IMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD
|
|
- Cora Summers
- 6 years ago
- Views:
Transcription
1 IMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD Date: Monday, th May 5 File Reference: 76C55mfcSchneidingAustralia Koikas Acoustics Pty Ltd Commercial, Unit 7, Forest Road, Bexley NSW 7 Date: th May 5 Reference: 76C55mfcSchneidingAustralia
2 DOCUMENT CONTROL Project Title Impact Noise Testing Timber ing & Acoustic Underlay Testing Schneid ing Australia Pty Ltd Our Project Number 77 Our File Reference File Link 76C55mfcSchneidingAustralia Z:\ACOUSTICS\ACOUSTICS 5\Compliance\Partition Testing Impact\76C55mfcSchneidingAustralia.docx Revision V /5/5 Prepared By Approved By Michael Fan Chiang Nick Koikas Client Schneid ing Australia Pty Ltd Attention: William Yu w.yu@schneidflooring.com.au The information contained herein should not be reproduced except in full. The information provided in this report relates to acoustic matters only. Supplementary advice should be sought for other matters relating to construction, design, structural, fire-rating, water proofing, and the likes. Date: th May 5 Reference: 76C55mfcSchneidingAustralia
3 IMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD CONTENTS. CONSULTANT'S BRIEF TESTING SAMPLES AND CONDITIONS IMPACT NOISE CRITERION BCA REQUIREMENT AAAC STAR RATING PERFORMANCE REQUIREMENTS IMPACT NOISE TESTING ASSESSMENT PROCEDURES AMBIENT BACKGROUND NOISE MEASUREMENT REVERBERATION TIME MEASUREMENTS INSTRUMENTATION AND CALIBRATION MEASURED RESULTS CONCLUSION... Appendix A - Performance Graphs and Calculations Date: th May 5 Reference: 76C55mfcSchneidingAustralia 3
4 IMPACT NOISE TESTING TIMBER FLOORING & ACOUSTIC UNDERLAY TESTING SCHNEID FLOORING AUSTRALIA PTY LTD. CONSULTANT'S BRIEF Koikas Acoustics was requested by Schneid ing Australia Pty Ltd to conduct impact noise tests on four (4) different timber floor systems. Impact noise tests were conducted with one type of timber flooring on four (4) different underlays. Testing was undertaken between two sole occupancy units in Campsie. The aim of the test was to calculate the impact isolation performance of the timber flooring used in conjunction with four (4) different underlays. Test results were compared to the acoustics requirements of Part F5 of BCA (Building Codes of Australia) and the standards prescribed by the Association of Australian Acoustical Consultants (AAAC). Date: th May 5 Reference: 76C55mfcSchneidingAustralia 4
5 . TESTING SAMPLES AND CONDITIONS Koikas Acoustics has been advised that the ceiling/floor system between the living/dining/kitchen areas of residential units is constructed with following building materials: Living/Dining/Kitchen Areas mm thick concrete slab; Approximately 8 mm deep suspended ceiling cavity; 5 mm thick insulation batts, and 3 mm thick plasterboard ceiling. Hereafter is referred to as the existing ceiling/floor system ECFS. The tests were conducted on the existing ceiling/floor system (ECFS) with the following timber flooring and acoustic underlays: Test : mm KSP Lignified ing over mm Rubber Underlay with Silver Foil Test : mm KSP Lignified ing over 3.5 mm Standard IXPE Underlay (Light Green) Test 3: mm KSP Lignified ing over mm HD IXPE (Green) Test 4: mm KSP Lignified ing over mm ST standard IXPE (White) Date: th May 5 Reference: 76C55mfcSchneidingAustralia 5
6 3. IMPACT NOISE CRITERION 3. BCA REQUIREMENT In accordance with current BCA, a floor in a Class or 3 building must have an D ntw +C tr (airborne) not less than 45 and an L ntw +Ci (impact) not more than 6 if it separates- (i) (ii) sole-occupancy units; or a sole-occupancy unit from a plant room, lift shaft, stairway, public corridor, public lobby or the like, or parts of a different classification. 3. AAAC STAR RATING PERFORMANCE REQUIREMENTS Reproduced from the AAAC Guideline for Apartment and Townhouse Acoustic Ratings, the following Table (Section C) describes the acoustic ratings with reference to the Star Rating System. Table. Star Rating requirements for Inter-tenancy Activities Published by the AAAC INTER-TENANCY ACTIVITIES Star 3 Star 4 Star 5 Star 6 Star (a) Airborne sound insulation for walls and floors - Between separate tenancies DnTw + Ctr Between a lobby/corridor & bedroom DnTw + Ctr Between a lobby/corridor & living area DnTw + Ctr (b) Corridor, foyer to living space via door(s) DnTw (c) Impact isolation of floors - Between tenancies LnTw Between all other spaces & tenancies LnTw (d) Impact isolation of walls - Between tenancies No Yes Yes Yes Yes - Between common areas & tenancies No No No Yes Yes Date: th May 5 Reference: 76C55mfcSchneidingAustralia 6
7 4. IMPACT NOISE TESTING The testing of the ceiling/floor system with the mm KSP Lignified ing and four (4) different underlays were conducted inside the unfurnished living/dining/kitchen spaces from one residential unit (upper floor level) to another unit (lower floor level) directly below within a residential building in Campsie on Thursday 7 th May ASSESSMENT PROCEDURES Spectrum sound level measurements of transmitted impact noise were recorded in /3 octave band centre frequencies between 5 and, Hertz. A standardised BSWA Technology Co. Type TM S/N 4454 Tapping Machine was used to generate the sound field in the source rooms for the impact noise test. Impact noise measurements were carried out in accordance with the recommendations of AS/NZS ISO 4.7:6 Field measurements of impact sound insulation of floors. This document provides information on appropriate measurement equipment and the proper implementation of measurement practices so as to achieve reliable results of impact sound insulation between rooms in buildings. For determining a single number quantity for impact sound insulation between rooms in buildings when measurements are conducted in-situ, L nt,w + Ci (weighted standardised impact sound pressure level + spectrum adaptation term), the relevant standard is AS/NZS ISO Impact sound insulation. The calculated L nt,w + Ci derived from applying the formulae in this standard allows for a comparison between these calculated levels and the nominated acceptable levels outlined in the Verification Methods of the Building Code of Australia (BCA). 4. AMBIENT BACKGROUND NOISE MEASUREMENT A measure of the underlying ambient noise was taken in the receiving rooms to account for the perceived noise floor in the space. Inaccuracies in the measurements and calculations can occur in areas of high ambient noise however the location of the site and receiver rooms meant little ambient noise was evident in this case. Ambient noise levels in each /3 octave frequency bands were measured to take into account the effect of ambient noise during the recording of the transmitted impact noise levels. Date: th May 5 Reference: 76C55mfcSchneidingAustralia 7
8 4.3 REVERBERATION TIME MEASUREMENTS To determine the L nt,w + Ci or L nw, reverberation time measurements need to be performed in the receiving rooms. The reverberation time in the receiver room is calculated to standardise the airborne/impact noise transmission measurements to reference reverberation time of.5 seconds as required by AS/NZS ISO 4.7:6 Section 3.4, and AS ISO Section 3.4. Reverberation time measurements were conducted using the balloon source method. This consisted of bursting a large balloon and measuring the decay of sound pressure level using a spectrum analyser. This transient response was analysed by the sound level meter and a measure of the reverberation time in /3 octave bands was used to calculate the standardised impact noise rating. 4.4 INSTRUMENTATION AND CALIBRATION NTi XL Type Approved (TA) precision spectrum analyser S/N AA-63-E was used to measure the impact noise levels. The equipment used for taking noise level measurements is traceable to NATA certification. Field calibrations were taken before and after the measurements with a NATA calibrated field calibrator. There was no system drifts. Date: th May 5 Reference: 76C55mfcSchneidingAustralia 8
9 5. MEASURED RESULTS The results of the impact noise test is summarised in Table Below. Table. Impact Noise Insulation Performance Summary Testing Samples L ntw, (Ci) BCA Criterion AAAC Star Rating FIIC Improvement in Acoustic Rating L ntw Test : ECFS 6 (-) N/A 4 - Test Ceiling/ System: mm KSP Lignified ing mm Rubber Underlay with Silver Foil ECFS Test Ceiling/ System: mm KSP Lignified ing 3.5 mm Standard IXPE Underlay (Light Green) ECFS Test 3 Ceiling/ System: mm KSP Lignified ing mm HD IXPE (Green) ECFS Test 4 Ceiling/ System: mm KSP Lignified ing mm ST Standard IXPE (White) ECFS Test 5 Ceiling/ System (Additional Testing): mm KSP Lignified ing ECFS 48 () () () LnTw+Ci () (-) 4 6. All testing results were compared to the acoustic rating tested with the bare concrete floor (Test ) and the improvement in LnTw rating is specified. The following are also noted: All tests were undertaken with mm thick concrete sub-base, 5 mm insulation batts fitted in 8 mm ceiling cavity and one layer of 3mm suspended plasterboard ceiling. The relation between Field Impact Isolation Class (FIIC) and Impact Isolation Class (IIC) can be described by the formula FIIC + 5 IIC. All the ceiling/floor system tested have also met the BCA 3 criterion (L ntw +Ci 6) for impact noise insulation. The lower the rating number the better the acoustic performance. The concrete slab is joined to the concrete wall which is a homogenous wall connecting from residential units on the upper floor level to the lower floor level. Ceiling/floor cavities without insulation batts will provide less impact insulation. It is expected that the acoustic performance will be worse by 5 rating points. Date: th May 5 Reference: 76C55mfcSchneidingAustralia 9
10 6. CONCLUSION Koikas Acoustics was requested by Schneid ing Australian Pty Ltd to undertake impact noise tests on ceiling/floor system with mm KSP Lignified ing and four (4) different types of underlay samples. The acoustic performances of various ceiling/floor configurations were calculated and compared against the acoustic requirements of the current BCA and AAAC star ratings. The calculated acoustic rating of each tested flooring sample was summarised and presented in Table of this report. Detailed graphically presentation of the acoustic performance of each tested flooring sample is attached as Appendix A. All tested flooring samples have complied with current BCA acoustic requirements and achieved AAAC Star Rating of 4. It is recommended that testing be conducted prior to any full fit-out as the sub-base ceiling floor system and the wall junctions can impact upon the resultant flanking noise in the unit below. The above report should be reproduced in full including the attached Appendix. Date: th May 5 Reference: 76C55mfcSchneidingAustralia
11 APPENDIX A A P P E N D I X A APPENDIX A
12 FIELD MEASUREMENTS OF IMPACT SOUND INSULATION OF FLOORS (TEST ) Date of T est : Thursday, 7 May 5 Project No. : 76 Testing Company : Koi kas Acoustics Checked by : Place of T est: Client Client Address Nick Koikas Residential Flat Unit i n Campsie Schneid in g Australia Pty Ltd Residential Flat Unit i n Campsie Name Thickness (mm ) Density (SI) Description mm KSP Lignified ing -- of mm Rubber Underlay with S ilver Foil -- mm concrete slab + 8 mm ceilin g cavity + 5 mm in sulation batts System 3 mm Pl asterboard ceil in g 3 -- Room Width : 3.5 m Length : 5.5 m Area : 9. 5 m Sample Width : m Length : m Area : m Room Surfaces Location Width Length Area Height Volume Walls Ceiling Receiver Rm Unit Plasterboard concrete Plasterboard Frequency L'nT (one-third octave) db f Sub Base Sub Base Sub Base Hz Underlay Standardised Impact Sound Pressure Level, L'nT, [db] Reference Line Sub B a se Sub- Base & Sub B a se, & Und erlay Frequency, f, [Hz] Sub Base Sub Base & Flo or Sub Base, & Underlay L'nT,w 6 AS ISO L'nT,w 48 AS ISO L'nT,w 48 AS ISO Ci - AS ISO Ci - AS ISO Ci AS ISO Ci(5-5 ) -9 AS ISO Ci(5-5 ) AS ISO Ci(5-5 ) AS ISO Ci(63- ) - AS ISO Ci(63- ) AS ISO Ci(63- ) AS ISO AAAC Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e FI IC 4 ASTM E7-4 FI IC 6 ASTM E7-4 FI IC 6 ASTM E7-4 Definitions of Noise Metrics 5 4 Improvement of Impact Sound Insulation FIIC: Field I mpact Insulation Class is a single-number rating of how well a floor system attenuates impact type sounds, such as footsteps. Calculated from third-octave band normalised impact sound pressure level data and referenced to m as described in ASTM E989. The hi gher the si ngle-number rating, the better i ts impact insulation performance. Impact Noise Reduction [db] Improveme nt of impact sou nd insulation delta L between (sub-b ase w ith underlay and fl oor covering) and (sub-base with floor covering) Improveme nt of impact sou nd insulation delta L between (sub-b ase w ith underlay and fl oor covering) and (sub- bas e) Third Octave Band, f, [Hz] L'nT,w: The Weighted Standardised Impact Sound Pressure Level when measured i n situ referenced to a reverberation time (RT6) of.5 seconds. Used by the AAAC to determi ne their respective Star Rating. Ci: Spectrum adaption term is a low frequency correction factor. Typically for massive fl oors such as concrete, the values are about zero while for timber joist floors Ci is positive because of the low resonant frequencies. Considers frequency range between -and 5 Hz. Ci(5-5): Same as above, but for the frequency range 5-5 Hz. Ci(5-): Same as above, but for the frequency range 5 - H z. AA AC Star R L'nT,w FIIC Comments Below BCA 6 Clearly Audible Audible Barely Inaudible Normally Inaudible
13 FIELD MEASUREMENTS OF IMPACT SOUND INSULATION OF FLOORS (TEST ) Date of T est : Thursday, 7 May 5 Project No. : 76 Testing Company : Koikas Acoustics Checked by : Place of T est: Client Client Address Nick Koikas Residential Flat Unit i n Campsie Schneid ing Australia Pty Ltd Residential Flat Unit i n Campsie Name Thickness (mm ) Density (SI) Description mm KSP Lignified ing -- of 3. 5 mm S tandard IXPE (Light Green) mm concrete slab + 8 mm ceiling cavity + 5 mm insulation batts System 3 m m Pl asterboard ceil in g 3 -- Room Width : 3.5 m Length : 5.5 m Area : 9. 5 m Sample Width : m Length : m Area : m Room Surfaces Location Width Length Area Height Volume Walls Ceiling Receiver Rm Unit Plasterboard concrete Plasterboard Frequency L'nT (one-third octave) db f Sub Base Sub Base Sub Base Hz Underlay Sub Base Standardised Impact Sound Pressure Level, L'nT, [db] Reference Line Sub Base Sub-Base & Sub Base, & Underlay Sub Base & Sub Base, & Underlay L'nT,w 6 AS I SO L'nT,w 48 AS I SO L'nT,w 47 AS I SO Ci - AS I SO Ci - AS I SO Ci AS I SO Ci( AS I SO Ci(5-5 ) AS I SO Ci(5-5 AS I SO Ci(63- - AS I SO Ci(63- ) AS I SO Ci(63- AS I SO AAAC Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e FI IC 4 ASTM E7-4 FI IC 6 ASTM E7-4 FI IC 6 ASTM E Frequency, f, [Hz] Definitions of Noise Metrics FIIC: 5 Improvement of Impact Sound Insulation Field I mpact Insulation Class is a single-number rating of how well a floor system attenuates im pact type sou nds, such as footsteps. Calculated from third-octave band normali sed im pact sou nd pressure level data and referenced to m as described in ASTM E989. The hi gher the single-number rating, the better its im pact insul ation performance. Impact Noise Reduction [db] Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub-base with floor covering) Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub- base) Third Octave Band, f, [Hz] L'nT,w: The Weighted Standardised Impact Sound P ressure Level when measured in s itu referenced to a reverberation time (RT6) of.5 seconds. Used by the AAAC to determine their respective Star Ci: Spectrum adaption term is a low frequency correction factor. Typicall y for m assive floors such as concrete, the values are about zero whil e for timber joist floors Ci is posi tive because of the low resonant frequencies. Considers frequency range between - Ci(5-5): Same as above, but for the frequency range 5-5 Hz. Ci(5-): Same as above, but for the frequency range 5 - Hz. AA AC Star R L'nT,w FIIC Below Clea rly Barely Normally Comments Audible BCA 6 Audible Inaudible Inaudible
14 FIELD MEASUREMENTS OF IMPACT SOUND INSULATION OF FLOORS (TEST 3) Date of Test : Project No. : 76 Testing Company : Koikas Acoustics Checked by : Place of Test: Client Client Address Description of System Thursday, 7 May 5 Nick Koikas Residential Flat Unit in Campsie Schneid ing Australia Pty Ltd Residential Flat Unit in Campsie Name Thickness (mm) Density (SI) mm KSP Lignified ing -- mm HD IXPE (Green) -- mm concrete slab + 8 mm ceiling cavity + 5 mm insulation batts mm Plasterboard ceiling 3 -- Room Width : 3.5 m Length : 5.5 m Area : 9.5 m Sample Width : m Length : m Area : m Room Surfaces Location Width Length Area Height Volume Walls Ceiling Receiver Rm Unit Plasterboard concrete Plasterboard Frequency L'nT (one-third octave) db f Sub Base Sub Base Sub Base Hz Underlay Standardised Impact Sound Pressure Level, L'nT, [db] Reference Line Sub Ba se Sub-Base & Sub Ba se, & Underlay Sub Base Sub Base & Sub Base, & Underlay L'nT,w 6 AS ISO L'nT,w 48 AS ISO L'nT,w 47 AS ISO Ci - AS ISO Ci - AS ISO Ci AS ISO Ci(5-5) -9 AS ISO Ci(5-5) AS ISO Ci(5-5) AS ISO Ci(63-) - AS ISO Ci(63-) AS ISO Ci(63-) AS ISO AAAC Star AAAC Guidleline AAAC 4 Star AAAC Guidleline AAAC 4 Star AAAC Guidleline FIIC 4 ASTM E7-4 FIIC 6 ASTM E7-4 FIIC 6 ASTM E Frequency, f, [Hz] Definitions of Noise Metrics FIIC: 4 Improvement of Impact Sound Insulation Field Impact Insulation Class is a single-number rating of how well a floor system attenuates impact type sounds, such as footsteps. Calculated from third-octave band normalised impact sound 34 pressure level data and referenced to m as described in ASTM 3 9 E989. The higher the single-number rating, the better its impact insulation performance. 4 L'nT,w: Impact Noise Reduction [db] The Weighted Standardised Impact Sound Pressure Level when measured in situ referenced to a reverberation time (RT6) of.5 seconds. Used by the AAAC to determine their respective Star Rating. Ci: Spectrum adaption term is a low frequency correction factor. Typically for massive floors such as concrete, the values are about zero while for timber joist floors Ci is positive because of the low resonant frequencies. Considers frequency range between and 5 Hz. Ci(5-5): Same as above, but for the frequency range 5-5 Hz. - Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub-base with floor covering) Ci(5-): Same as above, but for the frequency range 5 - Hz. Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub- base) AAAC Star R L'nT,w FIIC Third Octave Band, f, [Hz] Comments Below BCA 6 Clearly Audible Audible Barely Inaudible Normally Inaudible
15 FIELD MEASUREMENTS OF IMPACT SOUND INSULATION OF FLOORS (TEST 4) Date of T est : Thursday, 7 May 5 Project No. : 76 Testing Company : Koikas Acoustics Checked by : Place of T est: Client Client Address Nick Koikas Residential Flat Unit i n Campsie Schneid ing Australia Pty Ltd Residential Flat Unit i n Campsie Name Thickness (mm ) Density (SI) Description mm KSP Lignified ing -- of mm ST Standard IXPE (White) -- mm concrete slab + 8 mm ceiling cavity + 5 mm insulation batts System 3 m m Pl asterboard ceil in g 3 -- Room Width : 3.5 m Length : 5.5 m Area : 9. 5 m Sample Width : m Length : m Area : m Room Surfaces Location Width Length Area Height Volume Walls Ceiling Receiver Rm Unit Plasterboard concrete Plasterboard Frequency L'nT (one-third octave) db f Sub Base Sub Base Sub Base Hz Underlay Sub Base Standardised Impact Sound Pressure Level, L'nT, [db] Reference Line Sub Base Sub-Base & Sub Base, & Underlay Sub Base & Sub Base, & Underlay L'nT,w 6 AS I SO L'nT,w 48 AS I SO L'nT,w 48 AS I SO Ci - AS I SO Ci - AS I SO Ci AS I SO Ci( AS I SO Ci(5-5 ) AS I SO Ci(5-5 AS I SO Ci(63- - AS I SO Ci(63- ) AS I SO Ci(63- AS I SO AAAC Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e AAAC 4 Star AAAC Guidlelin e FI IC 4 ASTM E7-4 FI IC 6 ASTM E7-4 FI IC 6 ASTM E Frequency, f, [Hz] Definitions of Noise Metrics FIIC: 4 Improvement of Impact Sound Insulation Field I mpact Insulation Class is a single-number rating of how well a floor system attenuates im pact type sou nds, such as footsteps. Calculated from third-octave band normali sed im pact sou nd pressure level data and referenced to m as described in ASTM E989. The hi gher the single-number rating, the better its im pact insul ation performance. Impact Noise Reduction [db] Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub-base with floor covering) L'nT,w: The Weighted Standardised Impact Sound P ressure Level when measured in situ referenced to a reverberation time (RT6) of.5 seconds. Used by the AAAC to determine their respective Star Ci: Spectrum adaption term is a low frequency correction factor. Typicall y for m assive floors such as concrete, the values are about zero whil e for timber joist floors Ci is positive because of the low reson ant frequencies. Considers frequency range between Ci(5-5): Same as above, but for the frequency range 5-5 Hz. Ci(5-): Same as above, but for the frequency range 5 - Hz. Improvement of impact sound insulation delta L between (sub-base with underlay and floor covering) and (sub- base) AA AC Star R L'nT,w Third Octave Band, f, [Hz] FIIC 45 Below 55 Clea rly 6 65 Barely 7 Normally Comments Audible BCA 6 Audible Inaudible Inaudible
THE FRAME RESIDENTIAL DEVELOPMENT, SPORTCITY, MANCHESTER THE CONCRETE CENTRE LTD 1.0 INTRODUCTION...2
Concrete Centre Limited The Frame Residential Development, Sport City, Manchester Sound Insulation Test Report 2 August 2005 PROJECT: CLIENT: The Frame Residential Development, Sportcity, Manchester Concrete
More informationAcoustic Design Criteria
Apartment Acoustics Apartment Buildings Acoustic Design Criteria Building Code of Australia: - Intertenancy walls and floors - Corridor walls and doors - Floor impact isolation - Lift, stair and core walls
More informationKINETICS NOISE CONTROL TEST REPORT # AT001084
KINETICS NOISE CONTROL TEST REPORT # AT001084 KINETICS NOISE CONTROL PRODUCTS: o MODEL ISOGRID ACOUSTICAL RATINGS: o STC 63 o IIC 50 TESTING AGENCY & REPORT NUMBER: o NRC-CNRC o B-3463.6 KINETICS DRAWING
More informationCASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS
Abstract CASE STUDY OF THE SOUND REDUCTION OF VARIOUS RESIDENTIAL GLAZING TREATMENTS Greg Barry 1, Darren Jurevicius 2 and Matthew Stead 3 1 Resonate Acoustics, Adelaide SA 5082, Australia Email: greg.barry@resonateacoustics.com
More informationKINETICS NOISE CONTROL TEST REPORT #AT001110
KINETICS NOISE CONTROL TEST REPORT #AT001110 KINETICS NOISE CONTROL PRODUCTS: o NONE ACOUSTICAL RATINGS: o STC 53 o IIC 29 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o REPORT NO. A1-010601.1 o DATED:
More informationCanterbury Road, Campsie Acoustic Impact Assessment for DA Submission
Report No. 20C-11-0098-TRP-463732-2 8 th August 2011 Acoustics Vibration Air Quality Mechanical & Structural Systems Fluid Mechanics Sustainability Building Technologies DOCUMENT CONTROL REPORT NO: LIBRARY
More informationKINETICS NOISE CONTROL TEST REPORT #AT001067
KINETICS NOISE CONTROL TEST REPORT #AT001067 KINETICS NOISE CONTROL PRODUCTS: o FLM- NEOPRENE PAD ACOUSTICAL RATINGS: o STC 69 o IIC 61 TESTING AGENCY & REPORT NUMBER: o NATIONAL RESEARCH COUNCIL OF CANADA
More informationLaboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO )
Reference no. T1638-1 Laboratory measurements of the reduction of transmitted impact sound by floor coverings on a heavyweight reference floor (According to ISO 10140 3) AUCKLAND UNISERVICES LIMITED a
More informationKINETICS NOISE CONTROL TEST REPORT #AT001035
KINETICS NOISE CONTROL TEST REPORT #AT001035 KINETICS NOISE CONTROL PRODUCTS: o RIM I-2-16 ACOUSTICAL RATINGS: o STC 66 o IIC 63 TESTING AGENCY & REPORT NUMBER: o NRC-CANADA o B-3140.1 KINETICS DRAWING
More informationThis page was. intentionally. left blank
CONSTRUCTION Measurement of Airborne Sound Insulation of 8 Wall Assemblies Measurement of Airborne and Impact Sound Insulation of 29 Floor Assemblies Nordic Engineered Wood Report No. A1-006070.10 July
More informationKINETICS NOISE CONTROL TEST REPORT #AT001108
KINETICS NOISE CONTROL TEST REPORT #AT001108 KINETICS NOISE CONTROL PRODUCTS: o 1 RIM ACOUSTICAL RATINGS: o ATSC 49 o FIIC 48 TESTING AGENCY & REPORT NUMBER: o ACENTECH, INC. o PROJECT NO. 619530 o DATED:
More informationEdition October May (always refer to the latest manual as set out on
LOXO PANEL INTER AND BLOCK TENANCY SYSTEMS WALLS TECHNICAL FIRE AND ACOUSTIC MANUAL REPORT PRODUCT DESCRIPTION AND BUILDING SYSTEM DETAILS Edition October May 2015 2014 (always refer to the latest manual
More informationSOUND INSULATION TESTING IN DWELLINGS
SOUND INSULATION TESTING IN DWELLINGS Chris Dilworth, AWN Consulting This Presentation Discusses the standards by which we judge sound insulation performance. Presents the results of sound insulation tests
More informationCJ Buma. To: Steelform Building Products Inc. Wednesday, 2007 May Avenue Edmonton, AB, T6B 2V2. Attn: Mr.
To: Steelform Building Products Inc. Wednesday, 2007 May 7 4104 69 Avenue Edmonton, AB, T6B 2V2 Attn: Mr. Marty MacDonald aci Acoustical Consultants Inc. Suite 107, 9920-63Ave Edmonton, Alberta, Canada
More informationMeasurements of junction vibration level differences of timber framed constructions
Measurements of junction vibration level differences of timber framed constructions Anders HOMB 1 1 NTNU Trondheim. Norwegian University of Science and Technology ABSTRACT Flanking transmission of supporting
More informationGIB Quiet Clip GIB CBI March Features and Benefits
CBI - 5113 March 2002 GIB Quiet Clip Features and Benefits No special flooring systems required Easy fit Installation Significantly improves low frequency sound transmission Significantly improves low
More informationA working acoustician s guide to compliance and the NCC(BCA)
Proceedings of ACOUSTICS 2016 A working acoustician s guide to compliance and the NCC(BCA) Roger Hawkins Palmer Acoustics. (Australia) Pty Ltd, Park Ridge, Queensland, Australia ABSTRACT The Building Code
More informationJune Residential Refurbishment Separating walls
June 2010 Residential Refurbishment 3.6.1 Separating walls Residential refurbishment 3.0 Residential Refurbishment Separating Walls Contents Introduction find online page Solution optimiser and pathfinder
More informationDelia Chamberlain, Vice President, Kolay Floors Steve Hedback and Joel Esselstrom, SSA Acoustic, LLP
SSA Acoustics LLP 222 Etruria St, Suite 100 Seattle, WA 98109 Office: (206) 839-0819 TO: FROM: DATE: May 24, 2017 Delia Chamberlain, Vice President, Kolay Floors Steve Hedback and Joel Esselstrom, SSA
More informationAcoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A August 2016 CONSTRUCTION
CONSTRUCTION Acoustic Testing of CLT and Glulam Floor Assemblies Nordic Engineered Wood Report No. A1-008253.1 19 August 2016 The results in this report only apply to the specimen that was tested Page
More informationSound Insulation Test Easterton of Duntelchaig, Farr, Inverness, IV2 6AW
10 Colinton Road Edinburgh, EH10 5DT T:0845 062 0000 F: 0131 455 2563 E: rmp@napier.ac.uk I: w w w.rmp.biz BRIEF FOR CONSULTANCY: To assess the level of sound insulation of the party wall in the new build
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E Rendered to REGUPOL AMERICA
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 492 AND ASTM E 2179 Rendered to REGUPOL AMERICA Series/Model: Regupol 6 mm SonusWave Impact Sound Underlayment Specimen Type: Concrete Slab - 152 mm Overall Size:
More informationDesign Standards Brief Section 13 Acoustics
Property Services Design Standards Brief Section 13 Acoustics Issue 6 2009 Section 13 Acoustics 13 CONTENTS 13.1 INTRODUCTION...3 13.2 NOMENCLATURE...3 13.3 APPLICABLE STANDARDS...4 13.4 ARCHITECTURAL
More informationLABORATORY MEASUREMENTS OF THE SOUND REDUCTION INDEX ROCKWOOL ABLATIVE COATED BATTS
eport No. L/3132 Page 1 of 10 for ockwool UK Limited Pencoed Bridgend CF35 6NY Dated: 30 November 2009 LABOATOY MEASUEMENTS OF THE SOUND EDUCTION INDEX OF OCKWOOL ABLATIVE COATED BATTS eport Author: M
More informationSignatures are required on this document for an official laboratory test report. Copies of this document without signatures are for reference only.
ASTM E 90: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements ASTM E 492: Laboratory Measurement of Impact Sound Transmission through Floor- Ceiling Assemblies Using
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationCertificate number: CM40087 Rev3
Certification Body: ABN: 80 111 217 568 JAS-ANZ Accreditation No. Z4450210AK PO Box 7144, Sippy Downs Qld 4556 +61 (07) 5445 2199 www.certmark.org Certificate Holder: ABN: 22 750 783 065 19 Lowermill Rd,
More informationSECTION E Ceiling Systems. Contents. Introduction. Design Considerations. Installation. Components. System Specifications. Floor/Ceiling Systems
SECTION E Ceiling Systems. Contents. SUBJECT Introduction Design Considerations Installation Components PAGE E2 E2 E4 E4 System Specifications Floor/Ceiling Systems Roof/Ceiling Systems E6 E12 Floor or
More informationImportant Notice. QuietRock by PABCO Gypsum Cherry Street Newark, CA
Important Notice In August 1, 2013, PABCO Gypsum, a division of PABCO building products, LLC acquired the QuietRock business and operations from Serious Energy, Inc. Serious Energy, Inc. corporate structure
More informationSOUND SOLUTIONS TO MEET THE APPROVED DOCUMENT E (2003 EDITION) August 2008
SOUND SOLUTIONS TO MEET THE APPROVED DOCUMENT E (2003 EDITION) August 2008 PART E AT A GLANCE The New Approved Document E, (2003 Edition) was implemented on 1st July 2003. This applies to houses, flats,
More informationAcoustic Detailing For Steel Construction
SCI PUBLICATION P372 Acoustic Detailing For Steel Construction A G J Way MEng CEng MICE G H Couchman MA PhD CEng MICE Published by: The Steel Construction Institute Silwood Park Ascot Berkshire SL5 7QN
More informationWhite Paper. A guide to the acoustic performance of Smarts Systems Products. Building Regulations Document E Resistance to the passage of sound
White Paper. A guide to the acoustic performance of Smarts Systems Products. Building Regulations Document E Smart Systems Ltd. January 2007 Contents Building Regulations...4 Acoustic Performance - Overview...5
More informationTesting Procedure: AS ISO
RMIT University Building 1 Level 1 Room 1 124 La Trobe Street Melbourne VIC 3000 Australia GPO Box 2476V Melbourne VIC 3001 Australia Tel. +61 3 9925 2000 Fax +61 3 9925 2000 www.rmit.edu.au REPORT ON
More informationASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements
ASTM E 90-09: Laboratory Measurement of Airborne Sound Transmission of Building Partitions and Elements 1 of 7 TEST : Acoustical Surfaces, Inc. Report Date: May 25, 2011 Test Date: September 28, 2010 Test
More informationSWEDISH STANDARD SS
SWEDISH STANDARD SS 02 52 68 Approved 2001-06-21 Edition 1 Acoustics Sound classification of spaces in buildings Institutional premises, rooms for education, preschools and leisure-time centres, rooms
More informationSPECIFIERS GUIDE VERSION 3 OCT 2016
SPECIFIERS GUIDE VERSION 3 OCT 2016 CONTENTS ABOUT US... 1 ACOUSTIFLOR Concrete Structure... 3 Wooden Structure... 13 DEKCRADLE Product Information... 22 Datasheet... 26 WARRANTIES / INSTALL MANUAL AcoustiFlor...
More informationThe Optimization of a Wooden Floor Design Based on Validated Finite Element Models
The Optimization of a Wooden Floor Design Based on Validated Finite Element Models Jeffrey MAHN 1 ; Carl HOPKINS 2 ; Marios FILIPPOUPOLITIS 2 ; Ulrich SCHANDA 3 ; Raphael VÖLTL 3 ; Luboš KRAJČI 4 1 National
More informationSection Sound Control
Ministry of Municipal Affairs PROPOSED CHANGE TO THE 2012 BUILDING CODE O. REG. 332/12 AS AMENDED CHANGE NUMBER: SOURCE: B-09-11-01 Ontario-NBC CODE REFERENCE: Division B / 9.11. DESCRIPTION OF THE PROPOSED
More informationRSIC-1 ACOUSTIC ASSEMBLY
RSIC-1 ACOUSTIC ASSEMBLY FLOOR/CEILING ASSEMBLY DIRECT FIX TO CONCRETE SLAB FCS3 DSWA FIIC 69 PAC INTERNATIONAL Inc. Toll Free 866-774-2100 Telephone 503-649-7700 CONSTRUCTION * Ceramic Tile * 1/4" James
More informationFootfall vibration analysis of a high precision manufacturing facility
Footfall vibration analysis of a high precision manufacturing facility Jason GAEKWAD 1 ; Yong Keat LEE 1 ; Neil MACKENZIE 1 1 Aurecon Pty Ltd, Australia ABSTRACT High tech manufacturing facilities often
More informationRR-337 Apparent Sound Insulation in Cold-Formed Steel-Framed Buildings. Christoph Hoeller, David Quirt, Berndt Zeitler, Ivan Sabourin.
Construction RR-337 Apparent Sound Insulation in Cold-Formed Steel-Framed Buildings Christoph Hoeller, David Quirt, Berndt Zeitler, Ivan Sabourin 07 April 2017 Page 1 of 108 DRAFT 1 st edition October
More information4-Acoustics: Background
4-Acoustics: Background In the past acoustics for buildings especially concert halls was done by luck. A design would be done that worked well and then it would be mimicked. Other times awful designs emerged
More informationMeasurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes
Prof. Dr.-Ing. H.M. Fischer Report Nr. FEB/FS-75/13 3e Measurement of the insertion loss of the pipe clamp FRSPlus for 4 sewer pipes Client: fischerwerke GmbH & Co. KG Weinhalde 14 18 72178 Waldachtal
More informationStructural Products. Multideck 50-V3 Galvanised Steel Floor Decking System
Structural Products & Systems Multideck Multideck 50-V3 Galvanised Steel Floor Decking System Meadowhall Extension, Sheffield UK. Image courtesy of MSW (UK) Ltd. 2 Introduction Structural Products & Systems,
More informationPREDICTING SOUND INSULATION PERFORMANCE
Auckland Christchurch Kuala Lumpur Melbourne Sydney Wellington www.marshallday.com PREDICTING SOUND INSULATION PERFORMANCE USING SOUND INSULATION SOFTWARE TO PREDICT NON-ACHIEVEMENT OF PERFORMANCE STANDARDS
More informationThe uncertainty in sound insulation of an industrially prefabricated lightweight timber construction
The uncertainty in sound insulation of an industrially prefabricated lightweight timber construction Rikard ÖQVIST 1 1 Tyréns AB, Sweden ABSTRACT The variations in sound insulation are often large for
More informationAustralian Standard. Methods for determination of sound transmission class and noise isolation class of building partitions AS
AS 1276 1979 Australian Standard Methods for determination of sound transmission class and noise isolation class of building partitions The following scientific, industrial and governmental organizations
More informationTimber-framed Systems for External Noise
11 Timber-framed Systems for External Noise Technical Design Guide issued by Forest and Wood Products Australia Technical Design Guide issued by Forest and Wood Products Australia Technical Design Guide
More informationMEASUREMENT AND LEVEL OF INFRASOUND FROM WIND FARMS AND OTHER SOURCES
MEASUREMENT AND LEVEL OF INFRASOUND FROM WIND FARMS AND OTHER SOURCES Chris Turnbull 1, Jason Turner 1 and Daniel Walsh 2 1 Sonus Pty Ltd, 17 Ruthven Avenue, Adelaide, South Australia 5000 2 Pacific Hydro
More informationAcoustics 08 Paris 3059
Innovative building systems to improve the acoustical quality in lightweight masonry constructions: Application of resilient joints at junctions - PART 2: Study cases modelled according to the standard
More informationGuide for Sound Insulation in Wood Frame Construction
National Research Council Canada Conseil national de recherches Canada Guide for Sound Insulation in Wood Frame Construction Research Report 219, March 2006 J.D. Quirt, T.R.T. Nightingale, F. King Preamble
More informationDay Night Day Night Day Night Residential site and amphitheatre Green Non residential site boundary Red
Plant Areas External plant must meet the following noise suppression requirement as adopted by the Landlord: 1. Air handling units 45db measured at 3metres from source. 2. Heat rejection plant 45db measured
More informationClassification scheme of floor impact sounds with the standard rubber ball in dwellings
Classification scheme of floor impact sounds with the standard rubber ball in dwellings Hiroshi SATO 1 ; Junichi YOSHIMURA 2 1 National Institute of Advanced Industrial Science and Technology, Japan 2
More informationDesign. Boral CinemaZone Fact Sheet. Windows. Acoustic sealants. Sound absorptive panels. Ventilation. Floor coverings. The vision.
Windows Like doorways, windows can be a significant source of sound leakage. For maximum isolation, windows should either be removed or built over internally - leaving the house facade unaffected. If natural
More informationFire Safety and Performance of Wood in Multi-Residential and Commercial Buildings. Boris Iskra Forest & Wood Products Australia
Fire Safety and Performance of Wood in Multi-Residential and Commercial Buildings Boris Iskra Forest & Wood Products Australia This Presentation 1. Fire Hazard Properties Building Code of Australia Volume
More informationExperimental measurements of flanking transmission in CLT structures
Challenges and Solutions in Acoustical Measurements and Design: Paper ICA216-41 Experimental measurements of flanking transmission in CLT structures Luca Barbaresi (a), Federica Morandi (b), Massimo Garai
More informationicore HR outperforms other building boards in many important ways including the following:
icore HR is a new and innovative system designed to provide high performance separating walls between units and apartments in high-rise commercial projects. icore HR system provides exceptional fire and
More informationInsulwhite. Insulation WHITE-FACED THERMO REFLECTIVE INSULATION
Insulation A4/6 TB055W AW2244 Issue 6 Oct 2017 WHITE-FACED THERMO REFLECTIVE INSULATION Innovative cross-linked closed cell insulation core 3-in-1 Insulation, vapour barrier and radiant barrier Helps achieve
More informationIndex. Other Speedpanel Projects:
Company Profile Speedpanel is an unlisted public company with a manufacturing facility based in Kilsyth, Victoria. Speedpanel was introduced to the Australian market early in 2000 and has grown steadily
More informationSelecting partitions
email: bgtechnical.enquiries@bpb.com www.british-gypsum.com/health Introduction 6 Performance matrix 8 Worked examples 0 your partition type Solutions up to R w db This section will guide you through the
More informationE R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to SENECA RADIANT TECHNOLOGIES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to SENECA RADIANT TECHNOLOGIES Series/Model: Floor/Ceiling Assembly Specimen Type: Dimensional Lumber - 2x10 Overall Size: 3023 mm by
More informationLECTURE 3 Impact sound insulation
Rak-43.3415 Building Physics Design 2 ACOUSTICAL DESIGN Autumn 2016 LECTURE 3 Impact sound insulation Matias Remes, M.Sc. FISE A acoustics Impact sound insulation (Askelääneneristys) When one needs to
More informationAustralian/New Zealand Standard
AS/NZS 4859.1:2002 (Incorporating Amendment No. 1) AS/NZS 4859.1:2002 Australian/New Zealand Standard Materials for the thermal insulation of buildings Part 1: General criteria and technical provisions
More informationTechnical Features Sound Construction Design Aid For Office Acoustics
Technical Features Sound Construction Design Aid For Office Acoustics HOW TO DETERMINE COMPOSITE SOUND ISOLATION RATINGS FOR OFFICES BY COMBINING PERFORMANCE OF WALLS, CEILINGS AND FLOORS by Vincent M.
More informationDETAILED ANALYSIS OF MEASUREMENT RESULTS OF FLANKING TRANSMISSION ACROSS A JUNCTION COM- POSED OF DOUBLE WALLS CARRIED OUT ON A HALF SCALED TEST BENCH
DETAILED ANALYSIS OF MEASUREMENT RESULTS OF FLANKING TRANSMISSION ACROSS A JUNCTION COM- POSED OF DOUBLE WALLS CARRIED OUT ON A HALF SCALED TEST BENCH. Charlotte Crispin, Christian Mertens and Arne Dijckmans
More informationReport for CSR Hebel. Impact of various wall and floor construction options on 5 star compliance for two houses. by Tony Isaacs Consulting Pty Ltd
Tony Isaacs Consulting Pty Ltd Sustainable Buildings Specialist Report for CSR Hebel Impact of various wall and floor construction options on 5 star compliance for two houses by Tony Isaacs Consulting
More informationBuilding regulations now in force
BCA Section J: Guide to compliance Publication date July 2008 Building regulations now in force BCA SECTION J: Mandatory energy efficiency measures for non-residential construction The new BCA Section
More informationinter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering August 2000, Nice, FRANCE
Copyright SFA - InterNoise 2000 1 inter.noise 2000 The 29th International Congress and Exhibition on Noise Control Engineering 27-30 August 2000, Nice, FRANCE I-INCE Classification: 5.1 INCLUSION OF DAMPING
More informationSpecialists in Acoustic Flooring and House to Flat Conversions
Sound Solution Consultants Ltd Po Box 755 Capel St Mary Ipswich Suffolk IP9 2WF Tel No: 0845 5212096 Fax No: 0845 5212097 Email: mpconsultservice@aol.com Specialists in Acoustic Flooring and House to Flat
More informationSUGGESTED COST-EFFECTIVE COLD-FORMED STEEL FIRE AND ACOUSTIC-RATED WALL AND FLOOR/ CEILING ASSEMBLIES FOR MULTI-UNIT STRUCTURES
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 SUGGESTED COST-EFFECTIVE COLD-FORMED STEEL FIRE AND ACOUSTIC-RATED WALL AND FLOOR/
More informationPart E robustdetails. robustdetails. January 2017 Update Pack. Dear Colleague,
Part E Pack Dear Colleague, This is the first 2017 update to the Part E Robust Details Handbook. In this update pack, we have focussed on clarifying the situation on incorporating underfloor heating (UFH)
More informationH R0 ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492. Rendered to AMORIM CORK COMPOSITES
ACOUSTICAL PERFORMANCE TEST REPORT ASTM E 90 AND ASTM E 492 Rendered to AMORIM CORK COMPOSITES Series/Model: AcoustiCORK ECOx2 Sound Reduction Underlayment for LVT Plank Flooring Specimen Type: 152 mm
More informationEvidence of Performance Joint sound reduction of filling material
Evidence of Performance Test Report No. 13-002455-PR01 (PB Z6-K02-04-en-01) ift Rosenheim 13.09.2013 Client Soudal N. V. Everdongenlaan 18-20 2300 Turnhout Belgium Product Designation Thickness of sealant
More informationThe Perfect Choice for Mezzanines in Custom Metal Buildings
The Perfect Choice for Mezzanines in Custom Metal Buildings Ecospan composite floor system. The Ecospan Composite Floor System is an innovative, simple, effective and economical method of providing all
More informationHEAVY-WEIGHT FLOOR IMPACT SOUND IN REINFORCED CONCRETE STRUCTURES
HEAVY-WEIGHT FLOOR IMPACT SOUND IN REINFORCED CONCRETE STRUCTURES J. Y. Jeon,J. H. Jeong and S. H. Seo School of Architectural Engineering, Hanyang University, Seoul 133-791, Korea Abstract The purpose
More informationFire Resistant: Achieves FRL levels of 90/90/90 for load bearing walls.
( ) is a new and innovative system designed to provide high performance separating walls between units and apartments in low-rise residential and commercial projects. provides exceptional fire and acoustic
More informationInsulated Roof & Wall Panels. Foilback KS1000 FB Insulated Roof Panels. Product Data Sheet
Insulated Roof & Wall Panels Foilback KS1000 FB Insulated Roof Panels Overview Kingspan Foilback is supplied with a pre-painted Steel external (Aluzinc also available on request) with a choice of silver
More informationGARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES
GARAGE STRUCTURE VIBRATION TRANSMISSION TO HUMAN OCCUPIED SPACES Jack B. Evans* 1 1 JEAcoustics / Engineered Vibration Acoustic & Noise Solutions 175 West Koenig Lane, Austin, Texas 78756, USA Evans(at)JEAcoustics.com
More informationCI/SfB. November Design Guide Concrete block masonry
CI/SfB November 1997 Ff Design Guide Concrete block masonry Design Guide concrete block masonry This Topblock Design Guide contains detailed information on the design and performance of constructions using
More informationImpact Noise Reduction of Underfloor Heating Systems
Impact Noise Reduction of Underfloor Heating Systems Antonino Di Bella, Leonardo Luison DFT - Department of Technical Physics, University of Padova, Padua, Italy. Summary Underfloor heating systems are
More informationIMPACT SOUND REDUCTION OF CONCRETE LAYERS CONTAINING CORK GRANULES
IMPACT SOUND REDUCTION OF CONCRETE LAYERS CONTAINING CORK GRANULES Anabela Moreira 1, Julieta António 2, António Tadeu 2 1 Department of Civil Engineering, Polytechnic School of Tomar-IPT, Campus Tomar,
More informationControlled Environments. Product Data Sheet. Controlled Environment Panel System KS1100 CS
Controlled Environments Controlled Environment Panel System KS1100 CS Overview Kingspan controlled environment panel systems are designed for use within temperature controlled and hygiene safe environments
More informationInsuliner. Insulation REFLECTIVE INSULATION FOR USE WHERE
Insulation A4/8 TB055G2 AW2235 Issue 8 Sep 2017 Insuliner REFLECTIVE INSULATION FOR USE WHERE it acts as the WALL OR CEILING LINING Group 2 NCC fire classification Designed for warehouses and commercial
More informationCorporate Environments
Acoustics and the Impact on Corporate Environments falconproducts.com Achieving High-Quality Acoustics in Corporate Settings Knowledge is power. Here s what you need to know about sound, noise and creating
More informationVisions for the Future of Housing
Proceedings of the XXXVIII IAHS World Congress Visions for the Future of Housing edited by Oktay Ural Muhammed Şahin Derin Ural International Association for Housing Science Proceedings of the XXXVIII
More informationCeiling Attenuation Class Systems SYSTEMS 280
SYSTEMS 280 Ceiling Attenuation Class Ceiling Attenuation Class (CAC) ceiling systems display resistance to sound passing up and over a wall. The sound insulation rating given for the ceiling system indicates
More informationSound Insulation for Glass and Panel
SEMINAR ON TESTING AND CERTIFICATION OF GREEN CONSTRUCTION MATERIALS Sound Insulation for Glass and Panel Ir Dr CHONG Fan HIGHLIGHTS 1. Sound insulation of building construction 2. Sound insulation tests
More informationCasoLine MF Concealed grid MF suspended ceiling system
Concealed grid MF suspended ceiling system! This section includes updated information, added since it was first published in July 009. Please see the WHITE BOOK update document for details. Last updated
More informationURSA MINERAL WOOL URSA Acoustic Roll
- 073_Layout 1 02/10/2017 10:19 Page 1 URSA UK LTD Crest House 102-104 Church Road Teddington, Middlesex TW11 8PY United Kingdom Tel : 020 8977 96 97 Fax : 020 8977 94 56 Web : www.ursa-uk.co.uk E-mail
More informationGTEK TM SOUND GTEK TM IMPACT
APRIL 2016 TECHNICAL BROCHURE GTEK TM SOUND GTEK TM IMPACT gtekplasterboard.com.au GTEK TM SOUND WHY GTEK TM? WITH OUR ALL-AUSTRALIAN GTEK RANGE OF INTERIOR LINING PRODUCTS, YOU BENEFIT FROM SUSTAINABLE,
More informationARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS
13080/KIN BuyLine 1062 Providing solutions to common noise and vibration problems since 1958. ARCHITECTURAL AND STRUCTURAL NOISE CONTROL SOLUTIONS IIC 51 STC 72 FLOOR/CEILING STC 84 IIC 70 FLOOR/CEILING
More informationNYU Core: Post-EIS Façade Improvement Acoustical Assessment
NYU Core: Post-EIS Façade Improvement Acoustical Assessment Revised Version: September 24, 2012 Prepared by: AKRF, Inc. for New York University DRAFT FOR CLIENT REVIEW Table of Contents Introduction...
More informationNew Dutch Code of Practice NTR 5076 for equipment noise in dwellings and apartments
New Dutch Code of Practice NTR 5076 for equipment noise in dwellings and apartments Wim Beentjes MSC LBP Sight.BV PObox 1475 3430BL Nieuwegein, The Netherlands. Summary During the last decade there were
More informationJ. A. FERREIRA, F. B. DINIZ, A. FERREIRA and P. H. T. ZANNIN
ARCHIVES OF ACOUSTICS 29, 1, 123 127 (2004) TECHNICAL NOTES EVALUATION OF ACOUSTICAL PARAMETERS OF A BRAZILIAN POPULAR HOUSING MODEL J. A. FERREIRA, F. B. DINIZ, A. FERREIRA and P. H. T. ZANNIN Laboratory
More informationACOUSTIC DESIGN OF THE AUDITORIUM IN THE CHURCH OF RISPESCIA
ACOUSTIC DESIGN OF THE AUDITORIUM IN THE CHURCH OF RISPESCIA Sergio Luzzi and Lucia Busa Vie en.ro.se. ingegneria, Via Stradivari, 19, 50127 Florence, Italy email: sergio.luzzi@vienrose.it The authors
More informationAcoustic design of industrial spaces. The reduction of noise levels and increase of production
Acoustic design of industrial spaces The reduction of noise levels and increase of production Contents. Introduction. Acoustic measurements Effect of acoustical treatment with suspended ceiling and wall
More informationAcoustic Cradle Levelling System
Acoustic Cradle Levelling System CONCRETE FLOOR CRADLE & BATTEN Datasheet 52 01 18mm t&g chipboard @ 400mm centres 02 40mm min directly applied sand & cement or proprietary screed (min 80kg/m 2 ) 03 03
More informationRetroshield XL TM. Insulation THERMO REFLECTIVE INSULATION
Insulation A4/6 TB055F AW2002 Issue 4 Sept 2015 THERMO REFLECTIVE INSULATION Innovative cross-linked closed-cell insulation core Improved Class 0 fire performance to stringent international standards 3-in-1
More informationLaboratory measurement of vibration and secondary noise transmission loss for rubber elastomer mats
12th ICBEN Congress on Noise as a Public Health Problem Laboratory measurement of vibration and secondary noise transmission loss for rubber elastomer mats Hui Li 1, Xiang Yan 1, Jianghua Wang 1 1 Acoustical
More information