PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT SHOPPERS DRUG MART. January 2016

Size: px
Start display at page:

Download "PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT SHOPPERS DRUG MART. January 2016"

Transcription

1 The Odan/Detech Group Inc. P: (905) F: (905) SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT Prepared For: SHOPPERS DRUG MART January 2016

2 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT i TABLE OF CONTENTS DESCRIPTION page 1.0 BACKGROUND SCOPE OF WORK DESIGN CONSIDERATIONS 2 A) Sanitary Waste Water Disposal 2 B) Water Distribution 3 C) Stormwater Management CONCLUSIONS 7 Note: This report should be read in conjunction with the Site Servicing & Grading Plans prepared by The Odan/Detech Group Inc. APPENDIX A Aerial Photo of Site Site Plan prepared by Turner Fleischer Architects APPENDIX B Sanitary Flow Calculation from Site Fire flow calculation Maximum Day and Fire Flow Scenario Diagram prepared by J.L. Richards & Associates Ltd. City of Ottawa Water Boundary Conditions APPENDIX C Excerpts from Proposed Storm Sewer Servicing Report prepared by J.L. Richards & Associates Ltd. - Allowable flow calculation year storm design sheet - ICD 9 and 10 required and provided ponding volumes - Site Drainage Plan Dwg - Ponding Plan Dwg

3 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT BACKGROUND The property under study is located at the north-east corner of River Road and Earl Armstrong Road, Ottawa, ON. The current site area is 5.07ha. It is proposed to add a Shopper Drug Mart to the south side of the parking lot. Refer to Architectural site plan for further information regarding the proposed layout of the site including building location, asphalt and concrete curbing etc. This report will evaluate the serviceability of the site with respect to sanitary, water and storm services and also evaluate the stormwater management (SWM) strategy that will be implemented to meet the City standards. 2.0 SCOPE OF WORK The Odan/Detech Group Inc. was retained by the Owner Shoppers Drug Mart, to review the site, collect data, evaluate the site for the proposed land use and present the findings in a stormwater management report. The scope of work in brief involves the following: a) Field work to establish existing features and elevations on the site. b) Review a soils report to establish the suitability of the proposed development. c) Collecting existing servicing drawings from the City of Ottawa and governing agencies in order to establish availability and feasibility of site servicing. d) Meetings/conversations with the City of Ottawa and RVCA. e) Evaluation of the data. If suitable, make recommendations on how to best utilize the site. f) Prepare a design brief and final design drawings.

4 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT DESIGN CONSIDERATIONS A) SANITARY WASTE WATER DISPOSAL The existing sanitary sewer outlet for Riverside South Plaza located at River Road and Earl Armstrong Road is located at the west boundary line west of the existing Food Store on River Road. Refer to Engineering plans prepared by JL Richards for Phase 1 and 2 of the existing development for further details. The existing sanitary sewer located on River Road flows in a northerly direction towards on River Road. The existing sanitary sewer is a 525mm sewer at 0.10%. This sanitary sewer outlets to the 525mm dia. sanitary sewer located within the existing subdivision to the north at Shoreline Drive. Expected sanitary flows from the proposed Shopper Drug Mart and existing development are shown as follows in Table 1. Refer to Appendix B for detailed sanitary calculations. The City standard average flow of 0.60 L/sec/ha for commercial and a peaking factor of 1.5 was used to determine the sanitary flows for the site. The existing gas bar was not included in the sanitary flow calculation since it is a separate entity with its own servicing. Table 1 Calculated Sanitary Sewage Flows for Commercial Development From Land Use (L/s) PROPOSED Commercial Retail From Infiltration (L/s) Total (L/s) Existing Site The proposed land use sanitary flows were based on 50,000 L/gross ha/day with a peaking factor of 1.5 and an Infiltration rate of 0.28 L/sec/ha.

5 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT 3 B) WATER DISTRIBUTION Presently the site is serviced from River Road through the development to the north and south entrance locations from River Road. The water main on River Road is a 300mm dia. water main reduced to a 200mm dia. water main as it enters the site. It is proposed to utilize the existing 200mm dia. water main to service the proposed Shoppers Drug Mart for both fire and domestic. Refer to Engineering plans for proposed water service layout. The pressures and volumes must be sufficient for Peak hour conditions and under fire conditions as established by the Ministry of Environment and the Fire Underwriters Survey booklet (1981). The minimal residual pressure under fire conditions is 140 kpa (20.3 psi). According to the MOEE criteria the allowable pressures are as follows: Condition Allowable Pressures (kpa) min. max. 1) Min. Hour 275 (40psi) 700 (101psi) 2) Peak Hour 275 (40 psi) 700 (101 psi) 3) Peak Day + Fire Flow 140 (20 psi) 700 (101 psi) The domestic water demand of the site was provided by Shoppers Drug Mart using Delcan Corporation s Site Servicing & Stormwater Management Report prepared in February The Shoppers Drug Mart in this report is located in Ottawa and is slightly larger (15,954 ft 2 ) than the proposed Shoppers Drug Mart (15,588ft 2 ). The water demand is as follows: a) Average Day domestic demand 0.33 L/s b) Peak day demand x daily demand 0.50 L/s c) Peak hour demand x daily demand 0.90 L/s d) Fire flow for retail space as per FUS 1999 manual 50 L/s The fire flow demand calculation can be found in Appendix B. Table 2 is a summary of the total water demand for the proposed Shoppers Drug Mart.

6 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT 4 Table 2 Total Water Demand for Proposed Shoppers Drug Mart L/s USGM Peak Day Demand Fire Flow Demand Total Water Demand Flow at 20 PSI Residual Pressure In October 2003, JL Richards completed a Hydraulic Network Analysis which included this development known as Riverside South Plaza. Flows and pressures were obtained from this report. The diagram demonstrating the results from RL Richards for the maximum day and fire flow scenario is shown in Appendix B. The WaterCAD model included the existing stores (Retail A, B and the bank) in its analysis. The maximum day and fire flow at the location of the proposed water service connection for the proposed Shoppers Drug Mart is L/s which is greater than the required L/s. Therefore, the watermain has sufficient water capacity to meet the fire demands required for the proposed site. Table 3 shows the total water demand for the entire site. The existing demands were obtained from the same report prepared by JL Richards. Table 3 Total Water Demand for Entire Site Building Area (m 2 ) Demand (L/s) Avg. Day Max Day Peak Hr Existing Retail A Existing Retail B Existing Bank Proposed Shoppers Drug Mart Total Demand (L/s) Fire Flow (L/s) 50 Peak Day + Fire Flow (L/s) 63.2 The total demand for the site including the proposed Shoppers Drug Mart is 63.2 L/s which is less than the available flow of L/s; therefore, there is sufficient capacity to accommodate the existing buildings and the proposed Shoppers Drug Mart. The water boundary conditions were provided by the City of Ottawa using the water demand and fire flow demand of the proposed Shoppers Drug Mart. The head at the connection point of the analysis using the maximum day and fire flow demand of the proposed store is 143.8m at a pressure of 77.3 psi. The water boundary report is found in Appendix B.

7 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT 5 C) STORM WATER MANAGEMENT Storm water management for the site will follow the approved report completed by J.L.Richards titled Proposed Storm Sewer Servicing Report, Urbandale Corporation Riverside South Plaza, City of Ottawa dated October 2003 and revised May Existing Site Conditions: Currently the site has an existing Food Store, Strip Plaza and Scotia Bank with related parking. As per J.L. Richards storm sewer servicing report, ICD s and rooftop controls were installed and implemented throughout the development to control flow from the 5 year to 100 year design storm. The storm servicing for this site includes 14 ICDs at various manhole/catchbasin locations within the property with various rates and their corresponding ponding storages in the parking lot. Rooftops with storm flow controls and ponding storage were also included in the storm servicing plan. Retail C (the existing Scotia bank) was proposed without roof top controls. The flows on site should be detained on site to a maximum allowable release rate of L/s as determined using the Rational method in J.L. Richard s report. The excerpt demonstrating this calculation in the report is provided in Appendix C. Q = 2.78 CiA = 2.78 (0.8)(62.85mm/hr)(5.07ha) = L/s The actual flow reported by J.L. Richards using the ICDs and rooftop controls under a 100 year storm was calculated to be L/s. The storm sewer design sheet for the 100-year storm from the J.L. Richards s report is included in Appendix C. J.L. Richards storm sewer servicing report demonstrates that the site does not exceed the allowable flows and provides for adequate storage throughout. Post Development Site Conditions: In order to maintain post development flows at or below the total allowable flows of L/s 5 year and to 100 year to the downstream storm system, parking and rooftop controls will be implemented on site. The proposed addition of the Shoppers Drug Mart has added rooftop area to the parking area. The location of the Shoppers Drug Mart has resulted in a loss of surface ponding volume in the area. In order to maintain the ponding and achieve the required storage rooftop controls together with rooftop storage will be utilized.

8 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT 6 The total rooftop storage can be calculated as follows: Relationship for Rooftop Control Devices Area of Roof = 1448 m 2 Number of Weirs = 4 Head (m) Volume (m 3 ) Discharge (L/s) Volume (ha-m) Discharge (m 3 /s) Therefore the maximum flow from the roof during a 100 year storm event will be limited to 9.0 L/sec to a maximum of 150mm ponding depth. The rooftop is replacing an existing surface ponding area in which the ponding volume is 72.2m 3 at the existing catch basin that is proposed to be removed (Area 10B in the J.L. Richard s ponding plan in Appendix C). The site drainage plan from J.L. Richard s report is also included in Appendix D. There is also ponding in the parking lot to the north of the proposed Shoppers Drug Mart (Area 10A in the J.L. Richard s ponding plan in Appendix C) that provided 212.5m 3 of volume. An existing 225mm orifice plate (ICD 10 in J.L. Richard s report) is located at EX CBMH 1 as labelled in the servicing plan. The maximum total release rate of this orifice plate is 170 L/sec. This existing orifice plate controlled both storage areas. The proposed Shoppers Drug Mart will reduce the total ponding volume for the parking lot in the north (Area 10A) to m 3 which includes the outlet catch basin volume where the 225mm orifice plate is located. The 100- year storm ponding volume required at this orifice plate as per the report is 104.5m 3. Therefore, the existing parking lot volume north of the proposed retail store still provides more storage than required. The required and provided ponding volume calculations for ICD 10 are shown in Appendix C. The proposed Shoppers Drug Mart rooftop will control flows to 9.0 L/sec and provide for a storage volume of 95m 3, an increase of 23m 3 from 72m 3. Furthermore, the additional flow from the rooftop will be controlled via the existing 225mm orifice plate. The surrounding pavers and asphalt areas of the proposed Shoppers Drug Mart will be graded towards the parking lot to the north or drained by proposed storm sewers to the existing storm sewer with the existing 225mm orifice plate. The storm tributary area draining to this orifice plate remains approximately the same. There is a small area to the east of the Shoppers Drug Mart that will be graded to drain towards EX CB 5 as labelled in the servicing plan. This area has existing storage of 197m 3 (Area 9) that is controlled by ICD 9 and will remain the same volume. The required volume for this drainage area is 63m 3 which is much less than the volume provided. Therefore, there is storage room for the extra proposed area draining to this catch basin. The required and provided ponding volume calculations for ICD 9 are shown in Appendix C. There is some uncontrolled flow that will be compensated by restricted flow from the rooftop controls provided on the proposed Shoppers Drug Mart roof. The composition of this area remains the same since the proposed landscaping area remains approximately the same as in existing conditions. As such the addition of the Shoppers Drug Mart to the proposed development will not impact existing storm water management for the site as outlined within the J.L. Richards report Proposed Storm Sewer Servicing Report, Urbandale Corporation Riverside South Plaza, City of

9 PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD ENGINEERING REPORT 7 Ottawa dated October 2003 and revised May It has improved upon the existing conditions. Water Quality: There will be no change to water quality for the development. Rooftop water is considered clean water, 80% TSS removal. There has been an overall increase in rooftop and decrease in asphalt area. In addition, this site is serviced by the stormwater management pond, Pond No. 1 of the South Urban Community Stormwater Management Facility located north of the proposed site. 4.0 CONCLUSIONS Our investigation has determined that the site is serviceable utilizing existing sanitary sewers, and existing storm and watermain infrastructure adjacent to the site. The storm water management for the existing site will be improved for both quantity and quality. Both water quantity and water quality objectives been achieved, maintained and improved upon. Respectfully Submitted; The Odan Detech Group Inc. January 25 th, 2016 Christine Metrie, B.Eng.Mgt., EIT JOHN KRPAN, M.S.C.E., P.Eng. DATE

10 APPENDIX A Aerial Photo of Existing Site Site Plan by Turner Fleischer Architects

11 Aerial Photo of Existing Site Subject Site

12

13 APPENDIX B Sanitary Flow Calculation from Site Fire Flow Calculation Maximum Day and Fire Flow Scenario Diagram prepared by RL Richards & Associates Ltd. City of Ottawa Water Boundary Conditions

14 SANITARY FLOW CALCULATIONS SCENERIO: FULL DEVELOPMENT This program calculates the sanitary discharge from various land use FILL IN COLOURED CELLS AS REQUIRED COMMERCIAL SITE AREA (ha) = 4.81 NOTE: SITE IS 3.32 ha, incl. Proposed Rexall Development RESIDENTIAL SITE AREA (ha) = TOTAL SITE AREA (ha) = 4.81 LAND USE NUMBER OF UNITS SITE AREA, (ha) GROSS FLOOR AREA, m2 TOTAL POPULATION TOTAL DAILY FLOW (LITERS) AVERAGE DAILY FLOW l/sec PEAKING FACTOR, M TOTAL FLOW FROM LAND USE, l/sec RESIDENTIAL Density 1, using 86 person/site area RESIDENTIAL Density 2, using 170 persons/site area RESIDENTIAL Density 3, using 270 persons/site area RESIDENTIAL Density 3, using 2.7 persons/unit RESIDENTIAL Density 4, using 400person/site area RESIDENTIAL Density 4, using 2.0 persons/unit COMMERCIAL, Using 136 persons/ha COMMERCIAL, Using 0.60 L/sec per ha OFFICES, Using 1.1 persons/100 m2 INDUSTRIAL, Using 136 persons/ha TOTAL V1= Q1= 0.00 Q2= 4.33 Q = (MqP/86400) + A * I (L/sec) Qinfil 1.35 Qtot 5.68 Q1= total flow from Residential Land Use (L/sec) where : P is population Q2= total flow from Commercial Land Use (L/sec) q = L/sec/person for residential and Qinfil = total flow from infiltration (L/sec) q = 0.60 L/sec/ha for commercial and offices Qtot = total flow (Land use + infiltration) A = gross site area i = 0.15 L/sec/ha (infiltration rate) V1= Total Volume from Land Use in liters Peaking Factor M = 1 + [14 / (4 + (P/1000,1/2))] (for reside Peaking Factor M = 2.5 (for Commercial)

15 FIRE FLOW CALCULATION WATER SUPPLY FOR PUBLIC FIRE PROTECTION, FIRE UNDERWRITERS SURVEY GUIDE FOR DETERMINATION OF REQUIRED FIRE FLOWS F = 220 x C x A Where: F = required fire flow in liters per minute C= Coefficient related to the type of construction A = the total floor area in square meters (excluding basements) in the building considered LOCATION: River and Earl Armstrong, Ottawa PROJECT: Proposed Shoppers Drug Mart OBC OCCUPANCY: Commercial Retail PROJECT No BUILDING FOOT PRINT (m2): 1448 Contents Charge # OF STOREYS 1 Non Combustible 25% limited Combustible 15% Combustible 0% CONSTRUCTION CLASS: FIRE RESISTIVE Free Burning 15% ` Rapid Buring 25% AUTOMATED SPRINKLER PROTECTION Credit Total NFPA 13 sprinkler standard yes 30% Standard Water Supply yes 10% 50% Fully Supervised System yes 10% 50% CONTENTS FACTOR: Combustible CHARGE: 0% Separation Charge EXPOSURE 1 (south) Distance to Exposure Building (m) > m 25% 0% Length Height m 20% EXPOSURE 2 (east) Distance to Exposure Building (m) m 15% 0% Length Height m 10% EXPOSURE 3 (west) Distance to Exposure Building (m) % 0% Length Height > 45 m 0% Total: EXPOSURE 4 (north) Distance to Exposure Building (m) 70 Length Height 0% 0% no more than 75% ARE BUILDINGS CONTIGUOUS: FIRE RESISTANT BUILDING No Are vertical openings and exterior vertical communications protected with a minimum one (1) h No CALCULATIONS C = 0.6 Fire Resistive A = 1448 m2 (2 largest floor + 50% of 8 above floors) STOREY AREAS m2 F = 5023 L/min 1448 Round to Nearest 1000 L/min F = 6000 L/min must be > 2000 L/min CORRECTION FACTORS: OCCUPANCY 0 L/min FIRE FLOW ADJUSTED FOR OCCUPANCY 6000 L/min REDUCTION FOR SPRINKLER 3000 L/min EXPOSURE CHARGE 0 L/min REQUIRED FIRE FLOW F = 3000 L/min Round to Nearest 1000 L/min F = 3000 L/min 793 usgm F = 50 L/sec

16 Maximum Day and Fire Flow Scenario WaterCAD diagram prepared by JL Richards & Associates in their Hydraulics Network Analysis Report

17 Information Provided: Date provided: 12 November 2015 Boundary Conditions at Riverside Plaza Criteria Average Demand 0.33 Maximum Daily Demand 0.50 Peak Hourly Demand 0.90 Fire Flow Demand 50 Demand (L/s) Location:

18 Results Connection-1: Criteria Head (m) Pressure (psi) Max HGL PKHR MXDY + Fire Flow (50 L/s) Note: The site is assessed based on existing and reconfiguration zone conditions and the governing BCs are provided. Considerations 1. According to the City of Ottawa Water Design Guidelines as well as the Ontario Building Code, the maximum pressure at any point within a distribution system shall not exceed 80 psi in occupied areas. Measures should be taken to try to reduce the residual pressure below 80 psi without the use of special pressure control equipment. In circumstances where the residual pressure cannot be reduced below 80 psi without the use of pressure control equipment, a pressure reducing valve (PRV) should be installed at site. Disclaimer The boundary condition information is based on current operation of the city water distribution system. The computer model simulation is based on the best information available at the time. The operation of the water distribution system can change on a regular basis, resulting in a variation in boundary conditions. The physical properties of watermains deteriorate over time, as such must be assumed in the absence of actual field test data. The variation in physical watermain properties can therefore alter the results of the computer model simulation. Fire Flow analysis is a reflection of available flow in the watermain; there may be additional restrictions that occur between the watermain and the hydrant that the model cannot take into account.

19 APPENDIX C Excerpts from Proposed Storm Sewer Servicing Report prepared by J.L. Richards & Associates Ltd. - Allowable flow calculation year storm design sheet - ICD 9 and 10 required and provided ponding volumes - Site Drainage Plan Dwg - Ponding Plan Dwg

20

21

22

23

24

25

26

Julia Bahen, Urban Strategies Inc.

Julia Bahen, Urban Strategies Inc. THE MUNICIPAL INFRASTRUCTURE GROUP LTD. 8800 Dufferin Street, Suite 200 Vaughan, Ontario L4K 0C5 T 905.738.5700 F 905.738.0065 www.tmig.ca TECHNICAL MEMORANDUM DATE June 13, 2017 TO CC SUBJECT FROM PROJECT

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. SERVICING BRIEF Mutchmor Public School Addition 185 Fifth Avenue Ottawa, Ontario Report No. 12073-SB February 15, 2013 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading & Drainage

More information

Servicing and Stormwater Management Brief 4450 Limebank Road Residential Development

Servicing and Stormwater Management Brief 4450 Limebank Road Residential Development Servicing and Stormwater Management Brief 4450 Limebank Road Residential Development Project # 160401232 Prepared for: Urbandale Corporation Prepared by: Stantec Consulting Ltd. Submission 3: Oct. 20,

More information

ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 6401 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT

ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 6401 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 641 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT Prepared by: NOVATECH ENGINEERING CONSULTANTS LTD. Suite 2, 24 Michael Cowpland

More information

Envie Champagne Avenue

Envie Champagne Avenue Envie - 101 Champagne Avenue Site Servicing and Stormwater Management Report Type of Document Site Plan Submission Project Name Envie - 101 Champagne Avenue Project Number 00219439-A0 Prepared By: J. Fitzpatrick,

More information

6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON

6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON 6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON STORM WATER MANAGEMENT DESIGN BRIEF NEW DEVELOPMENT DRAINAGE SYSTEM REV 0 August 29, 2017 PREPARED BY: HALLEX PROJECT #170532 HALLEX NIAGARA HALLEX HAMILTON

More information

ULTRAMAR LTD 3467 Hawthorne Road Ottawa, Ontario SITE SERVICING & STORMWATER MANAGEMENT REPORT. Submitted to:

ULTRAMAR LTD 3467 Hawthorne Road Ottawa, Ontario SITE SERVICING & STORMWATER MANAGEMENT REPORT. Submitted to: ULTRAMAR LTD 3467 Hawthorne Road Ottawa, Ontario SITE SERVICING & STORMWATER MANAGEMENT REPORT Submitted to: Manon Renaud Architect 443 Saint-Claude, Montréal (QC) H2Y 3B6 Submitted by: Delcan Corporation

More information

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT Adopted by City Council: May 21, 2007 X:\General Eng\DESIGN STANDARDS\Engineering Design Standards

More information

ASSESSMENT OF ADEQUACY OF PUBLIC SERVICES BRIGIL 460 ST. LAURENT BOULEVARD

ASSESSMENT OF ADEQUACY OF PUBLIC SERVICES BRIGIL 460 ST. LAURENT BOULEVARD ASSESSMENT OF ADEQUACY OF PUBLIC SERVICES FOR BRIGIL 460 ST. LAURENT BOULEVARD CITY OF OTTAWA PROJECT NO.: 11-538 MAY 2012 REV 1 DSEL ASSESSMENT OF ADEQUACY OF PUBLIC SERVICES FOR BRIGIL 460 ST. LAURENT

More information

Municipal Stormwater Ordinances Summary Table

Municipal Stormwater Ordinances Summary Table APPENDIX F Municipal Ordinances Summary Table Municipality Abington Bryn Athyn Borough Hatboro Borough Ordinance, SALDO Runoff equals pre post Erosion Sediment Control Water Quality Requirements Any which

More information

FUN NCTIONAL SER RVICING AN ND STO R MA ORMWATER ANAGEMENT PREPARED FOR: CITY O 333 AN REET EAST ND 351 KING STR OF TORONTO VICTORIA PA

FUN NCTIONAL SER RVICING AN ND STO R MA ORMWATER ANAGEMENT PREPARED FOR: CITY O 333 AN REET EAST ND 351 KING STR OF TORONTO VICTORIA PA FUN NCTIONAL SER RVICING AN ND STO ORMWATER R MA ANAGEMENT T RE PORT 333 AN ND 351 KING STR REET EAST P PREPARED FOR: CITY O OF TORONTO F IRST GULF COR PORATION 3 751 VICTORIA PA ARK AVENUE T TORONTO,

More information

City of Redwood City Stormwater Pollution Prevention Program. Drainage Guidelines for Residential Development

City of Redwood City Stormwater Pollution Prevention Program. Drainage Guidelines for Residential Development City of Redwood City Stormwater Pollution Prevention Program Drainage Guidelines for Residential Development General Requirements A. Plot & Finished Grading Plan must be submitted with Building Permit

More information

3. Sanitary Plumbing Single Stack System

3. Sanitary Plumbing Single Stack System 3. Sanitary Plumbing Single Stack System On completion of this section, students should be able to: Design, install and develop bills of quantities for the Single Stack Systems for domestic, commercial

More information

STORM WATER MANAGEMENT REPORT

STORM WATER MANAGEMENT REPORT Silvercreek Junction STORM WATER MANAGEMENT REPORT Howitt Creek at the Silvercreek Parkway Site Guelph, Ontario August, 2008 TSH File 22304A-04 August 19, 2008 STORMWATER MANAGEMENT REPORT Howitt Creek

More information

TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK

TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK TOWN OF MOUNT PLEASANT WESTCHESTER COUNTY, NEW YORK COST EVALUATION FOR ROLLING HILLS AREA WATER MAIN EXTENSION PROFESSIONAL CONSULTING, LLC. Octagon 10, Office Center 1719 Route 10, Suite 225 Parsippany,

More information

DIVISION 5 STORM DRAINAGE CRITERIA

DIVISION 5 STORM DRAINAGE CRITERIA DIVISION 5 STORM DRAINAGE CRITERIA Section 5.01 GENERAL The following storm drainage design criteria shall apply to all storm drainage designs in the City. Additional design criteria are specified in the

More information

Changes in Assessment Report for the Labatte-Mastronardi Drain

Changes in Assessment Report for the Labatte-Mastronardi Drain Changes in Assessment Report for the Labatte-Mastronardi Drain Roll No. 590-06800, 590-06850 and 590-06901 Municipality of Leamington February 16, 2016 Project No. 15-012 February 16, 2016 The Municipality

More information

Please find attached a copy of our Traffic Memo for the proposed dental clinic at 3012 St. Joseph Blvd.

Please find attached a copy of our Traffic Memo for the proposed dental clinic at 3012 St. Joseph Blvd. April 5, 203 Drs. George Barlas, Marc Beaupre, John Kokkinakis, Pierre Maranger Place D Orleans Dental Office 0 Place D Orleans Drive Orleans, Ontario KC 2L9 Dear Dr. Barlas, Dr. Beaupre, Dr. Kokkinakis,

More information

Site Utility Study. Prepared By: Rodolfo Ibarra, PE, PA SW 117 th Avenue Unit #3 Miami, Florida 33177

Site Utility Study. Prepared By: Rodolfo Ibarra, PE, PA SW 117 th Avenue Unit #3 Miami, Florida 33177 WEST BRICKELL CENTRE Major Use Special Permit 290 SW 10 th Street, 245 SW 11 th Street,240-270 SW 10 th Street, 251-253 SW 11 th Street, 255 SW 11 th Street, and 267 SW 11 th Street Site Utility Study

More information

City of Saint John. Storm Drainage Design Criteria Manual

City of Saint John. Storm Drainage Design Criteria Manual Storm Drainage Design Criteria Manual March 7, 2016 LIST OF 2016 REVISIONS PAGES SECTION TITLE iii, iv, v, vi All Table of Contents 31-35 3 SUBMISSION REQUIREMENTS March 7, 2016 Page i DISCLAIMER The material

More information

RECOMMENDATION: Staff recommends approval and provides the following motion for the commission s consideration:

RECOMMENDATION: Staff recommends approval and provides the following motion for the commission s consideration: PZ Case No. 17-09 Planning & Zoning Commission COMMUNITY DEVELOPMENT DEPARTMENT March 13, 2017 Subject: Consider making a recommendation on PZ Case No. 17-09; the site plans for Amega Garage Doors at 4901

More information

Chapter 7. Street Drainage. 7.0 Introduction. 7.1 Function of Streets in the Drainage System. 7.2 Street Classification

Chapter 7. Street Drainage. 7.0 Introduction. 7.1 Function of Streets in the Drainage System. 7.2 Street Classification 7. Introduction This chapter summarizes methods to evaluate runoff conveyance in various street cross sections and curb types in the Town of Castle Rock and identifies acceptable upper limits of street

More information

1956 Altona Road, City of Pickering Functional Servicing and Stormwater Management Report. Marshall Homes. Project # E15031

1956 Altona Road, City of Pickering Functional Servicing and Stormwater Management Report. Marshall Homes. Project # E15031 1956 Altona Road, City of Pickering Functional Servicing and Stormwater Management Report Marshall Homes Project # E15031 August 2016 Table of Contents 1.0 Introduction and Background... 1 2.0 Existing

More information

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN

CHECKLIST FOR STREETS, INLETS, AND STORM SEWER DESIGN CHECKLIST FOR STREETS, INLETS, I. STREET CLASSIFICATION AND DESIGN CRITERIA A. Determine drainage classification for the roadway section using Table 7-1 or Table 7-2. B. Determine the allowable flow depth

More information

The Islamic University of Gaza- Civil Engineering Department Sanitary Engineering- ECIV 4325 L5. Storm water Management

The Islamic University of Gaza- Civil Engineering Department Sanitary Engineering- ECIV 4325 L5. Storm water Management The Islamic University of Gaza- Civil Engineering Department Sanitary Engineering- ECIV 4325 L5. Storm water Management Husam Al-Najar Storm water management : Collection System Design principles The Objectives

More information

Sag Pipe (depressed sewers, or Inverted siphons) Dr. Sataa A. Al-Bayati(10-11)

Sag Pipe (depressed sewers, or Inverted siphons) Dr. Sataa A. Al-Bayati(10-11) بسم هللا الرحمن الرحيم Sag Pipe (depressed sewers, or Inverted siphons) Dr. Sataa A. Al-Bayati(10-11) A sewer that drops below the hydraulic gradient to pass under an obstruction, such as a railroad cut,

More information

Water supply components

Water supply components Water supply components Water sources structures (Dams, wells, reservoirs) Surface water Groundewater Pipelines from source Water treatment plant components Pumping stations Storage (elevated tanks) Distribution

More information

FUNCTIONAL SERVICING REPORT ONTARIO STREET RESIDENTIAL TOWNHOUSE DEVELOPMENT BUCCI HOMES TOWN OF MILTON REGION OF HALTON.

FUNCTIONAL SERVICING REPORT ONTARIO STREET RESIDENTIAL TOWNHOUSE DEVELOPMENT BUCCI HOMES TOWN OF MILTON REGION OF HALTON. FUNCTIONAL SERVICING REPORT 405-475 ONTARIO STREET RESIDENTIAL TOWNHOUSE DEVELOPMENT BUCCI HOMES TOWN OF MILTON REGION OF HALTON Submitted to: Submitted by: AMEC Earth & Environmental, a division of AMEC

More information

APPENDIX G Fire BMPs

APPENDIX G Fire BMPs APPENDIX G Fire BMPs BEST MANAGEMENT PRACTICES Plan for URBAN RUNOFF MANAGEMENT PARTICIPATING RIVERSIDE COUNTY FIRE FIGHTING AGENCIES City of Corona Fire Department City of Hemet Fire Department City of

More information

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES

SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES SECTION 4 - DESIGN STANDARDS FOR WATER DISTRIBUTION FACILITIES 4.1 GENERAL REQUIREMENTS 4.1.1 Water and fire protection distribution facilities are to be provided solely for the purpose of supplying potable

More information

TECHNICAL BULLETIN. Synthetic Turf Athletic Field Drainage Design Assistance

TECHNICAL BULLETIN. Synthetic Turf Athletic Field Drainage Design Assistance TECHNICAL BULLETIN Synthetic Turf Athletic Field Drainage Design Assistance The SportsEdge HQ geocomposite strip drain products are engineered specifically for use in synthetic turf athletic field base

More information

Learning objectives. Upon successful completion of this lecture, the participants will be able to:

Learning objectives. Upon successful completion of this lecture, the participants will be able to: Solomon Seyoum Learning objectives Upon successful completion of this lecture, the participants will be able to: Describe and perform the required step for designing sewer system networks Outline Design

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

SITE PLAN AND ARCHITECTURAL REVIEW APPLICATION

SITE PLAN AND ARCHITECTURAL REVIEW APPLICATION SITE PLAN AND ARCHITECTURAL REVIEW APPLICATION CITY OF GENEVA, NEW YORK The purpose of the site plan and architectural review process is to secure compliance with the City s Zoning Ordinance and to promote

More information

The following is required for a complete permit submittal for each unit.

The following is required for a complete permit submittal for each unit. P: (847)810-3502 OR (847)810-3503/3521, F: (847)615-4383 MULTI-FAMILY OR COMMERCIAL ADDITION OR ALTERATION PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. MULTI-FAMILY

More information

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction.

Contact the Jurisdictional Engineer for materials allowed by each jurisdiction. Design Manual Chapter 3 - Sanitary Sewers 3C - Facility Design 3C-1 Facility Design A. Capacity of Pipe Pipe sizes 15 inches and smaller should carry the peak flow at a depth of no more than 0.67 of the

More information

Received by:* Date Received:* Zoning Approval:* Date:* PERMIT#:* *ZONING: *SETBACKS: FRONT ft/ SIDE ft/ REAR ft *FLOOD ZONE:

Received by:* Date Received:* Zoning Approval:* Date:* PERMIT#:* *ZONING: *SETBACKS: FRONT ft/ SIDE ft/ REAR ft *FLOOD ZONE: HENDRY COUNTY BUILDING, LICENSING & CODE ENFORCEMENT POST OFFICE BOX 2340 * 640 SOUTH MAIN STREET * LABELLE, FLORIDA 33975 * (863) 675-5245 * FAX: (863) 674-4194 1100 OLYMPIA ST CLEWISTON, FLORIDA 33440

More information

3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES

3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES 3.0 DESIGN CRITERIA FOR SANITARY SEWER FACILITIES All sanitary sewers shall be designed in accordance with these Design Standards, LBWD Rules and Regulations, and to accepted engineering principles. In

More information

CE 3150 Reinforced Concrete Design Design Project

CE 3150 Reinforced Concrete Design Design Project Problem Description For this design project you will work in your project groups to complete a partial design of an office building. Specifically, you will design and fully detail three components: 1.

More information

ADDENDUM NO. FIVE TO THE DESIGN-BUILD REQUEST FOR PROPOSAL (RFP) DOCUMENTS September 26, 2016

ADDENDUM NO. FIVE TO THE DESIGN-BUILD REQUEST FOR PROPOSAL (RFP) DOCUMENTS September 26, 2016 I. GENERAL ADDENDUM NO. FIVE TO THE DESIGN-BUILD REQUEST FOR PROPOSAL (RFP) DOCUMENTS September 26, 2016 The following changes, additions, or deletions shall be made to the following documents; all other

More information

SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017

SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017 SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017 I. CONSTRUCTION PREREQUISITES 1.0 Pre-construction Survey A pre-construction survey of all existing infrastructure within

More information

Town of Petawawa Infrastructure Study Update 2013

Town of Petawawa Infrastructure Study Update 2013 2013 TABLE OF CONTENTS Chapter 1 Overview Chapter 2 Sanitary Sewer System Chapter 3 Storm Drainage System Chapter 4 Road System Chapter 5 Water Distribution System Chapter 6 Comprehensive Plan Appendix

More information

ENGINEERING INFRASTRUCTURE REPORT 32 & 34 TENNYSON AVE, TAKAPUNA ISSUED FOR RESOURCE CONSENT

ENGINEERING INFRASTRUCTURE REPORT 32 & 34 TENNYSON AVE, TAKAPUNA ISSUED FOR RESOURCE CONSENT ENGINEERING INFRASTRUCTURE ENGINEERING INFRASTRUCTURE REPORT 32 & 34 TENNYSON AVE, TAKAPUNA ISSUED FOR RESOURCE CONSENT Job No 37240R#C Date May 17 Level 1, 12 14 Como Street, PO Box 33 426, Takapuna,

More information

APPENDIX G HYDRAULIC GRADE LINE

APPENDIX G HYDRAULIC GRADE LINE Storm Drainage 13-G-1 APPENDIX G HYDRAULIC GRADE LINE 1.0 Introduction The hydraulic grade line is used to aid the designer in determining the acceptability of a proposed or evaluation of an existing storm

More information

This is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations.

This is only a general checklist; please refer to the CVWD Development Design Manual (DDM) for all requirements and regulations. COACHELLA VALLEY WATER DISTRICT DOMESTIC WATER CHECKLIST Tract/Parcel No: Project Common Name: Developer: Engineer: Engineer Signature: Date: Phone: Phone: Print: This is only a general checklist; please

More information

City of Grenora, ND Municipal Infrastructure Needs Assessment August 2012

City of Grenora, ND Municipal Infrastructure Needs Assessment August 2012 City of Grenora, ND Municipal Infrastructure Needs Assessment August 2012 Project made possible by US Dept. of HUD Regional Substantiality Planning Grant and ND Energy Development Infrastructure and Impact

More information

REQUEST FOR COUNCIL ACTION

REQUEST FOR COUNCIL ACTION REQUEST FOR COUNCIL ACTION Date: May 22, 2017 Item No.: 7.c Department Approval City Manager Approval Item Description: 1681 Rice Street Non-Residential Stormwater Impact Fee Appeal 1 2 3 4 5 6 7 8 9 10

More information

BUILDING PERMIT INFORMATION GUIDE FOR THE HOMEOWNER

BUILDING PERMIT INFORMATION GUIDE FOR THE HOMEOWNER THE CORPORATION OF THE MUNICIPALITY OF SOUTH HURON 322 Main Street South, P.O. Box 759, Exeter, Ontario N0M 1S6 PHONE: (519) 235-0310 FAX: (519) 235-3304 TOLL FREE: 1-877-204-0747 WEBSITE: www.southhuron.ca

More information

SECTION 3 DRAINAGE. 3-1 General. 3-2 Drainage Ordinances and Legal Requirements

SECTION 3 DRAINAGE. 3-1 General. 3-2 Drainage Ordinances and Legal Requirements SECTION 3 DRAINAGE 3-1 General All Drainage plans for proposed development shall be prepared by a Professional Engineer registered in Virginia, except as noted below. Further, their seal and signature

More information

Regional District of Okanagan-Similkameen 101 Martin Street Penticton, BC V2A 5J9. November 2008 Project No

Regional District of Okanagan-Similkameen 101 Martin Street Penticton, BC V2A 5J9. November 2008 Project No Sawmill Road Area Sanitary Sewer Feasibility Study Regional District of Okanagan-Similkameen 101 Martin Street Penticton, BC V2A 5J9 November 2008 Project No. 104258 Table of Contents SECTION TITLE PAGE

More information

TES Industrial Development SW ¼ SEC Lacombe County Outline Plan

TES Industrial Development SW ¼ SEC Lacombe County Outline Plan TES Industrial Development Lacombe County Outline Plan 112849297 June 2012 am v:\1128\active\112849297\07_reports_studies\rpt_tes_20120508.doc i Table of Contents 1.0 INTRODUCTION... 1 1.1 PURPOSE... 1

More information

City of Wheat Ridge Site Drainage Requirements

City of Wheat Ridge Site Drainage Requirements City of Wheat Ridge Site Drainage Requirements I. INTRODUCTION Purpose The City of Wheat Ridge ( the City ) has specific Site Drainage Requirements that must be followed by proposed developments or re-developments.

More information

RESIDENTIAL CONSTRUCTION New Dwellings and Additions

RESIDENTIAL CONSTRUCTION New Dwellings and Additions How to Obtain a Building Permit For RESIDENTIAL CONSTRUCTION New Dwellings and Additions MIAMI COUNTY, KANSAS CODE SERVICES DEPARTMENT 201 South Pearl Street, Suite 201 Paola, Kansas 66071-1777 Phone:

More information

BUILDING A STRUCTURE IN THE FLOODPLAIN. IMPORTANT REQUIREMENTS Of Warren County Floodplain Management Ordinance

BUILDING A STRUCTURE IN THE FLOODPLAIN. IMPORTANT REQUIREMENTS Of Warren County Floodplain Management Ordinance BUILDING A STRUCTURE IN THE FLOODPLAIN When you apply for a zoning permit to build a home or other structure and it is determined your land is in the floodplain, the following procedures will apply: 1.

More information

District of Barriere A GUIDE TO BUILDING PERMITS

District of Barriere A GUIDE TO BUILDING PERMITS District of Barriere A GUIDE TO BUILDING PERMITS THIS BROCHURE EXPLAINS: When a Building Permit is required Building Application Procedure District of Barriere Review of the Permit Application Additional

More information

City of Elgin SUBDIVISION FINAL ENGINEERING Engineering Submittal Checklist

City of Elgin SUBDIVISION FINAL ENGINEERING Engineering Submittal Checklist If this is a re-submittal, please provide a point-by-point response to previous review comments, identifying how each comment has been addressed, location in the plan set of the changes made to address

More information

Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES

Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES Section V WATER DISTRIBUTION SYSTEM DESIGN GUIDELINES A. GENERAL 1. The following water system design guidelines are based on Federal, State and local health requirements and the Hilton Head No. 1 Public

More information

LEVAC ROBICHAUD LECLERC Consulting Engineers/Ingénieurs conseils Rockland Hawkesbury Gatineau

LEVAC ROBICHAUD LECLERC Consulting Engineers/Ingénieurs conseils Rockland Hawkesbury Gatineau LEVAC ROBICHAUD LECLERC Consulting Engineers/Ingénieurs conseils Rockland Hawkesbury Gatineau Site Servicing Brief Proposed Oakwood Designers & Builders Inc. Headquarters 865 Taylor Creek Drive, Orleans,

More information

STORMWATER RUNOFF AND WATER QUALITY IMPACT REVIEW

STORMWATER RUNOFF AND WATER QUALITY IMPACT REVIEW SUBCHAPTER 8 STORMWATER RUNOFF AND WATER QUALITY IMPACT REVIEW 7:45-8.1 Purpose and scope of review Except for those projects expressly exempted by this chapter or waived by the Commission, the Commission

More information

DEVELOPMENT ENGINEERING REVIEW MANUAL (Regional Services)

DEVELOPMENT ENGINEERING REVIEW MANUAL (Regional Services) DEVELOPMENT ENGINEERING REVIEW MANUAL (Regional Services) FEBRUARY, 2005 PLANNING AND TRANSPORTATION SERVICES PLANNING AND PUBLIC WORKS DEPARTMENT TABLE OF CONTENTS Introduction 1 Application Review 1.1

More information

EXAMPLE Stormwater Management Plans w/ CSS BMP Sizing Calculator (v2.1)

EXAMPLE Stormwater Management Plans w/ CSS BMP Sizing Calculator (v2.1) 525 Golden Gate Avenue, 11th Floor San Francisco, CA 94102 EXAMPLE Stormwater Management Plans w/ CSS BMP Sizing Calculator (v2.1) The following example Stormwater Management Plans (SMPs) are provided

More information

Corridor Pressurization System Performance in Multi-Unit Residential Buildings

Corridor Pressurization System Performance in Multi-Unit Residential Buildings Corridor Pressurization System Performance in Multi-Unit Residential Buildings Lorne Ricketts Student Member ASHRAE John Straube, PhD, P.Eng. Associate Member ASHRAE ABSTRACT Corridor pressurization based

More information

COLE ENGINEERING GROUP LTD.

COLE ENGINEERING GROUP LTD. CITY OF MARKHAM PROJECT FILE Stormwater Management Facilities Retrofit Municipal Class EA ES12-0316 COLE ENGINEERING GROUP LTD SEPTEMBER 2015 [ Month Year ] HEAD OFFICE 70 Valleywood Drive Markham, ON

More information

SITE PLAN CERTIFICATION REQUIREMENTS Rev 2 May 25, 2017

SITE PLAN CERTIFICATION REQUIREMENTS Rev 2 May 25, 2017 SITE PLAN CERTIFICATION REQUIREMENTS Rev 2 May 25, 2017 I. CONSTRUCTION PREREQUISITES 1.1. Pre-construction Survey A preconstruction survey of all existing infrastructure within the right of way (ROW)

More information

Minn. Stat. Sec.18C.305 BULK PESTICIDE/FERTILIZER STORAGE - NEW PERMIT APPLICATION

Minn. Stat. Sec.18C.305 BULK PESTICIDE/FERTILIZER STORAGE - NEW PERMIT APPLICATION Pesticide & Fertilizer Management Division, Ph. 651-201-6274 REQUIRES NEW PERMIT NUMBER: Minn. Stat. Sec.18C.305 BULK PESTICIDE/FERTILIZER STORAGE - NEW PERMIT APPLICATION NEW FACILITY SITE CHANGE IN OWNERSHIP

More information

2011 Guidance Manual for Development Stormwater Quality Control Measures

2011 Guidance Manual for Development Stormwater Quality Control Measures CITY OF MODESTO STORMWATER MANAGEMENT PROGRAM 2011 Guidance Manual for Development Stormwater Quality Control Measures Prepared for NPDES Permit No. CAS083526; Order R5-2008-0092 This page intentionally

More information

STORMWATER AND EROSION CONTROL PERMIT

STORMWATER AND EROSION CONTROL PERMIT STORMWATER MANAGEMENT AND EROSION CONTROL PERMIT INSTRUCTIONS AND INFORMATION Any project that involves the disturbance of ANY quantity of land requires the applicant to receive approval for the project

More information

Richland County Department of Public Works Engineering (Land Development) Division

Richland County Department of Public Works Engineering (Land Development) Division Richland County Department of Public Works Engineering (Land Development) Division Commercial Projects What is a Commercial Project? Projects that are not related to residential single family homes and/or

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

The following is required for a complete permit submittal for each unit.

The following is required for a complete permit submittal for each unit. P: (847)810-3503 OR (847)810-3503/3521, F: (847)615-4383 NEW MULTI-FAMILY DWELLING OR COMMERCIAL PERMIT REQUIREMENTS The following is required for a complete permit submittal for each unit. NEW MULTI-FAMILY

More information

CITY OF WINTER PARK SETBACK/COVERAGE WORKSHEET GUIDE FOR SINGLE FAMILY ZONING

CITY OF WINTER PARK SETBACK/COVERAGE WORKSHEET GUIDE FOR SINGLE FAMILY ZONING CITY OF WINTER PARK SETBACK/COVERAGE WORKSHEET GUIDE FOR SINGLE FAMILY ZONING See Setback/Coverage Worksheet & Criteria: Pages 1-4 & Accessory Structure Guide Step 1 Step 2 Step 3 Step 4 Step 5 Step 6

More information

Summary of Detention Pond Calculation Canyon Estates American Canyon, California

Summary of Detention Pond Calculation Canyon Estates American Canyon, California July 15, 2015 Bellecci & Associates, Inc Summary of Detention Pond Calculation Canyon Estates American Canyon, California 1. Methodology: Method: Unit Hydrograph Software: Bentley Pond Pack Version 8i

More information

APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT

APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT APPLICATION FOR PUBLIC INFRASTRUCTURE PERMIT Engineering Division 550 Landa Street New Braunfels, Texas 78130 (830) 221-4020 1. Subdivision Plat Name: Location Description/ Nearest Intersection: Acreage:

More information

SEWER SYSTEM DESIGN GUIDELINES

SEWER SYSTEM DESIGN GUIDELINES SEWER SYSTEM DESIGN GUIDELINES PART 1 GENERAL 1.1 GENERAL GUIDELINES A. The following sewer system design guidelines are based on Federal, State and Local health requirements, and the Berkeley County Water

More information

SAN GORGONIO PASS CAMPUS - PHASE I

SAN GORGONIO PASS CAMPUS - PHASE I SAN GORGONIO PASS CAMPUS - PHASE I Banning, CA DRAINAGE STUDY June 16, 2010 Reference 106-195 PREPARED BY: Encompass Associates, Inc. 5699 Cousins Place Rancho Cucamonga, CA 91737 909-684-0093 Fax-909-586-6979

More information

City of North Miami Beach, Florida COMMUNITY DEVELOPMENT DEPARTMENT

City of North Miami Beach, Florida COMMUNITY DEVELOPMENT DEPARTMENT City of North Miami Beach, Florida COMMUNITY DEVELOPMENT DEPARTMENT TO: Planning and Zoning Board FROM: Carlos M. Rivero, City Planner DATE: August 10, 2015 RE: Storage Facility P&Z ITEM # 15-010 OWNER

More information

The City of Cocoa (City) is located in east

The City of Cocoa (City) is located in east FWRJ Reclaimed Water and Stormwater: A Perfect Pair to Meet Total Maximum Daily Load Wasteload Allocations? Danielle Honour, James Wittig, John A. Walsh, and Don Stevens Danielle Honour, P.E., D.WRE, and

More information

City of Jacksonville Development Guide Building Permits

City of Jacksonville Development Guide Building Permits City of Jacksonville TX City of Jacksonville Development Guide Building Permits A publication to help understand the Building Permit process in the City Jacksonville. Building Department 2011 J Revised

More information

Location Drainage Study

Location Drainage Study Location Drainage Study PROJECT ROUTE: LIMITS: MUNICIPALITY/COUNTY: JOB NUMBER: IL 47 at Burlington Road 750ft NW to 750ft SE of IL 47(Burlington), & 1000ft S to 1000ft N of Burlington (IL47) Kane County

More information

Modelling Climate Change and Urbanization Impacts on Urban Stormwater and Adaptation Capacity

Modelling Climate Change and Urbanization Impacts on Urban Stormwater and Adaptation Capacity 9th International Conference on Urban Drainage Modelling, Belgrade 2012 C4. Climate change impacts, pp.287-288 Modelling Climate Change and Urbanization Impacts on Urban Stormwater and Adaptation Capacity

More information

TORONTO GREEN STANDARD VERSION 2.0

TORONTO GREEN STANDARD VERSION 2.0 For New Mid to High Rise Residential and all New Non-Residential The Toronto Green Standard (TGS) is a two-tier set of performance measures, with supporting guidelines for new development. Its purpose

More information

Infiltration Guidelines

Infiltration Guidelines Appendix E Infiltration Guidelines As a stormwater management method, infiltration means retaining or detaining water within soils to reduce runoff. Infiltration can be a cost-effective method to manage

More information

GRAY WATER SYSTEMS FOR RESIDENTIAL BUILDINGS

GRAY WATER SYSTEMS FOR RESIDENTIAL BUILDINGS INFORMATION BULLETIN / PUBLIC - PLUMBING CODE REFERENCE NO.: LAMC 94.1502.0 Effective: 01-01-2017 DOCUMENT NO.: P/PC 2017-012 Revised: Previously Issued As: P/PC 20014-012 GRAY WATER SYSTEMS FOR RESIDENTIAL

More information

LOCATION AND DESIGN DIVISION

LOCATION AND DESIGN DIVISION VIRGINIA DEPARTMENT OF TRANSPORTATION LOCATION AND DESIGN DIVISION INSTRUCTIONAL AND INFORMATIONAL MEMORANDUM GENERAL SUBJECT: Virginia Stormwater Management Program SPECIFIC SUBJECT: Application of the

More information

UNIVERSITY OF OREGON NORTH CAMPUS CONDITIONAL USE PERMIT PROJECT Draft Conditional Use Permit Stormwater, Sanitary Sewer, and Water Analysis Report

UNIVERSITY OF OREGON NORTH CAMPUS CONDITIONAL USE PERMIT PROJECT Draft Conditional Use Permit Stormwater, Sanitary Sewer, and Water Analysis Report UNIVERSITY OF OREGON NORTH CAMPUS CONDITIONAL USE PERMIT PROJECT Draft Conditional Use Permit Stormwater, Sanitary Sewer, and Water Analysis Report Prepared for: Cameron McCarthy Landscape Architects LLP

More information

SECTION STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 402 STORM DRAINAGE DESIGN CRITERIA 400-1

SECTION STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 402 STORM DRAINAGE DESIGN CRITERIA 400-1 CITY OF THORNTON Standards and Specifications Revised: October 2012 SECTION 400 - STORM DRAINAGE DESIGN, GRADING, AND WATER QUALITY TECHNICAL CRITERIA TABLE OF CONTENTS PAGE 401 GENERAL PROVISIONS 400-1

More information

Section 1 OBC FADS /13 Access to Parking Areas

Section 1 OBC FADS /13 Access to Parking Areas Section 1 OBC 3.8.2.2 4.3.12/13 Access to Parking Areas A barrier-free path of travel is provided from: a) the entrance to the exterior parking area b) at least one parking level where a passenger elevator

More information

CHESAPEAKE BAY TMDL ACTION PLAN ( MS4 General Permit)

CHESAPEAKE BAY TMDL ACTION PLAN ( MS4 General Permit) CHESAPEAKE BAY TMDL ACTION PLAN (2013 2018 MS4 General Permit) Central Virginia Community College A Plan for Achieving a 5% Reduction of Existing Loads June 30, 2015 Main Campus This plan satisfies the

More information

CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL

CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL CHAPTER 6 COLLECTION SYSTEM HYDRAULIC MODEL INTRODUCTION The District developed a hydraulic model of the sanitary sewer system as part the 2000 Wastewater Comprehensive Plan. The output from this model

More information

Residential Building Permit Application

Residential Building Permit Application City of Twin Falls Building Department 324 Hansen Street East P.O. Box 1907 Twin Falls, ID 83303-1907 208-735-7238 208-736-2256 www.tfid.org PROJECT INFORMATION Project Residential Building Permit Application

More information

Modelling and Analysis of EES Systems Using SWMM

Modelling and Analysis of EES Systems Using SWMM Planning and Design of a Right-of-Way LID (Etobicoke Exfiltration System) July 24 th 2015 Toronto, Ontario, Canada ling and Analysis of EES Systems Using SWMM Darko Joksimovic Department of Civil Engineering,

More information

GRAND NIAGARA Proposed Secondary Plan

GRAND NIAGARA Proposed Secondary Plan GRAND NIAGARA Proposed Secondary Plan Public Open House #3 January 17. 2017 scope + process BUILT Grand Niagara Secondary Plan The Grand Niagara Secondary Plan will establish a framework for the future

More information

BUILDING PERMIT APPLICATION PACKAGE

BUILDING PERMIT APPLICATION PACKAGE BUILDING PERMIT APPLICATION PACKAGE NOTICE TO BUILDING PERMIT APPLICANTS In addition to completed applications forms, the following documentation is required to accompany all building permit applications

More information

Element Z General Design Requirements Existing Facilities Information

Element Z General Design Requirements Existing Facilities Information Anderson Central 100B, PART 1 - INTRODUCTION 1.01 OVERVIEW A. This Section provides general information for building systems and components. B. Refer to the Owner s Design Guideline Elements A though G

More information

Civic Address (Street No. & Name):

Civic Address (Street No. & Name): Building Permit District of Squamish 37955 2nd Avenue, PO Box 310 Squamish, BC V8B 0A3 604.815.5011 www.squamish.ca Application Form Civic Address (Street No. & Name): OFFICE USE ONLY: Folio/Roll No.:

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

Stormwater Local Design Manual For Houston County, Georgia

Stormwater Local Design Manual For Houston County, Georgia Stormwater Local Design Manual For Houston County, Georgia Adopted November 15, 2005 TABLE OF CONTENTS 1. FORWARD... 1 2. GENERAL LEVEL OF SERVICE STANDARDS... 2 2.1. DETENTION REQUIREMENTS... 2 2.1.1.

More information

Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17)

Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17) Baseline Hillside Ordinance Correction Sheet (Ordinance No. 184,802 Effective 3/17/17) Plan Check #: Permit App. #: Job Address: Zone: Maximum Allowed RFA: Plan Check Engineer: Phone: Fax: (E-mail: firstname.lastname@lacity.org)

More information

APPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix.

APPENDIX C INLETS. The application and types of storm drainage inlets are presented in detail in this Appendix. Storm Drainage 13-C-1 APPENDIX C INLETS 1.0 Introduction The application and types of storm drainage inlets are presented in detail in this Appendix. 2.0 Inlet Locations Inlets are required at locations

More information

OFFICE OF THE COMMUNITY & NEIGHBORHOOD SERVICES City Hall Holland, Michigan

OFFICE OF THE COMMUNITY & NEIGHBORHOOD SERVICES City Hall Holland, Michigan OFFICE OF THE COMMUNITY & NEIGHBORHOOD SERVICES City Hall Holland, Michigan Community & Neighborhood Services Report To: Planning Commission Date: March 14, 2017 Subject: Site Plan Review New storage building

More information