1 RECAPP Facility Evaluation Report Private Sector Landlord MHRH - Regional Resource Centre B9559B Medicine Hat Report run on: April 7, 214 2:21 PM

2 Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement : Construction : Facility Details MHRH - Regional Resource 631 Prospect Drive S. W. Medicine Hat B9559B 4,181. $ 1972 Most Recent Consultant Evaluation Evaluation Company: Berry Architecture + Associates Evaluation Date: December Evaluator Name: Evaluation FCR: % Steven De Grandis Total Maintenance Events Next 5 years: $2,359,4 Current 5 year Facility Condition Index (FCI): % General Summary: The Regional Resource Centre building is a single storey building with a full basement and an estimated construction date of as indicated by onsite staff. The building area is estimated at 42m2 total or 21m2 per floor level. The building has over gone continued programming changes and as a result has seen various renovations to interior spaces. Exterior finishes consist of brick to the majority of the wall surfaces and parging to the foundation. The building structure is original construction consisting of cast in place and concrete block foundations, OWSJ joist supporting the main floor concrete slab and sloped wood roof trusses. The building underwent noteable interior renovations in 24 to the basement west wing and 28 renovations to the basement east wing and main floor west wing. Overall the building is considered to be in acceptable condition. Structural Summary: The building structure consists of assumed reinforced cast in place concrete and concrete block foundations on reinforced concrete strip and pad footings. The main floor is a structural slab supported by OWSJ and concrete beams. Interior load bearing walls to main floor are assumed wood stud walls while the exterior walls are the continued construction of cast in place concrete and concrete block. The roof structure is sloped engineered wood roof trusses. Overall the structure is considered to be in acceptable condition. Envelope Summary: The majority of the exterior wall finish is masonry brick with a small extent of painted block and parging to the foundation. The majority of windows are the original aluminum fixed and single hung windows. A small portion of the operable single hung windows have been replaced with vinyl single hung windows noted in various locations to replace failed units. Entrance doors are a mixture of aluminum storefront doors to most entrances, double solid wood core doors and metal entrance doors. The roofing is asphalt shingles on plywood sheathing. The envelope overall rating is acceptable. Interior Summary: Interior finishes vary in install dates with materials consisting of resilient flooring, ceramic tile, carpeting and painted concrete floors. Walls are typically painted gypsum clad walls while the mechanical room was noted to be painted block and brick masonry walls. Ceiling finishes are typically textured stucco but sections of Acoustic T-bar ceilings and painted gypsum was also noted. Interior doors are hollow core and solid core wood doors and metal utility doors. Rated door labels were noted to required rated spaces. Wood constructed casework with painted and plastic laminate surfaces was noted in kitchen/coffee areas on both floor levels. Interior finishes are generally in acceptable condition. Mechanical Summary: The CRC Building was constructed in 1957 with few f the modern conveniences. Heat is provided by a central steam plant and distributed through the building with a perimeter heating system that has little to know control. The heating zones are regulated by manual balancing valves and operate further on wild loops, leading to lots of occupant complaints. In 1973 cooling was added. Fan coils were installed in almost all rooms using a chilled water system from the central plant. These units have reached the normal end of their life and is requiring excessive maintenance. There is a mixture of original and newer plumbing fixtures. These are generally acceptable to good. Hot water is provided through a steam/hot water heat exchanger and two storage tanks. These are also original and requires upgrading. Overall the building condition is acceptable with the fan coils, heating and controls being marginal. Data Current as of: April 7, 214 2:21 PM Page 2 of 35

3 Electrical Summary: The service to the building is 12/28V, 3 phase, 4 wire and rated 4A, the branch circuit panelboards are location through the building. The mixed T-12 and T-8 lamp fluorescent fixtures are used for most interior lighting, the HPS lights are used for exterior lighting. The fire alarm, intrusion detection and security access system meet current facility operation requirements. The overall rating for electrical systems is "Acceptable" Guide Condition Performance 1 - Critical Unsafe, high risk of injury or critical system failure. 2 - Poor Does not meet requirements, has significant deficiencies. May have high operating/maintenance costs. 3 - Marginal Meets minimum requirements, has significant deficiencies. May have above average operating maintenance costs. Meets present requirements, minor deficiencies. Average operating/maintenance costs. Meets all present requirements. No deficiencies. 6 - Excellent As new/state of the art, meets present and foreseeable requirements. Data Current as of: April 7, 214 2:21 PM Page 3 of 35

4 S1 STRUCTURAL A11 Standard Foundations* Conventional reinforced strip and pad footings. A13 Slab on Grade* Assumed reinforced basement slab on grade. A22 Basement Walls (& Crawl Space)* Reinforced cast in place concrete walls and concrete block walls. B11.1 Floor Structural Frame (Building Frame)* OWSJ joists and concrete beams support the concrete main floor structure. B11.2 Structural Interior Walls Supporting Floors (or Roof)* Reinforced cast in place concrete walls and concrete block walls to interior basement walls. Assumed wood stud bearing walls to corridors on main floor supporting the roof structure. B11.3 Floor Decks, Slabs, and Toppings* Reinforced concrete main floor slab. Sections of the basement level have raised wood floors. Data Current as of: April 7, 214 2:21 PM Page 4 of 35

5 B11.6 Ramps: Exterior* Barrier free ramp at main entrance and North elevation basement entrances (2) Upgrade RRC Main Entrance Wheelchair Ramp.- (1 Ramp) Concern: RRC wheelchair ramp and sidewalk, brick sidewalk to main entrance, and steps from ground level parking have become tripping hazzards as they have deteriorated and need to be resurfaced. The existing concrete wheel chair ramp has deteriorated and is not code compliant. Recommendation: Steps and sidewalks need upgrading. Wheelchair access to upper level in RRC is crumbling and will not accomodate some wheelchairs. Consequences of Deferral: OH&S and code compliancy concerns. Repair 215 $136,13 High : B11.7 Exterior Stairs* Cast in place concrete stairs to entrances on the main floor and basement complete with painted metal railings. Repair Stairs.- (3 stairs) Concern: Concrete stairs at 3 building entrances have deteriorated and in need of replacement. Recommendation: Repair steps and upgrade the concrete wheel chair ramp. Repair 215 $132, High : Data Current as of: April 7, 214 2:21 PM Page 5 of 35

6 B11.9 Floor Construction Fireproofing* Concealed ceiling spaces were not reviewed. Assumed fire ratings are acceptable due to concrete main floor slab construction. B11.1 Floor Construction Firestopping* Through wall and through floor penetrations, where visible, did not have the required fire caulking installed. 2 - Poor Install Fire Caulking (entire building). - (21 sq.m.) Concern: Fire caulking was not noted on through wall and through floor penetrations where visible. Does not meet code requirements. Recommendation: Install fire caulking around all required penetrations. Consequences of Deferral: Code issue. Code Upgrade 215 $25, High : B12.1 Roof Structural Frame* Engineered sloped wood roof trusses. B12.6 Roof Construction Fireproofing* Concealed ceiling spaces were not reviewed. Assumed fire rating requirements met. Data Current as of: April 7, 214 2:21 PM Page 6 of 35

7 S2 ENVELOPE B Brick Masonry: Ext. Wall Skin* Exterior brick wall finish is the majority exterior finish. Assumed cavity wall construction with cast in place concrete or concrete block back up walls. B Cement Plaster (Stucco): Ext. Wall* Stucco parging to partial above grade foundations. Extends approximately 16" (46mm) above grade. B Joint Sealers (caulking): Ext. Wall** Caulking around windows, doors and metal flashing. 3 - Marginal 2 Replace Caulking.- (17m) Concern: Caulking is dried and hard, cracked and is missing in multiple sections. Recommendation: Remove existing caulking and replace with new. Recommended to complete replacement at the same time as the recommended window replacement. Failure Replacement 215 $56,882 Medium : B Paints (& Stains): Ext. Wall** Painted concrete block Refinish Painted Exterior Surfaces.- (4m2) 217 $1,36 : Data Current as of: April 7, 214 2:21 PM Page 7 of 35

8 B Cast-in-place Concrete: Ext. Wall Const* Exterior walls to both levels have CIP exterior back up walls, as part of the cavity wall system. The full extent of concrete walls is unknown due to concealed wall cavities and limited existing drawings. B Masonry Units: Ext. Wall Const.* CMU block walls were noted in the basement mechanical room. The full extent of block walls is unknown due to concealed wall cavities and limited existing drawings. B21.3 Exterior Wall Vapour Retarders, Air Barriers, and Insulation* Assumed air/vapour barriers and insulations installed. B21.9 Exterior Soffits* Prefinished perforated metal soffits to entire building roof overhang perimeter B Aluminum Windows (Glass & Frame)** 3 - Marginal 4 Replace Aluminum Windows.- (525m2) Concern: The windows are inefficient increasing operating costs, their tracks are continuously sticking and preventing the windows from opening. Staff safety has also become a concern. Recommendation: Replace the existing fixed and single hung aluminum windows. Consequences of Deferral: Increased operations costs and staff safety. Failure Replacement 215 $61,64 High : Data Current as of: April 7, 214 2:21 PM Page 8 of 35

9 B Wood Windows (Glass & Frame)** Painted wood windows to front building extension housing the main entance, board room and office/storage rooms. Fixed upper windows with operable lower slider window. 35 Replace Wood Windows with PVC Windows.- (38m2) 217 $4,369 : B Vinyl, Fibreglass & Plastic Windows** PVC operable single hung windows to the basement and main floor levels. These windows replaced failed aluminum windows Replace PVC Windows.- (2m2) 239 $21,247 : B Aluminum-Framed Storefronts: Doors** Double and single leaf aluminum entrance doors on aluminum frame with sidelites and transom. Automatic openers for barrier free access is installed on the main entrance door and the basement west wing door. 2 3 Replace Aluminum Storefront Doors.- (4 double doors + 4 Single Doors) 23 $57,719 : Data Current as of: April 7, 214 2:21 PM Page 9 of 35

10 B Metal Entrance Door** Metal entrance door to one stairwell accessed from the south side of the building. 3 Replace Metal Entrance Door.- (1 Double Door) 217 $2,83 : B Asphalt Shingles** Asphalt shingled sloped roofing on plywood sheathing. Assumed vapour barrier installed with asphalt shingles. Recommended replacement with asphalt shingles. 3 - Marginal Replace Asphalt Shingles & Vapour Barrier.- (24m2) Concern: Asphalt shingles have reached the end of there life cycle and are soon to fail leading to interior moisture concerns. Recommendation: Remove existing shingles and replace with new. Consequences of Deferral: Potential interior moisture damages. Failure Replacement 215 $14,52 Medium : B32.2 Other Roofing Openings (Hatch, Vent, etc)* Standard roof ventilation and plumbing stack penetrations. Data Current as of: April 7, 214 2:21 PM Page 1 of 35

11 S3 INTERIOR C11.1 Interior Fixed Partitions* Load bearing partitions are poured concrete and concrete block masonry. Non-load bearing partitions are brick masonry, steel studs and wood studs. C11.5 Interior Windows* Two way mirror to children observation room on the main floor, Room C11.6 Interior Glazed Partitions and Storefronts* Wood framed interior glazed partition at front entrance vestibule. C12.1 Interior Swinging Doors (& Hardware)* Solid core and hollow core wood doors with stained wood finish in painted wood frames. Stairwell doors have georgian wired viewing panels installed. Pressed steel doors & frames to mechanical rooms. Dutch doors noted at two room locations. Data Current as of: April 7, 214 2:21 PM Page 11 of 35

12 C12.3 Interior Fire Doors* Original wood and hollow metal fire doors on steel frames to fire rated rooms. Storage room and stairwell doors do not have the required rated doors and frames installed. 3 - Marginal Install fire doors, frames and hardware.- (11 doors) Concern: No ULC labels on doors and frames, that require a fire rating. Current code requires ULC labeled hollow metal doors and steel frames for the required doors. Recommendation: Replace wood doors and steel frames with fire rated hollow metal doors and steel frames with required rating, complete with new set of hardware. These include entrance doors to tenant areas from hallways, mechanical room, stairwells, and storage rooms. Consequences of Deferral: Integrity of fire separation compromised. Code Upgrade 215 $14,999 Medium : C12.4 Interior Sliding and Folding Doors* Wood and aluminum sliding closet doors in tenant spaces. C13.1 Visual Display Boards** Tack boards in various tenant spaces. White board in west wing Staff Room (213) and the main floor board room. 2 2 Replace 8 Tack Boards and 2 white boards. 22 $3,6 : Data Current as of: April 7, 214 2:21 PM Page 12 of 35

13 C13.2 Fabricated Compartments (Toilets/Showers)** Prefabricated metal toilet compartments in washrooms on the main floor and basement. 3 Replace fabricated compartment.- (8 stalls) 217 $11,42 : C13.8 Interior Identifying Devices* Lamicoid signs with room numbers and various names throughout the facility. 2 C13.12 Storage Shelving* Large number of wood and metal storage shelving throughout in tenant areas. C13.14 Toilet, Bath, and Laundry Accessories* Stainless steel toilet roll and paper towel dispensers, waste receptacles, mirrors, grab bars, soap dispensers, and napkin dispenser in the Female Washrooms throughout the facility. 2 C21 Stair Construction* Concrete stairs in stairwells with metal balusters and wood hand rails, balusters and landing railings are not to code (see C22.8). Wood stairs and ramp from basement raised wood floor to basement slab transition. Data Current as of: April 7, 214 2:21 PM Page 13 of 35

14 C22.5 Resilient Stair Finishes** Rubber treads and risers in exit stairs Replace Resilient Stair Finish.- (13 m2) 217 $13,5 : C22.6 Carpet Stair Finishes** Carpet finish to basement corridor stairs and ramps. 3 - Marginal Replace carpet stair finishes.- (25 m2) Concern: Carpets are worn and dated. Recommendation: Remove existing carpets and replace with resilient flooring. Failure Replacement 215 $2,719 Low : C22.8 Stair Railings and Balustrades* Exiting stairs have angled metal railings with wood hand rails. South exit stairwells have painted wood installed over metal to meet current code requirements. Landing railings do not meet code requirement height. Wood wall mounted hand rails to basement stairs, wood railings to basment ramps. None of the handrails have the code required handrail extensions. 3 - Marginal Replace Stair and Landing Railings.- (5 Stairwells + 4 Basement Corridor stairs and ramps) Code Upgrade 215 $5, Low : Data Current as of: April 7, 214 2:21 PM Page 14 of 35

15 C22.1 Stair Painting* Painted concrete stairs to exit stairwell below the main entrance C31.2 Wall Paneling** Decorative stained wood paneling to boardroom and room Replace Wood Panelling.- (45 m) 217 $5,27 : C31.11 Interior Wall Painting* - Painted plaster, cast in place concrete and concrete block walls. Painting touch ups completed as necessary under maintenance budgets. C31.11 Interior Wall Painting* - 24 Painted gypsum clad walls to basement west wing currently being used as the seniors outreach wing. 24 C31.11 Interior Wall Painting* - 28 Painted gypsum clad walls to main floor west wing & basement east wing. 28 C31.14 Other Wall Finishes* Decorative clay masonry tile in room 276. Data Current as of: April 7, 214 2:21 PM Page 15 of 35

16 C Painted Concrete Floor Finishes* The mechanical room, various storage rooms and currently the unused basement area in room Marginal Repaint concrete floors.- (2m2) Concern: Painted concrete flooring is very worn and faded due to its age. Recommendation: Repaint concrete floor services with new coat of paint. Failure Replacement 215 $5,2 Low : C32.2 Tile Floor Finishes** 25 x 25mm ceramic mosaic tiles in main floor women's washroom near room 267, and the washrooms 227 and Replace Mosiac Tile.- (4m2) 217 $8,31 : Data Current as of: April 7, 214 2:21 PM Page 16 of 35

17 C32.7 Resilient Flooring** - Original VCT (vinyl composite tile) or ACT (asbestos composite tile) flooring in janitor rooms and sections of one mens washrooms. 3 - Marginal 2 Replace VCT and ACT Flooring.- (15m2) Concern: Existing tile is very stained and worn, dated in appearance and may contain asbestos. Recommendation: Remove and replace the existing flooring with new vinyl sheet flooring. Failure Replacement 215 $1, Low : C32.7 Resilient Flooring** - 24 Sheet vinyl flooring in the Seniors Outreach centre (basement west wing) to majority of rooms and spaces Replace Vinyl Sheet Flooring.- (43m2) 224 $39,564 : C32.7 Resilient Flooring** - 28 Vinyl Sheet Flooring to the main floor west wing and basement east wing in majority of room and spaces Replace Vinyl Sheet Flooring.- (82m2) 228 $75,449 : Data Current as of: April 7, 214 2:21 PM Page 17 of 35

18 C32.8 Carpet Flooring** Existing carpet flooring to main and basement levels in varying years of installation. Average age of install was estimated as 1982 by site representative. 3 - Marginal Replace Carpets with Vinyl Sheet Flooring.- (25m2) Concern: The flooring in the Community Resource Centre in the non renovated areas is carpet which is in very poor condition. The floor is very difficult to maintain. The carpet should be changed to vinyl for infection control issues. Recommendation: Remove the existing carpets and replace with vinyl sheet flooring. Consequences of Deferral: Health concern. Failure Replacement 215 $23,25 High : C32.8 Carpet Flooring** - 24 Carpet flooring in seniors outreach centre wing office, room Replace Carpet Flooring.- (14m2) 219 $1,172 : C32.8 Carpet Flooring** - 28 Carpet flooring to main floor west wing offices and staff room Replace Carpets.- (165m2) 223 $13,83 : Data Current as of: April 7, 214 2:21 PM Page 18 of 35

19 C33.1 Concrete Ceiling Finishes (Unpainted)* Mechanical room and a storage room ceilings. C33.6 Acoustic Ceiling Treatment (Susp. T-Bar)** Suspended acoustic tile ceilings to the basement level and sections of the main floor. Acoustic ceiling tile ceiling finish (not suspended) Replace Acoustic Ceiling Finishes.- (16m2) 217 $56,742 : C33.6 Acoustic Ceiling Treatment (Susp. T-Bar)** - 24 Suspended acoustic tile ceilings to the Seniors Outreach Centre (basement west wing) Replace T-Bar Ceilings.- (43m2) 229 $23,18 : C33.6 Acoustic Ceiling Treatment (Susp. T-Bar)** - 28 Suspended acoustic tile ceilings to the main floor west wing and basement east wing Replace T-Bar Ceilings.- (86m2) 233 $46,36 : Data Current as of: April 7, 214 2:21 PM Page 19 of 35

20 C33.7 Interior Ceiling Painting* All plaster and gypsum board ceiling surfaces. 198 Data Current as of: April 7, 214 2:21 PM Page 2 of 35

21 S4 MECHANICAL D21.4 Sinks** x cement mop sink 1x enameled steel mop sink Replace Sinks.- (2) 217 $6,1 : D21.4 Sinks** - 2 8x stainless steel single bowl kitchen sinks 2x stainless steel double bowl kitchen sinks 1x plastic mop sink 2 3 Replace Sinks.- (11) 23 $21,4 : D21.4 Sinks** x stainless steel single bowl kitchen sinks 2x stainless steel double bowl kitchen sinks 27 3 Replace Sinks.- (5) 237 $9,2 : Data Current as of: April 7, 214 2:21 PM Page 21 of 35

22 D21.8 Drinking Fountains/Coolers** There is a vitreous china drinking fountain on each of the two floors. None are refrigerated. 35 Replace Drinking Fountains.- (2) 217 $3,9 : D21.1 Washroom Fixtures (WC, Lav, Urnl)** x china tank toilet 7x china wal hung basin 3x china urinal, floor mount Replace WC (1), UR (3) and LAV (7) 217 $22,2 : D21.1 Washroom Fixtures (WC, Lav, Urnl)** - 2 2x china tank toilet 2x china toilet c/w flush valve 4x china counter top basins 2 35 Replace WC (4) and LAV (4) 235 $16,9 : Data Current as of: April 7, 214 2:21 PM Page 22 of 35

23 D21.1 Washroom Fixtures (WC, Lav, Urnl)** x china tank toilet 6x china wall hung and counter top basins Replace WC (1) and LAV (6) 242 $35,2 : D Piping Specialties (Backflow Preventers)** A backflow preventor is located in the mechanical room Replace Backflow Preventor.- (1) 217 $3,8 : D Water Storage Tanks** 2x 3 gal(2271 L total) hot water storage tanks c/w separate heat exchanger using steam from central plant to heat domestic hot water Capacity Size Capacity Unit litre Replace Storage Tanks(2) 217 $32,3 : D Ducts: Air Distribution* Duct could not be inspected by we suspect there are duct from the fan coils to the diffusers in each room installed in Data Current as of: April 7, 214 2:21 PM Page 23 of 35

24 D Hot Water Distribution Systems** Perimeter baseboard heating c/w circulation pumps using steam from central plan as heat source. 3 - Marginal 4 Replace Hot Water Distribution System.- (4181 sq.m) Concern: The 4 heating pumps, domestic water heaters, isolation valves and electrical contactors located in the mechanical room were installed in 1957 and have exceeded their normal 25 year service life. Parts are no longer available. Zones are on wild loops with no zone valves in perimeter heating and/or zone valves are stuck and not operational. Recommendation: Replace the heating pumps, hot water tanks, valves, and electrical contactors, perimeter heating and zone valves. Consequences of Deferral: Poor heating in building with hot/cold zones and occupant discomfort leading to lower productivity. Failure Replacement 215 $511, High : D Fans: Exhaust** There are two exhaust fans in the attic. The fan motors were refurbished in 28. Housings are original and still acceptable. 3 Replace Fans.- (2) 217 $2,7 : Data Current as of: April 7, 214 2:21 PM Page 24 of 35

25 D34.5 Heat Exchangers** Steam to hot water heat exchangers for heating and domestic hot water generation. 3 Replace Heat Exchangers.- (3) Concern: The building 3 Steam to Hot Water Convertors are 5 years old have exceeded their expected life cycle. Recommendation: Install Energy Efficient Condensing Boilers 217 $55,7 : D Fan Coil Units** York chilled water fan coils were install through out the building in There are frequent motor failures. Units are also past expected lifespan. 3 - Marginal Replace Fan Coils.- (141) Concern: Chilled water fan coils were install through out the building. Recommendation: Replace Fan Coils. Program Functional Upgrade 215 $91,8 Low : Data Current as of: April 7, 214 2:21 PM Page 25 of 35

26 D Pneumatic Controls** Pneumatic controls with compressor in central boiler plant. All zones have thermostats controlling cooling. Heating is at present not controlled and zones are on wild loops providing little to no control. We recommend that the pneumatic controls be scrapped and a new modern DDC system c/w zone valves be installed. We still provide a pneumatic control replacement/upgrade cost. 4 Replace Pneumatic Controls(Demolition only) - (4181 sq.m) Concern: No heating control in zones due to absence of control valves. Recommendation: Remove pneumatic controls and install electronic control system. See D Consequences of Deferral: Occupant complaints and low productivity due to discomfort. Program Functional Upgrade 215 $1, : Data Current as of: April 7, 214 2:21 PM Page 26 of 35

27 D Building Systems Controls (BMCS, EMCS)** There is a very limited building management system control at present. 2 - Poor 2 Install BMCS System.- (4181 sq.m) Concern: The existing system has limited energy management capability and not connected to the main hospital Building Management System. Controlling this building is very difficult. Recommendation: Connect the Community resource centre building to the main Building Management System Consequences of Deferral: No building control with poor heating resulting in occupant complaints. Operating Efficiency Upgrade 215 $146, Medium : Install BMS Cabinet in Mechanical Room RRC.- (1) Concern: The existing system has limited energy management capability as it is not connected to the hospital BMS System. Recommendation: Connect RRC to Hospital BMS System Consequences of Deferral: No building control with poor heating resulting in occupant complaints. Energy Efficiency Upgrade 215 $36, : D43.1 Fire Extinguisher, Cabinets and Accessories* There are six fire hose cabinets in the building, each with an ABC fire extinguisher. Two fire department connections are located in the front and back of the building respectively. Data Current as of: April 7, 214 2:21 PM Page 27 of 35

28 S5 ELECTRICAL D51.3 Main Electrical Switchboards (Main Distribution)** The service to the building is fed from hospital nearby; the service was upgraded to 4A 12/28V system in 1985, but the distribution equipment were still originally installed with the building Replace Main Electrical Switchboard.- (1) 217 $16, : D51.5 Electrical Branch Circuit Panelboards (Secondary Distribution)** The panels are installed through the facility and most of them are at full capacity Replace 6 Electrical Branch Circuit Panelboards 217 $3, : D Motor Starters and Accessories** The standalone magnetic starters and load switches are used for mechanical ventilation and pump controls Replace 15 Motor Starters and Accessories 217 $9, : D52.1 Electrical Branch Wiring* All the wires are copper and installed in the conduits Data Current as of: April 7, 214 2:21 PM Page 28 of 35

29 D Interior Incandescent Fixtures* The fixtures are used in the storage and boiler rooms D Interior Fluorescent Fixtures**- 212 The T-8 lamp fluorescent fixtures are installed at administration renovation area Replace 6 Interior Fluorescent Fixtures 242 $24, : D Interior Fluorescent Fixtures**-1973 The T-12 lamp fluorescent fixtures are still used for most of the space of the facility Replace 28 Interior Fluorescent Fixtures 217 $112, : D Emergency Lighting Battery Packs** The battery packs and remote heads are installed through building hallways and common areas Replace 12 Emergency Lighting Battery Packs 217 $14,4 : Data Current as of: April 7, 214 2:21 PM Page 29 of 35

30 D Exit Signs* All the fixtures are retrofit with LED Lamps 25 D Exterior H.P. Sodium Fixtures* The wall packs are installed perimeter of the building D Lighting Accessories: Exterior (Lighting Controls)* The exterior lighting is controlled by photo cell 1973 D53.1 Detection and Fire Alarm** The hardwired Simplex 42 control panel is used for entire building fire alarm system, Replace Detection and Fire Alarm System.- (21 sq. m.) 217 $7, : D Intrusion Detection** The DSC control panel is used for intrusion detection system and have motion sensors installed in the hallways and door contactors at exterior door Replace Intrusion Detection System. - (21 sq. m.) 237 $35, : Data Current as of: April 7, 214 2:21 PM Page 3 of 35

31 D Security Access** The AMAG door access is installed and have Siemens FOB units and position switches installed at exterior doors and some secured areas Replace security access. - (21 sq. m.) 237 $2, : D Data Systems* One patch panel is installed and tied to hospital main server. 25 D Local Area Network Systems* The data outlets are installed in the offices and wireless access though entire building. 25 Data Current as of: April 7, 214 2:21 PM Page 31 of 35

32 S6 EQUIPMENT, FURNISHINGS AND SPECIAL CONSTRUCTION E19.4 Residential Equipment* Range, fridge coffee machines and microwaves to staff rooms and kitchens. 2 E21.2 Fixed Casework** Kitchen and staff area millwork in un-renovated areas of the building. Rooms 17, 237 & 247. Painted wood millwork with plastic laminate counter tops Replace Millwork.- (18m) 217 $16,562 : E21.2 Fixed Casework** - 24 Kitchen, staff area and washroom millwork in seniors outreach centre (basement west wing). Plastic Laminate and stained wood finished millwork with plastic laminate counter tops and backsplash Replace Millwork.- (25m) 239 $23,4 : E21.2 Fixed Casework** - 28 Kitchen, staff area and washroom millwork in basement east wing and main floor west wing. Plastic Laminate and stained wood finished millwork with plastic laminate counter tops and backsplash Replace Millwork.- (3m) 243 $27,61 : Data Current as of: April 7, 214 2:21 PM Page 32 of 35

33 E Blinds** Vertical cloth and vinyl blinds to all exterior windows Replace Blinds.- (583m2) 229 $73,15 : E Furniture* Standard office furnishings throughout the facility Data Current as of: April 7, 214 2:21 PM Page 33 of 35

34 S8 SPECIAL ASSESSMENT K41.1 Barrier Free Route: Parking to Entrance* Barrier free access is provided to the building via 3 entrance ramps. Two ramps to the lower basement entrance and one large ramp to the upper main entrance. K41.2 Barrier Free Entrances* Barrier free entrances have automatic push buttons installed for ease of access. 2 K41.3 Barrier Free Interior Circulation* Each level is accessible from the outside of the building, although visitors and tenants with barrier free needs can not move to each level from within the building. K41.4 Barrier Free Washrooms* Barrier free washrooms were noted in the building. 24 K42.3 Other Codes* Dead end corridors in each wing on both main and basement levels. 2 - Poor K43.1 Asbestos* The site representative indicated an asbestos management plan is in place for the building. K43.4 Mould* No mould was reported or found. Data Current as of: April 7, 214 2:21 PM Page 34 of 35

35 K51.1 Site Documentation* Site Aerial Photo and Site Plan sketch. 213 Site Plan.jpg K51.2 Building Documentation* Building Main and Basement Plans 213 Basement Plan.jpg Data Current as of: April 7, 214 2:21 PM Page 35 of 35

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Foothills School Div #38 Sheep River School B3839A Okotoks Report run on: February 27, 29 2:28 PM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Horizon School Division #67 Ace Place Learning Center B4961A Taber Report run on: November 2, 28 4:18 PM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Norwood Elementary School B3234A Edmonton Report run on: January 11, 213 1:17 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Edmonton Glenrose Rehabilitation Building - Annex B25J Edmonton Report run on: February 15, 213 1:9 AM Building Name: Address: Location: Building

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Hazeldean Elementary School B3146A Edmonton Report run on: April 7, 211 5:2 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Avonmore Elementary School B347A Edmonton Report run on: March 8, 211 1:28 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Golden Hills School Division N. 75 Trochu Valley Outreach School B4948A Trochu Report run on: January 15, 29 9:3 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report David Thompson Regional Health Authority Bentley Care Centre B0992A Bentley Report run on: April 4, 2012 10:54 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Buffalo Trail Regional Div #28 Clandonald School B2943A Clandonald Report run on: January 11, 213 1:3 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Peace Wapiti School Div No. 76 Bonanza School B2463A Bonanza Report run on: April 11, 211 11:6 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205 5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1951 3,813 Page 1 of 25 1. Architectural / Structural & Site Exec Summary Hillcrest Public School is a two storey structure of masonry

More information

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free

Work Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free / / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Avalon Junior High School B346A Edmonton Report run on: April 7, 211 4:56 PM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Central Centennial Centre - Laundry Building B636B Ponoka Report run on: March 22, 213 1:8 AM Building Name: Address: Location: Building Id: Gross

More information

Sacred Heart Community Health Centre B1125A AVS. Asset Assessment Report. Sacred Heart Community Health Centre B1125A

Sacred Heart Community Health Centre B1125A AVS. Asset Assessment Report. Sacred Heart Community Health Centre B1125A AVS Asset Assessment Report Sacred Heart Community Health Centre B1125A Page 1 of 132 Asset ID Asset Name Location B1125A Sacred Heart Community Health Centre McLennan Address 350-3 Avenue N. W. Verification

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Spy Hill Complex - Southern Alberta Forensic Psychiatry Centre B6238B Calgary Report run on: March 28, 214 2:36 PM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-Edmonton Seventh Street Plaza (North Tower) B9771B Edmonton Report run on: March 18, 213 1:33 AM Building Name: Address: Location: Building Id:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Donnan Elementary / Junior High School B391A Edmonton Report run on: March 8, 211 1:35 AM Building Name: Address: Location: Building Id:

More information

Thurgood Marshall Recreation Center Summary

Thurgood Marshall Recreation Center Summary Thurgood Marshall Recreation Center Summary Address Building Purpose 5150 Mark Trail Way Dallas, TX 75232 Recreation Center Original Year of Construction 1970 Building Area 21,300 SF Inspection Date August

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Virginia Park Elementary School B3353A Edmonton Report run on: March 19, 29 11:58 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Stanley Jones Elementary School B2832A Calgary Report run on: April 7, 211 4:52 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Grande Prairie S Dist #2357 Aspen Grove School B3493A Grande Prairie Report run on: March 1, 213 11:16 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Chinook's Edge School Division No. 73 Mother Teresa School B4713B Sylvan Lake Report run on: January 29, 213 11:2 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 St. Kevin Catholic Junior High School B339A Edmonton Report run on: April 11, 211 11:2 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012

Existing Site Aerial Frederick High School Feasibility Study September 5, 2012 Existing Site Aerial Building Developmental History 1981 1966 1939 1977 1978 1955 1966 Exterior Roof: Most of existing roof has multi ply built up roofing. Some areas have gravel ballast, others have cap

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Northern Lights School Div #69 Cold Lake Public School B2965A Cold Lake Report run on: April 11, 211 11:13 AM Building Name: Address: Location: Building Id: Gross Area

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Winterburn Elementary / Junior High School B3367A Edmonton Report run on: April 1, 2010 11:02 AM Building Name: Address: Location: Building

More information

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Warnica PS, 9283

Simcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Warnica PS, 9283 5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1964 3,035 Page 1 of 27 1. Architectural / Structural & Site Exec Summary Warnica Public School is a one storey structure of masonry construction

More information

Timberglen Recreation Center Summary

Timberglen Recreation Center Summary Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,

More information

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School

HILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School HILLSIDE ELEMENTARY SCHOOL Overview: The is located at 98 Belmont Drive and consists of a two-story building which has had a number of additions added to it over the years, the latest of which was a two-story

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...

More information

4.1.3 Project Manual

4.1.3 Project Manual 4.1.3 Project Manual (*Section requires Filed Sub-Bid) PROCUREMENT AND CONTRACTING REQUIREMENTS GROUP Division 00 Procurement and Contracting Requirements Section 00 01 03 Project Directory Section 01

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Elbow Park Elementary School B262A Calgary Report run on: March 16, 211 4:2 PM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI

Toronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI BCA Report Porfolio Development Size Construction TCHC - All Op Units Scattered Units (CHU 20),005 Sq.Ft. 925 Floor Above Grade 2 Divisional Units Page of 43 Description This dwelling unit is a detached

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Grande Yellowhead Public School Division No. 77 Evansview School B3388A Evansburg Report run on: October 28, 211 9:53 AM Building Name: Address: Location: Building Id:

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Grande Prairie Roman Catholic Separate School Division No. 28 Ste. Marie Catholic School B447A Spirit River Report run on: March 7, 213 2:27 PM Building Name: Address:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Pembina Hills Regional Div #7 Dunstable School B253A Busby Report run on: January 1, 212 11:53 PM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Wildwood Elementary School B2865A Calgary Report run on: March 25, 2010 10:20 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Lethbridge School Dist #51 Lethbridge Collegiate Institute B3687A Lethbridge Report run on: April 12, 211 9:39 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 Holy Cross Catholic Elementary / Junior High School B3153A Edmonton Report run on: March 2, 212 1:54 AM Building Name: Address: Location: Building Id:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Woodbine Elementary School B2872A Calgary Report run on: March 5, 29 11:15 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Aspen Regional Health Authority Westlock Healthcare Centre B1184A Westlock Report run on: March 29, 2010 9:58 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 York Elementary School B3371A Edmonton Report run on: March 19, 29 11:59 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Capital Health Misericordia Site - Cabrini Centre B23E Edmonton Report run on: March 8, 212 9:4 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS Watercrest - Sand Hill - Columbia, SC 00 0110-1 TABLE OF CONTENTS DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS INTRODUCTORY INFORMATION Document 00 0101 Document 00 0110 Project Title Page CONTRACTING

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Greater Southern Public Francophone Education Region No. 4 Ecole de La Rose Sauvage B2746A Calgary Report run on: January 26, 2 4:3 PM Building Name: Address: Location:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Keeler Elementary School B2691A Calgary Report run on: March 27, 212 1:9 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 St. Brendan Elementary School B3288A Edmonton Report run on: April 7, 211 5:7 PM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Northern Gateway Reg Div #1 Sangudo Jr. / Sr. High School B399A Sangudo Report run on: January 11, 212 12:1 AM Building Name: Address: Location: Building Id: Gross Area

More information

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Abbott Elementary School B332A Edmonton Report run on: April 7, 211 4:55 PM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 La Perle Elementary School B3188A Edmonton Report run on: March 28, 214 11:41 AM Building Name: Address: Location: Building Id: Gross Area

More information

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3

Deficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3 School and Site Level Deficiencies Site Concrete Walks Are Damaged And Require Replacement 5539 4,000 SF 3 Bus drop-off area does not have a canopy. 14005 250 LF 5 Paved Play Requires Recoating And Resurfacing

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Victoria School Of Performing And Visual Arts B3351A Edmonton Report run on: March 19, 214 9:38 AM Building Name: Address: Location: Building

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Hillview Elementary School B3151A Edmonton Report run on: March 16, 212 2:15 PM Building Name: Address: Location: Building Id: Gross Area

More information

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements

CM ASSIGNMENT OF TEMPORARY FACILITIES see included IU Project Site Requirements SECTION A CM INSTRUCTIONS TO BIDDERS SECTION B BID CATEGORY DESCRIPTIONS & BID FORMS BC-07: Building HVAC and Plumbing BC-08: Building Electric BC-09: General Trades BC-10: Masonry BC-11: Precast Structural

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-North Beaverlodge Municipal Hospital B991A Beaverlodge Report run on: November 29, 213 1:13 AM Building Name: Address: Location: Building Id: Gross

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Aspen View Regional Div #19 Radway School B3898A Radway Report run on: January 11, 213 1:24 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

MODULAR BUILDING SPECIFICATIONS

MODULAR BUILDING SPECIFICATIONS Use Group A - Assembly B Business E Education I - Institutional Construction Type Type II Non Combustible Type V - Wood Floor 12 Outrigger Frame with Cross members Frame: 12 Perimeter Steel Main Beams

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Elk Island Pub Sch Reg Div #14 James Mowat School B3447A Fort Saskatchewan Report run on: March 16, 212 2:18 PM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary RCSSD #1 St. Jean Brebeuf Junior High School B2548A Calgary Report run on: April 15, 211 9:25 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report East Central Alta Catholic Separate School Reg Division No. 16 Theresetta Roman Catholic School B2928A Castor Report run on: May 2, 25 4:56 PM Facility Details Building

More information

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM)

SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) SPACE TYPE: PHYSICAL FITNESS (EXERCISE ROOM) Construction Criteria The unit costs for the Physical Fitness Center (Exercise Room) space type are based on the construction quality and design features in

More information

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2 School and Site Level Deficiencies Site K Play Area Requires Impact Resistant Material 1320 1 Ea. 2 Exterior Basketball Goals Are Damaged And Require Replacement 1322 1 Ea. 4 Bus drop-off area does not

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report St. Thomas Aquinas Roman Catholic Separate Regional Div No. 38 Sacred Heart School B4255A Wetaskiwin Report run on: March 28, 212 1:1 AM Building Name: Address: Location:

More information

TABLE OF CONTENTS Updated 1/2014 SECTION TITLE DATE

TABLE OF CONTENTS Updated 1/2014 SECTION TITLE DATE TABLE OF CONTENTS SECTION TITLE DATE Division 00 Procurement and Contracting Requirements 000101... Project Title Page 000116... CAD Standards 001116... Invitation to Bid 002113... Instructions to Bidders

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Belmont Elementary School B355A Edmonton Report run on: March 8, 211 1:31 AM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 James Short Memorial Elementary School B2682A Calgary Report run on: April 4, 213 9:2 AM Building Name: Address: Location: Building Id: Gross

More information

Whitley Shower Locker Toilet Facilities

Whitley Shower Locker Toilet Facilities Whitley Manufacturing Co., Inc. 201 W. First Street S. Whitley, IN 46787 Phone (260) 723-5131 Sales Fax (260) 723-6396 whitley@whitleyman.com Building Type Building Code Whitley Shower Locker Toilet Facilities

More information

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School

HERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School HERITAGE MIDDLE SCHOOL Overview: The is located at 20 Foxcroft Drive and consists of a three-story building with Three-Story Classroom and Multi-Purpose Room Additions completed in 2002. The building has

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Red Deer Public Schl Dist 14 Aspen Heights Elementary School B9368A Red Deer Report run on: April 18, 211 5:25 PM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Fort Mcmurray Roman Catholic Separate School Division No. 32 Sister Mary Phillps Elementary School B3434A Fort McMurray Report run on: January 1, 212 11:58 PM Building

More information

Delta Gamma Sorority Renovation Budget Scope 3/7/2018

Delta Gamma Sorority Renovation Budget Scope 3/7/2018 Delta Gamma Sorority Renovation Budget Scope 3/7/2018 PROJECT: Barbara Cerni Delta Gamma Sorority Tallahassee, Fla. This scope is based on the 50% Construction Documents drawn by BKJ Architecture dated

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Brander Gardens Elementarty School B363A Edmonton Report run on: March 8, 211 1:33 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Brightview Elementary School B364A Edmonton Report run on: March 8, 211 1:34 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Calgary School District #19 Ethel M. Johnson Elementary School B2627A Calgary Report run on: March 27, 212 1:5 AM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton School District No. 7 Strathcona Composite High School B3337A Edmonton Report run on: January 23, 27 3:55 PM Building Name: Address: Location: Building Id: Gross

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Rocky View Sch Div #41 Ralph McCall School B4755A Airdrie Report run on: March 26, 29 1:16 AM Building Name: Address: Location: Building Id: Gross Area (sq. m): Replacement

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Greater St. Albert Catholic Regional Division No. 29 Albert Lacombe Elementary School B462A St. Albert Report run on: January 18, 212 1:55 AM Building Name: Address: Location:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Chinook Regional Health Authority Raymond Health Centre B1143A Raymond Report run on: April 14, 21 4:24 PM Building Name: Address: Location: Building Id: Gross Area (sq.

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Grande Yellowhead Public School Division No. 77 Jasper Junior Senior High School B366A Jasper Report run on: March 8, 211 1:41 AM Building Name: Address: Location: Building

More information

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA

SANDTOWN CROSSING PROFESSIONAL OFFICE PARK Atlanta, GA Atlanta, GA LOCATED AT CAMP CREEK PARKWAY AND CAMPBELLTON ROAD For Sale or Lease Single units start at 1,176sf and can be combined to exact specification Custom Designed Medical and Professional finishes

More information

VOLUME 4 DIVISION SPECIFICATIONS

VOLUME 4 DIVISION SPECIFICATIONS Page 1 Section Title Consultant Pages VOLUME 4 DIVISION 00-01 SPECIFICATIONS Division 00 - Procurement and Contracting Requirements 00 01 07 SEALS PAGE All 5 00 01 11r6 TABLE OF CONTENTS All 7 00 21 13r1

More information

BENSON CITY HALL/POLICE DEPARTMENT FACILITY ASSESSMENT AND FEASIBILITY STUDY

BENSON CITY HALL/POLICE DEPARTMENT FACILITY ASSESSMENT AND FEASIBILITY STUDY BENSON CITY HALL/POLICE DEPARTMENT FACILITY ASSESSMENT AND FEASIBILITY STUDY Prepared for the City of Benson, Minnesota by Widseth Smith Nolting May 2016 City of Benson, Minnesota CITY HALL/POLICE STATION

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Grande Prairie Roman Catholic Separate School Division No. 28 Ecole St. Gerard Roman Catholic Separate School B3496A Grande Prairie Report run on: September 15, 21 11:3

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report The Board of Trustees of Chinook's Edge School Division No. 73 Hugh Sutherland School B9334A Carstairs Report run on: March 8, 211 1:57 AM Building Name: Address: Location:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 St. Anne Catholic Elementary School B3281A Edmonton Report run on: October 28, 211 9:53 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Alberta Health Services-North Aspen Corporate Offices B1185A Westlock Report run on: February 15, 213 1:12 AM Building Name: Address: Location: Building Id: Gross Area

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Aspen Regional Health Authority Smoky Lake Continuing Care Centre B1199A Smoky Lake Report run on: April 15, 9:24 AM Building Name: Address: Location: Building Id: Gross

More information

Asset Overview Report By Asset Name

Asset Overview Report By Asset Name School District: Coast Mountains Asset: STEWART ELEMENTARY Facility: STEWART ELEMENTARY Asset Number: 107177 Assets are ordered by Asset Name Currency: CAD Statistics FCI Cost: 2,543,413 FCI: 0.59 RI Cost:

More information

RECAPP Facility Evaluation Report

RECAPP Facility Evaluation Report RECAPP Facility Evaluation Report Edmonton RCSSD #7 St. Hilda Catholic Elementary / Junior High School B333A Edmonton Report run on: April 11, 211 11:19 AM Building Name: Address: Location: Building Id:

More information

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018 G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake

More information