9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement

Size: px
Start display at page:

Download "9/20/2016 4:01 PM. Second Revision No NFPA [ New Section after ] Submitter Information Verification. Committee Statement"

Transcription

1 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with the provisions of The provisions of shall not apply to display bathtubs, bathtub-shower combinations, or showers. Submittal Date: Thu Jul 21 11:19:40 EDT 2016 The provisions of provides necessary safety for showers and bathtubs. Significant justification was provided by the submitter. The provisions of exempt display showers and bathtubs from the provisions of so as to not over-apply the provisions. It is not intended that the provisions of apply to all merchandise and fixture displays found in some mercantile occupancies. Response Message: Public Comment No. 175-NFPA [New Section after ]

2 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Special Definitions. The following is a list of special terms used in this chapter: (1) Anchor Building. A building housing any occupancy having low- or ordinary-hazard contents and having direct access to a mall structure, but having all required means of egress independent of the mall concourse. (See ) (2) Food Court. A public seating area located in a mall concourse that serves adjacent food preparation tenant spaces. (See ) (3) Gross Leasable Area. Fifty percent of major tenant areas, and 100 percent of all other floor areas designated for tenant occupancy and exclusive use, including storage areas. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. (See ) (4) Mall c C oncourse. A roofed or covered common pedestrian area within a mall structure that serves as access for two or more tenants and does not exceed three levels that are open to each other. (See ) (a)* Open Mall Concourse. A mall concourse that either (1) has 50 percent or more of the total area of the solid mall concourse perimeter walls and solid roof area open to the atmosphere with openings distributed uniformly over the length of the mall concourse, or (2) has an approved open mall concourse engineering analysis. (b) Enclosed Mall Concourse. A mall concourse that does not meet the definition of open mall concourse. (5)* Mall Structures. A single building enclosing a number of tenants and occupancies wherein two or more tenants have a main entrance into one or more mall concourses. For the purpose of this chapter, anchor buildings shall not be considered as a part of the mall structure. (See ) (6) Major Tenant. A tenant space, in a mall structure, with one or more main entrances from the exterior that also serve as exits and are independent of the mall concourse. (See ) Supplemental Information File Name A _4_a_.docx A _5_.docx Description Submittal Date: Mon Aug 01 14:46:47 EDT 2016 Response Message: The proposed changes are the result of task group work that was initiated at the completion of the 2015 revision cycle. The focus of the task group was to update terminology related to shopping malls to better describe the applicability and intent of the Code sections as well as develop language to address both enclosed and open mall concourses. The changes proposed here as public comments represent a continuation of the work proposed during the First Draft stage. The focus of these changes is to clarify the proposed definitions of open and enclosed mall concourses and to address the impact of these new definitions on the current mall provisions. Open mall concourses are becoming a very common design of mall type structures where as much of the pedestrian area is open to the outside. The provisions developed here recognize this now popular design approach and also recognize that the hazards with open mall concourses are different than enclosed mall concourses. Much thought and discussion was contributed by the full committee during the Second Draft meeting. Annex language was carefully developed to assist users in understanding and applying the new open mall concourse concept. The changes proposed in the multiple Second Revisions throughout Section incorporate the concept of open mall concourse as set forth in the definitions shown in this revision. Public Comment No. 125-NFPA [Section No ]

3 A (4)(a) An open mall concourse is permitted to serve as the public way provided that the open mall concourse meets the definition of public way in accordance with this Code. It is intended that the open mall concourse be designed, constructed, and arranged to permit the natural venting of smoke and other products of combustion to the outside air through openings in the walls, roof, or combination thereof of the mall concourse. The solid area of the mall concourse walls and horizontal projection of the solid area of any roof structures, including shade structures, awnings, and canopies, that cover the mall concourse is to be summed to determine the aggregate area of solid construction associated with the mall concourse. A mall concourse can be considered an open mall concourse where at least fifty percent (50%) of the aggregate area of solid construction is open to the atmosphere. Open areas can include entrances to the mall concourse (e.g. such as barred gates which allow air to pass through versus an entrance storefront), clearstory spaces between the mall building (structure which houses tenants) and the roof above, and openings in the roof assembly. In order for the openings to be effective they must also be distributed uniformly over the length of the mall concourse. Caution must be exercised in the design and construction so as to not create areas of possible congestion for smoke and hot gasses to accumulate, such as a pitched (steep slope) roof assembly within the mall concourse. Roof assemblies are permitted to have holes or open areas which represent openings to the outside. The roof assembly is also permitted to consist of a structure or assembly which allows the venting of the mall concourse. Examples of these vented roof structures include a roof trellis or an exposed roof structural frame only with no roofing materials. These types of structures that would permit the omission of automatic sprinkler protection, in accordance with NFPA 13, could be included to serve as open space for the purposes of the calculation of areas open to the outside air. Caution should be taken not to allow vegetation to grow into and around these structures which could reduce or impede the venting capabilities.

4 A (5) A mall structure can include either an enclosed mall concourse or an open mall concourse. A mall structure may be enclosed by construction which could range from total enclosure to construction which is open, either partially or totally, to the outer air. For structures without complete walls and/or roof, the termination of the mall exit discharge would determine the extent of the structure.

5 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] General The mall structure shall be treated as a single building for the purpose of calculation of means of egress and shall be subject to the requirements for appropriate occupancies, except as modified by the provisions of ;, and the mall concourse shall be of a clear width not less than that needed to accommodate egress requirements as set forth in other sections of this Code * Open Mall Concourse Engineering Analysis. A mall concourse shall be permitted to be classified as an open mall concourse where an approved engineering analysis demonstrates that the mall concourse is designed to keep the smoke layer interface at 6 ft (1830 mm) above the highest walking level surface open to the mall concourse, for a period equal to 1.5 times the calculated egress time or 20 minutes, whichever is greater. Supplemental Information File Name A docx Description Submittal Date: Mon Aug 01 14:49:07 EDT 2016 Response Message: New section sets performance criteria which can be used to define an open mall concourse in order to apply the new provisions for open mall concourses, as newly defined, throughout The performance criteria is based on other engineering analyses in the code such as atria.

6 A Multiple fire scenarios may need to be considered to evaluate overall tenability of the mall concourse space. See Section 5.5.

7 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] * Pedestrian Way Travel Distance. The mall concourse shall be permitted to be considered a pedestrian way, provided that the criteria of and are met The travel distance within a tenant space to an exit or to the mall concourse shall not exceed the maximum travel distance permitted by the occupancy chapter An additional 200 ft (61 m) shall be permitted for travel through the enclosed mall concourse space or 300 ft (91 m) for travel through the open mall concourse, provided that all the following requirements are met: (1)* The mall concourse shall be of a clear width not less than that needed to accommodate egress requirements, as set forth in other sections of this chapter, but shall be not less than 20 ft (6100 mm) wide in its narrowest dimension. (2) On each side of the mall floor area, the mall concourse shall be provided with an unobstructed exit access of not less than 10 ft (3050 mm) in clear width parallel to, and adjacent to, the mall tenant front. (3)* The exit access specified in (2) shall lead to an exit having a width of not less than 66 in. (1675 mm). (4) The mall concourse, and all buildings connected thereto, except open parking structures, shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with (1), which shall be installed in such a manner that any portion of the system serving tenant spaces can be taken out of service without affecting the operation of the portion of the system serving the mall concourse. (5)* Walls dividing tenant spaces from each other shall have a fire resistance rating of not less than 1 hour, and all of the following also shall apply: (a) (b) The partition shall extend to the underside of the ceiling or to the floor or roof or floor deck above. No separation shall be required between a tenant space and the mall concourse. (6)* Mall concourses with a floor opening connecting more than two levels shall be provided with a smoke control system. Supplemental Information File Name A _1_.docx Description Submittal Date: Mon Aug 01 14:52:24 EDT 2016 The concept of pedestrian way was used in the code to prevent the mall concourse from being enforced as a corridor. The term pedestrian way is not defined in the Code and is not used in any other provisions in Section Section includes provisions for travel distance within the tenant space and the mall concourse area so the change in title reflects the requirements. The change more clearly coordinates with title and application of new terminology in this chapter and those used by current industry standards : The code has other scenarios where additional travel is permitted in exterior environments, or scenarios where extra protection features offer additional safety to occupants. The travel distance extension here represents a similar principle with comparable hazards and

8 of 28 9/20/2016 4:01 PM conditions (example: where special provisions have been made for the control and removal of smoke and products of combustion such as smoke protected assembly seating ( /13), outdoor stadia, facilities with exterior exit access and egress components which are open to the outside air). The new definition of open mall concourse provides support for increase in travel distance. A (1): New annex reference sends users to a section in the general mercantile on wheeled carts or kiosks obstructing a means of egress to assist in enforcing the clear width (5): Consistent terminology from Chapter 8 and definition. Without deck the demarcation is left up to the AHJ. Clarifies the termination point of the partition. Has to extend to the finished deck of the roof or floor. Response Message:

9 A (1) See Section

10 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Dead ends not exceeding a length equal to twice the width of the mall concourse for enclosed mall concourses or two and a half times the width of the mall concourse for open mall concourses, measured at the narrowest location within the dead-end portion of the mall concourse, shall be permitted. Submittal Date: Mon Aug 01 15:00:27 EDT 2016 The increase in dead end travel compares to other occupancies that allow from 20 to 50 ft. Many occupancies allow a 20 ft dead end in nonsprinklered buildings and an increase to 50 ft where the building is protected throughout by an automatic sprinkler system. This proposed increase in dead end travel for open mall concourses represents the specific hazards associated with open mall concourses based upon the new definition proposed for open mall concourses. The change coordinates with other occupancies where special arrangements have been provided to prevent for the accumulation of smoke in the means of egress. Response Message:

11 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] * Emergency lighting shall be provided in accordance with Supplemental Information File Name A docx Description Submittal Date: Mon Aug 01 21:20:26 EDT 2016 Response Message: A pointer back to the core chapter section on emergency lighting reminds users about the application of emergency lighting. The means of egress including exit access and exit discharge will need to be defined based on whether the structure is being enforced as an open mall concourse or an enclosed mall concourse.

12 A For the purposes of emergency lighting the open mall concourse should be considered a component of the means of egress. See Section

13 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Emergency Forces Notification. Emergency forces notification shall be provided and shall include notifying all of the following: (1) Fire department in accordance with (2) Local Approved, local emergency organization, if provided Submittal Date: Mon Aug 01 15:13:30 EDT 2016 Response Message: The local emergency organization should also be approved by the Authority Having Jurisdiction. The language is consistent with NFPA 5000.

14 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] Risk Analysis for Mass Notification. Mall structures shall conduct a risk analysis to determine the need for a mass notification system in accordance with Section Submittal Date: Mon Aug 01 12:20:21 EDT 2016 Response Message: After the First Draft meeting a task group was established to develop text for if and when the new provisions of Section 9.14 should apply to mercantile and business occupancies. After multiple meetings of the task group as well as input from the full committee the proposed text identifies mall structures as appropriate mercantile occupancies for requiring a risk analysis to determine if a mass notification system is required. Mall structures are large structures that incorporate a number of different tenant uses and tend to have a higher occupant load. There have been multiple recent events in mall structures that would support the requirement for a risk analysis for mass notification systems. These systems can provide real time communication and response to the occupants.

15 0 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Kiosks. Kiosks and similar structures (temporary or permanent) shall not be considered tenant spaces and shall meet all of the following requirements: (1) Combustible kiosks and similar structures shall be constructed of any of the following materials: (a) Fire-retardant-treated wood complying with the requirements for fire-retardant-impregnated wood in NFPA 703, Standard for Fire Retardant Treated Wood and Fire-Retardant Coatings for Building Materials (b) Light-transmitting plastics complying with the building code (c) Foamed plastics having a maximum heat release rate not greater than 100 kw when tested in accordance with ANSI/UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes, or in accordance with NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, using the 20 kw ignition source (d) Metal composite material (MCM) having a flame spread index not greater than 25 and a smoke developed index not greater than 450 in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, when tested as an assembly in the maximum thickness intended for use (e) Textiles and films meeting the flame propagation performance criteria contained in NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films Kiosks or similar structures located within the mall concourse shall be protected with approved fire suppression and detection devices. (2) The minimum horizontal separation between kiosks, or groups of kiosks, and other structures within the mall concourse shall be 20 ft (6100 mm). (3) Each kiosk, or group of kiosks, or similar structure shall have a maximum area of 300 ft 2 (27.8 m 2 ). Submittal Date: Mon Aug 01 15:14:27 EDT 2016 Response Message: Provisions for the protection of kiosks have been moved to Section for extinguishing systems which retains the extinguishment provisions in same section.

16 1 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] * Smoke Control. Smoke control in accordance with Section 9.3 and complying with 8.6.7(5) shall be provided in a an enclosed mall concourse with floor openings connecting more than two levels stories. Submittal Date: Mon Aug 01 15:16:58 EDT 2016 This proposed change to mandate smoke control only for enclosed mall concourses connecting more than two levels represents the specific hazards associated with open versus enclosed mall concourses based upon the new definition proposed for open mall concourses. The change coordinates with other occupancies and other changes within the mall section where special arrangements have been provided to prevent for the accumulation of smoke in the means of egress. Response Message:

17 2 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Automatic Extinguishing Systems The mall structure and all anchor buildings shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with (1) and through The system shall be installed in such a manner that any portion of the system serving tenant spaces can be taken out of service without affecting the operation of the portion of the system serving the mall concourse * Any shade structures, canopies, awnings, or similar structures in the open mall concourse shall be protected by an approved, supervised automatic sprinkler system in accordance with Section * Kiosks or similar structures located within the enclosed mall concourse shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Supplemental Information File Name A docx A docx Description Submittal Date: Mon Aug 01 15:42:52 EDT and Annex: Many open mall concourses contain shade structures and other features that may necessitate the need for automatic sprinkler protection. The proposed languages points user to the applicable section of Chapter 9 and then to NFPA 13 for the necessary guidance on how to protect these features : This text was formerly located in the section specifically for kiosks and is being relocated here to keep requirements for extinguishment in one section; makes the section more user friendly. Response Message:

18 A Examples of these roof type structures include but are not limited to shade structures, canopies, awnings or other similar structures located above the open mall concourse which serve as a screen or shelter from the sun, rain, or other atmospheric and climatological effects. However, these structures are designed to only partially enclose the area above a mall concourse, allow the mall concourse to be open to the atmosphere, and not serve as roof that is designed to separate the conditioned space of the mall concourse from the exterior atmosphere. These structures are permitted to be supported by the mall building, mall concourse walls, or can be self-supporting. It is intended that these structures be protected by a supervised automatic sprinkler system where required by NFPA 13 unless allowed to be omitted with approval of the AHJ.

19 A Sprinklers may be omitted in kiosks located in portions of open mall concourses where no roof exists. Where sprinklers are provided at the mall concourse ceiling, the obstruction provisions of NFPA 13 also apply.

20 3 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Special Definitions. The following is a list of special terms used in this chapter: (1) Anchor Building. A building housing any occupancy having low- or ordinary-hazard contents and having direct access to a mall structure, but having all required means of egress independent of the mall concourse. (See ) (2) Food Court. A public seating area located in a mall concourse that serves adjacent food preparation tenant spaces. (See ) (3) Gross Leasable Area. Fifty percent of major tenant areas, and 100 percent of all other floor areas designated for tenant occupancy and exclusive use, including storage areas. The area of tenant occupancy is measured from the centerlines of joint partitions to the outside of the tenant walls. (See ) (4) Mall Concourse. A roofed or covered common pedestrian area within a mall structure that serves as access for two or more tenants and does not exceed three levels that are open to each other. (See ) (a)* Open Mall Concourse. A mall concourse that either (1) has 50 percent or more of the total area of the solid mall concourse perimeter walls and solid roof area open to the atmosphere with openings distributed uniformly over the length of the mall concourse, or (2) has an approved open mall concourse engineering analysis. (b) Enclosed Mall Concourse. A mall concourse that does not meet the definition of open mall concourse. (5)* Mall Structure. A single building enclosing a number of tenants and occupancies wherein two or more tenants have a main entrance into one or more mall concourses. For the purpose of this chapter, anchor buildings shall not be considered as a part of the mall structure. (See ) (6)* Major Tenant. A tenant space, in a mall structure, with one or more main entrances from the exterior that also serve as exits and are independent of the mall concourse. (See ) Supplemental Information File Name A _4_a_.docx A _5_.docx Description Submittal Date: Tue Aug 02 10:52:22 EDT 2016 Response Message: he proposed changes are the result of task group work that was initiated at the completion of the 2015 revision cycle. The focus of the task group was to update terminology related to shopping malls to better describe the applicability and intent of the Code sections as well as develop language to address both enclosed and open mall concourses. The changes proposed here as public comments represent a continuation of the work proposed during the First Draft stage. The focus of these changes is to clarify the proposed definitions of open and enclosed mall concourses and to address the impact of these new definitions on the current mall provisions. Open mall concourses are becoming a very common design of mall type structures where as much of the pedestrian area is open to the outside. The provisions developed here recognize this now popular design approach and also recognize that the hazards with open mall concourses are different than enclosed mall concourses. Much thought and discussion was contributed by the full committee during the Second Draft meeting. Annex language was carefully developed to assist users in understanding and applying the new open mall concourse concept. The changes proposed in the multiple Second Revisions throughout Section incorporate the concept of open mall concourse as set forth in the definitions shown in this revision. Public Comment No. 133-NFPA [Section No ]

21 A (4)(a) An open mall concourse is permitted to serve as the public way provided that the open mall concourse meets the definition of public way in accordance with this Code. It is intended that the open mall concourse be designed, constructed, and arranged to permit the natural venting of smoke and other products of combustion to the outside air through openings in the walls, roof, or combination thereof of the mall concourse. The solid area of the mall concourse walls and horizontal projection of the solid area of any roof structures, including shade structures, awnings, and canopies, that cover the mall concourse is to be summed to determine the aggregate area of solid construction associated with the mall concourse. A mall concourse can be considered an open mall concourse where at least fifty percent (50%) of the aggregate area of solid construction is open to the atmosphere. Open areas can include entrances to the mall concourse (e.g. such as barred gates which allow air to pass through versus an entrance storefront), clearstory spaces between the mall building (structure which houses tenants) and the roof above, and openings in the roof assembly. In order for the openings to be effective they must also be distributed uniformly over the length of the mall concourse. Caution must be exercised in the design and construction so as to not create areas of possible congestion for smoke and hot gasses to accumulate, such as a pitched (steep slope) roof assembly within the mall concourse. Roof assemblies are permitted to have holes or open areas which represent openings to the outside. The roof assembly is also permitted to consist of a structure or assembly which allows the venting of the mall concourse. Examples of these vented roof structures include a roof trellis or an exposed roof structural frame only with no roofing materials. These types of structures that would permit the omission of automatic sprinkler protection, in accordance with NFPA 13, could be included to serve as open space for the purposes of the calculation of areas open to the outside air. Caution should be taken not to allow vegetation to grow into and around these structures which could reduce or impede the venting capabilities.

22 A (5) A mall structure can include either an enclosed mall concourse or an open mall concourse. A mall structure may be enclosed by construction which could range from total enclosure to construction which is open, either partially or totally, to the outer air. For structures without complete walls and/or roof, the termination of the mall exit discharge would determine the extent of the structure.

23 4 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] General The mall structure shall be treated as a single building for the purpose of calculation of means of egress and shall be subject to the requirements for appropriate occupancies, except as modified by the provisions of , and the mall concourse shall be of a clear width not less than that needed to accommodate egress requirements as set forth in other sections of this Code * Open Mall Concourse Engineering Analysis. A mall concourse shall be permitted to be classified as an open mall concourse where an approved engineering analysis demonstrates that the mall concourse is designed to keep the smoke layer interface at 6 ft (1830 mm) above the highest walking level surface open to the mall concourse, for a period equal to 1.5 times the calculated egress time or 20 minutes, whichever is greater. Supplemental Information File Name A docx Description Submittal Date: Tue Aug 02 11:35:51 EDT 2016 Response Message: New section sets performance criteria which can be used to define an open mall concourse in order to apply the new provisions for open mall concourses, as newly defined, throughout The performance criteria is based on other engineering analyses in the code such as atria.

24 A Multiple fire scenarios may need to be considered to evaluate overall tenability of the mall concourse space. See Section 5.5.

25 5 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] * Pedestrian Way. Travel Distance. The mall concourse shall be permitted to be considered a pedestrian way, provided that the criteria of and are met The travel distance within a tenant space to an exit or to the mall concourse shall not exceed the maximum travel distance permitted by the occupancy chapter An additional 200 ft (61 m) shall be permitted for travel through the mall space enclosed mall concourse or 300 ft (91 m) for travel through the open mall concourse, provided that all the following requirements are met: (1)* The mall concourse shall be of a clear width not less than that needed to accommodate egress requirements, as set forth in other sections of this chapter, but shall be not less than 20 ft (6100 mm) wide in its narrowest dimension. (2) On each side of the mall floor area, the mall concourse shall be provided with an unobstructed exit access of not less than 10 ft (3050 mm) in clear width parallel to, and adjacent to, the mall tenant front. (3)* The exit access specified in (2) shall lead to an exit having a width of not less than 66 in. (1675 mm). (4) The mall concourse, and all buildings connected thereto, except open parking structures, shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with (1). (5) Walls dividing tenant spaces from each other shall extend from the floor to the underside of the roof deck, to the floor deck above, or to the a ceiling where the ceiling that is constructed to limit the transfer of smoke, or to the ceiling where the wall is constructed with a fire resistance rating of not less than 1 hour and all of the following also shall apply: (a) Where the tenant areas are provided with an engineered smoke control system, walls shall not be required to divide tenant spaces from each other. (b) No separation shall be required between a tenant space and the mall concourse. (6)* Malls with a floor opening connecting more than two levels shall be provided with a smoke control system. Supplemental Information File Name A _1.docx Description Submittal Date: Tue Aug 02 13:49:05 EDT 2016 The concept of pedestrian way was used in the code to prevent the mall concourse from being enforced as a corridor. The term pedestrian way is not defined in the Code and is not used in any other provisions in Section Section includes provisions for travel distance within the tenant space and the mall concourse area so the change in title reflects the requirements. The change more clearly coordinates with title and application of new terminology in this chapter and those used by current industry standards : The code has other scenarios where additional travel is permitted in exterior environments, or scenarios where extra protection features offer additional safety to occupants. The travel distance extension here represents a similar principle with comparable hazards and conditions (example: where special provisions have been made for the control and removal of smoke and products of combustion such as smoke protected assembly seating, outdoor stadia, facilities with exterior exit access and egress components which are open to the outside air). The new definition of open mall concourse provides support for increase in travel distance. A (1): New annex reference sends users to a section in the general mercantile on wheeled carts or kiosks obstructing a means of egress to assist in enforcing the clear width.

26 6 of 28 9/20/2016 4:01 PM Response Message: (5): Current edition text had the effect of being more restrictive than Chapter 36 for new construction. Changes recognize how malls may be built as new and do not cause a conflict between new and existing.

27 A (1) See Section

28 7 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Dead ends not exceeding a length equal to twice the width of the mall concourse for enclosed mall concourses or two and a half times the width of the mall concourse for open mall concourses, measured at the narrowest location within the dead-end portion of the mall concourse, shall be permitted. Submittal Date: Tue Aug 02 14:10:21 EDT 2016 Response Message: The increase in dead end travel compares to other occupancies that allow from 20 to 50 ft. Many occupancies allow a 20 ft dead end in nonsprinklered buildings and an increase to 50 ft where the building is protected throughout by an automatic sprinkler system. This proposed increase in dead end travel for open mall concourses represents the specific hazards associated with open mall concourses based upon the new definition proposed for open mall concourses. The change coordinates with other occupancies where special arrangements have been provided to prevent for the accumulation of smoke in the means of egress.

29 8 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] * Emergency lighting shall be provided in accordance with Supplemental Information File Name A docx Description Submittal Date: Tue Aug 02 14:13:35 EDT 2016 Response Message: A pointer back to the core chapter section on emergency lighting reminds users about the application of emergency lighting. The means of egress including exit access and exit discharge will need to be defined based on whether the structure is being enforced as an open mall concourse or an enclosed mall concourse.

30 A For the purposes of emergency lighting the open mall concourse should be considered a component of the means of egress. See Section

31 9 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Emergency Forces Notification. Emergency forces notification shall be provided and shall include notifying all of the following: (1) Fire department in accordance with (2) Local Approved, local emergency organization, if provided Submittal Date: Tue Aug 02 14:38:49 EDT 2016 Response Message: The local emergency organization should also be approved by the Authority Having Jurisdiction. The language is consistent with NFPA 5000.

32 0 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Kiosks. Kiosks and similar structures (temporary or permanent) shall not be considered as tenant spaces and shall meet all of the following requirements: (1) Combustible kiosks and similar structures shall be constructed of any of the following materials: (a) Fire-retardant-treated wood complying with the requirements for fire-retardant-impregnated wood in NFPA 703, Standard for Fire Retardant Treated Wood and Fire-Retardant Coatings for Building Materials (b) Light-transmitting plastics complying with the building code (c) Foamed plastics having a maximum heat release rate not greater than 100 kw when tested in accordance with ANSI/UL 1975, Standard for Fire Tests for Foamed Plastics Used for Decorative Purposes, or in accordance with NFPA 289, Standard Method of Fire Test for Individual Fuel Packages, using the 20 kw ignition source (d) Metal composite material (MCM) having a flame spread index not greater than 25 and a smoke developed index not greater than 450 in accordance with ASTM E84, Standard Test Method for Surface Burning Characteristics of Building Materials, or ANSI/UL 723, Standard for Test for Surface Burning Characteristics of Building Materials, when tested as an assembly in the maximum thickness intended for use (e) Textiles and films meeting the flame propagation performance criteria contained in Test Method 1 or Test Method 2, as appropriate, of NFPA 701, Standard Methods of Fire Tests for Flame Propagation of Textiles and Films Kiosks or similar structures located within the mall concourse shall be protected with approved fire suppression and detection devices. (2) The minimum horizontal separation between kiosks, or groups of kiosks, and other structures within the mall concourse shall be 20 ft (6100 mm). (3) Each kiosk, or group of kiosks, or similar structure shall have a maximum area of 300 ft 2 (27.8 m 2 ) * Automatic Extinguishing Systems. Kiosks or similar structures located within the enclosed mall concourse shall be protected throughout by an approved, supervised automatic sprinkler system in accordance with Section 9.7. Supplemental Information File Name A docx Description Submittal Date: Tue Aug 02 14:45:54 EDT 2016 Response Message: The provisions for kiosk fire protection systems is being moved to a separate section for extinguishing systems. The change aligns the section with the way the requirements are presented in Chapter 36 and also leaves room for additional extinguishment provisions to be added in the future if necessary.

33 A Sprinklers may be omitted in kiosks located in portions of open mall concourses where no roof exists. Where sprinklers are provided at the mall concourse ceiling, the obstruction provisions of NFPA 13 also apply.

34 1 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] Grab Bars for Bathtubs, Bathtub-Shower Combinations, and Showers Where bathtubs, bathtub-shower combinations, or showers are present, grab bars shall be provided in accordance with the provisions of The provisions of shall not apply to display bathtubs, bathtub-shower combinations, or showers. Submittal Date: Thu Jul 21 11:29:32 EDT 2016 The provisions of provides necessary safety for showers and bathtubs in business occupancies. Significant justification was provided by the submitter. The provisions of exempt display showers and bathtubs from the provisions of so as to not over-apply the provisions. It is not intended that the provisions of apply to all merchandise and fixture displays found in some business occupancies where merchandise is on display but where no sales are occurring. Response Message: Public Comment No. 176-NFPA [New Section after ]

35 2 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] * Door Locking to Prevent Unwanted Entry. Where approved, doors, other than those complying with , shall be permitted to be locked to prevent unwanted entry provided that all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, a tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than one releasing operation. (4) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (5) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, a tool, or special knowledge or effort. (6) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (7) The locking means does not modify the door closer, panic hardware, or fire exit hardware. (8) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80. Supplemental Information File Name A docx Description Submittal Date: Mon Aug 01 11:34:45 EDT 2016 Response Message: The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions proposed as part of 38/ cover the concerns for accomplishing door locking in business occupancies, such as those buildings on college and university campuses, in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. While the provisions are written to apply to doors in business occupancies, the annex text clarifies the intent of this section is to apply only to doors where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces. There have been recent events where security has been an issue in both office buildings and well as educational settings where both uses could benefit from the security offered from this proposed text. Public Comment No. 190-NFPA [New Section after ]

36 A The intent of this section is to apply only where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces.

37 3 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] Supplemental Information File Name A docx Description Submittal Date: Mon Aug 01 14:14:27 EDT 2016 Response Message: The proposed section specifically addresses business occupancies that contain classrooms and where the building is owned, rented or leased by a college or university. This language is intended to apply to classroom buildings on college and university campuses that fall under the business occupancy classification. Those buildings with larger classrooms (50 or more occupants) that are classified as assembly occupancies would need to apply the provisions appropriate to that occupancy. Colleges and university settings have demonstrated a need for better communication of emergencies due to recent events on college campuses over the past decade. Annex: Clarifies that a new risk analysis is not always required where an existing risk analysis addresses the issues presented when adding a new building.

38 A It is not the intent of this section to require a new risk analysis where an existing risk analysis addresses the issues or arrangements associated with a new building.

39 4 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Integrated Fire Protection Systems. Integrated fire protection systems shall be tested in accordance with Submittal Date: Fri Jul 22 09:39:41 EDT 2016 Response Message: The committee supports the requirement for integrated testing of fire protection and life safety systems for high-rise business occupancies. This change was added to the 11.8 section for high-rise buildings.

40 5 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] * Door Locking to Prevent Unwanted Entry. Where approved, doors, other than those complying with , shall be permitted to be locked to prevent unwanted entry provided that all of the following conditions are met: (1) The locking means shall be capable of being engaged without opening the door. (2) The unlocking and unlatching operation from the egress side of the door shall be accomplished without the use of a key, a tool, or special knowledge or effort. (3) The releasing mechanism shall open the door leaf with not more than one releasing operation. (4) For existing doors, the releasing mechanism shall open the door leaf with not more than two releasing operations. (5) The releasing mechanism for unlocking and unlatching shall be located at a height not less than 34 in. (865 mm) and not exceeding 48 in. (1220 mm) above the finished floor. (6) Locks, if remotely engaged, shall be unlockable from the egress side of the door without the use of a key, a tool, or special knowledge or effort. (7) The door is capable of being unlocked and opened from outside the room with the necessary key or other credential. (8) The locking means does not modify the door closer, panic hardware, or fire exit hardware. (9) Modifications to required fire door assemblies, including door hardware, shall be in accordance with NFPA 80. Supplemental Information File Name A docx Description Submittal Date: Mon Aug 01 11:37:55 EDT 2016 The Workshop on School Safety, Codes and Security Final Report documented the need to lock classroom doors against unwanted entry. The multiple provisions proposed as part of 38/ cover the concerns for accomplishing door locking in business occupancies, such as those buildings on college and university campuses, in a safe manner. The detailed criteria will weed out the dangerous hardware and locking means being promoted in the marketplace by those unfamiliar with traditional egress needs. While the provisions are written to apply to doors in business occupancies, the annex text clarifies the intent of this section is to apply only to doors where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces. There have been recent events where security has been an issue in both office buildings and well as educational settings where both uses could benefit from the security offered from this proposed text. Response Message: For existing doors, it is permitted that the releasing mechanism can open the door with not more than two releasing operations. The proposed language supports a safe installation and necessary guidance for situations that are already occurring in existing buildings. The language is written so that it is done to protect occupants but also to ensure door is operable for safe and quick egress during emergencies. The recognizes that hardware does exists, and could be used, that allows two locking mechanisms/devices with one releasing action, such as residential hotel locks. The proposed language addresses the inevitable existing conditions that cannot utilize the "hotel locks." Public Comment No. 192-NFPA [New Section after ]

41 A The intent of this section is to apply only where specialized security measures are needed to prevent unwanted entry. Examples of doors that may use these provisions include college and university classroom doors, areas of office spaces open to the public, laboratories, instructional rooms or spaces.

42 6 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] Medical Gas. Medical gas storage areas and the operation, management, and maintenance of medical gases shall be in accordance with NFPA 99. Submittal Date: Fri Jul 22 11:35:54 EDT 2016 Response Message: In response to Input No. 5549, the committee reviewed scope of 99 and supports the reference to NFPA 99 for medical gas storage. Provisions existing in NFPA 99 that are appropriate for existing buildings.

43 7 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ New Section after ] High-rise buildings shall comply with for integrated fire protection and life safety system testing. Submittal Date: Fri Jul 22 09:42:45 EDT 2016 Response Message: The threshold for requiring integrated testing of fire protection and life safety systems in accordance with the new is appropriate for existing high-rise business occupancies. As proposed during the First Draft, all existing business occupancies would require compliance with Section 11.8 requires existing occupancy chapters to specifically reference portions of 11.8 that are required for that existing occupancy. Public Comment No. 219-NFPA [New Section after ]

44 8 of 28 9/20/2016 4:01 PM Second Revision No NFPA [ Section No ] Integrated Fire Protection Systems. Integrated fire protection systems shall be tested in accordance with Submittal Date: Wed Aug 03 10:16:53 EDT 2016 Response Message: Integrated testing of fire protection and life safety systems should be required only for existing high-rise business occupancies. Text is being added to the high-rise Section of Chapter 39 to address this requirement. The change addresses the submitter's request to limit the provisions for integrated testing to high-rise buildings. Public Comment No. 167-NFPA [Section No ]

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] National Fire Protection Association Report of 13 http://submittals.nfpa.org/terraviewweb/contentfetcher?commentpara... 10/28/2015 10:35 AM First Revision No. 5501-NFPA 5000-2015 [ Section No. 3.3.220.4

More information

Report on First Revision June 2014 NFPA 5000

Report on First Revision June 2014 NFPA 5000 5000 FR520 BLD-FUR (10.1 and 10.2) 10.1* General. 10.1.1 Application. Interior finish for buildings shall comply with this chapter. 10.1.2 Automatic Sprinkler Systems. Where another provision of this chapter

More information

11.1.2* Adjacent Hazards or Design Methods. For buildings with two or more adjacent hazards or design methods, the following shall apply:

11.1.2* Adjacent Hazards or Design Methods. For buildings with two or more adjacent hazards or design methods, the following shall apply: 10 of 474 11/7/2013 12:33 PM First Revision No. 260-NFPA 13-2013 [ Section No. 11.1.2 ] 11.1.2* Adjacent Hazards or Design Methods. For buildings with two or more adjacent hazards or design methods, the

More information

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY

SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY CHAPTER 4 SPECIAL DETAILED REQUIREMENTS BASED ON USE AND OCCUPANCY SECTION 401 SCOPE 401.1 Detailed use and occupancy requirements. In addition to the occupancy and construction requirements in this code,

More information

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION BC 2601 SECTION BC 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION BC 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic

More information

First Revision No NFPA [ Section No ]

First Revision No NFPA [ Section No ] First Revision No. 1001-NFPA 5000-2015 [ Section No. 7.2.5.6.8 ] Global FR-6108 7.2.5.6.8 Exterior Nonbearing Walls. Exterior nonbearing walls tested shall be permitted when tested in accordance with,

More information

2015 IBC Exit Systems

2015 IBC Exit Systems Objectives 2015 IBC Exit Systems Based on the 2015 International Building Code Upon completion, participants will be better able to: Determine those means of egress components that are defined as exits

More information

Applying the Building Code During Design

Applying the Building Code During Design Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education

More information

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION

CHAPTER 26 PLASTIC SECTION 2601 SECTION 2603 GENERAL FOAM PLASTIC INSULATION CHAPTER 26 PLASTIC SECTION 2601 GENERAL 2601.1 Scope. These provisions shall govern the materials, design, application, construction and installation of foam plastic, foam plastic insulation, plastic veneer,

More information

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax:

City of Des Moines. Permit and Development Center 602 Robert D Ray Drive Des Moines, IA Phone: Fax: City of Des Moines Permit and Development Center 602 Robert D Ray Drive Des Moines, IA 50309 Phone: 515-283-4200 Fax: 515-283-4270 This Code Analysis Form must be completed and returned with the Building

More information

Building Codes and Ordinances ARC 227

Building Codes and Ordinances ARC 227 Building Codes and Ordinances ARC 227 Week 6 Fire Resistive Construction 03.02.10 Instructor: Rick Staub, AIA Email: staub@pointonearchitects.com Phone: 860-434-7707 Fire Resistive Construction Passive

More information

2012 IBC Exit Systems

2012 IBC Exit Systems Accreditation Based on the 2012 International Building Code The International Code Council has been accredited as an Authorized Provider by the International Association for Continuing Education and Training

More information

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017

Minnesota Healthcare Engineers Association, Fall Conference. Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Minnesota Healthcare Engineers Association, Fall Conference Bob Dehler, P.E. Engineering Program Manager September 14, 2017 Categories of Rehabilitation Work in Healthcare Facilities Bob Dehler, P.E. robert.dehler@state.mn.us

More information

INTERIOR FINISHES CHAPTER 8

INTERIOR FINISHES CHAPTER 8 CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.1.1 Interior finishes.

More information

Code Review for Theaters and Props

Code Review for Theaters and Props Code Review for Theaters and Props I. INTRODUCTION Fire- and Life-Safety Group (FLS) This document was prepared to list the requirements for theaters and props. These requirements are based on the 2007

More information

INTERIOR FINISHES CHAPTER 8

INTERIOR FINISHES CHAPTER 8 CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.2 Interior wall and

More information

INTERIOR FINISHES CHAPTER 8

INTERIOR FINISHES CHAPTER 8 CHAPTER 8 INTERIOR FINISHES SECTION 801 GENERAL 801.1 Scope. Provisions of this chapter shall govern the use of materials used as interior finishes, trim and decorative materials. 801.2 Interior wall and

More information

Interior FRT Wood. References to ICC Building Codes

Interior FRT Wood. References to ICC Building Codes Interior FRT Wood References to ICC Building Codes Table of Contents International Building Code (IBC) 1 International Residential Code (IRC) 6 International Mechanical Code (IMC) 7 INTERNATIONAL BUILDING

More information

High Piled Combustible Storage Guideline

High Piled Combustible Storage Guideline Moreno Valley High Piled Combustible Storage Approved and Authorized By: Adria Reinertson, Fire Marshal Issued: May 5, 2017 Rev: 7-28-16 City of Moreno Valley Fire Department Page 1 of 19 High Piled Storage

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

The Building Codes A.R.E. Building Design and Construction Exam Prep

The Building Codes A.R.E. Building Design and Construction Exam Prep Know Thy Codes! The Building Codes Building Codes The Code of Hammurabi 4000bc Developed 19 th and 20 th c. Codes define what you can and can t do Allowable area and height based on degree of danger Fire

More information

Minnesota Health Care Engineers Association

Minnesota Health Care Engineers Association Minnesota Health Care Engineers Association Life Safety Code Potpourri Friday, May 1, 2015 Presenter: Bob Dehler, P.E., Engineering Program Manager, Minnesota Department of Health Minnesota Department

More information

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW

HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com

More information

UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011

UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011 UNIVERSITY OF ARIZONA CONSTRUCTION AND RENOVATION PERMITTING PROCEDURE ADOPTED: JULY 2011 CONTENTS A. PURPOSE B. DESIGNATED RESPONSIBILITIES C. DEFINITIONS D. PROJECT SUBMITTAL PROCEDURE E. REQUIREMENTS

More information

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm).

Work Group Item Stairways serving an occupant load of less than 50 shall have a width of not less than 36 inches (914 mm). IBC-12/13 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15 (IFC [B] 1009.1, 1009.4, 1009.7.2, 1009.7.4, 1009.8, 1009.10, 1009.15) Proponent: S. Bajnai, Chesterfield County, VA, ICC Building

More information

NFPA 30-FLC-SWC Second Revisions Report

NFPA 30-FLC-SWC Second Revisions Report of 44 9/6/2016 1:40 PM Second Revision No. 214-NFPA 30-2016 [ Global Comment ] See attached Word doc for changes to Sections 9.2, 12.2, and 16.2. Supplemental Information File Name 30-GLOBAL_SR_214-EDITED.docx

More information

TENTS AND OTHER MEMBRANE STRUCTURES

TENTS AND OTHER MEMBRANE STRUCTURES CHAPTER 31 TENTS AND OTHER MEMBRANE STRUCTURES SECTION 3101 GENERAL 3101.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 3103 are applicable only to temporary

More information

2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code

2012 IBC Assembly Means of Egress. Based on the 2012 International Building Code 2012 IBC Assembly Means of Egress Based on the 2012 International Building Code Overview This seminar deals with those means of egress provisions of the IBC that are intended to address the concerns related

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

INTERIOR ENVIRONMENT

INTERIOR ENVIRONMENT CHAPTER 12 INTERIOR ENVIRONMENT > SECTION 1201 GENERAL 1201.1 Scope. The provisions of this chapter shall govern ventilation, temperature control, lighting, yards and courts, sound transmission, room dimensions,

More information

TENTS AND MEMBRANE STRUCTURES

TENTS AND MEMBRANE STRUCTURES CHAPTER 24 TENTS AND MEMBRANE STRUCTURES SECTION 2401 GENERAL 2401.1 Scope. Tents and membrane structures shall comply with this chapter. The provisions of Section 2403 are applicable only to temporary

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary SECTION 1005 MEANS OF EGRESS SIZING [B] 1005.1 General. All portions of the means of egress system shall be sized in accordance with this section. Exception: Means of egress complying with Section 1028.

More information

WON-DOOR CORPORATION Won-Door FireGuard Applications

WON-DOOR CORPORATION Won-Door FireGuard Applications WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis WON-DOOR CORPORATION Won-Door FireGuard Applications A Code Analysis THE INTERNATIONAL BUILDING CODE is widely recognized in the United

More information

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS

EXETER TOWNSHIP HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS HOOD AND DUCT SYSTEMS FOR COMMERCIAL KITCHENS POLICY STATEMENT This policy applies to NEW Hood and Duct systems. The Authority Having Jurisdiction will not waive major criteria in the applicable standards

More information

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes

Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Analysis of Changes for the 5 th Edition (2014) of the Florida Codes Changes to the Florida Building Code, Existing Building This Analysis of Changes for the 5 th Edition (2014) of the Florida Codes is

More information

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system.

1. Frozen food warehouses used solely for storage of Class I and II commodities where protected by an approved automatic sprinkler system. Draft curtains are typically used in warehouses, aircraft hangars and large industrial plants to contain or channel smoke that rises to the ceiling in a fire. They can keep the smoke from rolling across

More information

WOOD USE IN NONCOMBUSTIBLE BUILDINGS

WOOD USE IN NONCOMBUSTIBLE BUILDINGS INTRODUCTION The National Building Code of Canada (NBCC) 1 requires that some buildings be of noncombustible construction under its prescriptive requirements. Its use in certain types of buildings such

More information

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES)

2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) 2018 APPENDIX B BUILDING CODE SUMMARY FOR ALL COMMERCIAL PROJECTS (EXCEPT 1 AND 2-FAMILY DWELLINGS AND TOWNHOUSES) (Reproduce the following data on the building plans sheet 1 or 2) Name of Project: Address:

More information

2007 Title 24 Accessibility Code Updates and ADA Issues

2007 Title 24 Accessibility Code Updates and ADA Issues 2007 Title 24 Accessibility Code Updates and ADA Issues C.A.S.H. Workshop June 2007 Introduction Update on ADA Certification of the California Building Code Overview of significant changes to accessibility

More information

2009 IBC Section 1024 Approved Luminous Egress Path Markings

2009 IBC Section 1024 Approved Luminous Egress Path Markings 2009 IBC Section 1024 Approved Luminous Egress Path Markings Where Required Buildings of Groups A (Assembly), B (Business), E (Education), I (Institutional), M (Mercantile) and R-1 (Residential transient

More information

Comparison of the life safety elements of the 1997 UBC and the IBC 2000.

Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Comparison of the life safety elements of the 1997 UBC and the IBC 2000. Introduction The Building Performance Research Institute s mission is primarily one of education on building safety and performance.

More information

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617)

Code Requirements for Existing Buildings. R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) Code Requirements for Existing Buildings R. W. Sullivan, Inc. 529 Main St., Suite 203 Charlestown, MA (617) 523-8227 www.rwsullivan.com R.W. Sullivan Engineering (RWS) was established in 1945 and currently

More information

2015 IBC Accessible Means of Egress

2015 IBC Accessible Means of Egress 2015 IBC Accessible Means of Egress Based on the 2015 International Building Code Description Upon completion, the participant will be able to apply the accessible means of egress provisions of Section

More information

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION

Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Chapter 4-16 SPECIAL DESIGN STANDARDS FOR TYPE V CONSTRUCTION Sections: 4-16-01 PURPOSE 4-16-02 APPLICABLE AREA 4-16-03 CONSTRUCTION AND OCCUPANCY 4-16-04 UPPER BUILDING AREA, HEIGHT, NUMBER OF STORIES

More information

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT

SPARTANBURG COUNTY BUILDING CODES DEPARTMENT SPARTANBURG COUNTY BUILDING CODES DEPARTMENT PLAN REVIEW CHECK LIST REQUIREMENTS FOR COMMERCIAL BUILDING PERMITS Plan Review Coordinator Kris Brannon 864-596-3180 366 N. Church St Room 500 Spartanburg,

More information

UBC. (1997 Edition) (p.1-116) 2-hr. shaft required for

UBC. (1997 Edition) (p.1-116) 2-hr. shaft required for Protection of Shaft Enclosures (Exit Stairs) Protection of Shaft Enclosures (Other Shafts) Comparison on Fire Safety Provisions* (Revised 2/28/03) (S) = Small difference in fire protection, (M) = Moderate

More information

ICC CODE CORNER 2012 IFC Code & Commentary

ICC CODE CORNER 2012 IFC Code & Commentary Chapter 10: Means of Egress General Comments The general criteria set forth in Chapter 10 regulating the design of the means of egress are established as the primary method for protection of people in

More information

Occupancy classification. Ancillary use areas shall be individually classified in accordance with Section

Occupancy classification. Ancillary use areas shall be individually classified in accordance with Section 3. Assembly areas that are accessory to Group E occupancies are not considered separate occupancies except when applying the assembly occupancy requirements of Chapter 11. 4. Accessory religious educational

More information

EXIT ACCESS RAMP. An interior ramp that is not a required interior exit ramp.

EXIT ACCESS RAMP. An interior ramp that is not a required interior exit ramp. Coordination with language throughout code 10/05/2011 Stair vs. stairway Repetitive language with stairways and ramps Including ramps when applicable The locations for stair, stairway and ramp as used

More information

ACCESSIBLE REST ROOM Code Requirements

ACCESSIBLE REST ROOM Code Requirements ACCESSIBLE REST ROOM Code Requirements Applicable Code References (Effective December 31, 2005) (Amendments effective August 1, 2009) 2003 International Building Code portion of the 2005 State Building

More information

FS , 712, 713, 714

FS , 712, 713, 714 VERTICAL OPENINGS STUDY GROUP REPORT TO CTC MEETNG CHICAGO, IL JUNE 28-29, 2012 PUBLIC COMMENTS CTC Code Change Proposal FS50-12 was Approved as Modified as shown below - No public comments for the Group

More information

MARBLEHEAD FIRE DEPARTMENT Standard Operating Guideline Draft for Photovoltaic/Solar Installations

MARBLEHEAD FIRE DEPARTMENT Standard Operating Guideline Draft for Photovoltaic/Solar Installations TOWN OF MARBLEHEAD FIRE DEPARTMENT Marblehead Fire Department Installation Guidelines for Photovoltaic/Solar installations July 1, 2015 Updated December 2015 MARBLEHEAD FIRE DEPARTMENT Standard Operating

More information

2015 International Fire Code

2015 International Fire Code 1001, 1001.1, 1001.2, 1002, [BE] 1002.1, 1003, [BE] 1003.1, [BE] 1003.2, [BE] 1003.3, [BE] 1003.3.1, [BE] 1003.3.2, [BE] 1003.3.3, [BE] 1003.3.4, [BE] 1003.4, [BE] 1003.5, [BE] 1003.6, [BE] 1003.7, 1004,

More information

CHAPTER 6 TYPES OF CONSTRUCTION

CHAPTER 6 TYPES OF CONSTRUCTION CHAPTER 6 TYPES OF CONSTRUCTION SECTION 61 GENERAL 61.1 Scope. The provisions of this chapter shall control the classification of buildings as to type of construction. SECTION 62 CONSTRUCTION CLASSIFICATION

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER PRESCRIPTIVE COMPLIANCE METHOD 3 SECTION 301 GENERAL 301.2 Building materials. Building materials shall comply with the requirements of this section. 301.2.1 Existing materials. Materials already

More information

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e

E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e I N D E X E d u c a t i o n a l S e m i n a r s f o r B u i l d i n g & R e s i d e n t i a l C o d e Title Course Number *Seminar Length (days) Pg. Class Scheduling Policies 8 International Building Code

More information

IBC GENERAL. Code Change No: G4-06/07. Original Proposal

IBC GENERAL. Code Change No: G4-06/07. Original Proposal DOCUMENTATION IBC GENERAL Code Change No: G4-06/07 Original Proposal Sections: 112.1, 1612.3, 3109.4.1.8, 3202.1.2, 3202.3.4, 3202.4, 3303.6, 3306.2 (IEBC [B] 1401.6.1), 3308.1(IEBC [B] 1403.1), 3409.9

More information

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1

2015 IBC Update. Copyright 2014 International Code Council #1000PDF15 1 Goal 2015 IBC Update Based on the International Building Code (IBC ) The goal is to familiarize building officials, fire officials, plans examiners, inspectors, design professionals, contractors, and others

More information

OFFICE OF EDUCATIONAL FACILITIES FLORIDA BUILDING CODE SECTION 423 APPLICATION MATRIX

OFFICE OF EDUCATIONAL FACILITIES FLORIDA BUILDING CODE SECTION 423 APPLICATION MATRIX 423.1 Scope: Public educational facilities 423.2 Public schools and community colleges general requirements 423.2.1 Owner 423.2.2 Exemption from local requirements 423.2 Code enforcement 423.3.1 School

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

Overview of Revised School Regulation

Overview of Revised School Regulation Office of the State Fire Marshal Overview of Revised School Regulation By: Timothee Rodrique Director, OSFM October, 2003 Training Effective Fire Prevention through Public Education Introduction! Purpose

More information

Fire Retardants and Truss Design. Overview

Fire Retardants and Truss Design. Overview Fire Retardants and Truss Design Overview Introduction Fire retardant treatments (FRT) were developed to be applied to building materials, such as dimension lumber (FRTW) and plywood, to reduce the ability

More information

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO:

APPLICATION NUMBER:, TAX MAP KEY: STREET ADDRESS:, PRPOJECT: APPLICANT:, PHONE NO: MAILING ADDRESS:, FAX NO: COUNTY OF KAUAI BUILDING DIVISION, DEPARTMENT OF PUBLIC WORKS 4444 RICE STREET, SUITE 175, LIHUE, HAWAII 96766 Telephone: (808) 241-6655 Fax Number: (808) 241-6806 BUILDING CODE COMMERCIAL CHECKLIST APPLICATION

More information

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R.

COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. COMMUNITY RISK REDUCTION BUREAU MANUAL CODE REQUREMENTS 423.7 TEMPORARY TENTS AND MEMBRANE STRUCTURES EFFECTIVE: APRIL 1, 2016 AUTHORIZED: R. Pearce SCOPE This policy applies to temporary tents, air-supported,

More information

TEMPORARY MEMBRANE STRUCTURES, TENTS AND CANOPIES Created July 2005, Revised January 2012

TEMPORARY MEMBRANE STRUCTURES, TENTS AND CANOPIES Created July 2005, Revised January 2012 TEMPORARY MEMBRANE STRUCTURES, TENTS AND CANOPIES Created July 005, Revised January 01 COLORADO SPRINGS FIRE DEPARTMENT Division of the Fire Marshal If you have any questions or comments regarding the

More information

Chapter 1: Application and Administration

Chapter 1: Application and Administration Chapter 1: Application and Administration General Comments This chapter provides provisions regarding the purpose, scope, application, and administration of subsequent requirements of ICC 500. In addition

More information

WINDOW AND DOOR REPLACEMENT SAMPLE PLAN

WINDOW AND DOOR REPLACEMENT SAMPLE PLAN To aid in communication between yourself, the inspectors, and the plans examiners, we have prepared this sample plan to assist in the preparations of your plan for window and door replacement. Follow the

More information

Approved Items IBC-Means of Egress

Approved Items IBC-Means of Egress Important Changes to the 2018 IBC for R-2 (Apartments) Green - Favorable Action for Multifamily Construction Red - Unfavorable Action for Multifamily Construction Yellow - Item of interest to Multifamily

More information

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E.

Learning Objectives. Copyright Materials MULTI STORY WOOD FRAMED BUILDINGS. Prepared for Wood Products Council. Presented by James E. Churchill, P.E. NONSTRUCTURAL PROVISIONS FOR MULTI STORY WOOD FRAMED BUILDINGS 2010 CALIFORNIA BUILDING CODE (CBC ) Prepared for Wood Products Council WoodWorks Presented by James E. Churchill, P.E. Churchill Engineering,

More information

INTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004

INTERNATIONAL BUILDING CODE - ADOPTION AND AMENDMENTS Effective July 1, 2004 CITY OF MERCER ISLAND 9611 SE 36 th Street, Mercer Island, Washington 98040-3732 PHONE (206) 236-5300 FAX (206) 236-3645 TDD (206) 232-9598 www.ci.mercer-island.wa.us INTERNATIONAL BUILDING CODE - ADOPTION

More information

CONSTRUCTION TECHNOLOGY UPDATE

CONSTRUCTION TECHNOLOGY UPDATE CONSTRUCTION TECHNOLOGY UPDATE No. 78, September 2011 Building Egress Using Photoluminescent Markings by Noureddine Benichou and Guylene Proulx The use of photoluminescent material systems in buildings

More information

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1%

CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE 01. GENERAL ADMINISTRATION 6% Project Administration 1% CALIFORNIA COMMERCIAL BUILDING INSPECTOR CONTENT OUTLINE EXAM ID: I1 80 multiple-choice questions 3-1/2-hour time limit Open book 01. GENERAL ADMINISTRATION 6% 0101. Project Administration 1% Verify that

More information

IBC Significant Changes Summary Tier I

IBC Significant Changes Summary Tier I 2009-2015 IBC Significant Changes Summary Tier I 503 General Building Height & Area Limitations Methods for determining allowable heights and areas have been dramatically revised and reformatted to improve

More information

SITE PLAN CRITERIA FOR MUNICIPAL SOLID WASTE & RECYCLABLES STORAGE & ENCLOSURE REQUIREMENTS

SITE PLAN CRITERIA FOR MUNICIPAL SOLID WASTE & RECYCLABLES STORAGE & ENCLOSURE REQUIREMENTS SITE PLAN CRITERIA FOR MUNICIPAL SOLID WASTE & RECYCLABLES STORAGE & ENCLOSURE REQUIREMENTS April 2009 General Solid Waste and Recycling Service Responsibilities: The City of Denton is the exclusive provider

More information

E2-09/ (IFC [B] )

E2-09/ (IFC [B] ) Code Technology Committee 2010 Final Action Agenda The following are code changes and public comments to be considered at the 2010 Dallas Final Action Hearings that are related to the CTC Area of Study

More information

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs

2015 IBC Inspection of Fire-Resistance Rated Floors, Ceilings and Roofs Class Outline Inspection of Fire-Resistance-Rated Floors, Ceilings and Roofs Based on 2015 International Building Code, (IBC ) Introduction Determining fire resistance Test standards Definitions Alternate

More information

What is a Won-Door FireGuard Door?

What is a Won-Door FireGuard Door? What is a Won-Door FireGuard Door?. A horizontal sliding accordion fire door that meets all IBC requirements for use in a means of egress and has fire ratings up to 3 hours. A Reference Guide to special

More information

PRESCRIPTIVE COMPLIANCE METHOD

PRESCRIPTIVE COMPLIANCE METHOD CHAPTER 3 PRESCRIPTIVE COMPLIANCE METHOD [B] SECTION 301 GENERAL 301.1 Scope. The provisions of this chapter shall control the alteration, repair, addition and change of occupancy of existing structures,

More information

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard.

NOTE: Some guidance on a performance approach to natural ventilation systems design is provided in the Supplement to this Standard. 19 SECTION 3 NATURAL VENTILATION 3.1 SCOPE OF SECTION This Section specifies the means of achieving the quantity of outdoor air required in a naturally ventilated enclosure. The provisions described include

More information

IBC FIRE SAFETY. Code Change No: FS1-07/08. Original Proposal SECTION 702 DEFINITIONS

IBC FIRE SAFETY. Code Change No: FS1-07/08. Original Proposal SECTION 702 DEFINITIONS DOCUMENTATION IBC FIRE SAFETY Code Change No: FS1-07/08 Sections: 702.1, 704.8.2, 706.7 Proponent: Philip Brazil, PE, Reid Middleton, Inc., representing himself SECTION 702 DEFINITIONS 702.1 Definitions.

More information

One and Two Family Additions

One and Two Family Additions One and Two Family Additions An addition to a house, duplex, garage, or an accessory structure requires a building permit prior to performing any construction. Building Department & Permit Office Mon-Fri

More information

FIRE AND SMOKE PROTECTION FEATURES

FIRE AND SMOKE PROTECTION FEATURES CHAPTER 7 FIRE AND SMOKE PROTECTION FEATURES SECTION 70 GENERAL 70. Scope. The provisions of this chapter shall govern the materials, systems and assemblies used for structural fire resistance and fire-resistance-rated

More information

City of Valdosta Land Development Regulations

City of Valdosta Land Development Regulations Section 210-3 Urban Commercial Corridor Overlay District (A) Purpose. The purposes of the Urban Commercial Corridor Overlay District are to: (1) Promote the general health, safety, and welfare of the community.

More information

AIR CRE Industrial Building Standards

AIR CRE Industrial Building Standards AIR CRE Industrial Building Standards Established March 1993 AIR CRE 500 N Brand Blvd, Suite 900, Glendale CA, 91203 AIR CRE INDUSTRIAL BUILDING STANDARDS TABLE OF CONTENTS SECTION 1 Introduction P. 1

More information

Section 1 OBC FADS /13 Access to Parking Areas

Section 1 OBC FADS /13 Access to Parking Areas Section 1 OBC 3.8.2.2 4.3.12/13 Access to Parking Areas A barrier-free path of travel is provided from: a) the entrance to the exterior parking area b) at least one parking level where a passenger elevator

More information

780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES

780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES 780 CMR CHAPTER 34 EXISTING BUILDINGS STRUCTURES SECTION 3401 GENERAL 3401.1 Scope. Chapter 34 of the International Building Code 2009 is deleted in its entirety. The provisions of the International Existing

More information

HIGH PILED COMBUSTIBLE STORAGE CITY OF NOVI SUBMITTAL CHECKLIST In Accordance with Chapter 23 of the 2006 International Fire Code

HIGH PILED COMBUSTIBLE STORAGE CITY OF NOVI SUBMITTAL CHECKLIST In Accordance with Chapter 23 of the 2006 International Fire Code Project Name/Tenant: HIGH PILED COMBUSTIBLE STORAGE CITY OF NOVI SUBMITTAL CHECKLIST In Accordance with Chapter 23 of the 2006 International Fire Code Site Address: Applicant: Phone: Bldg/Unit/Suite: A

More information

Responsibilities: Effective Date: November Revision Date: January 27, VP, Facilities and Construction Management

Responsibilities: Effective Date: November Revision Date: January 27, VP, Facilities and Construction Management Title: Fire Safety Requirements for Interior Finish Materials Procedure Effective Date: November 2005 Revision Date: January 27, 2017 Issuing Authority: Responsible Officer: VP, Facilities and Construction

More information

Fire Inspection and Code Enforcement, 7 th Edition. Chapter 6 Building Construction: Components Inspector II

Fire Inspection and Code Enforcement, 7 th Edition. Chapter 6 Building Construction: Components Inspector II Fire Inspection and Code Enforcement, 7 th Edition Chapter 6 Building Construction: Components Today we will Discuss fire walls, party walls, fire partitions, and curtain walls Discuss roof types and coverings

More information

Commercial Remodel Permit

Commercial Remodel Permit Commercial Remodel Permit Zoning requirements Staff recommends always verifying the zoning requirements for your project before deciding to build. Warrensburg has eleven separate zoning districts, each

More information

Q. Do residential and historical buildings that are going to be protected with sprinklers need to conduct an LSE?

Q. Do residential and historical buildings that are going to be protected with sprinklers need to conduct an LSE? TECHNICAL AND CODE INTERPRETATION QUESTIONS: Q. For evaluation and scoring purposes, the Rules distinguish between Residential and Commercial occupancies. In terms of the referenced sections of the Chicago

More information

Chapter 11. Dwelling Units and Sleeping Units

Chapter 11. Dwelling Units and Sleeping Units 1101 General Chapter 11. Dwelling Units and Sleeping Units 1101.1 Scoping. Dwelling units and sleeping units required by the scoping provisions adopted by the administrative authority to be Accessible

More information

RS-2 District Schedule

RS-2 District Schedule District Schedule 1 Intent The intent of this Schedule is primarily to maintain the single-family residential character of the District, but also to conditionally permit laneway houses and in some instances

More information

Commercial Plans Application Checklist

Commercial Plans Application Checklist Botetourt County, Virginia Development Services Construction Compliance 5 West Main Street, Suite 100 Fincastle, Virginia 24090 Phone: (540) 473-8248 Fax: (540) 473-2018 www.botetourtva.gov Commercial

More information

Permit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department:

Permit Requirements: Building Codes: The City of Clanton has adopted the following codes which are enforced by the Building Department: Permit Requirements: Any owner, authorized agent, or contractor who desires to construct, enlarge, alter, repair, move, demolish, or change the occupancy of a building or structure, or to erect, install,

More information

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL

PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL FIRE DEPARTMENT 10573 E Stockton Blvd. Elk Grove, CA 95624 (916) 405-7100 Fax (916) 685-6622 www.yourcsd.com PLAN SUBMITTAL REQUIREMENTS - ARCHITECTURAL I Purpose To advise architects, engineers and contractors

More information

Report on First Revisions with Statement June 2014 NFPA 5000

Report on First Revisions with Statement June 2014 NFPA 5000 5000 FR704 BLD-BSY (Chapter 12) Recommendation: 54.5 Elevator Machine/Control Rooms and Machinery/Control Spaces. Elevator machine/control rooms and machinery/control spaces that contain solid-state equipment

More information

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X

READ ONLY. Adopting Agency BSC SFM. Adopt Entire Chapter X X X Adopt Entire Chapter as amended (amended sections listed below) X X X X X X CALIFORNIA PLUMBING CODE MATRIX ADOPTION TABLE CHAPTER 9 - VENTS (Matrix Adoption Tables are non-regulatory, intended only as an aid to the user. See Chapter 1 for state agency authority and building application.)

More information

FCIA Webinar Gypsum Wall Patching

FCIA Webinar Gypsum Wall Patching FCIA Webinar Gypsum Wall Patching Firestop Contractors International Association Hillside, IL +1-708-202-1108 - office Bill McHugh bill @ fcia.org Nestor Sanchez, USG Corp. nsanchez@usg.com DIIM Firestopping

More information