Classification of fire performance in accordance with BR 135: Annex B: Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs.
|
|
- Dominic Brent Bailey
- 5 years ago
- Views:
Transcription
1 Classification of fire performance in accordance with BR 135: Annex B: 2007 Prepared for: Alsecco (U.K) Ltd Whitebridge Way Stone Staffs. ST15 8GH 29 th June 2007 Classification report : Issue number: 1 Page 1 of 18
2 Contents 1 Introduction 4 2 Details of classified product General Description of the Alsecco Basic FS system General Description of product Substrate Insulated render system 5 3 Test reports in support of classification Test report Test results Observations 6 4 Classification and field of application Reference of classification Field of application 6 5 Limitations 7 Page 2 of 18
3 CLASSIFICATION OF FIRE PERFORMANCE IN ACCORDANCE WITH BR 135:ANNEX B:2007 Sponsor: Prepared by: Product name: Alsecco (U.K) Ltd, Whitebridge Way, Stone, Staffs. ST15 8GH BRE Testing, BRE, Bucknalls Lane, Garston, Watford, WD25 9XX, England Alsecco Basic FS Insulated Render System with 80 mm EPS insulation Classification report No.: Issue number: 1 Date of issue: 29 th June 2007 This classification report consists of eighteen pages and may only be used or reproduced in its entirety. Page 3 of 18
4 1 Introduction This classification report defines the classification assigned to the Alsecco (UK) Ltd, Basic FS Insulated Render System with 80mm EPS insulation in accordance with the procedures given in DG 501- BR 135: Annex B Fire performance criteria and classification method for BS :2005. This classification report should be read in conjunction with BRE test reports dated 7 November 2005, and dated 29 th June Details of classified product 2.1 General The product is described as an external insulation system. 2.2 Description of the Alsecco Basic FS system General Description of product The Alsecco Basic FS Insulated Render system comprises of three elements: the system substrate, a 6mm cement particle board on lightweight steel frame, breather membrane, a 15mm cavity and a second sheet of 10mm thick cement particle board, the insulation, and the external finish Substrate The substrate comprised of a Banro light gauge steel frame which was installed between the concrete floor lintels onto the face of the BRE test facility (Drawing reference BRE Test 013). The framework consisted of 150mm wide, 1.2 gauge steel sections secured to the lintels using tapcon fixings at 600mm centres between the vertical steel studs which were also set at 600mm centres. The vertical studs were fixed to the tracks using 25mm wafer head screws in to the rear of the studs. Sheets of 6mm thick New Pyrok cement particle board (nominally 1200mm x 2400mm) were then fixed to the light gauge steel frame using twin winged 4.8 x 38mm self drilling screws fixed at 300mm centres around the perimeters and 600mm along the studs. 50mm thick slabs of Rockwool FlexiSlab were fitted into the steel channel behind the 6mm cement particle board. (Drawing reference BRE Test 005). Page 4 of 18
5 A breather membrane sheet (Tyvek Housewrap) was fixed to the cement particle board and Alsecco Tophat drainage profiles were fixed horizontally at 600mm centres using Alescco FSHL M4x23 screws (Drawing Reference BRE Test 012 & 013). A 10mm thick cement particle board was then fixed to the top hat sections using Alescco FSHL M4x23 screws. This created a 15mm cavity between the two particle cement boards. Intumescent cavity fire barriers (Sealmaster cavity fire seals Product code CFS (40mm x 10mm)) were fitted at every floor slab level Insulated render system The Alsecco Basic FS Insulated Render System consisted of an 80mm thick expanded polystyrene (Alsecco PS 15 SE) insulation layer (density 15kg/m 3 ) which was fixed to the 10mm thick cement particle board using 100% coverage of Thermastick MP adhesive and Alsecco SBH-T100 mechanical fixings (Alsecco drawing reference BRE Test 0011). Horizontal fire barriers were fitted at every floor level and comprised of 500mm wide x 80mm thick slab of high density mineral wool applied in a continuous strip. The fire barriers were applied using a 100% coverage of Thermastick MP adhesive and Alsecco SBH-T100 mechanical fixings at a maximum of 400mm centres. The area of the barrier was double meshed with an overlap of 200mm above and below the barrier. The base coat comprised Armatop MP (4-5 mm) and reinforcing mesh 32. This was covered with a top primer (Primer SC) and a top coat (Silitect T 1.5mm). 3 Test reports in support of classification 3.1 Test report Name of Laboratory Name of sponsor Test reports/extended application report Nos. Test method / extended application rules & date BRE Testing, BRE Alsecco (UK) Ltd , dated 7 th November dated 29 th June 2007 BS : 2005 Page 5 of 18
6 3.2 Test results Test method & test number Parameter No. tests Results Fire spread test result time, t s (min) Compliance with parameters in BR135:Annex B: 2007 BS : 2005 External fire spread >15 minutes Compliant Internal fire spread Layer 1 insulation 1 >15 minutes Compliant Internal fire spread Layer 1 Void >15 minutes Compliant Burn through >15 minutes Compliant 3.3 Observations Mechanical Performance Some spalling of the render was observed during the test. Some molten material and flaming droplets were observed flowing from a crack in the render system above the hearth opening during the test. 4 Classification and field of application 4.1 Reference of classification This classification has been carried out in accordance with DG501- BR 135:Annex B Fire performance criteria and classification method for BS : Field of application This classification is valid only for the product as installed and detailed in Section 2 of this classification report. Page 6 of 18
7 5 Limitations This classification document does not represent type approval or certification of the product. The specification and interpretation of fire test methods are the subject of ongoing development and refinement. Changes in associated legislation may also occur. For these reasons, it is recommended that the relevance of test and classification reports over five years old should be considered by the user. The laboratory that issued the report will be able to offer, on behalf of the legal owner, a review of the procedures adopted for a particular test or classification to ensure that they are consistent with current practices, and if required may endorse the report. SIGNED APPROVED Dr S A Colwell Principal Consultant. Mr S Howard Principal Consultant BRE Testing Garston WD25 9XX T + 44 (0) F + 44 (0) E enquiries@brecertification.co.uk This report may only be distributed in its entirety and in accordance with the terms and conditions of the contract. Test results relate only to the items tested. We have no responsibility for the design, materials, workmanship or performance of the product or items tested. This report does not constitute an approval, certification or endorsement of the product tested. This report is made on behalf of BRE Testing. By receiving the report and action on it, the client accepts that no individual is personally liable in contract, tort or breach of statutory duty (including negligence). No third party has any right to rely on this report. Page 7 of 18
8 Page 8 of 18
9 Page 9 of 18
10 Page 10 of 18
11 Page 11 of 18
12 Page 12 of 18
13 Page 13 of 18
14 Page 14 of 18
15 Page 15 of 18
16 Page 16 of 18
17 Page 17 of 18
18 ==============REPORT ENDS============= Page 18 of 18
BRE Global Classification Report
BRE Global Classification Report Kingspan Ltd. BENCHMARK Engineered Façade system - Metallic Hook on Cassette. Classification of fire performance in accordance with BR 135: 2013 Annex B Prepared for: Kingspan
More informationBRE Global Test Report
BRE Global Test Report Classification of fire performance in accordance with BR 135: 2013 Annex B. Prepared for: Date: 02 July 2014 Report Number: 287129 Iso Systems and Aquarian Cladding Systems BRE Global
More informationBRE Global Classification Report
BRE Global Classification Report Kingspan Insulation Cladding system with a Terracota tile rainscreen. Classification of fire performance in accordance with BR 135: 2013 Annex B Prepared for: Kingspan
More informationBRE Global Classification Report
BRE Global Classification Report Classification of fire performance in accordance with BR135:2013 Annex B on a Kingspan BENCHMARK 80mm QuadCore TM Karrier & Dri Design Cassette system. Prepared for: Kingspan
More informationBS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system. Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA
BS8414 Part 1: 2002 Test on a Phenolic Insulated Rainscreen system Prepared for: Kingspan Insulation Ltd Pembridge Leominster Herefordshire HR6 9LA 8 December 2005 0578 Page 1 of 16 Prepared on behalf
More informationBS :2005 test on a Kingspan Benchmark External Wall Insulation System
BS 8414-2:2005 test on a Kingspan Benchmark External Wall Insulation Prepared for: Kingspan Ltd. Carrickmacross Road Kingscourt County Cavan Ireland 7 September 2011 0578 Page 1 of 30 Prepared on behalf
More informationClassification report for roofs/roof coverings exposed to external fire in accordance with BS EN : 2005+A1:2009
ification report for roofs/roof coverings exposed to external fire in accordance with BS EN 13501-5: 2005+A1:2009 Prepared for: Flex-R Ltd Unit 5 Central Park Bellfield Road High Wycombe Bucks HP13 5HG
More informationBRE Global Classification Report
BRE Global Classification Report Classification of fire performance in accordance with BR 135: 2013 Annex A for a ventilated façade system with Kingspan Kooltherm K15 insulation and Alpolic/fr panels.
More informationBRE Global Assessment Report
BRE Global Assessment Report An assessment of the fire performance of the Gebrik Insulating Brick Cladding System against BR 135, Third Edition Prepared for: Date: 13 April 2016 Aquarian Cladding Systems
More informationBRE Global Test Report
BRE Global Test Report BS 8414-2: 2005 Test on a Kingspan BENCHMARK 220mm QuadCore TM Wall liner panel with a Corium brick system. Prepared for: Kingspan Ltd Date: 7 th November 2016 Report Number: P102340-1000
More informationBRE Global Test Report
BRE Global Test Report BS 8414-2 : 2005 Test on a Gebrik Rainscreen Cladding System Prepared for: Isosystems and Aquarian Cladding Systems Date: 21 September 2015 Report Number: P100838-1000 Issue 2 BRE
More informationBRE Global Test Report
BRE Global Test Report BS 8414-1:2015 + A1:2017 test on ventilated façade system with Kingspan (K15) thermal insulation and ACM panels Prepared for: Date: 18 January 2017 Mitsubishi Chemical Corporation
More informationBRE Global Test Report
BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ST, 50mm Prepared for: L Isolante K-Flex S.p.A. Date: 26 May 2015 Report Number: P100094-1003- BRE Global Ltd Watford, Herts
More informationBS 476: Part 3: 2004 test on SureSeal EPDM 1.2mm on a plywood deck
BS 476: Part 3: 2004 test on SureSeal EPDM 1.2mm on a plywood deck Prepared for: Flex-R Ltd Unit 5 Central Park Bellfield Road High Wycombe Bucks HP13 5HG 5 th December 2012 Test report number 281504B
More informationBRE Global Ltd Watford, Herts WD25 9XX. d+b facades (UK) Ltd. The Packway, Larkhill, Salisbury, SP4 8PY. Customer Services
BRE Global Test Report BS 8414-1:2015 + A1:2017 test on d+b facades rain screen cladding system with 100mm-thick Rockwool insulation and aluminium cassette panels. Prepared for: d+b facades (UK) Ltd. Date:
More informationLaboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights
Laboratory Airborne and Impact Sound Insulation of a Robust Details Appendix F Floor with PhotonStar LED Ltd. Downlights Prepared for: PhotonStar LED Group plc Unit 8 Westlink Belbins Business Park Romsey
More informationBRE Global Test Report
BRE Global Test Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Multi-Pro, Multi-Pro XS and Render Pro Prepared for: Resistant Building Products
More informationLaboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation. Prepared for:
Laboratory Airborne Sound Insulation of Stud Walls with Warmcel 500 Insulation Prepared for: Excel Industries Limited Maerdy Industrial Estate (South) Rhymney Gwent NP22 5PY 18 th June 2010 0578 Tested
More informationFaçade excellence for every building. An overview of the alsecco external wall insulation systems
Façade excellence for every building An overview of the alsecco external wall insulation systems Changing the face of the façade Monotonous façade design has now become a thing of the past. Representing
More informationACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS
Our Ref: MK1801 ACOUSTIC PERFORMANCE AND STC RATING OF A PARTITION WALL WITH DOUBLE SOCKETS AND POLYSEAM PUTTY PADS AUCKLAND UNISERVICES LIMITED a wholly owned company of THE UNIVERSITY OF AUCKLAND PROJECT
More informationAlsecco (U.K.) Ltd THE ALSECCO ECOMIN200 RAIL EXTERNAL WALL INSULATION SYSTEM
CI/SfB (21.9) Rn7 (M2) Alsecco (U.K.) Ltd THE ALSECCO ECOMIN200 RAIL EXTERNAL WALL INSULATION SYSTEM Certificate No 96/3247 DETAIL SHEET 6 Product THIS DETAIL SHEET RELATES TO THE ALSECCO ECOMIN200 RAIL
More informationLoad testing of a PVC coated handrail system. 25 th March Test report number
Load testing of a PVC coated handrail system 25 th March 2010 Tested on behalf of BRE by Names Julian Pettifer and Felix Ahatty Position Senior Technician and Junior Engineer, Actions, Building Technology
More informationTesting of Three Ply Floor Protection Product Tensile and Tear Strength
Testing of Three Ply Floor Protection Product Tensile and Tear Strength Prepared for: Mr Maged Elias Best Choice Floors Protection Manufacturing LLC P.O. Box 81161 Dubai U.A.E 5 July 2010 Page 1 of 8 Prepared
More informationAn assessment of the fire performance of Sanders Fire-Rated Mortar penetration seal systems
An assessment of the fire performance of Sanders Fire-Rated Mortar penetration seal systems Prepared for: Sandersfire International Limited Hamlyn House 4 Beadles Lane Old Oxted Surrey RH8 9JJ 16 July
More informationBRE Global Client Report
BRE Global Client Report BS 8414-1:2015 + A1:2017 test referred to as DCLG test 1. Prepared for: DCLG Date: 27th July 2017 Report Number: B137611-1037 (DCLG test 1) Issue: 1.0 BRE Global Ltd Watford, Herts
More informationBRE Global Classification Report
BRE Global ification Report ification report for roofs/roof coverings exposed to external fire in accordance with EN 13501-5: 2005 + A1:2009 on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a
More informationBRE Global Test Report
BRE Global Test Report BS 476-7: 1997 Surface spread of flame test on K-Flex ECO + ALU Prepared for: L'Isolante K-Flex S.p.A. Date: 24 April 2015 Report Number: 261123 BRE Global Ltd Watford, Herts WD25
More informationBRE Global Test Report
BRE Global Test Report Ad-hoc fire resistance test on a galvanised steel Tunnel Ventilation Damper employing procedures and criteria from BS 476: Part 20 : 1987. Prepared for: Betec Cad Industries Date:
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 External fire exposure to roofs test on Flexitec 2020 on 9mm Masterboard calcium silicate base Prepared for: Res-Tec Ltd Date: 03 November 2017 Report Number:
More informationTest Report: Fire resistance test in accordance with BS EN :1999 on a nonloadbearing. incorporating Scolmore Doubled Switched electrical sockets
Test Report: Fire resistance test in accordance with BS EN 1364-1:1999 on a nonloadbearing wall incorporating Scolmore Doubled Switched electrical sockets Prepared for: Scolmore International Limited,
More informationBRE Global Classification Report
BRE Global Classification Report Classification of reaction to fire performance in accordance with EN 13501-1: 2007 + A1: 2009 on Vitracore G2 Prepared for: Valcan Limited Date: 12 December 2016 Report
More informationDesign No. HI/BP PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table 1
FIRESTOP JOINT SPRAY CFS-SP WB SILICONE JOINT SPRAY CFS-SP SIL F-RATING 2-HR. 2-HR. T-RATING -HR. -HR. APPLICATION THICKNESS PERIMETER FIRE BARRIER SYSTEM Hilti, Inc. ASTM E 2307 Table /8" WET FILM (/6"
More information8414-1: A1:2017
www..co.uk RE Global Client Report BS 8414-1:2015 + A1:2017 Test referred to as DCLG test 7. Prepared for: Date: Report Number: DCLG 18th August 2017 B137611-1037 (DCLG test 7) Issue: 2.0 BRE Global Ltd
More informationCALL TO TALK TO THE SAS TEAM
CALL 01647 24620 TO TALK TO THE SAS TEAM new EIFS.indd 1 1 8/29/2013 11:21:00 AM Contents Insulation overview Page 4 ProRend EIFS Adhesive System Installation Page 6 ProRend EIFS Rail System Installation
More informationBRE Global Test Report
BRE Global Test Report BS 6853: 1999 Incorporating Amendment No. 1 tests to specific requirements of Table 5 on Controltac 180 on 3mm Aluminium coated with EP300/Hydro Topcoat (Axalta, dft 100µm) Prepared
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited
More informationWind uplift testing on the Click Fit PV mounting system to MCS012. Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd.
Wind uplift testing on the Click Fit PV mounting system to MCS012 Prepared for: Gary Bowden Cleaner Air Solutions UK Ltd 4 th October 2010 Prepared by Name Dr P Blackmore Position Associate Director, Building
More informationBRE Global Assessment Report
BRE Global Assessment Report An assessment of the fire performance of FireWizard intumescent acrylic sealant/nor-coustic Acoustic Fire Rated Mastic Prepared for: Norseal Limited Date: 10 November 2015
More informationBRE Global Test Report
BRE Global Test Report BS 476: Part 3: 2004 + A1: 2006 + A2: 2007 External fire exposure to roofs test on SolFit Top Loader. Prepared for: SolFiT Ltd Date: 19 November 2016 Report Number: P105772-1000
More informationBRE Global Test Report
BRE Global Test Report BS 476-6: 1989 + A1: 2009 Fire propagation test on K-Flex ST, 19mm Prepared for: L'Isolante K-Flex Srl Date: 26 November 2015 Report Number: 266234 Issue: 2 BRE Global Ltd Watford,
More informationBRE Global Test Report
BRE Global Test Report CEN/TS 1187: 2012 Test 4 External fire exposure to roofs test on Sarnafil G410-12 EL membrane over SarnaTherm G/TR27 on a Plywood deck Prepared for: Sika Limited Date: 05 January
More informationCHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES. Chapter 10
CONTENTS 10.1 PLASTERWORK 10.2 SECOND AND THIRD FIX FINISHES 283 Chapter 10 FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 10.1 PLASTERWORK Workmanship i. All workmanship must be within the tolerances
More informationRainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres
01473 820850 celotex.co.uk Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres 1 Rainscreen Cladding Compliance Guide Compliance Guide This document provides
More informationWeathertightness test to BS 6375: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, single door with side screen
Weathertightness test to BS 6375: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, single door with side screen Prepared for: Mr. Dale Pegler Beaufort Secure Design Ltd 19 October 2009 0578 Page
More informationCHAPTER 10: Finishes CONTENTS 10.1 PLASTERWORK ND AND 3 RD FIX FINISHES
CONTENTS 10.1 PLASTERWORK 10.2 2 ND AND 3 RD FIX FINISHES FUNCTIONAL REQUIREMENT 10.1 Plasterwork Workmanship Design Technical Manual TS-011-09-010412 i. All workmanship must be within defined tolerances
More informationInternal Partitions - Timber Studs Internal Partitions - Steel Stud
Timber Studs PH Internal Partitions - Steel Stud / hour fire rating, integrity and insulation in accordance with the criteria of BS : Part and AS 0: Part. Nominal thickness of partition: mm PROMATECT -H
More informationAn introduction to Part L U-values
December 2010 An introduction to Part L This document provides a wide selection of building fabric constructions with their associated. It has been produced a support to our publication An introduction
More informationBasement Board High Performance (HP) 70 and 100
Basement Board High Performance (HP) 70 and 100 Floor and Wall Insulation - Basements Basement Board HP is a closed cell expanded polystyrene (EPS) insulation board which makes it suitable for use below
More informationCertificate of Assessment
Certificate of Assessment Certificate Number: 159/13 Revision: 03 Kemsley Fields Business Park Sittingbourne Kent ME9 8SR is authorised to use the BRE Global Certification Mark in association with the
More informationCI/SfB (41) x M2 June 2005 EPS
CI/SfB (41) x M2 June 2005 EPS INNOVATION PermaRock is the leading name in external wall insulation (EWI) and architectural façade systems in the United Kingdom, having pioneered the development of external
More informationHOW TO: CREATE METAL PARTITIONS WALL LININGS AND CEILINGS GTEC FRAMES
HOW TO: CREATE METAL PARTITIONS WALL LININGS AND CEILINGS GTEC FRAMES 1 METAL OR TIMBER? When creating stud partitions, wall linings and suspended ceilings the traditional method of installation has been
More informationFIRESTOP JOINT SPRAY CFS-SP WB. 2mm (0.079") WET FILM ± 7.5 ± 5
Design No. CEJ 27 P (HI/JS 20-05) Table. CONCRETE FLOOR ASSEMBLY: Max. two-hour rated concrete floor assembly made from either lightweight or normal weight concrete with a density of 00-50 pcf, with a
More informationRIW LIQUID ASPHALTIC COMPOSITION Membrane étanche à l humidité Feuchtigkeitssperre. Regulations. Requirement: C2(a) Resistance to moisture Comment:
RIW Ltd Arc House Terrace Road South Binfield Bracknell Berkshire RG42 4PZ Tel: 01344 397777 Fax: 01344 862010 e-mail: technical@riw.co.uk website: www.riw.co.uk CI/SfB a Vs1 Agrément Certificate No 89/2278
More informationBuilding Regulations
Bluebird Fixings Limited Westminster Industrial Estate Station Road North Hykeham Lincoln LN6 3QY Tel: 01522 697776 Fax: 01522 697771 CI/SfB Xt6 Agrément Certificate No 93/2878 Second issue* Designated
More informationWeathertightness test to BS EN :2006 +A1:2010 clauses 4.2, 4.5 and 4.14 on a Smart Architectural Aluminium Alitherm 700 reversible window
Weathertightness test to BS EN 14351-1:2006 +A1:2010 clauses 4.2, 4.5 and 4.14 on a Smart Architectural Aluminium Alitherm 700 reversible window Prepared for: Mr. M. Walford Smart Architectural Aluminium
More informationCavity Drain Systems.
Grommet & Nail Platon Sealing Rope Sheet Piling Platon P8 Platon P8 Platon Cornerstrip Platon P20 Membrane Reinforced Concrete incorporating: Triton TT Super Admix @ 1.2Kg/100Kg OPC Sheet Piling PLATON
More informationGUARANTEED ASPHALT LIMITED
GUARANTEED ASPHALT LIMITED GuaraTEC Installation Guide Installing our fully bonded hot melt system. 2016 Barratt Homes, Osiers Road Guaranteed Asphalt Limited 2 Mercury Way, London, SE14 5RR, 020 7277
More informationRegulations Detail Sheet 1
Electronic Copy Monarflex Geomembranes Ltd Lyon Way St Albans Herts AL4 0LB Tel: 01727 830116 Fax: 01727 858998 CI/SfB (21) Ln9 Agrément Certificate No 00/3668 Designated by Government to issue European
More informationFire Rated Cladding Seals
Trade Name: Astro Clad Ventilated Fire Barriers Fire Rated Cladding Seals Creates a fire barrier within rainscreen cladding Suitable for ventilated cavities from 15mm Tested to BS 476Part 20 : BS EN 1363-1
More informationPRODUCT SUSPENDED. Rainscreen Cladding Compliance Guide When specifying Celotex RS5000 in buildings above 18 metres
01473 820850 celotex.co.uk Update - IMPORTANT: On 23 June 2017, in view of the focus on components of rainscreen cladding systems, Celotex stopped the supply of Celotex RS5000, pending further clarity.
More informationThe extra strong, extra durable, sound resistant system that you can direct fix to
C0 Partitions The extra strong, extra durable, sound resistant system that you can direct fix to All our systems are covered by SpecSure when using genuine Gyproc and Isover products gyproc.ie Utilising
More informationTitle: WF Report No: Prepared for: International Petroleum Products Ltd Bradwell Hall Bradwell-On-Sea Essex CMO 7HX. Date: 24 th August 2015
Exova Warringtonfire Holmesfield Road Warrington WA1 2DS United Kingdom T : +44 (0) 1925 655 116 F : +44 (0) 1925 655 419 E : warrington@exova.com W: www.exova.com Title: The fire resistance performance
More informationCERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED
CERTIFICATE OF APPROVAL No CF 563 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Forge Industrial Estate,
More informationWeathertightness test to BS 6375: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, Bi-folding/ sliding door with standard threshold
Weathertightness test to BS 637: Part 1: 2009 on a Beaufort Secure Design Ltd open outward, Bi-folding/ sliding door with standard threshold Prepared for: Mr. Dale Pegler Beaufort Secure Design Ltd 26
More informationCERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED
CERTIFICATE OF APPROVAL No CF 563 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of SIDERISE INSULATION
More informationKnauf Wall Liner. Head Track. Brackets. Wall Lining Stud. Fixings. Knauf Plasterboard. Floor Track. 98 Wall Liner
The Knauf Wall Liner System is extremely versatile and can be specified for application on masonry backgrounds with moderate irregularities between 20mm and 125mm. It can accommodate any of the range of
More informationFire Testing Laboratory
Fire Testing Laboratory Page 1 of 39 TEST REPORT for 2148 S. 41st Street Lousiville, KY 40211 Standard Fire Test Method for Evaluation of Fire Propagation Characteristics of Exterior Non-Load- Bearing
More informationPremier Coatings Ltd Marley Farm Smarden Ashford Kent TN27 8PJ Tel: Fax:
CI/SfB Premier Coatings Ltd Marley Farm Smarden Ashford Kent TN27 8PJ Tel: 01233 770663 Fax: 01233 770633 (13.9) Ln6 Agrément Certificate No 92/2789 Second issue* Designated by Government to issue European
More informationStone and Masonry Veneer
Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over
More informationTT Vapour Membrane Data Pack
Triton Systems TT Vapour Membrane Data Pack BS8102: 2009 "Code of Practice for the protection of below ground structures from water from the ground" Triton Contact Details: Triton Chemical Manufacturing
More informationWall Linings. As well as complete dry lining solutions we also provide fast-drying parge coat to ensure airtightness,
Wall Linings Our versatile range of wall lining systems makes it easy to produce a high-quality, high-performance finished wall regardless of the background. Whether your priority is acoustic control,
More informationCERTIFICATE OF APPROVAL No CF 563 SIDERISE INSULATION LIMITED
CERTIFICATE OF APPROVAL No CF 563 1 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of Forge Industrial Estate,
More informationReduce the risk of fire spread during construction of timber frame buildings *
make it better Reduce the risk of fire spread during construction of timber frame buildings * *For use in accordance with STA separation guidelines for buildings with total floor area > 600 sq. m. Outstanding
More information3M CS-195+ Composite Sheet Product Description
Product Data Sheet 3M Product Description 3M Fire Barrier is a one-part composite system comprised of four components. The heart of the system is an organic/ inorganic, fire-resistive elastomeric sheet.
More informationLoss Prevention Standards
Introduction External Wall Insulation (EWI) systems were initially developed in Europe after Word War II to retrofit solid masonry walls with insulation. The systems were introduced to North America during
More informationCavity fire barriers. Cavity fire barriers. Fire separation within concealed spaces. C06 Floors and ceilings
Fire separation within concealed spaces Regulatory requirements demand that cavities and concealed spaces, in the structure or fabric of a building, are sub-divided or sealed by means of cavity barriers
More informationBAKOR HOT-APPLIED MONOLITHIC STRUCTURAL WATERPROOFING SYSTEM BAKOR C HOT-APPLIED MONOLITHIC MEMBRANE DAMP-PROOFING SYSTEM
Bauder Ltd 70 Landseer Road Ipswich Suffolk IP3 1DH Tel: 01473 257671 Fax: 01473 230761 e-mail: mail@bauder.co.uk website: www.bauder.co.uk APPROVAL INSPECTION TESTING CERTIFICATION TECHNICAL APPROVALS
More informationTake a closer look at the real performance
BUILT TO FIT Take a closer look at the real performance and eliminate the performance gap with Gapotape Gapotape is a revolutionary new product that has been specifically designed to eliminate the performance
More informationTYVEK ROOF LINING SYSTEMS DUPONT AIRGUARD REFLECTIVE
DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 879770 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com APPROVAL INSPECTION
More informationThe Passive Fire Protection Handbook
The Passive Fire Protection Handbook The UK s comprehensive guide to passive fire protection Chapter Ceilings, Floors and Roofs AUGUST 0 The Passive Fire Protection Handbook Contents Chapter : Introduction
More informationC05. S03. P02 P08 FireWall
! This section includes updated information, added since it was first published in December 2015. Last updated 16/12/2016 C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05
More informationCERTIFICATE OF APPROVAL No CF 5345 BERGER PAINTS EMIRATES LTD CO (LLC)
CERTIFICATE OF APPROVAL No CF 5345 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of P.O. BOX 27524, Dubai,
More informationA Handbook of thermal bridging details incorporating aircrete blocks
A Handbook of thermal bridging details incorporating aircrete blocks Book 1 Thermal bridging solutions for external wall partial fill cavity details and full fill party wall details Prepared for the Aircrete
More informationP.O. Box ZN Bleiswijk Brandpuntlaan Zuid NZ Bleiswijk
P.O. Box 554-2665 ZN Bleiswijk Brandpuntlaan Zuid 16-2665 NZ Bleiswijk 088 3473 723 nederland@efectis.com Product 110 Envirograf Firoblock 110V15 penetration seal in a standard flexible supporting construction
More informationUL Design System HW-D-1012 continued
UL System No. HW-D-1012 Assembly Ratings 1, 2 and 3 Hr (See Item 2) Nominal Joint Width 3 in. Class II and III Movement Capabilities 100% Compression or Extension Page 1 of 5 1. Floor Assembly The fire-rated
More informationCELOTEX INSULATION CELOTEX RANGE OF PIR INSULATION BOARDS FOR TIMBER-FRAME DWELLINGS
Celotex Limited Lady Lane Industrial Estate Hadleigh Ipswich Suffolk IP7 6BA Tel: 01473 822093 Fax: 01473 820880 e-mail: technical@celotex.co.uk website: www.celotex.co.uk APPROVAL INSPECTION TESTING CERTIFICATION
More informationCERTIFICATE OF APPROVAL No CF 429 PROMAT UK LTD
CERTIFICATE OF APPROVAL No CF 429 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of The Sterling Centre,
More informationFIRE PROTECTION. GTEC Shaftwall systems 244 GTEC Shaftwall Stairwell systems 248 GTEC Horizontal Shaftwall systems 249 GTEC Encasement systems 250
FIRE PROTECTION GTEC Shaftwall range uses a specially designed system to protect voids and shafts in buildings. It resists pressure changes and enables installation from one side of the shaft only. GTEC
More informationIndependent twin frame high performance acoustic separating wall system
C04 Partitions Independent twin frame high performance acoustic separating wall system All our systems are covered by SpecSure when using genuine Gyproc and Isover products is a lightweight, non-loadbearing
More informationGypWall QUIET Acoustic separating wall system
Acoustic separating wall system 90 Al Mafraq Hospital, Abu Dhabi 0 R w db 90 0 mins is a lightweight, non-loadbearing, twin framed acoustic separating wall, primarily used as a sound resisting wall in
More informationC05. S03. P02 P08 FireWall
! This section includes updated information, added since it was first published in December 2015. Last updated 29/03/2018 C05. S03. P02 P08 Including C05. S01. P02 Specialist partitions introduction C05
More informationCLASSIFICATION OF FIRE RESISTANCE IN ACCORDANCE WITH BS EN : A1:2009
Page 1 of 11 CLASSIFICATION OF FIRE RESISTANCE IN ACCORDANCE WITH BS EN 1501-2:2007 + A1:2009 Sponsor: Notified body number: Product name: Classification report number: Kingspan Limited ISOCAB France SAS-France
More informationFire Test Report. Test Number 1243 Dated 22 September Prepared for:
SPECIALIST VENTILATION SERVICES Ltd Unit 11A, Greencroft Industrial Park Annfield Plain, Stanley, County Durham, DH9 7YB Tel: 01207 529333 Fax: 01207 529444 E-mail: sales@specialistventilation.com Fire
More informationJune Non - Residential New Build Partition walls
June 2010 Non - Residential New Build 4.6.3 Partition walls Non-residential new build 4.0 Non-residential New Build Partition Walls Contents Introduction find online page Solution optimiser and pathfinder
More informationGREENSPAN CLADDING SYSTEM AQUAPANEL EXTERIOR CEMENT BOARD SYSTEM
Greenspan Products Limited Ballyhahill Co Limerick Ireland Tel: 00 353 698 2222 Fax: 00 353 698 2226 e-mail: info@greenspan.ie website: www.greenspan.ie GREENSPAN CLADDING SYSTEM APPROVAL INSPECTION TESTING
More informationBRE Global Assessment Report
BRE Global Assessment Report An assessment of the fire performance of Suresnap Fire Collars fitted around plastic pipes penetrating concrete floors against the adopted criteria of BS 476: Part 20: 1987
More informationLight steel frame walls
Light Steel Frame Walls Light steel frame walls Solution optimiser and pathfinder Overview Light steel framing is extensively used due to its good thermal and structural behaviour. Heat loss reduction
More informationTYVEK ROOF LINING SYSTEMS PRODUCT SHEET 3 TYVEK SD2 AIR LEAKAGE BARRIER/VAPOUR CONTROL LAYER
DuPont de Nemours (Luxembourg) S.à r.l. Rue General Patton L-2984 Luxembourg Tel: 01275 879770 Fax: 01275 879773 e-mail: tyvek.construction@lux.dupont.com website: www.tyvekhome.com Agrément Certificate
More information