GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D
|
|
- Gordon Booth
- 6 years ago
- Views:
Transcription
1 GST001 MV/LV TRANSFORMERS LOCAL SECTION CELG D In addition on what specified in the common part, the following requirements are prescribed: 3.1 LAWS Portaria INMETRO 378/2010 Requisitos de Avaliação da Conformidade para Transformadores de Distribuição em Líquido Isolante. Portaria Interministerial 104/2013 Regulamentação Específica de Transformadores de Distribuição em Líquido Isolante do Ministério de Minas e Energia. 3.3 LOCAL STANDARDS ABNT NBR 5440 E-MT-022 Transformadores para redes aéreas de distribuição - Requisitos. Especificación Técnica de Transformadores de Distribución: Fórmulas para Evaluación Económica INSTALLATION Mouting System Company Single-Pole Double-Pole Surface Level CELG 300 Not used Not used Table 1 Mounting System 5.12 LOSSES, SHORT CIRCUIT IMPEDANCES AND SOUND POWER LEVELS The losses shall be in compliance with E-MT TANK The active part, which is mounted to the tank walls, should have devices (hooks, holes, or others) that facilitate its removal and placement. These devices should be symmetrical and guarantee lifting without horizontal movement; and they should be different from the tank fastening supports. 6.4 INSULATING LIQUID AND MATERIAL The oil should have the following characteristics: GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 1
2 CHARACTERISTICS UNIT Appearance - VALUES Minimum Maximum The oil should be clear, free of suspended matter or sediment. Density 20/4 C - 0,861 (N) - 0,900 (N) 0,860 (P) Kinematic viscosity: 20 C - 25,0 (2) 40 C mm 2 /s - 11,0 (N) 12 (P) 100 C - 3,0 Fire point C 140,0 - Pour point C - -39,0 Neutralization index mg KOH/g - 0,03 Interfacial tension 25 C mn/m 40,0 - Color ASTM - - 1,0 Teor de água mg/kg - 25,0 Chlorides - Absent Sulfates - Absent Corrosive sulfur - Absent Dielectric strength kv 30,0 - Dielectric Loss Factor 100 C - 0,60 or % Dissipation Factor 90 C (3) - 0,50 Oxidation stability: - Neutralization index mg KOH/g - 0,40 -Borra % mass - 0,10 - Dissipation Factor 90 C (4) % - 20,0 Oxidation inhibitor content DBPC/DBP % mass 0,27 0,33 Percentage of carbons % To write Polychlorinated biphenyls (PCB) mg/kg Not detectable Total particle count / 10 ml (15000 / 100 ml) DBDS Content (dibenzyl -disulfide) mg/ml Not detectable (N) Naphthenic (P) Paraffinic Table 2 Insulating Liquid SOLID INSULATING MATERIAL The solid insulating material, of heat stable paper (equal or higher than Class E 120º C) will be required. GASKETS Seal materials of transformers should be nitrite rubber or higher, in accordance with ASTM D297, ASTM D2240 and ASTM D471. WEIGHT The maximum weights to transformers admitted are: Rated power 150 kva: 750 kg Rated power > 150 kva: 1200 kg GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 2
3 6.5 BUSHINGS The LV bushing must be located with Figure 4 and 5. The bushings should have the following characteristics: Rated Power (kva) Maximum Low Voltage (V) 380 Bushing Bushing Type 1,3/160 1,3/160 T1 75 1,3/400 1,3/160 T1 112,5 1,3/400 1,3/400 T ,3/800 1,3/400 T ,3/800 1,3/800 T3 Table 3 Bushings Type The bushings for single-phase transformers should be T1 1,3/160 A. The bushings should have the characteristics of Figure 10 and 11. Phase Markings and Identification The sequence for each phase of the distribution transformer should be marked. The identification should be engraved in high relief or bas-relief. During the draft approval stage, details for the required markings and identification will be indicated. 6.6 DE-ENERGIZED TAP-CHANGER The DETC will be located on the tank side and at the low voltage side installed to ensure tightness. The lid switch must be fixed to the tank in order to be unmissable SUPPORTING The mounting support for single-pole mounted transformer is also detailed in table below. Company Positon of the bracket Rated Power CELG Fixing bracket in the LV side All power values Table 4 Position of the Bracket GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 3
4 6.9 PAINTING The color is Munsell N ACCESSORIES Each transformer shall be provided with the accessories as indicate: Accessory Rated Power 300 kva Lifting and blocking devices X Oil drain and sampling plug or valve - Thermometer pocket - Over pressure valve X Oil level indicator - Supports for surge arresters X Earthing terminals X Rating plate X Table 5 Accessories LIFTING AND BLOCKING DEVICES Transformer shall be provided with Two hooks located in the top part of the tank. The hooks will allow fastening the suspension of the transformer, in such way as not to damage the bushing insulators of the terminals and accessories and ensure the suspension of the transformer in a horizontal position. Hook Lifting of the Active Part Two eyebolts or hooks designated for machine detanking shall be located on the structure of the active part. The eyebolts will allow fastening in such a way so as not to damage the bushing insulators of the terminals and ensure detanking with the cover in a horizontal position OIL LEVEL INDICATOR Internal marking paint in the tank SUPPORT FOR SURGE ARRESTER The transformer must be provided of a support (one each phase) for the installation of medium voltage arresters. The structures may be welded to the tank. The surge arresters are not considered in the supply EARTHING TERMINALS The transformers shall have a grounding connector, detailed in Figure below. GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 4
5 Figure 1 Grounding Connector RATING PLATES AND PLATE-HOLDERS The nameplate language shall be in Portuguese. Additional to data requested in IEC standard must be added: - Level noise; - Losses; - Winding material; - Serial number; - Purchase order number; - Date of manufacture (Day, Month, Year). The rating plates should have the following characteristics: GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 5
6 Figure 2 Rating Plates Single-phase Transformer GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 6
7 Figure 3 Rating Plates Three-phase Transformer CRITERIA FOR TYPE AND SPECIAL TESTS Type tests The selection of samples for type tests shall be two units by type of transformer. The rated power will be on agreement with the Distribution Company. Special Test Short-circuit test. The sample shall be one unit by type of transformer. The rated power will be on agreement with the Distribution Company SPECIAL TESTS Test for support fixed to tank (ABNT NBR 5440). 10 TRANSPORT AND PACKING The equipment should be individually packed onto treated wood or plastic pallets in a way suitable for transport, in such a way as to avoid any damage to equipment. The packing should be suitable for GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 7
8 introducing equipment into standard transport industry containers. All additional elements of the equipment should be packed into a single crate. Transformers should be transported with their complete oil load and accessories in place. The transformer should be completely secured in its packaging. Wood should be treated according to international plague control requirements, avoiding compounds dangerous to human health or the environment, such as pentachlorophenol and creosote. The treatment should consider at least: high toxicity to xylophagous organisms, high penetrability and staying power, chemical stability, and substances which are non-corrosive to metals and which do not affect the physical characteristics of wood. A visual inspection of the equipment will be carried out upon receiving it, checking for possible damage occurred during transport and the warehousing process. 12 FIGURES Figure 4 Single-phase Transformer GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 8
9 Figure 5 Three-phase Transformer GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 9
10 Figure 6 Supporting Single-phase Transformer Figure 7 Supporting Three-phase Transformer Figure 8 Reinforcement for Three-phase Transformer With P 225 kva GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 10
11 Figure 9 MV Bushings GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 11
12 Figure 10 LV Bushings (T1) GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 12
13 Figure 11 LV Bushings (T2 and T3) GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 13
14 COMMON LIST GS Type Code Distribution Company and Country Country Code Rated Power (kva) Rated MV (kv) Volt. Reg. (steps number x step%) GO - Brazil ,97-3x4,35% GO - Brazil ,97-3x4,35% GO - Brazil ,5 7,97-3x4,35% GO - Brazil ,97-3x4,35% GO - Brazil ,97-3x4,35% GO - Brazil ,5 19,97-3x4,35% GO - Brazil ,8-3x4,35% GO - Brazil ,8-3x4,35% GO - Brazil ,5 13,8-3x4,35% GO - Brazil ,8-3x4,35% GO - Brazil ,8-3x4,35% GO - Brazil ,5-3x4,35% GO - Brazil ,5-3x4,35% GO - Brazil ,5 34,5-3x4,35% GO - Brazil ,5-3x4,35% GO - Brazil ,5 34,5 GO - Brazil ,5 13,8 +2X2,5% -1X2,5% +2X2,5% -1x2,5% Rate d LV (kv) 440/ 440/ 440/ 440/ 440/ 440/ MV insulation level Um/LI/AC (kv) F (Hz) N. of phases 1P, 2P, 3P Connection Symbol Zsc (%) MV bushing type MV Minimum creepage distance (mm) LV bushing type Losses classes or max values 15/95/ P 2,5 Sol Sol. 8 Value Load Loss (W) No Load Loss (W) Noise level Sound Power (db) Wheels (Yes/No) Overall dimensions HxLxW (mm) No 1200x800x x800x 15/95/ P 2,5 Sol Sol No Value x800x 15/95/ P 2,5 Sol Sol No Value x800x 36/150/ P 3,0 Sol Sol No Value x800x 36/150/ P 3,0 Sol Sol No Value x800x 36/150/ P 3,0 Sol Sol No Value x /95/ P Dyn1 3,5 Sol Sol No Value x x /95/ P Dyn1 3,5 Sol Sol No 1300x /95/ P Dyn1 3,5 Sol Sol No 1300x /95/ P Dyn1 3,5 Sol Sol No 1800x /95/ P Dyn1 4,5 Sol Sol No Value x x /150/ P Dyn1 4,0 Sol Sol No 1600x /150/ P Dyn1 4,0 Sol Sol No 1600x /150/ P Dyn1 4,0 Sol Sol No 1600x /150/ P Dyn1 4,0 Sol Sol No 1600x /150/ P Dyn1 4,0 Sol Sol No 1300x /95/ P Dyn1 3,5 Sol Sol No Painting Brackets for pole (Yes/No) Brackets for arrester (Yes/No ) GST001 - Local Section CELG D Normatização Técnica e Desenhos de Rede 14
Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK
Dr B Pahlavanpour Senior Techncal Co-ordinator Nynas Naphthenics LTD UK IEC specification and maintenance guide for mineral insulating oil Dr B Pahlavanpour Nynas Naphthenics Ltd UK Three Important oil
More informationB. Provide liquid-filled secondary substation transformers as indicated on drawings.
SECTION 26 12 13 PART 1 - GENERAL 1.01 WORK INCLUDED A. Comply with the provisions of Sections 26 05 00. B. Provide liquid-filled secondary substation transformers as indicated on drawings. 1.02 RELATED
More informationSUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS PART I TENDER PROCEDURES
SUPPLY AND DELIVERY OF 200KVA EARTHING TRANSFORMER TENDER DOCUMENTS: SARAWAK ENERGY REF. NO. PLS-160091 PART I TENDER PROCEDURES SECTION 1 INTRODUCTION This Introduction should be read in conjunction with
More informationOil Diagnostics - Test Information
Oil Diagnostics - Test Information For both financial and operational reasons it is very important that transformers are managed efficiently. Optimising the future management of large transformers on networks
More informationThe complete guide to transformers and packaged substations
LAND LOGICAL POWER The complete guide to transformers and packaged substations Contents Land Logical Power transformers An introduction to the complete range of Land Logical Power transformers and package
More informationCONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977
CONSOLIDATED EDISON COMPANY OF NEW YORK, INC. 4 IRVING PLACE NEW YORK, NY 10003 ORANGE & ROCKLAND UTILITIES 390 WEST ROUTE 59 SPRING VALLEY, NY 10977 DISTRIBUTION ENGINEERING DEPARTMENT SPECIFICATION EO-5015
More informationSECTION MEDIUM VOLTAGE TRANSFORMERS
PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions, apply to this Section. 1.2 SUMMARY A. This Section includes the
More informationTechnical Specification for 24kV Cable Entry Transformers
Ergon Energy Corporation Limited Technical Specification for 24kV Cable Entry ETS02-03-02 Specification ETS02-03-02 Ver 6 Contents 1. Purpose and Scope... 1 2. References... 1 2.1 Applicable Standards...
More informationSECTION N EQUIPMENT FOR SUBSTATION MAINTENANCE
Page 89 SECTION N INDEX DESCRIPTION PAGE - INSULATED MODULAR RITZGLAS SCAFFOLD 90 - MODULAR RITZGLAS SCAFFOLD - MAIN PARTS 91 - TRUCK MOUNTED INSULATED LADDER FOR HOT LINES UP TO 500 kv WITH ROTATION SUPPORT
More informationTitle: YALE OFFICE OF FACILITIES PROCEDURE MANUAL Chapter: 01 - Yale Design Standard Division: Electrical Standards
Change History Date Description of Change Pages / Sections Modified Change Approver Initials 6/15/16 Updated division section from 16124 to 2605 - mgl44 13, removed references to other section 10/17/14
More informationZ5028 E3/Ci80 Horizontal bracket Mounting instructions
Z5028 E3/Ci80 Horizontal bracket Mounting instructions Z5028 E3/Ci80 Horizontal bracket References in the manual CAUTION! IMPORTANT! Symbols on the equipment This refers to a potentially dangerous situation
More informationInstallation, Inspection and Maintenance of Dry Type Transformers
Dry Type TX 1 of 8 Installation, Inspection and Maintenance of Dry Type Page 1 of 8 Dry Type TX 2 of 8 Table Of Contents Page Number 1. General... 3 2. Installation... 3 3. Safety Inspections... 4 4. Safety
More informationGUJARAT ENERGY TRANSMISSION CORPORATION LTD. TECHNICAL SPECIFICATIONS. 66 kv LIGHTNING ARRESTORS
GUJARAT ENERGY TRANSMISSION CORPORATION LTD. SARADAR PATEL VIDYUT BHAVAN, RACE COURSE, BARODA 390 007. TECHNICAL SPECIFICATIONS FOR 66 kv LIGHTNING ARRESTORS GETCO/ENGG/TECH SPECI.- 66 KV LA/R4/Jan11 Sign
More informationSilicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc.
Silicone Dielectric Fluids Fredi Jakob, Karl Jakob, Nicholas Perjanik Analytical ChemTech International, Inc. I. Introduction Mineral oil based dielectric fluids have been used more extensively than other
More informationSECTION HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS
SECTION 26 22 13 HIGH EFFICIENCY DISTRIBUTION TRANSFORMERS PART 1 GENERAL 1.1 WORK INCLUDED A. Dry-type, low-voltage, distribution transformers meeting US Department of Energy proposed Candidate Standard
More informationELECTRONIC BALLASTS FOR FLUORESCENTS LAMPS NBR e NBR 14418
COMPLEMENT Doc: 704-CRC-002-ILM ELECTRONIC BALLASTS FOR FLUORESCENTS LAMPS NBR 14417 e NBR 14418 Review: 05 page: 1/5 Prepared by: João Damião Checked by: Vanessa Hernandes Approved by: Arnaldo Barbulio
More information9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA
9KV/18KV METAL OXIDE LIGHTNING ARRESTORS WITHOUT GAPS WITH STANDARD NOMINAL DISCHARGE CURRENT 5KA Technical specification for 9KV/18KV 5KA Metal oxide Lightning Arrestors without Gap. ----------------------------------------------------------------------------------------------------------------
More informationZ5010 (Version 2) TV spigot with fixing plate Mounting instructions
Z5010 (Version 2) TV spigot with fixing plate Mounting instructions Z5010 (Version 2) TV spigot with fixing plate References in the manual CAUTION! IMPORTANT! Symbols on the equipment This refers to a
More informationZ5033 E3 Ball joint adapter Mounting instructions
Z5033 E3 Ball joint adapter Mounting instructions Z5033 E3 Ball joint adapter References in the manual This refers to a potentially dangerous situation which may lead to personal injury. This refers to
More informationAn Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application
An Insight into Design, Development & Testing of Insulation Piercing Connectors for LV Application Introduction Designed for Indoor and outdoor applications Non-tension tap and splice applications Used
More informationroduct Scope: Substation
roduct Scope: Substation Three Phase or Single Phase, 50 or 60 Hz, 55ºC, 65ºC, 75ºC, 55ºC/65ºC, 55ºC/75ºC, 65ºC/75ºC Envirotemp FR3 fluid or Mineral Oil Three Phase: 300 12,000 kva Single Phase: 167 6,667
More informationUnderground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11
Underground Residential Distribution (Specifications for Installation) PES March 2008 Spec 11 Underground Residential Distribution (URD) Index General Discussion... 1-2 Description... 3-7 Drawings (Available
More informationThree-sided barrier compliant to DIN EN ISO Depending on location, design also as wind protection. Clear height (DH) Three-sided barrier
of 5 Page Car SingleVario 06 Stack Parker 06 50 for vehicle up to 5.00 m = 6 long (50 for vehicle up to 5.0 m 7 long) Depending on location, design also as wind protection. Product Data CONFORMITY 06/06/G63
More informationZ5043 MAX Horizontal bracket Mounting instructions
Z5043 MAX Horizontal bracket Mounting instructions Z5043 MAX Horizontal bracket References in the manual This refers to a potentially dangerous situation which may lead to personal injury. This refers
More informationBEST ONE SUBMERSIBLE SUMP PUMPS EPA. Page Features & Applications 100 Exploded View 101 Pump & Motor Specifications 102 Selection Chart / Type key 103
CONTENTS -SPECIFICATIONS Page Features & Applications 100 Exploded View 101 Pump & Motor Specifications 102 Selection Chart / Type key 103 -PERFORMANCE CURVES Performance Curve Best One 200 Performance
More informationCCC Services for oil-filled- and XLPE-Cable Systems
sc CCC Services for oil-filled- and XLPE-Cable Systems Service Programme for Cable Systems As a supplier of MV- and HV-cable systems with several decades of experience, CCC GmbH Berlin offers the full
More informationSurge arrester 3EB4. with polymeric composite housing for operating aboard traction units
Transmittal, reproduction, dissemination and/or editing of this document as well as utilization of its contents and communication thereof to others without express authorization are prohibited. Offenders
More informationRead Only Copy Not For Distribution. Chapter 17. Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.2 QUANTITY OF WATER REQUIRED
Chapter 17 Private Potable Water Supply Systems 17.1 GENERAL REGULATIONS 17.1.1 Applicability The regulations in this chapter apply to any private potable water supply system where plumbing fixtures are
More informationNorth Eastern Electricity Supply Company of Odisha Limited
page-1 North Eastern Electricity Supply Company of Odisha Limited SECTION IV (B) TECHNICAL SPECIFICATIONS OF 33/.4 KV 100 KVA DISTRIBUTION TRANSFORMERS Tender No. : NESCO/DEPOSIT/13 Date: 02.01.13 GROUP-
More informationREQUEST FOR PROPOSAL 18/24/30 MVA 138 kv to kv 3φ Power Transformers with LTC WEATHERFORD MUNICIPAL UTILITY SYSTEM
REQUEST FOR PROPOSAL 18/24/30 MVA 138 kv to 13.09 kv 3φ Power Transformers with LTC WEATHERFORD MUNICIPAL UTILITY SYSTEM SECTION I - SCOPE A. The Weatherford Municipal Utility System invites qualified
More informationUFGS (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS
USACE / NAVFAC / AFCEC / NASA UFGS-26 35 33.00 40 (August 2013) --------------------------------- Preparing Activity: NASA Superseding UFGS-26 35 33.00 40 (August 2010) UNIFIED FACILITIES GUIDE SPECIFICATIONS
More informationOver pressure Switching pressure difference (typical) Lower range Upper range
Allfluid pressure switches electromechanical actuated -... 63 bar, G/2 For Ex zones and 2 (gases) as well as Ex zones 2 and (dusts) category II2G, type of protection EEx de IIC T6 Microswitch with gold
More informationCOMPLEMENT. Switches for Electrical Fixed Installations for household and similar purposes
COMPLEMENT Doc: 702-CRC-003-E Revision: 07 Page: 1/8 Elaborated by: Nelson Coelho/ Douglas Ferreira Checked by: Vanessa Hernandes Approved by: Nelson Coelho Approval date: 21/07/2016 1 OBJECTIVE This document
More informationDetails of technical leaflets/write-up on various pieces of equipment.
Details of technical leaflets/write-up on various pieces of equipment. (1) Insulator Designs: The insulators are provided in one, two, three, or four insulator designs per location and spaced to provide
More informationGeneral Requirements. Technical Specifications for Insulators of Transmission Lines
Islamic Republic of Iran Vice Presidency for Strategic Planning and Supervision General Technical Specification and Execution Procedures for Transmission and Subtransmission Networks Insulators of Transmission
More informationDRUM MOTOR 138LS 138.5Ø 0.10kW kW, with steel helical gearbox
8 DRUM MOTOR DRUM MOTOR 18LS 18.5Ø 0.10kW - 1.00kW, with steel helical gearbox Product description The drum motor 18LS is a very fl exible component thanks to the wide range of powers and speeds. Characteristics
More informationNEUTRAL GROUNDING TRANSFORMERS INSTALLATION AND MAINTENANCE INSTRUCTIONS
1 Table of Contents SECTION 1 Unpacking... 3 1.1 Shipping... 3 1.2 Receiving... 3 SECTION 2 Installation... 3 SECTION 3 Inspection... 4 SECTION 4 Connection... 4 4.1 Neutral Lead... 5 4.2 Ground Lead...
More informationABB Brasil. Power Transformers: Life Cycle and Operational Cost Optimization Electrical Sector Deregulation and Impacts. Power Products Division
LIMA PE Jornadas Técnicas 2015 2015Abr23 Dr. José Carlos Mendes Gte Tecnologia Transmissão e Produtos de Potência Gte Desenvolvimento & Engenharia Engenheiro Corporativo Executivo Global ABB Asea Brown
More informationNPS/002/020 Technical Specification for 11 & 20kV Power Cables
Version:- 3.1 of Issue:- Nov - 09 Page 1 of 11 NPS/002/020 Technical Specification for 11 & 20kV Power Cables 1. Purpose The purpose of this document is to detail Northern Powergrid (the Company) requirements
More informationTESTING PTE EARTHING
1 SCOPE This section of the Power Systems Live Working Manual details the procedures to be followed to achieve Safety from the System when carrying out examination, testing and remedial work on PTE (Pole
More informationLife Extension by Refurbishment of Transformers
Life Extension by Refurbishment of Transformers C. JAYASENAN by and SHIRISH KANUNGO SIEMENS, India SIEMENS, India c.jayasenan@siemens.com Shirish.Kanungo@siemens.com 1 6th International Conference on Large
More information- CONSTRUCTIONS 300 SECTIONAL VIEW DRAWING 300 SECTIONAL VIEW TABLE 301 QUANTITY FOR MODEL 302 MECHANICAL SEAL and BEARINGS 303
CONTENTS Page - SPECIFICATIONS 200 PERFORMANCE RANGE and SELECTION CHART 201 TYPE KEY 202 CURVE SPECIFICATIONS 203 PERFORMANCE CURVE 40 203 PERFORMANCE CURVE 80 204 - CONSTRUCTIONS 300 SECTIONAL VIEW DRAWING
More informationCannon Trident Connector System
These are low installed cost connectors rated for up to 13 A and 250 V ac. They are typically used for circuit board and internal wiring applications. Snap Together connectors facilitate easy assembly
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-BIPV-SM-P125-36
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More informationMonolithic Isolation Fittings
Monolithic Isolation Fittings The Industry s Dual O Ring Seal Standard Tests Include: 100% Hydrostatic Pressure & Electrical Tests 100% Ultrasonic of Welds 100% Magnetic Particle of Welds 100% Dye Penetrant
More informationElectric Service Standards
V: 1 of 6 A. Padmounted Requirements Complete requirements are contained in FPL specifications given to Customers for individual projects. Typical pad mounted transformer requirements include, but are
More informationUNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL
UNDERGROUND SERVICES - GENERAL SERVICE AND MULTI-UNIT RESIDENTIAL 8.01 GENERAL This material is not intended to cover service from OPPD s network in the downtown Omaha area. See Chapter 12 for details
More informationPHOTOVOLTAIC SOLAR ENERGY POLYCRYSTALLINE MODULES - SI-ESF-M-P156-60
Solar Innova uses the latest materials to manufacture photovoltaic modules. Our modules are ideal for any application that uses the photoelectric effect as a clean energy source because of its minimal
More informationSPECIA LT Y SEA LANT S
SPECIA LT Y SEA LANT S Novagard Flowable Sealants - 200 Series Description: Ideal for general industrial sealing and bonding applications requiring a flowable product, but retains enough thixotropy to
More informationMECKLENBURG COUNTY. Land Use and Environmental Service Agency Code Enforcement
MECKLENBURG COUNTY Land Use and Environmental Service Agency Code Enforcement Draft 11/17/08 Utility transformer issues began surfacing last year with questions of enforcement responsibilities due to utility
More informationProtection classification IP 23
TIG 180 AC/DC puls 290-020200-00000 TEAMWELDER TIG 180 AC/DC the specialist for aluminium welding TIG and MMA welding Ideal for aluminium: Optimum ignition and stabilisation of the alternating current
More informationMR 120/2015. SUPPLY OF 2 X 2MVA 415V/11kV 3 PHASE TRANSFORMERS
MR 120/2015 SUPPLY OF 2 X 2MVA 415V/11kV 3 PHASE TRANSFORMERS TRANSFORMER DETAILS: 2 x 2MVA 3Phase 11-6.3kV/415V YNd11 Transformer Voltage ratios: 11000-6.35/415volts Off circuit tapchanger, with tappings
More informationSECTION 07 TECHNICAL SPECIFICATIONS 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA)
SECTION 07 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO) GAPLESS LIGHTNING ARRESTER (LA) 7.0 TECHNICAL SPECIFICATIONS OF 11KV OUTDOOR TYPE SINGLE PHASE METAL OXIDE (ZNO)
More informationSPIRIT. Water purifier. Complete User Manual
SPIRIT Water purifier Complete User Manual Document No 822901692 Revision BB1522 Bluewater 2015 Contents INTRODUCTION...03 About this manual...03 Limited warranty...03 Environment information...03 Disposal...03
More informationSECTION SLUDGE HOLDING TANK DECANTER PUMP
PART 1 GENERAL 1.01 SCOPE OF WORK A. The Contractor shall furnish and install all materials, labor and equipment to put into service the Sludge Holding Tank Decanter Pumping System in accordance with the
More informationARRANGEMENT AND WORKING OF MULTIPORT FLOW SELECTOR VALVE IN PRODUCTION MANIFOLD:
GENERAL DESCRIPTION Crude oil well test manifold to be provide as Multiport Flow Selector (MPFS) technology. It provides a cost effective method for selecting and diverting well fluids from an individual
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationUnit Substation Transformer Construction Checklist (under 500 kva)
Unit Substation Transformer Checklist (under 500 kva) Building: Location: Submittal / Approvals Submittal. The above equipment and systems integral to them are complete and ready for functional testing.
More informationTechnical Specification for LV ABC Fuse Switch Disconnectors
Ergon Energy Corporation Limited Technical Specification for LV ABC Fuse ETS-06-02-02 Check this is the latest Process Zone version before use. Specification ETS 06-02-02 Ver 3 Contents 1. Purpose and
More informationTECHNICAL SPECIFICATION
UTTAR & DAKSHIN HARYANA BIJLI VITRAN NIGAM Specification No. CSC- XVIII/DH/UH/P&D/2009-2010 TECHNICAL SPECIFICATION FOR OUTDOOR TYPE SINGLE PHASE OIL IMMERSED COMPLETELY SELF PROTECTED DISTRIBUTION TRANSFORMERS
More informationAPEC 2016 Component Level Safety Certification in Systems- IEC /UL1577. MARK CANTRELL Senior Applications Engineer
APEC 2016 Component Level Safety Certification in Systems- IEC60747-17/UL1577 MARK CANTRELL Senior Applications Engineer 3/20/2016 Agenda What is safety isolation Isolation Concepts Regulatory Landscape
More informationTurbocharger / TPL-C Original assembly instructions English
Assembly Instructions Turbocharger / TPL-C Original assembly instructions English This document is valid for the TPL-C series: TPL79-C Purpose The assembly instructions explain how the ABB turbocharger
More informationSection ARMORED MEDIUM VOLTAGE CABLES SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR
PART 1 - GENERAL Section 26 05 15 SHIELDED 3 CONDUCTOR POWER CABLE - INTERLOCKED ARMOR 1.1 Cable shall be 15 kv, shielded, three conductor with ground, stranded copper, with continuously welded and corrugated
More informationLoading Arm Installation, Maintenance & Safety Manual
Loading Arm Installation, Maintenance & Safety Manual Version Loading Arm Hot Line: 1-800-547-9393 Dear OPW Customer: Thank you for selecting OPW Engineered Systems, Inc. ("OPW"), and giving us the opportunity
More information094: 2000 CEB STANDARD. MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA
094: 2000 CEB STANDARD MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEYLON ELECTRICITY BOARD SRI LANKA Specification for MEDIUM VOLTAGE PIN INSULATORS & HARDWARE (12kV & 36 kv) CEB Standard
More informationProduct Application. Prestige Power Post in White Epoxy Coated Aluminium Finish
Product Application 83 Prestige Power Post in White Epoxy Coated Aluminium Finish 84 Floor Distribution Technical Floor Distribution Technical 85 Range Technical Data Raised Floor Systems Interact Underfloor
More information- CONSTRUCTIONS 300 SECTIONAL VIEW 300 SECTIONAL TABLE 301 QUANTITY FOR MODEL 302 MECHANICAL SEAL 303 BEARINGS 304
CONTENTS Page - SPECIFICATIONS 200 PERFORMANCE RANGE and SELECTION CHART 201 TYPE KEY and CURVE SPECIFICATIONS 202 PERFORMANCE CURVE 40 203 PERFORMANCE CURVE 80 204 - CONSTRUCTIONS 300 SECTIONAL VIEW 300
More informationHIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61)
PART 1-GENERAL INTEGRALLY MOLDED FLANGED OUTLET (IMFO ) - COMPLETE DRAIN HIGH DENSITY CROSSLINKED POLYETHYLENE STORAGE TANKS WITH OXIDATION RESISTANT LINING SYSTEM (NSF/ANSI 61) 1.01 Requirements 1. The
More informationANSI/ ASME HST Performance Standard For Overhead Electric Wire Rope Hoists
SECTION 412213- BRIDGE CRANES Part 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections,
More informationMotor-driven Diaphragm Metering Pump
Motor-driven Diaphragm Metering Pump OPEN Easy, Tough and Safe This stylishly designed safe TACMINA metering pump is easy-to-use and user-friendly developed with excellent utility, functionality and durability.
More informationPRESSURE SWITCHES D-LT Electro-mechanical pneumatic pressure switches. 18D-LT x2 Electro-mechanical pneumatic pressure switches.
PRESSURE SWITCHES 8D-LT Electro-mechanical pneumatic pressure switches 8D-LT x Electro-mechanical pneumatic pressure switches Page -0 Page -0-0 8D-LT G/, / NPT or flange Microswitch with gold plated contacts
More informationOperations Manual. For Research Use Only. PH: EM: WEB:
Operations Manual For Research Use Only PH: 908-769-5555 EM: info@benchmarkscientific.com WEB: www.benchmarkscientific.com Thank you for choosing the BioClave Benchtop Sterilizer. Prior to operating this
More informationChange-over and monitoring unit For medical locations acc. to DIN VDE 0100 Part 710
Change-over and monitoring unit For medical locations acc. to DIN VDE 0100 Part 710 Operator manual Information on the manual Information on the manual Please read this manual, before using the change-over
More informationROLINX Laminated Busbar. Design Rules Version 01 (12/2015)
ROLINX Laminated Busbar Design Rules Version 01 (12/2015) Content 1. Introduction... 03 7. Features... 13 2. Configuration...03 8. Thermal parameters... 14 3. Products... 04 9. General parameters... 14
More informationNORTHWESTERN UNIVERSITY PROJECT NAME JOB # ISSUED: 03/29/2017
SECTION 26 0526 - GROUNDING AND BONDING FOR ELECTRICAL SYSTEMS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions
More informationInstallation plan. Washer-extractor PW 6107 EL. en - GB M.-Nr / 01
Installation plan Washer-extractor PW 6107 EL en - GB 10.11 M.-Nr. 09 270 450 / 01 M.-Nr. 09 270 450 / 01 2 Technical Datasheet Washer-extractor: Heating: PW 6107 Electric (EL) Legend: Solid circle
More informationST XX28 Stainless Steel Thermostatically Controlled Electric Model
DIXONS SURGICAL INSTRUMENTS LTD, 1 ROMAN COURT HURRICANE WAY, WICKFORD BUSINESS PARK WICKFORD, ESSEX, SS11 8YB, UK TEL: +44 (0)1268 764614 - FAX: +44 (0)1268 764615 EMAIL: info@dixons-uk.com - WEB: http://www.dixons-uk.com
More informationBakeMax Dough Mini Moulder BMMDM02
BakeMax Dough Mini Moulder BMMDM02 2 Instruction Manual 1. Preface ------------------------------------------- P2 2. Machine Introduction -------------------------------- P2 3. Machine Specification and
More informationDiffused Aeration Piping Equipment
1.0 General 1.1. The specifications in this section include all components of the Diffused Aeration System with the exception of the individual diffuser units. Refer to additional specification sections
More informationANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers"
References: ANSI/IEEE Standard C57.12"Standard Guide for Loading Mineral Oil Insulated Transformers" IEEE Project P1276 "IEEE Guide for the Application of High Temperature Insulation Materials in Liquid
More informationE 094 E 103 E 143 Tank top mounting Connection up to G1 Nominal flow rate up to 135 l/min
Return Filters E 9 E E Tank top mounting Connection up to G Nominal flow rate up to l/min Description Application In the return line circuits of hydraulic systems. Performance features Protection against
More informationThis guide can be used to prepare a specification for incorporating free standing jib cranes into a competitively bid construction project.
SECTION 14651 FREE STANDING JIB CRANE ***** Gorbel, Inc. manufacturers a broad range of material handling cranes including monorail, bridge, gantry, and jib cranes. Numerous work station and industrial
More informationDesign of Mercury Storage Containers
Design of Mercury Storage Containers Adam J. Carroll Remote Systems Group / Nuclear Science and Technology Division Oak Ridge National Laboratory October 13, 2009 Email: carrollaj@ornl.gov Phone: 1-865-576-7505
More informationFriday, May 29, Update on Testing Medium Voltage Cable and Switchgear Systems
Update on Testing Medium Voltage Cable and Switchgear Systems Friday, May 29, 2015 Presented by: Ashley Harkness Ashley.Harkness@Emerson.com Electrical Reliability Services Value--- When we find the one
More informationSECTION (Master Template Final-05) ELECTRICAL BOXES. A. Provide boxes for electrical equipment and wiring devices as follows:
SECTION 16130 (Master Template Final-05) ELECTRICAL BOXES PART 1 GENERAL 1.01 SECTION INCLUDES A. Provide boxes for electrical equipment and wiring devices as follows: 1. Wall and ceiling outlet boxes.
More informationRN Optical Termination Panel (RN OTP)
RN Optical Termination Panel (RN OTP) General The RN Optical Termination Panel(RN OTP) is specifically designed to house optical splitters while also catering for fiber termination in a single enclosure.
More information1. GENERAL INFORMATION CAUTIONS AND GENERAL NORMS DESCRIPTION AND INTENDED USE MARKING OF DTW WEIGHBRIDGES...
INDEX 1. GENERAL INFORMATION... 3 2. CAUTIONS AND GENERAL NORMS... 4 3. DESCRIPTION AND INTENDED USE... 5 4. MARKING OF DTW WEIGHBRIDGES... 5 4.1 TECHNICAL AND METROLOGICAL MARKING OF WEIGHING BARS...
More informationPIP PCEPA003 Process Analyzer System Field Installation Guidelines
January 2016 Process Control PIP PCEPA003 Process Analyzer System Field Installation Guidelines PURPOSE AND USE OF PROCESS INDUSTRY PRACTICES In an effort to minimize the cost of process industry facilities,
More informationELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200
ELECTRONIC EARTHING EQUIPMENT SERIES GRD 4200 The GRD 4200 is an electronic earthing equipment for tankers during loading and unloading operations of flammable liquids in places with danger of explosion.
More informationHotSwap MBP Maintenance Bypass
ENGLISH HotSwap MBP Maintenance Bypass MBP6K208 MBPK208 Installation and user manual Copyright 202 EATON All rights reserved. Service and suort: Call your local service representative SAFETY INSTRUCTIONS
More informationMODULAR ENCLOSURES FOR TRANSFORMER SUBSTATIONS
IG-021-GB General Instructions PF LIB Transformer Substations Secondary Distribution Switchgear Primary Distribution Switchgear Protection and Automation Low Voltage Boards Distribution Transformers Legal
More informationSECTION MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS
SECTION 11000 MECHANICAL EQUIPMENT - GENERAL REQUIREMENTS PART 1 - GENERAL 1.1 DESCRIPTION A. This section contains general information required to install mechanical equipment as shown on the plans and
More informationNEC 2014 Code Changes
NEC 2014 Code Changes Articles 280.21-300.50 CHANGES FROM 2011 TO 2014 CODE ARE IN RED Chapter 2 - Wiring and Protection ARTICLE 280 Surge Arresters, Over 1000 volts II. Instillation III. Connecting Surge
More informationYINGLI SOLAR TWINMAX MODULES Installation and User Manual
YINGLI SOLAR TWINMAX MODULES Installation and User Manual Revision Date Aug 3rd, 2016 Applicable for IEC certified products This manual applies to photovoltaic TwinMAX modules ( TwinMAX modules, also commonly
More informationDBI-SALA Uni 8 Overhead Horizontal Lifeline Cable System SECTION HORIZONTAL FALL PROTECTION - OVERHEAD CABLE
SECTION 112429.18 - HORIZONTAL FALL PROTECTION - OVERHEAD CABLE PART 1 - GENERAL 1.1 SECTION INCLUDES A. Provide overhead horizontal cable fall protection system, including end anchors, energy absorbers,
More informationISO INTERNATIONAL STANDARD. Petroleum and natural gas industries Packaged reciprocating gas compressors
INTERNATIONAL STANDARD ISO 13631 First edition 2002-08-01 Petroleum and natural gas industries Packaged reciprocating gas compressors Industries du pétrole et du gaz naturel Unités de compresseurs alternatifs
More informationMANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS
MANUFACTURER'S RESPONSIBILITIES AND REQUIREMENTS FOR FACTORY TESTS 1.0 MANUFACTURER'S RESPONSIBILITIES: The manufacturer's responsibilities include, but are not limited to: 1.1 Control of UL Mark - Restrict
More informationESD Packages. Ericssonvid Intern 1 (5) EAB/KL/FPR/KVO Kent Jäfvert F
1 (5) ESD Packages Abstract This document is a compilation of ESD-requirements and information on packages. Application These instructions (or other documents specifying equivalent requirements) are to
More informationPresentation to: Western Mining Electric Association
Presentation to: Western Mining Electric Association World s Largest Database of Test Records 4,000,000 Customer Transformer Test Records. World s Leading Reclaimer of Transformer Oil Over 1 Billion Gallons
More information