 PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION June 1, 2010 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON REFLECTIVE FOIL INSULATION SUBJECT: Proposed Revisions to the Acceptance Criteria for Reflective Foil Insulation, Subject AC02-0610-R1 (LS/RB)

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: ARCONIC ARCHITECTURAL PRODUCTS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3435 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A.

DIVISION: FINISHES SECTION: GYPSUM BOARD REPORT HOLDER: PANEL REY, S.A. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3831 Reissued 12/2017 This report is subject to renewal 12/2018. SECTION: 09 29 00

More information

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER:

LEGACY REPORT DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: EXTERIOR INSULATION AND FINISH SYSTEMS REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Legacy Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org NER 646 Reissued 07/2017 This report is subject to renewal 07/2018. DIVISION: 07 00 00 THERMAL

More information

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS

December 3, 2012 PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS December 3, 2012 TO: PARTIES INTERESTED IN INTUMESCENT FIRE-RESISTANT COATINGS FIELD-APPLIED TO PREFABRICATED WOOD I-JOISTS SUBJECT: Proposed Acceptance Criteria for Intumescent Fire-resistant Coatings

More information

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION

REPORT HOLDER: R.L. ADAMS PLASTICS, INC CROSSROADS COMMERCE PARKWAY WYOMING, MICHIGAN EVALUATION SUBJECT: POLYCORE BRAND INSULATION 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3914 Reissued 10/2017 This report is subject to renewal 10/2018. DIVISION: 07 00

More information

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT:

REPORT HOLDER: THE DOW CHEMICAL COMPANY 1501 LARKIN CENTER DRIVE MIDLAND, MICHIGAN EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3089 Reissued 07/2016 This report is subject to renewal 07/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: WATER RESISTIVE BARRIERS/WEATHER BARRIERS SECTION: AIR BARRIERS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1993 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: BONSAL AMERICAN, INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: BONSAL AMERICAN, INC. 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-2781 Reissued 02/2017 This report is subject to renewal 02/2018. DIVISION: 09 00 00 FINISHES

More information

ANSI/APA PRS Standard for Performance-Rated Structural Insulated Panels in Wall Applications

ANSI/APA PRS Standard for Performance-Rated Structural Insulated Panels in Wall Applications ANSI/APA PRS-610.1 Standard for Performance-Rated Structural Insulated Panels in Wall Applications 2008 APA - The Engineered Wood Association Draft 2 January 2008 Copyright 2008 by APA 7011 South 19th

More information

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015.

ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. ICC-ES Evaluation Report www.icc-es.org (800) 423-6587 (562) 699-0543 ESR-1365 Reissued March 2014 This report is subject to renewal April 1, 2015. A Subsidiary of the International Code Council DIVISION:

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: SHAKERTOWN 1992, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: SIDING REPORT HOLDER: SHAKERTOWN 1992, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2386 Reissued 04/2016 This report is subject to renewal 04/2018. DIVISION: 07 00 00 THERMAL

More information

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM

SECTION SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM PART 1- GENERAL 1.1 SUMMARY A. Section Includes: SECTION 084523 - SLOPED TRANSLUCENT METAL SKYLIGHT SYSTEM 1. Flat factory prefabricated structural insulated translucent sandwich panels; with glazed endwalls.

More information

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS

April 18, 2018 PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS April 18, 2018 TO: PARTIES INTERESTED IN FIBER REINFORCED PLASTIC (FRP) MODULAR WALL SYSTEMS SUBJECT: Proposed Revisions to the Acceptance Criteria for Fiber Reinforced Plastic (FRP) Modular Wall Systems,

More information

PER See all Pei ES Listings at:

PER See all Pei ES Listings at: Pei Evaluation Service is an accredited ISO Standard 17065 Product Certifier, accredited by the IAS. This Product Evaluation Report represents a product that Pei ES has Evaluated and has a Follow-up Service

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: AMERICAN EAGLE MATERIALS, LLC

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: AMERICAN EAGLE MATERIALS, LLC 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2729 Reissued 04/2017 This report is subject to renewal 04/2019. DIVISION: 09 00

More information

Combustible Exterior Wall Cladding Systems: An ICC Perspective

Combustible Exterior Wall Cladding Systems: An ICC Perspective Combustible Exterior Wall Cladding Systems: An ICC Perspective The tragic Grenfell Tower fire in London brought extensive public focus on combustible exterior wall systems, often called cladding, prompting

More information

Alply CLASSIC WALL Architectural Insulated Panel Wall System

Alply CLASSIC WALL Architectural Insulated Panel Wall System SECTION 07 42 13 INSULATED METAL WALL PANELS ALPLY Insulated Panels Alply CLASSIC WALL Architectural Insulated Panel Wall System PART 1 / GENERAL 1.1 SYSTEM DESCRIPTION A. Smooth, non-embossed steel, insulated

More information

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS

DIVISION: WOOD, PLASTICS AND COMPOSITES SECTION: STRUCTURAL PANELS REPORT HOLDER: FOUR SEASONS SOLAR PRODUCTS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2445 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 06 00

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code LEGACY REPORT ER-3414 Reissued January 1, 2004 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: GENTEK BUILDING PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (00) 423-657 (562) 699-0543 www.icc-es.org ESR-1133 Reissued 11/2017 This report is subject to renewal 11/201. DIVISION: 07 00 00

More information

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS

June 1, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS June 1, 2009 TO: PARTIES INTERESTED IN EVALUATION REPORTS ON STRUCTURAL WOOD-BASED PRODUCTS USED AS STUDS SUBJECT: Proposed Revisions to the Acceptance Criteria for Wood-based Studs, Subject AC202-0609-R1

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: METL SPAN, A DIVISION OF NCI GROUP, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2218 Reissued 09/2017 This report is subject to renewal 09/2018. DIVISION: 07 00

More information

DIVISION: MASONRY SECTION: MANUFACTURED BRICK MASONRY SECTION: MANUFACTURED STONE MASONRY REPORT HOLDER:

DIVISION: MASONRY SECTION: MANUFACTURED BRICK MASONRY SECTION: MANUFACTURED STONE MASONRY REPORT HOLDER: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3685 Reissued 09/2017 This report is subject to renewal 09/2018. SECTION: 04 71 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: CITADEL ARCHITECTURAL PRODUCTS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1015 Reissued 04/2017 This report is subject to renewal 04/2019. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL ROOF PANELS SECTION: METAL WALL PANELS REPORT HOLDER: 0 Most idely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-687 (62) 699-043 www.icc-es.org ESR-199 Reissued 0/2017 This report is subject to renewal 0/2019. DIVISION: 07 00 00 THERMAL AND MOISTURE

More information

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018

Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018 Originally Issued: 12/12/2014 Revised: 12/29/2017 Valid Through: 12/29/2018 TK Products A Division of Sierra Corporation TK-HYDROMAX 2001 SB DAMPPROOF COATING, TK-HYDROMAX 2002 SB FOUNDATION WATERPROOF

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued January 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued January 1, 2000 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: METAL WALL PANELS REPORT HOLDER: FCP, INC. 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2937 Reissued 05/2016 This report is subject to renewal 05/2018. DIVISION: 07 00 00 THERMAL

More information

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS

June 22, 2009 PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS June 22, 2009 TO: SUBJECT: PARTIES INTERESTED IN EVALUATION REPORTS ON COMPOSITE COLD-FORMED LIGHT GAGE STEEL AND CONCRETE MASONRY LINTELS Acceptance Criteria for Composite Cold-formed Light Gage Steel

More information

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC.

DIVISION: FINISHES SECTION: PORTLAND CEMENT PLASTERING REPORT HOLDER: OMEGA PRODUCTS INTERNATIONAL, INC. 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 23-587 (52) 99-053 www.icc-es.org ESR-119 Reissued 11/2017 This report is subject to renewal 11/2018. DIVISION: 09 00 00 FINISHES

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: 3A COMPOSITES USA INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: COMPOSITE WALL PANELS REPORT HOLDER: 3A COMPOSITES USA INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1114 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 07 00

More information

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS

December 1, 2014 PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS December 1, 2014 TO: PARTIES INTERESTED IN STRUCTURAL WOOD-BASED PRODUCTS SUBJECT: Proposed Revision to the ICC-ES Acceptance Criteria for Structural Wood-Based Products, Subject AC47-1214-R2-2 (JF/PC)

More information

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS

April 1, 2015 PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS April 1, 2015 TO: PARTIES INTERESTED IN FLEXIBLE FLASHING MATERIALS SUBJECT: Proposed Revisions to the Acceptance Criteria for Flexible Flashing Materials, Subject AC148-0415-R1 (ST/YM) Dear Colleague:

More information

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS

February 1, 2016 PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS February 1, 2016 TO: PARTIES INTERESTED IN EXTERIOR ULTRA-HIGH PERFORMANCE CONCRETE THIN WALL CLADDING PANELS SUBJECT: Proposed Revisions to the Acceptance Criteria for Exterior Ultra-high Performance

More information

1. ICC ES AC51 Draft Changes, Masonry Veneer Manufacturers Association (MVMA) Comments, dated September 24, 2007, compiled by John Woestman.

1. ICC ES AC51 Draft Changes, Masonry Veneer Manufacturers Association (MVMA) Comments, dated September 24, 2007, compiled by John Woestman. #15 ICC EVALUATION SERVICE, INC. Evaluate P Inform P Protect To: From: ICC-ES Evaluation Committee Elyse Levy, S.E. Date: October 5, 2007 Subject: Proposed Revisions to the Acceptance Criteria for Precast

More information

ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 CCRR-0131

ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 CCRR-0131 ARCHITECTURAL TESTING, Inc. Code Compliance Research Report #0774 Subject to Renewal: 10/27/09 Issued: 10/27/08 Visit for current status Revised 11/5/08 Page 1 of 10 Solatube International, Inc 2210 Oak

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: ASSOCIATED MATERIALS, INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: ASSOCIATED MATERIALS, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1258 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 07 00

More information

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC

HCD DSA OSHPD 1 2 1/AC AC SS SS/CC CALIFORNIA BUILDING CODE MATRIX ADOPTION TABLE CHAPTER 25 GYPSUM BOARD AND PLASTER (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority

More information

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD

EXCEL Medical Waste - Equipment Installation Section SECTION GYPSUM BOARD SECTION 09 29 00 GYPSUM BOARD PART 1 - GENERAL 1.1 DESCRIPTION This section specifies installation and finishing of gypsum board. 1.2 RELATED WORK A. Installation of steel framing members for walls, partitions,

More information

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960

PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 STUC-O-FLEX PERM-FLEX ASSEMBLY DIRECT APPLICATION TO CEMENTITIOUS SUBSTRATES MANUFACTURERS SPECIFICATION / SECTION 09960 PART 1 - GENERAL 1.01 DESCRIPTION Provide all labor, materials and equipment necessary

More information

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code.

Legacy report on the 1997 Uniform Building Code, the 2000 International Building Code and the 2000 International Residential Code. LEGACY REPORT ER-2895 Reissued March 1, 2004 www.icc-es.org Business/Regional Office 5360 Workman Mill Road, Whittier, California 90601 (562) 699-0543 Regional Office 900 Montclair Road, Suite A, Birmingham,

More information

Product Guide Specification

Product Guide Specification April 2014 6840 SW 81 Terrace Miami, Florida 33143 Phone 305-666-6676 Fax 305-666-7675 Website www.trimstonepanels.com E-mail stoneworks@stoneworksofart.com Product Guide Specification Specifier Notes:

More information

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code

LEGACY REPORT ER ICC Evaluation Service, Inc. Reissued October 1, Legacy report on the 1997 Uniform Building Code LEGACY REPORT Reissued October 1, 2007 ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California 90601 # (562) 699-0543 Regional Office # 900 Montclair

More information

PRODUCT GUIDE SPECIFICATION

PRODUCT GUIDE SPECIFICATION PRODUCT GUIDE SPECIFICATION Specifier Notes: This product guide specification is written according to the Construction Specifications Institute (CSI) 3-Part Format, including MasterFormat, SectionFormat,

More information

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal March 1, 2015

ICC-ES Evaluation Report Reissued March 2014 This report is subject to renewal March 1, 2015 ICC-ES Evaluation Report ESR-1694 Reissued March 2014 This report is subject to renewal March 1, 201 www.icc-es.org (800) 423-687 (62) 699-043 A Subsidiary of the International Code Council DIVISION: 07

More information

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation

Trusted ICC ES DIVISION: ATLANTA, CGF PRO, ENERGYS. Look. Conformity! Evaluation. ICC-ES Evaluation 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.orgg DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21 00 THERMAL INSULATION

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: FIBER-CEMENT SIDING REPORT HOLDER: EQUITONE 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3910 Issued 04/2017 This report is subject to renewal 04/2018. DIVISION: 07 00 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KP BUILDING PRODUCTS

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: KP BUILDING PRODUCTS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1517 Reissued 11/2016 This report is subject to renewal 11/2018. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: PLASTIC SIDING REPORT HOLDER: CERTAINTEED CORPORATION 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3085 Reissued 08/2017 This report is subject to renewal 08/2019. DIVISION: 07 00

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) LLC 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 3210 Valid: 03/15 to 03/16 DIVISION: 07 00 00 THERMAL AND MOISTURE PROTECTION SECTION: 07 21

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC.

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION REPORT HOLDER: DEMILEC (USA) INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4073 Issued 08/2017 This report is subject to renewal 08/2018. DIVISION: 07 00 00

More information

Magnum Board Section Digicon Information Inc. Page 1

Magnum Board Section Digicon Information Inc. Page 1 Digicon Information Inc. Page 1 This section includes sheathing for exterior walls for use in a potentially damp or wet exterior cladding environment. This sheathing section forms an exterior flat plane

More information

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year. Reissued November, 008 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office 60 Workman Mill Road, Whittier, California 9060 (6) 699-0

More information

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide.

The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice Guide applies to each section of the Guide. Note: This document has been divided into several sections in order to suit the limitations of the website. The Disclaimer located on the reverse side of the title page of the OAA Rain Penetration Practice

More information

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION

MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION STUC-O-FLEX - ELASTOMERIC ACRYLIC FINISH APPLICATION TO PORTLAND CEMENT PLASTER / CONCRETE RENDER MANUFACTURER S (SHORT FORM) SPECIFICATION / SECTION 09220-09 24 00 PART 1-GENERAL SCOPE: Manufacturer's

More information

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION

SECTION SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION SECTION 093000 - SHEET MEMBRANE WATERPROOFING AND CRACK ISOLATION PART 1 - GENERAL This specification includes the sheet membrane used as waterproofing, vapor retarder, and crack isolation in conjunction

More information

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year.

ESR ICC Evaluation Service, Inc. Reissued January 1, 2008 This report is subject to re-examination in one year. ESR-1967 Reissued January 1, 2008 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER:

DIVISION: THERMAL AND MOISTURE PROTECTION SECTION: THERMAL INSULATION SECTION: AIR BARRIERS REPORT HOLDER: 0 ICC ES Report ICC ES (800) 423 6587 (562) 699 0543 www.icc es.org 000 Most Widely Accepted and Trusted ESR 2717 Reissued 07/2015 This report is subject to renewal 07/2017. DIVISION: 07 00 00 THERMAL

More information

REPORT HOLDER: JAMES HARDIE BUILDING PRODUCTS, INC ELM AVENUE FONTANA, CALIFORNIA EVALUATION SUBJECT:

REPORT HOLDER: JAMES HARDIE BUILDING PRODUCTS, INC ELM AVENUE FONTANA, CALIFORNIA EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1844 Reissued 11/2017 This report is subject to renewal 11/2019. DIVISION: 06 00

More information

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS

June 1, 2012 PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS June 1, 2012 TO: PARTIES INTERESTED IN COLD-FORMED STEEL FRAMING MEMBERS SUBJECT: Proposed Revisions to the Acceptance Criteria for Cold-formed Steel Framing Members, Subject AC46-0612-R1 (WM/DM) Dear

More information

Originally Issued: 02/20/2015 Revised: 06/07/2017 Valid Through: 02/28/2018

Originally Issued: 02/20/2015 Revised: 06/07/2017 Valid Through: 02/28/2018 SACRAMENTO STUCCO CO., INC., Western 1-Kote Exterior Cementitious One-Coat Wall Coating System ADDITIONAL COMPANY NAMES AND PRODUCT NAMES: ASH GROVE PACKAGING, Ash Grove One-Coat Stucco System DRYVIT SYSTEMS,

More information