1 July 18, 2017 Dear Sir/Madam: Enclosed please find Minutes of the Pre-Proposal Meeting, Questions and Answers and Addendum No. 2 to SEPTA s RFP No ACAC BIV HVAC System Upgrade. Addendum No. 2 must be acknowledged by signing the attached Acknowledgement Sheet and including that sheet as part of your technical proposal. The due date for submission of proposals has been rescheduled to Thursday, August 3, 2017 by the close of business (4:30 P.M.). Proposals must be delivered to SEPTA, 1234 Market Street, 11th Floor, Philadelphia, Pennsylvania 19107, to the attention of Carolyn Caruso. All inquiries regarding this Procurement must be directed to Carolyn Caruso at (215) or ccaruso@septa.org. Thank you for your interest in the Authority. Sincerely, Carolyn Caruso Procurement Officer Procurement, Supply Chain & DBE Department

2 ADDENDUM NO. 2 July 19, 2017 ADDENDUM ACKNOWLEDGEMENT SHEET RFP No ACAC BIV HVAC System Upgrade The attached addendum to the Contract Documents is hereby part of the same and is incorporated in full as part of the Project. Proposer shall acknowledge Addendum No. 2 by signing and returning the Acknowledgement Sheet with the Technical Proposal. FIRM NAME (typed or printed) AUTHORIZED SIGNATURE TITLE NAME (typed or printed) DATE Addendum No. 2 includes: 1. The due date for submission of proposals has been rescheduled to Thursday, August 3, 2017 by the close of business (4:30 P.M.). 2. Add: Question and Answers from Pre-Proposal Meeting. 3. Add: Attachments A, B, C, D & E. A: Drawing of BIV Car Index Sheet B: Operator Requirements C: Maintenance Manual 1 D: Maintenance Manual 2 E: Maintenance Manual 3 4. Add: Attachment 13 - Buy America Certificate. Note: This form must be executed and submitted with your Technical Proposal. 5. Add: Sign-In Sheet for Site Visit.

3 The following Questions and Answers were submitted by the due date of June 15, QUESTIONS & ANSWERS TO RFP No ACAC Q1: Is it necessary to meet the full cooling performance when the input voltage is below nominal (e.g. 450v), as this has an impact on inverter sizing? A1: The specifications indicate a self-start at range of 550 VDC to 750 VDC. A minimum input of 450 VDC, is possible on the line. Full cooling performance is required at this minimum voltage but not below 450 VDC. Q2: We see an advantage to power the new overhead heaters from the inverter 3-phase supply in place of the 600v dc. Is this Ok for Septa? A2: SEPTA is agreeable to reviewing design alternatives for overhead heater. The Contractor is to provide details for powering heater by 600 VDC or from new Inverter. Q3: Can Septa provide more information on the function of the antenna next to the CCU? If necessary can it be relocated? A3: The vehicle identification antennae can be relocated but will be a time-consuming design process. Contractor will be responsible for evaluating EMI interference caused by local equipment. Contractor must interface with SEPTA signal dept. to test and assure track switches function properly at new location. Note: New equipment foundations, installation procedures and new cabling (if longer length) are to be supplied by contractor. Q4: Can Septa advise if relocation of the door control box is possible? A4: Relocation is not encouraged. Vendor must keep existing wiring, supports and accessibility to box s interior. New location will require new foundations, installation procedure, and new cabling, all provided by contractor. See arrangement of undercar equipment DWG for (OEM) equipment location. Q5: Can the auxiliary fuse in the existing knife switch be increased in ampacity without replacing the knife switch? Please provide the complete part number, manufacture and technical details of the knife switch. A5: SEPTA is not anticipating an increase in ampacity with a more efficient HVAC system. Contractor to submit design analysis indicating an actual need for increased ampacity with proposal. See attached parts manual for details on existing design. Q6: If it s decided that a new control box enclosure will be supplied, what s the expected NEMA rating of this box?

4 A6: The existing box is fabricated with carbon steel primed and painted for corrosive protection. The new boxes must meet or exceed existing box design or NEMA 4x. Q7: Will SEPTA consider a water ingress rating of something less than NEMA 6P? NEMA 6P is essentially the same as IP68 which is submersion for prolonged periods of time. No other equipment on the car has this level of protection. The duration of the leak-free period cannot be indefinite. Will a submersion duration of 3 hours be acceptable? Is SEPTA aware that a completely sealed NEMA 6P enclosure will dramatically increase the physical size of the inverter? A7: The intent of SEPTA s specification is to require protection from high pressure spray from SEPTA s car wash, not to have a submersible save box. SEPTA is agreeable to an alternative NEMA box that meets our needs. Q8: What material is required for use in the fabrication of the condensing unit frame, inverter box & control box (if replaced)? A8: Existing boxes are fabricated with carbon steel, primed and painted for corrosive protection. The new boxes must meet or exceed the existing box design or NEMA 4x. Foundation for equipment supports are to be fabricated from 304 L, stainless steel. Q9: Will SEPTA consider removing the existing small inverter for the evaporator blowers, and instead supply power, software, and control from the new equipment? A9: SEPTA prefers to use the existing inverter as a power source. Alternative controls, power, software, and wiring configurations must be submitted with the technical proposal. Q10: Will SEPTA consider splitting the DC/AC inverter(s) into two separate units in the event there is insufficient space under the car? A10: SEPTA prefers a single inverter but is agreeable to review alternative designs, which must be detailed in the Contractor s proposal. Q11: Is the wireless undercar antenna able to be relocated? If so, to what extent? A11: See Answer #3. Q12: Section 5.0: Scope: Five of each major subsystem units are required to be in contractor s scope of supply for maintenance purposes. What is the definition of the sub-system? A12: See Section 11 of the Scope of Work, which lists the definition of a sub-system. Q13: The contractor s recommendation is to power the heaters at 230 VAC. Is this acceptable to SEPTA? A13: See answer to question #2. Q14: Section 7.3.3: Floor Heat: If a contractor proposes the use of an alternate scheme for overall heating control in the car, is this acceptable to SEPTA?

5 A14: SEPTA is agreeable alternative heat controls, as long as they meet the required functionality. The Contractor should provide specific details with the technical proposal. Q15: Section 7.5.2: Design Criteria: This section requires the contractor to submit performance calculations with a load analysis of the car detailing the required heating and cooling capacities and required supply airflow using the revised design criteria [CDRL 14-04]. Will SEPTA provide the car dimensional drawings (including dimensions of the windows and doors), the overall thermal conductivity of the car and the solar heat gain coefficients of the window glass? Is the car interior temperature setpoint 72 F? A15: SEPTA will provide available OEM drawings upon request. Contractor must contact Carolyn Caruso to obtain copies of drawings. A list of drawings is provided with this correspondence along with appropriate sections of BIV Maintenance Manuals. SEPTA will provide dimensional data as requested. Design data such as thermal conductivity and solar heat gain will need to be measured and/or estimated during the design phase. Contractor to design HVAC system to meet specifications and operating environment of the BIV fleet. Contractor is responsible to obtain all measurements required for design. Contractor is to contact the buyer, Carolyn Caruso, for any future drawing requests. Q15-A: Will SEPTA provide information regarding the lighting load? A15-A: Yes: The BIV cars have 26 LED light fixtures with a load of 65.5 BTU/Hr. or 1703 BTU/Hr. load per car. Q15-B: Are there any other electrical cabinets/panels whose thermal dissipation should be considered during the load calculation? A15-B: Yes. There are electrical panels located within the car structure that should be considered. The contractor must design the HVAC system to meet the specifications and operating environment of the BIV fleet. Contractor is responsible to obtain all measurements required for design. Q15-C: Do the solar loads need to be considered for the load calculation? A15-C: Yes. Contractor to design HVAC system to meet specifications and operating environment of the BIV fleet. Contractor is responsible to obtain all measurements required for design. Q15-D: Do the door opening loads need to be considered? A15-D: Yes. Contractor is to design the HVAC system to meet the specifications and operating environment of the BIV fleet. The Contractor is responsible to obtain all measurements required for the design. Q16: Section : Evaporator Coil: What is the fin density of the evaporator coils currently installed? Does the current fin density need to be maintained? A16: Fin density is unknown. SEPTA is agreeable to the Contractor s recommendation for design, to be provided in the proposal. Q17: Section : Refrigerant Compressor: Is the compressor to be used a semi-hermetic piston compressor or a scroll compressor? A17: SEPTA prefers a scroll compressor but is agreeable to review alternative piston. Q18: Section : Condenser Coil assembly: It s stated in Section that the condenser coil has a fin density of 8 fins/inch. Would SEPTA be open to the use of coils with a slightly higher fin density?

6 A18: SEPTA is agreeable to a higher fin density, contractor to submit rational for increase. Q19: Section , : Is the information provided in these sections for reference only? A19: The provided reference data is a minimum. SEPTA is agreeable to ASHRE standards. Q20: Section : Is the qualification test referenced in this section the On-car test performed during pilot car installation/commissioning? A20: Yes. Q21: Section 7.6.7: Interior Car temperatures: Since the contractor is not modifying the ductwork of the car, do stratification requirements apply to a refurbished system? A21: The Contractor is to meet or exceed stratification of existing car. Q22: Section 12: Training: What is SEPTA s clearly defined scope of training? A22: Please see Attachment B Section 12 - Operator Requirements. See the attached job descriptions of participating trades and professionals. Contractor is to develop instructions and manuals to meet the needs of participants and convey information for properly maintaining new equipment. Q23: Please provide a copy of the maintenance manuals. A23: Please see Attachments: D Maintenance Manual 1 E Maintenance Manual 2 F Maintenance Manual 3 Q24: The new sensors will require additional cable to be installed, will this be allowed? A24: Yes. The Contractor is to supply cable and installation procedures and SEPTA will provide labor. Q25: Please provide the motor and inverter data for the evaporator blowers. A25: Please see Attachment F Maintenance Manual 3, Section , Page Q26: Does section mean the new inverter is to supply 37.5 volt power to control the HVAC contactors? Does this section also mean that the new inverter can use the existing low voltage for control as long as it doesn t overwhelm the converter? A26: Septa prefers Contractor to produce and supply their own power for controls to HVAC Contactors. Q27: Does the authority want the new inverter to replace the old converter and supply 37.5 VDC for the vehicle? A27: SEPTA is agreeable to reviewing the Contractors design and analysis for replacement, but the Contractor will be responsible for powering new equipment produced by the inverter and intergrading it into the vehicle s existing electrical system, including the battery charging system. Q28: Does the inverter for the evaporator blowers have an individual circuit for each blower motor? A28: No. There is one circuit for both motors. See attached drawing Fig Q29: Instead of thermistors we are proposing RTDs. Is this acceptable?

7 A29: Septa is agreeable to RTD; the Contractor should supply design and analysis with proposal. Q30: Please provide additional schematics and connection drawings. A30: Please see Attachment A Drawing of BIV Car Index Sheet. Q31: How much room is there in the existing evaporator blower envelope for increasing the length for the installation of the new overhead heaters? A31: The Contractor is to review available drawings and have an on-site engineer to obtain required dimensional information. Q32: Regarding Section This section states that the HVAC Contractor should be SEPTA approved. Is there an approval process to be followed? A32: No. There is no pre-approval process required. Q33: Regarding Section We request that the Authority provide drawings and maintenance manuals (Running Maintenance, Heavy Maintenance & Illustrated Parts Catalog) of the existing HVAC System. A33: Please see Attachments: D Maintenance Manual 1 E Maintenance Manual 2 F Maintenance Manual 3 Q34: Regarding Section We request that the Authority provide any additional existing car connection electrical schematics of the interface between the existing HVAC Controller and car body, other than those already provided in the specification. A34: Please see Attachments: D Maintenance Manual 1 E Maintenance Manual 2 F Maintenance Manual 3 Q35: Is the Authority planning to change any car body wiring to accommodate the microprocessor controller? A35: All changes required to accommodate microprocessor is the responsibility of the Contractor. Contractor is to provide material and procedures. SEPTA will provide labor. Q36: Regarding Section Duct Air Sensor - If the sensor is not currently installed, whose responsibility is it to supply the sensor and install the sensor? Will the Authority run new car body wiring for the sensor? A36: The Contractor is responsible for supplying sensors and the installation procedure. SEPTA will provide labor. Q37: Regarding Section Blower Assembly - Is the cabling required to connect the Inverter under the car and the blower motors in the ceiling, a part of the scope of supply by the Contractor? Will the authority be responsible for installation of the cabling at some future time? Will the bidder have to provide the engineering for routing of the cabling? If so can the existing conduit sizes and drawings of those areas be provided?

8 A37: The Contractor is responsible for supplying all material and procedures (routing). The Contractor is responsible for obtaining conduit size during the survey/design phase and provide connection provision. SEPTA will provide labor. Q38: Regarding Section Blower Assembly - Power to the Overhead Heaters: Is the Authority responsible for providing the high voltage power for the heaters? Is the car body wiring for the heaters available? A38: SEPTA is agreeable to 230 VAC or 600 VDC for ceiling reheat. SEPTA requires the continued use of 600 VDC for existing floor heat. Q39: Regarding Section Condenser Support Frame - Is there a material specified for the condenser support frame? A39: All structural supports are to be fabricated from 304 L stainless steel. Q40: Regarding Section Charging with Refrigerant - To determine accurate charge levels we recommend that the qualification testing and charge determination be done in accordance with ASHRAE standards. A40: SEPTA concurs, all qualification testing and charge determinations to be done to ASHRAE standards. Q41: Regarding Section Controller - The section states that thermistor sensors or approved solid-state temperature sensors should be utilized. Will the authority run new cabling in the car to support these components? A41: Contactor is responsible for supplying all sensors, cabling material, and installation procedures to meet the specification and design. SEPTA will supply labor. Q42: Regarding Section Car Interior Temperatures - Distribution of interior car temperatures is heavily influenced by the ducting system, car side seals and insulation. If the HVAC is proven to provide the request airflow and air temp, it may require major changes in the air ducting and diffusers. A42: Contractor to meet or exceed stratification of existing car. Q43: Regarding Section Car Interior Temperatures - any uninsulated or poorly insulated areas in the air ducting system could have condensation on them. Will it be the Contractor s responsibility to repair the air ducting system if necessary? A43: No, the contractor is not responsible to repair air ducting. Contractor to provide Septa with recommendations and SEPTA will make repairs Q44: Regarding Section Temperature Sensors - Since we are replacing the existing thermostats with thermistors will we be able to install new car body wiring? A44: Contractor is responsible to provide recommendations to meet specifications. Should new wiring be required, contractor is responsible for providing material and installation procedure. Septa will provide labor. Q45: Regarding Section Temperature Sensors - Does the supply air thermostat already exist? Is its function to control the maximum temperature difference between the temperature set point and the actual air temperature of the car interior? Does this limiting factor apply to pull down cooling and pull up heating when initially powering up the car? Can this be a thermistor located in the supply air duct? How would this sensor affect the return air sensing and/or control?

9 A45: SEPTA is not aware of existing sensors. The location of the thermistor and overall operation of the HVAC system is the responsibly of design Contractor. Q46: Regarding Section 7.9 Brake Compressor - Will need the data for the Wabtec conversion motor i.e. current draw, voltage, amp etc.? A46: Contractor should contact Wabtec for data. Q47: Regarding Section 7.9 Brake Compressor - Are there any weight restrictions or limitations on the equipment to be provided? A47: Contractor should match existing equipment weight as close as possible. Contractor should use the same equipment foundations Q48: Regarding Section 7.9 Brake Compressor - Given the complexity of the project and to provide the best value to the authority we request that the bid date be extended to August 3rd, A48: See Addendum No. 1 Q49: Regarding Section 7.11 Sustainability Q49-A: Will the Authority please clarify the criteria for determining minimum 10% more efficiency? A49-A: Power consumption. Q49-B: Is the improvement in efficiency determined by the electrical consumption of the system, the refrigeration capacity etc.? We would suggest that refrigeration efficiency should be determined by testing per ASHRAE Standards. Car level testing may not provide an accurate measure of refrigerant capacity of the HVAC unit. A49-B: SEPTA is agreeable to ASHRAE standards. END OF SECTION

10 MINUTES OF THE PREPROPOSAL MEETING RFP No BIV HVAC System Upgrade DATE: Thursday, June 8, 2017 TIME: PLACE: 10:00 AM SEPTA 1234 Market Street Conference Room 11C, 11 th Floor Philadelphia, PA PLEASE SEE ATTACHED SIGN-IN SHEET FOR THE LIST OF ATTENDEES. Carolyn Caruso welcomed the attendees and introduced SEPTA personnel and discussed contractual requirements and general information. John Macewen, Wayne Krahn and Ben Leonard reviewed the technical requirements of the scope of services. The meeting was adjourned at 11:00 A.M.

11 Attachment 13 Buy America Certificate

12 BUY AMERICA CERTFICATION This procurement is subject to the Federal Transit Administration Buy America Requirements in 49 CFR Part 661 and Federal Public Transportation Law 49 U.S.C. Chapter 53. A Buy America Certificate, as per attached format, must be completed and submitted with the bid in accordance with the requirements of 49 CFR A bid which does not include the certificate will be considered non-responsive. A waiver from the Buy America Provision may be sought by SEPTA if grounds for the waiver exist. Federal Public Transportation Law 49 U.S.C. 5323(j) permits the FTA participation on this contract only if steel, iron and manufactured products used in the contract are produced in the United States. 49 CFR requires that for steel, all manufacturing processes must take place in the United States, other than metallurgical processes involving refinement of steel additives. The steel requirements apply to all steel items including, but not limited to, structural steel, running rail, and contact rail. For manufactured products, 49 CFR requires that for a "manufactured product" to comply with the Buy America requirements, all of the manufacturing processes for the product must take place in the United States; and all items or material used in the product must be of United States origin. Bidder understands and agrees that, pursuant to 49 CFR , whether or not it certifies that it will comply with the applicable Buy America requirement, bidder is bound by its original certification and is not permitted to change its certification after bid opening. In addition, if bidder certifies that it will comply with the applicable Buy America requirements bidder understands and agrees that it is not eligible for a waiver of those requirements.

13 BUY AMERICA CERTIFICATE Certificate of Compliance With 49 U.S.C. 5323(j) {NOTE: Only one of the certifications below may be executed by the bidder. Failure to execute one or execution of both could result in rejection of the bid} The bidder or offeror hereby certifies that it will comply with the requirements of 49 U.S.C. 5323(j)(1), as amended and the applicable regulations in 49 CFR part 661. Date: Signature: Company: Name: Title: or Certificate for Non-Compliance With 49 U.S.C. 5323(j) The bidder or offeror hereby certifies that it cannot comply with the requirements of Section 49 U.S.C. 5323(j), but it may qualify for an exception to the requirement pursuant to 49 U.S.C. 5323(j), and the applicable regulations in 49 CFR Date: Signature: Company: Name: Title: Form 1 (Buy America Provision)

Distribution. Michael Piselli

Distribution. Michael Piselli 1234 Market Street,11 th Floor Philadelphia, PA 19107-3780 TO: FROM: SUBJECT: Distribution Michael Piselli RFP 15-00245-AMJP - Consultant Engineering & Administrative Support Services for ACS-64 Locomotives

More information

December 2, Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC).

December 2, Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC). December 2, 2016 Dear Sir/Madam Enclosed is Addendum No. 1 to SEPTA's Sealed Bid No. 16-00249-AMJP Frazer Shop & Yard Expansion Contract 2 (Re-Bid GC). The bid opening date and time scheduled for Wednesday,

More information

September 13, Enclosed is Addendum No. 6 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2.

September 13, Enclosed is Addendum No. 6 to SEPTA's Sealed Bid No AMJP Frazer Shop & Yard Expansion Contract 2. September 13, 2016 Dear Sir/Madam Enclosed is Addendum No. 6 to SEPTA's Sealed Bid No. 16-00138-AMJP Frazer Shop & Yard Expansion Contract 2. The bid opening date and time scheduled for Monday, September

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

C o u n t y o f F a i r f a x, V i r g i n i a

C o u n t y o f F a i r f a x, V i r g i n i a 001961 Page 2 C o u n t y o f F a i r f a x, V i r g i n i a A D D E N D U M DATE: August 2, 2016 ADDENDUM NO. 4 TO: REFERENCE: FOR: DUE DATE/TIME: ALL PROSPECTIVE BIDDERS Government Center Generator System

More information

Enclosed is Addendum No. 2 to SEPTA's Sealed Bid No ATMM 5 & Market Station Enhancement Project.

Enclosed is Addendum No. 2 to SEPTA's Sealed Bid No ATMM 5 & Market Station Enhancement Project. February 23, 2018 Dear Sir/Madam Enclosed is Addendum No. 2 to SEPTA's Sealed Bid No. 17-00265-ATMM 5 & Market Station Enhancement Project. The bid opening date and time scheduled for Wednesday, February

More information

ADDENDUM NO. 1 REQUEST FOR PROPOSAL REHABILITATION OF 1999 NEW FLYER BUS. September 5, 2018

ADDENDUM NO. 1 REQUEST FOR PROPOSAL REHABILITATION OF 1999 NEW FLYER BUS. September 5, 2018 ADDENDUM NO. 1 REQUEST FOR PROPOSAL REHABILITATION OF 1999 NEW FLYER BUS September 5, 2018 This Addendum No. 1 is in response to questions received from potential submitters. All responses must be reviewed

More information

has been changed to Thursday, December 14, 2017 at 10:30 A.M., prevailing Eastern Time.

has been changed to Thursday, December 14, 2017 at 10:30 A.M., prevailing Eastern Time. November 17, 2017 Dear Sir/Madam: Enclosed please find Addendum No. 4 to SB # 17-00181-ARLW - Janitorial, Landscaping, and Snow Removal Services at 30 th Street and University City Stations The bid opening

More information

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition

Architect s Project Number of 5 Decentralized HVAC Equipment District Master Specs 2013 Edition PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 23 81 00 DECENTRALIZED HVAC EQUIPMENT A. The other Contract Documents complement the requirements of this section. The General requirements apply to the work

More information

TECHNICAL QUESTIONS FOR ITB-DOT-17/ LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE

TECHNICAL QUESTIONS FOR ITB-DOT-17/ LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE TECHNICAL QUESTIONS FOR ITB-DOT-17/18-7004LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE Question 1: Question 2: Question 3: Question 4: Question 5: Question 6: When area configurations

More information

Janice Reedus, Director of Business & Auxiliary Services Campus Center Building A, Room Houbolt Road Joliet, IL 60431

Janice Reedus, Director of Business & Auxiliary Services Campus Center Building A, Room Houbolt Road Joliet, IL 60431 DATE: January 9, 2015 Addendum No. 1 Page 1 of 7 Joliet Junior College 1215 Houbolt Road Joliet, IL 60431 TO: Prospective Respondents SUBJECT: Addendum No. 1 PROJECT NAME: Commissioning Agent Services

More information

p!l,%l / he way tt> rpidly fly

p!l,%l / he way tt> rpidly fly l p!l,%l / he way tt> rpidly fly sr' 4 / //?j&(-w&0.l? E:bf?. C-?;i(-el9cl. I'i'i.?'r;c.'!j ('?a(ia '.!'3'i Q!' - Jjl'l??"-l') i" v?#?. -3 '. +?34'J-(3,Z X 4 Subject: Request for Proposal (RFP) No. 28958

More information

Issued for Bid West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS

Issued for Bid West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS 669.7403.001 West Alexandria, OH 05/2018 WWTP Improvements Contract 2 TABLE OF CONTENTS Page C-111 Advertisement for Bids 1-2 C-200 Instruction to Bidders 1-10 C-410 Bid Form for Construction Projects

More information

WESTERN MUNICIPAL WATER DISTRICT ADDENDUM NO. 2

WESTERN MUNICIPAL WATER DISTRICT ADDENDUM NO. 2 WESTERN MUNICIPAL WATER DISTRICT ADDENDUM NO. 2 TO THE BIDDING DOCUMENTS, CONTRACT, PLANS AND SPECIFICATIONS FOR Lake Hills 1860 Pressure Zone Booster Pump Station Emergency Generator Replacement Specification

More information

SECTION FIELD PANELS

SECTION FIELD PANELS Stanford University Facilities Design Guidelines SECTION 25 14 23 FIELD PANELS PART 1 - GENERAL 1.1 SUMMARY A. This section includes control panel and enclosure requirements for building control systems.

More information

REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258.

REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258. Permit Number REScheck Compliance Certificate Massachusetts Energy Code REScheck Software Version 3.6 Release 1 Data filename: O:\REScheck 38\38258.rck Checked By/Date PROJECT TITLE: All American / Whalen

More information

Revisions. SEPTA Specification

Revisions. SEPTA Specification Revisions SEPTA Specification Change No. Release Date Reason for Change Release Approval 1 7/14/2016 Correct document quantities description 6.0, 7.1 change from one (1) to two (2) test units PJD 7/14/2016

More information

BID ADDENDUM NO. 3 FOR SOLANO COUNTY TRANSIT OPERATIONS & MAINTENANCE FACILITY COMPRESSED NATURAL GAS PROJECT

BID ADDENDUM NO. 3 FOR SOLANO COUNTY TRANSIT OPERATIONS & MAINTENANCE FACILITY COMPRESSED NATURAL GAS PROJECT 8-25-2016 BID ADDENDUM NO. 3 FOR SOLANO COUNTY TRANSIT OPERATIONS & MAINTENANCE FACILITY COMPRESSED NATURAL GAS PROJECT City of Vallejo Solano County, California 94589 Pre-Bid Meeting: 2:00 PM, Thursday,

More information

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1.

The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1. PAGE 1 of 5 1.1. REFERENCE STANDARDS 1.1.1. The factory assembled air handler shall conform to the requirements outlined ASHRAE 90.1. 1.1.2. Unit shall be designed to conform to ASHRAE 15. 1.1.3. Unit

More information

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

Addendum 3 publishes and answers questions related to the Request for Qualifications ( RFQ ) issued on November 24, 2014:

Addendum 3 publishes and answers questions related to the Request for Qualifications ( RFQ ) issued on November 24, 2014: www.dot.state.pa.us Date: December 18, 2014 Subject: Questions and Answers Regarding RFQ Solicitation: CNG Fueling for Transit Agencies Partnership Project SOQ Due Date: No later than 11:00 a.m. Eastern

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR Conway, South Carolina

Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR Conway, South Carolina Project Manual for Coastal Carolina University RE-BID WILLIAMS BRICE RENOVATION AND REPAIR Conway, South Carolina DWG Consulting Engineers 1009 Anna Knapp Blvd. Suite 202 Mt Pleasant, South Carolina 29464

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R

Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R Outdoor + Switchgear, Walk-in Equipment Buildings Low & Medium Voltage NEMA 3R Product Brochure www.apt-power.com 433 N. 36 th Street PROVIDING A COMPREHENSIVE Lafayette, IN 47905 www.apt-power.com 433

More information

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES

DOWNTOWN UNDERGROUND NETWORK SECONDARY SERVICES GUIDELINES Guidelines effective March 5, 2007 NES is committed to providing safe, reliable electric service at a reasonable price for all of our customers. These guidelines offer direction for activities relating

More information

REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW:

REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: Police Headquarters Project REQUEST FOR PROPOSALS March 4, 2010 PROJECT OVERVIEW: General description The objective is to renovate an approximately 18 x 24 section of the two-bay attached garage at Town

More information

SECTION AIR COILS

SECTION AIR COILS SECTION 23 82 16 PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between // // if not applicable to project. Also delete any other item or paragraph

More information

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS

PIKES PEAK PARKING RESTORATION TABLE OF CONTENTS 23 HEATING, VENTILATING AND AIR CONDITIONING TABLE OF CONTENTS TABLE OF CONTENTS DIVISION 23 HEATING, VENTILATING AND AIR CONDITIONING - Basic HVAC Requirements 238239.19 - Wall and Ceiling Unit Heaters

More information

Commonwealth of Massachusetts

Commonwealth of Massachusetts Commonwealth of Massachusetts Manufactured Buildings Program Transmittal Form for all correspondences relating to Manufactured Buildings and Building Components To: Kimberly Spencer, Manufactured Buildings

More information

Procurement Department Bid Office Customer Center 1 st Floor, Room W. Church Street Jacksonville, Florida 32202

Procurement Department Bid Office Customer Center 1 st Floor, Room W. Church Street Jacksonville, Florida 32202 Procurement Department Bid Office Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 October 26, 2017 ADDENDUM NUMBER: ONE (1) TITLE: Arc-Resistant Metal-Clad Switchgear

More information

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3

MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 9,000 BTUH. Rev. 1.3 MHWW-09-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 9,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 9,000 BTUH Multiaqua Model

More information

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3

MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 18,000 BTUH. Rev. 1.3 MHWW-18-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 18,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 18,000 BTUH Multiaqua Model

More information

MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 12,000 BTUH. Rev. 1.3

MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil. Heat / Cool Fan Coil 12,000 BTUH. Rev. 1.3 MHWW-12-H-1 Chilled/Hot Water Hi-Wall Fan Coil Heat / Cool Fan Coil 12,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Hi-Wall Fan Coil 2-Pipe Nominal Size: 12,000 BTUH Multiaqua Model

More information

Southeastern Pennsylvania Transportation Authority 1234 Market Street Philadelphia, PA

Southeastern Pennsylvania Transportation Authority 1234 Market Street Philadelphia, PA BUILDING THEFUTURE Southeastern Pennsylvania Transportation Authority 1234 Market Street Philadelphia, PA 19107-3780 March 8,2017 Dear Sir/Madam: Subject: Sealed Bid No. 17-00010-AMZK Enclosed please find

More information

CONSTRUCTION REQUIREMENTS

CONSTRUCTION REQUIREMENTS CONSTRUCTION REQUIREMENTS Note: The buildings on the UCCS campus are divided into two categories: General Fund and Auxiliaries. General Fund Buildings include academic and administrative functions. Auxiliary

More information

CITY OF CHINO HILLS. Request for Proposals (RFP) for. On-call Electrical Repair Service. On-call Electrical Repair including Water and Wastewater

CITY OF CHINO HILLS. Request for Proposals (RFP) for. On-call Electrical Repair Service. On-call Electrical Repair including Water and Wastewater CITY OF CHINO HILLS Request for Proposals (RFP) for On-call Electrical Repair Service March 30, 2016 Department: Project Name: Public Works On-call Electrical Repair including Water and Wastewater Proposal

More information

Questar ThermWise Duct Technical Specifications

Questar ThermWise Duct Technical Specifications Questar ThermWise Duct Technical Specifications 1. Introduction and Scope: This document sets forth the specifications for duct sealing and duct insulation in accordance to Questar ThermWise Weatherization

More information

Capital Projects Group Air Terminal Units Specification

Capital Projects Group Air Terminal Units Specification Capital Projects Group Air Terminal Units Specification Specification 23 36 00 Revision 0 Date: August 2018 Air Terminal Units Specification Specification 23 36 00 Publication Date: August 2018 COPYRIGHT

More information

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS

SECTION PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS SECTION 23 74 13 PACKAGED, OUTDOOR, CENTRAL-STATION AIR-HANDLING UNITS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT

SECTION GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT SECTION 23 05 12 GENERAL MOTOR REQUIREMENTS FOR HVAC AND STEAM GENERATION EQUIPMENT PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between // // if not applicable to project. Also delete

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number

SECTION 16496A MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number MTS MANUAL TRANSFER SWITCH (MANUAL CONTROL ONLY) Note to Spec Writer: { } Denotes EATON Feature reference number PART 1 GENERAL 01 02 03 04 SCOPE Furnish and install Manual Transfer Switches (MTS) and

More information

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH

CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH CFFWA-20-1-U Chilled/Hot Water Universal Mount Fan Coil 2-Pipe Heat / Cool Fan Coil 60,000 BTUH Rev. 1.3 HVAC Guide Specifications Chilled and Hot Water Universal Mount Fan Coil 2-Pipe Nominal Size: 60,000

More information

Price High Performance Horizontal Fan Coil Units

Price High Performance Horizontal Fan Coil Units Price High Performance Horizontal Fan Coil Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 82 19 Fan Coil Units The following specification is for a defined application. Price would

More information

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE

SECTION METAL-ENCLOSED BUS MEDIUM VOLTAGE METAL-ENCLOSED BUS MEDIUM VOLTAGE PART 1 GENERAL 1.01 1.02 1.03 1.04 1.05 SCOPE The Contractor shall furnish and install the equipment as specified herein and as shown on the contract drawings. The medium

More information

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump

Pump Specifications 450 Series 1/2 hp Submersible Sump Pump Pump Specifications 450 Series 1/2 hp Submersible Sump Pump 450_P1 R1/27/2012 Copyright 2012 Liberty Pumps Inc. All rights reserved. Specifications subject to change without notice. 450-Series Dimensional

More information

Addendum No Variable Frequency Drives Section A, revise per following:

Addendum No Variable Frequency Drives Section A, revise per following: Date of Addendum: Jan. 7, 2013 CWA Contract: LPS-311 Addendum No. 2 Project: Lynchburg Pump Station VFD Replacement for P-208 & P-209 From: Rahim Tazeh, PE Infrastructure Associates 6117 Richmond, Suite

More information

Southeastern Pennsylvania Transportation Authority 1234 Market Street* Philadelphia, PA

Southeastern Pennsylvania Transportation Authority 1234 Market Street* Philadelphia, PA BUILDING THEFUTURE Southeastern Pennsylvania Transportation Authority 1234 Market Street* Philadelphia, PA 19107-3780 April 21, 2017 Dear Sir/Madam: Subject: Scaled Bid No. 16-00298-AMZK Enclosed please

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

Project Manual Index of Specifications Shenandoah Schools Concession Building

Project Manual Index of Specifications Shenandoah Schools Concession Building INDEX OF SPECIFICATIONS Division 0..BIDDING AND CONTRACT REQUIREMENTS 00 11 13 Advertisement for Bids 00 21 13 Instructions to Bidders 00 41 00 Bid Forms 00 43 13 Bid Security Form 00 72 00 General Conditions

More information

SCOPE OF WORK SUBSTATIONS

SCOPE OF WORK SUBSTATIONS Page 2 of 11 REVISION CONTROL Issued for Internal Review Issued for Client Review Issued for DFS REVISION HISTORY Revision Date Pages Revised Remarks 00 29/08/2017 Multiple Comments incorporated 01 05/04/2018

More information

RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number:

RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number: RENOVATION OF THE VIA BUILDING FOR THE GUELPH TRANSIT TERMINAL FROM THE PRE- QUALIFIED GENERAL CONTRACTORS Reference Number: 13-146 A D D E N D U M NO. 1 The following shall form part of the tender documents

More information

B. Provide equipment complying with this specification and manufactured by one of the following:

B. Provide equipment complying with this specification and manufactured by one of the following: SECTION 230910 PAINT SPRAY BOOTH PART 1 - GENERAL 1.1 SUMMARY A. Section Includes: 1. Provide Paint Spray Booth, Prep Booth and Paint Mix Room, and associated ventilation equipment, complying with the

More information

August 17, Dear Sir/Madam:

August 17, Dear Sir/Madam: August 17, 2017 Dear Sir/Madam: Attached is Addendum No. 2 for SEPTA's Sealed Bid Number 17-00156-AKLM, Woodland Avenue Replacement Bridge Project. The bid opening date and time scheduled for Tuesday,

More information

ADDENDUM NO. 2 Page 1 of 13

ADDENDUM NO. 2 Page 1 of 13 ADDENDUM NO. 2 Page of 3 TO THE CAMPUS WIDE ENERGY MANAGEMENT METERING SYSTEM BID (PROJECT # SBCMP0000027800) FOR THE CAMPUS OF CALIFORNIA STATE UNIVERSITY, SAN BERNARDINO. Prepared by: Procurement and

More information

AMENDMENT OF SOLICITATION

AMENDMENT OF SOLICITATION Metropolitan Washington Airports Authority PROCUREMENT AND CONTRACTS DEPT. AMENDMENT OF SOLICITATION PAGE 1 Metropolitan Washington Airports Authority 1A. AMENDMENT OF SOLICITATION NO. 1B. DATED Procurement

More information

Power Zone Center. Your solution for power distribution and control systems

Power Zone Center. Your solution for power distribution and control systems Power Zone Center Your solution for power distribution and control systems The Strength of One Powerful When you need to install a new power distribution center in your facility, you need it done in fastest

More information

Florida Army National Guard Construction Facilities Management Office. Scope of Work:

Florida Army National Guard Construction Facilities Management Office. Scope of Work: Florida Army National Guard Construction Facilities Management Office Florida Armory Revitalization Program (FARP) Design Guidelines September 2011 Scope of Work: To provide complete design for the renovation/alterations

More information

Revised Drawings A, E, and M dated 11/13/18 (that include additional specifications)

Revised Drawings A, E, and M dated 11/13/18 (that include additional specifications) Addendum No. 1 To: All Prospective Bidders Description: Holocaust Resource Center Expansion Stockton University Galloway, New Jersey 08205 Bid Number: B190003 Date: November 19, 2018 Pursuant to N.J.S.A.

More information

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard

SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard SUGGESTED SPECIFICATION for Low Voltage (600V) Generator Paralleling Switchboard PART 1 GENERAL 1.1 Scope A. The intent of this specification is to provide power control for the parallel operation of generator

More information

PORTLAND COMMUNITY COLLEGE SW 49 th Avenue Portland, Oregon ADDENDUM NO. 4

PORTLAND COMMUNITY COLLEGE SW 49 th Avenue Portland, Oregon ADDENDUM NO. 4 RE: ITB: PORTLAND COMMUNITY COLLEGE 12000 SW 49 th Avenue Portland, Oregon 97219 Sylvania Campus Bookstore Remodel Dated: February 22, 2017 April 11, 2017 ADDENDUM NO. 4 This addendum, together with the

More information

PART 1- General LULA Elevator Section 14200

PART 1- General LULA Elevator Section 14200 PART 1- General LULA Elevator Section 14200 1.1 Scope To furnish all labour, materials and equipment necessary or required to fully complete the installation of the lift as indicated on the drawings and

More information

FROM: MONDAY, FEBRUARY 4 TH, 2:00 P.M. TO: MONDAY, FEBRUARY 11 TH, 2:OO P.M.

FROM: MONDAY, FEBRUARY 4 TH, 2:00 P.M. TO: MONDAY, FEBRUARY 11 TH, 2:OO P.M. TORONTO TRANSIT COMMISSION MATERIALS AND PROCUREMENT DEPARTMENT ADDENDUM NO._1 PROPOSAL NO.: P08BK13013 TITLE: SUPPLY OF VARIOUS ELECTRICAL COMPONENTS AND SUPPLIES FOR UP TO A THREE (3) YEAR TERM 1. This

More information

OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, CT BUILDING RFP NO.: RFP OPENING DATE: APRIL 16, 3:00 PM ADDENDUM #4.

OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, CT BUILDING RFP NO.: RFP OPENING DATE: APRIL 16, 3:00 PM ADDENDUM #4. OFFICE OF PROCUREMENT COOLING TOWER REPLACEMENT, RFP NO.: 618-009 RFP OPENING DATE: APRIL 16, 2018 @ 3:00 PM ADDENDUM #4 April 9, 2018 THIS ADDENDUM IS TO PROVIDE ANSWERS TO THE FOLLOWING QUESTIONS: NOTE:

More information

ADDENDUM NUMBER ONE BRISTOL WATER FILTRATION PLANT MCC UPGRADE CITY OF BRISTOL, TENNESSEE

ADDENDUM NUMBER ONE BRISTOL WATER FILTRATION PLANT MCC UPGRADE CITY OF BRISTOL, TENNESSEE ADDENDUM NUMBER ONE BRISTOL WATER FILTRATION PLANT MCC UPGRADE CITY OF BRISTOL, TENNESSEE Pre-bid Meeting minutes are attached to this Addendum. I. QUESTIONS 1. Can an allowance for Power Company costs

More information

Homes Across Nebraska Are Being Built to the Latest National Energy Standards Is Yours?

Homes Across Nebraska Are Being Built to the Latest National Energy Standards Is Yours? Homes Across Nebraska Are Being Built to the Latest National Energy Standards Is Yours? A home buyer s guide to the energy efficiency requirements of the 2012 International Energy Conservation Code Nebraska

More information

SECTION AIR TERMINAL UNITS

SECTION AIR TERMINAL UNITS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Specification Sections, apply to this Section. B. Related Sections:

More information

Sonoma County Energy Independence Program APPENDIX A ELIGIBLE IMPROVEMENTS

Sonoma County Energy Independence Program APPENDIX A ELIGIBLE IMPROVEMENTS Sonoma County Energy Independence Program APPENDIX A ELIGIBLE IMPROVEMENTS The Sonoma County Energy Independence Program offers SCEIP funds for a number of equipment types, including water conservation

More information

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing.

B. ASHRAE 1991 HVAC Applications Handbook: Chapter 34--Testing, Adjusting and Balancing. PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 230593 TESTING, ADJUSTING, AND BALANCING A. Drawings and general provisions of Contract, including General and Supplementary Conditions and Division 1 Specification

More information

CITY OF JOPLIN, MISSOURI

CITY OF JOPLIN, MISSOURI CITY OF JOPLIN, MISSOURI BID PACKAGE 2016-07 For Memorial Hall Elevator Repairs And Modernization JOPLIN PARKS DEPARTMENT 3010 W. FIRST STREET JOPLIN, MO 64801 (417) 624-6937 1 Notice to Contractors Notice

More information

MINNESOTA STATE SECTION ADVERTISEMENT FOR BIDS

MINNESOTA STATE SECTION ADVERTISEMENT FOR BIDS MINNESOTA STATE SECTION 00 11 13 ADVERTISEMENT FOR BIDS Sealed Bids for: will be received by: Ridgewater College Commercial Chiller Purchase Ridgewater College Willmar Campus 2101 15 th Ave. N.W Willmar,

More information

Dick s Sporting Goods Demolition Package

Dick s Sporting Goods Demolition Package REQUEST FOR PROPOSAL FOR COMPETITIVE SEALED PROPOSALS TO PROVIDE: Dick s Sporting Goods Demolition Package at Salt Lake City, UT 2425 E. Camelback Rd. Suite 750 Phoenix AZ 85016 Notice of Extended Payment

More information

Addendum #3 To Request for Proposal For Rackham Relocations: Project / Dated December 13, 2018

Addendum #3 To Request for Proposal For Rackham Relocations: Project / Dated December 13, 2018 Division of Finance and Business Operations Procurement & Strategic Sourcing 5700 Cass Avenue, suite 4200 Detroit, Michigan 48202 (313) 577-3734 FAX (313) 577-3747 January 11, 2019 Addendum #3 To Request

More information

Division 00 Procurement and Contracting Requirements

Division 00 Procurement and Contracting Requirements SECTION 00 01 10 TABLE OF CONTENTS Division SECTION NO. VOLUME ONE Title SECTION TITLE Division 00 Procurement and Contracting Requirements 00 11 00 Invitation to Bidders 00 21 00 Instructions to Bidders

More information

1. Are there plans and specs for this project? Yes, the plans and specs are within the RFP and can also be found at the RFP website.

1. Are there plans and specs for this project? Yes, the plans and specs are within the RFP and can also be found at the RFP website. Access Control and CCTV for 110 William Street Project #6622 / Contract #6622-0001 Questions & Answers August 8, 2016 1. Are there plans and specs for this project? Yes, the plans and specs are within

More information

Town of Milton Halton Paramedic Services Station No. 17 and Milton Fire Station No. 5 Tender No and

Town of Milton Halton Paramedic Services Station No. 17 and Milton Fire Station No. 5 Tender No and Town of Milton No. 17 and Milton Fire Station No. 5 Tender No. 19-500-1 and 19-500-2 BID SUBMISSION 19-500-2 Part Two In accordance with Tender No. 19-500-2, Tender Form Part Two must be submitted electronically

More information

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011

Inspection Report. Prepared for: Gil Turiel. Property Address: 545 Briar Run Court Loganville, GA Date: July 17, 2011 Inspection Report Prepared for: Gil Turiel Property Address: Loganville, GA 30052 Date: July 17, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT

More information

INVITATION TO BID. (This is not an order.)

INVITATION TO BID. (This is not an order.) CITY OF CLEVELAND INVITATION TO BID Page 1 of 2 (This is not an order.) Buyer: Rashaun Billy 216-664-2626 rbilly@city.cleveland.oh.us Requestor: Vakedia Stiggers Division of Purchases & Supplies 216-664-7058

More information

AE R1 November, 2003

AE R1 November, 2003 AE4-1327 R1 November, 2003 ECONOMIZED VAPOR INJECTION (EVI) COMPRESSORS Introduction The Refrigeration Economized Vapor Injection (EVI) Compressor was developed to provide improved capacity and performance.

More information

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0 Qualifying Homes The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or less; Units in multi-family buildings that are

More information

Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification No.

Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification No. Project :RFQ165_ Macau International Airport- Construction Works for New Hangar Date :31 May 2013 Subject :Tender Clarification 1 01 Allow any alternative design for composite beam and slab for the structural

More information

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School A D D E N D U M # 1 DATE: TO: FROM: PROJECT: All Bidders Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School CBI JOB NO.: 11063 The following items shall modify

More information

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS

SECTION PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS SECTION 22 14 36 PACKAGED, SUBMERSIBLE, DRAINAGE PUMP UNITS PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTE: Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

4. GENERAL REQUIREMENTS

4. GENERAL REQUIREMENTS 4. GENERAL REQUIREMENTS 4.1 APPLICATION FOR SERVICE Application for service must be made to, and accepted by, the Company before service will be furnished. At the time of application, the Customer shall

More information

DIRECTIVE 15H-9 Issue date: October 2018 COMMISSIONING

DIRECTIVE 15H-9 Issue date: October 2018 COMMISSIONING DIRECTIVE 15H-9 Issue date: October 2018 COMMISSIONING Purpose: The purpose of this Directive is to describe, in outline, the requirements of Commissioning on SUCF Projects. 1. Applicability a. New York

More information

Price Fan Powered Terminal Units

Price Fan Powered Terminal Units Price Fan Powered Terminal Units Division 23 Heating, Ventilating, and Air Conditioning Section 23 3600 Air Terminal Units The following specification is for a defined application. Price would be pleased

More information

T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ

T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ REFRIGERANT CONDENSERS Guide Specifications T-Series SPLIT SYSTEM UNITS TSA R-410A - 60 HZ September 5, 2012 Note: This Specification is for Allied Commercial T-Series 6- to 20-ton, outdoor air conditioner

More information

CHARLES COUNTY GOVERNMENT ITB NO WAKEFIELD PUMPING STATION UPGRADE

CHARLES COUNTY GOVERNMENT ITB NO WAKEFIELD PUMPING STATION UPGRADE CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 February 27, 2014 ITB NO. 14-33 WAKEFIELD PUMPING STATION UPGRADE ADDENDUM NUMBER

More information

The Housing Authority of the County of Marin ( MHA ) 4020 Civic Center Drive. San Rafael, CA Addendum #1. Released October 3, 2016

The Housing Authority of the County of Marin ( MHA ) 4020 Civic Center Drive. San Rafael, CA Addendum #1. Released October 3, 2016 The Housing Authority of the County of Marin ( MHA ) 4020 Civic Center Drive San Rafael, CA 94903 Addendum #1 Released October 3, 2016 Addendum #1 to IFB MHA-010-2016 Re-Roofing, HVAC Unit Replacements

More information

SECTION HEAT TRACING FOR PLUMBING PIPING

SECTION HEAT TRACING FOR PLUMBING PIPING SECTION 22 05 33 HEAT TRACING FOR PLUMBING PIPING PART 1 - GENERAL 1.1 DESCRIPTION SPEC WRITER NOTES: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph not

More information

REQUEST FOR PROPOSAL (RFP) for the Construction of Base Building Requirements for the new Alaska Gallery exhibit.

REQUEST FOR PROPOSAL (RFP) for the Construction of Base Building Requirements for the new Alaska Gallery exhibit. REQUEST FOR PROPOSAL (RFP) for the Construction of Base Building Requirements for the new Alaska Gallery exhibit. 1. INVITATION The Anchorage Museum is soliciting bids from qualified general contractors

More information

REQUEST FOR PROPOSALS ENERGY AUDIT GASTONIA HOUSING AUTHORITY MARCH 23, 2009

REQUEST FOR PROPOSALS ENERGY AUDIT GASTONIA HOUSING AUTHORITY MARCH 23, 2009 REQUEST FOR PROPOSALS ENERGY AUDIT GASTONIA HOUSING AUTHORITY MARCH 23, 2009 1.0 ADVERTISEMENT The Gastonia Housing Authority (GHA) hereby requests proposals from qualified firms to provide services to

More information

Request for Bids. At The Greenville-Spartanburg International Airport

Request for Bids. At The Greenville-Spartanburg International Airport Request for Bids At The Greenville-Spartanburg International Airport Addendum No. 2 June 27, 2011 All Bidders shall include with their bid submittal a signed statement indicating they have reviewed and

More information

Permit Application Commercial / Industrial / Multi-Family BUILDING, ELECTRICAL, MECHANICAL, PLUMBING, BUILDING SEWER & WATER SERVICE

Permit Application Commercial / Industrial / Multi-Family BUILDING, ELECTRICAL, MECHANICAL, PLUMBING, BUILDING SEWER & WATER SERVICE STAFF USE ONLY RECEIVED BY: DATE: Permit Application Commercial / Industrial / Multi-Family BUILDING, ELECTRICAL, MECHANICAL, PLUMBING, BUILDING SEWER & WATER SERVICE Applicant must complete numbered items

More information

MEMPHIS-SHELBY COUNTY AIRPORT AUTHORITY MEMPHIS, TENNESSEE

MEMPHIS-SHELBY COUNTY AIRPORT AUTHORITY MEMPHIS, TENNESSEE QUESTIONS AND ANSWERS REGARDING MSCAA PROJECT 14-1374-03/04 CONCOURSE MODERNIZATION PASSENGER BOARDING BRIDGES 05/23/2018 1. Project timing for accurate pricing of the equipment (Walkways, PCA, GPU and

More information

IECC 2006 with Hawaii Amendments

IECC 2006 with Hawaii Amendments IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.

More information

3. Delete Sales Contract Exhibit 1-1, Price Proposal Page, and replace with the attached Revised Exhibit 1-1, Price Proposal Page.

3. Delete Sales Contract Exhibit 1-1, Price Proposal Page, and replace with the attached Revised Exhibit 1-1, Price Proposal Page. Metra... The way to really fly. 547 W Jackson Boulevard Chicago, IL 60661 312.322.6900 TTY 1 312.322.6774 September 16, 2016 Subject: Invitation for Bid No. 50544 Sale I Scrapping of Bi-Level Commuter

More information

Illinois Valley Regional Dispatch RFP Disclaimer Logging Recorder

Illinois Valley Regional Dispatch RFP Disclaimer Logging Recorder Illinois Valley Regional Dispatch RFP Disclaimer Logging Recorder To the extent any of the following requirements are propriety or vendor specific or in any way limits open and competitive proposals IVRD

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information