1 LEAD-BASED PAINT INSPECTION REPORT CITY HALL 230 WEST STEPHENSON STREET FREEPORT, ILLINOIS Prepared For: 201 PRAIRIE STREET, SUITE 208 ROCKFORD, ILLINOIS Inspector and Report Prepared By: INNERSPACE ENVIRONMENTAL ASSESSMENT, INC. P. O. Box 231 Elburn, Illinois Phone: (630) Fax: (630) James W. Sundberg Illinois Department of Public Health Licensed Risk Assessment/Inspector License # 1743 Signature 7/8/2013 Report Date

2 INTRODUCTION This is a Lead-Based Paint (LBP) Inspection Report of located at 230 West Stephenson Street, Freeport, Illinois. This was a comprehensive inspection of the building. Included in the inspection were the Interior and Exterior Components in and around the all additions of the Building. This inspection was conducted on July 1, The building in this inspection consists of one original building. Much of the interior buildings had, at the time of this inspection, been renovated over the years. Painted components were the focus of this inspection. All painted, varnished, and shellacked surfaces were inspected for lead based paint (LBP). This was a fairly comprehensive LBP Inspection, as defined by the United States Department of Housing and Urban Development (HUD). GOVERNING PROTOCOLS The protocol used for this inspection is based on the practices and procedures in the United States Department of Housing and Urban Development s (HUD) Guidelines for the Evaluation and Control of Lead-Based Paint Hazards in Housing, 2012 Revision (HUD Guidelines) including the 1997 Chapter 7 revisions, the United States Environmental Protection Agency s (USEPA) 40 CFR Part 745 (Lead; Identification of Dangerous Levels of Lead; Final Rule; January 5, 2001). HUD publishes the only known protocols for Lead Based Paint Inspections. The HUD Guidelines and 40 CFR Part 745 set a regulatory level of 1.0 mg/cm 2 for lead in paint. This inspection was conducted using this level as the definition of Lead Based Paint (LBP). Any XRF result that is equal to or greater than 1.0 mg/cm 2 should be considered by State and Federal law to be POSITIVE for LBP. INSPECTION METHODOLOGY Areas identified by IEA s client were inspected for lead paint using X-Ray Fluorescence Analyzer (XRF) instrumentation. All suspect materials that were painted, varnished, shellacked, stained, or otherwise coated within IEA s scope of work were inspected. XRF Operational Requirements The following requirements were followed for all XRF testing performed during this inspection. Safety Considerations XRF instruments were only operated by individuals who have successfully completed the Manufacturer s Training requirements for the LPA-1 Lead Paint Analyzer. Care was taken not to expose occupants or workers to measurable amounts of radiation during the inspection process.

3 Instrument Selection The instruments used to perform the inspection were the LPA-1 XRF lead based paint spectrum analyzers. The instruments are manufactured by Radiation Monitoring Devices, LLC of Watertown, MA, and have a HUD approved Performance Characteristic Sheet (PCS). The LPA-1 PCS can be found in Appendix G. The LPA-1 method of measurement is based on spectrometric analysis of lead K-shell X-ray fluorescence within a controlled depth of measurement. The controlled depth concept restricts the penetration of the K-shell X-rays into the substrate so that the system cannot be mislead by the presence of lead pipes or other objects located deep in a wall. Instrument Calibration There are three modes of measurements in the instruments, Standard Mode, Quick Mode, and Time Corrected mode. Calibration checks are taken using the Time Corrected mode of operation. This mode automatically adjusts the time of the reading depending on the age of the source. (The older the source, the longer the reading.) Three calibration checks are taken using a National Institute of Standards and Testing (NIST) 1.02 mg/cm 2 standard on a wood block. These checks are taken at the beginning of each day (or job), at least every four hours during the ongoing inspection, and at the end of each day (or job). Calibrations performed during this inspection indicate the XRF instruments were operating within the PCS specifications. Documentation of all calibration checks can be found throughout this report. Substrate Correction The inspection measurements are taken in the Quick Mode. In the Quick Mode, the analyzer seeks the shortest period of time to assure a definitive measurement with a 95% confidence. The LPA-1 analyzer concludes a measurement once this level of confidence is achieved, typically between 4 and 8 seconds depending on the regulatory level, which is set in the machine before the inspection begins. The PCS indicates that no substrate correction is required when the instrument is operated in the Quick mode. Interference The LPA-1 XRF is not affected by spectral interference s. Flat surfaces were tested whenever possible. All measurements were reported on the raw data forms and are provided in the report. XRF Measurement Requirements The buildings were considered, in the judgement of the Lead Inspector, to be three separate testing buildings. Each of the support structures (for the red and purple lines) was separated into their own testing areas. Identified areas by IEA s client were tested to identify the presence of lead in the surface coating. These areas included all accessible exterior and interior areas. Each of the areas was divided into their own report. Overall, there were seven (7) individual reports from the inspection. A list of each component, broken down by area, is provided in the Distribution Report (Appendix C). Please note, there are 7 Distribution Reports for the separate areas.

4 Inconclusive XRF Results According to the PCS, the LPA-1 does not have an inconclusive range on any of the six discussed substrates (brick, concrete, drywall, metal, plaster, and wood). However, the manufacturer of this device (RMD) states that any reading that is at the threshold for lead (1.0 mg/cm 2 ) is inconclusive. An inconclusive result means that the amount of lead present in the paint film, is too near to the regulatory level to determine, with 95% confidence level, that the measured concentration of lead is above the regulatory level (POSITIVE) or below the regulatory level (NEGATIVE) for LBP. Any reading at this level in the final report should be assumed as Positive for LBP. Quality Control Measurements and Samples For XRF measurements, a minimum of 1% of the shots were repeated for quality control purposes. The repeat shots provide a measure of the precision or the XRF instrument. All of the repeated readings were within statistical limits of 95% probability of the original shot. Document Review No documentation review was conducted as part of this LBP inspection. In the absence of construction history documentation, the lead paint inspector combined components of similar construction and painting histories together into homogeneous structures. Documentation XRF Scope Sheets were thoroughly completed, indicating the date of the inspection, name of inspector, the structure/unit/room name, sample location, and numerical XRF results of each testing combination. Copies of these sheets are located in the Inspector s file. The results of the inspection are contained in a series of reports. The format of each report complies with the HUD Guidelines, Chapter 7, and contains information about testing location, testing combination, paint condition, result levels, and XRF operation mode. Each report has its own unique job number. The job number is a time stamp of when that particular job was started, and which XRF instrument was used to perform the inspection. For this building, the job corresponds to the inspector and the rooms he inspected. Two (2) inspectors and one (1) XRF conducted this inspection.

5 LEAD BASED PAINT REPORTS At the completion of each job, a series of reports are generated that contain all of the required information from the inspection. The reports are included in the Appendix and are as follows: Summary Report This report indicates all the results that were at or above the regulatory level that was set in the instrument. In this inspection, the regulatory level was set at 1.0 mg/cm 2. The XRF Summary Report is included in Appendix A. Detailed Report The Detailed Report lists every reading taken in each room equivalent inspected. This report is generated per XRF job. The XRF Detailed Report is included in Appendix B. Distribution Report The Distribution Report provides a listing of every testing combination with the total number and percent of Positive, Negative, and Inconclusive results for each testing combination. This report is also generated per XRF job. The XRF Distribution Report is included in Appendix C. Definitions Room Equivalent as defined in HUD Chapter 7, may be a living room, a kitchen, a hallway, a bathroom, a stairway, etc. A closet is considered to be Part of a room, not a separate room equivalent. Component is a structure such as a window casing, a door, or a wall etc. that is within a Room Equivalent. A window system, consists of two components; the window sill and the window apron. Each of these two components must be tested separately if they are present. The Door System consists for the components of the Door Panel, and the Door Casing/Jamb System. The door casing system consists of the door casing, header, and door jamb. The door panel and the door casing/jamb system must be tested separately. Substrate is the material upon which the paint or other coating is applied to. There are six basic substrates. They are Brick, Concrete, Drywall, Metal, Plaster, and Wood. Testing Combination is composed of a Room Equivalent, a Component, and a Substrate. Color is no longer considered part of a testing combination under HUD 1997 Revised Guidelines. However, where color may have been considered by the inspector to be of concern, that testing combination was tested. Only one of each testing combination within a room equivalent was required to be tested. However, at least one test is required on each wall within each room equivalent. All testing combinations within each room equivalent were tested. All four walls within each room equivalent were tested.

6 Spatial Orientation Each wall within a room equivalent is labeled A, B, C, or D in the reports and on the room diagrams. Throughout the all of the Inspection and Inspection Reports, the A wall is always facing to the South (Street Address). Walls B, C, and D continue around the particular room in a clockwise motion. In this report, Wall B is to the West, Wall C is to the North, and Wall D is to the East.

7 FINDINGS There were a total of 628 XRF readings taken throughout the areas identified by IEA s client to be inspected for Lead Based Paint in and around the Building. The Inspector took an additional 12 readings while calibrating their XRF. Table I summarizes all components that were identified with lead at or above the regulatory level for lead. A detailed list of components that tested positive for lead in specific rooms can be found in the Summary Report (Appendix A) in this report. RESPONSE ACTION(S) Interim Controls and Abatement Hazard Control Options Each component identified with lead can managed in many different ways. The range of fixes can be minimal like paint film stabilization to complete removal of the component. The Property Owner, ultimately, must make the decision as to what to do to Components that contain Lead Based Paint. The decisions might be impacted by variables such as Federal Grant Money used and/or End Result for the Project. If the end result of the Project will allow children to occupy the space, IEA recommends that wherever possible, LBP Components be removed from the Building. Work performed on these components should also be performed by Illinois Department of Public Health (IDPH) Licensed Lead Abatement Contractors. Work should be performed in accordance with the HUD Guidelines for the Evaluation and Control of Lead Based Paint Hazards in Housing describe the process. Detailed guidance can be provided by IEA as the Project moves forward. Rough cost estimates for minimal (I for Interim Controls) and ultimate (A for Abatement) control measures are included in Table I of this report. Demolition of the building or parts of the building is not included in these rough cost estimates. Precise cost estimates should be obtained from IDPH-Licensed Lead Based Paint Abatement Contractor. The costs should include labor, materials, worker protection, site containment and cleanup. Clearance testing should be performed at the conclusion of any lead task. Acceptable results should be obtained before residents reoccupy that space. Based on the work and amount of money being spent on the project, abatement options may be the only hazard control options selected. Refer to subpart J of 24 CFR Part 35 for details. Chapter 11 gives detailed guidance on Interim Controls. Chapter 12 describes all Abatement approaches except Encapsulation.

8 TABLE I GENERAL LBP COMPONENTS WITH QUANTITIES AND ROUGH COST ESTIMATES FOR CORRECTIVE ACTION (S) LOCATION/ ROOM Exterior Original Building Interior 1 Foyer (Main Stairs) Interior 1 Janitor s Closet Interior 1 West Entry and Mezzanine South Stairs Interior Water Reception and Offices and Back Storage Interior Water Back Storage and Toilet Interior Mezzanine, All Rooms Interior Mezz North Stair and 1 West Stair Interior Mezzanine North Stair COMPONENT SUBSTRATE ROUGH QUANTITIES Older Door Casings/Jamb Transom Casings, Wall C Walls and Ceilings Wood Wood Plaster 2 Units 600 ft 2 ROUGH COST ESTIMATES FOR CORRECTIVE ACTION Interim Controls $ 150 $ 1,800 Abatement $ 1,500 $ 3,600 5,000 ft 2 $ 15,000 $ 20,000 Walls A and D Brick 150 ft 2 $ 450 $ 750 Walls and Ceiling Walls and Ceiling Support Columns Shared Door Panel Plaster 5,000 ft 2 $ 15,000 $ 25,000 Plaster Metal Wood 10,000 ft ft 2 1 Unit $ 30,000 $ 900 $ 50,000 $ 1,500 $ 100 $ 200 Ceiling Plaster 2,000 ft 2 $ 6,000 $ 12,000 Stair Treads and Risers Wall and Ceiling Metal 1,000 ft 2 $ 3,000 $ 6,000 Concrete (Plaster) 5,000 ft 2 $ 15,000 $ 30,000

9 TABLE I, continued GENERAL LBP COMPONENTS WITH QUANTITIES AND ROUGH COST ESTIMATES FOR CORRECTIVE ACTION (S) LOCATION/ ROOM Interior 2 nd Floor (Ctr Hall, S Hall, Treasurer, SE Toilets, Counci, Finance, Accountant, Housing) Interior NW Basement Interior Basement Vault Interior Basement SE Stair, Elevator Room, and Shooting Area Interior Basement Shooting Area Interior Township Large Office Interior Township Storage and Meter Rooms COMPONENT SUBSTRATE ROUGH QUANTITIES Walls and Ceiling Door Components ROUGH COST ESTIMATES FOR CORRECTIVE ACTION Interim Controls Abatement Plaster 50,000 ft 2 $ 150,000 $ 300,000 Wood 1 Unit $ 150 $ 500 Door Casings Metal 20 ft 2 $ 60 $ 300 Walls Brick 600 ft 2 $ 1,800 $ 9,000 Door Casings Wood 20 ft 2 $ 60 $ 300 Sewer Pipe Metal 200 ft 2 $ 600 $ 3,000 Walls Old Door Components Brick Wood 2,000 ft Units $ 6,000 $ 300 $ 30,000 $ 750

10 CERTIFICATION The inspection was conducted by an experienced lead paint inspector/risk assessor and is licensed as such by the Illinois Department of Public Health. The work performed complies with HUD sampling protocols, state, local and other specified regulatory requirements. James W. Sundberg Licensed Lead Risk Assessor Illinois 1743 July 8, 2013 Date

11 APPENDICES

12 APPENDIX A Summary Report

13

14

15

16 APPENDIX B Detailed Report

17

18

19

20

21

22

23

24

25

26

27

28

29

30 APPENDIX C Distribution Report

31

32 APPENDIX D Inspector Licensing

33

34 APPENDIX E XRF Performance Characteristic Sheets

35

36

37

38

39 APPENDIX F Floor Layouts

40

41

42

43

LEAD-BASED PAINT INSPECTION

LEAD-BASED PAINT INSPECTION LEAD-BASED PAINT INSPECTION Performed For: WILL COUNTY 302 N. Chicago Street Joliet, IL 60432 Project Location: WILL COUNTY STATE'S ATTORNEY BUILDING 121 N. Chicago Street Joliet, IL 60432 May 8, 2017

More information

LEAD BASED PAINT INSPECTION

LEAD BASED PAINT INSPECTION LEAD BASED PAINT INSPECTION 251 South Seventh Street, Ann Arbor, Michigan 48103 PREPARED FOR Norstar Development USA, LP 733 Broadway Albany, NY 12207 ON BEHALF OF The Ann Arbor Housing Commission 727

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2270

More information

Learn Charter School Excel Campus

Learn Charter School Excel Campus ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Asbestos-Containing Material and Hazardous Material Survey Summary Report

Asbestos-Containing Material and Hazardous Material Survey Summary Report Asbestos-Containing Material and Hazardous Material Survey Summary Report Site: Haas Park Fieldhouse PS1757 2404 North Washtenaw Street Chicago, Illinois 60647 Survey Date: January 15, 2010 PBCC Project

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-381X

More information

LEAD-BASED PAINT PRESENT

LEAD-BASED PAINT PRESENT June 5, 2009 Mr. A.L. 26 ##th Street ###, NY 11102 Via email: LEAD-BASED PAINT PRESENT Door Components Enclosed you will find the results of the Lead-Based Paint Inspection (utilizing an X-Ray Fluorescence

More information

PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278

PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278 PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278 PREPARED FOR: Mr. Roberto Aguirre City of San Francisco DPW, SAR, BCM 1680 Mission Street San Francisco, California PREPARED

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-3013

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Lead Risk Assessment Report For the property at: 2933 Del Marr Circle Colorado Springs, CO 80910

Lead Risk Assessment Report For the property at: 2933 Del Marr Circle Colorado Springs, CO 80910 Lead Risk Assessment Report For the property at: 2933 Del Marr Circle Colorado Springs, CO 80910 Property Owner: Barnes McCammon 2933 Del Marr Circle, Colorado Springs, CO 80910 (719) 359-6652 Year built:

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Asbestos/Lead Paint Survey

Asbestos/Lead Paint Survey Asbestos/ Survey At: Camp Lejeune Bldg. 500 Repair Indoor Physical Fitness Center Prepared for: The Walker Group Architecture Inc. PO Box 541 New Bern, NC 28563 PEI Project No.: Walker Group Project No.:

More information

April 12, 2011 (revised July 19, 2011) Project Number

April 12, 2011 (revised July 19, 2011) Project Number Environmental Consultants 1360 Truxtun Avenue 843 746-8525 and Contractors Suite 100 FAX 843 746-8865 North Charleston, SC 29405 www.scsengineers.com April 12, 2011 (revised July 19, 2011) Project Number

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-0027

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2059

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2059

More information

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION NARRATIVE REPORT 1.0 BUILDING INFORMATION Bentson Bunker Fieldhouse was originally constructed in 1931; the building has had several renovations, notably, a 1976-1980 multi-phase renovation throughout

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free / / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary

More information

Lead Based Paint Policy

Lead Based Paint Policy Lead Based Paint Policy 1. Guidance for the removal or maintenance of lead-based paint has undergone changes that affect the painting industry. The U.S. Department of Housing and Urban Development (HUD)

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2207

More information

LEAD-BASED PAINT INVESTIGATION REPORT

LEAD-BASED PAINT INVESTIGATION REPORT LEAD-BASED PAINT INVESTIGATION REPORT US-21 (SEA ISLAND PARKWAY) BRIDGE OVER HARBOR RIVER BEAUFORT COUNTY, SC SCDOT BRIDGE #072002100200 SCDOT PROJECT #P026862 PREPARED FOR: PREPARED BY: F&ME Consultants

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

EPA s Lead Program Rule At-A-Glance

EPA s Lead Program Rule At-A-Glance EPA s Lead Program Rule At-A-Glance FLOW CHART 1: Do the Requirements Apply to the Renovation? If you will be getting paid to do work that disturbs painted surfaces in a pre-1978 home, apartment building,

More information

BUILDING PERMIT INFORMATION GUIDE FOR THE HOMEOWNER

BUILDING PERMIT INFORMATION GUIDE FOR THE HOMEOWNER THE CORPORATION OF THE MUNICIPALITY OF SOUTH HURON 322 Main Street South, P.O. Box 759, Exeter, Ontario N0M 1S6 PHONE: (519) 235-0310 FAX: (519) 235-3304 TOLL FREE: 1-877-204-0747 WEBSITE: www.southhuron.ca

More information

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR INSPECTORS. For

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR INSPECTORS. For ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR CITY OF ROCK HILL 150 Johnston Street Rock Hill, SC 29731 (803) 448-3351 LOCATION Vacant Building 302 Sidney Street Rock Hill, South Carolina INSPECTION

More information

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS

HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS St. Louis County Department of Public Works Division of Code Enforcement HOUSE REPAIRS & RENOVATIONS BUILDING PERMIT REQUIREMENTS This guide is intended to provide the homeowner or contractor with the

More information

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here

RESIDENTIAL MOLD ASSESSMENT. Final Report. Your Address Here 2847 Barnard Street San Diego California 92110 Phone 619.501.0185 Mobile 619.203.9774 Fax 619.501.9843 hoveyenv@cox.net RESIDENTIAL MOLD ASSESSMENT Final Report Your Address Here September 1, 2003 Prepared

More information

LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT. for

LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT. for LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT for Michigan State University Physical Plant Division Engineering and Architectural Services Department

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

Health Chapter STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES ADMINISTRATIVE CODE

Health Chapter STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES ADMINISTRATIVE CODE STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES ADMINISTRATIVE CODE CHAPTER 420-3-27 LEAD HAZARD REDUCTION CONTRACTOR CERTIFICATION TABLE OF CONTENTS 420-3-27-.01 Purpose 420-3-27-.02 Applicability

More information

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018)

BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) BASEMENT FINISH PERMIT AND BUILDING CODE REQUIREMENTS (REVISED 3/6/2018) PERMIT SUBMITTAL CHECKLIST: Signed and completed Building Permit application form. A separate Electrical permit is required from

More information

CITY OF CRANSTON RESIDENTIAL PERMIT PROCEDURE BASEMENT RENOVATION

CITY OF CRANSTON RESIDENTIAL PERMIT PROCEDURE BASEMENT RENOVATION CITY OF CRANSTON RESIDENTIAL PERMIT PROCEDURE BASEMENT RENOVATION WE WILL NOT ACCEPT ANY PLANS OR PAPERWORK TO START THE REVIEW PROCESS UNTIL ALL ITEMS BELOW ARE SUBMITTED TO US AT THE SAME TIME. PLANS

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

APPROACH FOR IMPLEMENTION OF HUD S LEAD SAFE HOUSING RULE REGULATIONS (24 CFR Part 35, Subpart H, )

APPROACH FOR IMPLEMENTION OF HUD S LEAD SAFE HOUSING RULE REGULATIONS (24 CFR Part 35, Subpart H, ) January 16, 2008 Mississippi Development Authority Homeowner Elevation Grant Program and Small Rental Assistance Program in Hancock, Harrison, Jackson, and Pearl River Counties, Mississippi APPROACH FOR

More information

Final Asbestos Inspection Report and Lead Paint Survey

Final Asbestos Inspection Report and Lead Paint Survey Final Asbestos Inspection Report and Lead Paint Survey Proposed Retail Takeover, Store #3178-00 2444 East Powell Boulevard Gresham, Multnomah County, Oregon October 7, 2011 Terracon Project No. 82117017

More information

Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624

Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624 Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624 Prepared for: City of Anderson Community Development Department 601 South Main Street Anderson,

More information

Subject: Lucretia Mott School No. 3 Rehabilitation. Figure 1 Figure 2 Figure 3

Subject: Lucretia Mott School No. 3 Rehabilitation. Figure 1 Figure 2 Figure 3 MEMORANDUM To: Ashley Rosenthal Payne, Indianapolis Historic Preservation Commission Adrienne Schmetzer, Indiana Housing and Community Development Authority Architecture Preservation Interior Design Landscape

More information

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS

BASEMENT FINISH CONSTRUCTION PLANS REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS BASEMENT FINISH REFERENCE: 2015 INTERNATIONAL RESIDENTIAL CODE. PERMITS A construction permit is required. A homeowner may perform the construction work on his own property where he resides, without a

More information

Common Household Contaminants: The Hazards and the Laws

Common Household Contaminants: The Hazards and the Laws The National Center for Healthy Housing (NCHH) developed this summary to serve as a short guide for health and housing professionals on common household contaminants. It is not comprehensive. As a guide,

More information

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22 Page 1 of 22 Asbestos Survey Project Summary Pursuant to your request; Environmental, Inc., has performed an Asbestos Building Survey on 8/13/2014 and limited to the above referenced location. The Interior/Exterior/Roof

More information

Asbestos Survey Report

Asbestos Survey Report Asbestos Survey Report Downtown Duluth Old City Hall Block Buildings for renovation 3087 Main Street, 3097 Main Street, New Dawn Theater, 3530 W. Lawrenceville Street, Old City Hall/Church Duluth, Georgia

More information

Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624

Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624 Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624 Prepared for: City of Anderson Community Development Department 601 South Main Street Anderson,

More information

REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES

REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES REQUIREMENTS FOR SUBSTANTIALLY DAMAGED AND SUBSTANTIALLY IMPROVED STRUCTURES If your home or business incurred damage, the engineering department, in conjunction with the Flood Mitigation Officer, will

More information

CERTIFICATE OF INSPECTION

CERTIFICATE OF INSPECTION CERTIFICATE OF INSPECTION Residential Certificate of Inspection (CI) for all Sales and Rentals Please Note the following Important Information: PLEASE SEE ATTACHED FEE SCHEDULE CHANGES. PLEASE SEE ATTACHED

More information

STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES CHAPTER LEAD HAZARD REDUCTION CONTRACTOR CERTIFICATION TABLE OF CONTENTS

STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES CHAPTER LEAD HAZARD REDUCTION CONTRACTOR CERTIFICATION TABLE OF CONTENTS STATE BOARD OF HEALTH BUREAU OF ENVIRONMENTAL SERVICES CHAPTER 420-3-27 LEAD HAZARD REDUCTION CONTRACTOR CERTIFICATION TABLE OF CONTENTS 420-3-27-.01 Purpose 420-3-27-.02 Applicability 420-3-27-.03 Definitions

More information

Rebuilding your Home after the storm? Adding on, renovating, or remodeling your home? Here's information YOU need to know about the 50% Rule.

Rebuilding your Home after the storm? Adding on, renovating, or remodeling your home? Here's information YOU need to know about the 50% Rule. FEMA 50% RULE - SUBSTANTIAL IMPROVEMENT SUBSTANTIAL IMPROVEMENT/DAMAGE Z101-0410 NOTICE TO PROPERTY OWNERS Rebuilding your Home after the storm? Adding on, renovating, or remodeling your home? Here's information

More information

Building & Fire Appeals Board

Building & Fire Appeals Board Building & Fire Appeals Board Date: March 10, 2016 Time: 3:30 p.m. - 5:00 p.m. Location: St Etienne Room City of Des Moines Armory Building 602 Robert D. Ray Drive Des Moines, Iowa 50309-1881 Summersfield

More information

Statement of the. National Lumber and Building Material Dealers Association. Review of the 2008 Lead Renovation, Repair and Painting Program;

Statement of the. National Lumber and Building Material Dealers Association. Review of the 2008 Lead Renovation, Repair and Painting Program; Statement of the National Lumber and Building Material Dealers Association on Review of the 2008 Lead Renovation, Repair and Painting Program; (EPA HQ OPPT 2016 0126) September 7, 2016 2025 M Street, NW,

More information

TSI SAMPLE MANAGEMENT PLANNER INITIAL. Training Services International, Inc. Qualifications & Functions

TSI SAMPLE MANAGEMENT PLANNER INITIAL. Training Services International, Inc. Qualifications & Functions MANAGEMENT PLANNER INITIAL Asbestos Training Course Federal Edition Training Services International www.training.com What management planning qualifications exist? How do I become certified to perform

More information

Doors, Windows, Stairs & Fireplaces Doors Doors Outdoor Entry Outdoor Entry Doors Doors Outdoor Entry Outdoor Entry

Doors, Windows, Stairs & Fireplaces Doors Doors Outdoor Entry Outdoor Entry Doors Doors Outdoor Entry Outdoor Entry Doors, Windows, Stairs & Fireplaces Doors Outdoor Entry 36 minimum entry Main/guest entrance open to social area Easy use lever handles Doors Outdoor Entry Weather resistant surface Solid wood or foam

More information

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard.

Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. City of Gibraltar Pre-Sale Inspection Report Checklist FLATWORK: Repair or replace section of driveway, approach, or sidewalk that are a trip hazard. EXTERIOR PROPERTY: Fences/Sheds/Retaining walls: Repair,

More information

Commercial Remodel Permit

Commercial Remodel Permit Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each

More information

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up

TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM Form 15 Work Write-Up Owner-Builder Applicant Owner-Builder Co-Applicant Physical Address: City,

More information

November 12, Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California

November 12, Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California November 12, 2014 Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California 95993-2240 RE: Pre-Renovation Asbestos Survey Report 5862 Rupert Avenue, Marysville, California

More information

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY:

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: PROJECT NO. 1197 REPORT TO CITY OF STRATFORD ON ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: 1099 KINGSTON ROAD, SUITE 260 PICKERING, ONTARIO L1V 1B5 Tel: (416) 410-4333

More information

Lead Paint Hazard Assessment

Lead Paint Hazard Assessment Lead Paint Hazard Assessment Hayhurst Elementary School B-Classrooms 14 and 15 5037 SW Iowa Street, Portland, OR Prepared for: Portland Public Schools 501 N Dixon Street Portland, Oregon 97227 September

More information

LEAD-BASED PAINT INSPECTION AND RISK ASSESSMENT REPORT. 44 Moss Highland Park, Michigan. Prepared For:

LEAD-BASED PAINT INSPECTION AND RISK ASSESSMENT REPORT. 44 Moss Highland Park, Michigan. Prepared For: Tri-Tech Building Hygiene Services LEAD-BASED PAINT INSPECTION AND RISK ASSESSMENT REPORT 44 Moss Highland Park, Michigan Prepared For: Ms. Charlene Turner Johnson Highland Park Homeownership Collaborative

More information

HQS Inspection Guidebook

HQS Inspection Guidebook Chicago Housing Authority Housing Choice Voucher Program HQS Inspection Guidebook September 2017 www.thecha.org/hcv Housing Choice Voucher Program HQS Inspection Guidebook Version # Efective Date 1 March

More information

SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT

SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT Prepared For: TALLEY & SMITH ARCHITECTURE, INC. 409 EAST MARION STREET SHELBY, NORTH CAROLINA 28150 Regarding: DELIVERY ORDER NO. 0051 FY 15 DEMOLISH FACILITIES,

More information

2012 IRC Sections R303 R310 Building Planning II

2012 IRC Sections R303 R310 Building Planning II Study Session 3 2012 IRC Sections R303 R310 Building Planning II OBJECTIVE: To develop an understanding of the health and safety criteria of the code, including light and ventilation; minimum room areas

More information

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS

More information

1116 Willow Pass Court DESTRUCTIVE TESTING Concord, CA SFUSD PROJECT NO SAN FRANCISCO UNIFIED SCHOOL DISTRICT

1116 Willow Pass Court DESTRUCTIVE TESTING Concord, CA SFUSD PROJECT NO SAN FRANCISCO UNIFIED SCHOOL DISTRICT SUMMARY OF HAZARDOUS MATERIALS WORK DESTRUCTIVE TESTING 1.01 GENERAL A. The San Francisco Unified School District (SFUSD) is soliciting proposals for conducting asbestos related work to support Destructive

More information

ASBESTOS INSPECTION REPORT

ASBESTOS INSPECTION REPORT ASBESTOS INSPECTION REPORT FOR SPARTANBURG COUNTY P.O. Box 5666 Spartanburg, South Carolina 29304 LOCATION 904 Beverly Drive Spartanburg, South Carolina INSPECTION DATE: April 5, 2017 REPORT DATE: April

More information

July 13, 2011 TTL Project No NESHAP Asbestos and Limited Hazardous Materials Survey Report 500 North Congress Street Ypsilanti, Michigan

July 13, 2011 TTL Project No NESHAP Asbestos and Limited Hazardous Materials Survey Report 500 North Congress Street Ypsilanti, Michigan July 13, 2011 TTL Project No. 7615.02 Ms. Paula Boase Downriver Community Conference Brownfield Consortium 15100 Northline Road Southgate, Michigan 48195 Dear Ms. Boase: NESHAP Asbestos and Limited Hazardous

More information

Limited Asbestos Demolition Survey

Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Former Fire Station Facility 25 to 45 S. Orlando Avenue Cocoa Beach, Florida Client: City of Cocoa Beach Public Works Department 1600

More information

Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina

Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina Prepared for: Northside Development Group 410 Magnolia Street Spartanburg, South Carolina Prepared by: Apex Environmental

More information

Applying for Permits to build a new house in Linn County

Applying for Permits to build a new house in Linn County Planning & Development Linn County, Iowa Building Division Linn County Building Code Residential Guidelines Single Family Dwellings Page 1 of 4 Applying for Permits to build a new house in Linn County

More information

THE RESTORE LOUISIANA REIMBURSEMENT ESTIMATE

THE RESTORE LOUISIANA REIMBURSEMENT ESTIMATE THE RESTORE LOUISIANA REIMBURSEMENT ESTIMATE Reimbursement estimates are component by component assessments of the value of completed repairs. They are produced through the use of Xactimate assessment

More information

Budget Estimate Basic Tenant Improvement

Budget Estimate Basic Tenant Improvement Building work rules, conditions and insurance: 1. Review the work rules. If they are not available no budget should be provided. 2. Hours available for construction 3. Insurance requirements 4. Entities

More information

Basement Renovation Guide For Residential Dwellings

Basement Renovation Guide For Residential Dwellings 1 Development Services Department Building Permit & Inspection Services Basement Renovation Guide For Residential Dwellings This document is a guide for home owners and does not cover all possible conditions.

More information

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit:

TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION Ext. 395 Needed to Obtain Permit: TOWN OF ROTTERDAM RESIDENTIAL BUILDING PERMIT APPLICATION 355-7575 Ext. 395 Needed to Obtain Permit: 1. Building Permit Application, and/or residential plumbing permit application, as applicable, to be

More information

LASALLE - BACKUS EDUCATION CAMPUS

LASALLE - BACKUS EDUCATION CAMPUS INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements

CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT. Submittal Requirements CITY OF HAGERSTOWN PLANNING & CODE ADMINISTRATION DEPARTMENT 1 East Franklin Street Phone: 301-790-4163 Third Floor Hagerstown, MD 21740 Fax: 301-791-2650 BUILDING PERMIT APPLICATION FOR RESIDENTIAL ACCESSORY

More information

4. Number of drawings required: ( ) Locations of nearest streets

4. Number of drawings required: ( ) Locations of nearest streets CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us COMMERCIAL BUILDING PLAN REQUIREMENTS

More information

Building Construction Occupations

Building Construction Occupations Job Ready Assessment Blueprint Building Construction Occupations Test Code: 2011 / Version 01 Measuring What Matters Specific Competencies and Skills Tested in this Assessment: Safety and General Knowledge

More information

Building Regulations; Construction 11

Building Regulations; Construction 11 Building Regulations; Construction 11 b. Ceilings or roofs shall have a minimum of an "R" factor of 12; and c. Where the roof serves also as the finished ceiling a vent space of two inches shall be required

More information

BUILDING PERMIT APPLICATION

BUILDING PERMIT APPLICATION TOWN OF LEICESTER 132 Main Street Post Office Box 197 Leicester, New York 14481 Phone: (585) 382-3231 FAX: (585) 382-9766 BUILDING PERMIT APPLICATION All Town of Leicester property owners are required

More information

PeachStone Capital, Inc. Atlanta s Hard Money Lender When timing is everything, we close! Hard Money Loan Property Worksheet Checklist

PeachStone Capital, Inc. Atlanta s Hard Money Lender When timing is everything, we close! Hard Money Loan Property Worksheet Checklist Hard Money Loan Property Worksheet Checklist Please complete ALL requested information. Incomplete applications will NOT be reviewed! Fully executed purchase and sale agreement including all exhibits,

More information

Prepared for Florida State University Facilities Planning& Construction By Environmental Health & Safety Tallahassee, Fl

Prepared for Florida State University Facilities Planning& Construction By Environmental Health & Safety Tallahassee, Fl SITE ASSESSMENT CHECKLIST FOR DEMOLITION AND RENOVATION PROJECTS INSERT BUILDING NAME FSU BUILDING NUMBER XXX CAMPUS OF FLORIDA STATE UNIVERSITY TALLAHASSEE, FLORIDA Prepared for Florida State University

More information

Lead Management Program

Lead Management Program Syracuse University Lead Management Program Requirements for Departments Managing Projects That Involve Lead-Containing Materials 2017 Prepared by: Syracuse University Environmental Health & Safety Services

More information

Rowan University Asbestos Management Program

Rowan University Asbestos Management Program Rowan University Asbestos Management Program Table of Contents I. Introduction II. Regulatory Compliance III. Department Responsibilities for Asbestos A. EHS (Safety Specialist Staff) B. EHS (Asbestos

More information

U.S. Department of Housing and Urban Development Community Planning and Development

U.S. Department of Housing and Urban Development Community Planning and Development U.S. Department of Housing and Urban Development Community Planning and Development Special Attention of: Notice: CPD-16-02 Regional Directors Field Office Directors Issued: February 8, 2016 CPD Division

More information

Crothers Environmental Group, LLC

Crothers Environmental Group, LLC , LLC Morrisville, Vermont 05661 Phone 802-888-1936 info@crothersiaq.com June 26, 2009 Mr. Joe Aja, Project Engineer State of Vermont - Department of Buildings & General Services 5 Perry Street, Suite

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall

Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall July 3, 2007 REPORT: Full Building Survey TO: Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall FROM: Bryan

More information

RESIDENTIAL BUILDING REQUIREMENTS

RESIDENTIAL BUILDING REQUIREMENTS RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell

More information

N.J.A.C. 5: New Jersey Register, Vol. 49 No. XX, September 5, 2017

N.J.A.C. 5: New Jersey Register, Vol. 49 No. XX, September 5, 2017 N.J.A.C. 5:17-1.1 New Jersey Register, Vol. 49 No. XX, September 5, 2017 HAZARD EVALUATION AND ABATEMENT CODE > SUBCHAPTER 1. GENERAL PROVISIONS 5:17-1.1 Title; scope; intent (a) This chapter, adopted

More information

Pre-Renovation Asbestos Survey

Pre-Renovation Asbestos Survey Pre-Renovation Asbestos Survey L640 Level 2 Remodel College Complex Los Medanos College Pittsburg, California November 23, 2016 Terracon Project No. R1167D98 Prepared for: Contra Costa Community College

More information

Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No

Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No. 1419-15-020 Prepared for: Marshall Waters Woody Associates 1736 E. Sunshine Street, #311 Springfield,

More information