Assessment Completed by: Asbestos Inspections, LLC 4686 Pee Dee Highway Conway, South Carolina (843)

Size: px
Start display at page:

Download "Assessment Completed by: Asbestos Inspections, LLC 4686 Pee Dee Highway Conway, South Carolina (843)"

Transcription

1 LIMITED ASBESTOS AND LEAD-BASED PAINT INSPECTION REPORT FORMER FLORENCE POST OFFICE Florence, South Carolina Asbestos Inspections, LLC Project # Performed in general accordance with SCDHEC regulation along with OSHA regulation 29 CFR 1926 and 29 CFR Assessment Completed by: Asbestos Inspections, LLC 4686 Pee Dee Highway Conway, South Carolina (843) Dawn Schoolcraft SCDHEC ID# BI Assessment Completed For: Francis Marion University Mr. Mike Richey P.O. Box Florence, South Carolina Inspection Completed On February 9-10, 2017 Report Prepared On February 22, 2017

2 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 TABLE OF CONTENTS 1.0 SIGNATURE PAGE COVER LETTER EXECUTIVE SUMMARY Scope and Purpose Facility Conditions Findings and Conclusions... 6 a. Asbestos... 6 b. Lead-Based ASBESTOS ASSESSMENT DATA LEAD-BASED PAINT ASSESSMENT DATA CONCLUSIONS a. Asbestos a. Lead-Based Appendix 1 Site Location Plan and Sample Location Plans (Figures 1 thru 6) Appendix 2 Photographs Appendix 3 Asbestos Laboratory Results Appendix 4 Lead-Based Laboratory Results Page 2 of 14

3 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, SIGNATURE PAGE This report has been performed at the request of Mr. Mike Richey, with Francis Marion University. The inspection was conducted by Mrs. Dawn Schoolcraft with Asbestos Inspections, LLC on February 9-10, The report was prepared and reviewed by the undersigned inspector. Inspection Performed by: SCDEHC # Expires Signature Date Dawn Schoolcraft BI /17/18 Dawn Schoolcraft 2/9/-2/10/17 Report Prepared by: Dawn Schoolcraft BI /17/18 Dawn Schoolcraft 2/22/17 Report Reviewed by: Dawn Schoolcraft BI /17/18 Dawn Schoolcraft 2/22/17 Page 3 of 14

4 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, COVER LETTER February 22, 2017 Francis Marion University Mr. Mike Richey P.O. Box Florence, South Carolina Subject: Limited Asbestos and Lead-Based Inspection Report Former Florence Post Office Florence, South Carolina Asbestos Inspections, LLC Project # Dear Mr. Richey: Asbestos Inspections, LLC has completed a Limited Asbestos and Lead-Based Inspection for the former Florence Post Office located at 201 West Evans Street, in Florence, South Carolina. The asbestos inspection was completed on February 9-10, 2017 by a South Carolina Department of Health and Environmental Control (SCDHEC) building inspector. The lead-based paint inspection was completed by a licensed lead paint inspector. The following report summarizes the project background, assessment procedures, results, and conclusions. The results presented in this report are indicative of conditions during the time of the inspection and of the specific areas outlined. The information provided in this report should not be used as a bidding document and field conditions should be verified. Should suspect building materials, not included within this report, be identified or impacted during the destructive activities, bulk samples must be collected and analyzed for asbestos content. I appreciate this opportunity to provide my services. Should you have any questions concerning this report, please contact me at (843) or (843) Sincerely, Dawn Schoolcraft Dawn Schoolcraft Asbestos Building Inspector (SCDHEC #BI-00738) Lead Inspector (License #LBP-I-I ) Page 4 of 14

5 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, EXECUTIVE SUMMARY 3.1 Scope and Purpose Mr. Mike Richey with Francis Marion University, requested this assessment for the former Florence Post Office located at 201 West Evans Street, in Florence, South Carolina. It is our understanding that the University is interested in potentially buying the facility and renovate select areas for use by the school. The purpose of this assessment is to identify asbestos containing materials (ACMs) prior to the scheduled renovations. The inspection was completed in accordance with procedures specified in SCDHEC regulation along with Occupational Safety and Health Administration (OSHA) regulation 29 Code of the Federal Regulations (CFR) 1926 and Lead-Based Inspection along with Occupational Safety and Health Administration (OSHA) Lead in Construction Standard regulation 29 Code of the Federal Regulations (CFR) The lead paint chip samples collected were analyzed by a laboratory recognized under the Environmental Protection Agencies (EPA) National Lead Laboratory Accreditation Program (NLLAP). The representative asbestos bulk samples collected were analyzed by a National Voluntary Laboratory Accreditation Program (NVLAP) certified laboratory which is administered by the National Institute of Standards and Technology (NIST). This report has been prepared in accordance with Environmental Protection Agency (EPA) 40 CFR, (a)(4). 3.2 Facility Conditions The subject facility is approximately 30,000 square-feet in size and is comprised of both 2 and 3-stories with an attic and a basement. At this time, renovations are to include the interior of the structure and the 2 nd floor asphalt built-up roof. The interior consists of mostly plaster walls and ceilings, suspended ceiling tile, wood paneled walls, terrazzo floor, sheetrock, thermal system insulation (TSI), texture coated ceiling, carpet, wood floors, and multiple vinyl floor coverings. The former boiler system remains in the basement, to include the pipe insulation used to heat the building and supply hot water. Remnant 9 x9 floor tile mastic was also observed in the basement. The building was occupied during our inspection and is currently used as a courthouse by Florence County. Every attempt was made to identify suspect asbestos containing material. There was an accessible shaft identified in the basement, which appeared to have been closed off. We were able to identify various pipe insulations and HVAC ducting in areas that are not easily accessible, due to renovations that have taken place throughout the years. The possibility exists that suspect materials were undetected in inaccessible areas such as areas deemed unsafe to enter, locked rooms, behind exterior veneer, pipe chases, or wall voids. If additional suspect materials not included in this report are discovered during renovation, bulk samples should be collected and analyzed for asbestos content. Page 5 of 14

6 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, Findings and Conclusions a. Asbestos The EPA and SCDHEC define materials as asbestos containing if an asbestos content >1% is identified in a representative sample. Asbestos >1% was detected in the following materials sampled and analyzed: DM2 HVAC duct mastic in basement I.O. Gallery (approximately 50 sf) DM3 HVAC duct mastic in 2 nd and 3 rd floor halls above ceiling tile (approximately 170 sf) I1 Boiler insulation in basement (approximately 500 sf) I2 Pipe insulation wrap to include elbows in basement and throughout other areas such as 1 st floor passage and 2 nd floor rooms (approximately 2,500 lf). No pipe insulation was observed on the 3 rd floor rooms or above the ceiling tile. I4 Water tank insulation in basement (approximately 50 sf) I5 Cardboard insulation in basement (approximately 480 sf) I6 Furnace board insulation in basement (approximately 480 sf) I8 Chilled water pipe insulation (approximately 600 lf) I9 HVAC insulation 2 nd and 3 rd floor mechanical rooms and the attic (approximately 1,200 sf) I10 Tar wrapped pipe insulation in attic (approximately 60 lf) RF1 Silver painted roof flashing on 2 nd floor roof (approximately 140 sf) No asbestos >1% was detected in the remaining samples collected and analyzed. Per SCDHEC regulations, the asbestos containing materials should be removed by a licensed abatement contractor prior to any destructive activities at the facility. Due to the quantity of regulated ACMs identified, an asbestos abatement plan will be required prior to abatement. Additionally, asbestos air monitoring will be required during abatement activities. A copy of this report along with an application for abatement and demolition must be submitted to SCDHEC 10 working days prior to any abatement and demolition activities. Additionally, a copy of this report should be provided to the contractors to assist with compliance with applicable State and Federal regulations. b. Lead-Based OSHA defines paint as lead-based if an amount greater than 0.06% lead by weight is identified in a paint chip sample. The SCDHEC requires the disposal of paint coated items be placed in a Municipal Solid Waste lined landfill. Based on samples collected from the previous inspection and along with the samples collected during this inspection, lead greater than 1.0 mg/cm 2 was identified in the following paint coated surfaces sampled and analyzed: P-01 Blue painted plaster walls P-02 Tan painted plaster walls P-04 Green painted plaster walls P-05 Red painted brick wall in basement P-07 Beige/Tan painted plaster walls Please know that traces of lead was identified in the remaining samples collected and analyzed. Any work and/or disturbance to the painted surfaces within the facility, must at a minimum, be done in accordance with Page 6 of 14

7 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 federal regulations governing Lead-Safe Work Practices, 24 CFR A copy of this report should be provided to the contractors to assist with compliance with applicable State and Federal regulations. The results presented in this report are indicative of conditions during the time of the assessment. The information provided in this report should not be used as a bidding document and field conditions and quantities should be verified. 4.0 ASBESTOS ASSESSMENT DATA The assessment was performed by observing and sampling suspect ACMs in the structure prior to the scheduled demolition. Representative bulk samples were then extracted, recorded on a chain of custody, and submitted to CEI Labs of Cary, North Carolina for laboratory analysis. The samples were tested via Polarized Light Microscopy (PLM); however, SCDHEC requires a Transmission Electron Microscopy (TEM) test be performed for all non-friable organically bound material found negative via PLM. The following table exhibits the suspect material sampled, location, quantity of material sampled, condition of material, potential for future disturbance, laboratory test method, and laboratory result for each sample collected. Sample # P1-01 P1-02 P1-03 P1-04 P1-05 P1-06 P1-07 P1-08 P1-09 Material Plaster Skim Coat - Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Plaster Skim Coat - Plaster Base Coat - Gray Location Walls and Ceilings Throughout Cat./# Samples S/9 Qty. 60,000 sf Page 7 of 14 Asbestos Type % Cond. Pot. Dist. Haz. Assess. Test Method

8 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Sample Cat./# Asbestos Pot. Haz. Test Material Location Qty. % Cond. # Samples Type Dist. Assess. Method DM1-01 Duct Mastic Tan ND 0 G/NF PSD 3 PLM Basement DM1-02 Duct Mastic - Tan TSI/3 100 sf ND 0 G/NF PSD 3 PLM I.O. Gallery DM1-03 Duct Mastic - Tan ND 0 G/NF PSD 3 TEM DM2-01 Duct Mastic Black Chrysotile 5 G/NF PSD 3 PLM Basement DM2-02 Duct Mastic Black TSI/3 50 sf I.O. Gallery DM2-03 Duct Mastic Black DM3-01 Duct Mastic/Wrap - Black 2 ND & 3 RD Chrysotile 5 G/NF PSD 3 PLM DM3-02 Duct Mastic/Wrap Floor Hall Black Above TSI/3 170 sf Duct Mastic/Wrap - Ceiling Tile DM Black F1-01 Flooring - Brown ND 0 G/NF PSD 3 PLM Basement F1-02 Flooring - Brown M/3 350 sf ND 0 G/NF PSD 3 PLM I.O. Gallery F1-03 Flooring - Brown ND 0 G/NF PSD 3 TEM F2-01 Mastic - Black Basement ND 0 G/NF PSD 3 PLM F2-02 Mastic Black Mastic M/3 2,000 sf ND 0 G/NF PSD 3 PLM F2-03 Mastic - Black Remnant ND 0 G/NF PSD 3 TEM Floor Tile ND 0 G/NF PSD 3 PLM Mastic - Yellow ND 0 G/NF PSD 3 PLM F3-01 Floor Tile - Black ND 0 G/NF PSD 3 PLM Mastic - Yellow ND 0 G/NF PSD 3 PLM Floor Tile ND 0 G/NF PSD 3 PLM Mastic - Yellow 1 st Floor ND 0 G/NF PSD 3 PLM F3-02 M/3 120 sf Floor Tile - Black Kitchen ND 0 G/NF PSD 3 PLM Mastic - Yellow ND 0 G/NF PSD 3 PLM Floor Tile ND 0 G/NF PSD 3 TEM Mastic - Yellow ND 0 G/NF PSD 3 TEM F3-03 Floor Tile - Black ND 0 G/NF PSD 3 TEM Mastic - Yellow ND 0 G/NF PSD 3 TEM Floor Tile Blue ND 0 G/NF PSD 3 PLM F4-01 Floor Tile Pink ND 0 G/NF PSD 3 PLM Mastic - Tan ND 0 G/NF PSD 3 PLM Floor Tile Blue 1 st Floor ND 0 G/NF PSD 3 PLM F4-02 Floor Tile Pink Rear M/3 120 sf ND 0 G/NF PSD 3 PLM Mastic - Tan Bathroom ND 0 G/NF PSD 3 PLM Floor Tile Blue ND 0 G/NF PSD 3 TEM F4-03 Floor Tile Pink ND 0 G/NF PSD 3 TEM Mastic - Tan ND 0 G/NF PSD 3 TEM F5-01 Flooring Brown 2 nd Floor ND 0 G/NF PSD 3 PLM Record F5-02 Flooring Brown M/3 300 sf Room & ND 0 G/NF PSD 3 PLM F5-03 Flooring Brown Mech. Room ND 0 G/NF PSD 3 TEM Covebase Mastic - VCB1-01 ND 0 G/NF PSD 3 PLM Yellow 1 st Floor Covebase Mastic - VCB1-02 Rear M/3 50 lf ND 0 G/NF PSD 3 PLM Yellow Bathroom Covebase Mastic - VCB1-03 ND 0 G/NF PSD 3 TEM Yellow Sheetrock SR1-01 Joint Compound - Sheetrock 1 st Floor 12,000 SR1-02 Joint Compound - S/7 Law Offices sf Sheetrock SR1-03 Joint Compound - Page 8 of 14

9 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Sample Cat./# Asbestos Pot. Haz. Test Material Location Qty. % Cond. # Samples Type Dist. Assess. Method Sheetrock SR1-04 Joint Compound Sheetrock SR1-05 Joint Compound - Sheetrock SR1-06 Joint Compound - Sheetrock SR1-07 Joint Compound - Plaster Skim Coat - P2-01 Plaster Base Coat - Gray HVAC Plaster Skim Coat - Chases In P2-02 Lobby s and S/3 700 sf Plaster Base Coat - Select Gray Rooms Plaster Skim Coat - P2-03 Plaster Base Coat - Gray TC1-01 Textured Ceiling - TC1-02 Textured Ceiling - TC1-03 Textured Ceiling - 1 st Floor Law Offices S/5 2,700 sf TC1-04 Textured Ceiling - TC1-05 Textured Ceiling - CT-01 Ceiling Tile /Off- 2 nd and 3 rd CT-02 Ceiling Tile Floor Halls /Off- and Court M/3 2,400 sf CT-03 Ceiling Tile Room /Off- M1-01 Ceiling Tile Track Mastic - Brown ND 0 G/NF PSD 3 PLM M1-02 Ceiling Tile Track 2 nd and 3 rd Mastic - Brown Floor Halls M/3 50 sf ND 0 G/NF PSD 3 PLM Ceiling Tile Track M1-03 ND 0 G/NF PSD 3 TEM Mastic - Brown WT1-01 Wall Texture - 3 rd Floor Jail WT1-02 Wall Texture - S/3 380 sf Bath WT1-03 Wall Texture - I1-01 Boiler Insulation /Off- Chrysotile 50 G/F PSD 3 PLM I1-02 Boiler Insulation Basement /Off- Boiler TSI/3 500 sf I1-03 Boiler Insulation /Off I2-01 Pipe Insulation Wrap - Basement- Gray TSI/3 2,500 lf Pipe Insulation - Feathery Chrysotile 25 G/F PSD 3 PLM Insulation Page 9 of 14

10 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Sample # I2-02 I2-03 I3-01 I3-02 I3-03 I4-01 I4-02 I4-03 I5-01 I5-02 I5-03 I6-01 I6-02 I6-03 I7-01 I7-02 I7-03 I8-01 I8-02 I8-03 I9-01 Material Pipe Insulation Wrap - Gray Pipe Insulation - Pipe Insulation Wrap - Gray Pipe Insulation - Cloth Wrapped Insulation - Tan Cloth Wrapped Insulation - Tan Cloth Wrapped Insulation - Tan Water Tank Insulation - Water Tank Insulation Water Tank Insulation - Cardboard Insulation Brown Cardboard Insulation Brown Cardboard Insulation Brown Furnace Board Insulation - Furnace Board Insulation Furnace Board Insulation - Cloth Wrapped Insulation Tan/Yellow Cloth Wrapped Insulation Tan/Yellow Cloth Wrapped Insulation Tan/Yellow Location Also found throughout other areas to include 1 st floor passage and 2 nd floor rooms Basement Pipe Fiberglass Insulation Cat./# Samples TSI/3 Qty. 50 lf Basement TSI/3 50 sf Basement Old Furnace Basement Old Furnace Basement Pipe Fiberglass Insulation also on 2 nd floor hall above ceiling tile and 1 st floor lobby TSI/3 TSI/3 TSI/3 480 sf 480 sf 500 lf Page 10 of 14 Asbestos Type % Cond. Pot. Dist. Haz. Assess. Test Method Chrysotile 35 G/F PSD 3 PLM Chrysotile 5 G/F PSD 3 PLM Chrysotile 65 G/F PSD 3 PLM Cloth Wrap - Tan Brown Paper - Brown Black Paper - Black Chrysotile 25 G/NF PSD 3 PLM Brown Insulation - Brown Cloth Wrap - Tan Chilled Brown Paper - Brown Water Black Paper - Black TSI/3 600 lf Supply - Brown Insulation - Basement Brown Cloth Wrap - Tan Brown Paper - Brown Black Paper - Black Brown Insulation - Brown HVAC Insulation - 2 nd, 3 rd, and Attic TSI/3 1,200 sf Chrysotile 10 G/F PSD 3 PLM

11 Sample # Material Location Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Cat./# Samples Qty. Asbestos Type % Cond. Pot. Dist. Haz. Assess. Test Method I9-02 HVAC Insulation HVAC Insulation HVAC Insulation - I Tar Wrap - Black Chrysotile 25 G/NF PSD 3 PLM I10-01 Insulation - Brown I10-02 Tar Wrap - Black Attic Pipe TSI/3 60 lf Insulation - Brown Insulation I10-03 Tar Wrap - Black Insulation - Brown RF1-01 Roof Flashing Silver Chrysotile 3 G/NF PSD 3 PLM Roof Flashing Tar - Black ND 0 G/NF PSD 3 PLM RF1-02 Roof Flashing 2 nd Floor Silver Roof M/3 140 sf Roof Flashing Tar - Flashing Black Roof Flashing Silver RF1-03 Roof Flashing Tar Black Shingle /Black ND 0 G/NF PSD 3 PLM RF2-01 Tar - Black ND 0 G/NF PSD 3 PLM Shingle /Black 2dn Floor ND 0 G/NF PSD 3 PLM RF2-02 M/3 140 sf Tar - Black Parapet Wall ND 0 G/NF PSD 3 PLM Shingle /Black ND 0 G/NF PSD 3 TEM RF2-03 Tar - Black ND 0 G/NF PSD 3 TEM R-01 Roof Tar - Black 2 nd ND 0 G/NF PSD 3 PLM Floor R-02 Roof Tar - Black M/3 1,200 sf ND 0 G/NF PSD 3 PLM Roof R-03 Roof Tar - Black ND 0 G/NF PSD 3 TEM Abbreviations and Hazard Assessment Key Category and Sampling # s Miscellaneous (M) = 3 samples required Surfacing (S) = <1,000 sf = 3 samples required; 1,000-5,000 sf = 5 samples; >5,000 sf = 7 samples Thermal System Insulation (TSI) = < 6 sf = 1 sample required; > 6 sf = 3 samples Present Condition F = Friable G = Good (very localized limited damage) NF = Non-friable D = Damaged (Damage of less than 10% distributed and less than 25% localized) SD = Significantly Damaged (Damage equal to or greater than 10% distributed/25% localized) Potential for Future Disturbance LPD = Low potential for disturbance (Contact, vibration, and air erosion all of low concern) PD = Potential for damage (Contact, vibration, or air erosion of moderate concern) PSD = Potential for significant damage (Contact, vibration, or air erosion of high concern) Hazard Assessment Present Condition Versus Potential for Future Disturbance Good Damaged Significantly Damaged = 7 LPD = 1 LPD = 4 PD = 2 PD = 5 PSD = 3 PSD = 6 Page 11 of 14

12 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Test Method PLM = Polarized Light Microscopy TEM = Transmission Electron Microscopy (required by SCDHEC for confirmation of negative results for non-friable organically bound materials) -- = Sample not analyzed due to positive PLM results. Misc. sf = Square Feet lf = Linear Feet ND = EPA, SCDHEC, and OSHA define a material as asbestos containing if an asbestos content greater than 1% is detected. Please understand that quantities are estimated and should not be used for bidding purposes. Field conditions should be verified prior to bidding. 5.0 LEAD-BASED PAINT ASSESSMENT DATA The assessment was performed by identifying paint coated surfaces associated with the structure. chip samples were then collected for each painted surface of the structure s building components, which includes but is not limited to shutters, siding, exterior trim, window trim, window sills, interior and exterior doors, door frames, walls, baseboards, chair rails and floors. The samples collected were approximately 1-4 square inches in size and included all layers of paint, placed inside an appropriate sample container, and labeled accordingly using a unique identification number. A chain of custody was completed for the samples with project specific information and then submitted to EMSL Analytical, Inc. for analysis. The samples collected were analyzed via EPA Method SW B/7000B. The following outlines the paint chip samples collected and analyzed: Sample # Substrate Component Color Location Condition Page 12 of 14 Lead Concentration (mg/cm 2 ) P-01 Plaster Wall Blue Storage Intact 24 P-02 Plaster Wall Tan Basement Poor 1.7 P-03 Wood Trim Green/Gray Basement Poor 0.17 P-04 Plaster Wall Green Basement Poor 1.0 P-05 Brick Wall Red Basement Poor 1.5 P-06 Brick Wall Tan Basement Poor P-07 Plaster Wall Beige/Tan Basement Poor 2.8 P-08 Metal Door Green/Gray Basement Poor 0.60 P-09 Plaster Wall Beige Basement Poor P-10 Wood Window Sill Basement Poor P-11 Plaster Wall 1 st Floor Good P-12 Plaster Wall Black 1 st Floor Good 0.15 *mg/cm 2 = milligrams per cubic centimeter Condition Assessment Key Type of Bldg. Component Exterior components with large surface area Total Area of Deteriorated on Each Component Intact Fair 1 Poor 2 Less than or equal to 10 square feet Entire surface area is intact More than 10 square feet

13 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Interior components with large surface area Interior and exterior components with small surface areas Entire surface area is intact Entire surface area is intact Less than or equal to 2 square feet Less than or equal to 10% of the total surface area of component More than 2 square feet More than 10% of the total surface area or the component Superscript 1 = surfaces in fair condition should be repaired and/or monitored, but are not considered to be lead based paint hazards. Superscript 2 = surfaces in poor condition are considered to be lead based paint hazards as defined by Title X and should be addressed through abatement or interim controls. Composite soil samples were not collected during this inspection. Grass and shrubs covered the perimeter area around the house and most of the yard is covered with grass with the exception of the driveway. No paint flakes were observed on the ground surface around the house. Site location and sample locations are identified as Figures 1 thru 6 of Appendix 1 of this report, photographs are in Appendix 2, and laboratory results are in Appendix 3 and CONCLUSIONS a. Asbestos The EPA and SCDHEC define materials as asbestos containing if an asbestos content >1% is detected in a representative sample. Asbestos >1 % was detected in the following materials sampled and analyzed for the former Florence Post Office located at 201 West Evans Street, in Florence, South Carolina: DM2 HVAC duct mastic in basement I.O. Gallery (approximately 50 sf) DM3 HVAC duct mastic in 2 nd and 3 rd floor halls above ceiling tile (approximately 170 sf) I1 Boiler insulation in basement (approximately 500 sf) I2 Pipe insulation wrap to include elbows in basement and throughout other areas such as 1 st floor passage and 2 nd floor rooms (approximately 2,500 lf). No pipe insulation was observed on the 3 rd floor rooms or above the ceiling tile. I4 Water tank insulation in basement (approximately 50 sf) I5 Cardboard insulation in basement (approximately 480 sf) I6 Furnace board insulation in basement (approximately 480 sf) I8 Chilled water pipe insulation (approximately 600 lf) I9 HVAC insulation 2 nd and 3 rd floor mechanical rooms and the attic (approximately 1,200 sf) I10 Tar wrapped pipe insulation in attic (approximately 60 lf) RF1 Silver painted roof flashing on 2 nd floor roof (approximately 140 sf) No asbestos >1% was detected in the remaining samples collected and analyzed. Per SCDHEC regulations, the asbestos containing materials should be removed by a licensed abatement contractor prior to any destructive activities at the facility. Due to the quantity of regulated ACMs identified, an asbestos abatement plan will be required prior to abatement. Additionally, asbestos air monitoring will be required during abatement activities. Page 13 of 14

14 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 The possibility exists that suspect materials were undetected in inaccessible areas such as areas deemed unsafe to enter, locked rooms, behind exterior veneer, pipe chases, below the wood roof decking, or wall voids. If additional suspect materials not included in this report are discovered during demolition, bulk samples should be collected and analyzed for asbestos content. A copy of this report along with an application for abatement and demolition must be submitted to SCDHEC 10 working days prior to any abatement and demolition activities. Additionally, a copy of this report should be provided to the contractors to assist with compliance with applicable State and Federal regulations. a. Lead-Based OSHA defines paint as lead-based if an amount greater than 1.0 mg/cm 2 is identified in a paint chip sample. The SCDHEC requires the disposal of paint coated items be placed in a Municipal Solid Waste lined landfill. Based on samples collected from the previous inspection and along with the samples collected during this inspection, lead greater than 1.0 mg/cm 2 was identified in the following paint coated surfaces sampled and analyzed: P-01 Blue painted plaster walls P-02 Tan painted plaster walls P-04 Green painted plaster walls P-05 Red painted brick wall in basement P-07 Beige/Tan painted plaster walls Please know that traces of lead was identified in the samples collected and analyzed. Any work and/or disturbance to the painted surfaces within the facility, at a minimum, be done in accordance with federal regulations governing Lead-Safe Work Practices, 24 CFR A copy of this report should be provided to the contractors to assist with compliance with applicable State and Federal regulations. Page 14 of 14

15 APPENDIX 1 Site Location Plan and Sample Location Plan (Figures 1 thru 6)

16 Subject Structure Site Location Plan Former Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/22/17 Source: Google Earth Figure 1

17 Basement I5 (01-03) I6 (01-03) P1-03 DM1 (01-03) P1-02 F1 (01-03) DM2 (01-03) I2 (01-03) I4 (01-03) P-09 P-10 I1 (01-03) I3 (01-03) P-08 P-05 I7 (01-03) P-04 I8 (01-02) I8-03 I9 Identified on HVAC unit P-03 P-06 P-07 F2-03 F2-02 F2-01 P-02 Notes: Basement contains majority of asbestos containing pipe insulation and boiler/tank insulation. These pipes run throughout the basement and in mulitple runs simultaneously. Please see photos for views of these areas. Asbestos Sample Location Plan Former Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/20/2017 Source: N/A Figure 2 LEGEND Sample Location Asbestos Containing Sample Location Lead-Based Chip Sample

18 1st Floor P1-05 I2 was identified in passage (4 runs) VCB1 (01-03) F4 (01-03) P1-04 SR1-03 F3-01 SR1-05 F3-02 F3-03 P-11 SR1-07 P-12 SR1-01 SR1-02 SR1-06 SR1-04 TC1-03 TC1-05 TC1-04 TC1-02 TC1-01 P-01 P1-01 LEGEND Asbestos Sample Location Plan Former Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/20/2017 Source: N/A Figure 3 Sample Location Asbestos Containing Sample Location Lead-Based Chip Sample

19 2nd Floor RF2-03 P1-06 RF2-02 I2 Identified in ceiling of 2nd floor rooms R-01 R-02 R-03 RF1-01 RF1-02 RF1-03 RF2-01 CT1-01 DM3 Identified above ceiling tile in all halls I9 Identified on HVAC unit CT1-03 CT1-02 M1-03 M1-02 M1-01 F5-01F5-02 DM3-03DM3-02 DM3-01 I9 (01-03) F5-03 LEGEND Asbestos Sample Location Plan Former Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/20/2017 Source: N/A Figure 4 Sample Location Asbestos Containing Sample Location Lead-Based Chip Sample

20 3rd Floor WT (01-03) P1-07 P2-01 P2-02 DM3 Identified above ceiling tile in all halls I9 Identified on HVAC unit P2-03 LEGEND Asbestos Sample Location Plan Former Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/20/2017 Source: N/A Figure 5 Sample Location Asbestos Containing Sample Location Lead-Based Chip Sample

21 Attic 01 I9 Identified on HVAC unit I9 Identified on HVAC unit I9 Identified on HVAC unit P1-08 P1-09 I9 Identified on HVAC unit I9 Identified on HVAC unit I9 Identified on HVAC unit I9 Identified on HVAC unit I10 (01-02) I10-03 LEGEND Asbestos Sample Location Plan Florence Post Office Florence, SC Project # Scale: Not to Scale Reviewed By: DS Date: 2/20/2017 Source: N/A Figure 6 Sample Location Asbestos Containing Sample Location Lead-Based Chip Sample

22 APPENDIX 2 Photographs

23 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Front of building 1 st floor left office 1 st floor left storage 1 st floor law offices

24 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, st floor kitchen 1 st floor rear bathroom 1 st floor right rear offices Basement front left office pipe insulation in ceiling (multiple runs)

25 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Basement boiler room showing multiple runs of pipe insulation Boiler showing asbestos containg insulation and multiple runs of pipe insulation Basement mech room showing I9 and multiple runs of pipe insulation Basement P.O. Storage showing multiple runs of pipe insulation to include the chilled water line

26 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Basement showing multiple runs of pipe insulation I.O. Gallery (hidden access) I.O. Gallery (hidden access) 2 nd floor court room

27 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, nd floor roof 2 nd floor HVAC insulation (I9) 2 nd floor hall DM3 identified on HVAC duct above ceiling tile in 2 nd and 3 rd floor halls

28 Limited Asbestos and Lead-Based Inspection Report FORMER FLORENCE POST OFFICE Project Number February 22, 2017 Room in attic showing HVAC insulation (I9) Attic mechanical equipment I10 in attic (asbestos tar on pipe insulation) Another view of I9 in attic

29 APPENDIX 3 Asbestos Laboratory Results

30 February 14, 2017 Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC CLIENT PROJECT: Former Florence Post Office CEI LAB CODE: A Dear Customer: Enclosed are asbestos analysis results for PLM Bulk samples received at our laboratory on February 13, The samples were analyzed for asbestos using polarizing light microscopy (PLM) per the EPA 600 Method. Sample results containing >1% asbestos are considered asbestos-containing materials (ACMs) per EPA regulatory requirements. The detection limit for the EPA 600 Method is <1% asbestos by weight as determined by visual estimation. Thank you for your business and we look forward to continuing good relations. If you have any questions, please feel free to call our office at Kind Regards, Tianbao Bai, Ph.D., CIH Laboratory Director 730 SE Maynard Road Cary, NC

31 ASBESTOS ANALYTICAL REPORT By: Polarized Light Microscopy Prepared for Asbestos Inspections LLC CLIENT PROJECT: Former Florence Post Office CEI LAB CODE: A TEST METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 REPORT DATE: 02/14/17 TOTAL SAMPLES ANALYZED: 67 # SAMPLES >1% ASBESTOS: 11 TEL:

32 Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY PROJECT: Former Florence Post Office CEI LAB CODE: A METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 Client ID Layer Lab ID Color Sample Description P1-01 P1-02 P1-03 P1-04 P1-05 P1-06 P1-07 P1-08 P1-09 DM1-01 DM1-02 DM1-03 ASBESTOS % A Plaster Skim Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat A Tan Duct Mastic A Tan Duct Mastic A Sample Submitted for TEM Analysis DM2-01 A Black Duct Mastic Chrysotile 5% DM2-02 DM2-03 A A Sample Not Analyzed per COC Sample Not Analyzed per COC DM3-01 A Black Duct Mastic/wrap Chrysotile 5% DM3-02 DM3-03 F1-01 F1-02 F1-03 F2-01 A A Sample Not Analyzed per COC Sample Not Analyzed per COC A Brown Flooring A Brown Flooring A Sample Submitted for TEM Analysis A Black Mastic Page 1 of 5

33 Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY PROJECT: Former Florence Post Office CEI LAB CODE: A METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 Client ID Layer Lab ID Color Sample Description ASBESTOS % F2-02 F2-03 F3-01 F3-02 F3-03 F4-01 F4-02 F4-03 F5-01 F5-02 F5-03 VCB1-01 VCB1-02 VCB1-03 SR1-01 SR1-02 A Black Mastic A Sample Submitted for TEM Analysis A A Floor Tile A B Yellow Mastic A C Black Floor Tile A D Yellow Mastic A A Floor Tile A B Yellow Mastic A C Black Floor Tile A D Yellow Mastic A Sample Submitted for TEM Analysis A A Blue Floor Tile A B Pink Floor Tile A C Tan Mastic A A Blue Floor Tile A B Pink Floor Tile A C Tan Mastic A Sample Submitted for TEM Analysis A Brown Flooring A Brown Flooring A Sample Submitted for TEM Analysis A Yellow Covebase Mastic A Yellow Covebase Mastic A Sample Submitted for TEM Analysis Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Sheetrock Page 2 of 5

34 Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY PROJECT: Former Florence Post Office CEI LAB CODE: A METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 Client ID Layer Lab ID Color Sample Description ASBESTOS % SR1-03 SR1-04 SR1-05 SR1-06 SR1-07 P2-01 P2-02 P2-03 TC1-01 TC1-02 TC1-03 TC1-04 TC1-05 CT-01 CT-02 CT-03 M1-01 M1-02 M1-03 WT1-01 WT1-02 Layer 2 A Joint Compound Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Sheetrock Layer 2 A Joint Compound Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat Layer 1 A Plaster Skim Coat Layer 2 A Gray Plaster Base Coat A Textured Ceiling A Textured Ceiling A Textured Ceiling A Textured Ceiling A Textured Ceiling A ,Off-white Ceiling Tile A ,Off-white Ceiling Tile A ,Off-white Ceiling Tile A Brown Ceiling Tile Track Mastic A Brown Ceiling Tile Track Mastic A Sample Submitted for TEM Analysis A Wall Texture A Wall Texture Page 3 of 5

35 Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY PROJECT: Former Florence Post Office CEI LAB CODE: A METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 Client ID Layer Lab ID Color Sample Description ASBESTOS % WT1-03 A Wall Texture I1-01 A ,Off-white Boiler Insulation Chrysotile 50% I1-02 I1-03 I2-01 I2-02 I2-03 I3-01 I3-02 I3-03 A A Sample Not Analyzed per COC Sample Not Analyzed per COC Layer 1 A Gray Pipe Insulation Wrap Layer 2 A Pipe Insulation Chrysotile 25% A A Sample Not Analyzed per COC Sample Not Analyzed per COC A Tan Cloth Wrapped Insulation A Tan Cloth Wrapped Insulation A Tan Cloth Wrapped Insulation I4-01 A Water Tank Insulation Chrysotile 35% I4-02 I4-03 A A Sample Not Analyzed per COC Sample Not Analyzed per COC I5-01 A Brown Cardboard Insulation Chrysotile 5% I5-02 I5-03 A A Sample Not Analyzed per COC Sample Not Analyzed per COC I6-01 A Furnace Board Insulation Chrysotile 65% I6-02 I6-03 I7-01 I7-02 I7-03 I8-01 I8-02 I8-03 A A Sample Not Analyzed per COC Sample Not Analyzed per COC A Tan,Yellow Cloth Wrapped Insulation A Tan,Yellow Cloth Wrapped Insulation A Tan,Yellow Cloth Wrapped Insulation Layer 1 A Tan Cloth Wrap Layer 2 A Brown Brown Paper Layer 3 A Black Black Paper Chrysotile 25% Layer 4 A Brown Brown Insulation A A Sample Not Analyzed per COC Sample Not Analyzed per COC I9-01 A HVAC Insulation Chrysotile 10% I9-02 A Sample Not Analyzed per COC Page 4 of 5

36 Asbestos Report Summary By: POLARIZING LIGHT MICROSCOPY PROJECT: Former Florence Post Office CEI LAB CODE: A METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 Client ID Layer Lab ID Color Sample Description ASBESTOS % I9-03 A Sample Not Analyzed per COC I10-01 Layer 1 A Black Tar Wrap Chrysotile 25% I10-02 I10-03 Layer 2 A Brown Insulation A A Sample Not Analyzed per COC Sample Not Analyzed per COC RF1-01 Layer 1 A Silver Roof Flashing Chrysotile 3% RF1-02 RF1-03 RF2-01 RF2-02 RF2-03 R-01 R-02 R-03 Layer 2 A Black Roof Flashing Tar A A Sample Not Analyzed per COC Sample Not Analyzed per COC Layer 1 A ,Black Shingle Layer 2 A Black Tar Layer 1 A ,Black Shingle Layer 2 A Black Tar A Sample Submitted for TEM Analysis A Black Roof Tar A Black Roof Tar A Sample Submitted for TEM Analysis Page 5 of 5

37 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID P1-01 A Lab Description Plaster Skim Coat Lab Notes: No base coat present. P1-02 Layer 1 A Layer 2 A P1-03 Layer 1 A Layer 2 A P1-04 Layer 1 A Layer 2 A Plaster Skim Coat Plaster Base Coat Plaster Skim Coat Plaster Base Coat Plaster Skim Coat Plaster Base Coat Lab Attributes Gray Gray Gray NON-ASBESTOS COMPONENTS Non- <1% <1% <1% Cellulose Cellulose Cellulose 5% 50% 45% 5% 50% 45% 40% 60% 5% 50% 45% 40% 60% 5% 50% 45% 40% 60% Calc Carb Calc Carb Silicates Calc Carb Silicates Calc Carb Silicates ASBESTOS % Page 1 of 18

38 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % P1-05 Layer 1 A Plaster Skim Coat 5% 50% 45% Calc Carb Layer 2 A Plaster Base Coat Gray 50% 25% 25% Silicates Perlite P1-06 Layer 1 A Plaster Skim Coat 5% 50% 45% Calc Carb Layer 2 A Plaster Base Coat Gray <1% Cellulose 40% 60% Silicates P1-07 Layer 1 A Plaster Skim Coat 5% 50% 45% Calc Carb Layer 2 A Plaster Base Coat Gray <1% Cellulose 40% 60% Silicates P1-08 Layer 1 A Plaster Skim Coat 5% 50% 45% Calc Carb Page 2 of 18

39 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % Layer 2 A Plaster Base Coat Gray <1% Cellulose 40% 60% Silicates P1-09 Layer 1 A Plaster Skim Coat 5% 50% 45% Calc Carb Layer 2 A Plaster Base Coat Gray <1% Cellulose 40% 60% Silicates DM1-01 A Duct Mastic Tan 100% Mastic DM1-02 A Duct Mastic Tan 100% Mastic DM1-03 A Sample Submitted for TEM Analysis DM2-01 A Duct Mastic Black 95% Mastic 5% Chrysotile DM2-02 A Sample Not Analyzed per COC DM2-03 A Sample Not Analyzed per COC Page 3 of 18

40 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % DM3-01 A Duct Mastic/wrap Black 25% Fiberglass 70% Mastic 5% Chrysotile DM3-02 A Sample Not Analyzed per COC DM3-03 A Sample Not Analyzed per COC F1-01 A Flooring Brown 25% Cellulose 75% Vinyl F1-02 A Flooring Brown 25% Cellulose 75% Vinyl F1-03 A Sample Submitted for TEM Analysis F2-01 A Mastic Black 95% 5% Mastic Silicates F2-02 A Mastic Black 95% 5% Mastic Silicates F2-03 A Sample Submitted for TEM Analysis Page 4 of 18

41 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % F3-01 A A Floor Tile 80% 20% Vinyl Calc Carb A B Mastic Yellow 2% Talc 98% Mastic A C Floor Tile Black 80% 20% Vinyl Calc Carb A D Mastic 100% Mastic Yellow F3-02 A A Floor Tile 80% 20% Vinyl Calc Carb A B Mastic Yellow 2% Talc 98% Mastic A C Floor Tile Black 80% 20% Vinyl Calc Carb Page 5 of 18

42 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % A D Mastic 100% Mastic Yellow F3-03 A Sample Submitted for TEM Analysis F4-01 A A Floor Tile Blue 75% 25% Vinyl Calc Carb A B Floor Tile Pink 75% 25% Vinyl Calc Carb A C Mastic 100% Mastic Tan F4-02 A A Floor Tile Blue 75% 25% Vinyl Calc Carb A B Floor Tile Pink 75% 25% Vinyl Calc Carb A C Mastic 100% Mastic Tan Page 6 of 18

43 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % F4-03 A Sample Submitted for TEM Analysis F5-01 A Flooring Brown 20% Cellulose 80% Vinyl F5-02 A Flooring Brown 20% Cellulose 80% Vinyl F5-03 A Sample Submitted for TEM Analysis VCB1-01 A Covebase Mastic Yellow 100% <1% Mastic VCB1-02 A Covebase Mastic Yellow 100% <1% Mastic VCB1-03 A Sample Submitted for TEM Analysis SR1-01 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb Page 7 of 18

44 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % SR1-02 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb SR1-03 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb SR1-04 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb SR1-05 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Page 8 of 18

45 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % Layer 2 A Joint Compound 5% 40% 55% Calc Carb SR1-06 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb SR1-07 Layer 1 A Sheetrock 10% Cellulose 90% Gypsum Layer 2 A Joint Compound 5% 40% 55% Calc Carb P2-01 Layer 1 A Plaster Skim Coat 5% 45% 50% Calc Carb Layer 2 A Plaster Base Coat Gray 50% 25% 25% Silicates Perlite Page 9 of 18

46 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % P2-02 Layer 1 A Plaster Skim Coat 5% 45% 50% Calc Carb Layer 2 A Plaster Base Coat Gray 50% 25% 25% Silicates Perlite P2-03 Layer 1 A Plaster Skim Coat 5% 45% 50% Calc Carb Layer 2 A Plaster Base Coat Gray 50% 25% 25% Silicates Perlite TC1-01 A Textured Ceiling 10% 75% 15% Vermiculite TC1-02 A Textured Ceiling 10% 75% 15% Vermiculite TC1-03 A Textured Ceiling 10% 75% 15% Vermiculite Page 10 of 18

47 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % TC1-04 A Textured Ceiling 10% 75% 15% Vermiculite TC1-05 A Textured Ceiling 10% 75% 15% Vermiculite CT-01 A Ceiling Tile,Off-white 35% 35% Cellulose Fiberglass 5% 25% Perlite Loosely CT-02 A Ceiling Tile,Off-white 35% 35% Cellulose Fiberglass 5% 25% Perlite Loosely CT-03 A Ceiling Tile,Off-white 35% 35% Cellulose Fiberglass 5% 25% Perlite Loosely M1-01 A Ceiling Tile Track Mastic Brown 2% Talc 98% Mastic M1-02 A Ceiling Tile Track Mastic Brown 2% Talc 98% Mastic M1-03 A Sample Submitted for TEM Analysis Page 11 of 18

48 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % WT1-01 A Wall Texture 20% 45% 35% Silicates WT1-02 A Wall Texture 20% 45% 35% Silicates WT1-03 A Wall Texture 20% 45% 35% Silicates I1-01 A Boiler Insulation,Off-white Loosely 5% 45% 50% Chrysotile I1-02 A Sample Not Analyzed per COC I1-03 A Sample Not Analyzed per COC I2-01 Layer 1 A Pipe Insulation Wrap Gray 85% Cellulose 5% 10% Layer 2 A Pipe Insulation Loosely 60% 15% Calc Carb 25% Chrysotile I2-02 A Sample Not Analyzed per COC Page 12 of 18

49 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % I2-03 A Sample Not Analyzed per COC I3-01 A Cloth Wrapped Insulation Tan 10% 75% Cellulose Fiberglass 5% 10% Loosely I3-02 A Cloth Wrapped Insulation Tan 10% 75% Cellulose Fiberglass 5% 10% Loosely I3-03 A Cloth Wrapped Insulation Tan 10% 75% Cellulose Fiberglass 5% 10% Loosely I4-01 A Water Tank Insulation 5% 60% 35% Chrysotile Loosely I4-02 A Sample Not Analyzed per COC I4-03 A Sample Not Analyzed per COC I5-01 A Cardboard Insulation Brown 85% Cellulose 10% 5% Chrysotile Loosely I5-02 A Sample Not Analyzed per COC I5-03 A Sample Not Analyzed per COC Page 13 of 18

50 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % I6-01 A Furnace Board Insulation Loosely 35% 65% Chrysotile I6-02 A Sample Not Analyzed per COC I6-03 A Sample Not Analyzed per COC I7-01 A Cloth Wrapped Insulation Tan,Yellow Loose 80% 15% Cellulose Fiberglass 5% I7-02 A Cloth Wrapped Insulation Tan,Yellow Loose 80% 15% Cellulose Fiberglass 5% I7-03 A Cloth Wrapped Insulation Tan,Yellow Loose 80% 15% Cellulose Fiberglass 5% I8-01 Layer 1 A Cloth Wrap Tan Loose 95% Cellulose 5% Layer 2 A Brown Paper Brown Loosely 100% Cellulose Page 14 of 18

51 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % Layer 3 A Black Paper Black Loosely 35% Cellulose 40% Tar 25% Chrysotile Layer 4 A Brown Insulation Brown Loosely 90% Fiberglass 10% I8-02 A Sample Not Analyzed per COC I8-03 A Sample Not Analyzed per COC I9-01 A HVAC Insulation Loosely 15% Fiberglass 75% 10% Chrysotile I9-02 A Sample Not Analyzed per COC I9-03 A Sample Not Analyzed per COC I10-01 Layer 1 A Tar Wrap Black Loosely 35% Cellulose 40% Tar 25% Chrysotile Layer 2 A Insulation Brown Loosely 90% Fiberglass 10% I10-02 A Sample Not Analyzed per COC Page 15 of 18

52 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % I10-03 A Sample Not Analyzed per COC RF1-01 Layer 1 A Roof Flashing Silver 97% 3% Chrysotile Layer 2 A Roof Flashing Tar Homogeneous Black 100% Tar RF1-02 A Sample Not Analyzed per COC RF1-03 A Sample Not Analyzed per COC RF2-01 Layer 1 A Shingle,Black 35% Cellulose 45% 20% Tar Silicates Layer 2 A Tar Black 30% Cellulose 70% Tar RF2-02 Layer 1 A Shingle,Black 35% Cellulose 45% 20% Tar Silicates Layer 2 A Tar Black 30% Cellulose 70% Tar Page 16 of 18

53 ASBESTOS BULK ANALYSIS By: POLARIZING LIGHT MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office ASBESTOS BULK PLM, EPA 600 METHOD Client ID Lab ID Lab Description Lab Attributes NON-ASBESTOS COMPONENTS Non- ASBESTOS % RF2-03 A Sample Submitted for TEM Analysis R-01 A Roof Tar Black 75% 25% Tar Gravel R-02 A Roof Tar Black 75% 25% Tar Gravel R-03 A Sample Submitted for TEM Analysis Page 17 of 18

54 LEGEND: Non-Anth = Non-Asbestiform Anthophyllite Non-Trem = Non-Asbestiform Tremolite Calc Carb = Calcium Carbonate METHOD: EPA 600 / R93 / 116 and EPA 600 / M4-82 / 020 REPORTING LIMIT: <1% by visual estimation REGULATORY LIMIT: >1% by weight Due to the limitations of the EPA 600 method, nonfriable organically bound materials (NOBs) such as vinyl floor tiles can be difficult to analyze via polarized light microscopy (PLM). EPA recommends that all NOBs analyzed by PLM, and found not to contain asbestos, be further analyzed by Transmission Electron Microscopy (TEM). Please note that PLM analysis of dust and soil samples for asbestos is not covered under NVLAP accreditation. Estimated measurement of uncertainty is available on request. This report relates only to the samples tested or analyzed and may not be reproduced, except in full, without written approval by CEI Labs, Inc. CEI Labs makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. Interpretation of the analytical results is the sole responsibility of the client. Samples were received in acceptable condition unless otherwise noted. This report may not be used by the client to claim product endorsement by NVLAP or any other agency of the U.S. Government. ANALYST: Greg Ruff APPROVED BY: Tianbao Bai, Ph.D., CIH Laboratory Director Page 18 of 18

55

56

57

58 February 17, 2017 Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC CLIENT PROJECT: Former Florence Post Office CEI LAB CODE: T Dear Customer: Enclosed are asbestos analysis results for TEM bulk samples received at our laboratory on February 14, The samples were analyzed for asbestos using transmission electron microscopy (TEM) per Chatfield Method. Sample results containing > 1% asbestos are considered asbestos-containing materials (ACMs) per the EPA regulatory requirements. The detection limit for the TEM Chatfield method is <1% depending on the processed weight and constituents of the sample. Thank you for your business and we look forward to continuing good relations. If you have any questions, please feel free to call our office at Kind Regards, Tianbao Bai, Ph.D., CIH Laboratory Director 730 SE Maynard Road Cary, NC

59 ASBESTOS ANALYTICAL REPORT By: Transmission Electron Microscopy Prepared for Asbestos Inspections LLC CLIENT PROJECT: Former Florence Post Office CEI LAB CODE: T TEST METHOD: Bulk Chatfield EPA 600 / R93 / 116 REPORT DATE: 02/17/17 TEL:

60 ASBESTOS BULK ANALYSIS By: TRANSMISSION ELECTRON MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office TEM BULK CHATFIELD / EPA 600 / R93 / 116 Client ID Lab ID Material Description Sample Weight (g) Organic Material % Acid Soluble Material % Acid Insoluble Material % Asbestos % DM1-03 Tan Duct Mastic None T58643 Detected F1-03 Brown Flooring None T58644 Detected F2-03 Black Mastic None T58645 Detected F3-03 Floor Tile None T58646 Detected F3-03 Yellow Mastic None T58647 Detected F3-03 Black Floor Tile None T58648 Detected F3-03 Yellow Mastic None T58649 Detected F4-03 Blue Floor Tile None T58650 Detected F4-03 Pink Floor Tile None T58651 Detected F4-03 Tan Mastic None T58652 Detected F5-03 Brown Flooring None T58653 Detected VCB1-03 Yellow Covebase Mastic None T58654 Detected Page 1 of 3

61 ASBESTOS BULK ANALYSIS By: TRANSMISSION ELECTRON MICROSCOPY Client: Asbestos Inspections LLC 4686 Peedee Hwy Conway, SC Project: Former Florence Post Office TEM BULK CHATFIELD / EPA 600 / R93 / 116 Client ID Lab ID Material Description M1-03 Brown Ceiling Tile Track T58655 Mastic Sample Weight (g) Organic Material % Acid Soluble Material % Acid Insoluble Material % Asbestos % None Detected RF2-03, Black Shingle None T58656 Detected RF2-03 Black Tar None T58657 Detected R-03 Black Roof Tar None T58658 Detected Page 2 of 3

62 LEGEND: None METHOD: CHATFIELD & EPA/600/R-93/116 LIMIT OF DETECTION: Varies with the weight and constituents of the sample (<1%) REGULATORY LIMIT: >1% by weight This report relates only to the samples tested or analyzed and may not be reproduced, except in full, without written approval by CEI Labs, Inc. CEI Labs makes no warranty representation regarding the accuracy of client submitted information in preparing and presenting analytical results. Interpretation of the analytical results is the sole responsibility of the client. Estimated measurement of uncertainty is available on request. Samples were received in acceptable condition unless otherwise noted. ANALYST: Jennifer Turner APPROVED BY: Tianbao Bai, Ph.D., CIH Laboratory Director Page 3 of 3

63

64

65

66 APPENDIX 4 Lead-Based Laboratory Results

67 EMSL Analytical, Inc. 376 Crompton Street, Charlotte, NC Phone/Fax: (704) / (704) charlottelab@emsl.com EMSL Order: CustomerID: CustomerPO: ProjectID: AISC42 Attn: Dawn Schoolcraft Asbestos Inspections, LLC 4686 Pee Dee Hwy. Conway, SC Phone: (843) Fax: Received: 02/15/17 10:15 AM Collected: 2/10/2017 Project: Former Florence Post Office Test Report: Lead in Chips by Flame AAS (SW B/7000B)* Lead Client Sample Description Lab ID Collected Analyzed Area Samp Wt Concentration P /10/2017 2/16/ cm² g 24 mg/cm² Site: Blue Plaster Wall P /10/2017 2/16/ cm² g 1.7 mg/cm² Site: Tan Plaster Wall P /10/2017 2/16/ cm² g 0.17 mg/cm² Site: Wood Trim Green/ Gray P /10/2017 2/16/ cm² g 1.0 mg/cm² Site: Green Plaster Wall P /10/2017 2/16/ cm² g 1.5 mg/cm² Site: Red Brick P /10/2017 2/16/ cm² g mg/cm² Site: Tan Brick P /10/2017 2/16/ cm² g 2.8 mg/cm² Site: Beige Plaster Wall P /10/2017 2/16/ cm² g 0.60 mg/cm² Site: Green/ Gray Metal Door P /10/2017 2/16/ cm² g mg/cm² Site: Beige Plaster Wall P /10/2017 2/16/ cm² g mg/cm² Site: Wood Window Sill P /10/2017 2/16/ cm² g mg/cm² Site: Plaster Wall P /10/2017 2/16/ cm² g 0.15 mg/cm² Site: Black Plaster Wall Kyle Collins, Technical Manager or other approved signatory *Analysis following Lead in by EMSL SOP/Determination of Environmental Lead by FLAA. Reporting limit is % wt based on the minimum sample weight per our SOP. Unless noted, results in this report are not blank corrected. This report relates only to the samples reported above and may not be reproduced, except in full, without written approval by EMSL. EMSL bears no responsibility for sample collection activities. Samples received in good condition unless otherwise noted. "<" (less than) result signifies that the analyte was not detected at or above the reporting limit. Measurement of uncertainty is available upon request. The QC data associated with the sample results included in this report meet the recovery and precision requirements unless specifically indicated otherwise. Definitions of modifications are available upon request. Samples analyzed by EMSL Analytical, Inc. Charlotte, NC AIHA-LAP, LLC - ELLAP Initial report from 02/16/ :38:56 Test Report ChmSnglePrm/nQC Printed: 2/16/2017 2:38:56 PM Page 1 of 1

68 OrderID: Page 1 Of 2

69 OrderID: Page 2 Of 2

Assessment Completed by: Asbestos Inspections, LLC 4686 Pee Dee Highway Conway, South Carolina (843)

Assessment Completed by: Asbestos Inspections, LLC 4686 Pee Dee Highway Conway, South Carolina (843) ASBESTOS INSPECTION REPORT 1814 PRINCE STREET 2-STORY Georgetown, South Carolina Asbestos Inspections, LLC Project # 2017-48 Performed in general accordance with SCDHEC regulation 61-86.1 along with OSHA

More information

November 12, Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California

November 12, Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California November 12, 2014 Mr. Derek Sandgren Helm Properties 1520 Butte House Road, Suite 400 Yuba City, California 95993-2240 RE: Pre-Renovation Asbestos Survey Report 5862 Rupert Avenue, Marysville, California

More information

ASBESTOS SURVEY. Old Detective s Building Wadesboro, NC INSPECTED &PREPARED BY:

ASBESTOS SURVEY. Old Detective s Building Wadesboro, NC INSPECTED &PREPARED BY: ASBESTOS SURVEY Old Detective s Building Wadesboro, NC PREPARED FOR: Alex Sewell Town Manager Town of Wadesboro 124 E. Wade Street Wadesboro, NC Date of Inspection September 28, 2016 Date of Report October

More information

Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624

Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624 Asbestos & Lead Based Paint Assessment City of Anderson 225 Caughlin Avenue Anderson, South Carolina 29624 Prepared for: City of Anderson Community Development Department 601 South Main Street Anderson,

More information

Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624

Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624 Asbestos & Lead Based Paint Assessment City of Anderson 220 Wardlaw Street Anderson, South Carolina 29624 Prepared for: City of Anderson Community Development Department 601 South Main Street Anderson,

More information

ASBESTOS INSPECTION REPORT Completed in accordance with 40 CFR, and (a)(4)

ASBESTOS INSPECTION REPORT Completed in accordance with 40 CFR, and (a)(4) ASBESTOS INSPECTION REPORT Completed in accordance with 40 CFR, 763.86 and 763.85(a)(4) Assessment Completed for Clint Moore, ASLA Planning, Research and Development City of Florence 324 West Evans Street

More information

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR INSPECTORS. For

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR INSPECTORS. For ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR CITY OF ROCK HILL 150 Johnston Street Rock Hill, SC 29731 (803) 448-3351 LOCATION Vacant Building 302 Sidney Street Rock Hill, South Carolina INSPECTION

More information

Prepared for: Infrastructure Consulting Engineers, PLLC Turnbull Avenue North Charleston, South Carolina 29405

Prepared for: Infrastructure Consulting Engineers, PLLC Turnbull Avenue North Charleston, South Carolina 29405 ASBESTOS & LEAD-BASED PAINT ASSESSMENT REPORT I-85 Widening MM80-96 SC 18 BRIDGE OVER I-85 STRUCTURE NO. 1140001800400 GAFFNEY, SOUTH CAROLINA S&ME Project No. 1426-14-161 Prepared for: Infrastructure

More information

Transmitted via electronic mail to

Transmitted via electronic mail to October 1, 2016 Alex Sewell Town Manager Town of Wadesboro 124 E. Wade Street Wadesboro, NC Transmitted via electronic mail to wadesboromanager@windstream.net Re: 125 S. Washington Street Asbestos Sampling

More information

AHERA/NESHAP ASBESTOS INSPECTION REPORT

AHERA/NESHAP ASBESTOS INSPECTION REPORT AHERA/NESHAP ASBESTOS INSPECTION REPORT CLIENT: Julie M. Wilkie City of Greenwood Assistant City Manager 520 Monument St., PO Box 40 Greenwood, SC 29648 (864) 942-8411 LOCATION: 118 Singleton Ct Greenwood,

More information

Limited Asbestos Demolition Survey

Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Limited Asbestos Demolition Survey Former Fire Station Facility 25 to 45 S. Orlando Avenue Cocoa Beach, Florida Client: City of Cocoa Beach Public Works Department 1600

More information

Asbestos Inspection Cover Letter

Asbestos Inspection Cover Letter Asbestos Inspection Cover Letter Date Issued: January 27, 2016 Site Name/Location Residential Structure 4 Cauthen Street Rock Hill, South Carolina Asbestos Inspection Performed For Hank Williams Right

More information

Asbestos Survey & Lead-Based Paint Inspection/Risk Assessment Report

Asbestos Survey & Lead-Based Paint Inspection/Risk Assessment Report Asbestos Survey & Lead-Based Paint Inspection/Risk Assessment Report Fourplex 861 and 863 Burr Street, St. Paul, MN 55130 Property BB Housing Associates (651) 260-5528 Property Owner & Phone Number Submitted

More information

July 13, 2011 TTL Project No NESHAP Asbestos and Limited Hazardous Materials Survey Report 500 North Congress Street Ypsilanti, Michigan

July 13, 2011 TTL Project No NESHAP Asbestos and Limited Hazardous Materials Survey Report 500 North Congress Street Ypsilanti, Michigan July 13, 2011 TTL Project No. 7615.02 Ms. Paula Boase Downriver Community Conference Brownfield Consortium 15100 Northline Road Southgate, Michigan 48195 Dear Ms. Boase: NESHAP Asbestos and Limited Hazardous

More information

ASBESTOS INSPECTION REPORT

ASBESTOS INSPECTION REPORT ASBESTOS INSPECTION REPORT FOR SPARTANBURG COUNTY P.O. Box 5666 Spartanburg, South Carolina 29304 LOCATION 904 Beverly Drive Spartanburg, South Carolina INSPECTION DATE: April 5, 2017 REPORT DATE: April

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No

Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No Asbestos & Lead-Based Paint Survey Report Fort Gordon Gate 1 AAFES Station Augusta, Georgia S&ME Project No. 1419-15-020 Prepared for: Marshall Waters Woody Associates 1736 E. Sunshine Street, #311 Springfield,

More information

Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina

Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina Asbestos Containing Materials Assessment 631 Fulton Avenue Spartanburg, South Carolina Prepared for: Northside Development Group 410 Magnolia Street Spartanburg, South Carolina Prepared by: Apex Environmental

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Asbestos Survey Report

Asbestos Survey Report Asbestos Survey Report Downtown Duluth Old City Hall Block Buildings for renovation 3087 Main Street, 3097 Main Street, New Dawn Theater, 3530 W. Lawrenceville Street, Old City Hall/Church Duluth, Georgia

More information

S (Blacksburg Hwy) Bridge over I-85 (Exit 100) Cherokee County, South Carolina Asbestos and Lead-Based Paint Survey Report - Revised

S (Blacksburg Hwy) Bridge over I-85 (Exit 100) Cherokee County, South Carolina Asbestos and Lead-Based Paint Survey Report - Revised S-11-83 (Blacksburg Hwy) Bridge over I-85 (Exit 100) Cherokee County, South Carolina Asbestos and Lead-Based Paint Survey Report - Revised ARM Project # 16-314-15 April 17, 2017 Prepared For: HDR-ICA 1122

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2207

More information

ASBESTOS-CONTAINING MATERIALS SURVEY AND LEAD-BASED PAINT SURVEY OLD CITY HALL 229 WALNUT STREET GREEN COVE SPRINGS, CLAY COUNTY, FLORIDA

ASBESTOS-CONTAINING MATERIALS SURVEY AND LEAD-BASED PAINT SURVEY OLD CITY HALL 229 WALNUT STREET GREEN COVE SPRINGS, CLAY COUNTY, FLORIDA ASBESTOS-CONTAINING MATERIALS SURVEY AND LEAD-BASED PAINT SURVEY OLD CITY HALL 229 WALNUT STREET GREEN COVE SPRINGS, CLAY COUNTY, FLORIDA PREPARED FOR: Mr. Steve Thomas Field Supervisor Public Works 900

More information

PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278

PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278 PIER 26 and 28 BULKHEAD LIMITED ASBESTOS and LEAD SURVEY NTE Project No.: NT-3278 PREPARED FOR: Mr. Roberto Aguirre City of San Francisco DPW, SAR, BCM 1680 Mission Street San Francisco, California PREPARED

More information

HAZARDOUS MATERIAL INSPECTION

HAZARDOUS MATERIAL INSPECTION HAZARDOUS MATERIAL INSPECTION Former School Building 16 Dewey Ave. Sandwich, MA 02563 Prepared For: Town of Sandwich 130 Main Street Sandwich, MA 02563 Attn.: Ted Hamilton Facilities Director April 20,

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

PRE-DEMOLITION ASBESTOS INSPECTION REPORT FOR VACANT RESIDENCE 326 NE 7 TH TERRACE OCALA, FLORIDA. Prepared for

PRE-DEMOLITION ASBESTOS INSPECTION REPORT FOR VACANT RESIDENCE 326 NE 7 TH TERRACE OCALA, FLORIDA. Prepared for ENVIRONMENTAL SERVICES, LLC PRE-DEMOLITION ASBESTOS INSPECTION REPORT FOR VACANT RESIDENCE 326 NE 7 TH TERRACE OCALA, FLORIDA Prepared for CITY OF OCALA REVITILIZATION STRATEGIES-CODE ENFORCEMENT DIVISION

More information

Asbestos/Lead Paint Survey

Asbestos/Lead Paint Survey Asbestos/ Survey At: Camp Lejeune Bldg. 500 Repair Indoor Physical Fitness Center Prepared for: The Walker Group Architecture Inc. PO Box 541 New Bern, NC 28563 PEI Project No.: Walker Group Project No.:

More information

LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT. for

LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT. for LIMITED POTENTIALLY HAZARDOUS MATERIAL BUILDING INSPECTION REPORT AND ASBESTOS BUILDING INSPECTION REPORT for Michigan State University Physical Plant Division Engineering and Architectural Services Department

More information

Asbestos/Lead Paint Survey

Asbestos/Lead Paint Survey Asbestos/ Survey At: Camp Lejeune Bldg 1810 Repair and Reconfigure Warehouse Prepared for: The Walker Group Architecture Inc. PO Box 541 New Bern, NC 28563 PEI Project No.: Walker Group Project No.: 5120-17-0002-2AL

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

ASBESTOS ASSESSMENT Curtis House Memorial University of Newfoundland St. John s, NL

ASBESTOS ASSESSMENT Curtis House Memorial University of Newfoundland St. John s, NL Project #: 13916 ASBESTOS ASSESSMENT Curtis House Memorial University of Newfoundland St. John s, NL Prepared for: Sheila Miller Director, Department of Health and Safety Memorial University of Newfoundland

More information

Learn Charter School Excel Campus

Learn Charter School Excel Campus ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2270

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT. for. Barton Malow/Clark MSU Spartan Stadium 58 Shaw Lane East Lansing, Michigan

POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT. for. Barton Malow/Clark MSU Spartan Stadium 58 Shaw Lane East Lansing, Michigan POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT for Barton Malow/Clark MSU Spartan Stadium 58 Shaw Lane East Lansing, Michigan 48824-1215 at Michigan State University I.M. West Building East

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-0027

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-381X

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

ASBESTOS AND LEAD PAINT BUILDING MATERIALS SURVEY FOR: COUGHLAN COLLEGE MEMORIAL UNIVERSITY OF NEWFOUNDLAND

ASBESTOS AND LEAD PAINT BUILDING MATERIALS SURVEY FOR: COUGHLAN COLLEGE MEMORIAL UNIVERSITY OF NEWFOUNDLAND ASBESTOS AND LEAD PAINT BUILDING MATERIALS SURVEY FOR: COUGHLAN COLLEGE MEMORIAL UNIVERSITY OF NEWFOUNDLAND Prepared for: Memorial University of Newfoundland St. John s, NL Pinchin LeBlanc Environmental

More information

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION

NARRATIVE REPORT 1.0 BUILDING INFORMATION 2.0 ASBESTOS SURVEY INFORMATION NARRATIVE REPORT 1.0 BUILDING INFORMATION Bentson Bunker Fieldhouse was originally constructed in 1931; the building has had several renovations, notably, a 1976-1980 multi-phase renovation throughout

More information

POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT. for. SSOE, Inc Wilshire Drive Suite 260 Troy, Michigan 48084

POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT. for. SSOE, Inc Wilshire Drive Suite 260 Troy, Michigan 48084 POTENTIALLY HAZARDOUS MATERIALS BUILDING INSPECTION REPORT for SSOE, Inc. 1050 Wilshire Drive Suite 260 Troy, Michigan 48084 at Michigan State University Physics Astronomy Building (Now Psychology) East

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2059

More information

Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall

Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall July 3, 2007 REPORT: Full Building Survey TO: Tim Nelson, Facilities Management's Asbestos Coordinator, 400 Donhowe Building Dan Allen, Associate Director, Recreation Sports, 108 Cooke Hall FROM: Bryan

More information

Asbestos-Containing Material and Hazardous Material Survey Summary Report

Asbestos-Containing Material and Hazardous Material Survey Summary Report Asbestos-Containing Material and Hazardous Material Survey Summary Report Site: Haas Park Fieldhouse PS1757 2404 North Washtenaw Street Chicago, Illinois 60647 Survey Date: January 15, 2010 PBCC Project

More information

Residential Building 4173 Clover Avenue Vadnais Heights, Minnesota. Prepared for. Ramsey County. Project B April 9, 2018

Residential Building 4173 Clover Avenue Vadnais Heights, Minnesota. Prepared for. Ramsey County. Project B April 9, 2018 Pre-Renovation Hazardous Building Materials Inspection Report Residential Building 4173 Clover Avenue Vadnais Heights, Minnesota Prepared for Ramsey County Project B1801954 April 9, 2018 Braun Intertec

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-2059

More information

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22

Asbestos Consulting Radon Measurements Lead Assessments Indoor Air Quality Testing Mold Investigations. Project Number: Page 1 of 22 Page 1 of 22 Asbestos Survey Project Summary Pursuant to your request; Environmental, Inc., has performed an Asbestos Building Survey on 8/13/2014 and limited to the above referenced location. The Interior/Exterior/Roof

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Hazardous Building Material Survey of the Former Willamette Industries Mill Site in Sweet Home, Oregon

Hazardous Building Material Survey of the Former Willamette Industries Mill Site in Sweet Home, Oregon A SERVICE-DISABLED VETERAN-OWNED SMALL BUSINESS Environmental Remediation Asbestos/Lead/Mold/PCBs/Heat & Moisture Detection/Dry Ice Blasting/Demolition/Radon A COMMITMENT TO EXCELLENCE 23525 Hwy. 99 E.

More information

Report of. Asbestos Survey

Report of. Asbestos Survey Report of Asbestos Survey of Curtis Block and Marlowe Buildings 14501, 14505, 14509, 14511 & 14515 Detroit Avenue and 1412 Marlowe Avenue Lakewood, Ohio 44107 Prepared for City of Lakewood 12650 Detroit

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

Residential Building 718 Orange Avenue East St. Paul, Minnesota. Prepared for. Ramsey County. Project B March 22, 2018

Residential Building 718 Orange Avenue East St. Paul, Minnesota. Prepared for. Ramsey County. Project B March 22, 2018 Pre-Renovation Hazardous Building Materials Inspection Report Residential Building 718 Orange Avenue East St. Paul, Minnesota Prepared for Ramsey County Project B1801954 March 22, 2018 Braun Intertec Corporation

More information

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR

ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR ASBESTOS INSPECTION AND LEAD TESTING REPORT FOR SPARTANBURG COUNTY Community Development Department 366 North Church Street Spartanburg, South Carolina 29303 LOCATION 281 Old Howard Gap Road Spartanburg,

More information

April 12, 2011 (revised July 19, 2011) Project Number

April 12, 2011 (revised July 19, 2011) Project Number Environmental Consultants 1360 Truxtun Avenue 843 746-8525 and Contractors Suite 100 FAX 843 746-8865 North Charleston, SC 29405 www.scsengineers.com April 12, 2011 (revised July 19, 2011) Project Number

More information

Asbestos Containing Building Material Survey

Asbestos Containing Building Material Survey Former 55 th Street South Trust Bank - ACBM Survey Asbestos Containing Building Material Survey Former South Trust Bank Property 9 55 th Street South Birmingham, AL Submitted to: Kelleigh Gamble Housing

More information

ASBESTOS BUILDING INSPECTION

ASBESTOS BUILDING INSPECTION ASBESTOS BUILDING INSPECTION LOCATION: BURT HALL 2651 SW ORCHARD AVENUE CORVALLIS, OREGON 97331 NOVEMBER 28, 2008 FORENSIC ANALYTICAL PROJECT NO. PJ6263 PREPARED FOR: OREGON STATE UNIVERSITY 127 OAK CREEK

More information

ADDENDUM # 1 To: File IFB for: 24 Gus Garcia Demolition and Reconstruction

ADDENDUM # 1 To: File IFB for: 24 Gus Garcia Demolition and Reconstruction 818 S. FLORES ST. SAN ANTONIO, TEXAS 78204 www.saha.org Procurement Department ADDENDUM # 1 To: File 1601-909-62-4465 - IFB for: 24 Gus Garcia Demolition and Reconstruction Please note the following change:

More information

HERRON Enterprises USA, Inc.

HERRON Enterprises USA, Inc. Phone (303) 763 9639 To: City of Montrose / Mr. Mark Armstrong HERRON Project No.: 1120145 Job No.: Verbal Location: Multiple Buildings, 950 and 970 Chipeta Rd., Montrose, CO 81403 Dates of Service: November

More information

Dale Livingston, Asbestos Group, Environmental Health and Safety, 153 U-Tech Building, 2331 University Avenue S.E., Minneapolis, MN 55414

Dale Livingston, Asbestos Group, Environmental Health and Safety, 153 U-Tech Building, 2331 University Avenue S.E., Minneapolis, MN 55414 July 5, 2007 REPORT: Full Building Survey TO: Linda McCracken-Hunt, Project Development, 400 Shops Building Fay Thompson, Department of Environmental Health and Safety, Director Tim Nelson, Facilities

More information

1. Reference specification section C and replace with the following:

1. Reference specification section C and replace with the following: University of South Carolina Russell House Leadership and Service Center Renovation Columbia, SC Architect s Project No. 14.150.00 Addendum No. 1 Quackenbush Architects + Planners 1217 Hampton Street Columbia,

More information

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY:

PROJECT NO REPORT TO CITY OF STRATFORD ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: PROJECT NO. 1197 REPORT TO CITY OF STRATFORD ON ASBESTOS CONTAINING MATERIALS SURVEY ROW HOUSES STRATFORD, ONTARIO CONDUCTED BY: 1099 KINGSTON ROAD, SUITE 260 PICKERING, ONTARIO L1V 1B5 Tel: (416) 410-4333

More information

SOUND ENVIRONMENTAL SOLUTIONS, Inc.

SOUND ENVIRONMENTAL SOLUTIONS, Inc. SOU ENVIRONMENTAL SOLUTIONS, Inc. Indoor Air Quality Industrial Hygiene Safety Training Environmental Compliance October 13, 2011 Mr. John Kaniss Construction Manager Pacific Lutheran University Tacoma,

More information

Crothers Environmental Group, LLC

Crothers Environmental Group, LLC , LLC Morrisville, Vermont 05661 Phone 802-888-1936 info@crothersiaq.com June 26, 2009 Mr. Joe Aja, Project Engineer State of Vermont - Department of Buildings & General Services 5 Perry Street, Suite

More information

ASBESTOS ASSESSMENT Cartier Court Memorial University of Newfoundland St. John s, NL

ASBESTOS ASSESSMENT Cartier Court Memorial University of Newfoundland St. John s, NL Project #: 13916 ASBESTOS ASSESSMENT Cartier Court Memorial University of Newfoundland St. John s, NL Prepared for: Sheila Miller Director, Department of Health and Safety Memorial University of Newfoundland

More information

If the address on this form is different than the address of the building, submit a written explanation.

If the address on this form is different than the address of the building, submit a written explanation. ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: CHICAGO SCHOOL DIST 299 SCHOOL ID NUMBER: 14-016-2990-3013

More information

Pre-Renovation Asbestos Survey

Pre-Renovation Asbestos Survey Pre-Renovation Asbestos Survey L640 Level 2 Remodel College Complex Los Medanos College Pittsburg, California November 23, 2016 Terracon Project No. R1167D98 Prepared for: Contra Costa Community College

More information

AFFORDABLE ABATEMENT AND INSPECTIONS, LLC ASBESTOS CONTAINING MATERIAL REPORT

AFFORDABLE ABATEMENT AND INSPECTIONS, LLC ASBESTOS CONTAINING MATERIAL REPORT AFFORDABLE ABATEMENT AND INSPECTIONS, LLC ASBESTOS CONTAINING MATERIAL REPORT 16175 Woodingham DETROIT, MI 48215 PREPARED FOR: Detroit Land Bank Authority 65 Cadillac Square Suite 3200 Detroit, MI 48226

More information

RESULTS OF AN ASBESTOS and LEAD PAINT IDENTIFICATION SURVEY. Prepared For: Town of Bethlehem 2155 Main Street Bethlehem, New Hampshire 03574

RESULTS OF AN ASBESTOS and LEAD PAINT IDENTIFICATION SURVEY. Prepared For: Town of Bethlehem 2155 Main Street Bethlehem, New Hampshire 03574 RESULTS OF AN ASBESTOS and LEAD PAINT IDENTIFICATION SURVEY Prepared For: Town of Bethlehem 2155 Main Street Bethlehem, New Hampshire 03574 Performed at: Summit/Cruft Building 2111 Main Street Bethlehem,

More information

ASBESTOS ASSESSMENT Science Building Memorial University of Newfoundland St. John s, NL

ASBESTOS ASSESSMENT Science Building Memorial University of Newfoundland St. John s, NL Project #: 14610 ASBESTOS ASSESSMENT Science Building Memorial University of Newfoundland St. John s, NL Prepared for: Tina Giles-Murphy Director, Department of Health and Safety Memorial University of

More information

Asbestos Management Program April 27, 2017

Asbestos Management Program April 27, 2017 Asbestos Management Program April 27, 2017 1. INTRODUCTION 1.1. Purpose Indiana University Environmental Health and Safety (IUEHS) has developed this Program to identify practices and procedures for the

More information

LIMITED ASBESTOS INSPECTION REPORT

LIMITED ASBESTOS INSPECTION REPORT LIMITED ASBESTOS INSPECTION REPORT 6977 S Newland St. Littleton, CO 3/14/2018 Prepared for: New Customer Natasha Mitchell 6977 S Newland St. Littleton, CO 80128 303-960-6879 columbinegoldens@gmail.com

More information

ASBESTOS & HAZARDOUS MATERIALS INSPECTION

ASBESTOS & HAZARDOUS MATERIALS INSPECTION ASBESTOS & HAZARDOUS MATERIALS INSPECTION of Homewood Montessori School 7100 Hamilton Avenue Pittsburgh, Pennsylvania Prepared for Facilities Division Pittsburgh Public Schools 1305 Muriel Street 15203-1513

More information

LIMITED ASBESTOS IN NSPECTION 1262 BOOKCLIFF AVENUE GRAND JUNCTION, COLORADO

LIMITED ASBESTOS IN NSPECTION 1262 BOOKCLIFF AVENUE GRAND JUNCTION, COLORADO LIMITED ASBESTOS INSPECTION 1262 BOOKCLIFF AVENUEE GRAND JUNCTION, COLORADO Inspected by Grande River Environmental, LLC CDPHE CONSULTING FIRM #18631 October 3, 2177 LIMITED ASBESTOS INSPECTION 1262 BOOKCLIFF

More information

Report No: ACM October 29, 2012

Report No: ACM October 29, 2012 PbO3 ENVIRONMENTAL INCORPORATED TESTING & SVC. CO. Report No: ACM-0223-10-29-12-022 October 29, 2012 Client: Lunacon Construction Group 16890 South Dixie Highway Miami, Florida 33157 Attn: Ozzie Gomez

More information

SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT

SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT SURVEY REPORT FOR ASBESTOS AND LEAD-BASED PAINT Prepared For: TALLEY & SMITH ARCHITECTURE, INC. 409 EAST MARION STREET SHELBY, NORTH CAROLINA 28150 Regarding: DELIVERY ORDER NO. 0051 FY 15 DEMOLISH FACILITIES,

More information

LIMITED ASBESTOS-CONTAINING BUILDING MATERIALS SURVEY. Wal-Mart # Highway 51 North Ripley, TN ATC Project Number

LIMITED ASBESTOS-CONTAINING BUILDING MATERIALS SURVEY. Wal-Mart # Highway 51 North Ripley, TN ATC Project Number LIMITED ASBESTOS-CONTAINING BUILDING MATERIALS SURVEY Wal-Mart #0097 628 Highway 51 North Ripley, TN 38063 ATC Project Number 30.75300.0612 Prepared for: Wal-Mart Stores, Inc. Ms. Vicki Ingram Store Planning

More information

PRE-DEMOLITION ASBESTOS SURVEY Curtis Park Ballpark and Pool 1901 NW 24 Avenue Miami, FL 33125

PRE-DEMOLITION ASBESTOS SURVEY Curtis Park Ballpark and Pool 1901 NW 24 Avenue Miami, FL 33125 PRE-DEMOLITION ASBESTOS SURVEY Curtis Park Ballpark and Pool 1901 NW 24 Avenue Miami, FL 33125 Prepared For: City of Miami Capital Improvements & Transportation Program 444 SW 2 nd Avenue, 8 th Floor Miami,

More information

April 30, 2015 PREPARED FOR: Stantec, Inc. 55 Green Mountain Drive South Burlington, VT 05403

April 30, 2015 PREPARED FOR: Stantec, Inc. 55 Green Mountain Drive South Burlington, VT 05403 ASBESTOS INSPECTION REPORT 1079/ 1081, 1253 & 1371 Airport Drive, 3 & 4 Delaware Street, 53 North Henry Court, and 11 & 49 South Henry Court South Burlington, VT 05403 AIP 88 April 30, 2015 PREPARED FOR:

More information

FACILITY ASBESTOS MANAGEMENT PLAN

FACILITY ASBESTOS MANAGEMENT PLAN WASHINGTON ADVENTIST UNIVERSITY DEPARTMENT OF PUBLIC SAFETY DIVISION FACILITY ASBESTOS MANAGEMENT PLAN TAKOMA PARK CAMPUS REVIEWED and APPROVED BY: Patrick Farley WAU- V.P. of Finance Steven Lapham WAU-Executive

More information

Final Asbestos Inspection Report and Lead Paint Survey

Final Asbestos Inspection Report and Lead Paint Survey Final Asbestos Inspection Report and Lead Paint Survey Proposed Retail Takeover, Store #3178-00 2444 East Powell Boulevard Gresham, Multnomah County, Oregon October 7, 2011 Terracon Project No. 82117017

More information

THE CITY OF KENOSHA, WISCONSIN

THE CITY OF KENOSHA, WISCONSIN THE CITY OF KENOSHA, WISCONSIN REQUEST FOR QUOTATIONS TO RAZE GAS STATION BUILDING, CANOPY, SIGN AND LIGHTING AND TO PROPERLY REMOVE AND PROPERLY DISPOSE OF RESIDUAL MATERIAL & DEBRIS AT 704 75TH STREET

More information

FINAL REPORT. Asbestos-Containing Building Material Assessment

FINAL REPORT. Asbestos-Containing Building Material Assessment FINAL REPORT Asbestos-Containing Building Material Assessment Toronto Catholic District School Board Nativity of Our Lord Catholic School 35 Saffron Crescent Etobicoke, Ontario PROJECT NO. 1025760 PROJECT

More information

April 29, 2015 PREPARED FOR: Stantec, Inc. 55 Green Mountain Drive South Burlington, VT 05403

April 29, 2015 PREPARED FOR: Stantec, Inc. 55 Green Mountain Drive South Burlington, VT 05403 ASBESTOS INSPECTION REPORT 1089, 1233, 1383 Airport Drive, 69 Dumont Street, 238 Kirby Road, 5, 8, 11, 15/17 Ledoux Terrace, 13, 17 Maryland Street, 420 White Street South Burlington, VT 05403 AIP 94 April

More information

Asbestos, Lead and Hazardous Materials Pre-demolition Survey Report

Asbestos, Lead and Hazardous Materials Pre-demolition Survey Report A ACUMEN INDUSTRIAL HYGIENE INC 1032 IRVING ST. #922 SAN FRANCISCO CA 94122 TEL 415 242 6060 FAX 415 242 6006 WWW.ACUMEN-IH.COM Asbestos, Lead and Hazardous Materials Pre-demolition Survey Report for John

More information

SUMMARY OF BID ITEMS

SUMMARY OF BID ITEMS Addendum 4 Request for Information Village of North Palm Beach Contractor Solicitation Roof Replacement Library & Public Works Facility Invitation for Bids Bid Opening October 9, 2014 3:00 PM E.S.T. Following

More information

Asbestos and Lead-Based Paint Survey Report

Asbestos and Lead-Based Paint Survey Report Asbestos and Lead-Based Paint Survey Report GILDER CREEK WRRF RAS PUMP STATION BUILDING NO. 1 2824 EAST GEORGIA ROAD SIMPSONVILLE, SOUTH CAROLINA December 20, 2017 Terracon Project No. 86177249 Prepared

More information

Asbestos-Containing Material Inspection Mount Vernon Apartments 677 West Alexandrine Street Detroit, Michigan. Mount Vernon Apartments II LDHA, LP

Asbestos-Containing Material Inspection Mount Vernon Apartments 677 West Alexandrine Street Detroit, Michigan. Mount Vernon Apartments II LDHA, LP Asbestos-Containing Material Inspection Mount Vernon Apartments 677 West Alexandrine Street Detroit, Michigan Mount Vernon Apartments II LDHA, LP February 26, 2016 Asbestos-Containing Material Inspection

More information

SURVEY FINDINGS Building: 1101

SURVEY FINDINGS Building: 1101 SURVEY FINDINGS Building: 1101 Friable ACM identified DESCRIPTION LOCATION Date Quantity No friable ACM records found in database Non-friable ACM identified DESCRIPTION LOCATION Date Quantity ROOFING SEALANT,

More information

PREPARED FOR: City of Beverly Hills 345 North Foothill Road Beverly Hills, California 90210

PREPARED FOR: City of Beverly Hills 345 North Foothill Road Beverly Hills, California 90210 HAZARDOUS BUILDING MATERIAL SURVEY BEVERLY GARDENS PARK RESTROOM STRUCTURE SANTA MONICA BOULEVARD AND NORTH BEVERLY DRIVE BEVERLY HILLS, CALIFORNIA 90210 PREPARED FOR: City of Beverly Hills 345 North Foothill

More information

HERRON Enterprises USA, Inc.

HERRON Enterprises USA, Inc. Phone (33) 763 9639 HERRON Enterprises USA, Inc. Fax (33) 763 9686 E-Mail Lennie.Herron@comcast.net Hazardous Materials*Mold*Asbestos*Lead Paint www.herron-enterprises.com Environmental Services*Industrial

More information

ADDENDUM NO.: 1 TO THE CONTRACT DOCUMENTS For SCC SWING SPACE FOR MOHR HALL MODERNIZATION (Existing Temps)

ADDENDUM NO.: 1 TO THE CONTRACT DOCUMENTS For SCC SWING SPACE FOR MOHR HALL MODERNIZATION (Existing Temps) Los Rios Community College District Sacramento City College ADDENDUM NO.: 1 TO THE CONTRACT DOCUMENTS For SCC SWING SPACE FOR MOHR HALL MODERNIZATION (Existing Temps) GENERAL This addendum forms a part

More information

1. Sign-in sheet from the Pre-Proposal Conference on April 19, 2017 at Atherton Elementary.

1. Sign-in sheet from the Pre-Proposal Conference on April 19, 2017 at Atherton Elementary. DATE: April 20, 2017 ARLINGTON INDEPENDENT SCHOOL DISTRICT 1203 W. Pioneer Parkway Arlington, Texas 76013 ADDENDUM II FROM: Tammy Craig Director Purchasing RE: CSP 17-79 Amos & Atherton Elementary Renovations

More information

STUDIO 2LR ARCHITECTURE + INTERIORS

STUDIO 2LR ARCHITECTURE + INTERIORS STUDIO 2LR ARCHITECTURE + INTERIORS University of South Carolina Longstreet Theatre Exterior Renovations 1300 Greene Street, Columbia, South Carolina State Project Number: H27-6100-G May 22, 2015 ADDENDUM

More information

QuES&T Quality Environmental Solutions & Technologies, Inc.

QuES&T Quality Environmental Solutions & Technologies, Inc. QuES&T Quality Environmental Solutions & Technologies, Inc. August 31, 2015 SUNY Purchase Association 735 Anderson Hill Road Purchase, NY 10577 ATTN: Patrick Savolskis Via Email: patrick.savolskis@purchase.edu

More information

Explain in writing if the address of the building is different than the address on this form:

Explain in writing if the address of the building is different than the address on this form: ILLINOIS DEPARTMENT OF PUBLIC HEALTH AHERA THREE YEAR REINSPECTION ASBESTOS ABATEMENT PROGRAM SCHOOL INFORMATION FORM SECTION I NAME OF SCHOOL DISTRICT: SCHOOL ID NUMBER: ADDRESS OF SCHOOL: CITY: CHICAGO

More information

BRIGHAM YOUNG UNIVERSITY IDAHO ENVIRONMENTAL, HEALTH & SAFETY SAFETY DEPARTMENT ASBESTOS MANAGEMENT PROGRAM EH-006-R02

BRIGHAM YOUNG UNIVERSITY IDAHO ENVIRONMENTAL, HEALTH & SAFETY SAFETY DEPARTMENT ASBESTOS MANAGEMENT PROGRAM EH-006-R02 BRIGHAM YOUNG UNIVERSITY IDAHO ENVIRONMENTAL, HEALTH & SAFETY SAFETY DEPARTMENT ASBESTOS MANAGEMENT PROGRAM EH-006-R02 Department Title: Safety Department Page: 2 Department Title: Safety Department Page:

More information

Asbestos Survey Report University of Alaska Anchorage SSB Building-Mechanical Rooms (1 st, 3 rd Floors & Room 205) Prepared for:

Asbestos Survey Report University of Alaska Anchorage SSB Building-Mechanical Rooms (1 st, 3 rd Floors & Room 205) Prepared for: Asbestos Survey Report University of Alaska Anchorage SSB Building-s (1 st, 3 rd Floors & Room 205) Prepared for: University of Alaska Anchorage 3211Providence Drive Anchorage, AK 99508 Ms. Patricia Baum

More information