ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 6401 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT

Size: px
Start display at page:

Download "ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 6401 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT"

Transcription

1 ÉCOLE SECONDAIRE CATHOLIQUE SECTEUR ORLÉANS 641 RENAUD ROAD DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT Prepared by: NOVATECH ENGINEERING CONSULTANTS LTD. Suite 2, 24 Michael Cowpland Drive Kanata, Ontario K2M 1P6 December 2, 213 Revised May 23, 214 Ref: R Novatech File No

2

3 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. TABLE OF CONTENTS 1. INTRODUCTION Purpose Location and Site Description Consultation and Reference Material Reference Items PROPOSED DEVELOPMENT SITE SERVICING Sanitary Water Domestic Water Demand Water Supply for Fire-Fighting Storm and Stormwater Management Stormwater Management Criteria and Objectives Allowable Release Rate Post-Development Conditions SITE GRADING Major System Overflow Route Erosion and Sediment Control PHASING GEOTECHNICAL INVESTIGATIONS CONCLUSION... 1 LIST OF FIGURES Figure 1 Aerial Plan LIST OF APPENDICIES Appendix A: Correspondence Appendix B: Development Servicing Study Checklist Appendix C: Rational Method Calculations, IDF Curves Appendix D: SWM Summary Sheet, Storage Calculations, Storm Sewer Design Sheet Appendix E: Sample Calculations Appendix F: IPEX Inlet Control Device Information Appendix G: Control Flow Roof Drain Information LIST OF DRAWINGS General Plan of Services (C1) Grading Plan (C2) Stormwater Management Plan (C3) Novatech Engineering Consultants Ltd. i

4 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. 1. INTRODUCTION The Conseil des écoles catholiques du Centre-Est (CECCE) is proposing to construct a new high-school in Orleans and Novatech Engineering Consultants Ltd. (Novatech) has been retained to complete the site servicing and grading design for this project. 1.1 Purpose This report outlines the servicing aspects of the proposed development with respect to water, sanitary and storm drainage and addresses the approach to stormwater management. This report is being submitted in support of the site plan application for the subject property. 1.2 Location and Site Description The proposed catholic high-school will be located at 641 Renaud Road, on the east side of the future Belcourt Boulevard intersection, in the City of Ottawa. The subject property is bordered by Renaud Road to the south, the Belcourt Boulevard extension to the west and future residential developments to the north and east. Figure 1 Aerial Plan provides an aerial view of the site. The legal description of the property is designated as Part of Lots 2 & 3, Concession 3 (Ottawa Front) Geographic Township of Gloucester, in the City of Ottawa. Novatech Engineering Consultants Ltd. 1

5 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. 1.3 Consultation and Reference Material A pre-consultation meeting was held with the City of Ottawa on October 11, 213, at which time the client was advised of the general submission requirements. Refer to Appendix A for a summary of the correspondence from the pre-consultation meeting held with the City of Ottawa. A pre-consultation meeting was neither held with the Ministry of the Environment (MOE) nor with the Rideau Valley Conservation Authority (RVCA) regarding the proposed development. These agencies were however consulted as part of the Master Servicing Study for the Trails Edge and Orleans Business Park. We do anticipate requiring a permit from the RVCA in order to fill the existing drainage ditch located within the northern portion of the site Reference Items 1 The Servicing Report for Trails Edge and Orleans Business Park (Ref. No. 1-49) was prepared by DSEL, Revision 6, dated March 214. (Still under review by City of Ottawa) 2 The Geotechnical Investigation Report (LRL Ref. No. 1377) was prepared by LRL Associates Ltd. in November The Phase I Environmental Site Assessment (LRL Ref. No. 1377) was prepared by LRL Associates Ltd. on October 8, PROPOSED DEVELOPMENT The proposed development will consist of a 2-storey high-school and associated parking lot, bus drop-off, school yard and sports field. As per the City of Ottawa s request, the school will be located as close as possible to the northeast corner of Renaud Road and the Belcourt Boulevard intersection. The proposed school site will encompass the entire property and will be accessible from both Renaud Road and Belcourt Boulevard. The undeveloped site is approximately.6 hectares in size. 3. SITE SERVICING The objective of the site servicing design is to conform to the requirements of the City of Ottawa; to provide a suitable domestic water supply, proper sewage outlets and to ensure that appropriate fire protection is provided. The servicing criteria, expected sewage flows and water demands for the site have been established using the City of Ottawa municipal design guidelines for sewer and water distribution, which is consistent with the the Servicing Report for the Trails Edge and Orleans Business Park Report 1. The proposed school will be serviced by extending services to the future municipal watermain and storm sewer in the Belcourt Boulevard. A new sanitary service will be extended to the future municipal sanitary sewer in Renaud Road. Refer to the enclosed General Plan of Services and to the subsequent sections of the report for further details. The City of Ottawa Servicing Study Guidelines for Development Applications requires a Development Servicing Study Checklist to confirm that each applicable item is deemed Novatech Engineering Consultants Ltd. 2

6 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. complete and ready for review by City of Ottawa Infrastructure Approvals. A completed checklist is enclosed in Appendix B at the back of the report. 3.1 Sanitary The proposed high-school will be serviced by a 2mm dia. sanitary service connected to the future sanitary sewer in Renaud Road. The City of Ottawa design criteria were used to calculate the theoretical sanitary flows for the proposed school, which includes the anticipated future expansions. The following design criteria were taken from Section 4 Sanitary Sewer Systems and Appendix 4-A - Daily Sewage Flow For Various Types of Establishments of the City of Ottawa Sewer Design Guidelines: Average Daily Sewage Flows: Institutional Average Flow:, L/gross ha/day School with cafeteria, gym and showers: 9 L/person/day Institutional Peaking Factor = 1. Infiltration Allowance:.28 L/s/ha x.6 ha site = 1.42 L/s For comparison purposes the theoretical sanitary flows were calculated using two methods. Table 3.1A identifies the theoretical sanitary flows based on typical institutional flows relative to the site area, while Table 3.1B identifies the theoretical sanitary flows for the school based on a design population, using the above design criteria. Table 3.1A Theoretical Sanitary Flows based on the Site Area Site Area Average Flow (L/s) Peaking Factor Peak Flow (L/s) Infiltration Allowance (L/s) Total Flow (L/s) Table 3.1B Theoretical Sanitary Flows based on the Design Population Type of Use Design Parameter Average Flow (L/s) Peaking Factor Peak Flow (L/s) Total Flow (L/s) School 12 students * School 14 staff * Total ** * Includes the possible future expansion of the school **Includes an Infiltration allowance of 1.42 L/s The proposed 2mm dia. sanitary service will be a gravity pipe at a minimum slope of 1.% with a full flow conveyance capacity of 34.2 L/s and will have sufficient capacity to convey the theoretical sanitary flows calculated in Tables 3.1A and 3.1B. The sanitary service was sized to accommodate the larger, more conservative flows calculated by the Mechanical Engineer using Fixture Units. Novatech Engineering Consultants Ltd. 3

7 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. The proposed school site has been accounted for in the Master Servicing Study for the Trails Edge and Orleans Business Park prepared by DSEL. 3.2 Water The proposed building will be serviced by a 1mm dia. water service connected to the future 4mm dia. watermain in Belcourt Boulevard. The proposed 1mm diameter service will be sized to provide both the required domestic water demand and fire flow for the proposed school. A shut-off valve will be provided at the property line. The water meter will be located in the mechanical room inside the building; while the remote meter will be located on the exterior face of the building. A new on-site hydrant will be connected to the proposed water service and will be located near the main building entrance, within 4m of the building siamese connection Domestic Water Demand The City of Ottawa design criteria were used to calculate the theoretical water demand for the proposed school. The following design criteria were taken from Section 4 Water Distribution Systems of the Ottawa Design Guidelines Water Distribution: Maximum Day Demand = 2. x Average Day Demand Maximum Hour Demand = 2.2 x Maximum Day Demand Table identifies the theoretical domestic water demands for the proposed school based on the above design criteria. Table Theoretical Water Demand Type of Use Average Day Demand (L/s) Maximum Day Demand (L/s) Maximum Hour Demand (L/s) School 1.4 * *Taken from Table 3.1B above Water Supply for Fire-Fighting The proposed school will be sprinklered and supplied with a fire department siamese connection. A new on-site hydrant will be located near the main building entrance, within 4m of the siamese connection. Based on information provided by the Mechanical Engineer, the fire flow requirements for the building are expected to be in the order of 37 USGPM (or 23.6 L/s). The fire flow requirements include both sprinkler system and hose allowances in accordance with the OBC and NFPA 13. The sprinkler system will be designed by the fire protection (sprinkler) consultant as this process involves detailed hydraulic calculations based on building layout, pipe runs, head losses, fire pump requirements, etc. Booster pumps are not expected to be required. The above information is being provided to the City of Ottawa for use in the hydraulic analysis of the municipal watermain network. It is anticipated that the current City of Ottawa boundary conditions will not be applicable as they will be affected by the significant future developments in the area (including the future 4mm dia. watermain in Belcourt Boulevard). Novatech Engineering Consultants Ltd. 4

8 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. The proposed school site has been accounted for in the Master Servicing Study for the Trails Edge and Orleans Business Park prepared by DSEL. 3.3 Storm and Stormwater Management The stormwater management design for the proposed development will include on-site quantity control prior to releasing flows from the site. A detailed description of the sub-catchment areas and post-development flows are discussed in the subsequent sections of the report Stormwater Management Criteria and Objectives The criteria and objectives for the proposed stormwater management design are as follows: Provide a dual drainage system (i.e. minor and major system flows); Maximize the use of available storage on site; Control the post-development flows from the site to the maximum allowable release rate of 86 L/s for storms up to and including the 1:1 year design event (per DSEL Report 1 ). Create a defined major system overflow route to convey stormwater runoff exceeding the available on-site storage (greater than the 1:1 year event); and Provide guidelines to ensure that site preparation and construction is in accordance with the current Best Management Practices for Erosion and Sediment Control Allowable Release Rate As indicated in the Servicing Report for Trails Edge and Orleans Business Park Report 1, the maximum allowable release rate for the site was calculated to be 86 L/s Post-Development Conditions Under post-development conditions, the imperviousness of the site will increase significantly. In order to mitigate the stormwater related impacts due to the proposed development, flow from the site will be controlled by the use of multiple inlet control devices (ICD) and control flow roof drains prior to being directed into the municipal storm sewer system. Refer to the enclosed plans and to the subsequent sections of the report for further details Sub-catchment Areas A-1 to A-9 The post-development flow from sub-catchment areas A-1 to A-9 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 9. Stormwater runoff from these drainage areas will be temporarily stored on the surface of the paved bus drop-off and landscaped areas prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Novatech Engineering Consultants Ltd.

9 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Areas A-1 to A-9 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 2 mm dia L/s m³ 1:1 Year 2 mm dia L/s.6 m 13.7 m³ Max Volume Provided (m³) 139. m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Area A-1 The post-development flow from sub-catchment area A-1 will be attenuated by the use of an inlet control device installed in the outlet pipe of CB 1. Stormwater runoff from this drainage area will be temporarily stored on the surface prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from this sub-catchment area as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Drainage Area A-1 Design Event Orifice Plug Type ICD Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) Max Volume Provided (m³) 1: Year 77 mm dia 13.7 L/s - - 1:1 Year 77 mm dia 14.2 L/s.41 m 8.2 m³ 8.7 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix F for IPEX inlet control device information Sub-catchment Areas A-11 to A-13 The post-development flow from sub-catchment areas A-11 to A-13 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 13. Stormwater runoff from these drainage areas will be temporarily stored on the surface, adjacent to the sports field, prior to being discharged into the on-site storm sewer system. Novatech Engineering Consultants Ltd. 6

10 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Areas A-11 to A-13 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 14 mm dia. 8.7 L/s. m 7.4 m³ 1:1 Year 14 mm dia. 6. L/s.9 m m³ Max Volume Provided (m³) m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Areas A-14 to A-1 The post-development flow from sub-catchment areas A-14 to A-1 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 1. Stormwater runoff from these drainage areas will be temporarily stored on the surface (future parking lot expansion area) prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Areas A-14 to A-1 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 13 mm dia L/s m³ 1:1 Year 13 mm dia L/s.46 m 22. m³ Max Volume Provided (m³) 2. m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Areas A-16 to A-17 The post-development flow from sub-catchment areas A-16 to A-17 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 17. Stormwater runoff from these drainage areas will be temporarily stored on the surface of the paved parking lot prior to being discharged into the on-site storm sewer system. Novatech Engineering Consultants Ltd. 7

11 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table 3.1 summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table 3.1: Design Flow and Inlet Control Device Table Drainage Areas A-16 to A-17 Design Event Orifice Plug Type ICD Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) Max Volume Provided (m³) 1: Year 12 mm dia. 29. L/s.3 m 2.2 m³ 1:1 Year 12 mm dia. 3. L/s.44 m 2.1 m³ 24.8 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Areas A-18 to A-19 The post-development flow from sub-catchment areas A-18 to A-19 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 19. Stormwater runoff from these drainage areas will be temporarily stored on the surface of the paved parking lot prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Areas A-18 to A-19 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 16 mm dia L/s.3 m 2.6 m³ 1:1 Year 16 mm dia L/s.44 m 21.8 m³ Max Volume Provided (m³) 23.4 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Area A-2 The post-development flows from sub-catchment area A-2 will be attenuated by the use of twenty six (26) adjustable control flow roof drains. Stormwater runoff from this drainage area will be temporarily controlled on the roof, prior to being discharged into the on-site storm sewer Novatech Engineering Consultants Ltd. 8

12 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. system, via the building service. Each roof drain will control the flow to a maximum release rate of 3.8 L/s (or 6 USGPM) per drain at a maximum ponding depth of.1m above each drain. Table summarizes the post-development design flows from this sub-catchment area as well as the type of roof drains, the maximum ponding depths, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Roof Drain Table Drainage Area A-2 Design Event Control Flow Roof Drains Design Flow (L/s) Post-Development Conditions Ponding Depth (m) Surface Vol. Required (m³) Max Volume Provided (m³) 1: Year 1:1 Year Zurn Z-1 (US) Zurn Z-1 (US) 26 x 3.8L/s 98.8 L/s 26 x 3.8L/s 98.8 L/s Variable 26. m³.1 m 1.6 m³ 16. m³ As indicated in the table above, the building roof will provide sufficient storage for both the 1: year and 1:1 year design events. Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix G for roof drain information Sub-catchment Area A-21 The uncontrolled post-development flow from sub-catchment area A-21 was calculated using the Rational Method to be 13.6 L/s for the 1: year design event and 2.8 L/s for the 1:1 year design event. Refer to Appendix C for Rational Method calculations Sub-catchment Area A-22 The post-development flow from sub-catchment area A-22 will be attenuated by the use of an inlet control device installed in the outlet pipe of CB 22. Stormwater runoff from this drainage area will be temporarily stored on the surface prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from this sub-catchment area as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Novatech Engineering Consultants Ltd. 9

13 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Area A-22 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 117 mm dia. 3.8 L/s.4 m - 1:1 Year 117 mm dia L/s.62 m 1.1 m³ Max Volume Provided (m³) 1. m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Areas A-23 to A-24 The post-development flow from sub-catchment areas A-23 to A-24 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 24. Stormwater runoff from these drainage areas will be temporarily stored on the surface prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Drainage Areas A-23 to A-24 Design Event 1: Year 1:1 Year IPEX LMF Type ICD Tempest Vortex Tempest Vortex Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 7.2 L/s.6 m L/s.76 m 4.6 m³ Max Volume Provided (m³). m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix F for IPEX inlet control device information Sub-catchment Area A-2 The post-development flow from sub-catchment area A-2 will be attenuated by the use of an inlet control device installed in the outlet pipe of CB 2. Stormwater runoff from this drainage area will be temporarily stored on the surface prior to being discharged into the on-site storm sewer system. Novatech Engineering Consultants Ltd. 1

14 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table summarizes the post-development design flows from this sub-catchment area as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Drainage Area A-2 Design Event Orifice Plug Type ICD Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) Max Volume Provided (m³) 1: Year 79 mm dia L/s.4 m - 1:1 Year 79 mm dia. 1.4 L/s.6 m 8. m³ 8.4 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix F for IPEX inlet control device information Sub-catchment Areas A-26 to A-27 The post-development flow from sub-catchment areas A-26 to A-27 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 27. Stormwater runoff from these drainage areas will be temporarily stored on the surface of the paved parking lot prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Drainage Areas A-26 to A-27 Design Event Orifice Plug Type ICD Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year mm dia L/s.3 m 2.6 m³ 1:1 Year mm dia L/s.44 m 16.4 m³ Max Volume Provided (m³) 18.1 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix F for IPEX inlet control device information. Novatech Engineering Consultants Ltd. 11

15 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd Sub-catchment Areas A-28 to A-29 The post-development flow from sub-catchment areas A-28 to A-29 will be attenuated by the use of an inlet control device installed in the outlet pipe of CBMH 29. Stormwater runoff from these drainage areas will be temporarily stored on the surface of the paved parking lot prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from these sub-catchment areas as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Table : Design Flow and Inlet Control Device Table Design Event Orifice Plug Type ICD Design Flow (L/s) Drainage Areas A-28 to A-29 Post-Development Conditions Ponding Elevation (m) Volume Required (m³) 1: Year 97 mm dia L/s.3 m 2.6 m³ 1:1 Year 97 mm dia L/s.4 m 19. m³ Max Volume Provided (m³) 23.m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix E for sample orifice calculations Sub-catchment Area A-3 The uncontrolled post-development surface runoff from sub-catchment area A-3 was calculated using the Rational Method to be 1.3 L/s for the 1: year design event and 31.2 L/s for the 1:1 year design event. Refer to Appendix C for Rational Method calculations Sub-catchment Area A-31 The post-development flow from sub-catchment area A-2 will be attenuated by the use of an inlet control device installed in the outlet pipe of CB 3. Stormwater runoff from this drainage area will be temporarily stored on the surface prior to being discharged into the on-site storm sewer system. Table summarizes the post-development design flows from this sub-catchment area as well as the type of ICD, the anticipated ponding elevations, storage volumes required and storage volume provided for both the 1: year and the 1:1 year design events. Novatech Engineering Consultants Ltd. 12

16 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Table : Design Flow and Inlet Control Device Table Drainage Area A-31 Design Event Orifice Plug Type ICD Design Flow (L/s) Post-Development Conditions Ponding Elevation (m) Volume Required (m³) Max Volume Provided (m³) 1: Year 11 mm dia L/s.2 m - 1:1 Year 11 mm dia. 2.2 L/s.49 m 14.1 m³ 14.3 m³ Refer to Appendix C for Rational Method calculations, Appendix D for SWM summary and storage calculations and to Appendix F for IPEX inlet control device information Summary of Flows Table summarizes the post-development flows for both the 1: year and 1:1 year design events. Table : Summary of Post-Development flows from site Post-Development Flow (L/s) 1:1 year : year Design Event A-1 to A-9 A-1 A-11 to A-13 A-14 to A-1 A-16 to A-17 A-18 to A-19 A-2 A-21 A-22 A-23 to A-24 A-2 A-26 to A-27 A-28 to A-29 A-3 A-31 Total As indicated in the table above, the post-development flows from the site are well below the site allowable release rate of 86 L/s for both the 1: year and 1:1 year design events, thus allowing for a slight increase in flows in the future (if required). The proposed stormwater management system has been designed to accommodate the possible future expansion of the site. Should the bus loop be expanded in the future, the tributary flows from sub-catchment areas A-1 and A-31 would be increased slightly, however the increased bus loop area flows would be stored on the surface and controlled by ICDs. Should the school be expanded in the future, the tributary flows from sub-catchment areas A-8 and A-22 would be reduced due to the proposed building expansion. The controlled flows from sub-catchment areas A-23 and A-24 would be replaced with controlled building roof flows. The future parking lot expansion has already been accounted for in the weighted runoff coefficient calculations for sub-catchment areas A-14 and A-1. Similarly, the future portable roofs have Novatech Engineering Consultants Ltd. 13

17 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. already been accounted for in the weighted runoff coefficient calculations for sub-catchment areas A-1, A-19, A-22, A-2 and A Water Quality Control On-site water quality control is not required or provided as it will be provided by the downstream stormwater management facility (SWMF) as described in the Servicing Report for Trails Edge and Orleans Business Park Report SITE GRADING The existing site is generally flat and approximately 1.m below the current elevation of Renaud Road. An existing drainage ditch is located within the northern portion of the property and drains in a westerly direction towards Mud Creek, which is tributary to the East Urban Community (EUC) stormwater management facility (SWMF). The existing drainage ditch will be realigned (by others) on the north side of the school site as indicated on the enclosed plans and filled to accommodate the proposed development. The realignment of the drainage ditch, along with all appropriate applications for regulatory permits and approvals will be completed by others. The proposed site will have to be raised to match into the Renaud Road elevations and future Belcourt Boulevard elevations. The ground floor of the proposed school will be set at an elevation of 88.1m, slightly higher than the elevation of Renaud Road. The existing grades adjacent to the perimeter of the property will be raised to match into the future residential developments on the north and east side of the property. The proposed grading design includes considerations for the possible future school expansion. Refer to the enclosed plans for details. 4.1 Major System Overflow Route In the case of a major rainfall event exceeding the design storms provided for, the stormwater located within landscaped areas adjacent to the school will pond to a maximum depth of.3m prior to overflowing to a lower sub-catchment drainage area. Similarly, the stormwater located within the paved bus drop-off area will pond to a maximum depth of.26m before overflowing towards the paved parking area on the north side of the property. Stormwater located within the drainage swales adjacent to the sports field and running track will pond to a maximum depth of.3m before overflowing towards the paved parking lot. Stormwater located within the main parking lot area will pond to a maximum depth of.2m before overflowing into Belcourt Boulevard and ultimately into the realigned Mud Creek to the west. The major system overflow route is shown on the enclosed plan. 4.2 Erosion and Sediment Control To mitigate erosion and to prevent sediment from entering the storm sewer system, temporary erosion and sediment control measures will be implemented on-site during construction in accordance with the Best Management Practices for Erosion and Sediment Control. This includes the following temporary measures: Filter bags will be placed under the grates of nearby catchbasins, manholes and drains and will remain in place until vegetation has been established and construction is completed. Novatech Engineering Consultants Ltd. 14

18 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Silt fencing will be placed as per OPSS 77 and OPSD along the surrounding construction limits; Street sweeping and cleaning will be performed as required to suppress dust and to provide safe and clean roadways adjacent to the construction site. The proposed erosion and sediment control measures will be implemented prior to construction and will remain in place during all phases of construction. Regular inspection and maintenance of the erosion control measures will be undertaken regularly.. PHASING The proposed development will proceed as a single phase project. The enclosed plans do however indicate the possible future school expansion limits as well as the possible future parking lot and bus loop expansions. 6. GEOTECHNICAL INVESTIGATIONS A Geotechnical Investigation Report has been prepared by LRL Associates Ltd. for the proposed project. Refer to the Geotechnical Report 2 for subsurface conditions, construction recommendations and geotechnical inspection requirements. 7. CONCLUSION This report has been prepared in support of the site plan application for the proposed Orleans High School located at the intersection of Renaud Road and the future Belcourt Boulevard extension, in the City of Ottawa. The conclusions are as follows: The proposed development will consist of a 2-storey high-school complete with associated parking lot, bus drop-off, school yard and sports field. The proposed building will be serviced by extending services to the future municipal watermain and storm sewer in Belcourt Boulevard and to the future municipal sanitary sewer in Renaud Road. The building will be sprinklered and supplied with a fire department siamese connection. The siamese connection will be located within 4m of an on-site fire hydrant. Under post-development conditions, stormwater runoff from the site will consist of a combination of uncontrolled direct runoff and controlled flow. The controlled flow will be provided by the use of inlet control devices and control flow roof drains. The total post-development flow from the site will be controlled to a combined maximum rate of 38.2 L/s for the 1: year design event and to a combined maximum rate of 79.6 L/s for the 1:1 year design event, well below the allowable release rate of 86 L/s for the site. The stormwater management system has been designed to accommodate the possible future expansion of the school site. Novatech Engineering Consultants Ltd. 1

19

20 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX A Correspondence Novatech Engineering Consultants Ltd.

21

22

23

24

25

26 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX B Development Servicing Study Checklist Novatech Engineering Consultants Ltd.

27

28

29

30

31

32

33 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX C Rational Method Calculations, IDF Curves Novatech Engineering Consultants Ltd.

34 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. Novatech Engineering Consultants Ltd.

35 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. RATIONAL METHOD The Rational Method was used to determine the allowable release rate, pre-development and post-development runoff for the site. The equation is as follows: Q=2.78 CIA Where: Q is the runoff in L/s C is the weighted runoff coefficient* I is the rainfall intensity in mm/hr** A is the area in hectares *The weighted runoff coefficient is determined for each of the catchment areas as follows: C = (A perv x C perv) + (A imp x C imp) A tot Where: A perv is the pervious area in hectares C perv is the pervious area runoff coefficient (C perv=.2) A imp is the impervious area in hectares C imp is the impervious area runoff coefficient (C imp=.9) A tot is the catchment area (A perv + A imp) in hectares Note: Increase the C values above by 2% for the 1:1 year event (max. C imp=1.). ** The rainfall intensities used were taken from the City of Ottawa IDF curves. A time of concentration (t c) of 1 minutes was used for the post-development conditions, resulting in rainfall intensities of 14.2 mm/hr for the 1: year event and mm/hr for the 1:1 year event. SAMPLE POST-DEVELOPMENT FLOW CALCULATIONS AREA A-21: SHOP CLASS LOADING AREA Drainage Area (A) =.2 ha Impervious Area =.2 ha Pervious Area = NA Runoff Coefficient (C yr) =.9 Runoff Coefficient (C w1yr) = 1. Intensity (I ) = 14.2 mm/hr Intensity (I 1) = mm/hr C (.2.9) + (.2) yr = =.2 Q = 2.78 CIA Q = 2.78 x.9 x 14.2 x.2 Q = 13.6 L/s.9 Novatech Engineering Consultants Ltd.

36 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. C (.2 1.) + (.2) 1 yr = =.2 Q 1= 2.78 CIA Q 1= 2.78 x 1. x x.2 Q 1= 2.8 L/s 1. Refer to the SWM Summary Spreadsheets in Appendix D for post-development flow for all subcatchment drainage areas. Novatech Engineering Consultants Ltd.

37 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX D SWM Summary Sheet, Storage Calculations, Storm Sewer Design Sheet Novatech Engineering Consultants Ltd.

38

39

40

41

42

43

44

45

46

47

48

49 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX E Sample Calculations Novatech Engineering Consultants Ltd.

50 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. SAMPLE ORIFICE CALCULATION AREAS A-1 to A-9: ICD WITHIN OUTLET PIPE OF CBMH 9 In order to reduce the flow from these catchment areas an ICD will be installed in the outlet pipe of CBMH 9. Iterative calculations will be required to determine the orifice size, approximate design flow and head. The controlled flow through the orifice is assumed to be in the order of 12 L/s for the 1:1 year design event. The head is calculated from the water elevation to the centerline of the orifice and will be approximately 2.11m (.6m (8.31m +.23m)). Q =.62 x A x (2gh) 1/2.12=.62 x A x (2 x 9.81 x 2.11) 1/2 A =.3133 A = 3.14 x d 2 /4 d =.19974, therefore use a 2mm dia. orifice Iterative calculations were done to determine the release rate for the 1: year design event. The same orifice, with a design head of 1.96m (.6m (8.31m +.23m), will release the 1: year design event at the rate of: Q =.62 x A x (2gh) 1/2 Q =.62 x.3128 x (2 x 9.81 x 1.96) 1/2 Q =.1228 or 12.3 L/s Refer to the SWM Summary spreadsheets in Appendix D for the proposed orifice sizes. Novatech Engineering Consultants Ltd.

51 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX F IPEX Inlet Control Device Information Novatech Engineering Consultants Ltd.

52

53

54

55

56

57

58

59 Development Servicing Study and Stormwater Management Report Orleans H.S. - Renaud Rd. & Belcourt Blvd. APPENDIX G Control Flow Roof Drain Information Novatech Engineering Consultants Ltd.

60

61

62

63

64

65

66

67

68

69 GENERAL NOTES: 1. COORDINATE AND SCHEDULE ALL WORK WITH OTHER TRADES AND CONTRACTORS. 2. DETERMINE THE EXACT LOCATION, SIZE, MATERIAL AND ELEVATION OF ALL EXISTING UTILITIES PRIOR TO COMMENCING CONSTRUCTION. PROTECT AND ASSUME RESPONSIBILITY FOR ALL EXISTING UTILITIES WHETHER OR NOT SHOWN ON THIS DRAWING. 3. OBTAIN ALL NECESSARY PERMITS AND APPROVALS FROM THE CITY OF OTTAWA BEFORE COMMENCING CONSTRUCTION. 4. BEFORE COMMENCING CONSTRUCTION OBTAIN AND PROVIDE PROOF OF COMPREHENSIVE, ALL RISK AND OPERATIONAL LIABILITY INSURANCE FOR $2,,.. INSURANCE POLICY TO NAME OWNERS, ENGINEERS AND ARCHITECTS AS CO-INSURED RESTORE ALL DISTURBED AREAS ON-SITE AND OFF-SITE, INCLUDING TRENCHES AND SURFACES ON PUBLIC ROAD ALLOWANCES TO EXISTING CONDITIONS OR BETTER TO THE SATISFACTION OF THE CITY OF OTTAWA AND ENGINEER. 6. REMOVE FROM SITE ALL EXCESS EXCAVATED MATERIAL, ORGANIC MATERIAL AND DEBRIS UNLESS OTHERWISE INSTRUCTED BY ENGINEER. EXCAVATE AND REMOVE FROM SITE ANY CONTAMINATED MATERIAL. ALL CONTAMINATED MATERIAL SHALL BE DISPOSED OF AT A LICENSED LANDFILL FACILITY. 7. ALL ELEVATIONS ARE GEODETIC. REFER TO GEOTECHNICAL REPORT (No. 1377, DATED NOVEMBER 213), PREPARED BY LRL ASSOCIATES LTD, FOR SUBSURFACE CONDITIONS, CONSTRUCTION RECOMMENDATIONS, AND GEOTECHNICAL INSPECTION REQUIRE MENTS. THE GEOTECHNICAL CONSULTANT IS TO REVIEW ON-SITE CONDITIONS AFTER EXCAVATION PRIOR TO PLACEMENT OF THE GRANULAR MATERIAL. SEWER NOTES: WATERMAIN NOTES: SPECIFICATIONS: ITEM STORM / SANITARY MANHOLE SPEC. No. REFERENCE 71.1, 71.11, OPSD 71.12, CATCHBASIN (6x6mm) 7.1 OPSD CB, FRAME & COVER 4.2 OPSD STORM / SANITARY MH FRAME & COVER 41.1 OPSD WATERTIGHT FRAME AND COVER 41.3 OPSD SEWER TRENCH S6 & S7 CITY OF OTTAWA STORM SEWER PVC DR 3, CONC CLASS 6D SANITARY SEWER PVC DR 3 PERFORATED SUBDRAIN (LANDSCAPE AREA) S29,S3 & S31 CITY OF OTTAWA REFER TO ARCHITECT'S AND LANDSCAPE ARCHITECT'S DRAWINGS FOR BUILDING AND HARD SURFACE AREAS AND DIMENSIONS. 1. REFER TO DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT (R ) PREPARED BY NOVATECH ENGINEERING CONSULTANTS LTD. 11. SAW CUT AND KEY GRIND ASPHALT AT ALL ASPHALT TIE IN POINTS AS PER CITY OF OTTAWA STANDARDS (R1). SPECIFICATIONS: ITEM WATERMAIN TRENCHING THERMAL INSULATION IN SHALLOW TRENCHES THERMAL INSULATION OF WATERMAIN AT OPEN STRUCTURES WATERMAIN CROSSING BELOW SEWER HYDRANT INSTALLATION WATERMAIN SPEC. No. W17 W22 W23 REFERENCE CITY OF OTTAWA CITY OF OTTAWA CITY OF OTTAWA W2 W19 PVC DR18, PEX SDR9 CITY OF OTTAWA CITY OF OTTAWA 2. SUPPLY AND CONSTRUCT ALL WATERMAINS AND APPURTENANCES IN ACCORDANCE WITH THE CITY OF OTTAWA STANDARDS AND SPECIFICATIONS. EXCAVATION, INSTALLATION, BACKFILL AND RESTORATION OF ALL WATERMAINS BY THE CONTRACTOR. CONNECTIONS AND SHUT-OFFS AT THE MAIN AND CHLORINATION OF THE WATER SYSTEM SHALL BE PERFORMED BY CITY OFFICIALS. 3. WATERMAIN SHALL BE MINIMUM 2.4m DEPTH BELOW GRADE UNLESS OTHERWISE INDICATED. 4. WATER SERVICE IS TO BE CONSTRUCTED TO WITHIN 1.m OF FOUNDATION WALL AND CAPPED, UNLESS OTHERWISE INDICATED. 12. PROVIDE LINE/PARKING PAINTING. 2. SERVICES ARE TO BE CONSTRUCTED TO 1.m FROM FACE OF BUILDING AT A MINIMUM SLOPE OF 1.%. 13. CONTRACTOR TO PROVIDE THE CONSULTANT WITH A GENERAL PLAN OF SERVICES INDICATING ALL SERVICING AS-BUILT INFORMATION SHOWN ON THIS PLAN. AS-BUILT INFORMATION MUST INCLUDE: PIPE MATERIAL, SIZES, LENGTHS, SLOPES, INVERT AND T/G ELEVATIONS, STRUCTURE LOCATIONS, VALVE AND HYDRANT LOCATIONS, T/WM ELEVATIONS AND ANY ALIGNMENT CHANGES, ETC. 3. FLEXIBLE CONNECTIONS ARE REQUIRED FOR CONNECTING PIPES TO MANHOLES (FOR EXAMPLE KOR-N-SEAL, PSX: POSITIVE SEAL AND DURASEAL). THE CONCRETE CRADLE FOR THE PIPE CAN BE ELIMINATED. 4. THE OWNER SHALL REQUIRE THAT THE SITE SERVICING CONTRACTOR PERFORM FIELD TESTS FOR QUALITY CONTROL OF ALL SANITARY SEWERS. LEAKAGE TESTING SHALL BE COMPLETED IN ACCORDANCE WITH OPSS , AND DYE TESTING IS TO BE COMPLETED ON ALL SANITARY SERVICES TO CONFIRM PROPER CONNECTION TO THE SANITARY SEWER MAIN. THE FIELD TESTS SHALL BE PERFORMED IN THE PRESENCE OF A CERTIFIED PROFESSIONAL ENGINEER WHO SHALL SUBMIT A CERTIFIED COPY OF THE TEST RESULTS.. STORM MANHOLES AND CBMHS ARE TO HAVE 3mm SUMPS UNLESS OTHERWISE INDICATED. 6. ALL CATCHBASINS AND CATCHBASIN MANHOLES TO BE PROVIDED WITH MINIMUM 3 METER LONG PERFORATED SUBDRAINS WHICH EXTEND IN AT LEAST TWO DIRECTIONS FROM EACH CATCHBASIN AT PAVEMENT SUBGRADE LEVEL. 7. LEGEND PROPOSED CURB DC PROPOSED DEPRESSED CURB PROPOSED WATERMAIN AND DIAMETER VVB PROPOSED VALVE LOCATION PROPOSED SIAMESE CONNECTION PROPOSED WATER METER PROPOSED REMOTE METER SANMH 1 PROPOSED SANITARY MANHOLE & SEWER STMMH 1 PROPOSED STORM MANHOLE & SEWER T/G PROPOSED TOP OF GRATE ELEVATION DIRECTION OF FLOW CB 1 PROPOSED CATCHBASIN CBMH 1 PROPOSED CATCHBASIN MANHOLE PROPOSED ROOF DRAIN LD PROPOSED LANDSCAPE DRAIN SEEPAGE BARRIER LOCATION PER GEOTECHNICAL REPORT PROPOSED BIKE RACK PROPOSED SITE LIGHTING ISSUE NO. 26 ROOF DRAINS 3.8 L/S FLOW PER DRAIN.97m MAX PONDING DEPTH 6.m3 STORAGE VOLUME PER DRAIN 16.m3 TOTAL STORAGE VOLUME REV. NO. DATE YY/MM/DD ISSUE PROJECT TITLE/TITRE DU PROJET ADDRESS OTTAWA, ONTARIO DU CENTRE-EST 4, RUE LABELLE, OTTAWA, ON K1J 1A1 DRAWING TITLE/TITRE DU DESSIN SERVICING PLAN 1: STATION SURFACE TOP OF WM ELEVATION ELEVATION STATION DESCRIPTION CAP 1.m FROM BUILDING FACE SURFACE TOP OF WM ELEVATION ELEVATION DESCRIPTION DRAWN BY CHECKED BY CROSS BELOW SAN (CLEARANCE=.m) VALVE AND VALVE BOX HYDRANT DATE ISSUE No PROJ. No SCALE LSC FST REV. No 2 DRAWING/DESSIN C1 DECEMBER 213 FICHIER ACAD FILE: GP.dwg

70 GENERAL NOTES: 1. COORDINATE AND SCHEDULE ALL WORK WITH OTHER TRADES AND CONTRACTORS. 7. ALL ELEVATIONS ARE GEODETIC. REFER TO FOUR SITE BENCHMARKS AS INDICATED ON THE PLAN. 2. DETERMINE THE EXACT LOCATION, SIZE, MATERIAL AND ELEVATION OF ALL EXISTING SERVICES AND UTILITIES PRIOR TO COMMENCING CONSTRUCTION. PROTECT AND ASSUME RESPONSIBILITY FOR ALL EXISTING SERVICES AND UTILITIES WHETHER OR NOT SHOWN ON THIS DRAWING. 8. REFER TO GEOTECHNICAL REPORT No.1377 (DATED NOVEMBER, 1, 213) PREPARED BY LRL ASSOCIATES LTD., FOR SUBSURFACE CONDITIONS, CONSTRUCTION RECOMMENDATIONS, AND GEOTECHNICAL INSPECTION REQUIREMENTS. THE GEOTECHNICAL CONSULTANT IS TO REVIEW ON-SITE CONDITIONS AFTER EXCAVATION PRIOR TO PLACEMENT OF THE GRANULAR MATERIAL. 3. OBTAIN ALL NECESSARY PERMITS AND APPROVALS FROM THE CITY OF OTTAWA BEFORE COMMENCING CONSTRUCTION. 11. SAW CUT AND KEYGRIND ASPHALT AT ALL ROAD CUTS AND ASPHALT TIE IN POINTS AS PER CITY OF OTTAWA STANDARDS (R1). 12. CONTRACTOR TO PROVIDE THE CONSULTANT WITH A GRADING PLAN INDICATING THE AS-BUILT ELEVATION OF EVERY DESIGN GRADE SHOWN ON THIS PLAN DRAWING TITLE/TITRE DU DESSIN.4 86 PROPOSED HYDRANT.71 x 86. x T.7 B/W PROPOSED TOP OF WALL ELEVATION 1: YEAR PONDING LIMITS PROPOSED BIKE RACK 88.1 CB 1 CBMH 1 LD 2.% PROPOSED ENTRANCE/EXIT PROPOSED CATCHBASIN C/W CATCHBASIN LEAD GRADE AND DIRECTION STMMH 1 PROPOSED CATCHBASIN MANHOLE 1: DRAWN BY LSC PROPOSED LANDSCAPE DRAIN PROPOSED STORM MANHOLE & SEWER CHECKED BY FST PROPOSED CURB DC DIRECTION OF MAJOR OVERLAND FLOW PROPOSED DEPRESSED CURB PROPOSED ROOF DRAIN PROPOSED VALVE AND VALVE BOX PROPOSED SILT FENCE DATE ISSUE No PROJ. No SCALE PROPOSED BOTTOM OF WALL ELEVATION GRADING, SEDIMENT AND EROSION CONTROL PLAN 1:1 YEAR PONDING LIMITS PROPOSED ELEVATION /W x DU CENTRE-EST 4, RUE LABELLE, OTTAWA, ON K1J 1A1 88. LEGEND PROPOSED VALVE AND VALVE BOX ADDRESS OTTAWA, ONTARIO PROJECT TITLE/TITRE DU PROJET ROOF DRAINS 3.8 L/S FLOW PER DRAIN.97m MAX PONDING DEPTH 6.m 3 STORAGE VOLUME PER DRAIN 16.m3 TOTAL STORAGE VOLUME T/ W ISSUE W B/ 2.3 B/ W DATE YY/MM/DD T/W B/W REV. NO ISSUE NO /W /W.91 B /W T/W.9 T 7. 8 B T/W T/W T/ W W B/ T 8. B/W /W HEAVY DUTY (FULL DEPTH) mm HL3 mm HL8 1mm GRANULAR "A" 4mm GRANULAR "B" TYPE II LIGHT DUTY (FULL DEPTH) mm HL3 1mm GRANULAR "A" 3mm GRANULAR "B" TYPE II SEDIMENT AND EROSION CONTROL MEASURES MAY BE MODIFIED IN THE FIELD AT THE DISCRETION OF THE CITY OF OTTAWA SITE INSPECTOR OR THE CONSERVATION AUTHORITY THE CONTRACTOR SHALL ENSURE PROPER DUST CONTROL IS PROVIDED WITH THE APPLICATION OF WATER (AND IF REQUIRED, CALCIUM CHLORIDE) DURING DRY PERIODS ALL CURBS SHALL BE BARRIER CURB (1mm) UNLESS OTHERWISE NOTED AND CONSTRUCTED AS PER CITY OF OTTAWA STANDARDS (SC1.1) ROADWAYS ARE TO BE SWEPT AS REQUIRED OR AS DIRECTED BY THE ENGINEER AND/OR MUNICIPALITY ALL GRADES BY CURBS ARE EDGE OF PAVEMENT GRADES UNLESS OTHERWISE INDICATED THE CONTRACTOR ACKNOWLEDGES THAT FAILURE TO IMPLEMENT EROSION AND SEDIMENT CONTROL MEASURES MAY BE SUBJECT TO PENALTIES IMPOSED BY ANY APPLICABLE REGULATORY AGENCY MINIMUM OF 2% GRADE FOR PROPSED SIDEWALK WITHIN THE CITY R.O.W. UNLESS OTHERWISE NOTED THE CONTRACTOR SHALL IMMEDIATELY REPORT TO THE ENGINEER ANY ACCIDENTAL DISCHARGES OF SEDIMENT MATERIAL INTO ANY STORM SEWER SYSTEM. APPROPRIATE RESPONSE MEASURES, INCLUDING ANY REPAIRS TO EXISTING CONTROL MEASURES OR THE IMPLEMENTATION OF ADDITIONAL CONTROL MEASURES, SHALL BE CARRIED OUT BY THE CONTRACTOR WITHOUT DELAY THE SEDIMENT CONTROL MEASURES SHALL ONLY BE REMOVED WHEN, IN THE OPINION OF THE ENGINEER, THE MEASURES ARE NO LONGER REQUIRED. NO CONTROL MEASURES MAY BE PERMANENTLY REMOVED WITHOUT PRIOR AUTHORIZATION FROM THE ENGINEER. 4. GRADE AND/OR FILL BEHIND PROPOSED CURB AND BETWEEN BUILDINGS AND CURBS, WHERE REQUIRED TO PROVIDE POSITIVE DRAINAGE TO PREVENT SURFACE EROSION FROM ENTERING ANY STORM SEWER SYSTEM DURING CONSTRUCTION, FILTER BAGS WILL BE PLACED UNDER GRATES OF NEARBY CATCHBASINS AND STRUCTURES. A LIGHT DUTY SILT FENCE BARRIER WILL ALSO BE INSTALLED AROUND THE CONSTRUCTION AREA (WHERE APPLICABLE). THESE CONTROL MEASURES WILL REMAIN IN PLACE UNTIL CONSTRUCTION IS COMPLETE. PAVEMENT STRUCTURE: ALL EROSION AND SEDIMENT CONTROLS ARE TO BE INSTALLED TO THE SATISFACTION OF THE ENGINEER AND THE CITY OF OTTAWA. THEY ARE TO BE APPROPRIATE TO THE SITE CONDITIONS, PRIOR TO UNDERTAKING ANY SITE ALTERATIONS (FILLING, GRADING, REMOVAL OF VEGETATION, ETC.) AND DURING ALL PHASES OF SITE PREPARATION AND CONSTRUCTION. THESE PRACTICES ARE TO BE IMPLEMENTED IN ACCORDANCE WITH THE CURRENT BEST MANAGEMENT PRACTICES FOR EROSION AND SEDIMENT CONTROL AND SHOULD INCLUDE AS A MINIMUM THOSE MEASURES INDICATED ON THE PLAN. 8. REFER TO LANDSCAPE PLAN FOR PLANTING AND OTHER LANDSCAPE FEATURE DETAILS REMOVE FROM SITE ALL EXCESS EXCAVATED MATERIAL UNLESS OTHERWISE INSTRUCTED BY ENGINEER. EXCAVATE AND REMOVE FROM SITE ALL ORGANIC MATERIAL AND DEBRIS. ALL CONTAMINATED MATERIAL SHALL BE DISPOSED OF AT A LICENSED LANDFILL FACILITY. 1. ALL TOPSOIL, ORGANIC OR DELETERIOUS MATERIAL MUST BE ENTIRELY REMOVED FROM BENEATH THE PROPOSED BUILDING AND PAVED AREAS. 3. THE GRANULAR BASE SHOULD BE COMPACTED TO AT LEAST 98% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY VALUE. ANY ADDITIONAL GRANULAR FILL USED BELOW THE PROPOSED PAVEMENT SHOULD BE COMPACTED TO AT LEAST 9% OF THE STANDARD PROCTOR MAXIMUM DRY DENSITY VALUE. 1. REFER TO ARCHITECT'S AND LANDSCAPE ARCHITECT'S DRAWINGS FOR BUILDING AND HARD SURFACE AREAS AND DIMENSIONS.. RESTORE ALL DISTURBED AREAS ON-SITE AND OFF-SITE, INCLUDING TRENCHES AND SURFACES ON PUBLIC ROAD ALLOWANCES TO EXISTING CONDITIONS OR BETTER TO THE SATISFACTION OF THE CITY OF OTTAWA AND THE OTTAWA HOSPITAL. EROSION AND SEDIMENT CONTROL NOTES : 2. EXPOSED SUBGRADE IN PROPOSED PAVED AREAS SHOULD BE PROOF ROLLED WITH A LARGE STEEL DRUM ROLLER AND ANY SOFT AREAS EVIDENT FROM THE PROOF ROLLING SHOULD BE SUBEXCAVATED AND REPLACED WITH SUITABLE MATERIAL THAT IS FROST COMPATIBLE WITH THE EXISTING SOILS. 9. REFER TO 'DEVELOPMENT SERVICING STUDY AND STORMWATER MANAGEMENT REPORT' No. R PREPARED BY NOVATECH ENGINEERING CONSULTANTS LIMITED. 4. BEFORE COMMENCING CONSTRUCTION OBTAIN AND PROVIDE PROOF OF COMPREHENSIVE, ALL RISK AND OPERATIONAL LIABILITY INSURANCE FOR $2,,.. INSURANCE POLICY TO NAME OWNERS, ENGINEERS AND ARCHITECTS AS CO-INSURED AND THE CITY OF OTTAWA AS THIRD PARTY. GRADING NOTES: 1332 REV. No 2 2 DRAWING/DESSIN C2 DECEMBER 213 FICHIER ACAD FILE: GR

71 LEGEND PROPOSED CURB DC STMMH 1 T/G DRAINAGE AREA (hectares) PROPOSED DEPRESSED CURB PROPOSED STORM MANHOLE & SEWER PROPOSED TOP OF GRATE ELEVATION DIRECTION OF FLOW CB 1 CBMH 1 LD.3 A A A A18.76 DRAINAGE AREA NUMBER CATCHMENT AREA RUN-OFF COEFFICIENT (1: YR) STORM DRAINAGE AREA PROPOSED CATCHBASIN PROPOSED CATCHBASIN MANHOLE APPROXIMATE YEAR POND AREA PROPOSED ROOF DRAIN APPROXIMATE 1 YEAR POND AREA PROPOSED LANDSCAPE DRAIN.128 A A A A A A A A A A A A A A21.9 ISSUE NO. REV. NO. DATE YY/MM/DD ISSUE.64 A9.6. A A A A A A A6.6 PROJECT TITLE/TITRE DU PROJET 26 ROOF DRAINS 3.8 L/S FLOW PER DRAIN.97m MAX PONDING DEPTH 6.m 3 STORAGE VOLUME PER DRAIN 16.m3 TOTAL STORAGE VOLUME.118 A1.6.3 A2.6 ADDRESS OTTAWA, ONTARIO.8 A A A.6 DU CENTRE-EST 4, RUE LABELLE, OTTAWA, ON K1J 1A1 DRAWING TITLE/TITRE DU DESSIN STORMWATER MANAGEMENT PLAN 1: DRAWN BY CHECKED BY DATE ISSUE No PROJ. No SCALE LSC FST REV. No 2 DRAWING/DESSIN C3 DECEMBER 213 FICHIER ACAD FILE: SWM.dwg

Orleans Gardens Starbucks Drive Through Servicing and Stormwater Management Design Brief

Orleans Gardens Starbucks Drive Through Servicing and Stormwater Management Design Brief Report File #: 34197-5.2.2 Orleans Gardens Starbucks Drive Through Servicing and Stormwater Management Design Brief Prepared for North American Development Group by IBI Group June 2015 IBI GROUP REPORT

More information

FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT STUDY 405 TWEEDSMUIR AVENUE

FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT STUDY 405 TWEEDSMUIR AVENUE FUNCTIONAL SERVICING AND STORMWATER MANAGEMENT STUDY FOR CITY OF OTTAWA PROJECT NO.: 11-532 FOR TABLE OF CONTENTS 1.0 INTRODUCTION... 1 1.1 Existing Conditions... 2 1.2 Required Permits / Approvals...

More information

Functional Servicing Report. Winston Park West Proposed Business Park Development Project. Infrastructure Ontario (IO) September MU1

Functional Servicing Report. Winston Park West Proposed Business Park Development Project. Infrastructure Ontario (IO) September MU1 Functional Servicing Report Winston Park West Proposed Business Park Development Project (IO) September 2011 14-11208-001-MU1 Winston Park West 2 TABLE OF CONTENTS Page 1.0 INTRODUCTION... 3 1.1 SITE DESCRIPTION...

More information

Section H - Site Plan Guidelines

Section H - Site Plan Guidelines H1 GENERAL REQUIREMENTS The following is an outline of procedures and requirements for preparation and submission of Grading Plans, Site Alteration Plans (Erosion and Sediment Control Plans), Site Servicing

More information

Site Servicing & Stormwater Management Report for Site Plan Control Application. Proposed New Multi-Unit Development 284 Presland Road Ottawa, Ontario

Site Servicing & Stormwater Management Report for Site Plan Control Application. Proposed New Multi-Unit Development 284 Presland Road Ottawa, Ontario Site Servicing & Stormwater Management Report for Site Plan Control Application Proposed New Multi-Unit Development 284 Presland Road Ottawa, Ontario Prepared for: Martin Clement Attention: Mr. Martin

More information

Stormwater Management Report Bachman Terrace Residential Development

Stormwater Management Report Bachman Terrace Residential Development Stormwater Management Report Bachman Terrace Residential Development Project # 160401069 Prepared for: Tega Developments Prepared by: Stantec Consulting Ltd. April 14, 2014 Sign-off Sheet This document

More information

GENERAL PLAN OF SERVICING

GENERAL PLAN OF SERVICING No. REVISIONS By 400 333 Preston Street GENERAL PLAN OF SERVICING 38158 100 T UTILITY LEGEND TRANSFORMER SERVICING LEGEND SANITARY MANHOLE C/W IDENTIFICATION TRANSFORMER C/W CONCRETE WINGS SANITARY SEWER

More information

PROPOSED THREE-STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 19 R-PLAN ROCKINGHAM AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT

PROPOSED THREE-STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 19 R-PLAN ROCKINGHAM AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT PROPOSED THREE-STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 19 R-PLAN 149 1162 ROCKINGHAM AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT REPORT No. R-815-41 T. L. MAK ENGINEERING CONSULTANTS LTD. JUNE 2015

More information

New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario

New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario Site Servicing and Stormwater Management Report By Mohamad Salame, P.Eng. Kamco Technique Ltee. 60 Grand Avenue North Cambridge, Ontario N1S

More information

SANITARY AND STORM TRUNK SEWER DESIGN BRIEF KANATA RESEARCH PARK LANDS

SANITARY AND STORM TRUNK SEWER DESIGN BRIEF KANATA RESEARCH PARK LANDS SANITARY AND STORM TRUNK SEWER DESIGN BRIEF KANATA RESEARCH PARK LANDS Prepared By: NOVATECH Suite 200, 240 Michael Cowpland Drive Ottawa, Ontario K2M 1P6 August 8, 2014 Novatech File: 114060 Ref: R-2014-114

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. SERVICING BRIEF 406-408 Bank Street Ottawa, Ontario Report No. 10015-SB December 13, 2011 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading & Drainage - Storm & Sanitary Sewers

More information

STORM WATER REPORT. Proposed Row House Complex Clare and Hilson 566 Hilson Ave. & 148 Clare St. Ottawa, Ontario PREPARED FOR:

STORM WATER REPORT. Proposed Row House Complex Clare and Hilson 566 Hilson Ave. & 148 Clare St. Ottawa, Ontario PREPARED FOR: Civil Geotechnical Structural Environmental 210 Prescott Street, Unit 1 (613) 860-0923 P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613) 258-0475 STORM WATER REPORT Proposed Row House Complex Clare and

More information

TOWN OF MANCHESTER PLANNING AND ZONING COMMISSION Subdivision Application Minimum Submission Requirements

TOWN OF MANCHESTER PLANNING AND ZONING COMMISSION Subdivision Application Minimum Submission Requirements TOWN OF MANCHESTER PLANNING AND ZONING COMMISSION Subdivision Application Minimum Submission Requirements This checklist is to be completed and submitted with all Subdivision Applications. The Town reserves

More information

Site Servicing and Stormwater Management Report for Site Plan Control Application C&C Transportation 8015 Russell Road Ottawa, Ontario

Site Servicing and Stormwater Management Report for Site Plan Control Application C&C Transportation 8015 Russell Road Ottawa, Ontario Site Servicing and Stormwater Management Report for Site Plan Control Application C&C Transportation 8015 Russell Road Ottawa, Ontario Prepared for The C and C Group of Companies Attention: Mr. Bob Cousins

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. SERVICING BRIEF 2200 Prince of Wales Drive Ottawa, Ontario Report No. 11068-SB February 3, 2012 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading & Drainage - Storm & Sanitary

More information

SERVICING AND STORM WATER MANAGEMENT REPORT

SERVICING AND STORM WATER MANAGEMENT REPORT The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED BANK PLACE D ORLEANS MALL OTTAWA, ONTARIO SERVICING

More information

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects

Town of New Tecumseth Engineering Design Criteria and Standards for Subdivisions and Capital Works Projects 2.0 ROADWAYS 2.1 Road Classification 2.1.1 Standard Drawing Classification All Road Widths and Road Allowances shall be designed in accordance with the most recent Town of New Tecumseth Standards: TNT.SD

More information

P: (905) F: (905) PROPOSED BANK. Prepared For: ENT INC. JUNE Rev 0.docx

P: (905) F: (905) PROPOSED BANK. Prepared For: ENT INC. JUNE Rev 0.docx The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED BANK PLACE D ORLEANS MALL OTTAWA, ONTARIO SERVICING

More information

Longfields Subdivision, Block 7, City of Ottawa

Longfields Subdivision, Block 7, City of Ottawa Longfields Subdivision, Block 7, City of Ottawa 160400850/160401231 Prepared for: Campanale Homes Prepared by: Stantec Consulting Ltd. Table of Contents 1.0 INTRODUCTION...1.1 2.0 BACKGROUND...2.2 3.0

More information

SITE SERVICING PRELIMINARY DESIGN BRIEF

SITE SERVICING PRELIMINARY DESIGN BRIEF 855 Carling Avenue Proposed Redevelopment SITE SERVICING PRELIMINARY DESIGN BRIEF March 2010 March 23, 2010 RVA 081785 Arnon Corporation 1801 Woodward Dr. Ottawa, ON K2C 0R3 Attention: Mike Casey Re: 855

More information

Mofan Holdings Inc. 249 Bayview Drive

Mofan Holdings Inc. 249 Bayview Drive Mofan Holdings Inc. 249 Bayview Drive Functioning Service Report Project Number 213586 Prepared By: Yousef Saigh, P. Eng. exp Services Inc. 4 Cedar Pointe Drive, Unit L Barrie, ON L4N 5R7 Canada T: +1.705.719.1100

More information

PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT SHOPPERS DRUG MART. January 2016

PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG ROAD OTTAWA, ONTARIO ENGINEERING REPORT SHOPPERS DRUG MART. January 2016 The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED SHOPPERS DRUG MART RIVER ROAD AND EARL ARMSTRONG

More information

New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario

New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario New Retirement Home 6758 & 6766 Rocque Street Orleans, Ontario Site Servicing and Stormwater Management Report By Mohamad Salame, P.Eng. Kamco Technique Ltee. 60 Grand Avenue North Cambridge, Ontario N1S

More information

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 47 R PLAN CROYDEN AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT REPORT R

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 47 R PLAN CROYDEN AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT REPORT R PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOT 47 R PLAN 348 351 CROYDEN AVENUE CITY OF OTTAWA STORM DRAINAGE REPORT REPORT R 817 21 T.L. MAK ENGINEERING CONSULTANTS LTD. JUNE 2017 REFERENCE

More information

6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON

6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON 6 STOREY CONDOMINIUM 7480 DERRY ROAD WEST, MILTON STORM WATER MANAGEMENT DESIGN BRIEF NEW DEVELOPMENT DRAINAGE SYSTEM REV 0 August 29, 2017 PREPARED BY: HALLEX PROJECT #170532 HALLEX NIAGARA HALLEX HAMILTON

More information

Silver Seven Corporate Centre Phase 1

Silver Seven Corporate Centre Phase 1 SERVICING BRIEF Silver Seven Corporate Centre Phase 1 15 & 19 Frank Nighbor Place and 737 & 777 Silver Seven Road Kanata, Ontario Report No. 12022-SB May 31, 2012 Revised October 23, 2012 D. B. G R A Y

More information

WESTMINISTER WOODS EAST PHASE 10 (CLAIR/VICTORIA), GUELPH FUNCTIONAL SERVICING REPORT

WESTMINISTER WOODS EAST PHASE 10 (CLAIR/VICTORIA), GUELPH FUNCTIONAL SERVICING REPORT WESTMINISTER WOODS EAST PHASE 10 (CLAIR/VICTORIA), GUELPH FUNCTIONAL SERVICING REPORT Prepared for: West Minister Woods Ltd. R.R. #2 6783 Wellington Road #34 Cambridge ON N3C 2V4 Prepared by: Stantec Consulting

More information

Dunpar Developments Inc.

Dunpar Developments Inc. Dunpar Developments Inc. Proposed Townhouse Development 2158, 2168, 2180 and 2192 Trafalgar Road Oakville, Ontario Functional Servicing and Stormwater Management Report (in Support of a Re-Zoning and Site

More information

PROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M BANK STREET CITY OF OTTAWA STORM DRAINAGE REPORT

PROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M BANK STREET CITY OF OTTAWA STORM DRAINAGE REPORT PROPOSED FIVE STOREY MIXED USE BUILDING DEVELOPMENT SITE LOT 2 R PLAN M 2 7 BANK STREET CITY OF OTTAWA STORM DRAINAGE REPORT REPORT R 81 41 (REV. 2) MARCH 2017 T.L. MAK ENGINEERING CONSULTANTS LTD. JULY

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. STORMWATER MANAGEMENT REPORT 22 Perkins Street Ottawa, Ontario Report No. 13030-SWM February 6, 2015 D. B. G R A Y E N G I N E E R I N G I N. Stormwater Management - Grading & Drainage - Storm & Sanitary

More information

CHAPTER 17: STORM SEWER STANDARDS Introduction Administration Standards 17.1

CHAPTER 17: STORM SEWER STANDARDS Introduction Administration Standards 17.1 CHAPTER 17: STORM SEWER STANDARDS 17.00 Introduction 17.01 Administration 17.02 Standards 17.1 17.00 INTRODUCTION The purpose of this chapter is to provide guidance for the design and construction of storm

More information

SERVICING AND STORM WATER MANAGEMENT REPORT

SERVICING AND STORM WATER MANAGEMENT REPORT The Odan/Detech Group Inc. P: (905) 632-3811 F: (905) 632-3363 5230 SOUTH SERVICE ROAD, UNIT 107 BURLINGTON, ONTARIO, L7L 5K2 www.odandetech.com PROPOSED MASTERMIND TOYS RETAIL BUILDING PLACE D ORLEANS

More information

D. B. G R A Y E N G I N E E R I N G I N C.

D. B. G R A Y E N G I N E E R I N G I N C. SERVICING BRIEF Mutchmor Public School Addition 185 Fifth Avenue Ottawa, Ontario Report No. 12073-SB February 15, 2013 D. B. G R A Y E N G I N E E R I N G I N C. Stormwater Management - Grading & Drainage

More information

Design Specifications & Requirements Manual

Design Specifications & Requirements Manual 9 GRADING 9.1 GRADING REQUIREMENTS FOR VARIOUS SITUATIONS... 1 9.1.1 Subdivisions... 1 9.1.2 Site Plans... 1 9.1.3. Severances, Lifting of Part Lot Control & Infill Lots... 1 9.1.4 Blocks... 1 9.1.5 Capital

More information

Debrob Investments Limited FUNCTIONAL SERVICING REPORT DRAFT PLAN OF SUBDIVISION, CITYVIEW DRIVE CITY OF GUELPH

Debrob Investments Limited FUNCTIONAL SERVICING REPORT DRAFT PLAN OF SUBDIVISION, CITYVIEW DRIVE CITY OF GUELPH JULY 2013 DOCUMENT CONTROL Client: Project Name: Report Title: IBI Reference: 25528 Cityview Drive Version: JULY 2013 Digital Master: Originator: Reviewer: Authorization: [File Location] Scott MacDonald,

More information

SITE SERVICING REPORT CHOICE PROPERTIES 1251 STITTSVILLE MAIN STREET

SITE SERVICING REPORT CHOICE PROPERTIES 1251 STITTSVILLE MAIN STREET 120 Iber Road, Suite 103 Ottawa, Ontario K2S 1E9 Tel. (613)836-0856 Fax (613) 836-7183 www.dsel.ca SITE SERVICING REPORT FOR CHOICE PROPERTIES 1251 STITTSVILLE MAIN STREET CITY OF OTTAWA PROJECT NO.: 17-959

More information

Orleans Family Health Hub

Orleans Family Health Hub Orleans Family Health Hub Stormwater Management & Servicing Report Type of Document: Site Plan Application Project Name: Orleans Family Health Hub (OFHH) Project Number OTT-00240132-A0 Prepared By: exp

More information

A Stormwater Management Plan and Sediment Control Plan are required for all proposed developments within the City of Richmond.

A Stormwater Management Plan and Sediment Control Plan are required for all proposed developments within the City of Richmond. Engineering Page 3-1 3.0 STORM DRAINAGE 3.1 GENERAL Good drainage is vital to flat urban areas such as Lulu Island. It is essential that every storm sewer must be designed accurately minimizing conflicts

More information

Site Servicing and Stormwater Management Report Sélection Retraite - Orléans

Site Servicing and Stormwater Management Report Sélection Retraite - Orléans Site Servicing and Stormwater Management Report Sélection Retraite - Orléans Project # 160401451 November 22, 2018 Prepared for: Réseau Sélection Developpement Hors Quebec Inc. Prepared by: Stantec Consulting

More information

LOT GRADING GUIDELINES FOR LOW DENSITY RESIDENTIAL PROPERTIES

LOT GRADING GUIDELINES FOR LOW DENSITY RESIDENTIAL PROPERTIES LOT GRADING GUIDELINES FOR LOW DENSITY RESIDENTIAL PROPERTIES Contents LOT GRADING GUIDELINES... 3 LOW DENSITY RESIDENTIAL PROPERTIES... 3 Introduction... 3 Definitions:... 3 Purpose... 3 LOT GRADING APPROVAL

More information

Riverside South Block 3/4, Richcraft Group of Companies Inc., City of Ottawa SERVICING REPORT

Riverside South Block 3/4, Richcraft Group of Companies Inc., City of Ottawa SERVICING REPORT Riverside South Block 3/4, Richcraft Group of Companies Inc., City of Ottawa SERVICING REPORT Prepared by: Stantec Consulting Ltd. 1505 Laperriere Avenue Ottawa, ON K1Z 7T1 File: 160401004/83 January 17,

More information

HOTEL KANATA 140 HEARST WAY KANATA, ONTARIO STORMWATER MANAGEMENT REPORT. Prepared for: David Johnston Architect. Prepared By:

HOTEL KANATA 140 HEARST WAY KANATA, ONTARIO STORMWATER MANAGEMENT REPORT. Prepared for: David Johnston Architect. Prepared By: HOTEL KANATA 140 HEARST WAY KANATA, ONTARIO STORMWATER MANAGEMENT REPORT Prepared for: David Johnston Architect Prepared By: BaseTech Consulting Inc. 309 Roywood Crescent Newmarket, Ontario L3Y 1A6 BCI

More information

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT

CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT CITY OF ASTORIA PUBLIC WORKS ENGINEERING DIVISION ENGINEERING DESIGN STANDARDS FOR IN-FILL DEVELOPMENT Adopted by City Council: May 21, 2007 X:\General Eng\DESIGN STANDARDS\Engineering Design Standards

More information

Design Specifications & Requirements Manual

Design Specifications & Requirements Manual 9 GRADING 9.1 GRADING REQUIREMENTS FOR VARIOUS SITUATIONS... 1 9.1.1 Subdivisions... 1 9.1.2 Site Plans... 1 9.1.3. Severances, Lifting of Part Lot Control & Infill Lots... 1 9.1.4 Blocks... 1 9.1.5 Capital

More information

CONSTRUCTION PLAN CHECKLIST

CONSTRUCTION PLAN CHECKLIST CONSTRUCTION PLAN CHECKLIST The design engineer is responsible for ensuring that plans submitted for city review are in accordance with this checklist. It is requested that the executed checklist be submitted

More information

LOT GRADING GUIDELINES FOR COMMERCIAL, INDUSTRIAL, INSTITUTIONAL, MEDIUM AND HIGH DENSITY RESIDENTIAL PROPERTIES

LOT GRADING GUIDELINES FOR COMMERCIAL, INDUSTRIAL, INSTITUTIONAL, MEDIUM AND HIGH DENSITY RESIDENTIAL PROPERTIES LOT GRADING GUIDELINES FOR COMMERCIAL, INDUSTRIAL, INSTITUTIONAL, MEDIUM AND HIGH DENSITY RESIDENTIAL PROPERTIES Contents COMMERCIAL, INDUSTRIAL, INSTITUTIONAL, MEDIUM AND HIGH DENSITY... 1 RESIDENTIAL

More information

Detailed Stormwater Management Report David Manchester Road

Detailed Stormwater Management Report David Manchester Road Detailed Stormwater Management Report David Manchester Road Prepared for: Nortrax Canada Inc. 189 Cardevco Road Carp, Ontario K0A 1L0 Prepared by: McIntosh Perry Consulting Engineers Ltd. 115 Walgreen

More information

SUPPLEMENTAL DRAWINGS

SUPPLEMENTAL DRAWINGS CITY OF GREATER SUDBURY SUPPLEMENTAL DRAWINGS TO THE ONTARIO PROVINCIAL STANDARD DRAWINGS Rev: February 2012 CITY OF GREATER SUDBURY STANDARD DRAWINGS TABLE OF CONTENTS Greater Sudbury Standard Drawings

More information

SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017

SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017 SUBDIVISION AND OFF-SITE SERVICING CERTIFICATION REQUIREMENTS Rev 5 May 25, 2017 I. CONSTRUCTION PREREQUISITES 1.0 Pre-construction Survey A pre-construction survey of all existing infrastructure within

More information

Orleans Family Health Hub

Orleans Family Health Hub Orleans Family Health Hub Stormwater Management & Servicing Report Type of Document: Site Plan Application Project Name: Orleans Family Health Hub (OFHH) Project Number OTT-00240132-A0 Prepared By: exp

More information

STORM WATER REPORT ASPHALT AND CONCRETE PLANTS 891 JINKINSON SIDE ROAD, ASHTON CITY OF OTTAWA, ONTARIO PREPARED FOR:

STORM WATER REPORT ASPHALT AND CONCRETE PLANTS 891 JINKINSON SIDE ROAD, ASHTON CITY OF OTTAWA, ONTARIO PREPARED FOR: Civil Geotechnical Structural Environmental 210 Prescott Street, Unit 1 (613) 860-0923 P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613) 258-0475 STORM WATER REPORT ASPHALT AND CONCRETE PLANTS 891 JINKINSON

More information

Please ensure receipt of this Addendum is acknowledged on page 1 of the Form of Tender.

Please ensure receipt of this Addendum is acknowledged on page 1 of the Form of Tender. No. 1 Project: 47th Ave Road Reconstruction Owner: District of Chetwynd Date: March 5, 2019 Ref. No.: 1320.0095.01 This Addendum is issued prior to Tender Closing Date, in accordance with the Tender Documents

More information

THE REGIONAL MUNICIPALITY OF PEEL STANDARD SPECIFICATIONS FOR RESTORATION

THE REGIONAL MUNICIPALITY OF PEEL STANDARD SPECIFICATIONS FOR RESTORATION THE REGIONAL MUNICIPALITY OF PEEL STANDARD SPECIFICATIONS FOR RESTORATION Standard Specifications for Restoration INDEX PAGE R.1 GENERAL...1 R.2 SCOPE...1 R.3 MATERIALS...1 R.4 CONSTRUCTION...2 R.4.1 General...2

More information

APPENDIX F: DRAINAGE AND STORMWATER MANAGEMENT

APPENDIX F: DRAINAGE AND STORMWATER MANAGEMENT APPENDIX F: DRAINAGE AND STORMWATER MANAGEMENT Downtown Ottawa Transit Tunnel: Tunney s Pasture to Blair Station via a Downtown LRT Tunnel Prepared for: City of Ottawa 110 Laurier Avenue West Ottawa, ON

More information

ADDENDUM NO. 1 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON 2015 Capital Works 2015-Tender-02

ADDENDUM NO. 1 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON 2015 Capital Works 2015-Tender-02 ADDENDUM NO. 1 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON April 23, 2015 To All Tenderers: This Addendum is issued prior to the Tender Closing Date April 30, 2015, in accordance

More information

LOT GRADING GUIDELINES

LOT GRADING GUIDELINES LOT GRADING GUIDELINES RESIDENTIAL PROPERTIES The Drainage Bylaw 18093 came into effect on January 1, 2018 replacing previous versions of the Drainage Bylaw 16200. This Bylaw requires that all single family,

More information

Municipal Inspection and Construction Guidelines Section I Roadworks SECTION I ROADWORKS I-1 GENERAL

Municipal Inspection and Construction Guidelines Section I Roadworks SECTION I ROADWORKS I-1 GENERAL I-1 GENERAL SECTION I ROADWORKS The Consultant Engineer is to monitor all specified asphalt, granular materials and sub-grade preparation to ensure all road and curb construction is undertaken as outlined

More information

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN 441 324 326 DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT REPORT No. R 817 79A T. L. MAK ENGINEERING CONSULTANTS LTD.

More information

Amendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water Supply Services

Amendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water Supply Services Engineering & Construction Services Division Standard Specifications for Sewers and Watermains TS 493 September 2017 Amendment to OPSS 493 (Nov 2015) Construction Specification for Temporary Potable Water

More information

CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES

CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 493 NOVEMBER 2015 CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES TABLE OF CONTENTS 493.01 SCOPE 493.02 REFERENCES 493.03 DEFINITIONS

More information

Functional Servicing and Stormwater Management Report Appleby Mall Residential Burlington ON

Functional Servicing and Stormwater Management Report Appleby Mall Residential Burlington ON Functional Servicing and Stormwater Management Report Appleby Mall Residential Burlington ON Prepared By: R.J. Burnside & Associates Limited 1465 Pickering Parkway, Suite 200 Pickering ON L1V 7G7 Prepared

More information

ADDENDUM NO. 2 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON 2015 Capital Works 2015-Tender-02

ADDENDUM NO. 2 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON 2015 Capital Works 2015-Tender-02 ADDENDUM NO. 2 TO THE TENDER DOCUMENTS FOR THE CORPORATION OF THE CITY OF PENTICTON April 28, 2015 To All Tenderers: This Addendum is issued prior to the Tender Closing Date April 30, 2015, in accordance

More information

SECTION 12 STANDARDS FOR CONSTRUCTION PLANS AND SPECIFICATIONS

SECTION 12 STANDARDS FOR CONSTRUCTION PLANS AND SPECIFICATIONS SECTION 12 STANDARDS FOR CONSTRUCTION PLANS AND SPECIFICATIONS 12.1 The subdivider shall construct and install the improvements in accordance with the County's Standards for Construction Plans and Specifications

More information

CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES

CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 493 NOVEMBER 2009 (Reissued November 2010) CONSTRUCTION SPECIFICATION FOR TEMPORARY POTABLE WATER SUPPLY SERVICES TABLE OF CONTENTS 493.01 SCOPE 493.02

More information

TOWNSHIP OF TINY LOT GRADING/DRAINAGE PLAN PROCEDURE

TOWNSHIP OF TINY LOT GRADING/DRAINAGE PLAN PROCEDURE TOWNSHIP OF TINY LOT GRADING/DRAINAGE PLAN PROCEDURE Approved: December 2015 Revised: April 2017 TABLE OF CONTENTS Section 1.0 Introduction... 2 Section 2.0 Policy... 2 Section 3.0 Preparation of the Lot

More information

Ordinance No Lot Surface Drainage

Ordinance No Lot Surface Drainage Ordinance No. 35-2008 - Lot Surface Drainage The Township has adopted a new Lot Surface Drainage Ordinance which amends Chapter 170, Article IX, Subdivision and Site Plan Review by adding a new Section

More information

Schedule A DISTRICT OF MAPLE RIDGE Watercourse Protection Bylaw

Schedule A DISTRICT OF MAPLE RIDGE Watercourse Protection Bylaw Schedule A DISTRICT OF MAPLE RIDGE Watercourse Protection Bylaw 6410 2006 The Erosion and Sediment Control plan should seek (i) to protect the soil surface from erosion where possible and (ii) capture

More information

Storm Sewers, Page 2

Storm Sewers, Page 2 Storm Sewers storm sewer systems are dendritic systems used to collect and direct stormwater runoff storm sewer systems are integral components of any urban infrastructure curbs, gutters and storm inlets

More information

STORMWATER MANAGEMENT REPORT. Dundas Square Gardens Inc. High Rise Residential/Commercial Development

STORMWATER MANAGEMENT REPORT. Dundas Square Gardens Inc. High Rise Residential/Commercial Development STORMWATER MANAGEMENT REPORT Dundas Square Gardens Inc. Revised: April 6, 2016 Revised: January 12, 2016 Revised: July 10, 2015 OUR FILE: 14-RE-352 June 16, 2014 TABLE OF CONTENTS PAGE 1.0 Scope of work

More information

Site Servicing and Stormwater Management Report Orleans II Development Mer Bleue Road Phase 2

Site Servicing and Stormwater Management Report Orleans II Development Mer Bleue Road Phase 2 Site Servicing and Stormwater Management Report Orleans II Development - 2025 Mer Bleue Road Phase 2 Project # 160401242 Prepared for: SmartREIT (Orleans II) Inc. and Mer Bleue Shopping Centres Limited

More information

RETENTION BASIN EXAMPLE

RETENTION BASIN EXAMPLE -7 Given: Total Tributary Area = 7.5 ac o Tributary Area within Existing R/W = 5.8 ac o Tributary Area, Impervious, Outside of R/W = 0.0 ac o Tributary Area, Pervious, Outside of R/W = 1.7 ac o Tributary

More information

City of St. Catharines Standard Drawings JULY Revised July 21, 2017 TES-ENG (SH)

City of St. Catharines Standard Drawings JULY Revised July 21, 2017 TES-ENG (SH) City of St. Catharines Standard Drawings JULY 2017 Revised July 21, 2017 TES-ENG (SH) Roads Dwg No. Revision Standard Sidewalk Detail 110-2001 1 Monolithic Curb-Faced Sidewalk for Concrete Road 110-2002

More information

CITY OF GUELPH CONTRACT NO SUPPLEMENTAL SPECIAL PROVISIONS

CITY OF GUELPH CONTRACT NO SUPPLEMENTAL SPECIAL PROVISIONS CITY OF GUELPH CONTRACT NO. 2-1308 SUPPLEMENTAL SPECIAL PROVISIONS SSP 1 INDEX 1. GENERAL INFORMATION... 8 2. SITE PREPARATION & MOBILIZATION (TENDER ITEM A1.0)... 10 3. SEDIMENT AND EROSION CONTROL (TENDER

More information

July 21, 2017 DSEL File No.:

July 21, 2017 DSEL File No.: 120 Iber Road, Unit 103 Stittsville, Ontario K2S 1E9 Tel (613) 836-0856 Fax (613) 836-7183 www.dsel.ca July 21, 2017 DSEL File No.: 16-855 City of Ottawa Infrastructure Services and Community Sustainability

More information

SCHAEFFERS FUNCTIONAL SERVICING REPORT PROPOSED RESIDENTIAL DEVELOPMENT LAKESHORE ROAD WEST TOWN OF OAKVILLE

SCHAEFFERS FUNCTIONAL SERVICING REPORT PROPOSED RESIDENTIAL DEVELOPMENT LAKESHORE ROAD WEST TOWN OF OAKVILLE FUNCTIONAL SERVICING REPORT PROPOSED RESIDENTIAL DEVELOPMENT 346 362 LAKESHORE ROAD WEST TOWN OF OAKVILLE PROJECT 2016-4442 JULY 2017 REVISED: APRIL 2017 C O N S U L T I N G E N G I N E E R S 64 Jardin

More information

DESIGN BRIEF MIX-USE DEVELOPMENT ICON 505 PRESTON STREET OTTAWA, ONTARIO

DESIGN BRIEF MIX-USE DEVELOPMENT ICON 505 PRESTON STREET OTTAWA, ONTARIO CLARIDGE HOMES (PRESTON) INC. DESIGN BRIEF MIX-USE DEVELOPMENT ICON 505 PRESTON STREET OTTAWA, ONTARIO PROJECT: 31637-5.2.2 OCTOBER 2014 IBI GROUP PROJECT: 31637-5.2.2 TABLE OF CONTENTS 1. INTRODUCTION...

More information

OHM Groups. FUNCTIONAL SERVICING REPORT 33 Arkell Road City of Guelph August 5, Prepared By:

OHM Groups. FUNCTIONAL SERVICING REPORT 33 Arkell Road City of Guelph August 5, Prepared By: Prepared By: OHM Groups FUNCTIONAL SERVICING REPORT 33 Arkell Road City of Guelph 114169 August 5, 2015 Guelph Owen Sound Listowel Kitchener Exeter Hamilton GTA 650 Woodlawn Rd. W., Block C, Unit 2, Guelph

More information

PRELIMINARY MUNICIPAL SERVICING REPORT NORTHWOODS SUBDIVISION. Prepared for: North Grassie Properties Inc.

PRELIMINARY MUNICIPAL SERVICING REPORT NORTHWOODS SUBDIVISION. Prepared for: North Grassie Properties Inc. PRELIMINARY MUNICIPAL SERVICING REPORT SUBDIVISION Prepared for: North Grassie Properties Inc. Prepared by: Stantec Consulting Ltd. 905 Waverley St. Winnipeg, MB R3T 5P4 July 2012 File: 116808030 SUBDIVISION

More information

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT

PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT PROPOSED THREE STOREY RESIDENTIAL APARTMENT BUILDING SITE LOTS 187 AND 188 R PLAN 441 324 326 DONALD STREET CITY OF OTTAWA SERVICEABILITY REPORT REPORT No. R 817 79A REV. 1 MAY 2018 T. L. MAK ENGINEERING

More information

DERRY GREEN BUSINESS PARK WATER AND WASTEWATER SERVICING AREA SERVICING PLAN

DERRY GREEN BUSINESS PARK WATER AND WASTEWATER SERVICING AREA SERVICING PLAN DERRY GREEN BUSINESS PARK WATER AND WASTEWATER SERVICING AREA SERVICING PLAN Submitted to: Town of Milton Regional Municipality of Halton Submitted by: AMEC Earth & Environmental 3215 North Service Road

More information

SITE SERVICES GUELPH TRANSIT OPERATIONS & MAINTENANCE SECTION WATSON ROAD FACILITY PAGE 1 OF 6 WATER RECLAMATION PROJECT JUNE 2013

SITE SERVICES GUELPH TRANSIT OPERATIONS & MAINTENANCE SECTION WATSON ROAD FACILITY PAGE 1 OF 6 WATER RECLAMATION PROJECT JUNE 2013 WATSON ROAD FACILITY PAGE 1 OF 6 PART 1 GENERAL 1.1 Description The work covered by this Section includes all labour, materials, equipment, and supervision necessary to complete the site services as shown

More information

STORM WATER REPORT ASPHALT AND CONCRETE PLANTS JINKINSON SIDE ROAD, ASHTON CITY OF OTTAWA, ONTARIO PREPARED FOR:

STORM WATER REPORT ASPHALT AND CONCRETE PLANTS JINKINSON SIDE ROAD, ASHTON CITY OF OTTAWA, ONTARIO PREPARED FOR: Civil Geotechnical Structural Environmental Industrial Health & Safety (613) 860-0923 210 Prescott Street P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613) 258-0475 STORM WATER REPORT ASPHALT AND CONCRETE

More information

TOWN of LAKESHORE SUBDIVISION DEVELOPMENT PLAN CHECKLIST

TOWN of LAKESHORE SUBDIVISION DEVELOPMENT PLAN CHECKLIST Project Name: Project Location: Date Submitted: TOWN of LAKESHORE SUBDIVISION DEVELOPMENT PLAN CHECKLIST Last Revised January 31, 2014 Name Phone Number E-mail Address Owner: Contractor/ Engineer: ( )

More information

CONSTRUCTION SPECIFICATION FOR SITE RESTORATION FOLLOWING INSTALLATION OF PIPELINES, UTILITIES, AND ASSOCIATED STRUCTURES

CONSTRUCTION SPECIFICATION FOR SITE RESTORATION FOLLOWING INSTALLATION OF PIPELINES, UTILITIES, AND ASSOCIATED STRUCTURES ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 492 NOVEMBER 2010 CONSTRUCTION SPECIFICATION FOR SITE RESTORATION FOLLOWING INSTALLATION OF PIPELINES, UTILITIES, AND ASSOCIATED STRUCTURES TABLE OF

More information

215 Sanders Street, Unit 1 (613) Prescott Street, Unit 1 P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613)

215 Sanders Street, Unit 1 (613) Prescott Street, Unit 1 P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613) Civil Geotechnical Structural Environmental 215 Sanders Street, Unit 1 (613) 860-0923 210 Prescott Street, Unit 1 P.O. Box 189 Kemptville, Ontario K0G 1J0 FAX: (613) 258-0475 March 29, 2016 2343065 Ontario

More information

Town of Friday Harbor PO Box 219 / Friday Harbor / WA / (360) / fax (360) /

Town of Friday Harbor PO Box 219 / Friday Harbor / WA / (360) / fax (360) / Town of Friday Harbor PO Box 219 / Friday Harbor / WA / 98250 (360) 378-2810 / fax (360) 378-5339 / www.fridayharbor.org LAND CLEARING, GRADING, OR FILLING PERMIT APPLICATION APPLICATION DATE GRD No. APPLICANT/FRANCHISE

More information

CONSTRUCTION SPECIFICATION FOR DEWATERING

CONSTRUCTION SPECIFICATION FOR DEWATERING ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS.PROV 517 NOVEMBER 2016 CONSTRUCTION SPECIFICATION FOR DEWATERING TABLE OF CONTENTS 517.01 SCOPE 517.02 REFERENCES 517.03 DEFINITIONS 517.04 DESIGN

More information

Stormwater Management & Servicing Report KMA Mosque and Community Centre 351 Sandhill Road, Ottawa, Ontario

Stormwater Management & Servicing Report KMA Mosque and Community Centre 351 Sandhill Road, Ottawa, Ontario Stormwater Management & Servicing Report KMA Mosque and Community Centre 351 Sandhill Road, Ottawa, Ontario Client: Kanata Muslim Association 351 Sandhill Road Ottawa, Ontario K2K 1X7 Project Number: OTT-00238564-A0

More information

Section 403. DRAINAGE STRUCTURES

Section 403. DRAINAGE STRUCTURES 403.01 Section 403. DRAINAGE STRUCTURES 403.01. Description. This work consists of adjusting, constructing, or temporarily lowering drainage structures and cleaning existing drainage structures and leads

More information

E. STORMWATER MANAGEMENT

E. STORMWATER MANAGEMENT E. STORMWATER MANAGEMENT 1. Existing Conditions The Project Site is located within the Lower Hudson Watershed. According to the New York State Department of Environmental Conservation (NYSDEC), Lower Hudson

More information

City of St. Catharines Standard Drawings SEPTEMBER Revised September 6, 2018 TES-ENG (SH)

City of St. Catharines Standard Drawings SEPTEMBER Revised September 6, 2018 TES-ENG (SH) City of St. Catharines Standard Drawings SEPTEMBER 2018 Revised September 6, 2018 TES-ENG (SH) Roads Dwg No. Revision Standard Sidewalk Detail 110-2001 2 Monolithic Curb-Faced Sidewalk 110-2002 3 Sidewalk

More information

Construction Inspection Checklists

Construction Inspection Checklists III. Construction Inspection Checklists 33 Bioretention - Construction Inspection Checklist Project: Location: Site Status: Date: Time: Inspector: Construction Sequence Satisfactory / Unsatisfactory Comments

More information

CEAA ENVIRONMENTAL ENVIRONMENTAL IMPACT ASSESSMENT AMBASSADOR BRIDGE ENHANCEMENT PROJECT. Replacement Span and Plaza Expansion APPENDIX E

CEAA ENVIRONMENTAL ENVIRONMENTAL IMPACT ASSESSMENT AMBASSADOR BRIDGE ENHANCEMENT PROJECT. Replacement Span and Plaza Expansion APPENDIX E Ambassador Bridge Enhancement Project CEAA ENVIRONMENTAL ENVIRONMENTAL IMPACT ASSESSMENT AMBASSADOR BRIDGE ENHANCEMENT PROJECT Replacement Span and Plaza Expansion APPENDIX E DRAFT EROSION AND SEDIMENT

More information

Stormwater Management The District exercises regulatory authority for Stormwater Management in the City of Edina.

Stormwater Management The District exercises regulatory authority for Stormwater Management in the City of Edina. Permit Application No.: 7-56 Rules: Erosion Control, Stormwater Management Applicant: Edina Public Schools Received:0/7/207 Project: South View Middle School Addition and Bus Parking Complete: /27/207

More information

PUBLIC WORKS DEPARTMENT GENERAL NOTES

PUBLIC WORKS DEPARTMENT GENERAL NOTES PUBLIC WORKS DEPARTMENT GENERAL NOTES 1. All construction shall be in strict accordance with the standards of the City of Southlake and governed by the North Central Texas Council of Government's Standard

More information

SECTION SITE PREPARATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION SITE PREPARATION. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 311000 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

Beaumont Lot Grading Guidelines

Beaumont Lot Grading Guidelines Beaumont Lot Grading Guidelines Updated: 2019-01-14 CONTENTS LOT GRADING OVERVIEW... 3 INTRODUCTION... 3 PURPOSE... 3 DEFINITIONS... 3 LOT GRADING REQUIREMENTS... 3 DESIGN GRADES AND EXISTING GRADES...

More information

APPENDIX E APPENDIX E ESTIMATING RUNOFF FOR SMALL WATERSHEDS

APPENDIX E APPENDIX E ESTIMATING RUNOFF FOR SMALL WATERSHEDS APPENDIX E ESTIMATING RUNOFF FOR SMALL WATERSHEDS March 18, 2003 This page left blank intentionally. March 18, 2003 TABLES Table E.1 Table E.2 Return Frequencies for Roadway Drainage Design Rational Method

More information

TABLE OF CONTENTS SECTION 700 STORM DRAINAGE STANDARDS...

TABLE OF CONTENTS SECTION 700 STORM DRAINAGE STANDARDS... TABLE OF CONTENTS SECTION 700 STORM DRAINAGE STANDARDS... 700-1 701 GENERAL... 700-1 702 GENERAL REQUIREMENTS... 700-1 703 GENERAL DESIGN STANDARDS... 700-2 704 POND DESIGN STANDARDS... 700-2 705 EROSION

More information

IV.E. HYDROLOGY AND WATER QUALITY

IV.E. HYDROLOGY AND WATER QUALITY IV.E. HYDROLOGY AND WATER QUALITY The following section presents the information provided in the hydrology report prepared by Sukow Engineering. Supporting hydrology data from this report is included in

More information