INVESTIGATION OF WIND PROJECTILE RESISTANCE OF CONCRETE MASONRY WALLS AND CEILING PANELS WITH WIDE SPACED REINFORCEMENT FOR ABOVE GROUND SHELTERS

Size: px
Start display at page:

Download "INVESTIGATION OF WIND PROJECTILE RESISTANCE OF CONCRETE MASONRY WALLS AND CEILING PANELS WITH WIDE SPACED REINFORCEMENT FOR ABOVE GROUND SHELTERS"

Transcription

1 Test Report INVESTIGATION OF WIND PROJECTILE RESISTANCE OF CONCRETE MASONRY WALLS AND CEILING PANELS WITH WIDE SPACED REINFORCEMENT FOR ABOVE GROUND SHELTERS Submitted to National Concrete Masonry Association Sunrise Valley Drive Herndon, Virginia Testing Performed by The Wind Science and Engineering Research Center Texas Tech University Box Lubbock, TX Investigators Ernst W. Kiesling, Ph.D., P.E. Larry J. Tanner, P.E. Date Submitted September 26, 2003

2 Investigation of the Projectile Resistance of Concrete Masonry Walls and Ceilings with Wide Spaced Reinforcing for Above Ground Tornado Shelters Overview of Project Mr. Dennis Graber, Director of Technical Publications for the National Concrete Masonry Association contacted the Wind Science and Engineering (WISE) Research Center at Texas Tech University to assess the ability of their reinforced wall panels and ceiling systems for above ground shelters to resist tornado forces and debris impacts. Tests were conducted on September 12, The specifics about each test, results, and conclusions follow. Concrete masonry units reinforced with 3000-p.s.i. concrete and #4 rebar in each block cell is a shelter wall standard contained in FEMA 320, Taking Shelter from the Storm. The tests conducted in September were directed at two series of wall panels and one series of ceiling panels with different reinforcement from that included in FEMA 320. Series One: 4-ft. x 6-ft. test panel constructed with 8-in.CMU block layed with 3/8-in. mortar joints of Type S masonry cement mortar, in accordance with ASTM C270 by the Proportion Method. The masonry units included both solid end blocks and eared end block, see Figure 1. Each masonry cell was grouted full with fine grout in accordance with ASTM C476 by the Proportion Method. The head joint between the solid end blocks and the eared blocks was bedded with Type S masonry cement mortar. No. 5 steel reinforcing was placed at 4-ft. on center, refer to Figure 2. Series Two: 4-ft. x 4.67-ft. test constructed with 6-in.CMU block layed with 3/8-in. mortar joints of Type S masonry cement mortar, in accordance with ASTM C270 by the Proportion Method. The masonry units included only solid end blocks, see Figure 1. Each masonry cell was grouted full with fine grout in accordance with ASTM C476 by the Proportion Method. No. 4 steel reinforcing was placed at 32-in. on center, refer to Figure 3. 2

3 Series Three: 4-ft. x 4-ft. roof section utilizing three rows of solid CMU units, 4-in. x 8-in. x 16-in. Three rows of block were layed on 51-in. long Block Joists with three blocks installed vertically and five blocks layed horizontally. The roof section was grouted full with fine grout in accordance with ASTM C476 by the Proportion Method. The panel was further reinforced with 7- #4 rebars layed perpendicular to the joists, refer to Figures 4 & 5. The missile criterion used for the tests was a 15-lb. 2x4-in. wood board traveling along the board s longitudinal axis, striking the panel perpendicular to the panel face. For test subjects inclined at 30 degrees or greater from the horizontal, the tornado test criterion uses this missile traveling at 100-mph which corresponds to debris propelled horizontally by a 250-mph ground speed wind and is the criterion used in designing for occupant protection. For test subjects inclined less than 30 degrees, the test missile speed is 67-mph which related the missile dropped vertically by the 250-mph ground speed tornado. Additional factors of safety are inherent in the criterion, since there is a very small probability that a missile will be traveling along its axis and will strike a wall perpendicular to its surface. A pressure test was not conducted. The missile criterion used in the test is consistent with the guidelines of FEMA 320, Taking Shelter from the Storm. 3

4 Figure 1 4

5 Figure 2 5

6 Figure 3 6

7 Figure 4 7

8 Figure 5 8

9 Testing From September 12, 2003 Series One Panel The panel was mounted against the reaction frame and readied for testing. Panel Mounted for Testing 9

10 Missile Shot I 103 mph The missile impacted the center of the wall over a mortar joint with eared blocks. The force of the impact caused the missile to shatter thereby allowing the panel to be struck by multiple portions of the missile. There was no remarkable damage. Impact Point 8-in. CMU Panel Impacted by Missile I 10

11 Primary Impact Secondary Impacts Panel Struck by Multiple Impacts of Shattered Missile I 11

12 Missile Shot II 102 mph The missile impacted the center of a standard CMU block unit. The missile shattered on impact and produced no remarkable damage. Impact 1 Impact II Test Panel Impacted by Missile II 12

13 Missile Shot III 101 mph The missile impacted a mortar joint connecting standard and eared block units. The missile shattered and produced no remarkable damage. Impact III Series One Panel Impacted by Missile III 13

14 Testing From September 12, 2003 Series Two Panel Missile Shot I 101 mph The missile impacted the center of the 6-in. CMU block wall. The missile produced hairline vertical cracking through the mortar joint on the backside (safe side) of the panel directly above and below the impact point. Impact Point Series Two Panel after Impact 14

15 Hairline Cracking Series Two Panel Cracked by Missile I 15

16 Missile Shot II 103 mph The missile impacted a mortar joint directly below the first impact. The impact produced additional cracking and widening of the initial crack on the safe side of the panel. Horizontal cracking on the safe side extended from the impact point through the mortar joints out to the wall edges. The impact side exhibited both vertical and horizontal cracking at the point of impact. Impact I Impact II Series Two Panel Impacted by Missile II 16

17 Mortar Crack Series Two Panel Backside (Safe Side) Cracked by Missile II 17

18 Missile Shot III 100 mph The missile impacted adjacent and to the right of Impact 2. The impact produced additional widening of the horizontal crack produced by Impact 2 and produced slight spalling at the block seam on the safe side surface. Impact I Impact II Impact III Series Two Panel Impacted by Missile III 18

19 Horizontal Crack With Spalling Series Three Panel Safe Side Cracked by Missile III 19

20 Testing From September 12, 2003 Series Three Panel Missile Shot I 70 mph The Series Three Panel was a roof panel installed vertically for testing. The panel was impacted on the right center, adjacent the block joist. The impact produced no remarkable damage. Block Joist Impact I Series Three Panel Impacted Adjacent a Block Joist 20

21 Missile Shot II 68 mph The Series Three Panel was a roof panel was impacted in the panel center. The impact produced no remarkable damage. Impact II Series Three Panel after Impact I 21

22 Missile Shot III 70 mph The Series Three Roof Panel was impacted over the bottom center of the panel. The missile produced no remarkable damage. Impact Point III Series Three Panel Impacted by Missile II 22

23 Missile Shot IV 103 mph Previous tests of the Series Three Panel were conducted at speeds required for roof surfaces, 67 mph, +/- 5mph. The final test was conducted utilizing the vertical wall speed requirements. The missile impacted the panel center without producing any remarkable damage. Impact IV Series Three Panel Impacted by Missile IV 23

24 Conclusions Within the bounds of reasonable engineering and technical certainty, and subject to change if additional information becomes available, the following is my professional opinion: Tests on the Series One 8-in. CMU wall panel, the Series Two 6-in. CMU wall panel and the Series Three CMU roof panel were successful. The test missile neither perforated the test subjects or produced hazardous spalling on the safe side of the wall. The 15-lb. 2x4 missile traveling horizontally at 100 mph is required by FEMA 320 and relates to a missile propelled by a 250 mph ground speed tornado. The vertical test missile traveling at 67 mph relates to the missile dropped by a 250 mph ground speed tornado. The Series One, Two and Three panels are consistent with the debris impact resistance required by the FEMA 320, Taking Shelter from the Storm guidelines. Larry J. Tanner, P.E. Use of Testing Report and TTU and WISE Logos The written report and supplemental photos and/or videos may be referenced or distributed by your company. But, Texas Tech University cannot endorse products nor can the name of the University or any of its units or personnel be used in advertising without first securing written permission from the University. Any misuse or misrepresentation of the report and/or pictures will result in action being taken by the University against the responsible parties. Storm shelter manufacturers or producers who have had products tested at Texas Tech University can use the Texas Tech University Wind Engineering logo provided they conform to the following: I. The Texas Tech University Wind Engineering logo may not be so prominent as to mislead the public or unduly play upon the Texas Tech University Wind Engineering name. II. Whenever the logo is used one of the two alternative statements below is to be employed in the text: Alternate 1 whole shelter The use of the Texas Tech University Wind Engineering logo signifies that the complete shelter structure was tested and successfully passed missile impact resistance tests at Texas Tech University. Alternate 2 - shelter component The use of the Texas Tech University Wind Engineering logo does not signify that the entire shelter structure was tested at Texas Tech, but rather only [shelter component name explicitly] was tested and successfully passed missile impact resistance tests at Texas Tech University. III. All advertising and promotional texts containing the use of the Texas Tech University Wind Engineering logo are to be presented to the Texas Tech University Office of Technology Transfer and Intellectual Property for review and approval before distribution. Texas Tech University will challenge any use of the Texas Tech University Wind Engineering logo that does not conform to the above standards. 24

Wind Science & Engineering Research Center Debris Impact Test Facility P.O. Box Lubbock, Texas MANUFACTURER S IDENTIFICATION

Wind Science & Engineering Research Center Debris Impact Test Facility P.O. Box Lubbock, Texas MANUFACTURER S IDENTIFICATION 1.0 MANUFACTURER S IDENTIFICATION 1.1 NAME OF APPLICANT: Western States Clay Products Assoc. 9780 S. 5200 W. West Jordan, Utah 84081 1.2 CONTACT PERSON: Mr. Jeff Elder 1.3 TEST LAB CERTIFICATION: Federal

More information

Wind Science & Engineering Research Center Debris Impact Test Facility P.O. Box Lubbock, Texas MANUFACTURER S IDENTIFICATION

Wind Science & Engineering Research Center Debris Impact Test Facility P.O. Box Lubbock, Texas MANUFACTURER S IDENTIFICATION 1.0 MANUFACTURER S IDENTIFICATION 1.1 NAME OF APPLICANT: Mason Greenstar P.O. Box 1420 Mason, Texas 76856 1.2 CONTACT PERSON: Mr. Zach Rabon 1.3 TEST LAB CERTIFICATION: Federal Emergency Management Agency

More information

APPENDIX A.1 TEST PROTOCOLS A PROTOCOLS FOR DEBRIS IMPACT TESTING

APPENDIX A.1 TEST PROTOCOLS A PROTOCOLS FOR DEBRIS IMPACT TESTING APPENDIX A.1 TEST PROTOCOLS The National Wind Institute, Debris Impact Test Facility (NWI - DIF) at Texas Tech University (TTU) performs debris impact tests on storms shelters, shelter components, and

More information

Investigation of Wind Projectile Resistance of Insulating Concrete Form Homes. by Ernst W. Kiesling, Ph.D., P.E. Russell Carter, BSCE, EIT

Investigation of Wind Projectile Resistance of Insulating Concrete Form Homes. by Ernst W. Kiesling, Ph.D., P.E. Russell Carter, BSCE, EIT Investigation of Wind Projectile Resistance of Insulating Concrete Form Homes by Ernst W. Kiesling, Ph.D., P.E. Russell Carter, BSCE, EIT R E S E A R C H & D E V E L O P M E N T B U L L E T I N RP122 Investigation

More information

Chapter 8 - Testing. Ernst W. Kiesling, P.E., Ph.D. Professor of Civil Engineering. and. Executive Director

Chapter 8 - Testing. Ernst W. Kiesling, P.E., Ph.D. Professor of Civil Engineering. and. Executive Director ICC/NSSA Standards Preview Chapter 8 - Testing by Ernst W. Kiesling, P.E., Ph.D. Professor of Civil Engineering Texas Tech University and Executive Director National Storm Shelter Association (NSSA) presented

More information

IMPACT RESISTANCE OF BRICK VENEER STRUCTURES TO HURRICANE DEBRIS

IMPACT RESISTANCE OF BRICK VENEER STRUCTURES TO HURRICANE DEBRIS 10 th Canadian Masonry Symposium, Banff, Alberta, June 8 12, 2005 IMPACT RESISTANCE OF BRICK VENEER STRUCTURES TO HURRICANE DEBRIS Richard M. Bennett 1, J. Gregg Borchelt 2, Jim Bryja 3, and Bill Kjorlien

More information

SHRC SHELTERS STACI CUCCIO, FLINT HOLBROOK, KEVIN ROEWE, & JARED SWART

SHRC SHELTERS STACI CUCCIO, FLINT HOLBROOK, KEVIN ROEWE, & JARED SWART SHRC SHELTERS STACI CUCCIO, FLINT HOLBROOK, KEVIN ROEWE, & JARED SWART MISSION Create safe economical shelter designs Design outstanding features Satisfy client & market demands PROBLEM STATEMENT Storm

More information

Hurricane wind shelter retrofit room standards for existing houses

Hurricane wind shelter retrofit room standards for existing houses Safety and Security Engineering 653 Hurricane wind shelter retrofit room standards for existing houses N. Yazdani 1, T. Townsend 1 & D. KilCollins 2 1 Florida A & M University- Florida State College of

More information

National Wind Institute Debris Impact Facility- Texas Tech University P.O. Box Lubbock, Texas

National Wind Institute Debris Impact Facility- Texas Tech University P.O. Box Lubbock, Texas 1.0 MNUFCTURER S IDENTIFICTION 1.1 NME OF PPLICNT: Bleeding Edge 101 Industrial Park Dr. Sullivan, MO 63080 1.2 CONTCT PERSON: Mr. George Sturmon 1.3 TEST LB CERTIFICTION: Federal Emergency Management

More information

2001 COMPANY. WIND BLOWN DEBRIS RESISTANT ROOF ASSEMBLIES Hurricane 140 Mph And Tornado 250 Mph Wind Blown Debris

2001 COMPANY. WIND BLOWN DEBRIS RESISTANT ROOF ASSEMBLIES Hurricane 140 Mph And Tornado 250 Mph Wind Blown Debris WIND BLOWN DEBRIS RESISTANT ROOF ASSEMBLIES Hurricane 140 Mph And Tornado 250 Mph Wind Blown Debris The Texas Tech Wind Blown Debris Test requires three impacts by the butt end of a 2 x 4 shot out of an

More information

Coping with Nature s Most Powerful Storms

Coping with Nature s Most Powerful Storms Coping with Nature s Most Powerful Storms Intertek, the NSSA and Texas Tech Team Up to Create Certification Program for Tornado Resistant Products Rick Curkeet, Chief Engineer, Intertek Larry Tanner, Research

More information

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX.

DESIGNING SAFE ROOMS AND SAFE HOMES WITH LOGIX. . Actual ICF-Built Home That Survived Katrina Table of Contents Section Page Overview Logix Wind Resistance Advantages...3 Logix Wall Engineering To 300 MPH Wind Rating...6 Fema-Compliant Design Specifications

More information

National Wind Institute Debris Impact Facility- Texas Tech University P.O. Box Lubbock, Texas

National Wind Institute Debris Impact Facility- Texas Tech University P.O. Box Lubbock, Texas National Wind Institute Debris Impact Facility- Texas Tech University P.O. Box 43155 Lubbock, Texas 79409-1023 Report No. _20140725A Specimen No. 2 Test Date: _July 25, 2014_ 1.0 MANUFACTURER S IDENTIFICATION

More information

STRUCTURAL DESIGN CRITERIA

STRUCTURAL DESIGN CRITERIA CHAPTER 3 STRUCTURAL DESIGN CRITERIA SECTION 301 GENERAL 301.1 Scope. Loads and load combinations shall be determined in accordance with ASCE 7 unless otherwise noted. Structural elements of the storm

More information

STRUCTURAL DESIGN CRITERIA

STRUCTURAL DESIGN CRITERIA CHAPTER 3 STRUCTURAL DESIGN CRITERIA SECTION 301 GENERAL 301.1 Scope. Loads and load combinations shall be determined in accordance with ASCE 7 unless otherwise noted. Structural elements of the storm

More information

Keynote Address--The Role of Safe Rooms in Disaster Resistant Universities

Keynote Address--The Role of Safe Rooms in Disaster Resistant Universities University of New Orleans ScholarWorks@UNO DRU Workshop 2013 Presentations Disaster Resistant University Workshop: Linking Mitigation and Resilience Conferences and Workshops 3-1-2013 Keynote Address--The

More information

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS

REPORT HOLDER: AEROSMITH FASTENING SYSTEMS 5621 DIVIDEND ROAD INDIANAPOLIS, INDIANA EVALUATION SUBJECT: AEROSMITH 3000 SERIES FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-3833 Reissued 08/2017 This report is subject to renewal 08/2018. DIVISION: 03 00

More information

Frequently Asked Questions. Design and Construction Guidance for Community Shelters FEMA 361 / July 2000 First Edition FEMA

Frequently Asked Questions. Design and Construction Guidance for Community Shelters FEMA 361 / July 2000 First Edition FEMA Frequently Asked Questions Design and Construction Guidance for Community Shelters FEMA 361 / July 2000 First Edition FEMA In Association With: FEMA 361 Chapter 1 Introduction 1.1 What shelter costs are

More information

Research Evaluation of Single Lift Grouting in Concrete Masonry Wall Panels

Research Evaluation of Single Lift Grouting in Concrete Masonry Wall Panels Research Evaluation of Single Lift Grouting in Concrete Masonry Wall Panels Jeffrey H. Greenwald, P.E, Dennis W. Graber, P.E., J. Marcus Cherundolo, EIT Abstract The objective of this research was to investigate

More information

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads

ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS. TEK 17-1C Structural (2009) Related TEK: Uniform load. Triangular load. Concentrated loads An information series from the national authority on concrete masonry technology ALLOWABLE STRESS DESIGN OF CONCRETE MASONRY LINTELS TEK 17-1C Structural (2009) INTRODUCTION Lintels and beams are horizontal

More information

Oklahoma Outline. The concept arrives Burnett, Texas ICC ICC/NSSA Standard for the Design And Construction Of Storm Shelters

Oklahoma Outline. The concept arrives Burnett, Texas ICC ICC/NSSA Standard for the Design And Construction Of Storm Shelters To help protect your privacy, PowerPoint has blocked automatic download of this picture. Safe Room Standards and Guidelines 2015 Applications Oklahoma 1999 Presented to National Tornado Summit 2015 Oklahoma

More information

Handout. ICC-NSSA Storm Shelters. Presenter. ICC NSSA Storm Shelters Webinar. International Code Council 1. Ernst W. Kiesling, P.E.

Handout. ICC-NSSA Storm Shelters. Presenter. ICC NSSA Storm Shelters Webinar. International Code Council 1. Ernst W. Kiesling, P.E. 1 If you need assistance please contact us at 1-888-ICC-SAFE (422-7233), extension 33818 IMPORTANT NOTICE: This Adobe Connect service includes a feature that allows audio and any documents and other materials

More information

Masonry Wall Bracing. A Simplified Approach To Bracing Masonry Walls Under Construction. Masonry Bracing Task Force.

Masonry Wall Bracing. A Simplified Approach To Bracing Masonry Walls Under Construction. Masonry Bracing Task Force. Masonry Wall Bracing A Simplified Approach To Bracing Masonry Walls Under Construction Produced by the Masonry Wall Bracing A Simplified Approach to Bracing Masonry Walls Under Construction Produced by

More information

TECHNICAL INFORMATION

TECHNICAL INFORMATION TECHNICAL INFORMATION SECTION 07320 TWO-PIECE TAPERED MISSION CLAY ROOFING TILE PART 1 GENERAL 1.01 SECTION INCLUDES A. Formed clay roofing tiles, complete with components and other required accessories

More information

The Perfect Block OEM ICC Equivalent Product Compliance Report

The Perfect Block OEM ICC Equivalent Product Compliance Report 8960 W. Larkspur Drive, Ste. 105 Peoria AZ. 85381 Phone 888.623.ICCF (4223) Email: info@theperfectblock.com Manufacturer: The Perfect Block OEM ICC Equivalent Product Compliance Report Eco Building Systems

More information

Pulaski County, Virginia Practical Wall Bracing

Pulaski County, Virginia Practical Wall Bracing Pulaski County, Virginia Practical Wall Bracing Based on the 2012 Virginia Residential Code The information herein provides guidelines for complying with the most common Practical Wall Bracing provisions

More information

Window Evaluation. Subject: Series 200 Horizontal Sliding Impact-Resistant Windows. Report Rendered to:

Window Evaluation. Subject: Series 200 Horizontal Sliding Impact-Resistant Windows. Report Rendered to: April 25, 2010 99509.04-122-34 1 9 Window Evaluation Subject: Series 200 Horizontal Sliding Impact-Resistant Windows Report 99509.04-122-34 Rendered to: SHOWCASE WINDOWS, ENLIGHT INDUSTRIES, LLC 4902 Gulf

More information

ASD OF CONCRETE MASONRY LINTELS BASED ON THE 2012 IBC/2011 MSJC. TEK 17-1D Structural (2011) Related TEK: 14-7C, 14-13B, 17-1C, 17-2A

ASD OF CONCRETE MASONRY LINTELS BASED ON THE 2012 IBC/2011 MSJC. TEK 17-1D Structural (2011) Related TEK: 14-7C, 14-13B, 17-1C, 17-2A n information series from the national authority on concrete masonry technology SD OF CONCRETE MSONRY LINTELS BSED ON THE 2012 IBC/2011 MSJC TEK 17-1D Structural (2011) INTRODUCTION Lintels and beams are

More information

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015

Trusted SECTION: 04 HILTI, INC. TULSA, Conformity! ICC-ES Evaluation. not specifically. Copyright 2015 0 ICC ES Report ICC ES (800) 42 6587 (562) 699 054 www.icc es.orgg 000 Most Widely Accepted and Trusted ESR 2269 Reissued 02/205 This report is subject to renewal 02/207. DIVISION: 0 00 00 CONCRETE SECTION:

More information

ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC

ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC Standards Action - May 2, 2014 - Page 43 of 50 Pages International Code Council ICC/NSSA STANDARD FOR THE DESIGN AND CONSTRUCTION OF STORM SHELTERS ICC 500-2013 edition Public Comment Draft #3 The ICC

More information

FORTIFIED Home High Wind. Bronze New Roof Requirements

FORTIFIED Home High Wind. Bronze New Roof Requirements THE DECK (PREP MATERIAL, FASTENING) THE ROOF DECK SEALING THE ROOF DECK All existing roof cover and flashings shall be removed; deck shall be a clean, workable surface free from debris. Damaged or rotten

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3056 Reissued 10/2015 This report is subject to renewal 10/2017. DIVISION: 04 00 00 MASONRY

More information

Exploring DDESB Acceptance Criteria for Containment of Small Charge Weights

Exploring DDESB Acceptance Criteria for Containment of Small Charge Weights Exploring DDESB Acceptance Criteria for Containment of Small Charge Weights Jason R. Florek, Ph.D. and Khaled El-Domiaty, P.E. Baker Engineering and Risk Consultants, Inc. 2500 Wilson Blvd., Suite 225,

More information

Limited Exterior Masonry Assessment Roosevelt Elementary School

Limited Exterior Masonry Assessment Roosevelt Elementary School Limited Exterior Volume 2 of 2 November 29. 2007 Produced for: Medford Public Schools Medford, Oregon In Consultation with: 710 NE 21 st Avenue, Suite 200, Portland, Oregon 97232 P: 503.517.0283 F: 503.517.0285

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 42 687 (62) 699 04 www.icc es.org ESR 06 Reissued 0/207 This report is subject to renewal 0/208. DIVISION: 04 00 00 MASONRY

More information

3-Hour Fire Rating. Assembly Information

3-Hour Fire Rating. Assembly Information 3-Hour Fire Rating 6 C.M.U. Assembly Information 1. Preferred product 910330 c.m.u. 6" x 8" x 16" nominal 2. Portland cement stucco - 1/2" thick applied directly to C.M.U. 3. Wood or steel furring members

More information

*Corrected October 2005

*Corrected October 2005 ESR-1056* Reissued December 1, 2004 This report is subject to re-examination in two years. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office # 5360 Workman Mill Road, Whittier, California

More information

SELECT APPROPRIATE SECTIONS FOR BELOW; DELETE OTHERS

SELECT APPROPRIATE SECTIONS FOR BELOW; DELETE OTHERS Master Specifications 03440-1 SECTION 03440 REINFORCED AUTOCLAVED AERATED CONCRETE PANELS Date: 04-19-07 SECTION REQUIRES EDITOR TO MAKE SELECTIONS - GENERALLY SELECTIONS ARE PRECEDED BY **. SPEC EDITOR

More information

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year.

ESR-2269 Reissued November 1, 2008 This report is subject to re-examination in one year. Reissued November, 008 This report is subject to re-examination in one year. ICC Evaluation Service, Inc. www.icc-es.org Business/Regional Office 60 Workman Mill Road, Whittier, California 9060 (6) 699-0

More information

ABOVEGROUND HOME FALLOUT SHELTER H-12-2 / November 1983 (Supercedes H-12-2 dated June 1980)

ABOVEGROUND HOME FALLOUT SHELTER H-12-2 / November 1983 (Supercedes H-12-2 dated June 1980) ABOVEGROUND HOME FALLOUT SHELTER H-12-2 / November 1983 (Supercedes H-12-2 dated June 1980) Page 1 General Information This family shelter is intended for persons who prefer an aboveground shelter or,

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3196 Reissued 10/2018 This report is subject to renewal 10/2019. SECTION: 04 05 19.16

More information

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK ND AND 3 RD FIX FINISHES

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK ND AND 3 RD FIX FINISHES CONTENTS 10.1 PLASTERWORK 10.2 2 ND AND 3 RD FIX FINISHES FUNCTIONAL REQUIREMENT 10.1 Plasterwork Workmanship Design Technical Manual TS-011-09-010412 i. All workmanship must be within defined tolerances

More information

Plan Check No. Checked by: An Appointment Is Required for Verification

Plan Check No. Checked by: An Appointment Is Required for Verification SUPPLEMENTAL CORRECTION SHEET UNREINFORCED MASONRY (URM) RETROFIT ( 2002 LABC ) Plan Check No. Checked by: Permit Appl. # An Appointment Is Required for Verification Job Address: For appt. call: APPLICATION

More information

5 Load Determination and Structural Design Criteria

5 Load Determination and Structural Design Criteria 5 Load Determination and Structural Design Criteria This chapter presents a summary of previous research and testing and outlines the recommended methods and criteria for use in the structural design of

More information

S T R U C T U R. Technology. magazine. Software for the Structural Design of Masonry. The Design Basis. Copyright

S T R U C T U R. Technology. magazine. Software for the Structural Design of Masonry. The Design Basis. Copyright Software for the Structural Design of Masonry By Russell H. Brown, James K. Nelson, Jr. and Dennis Graber Using software can free the design engineer from the drudgery of routine calculations and enable

More information

SECTION CEMENTITIOUS WOOD FIBER DECKS

SECTION CEMENTITIOUS WOOD FIBER DECKS PART 1 - GENERAL 1.1 DESCRIPTION SECTION 03 51 13 CEMENTITIOUS WOOD FIBER DECKS SPEC WRITE NOTES: 1. Delete between // // if not applicable to project. 2. Also delete any other item or paragraph not applicable

More information

APPENDIX I NASP TEST PROTOCOLS

APPENDIX I NASP TEST PROTOCOLS APPENDIX I NASP TEST PROTOCOLS I-1 I-2 I-3 I-4 NASP STRAND BOND TEST (DRAFT) Standard Test Method to Assess the Bond of 0.5 in. (12.7 mm) and 0.6 in. (15.24 mm) Seven Wire Strand with Cementitious Materials

More information

SPECIFICATIONS PRECAST PRESTRESSED CONCRETE PART 1 GENERAL 1.6.2.5 Openings, inserts and related reinforcement 1.6.3 Each drawing submitted to bear stamp of 1.1 Related Work qualified Professional Engineer

More information

Comparison letter for MegaMet s MegaStorm Door against door construction details in FEMA 361 section 7.4.1

Comparison letter for MegaMet s MegaStorm Door against door construction details in FEMA 361 section 7.4.1 October 20, 2014 MegaMet Industries, Inc. P.O Box 635 Birmingham, AL 35201 ATTN: Re: Edward Wall ewalljr777@gmail.com Comparison letter for MegaMet s MegaStorm Door against door construction details in

More information

Designation: TTU NWI DIF Air Bladder Standard Scope

Designation: TTU NWI DIF Air Bladder Standard Scope Designation: TTU NWI DIF Air Bladder Standard 1.1.2016 Standard Test Method for Structural Performance of Exterior Doors, Windows, Curtain Walls, and Skylights by Uniform Static Air Pressure Difference

More information

WALL SYSTEMS ( Ref: The Building Illustrated, Ching, Francis DK )

WALL SYSTEMS ( Ref: The Building Illustrated, Ching, Francis DK ) WALL SYSTEMS ( Ref: The Building Illustrated, Ching, Francis DK ) 1.0 Comparative wall systems Wood stud walls * walls are normally 2x4, but may be 2x6. * studs are spaced 16. * studs carry vertical loads.

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A7795.01 109 44 Rendered to: LEED HIMMEL INDUSTRIES, INC. Hamden, Connecticut INSULPANE OF CT INC. Hamden, Connecticut PRODUCT

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 3196 Reissued 10/2017 This report is subject to renewal 10/2018. SECTION: 04 05 19.16

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 1678 Reissued 03/2017 This report is subject to renewal 03/2018. DIVISION: 04 00 00 MASONRY

More information

Storm Shelter Senior Design Team. Reese Hundley Sean Mallory Heidi Stair Katie Whitehurst

Storm Shelter Senior Design Team. Reese Hundley Sean Mallory Heidi Stair Katie Whitehurst Storm Shelter Senior Design Team Reese Hundley Sean Mallory Heidi Stair Katie Whitehurst What to Expect Project Objective Company Background Last Semester FEMA Standards Design/Testing Procedures Conclusion/Recommendations

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT:

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: DEWALT 701 EAST JOPPA ROAD TOWSON, MARYLAND EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 4042 Issued 07/2017 This report is subject to renewal 07/2018. DIVISION: 04 00 00

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: 5956 WEST LAS POSITAS BOULEVARD PLEASANTON, CALIFORNIA 94588 0 ICC ES Report ICC ES (800) 4 687 (6) 699 04 www.icc es.org 000 Most Widely Accepted and Trusted ESR 06 Valid: 0/ to 0/6 DIVISION: 04 00 00 MASONRY SECTION: 04 0 9.6 MASONRY ANCHORS REPORT HOLDER: SIMPSON

More information

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES. Chapter 10

CHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES. Chapter 10 CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES 283 Chapter 10 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 10.1 PLASTERWORK Workmanship i. All workmanship must be within the tolerances

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: POWERS FASTENERS, INC. 701 EAST JOPPA ROAD TOWSON, MARYLAND 21286 0 ICC-ES Report ICC-ES (800) -687 (6) 6-0 www.icc-es.org 000 Most Widely Accepted and Trusted ESR-678 Reissued 0/0 This report is subject to renewal 0/06 DIVISION: 0 00 00 MASONRY SECTION: 0 0.6 MASONRY

More information

NCMA TEK. TEK 14-5A Structural (2006) LOADBEARING CONCRETE MASONRY WALL DESIGN

NCMA TEK. TEK 14-5A Structural (2006) LOADBEARING CONCRETE MASONRY WALL DESIGN NCMA TEK National Concrete Masonry Association an information series from the national authority on concrete masonry technology LOADBEARING CONCRETE MASONRY WALL DESIGN TEK 14-5A Structural (26) Keywords:

More information

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003)

NCMA TEK RESIDENTIAL DETAILS FOR HIGH WIND AREAS. TEK 5-11 Details (2003) NCM TEK National Concrete Masonry ssociation an information series from the national authority on concrete masonry technology RESIDENTIL DETILS FOR HIGH WIND RES TEK 5-11 Details (2003) Keywords: architectural

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-1663 Reissued 03/2017 This report is subject to renewal 03/2019. DIVISION: 03 00 00 CONCRETE

More information

1.5-Hour Fire Rating. Assembly Information

1.5-Hour Fire Rating. Assembly Information 1.5-Hour Fire Rating 6 C.M.U. Assembly Information 1. Preferred product 910350 c.m.u. 6" x 8" x 16" nominal 2. Portland cement stucco - 1/2" thick applied directly to C.M.U. 3. ASTM C-270 Masonry Mortar,

More information

Masonry and Cold-Formed Steel Requirements

Masonry and Cold-Formed Steel Requirements PC UFC Briefing September 21-22, 2004 Masonry and Cold-Formed Steel Requirements David Stevens, ARA Masonry Requirements Composite Construction Masonry is often used in composite construction, such as

More information

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures.

CTP STITCH-TIE AGAIN! Quick and easy way to re-anchor existing veneers to back-up structures. Helical Wall Tie System for Stabilizing Veneers and Structural Repair AGAIN! ANOTHER CTP SOLUTION! CTP STITCH-TIE Quick and easy way to re-anchor existing veneers to back-up structures. Brick to Concrete

More information

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit

Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Supplemental Plan Check List for Unreinforced Masonry (URM) Retrofit Plan Check/PCIS App #: Job Address: P.C. Engineer: Phone: (E -mail: first name.last name@ lacity.org) For instructions and other information,

More information

TORNADO & HIGH WIND SHELTERING WITH MASONRY

TORNADO & HIGH WIND SHELTERING WITH MASONRY J.B. SPEED SCHOOL OF ENGINEERING TORNADO & HIGH WIND SHELTERING WITH MASONRY Mark McGinley, PE, PhD, FASTM Professor and Endowed Chair for Infrastructure Research Civil and Environmental Engineering, University

More information

To: Firm: Project: Product Specified: Specified Location:

To: Firm: Project: Product Specified: Specified Location: Submittal Substitution Request To: Firm: Project: Product Specified: Specified Location: Attached information includes product description, installation instructions and technical data needed for review

More information

SECTION UNIT MASONRY

SECTION UNIT MASONRY SECTION 04200 UNIT MASONRY PART 1 GENERAL 1.01 SUMMARY A. Furnish labor, materials, and equipment and perform functions required in the installation and maintenance of the work covered by this Section.

More information

GPD Glass Performance Days GLASS PERFORMANCE DAYS Tampere, Finland June 24 26, 2015 CONFERENCE PROCEEDINGS

GPD Glass Performance Days GLASS PERFORMANCE DAYS Tampere, Finland June 24 26, 2015 CONFERENCE PROCEEDINGS GPD Glass Performance Days 2015-1 - GLASS PERFORMANCE DAYS 2015 Tampere, Finland June 24 26, 2015 CONFERENCE PROCEEDINGS Designing Impact Glazing to Meet Tornado Performance Standards Laminated Glass /

More information

TRABUE, HANSEN & HINSHAW, Inc.

TRABUE, HANSEN & HINSHAW, Inc. CONSULTING ENGINEERS 1901 Pennsylvania Drive Columbia, MO 65202 TRABUE, HANSEN & HINSHAW, Inc. March 4, 2014 Mr. Larry Hubbard Director of Campus Facilities Plan, Design & Construction E111 General Services

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 687 (6) 699 0 www.icc es.org ESR 8 Reissued 0/08 This report is subject to renewal 0/09. DIVISION: 0 00 00 MASONRY SECTION:

More information

Section CONCRETE SIDEWALKS. 1. Payment for concrete sidewalks is on square foot basis.

Section CONCRETE SIDEWALKS. 1. Payment for concrete sidewalks is on square foot basis. PART 1 GENERAL 1.01 SUMMARY A. This Section includes the following: Section 02775 1. Reinforced concrete sidewalks. 2. Wheelchair Ramps. 1.02 MEASUREMENT AND PAYMENT A. Unit Prices. 1. Payment for concrete

More information

Conditions of the Contract and Division 1 General Requirements are a part of this section.

Conditions of the Contract and Division 1 General Requirements are a part of this section. NOTES TO SPECIFIER General notes about the specifications and the reasons for them are listed here in general statements. Use this as a guide when choosing the correct selection of statements that apply

More information

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued)

Table 3. Detailed Comparison of Structural Provisions of IRC 2000 and 1997 NEHRP (Continued) 2000 IRC 1997 NEHRP Section Provision Section Provision Comments CHAPTER 3 BUILDING PLANNING R301 DESIGN CRITERIA R301.2.2 Seismic Provisions R301.2.2.1 Determination of Seismic Design Category R301.2.2.1.1

More information

A n c h o r a g e. M o v e m e n t. M o i s t ur e A SYSTEMS APPROACH TO THE DESIGN AND EXECUTION OF MASONRY CAVITY AND VENEER WALL SYSTEMS

A n c h o r a g e. M o v e m e n t. M o i s t ur e A SYSTEMS APPROACH TO THE DESIGN AND EXECUTION OF MASONRY CAVITY AND VENEER WALL SYSTEMS A SYSTEMS APPROACH TO THE DESIGN AND EXECUTION OF MASONRY CAVITY AND VENEER WALL SYSTEMS To successfully design and build masonry cavity walls and veneers, one must take a systems approach. A masonry wall

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC. EVALUATION SUBJECT: KWIK BOLT TZ MASONRY ANCHORS 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 4 687 (6) 699 04 www.icc es.org ESR 78 Reissued 07/018 This report is subject to renewal 07/019. DIVISION: 04 00 00 MASONRY

More information

Closed-Cell Spray Foam Insulation. Performance in Residential and Commercial Buildings During Adverse Weather

Closed-Cell Spray Foam Insulation. Performance in Residential and Commercial Buildings During Adverse Weather Closed-Cell Spray Foam Insulation Performance in Residential and Commercial Buildings During Adverse Weather July, 2006 Although all statements and information contained herein are believed to be accurate

More information

Commonwealth of Pennsylvania PA Test Method No. 606 Department of Transportation March 2016 Page 1. Laboratory Testing Section. Method of Test for

Commonwealth of Pennsylvania PA Test Method No. 606 Department of Transportation March 2016 Page 1. Laboratory Testing Section. Method of Test for Page 1 Laboratory Testing Section Method of Test for 1. Scope OBTAINING AND TESTING DRILLED CORES OF CONCRETE 1.1 This method covers the procedures for obtaining, preparing, and testing cores drilled from

More information

Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION

Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION Technical Notes 24G - The Contemporary Bearing Wall - Detailing [Dec. 1968] (Reissued Feb. 1987) INTRODUCTION The selection of a wall type and appropriate connection details is one of the most important

More information

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40

PRODUCT EVALUATION Effective Date: June 1, 2013 GDR-40 TEXAS DEPARTMENT OF INSURANCE Engineering Services Program / MC 103-3A 333 Guadalupe Street P.O. Box 149104 Austin, Texas 78714-9104 Phone No. (512) 322-2212 Fax No. (512) 463-6693 PRODUCT EVALUATION Effective

More information

Shear Strength Evaluation of the EP Henry Cast Stone Wall System

Shear Strength Evaluation of the EP Henry Cast Stone Wall System Shear Strength Evaluation of the EP Henry Cast Stone Wall System for EP Henry Corporation PO Box 615 Woodbury, NJ 08096 Conducted by: Project No. 14-539-2 Date: Page 1 of 12 RESEARCH AND DEVELOPMENT LABORATORY

More information

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5 WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 1 OCTOBER 5, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI Table of Contents Table of Contents

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT:

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2269 Reissued 02/2017 This report is subject to renewal 02/2019. DIVISION: 03 00

More information

NCMA TEK DESIGN AND CONSTRUCTION OF DRY-STACK MASONRY WALLS TEK Provided by: Cinder & Concrete Block Corporation

NCMA TEK DESIGN AND CONSTRUCTION OF DRY-STACK MASONRY WALLS TEK Provided by: Cinder & Concrete Block Corporation Provided by: Cinder & Concrete Block Corporation National Concrete Masonry Association an information series from the national authority on concrete masonry technology NCMA TEK DESIGN AND CONSTRUCTION

More information

ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax:

ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA Tel: Fax: ROOME & GUARRACINO, LLC Consulting Structural Engineers 48 Grove Street Somerville, MA 02144 Tel: 617.628.1700 Fax: 617.628.1711 March 3, 2016 Mr. Jeff Hoover, Principal Tappe Architects, 6 Edgerly Place

More information

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024

DIVISION: MASONRY SECTION: MASONRY ANCHORS REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS 75024 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 423-6587 (562) 699-0543 www.icc-es.org ESR-4143 Issued 01/2018 This report is subject to renewal 01/2019. DIVISION: 04 00 00

More information

STRUCTURAL CONDITION ASSESSMENT

STRUCTURAL CONDITION ASSESSMENT STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 100-95 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS 1. 2. Scope 1.1 This Protocol covers the determination of the water infiltration

More information

Australian Standard. The design and installation of corrugated fibre-reinforced cement roofing and wall cladding AS

Australian Standard. The design and installation of corrugated fibre-reinforced cement roofing and wall cladding AS AS 1639 1990 Australian Standard The design and installation of corrugated fibre-reinforced cement roofing and wall cladding This Australian Standard was prepared by Committee BD/40, Fibre Cement Building

More information

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama

ASTM E 1886 and ASTM E 1996 TEST REPORT. Report No.: A Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama Architectural Testing ASTM E 1886 and ASTM E 1996 TEST REPORT Report No.: A2653.02 401 44 Rendered to: CORAL ARCHITECTURAL PRODUCTS Tuscaloosa, Alabama PRODUCT TYPE: Curtain Wall SERIES/MODEL: PW257 Captured

More information

PRECAST CONCRETE PRODUCTS

PRECAST CONCRETE PRODUCTS R LEADERS IN THE INDUSTRY TM CONCRETE PRODUCTS SILLS THRESHOLDS PARKING BUMPERS U - LINTELS SCUPPERS February 2012 COMPANY HISTORY Cast-Crete was founded in Tampa Bay, Florida in 1955 as a producer of

More information

1-2-3MORTAR Modified Portland cement based mortar, to be used to adhere any prefabricated construction elements

1-2-3MORTAR Modified Portland cement based mortar, to be used to adhere any prefabricated construction elements 1-2-3MORTAR Modified Portland cement based mortar, to be used to adhere any prefabricated construction elements Data Sheet DESCRIPTION 1-2-3MORTAR is a ready to use commercial grade mason mix used for

More information

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS

REPORT HOLDER: HILTI, INC DALLAS PARKWAY, SUITE 1000 PLANO, TEXAS EVALUATION SUBJECT: HILTI LOW-VELOCITY POWER-ACTUATED FASTENERS 0 Most Widely Accepted and Trusted ICC-ES Evaluation Report ICC-ES 000 (800) 42-6587 (562) 699-054 www.icc-es.org ESR-1752 Reissued 09/2017 This report is subject to renewal 09/2019. DIVISION: 0 00 00

More information

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS

TESTING APPLICATION STANDARD (TAS) No TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS TESTING APPLICATION STANDARD (TAS) No. 100-95 TEST PROCEDURE FOR WIND AND WIND DRIVEN RAIN RESISTANCE OF DISCONTINUOUS ROOF SYSTEMS 1. 2. Scope 1.1 This Protocol covers the determination of the water infiltration

More information

REINFORCING TABLES INSTALLATION MANUAL

REINFORCING TABLES INSTALLATION MANUAL REINFORCING TABLES 201 REINFORCING TABLES Design Limitations Introduction The structural wall reinforcing and lintel design tables contained within the Appendix of NUDURA s Installation Manual have been

More information

APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details)

APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details) APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details) City of San Jacinto 595 S. San Jacinto Ave San Jacinto CA 92583 951.487.7330 fax 951.654.9896 Must print legibly, submit

More information

KELLER PARKWAY - FM 1709

KELLER PARKWAY - FM 1709 Jurisdiction of Project REGULATORY AUTHORITIES: CITY OF KELLER COMMUNITY DEVELOPMENT MAILING ADDRESS: P.O. BOX 770, KELLER, TX 76244-0770 PHYSICAL ADDRESS: KELLER TOWN HALL, 1100 BEAR CREEK PKWY COMMUNITYDEVELOPMENT@CITYOFKELLER.COM

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information