BIM-MEP AUS PRACTICES

Size: px
Start display at page:

Download "BIM-MEP AUS PRACTICES"

Transcription

1 BIM-MEP AUS PRACTICES Issued By: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia Revision: Initial Release Date

2 Acknowledgements BIM-MEP AUS acknowledges the contributions of those organisations involved in the development and review of this document including principal contributors: A.G. Coombs Pty Ltd CSR Building Products Ltd D&E Air conditioning Pty Ltd Ductmakers Pty Ltd Fletcher Insulation Pty Ltd Insulation Council of Australia and New Zealand Kavanagh Industries Pty Ltd Knauf Insulation Pty Ltd Marshall Day Acoustics Pty Ltd Norman Disney & Young Pty Ltd Resonate Acoustics Australian Chamber of Commerce and Industry Formatting conventions In addition to standard text formatting for Section and Clause Headings, Table Headings, etc the table below shows other text formats that are used in BIM-MEP AUS Standards and reference documents and their application: Text Type Example Indicates Normal italicized text BIM Execution Plan The generic title for a type of document Bold italicised text BIM-MEP AUS Specification The name of a specific referenced document or standard or term Dark red text LOD First reference to a term or abbreviation that is defined in the website glossary under Practices Blue text Hyperlink/weblink Blue italicised text Explanatory notes Specification explanatory notes or reference information Green text Future Develop This indicates sections or requirements which are still under development but planned to be included within BIM-MEP AUS KEEPING BIM-MEP AUS UP-TO-DATE BIM-MEP AUS software and model content is regularly updated to reflect changes in legislation, technology and industry practice. Feedback and suggestions in relation to the standards via the BIM-MEP AUS website are welcome. Updates to software and content are managed and delivered through the BIM-MEP AUS website to registered BIM- MEP AUS users. LIABILITY DISCLAIMER BIM-MEP AUS makes no warranty, expressed or implied, including but not limited to any implied warranties of merchantability and fitness for a particular purpose, nor assume any legal liability or responsibility for the accuracy, completeness, or usefulness of the information in this document. In no event shall BIM-MEP AUS or its agents be liable for damages or losses resulting from your use of, or reliance on the information provided in this document. COPYRIGHT BIM-MEP AUS All rights reserved. BIM-MEP AUS Page 2

3 Table of Contents 1 INTRODUCTION Scope References Objectives MODEL WORKFLOW Model workflow Ductwork Systems, Services and Specifications Ductwork System Schematics Design Model Construction Model Commissioned As-Built Model RELEVANT STANDARDS DUCTWORK INSULATION DUCTWORK LININGS LINING AND INSULATION CODES General Codes Insulation Wrap /Lining Schedules DRAFTING STANDARDS...15 BIM-MEP AUS Page 3

4 1 INTRODUCTION 1.1 Scope This document sets out the BIM-MEP AUS specification for rigid ductwork linings and insulation wraps. The specification addresses: Ductwork internal acoustic and thermal insulation linings Ductwork external insulation wraps. Fire resistance systems including fire resistance wraps and sprays are nominated in the BIM-MEP AUS Fire Rated Ductwork Systems Specification. 1.2 References This specification should be read in conjunction with the following specifications and documents: BIM-MEP AUS Rigid Ductwork Specification this specification specifies the requirements for rigid rectangular and round ductwork for air handling systems; BIM-MEP AUS Fire Rated Ductwork Systems Specification this specification specifies the requirements for fire resistant ductwork; BIM-MEP AUS Airside Systems, Plant and Equipment Schedule this Excel based schedule provides the complete listing of ductwork systems, plant and equipment names as well as designation of ductwork system colours; BIM-MEP AUS Master Shared Parameter Schedule this document provides the reference for all shared parameter names used within the BIM-MEP AUS IFM and MCM models the Excel formatted schedule provides the Revit classification and GUID for each parameter; and BIM-MEP AUS Template Add-in this template provides the templated services for the insulation wraps and internal linings. These documents can be accessed through the BIM-MEP AUS website. 1.3 Objectives Benefits sought through the development and implementation of this specification include: A structured approach to the specification and modelling of ductwork lining and insulation requirements; Reliable and accurate Design-to-Fabrication workflows; and Industry standardization delivering improved supply chain efficiency, reduced project costs and risks. BIM-MEP AUS Page 4

5 2 MODEL WORKFLOW 2.1 Model workflow This standard supports the implementation of the Design to As-Built workflow that sees the progressive development of the MEP model through to an as-built status. The BIM-MEP AUS constructible Revit template add-in is intended to support a range of design and construction activities including system and engineering checks, construction planning, scheduling and BIM to Field workflows. BIM-MEP AUS design models nominate systems and services and whilst not providing shop drawing level detailing, are fully specified and constructible. BIM-MEP AUS Revit construction models provide construction level detailing and manufacturer s certified content suitable for approval submissions. The ductwork component of the model includes insulation and lining types and should be read in conjunction with the duct fabricators manufacturing specifications to determine code and design compliance. BIM-MEP AUS Commissioned As-Built Models incorporating any field installation changes provide the basis for future design and documentation of modifications to the installation and the ongoing management of accurate as-built records through the building s life cycle. Export of the constructible Autodesk Revit MEP ductwork model to the Autodesk Fabrication Suite allows the ductwork to be detailed for fabrication and site installation set-out. This process adds further detail to the model including: Piece marking Ductwork reinforcement and fabrication data Hanger and penetration site set outs. BIM-MEP AUS Page 5

6 2.2 Ductwork Systems, Services and Specifications A key feature of the BIM-MEP AUS approach to ductwork modelling is the use of defined ductwork systems, services and specifications. This approach draws from the Autodesk Fabrication approach to modelling and is important if the full potential of constructible Revit MEP modelling workflows are to be leveraged by designers and constructors. Systems define the type of reticulation system: Supply Air System, Smoke Spill System, Clean Air System, etc. Services set the system type, applicable specification and routing preferences. Specifications detail the quality standards for each ductwork, insulation and lining type. In BIM-MEP AUS the system and service must be selected to both model the system and nominate the required ducting, insulation and lining specifications. The use of this modelling approach provides significant benefits for downstream engineering validation, coordination and scheduling take-offs. 2.3 Ductwork System Schematics Ducting system design should begin with the system schematics and functional control strategies. These are key to conveying the design intent and are also the starting point for the modelling of the ductwork layouts. Best practice air side schematics convey the system architecture and include: Building compartmentation Smoke and fire rated walls Duct sizes and design flows Monitoring and control strategies. The BIM-MEP AUS template is not intended to generate the schematic from the design model. 2.4 Design Model The BIM-MEP AUS Revit Template allows engineers and modellers to design and specify systems using constructible ducting services. Design ducting service specifications are based on AS and connect plant, equipment and fittings to form complete systems. It is important that the ductwork and insulation be modelled by both system and service specification if it is to be fully leveraged within the Design to Commissioned As-built workflow. The use of BIM-MEP AUS constructible services allows a range of engineering checks and calculations to be completed with greater accuracy. The aim is to support the following engineering tasks: Design flow calculations; Estimation of design flow system pressure losses; and Review of ducting system specification compliance. BIM-MEP AUS Page 6

7 2.5 Construction Model The virtual build of the design model into the LOD 400 construction model generates a model that is suitable for approval submissions and includes all ductwork systems fully designated in terms of system type, service and specification. The development of the design model to the LOD 400 construction model typically involves a number of tasks: Breaking the ductwork into segment lengths; Value engineering to determine the most cost effective service and layout within specification; Changing-out of the design content with manufacturer s certified content for end of line plant and equipment such as fan coil units and fans; Checking option costs against original estimates and/or budget; Final services coordination and routing; and System engineering checks and finalisation of pressure loss calculations and fan selections. Once the construction model is finalized and required approvals received it is possible to convert the model to a Fabrication Model for: Procurement scheduling Final hanger layout and site layout Generation of CAM files for manufacture. 2.6 Commissioned As-Built Model The generation of the LOD 500 model from the approved LOD400 typically involves up-dating the model with BIM-to Field information returned from the field. BIM-MEP AUS Page 7

8 3 RELEVANT STANDARDS There are a number of requirements in the National Construction Code as well as Australian standards that relate to ductwork lining and insulation. Codes and standards referenced in this specification include: General Requirements NCC/ BCA : National Construction Code / Building Code of Australia Ductwork AS : Ductwork for air-handling systems in buildings - Part 2: Rigid duct. AS : The use of ventilation and air conditioning in buildings Part 1: Fire and Smoke Control in multi-compartment buildings AS : The use of ventilation and air conditioning in buildings Part 2: Mechanical Ventilation in buildings Insulation AS AS : Thermal Insulation of pipework, ductwork and equipment Selection, installation and finish : Thermal resistance of insulation for ductwork used in building air conditioning. AS/NZS : Materials for the thermal insulation of buildings - General criteria and technical provisions. Testing AS AS : Methods of fire tests on building materials, components and structures - Simultaneous determination of ignitability, flame propagation, heat release and smoke release : Methods for fire tests on building materials, components and structures - Fire-resistance test of elements of construction AS/NZS : Materials for the thermal insulation of buildings - General criteria and technical provisions UL : Factory-Made Air Ducts and Air Connectors BIM-MEP AUS Page 8

9 4 DUCTWORK INSULATION Insulation applied to the external surface of the ductwork serves the principal purposes of: reducing thermal energy gains or losses assuring system efficiency and uniform supply air temperature across a system, and minimization of condensation risk. Minimum ductwork thermal insulation performance is nominated by the BCA with the required R values determined by a combination of system type, climatic zone and ductwork location. For all zones, except Alpine Zone 8, the insulation requirements within the BCA have been aligned as set out in Table Table BCA Required Thermal R Ratings for insulation ratings (except Zone 8 Alpine) Ductwork Location R-Value Within a conditioned space 1.2 All other locations within the building envelope 2.0 Where exposed to direct sunlight 3.0 The BCA also requires that ductwork insulation: comply with the fire hazard properties set out in AS 4254 and AS1668.1, and for cold air ductwork systems, incorporate a vapour barrier on the outside surface of the insulation. To meet these requirements, the majority of ductwork insulation wrap products are manufactured from kg/m 3 glass wool with a foil facing providing the required vapour barrier. The glass wool insulation thickness required to achieve R1.2. is typically of the order of 38 to 40mm whilst for R2.0 the required thickness is generally 75mm. It is noted these insulation wrap products are not suitable for ductwork exposed to weather or sunlight and hence R3.0 insulation wrap is not typically available. Polyester wool provides an alternative product choice to glass wool with respect to the bulk insulation material, however it is noted that this product has a lower thermal resistance value and hence is typically thicker to achieve the required R value. Stone wool (Rockwool ) is a fully imported product and hence should not be specified except where the higher temperature rating of stone wool is required. BIM-MEP AUS Page 9

10 5 DUCTWORK LININGS Ductwork linings are applied to the internal surface of the ductwork and are typically used where: In-duct noise attenuation is required; and/or Ductwork is exposed to view and/or the weather. The use of internal lining impacts the ductwork fabrication to a significant extent and hence there is a need to integrate the lining specification with the ductwork manufacturing fabrication specifications. Ductwork lining thermal insulation values are nominated by the BCA with the required minimum R values determined by the system type, climatic zone and ductwork location. Table 5.1 BCA Required Thermal R Ratings for Internal Linings (except for Zone 8 Alpine) Location R-Value Within a conditioned space 1.2 All other locations within the building envelope 2.0 Where exposed to direct sunlight 3.0 The BCA also requires that ductwork insulation: comply with the fire hazard properties set out in AS 4254 and AS1668.1, and for cold air ductwork systems, incorporate a vapour barrier on the outside surface of the insulation. Ductwork linings for smoke spill and kitchen exhaust systems and sub-ducts are also required to be faced with perforated metal in order to comply with AS The preferred basis of design for ductwork internal linings is 32kg/m 3 glass wool. This product density provides tested acoustic performance that meets the majority of project requirements. The standard range of industry lining facings are: Heavy Duty Perforated Foil Continuous Acoustic Membrane preferred for general acoustic applications preferred where the surface is required to be cleaned and/or high levels of fibre containment are required. Representative Products include: Acoustituff (CSR - Bradford) VapaStop (Fletcher Insulation) Perforated Metal with Continuous Acoustic Membrane preferred for trafficable ductwork and/or where required for compliance with AS smoke exhaust and kitchen exhaust systems. BIM-MEP AUS Page 10

11 There are a number of proprietary facings that may also be suitable for specific applications, including Premium Acoustic Fabric ( such as CSR-Bradford Ultraphon ) Bonded Matt Face. It is noted that Mylar facings have been specified for clean room and kitchen exhaust systems in the past, however Continuous Acoustic Membranes products are now generally considered to provide a superior facing for these applications. Further details in relation to the specifications for these facings can be accessed through ICANZ member companies. BIM-MEP AUS Page 11

12 6 LINING AND INSULATION CODES 6.1 General BIM-MEP AUS ductwork linings and insulation specification codes are intended to meet the majority of project requirements. The BIM-MEP AUS coding system incorporates a number of default values that support product standardization and compliance, whilst not limiting opportunities for innovation. The following default values are noted within the coding system: Ductwork Acoustic Linings Standard glass wool density for internal linings: 32kg/m 3 Standard internal lining thicknesses: Ductwork External Insulation Wraps Standard glass wool density for external linings: 22kg. 50mm, 75mm and 100mm for R1.2, R2.0 and R3.0 respectively. Standard external insulation wrap thicknesses: 50mm or 75mm for R1.2 and R2.0 respectively Standard facing: Heavy Duty Foil Where a non-default insulation density or thickness are required - these appear as suffix codes. 6.2 Codes The BIM-MEP AUS codes are as follows Table Lining / Insulation Type Lining/Insulation Wrap Type Code External Insulation Wrap IW Duct Acoustic Liner AL Table Material Codes - Insulation Material Code Glass wool GW Polyester PE Stone Wool SW BIM-MEP AUS Page 12

13 Table Material Codes - Density Density kg/m 3 Code 18 18KG 22 22KG 24 24KG 32 32KG 48 48KG Note 1 : Default Values: For external insulation 22Kg/m 3 / For acoustic linings 32Kg/m 3. Table Facing Codes Facing Heavy Duty Perforated Foil Continuous Acoustic Membrane Perforated Metal / CAM Premium Acoustic Fabric Bonded Matt Face Facing Code HDP CAM PMM PAF BMF Table Lining and Insulation Thermal Resistance Codes and thicknesses Lining Thermal Resistance K m 2 /W Code Nominal Thickness mm 1.2 R1.2 50mm 2.0 R2.0 75mm 3.0 R mm Insulation Wrap Thermal Resistance K m 2 /W Code Nominal Thickness mm 1.2 R1.2 50mm 2.0 R2.0 75mm BIM-MEP AUS Page 13

14 6.3 Insulation Wrap /Lining Schedules The insulation wrap /lining scheduling syntax is as follows: INSULATION WRAP / LINING TYPE INSULATION MATERIAL TYPE, THERMAL RESISTANCE VALUE, FACING TYPE, DENSITY The following provides representative examples of scheduling syntax and codes for a number of industry standard insulation and lining services. IW-PER1.2 AL-GWR1.2CAM AL-GWR2.0PMM External insulation comprising 50mm thick 22kg/m 3 polyester wool faced with heavy duty foil to provide a material R value of 1.2 K m 2 /W Acoustic internal lining comprising 50mm thick 32kg/m 3 glass wool faced with continuous acoustic membrane to provide a material R value of 1.2 K m 2 /W Acoustic internal lining comprising 75mm thick 32kg/m 3 glass wool faced with heavy duty perforated metal with continuous acoustic membrane to provide a material R value of 2.0 K m 2 /W A representative example of scheduling code for a non-standard insulation and lining service is as follows. AL-GWR1.2CAM48KG Acoustic internal lining using 50mm thick special order 48kg/m 3 glass wool faced with continuous acoustic membrane to provide an overall R value of 1.2 K m 2 /W BIM-MEP AUS Page 14

15 7 DRAFTING STANDARDS The BIM-MEP AUS Template Add-In provides standard representations for internal linings and insulation wraps that combine established design and shop drawing practices to enable clear indication of the requirements at all points through the design to as-built workflow. The hatching type indicates the type of insulation wrap or lining as follows: External Insulation Wrap single hatch Internal Lining with non-perforated metal facing Internal Lining with perforated metal facing The requirements with respect to the insulation specification are coded noting that the IW or AL code is not required due to the use of the hatching indicating the type. Differentiation of the perforated metal lining requirement has been provided due to the significant impacts that this requirement has with respect to ductwork manufacture and cost. BIM-MEP AUS Page 15

BIM-MEP AUS SPECIFICATION Passive Chilled Beams

BIM-MEP AUS SPECIFICATION Passive Chilled Beams BIM-MEP AUS SPECIFICATION s Issued By: Revision: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia REV B Date Acknowledgements BIM-MEP AUS greatly acknowledges the contributions of the following

More information

BIM-MEP AUS MODELS. Damper Specification. Issued By: BIM-MEP AUS. 30 Cromwell Street, Burwood 3205 VIC Australia. Revision: Initial Release

BIM-MEP AUS MODELS. Damper Specification. Issued By: BIM-MEP AUS. 30 Cromwell Street, Burwood 3205 VIC Australia. Revision: Initial Release MODELS Issued By: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia Revision: Initial Release Date Acknowledgements BIM-MEP AUS greatly acknowledges the contributions of the following organisations

More information

BIM-MEP AUS SPECIFICATION Fan Coil Units

BIM-MEP AUS SPECIFICATION Fan Coil Units BIM-MEP AUS SPECIFICATION Issued By: Revision: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia REV A Date Acknowledgements BIM-MEP AUS greatly acknowledges the contributions of the following

More information

BIM-MEP AUS SPECIFICATION

BIM-MEP AUS SPECIFICATION BIM-MEP AUS SPECIFICATION Issued By: Revision: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia F Date Acknowledgements BIM-MEP AUS acknowledges the contributions of the Pump Industry Australia

More information

KINGSPAN KOOLDUCT SYSTEM. Product. Scope. Building Regulations. Appraisal No. 771 [2017]

KINGSPAN KOOLDUCT SYSTEM. Product. Scope. Building Regulations. Appraisal No. 771 [2017] KINGSPAN KOOLDUCT SYSTEM This Appraisal replaces BRANZ Appraisal No 771 (2012) s Technical Assessments of products for building and construction. Product 1.1 The Kingspan KoolDuct System is pre-insulated

More information

mass-loaded vinyl noise barrier composite SOUNDLAG SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com

mass-loaded vinyl noise barrier composite SOUNDLAG SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com mass-loaded vinyl noise barrier composite SOUNDLAG TM SOUNDPROOFING SOLUTIONS FOR ALL INDUSTRIES pyroteknc.com Acoustic treatment for noisy pipes The trend towards high-density living and lightweight building

More information

Ductslab and Ductwrap

Ductslab and Ductwrap Ductslab and Ductwrap For the thermal insulation of ductwork and water storage tanks ROCKWOOL provide thermal insulation for air conditioning, warm air and extract ducts used in the internal and external

More information

BIM-MEP AUS SPECIFICATION

BIM-MEP AUS SPECIFICATION BIM-MEP AUS SPECIFICATION Issued By: Revision: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia REV B Date Acknowledgements BIM-MEP AUS acknowledges the contributions of the contributors in the

More information

Sarking & Insulation Products A Blue Chip Company

Sarking & Insulation Products A Blue Chip Company Sarking & Insulation Products A Blue Chip Company [6] Contents [Brand Name] [] 3. 4. 6. 8. 10. 10. 11. 11. Company Overview Sarking & Breather Membrane Foam Insulation PIR Rigid Board Insulation Glass

More information

KOMBI PVA KOMBI PVA 1 CC

KOMBI PVA KOMBI PVA 1 CC KOMBI PVA ** Radius of bend Max. supply pressure *D= Ø internal nominal Flame retardant (categoria II) - 10 C +120 C 0 Pa PVC/ALUMINIUM combined flexible duct that combines the high mechanical resistance

More information

KOOLTHERM K12 FRAMING BOARD AND K15 RAINSCREEN BOARD BCA Certificate number: CM Date of issue: 15/08/2017. Date of expiry: 21/03/2020

KOOLTHERM K12 FRAMING BOARD AND K15 RAINSCREEN BOARD BCA Certificate number: CM Date of issue: 15/08/2017. Date of expiry: 21/03/2020 Certification Body: SAI Global Certification Services Pty Limited (ACN 108 716 669) Trading as SAI Global JAS-ANZ Accreditation No. Z1440295AS Address: 680 George Street, Sydney, NSW 2000 Website: www.saiglobal.com

More information

TECHWRAP2 AND TECHTUBE Acoustic solutions for pipework and equipment

TECHWRAP2 AND TECHTUBE Acoustic solutions for pipework and equipment TECHWRAP2 AND TECHTUBE Acoustic solutions for pipework and equipment TECHWRAP2 AND TECHTUBE Techwrap 2 and Techtube are high performance acoustic solutions for pipes and equipment. ROCKWOOL Techwrap2 and

More information

BIM-MEP AUS SPECIFICATION

BIM-MEP AUS SPECIFICATION BIM-MEP AUS SPECIFICATION Issued By: Revision: BIM-MEP AUS 30 Cromwell Street, Burwood 3205 VIC Australia REV D Date Acknowledgements BIM-MEP AUS acknowledges the contributions of the following organisations

More information

07 MECHANICAL 0745p FANTECH attenuators and acoustic louvres

07 MECHANICAL 0745p FANTECH attenuators and acoustic louvres 0745P FANTECH ATTENUATORS AND ACOUSTIC LOUVRES Branded worksection This branded worksection Template has been developed by NATSPEC in conjunction with FANTECH and may be used whilst the Product Partner

More information

Ductslab and Ductwrap

Ductslab and Ductwrap CONSTRUCTION TYPE: DUCTS AND TANKS Ductslab and Ductwrap For the thermal insulation of ductwork and water storage tanks ROCKWOOL provide thermal insulation for air conditioning, warm air and extract ducts

More information

EARTHWOOL GLASSWOOL INSULATION. Product. Scope. Building Regulations. Appraisal No. 648 [2016]

EARTHWOOL GLASSWOOL INSULATION. Product. Scope. Building Regulations. Appraisal No. 648 [2016] EARTHWOOL GLASSWOOL This Appraisal replaces BRANZ Appraisal No. 648 (2009) BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Earthwool glasswool insulation is

More information

Australian/New Zealand Standard

Australian/New Zealand Standard AS/NZS 4859.1:2002 (Incorporating Amendment No. 1) AS/NZS 4859.1:2002 Australian/New Zealand Standard Materials for the thermal insulation of buildings Part 1: General criteria and technical provisions

More information

RockLap H&V pipe sections

RockLap H&V pipe sections RockLap H&V pipe sections For rapid, efficient pipework insulation RockLap H&V Pipe Sections are strong lengths of pre-formed insulation with a one piece, factory applied foil facing with integral self-adhesive

More information

BIMMEP AUS MODELS. Mechanical Piping Services Specification. Issued By: BIMMEP AUS. 30 Cromwell Street, Burwood 3205 VIC Australia.

BIMMEP AUS MODELS. Mechanical Piping Services Specification. Issued By: BIMMEP AUS. 30 Cromwell Street, Burwood 3205 VIC Australia. BIMMEP AUS MODELS Issued By: BIMMEP AUS Revision: 0 Date October 2014 30 Cromwell Street, Burwood 3205 VIC Australia Acknowledgements BIMMEP AUS acknowledges the contributions of those organisations involved

More information

Construction. Sarnafil TS Polymeric membrane for roof waterproofing. Product Description

Construction. Sarnafil TS Polymeric membrane for roof waterproofing. Product Description January, 2009 Sarnafil TS 77-15 Polymeric membrane for roof waterproofing Construction Product Description Uses Characteristics / Advantages Approval / Standards Sarnafil TS 77-15 (thickness 1.5 mm) is

More information

e u g o l a t a C

e u g o l a t a C 2006 2007 Catalogue The Sisalation Story The Homebush plant commenced production on the 26th of October 1951. Originally a joint venture partnership between Australian company F.W. Williams and the American

More information

PRODUCT TECHNICAL DATA SHEET WEATHER PRO TM INSULATION JACKET

PRODUCT TECHNICAL DATA SHEET WEATHER PRO TM INSULATION JACKET PRODUCT TECHNICAL DATA SHEET WEATHER PRO TM INSULATION JACKET ALL WEATHER PROTECTIVE INSULATION JACKETING SYSTEM AUTHOR: CHRIS EVANS DATE: 17.02.2015 VERSION: 1.1 WORLD-CLASS INSULATION + PFP THE WEATHER

More information

Division 15 INSULATION Section 15100

Division 15 INSULATION Section 15100 Page 1 of 5 SECTION PAGE PART 1 GENERAL 2 1.1 General 2 1.2 References 2 1.3 Work Included 2 1.4 Related Work 2 1.5 Quality Assurance 3 PART 2 PRODUCTS 3 2.1 Description 3 PART 3 EXECUTION 3 3.1 Workmanship

More information

PRODUCT GUIDE T HERMOFOIL THERMOFOIL

PRODUCT GUIDE T HERMOFOIL THERMOFOIL PRODUCT GUIDE T HERMOFOIL THERMOFOIL Applications Product Benefits CSR Bradford THERMOFOIL Vapour and mechanical barrier for wrapping timber frames with brick veneer cladding. Breathable moisture and mechanical

More information

NRG Greenboard Insulated Wall Cladding System

NRG Greenboard Insulated Wall Cladding System Certificate number: CM30005 Rev11 Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global-mark.com.au Certificate Holder: MFT Holdings QLD Pty

More information

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds.

A. This Section includes duct and plenum insulation; accessories and attachments; and sealing compounds. SECTION 230713 DUCT INSULATION PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,

More information

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks.

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks. DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks. DUCTWRAP AND DUCTSLAB ROCKWOOL Ductwrap and Ductslab provide thermal insulation for air conditioning, warm air and

More information

Capital Projects Group Air Terminal Units Specification

Capital Projects Group Air Terminal Units Specification Capital Projects Group Air Terminal Units Specification Specification 23 36 00 Revision 0 Date: August 2018 Air Terminal Units Specification Specification 23 36 00 Publication Date: August 2018 COPYRIGHT

More information

SECTION AIR DISTRIBUTION

SECTION AIR DISTRIBUTION SECTION 15880 AIR DISTRIBUTION PART 1 GENERAL 1.1 SUMMARY A. This section describes minimum requirements, products and methods of execution relating to the project air distribution systems. PART 2 PRODUCTS

More information

SP FIRESTOP OSCB 60 & 120 Open-state cavity barrier only for use with RAINSCREEN DUO SLAB

SP FIRESTOP OSCB 60 & 120 Open-state cavity barrier only for use with RAINSCREEN DUO SLAB SP FIRESTOP OSCB 60 & 120 Open-state cavity barrier only for use with RAINSCREEN DUO SLAB SP FIRESTOP OSCB 60 & 120 Consisting of an advanced intumescent strip fixed to high density non-combustible ROCKWOOL

More information

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks.

DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks. DUCTWRAP AND DUCTSLAB For the thermal insulation of ductwork and water storage tanks. DUCTWRAP AND DUCTSLAB ROCKWOOL Ductwrap and Ductslab provide thermal insulation for air conditioning, warm air and

More information

Construction. Sarnafil G Felt. Polymeric membrane for roof waterproofing. Product Description

Construction. Sarnafil G Felt. Polymeric membrane for roof waterproofing. Product Description Roofing Product Data Sheet Edition 03.2012 Identification no: 02 09 05 05 215 0 120000/1 Version no. 01 Sarnafil G 410-12 Felt Polymeric membrane for roof waterproofing Construction Product Description

More information

Owens Corning Ecotouch RA Series Insulation

Owens Corning Ecotouch RA Series Insulation Owens Corning Ecotouch RA Series Insulation Owens Corning advantages with Ecotouch RA Series Insulation for Double Wall Spiral Ducts are: An Industry first in clearly naming and promoting and offering

More information

PRODUCT GUIDE ROCKWOOL INDUSTRIAL INDUSTRIAL ROCKWOOL

PRODUCT GUIDE ROCKWOOL INDUSTRIAL INDUSTRIAL ROCKWOOL PRODUCT GUIDE INDUSTRIAL ROCKWOOL Applications General purpose industrial insulation, including use on process equipment, vessels, tanks and reactors. Ideal for the power generation and petrochemical industries.

More information

GUIDE SPECIFICATION: DUCT LINER

GUIDE SPECIFICATION: DUCT LINER GUIDE SPECIFICATION: DUCT LINER This specification guide includes thermal & acoustical insulation for ductwork and air handling systems. This section is based on the format recommended by MICA (Midwest

More information

PJ BOWERS P/L ATF PJ Bowers Family Trust

PJ BOWERS P/L ATF PJ Bowers Family Trust PJ BOWERS P/L ATF PJ Bowers Family Trust PH. 07 5593 8277 FAX. 07 5593 8477 MOB: 0434 778 355 13 Central Drv, Burleigh Heads, Qld 4220. Web : www.pjbowers.com.au Email : terry@pjbowers.com.au The Secretary,

More information

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts.

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIRE DUCT SYSTEMS Rectangular and circular, single layer fire protection for steel ductwork. As part of

More information

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts.

FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIREPRO FIRE DUCT SYSTEMS Single layer fire protection for rectangular, circular and oval ducts. FIRE DUCT SYSTEMS Rectangular and circular, single layer fire protection for steel ductwork. As part of

More information

Earthwool Glasswool Insulation

Earthwool Glasswool Insulation Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global-mark.com.au Certificate Holder: Knauf Insulation Pty Ltd Unit 2 44 Borthwick Avenue Murarrie,

More information

Air Duct Board-M with Hydroshield Technology. Knauf Data Sheet AH-DS

Air Duct Board-M with Hydroshield Technology. Knauf Data Sheet AH-DS Air Duct Board-M with Hydroshield Technology Knauf Data Sheet AH-DS-6 08-06 Knauf Air Duct Board-M is faced with a tightly bonded black mat for greater airstream surface durability. Available in both EI-475

More information

FLEXITHERM Double layer with Graphite Core Insulation

FLEXITHERM Double layer with Graphite Core Insulation Technical Data Sheet Date March 2016 Replaces June 2014 FLEXITHERM Double layer with Graphite Core Insulation DESCRIPTION: Graphite core insulation is graphite enhanced expanded polystyrene insulation

More information

344 Edmonton Street, Winnipeg, Manitoba, Transport Canada Accommodation Fit-Up. Project No.: R September 13, 2016

344 Edmonton Street, Winnipeg, Manitoba, Transport Canada Accommodation Fit-Up. Project No.: R September 13, 2016 Public Works and Government Services Canada 344 Edmonton Street, Winnipeg, Manitoba, Transport Canada Accommodation Fit-Up Addendum No. 6 Page 1 of 2 Project No.: R.055495.003 September 13, 2016 The following

More information

Product Catalogue

Product Catalogue www.bluechipgroup.net.au Product Catalogue INSULATION PRODUCTS 4 INSULSARK Heavy Duty Sarking 6 8 INSULBLUE iboard C8 Foam Insulation Cavity Insulation Board 10 iboard S10 Soffit Insulation Board 12 iboard

More information

THIS TO CERTIFY THAT. FlameGuard

THIS TO CERTIFY THAT. FlameGuard Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: Metecno Pty Ltd ABN: 44 096 402 934

More information

ABOUT VITRADUAL KEY FEATURES

ABOUT VITRADUAL KEY FEATURES ABOUT VITRADUAL Manufactured by Fairview; Vitradual is a 3mm non-combustible aluminium cassette cladding system. Designed to complement our existing Vitracore G2; Vitradual forms part of Fairview s range

More information

ASI National Structural Steelwork Compliance Scheme. A Guide for Clients, Builders and Prime Contractors

ASI National Structural Steelwork Compliance Scheme. A Guide for Clients, Builders and Prime Contractors ASI National Structural Steelwork Compliance Scheme A Guide for Clients, Builders and Prime Contractors Version 2, 2017 USE OF THIS GUIDE This document is intended to be used by bodies responsible for

More information

ACOUSTIC BARRIERS DWX SERIES FOR DUCTWORK

ACOUSTIC BARRIERS DWX SERIES FOR DUCTWORK DWX SERIES ACOUSTIC BARRIERS FOR DUCTWORK A SOFT FLEXIBLE QUILT WITH AN OUTER HEAVY POLYMERIC ACOUSTIC MEMBRANE, OFFERING EXCELLENT DURABILITY AND SOUND INSULATION QUALITIES, THAT CAN BE USED IN A VARIETY

More information

Building Services Engineer (mechanical) model career pathway Version 1.0

Building Services Engineer (mechanical) model career pathway Version 1.0 April 2013 Building Services Engineer (mechanical) model career pathway Version 1.0 AIRAH Strategic aim #2 - Closing the skills gap Prepared by: The Australian Institute of Refrigeration Air Conditioning

More information

Acronem Consulting Australia Pty Ltd

Acronem Consulting Australia Pty Ltd Acronem Consulting Australia Pty Ltd Solutions Engineered Marketing Technical Literature New Product Development Structural Engineering Design Research Reporting Building Codes, Standards and Regulations

More information

The great Aussie shed deserves great Australian insulation

The great Aussie shed deserves great Australian insulation polyair unicell The great Aussie shed deserves great Australian insulation FULLY COMPLIANT TO THE BCA Extra heavy duty Commercial grade Australian made 15 year warranty Why choose Bradford Polyair Unicell?

More information

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION

DSC BUILDING 1200 ALTERATIONS OCTOBER 2011 SECTION DUCT INSULATION SECTION 230713 DUCT INSULATION PART 1 GENERAL 1.1 SUMMARY A. Related Sections: 1. 233113 Ductwork and Accessories 1.2 REFERENCES A. American Society for Testing and Materials (ASTM): 1. E84-96a Test Method

More information

SAFEBRIDGE HIGH PERFORMANCE ROOF INSULATION SYSTEM

SAFEBRIDGE HIGH PERFORMANCE ROOF INSULATION SYSTEM SAFEBRIDGE HIGH PERFORMANCE ROOF INSULATION SYSTEM Safebridge Key Benefits Creates a safer roof environment for workers during construction Code compliant with BCA/NCC Section J Uses the purlin space without

More information

K18 Insulated Plasterboard

K18 Insulated Plasterboard Insulation A4/8 K18 AW2203 Issue 11 Sep 2017 K18 Insulated INSULATED DRY-LINING PLASTERBOARD FOR MECHANICAL FIXING Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell insulation

More information

ASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional

ASF FR Board PRO RANGE Coated Mineral Wool Board for the Professional Technical Data Sheet Version: 1 Revision Date: 11-04-2011 Description ASF FR Board has been designed to maintain the fire resistance of separating walls and floors where they are breached by single or

More information

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation

Recommended Design Considerations. and. Guide Specifications For. Commercial Building Insulation Recommended Design Considerations and Guide Specifications For Commercial Building Insulation Date of Issue: October 1, 2004 Recommended Design Considerations and Guide Specifications For Commercial Building

More information

2017/12/8 SPECIFICATION 2017 VERSION 1.0 NANOSOX FABRIC AIR DISPERSION SYSTEM

2017/12/8 SPECIFICATION 2017 VERSION 1.0 NANOSOX FABRIC AIR DISPERSION SYSTEM 2017/12/8 SPECIFICATION 2017 VERSION 1.0 NANOSOX FABRIC AIR DISPERSION SYSTEM All rights reserved. Unless otherwise specified, no part of the following standards and specification may be reproduced or

More information

CSR Cemintel Territory Series Wall Cladding System

CSR Cemintel Territory Series Wall Cladding System Certificate number: CM30048 Rev4 Global-Mark Pty Ltd, Suite 4.07, 32 Delhi Road, North Ryde NSW 2113, Australia Tel: +61 (0)2 9886 0222 - www.global- Mark.com.au Certificate Holder: CSR Building Products

More information

Technical Submission Spiralite Pre-insulated Ductwork

Technical Submission Spiralite Pre-insulated Ductwork Technical Submission Spiralite Pre-insulated Ductwork This Spiralite technical submission and performance specification covers air-distribution HVAC ductwork systems and insulation requirements. It is

More information

K3 Floorboard. Insulation INSULATION FOR FLOORS

K3 Floorboard. Insulation INSULATION FOR FLOORS Insulation A4/6 K3 AW2385 Issue 7 Oct 2018 INSULATION FOR FLOORS K3 Floorboard Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell insulation core Resistant to the passage

More information

CHOOSE THE PERFECT GLASS FOR YOU.

CHOOSE THE PERFECT GLASS FOR YOU. CHOOSE THE PERFECT GLASS FOR YOU. SET YOUR OWN TREND. Nothing is more intensely personal than your home. It is a reflection of who you are and reveals how you live. The design decisions you make will determine

More information

THIS TO CERTIFY THAT. Firetek Panel. Structure - Structural Reliability

THIS TO CERTIFY THAT. Firetek Panel. Structure - Structural Reliability Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: Building Solutions Pty Ltd ABN: 22

More information

PINK BATTS POLYESTER INSULATION. Product. Scope. Building Regulations. Appraisal No. 999 [2018] Appraisal No. 999 (2018) BRANZ Appraisals

PINK BATTS POLYESTER INSULATION. Product. Scope. Building Regulations. Appraisal No. 999 [2018] Appraisal No. 999 (2018) BRANZ Appraisals OVER 80% RECYCLED GLASS PROVEN SAFE OVER 80% RECYCLED GLASS PROVEN SAFE PINK BATTS POLYESTER BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Pink Batts Polyester

More information

Ozone Panel 120 Acoustic Assessment and Optimization

Ozone Panel 120 Acoustic Assessment and Optimization Vipac Engineers & Scientists Ltd 279 Normanby Road, Private Bag 16 Document No. Port Melbourne VIC 3207 30U-12-0010-DRP-258904-0 Australia t. +61 3 9647 9700 f. +61 3 9646 4370 1 Aug 2012 www.vipac.com.au

More information

ROCKWOOL Tapered Roofing

ROCKWOOL Tapered Roofing ROCKWOOL Tapered Roofing High Performance Tapered Insulation Boards The range is engineered to meet the demand for tapered solutions for existing and new flat roof constructions. The system is backed by

More information

ProRox Board Products Catalogue NEW. High Temperature Board (Slab), Flex and Wrap (Mat) products for Industrial Applications PRODUCT NAMES

ProRox Board Products Catalogue NEW. High Temperature Board (Slab), Flex and Wrap (Mat) products for Industrial Applications PRODUCT NAMES HIGH TEMPERATURE INDUSTRIAL/MECHANICAL INSULATION PRODUCT NAMES ProRox Board Products Catalogue High Temperature Board (Slab), Flex and Wrap (Mat) products for Industrial Applications New product names,

More information

Adam Sweet 2KGAL DW AST DUAL FUEL STORAGE TANK FOR A GENERATOR - NO DRAWINGS 5/9/2017 False

Adam Sweet 2KGAL DW AST DUAL FUEL STORAGE TANK FOR A GENERATOR - NO DRAWINGS 5/9/2017 False Above Ground Concrete Encased Fuel Storage Tank System Category: Tanks Project ID #: 1004373561 Street Address: To Be Announced Woodstock CT Staff Estimate Value $60,000.00 06281 County: Windham Stage:

More information

The fire resistance of 3M Fire Barrier Duct Wrap 615+ protection system

The fire resistance of 3M Fire Barrier Duct Wrap 615+ protection system INFRASTRUCTURE TECHNOLOGIES The fire resistance of 3M Fire Barrier Duct Wrap 615+ protection system Short Form Assessment Report Author: Keith.Nicholls@csiro.au Assessment Number: Short Form Report FCO

More information

AS Certified ALCADEX

AS Certified ALCADEX A1 AS1530.1 Certified www.alcadex.com.au 1800 ALCADEX ALCADEX A1 AS1530.1 Certified Non Combustible Aluminium Composite Made for the Australian Construction Industry www.alcadex.com.au Recent fire related

More information

A GUIDE TO WINDOW AND DOOR SELECTION

A GUIDE TO WINDOW AND DOOR SELECTION Australian window association guide series A GUIDE TO WINDOW AND DOOR SELECTION An industry guide to the selection and certification of windows and doors Background Foreword As part of its commitment to

More information

the knowledge to produce solutions Total Facade Solutions

the knowledge to produce solutions Total Facade Solutions the knowledge to produce solutions Total Facade Solutions what is a total facade solution? Introduction The design concept behind exterior cladding has been around for many years. However, the more traditional

More information

ASSESSMENT REPORT. EWFA Report No: b 3. Report Sponsor: Timberwood Panels Pty Ltd National Blvd Campbellfield VIC 3061

ASSESSMENT REPORT. EWFA Report No: b 3. Report Sponsor: Timberwood Panels Pty Ltd National Blvd Campbellfield VIC 3061 ASSESSMENT REPORT The Group Number and Average Specific Extinction Area of OSB Timber nominated by the test sponsor as Timberwood Panels OSB Light, an uncoated oriented strand board wall and ceiling lining

More information

Certificate number: CM40087 Rev3

Certificate number: CM40087 Rev3 Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: ABN: 22 750 783 065 19 Lowermill Rd,

More information

Price List Effective From 1st March

Price List Effective From 1st March List Effective From st March 2008 www.pinkbatts.com.au RESIDENTIAL COMMERCIAL INDUSTRIAL INDEX Quantity Calculator How many s will I need...3 Residential Thermal Insulation Pink Batts (Walls)...4 Pink

More information

Eclipse TM Air Duct Board. Knauf Data Sheet AH-DS

Eclipse TM Air Duct Board. Knauf Data Sheet AH-DS Eclipse TM Air Duct Board Knauf Data Sheet AH-DS-10 01-08 Eclipse Air Duct Board Description Knauf Eclipse Air Duct Board is a rigid fiber glass board faced on one side with a foil-scrim-kraft (FSK) vapor

More information

SNUG UNDERFLOOR INSULATION. Product. Scope. Building Regulations. Appraisal No [2018] Appraisal No (2018) Amended 28 June 2018

SNUG UNDERFLOOR INSULATION. Product. Scope. Building Regulations. Appraisal No [2018] Appraisal No (2018) Amended 28 June 2018 SNUG UNDERFLOOR INSULATION Amended 28 June 2018 BRANZ Appraisals Technical Assessments of products for building and construction. Product 1.1 Snug Underfloor Insulation is a polyester thermal insulating

More information

BEAMCLAD SYSTEMS. Fire protection solutions for structural steel & soffit protection

BEAMCLAD SYSTEMS. Fire protection solutions for structural steel & soffit protection BEAMCLAD SYSTEMS Fire protection solutions for structural steel & soffit protection FIREPRO BEAMCLAD SYSTEMS ROCKWOOL BEAMCLAD systems boast a complete tool-box of options. They offer contractors simple

More information

Roof. Application. Features and Benefits PINK BATTS CEILING INSULATION. pinkbatts.co.nz PRODUCT DATA SHEET

Roof. Application. Features and Benefits PINK BATTS CEILING INSULATION. pinkbatts.co.nz PRODUCT DATA SHEET Application Pink Batts ceiling insulation is a lightweight flexible glass wool insulation product designed to: Thermally insulate ceilings in new homes, be retrofitted into existing homes without insulation,

More information

Insulation TECHNICAL DATA SHEET. Low Energy Low Carbon Buildings. CI/SfB (57.9) In7 (M2) First Issue April 2016

Insulation TECHNICAL DATA SHEET. Low Energy Low Carbon Buildings. CI/SfB (57.9) In7 (M2) First Issue April 2016 Insulation CI/SfB (57.9) In7 (M2) First Issue April 2016 The Kingspan TECHNICAL DATA SHEET System Low Energy Low Carbon Buildings Introduction The Kingspan KoolDuct System is an innovative lightweight

More information

Environmental credentials. Energy efficiency and environmental protection with KIMMCO glass mineral wool

Environmental credentials. Energy efficiency and environmental protection with KIMMCO glass mineral wool SAINT-GOBAIN Environmental credentials. Energy efficiency and environmental protection with KIMMCO glass mineral wool More and more specifiers and users are insisting on the use of insulation materials

More information

A4/6 PS AW1551 Issue 4 Nov Permishield

A4/6 PS AW1551 Issue 4 Nov Permishield Insulation A4/6 PS AW1551 Issue 4 Nov 2013 Vapour-permeable INSULATION MEMBRANE 3-in-1 Insulation, thermal break and vapour-permeable sarking Helps achieve a 6-star house energy rating Fibre-free, non-allergenic,

More information

Insulbreak. Insulation. thermal break solution

Insulbreak. Insulation. thermal break solution Insulation A4/8 TB AW2199 Issue 8 May 2017 Insulbreak thermal break solution 3-in-1 Insulation, thermal break and vapour barrier Delivers a R0.20 thermal break solution for steel-framed construction Helps

More information

Roofing. Polymeric sheet for roof waterproofing. Product Description. Tests. Product Data Sheet Edition _1

Roofing. Polymeric sheet for roof waterproofing. Product Description. Tests. Product Data Sheet Edition _1 Product Data Sheet Edition 2014-09_1 Polymeric sheet for roof waterproofing Product Description (thickness 1.5 mm) is a Polyester reinforced, multi-layer, synthetic roof waterproofing sheet based on premium-quality

More information

04 ENCLOSURE 0472p CSR BRADFORD in acoustic insulation

04 ENCLOSURE 0472p CSR BRADFORD in acoustic insulation 0472P CSR BRADFORD IN ACOUSTIC INSULATION Branded worksection This branded worksection Template has been developed by NATSPEC in conjunction with CSR Bradford and may be used whilst the Product Partner

More information

SECTION INSULATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION INSULATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 072100 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

Fire Safety Compliance Guide: Wall and Ceiling Linings

Fire Safety Compliance Guide: Wall and Ceiling Linings Insulation A4/8 AW2140 Issue 1a Oct 2016 Fire Safety Compliance Guide: Wall and Ceiling Linings FOR WAREHOUSES AND COMMERCIAL OR INDUSTRIAL SHEDS WHERE THE INSULATION ACTS AS THE WALL OR CEILING LINING

More information

K8 Cavity Board. Insulation CAVITY WALL INSULATION

K8 Cavity Board. Insulation CAVITY WALL INSULATION Insulation A4/6 K8 AW2194 Issue 13 Sep 2017 CAVITY WALL INSULATION Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell insulation core Clear cavity is maintained resists

More information

Soffit Board. Insulation

Soffit Board. Insulation Insulation A4/8 K10+ AW2200 Issue 4 Sep 2017 K10 Soffit Board INSULATED FIBRE CEMENT SHEET for concrete soffits Super high performance rigid thermoset phenolic insulation Non combustible building board

More information

SECTION DUCT INSULATION

SECTION DUCT INSULATION SECTION 23 07 13 - DUCT INSULATION PART I - GENERAL 1.1 SECTION INCLUDES A. Ductwork Insulation B. Fan and Equipment Insulation C. Insulation Jackets D. Insulation Lagging 1.2 RELATED SECTIONS A. Section

More information

Semi Rigid Duct Regaduct Acoustic ADC

Semi Rigid Duct Regaduct Acoustic ADC Semi Rigid Duct Regaduct Acoustic ADC High sound absorption Excellent thermal insulation Bendable down to 1D x throat radius Size range 63mm to mm Lengths up to 5 metres Light weight and self supporting

More information

SECTION MECHANICAL INSULATION

SECTION MECHANICAL INSULATION SECTION 15250 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division-1 Specification sections, apply to work

More information

Guideline Specifications

Guideline Specifications Page 1 of 7 PART 1 Guideline Specifications Exterior Aluminum/Composite Wall Panels GENERAL ARROWHEAD 508 SYSTEM Pressure Equalized Rainscreen SECTION 07410 1.01 SUMMARY A. Work of this section included

More information

Appraisal Report for. Building Product Accreditation. For the. NuCLAD. polystyrene exterior insulation and finishing system

Appraisal Report for. Building Product Accreditation. For the. NuCLAD. polystyrene exterior insulation and finishing system Appraisal Report for Building Product Accreditation For the NuCLAD polystyrene exterior insulation and finishing system (an external wall cladding system for Class 1a & 10 buildings) Report prepared by

More information

THIS TO CERTIFY THAT. Ritek Roof Panels. Structure - Structural Reliability

THIS TO CERTIFY THAT. Ritek Roof Panels. Structure - Structural Reliability Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: Building Solutions Pty Ltd ABN: 22

More information

1 of 17. PO Box Bellevue Rd, Newark, DE V F

1 of 17. PO Box Bellevue Rd, Newark, DE V F 1 of 17 Raw Material Manufactured from 4 8-foot sheets Fiber-reinforced 1-mil aluminumfaced polyisocyanurate panels 0.032 embossed aluminum Other patterns and stainless steel are available Necessary supplies

More information

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS

K15 Rainscreen Board. Insulation INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS Insulation A4/6 K15 AW2161 Issue 3 Dec 2016 INSULATION FOR USE BEHIND RAINSCREEN CLADDING SYSTEMS Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell insulation core Suitable

More information

Brisbane 24 th Feb, 2015

Brisbane 24 th Feb, 2015 Alternative solutions Brisbane 24 th Feb, 2015 Evidence based design and the approach to alternative solutions Ken Thomson, Associate ESD, Erbas & Associates Engineers for Building services 1 Agenda Quick

More information

ACOUSTIC MEMBRANE High performance sound-deadening

ACOUSTIC MEMBRANE High performance sound-deadening ACOUSTIC MEMBRANE High performance sound-deadening ACOUSTIC MEMBRANE ROCKWOOL Acoustic Membrane is a high-density polymer designed to reduce sound transfer through a flat roof buildup by adding to its

More information

Australasian Health Facility Guidelines. Part E - Building Services and Environmental Design Introduction

Australasian Health Facility Guidelines. Part E - Building Services and Environmental Design Introduction Australasian Health Facility Guidelines Part E - Building Services and Environmental Design 0001 - Introduction Revision 5 01 March 2016 COPYRIGHT AND DISCLAIMER Copyright 2015 Australasian Health Infrastructure

More information

K5 External Wall Board

K5 External Wall Board Insulation A4/6 K5 AW2194 Issue 9 Apr 2017 INSULATION FOR USE BEHIND TRADITIONAL AND LIGHTWEIGHT POLYMER MODIFIED RENDERS Super high performance rigid thermoset phenolic insulation Fibre-free, closed cell

More information