1 UCSF Mission Bay Campus Arthur and Toni Rembe Rock Hall th Street San Francisco, California Monitoring Based Recommissioning Project Project Implementation: June 2005 to December 2005 Funded by a grant from PG&E (under the UC / CSU / IOU Partnership Program) UCSF Rock Hall Building Occupancy Date: February 2004 Building GSF: 176,000 Building Type: Research Laboratory Baseline Utility Consumption (0/04 02/05): Electricity: 8,441,600 H/year Peak Demand: 1781 atural Gas: 450,09 Therms/year Specific Energy Consumption Peak Watts/GSF: 10.1 Annual H/GSF: 48.0 Annual Therms/GSF: 2.56 Electrical ALF 0.54 UC/CSU/IOU Partnership Energy Efficiency Grant Program: Project Highlights Initial/Perceived Deficiencies: Variable volume air handlers essentially operating at constant flow, excessive chiller cycling and loading, insufficient meters and instrumentation within basic system, existing instruments not functioning and/or out of calibration. Program Premise: Significant energy savings are achievable in existing buildings through retrocommissioning and by providing additional metering/monitoring to facilitate improved building performance. Project Funding: $270,000 Proposed Energy Savings Target: 409,260 KWH & 47 KW & 1,100 Therms Required Project Completion Date: December 1, 2005 Actual Energy Savings Harvested: 720,08 KWH & 7 KW & 76,987 Therms 1

2 Measures Implemented 1. Programmed night setback airflows at zone terminal boxes 2. Revised room level airflow set points at terminal boxes served by air handlers. Calibrated required static pressure setpoints within airside and waterside systems. 4. Calibrated and/or replaced temperature and pressure sensors within CHW and HW Systems. 5. Installed Flow meters at steam, heating & domestic hot water systems 6. Installed Flow meter & bypass valve at chilled water system Cleaver Brooks 400 HP 16,29,000 BTU atural Gas fired Boiler Cleaver Brooks CB Hawk Controller 80 psi to 5 psi Steam pressure reducing station Boiler atural Gas meter Gas Meter amplifiers 80 psi Steam flow meter to 5 psi pressure reducing station 80 psi Steam flow meter to East equipment on 2 nd & 4 th fl. Chilled Water Pressure Transducer Condenser Water Pressure Transducer 2

3 EQUIPMET/STATEPOITS METERED I.D. Type Volts Phase HP VFD Unit Interval Meter P01 CW Pump 25 P02 CW Pump 25 P0 CW Pump 25 P04 CW Pump 25 P05 CHW Pump 40 P06 CHW Pump 40 P07 CHW Pump 40 P08 HHW Pump 20 P09 HHW Pump 20 P10 HHW Pump 20 CH01 Chiller ~220 CH02 Chiller ~220 CH0 Chiller ~220 CT01 Tower Fan 20 CT02 Tower Fan 20 CT0 Tower Fan 20 AHU01 Supply Fan 75 AHU02 Supply Fan 75 AHU0 Supply Fan 100 AHU04 Supply Fan 100 AHU05 Supply Fan 150 AHU06 Supply Fan 150 OAT Temperature F Hobo OA RH R. Humidity RH Hobo MEASURES 1&2: AIR HADLIG SSTEM Categories For Airflow Modifications: Minimum airflow setpoints high. Airflow for future equipment incorporated where equipment was not actually installed. Introduced variable air volume in certain boxes previously balanced as constant air volume. Additional Items Implemented: ight setback airflows introduced. Static pressure setpoints verified and revised with aid of air balancing contractor. Building exhaust fans also had static pressure revisions. Reduced flow at exhaust fans by introducing better seals at rooftop exhaust fans (preventing reverse flow) thus reducing fan energy consumption. AHU AHU Comparison (Baseline And Post Improvement) y = x y = x AHU Comparison (Energy Reduction) The average temperatures were 57 deg F for both the days. Baseline : 22 August and Post Improvement: ovember, OA Temp (degf) Post Improvement Baseline Linear (Best Fit Lines)

4 Measures,4&5: Calibration/Replacement Of Existing Sensors Air Handling Units and Exhaust Fans static pressure setpoints adjusted and sensors calibrated. Chilled water flow through chillers calibrated flow adjusted. Chilled water/heating water pumps pressure sensors replaced with diaphragm double ended Serta Type DP transducers, pressure gages also installed. Adjusted AHU5 heating hot water valve that was not closing causing chilled water valve to open. Added steam flow meters and heating and domestic water flow meters. Calibration/Replacement Of Existing Chilled Water System Sensors CHW PUMP (200 AUG) Pre Project Post Project DATE/TIME CHW PUMP (200 AUG) CHW Pump operation Aug 200 Measure 6: Chilled Water Remote Bypass Initial issue chiller cycling too much, especially at low loads. Chilled water bypass valve necessary to ensure minimum flow through primaryonly loop variable frequency drive chiller. Owner requested to move location of bypass from chiller room to remote location (end of loop at roof location). Added magnetic type flow meter at bypass leg, to ensure consistent measurable minimum flow of chilled water necessary for primaryonly loop system. Programmed free cooling sequence into chilled water system by opening air handling unit chilled water valves during nighttime/low loads with pumps running without chiller. 4

5 Free Cooling Most common on airside as an economizer cycle. Waterside economizer typically includes running cooling towers and using condenser water as cooling source for air handling coils. This application does not include the use of cooling towers. Instead, water within the chilled water loop is run to the outside and aircooled at air handling unit coils by keeping the chilled water coils open. Generally this has allowed for chillers to remain off during nighttime hours while cooling electrical room fan coil units with constant heat loads. Chilled Water System Baseline Versus Post Improvement The chilled water system assessed includes the chillers and the CHW pumps. The average temperatures were 57 degf for both the days. Baseline : 22 August and Post Improvement: ovember, During the post improvement monitoring while the outdoor air temperature was below 58 F, the chillers and chilled water pumps were not running. y = x y = x Outside Air Temperature (OAT) in deg F Post Improvement Baseline Post Improvement (o Load) Linear (Best Fit Lines) Monthly Gas Consumption (Measures Implemented In SepOct 2005) atural Gas consumption (Therm) 50,000 45,000 40,000 5,000 0,000 Therm 25,000 20,000 15,000 10,000 5,000 0 Average OAT July (65F) August (67F) Sept (68F) October (61F) ovember (55F) December (52F) January (50F) February (55F) March (58F) April (57F) May (62F) June (62F) July (65F) August (64F) September (6F) October (62F) ovember (58F) December (5F) January (52F) February (5F)

6 Monthly Gas Consumption (Measures Implemented In SepOct 2005) Utility Data Comparison (Post and Pre MBCx) Month 50,000 45,000 40,000 5,000 0,000 25,000 20,000 68F 6F 61F 62F 55F 58F 52F 5F 50F 52F 55F 5F 15,000 10,000 5,000 0 Sept October ovember December Jan Feb atural Gas (Therm) (Sep 2004 thru Jan 2005, versus Sep 2005 thru Jan 2006) Pre MBCx Post MBCx Building Hvac Energy Use Distribution Before Retrocommissioning (Baseline) and After Measures Were Implemented HVAC Equipment electric consumption (Baseline) HVAC equipment electric consumption (Post Improvement) HHWP h 0% CHWP h 4% CWP h 4% CT h 1% HHWP h 1% CWP h 7% CT h 1% CHWP h 2% CH h 18% CH h 18% AHU h 71% AHU h 7% Hvac Equipment Energy Consumption Summary Equipment h comparison to Total h AHU 1h AHU 2h AHU AHU 4h AHU 5h AHU 6h CH1h CH2h CHh CHWP5h CHWP6h CHWP7h HWP8h HWP9h HWP10h CWP1h CWP2h CWPh CWP4h CTF2 h CTF h Total h Equipment Post Improvement Baseline 6

7 Energy Savings Breakdown Electricity Consumption: Air handler fan energy Exhaust fan energy reduction Chiller energy reduction Chilled water pump energy reduction Total: 77,864 H 280,20 H 8,784 H 5,070 H 720,08 H Electricity Demand: Air handler fan energy Exhaust fan energy reduction Total: Energy Savings Summary Project Targets: Electric Consumption Savings h 409,260 h Electric Demand Savings 47 Therm Savings 1,100 Therms Actual Harvested: Electric Consumption Savings h Electric Demand Savings Therm Savings Percentage of Total Electric Consumption Saving Over Target Percentage of Total Electric Demand Saving Over Target Percentage of Total Therm Saving Over Target 720,08 h 7 76,987 Therms 176% 155% 588% Financial Considerations Annual Electrical Utility Charge 11 cents/h: $79,204 Annual atural Gas Utility Charge $1/Therm: $76,987 Total Annual Savings: $156,191 Simple Payback Period for $270,000 grant: 1.7 years Estimated 20year value of savings in current dollars: $.12 Million. 7

8 Questions? 2 5 psi Steam to Water semi instantaneous water heaters 25 GPM each EWT 40 F, LWT 140 F 2400 PPH Steam each City Water Make up Temperature Sensors Domestic Hot Water Return 5 psi Steam to Water Heating Hot Water System 0 GPM 140 F EWT 180 F LWT 6,860 PPH Steam@ 0 PSI VFD s for pump motors HHW Pumps 20 HP motor Rated 50 Head 8

9 Variable Primary Chilled Water System 50 Ton 167 Trane Centrifugal Chillers Chilled Water Pressure Transducer Condenser Water Pressure Transducer Chilled Water Manual Bypass Valve Chiller CHW Isolation Valves CHW Flow Sensor 9

10 Chilled Water Valve 40 HP 812 GPM Chiller Water Pumps VFD s for CHW Pump Motors Water Roof top Chilled Bypass 10

11 Rooftop General Exhaust ACF EF 4 & 5 Exhaust Air Dilution Damper Roof top Exhaust Air Dampers Exhaust Fan Isolation Damper 11

12 General Exhaust Air Dilution Damper Supply Air Handler averaging air temperature sensor The Team UCOP Project Manager: Maric Munn, PE UCSF Project Manager: Jeff Hughes, PE UCSF Project Director: Sukhi Sandhu, PE UCSF Building Chief Engineer: Bruno Cekovic Building Engineers involved: Frank Plut & Ronny Melo Engineering Consultant/Commissioning Agent: Raj Daswani, PE (ARUP) Controls Contractor: amas, Inc. PG&E Project Manager: Mark Bramfitt Rock Hall Atrium 12

Chilled Water Energy Savings Study

Chilled Water Energy Savings Study 1 Chilled Water Energy Savings Study Pressure Dependent Valve Sizing and Valve Authority Pressure Independent Valves (Mechanical and Electronic) Chilled Water System Design MIT Beta Site Study-Correcting

More information

Retro-Commissioning in Hospitals

Retro-Commissioning in Hospitals Retro-Commissioning in Hospitals American Society of Healthcare Engineering () Introduction Elements of the Health Facility Retro-Cx Process Retro-Cx Case Studies Hospital Hospital Oklahoma Heart Hospital

More information

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne

Existing Building Cx: Processes & Results A Cultural Journey. Barry Abramson Senior Vice President Servidyne Existing Building Cx: Processes & Results A Cultural Journey Barry Abramson Senior Vice President Servidyne AIA Quality Assurance Learning Objectives 1. Define the key steps in the process of retrocommissioning

More information

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training

City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training City of Fort Collins Building Automation Systems Enhances Savings and Commissioning Efficiency Works Training November 18, 2015 Agenda Commissioning Monitoring Based Commissioning Building Tune up Case

More information

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates

9/13/2011. Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center. Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Mark Hanicits, Director of Facilities and Safety, MetroSouth Medical Center September 21 st, 2011 4:15pm 5:15pm Terry Malloy P.E., Cxa, Project Manager, Teng & Associates Energy consumption (BTU/SF) in

More information

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation

Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY AHR Expo Innovation Award Winner in the Category of Building Automation Knowledge is Power Belimo Energy Valve CHW DELTA T MITIGATION STUDY 2014 AHR Expo Innovation Award Winner in the Category of Building Automation The Belimo Energy Valve won the Technical Innovation of

More information

Use of Building Automation Systems for (Retro)Commissioning

Use of Building Automation Systems for (Retro)Commissioning Center for Energy and Environment Use of Building Automation Systems for (Retro)Commissioning Neal Ray, Center for Energy and Environment Gustav Brändström, Center for Energy and Environment January 17,

More information

Large Campus Chilled Water System RetroCx

Large Campus Chilled Water System RetroCx Large Campus Chilled Water System RetroCx Leonard Rozek, President E Cube, Inc. 21 st National Conference on Building Commissioning AIA Quality Assurance The Building Commissioning Association is a Registered

More information

Optimizing Energy Use in a HealthCare Setting. Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning

Optimizing Energy Use in a HealthCare Setting. Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning Optimizing Energy Use in a HealthCare Setting Michael P. Della Barba Environmental Health & Engineering, Director of Commissioning AIA Quality Assurance The Building Commissioning Association is a Registered

More information

Teague Research Center

Teague Research Center Continuous Commissioning Report for the Teague Research Center Building #445 Submitted to: Utilities Energy Office Physical Plant Department Texas A&M University Prepared by: Energy Systems Laboratory

More information

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations

5/7/2012. Agenda. What is High Performance? Ensuring a Successful Transition to Sustainable, High-Performance Operations Ensuring a Successful Transition to Sustainable, High-Performance Operations Ed Tinsley, PE, LEED AP, HFDP, CHFM, CHC Managing Principal, TME, Inc. Agenda What is High Performance Operations? High Performance

More information

Universal Translator 3: A free software tool to support your data processing needs

Universal Translator 3: A free software tool to support your data processing needs Session: Tools and Resources: Your Knowledge Center Universal Translator 3: A free software tool to support your data processing needs Ryan Stroupe PG&E Pacific Energy Center August 11, 2016 Rhode Island

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Energy Reduction Strategy Through 2020

Energy Reduction Strategy Through 2020 Through 2020 Revised: August 2017 Executive Summary Auburn University is a land, sea and space grant university established in 1856. The university consists of 11,629,000 square feet on 1,840 acres and

More information

CCC/IOU Statewide Partnership SCE Pilot RCx Program

CCC/IOU Statewide Partnership SCE Pilot RCx Program CCC/IOU Statewide Partnership SCE Pilot RCx Program Investigation Report College of the Desert Multi-Agency Library 43-500 Monterey Ave Palm Desert, CA 92260 December 31, 2013 Prepared by (562) 439-1600

More information

Walter Reed National Military Medical Center Bethesda, MD

Walter Reed National Military Medical Center Bethesda, MD Walter Reed National Military Medical Center Bethesda, MD Technical Report Three: Mechanical Systems Existing Conditions Evaluation Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date:

More information

Ground-Coupled Heat Pump And Energy Storage

Ground-Coupled Heat Pump And Energy Storage Ground-Coupled Heat Pump And Energy Storage By Ed Lohrenz, Member ASHRAE; and Sergio Almeida, P.Eng., Member ASHRAE Ground-coupled heat pump (GCHP) systems consume less purchased energy than an HVAC system

More information

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader

Building Controls Strategies Conference. Retro-Commissioning with BAS Overview. 10 March Steve Brown, CAP ESD Controls Team Leader Building Controls Strategies Conference Retro-Commissioning with BAS Overview 10 March 2015 Steve Brown, CAP ESD Controls Team Leader Kevin Caho PE, LEED AP ESD Energy Engineer Agenda BAS Overview RCx

More information

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC

LIBRARY ENERGY WALK- THROUGH. Andy Robinson, Training and Education, SEDAC LIBRARY ENERGY WALK- THROUGH Andy Robinson, Training and Education, SEDAC ILLINOIS ENERGY NOW University of Illinois 360 Energy Group 2 WHAT WE DO SEDAC Free Services Outreach and Training Energy Assistance

More information

Chilled Water Plant Design American Standard Inc.

Chilled Water Plant Design American Standard Inc. Chilled Water Plant Design 2003 American Standard Inc. Agenda Earthwise System Variable Primary Flow Series Configuration Case Study 20,000RT Project Parallel, primary/secondary, low temp, YK Series-counter,

More information

Performance Monitoring for Efficiency

Performance Monitoring for Efficiency Performance Monitoring for Efficiency THOMAS ANDERSON, CCP EMILY CROSS, MASc, PEng, CEM Burlington, Vermont cx associates.com tom@cx associates.com emily@cx associates.com Efficiency Vermont is a Registered

More information

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure

Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure Advantages of Financing Continuous Commissioning As An Energy Conservation Retrofit Measure Guanghua Wei, P.E. Malcolm Verdict, C.E.M Joseph T. Martinez Energy Systems Laboratory, 3581 TAMU Texas A&M University

More information

Recommissioning Energy Savings Persistence

Recommissioning Energy Savings Persistence Recommissioning Energy Savings Persistence Martin Selch and James Bradford, PE, PhD Nexant, Inc. Synopsis Utilities, administrators, or turnkey providers in many areas around the country offer recommissioning

More information

Energy Efficiency in Multi-Tenant Office Buildings

Energy Efficiency in Multi-Tenant Office Buildings Energy Efficiency in Multi-Tenant Office Buildings Presented by David Herman, PE, LEED AP Principal, EnerG Associates, LLC 3/10/2015 1 Learning Objectives 1. List the principal sources and uses of energy

More information

Existing Building Upgrades

Existing Building Upgrades Existing Building Upgrades Greg Swiss - Building Energy Specialist Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign Providing effective strategies for public and

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

Large University Central Chiller Plant Design Considerations

Large University Central Chiller Plant Design Considerations Carrier Engineering Newsletter Volume 5, Issue 3 Large University Central Chiller Plant Design Considerations Large campus chilled water plants have unique constraints and need careful evaluation for successful

More information

High Technology Energy Savings Guide

High Technology Energy Savings Guide High Technology Energy Savings Guide The high-tech industry is a crucial and dynamic part of Oregon s economy that is expected to grow faster than other industries over the next decade. Working in a highly

More information

Chilled Beams. The new system of choice?

Chilled Beams. The new system of choice? Chilled Beams The new system of choice? Presented By: Kevin M. Pope P.E. Jason Leffingwell Hammel Green And Abrahamson, Inc. and Ken Bauer, P.E., LEED AP Butters-Fetting Co., Inc. History of Chilled Beams

More information

Success with MEASUREMENT & VERIFICATION

Success with MEASUREMENT & VERIFICATION 2016 Success with MEASUREMENT & VERIFICATION Prepared for the North Carolina Department of Environmental Quality. Project funded by the U.S. Department of Energy, Office of Energy Efficiency and Renewable

More information

Where Does It All Go?

Where Does It All Go? Where Does It All Go? Using Simple Loggers to Dis-aggregate Whole Building Energy Data Ryan Stroupe, Pacific Energy Center April 2, 26 San Francisco, California Topics Covered Here Value of baselining

More information

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES

Texas Hospital. Central Plant Redesign. Central Utility Plant SECOND PLACE HEALTH CARE FACILITIES, EXISTING 2013 ASHRAE TECHNOLOGY AWARD CASE STUDIES This article was published in ASHRAE Journal, January 2014. Copyright 2014 ASHRAE. Posted at www. ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis

ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis ISPE CASA Energy Management Forum - Energy Management of Capital Projects at Novartis Lee Willmon, Head of Health, Safety and Environment Vaccines and Diagnostics Holly Springs, NC 16 Sept 10 Agenda Holly

More information

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan

Indiana University Glick Eye Institute. LEED Measurement & Verification Plan Indiana University Glick Eye Institute LEED Measurement & Verification Plan April 10, 2012 1 Table of Contents General Introduction... 3 Facility Description... 4 M&V Objectives... 4 M&V Approach/Option...

More information

Persistence Tracking in a Retro-commissioning Program

Persistence Tracking in a Retro-commissioning Program Persistence Tracking in a Retro-commissioning Program Mike Eardley Architectural Energy Corporation Synopsis The persistence of energy savings and electrical demand reductions created by retrocommissioning

More information

FACILITIES MANAGEMENT Energy Conservation Projects Summary Updated 05/22/2016

FACILITIES MANAGEMENT Energy Conservation Projects Summary Updated 05/22/2016 FACILITIES MANAGEMENT Energy Conservation Projects Summary Updated 05/22/2016 Utility Operations Completed in FY16 Buchtel Parking Garage LED Lighting Upgrades - Project scope includes the upgrade of (139)

More information

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS

ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS ARE YOUR VARIABLE SPEED PUMPING APPLICATIONS DELIVERING THE PREDICTED SAVINGS? IMPROVING CONTROL TO MAXIMIZE RESULTS University of Dayton, Dayton, Ohio Vijay Gopalakrishnan, Lead Engineer Alexandra Brogan,

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency

Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Case Study for Fortune 500 Telecom: Retrofitting Pneumatic Controls for Energy Efficiency Summary Major Fortune 500 Telecom Company Estimated 40% the corporate building portfolio still use pneumatic thermostats

More information

SGM Engineering, Inc.

SGM Engineering, Inc. SGM Engineering, Inc. 1. What is a typical Central Energy Plant consists of? BAS controls, chillers, pumps, cooling towers, electrical distribution, piping, chemicals, heating systems, and generators.

More information

Baffled Openings at Chain Link Fencing: Design shall consist of two end-posts set 4 feet apart, and a 10 foot wide chain-link fence panel equal in height as the adjacent fence. Chain link fence panel shall

More information

UC STRATEGIC ENERGY PLAN

UC STRATEGIC ENERGY PLAN UC STRATEGIC ENERGY PLAN University of California, San Francisco University of California, San Francisco Medical Center FINAL Prepared for University of California Office of the President September 2,

More information

Retro-Commissioning for Existing Facilities

Retro-Commissioning for Existing Facilities Retro-Commissioning for Existing Facilities Tom Meyer Director, Technical Programs National Environmental Balancing Bureau 8575 Grovemont Circle Gaithersburg, Maryland 20877 (301) 977-3698 www.nebb.org

More information

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE

RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT. Adam Renzi, PE RETRO-COMMISSIONING: AN OWNER S LOOK AT THE TRUE COSTS AND RETURN ON INVESTMENT Adam Renzi, PE AIA Quality Assurance The Building Commissioning Association is a Registered Provider with The American Institute

More information

Centre for Addiction and Mental Health Queen Street Campus Energy Conservation and Demand Management Plan

Centre for Addiction and Mental Health Queen Street Campus Energy Conservation and Demand Management Plan Centre for Addiction and Mental Health Queen Street Campus Energy Conservation and Demand Management Plan In Transition to Sustainable Infrastructure The Centre for Addiction and Mental Health is in the

More information

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants

Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Small Oil-Less Centrifugal Compressors: Bringing Energy Efficiency and Reduced Costs to Chiller Plants Ben Erpelding and Annika Moman, San Diego Regional Energy Office ABSTRACT According the U.S. Department

More information

Condenser Water Heat Recovery"

Condenser Water Heat Recovery PLEASE MUTE CELL PHONES Condenser Water Heat Recovery" Julian de Bullet ASHRAE Distinguished Lecturer Director of Industry Relations McQuay International 703-395-5054 1 What Is Sustainability? sustainable

More information

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations

Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Low-Hanging Fruit Simple Steps Toward Energy Effective Building Operations Roger Ebbage Northwest Water / Energy Education Institute Lane Community College May 7-9 Enzian Inn - Leavenworth, Washington

More information

Retrocommissioning (RCx)

Retrocommissioning (RCx) Retrocommissioning (RCx) Facilities & Services - Engineering Services Saving the planet, two buildings at a time. Mr. Karl Helmink Mr. Damon McFall Creating a Sustainable Campus What is Retrocommissioning

More information

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering

Do-It-Yourself Energy Audit. Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Do-It-Yourself Energy Audit Bob Furgeson, PE CEM CBCP GBE CEA Shive-Hattery Architects+Engineering Agenda» Basic Terminology» Background» Benchmarking» Audit Types/ASHRAE Standard» Building Audit Systems

More information

Italcementi Center for Research and Innovation

Italcementi Center for Research and Innovation Italcementi Center for Research and Innovation Bergamo, Italy LEED-NC v2.1 EAc1 A. Project Narrative (Viridian) analyzed the energy use of the proposed Italcementi Center for Research and Innovation located

More information

Energy Conservation and Finances Using NYPA Performance Contracts. SUNY Sustainability Conference September 19-20, 2011

Energy Conservation and Finances Using NYPA Performance Contracts. SUNY Sustainability Conference September 19-20, 2011 Energy Conservation and Finances Using NYPA Performance Contracts SUNY Sustainability Conference September 19-20, 2011 By The Numbers Acres......... 476 Buildings...... 76 Square Feet.... 2.6M + Student

More information

Building X Retrocommissioning Final Report

Building X Retrocommissioning Final Report Building X Retrocommissioning Final Report A study done by Portland Energy Conservation, Inc. (PECI) And Partner IMPORTANT NOTICE: This sample document is provided for instructional purposes only. CCC

More information

Acutherm was spec d here. Building Automation Guide for Therma-Fuser Systems

Acutherm was spec d here. Building Automation Guide for Therma-Fuser Systems Building Automation Guide for Therma-Fuser Systems Acutherm was spec d here BUILDING AUTOMATION OPTIONS FOR THERMA-FUSER SYSTEMS As energy costs continue to rise, the management of energy while balancing

More information

Sea Water Heat Pump Project

Sea Water Heat Pump Project Sea Water Heat Pump Project Alaska SeaLife Center, Seward, AK Presenter: Andy Baker, PE, YourCleanEnergy LLC JCOS Forum Juneau Library April 11, 2013 This powerpoint Copyright 2013 by YourCleanEnergy LLC,

More information

B. System Design and Performance Requirements

B. System Design and Performance Requirements 15625 Water Chillers This document provides design standards only, and is not intended for use, in whole or in part, as a specification. Do not copy this information verbatim in specifications or in notes

More information

Mission Critical Commissioning for Healthcare Facilities

Mission Critical Commissioning for Healthcare Facilities Mission Critical Commissioning for Healthcare Facilities Steven R. Rusty Ross SSRCx, LLC Synopsis Healthcare Facilities serve a critical and unique mission. Few facilities delivered by the construction

More information

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study

Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study North Orange County Community College District Campus-Wide Cooling Plant Load Analysis & Thermal Energy Storage (TES) System Concept Engineering Study Fullerton College Final September 8, 2017 Table of

More information

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013

NEBBinar: Managing Building Performance through Commissioning. March 28, 2013 NEBBinar: Managing Building Performance through Commissioning March 28, 2013 0 Moderator Jim Huber, NEBB Vice President and President of Complete Commissioning Jim Huber is the President of Complete Commissioning.

More information

UC STRATEGIC ENERGY PLAN

UC STRATEGIC ENERGY PLAN UC STRATEGIC ENERGY PLAN University of California, Riverside FINAL Prepared for University of California Office of the President October 9, 28 Prepared by: Newcomb Anderson McCormick, Inc. 21 Mission Street,

More information

Monitoring-Based Commissioning (MBCx) Plan Template

Monitoring-Based Commissioning (MBCx) Plan Template Monitoring-Based Commissioning (MBCx) Plan Template Hannah Kramer Eliot Crowe Jessica Granderson Building Technology and Urban Systems Division Lawrence Berkeley National Laboratory Prepared for Amy Jiron

More information

Energy Treasure Hunt ESI Members Meeting. Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity

Energy Treasure Hunt ESI Members Meeting. Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity Energy Treasure Hunt 2017 ESI Members Meeting Shaunna Tobin, TE Connectivity Kelli Swain, TE Connectivity Agenda What is an Energy Treasure Hunt? What value do they bring? What are the results? Who are

More information

Energy Audit Baseline & Economic Analysis. Mr. Jirayut Charoenchatchai Manager,Energy Efficiency Div. Bright Management Consulting Co.,Ltd.

Energy Audit Baseline & Economic Analysis. Mr. Jirayut Charoenchatchai Manager,Energy Efficiency Div. Bright Management Consulting Co.,Ltd. Energy Audit Baseline & Economic Analysis Mr. Jirayut Charoenchatchai Manager,Energy Efficiency Div. Bright Management Consulting Co.,Ltd. Page 1 Content Energy Audit Approach Criteria for Data Collection

More information

IMPROVING CAMPUS CHILLED WATER SYSTEMS WITH INTELLIGENT CONTROL VALVES: A FIELD STUDY

IMPROVING CAMPUS CHILLED WATER SYSTEMS WITH INTELLIGENT CONTROL VALVES: A FIELD STUDY 102 IMPROVING CAMPUS CHILLED WATER SYSTEMS WITH INTELLIGENT CONTROL VALVES: A FIELD STUDY Gregor P. Henze Department of Civil, Environmental and Architectural Engineering University of Colorado Boulder

More information

Financial Validation Assessment Report

Financial Validation Assessment Report November 2013 Financial Validation Assessment Report Higher Education Institution Chiller Replacement / Chicago, IL Attn: Chief Financial Officer / Higher Education Institution Primera Engineers, Ltd.

More information

REPORT DOCUMENTATION PAGE

REPORT DOCUMENTATION PAGE REPORT DOCUMENTATION PAGE Form Approved OMBNo.0704-018 Public reporting burden for this collection of information is estimated to average 1 hour per response, including the time for reviewing instructions,

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 3 Project Name: Av. Cabildo 3067, 4 piso 02/13/2011 DESIGN COOLING DESIGN HEATING COOLING DATA AT Feb 1500 HEATING DATA AT DES HTG COOLING OA DB / WB 34.9 C / 23.8

More information

Central Chiller Plants

Central Chiller Plants Central Chiller Plants Institute for Facilities Management New Orleans, LA January 18,2016 Course 319 Presenter: John Vucci Associate Director HVAC Systems University of Maryland College Park, Maryland

More information

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems

Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems AIHEC VENT 2006 Recommended Methods to Evaluate Performance of Variable Air Volume Fume Hood Systems Thomas C. Smith Exposure Control Technologies, Inc. Safety is the Primary Objective Lab Occupancy 26%

More information

UC Irvine Energy Efficiency Energy Storage Energy Optimization. Matt Gudorf CEM, LEED AP Assistant Director Energy, Engineering, and Inspection

UC Irvine Energy Efficiency Energy Storage Energy Optimization. Matt Gudorf CEM, LEED AP Assistant Director Energy, Engineering, and Inspection UC Irvine Energy Efficiency Energy Storage Energy Optimization Matt Gudorf CEM, LEED AP Assistant Director Energy, Engineering, and Inspection Quick Facts Established in 1965 Comprehensive Research University

More information

BEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign

BEYOND O&M. Shawn Maurer SEDAC Building Energy Specialist. Smart Energy Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign BEYOND O&M Shawn Maurer SEDAC Building Specialist Smart Design Assistance Center (SEDAC), University of Illinois at Urbana Champaign PRESENTATION OVERVIEW and Take away: Regular costs less over the long

More information

Energy Trust of Oregon New Buildings Program Technical Guidelines

Energy Trust of Oregon New Buildings Program Technical Guidelines Energy Trust of Oregon New Buildings Program Technical Guidelines V2016.1 160222 Section 1 Introduction... 3 1.1 Oregon Code Requirements... 3 1.2 Modeled Savings (2010 and 2014 Code Projects)... 4 1.3

More information

Pacific Energy Center

Pacific Energy Center Pacific Energy Center's Retro-Commissioning Workshops: Developing Expertise through Interactive Training Ryan Stroupe, Pacific Energy Center Virginia Waik, City of Palo Alto Rishabh Kasliwal, Cogent Energy

More information

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE

Doubling Down on Not Balancing Variable Flow Hydronic Systems BY STEVEN T. TAYLOR, P.E., FELLOW ASHRAE This article was published in ASHRAE Journal, December 2017. Copyright 2017 ASHRAE. Posted at www.ashrae.org. This article may not be copied and/or distributed electronically or in paper form without permission

More information

No Cost/Low Cost Energy

No Cost/Low Cost Energy No Cost/Low Cost Energy Saving Strategies Randall D. Manteufel University of Texas at San Antonio Energy Efficiency in Local Government andschool Districts in the Border Region No Cost/Low Cost Relatively

More information

Small Building Tune-up Pilot Program. Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc.

Small Building Tune-up Pilot Program. Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc. Small Building Tune-up Pilot Program Kevin Afflerbaugh, LEED AP Jim Zarske, PE, CEM, LEED AP Nexant, Inc. AIA Quality Assurance Learning Objectives 1. The significant, yet untapped commissioning opportunities

More information

Energy Retrofit Loan Program

Energy Retrofit Loan Program Energy Retrofit Loan Program Service Provider Profile General Firm Information Bright Power, Inc. 11 Hanover Square, 21 st Floor, New York, NY 10005 Primary Contact: James Hannah, (212) 803-5868 x2106,

More information

Union College Combined Cooling, Heat and Power Project

Union College Combined Cooling, Heat and Power Project Union College Combined Cooling, Heat and Power Project Presented by: Mark Donovan, PE Union College, Assistant Director of Utilities Aaron Bolhous, PEng CHA, Project Engineer Agenda Introduction to Union

More information

Energy Modeling Applications for Existing Buildings

Energy Modeling Applications for Existing Buildings Energy Modeling Applications for Existing Buildings Presented by: Clark Denson PE, CEM, BEMP, LEED AP BD+C 4/27/12 Learning Objectives 1. List available methods and tools for energy modeling 2. Explain

More information

DesignTools Software Energy Analyzer User Manual

DesignTools Software Energy Analyzer User Manual DesignTools Software Energy Analyzer User Manual Table of Contents Introduction...1 Installing Energy Analyzer...3 Getting Started...4 General...4 Project Details (Energy Analyzer Wizard Application)...5

More information

Chilled Water System Optimization

Chilled Water System Optimization Advanced HVAC Diagnostics and Control Strategies Chilled Water System Optimization Brian Leduc Carrier Corporation August 16, 2017 Contents of this presentation 2017 Carrier Corporation Tampa Convention

More information

Energy Saving Calculations for Recommissioning and Design

Energy Saving Calculations for Recommissioning and Design ASHRAE December Chapter Meeting Energy Saving Calculations for Recommissioning and Design Gustav Brändström Angela Vreeland December 13, 2011 Agenda Agenda Introduction Trending and Trend Data TMY and

More information

ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN

ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN ENERGY AND WATER CONSERVATION AND DEMAND MANAGEMENT PLAN 2014 2019 CONTENTS EXECUTIVE SUMMARY... 3 1. CENTENNIAL COLLEGE - DISTRIBUTION OF ENERGY CONSUMPTION IN 2012... 4 1.1. Overview of Centennial College

More information

Overall Sustainable Design

Overall Sustainable Design Overall Sustainable Design HVAC Design UC Merced Classroom and Office Building & the Central Plant These two projects demonstrate an integrated approach to building a more sustainable campus from the bottom

More information

PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools. Art Munns Senior Project Engineer OCI Associates, Inc.

PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools. Art Munns Senior Project Engineer OCI Associates, Inc. PRESENTATION BY: Sean P. Murray Energy/Facility Use Manager St. Lucie County Public Schools Jason Smith, PE, LEED AP BD+C, CEM Principal / Dir. of Mech. Engineering OCI Associates, Inc. Art Munns Senior

More information

Thesis Proposal. Park. Findlay 12/10/2010. Connor Blood

Thesis Proposal. Park. Findlay 12/10/2010. Connor Blood 1 Park Place Corporate Center One Mechanical Senior Thesis Project Thesis Proposal Park Place Corporate Center One Findlay Township,, PA 12/10/2010 Proposal Connor Blood 2 Park Place Corporate Center One

More information

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m.

Air Source Heat Pumps in the Commercial Market. Thursday, February 5, :00-10:30 a.m. Air Source Heat Pumps in the Commercial Market Thursday, February 5, 2015 9:00-10:30 a.m. 1. Commercial Equipment Applications, Benefits, Limitations 2. Case Studies 3. Efficiency Vermont Technical & Financial

More information

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING

CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING CONDENSING TEMPERATURE CONTROL THROUGH ENERGY MANAGEMENT SYSTEM SIMULATON FOR A LARGE OFFICE BUILDING Young-Hoon Kwak 1, Dong-Seok Kong 1, Se-Hwan Cheon 1, Ro-Yeul Kwak 2, and Jung-Ho Huh 3 1 Department

More information

Caribbean Hotel Energy Efficiency Action (CHENACT)

Caribbean Hotel Energy Efficiency Action (CHENACT) Caribbean Hotel Energy Efficiency Action (CHENACT) Energy Efficiency Opportunities for Caribbean Hotels 31 st March 2010 Presented by: Andre Escalante Agenda Air Conditioning Energy Efficient Lighting

More information

Hourly Analysis Program v.4.1 Page 1 of 1

Hourly Analysis Program v.4.1 Page 1 of 1 Air System Design Load Summary for Zona 8 DESIGN COOLING DESIGN HEATING COOLING DATA AT Dec 1700 HEATING DATA AT DES HTG COOLING OA DB / WB 33.1 C / 23.5 C HEATING OA DB / WB -0.6 C / -3.2 C Sensible Latent

More information

THE KEMPER BUILDING 1 EAST WACKER DRIVE PHIL KEUHN SIEBEN ENERGY ASSOCIATES

THE KEMPER BUILDING 1 EAST WACKER DRIVE PHIL KEUHN SIEBEN ENERGY ASSOCIATES THE KEMPER BUILDING 1 EAST WACKER DRIVE BY PHIL KEUHN OF SIEBEN ENERGY ASSOCIATES CHAPTERfREGIONAL TECHNOLOGY A WARD - SHORT FORM 1. Category (Check one and indicate New or Existing, if applicable).,..(!)~8(}~lnerc[~i~~ii9in:~~).,...;;().

More information

PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA

PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA STATE OF CALIFORNIA PUBLIC UTILITIES COMMISSION 505 VAN NESS AVENUE SAN FRANCISCO, CA 94102-3298 Edmund G. Brown Jr., Governor TO: All Parties in R.13-11-005 FROM: Robert Hansen, Utilities Engineer DATE:

More information

Normal Children's Discovery Museum, LEED Silver:

Normal Children's Discovery Museum, LEED Silver: Normal Children's Discovery Museum, LEED Silver: Post Occupancy Energy Performance October 28, 2010 Hosted by: USGBC Illinois Chapter, Central Illinois Branch Sponsored by: ASHRAE Central Illinois Chapter

More information

Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System

Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System Retrocommissioning Within the U.S. Green Building Council s LEED for Existing Buildings (LEED-EB) Certification System Eric Baxter, Hannah Friedman, Larry Luskay, and Tudi Haasl, Portland Energy Conservation,

More information

Request for Proposals Town of Plymouth, New Hampshire

Request for Proposals Town of Plymouth, New Hampshire 1. General Information Request for Proposals Town of Plymouth, New Hampshire Building Energy Audits The Town of Plymouth is seeking bids for qualified individuals or firms to provide six (6) Building Energy

More information

Variable Frequency Drives

Variable Frequency Drives 10 Energy According to the U.S. Department of Energy, buildings use 39% of the energy and 74% of the electricity produced each year in the United States. The Energy & Atmosphere category encourages a wide

More information

Walter Reed National Military Medical Center Bethesda, MD

Walter Reed National Military Medical Center Bethesda, MD Walter Reed National Military Medical Center Bethesda, MD Technical Report One: ASHRAE Standard 62.1 2007 and 90.1 2007 Analysis Prepared For: Dr. James D. Freihaut Prepared By: Justin Herzing Date: 10/05/2009

More information

Implications of Measured Commercial Building Loads on Geothermal System Sizing

Implications of Measured Commercial Building Loads on Geothermal System Sizing Implications of Measured Commercial Building Loads on Geothermal System Sizing ASHRAE Annual Meeting June 23, 1999 Hugh I Henderson, Jr.. P.E. CDH Energy Corp. Cazenovia,, NY www.cdhenergy.com Overview

More information

Operational Performance Characterization of a Heat Pump System Utilizing Recycled Water as Heat Sink and Heat Source in a Cool and Dry Climate

Operational Performance Characterization of a Heat Pump System Utilizing Recycled Water as Heat Sink and Heat Source in a Cool and Dry Climate energies Article Operational Performance Characterization of a Heat Pump System Utilizing Recycled Water as Heat Sink and Heat Source in a Cool and Dry Climate Piljae Im 1, Xiaobing Liu 1, * and Hugh Henderson

More information

Chilled Water Plant Redesign

Chilled Water Plant Redesign 17 Chilled Water Plant Redesign OVERVIEW The chilled water plant redesign includes the addition of a thermal energy storage system. This allows for economic and operational benefits for the facility by

More information