DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS

Size: px
Start display at page:

Download "DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS"

Transcription

1 The 20 th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, August 27 September 01, 2017 DESIGN OF ROTATING WHEEL DIP TEST SYSTEM FOR STANDARD TRACKING AND EROSION TESTING OF POLYMERIC INSULATORS J. V. Klüss 1* and J. Hamilton 1 1 Mississippi State University, 406 Hardy Road, Mississippi State, MS 39762, USA * joni@ece.msstate.edu Abstract: Surface tracking and erosion the irreversible degradation on the surface of an insulator can lead to significant increase in surface conduction ultimately leading to failure of an insulator. Polymeric insulation (non-ceramic insulators, NCI) have numerous advantages over traditional ceramic insulators, including superior hydrophobicity correlating to reduced surface leakage current. However, polymers are prone to degradation and aging resulting from electrical, chemical and environmental stress. Tracking and erosion tests expose test samples to artificial harsh environments to verify the suitability of insulator designs and materials (detect weaknesses) by applying continuous, cyclic or combined stresses. Various forms of tracking and erosion testing exist incline plane (IEC 60587), spray (method 1) or rotating wheel dip tests (RWDT, method 2). Numerous standards such as CSA C310-09, ANSI/NEMA C29.13 and IEEE Std. C37.41, and IEC define the required conditions and procedures for rotating wheel dip tests saline solution, voltage stress, exposure cycles, recovery periods, etc. However, instructions for how to build such setups are not given. The Mississippi State University High Voltage Laboratory is constructing four independent setups for different insulator types and voltage ratings. Simplicity of design and cost effectiveness are priorities. This paper presents the components, configurations, and alternatives for constructing a cost effective stand-alone RWDT system for tracking and erosion testing of NCIs as well as compares the procedures and acceptance criteria presented in various standards. 1 INTRODUCTION In some parts of the world, contamination is the dominant design criterion, dictating the design of line or substation insulation. Contamination flashover requires sufficient deposit (contaminant) on the insulator surface as well as moisture. The contamination by itself does not create a problem, but the mixture of contamination and moisture produces an electrically conducting layer on the insulator surface. Depending on the insulator design, current may concentrate in localized areas resulting in increased surface heating and the formation of a dry band (localized dry region). These dry areas interrupt the current thus forming a voltage across them. Once voltage increases sufficiently high, flashover occurs across the bands and eventually bridges across the entire insulator. [2]. Contamination flashover can be mitigated by improving insulator designs as well as material properties. Ceramic insulators are made from arc resistance material, with excellent internal strength, and immunity to ultraviolet (UV) radiation. For ceramics, the main parameter of contamination performance is creepage (leakage) distance high leakage distance improves performance. Polymer insulators (composites) are not as arc resistant as ceramics and are affect by UV radiation. However, better contamination performance, lighter weight, high flexibility, less maintenance, resistance to vandalism, and easy manufacturability to long lengths makes them a desirable option when selecting insulators for outdoor applications [2]. Ceramics have a well-known performance history and are considered reliable and long lasting. Failures are typically related to incorrect manufacturing process, poor raw materials, or improper application. Non-ceramic insulators (NCIs) were first introduced in the 1960s and experienced a range of different problems related to inappropriate housing materials and manufacturing resulting in water penetration, hardware separation, chalking, tracking, erosion and UV damage. Technological advances in the 1980s resolved many of these issues and NCIs have seen extensive application within the last decades as replacements for suspension and post type ceramic insulators [1]. The first NCIs were made from epoxy and experienced problems outdoors and in contaminated environments. Now, the inner core is typically made from fiberglass providing mechanical strength and is surrounded by a polymer housing and sheds. One of the key characteristics affecting the contamination performance of NCIs is surface hydrophobicity (ability to repel water). As explained earlier, contamination flashover involves dry band arcing which develops due to heating and evaporation of conducting liquid paths. For surfaces with high

2 hydrophobicity, water forms individual beads or droplets. This formation of droplets inhibits leakage current (discontinuous current path) and the associated dry band arcing [1]. Exposure to surface discharge, corona, and chemicals reduces the hydrophobicity of polymer surfaces. Surface tracking refers to the process that forms irreversible degradation by formation of conductive paths (tracks) starting and developing on the surface of an insulating material [5]. Erosion refers to irreversible and non-conducting degradation of the surface of the insulator that occurs by loss of material [4]. As the outer layer s resistance to tracking and erosion under contaminated and wet conditions is of particular importance, most industry standards include tracking and erosion tests. 2 TRACKING AND EROSION IEC TR points out that tracking and erosion tests are not considered ageing tests as the test does not replicate real life degradation conditions nor does it accelerate conditions to provide a lifeequivalent test in a short time [4]. Instead, tracking and erosion tests are better described as screening tests used to detect weaknesses related to inadequate materials and designs. The transition from healthy insulation to failure is unpredictable and occurs rapidly. The time and speed of this transition is dependent on a number of parameters insulator material, design, and operating environment. The silicone surface (housing) on modern composite insulators has the ability to recover its highly hydrophobic surface state after it has been lost as a consequence of discharge. This is due to high and low molecular chains constantly breaking down and recombining. This restoration process is expected to last for the expected life of the insulator [1]. The shed material is significant in defining tracking and erosion resistance, but the shape of the sheds also has an influence in defining the leakage path. Thus, the tracking and erosion test should assess all of the aforementioned contributors. The test provides a general indication of the quality of the design and material with respect to the harsh (but not extreme) environment [4]. A number of different standardized tests for evaluating the erosion resistance of outdoor insulators exist, including e.g., the inclined plane tracking and erosion test (IPT), salt-fog test, and the rotating wheel dip test (RWDT). The rotating wheel test has several alternative configurations spray or dip. This paper provides the details for constructing the setup for dipping the insulator in a saline solution, hereafter referred to as the RWDT setup ( Method 2 in [6] or Tracking Wheel # 2 in [5]). 2.1 Standard Procedures The original tracking wheel test was introduced in the Canadian Electrical Association Light Weight Insulator Working Group CEA LWIWG-01 in 1991 [4]. The procedure called for applied voltage stress equivalent to 35 V/mm of leakage distance. The insulator sample was dipped into a NaCl solution of 1.40 g/l of water and allowed to drip. This process was repeated 30,000 without interruptions. To successfully meet the acceptance criteria, surface tracking, erosion to the core, and puncturing of the shed or housing was not allowed. In addition, every unit needed to pass a steep front impulse test and a power frequency voltage test. In later versions, a 24 hour rest period was introduced where the dip tank is empty (to allow for the hydrophobicity recovery mentioned earlier). Although the descriptions slightly differ between the different IEEE, ANSI/NEMA, IEC, CSA standards [2 5] as well as various national level standards (e.g., PN-EN [7]), the overall procedure today remains the same. A number of samples are selected for the test (two pairs of identical insulators as described in IEC or three samples as described in CSA, IEEE, and ANSI/NEMA). Each insulator is exposed to 30,000 cycles where one cycle consists of 4 periods (positions) energized period, cooling period, dip period, and drip period (Figure 1) Figure 1: The four positions (periods) within a complete cycle in the tracking and erosion test (rotating wheel dip test, RWDT). During the dip period, the insulators sample is submerged in a saline solution consisting of deionized water with 1.40 g/l (± 0.06) During the energizing period, power frequency voltage across the sample shall be:

3 35 V per millimeter of leakage distance (according to ANSI/NEMA C for composite deadends and CSA for polymeric cutouts) No less than 58% of the device s maximum rated voltage (according to ANSI/NEMA C for fuses and accessories) Creepage distance (in mm) divided by 28.6 (according to IEC TR for polymeric insulators). For all of the discussed standards, a maximum voltage drop of 5% is allowed when the test circuit is loaded with a resistive current of 250 ma. The cycle time is approximately 200 seconds. IEC and CSA present fixed 40 second stationary periods in each position with an approximate 8 second transition time between positions. ANSI/NEMA and IEEE defines the stationary periods as no less than 80% of the cycle time which is given as 200 ± 25 seconds. All, except EIC require a 24 hour rest period without the saline solution every 4 days. IEC and CSA (but not IEEE and ANSI/NEMA) requires the solution to be replaced weekly. Allowable maintenance periods vary between standards. IEEE and ANSI/NEMA allows up to 8 hours with the full cycle remaining valid (not included in the cumulative test time). IEC and CSA permit 1 hour interruptions as well as one 60 hour longer interruption. An additional testing time of three times the duration of this longer interruption needs to be added to the total duration. Thus, only considering the required 30,000 cycles with an approximate duration of 200 seconds as well as the mandatory 24 hour rest every 4 days, the approximate duration for the tracking and erosion test is 2083 hours (86.6 days, not including maintenance interruptions). As such, the construction of multiple test setups allowing for concurrent testing of different insulator types and classes (for example, prototype testing of a new product) considerably reduces the cumulative test duration. 2.2 Standard Acceptance Criteria The major differences between various standards is apparent in the acceptance criteria. IEC simply requires a resistance measurement after completing the full 30,000 cycles 1. Resistance is measured with a minimum of 1 kv DC with the 1 In fact, IEC has selected the 1000 hour salt fog test as the only standardized test in IEC applicable to all insulator types in place of the tracking wheel and 5000h (multiple stress) test. probes 5-10 mm apart. Measured resistance has to be greater than 2 MΩ. For composite insulators, erosion is not allowed to reach the core, nor is any puncturing of the shed or housing permitted. IEEE C37.41 requires measured resistance to be greater than 3 MΩ and CSA requires R > 1 MΩ. In addition to resistance measurements, both CSA and IEEE require a steep front impulse (1000 kv/µs) test as well as a power frequency test. The power frequency test compares the average flashover voltage with that obtained from an unconditioned reference sample, as well as subjects the conditioned samples to 80% of the reference flashover voltage for 30 minutes. Both standards also record the temperature immediately after removal of test voltage (10 C maximum allowable temperature rise with respect to reference samples). In addition to the aforementioned tests, IEEE C37.41 requires a lightning impulse withstand test at 80% of the sample s rating. IEEE C37.41 specifically states that pre-boiling the tested samples is not required. Similar to the other standards, the post-cycling evaluation in ANSI/NEMA C calls for a steep-front impulse voltage test and power frequency test as detailed in Clause 7.1 of that standard. However, Clause 7.1 refers to the Water Penetration Test which includes preconditioning of the samples prior to performing the steep front impulse and power frequency test. The preconditioning includes, measuring the hardness of the sample sheds before and after a 100 hour boil in 0.1% NaCl water mixture. 3 DEVELOPED RWDT SETUP As was mentioned earlier, multiple testing setups allowing for concurrent testing of different insulator types and classes significantly reduces total test duration when assessing a large batch of insulators. Although the procedure is the same for the various test samples, the design must allow for customization catering to varying test voltages, different insulator dimensions and shapes, as well as alternative cycling periods and transition durations. The discussed standards provide the testing procedures and acceptance criteria, but they do not define the test setup needed to stress the samples. A number of authors [8, 9] have presented experimental data obtained using RWTD setups but do not go into detail concerning their construction. Some construction details are available in [10-12] but involve programming of the rotating wheel (software). [7] presents an impressive assembly, but may not be the most economical construction. Mississippi State University High Voltage Laboratory (hereafter referred to as MSU) is constructing four RWDT setups. As such, the main criteria are focused on cost-effectiveness,

4 simplicity, and assembly from readily available resources. The goal is to allow for simultaneous testing of four difference classes or types of insulators. The different insulator types include, suspension type insulators (deadends), support (post) insulators, pin insulators, and fuse cutouts. The different types, as well as different classes within a particular type of insulator, all have different leakage distances. IEC TR for polymeric insulators restricts the creepage distance to mm for the samples to be tested. IEEE, CSA, ANSI/NEMA for cutouts and deadends do not include such a creepage range. The minimum leakage distances for distribution deadend insulators range from 355mm (class DS- 15) to 1190 mm (DS-69 kv) [6]. For 1190 mm leakage distance, the IEC would define the required voltage stress to be 1190/28.6 = kv. ANSI/NEMA calculates the corresponding value in a slightly different manner, but produces a similar voltage equal to kv. The typical expected cutouts to be tested at MSU are within 38 kv ratings. ANSI/NEMA C requires no less than 58% of the device s maximum rated voltage, which corresponds to 22 kv. Although ANSI/NEMA C for composite line post insulators requires the samples to be tested according ANSI C29.11 Clause 7.3, which is a spray method (not RDWT) [14], if one were to perform the RDWT on post insulators, class samples with creepage distance equal to 1346 mm would require a voltage stress of approximately 47 kv. Overall, the typical samples to be tested would require a maximum AC voltage stress of 50 kv. In general, approximate clearances for AC-voltage (50/60 Hz) range kvrms/m where 150 kvrms/m could be used as an average approximation [13]. Thus, for the expected maximum stress of 50 kv, minimum clearance between grounded and energized components in the constructed test setup must be approximately 30 cm. As the construction is highly inhomogeneous, this minimum clearance value should be increased further to avoid flashover. Simulations could be used to assess the detailed geometry or alternatively a sufficiently large margin added to the theoretical clearances. Field grading can also be used as needed. Along with creepage distance and the corresponding test voltage level, the height of the samples also dictates minimum dimensions for the test assembly. The tested samples must be completely submerged in the saline solution during the dip stage. For example, class DS-69 composite deadend insulators have a section length of 750 ± 75 mm. This defines the required depth of the saline solution tank. If regular off-the shelf containers are used (typically bathtub shaped), products with depths of 750 mm also have considerable width, thus increasing the total volume of the tank. As such, to minimize the volume of needed saline solution, a narrow rectangular tank should be used. One should nevertheless be careful not to make the tank too narrow to limit the available space for e.g., cutouts with the fuses and disconnector assemblies. As evident, the test sample characteristics (shape and size) are dominating variables in defining the dimension of the tracking and erosion test setup. 3.1 Components The design can be optimized using customized solutions but this option typically increases costs. As such, one priority in the MSU design was to implements as many standard products and commercially available materials as possible along with resources already available at the MSU High Voltage Laboratory. The constructed setup is shown in Figure 2. Figure 2: MSU design. A.) controller, B.) voltage and current display, C.) HV source and voltage divider, D.) HV electrode, E.) voltage control (variac), F.) cooling fan, G.) motor Frame Since different samples require different clearances, the frame is constructed from 1.5 x 1.5 T-slot aluminium extrusions allowing for easy adjustability while also providing the necessary mechanical support. Furthermore, the construct can be easily disassembled for storage when not in use. The T-slots also allows for convenient routing of wires.

5 3.1.2 Rotating Wheel Like the frame, the mounting wheel was designed to allow for adjustability. The custom designed wheel and mounts are milled from aluminium and allow for the use of different test specimens. The wheel is grounded and separated from the motor using a fiberglass (insulated) shaft to avoid any current flowing into the motor during the energization stage Contact Electrode Different samples (cutouts, deadends, etc.) require different contacts. The spherical electrode shown in Figure 3 is suspended using fiberglass guy strain insulators and has several degrees of freedom and convenient height adjustment allowing for a smooth but solid contact when the sample transitions into position Control Board A custom microcontroller board was initially designed for controlling the rotation of the wheel [15]. Upon further consideration, the control board was replaced by an off-the-shelf pulse controller in efforts to simplify the build. The pulse controller is bundled with a control software that allows the user to setup simple control algorithms, making the required cycling protocol easier to replicate. The protocol needs only to be initiated by the software e.g., using a laptop, after which the computer system can be disconnected and used to program the cycles for the other three RWDT systems. Thus, upon initiation of the cycling process, the system is genuinely a stand-alone test assembly. Each control cycle is determined by taking the steps per revolution, which is set on the stepper motor driver, and dividing by the number of test specimens attached to the wheel. The start and stop functions are also handled by the pulse controller. The pulse controller will hold the ON/OFF pin high, 5VDC, when the cycle is intended to progress and will pull the ON/OFF pin low, 0VDC, when the cycle ends. The original microcontroller board will be further developed and used for handling the safety interlock system, safety lighting, and other I/O needs Saline Solution Tank As mentioned earlier, a custom fit tank can be manufactured for the submersion of the samples to minimize the required volume of saline content. To reduce expenses, an off-the-shelf high-density resin water tank was selected for the MSU design. The composite material resists corrosion from the saline solution used in testing. The tanks of all four tracking and erosion setups are connected in series with a pump to drain the solution when needed. Figure 3: Flexible contact between sample and HV electrode Motor and Driver A commercially available high torque stepper motor with sufficient torque to rotate the wheel with the multitude of different test specimens was selected. A stepper motor allows for precise control of the rotations abiding to the varying standard transition time and stationary periods within a cycle. The MSU design utilizes a NEMA 34, 1700 oz-in bipolar torque, 2.5 A stepper motor selected based on its high torque rating enabling the testing of larger test specimens. To ensure compatibility, the stepper motor driver was selected based on the motor manufacturer suggestions Voltage Supply Expenses related to the procurement of four individual voltage supplies were averted by utilizing existing test transformers available at the MSU laboratory. Variable autotransformers (also commercial products) are used to regulate the voltage supply to the test samples. Capacitive voltage dividers are used to measure the applied voltage (suitable high voltage probes can also be utilized). Pearson coils monitor current. Digital displays present current and voltage values. Hand held multi-meters or other data acquisition units displaying values can also be used to observe the test voltage or alternatively digitizers (more costly) can be used to record waveforms. The HV components are all situated on top of the frame

6 behind Plexiglas for additional safety as well as minimising the dimensions of the construction (floor space). All of the transformers selected to supply adequate voltage stress within the varying sample classes are single phase dry type voltage transformers and have fairly similar dimensions and weight thus allowing all to be installed in a similar manner at the top of the construction behind the touch barrier. 3.2 Budget The total cost of the presented RWDT test system is approximately $2500 USD per assembly. This includes the frame, stepper motor, stepper motor driver, controller, control system power supplies, and machining of the mounting wheel. The cost of the entire assembly (without prior available resources) is approximately $4000 USD. The voltage supply and measurement system form the major cost associated with the construction of a tracking and erosion test assembly. These costs were minimized by using devices already available at the MSU laboratory. When designing the tracking and erosion test fixture, the need for making the design as economical as possible was a large factor as the need for testing multiple samples in parallel is required to keep the test program on schedule. 4 CONCLUSIONS The requirements and acceptance criteria may vary within different standard but the procedure for tracking and erosion is rather consistent. In order to find defective specimens, samples are exposed to four stages energization, cooling, dipping, and dripping. This cycle is repeated 30,000 times corresponding to a test duration of approximately 3 months. Multiple simultaneous test assemblies would considerably reduce the total testing time for a large batch of different samples. To minimize construction costs, this paper presents a practical self-contained design assembled from common easily available components. The design, including the controller circuit is freely available for anybody to use for the construction of a tracking and erosion test setup suitable for their own needs. The first test trials with the presented design are pending upon arrival of test samples. REFERENCES [1] E. Kuffel, W.S. Zaengl, and J. Kuffel, High Voltage Engineering: Fundamentals, 2 nd Ed., Newnes, 2000, pp [2] A. R. Hileman, Insulation Coordination for Power Systems Marcel Dekker, 1999, pp [3] IEEE Std. C37.41, Design Tests for High- Voltage (>1000 V) Fuses and Accessories, [4] IEC/TR 62730, Technical Report HV polymeric insulators for indoor and outdoor use tracking and erosion testing by wheel test and 5000h test, [5] C310-09, Canadian Standards Association Distribution class polymeric cutouts, [6] ANSI/NEMA C29.13, American National Standard for Insulators Composite- Distribution Deadend Type, [7] T. Samborski, A. Zbrowksi, and S. Koziol, The system for testing the resistance to the surface discharge and erosion of the polymeric insulators, Prezeglad Elektrotechniczny, Vol. 88, No. 3a/2012, pp , [8] H. Ullrich, and S. Gubanski, Accelerated Laboratory Ageing of Model Insulator Samples with Semiconducting Glazes, International Symposium on Electrical Insulating Materials, Himeji, Japan, November 2001, pp [9] R. Tripathi, S. Grzybowksi, and R. Ward, Electrical Degradation of 15 kv Composite Insulator under Accelerated Aging Conditions, Electrical Insulation Conference, Ottawa, Ontario, Canada, June, [10] A. Muncivi, P. Sarkar, and A. Haddad, Tracking Wheel Test Facilities, 44th International Universities Power Engineering Conference (UPEC), Glasgow, United Kingdom, September, [11] A.S. Krzma, M. Albano, A. Haddad, Comparative Performance of 11 kv Silicone Rubber Polymeric Insulators under Rotating Wheel Dip Test, 49th International Universities Power Engineering Conference (UPEC), Cluj- Napoca, Romania, September, [12] A. Gazzola, Tracking Wheel Test for DC Polymeric Insulators, Thesis, Universita Degli Studi di Padova, [13] J. Kluss, and A. Dickerson, The Effect of Inhomogeneous Ambient Conditions on Air Clearances in High Voltage Laboratories, 35 th Electrical Insulation Conference (EIC), Baltimore, USA, [14] ANSI/NEMA C29.11, Composite Insulators Test Methods, [15] J. Hamilton, Tracking and Erosion Build, URL: last accessed: June 14, 2017.

Polymer Cutout Testing Recommendations

Polymer Cutout Testing Recommendations 1 Polymer Cutout Testing Recommendations High Voltage Fuse Subcommittee May 2012 Frank Lambert Recommended Tests 1. Water Diffusion Tests (CAN/CSA 310 09 7.3) 2. DyePenetration (ANSI C29.13 Section 7.3)

More information

Composite Insulator Components

Composite Insulator Components Composite Insulator Components Composite insulator components A composite insulator is made of at least two insulating parts a core and housing. It is equipped with end fittings. Core. The core is the

More information

Polymer Cutout Evaluation NEETRAC

Polymer Cutout Evaluation NEETRAC Polymer Cutout Evaluation NEETRAC Frank C. Lambert Georgia Tech / NEETRAC High Voltage Fuses Subcommittee Calgary, Alberta October 14, 2008 1 NEETRAC Members 2008-2009 1. 3M 2. ABB 3. ACA Conductor Accessories

More information

Polluted Outdoor Insulators Maintenance and Washing

Polluted Outdoor Insulators Maintenance and Washing Polluted Outdoor Insulators Maintenance and Washing Ali Naderian, PhD, PEng, SM IEEE Toronto, Canada February 2018 ali.naderian@ieee.org 1 برگزار کنندگان ایکهربا سامانه تجهیزات صنعت برق ایران کارشناسان

More information

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS

INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS INCLINED PLANE TESTS OF COMPOSITE, SILICONE RUBBER AND COMPOSITE SILICONE RUBBER COATED MATERIALS M N R Baharom 1*, Ian Cotton 1 1 School of Electrical & Electronic Engineering, The University of Manchester,

More information

Panagiotis Charalampidis

Panagiotis Charalampidis Textured Insulators for Overhead Lines and Substations I. INTRODUCTION Panagiotis Charalampidis High Voltage Energy Systems Group, School of Engineering, Cardiff University, The Parade, Cardiff CF24 3AA,

More information

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS

COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS COMPARATIVE LABORATORY PERFORMANCE CHARACTERISATION OF SILICONE RUBBER TEXTURED INSULATORS BY ADNAN SALAMA KRZMA B.SC., M.SC., ELECTRICAL ENGINEERING Thesis submitted to Cardiff University In candidature

More information

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test

Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test Ageing Deterioration of Silicone Rubber Polymer Insulator under Salt Water Dip Wheel Test J. Grasaesom, S. Thong-om, W. Payakcho and B. Marungsri* Abstract This paper presents the experimental results

More information

Development of Composite Line Spacers for Distribution Lines

Development of Composite Line Spacers for Distribution Lines Development of Composite Line Spacers for Distribution Lines Ichiro Sumitani / Toshiko Kurosawa TOKYO ELECTRIC POWER COMPANY 4-1 Egasaki-Cho, Tsurumi-Ku, Yokohama, 230-8510JAPAN Tel : +81 45 585 8561 Fax

More information

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications

Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 16th NATIONAL POWER SYSTEMS CONFERENCE, 15th-17th DECEMBER, 2010 687 Research methodology for the life evaluation of Hollow polymer insulators for High Voltage Applications 1. S.Farook, Research scholar,

More information

UNS 5kA Arrester. Certified Test Report IEC

UNS 5kA Arrester. Certified Test Report IEC CP No.: CP0504 Page 1 of 10 UNS 5kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators

HIGH VOLTAGE INSULATORS. By JP Holtzhausen. Glass. Bushings & hollow core insulators. Cap & pin insulators HIGH VOLTAGE INSULATORS By JP Holtzhausen The principal dielectric used on overhead power lines is air at atmospheric pressure. The air, surrounding the bare high voltage aluminium or steel- cored aluminium

More information

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R

Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R PAGE: 1 Test Requests: R18-01-03 Report Number: R18-01-03 Prototype Test Report ANSI C29.17 Quadri*Sil Line Post Insulators 2.5 Dia. Rod HPS Silicone rubber R18-01-03 Introduction: Sample Quadri*Sil line

More information

UHS 10kA Arrester. Certified Test Report IEC

UHS 10kA Arrester. Certified Test Report IEC CP No.: CP0606 Page 1 of 10 UHS 10kA Arrester Certified Test Report IEC 60099-4 2004 CERTIFICATION Statements made and data shown are, to the best of our knowledge and belief, correct and within the usual

More information

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION

EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION EXPERIMENTAL INVESTIGATION OF EFFECT OF UV RADIATION ON FLASHOVER VOLTAGE OF POLYMERIC INSULATORS WITH AND WITHOUT CONTAMINATION A. Majzoobi *, I. A. Joneidi, S. Mohajer, H.Mohseni and A. A. Shayegani

More information

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018

Evaluation Test Procedures for Distribution Crossarms. Southeastern Electric Exchange November, 2018 Evaluation Test Procedures for Distribution Crossarms Southeastern Electric Exchange November, 2018 What: Research, Testing and Applications Center in the School of Electrical & Computer Engineering at

More information

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions

Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various Pollution Conditions at Costal Regions Volume 114 No. 9 217, 1-9 ISSN: 1311-88 (printed version); ISSN: 1314-3395 (on-line version) url: http://www.ijpam.eu ijpam.eu Performance Analysis of 33 kv Polymer and Porcelain Insulators under Various

More information

Transmission Silicone Insulators Line Post 69 kv to 230 kv

Transmission Silicone Insulators Line Post 69 kv to 230 kv K-LINE INSULATORS LIMITED Catalogue T-LP Transmission Silicone Insulators Line Post 69 kv to 230 kv ISO9001 SAI GLOBAL FILE No. 000117 Transmission Silicone Insulators Line Post Today transmission lines

More information

Performance investigation of composite and RTV SIR coated insulators at a coastal test station

Performance investigation of composite and RTV SIR coated insulators at a coastal test station Performance investigation of composite and RTV SIR coated insulators at a coastal test station K. Siderakis High Voltage Laboratory, Technological and Educational Institute of Crete D. Pylarinos High Voltage

More information

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated

PART MATERIAL REMARK Metal Case with Pig-tail. Brass (Metal Case) Copper (Pig-tail) Star Contact Copper Silver Plated 1. SCOPE This specification defines the technical requirements of TZ-D series thermal-link with PROFFUSE brand that are produced according to IEC 60691, UL 60691,GB 9816. 2. APPLICABLE STANDARDS IEC 60691,

More information

INSULATOR REQUERIMENTS:

INSULATOR REQUERIMENTS: 2017 INMR WORLD CONGRESS SITGES-BARCELONA, INSULATOR REQUERIMENTS: DESIGN CRITERIA, OPERATION PARAMETERS AND STANDARDS REVIEW JAVIER GARCÍA TECHNICAL AND PRODUCTION MANAGER CONTENTS q INTRODUCTION q MECHANICAL

More information

GROUP A. Polymeric Insulators.

GROUP A. Polymeric Insulators. GROUP A Polymeric Insulators PYUNGIL Bldg., 1475-10, Gwanyang 2-dong, Dongan-gu, Anyang-si, Gyeonggi-do, 431-808, Korea Tel : 82-31-420-6650~3 FAX : 82-31-424-7300 www.pyungil.com Silicone Railway

More information

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia.

Reprinted from the Proceedings of the 2001 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. Copyright 21 IEEE. Reprinted from the Proceedings of the 21 IEEE/PES Transmission and Distribution Conference and Exposition, Atlanta, Georgia. This material is posted here with permission of the IEEE.

More information

Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators

Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators Effect of Some of Climatic Conditions in the Performance of Outdoor HV Silicone Rubber Insulators By Abdelbaset Shaban Nekeb Thesis submitted to Cardiff University in candidature for the degree of DOCTOR

More information

Polymer Suspension Insulators 69kV to 765kV

Polymer Suspension Insulators 69kV to 765kV CATALOG Polymer Suspension Insulators 69kV to 765kV NGK Locke Polymer Insulators, Inc. Virginia Beach, Virginia, U.S.A. TABLE of CONTENTS Table of Contents... 1 Design Features... 2 Material... 2 Definition

More information

PS2: Lifetime management, deterioration and ageing of substation equipment

PS2: Lifetime management, deterioration and ageing of substation equipment PS2: Lifetime management, deterioration and ageing of substation equipment Ageing and deterioration of composite post insulators exposed to high electric field in 220 kv and 400 kv switchyards in Swedish

More information

ENGINEERING SPECIFICATION EE SPEC

ENGINEERING SPECIFICATION EE SPEC /. Company Directive ENGINEERING SPECIFICATION EE SPEC : 84/1 Relating to Surge Arresters EE SPEC : 84/1 20 December 2013-1 of 7 - IMPLEMENTATION PLAN Introduction This document defines the surge arresters

More information

SECTION FIELD PANELS

SECTION FIELD PANELS Stanford University Facilities Design Guidelines SECTION 25 14 23 FIELD PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section includes control panel and enclosure requirements for building control systems.

More information

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer

APEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape

More information

fire Charcoat Charcoat IC Passive Protection

fire Charcoat Charcoat IC Passive Protection Charcoat fire Protection Passive insulator protection Coating for the protection of pollution flashover on exterior and interior high voltage insulators Charcoat IC General information CharCoat IC is a

More information

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester

Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester Artificial Accelerated Ageing Test of Silicone Rubber Housing Material for Lightning Arrester W. Payakcho, J. Grasaesom, S. Thong-om and B. Marungsri* Abstract This paper presents the experimental results

More information

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations

Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Predicting Contamination Flashover of Insulators: Successes and Shortcomings of Tests and Simulations Ravi S. Gorur and S. Venkataraman (Ph. D Student), Arizona State University Perhaps no single area

More information

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH

30-SDMS-01 SPECIFICATIONS FOR LOAD BREAK SWITCH SPECIFICATIONS FOR LOAD BREAK SWITCH This specification is property of SEC and subject to change or modification without any notice TABLE OF CONTENTS 1.0 SCOPE 3 2.0 CROSS REFERENCES 3 3.0 APPLICABLE CODES

More information

Energy Division Insulators

Energy Division  Insulators Energy Division http://energy.tycoelectronics.com Insulators R Insulators Tyco Electronics Energy Division covers a wide range of polymeric, hybrid and porcelain insulators. For decades all these products

More information

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators

Effect of UV-Rays and Salt Contamination on 33kV Silicon Composite Insulators IOSR Journal of Electrical and Electronics Engineering (IOSR-JEEE) e-issn: 2278-1676,p-ISSN: 2320-3331, Volume 11, Issue 6 Ver. II (Nov. Dec. 2016), PP 45-55 www.iosrjournals.org Effect of UV-Rays and

More information

Investigation of leakage current flow through wooden poles structures on overhead distribution system

Investigation of leakage current flow through wooden poles structures on overhead distribution system Proceedings of the 7th WSEAS International Conference on Power Systems, Beijing, China, September 15-17, 2007 120 Investigation of leakage current flow through wooden poles structures on overhead distribution

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTERNATIONAL STANDARD IEC 62217 First edition 2005-10 Polymeric insulators for indoor and outdoor use with a nominal voltage >1 000 V General definitions, test methods and acceptance criteria Reference

More information

Cigré WG C Topics: The selection of insulators with respect to polluted conditions

Cigré WG C Topics: The selection of insulators with respect to polluted conditions Cigré Guide for the selection of insulators with respect to contamination conditions Chris Engelbrecht: Convener Topics: The selection of insulators with respect to polluted conditions Present practise

More information

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled

ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS. Abdelrahman Khaled ESDD PREDICTION OF OUTDOOR POLYMER INSULATORS by Abdelrahman Khaled A Thesis Presented to the Faculty of the American University of Sharjah College of Engineering in Partial Fulfillment of the Requirements

More information

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators

NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators Version:- 3.1 Date of Issue:- June 2014 Page 1 of 13 NPS/003/015 Technical Specification for 33kV, 66kV and 132kV Post Insulators 1. Purpose This document is the technical specification for 33kV, 66kV

More information

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN

Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN 21, rue d Artois, F-75008 PARIS B3-115 CIGRE 2014 http : //www.cigre.org Selection between indoor or outdoor DC yards D. WU*, U. ÅSTRÖM, L. ARÉVALO, R. MONTAÑO, B. JACOBSON ABB HVDC SWEDEN SUMMARY In an

More information

Accreditation Scope by Certification Test Order

Accreditation Scope by Certification Test Order Organization NEMA MW 1000 NEMA RE-2 Section 4.11 ASTM D149 ASTM D150 ASTM D256 ASTM D257 ASTM D495 ASTM D570 ASTM D635 ASTM D638 ASTM D790 ASTM D882 ASTM D1653 ASTM D1676 ASTM D1822 ASTM D1830 ASTM D1876

More information

Characterisation of Textured Insulators for Overhead Lines and Substations

Characterisation of Textured Insulators for Overhead Lines and Substations Characterisation of Textured Insulators for Overhead Lines and Substations By Panagiotis Charalampidis A thesis submitted to Cardiff University in candidature for the degree of DOCTOR OF PHILOSOPHY High

More information

Cutouts and Fuse Links Equipment to protect against faults and over-current conditions on power distribution systems. Open-Type Cutouts Linkbreak Cutouts Loadbreak Cutouts Cutout-Arrester Combinations

More information

Shielding Effectiveness Measurement of EMI Gaskets and Flange Treatments Subjected to Salt Fog Exposure (20 x 20 Aperture)

Shielding Effectiveness Measurement of EMI Gaskets and Flange Treatments Subjected to Salt Fog Exposure (20 x 20 Aperture) CHO-TM201 July/1992 Shielding Effectiveness Measurement of EMI Gaskets and Flange Treatments Subjected to Salt Fog Exposure (20 x 20 Aperture) Prepared By: David C. Inman Test Service Technical Manager

More information

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES

SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES SERIES 800 / 810 SPECIFICATION 15KV & 25KV PADMOUNTED LIQUID-INSULATED VACUUM LOAD INTERRUPTER ASSEMBLIES MANUALLY OPERATED / REMOTELY OPERATED DEAD FRONT PADMOUNTED SWITCHGEAR WITH VACUUM LOAD INTERRUPTING

More information

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development

INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development INSULATION, ASSET AND WILDLIFE PROTECTION Steve Parker, Business Development MARKET FORCES THAT INFLUENCE RAYCHEM SALES PUBLIC UTILITY COMMISSIONS (System Reliability) SALES US FISH & WILDLIFE (Avian Electrocutions)

More information

Pins Insulator. Composite/Polymers Insulators

Pins Insulator. Composite/Polymers Insulators Composite/Polymers Insulators Electric network in India operates under very harsh environments. Industrial pollution, marshy land, hilly and unfriendly terrain, extreme weather, coastal region etc. make

More information

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS

FIBRE REINFORCED PLASTICS IN HIGH VOLTAGE APPLICATIONS FBRE RENFORCED PLASTCS N HGH VOLTAGE APPLCATONS Volker Bergmann, Reinhausen Power Composites GmbH Page 1 OVERVEW 1. ntroduction 2. Hollow core composite insulators and their application 3. Dielectric and

More information

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type

SPECIFICATION FOR 11 & 33kV COMPOSITE INSULATORS Part 1: Pin Type Doc. KPLC1/3CB/TSP/04/017/1 1 Page 1 of 7 TABLE OF CONTENTS 0.1 Circulation List 0.2 Amendment Record FOREWORD 1. SCOPE 2. REFERENCES 3. TERMS AND DEFINITIONS 4. REQUIREMENTS 5. TESTS AND INSPECTION 6.

More information

ReCoTec ROTAFIL COMPOSITE MATERIALS FOR HIGHEST ELECTRICAL AND MECHANICAL REQUIREMENTS.

ReCoTec ROTAFIL COMPOSITE MATERIALS FOR HIGHEST ELECTRICAL AND MECHANICAL REQUIREMENTS. ReCoTec ROTAFIL COMPOSITE MATERIALS FOR HIGHEST ELECTRICAL AND MECHANICAL REQUIREMENTS. P OW E R C O MP O S IT E S ReCoTec ReCoTec HIGH QUALITY MADE IN GERMANY. 2 BECAUSE GOOD IS NOT GOOD ENOUGH. The Reinhausen

More information

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS

A3-110 LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS 21, rue d'artois, F-75008 Paris http://www.cigre.org A3-110 Session 2004 CIGRÉ LONG TERM PERFORMANCE OF POLYMER HOUSED MO-SURGE ARRESTERS B. RICHTER*, W. SCHMIDT K. KANNUS, K. LAHTI ABB SWITZERLAND LTD.

More information

ELECTRICAL INSPECTION BULLETIN (Effective )

ELECTRICAL INSPECTION BULLETIN (Effective ) ELECTRICAL INSPECTION BULLETIN (Effective 2009-02-01) Rule 36-000 Customer Owned High Voltage Installations With the increase in customer own high voltage equipment there appears to be confusion over which

More information

ILMOS Insulator Leakage Current Monitor

ILMOS Insulator Leakage Current Monitor ILMOS Insulator Leakage Current Monitor Author: Eugenio Concha G Psptechnologies Inc. econcha@psptechnologies.com 1) Introduction increasing the leakage length of the insulators in the most vulnerable

More information

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1

Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 Effects of Creepage distance on Leakage Current of 220kV Long Rod Insulators at Different Severity Level of Salt Contamination Vijendra Singh Parihar 1, Prof. Anil Kumar Kori 2 1 PG Student 2 Associate

More information

Walk through the associated design considerations associated with transmission line design

Walk through the associated design considerations associated with transmission line design Walk through the associated design considerations associated with transmission line design Follow-up to Transmission Design 101 (2012) & Transmission Design 102 (2013) Additional design considerations

More information

New designed XLPE-insulated cables substituting paper-insulated pipe type cables

New designed XLPE-insulated cables substituting paper-insulated pipe type cables MODERN CABLE SYSTEMS IN STEEL PIPES New designed XLPE-insulated cables substituting paper-insulated pipe type cables Volker AUE, Nexans Deutschland Industries, Germany, Volker.Aue@nexans.com Wilfried ROSEBROCK,

More information

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv

DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv K-LINE INSULATORS LIMITED TORONTO, ONTARIO, CANADA Catalogue D-DS DISTRIBUTION SILICONE INSULATORS Deadend / Suspension 15 kv to 69 kv ISO9001 SAI GLOBAL FILE No. 000117 Distribution Silicone Insulators

More information

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator

Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Effect of Metal Ring on the Field Distribution of Outdoor Polymeric Insulator Veeresh A G Meenakshendra A Khamitkar MTech(Power System Engineering) MTech(Power System Engineering) SDM College Of Engineering

More information

Overview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications

Overview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications Overview of Silicone Elastomers, Gels & Auxiliary Materials for Cable Accessory Applications Authors: Dr. Jens Lambrecht, Dr. Konrad Hindelang Wacker Chemie AG Munich, Germany 1. INTRODUCTION The first

More information

Comparison of effects of Various Contaminations on SiR insulators

Comparison of effects of Various Contaminations on SiR insulators Volume 120 No. 6 2018, 609-620 ISSN: 1314-3395 (on-line version) url: http://www.acadpubl.eu/hub/ http://www.acadpubl.eu/hub/ Comparison of effects of Various Contaminations on SiR insulators Satheesh

More information

Diagnostic Techniques of Composite Insulators

Diagnostic Techniques of Composite Insulators Diagnostic Techniques of Composite Insulators to learn more - join CITI Those which are considered low cost turn into pricy. This statement applies to various aspects but in particular to power lines NCI

More information

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and

COASTAL INDIA. Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Supply & Application of: Epsilon Midsun 570 Gen-4 RTV HVIC (High Voltage Insulator Coating) and Epsilon Midsun 579 RTV Anti-Corrosion Coating In COASTAL INDIA Supply & Application of 8,000kg of Epsilon

More information

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan

Mitigating Contamination Related Issues on T&D Equipment. Lily Hoyer Simon Chan Mitigating Contamination Related Issues on T&D Equipment Lily Hoyer Simon Chan Substation Insulator Pollution Contamination Management PRESENTED BY LILY HOYER T&D ASSET MANAGEMENT ENMAX POWER CORPERATION

More information

15~35KV Termination Kit

15~35KV Termination Kit 15~35KV Termination Kit Luyon Corporation 21221 Western Ave., #210 Torrance, CA 90501, U.S.A. Advantages of Silicone Rubber Power Cable Accessories Feature of silicone rubber: Silicone rubber is a unique

More information

Data Sheet 110kV TD123II dry type outdoor termination

Data Sheet 110kV TD123II dry type outdoor termination 3 Data Sheet 110kV TD123II dry type outdoor termination 1. Product Description: 3M 110kV TD123II dry type outdoor termination meets requirement of test and product according to IEC60840 and GB11017.3,

More information

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages:

Journal of Operation and Automation in Power Engineering. Vol. 1, No. 2, Summer & Fall 2013, Pages: Journal of Operation and Automation in Power Engineering Vol. 1, No. 2, Summer & Fall 2013, Pages: 74-83 http://journals.uma.ac.ir/joape Impact of Pollution Location on Time and Frequency Characteristics

More information

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment

CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment CO 2 Cleaning and Its Effectiveness in Cleaning Energized Medium-Voltage Equipment Abstract This paper provides an overview of how CO 2 cleaning works on energized electrical equipment. It also presents

More information

Equipment Specifications Low Voltage. Active Harmonic Filter

Equipment Specifications Low Voltage. Active Harmonic Filter Equipment Specifications Low Voltage Active Harmonic Filter 1.0 General Description This section contains the design standards, general equipment type and configuration, components, product description,

More information

INSULATORS NEW. See page J-4 for more information.

INSULATORS NEW. See page J-4 for more information. INSULATORS INSULATORS NEW Improved 23613 Dead End/Suspension Insulator Salisbury s Improved 23613 Dead End/Suspension Insulator has aluminum end fittings. These new end fittings create a lightweight product

More information

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES

POLLUTION PERFORMANCE OF SILICONE AND EPDM INSULATOR PROFILES Clive LUMB 22/09/05 Originally presented to CIGRE C4.3.03, submitted to 36-WG11 to illustrate: Importance of insulating length Importance of worst case and best case testing of composites. 36-WG11/Paris/216

More information

TEMPERED GLASS INSULATORS

TEMPERED GLASS INSULATORS TEMPERED GLASS INSULATORS SUSPENSION-TYPE» Non-conducing support composed of an insulating glass piece and iron fittings allowing other units to be connected in series. A fastening iron fitting is included

More information

INTERNATIONAL STANDARD

INTERNATIONAL STANDARD INTENATIONAL STANDAD IEC 62217 First edition 2005-10 Polymeric insulators for indoor and outdoor use with a nominal voltage >1 000 V General definitions, test methods and acceptance criteria eference number

More information

Design Objective

Design Objective Design Objective 108-115096 Low profile 5A battery connector 2015.03.03 REV:A 1.0 Scope: 1.1 Content: This specification covers the requirements for product performance, test methods and quality assurance

More information

6C-001 High-Voltage Pin-Type Insulator

6C-001 High-Voltage Pin-Type Insulator DISCLAIMER: This translation may be used for reference purpose only. This English version is not an official translation of the original Japanese document. In cases where any differences occur between

More information

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle.

INSULATORS. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Industry photo: should be a the same image as larger industry photo. Either a different crop or different angle. Human photo. Can be environmental/ documentaty style or portrait of engineer. industry photo.

More information

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions

Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions Electr Eng (2018) 100:1729 1738 https://doi.org/10.1007/s00202-017-0652-x ORIGINAL PAPER Measurement of surface resistance of silicone rubber sheets under polluted and dry band conditions Arshad 1 A. Nekahi

More information

Leakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica

Leakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica Leakage Current and Carbon Track Analysis of LLDPE-Natural Rubber Blends Filled with Nano Silica F.L.Muhamedin, M.A.M.Piah, and N. F. Kasri Institute of High Voltage and High Current Faculty Of Electrical

More information

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions

Experimental analysis of hydrophobic characteristics of Silicone rubber (SiR) insulators under different climatic conditions International Journal of Physical Sciences Vol. 7(47), pp. 6162-6168, 16 December, 2012 Available online at http://www.academicjournals.org/ijps DOI: 10.5897/IJPS12.508 ISSN 1992-1950 2012 Academic Journals

More information

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS

PERFORMANCE ANALYSIS OF OVERHEAD PORCELAIN INSULATOR UNDER DIFFERENT CONTAMINATIONS International Journal of Mechanical Engineering and Technology (IJMET) Volume 8, Issue 10, October 2017, pp. 241 245, Article ID: IJMET_08_10_028 Available online at http://www.iaeme.com/ijmet/issues.asp?jtype=ijmet&vtype=8&itype=10

More information

Outdoor High Voltage Non-Ceramic Insulators

Outdoor High Voltage Non-Ceramic Insulators Outdoor High Voltage Non-Ceramic Insulators V.P. Karthika 1, P. Anitha 2, A. Hearty Rugesh 3 1 Teaching Fellow, 2 Assistant Professor, 3 UG Student 1, 2, 3 Department of EEE, Anna University, Thoothukudi

More information

MACLEAN POWER SYSTEMS

MACLEAN POWER SYSTEMS Engineering Test Report MacLean Power Systems Cumulative Crossarm Test Report For: PX, PW, PW-SPDE, PZ, PY Profiles Version: A Date: 1/27/14 Page 1 of 15 ABSTRACT A cumulative test report was assembled

More information

High Quality Porcelain Insulators for Transmission Lines

High Quality Porcelain Insulators for Transmission Lines Our Customers World Wide High Quality Porcelain Insulators for Transmission Lines 765kV KEPCO / KOREA Tangjin - Sin Ansomg 735kV H-Q / CANADA Manic - Churchill, James Bay 765kV PGCI / INDIA Kishenpur -

More information

SECTION A. NEC Compliance: Comply with NEC as applicable to installation and construction of electrical power/distribution transformers.

SECTION A. NEC Compliance: Comply with NEC as applicable to installation and construction of electrical power/distribution transformers. N 16461 DRY TYPE TRANSFORMERS PART 1 - GENERAL 1.01 WORK INCLUDED: A. Copper-wound transformer optimized for light loading, meeting US Department of Energy proposed Candidate Standard Level (CSL) 3 efficiency,

More information

PRY-MOULD. High Voltage Accessories for Extruded Cables

PRY-MOULD. High Voltage Accessories for Extruded Cables PRY-MOULD High Voltage Accessories for Extruded Cables Linking the future As the worldwide leader in the cable industry, Prysmian Group believes in the effective, efficient and sustainable supply of energy

More information

KEMA INSPECTION REPORT

KEMA INSPECTION REPORT KEMA INSPECTION REPORT 3190-15 Object Power cable system consisting of a single core power cable, outdoor termination, GIS termination and a joint 127/220 (245) kv 1x1000 mm 2 Cu XLPE Client GAON Cable,

More information

IAS Accreditation Number ELTEK International Laboratories

IAS Accreditation Number ELTEK International Laboratories IAS Accreditation Number TL-457 Company Name Address 248 Hughes Lane St. Charles, Missouri 63301 Contact Name Lisa Horner, Quality Manager Telephone +1 (636) 949-5835 Effective Date of Scope July 20, 2018

More information

The complete guide to transformers and packaged substations

The complete guide to transformers and packaged substations LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package

More information

BEHAVIOUR OF NANO SIO 2 FILLED SILICONE RUBBER NANOCOMPOSITESS

BEHAVIOUR OF NANO SIO 2 FILLED SILICONE RUBBER NANOCOMPOSITESS International Journal of Mechanical Engineering and Technology (IJMET) Volume 9, Issue 12, December 2018, pp. 575 584, Article ID: IJMET_09_12_0600 Available online at http://www.ia aeme.com/ijmet/issues.asp?jtype=ijmet&vtype=

More information

Electric field analysis of 132kV EPDM insulator and correlation with ageing features

Electric field analysis of 132kV EPDM insulator and correlation with ageing features 2013 Electrical Insulation Conference, Ottawa, Ontario, Canada, 2 to 5 June 2013 Electric field analysis of 132kV EPDM insulator and correlation with ageing features Antonios Tzimas, Christos Zachariades

More information

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents

Investigation of Chloride Ingress in Cracked Concrete Treated with Water Repellent Agents Hydrophobe V 5 th International Conference on Water Repellent Treatment of Building Materials Aedificatio Publishers, 299-310 (2008) Investigation of Chloride Ingress in Cracked Concrete Treated with Water

More information

MATERIAL SPECIFICATION FOR UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR LED TRAFFIC SIGNALS

MATERIAL SPECIFICATION FOR UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR LED TRAFFIC SIGNALS ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 2475 April 2017 MATERIAL SPECIFICATION FOR UNINTERRUPTIBLE POWER SUPPLY SYSTEMS FOR LED TRAFFIC SIGNALS TABLE OF CONTENTS 2475.01 SCOPE 2475.02

More information

Comparative Corrosion and Current Burst Testing of Copper and Aluminum Electrical Power Connectors

Comparative Corrosion and Current Burst Testing of Copper and Aluminum Electrical Power Connectors Copyright 5 IEEE. Reprinted from Industry Applications Conference, 5. This material is posted here with permission of the IEEE. Such permission of the IEEE does not in any way imply IEEE endorsement of

More information

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters

NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters Version:- 5.0 Date of Issue:- October 2017 Page 1 of 18 NPS/001/008 Technical Specification for Gapless Metal Oxide Surge Arresters 1. Purpose The purpose of this document is to detail the technical requirements

More information

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008

Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 Important Considerations for Specifying MV Mining Switchgear Western Mining Electrical Association Edmonton, Canada June 13, 2008 (Above 1000V and up to 38kV for Surface Mining) Key Components of Specification:

More information

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators

Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators Laboratory Investigation on Hydrophobicity and Tracking performance of Field Aged Composite Insulators N. Mavrikakis Faculty of Engineering Aristotle University of Thessaloniki nmavrika@auth.gr K. Siderakis

More information

Risk assessment of pollution on a 66kV composite insulator using ANSYS

Risk assessment of pollution on a 66kV composite insulator using ANSYS Risk assessment of pollution on a 66kV composite insulator using ANSYS Ms. N H M Netravati 1, Mrs. Sunitha N.S 2, Dr.Shivakumara Aradhya R.S. 3, Dr. K.N Ravi 4 M.Tech. student 1, Assistant Professor 2,

More information

Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm

Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm DATASHEET - CI45E-200-RAL7032 Delivery program Insulated enclosure, +knockouts, RAL7032, HxWxD=500x375x225mm Part no. CI45E-200-RAL7032 Catalog No. 090160 EL-Nummer (Norway) 2502339 Dimensions mm Product

More information

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines

Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission overhead lines :, Lr.4 iecii 2009 ITIITtM iim i Now TerMrrkçes âi Tims,rsGq, OeJj & ConTnuniatNo A. Critical design, testing and manufacturing features for the selection of high quality composite insulators for transmission

More information

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv)

General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators (63 kv- 400 kv) Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Substation Insulators

More information