Energy Audit. Town of Charlemont. Highway Garage. 12 Factory Rd. Charlemont, MA August 31, 2018

Size: px
Start display at page:

Download "Energy Audit. Town of Charlemont. Highway Garage. 12 Factory Rd. Charlemont, MA August 31, 2018"

Transcription

1 Energy Audit Town of Charlemont Highway Garage 12 Factory Rd. Charlemont, MA August 31, 2018 Prepared by: Bowman Engineering, Inc. PO Box 410 Greenfield, MA (413) Preparer: Thomas Bowman, P.E.

2 Executive Summary The Highway Garage was evaluated based on data gathered during a site walkthrough, energy data provided by the Town of Charlemont and discussions with building staff. There are four energy conservation measures (ECMs) that have been identified through the audit process. The specific ECMs that are recommended are summarized in the following table, along with the estimated cost and savings. ECM # Description ECM Cost Energy Conservation Measures Summary Building Annual Usage (MMBtu) Propane (gal) Usage Savings 1 New Condensing Boiler $10, $988 $ Storm Windows $ $185 $ Garage Door Seals $ $36 $ Personnel Door Seals $ $3 $ MMBtu Annual Cost Savings Rebates/Grants Payback (years) Page 1 of 13

3 Table of Contents EXECUTIVE SUMMARY... 1 TABLE OF CONTENTS... 2 INTRODUCTION... 3 FACILITY DESCRIPTION... 4 ENERGY ANALYSIS... 6 ENERGY CONSERVATION MEASURES... 7 ECM 1 NEW CONDENSING BOILER... 7 ECM 2 STORM WINDOWS... 8 ECM 3 GARAGE DOOR SEALS... 9 ECM 4 PERSONNEL DOOR SEAL OPERATIONS/MAINTENANCE MEASURES OTHER CONSIDERATIONS CLEAN ENERGY OPPORTUNITIES Page 2 of 13

4 Introduction The purpose of this audit report is to provide the Town of Charlemont with a list of energy conservation measures along with their associated cost and estimated energy savings. The approach taken in this audit included a thorough inspection of the building and associated systems and equipment. The primary areas covered in the audit included the building envelope, electrical system, HVAC system and operational and maintenance procedures. A major element of the audit also included an initial interview and ongoing consultation with operational and maintenance personnel and/or building occupants. This approach is critical to the quality of the audit process since the input of building personnel is invaluable to the effort to obtain accurate information required for the audit. The recommendations within this report are based on the data from the MassEnergyInsight (MEI) account for the Town as well as data provided by FRCOG for delivered fuels. The energy savings and energy production figures are projected estimates based on conceptual project upgrades, information gathered at the site, and from the historical utility information provided. The actual savings may vary from these estimates due to a variety of factors. The figures used for the cost of recommended upgrades are opinions of probable cost and are intended to be used for feasibility purposes only. This audit report is not a design document and shall not be used as such. The recommended measures are provided for budget and planning purposes only. Any recommended measures that are pursued by the Town should first include additional detailed study and design by a qualified engineer and/or contractor before competitive bidding is undertaken in accordance with the Massachusetts Procurement Guidelines. The scope of the audit did not include inspection, sampling, testing or analysis for the presence of hazardous materials. Therefore, such conditions should be evaluated separately before implementing any recommendations provided in this report. Page 3 of 13

5 Facility Description The Highway Garage is located at 12 Factory Rd. and includes high bay space for department vehicles, as well as an office, breakroom, restrooms, mechanical room and police department. The building (circa. 1995) has a total of 5,778 square feet, which includes 4,730 square feet of high bay space. The building is typically staffed by 1 4 people from 6:30 am to 2:30 pm, Monday through Friday, for five months of the year and 6:30 am to 4:30 pm, Monday through Thursday, for seven months of the year. Occupied periods for the Police Department are variable. The building is steel framed on a 4 foot concrete foundation wall, slab on grade. The exterior walls and roof are sheet metal. The high bay space has a ceiling height of 19-7 at the peak and 17-3 at the eaves. Building Envelope Based on discussion with building occupants and confirmed by probing in select areas, the walls above the foundation walls are insulated with a 5 inch thick blanket insulation with vapor barrier and by visual observation from the floor the ceiling appears to be the same. The partition walls within the office area are concrete block and there is 4 inches of fiberglass batt installed above the suspended ceiling. The windows are original single pane slider windows, which are reportedly leaky. The windows include screens, but not storm windows. The interior finishes include sheet metal walls in the high bay space with no ceiling finish. The floor finish is bare concrete throughout the building. Electrical and Lighting The electrical capacity of the main building electrical panel is not readily apparent, but appears to be upwards of 400 amps. Heating, Ventilation and Air Conditioning Heating for the building is provided by a single H. B. Smith cast iron propane fired boiler (M/N: GB100- W-11 COND) with a maximum rated input of 250 MBH. Based on the equipment serial number, the boiler was manufactured in July, 1996 and is nearing its natural end of life. The boiler is controlled by a two thermostats; one zone for the office and one for the garage space. The garage thermostat is set to maintain a setpoint of 68 o F. The office thermostat only has a relative scale and does not provide a specific setpoint. The heating distribution is a radiant floor system and the thickness of the floor and the characteristics of the underfloor insulation, if any exists, is unknown. Therefore, it may not be beneficial to provide an evening setback temperature as there may be a significant lag in the morning response time. At the time of the inspection, the boiler was observed to run periodically when the outside temperature was in the mid-60s. Also, a high level of soot was observed throughout the entire mechanical room. The boiler is supplied by a 1,000 gallon underground propane tank. Page 4 of 13

6 Cooling is provided by a three unit Samsung multi-split cooling system, with a 7,000 BTUH wall mounted indoor unit located in the office, breakroom and police department. According to the nameplate of the equipment, the units were manufactured in Domestic water heating needs are met by a small electric water heater, which is located in the mechanical room. The water heater serves the needs of two restrooms and the breakroom sink. The major electrically powered tools include two (2) welders and one (1) plasma cutter. Page 5 of 13

7 Energy Analysis The Highway Garage uses electricity for power and lighting. Propane is used to meet the space heating needs. The historical energy usage and costs are summarized in the following table and charts. Historical Energy Data - (MMBtu and dollars) Electric (FY18) Propane (Avg. FY16-18) Total Conditioned Area (ft 2 ) Usage Cost Usage Cost Usage Cost 5, $4, $ 4, $ 9, Energy Usage Energy Cost 21% 48% 52% 79% Electric Propane Electric Propane The Energy Performance Summary for the Highway Garage is provided below. The total energy index (TEI) is a measure of energy intensity, or annual energy usage per square foot of building area. Similarly, the energy cost index (ECI) is a measure of annual energy costs per square foot of building area. The index values provided in the table below are substantially lower than the comparable values reported in the recent CEE report. The difference is due to the fact that during the site inspection it was determined that the building s conditioned space (5,778 sq. ft.) is much greater than building s total reported floor space. Energy Performance Summary Conditioned Area Total Energy Index Energy Cost Index Year (ft2) (kbtu/ft2-yr) ($/ft2-yr) FY2018 5, $1.59 Page 6 of 13

8 Energy Conservation Measures The Energy Conservation Measures (ECMs) in this section are recommended based on available information at the time of the audit. Equipment specifications and associated costs are provided for budgetary planning purposes only. Detailed equipment sizing, code compliance, and system design should be performed prior to final equipment and material selection and procurement. ECM 1 New Condensing Boiler Description The existing boiler has reached its natural end of life and is not ideally suited to a radiant floor heating system. A new high efficiency modulating condensing boiler would work well with the radiant floor system since the boiler would be able to operate in the condensing range during nearly the entire heating season. This would significantly increase the energy efficiency of the system. The following inputs were used for the analysis: Existing Boiler Seasonal Efficiency: 70% Proposed Boiler Seasonal Efficiency: 95% Fuel Rate: $1.35/gal. (5/1/18 delivery) Operation There are no operational changes associated with this ECM. Initial Cost Estimate Highway Garage Heating System Description Qty. Unit Cost Code Unit Price O&P Ext. Price New Condensing Boiler (161 MBH) 1 Ea. Supply House $ 8, $ 8, Balance of Plant 1 Ea. Estimated $ 1, $ 1, Electrical $ General Conditions $ Total $ 10, Annual Savings & Payback This ECM is estimated to result in savings of 732 gallons of propane (66.8 MMBTU). Annual dollar savings are provided below as a function of propane prices. Simple Payback at $1.350/gal: $10,835 $988 = 11.0 years (Base Case) Simple Payback at $1.013/gal: $10,835 $742 = 14.6 years Simple Payback at $1.688/gal: $10,835 $1,235 = 8.8 years Page 7 of 13

9 ECM 2 Storm Windows Description The existing windows are original to the building and are reported to be very drafty. This ECM recommends that storm windows (interior or exterior) be installed. The following inputs were used for the analysis: Existing Condition: R-1, Leaky Proposed Condition: R-2, Tight (windows with storms) Total Combined Window Area (North): 8.7 sf. Total Combined Window Area (East): 26.1 sf. Fuel Rate: $1.35/gal. (5/1/18 delivery) Operation There are no operational changes associated with this ECM. Initial Cost Estimate Material: Four windows at $35/ea. Labor: Four windows at $35/ea. Total: 4 x $70/ea. = $280 Annual Savings & Payback This ECM is estimated to result in savings of gallons of propane (12.5 MMBTU) and $185 annually. Simple Payback: $280 $185 = 1.5 years Page 8 of 13

10 ECM 3 Garage Door Seals Description The door seals on the garage doors should be adjusted. Proposed Condition: Adjust the existing side and threshold seals on five (5) garage doors. Fuel Rate: $1.35/gal. (5/1/18 delivery) Operation There are no operational changes associated with this ECM. Initial Cost Estimate Labor: $1/L.F. (Adjustments only; no new material required) Total: 210 L.F. x $1/sf. = $210 Annual Savings & Payback This ECM is estimated to result in savings of 26.9 gallons of propane (2.45 MMBTU) and $36 annually. Simple Payback: $210 $36 = 5.8 years Page 9 of 13

11 ECM 4 Personnel Door Seal Description The door seals for main personnel door should be replaced. Proposed Condition: Replace the seals on one (1) personnel door. Fuel Rate: $1.35/gal. (5/1/18 delivery) Operation There are no operational changes associated with this ECM. Initial Cost Estimate Material & Labor: $75 Total: $75 Annual Savings & Payback This ECM is estimated to result in savings of 2.5 gallons of propane (0.23 MMBTU) and $3 annually. Simple Payback: $75 $3 = 25 years Page 10 of 13

12 Operations/Maintenance Measures The quality of the maintenance and operation of the facility s energy systems has a direct effect on its energy efficiency. Energy efficiency needs to be a consideration when implementing facility modifications, equipment replacements, and general corrective actions. The following measures are recommended to be incorporated into the facility s preventative maintenance procedures where applicable. Building Envelope Caulking and weather stripping is functional and effective. Holes are patched in the building envelope. Cracked windowpanes are repaired. Storm windows, if used, are installed at the beginning of the heating season. Window air conditioners are removed prior to the heating season. Heating and Cooling The pilot lights of central boilers and furnaces are turned off in the summer. The burners are clean and fuel/air ratios are optimized. Heat exchange surfaces of boilers are clean and free of scale. Thermostats settings are reduced in unoccupied areas and set points are seasonally adjusted. Control valves and dampers are fully functional. Equipment is inspected for worn or damaged parts. Heating is uniform throughout the designated areas. Domestic Hot Water Domestic hot water heater temperature is set to the minimum temperature required. All hot water piping is insulated and not leaking. Tank-type water heaters are flushed as required. Lighting Over-lit areas are managed by bi-level switching or de-lamping. Energy efficient replacement lamps are in-stock. Lighting fixture reflective surfaces and translucent covers are clean. Walls are clean and bright. Timers and/or photocells are operating correctly on exterior lighting. Miscellaneous Refrigerator and freezer doors close and seal correctly. Office/computer equipment is either in the sleep or off mode when not used. All other recommended equipment specific preventive maintenance actions are conducted, Usage demands on the building/ equipment have not changed significantly since the original building commissioning or the most recent retro-commissioning. In addition, equipment replacement should be performed assuring that; All equipment replacements are not over/undersized for the particular application, All equipment replacements should be with energy conserving and/or high efficiency devices. Page 11 of 13

13 Other Considerations The boiler and venting system should be serviced on an annual basis to ensure safe and efficient operation of the equipment. Given the minimal domestic hot water (DHW) needs of the building there is no value in replacing the existing DHW heater as it is adequately sized. However, when the equipment fails consideration should be given to replacing it with a point-of-use (POU) hot water heater. Either one unit could be located in each restroom and under the breakroom sink or a single unit could serve all three loads. Repair/replace sagging insulation in the garage area. Page 12 of 13

14 Clean Energy Opportunities The Commonwealth of Massachusetts is dedicated to promoting clean energy as an alternative to traditional sources of energy. As such, the DOER and other agencies have developed a number of programs to promote the use of clean energy sources by potentially providing technical assistance and/or financial incentives based on project feasibility. Solar Energy Through various initiatives, the Commonwealth has encouraged the installation of solar photovoltaic (PV) power by homeowners, businesses and municipalities. This includes various options for financing PV projects, including third-party financing. With third-party financing, the PV system is owned and operated by an entity that is separate from the building owner or the PV installer. The third-party financing entity has sufficient financial capital to pay for the entire installation and to maintain and operate the system over its lifetime. In return, the building owner, or host site, signs a long term contract agreeing to purchase all the power produced by the PV system. Third-party financing is a way to install a large PV array with little or no up-front capital expense from the building owner or host site. This type of financing may be most applicable to entities such as nonprofits or public buildings. The third-party PV Owner can utilize the substantial tax incentives available for PV projects, along with rebates and other incentives, plus the sale of the electricity from the PV array to finance the PV project. Biomass Energy The Commonwealth of Massachusetts has an abundant and renewable source of wood. When this natural resource is harvested in a sustainable manner, it helps to maintain the health of the forests, while also providing a clean source of low-carbon domestic fuel. Locally produced wood also has a cost advantage over conventional fossil fuels, providing a strong financial benefit to using it as a fuel source for space heating and domestic hot water heating. Furthermore, the demand for this resource helps to foster the local economy as a result of the jobs that are created to manage, harvest, transport and process the raw wood into usable forms of fuel such as wood pellets. New England has a long history of burning wood for heat, but over the last few decades significant technological advancements have been made with regard to the equipment that is used to burn this fuel source. Wood-fired boilers and furnaces operate at thermal efficiencies comparable to those for fossil fueled systems and the fuel delivery systems are fully automated. Available equipment can be staged with other heating appliances and can be coupled with standard distributions systems. Through various initiatives, the Commonwealth has encouraged the use of biomass thermal energy systems for homeowners, businesses and municipalities. The following table lists the specific projects that might be appropriate for various clean energy technologies. Description: None Action Item: N/A Clean Energy Opportunities Page 13 of 13

Energy Audit. Town of Charlemont. Town Hall. 157 Main Street Charlemont, MA August 31, 2018

Energy Audit. Town of Charlemont. Town Hall. 157 Main Street Charlemont, MA August 31, 2018 Energy Audit Town of Charlemont Town Hall 157 Main Street Charlemont, MA 01339 August 31, 2018 Prepared by: Bowman Engineering, Inc. PO Box 410 Greenfield, MA 01302 (413) 303-0238 Preparer: Thomas Bowman,

More information

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information.

FOR ADDITIONS and REMODELS Before filling out this application, read Green Building & Green Points Guideline Booklet for more in-depth information. City of Boulder Residential Building Guide Green Building & Green Application Resource Conservation Ordinance 7565 www.bouldergeenpoints.com FOR ADDITIONS and REMODELS Before filling out this application,

More information

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT

Energy Assessment Report Clayville Elementary School DRAFT October George Washington Highway, Clayville, RI DRAFT Report Clayville Elementary School October 2016 3 George Washington Highway, Clayville, RI 02815 Clayville Elementary School Summary of Findings On behalf of the School Building Authority at Rhode Island

More information

R15: Potential Study. Introduction. Introduction. Study Components 3/7/2016

R15: Potential Study. Introduction. Introduction. Study Components 3/7/2016 R15: Potential Study Potential Savings in Connecticut Existing Single-Family Homes Connecticut EEB February 23, 2016 Matt Rusteika Introduction Used for program planning, measure targeting, context Quantifies

More information

Consumer Energy Tax Credit

Consumer Energy Tax Credit Consumer Energy Tax Credit FLAMMABLE AND COMBUSTIBLE LIQUIDS 2009 IFC Overview of Tax Credit Energy efficiency incentives for upgrades to existing homes are now available for 2009 and 2010. These tax incentives

More information

Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits

Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits AEP Ohio Customer Seminar Implementing Low-Cost Energy Savings Projects & Conducting Energy Audits Presented by: Julie Birchfield Customer Manager Energy Optimizers, USA May, 2018 Test your Energy IQ 11

More information

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007

Energy Auditing for Schools. Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Energy Auditing for Schools Maryland Energy Administration Eric Oliver, EMO Energy Solutions, LLC May 10, 2007 Schools Consumption breakdown 19% 6% 9% Space Heating 46% Water Heating Lighting Cooling 20%

More information

Energy Audit. Gen. John Nixon Elementary School 472 Concord Road Sudbury, MA 01776

Energy Audit. Gen. John Nixon Elementary School 472 Concord Road Sudbury, MA 01776 Energy Audit Gen. John Nixon Elementary School 472 Concord Road Sudbury, MA 01776 Prepared for: Massachusetts Department of Energy Resources Energy Audit Program Prepared by: Russell Friend PE Facility

More information

GENERAL MECHANICAL SYSTEM REQUIREMENTS

GENERAL MECHANICAL SYSTEM REQUIREMENTS CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisions of this chapter shall govern the installation of mechanical systems not specifically covered in other

More information

For more information about Ground Source Heat Pumps, call the Member Service Department at or visit our website at

For more information about Ground Source Heat Pumps, call the Member Service Department at or visit our website at For more information about Ground Source Heat Pumps, call the Member Service Department at 573-449-4181 or visit our website at www.booneelectric.coop. February 2019 Ground Source Heat Pumps: What are

More information

Results and Recommendations from Energy Audit of Nikolai. For VEEP Grants. City of Nikolai, Alaska

Results and Recommendations from Energy Audit of Nikolai. For VEEP Grants. City of Nikolai, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Nikolai For VEEP Grants City of Nikolai, Alaska June 20, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage, AK

More information

Home Energy Score Report

Home Energy Score Report Home Energy Score Report Home Sample Simple Score Minden NE, 68959 Audit Date Dec 1, 2017 08:00 am Audited By Sandy Michaels Tech Support sandy@snugghome.com 8 am to 6 pm Snugg Pro PO Box 82 Boulder CO,

More information

Results and Recommendations from Energy Audit of Kipnuk. For VEEP Grants. City of Kipnuk, Alaska

Results and Recommendations from Energy Audit of Kipnuk. For VEEP Grants. City of Kipnuk, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Kipnuk For VEEP Grants City of Kipnuk, Alaska June 20, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage, AK 99507

More information

Geoff Howland. Value Development Manager

Geoff Howland. Value Development Manager Geoff Howland Value Development Manager Chevron Energy Solutions MacArthur Plaza 5525 N. MacArthur Blvd Suite 290 Irving, TX 7 75038 Tel 972.550.3045 Cel 972.757.9154 Fax 972.550.3049 ghowland@chevron.com

More information

Madison's Home Inspections

Madison's Home Inspections Cover Page Madison's Home Inspections Property Inspection Report my street, Clarksville TN, 37043 Inspection prepared for: Gary Mann Agent: gary mann - Madison's Inspection Date: 0/4/2009 Time: 12 pm Age:

More information

Local Government Energy Audit: Energy Audit Report

Local Government Energy Audit: Energy Audit Report Local Government Energy Audit: Energy Audit Report Copyright 2017 TRC Energy Services. All rights reserved. Reproduction or distribution of the whole, or any part of the contents of this document without

More information

A Closer Look Inspection Service 2015 IECC Residential DFW area handout

A Closer Look Inspection Service 2015 IECC Residential DFW area handout 103.2 Information required on construction documents 1. Designation of the Thermal Building Envelope on the plans 2. Insulation Material and their R Value 3. Fenestration U and SHGC values 4. Area weighted

More information

Better By Design Energy Efficiency in Needham s Public Construction Projects

Better By Design Energy Efficiency in Needham s Public Construction Projects Better By Design Energy Efficiency in Needham s Public Construction Projects Green Needham Monday, November 26 th, 2012 7:00PM Needham Public Library Energy Efficiency in Town Projects Presenters tonight

More information

IECC Residential Significant Changes Summary. Tier I

IECC Residential Significant Changes Summary. Tier I 2009-2015 IECC Residential Significant Changes Summary Tier I R401.2 Compliance options for compliance are now prescriptive path, Total UA (which is part of prescriptive), Performance and the new Energy

More information

Energy Efficiency Programs

Energy Efficiency Programs Program Overviews Efficiency Programs Description Delivery Model Audit Requirement/ Multifamily - Existing Building Efficiency Alliant Services include free energy assessments, rebates for property owners

More information

Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY. LAST UPDATE: July 03, 2014

Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY. LAST UPDATE: July 03, 2014 Town of Farragut RESIDENTIAL CONSTRUCTION ENERGY EFFICIENCY LAST UPDATE: July 03, 2014 TABLE OF CONTENTS Front Cover Sheet Page 1 Table of Contents Page 2 Applying for a Gas/Mechanical Permit Page 2 Important

More information

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**)

Instant discount of 33% off improvement cost, up to $1,250 Plus, potential savings bonus of up to $250 (**) RESIDENTIAL PROGRAM HOME PERFORMANCE with ENERGY STAR IMPROVE YOUR HOME'S COMFORT. SAVE MONEY. REDUCE ENERGY. EARN S. Home Performance with ENERGY STAR offers homeowners instant discounts for making recommended

More information

Energy Efficiency Solutions for Multifamily Housing. Clark Energy Group LLC

Energy Efficiency Solutions for Multifamily Housing. Clark Energy Group LLC Energy Efficiency Solutions for Multifamily Housing Clark Energy Group LLC 1 Agenda About Clark Energy Group Energy Service Company (ESCO) Overview ESCO Services Utility Rate Forecasts Making the Decision

More information

ROXBURY TOWNSHIP TOWN HALL / POLICE DEPARTMENT ENERGY ASSESSMENT. for NEW JERSEY BUREAU OF PUBLIC UTILITIES CHA PROJECT NO

ROXBURY TOWNSHIP TOWN HALL / POLICE DEPARTMENT ENERGY ASSESSMENT. for NEW JERSEY BUREAU OF PUBLIC UTILITIES CHA PROJECT NO ROXBURY TOWNSHIP TOWN HALL / POLICE DEPARTMENT ENERGY ASSESSMENT for NEW JERSEY BUREAU OF PUBLIC UTILITIES CHA PROJECT NO. 20556 May 2010 Prepared by: CLOUGH HARBOUR & ASSOCIATES LLP 6 Campus Drive Parsippany,

More information

The Island University. A Campus of The Texas A&M University System Corpus Christi, Texas

The Island University. A Campus of The Texas A&M University System Corpus Christi, Texas ! The Island University A Campus of The Texas A&M University System Corpus Christi, Texas This document was prepared to comply with the Governor s Executive Order RP49 - October 27, 2005 relating to energy

More information

ENGLEWOOD CLIFFS PUBLIC SCHOOLS UPPER SCHOOL ELEMENTARY SCHOOL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO.

ENGLEWOOD CLIFFS PUBLIC SCHOOLS UPPER SCHOOL ELEMENTARY SCHOOL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. ENGLEWOOD CLIFFS PUBLIC SCHOOLS UPPER SCHOOL ELEMENTARY SCHOOL ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 24385 November 2012 Prepared by: 6 Campus Drive Parsippany, NJ

More information

Township of Parsippany Troy Hills Parsippany Troy Hills Department of Public Works 1 Pump House Road Parsippany, NJ 07054

Township of Parsippany Troy Hills Parsippany Troy Hills Department of Public Works 1 Pump House Road Parsippany, NJ 07054 Steven Winter Associates, Inc. 293 Route 18 South Telephone (866) 676-1972 Building System Consultants East Brunswick, NJ 08816 Web: www.swinter.com May 5, 2010 Local Government Energy Program Energy Audit

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: i Energy Audit Report Lift Station #1, 3, 5, 6, 7, 8, and 9 Copyright 2018 TRC Energy Services. All rights reserved. Reproduction or distribution of the whole, or any part

More information

County of Perth. Energy Conservation and Demand Management Plan

County of Perth. Energy Conservation and Demand Management Plan County of Perth Energy Conservation and Demand Management Plan 2014 Contents Introduction 2 Perth County Courthouse 3 24 St. Andrews 5 5 Huron Street 6 Listowel EMS Base 7 St. Mary s EMS Base 8 Mitchell

More information

Work Order (Bid Form) Blount County Community Action Agency, Inc.

Work Order (Bid Form) Blount County Community Action Agency, Inc. Blount County Community Action Agency, Inc. WORK ORDER INFORMATION Work Order Type: Weatherization Audit Name: 10001BL10082 CLIENT INFORMATION Address: MARYVILLE, TN 37804 AGENCY INFORMATION Agency: Blount

More information

Rebates for Improvements Home Efficiency Program Fort Collins Utilities

Rebates for Improvements Home Efficiency Program Fort Collins Utilities Rebates for Improvements Home Efficiency Program Fort Collins Utilities Revised 03/04/2013 This matrix summarizes information regarding Home Efficiency Program rebates for improving homes in Fort Collins.

More information

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0

ENERGY STAR Qualified Homes National Program Requirements, Version 3.0 Qualifying Homes The following homes are eligible to earn the ENERGY STAR: Single-family homes; Units in multi-family buildings that are three stories or less; Units in multi-family buildings that are

More information

Home Energy Score. Learn more at homeenergyscore.gov. Uses more energy. Uses less energy Milvia Street Berkeley, CA 94704

Home Energy Score. Learn more at homeenergyscore.gov. Uses more energy. Uses less energy Milvia Street Berkeley, CA 94704 ADDRESS 2120 Milvia Street Berkeley, CA 94704 HOME SIZE YEAR BUILT AIR CONDITIONING 1,450 square feet 1970 Your home's current score 3 Uses more energy 1 2 3 4 5 6 7 8 9 10 Uses less energy Learn more

More information

Property Condition Assessment

Property Condition Assessment Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE BASELINE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 54.4 kbtu/ 2/yr 21.8 High Performance 18.2 PHIUS - IES 60 MMBtu

More information

PV Generation Potential 17.1 kbtu/ft2/yr 15.4

PV Generation Potential 17.1 kbtu/ft2/yr 15.4 TOWNHOME PROTOTYPE HIGH PERFORMANCE 60 kbtu/sf/yr 50 kbtu/sf/yr 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 54.4 Baseline 21.8 kbtu/ 2/yr 15 MMBtu 12 MMBtu 9 MMBtu 6 MMBtu 3 MMBtu

More information

GENERAL MECHANICAL SYSTEM REQUIREMENTS

GENERAL MECHANICAL SYSTEM REQUIREMENTS CHAPTER 13 GENERAL MECHANICAL SYSTEM REQUIREMENTS SECTION M1301 GENERAL M1301.1 Scope. The provisionsof thischapter shall governthe installation of mechanical systems not specifically covered in other

More information

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012

THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 THE CITY OF FAYETTEVILLE ADOPTED THE 2009 INTERNATIONAL ENERGY CONSERVATION CODE (IECC) ON JULY 17, 2012 Compliance with the code for new residential construction, additions, and substantial remodels will

More information

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr

MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 10.8 kbtu/ 2/yr MID-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 50 kbtu/sf/yr 45.1 PROJECT INFORMATION 40 kbtu/sf/yr 30 kbtu/sf/yr 20 kbtu/sf/yr 10 kbtu/sf/yr 0 kbtu/sf/yr 13.0 kbtu/ft2/yr Baseline 10.8 kbtu/ft2/yr

More information

Measure 1 Seal Ducts Components Inspected

Measure 1 Seal Ducts Components Inspected WORK ORDER INFORMATION Work Order Type: Weatherization Audit Name: 1000049 CLIENT INFORMATION Client ID: 1002275 AGENCY INFORMATION Agency: Upper East Tennessee Human Development Agency Address: 301 Louis

More information

Comprehensive Energy Audit For Kongiganak Health Clinic

Comprehensive Energy Audit For Kongiganak Health Clinic Comprehensive Energy Audit For Kongiganak Health Clinic Prepared For Native Village of Kongiganak September 15, 2011 Prepared By: ANTHC DEHE Energy Projects Group Anchorage, Alaska 99508 1 Table of Contents

More information

LOGO. Trivium Level II Energy Audit

LOGO. Trivium Level II Energy Audit LOGO Trivium Level II Energy Audit Submission Date: 9/16/2016 Table of Contents 1.0 EXECUTIVE SUMMARY 3 2.0 SITE ENERGY CONSUMPTION 5 3.0 BACKGROUND INFORMATION 6 3.1 Description of the Client 6 3.2 Description

More information

CITY OF LINWOOD CITY HALL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO February 2011.

CITY OF LINWOOD CITY HALL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO February 2011. CITY OF LINWOOD CITY HALL ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 22215 February 2011 Prepared by: CLOUGH HARBOUR & ASSOCIATES LLP 6 Campus Drive Parsippany, NJ 07054

More information

CARBON MONOXIDE ALARMS

CARBON MONOXIDE ALARMS 7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 www.cityofapplevalley.org BUILDING PERMITS - Are required for all porch additions. PORCH INFORMATION ELECTRICAL PERMITS - Are

More information

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program

Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program Evergreen Project Implementation Plan Instructions Low Income Housing Tax Credit Program The following table provides a brief description of the documentation that will be required of successful LIHTC

More information

BOROUGH OF OCEANPORT BOROUGH HALL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES

BOROUGH OF OCEANPORT BOROUGH HALL ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES BOROUGH OF OCEANPORT BOROUGH HALL ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES BOROUGH OF OCEANPORT BOROUGH HALL ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO.

More information

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST

IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST IECC 2015 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Project: Date: Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other

More information

Nancy Kinner Donna Miller David Wetherbee Bath, ME June 24, 2018

Nancy Kinner Donna Miller David Wetherbee Bath, ME June 24, 2018 Grace Episcopal Church Energy for the Future Nancy Kinner Donna Miller David Wetherbee Bath, ME June 24, 2018 Grace: Energy for the Future Series 3 Meetings to Discuss Grace s Future Energy Needs Sunday,

More information

BISHOP FARMSTEAD OFFICES OF PINELANDS PRESERVATION ALLIANCE ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO.

BISHOP FARMSTEAD OFFICES OF PINELANDS PRESERVATION ALLIANCE ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. BISHOP FARMSTEAD OFFICES OF PINELANDS PRESERVATION ALLIANCE ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 23261 NOVEMBER 2011 Prepared by: 6 Campus Drive Parsippany, NJ 07054

More information

CITY OF NEWARK CITY HALL COMPLEX City Hall Building Police Building Courthouse ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES

CITY OF NEWARK CITY HALL COMPLEX City Hall Building Police Building Courthouse ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CITY OF NEWARK CITY HALL COMPLEX City Hall Building Police Building Courthouse ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 21823 February 2011 Prepared by: 6 Campus Drive

More information

Multifamily Net Zero Retrofit Market: Technical and Cost Benchmarks for San Francisco

Multifamily Net Zero Retrofit Market: Technical and Cost Benchmarks for San Francisco Multifamily Net Zero Retrofit Market: Technical and Cost Benchmarks for San Francisco 1 Table of Contents Acronym Key Analysis Process Retrofit Economics Technical Analysis Details 6 Unit Building Analysis

More information

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal

Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal Example LEED-NC v2.1 Energy & Atmosphere Credit 1 Submittal The following documentation provides an example submittal for the LEED-NC v2.1 Energy & Atmosphere Credit 1 (EAc1). This sample EAc1 submittal

More information

Reducing Costs with Energy Efficiency

Reducing Costs with Energy Efficiency Reducing Costs with Energy Efficiency Presented to Pennsylvania Demand Side Response Working Group February 9, 2007 2/9/2007 1 Austin Energy Municipally-owned 700,000 population Area > 400 sq. miles Generation

More information

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT

INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 7100 147 th Street West Telephone (952) 953-2588 Apple Valley, MN 55124-9016 Fax (952) 953-2515 www.cityofapplevalley.org INFORMATIONAL HANDOUT FOR FINISHING A BASEMENT 1. Submit plan showing the proposed

More information

Comprehensive Energy Audit For Eek Tribal Office/City Office

Comprehensive Energy Audit For Eek Tribal Office/City Office Comprehensive Energy Audit For Eek Tribal Office/City Office Prepared For: Native Village of Eek And City of Eek August 5, 2011 Prepared By: ANTHC-DEHE Energy Projects Group 1901 Bragaw St. Suite 200 Anchorage,

More information

ROXBURY TOWNSHIP PUBLIC LIBRARY ENERGY ASSESSMENT. for NEW JERSEY BUREAU OF PUBLIC UTILITIES

ROXBURY TOWNSHIP PUBLIC LIBRARY ENERGY ASSESSMENT. for NEW JERSEY BUREAU OF PUBLIC UTILITIES ROXBURY TOWNSHIP PUBLIC LIBRARY ENERGY ASSESSMENT for NEW JERSEY BUREAU OF PUBLIC UTILITIES ROXBURY TOWNSHIP PUBLIC LIBRARY ENERGY ASSESSMENT for NEW JERSEY BUREAU OF PUBLIC UTILITIES CHA PROJECT NO. 20556

More information

SUMMARY OF SERVICES & INCENTIVES

SUMMARY OF SERVICES & INCENTIVES SMALL BUSINESS PROGRAM 2017 SUMMARY OF SERVICES & INCENTIVES Effective through December 31, 2017 Last updated February 1, 2017 EFFICIENCY INCENTIVES SUMMARY The Focus on Energy Small Business Program offers

More information

Urban Revitalization Plan For Responsible and Sustainable Growth and Development City of Adel, Iowa

Urban Revitalization Plan For Responsible and Sustainable Growth and Development City of Adel, Iowa Urban Revitalization Plan For Responsible and Sustainable Growth and Development City of Adel, Iowa Residential Tax Abatement Program Application Applicant Name (Print) Address / City / State Phone Email

More information

CITY OF LINWOOD EMERGENCY MEDICAL SERVICE BUILDING ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO

CITY OF LINWOOD EMERGENCY MEDICAL SERVICE BUILDING ENERGY ASSESSMENT. for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO CITY OF LINWOOD EMERGENCY MEDICAL SERVICE BUILDING ENERGY ASSESSMENT for NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 22215 February 2011 Prepared by: CLOUGH HARBOUR & ASSOCIATES LLP 6 Campus Drive

More information

Energy Audit Report Lee Recycling Center Office and Facility 11 Recycling Center Rd, Lee NH August 16 & 17, 2011

Energy Audit Report Lee Recycling Center Office and Facility 11 Recycling Center Rd, Lee NH August 16 & 17, 2011 Energy Audit Report Lee Recycling Center Office and Facility 11 Recycling Center Rd, Lee NH August 16 & 17, 2011 S D E S G r o u p 2 W a s h i n g t o n S t r e e t S u i t e 2 0 6 D o v e r, N H 0 3 8

More information

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0.

2009 IECC with St Louis Amendments. Fenestration U-factor Skylight U-factor Glazed fenestration SHGC NR 0. Comparison Between Residential 2009 IECC with St Louis amendments, the 2015 IECC, and 2015 IECC w/ Building Codes Review Committee (BCRC) proposals: Climate Zone 4 Note: This document does not contain

More information

Application of Advanced Energy Technologies

Application of Advanced Energy Technologies GLOBALCON 2002 Philadelphia, Pennsylvania March 27, 2002 Application of Advanced Energy Technologies Michael K. West, Ph.D., P.E. Building Systems Scientist Advantek Consulting, Inc. www.advantekinc.com

More information

Comprehensive Energy Audit For Sleetmute Community Center

Comprehensive Energy Audit For Sleetmute Community Center Comprehensive Energy Audit For Sleetmute Community Center Prepared For The Traditional Council of Sleetmute, and the Alaska Rural Utility Collaborative Apr 26, 2011 Prepared By: ANTHC 1901 Bragaw St. Suite

More information

PROPERTY OVERVIEW PROPERTY HIGHLIGHTS. 2,340 SF Convenience Store. 3,508 SF Three Unit Strip Center. U-Haul Business. Sunoco Branded Gas Station

PROPERTY OVERVIEW PROPERTY HIGHLIGHTS. 2,340 SF Convenience Store. 3,508 SF Three Unit Strip Center. U-Haul Business. Sunoco Branded Gas Station RETAIL FOR SALE 5990 Asheville Highway, Hendersonville, NC 28791 OFFERING SUMMARY SALE PRICE: $1,350,000 LOT SIZE: 0.75 Acres YEAR BUILT: 1980 BUILDING SIZE: 5,848 SF RENOVATED: 2018 C-2 Commercial ZONING:

More information

Lawrence Township Municipal Building / EMS Garage 357 Main Street Cedarville, NJ 08311

Lawrence Township Municipal Building / EMS Garage 357 Main Street Cedarville, NJ 08311 Steven Winter Associates, Inc. 293 Route 18 South, Suite 330 Telephone: (866) 676-1972 Architects and Engineers East Brunswick, NJ 08816 E-mail:swinter@swinter.com www.swinter.com March 18 th, 2010 Local

More information

Work Order (Bid Form) Upper East Tennessee Human Development Agency

Work Order (Bid Form) Upper East Tennessee Human Development Agency Upper East Tennessee Human Development Agency WORK ORDER INFORMATION Work Order Type: Weatherization Audit Name: 18018UE10329 CLIENT INFORMATION Address: ERWIN, TN 37692 AGENCY INFORMATION Agency: Upper

More information

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr

LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE PV Genera on Poten al 17.9 kbtu/ 2/yr LOW-RISE APARTMENT BUILDING PROTOTYPE HIGH PERFORMANCE 40 kbtu/sf/yr 35 kbtu/sf/yr 30 kbtu/sf/yr 25 kbtu/sf/yr 20 kbtu/sf/yr 15 kbtu/sf/yr 10 kbtu/sf/yr 5 kbtu/sf/yr 0 kbtu/sf/yr 11.9 kbtu/ft2/yr 36.0

More information

Home Improvement Energy Tax Credits Explained

Home Improvement Energy Tax Credits Explained Home Improvement Energy Tax Credits Explained Your Local Home Improvement Specialist WHITE PAPER Through The Emergency Economic Stabilization Act of 2008 (the Bailout Bill ) and The American Recovery and

More information

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS

INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS INFORMATION GUIDE SECOND DWELLING UNITS BUILDING CODE BASICS November 2018 Contents 1. Introduction... 1 2. Ontario Building Code and Second Dwelling Units... 1 3. How Do I Make My Secondary Dwelling Unit

More information

Municipal Energy Assessment Phase I: Building Heating Analysis

Municipal Energy Assessment Phase I: Building Heating Analysis Municipal Energy Assessment Phase I: Building Heating Analysis In support of the Mohawk Trail Woodlands Partnership For Ashfield, Massachusetts September 27, 2017 Prepared by UMass Clean Energy Extension

More information

Investigative Energy Audit For. Koliganek IGAP Office Building. Prepared For Koliganek Village Council. Prepared By Curtis Boudreau, PE, CEM

Investigative Energy Audit For. Koliganek IGAP Office Building. Prepared For Koliganek Village Council. Prepared By Curtis Boudreau, PE, CEM Investigative Energy Audit For Koliganek IGAP Office Building Prepared For Koliganek Village Council Prepared By Curtis Boudreau, PE, CEM February 22, 2017 ANTHC DEHE 4500 Diplomacy Dr. Anchorage, AK 99508

More information

Results and Recommendations from Energy Audit of Shageluk. For VEEP Grants Village of Shageluk, Alaska

Results and Recommendations from Energy Audit of Shageluk. For VEEP Grants Village of Shageluk, Alaska ENERGY AUDIT POST INSTALLATION REPORT Results and Recommendations from Energy Audit of Shageluk For VEEP Grants Village of Shageluk, Alaska June 21, 2012 Prepared By:, Inc. 6643 Brayton Drive Anchorage,

More information

Construction Report NYSERDA Residential Performance Challenge

Construction Report NYSERDA Residential Performance Challenge Construction Report NYSERDA Residential Performance Challenge WELYTOK TOWNHOMES October 2014 Submitted to: NYSERDA 17 Columbia Circle Albany, NY 12203 Submitted by: HOMEPIC Team CDH Energy Corp. PO Box

More information

South Carolina Society for Hospital Engineers

South Carolina Society for Hospital Engineers South Carolina Society for Hospital Engineers Selecting Energy Partners: Criteria & Pitfalls and the Top 10 Ways to Reduce Energy in a Hospital Presented by Jon Dierking, PE, CEM, LEED AP Director of Energy

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: Energy Audit Report Copyright 2017 TRC Energy Services. All rights reserved. Reproduction or distribution of the whole, or any part of the contents of this document without

More information

2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach)

2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach) 2010 Residential Energy Checklist: Additions/Alterations (Prescriptive Approach) Component Less than equal to 100 sq. ft. Addition Less than equal to 1000 sq. ft. Addition Greater than 1000 sq. ft. Addition

More information

Monmouth County. June Final Energy Audit Report

Monmouth County. June Final Energy Audit Report A Monmouth County June 2010 Final Energy Audit Report Contents Executive Summary Section 1 Introduction 1.1 General... 1-1 1.2 Background... 1-1 1.3 Purpose and Scope... 1-2 Section 2 Facility Description

More information

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company.

ENERGY AUDIT. 123 Main Street Mississauga, Ontario. January 1, Report To: Mr. John Smith Smith Printing Company. Report To: Mr. John Smith Smith Printing Company ENERGY AUDIT 123 Main Street Mississauga, Ontario January 1, 2009 120 Carlton Street, Suite 212 Toronto, Ontario M5A 4K2 Tel 416-964-3246 Toll Free 1-866-964-3246

More information

10 TIPS FOR FALL AND WINTER FACILITY MAINTENANCE

10 TIPS FOR FALL AND WINTER FACILITY MAINTENANCE 10 TIPS FOR FALL AND WINTER FACILITY MAINTENANCE With the fall season upon us, we would like to share some tips for year-end facilities maintenance. 1. REDUCE YOUR TEMPERATURE SET POINTS You can reduce

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: Energy Audit Report West Cape May Elementary School West Cape May Board of Education Copyright 2018 TRC Energy Services. All rights reserved. Reproduction or distribution

More information

CA Statewide Codes and Standards Program

CA Statewide Codes and Standards Program Attachment C CA Statewide Codes and Standards Program Title 24, Part 11 Local Energy Efficiency Ordinances Chico Existing Building Efficiency Upgrade Cost-Effectiveness Study Prepared for: Marshall Hunt

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: Energy Audit Report Lake Riviera Middle School Brick Township Board of Education Copyright 2017 TRC Energy Services. All rights reserved. Reproduction or distribution of

More information

Training Certification Categories

Training Certification Categories Training Certification Categories Residential Residential Building Inspector structures are free from hazardous structural conditions and comply with the UCC. Duties include inspection of footings and

More information

Presentation Overview: NC Energy Code RESNET Standards HERS Index HERS Verification Process

Presentation Overview: NC Energy Code RESNET Standards HERS Index HERS Verification Process Presentation Overview: NC Energy Code RESNET Standards HERS Index HERS Verification Process NC Energy Code Requirements ENERGY STAR and NC Energy Code in Alignment RESNET Standards HERS Index A scoring

More information

MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT. For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO.

MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT. For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. MAYWOOD BOARD OF EDUCATION MEMORIAL ELEMENTARY SCHOOL ENERGY ASSESSMENT For NEW JERSEY BOARD OF PUBLIC UTILITIES CHA PROJECT NO. 24473 September 2012 Prepared by: 6 Campus Drive Parsippany, NJ 07054 (973)

More information

Connecticut Housing Finance Authority. Construction Guidelines: Energy Conservation 2019

Connecticut Housing Finance Authority. Construction Guidelines: Energy Conservation 2019 Connecticut Housing Finance Authority Construction Guidelines: Energy Conservation 2019 These Guidelines are effective I. Energy Conservation Guidelines Energy efficiency is strongly encouraged. An objective

More information

Work Order (Bid Form) Upper East Tennessee Human Development Agency

Work Order (Bid Form) Upper East Tennessee Human Development Agency Upper East Tennessee Human Development Agency WORK ORDER INFORMATION Work Order Type: Weatherization Audit Name: 18018UE10620 CLIENT INFORMATION Address: FALL BRANCH, TN 37656 AGENCY INFORMATION Agency:

More information

Applying Energy Code to Existing Buildings

Applying Energy Code to Existing Buildings Applying Energy Code to Existing Buildings Massachusetts Energy Code Technical Support Program 1 Who Is Mass Save? Mass Save is an initiative sponsored by Massachusetts gas and electric utilities and energy

More information

Klickitat PUD Residential Weatherization Energy Efficiency Program Participation Requirements and Instructions PROGRAM REQUIREMENTS

Klickitat PUD Residential Weatherization Energy Efficiency Program Participation Requirements and Instructions PROGRAM REQUIREMENTS Thank you for your interest in our Residential Weatherization Energy Efficiency Program. We are pleased that we have the opportunity to offer this service to you through our association with Bonneville

More information

Klickitat PUD Residential Weatherization Energy Efficiency Program Participation Requirements and Instructions PROGRAM REQUIREMENTS

Klickitat PUD Residential Weatherization Energy Efficiency Program Participation Requirements and Instructions PROGRAM REQUIREMENTS Thank you for your interest in our Residential Weatherization Energy Efficiency Program. We are pleased that we have the opportunity to offer this service to you through our association with Bonneville

More information

COST EFFECTIVE ENERGY EFFICIENCY MEASURES FOR 15% ABOVE 2009 IECC CODE COMPLIANT HOUSE FOR RESIDENTIAL BUILDINGS IN TEXAS

COST EFFECTIVE ENERGY EFFICIENCY MEASURES FOR 15% ABOVE 2009 IECC CODE COMPLIANT HOUSE FOR RESIDENTIAL BUILDINGS IN TEXAS COST EFFECTIVE ENERGY EFFICIENCY MEASURES FOR 15% ABOVE 2009 IECC CODE COMPLIANT HOUSE FOR RESIDENTIAL BUILDINGS IN TEXAS Hyojin Kim Research Associate Juan Carlos Baltazar, Ph.D. Associate Research Engineer

More information

Turning Data Into Action

Turning Data Into Action tearsheets Building Segment-Specific Packages of s Report Partners: sustainable energy partnerships Introduction These tearsheets have been created to make New York City building energy audit data actionable.

More information

Local Government Energy Audit:

Local Government Energy Audit: Local Government Energy Audit: Energy Audit Report Veterans Memorial Middle School Copyright 2017 TRC Energy Services. All rights reserved. Reproduction or distribution of the whole, or any part of the

More information

1234 Main St. Buyer Name. Table of Contents

1234 Main St. Buyer Name. Table of Contents AMERICAN PROFESSIONAL HOME INSPECTION 719.648.4098 drew@americanprofessionalhomeinspection.com http://www.amproinspection.com RESIDENTIAL REPORT 1234 Main St. Colorado Springs CO 80903 Buyer Name 10/02/2017

More information

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT.

ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT. ESL-TR-86/09-03 ENERGY ANALYSIS AND ENERGY CONSERVATION OPTION FOR THE WAREHOUSE FACILITY AT THE HUMAN SERVICES CENTER COMPLEX DRAFT REPORT Submitted by Mohsen Farzad Dennis O'Neal Prepared For Energy

More information

IECC 2006 with Hawaii Amendments

IECC 2006 with Hawaii Amendments IECC 2006 with Hawaii Amendments COMMERCIAL DESIGN CHECKLIST ENVELOPE REQUIREMENTS Instructions RECOMMENDED: List performance values, note exceptions that were applied, or provide other notes to the reviewer.

More information

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011 Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &

More information

Heat Pumps Community Workshop Manchester Library, Manchester

Heat Pumps Community Workshop Manchester Library, Manchester Heat Pumps Community Workshop Manchester Library, Manchester Jake Marin Program Manager HVAC/R Efficiency Vermont April 14, 2015 1 Our Roadmap Brief Technology Overview Heat Pump Economics Successful Applications

More information

Local Government Energy Audit: Energy Audit Report

Local Government Energy Audit: Energy Audit Report Local Government Energy Audit: Energy Audit Report Renaissance at Rand Montclair Board of Education 176 North Fullerton Avenue Montclair, New Jersey 07402 Copyright 2019 TRC Energy Services. All rights

More information

Municipal Energy Analysis Report: Clean Energy Site Assessment

Municipal Energy Analysis Report: Clean Energy Site Assessment Municipal Energy Analysis Report: Clean Energy Site Assessment For Pioneer Valley Regional School District, Massachusetts October 31, 2017 Prepared by UMass Clean Energy Extension 209 Agricultural Engineering

More information