2 Section 11 Rainwater Systems & Ancillaries Boundary Wall Gutter Rainwater Systems 2 Rainwater Systems Design Concepts 3-4 Specification, Design & Dimensions 5-6 Boundary Wall Gutter 7 Valley Gutter 8 Gutter Outlet Calculation 9 Components & Ordering 10 Order Form (Please photocopy sheets 1 and 2 before ordering) Eaves Gutter 13 Streamline Gutter System 14 Downpipe Construction 15 Downpipe Components Order Form (Please photocopy sheets 1 before ordering) 18 Rainwater Components Gutter Design Software 21 Membrane Gutter System Architectural Features & Ancillaries Components Facia Gutters
3 Rainwater Systems Introduction Ward Building Components are a leading supplier of all types of steel components to the UK construction industry. The Ward product range has evolved from over 40 years of experience in steel framed building design. The rainwater drainage systems have been formulated to combine hydraulic efficiency economy of design and practical site assembly. This experience of metal building construction allows us to offer a flexible service on design and manufacturing both standard and custom made items to suit the specifiers requirements. Valley and Boundary wall gutters are manufactured from galvanised steel with complimentary accessories to suit the individual project requirements. A range of standard profiles are available, these sections have been designed to cater for the majority of steel framed building applications and are offered with options on finish specification. Where design flexibility is needed custom made profiles in steel and in certain situations Aluminium, can be designed and manufactured to specific dimensions, a full design and technical service is available for both standard and custom rainwater systems. The Ward Streamline eaves gutter system meets today s need for an attractive yet economical fascia type gutter to compliment modern metal sidewall cladding profiles. Neat square downpipes and optional matching verge trim complete the system. Although Ward Rainwater systems are shown on steel framed buildings the construction methods and design of the systems ensure that they can be used to equal effect on concrete or timber structures. All products are manufactured using modern automated manufacturing facilities. All Ward Building Components manufacturing facilities comply with the ISO 9002 Quality Management System. Valley Gutter Ref. IGS Valley Gutter Ref. IGL Boundary Wall Gutter Ref. IGB 11:2
4 Rainwater Systems Design Concepts The design of Eaves, Boundary and Valley gutters on pitched roof metal clad buildings is based on the British Standard code of practice BS6367. This code of Practice provides advice on the best methods of designing gutters, gutter outlets and rainwater pipes along with advice on materials and construction techniques. The performance of the gutter and the capacity of the outlet to discharge water freely is particularly important with internal gutters where overflow into the building would be unacceptable under the prescribed operating conditions. The basis of the hydraulic and practical design principles assumed in the code are summarised as follows:- The Gutters are assumed to be laid nominally level. The Gutters are uniform in cross section being of a box or trapezoidal shape. Frictional effects on discharge are disregarded for certain outlet conditions. Weir overflows are recommended to internal gutters. Overflow of gutters in storm situations is not critical in externally mounted Eaves gutters. Strength of the gutter must be considered should it be needed to provide walkway access for maintenance in service. In terms of construction, Valley and boundary wall type gutters are manufactured from galvanised steel not less than 2.0 mm thickness and profiled to wrap around the steel supporting purlins. In the roof construction process these gutters are the first component of the roofing process to be laid and provide a natural access method along the building perimeter. Normally for the gutter to function as a walkway it should have a minimum overall width of 300 mm for boundary and 500 mm for valley gutters. The starting point for any gutter design is to correctly estimate the amount of water falling onto the roof. Rainfall rates vary throughout the country and are recorded on a statistical basis. The code of practice outlines a process, estimating the rainfall intensity, dependant on geographical location and the risk of the intensity being exceeded during the life of the building. Typical Applications Boundary Wall Gutter without Fascia Verge trim Sidewall cladding Ward eaves beam Boundary Wall Gutter with Fascia Verge trim Sidewall cladding Ward eaves beam Boundary wall gutter Roof cladding Rafter Stanchion Wall cladding Roof cladding Purlin Rafter Stanchion Section 11 - Rainwater Systems & Ancillaries 11:3
5 Rainwater Systems Design Concepts Components Spigot end Direction of lay Joggle end R.H. gutter length with outlet Seal Seal End maker-up Seal Optional spitter with weir Tapered outlet Stop-end right hand Custom Made Profiles Any practical shape of gutter can be produced, limited only by material girth. Gutter sections are supplied in standard module lengths of 2950mm and incorporate a standard joggle joint. * * Galvanised steel profile, 2mm and 3mm thickness * Dimensions to suit project s requirements * 20mm nominal Profile up to maximum material girth 1250mm 0.7mm liner, bright white polyester finish Rigid urethane insulation Typical Dimension Range Boundary Wall Depths Valley mm mm M10 bolt Standard Joggle Joint 40 or 50mm Joggle end Spigot end Direction of lay 11:4
6 Rainwater Systems Specification, Design & Dimensions Gutter Outlets The correct number, positioning, size and type of outlets are all factors that affect the drainage performance of the rainwater system. As a general rule it is good practice to allow at least two outlets in any one length of gutter. Outlets are designed to achieve the required discharge rate based on the head of water in the gutter. In order to optimise the design of the system 4 types of outlet may be used. Straight outlets are normally used for eaves, valley and boundary wall conditions where design conditions are not onerous. Tapered outlets offer best performance and economy for most valley and boundary wall gutters. The opening in the sole of the gutter tapers into a standard diameter downpipe of 100 or 150 mm. Box receivers are used for demanding flow conditions where practical conditions such as restrictions to downpipe position may otherwise restrict system performance. Syphonic outlets employ design methods outside of that described in BS6367 and are usually designed and supplied by specialists. They operate on the principle that the drain pipes flow full of water by not allowing air to enter the system. Syphonic outlets are easily incorporated into the Ward gutter range. Straight outlet (round), welded or loose Tapered outlet, welded or loose Weir overflow outlets positioned at the ends of the gutter cannot prevent flooding of the gutter profile but are recommended, since they can provide warning of blocked outlets or other problems with the gutter system. Gratings or wire balloons to protect the rainwater pipe are a potential source of blockage and are not recommended for conventional systems. Rainwater Pipes Rainwater pipes are normally circular in section and made of PVC or Aluminium and supported by brackets to the structure typically at 2.0 m centres. Bends and joints should be kept to a minimum and horizontal pipe runs should have falls and be designed to normal hydraulic principles. Syphonic systems involve greater design pressures and require special considerations. Typical Applications Roof cladding Valley gutter Outlet Specification of the galvanising weight is dependant on the exposure conditions and required life span of the building. In certain cases post galvanised gutters may be specified, this finish, due to the coating process, will require a minimum thickness of 3mm. Steel gutters of normal design dimensions require a minimum recommended thickness of 2mm. Experience has shown that gutters with sole dimensions in excess of 450 mm will require 3mm minimum thickness. Durability The cost and probability of maintenance will influence the choice of material and the galvanising thickness. Black bitumen coatings or similar are required on all steel gutters. These should be applied after about 12 months weathering of the new galvanised steel and will require regular re-application to remain effective. To minimise on site painting, the gutters can be supplied with a factory applied protective coating which includes manufacturer s performance warranty. Advice on periods to first maintenance and environmental conditions is outlined in British Steels Galvatite technical manual. Gutter Accessories Gutter accessories such as weir outlets, stop ends, jointing mastics and joint connectors are supplied using materials that are the same as or complimentary to the gutter profile used. Custom made accessories can be made to suit each unique building application. Stop-ends Section 11 - Rainwater Systems & Ancillaries Box receivers Materials Gutters are normally fabricated from pregalvanised steel to BS EN Two galvanising thicknesses are available namely Z275 and Z600, indicating the coating weight, including both sides, in grams per square metre. Corners Weirs - welded or loose 11:5
7 Rainwater Systems Specification, Design & Dimensions The following should be incorporated into the maintenance program:- Gutters, rainwater pipes, outlets and gratings should be inspected and thoroughly cleaned at least once a year. This should occur more frequently if :- The building is in an industrial area with significant discharge of airborne waste (paper, packaging etc) The building is near trees. The building is in an area subject to extremes of temperature. The gutter is equipped with high performance outlets. Maintenance Maintenance of a rainwater system is vitally important, almost as important as the initial design. All work must be carried out by qualified operatives complying with all current legislative safety requirements. A responsible person should be delegated within the building owner s organisation to monitor and ensure that the above processes occur. Failing this an external contractor or consultant should be appointed. The system should be inspected every five years by a specialist contractor or consultant, to check for component decay, damage or unauthorised alteration to the original specification. All maintenance works must be carried out by complying to all current safety legislation. Installation Installation must be carried out by qualified operatives complying with all current legislative safety requirements. Gutters are assembled so there is a joggle at the leading end. Seals must be fitted with care, in clean dry conditions avoiding any tendency to stretch the seal over bends in the profile. Prior to tightening the bolts correct alignment and seating of the gutter on its supports are checked. All bolts are tightened, starting from the centre of the sole working outwards to each side of the profile. Outlet positions, where possible, should be factory installed however if they are cut on site all burrs should be removed to avoid corrosion and ensure adequate surface for sealing. Damage to the gutter surface must be treated and all debris removed from the gutter prior to progressing with other roofing works. Insulation It is normally recommended that gutters have less insulation than the roof to enable prior melting of snow and ice. In practical terms this can be achieved by lowering the overall insulation U value compared with the roof, for example use 0.6 U value for the gutter insulation where the roof has 0.45 U value. Insulation thickness mm U value w/m 2 K :6
8 Standard Gutter Range - Boundary Wall Gutter To ensure ease of specification and procurement Ward offer a range of standard gutters to cater for the needs of most Industrial type buildings and provide optimal flow characteristics, economical design and practical site assembly. Material Specification Pre-galvanised finish: Available in 2mm or 3mm thickness. Manufactured from pre-galvanised steel sheet to BS EN 10142:1992 grade Fe P024 Z275. Finished Gutter Weight (kg/m) Thickness Girth 2mm (14g) 3mm (10g) 750mm Section 11 - Rainwater Systems & Ancillaries Alternative galvanised thickness and paint finish options are available to suit durability required. Contact Ward for availability. Best practice - after a suitable period of weathering we recommend that all galvanised gutters are given a heavy bituminous coating. Gutter Type IGB 107mm 442mm Insulation thickness mm U value w/m 2 K Roof slope angle mm mm Alternative bolt on straight outlet Outlet Seal Gutter Lengths Gutters are detailed on the basis of its total length. The gutter comprises a combination of plain lengths, outlet lengths and make-up lengths detailed to suit the requirements of the layout. maximum module length is 2950mm 100mm 100mm Outlet dia.+ 80mm Bolt on tapered outlet shown The direction of lay needs to be specified if:- 1 Outlet positions are not symmetric on plan along length 2 Outlet positions are not on CL of sole 3 Gutter profile is not symmetric Frame centres Frame centres Frame centres A Specify outlet type and diameter Stop-end * Section A-A A * * * Overall length of gutter Direction of lay * Client to specify running dimensions 11:7
9 Standard Gutter Range - Valley Gutter Material Specification (Both Profiles) Pre-galvanised finish: Available in 2mm or 3mm thickness. Manufactured from pre-galvanised steel sheet to BS EN 10142:1992 grade Fe P024 Z275. Finished Gutter Weight (kg/m) Thickness Girth 2mm (14g) 3mm (10g) 914mm mm Alternative galvanised thickness and paint finish options are available to suit durability required. Contact Ward for availability. Best practice - after a suitable period of weathering we recommend that all galvanised gutters are given a heavy bituminous coating. Gutter Type IGS Slope to suit clients requirements 590mm 333mm Insulation thickness mm U value w/m 2 K 127mm Tapered Outlets Weld on tapered outlet shown Available as welded on or bolt on items the taper provides enhanced efficiency. Ø 150mm Ø 225mm For example the 150/100 outlet provides the discharge capacity of a 150mm pipe while using a straight fallpipe of only 100mm diameter. 150mm 225mm Outlets are manufactured from 3mm galvanised steel. 150/100 Outlet 100mm 225/150 Outlet 100mm Ø 100mm Ø 150mm Gutter Type IGL 107mm 888mm 638mm Roof slope angle 127mm 11:8
10 11:9 Section 11 - Rainwater Systems & Ancillaries
11 Components & Ordering Ordering Gutters are normally manufactured from materials of maximum 1250 mm girth. Wherever possible standard lengths of 3000 mm are used giving an effective length, allowing for the joint, of 2950mm. When ordering the gutters, all that needs to be specified is the overall length of gutter for any one run along with the detail of the cross sectional dimensions, outlet position and size, material type and thickness. Service Ward provide a comprehensive technical advisory service to deal promptly and efficiently with any technical queries regarding gutters and their installation. Delivery Carriage is paid on goods delivered to British mainland, method of transport at our discretion, normally by road. 11:10
12 Section 11 - Rainwater Systems & Ancillaries PLEASE PHOTOCOPY Insulated Gutter Order Form Ward Insulated Panels Limited Sherburn, Malton, North Yorkshire, YO17 8PQ, England Tel: Fax: Internet: Client s Name: Contract No. (Office Use): Delivery Address: Client s Reference: Contact Name: Date Required: Order No.: Contact Phone No.: Page of Standard Gutter Profiles See pages 8 & 9 for details Boundary Wall Valley Valley Ref IGB Ref IGS Ref IGL Custom Gutter Profiles See page 5 for details (maximum girth = 1250mm) Dimensions and angles required:- State lengths and quantity on sheet 2 of this order form A A B B B 20 D X X X Y Y Y Boundary Type Mkd..... Valley Type Mkd..... Dim A = mm Dim A = mm Dim B = mm Dim B = mm Dim C = mm Dim C = mm Dim D = mm Dim D = mm Ref No. Dim X = degrees Dim X = degrees Ref No. Dim Y = degrees Dim Y = degrees Ref No. Fill in dimensions and angles noted above, otherwise reference separate drawing no Material Specification Stop Ends Thickness 2mm 3mm Other Type Weir Outlet Plain Coating G275 G600 Other Fixing Weld On Bolt On Insulation Insulation 40mm 50mm None 40mm Urethane Insulation Quantities will be to suit number of gutter runs ordered, as 50mm Urethane Insulation specified on sheet 2 of these order forms. Sheet 1 of 2 Outlet Type Weld On Bolt On Tapered 225/150 Tapered 150/100 Standard 150 Standard 100 Tick either weld on or bolt on with outlet type and diameters as listed. Bolt on outlets allow, flange diameter of 80mm plus diameter of pipe. C Signature C C Date
13 Insulated Gutter Order Form Sheet 2 of 2 Gutter Lengths Boundary Wall Type A Section A-A Valley Type 1 1 A Section A-A Corner Units J Type JJI K J K J Type JJE lengths Note: Corner units are manufactured to 1000mm module leg Detailing 1 Specify position of outlet centreline in sole 2 Specify overall gutter length (including insulation or corner units if applicable) 3 Specify outlet dimensions from start end of gutter A Overall gutter length as specified in Level sole - Specify angle K J = Joggle end - S = Spigot end Stop end at A B (as sheet 1) Corner unit at A B (specified below) Provide..... number of lengths as detailed Provide..... number of lengths as detailed 1000 module A A A 2950 max 2950 max Direction of lay Direction of lay Provide..... number of lengths opposite hand Direction of lay Provide..... number of lengths opposite hand No. corner units Type Angle K No. corner units Type Angle K above PLEASE PHOTOCOPY Ward Insulated Panels Limited Sherburn, Malton, North Yorkshire, YO17 8PQ, England Tel: Fax: Internet: J A S J B S Type SJI S K K Type SJE J J B B
14 Eaves Gutter Eaves constructions utilising an external gutter system are usually based around a purpose designed cold formed eaves member. These sections are formed to the roof pitch of the building, thus ensuring a good bearing surface for the roof and wall panels. In a normal eaves condition the end of the insulated roof panel features a cut back of the insulation to attain a drip edge and accommodate the external gutter detail. In the case of the Ward Roof - Low Pitch or Curved DR1000 panel the standard insulation cut back measurement is 65mm, for Ward Roof - Trapezoidal IP1000 the dimension is 75mm. This dimension provides a practical distance for erecting and fixing the eaves gutter without compromising strength. To maintain continuity of insulation around the eaves member, the wall panel is detailed to form a close joint with the underside of the roof panel. A compressible seal is used at this junction. In order to obtain clean building lines the Streamline range of cladding supported gutters is used. This purpose designed gutter section integrates with the standard verge flashing and preengineered corner units to provide an unbroken shadow line around the roof to wall junction of the building. Constructed in plastisol colour coated steel, the range of roof gutters covers roof slope increments from 2 to 24. The inner lip of the gutter is fixed to the underside of the insulated panel outer skin using 6 fixings per panel, the front lip is supported on arms fitted to the profile corrugations at 1.0 metre centres. External Gutter Fixing screws FX5 at all five positions shown Streamline gutter SG30 series Ward eaves beam 10 mm 35 mm 20 mm Ward gutter support 0.7mm thick double sided plastisol coated Ward Roof - Low Pitch DR1000 details shown as example, for exact details refer to relevant product section Profiled filler FDRN05WP Seal arm to panel using SX1902BG on crown of profile local to each fixing Do not fix support arms to snap caps where applicable Section 11 - Rainwater Systems & Ancillaries 1000mm Support arm centres 11:13
15 Streamline Gutter System Gutter support arms Gutter corner unit Butt strap Bracket Downpipe collar Gully adaptor Section through Butt Strap Joint Butt strap Flashing/gutter to be jointed SX0300ST sealant applied 6mm beads FX17R pop rivet Ward Streamline is the family of components which provide cladding and bracket supported gutter systems for the entire range of Ward insulated and profiled roofing systems. The gutter cross section, support arms and pre-formed corner units are manufactured to suit the specific profile dimensions of the Ward roof system being used. The components are joined to the verge flashings by means of pre-formed corner units to form a shadow-line construction around the roof to wall junction of the building. manufactured from 0.7mm thick double sided plastisol coated steel, the range of gutters covers roof slope increments from 2 to 24. The gutter is supported from the roof cladding using support arms sealed and fixed over the corrugations of the roof profile. Support arms may be colour matched to suit the roof sheet or the gutter. Gutter Support Arm GSA Supplied to suit panel profile with predrilled holes for fixing screw location. Gutter Corner Units Gutter corner units form the junction between gutter and verge. They are manufactured to suit increments of roof slope from 2 to 24. Connection is made by means of a butt strap joint detail to the gutter and a minimum 75mm overlap of the verge flashing. Downpipe Lengths Downpipes are available in any length up to 6.0m. Swan necks and shoe details are available as factory manufactured units or may be formed on site using the standard components. Gutter Joints Gutters are available in standard 6.0m lengths and in specified make up lengths up to 6.0m. The butt strap joint is site formed using a silicone mastic seal secured with pop rivets FX17R. Gutter lengths are joined on site by means of a pre-formed gutter section. Joints should occur close to but not at the position of the gutter support arm. To enhance appearance the rivets may be touched in with a colour matched paint. 11:14
16 Downpipe Construction The square downpipe of the Streamline Gutter System is designed to complement all functional and visual aspects of the eaves gutter components and is available in lengths of up to 6.0 metres. The downpipes are 95mm square and constructed from 0.7mm thick, double sided, plastisol coated steel, seam jointed at one corner, which is usually placed away from the line of sight. A range of accessories for fixing the downpipes are manufactured in the same materials. The size of the downpipe is designed to meet the gutter s flow capacity to produce an efficient and practical system. The following recommendations for the spacing of downpipes are based on the guidelines of BS 6367 Code of Practice for Drainage of Roofs and Paved Areas. The rate of rainfall used is 75mm per hour and calculations are on a gutter flow rate of 15 litres per second and a downpipe capacity of 7 litres per second. The distance between downpipes is determined by the least value of the following conditions. Downpipe Brackets The downpipe must be supported at centres not exceeding 3.0 metres. This must be provided within 200mm of the gutter and within 1.0 metre of the base. Two types of bracket are available. SDPB95 is suitable for fixing to profiled wall cladding such as Ward Wall - Profile Rib DR1000W and Ward Wall - Trapezoidal IP1000 sidewalls. This bracket may also be used on flat sidewall cladding. Where a concealed fixing is required to complement the wall cladding, bracket assembly SDPS95 is used. This bracket may only be fixed to flat sidewalls as the Ward Wall Insulated panel range. Downpipe Bracket Options Rivets FX17R Seam Downpipe Base The downpipe may be formed on site to give a shoe for discharge into the ground drainage. Alternatively, square to round gully adaptors may be used as the basis for linking to 100mm or 150mm diameter ground drainage. Downpipe Base Detail with Gully Adaptor Down pipe 154 diam. inside ref. SDGA95/ diam. inside ref.sdga95/10 Section 11 - Rainwater Systems & Ancillaries 1. Two downpipes are required as a minimum in any one length of gutter. 2. Downpipes to be spaced at maximum centres of 13 metres. (6.5 metres from a stop end). Fixing bracket SDPB95. The bends are formed on site to suit gutter offset 100sq. inside 3. Maximum roof area per downpipe - 300m diam. collar 200mm max. Fixing bracket assembly SDPS95 suitable for flat wall panels only Joint at Downpipe Downpipe/Gutter Connection The downpipe is connected to the underside of the gutter by means of sealing and rivetting to flanges formed during fitting on site. These flanges are formed with the assistance of an outlet forming tool FT95 3.0m max. Joints are formed between lengths of downpipe by using a joint collar SDPC95 rivetted and sealed to the ends of each pipe. Rivets each side FX17R m max. A downpipe support bracket must be used at each joint position. 65 Silicone sealant SX0300ST m max. Rivets each side FX17R 11:15
17 Downpipe Components Gutter Gutter sections are manufactured from 0.7mm thick steel with a plastisol coating on both sides. The principal angles and dimensions of the gutter varies with the roof pitch. For roof slopes in between those noted on the table, the gutter section is chosen by selecting the nearest higher tabulated pitch. Gutters are available in standard lengths of 6.0 metres and in specified make-up lengths up to 6.0 metres. each gutter length is available with a butt strap Roof Pitch Gutter Ref. SG3002 SG3004 SG3006 SG3009 SG3012 SG3015 SG3018 SG3021 SG Varies Gutter Support Arm GSA Supplied pre-punched for roof fixing screw location, manufactured from 0.7mm steel. Product DR1000 IP1000 Support Arm Ref. GSADR GSAIP Gutter to Verge Trim Corner Unit GCA30 The corner units are factory assembled from plastisol coated steel and are profiled to connect with the standard gutter and verge trim VF3. The unit incorporates a sealed and rivetted stop end for the gutter. All external joints and rivets are touched in with colour matched sealing compound Roof Pitch Corner Ref. for VF3 Verge Trim GCA3002 GCA3004 GCA3006 GCA3009 GCA3012 GCA3015 GCA3018 GCA3021 GCA :16
18 Downpipe Components Downpipe SDP95 Outlet Template SDPT mm Gully Adaptor SDGA95/ Outlet Forming Tool FT95 Collar SDPC95 Downpipe SDP95 Downpipes are available in any length up to 6.0 metres. Swan necks and shoe details are available as factory manufactured units or may be formed on site using the standard components. Brackets SDPB95 Used for fixing to profiled or flat sidewall cladding. Legs bent to shape on site. Collar SDPC95 The collar incorporates internal fins to assist location of the joining pipes and water flow. All downpipe joints must be bracket fixed to the side wall. Tools The outlet forming and template tools ensure successful marking and forming of the gutter base to accept the 95mm square downpipes. Section 11 - Rainwater Systems & Ancillaries 65 Gully Adaptors Gully adaptors manufactured in grey PVC enable connection of the downpipe to underground drainage Brackets SDPS95 100mm Gully Adaptor SDGA95/ Used to produce a concealed fixing to flat sidewall cladding Brackets SDPB95 Bends are formed on site to suit 11:17
19 Streamline Gutter Order Form Sheet 1 of 1 PLEASE PHOTOCOPY Ward Insulated Panels Limited Sherburn, Malton, North Yorkshire, YO17 8PQ, England Tel: Fax: Internet: Client s Name: Contract No. (Office Use): Delivery Address: Delivery reqd, w/comm: Roof Colour: Roof Slope: degrees Order No.: Gutter / Verge Colour: Downpipe Colour: Component Description Product Ref Quantity Gutter support arm GSA Gutter 6 metre length* SG30 Gutter length* mm* SG30 Gutter length* mm* SG30 Gutter/Verge corner right hand* GCU30R Gutter/Verge corner left hand* GCU30L Gutter external corner* GEC30 Gutter internal corner* GIC30 Gutter butt strap GBS30 Gutter stop end left hand GSE30L Gutter stop end right hand GSE30R Verge flashing 4 metres* VF3 Verge apex unit* VTA3 Verge valley unit* VTV3 Verge butt strap VFBS3 Verge flashing stop end VFE1 Verge flashing support zed VFS1 95sq Downpipe 6 metre length SDP95 95sq Downpipe length mm SDP95 95sq Downpipe length mm SDP95 Downpipe bracket to sidewall SDPB95 Downpipe collar (pipe to pipe) SPDC95 150mm Gulley to 95 Downpipe SDGA mm Gulley to 95 Downpipe SDGA9510 Outlet template 95sq SDPT95 Forming tool 95sq FT95 Fixing screws** FX5 Fixing screws** FX9 Pop rivets (multiples of 1000) FX17R Bulbtite rivets (multiples of 1000) FX12R Tube sealant, 6 diam bead 8m SX03000ST Tape seal 22.5m roll SX1902BG Factory formed downpipe components Swan neck Downpipes: Quantity A Swan necks: Offset = A = B = Angle = Shoes: Quantity X Shoes: Dim x = Offset 25 or 48 deg B mm mm (150mm min) mm (150mm min) (25 or 48 deg) 45 deg (100mm min) * Unless the number of butt straps required is stated, the quantity supplied will be to Ward spec ** Fixings supplied in multiples of 50 All orders are subject to Ward Insulated Panels Standard Terms and Conditions, a copy of which can be obtained from our Sherburn office. Signature Date
20 Rainwater Components Insulated and uninsulated gutters showing joint details. Guttering is supplied in insulated or uninsulated steel and aluminium in our full range of finishes, and can be made to any detail or design to meet all architectural requirements. Section 11 - Rainwater Systems & Ancillaries Available as valley or boundary wall gutters - manufactured in either g.b.m. or g.a.m. steel. Additional protective finishes can also be applied on request. A full range of accessories can be supplied as part of our gutter systems. A selection of outlets, sumps and corners are shown opposite. 11:19
21 Rainwater Components Lightweight pre-coated steel guttering available in lengths up to six metres supplied in an extensive range of finishes. The ever-increasing use of polyester powder coating finishes enhances the visual concept of the modern day building, at the same time serving it s purpose efficiently. Downpipes, brackets and accessories required for rainwater removal are amongst our current range. In fact whatever your architect requires we can design, fabricate and supply in aluminium, galvanised or pre-coated steel with polyester powder coated finishes if required, to suit each specific project. 11:20
22 11:21 Section 11 - Rainwater Systems & Ancillaries
23 11:22
24 Rainwater Components Section 11 - Rainwater Systems & Ancillaries Gutter Design Software Available to our clients is our new gutter design software. Advise us of your rainwater requirements and we will provide you with a full gutter design package specifying all technical data to confirm your gutter is of a functional design. 11:23
25 Membrane Gutter Specifications Membrane Gutter System Type A factory assembled insulated self supporting gutter lined on the external surface with a fully bonded weldable PVC membrane. The gutters are designed to be a low maintenance component and may be used as a walkway given suitable edge protection. Gutters are available in any configuration to suit the clients design requirements. Water Carrying Surface Steel Substrate mm thick steel (Grade British Steel BS EN : 1995 DX51D & AZ150) coated in Aluzinc to BS EN : 1995 DX51D & AZ150 and reverse lacquer protected steel sheet for exterior roofing applications. PVC laminate, Gutter Area - 400/D single ply polymeric roofing membrane, 0.6mm thick. General - A strong, weatherproof and uniform PVC polymeric membrane bonded to a weather protected, pretreated steel substrate using a cross linked vinyl acrylic adhesive so as to provide an integral weatherproof barrier for the minimum period of 20 years within normal European exposure limits. Insulation PIR insulation board, cut to suit the gutter profile and bonded in place. Alternatively EPS insulation may be specified. Each insulation material may be specified in a thickness to suit the U value requirements for the project. Internal Liner Sheet Substrate to be 0.7mm thick zinc coated steel grade FeE220G Z275 to BS EN : Internal coating to be Colorcoat Lining Enamel, 22 microns thick coloured white. Accessories Supports - where required, 50 x 6mm flat pre-galvanised steel straps are available. Factory fabrications - Corners, stop ends, tees, box outlets and section changes. Site materials and 200mm reinforced membrane jointing strips, outlet, overflow weirs, fixings and sealants. Assembly The inside and outside gutter skins are bonded to the insulation and the flanges where the surfaces come together are joined by clinching or riveting. Method of Jointing Joggle lapped joint. Standard joints to be made using 200mm membrane jointing strips, expansion joints to be made with 200mm membrane jointing strips. 11:24
26 A range of high quality membrane gutters and ancillaries is available to complete the Topdek system. Section 11 - Rainwater Systems & Ancillaries Membrane lined flashing Typical Outlet Typical Stop End Insulated Membrane Lined Gutters Reliable lifetime performance - 15 years warranty, in excess of 40 year life expectancy Superior quality, continuously sealed gutter - no through penetration, bolt or seal failure risk 50% faster installation - single component system Loss Prevention Certification Board (LPCB) certified insulation Suitable for conventional or siphonic drainage systems Project specific design, layout and dimensions Full ancillary range Jointing system accommodates thermal movement 11:25
27 Membrane Gutter Typical Details Joint Details Cross Section Insulated Hot air weld 50mm 100mm Loose Hot air weld 50mm Single skin Hot air weld 50mm Joggle 50mm 100mm Loose Hot air weld 50mm Joggle 50mm Riveted gutter skins 200mm reinforced PVC membrane strip Outlet Details Conventional Straight Outlet Conventional Tapered Outlet Syphonic Outlet Leafguard PVC Coated aluminium outlet Available in a range of other materials ie PVC and Aluminium Gutter Details Boundary Wall Gutter Valley Gutter 11:26
28 11:27 Section 11 - Rainwater Systems & Ancillaries
29 Architectural Features & Ancillaries Components Complimentary architectural features & ancillary components to integrate with the Ward range of insulated roof and wall panels are available from specialist suppliers. Please contact Ward for further details. Flashings Aperture Units Insulated Valley Gutters (membrane lined) Bonded Facia Panels Column Casings Rain Screen Panels Rainwater Pipes 11:28
30 Insulated Boundary Wall Gutter (membrane lined) Bullnoses Ridge Ventilators Section 11 - Rainwater Systems & Ancillaries Pre-formed Insulated Panels Facia Gutters Louvred Door Louvres 11:29
Trimform for panels, purlins & gutters. No obligation consultation
Trimform for panels, purlins & gutters. No obligation consultation Vers 1:02/2016 Trimform Insulated Panels Trimform insulated panels consist of two coated steel profile bonded to a core of PIR insulation;
More informationJ41 Reinforced bitumen membrane roof coverings
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/ General conditions. TYPES OF COVERING 115A SINGLE LAYER REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING warm roofing system
More informationBENCHMARK Evolution Axis
Sheet List EVO VT 00 B DIRECTION OF PREVAILING WIND VERTICAL PANEL JOINT & FASTENER LOCATIONS DIRECTION OF LAY FACTORY APPLIED WEATHER SEAL CONCEALED PANEL FIXING NOTE: FASTENER NUMBERS DEPEND ON THE ACTUAL
More informationBUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Two layer, EXCEL/SPOT fully adhered waterproofing system
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Two layer, EXCEL/SPOT
More informationHip Detail. Construction Details. KS1000 LP/CR Roof. Hip Detail STANDARD ENHANCED ENHANCED STANDARD. Mineral fibre insulation
Hip Detail Hip Detail STANDARD Mineral fibre insulation ENHANCED Hip flashing with 150mm sealed butt straps Panels site cut to suit rake angle Apex dam (Ref: LP1/A) Rake cut profiled filler sealed top
More informationspecification clauses 1
specification clauses 1 CI/SfB July 2006 (4-) Uniclass L7314 The following pages provide draft specifications for standard Bailey Systems. These will easily integrate with the National Building Specification.
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL WALL PANELS This Guide Specification
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationJ41 Reinforced bitumen membrane roof coverings
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. A comprehensive waterproofing system comprising two reinforced bituminous membranes fully adhered to thermal
More informationPromistyl 3005T - roofing
Metal Cladding Panel reference Arval Globalroof Promistyl 3005T ribbed face fix composite fire rated roofing panels Arval Promistyl 3005T Manufacturer ArcelorMittal Lammerdries 82440 Geel Belgium web site:
More informationTATA BLUESCOPE STEEL LIMITED PRODUCT SPECIFICATION LANGUAGE FOR PRE ENGINEERED STEEL BUILDING (BUTLER BUILDING SYSTEM- WITH MR-24 ROOF SYSTEM)
Section 1: General Product specification Language Item language Item No. Description EX. Works Supply Price Freight Erection Taxes & Duties Total Amount Item 1 Structural Members Supply of BUTLER Building
More informationStanding Seam Systems. NBS Specification. KingZip SF Standing Seam Roofing System
NBS Specification KingZip SF Standing Seam Roofing System H31 METAL PROFILED/FLAT SHEET CLADDING/COVERING To be read with Preliminaries/General conditions. TYPE OF CLADDING SYSTEM 140 METAL PROFILED CLADDING
More informationInsulated Roof. Architectural Features & Cladding Components
Insulated Roof & Wall Panels Fabrications Architectural Features & Cladding Components Fabrications Kingspan Insulated Panels is committed to providing both standard and bespoke products that combine architectural
More informationAluminium Coping Systems
Aluminium Coping Systems Excellence in aluminium engineering >Company Profile Alifabs leads the field in the design, production and installation of aluminium building products. Our experience spans some
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationJ41 Reinforced bitumen membrane roof coverings
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110 BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING Substrate: Plywood to
More informationFlashings TYPICAL SHAPES AND JOINTS
CONTENTS PAGE Also available Flashings Rainwater Components Facades & Rainscreen Panels 1-4 5-6 7-10 Bullnoses & other Architectural Features 11-14 Louvres 15-16 Materials 17 Colour Charts 18 Our Premises
More informationCorrugated sheet for single storey, sectional buildings and stables
Cl/SfB l (4-) Nf9 l l September 2011 l Corrugated sheet for single storey, sectional buildings and stables B5 Corrugated sheet and accessories Cembrit companies have been manufacturing corrugated sheets
More informationArchitectural Roof Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Roof Products Guide Specifications FORMED METAL ROOF AND WALL PANELS This Guide Specification
More informationSection 3 Ward Roof Trapezoidal IP1000
Section 3 Ward Roof Trapezoidal IP1000 Panel Dimensions 2 Product Data Sheets 3-5 Load Tables 6 Recommended Fastener Locations 7 End Lap Detail 8 Side Lap Detail 9 Ridge Detail 10-11 Verge Detail 12-15,
More informationSECTION ALUMINUM WALKWAY COVERS. A. The requirements of Division 1 specifications shall apply to work specified in the section.
SECTION 10 5300 ALUMINUM WALKWAY COVERS Part 1 General 1.01 Related Documents A. The requirements of Division 1 specifications shall apply to work specified in the section. 1.02 References A. International
More informationContents DESIGNER S STRUCTURAL PRODUCTS GUIDE. Tegral Purlins & Rails
DESIGNER S STRUCTURAL PRODUCTS GUIDE Introduction Contents Tegral Purlins & Rails Zeta Purlins & Rails Zeta Purlins page 8 Zeta Rails page 15 Zeta Purlin & Rail Cleats page 22 Zeta 2 Purlins & Rails Zeta
More informationInsulated Panel Systems United Kingdom. Fabrications Architectural Features & Cladding Components
Insulated Panel Systems United Kingdom Architectural Features & 2 Kingspan From Concept to Completion Our Manufacturing & Design Offering Extensive experience in fabrication techniques, combined with state-of-the-art
More informationKingspan Topdek KS1000 TD Insulated Single Ply Roofdeck Installation Guide
Insulated Roof & Wall Panels UK & Republic of Ireland Topdek KS1000 TD Insulated Single Ply Roofdeck Installation Guide June 2018 Topdek (KS1000 TD) Components Topdek (KS1000 TD) 514cw 50mm Wide Acrylic
More informationInsulated Roof & Wall Panels. KS1000 TD Data Sheet. Topdek Single Ply Roof Deck. Insulated Panels
Insulated Roof & Wall Panels KS1000 TD Data Sheet Topdek Single Ply Roof Deck Insulated Panels KS1000 TD Technical Data Product Overview Kingspan offers superior roof panel systems compared to conventional
More informationArchitectural Wall Products Guide Specifications
Western States Metal Roofing 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 Architectural Wall Products Guide Specifications FORMED METAL WALL PANELS This Guide Specification is
More informationArchitectural Roof and Wall Products Guide Specifications
Architectural Roof and Wall Products Guide Specifications 901 W. Watkins St. Phoenix, AZ 85007 PH: 602-495-0048 FX: 602-261-7726 FORMED METAL ROOF AND WALL PANELS This Guide Specification is to be used
More informationSPECIFICATIONS FOR PROPOSED
SPECIFICATIONS FOR PROPOSED PROFILED ROOF / WALL CLADDING Client: Site address: Proposed material: Proposed profile: Rib / Seam centers: Seam height: www.archtech.co.nz 0800 252 383 info@archtech.co.nz
More informationRAINWATER DISPOSAL SYSTEM PERFORMANCE STATEMENT
RAINWATER DISPOSAL SYSTEM PERFORMANCE STATEMENT 3.1.1 (a) Description Dimond rainwater disposal systems are available in a variety of materials together with the appropriate brackets and downpipes. Table
More informationB5 for garages, equestrian and other single storey buildings
Cl/SfB l (4-) l Nf9 l March 2017 l B5 for garages, equestrian and other single storey buildings Corrugated sheet and accessories www.cembrit.co.uk Cembrit companies have been manufacturing corrugated sheets
More informationFUNCTIONAL REQUIREMENTS
FUNCTIONAL REQUIREMENTS FUNCTIONAL REQUIREMENTS 7.6 BALCONIES Workmanship i. All workmanship must be within the tolerances defined in Chapter 1 of this manual. ii. All work is to be carried out by a technically
More informationArchitectural Roofing
ArcTray 1. GENERAL This section deals with the supply and fixing of ArcTray overlap rigid sheet metal profiled roofing and/or cladding complete with accessories. Documents 1.1 DOCUMENTS REFERRED TO Documents
More informationTYPICAL ROOF CONDITION LAYOUT
FIXED POINTS TYPICAL ROOF CONDITION LAYOUT 15 17 9 16 29 12 14 11 3 7 35 20 6 23 30 31 24 13 18 Typical Roof Condition Layout... 1 Low Eave Isometric View - Fixed/ Floating... 2 Low Eave Section - Fixed/
More informationOriginal Scandinavian rainwater system
Original Scandinavian rainwater system Siba Siba Square Contents Siba rainwater systems 3 Measuring 15-16 Siba 4-9 Gutter brackets 18-19 Siba Square 10-11 Gutters 20-23 Materials 12 Angles 24 Technical
More informationPluvia Product and Installation Guide
Pluvia Product and Installation Guide Valid from 1. April 2013 Siphonic System Elements Guide All Geberit Pluvia rainwater systems in the UK and Ireland are installed by fully trained Approved Installers,
More informationLIQUID APPLIED WATERPROOF ROOF COATINGS
J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. plywood, OSB3,
More information112mm. 117x75mm Polyflow. 130x70mm Ogee 68mm Round 65mm Square. 112mm Half Round 68mm Round. 65mm. Round. 112mm. 117x75mm Polyflow
Gutter and Systems A comprehensive range of fittings accompanies each rainwater profile in Polypipes unrivalled product range, to provide the specifier and installer with a complete roof drainage solution.
More informationContents. Timber framing to be installed in accordance with AS:1684 Metal framing to be installed in accordance with BCA Volume: 2
Contents BCA Codes 3 General 4 Fire Performances Thermal and Acoustic Insulation Wall Installation 4 Timber Frame Separation Walls 5 Steel Frame Separation Walls 6 External Fire Rated Walls 7 Floor Installation
More informationSECTION PRE-ENGINEERED EXTRUDED ALUMINUM DECKING WALKWAY COVERS SPECIFICATION
Awning Works Inc Aluminum Decking Walkway Cover Specification CSI- Division 10 SECTION 10530 PRE-ENGINEERED EXTRUDED ALUMINUM DECKING WALKWAY COVERS SPECIFICATION PART 1 GENERAL 1.01 DESCRIPTION OF WORK
More informationatlantic Monsoon gutters
atlantic Monsoon gutters CI/SfB August 2008 (37) Uniclass L7314:G34 complete aluminium eaves assemblies with fascia, soffits and rainwater systems using standard or bespoke details Bailey Atlantic Monsoon
More informationF Ü R D I E ZU K U N FT G E DAC HT. Flat roof vents. Soil vent pipes Refurbishment vents Cold roof vents
F Ü R D I E ZU K U N FT G E DAC HT. Flat roof vents 1 Soil vent pipes Refurbishment vents Cold roof vents F Ü R D I E ZU K U N FT G E DAC HT. alwitra waterproofing system Flat roof vents are part of the
More informationJ41 Reinforced bitumen membrane roof coverings
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING, EXCEL/SPOT, warm roof
More informationJ41 Reinforced bitumen membrane roof coverings
J41 Reinforced bitumen membrane roof coverings To be read with Preliminaries/General conditions. TYPES OF COVERING 110A BUILT-UP REINFORCED BITUMEN MEMBRANE WARM DECK ROOF COVERING, EXCEL/SPOT, warm roof
More informationLIQUID APPLIED WATERPROOF ROOF COATINGS
J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. Plywood, OSB3,
More informationROOFING & REINFORCEMENT SPECIALISTS
ROOFING & REINFORCEMENT SPECIALISTS CONTENTS. QUALITY CLADDING, AFFORDABLE PRICES ROOFING PROFILES... FORECLAD 200 FORECLAD 250 WALL PROFILES... FORECLAD 200 FORECLAD 250 LINER PROFILES... FL19 FL20 F200WL
More informationHi-Point TM off-site roof system
CI/SfB (27) Xh September 2006 Kalzip Ltd Hi-Point TM off-site roof system Benefits Hi-Point... off-site roof system with the benefits built-in A superior, simple and safer method of roof construction Health
More informationLight-Metal Roof Edge, Raised
NAIL WOOD CANT TO BLOCKING 2 ROWS STAGGERED EACH ROW 24 O.C. 1/2 MIN. 10 0 MAX. FASTEN 18 O.C. WITH NEOPRENE GASKETED FASTENERS 3-1/2 MIN. 4 6 JOINT COVER PLATE SET IN TWO BEADS OF SEALANT 4 MIN. SPECIFIED
More informationProduct Data Sheet (rev c 16/7/15) Product: BENCHMARK Roofliner System
APPLICATION The BENCHMARK Roofliner system is to be used as an insulated composite roof deck under site applied single-ply membranes or fully supported or self-supported aluminium, copper, zinc and stainless
More informationHoesch isodach integral Technical information
Technical information A company of ThyssenKrupp Steel tk Contents Page General 3 Main dimensions and properties 4 Corrosion protection 5 Thermal protection / Insulating core 5 Fire protection 5 Information
More informationCavity Tray Application
Cavity Trays Cavity Tray Block Cavity Trays Page 4 Door & Window Cavity Trays Page 8 Lead Chimney Trays Page 9 Inter-loc Horizontal Cavity Trays Page 7 Lintel Cavity Trays Page 8 Brick Cavity Trays Page
More informationGRP Flat Roofing Edge Trims
GRP Flat Roofing Edge Trims Compatible with GRP, rigid and flexible polyester, polyurethane, acrylic and alkyd systems. Trim Brochure and Technical Specification Guide General Information The Easy To Use
More informationSECTION 07530CP EPDM MEMBRANE ROOFING
PART 1 GENERAL 1.1 SUMMARY SECTION 07530CP EPDM MEMBRANE ROOFING A. Section includes: 1. Adhered membrane roofing and flashing 2. Mechanically fastened roof insulation 3. Walkway pads 1.2 ARCHITECTURAL
More informationG U T T E R SY S T E M
GUTTER SYSTEM Why should I buy steel gutters? A guttering system is a roof accessory that is used to quickly discharge hundreds of liters of water during a downpour. The Struga steel guttering system is
More informationRAINWATER DISPOSAL SYSTEM PERFORMANCE STATEMENT
RAINWATER DISPOSAL SYSTEM PERFORMANCE STATEMENT 3.1.1 (a) Description Dimond rainwater disposal systems are available in a variety of materials together with the appropriate brackets and downpipes. Table
More information* Other widths available upon request. 24 Gauge Galvalume - Standard Surface. Other gauges and aluminium available upon request.
is a concealed fastener architectural standing seam roof panel. The panels are easily installed over decking, utilizing metal clips. panels are ideally suited for decorative mansard, fascia and roofs.
More informationInsulated Roof & Wall Panels. KS1000 RT Roof Tile
Insulated Roof & Wall Panels KS1000 RT Roof Tile KS1000 RT Roof Tile 2 Contents Introduction 4 Applications 6 Product Data 10 Construction Details 16 3 Introduction Kingspan Roof Tile offers traditional
More informationTATA BLUESCOPE STEEL LIMITED PRODUCT SPECIFICATION LANGUAGE FOR PRE ENGINEERED STEEL BUILDING (BUTLER BUILDING SYSTEM- WITH BR-II ROOF SYSTEM)
Section 1: General Product specification Language Item language Item No. Description EX. Works Supply Price Freight Erection Taxes & Duties Total Amount Item 1 Structural Members Supply of BUTLER Building
More informationUnitised Curtain Wall Beaded
Unitised Curtain Wall Beaded Glazed Frame Unitised Curtain Wall Reference Brand: Sapa Building System Elegance 72 GF GENERAL DESCRIPTION Unitised curtain wall system using glazing beads for glass retention.
More informationInsulated Roof Panel Systems
Insulated Panels United Kingdom Roof Systems RW 1 Insulated Roof Panel Systems RW / Topdek 2 Aldi, Goldthorpe, UK 3 Insulated Roof Panel Systems Introduction Kingspan s range of insulated roof panels systems
More informationSpecification. Project Name: Project reference: Written: by: Cathal Quinn Tel:
Project reference: 010050 Specification Written: by: Cathal Quinn Email: cathal@moymaterials.com Tel: 07788 934895 Project Name: Moy Materials Victoria House (4 th Floor) Victoria Road Chelmsford CM1 1JR
More informationBlast Resistant Enhanced Curtain Wall. Reference Brand: Sapa Building System Elegance 85PF GENERAL DESCRIPTION PERFORMANCE
Blast Resistant Enhanced Curtain Wall Blast Resistant Enhanced Curtain Wall Reference Brand: Sapa Building System Elegance 85PF GENERAL DESCRIPTION Grid based thermally insulated curtain wall system with
More informationROOF RENOVATION OVERSHEETING SYSTEM
CI SfB (4-) Nn2 ROOF RENOVATION OVERSHEETING SYSTEM BBA BRITISH BOARD OF AGREMENT CERTIFICATE NO. 87 / 1823/C Renovation Oversheeting System The system has been developed using the proven Onduline weathering
More informationOnduline covers the world. More than 100 countries across the globe
Onduline covers the world Onduline was founded in 1950 to manufacture and market the now famous corrugated roofing sheets. The outstanding growth and success of Onduline in the last 60 years has seen the
More informationViking Enviroclad Waterproofing Membrane. EC01 Enviroclad Drip Edge Specify from the above three options
*lum ngle 50x50x1.6mm min. with 20mm lum fixing bar to mechanically secure membrane Enviroclad Waterproofing Membrane Substrate to comply with current Roofspec Masterspec specification Substrate Checksheet
More informationTuscaloosa Police Station
Tuscaloosa Police Station 3801 Trevor S Phillips Ave Tuscaloosa, AL 35401 Core Cut: Spray Foam Roof- ½ thick +- Single Ply Membrane Tapered EPS Insulation 2-6 Metal Deck PART 1 GENERAL 1.1 SCOPE OF WORK
More information50948-RHN Putney. Friday, 15 December This document includes: Code Section Revision Dated
50948-RHN Putney Friday, 15 December 2017 This document includes: Code Section Revision Dated Z11 Purpose made metalwork 1 Table of Contents Title Z11 Purpose made metalwork Page 3 Z11 Purpose made metalwork
More informationSPECIFICATIONS Section Gable Walkway Covers
Part 1: General 1.1 Related Documents SPECIFICATIONS Section 107303 Gable Walkway Covers A. The requirements of Division 1 specifications shall apply to work specified in the section. 1.2 Engineering Design
More informationNew versatile and effective dry fix solutions for the roofline and above
Cavity trays Access panels Loft access doors Gas barrier and damp proofing accessories Under floor and through wall ventilation Cavity closers and stops Air leakage solutions New versatile and effective
More informationSECTION METAL FRAMED SKYLIGHT. A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system.
SECTION 08625 METAL FRAMED SKYLIGHT PART 1 GENERAL 1.01 SECTION INCLUDES: A. Engineering, preparation of fabrication drawings and structural calculations for the entire skylight system. B. Fabrication
More informationSECTION FABRICATED ENGINEERED STRUCTURES. A. Pre-engineered, shop-fabricated structural steel building with formed purlin framing.
PART 1 GENERAL 1.1 RELATED DOCUMENTS SECTION 13 34 00 FABRICATED ENGINEERED STRUCTURES A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1
More informationOutline NBS Specification. Protec System to PVC Single Ply (Waterproofing Only)
Outline NBS Specification Protec System to PVC Single Ply (Waterproofing Only) This document is a guide to assist in the production of tender documents only and is not project specific. A site survey is
More informationCurtain Wall Stick System (Capped)
Curtain Wall Stick System (Capped) Stick Construction Capped Curtain Wall Reference Brand: Sapa Building System Elegance 52 ST GENERAL DESCRIPTION Grid based thermally insulated curtain wall system with
More informationNBS SECTION J42 - SCOPE OF WORKS
NBS SECTION J42 - SCOPE OF WORKS Section J42 deals with the installation of the Bauder Single Ply System, comprising single layer coverings of polymeric sheets, including vapour control layers and insulation
More informationBrownbuilt BROWNBUILT PROFILED SHEETING AND ACCESSORIES SHEETING FINISH FOR BROWNBUILT ROOF SHEETING FIXING BROWNBUILT BROWNBUILT FLASHINGS SAFETY
Brownbuilt BROWNBUILT PROFILED SHEETING AND ACCESSORIES SHEETING The roof sheeting shall be interlocking concealed-fix Brownbuilt profile roll-formed in continuous lengths and cut to length by a pneumatic
More informationLIQUID APPLIED WATERPROOF ROOF COATINGS
J31 LIQUID APPLIED WATERPROOF ROOF COATINGS To be read with Preliminaries/General conditions. TYPE(S) OF COATING 120 WARM DECK ROOF COATING Substrate: Suitable structural roof deck (e.g. Plywood, OSB3,
More informationCONTENTS INTRODUCTION 2 FREEFLOW RAINWATER SYSTEMS Square Line Rainwater System 3-5. Half-Round Rainwater System 6-8. Ogee Rainwater System 9-11
RAINWATER SYSTEMS CONTENTS INTRODUCTION 2 FREEFLOW RAINWATER SYSTEMS 3-3 Square Line Rainwater System 3-5 Half-Round Rainwater System -8 Ogee Rainwater System 9- Deep Rainwater System 2-3 INSTALLATION
More informationTechnical specifications Prefab Steel Canopy
Canopy Structure: Technical specifications Prefab Steel Canopy Design fabrication and installation of pre-engineered / pre- fabricated steel canopy as per the following specification: The canopy steel
More informationCI/Sfb. (47) Nh March Aluminium & Steel Profiled Cladding Systems RIGIDAL PROFILEDCLADDING
CI/Sfb (47) Nh March 2006 Aluminium & Profiled Cladding Systems RIGIDAL PROFILEDCLADDING The Rigidal Range of Profiled Cladding Rigidal Industries manufacture an extensive range of aluminium and steel
More informationPRE-ENGINEERED METAL BUILDING SYSTEM
PRE-ENGINEERED METAL BUILDING SYSTEM PART 1 GENERAL 1.1 SUMMARY A. The building shall include all primary and secondary structural framing members, connection bolts, roof and wall covering, flashing, gutter,
More informationSPECIFICATIONS Section Cantilevered Walkway Cover
Part 1: General 1.1 Related Documents SPECIFICATIONS Section 107301 Cantilevered Walkway Cover A. The requirements of Division 1 specifications shall apply to work specified in the section. 1.2 Engineering
More informationCERTIFICATE OF APPROVAL No CF 5073 LEMINAR AIR CONDITIONING INDUSTRIES L.L.C.
CERTIFICATE OF APPROVAL No CF 5073 This is to certify that, in accordance with TS00 General Requirements for Certification of Fire Protection Products The undermentioned products of PO Box 33539, Dubai,
More informationBRANZ Appraisal Certificate # 461 (2010) Internal wet areas.
SPECIFICATION FOR PROTECTO WRAP AFM-WM FOR INTERNAL WET AREAS BRANZ Appraisal Certificate # 461 (2010) Internal wet areas AFM/WM INTERNAL 0104 Page 1 AFM-WM INTERNAL SPECIFICATION PRODUCT DESCRIPTION Anti
More informationWall Linings. As well as complete dry lining solutions we also provide fast-drying parge coat to ensure airtightness,
Wall Linings Our versatile range of wall lining systems makes it easy to produce a high-quality, high-performance finished wall regardless of the background. Whether your priority is acoustic control,
More informationAddendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE
SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,
More informationPolymeric membrane for roof waterproofing
Roofing Product Data Sheet Edition 06.2012 Identification no. 02 09 05 05 100 0 180000 Version no. 01 Sikaplan -SGK 1.8 (Trocal SGK 1.8 mm) Polymeric membrane for roof waterproofing Construction Product
More informationGood ideas. for your new building. BUILDINGS. Ideas become reality
Good ideas for your new building. BUILDINGS Your creativity. Our experience. The design of a modern building is born out of a need to fulfill particular requirements economically together with a certain
More informationCONTENTS INTRODUCTION 2 FREEFLOW RAINWATER SYSTEMS Square Line Rainwater System 3-5. Half-Round Rainwater System 6-8. Ogee Rainwater System 9-11
RAINWATER SYSTEMS CONTENTS INTRODUCTION 2 FREEFLOW RAINWATER SYSTEMS 3-3 Square Line Rainwater System 3-5 Half-Round Rainwater System -8 Ogee Rainwater System 9- Deep Rainwater System 2-3 INSTALLATION
More informationStandard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces.
Standard specification for the application of Danosa Two-Layer waterproof roofing membrane to plywood & concrete surfaces. BRANZ Appraised No. 678 Ref: P3200 Rev 1 February 2016 Page 1 of 5 1.0 PREAMBLE:
More informationPipe Flashing Systems
Uniclass L52944:P71 EPIC E375:X71 CI/SfB (47) In6 Pipe Flashing Systems Pipe Flashing Systems The widest range of pipe flashings available to the market Contents Page Front Cover 1 Contents 2 Introduction
More information60 years. of progressive development
Dencroft has been providing a wide range of sectional buildings for over 60 years, making us one of the most experienced designers and manufacturers of quality garages in the UK. Innovation has played
More informationGuidance document January 2015
Guidance document January 2015 A GUIDE TO SITE INSTALLATION OF INSULATED ROOF PANELS This bulletin introduces the reader to key issues that need to be addressed for the installation of an insulated roof
More informationConstruction. Sarnafil G Felt. Polymeric membrane for roof waterproofing. Product Description
Roofing Product Data Sheet Edition 03.2012 Identification no: 02 09 05 05 215 0 120000/1 Version no. 01 Sarnafil G 410-12 Felt Polymeric membrane for roof waterproofing Construction Product Description
More informationProduction Technology
Introduction There has been a need to introduce new QUALITY PRODUCTS in the construction & Cold Storage industry in the region for many years. EIP was set up at Dubai Investment Park in the UAE to address
More informationCYCLONE Steel gutters and rainwater system. A steel rainwater system designed to protect in the toughest weather
STEEL AGAINST THE STORM UNICLASS L7314/P414 CI/Sfb (52.5) AUGUST 2015 CYCLONE Steel gutters and rainwater system A steel rainwater system designed to protect in the toughest weather Saint-Gobain PAM UK
More informationPAGE 415. Part 9. External works. 9.1 Garages. 9.2 Drives, paths and landscaping
PAGE 415 Part 9 External works 9.2 Drives, paths and landscaping Part 9 External works Chapter CONTENTS SCOPE Clause DESIGN Design standards D1 1 Statutory requirements D2 1 Garage foundations D3 1 Garage
More information