Fire and Rescue Space Needs Analysis
|
|
- Karin Johnson
- 5 years ago
- Views:
Transcription
1 T F A D R Fire and Rescue Space Needs Analysis 13 April 2017
2 INTRODUCTION The following pages contain multiple tables that describe each department and space in detail. The tables are broken into the major departments as listed on the Fire and Rescue s building summary table below. The following terms are the basis for understanding building programs: Net Assignable Area (NASF): This is the usable space for each item shown in the space tables. This number serves as the basis for pure program space. Net Usable Area (NUSF): Total Gross Area (GSF): This is the total usable area with a grossing factor that accounts for local circulation within the suite not listed in the space tables. This metric converts the Net Assignable Area into the total space required to connect spaces into a suite. In this building type, there is only one department and this factor is instead accounted for in the Total Gross Area factor, meaning NUSF is the same as NASF. This is the total usable area with a 30% grossing factor that accounts for all other building requirements not listed in the space tables. This metric scales the Net Usable Area into the total space required to connect department suites into a functional building. This factor is divided into three main categories; building service, horizontal and vertical circulation, and mechanical and electrical space. Planning with this metric implies a 70% efficiency of space utilization. Spaces shaded in blue indicate future positions that account for growth TABLE OF CONTENTS Projection Summary 3 Building Summary 4 Administration & Training 5 Residential & Living 7 Apparatus & Support 8 2
3 Projection Summary The table below represents a summary of the forecast matrix applied to the fire department as a method for developing growth projections over the next 20 years. The historic staff data over the previous 10 years was not available, so it has been replaced with the staff proposed growth. The fire department utilizes part time positions to staff the majority of the work force, and do not anticipate changing that model in the near future. The 60 positions listed as current part time actually staff only 4 positions, thus the growth to 90 implies the addition of 2 additional positions in this model. The full time growth is implemented by converting several part time employees to full time positions. The forecast model selected for space planing guidelines is the staff projection. Fire Department Annual Change Forecast Data 2016-Current Planning Number % Curernt Full-Time Staff (includes Fire Chief) % Curernt Part-Time Staff % Forecast Model Value : Actual 10 yr Number Increase (Not Provided) : Actual 10 yr Percentage Increase (Not Provided) 0.00% : OSBM 5 yr Percentage Increase 2.66% : U.S. Census 5 yr Percentage Increase 1.94% : U.S. Census 10 yr Percentage Increase 4.70% : Solid Waste 10 yr Percentage Increase 3.43% : Commercial Building Permits 1 yr Percentage Increase % : Residential Building Permits 1 yr Percentage Increase 7.56% : Calls for Service 1 yr Percentage Increase 3.19% Staff Projections Average (Items 3-6 and 8-10) Recommended Model: Staff Projection
4 Building Summary The table below represents a summary of the divisions witin the fire department. The current existing area represents the space currently used by the department, and is included for comparison purposes. The in-house estimated area is a reference to the programming completed by town staff, and is also included for comparison only. The current projected area conveys the surveyed space needs for the present, and the future projected area includes growth spaces that position the building for use across the next 20 years. Current Existing In-House Estimated Curent Needed Modeled Department Area (NUSF) Area (NUSF) Area (NUSF) Area (NUSF) Fire and Rescue Administration and Training 150-1,328 1,658 Residential and Living 1,007-3,483 3,483 Apparatus and Support 4,155-6,488 6,488 Total Net Usable Square Feet (NUSF) 5,312-11,299 11,629 30% Core Service (SF) (excludes apparatus bay) - - 1,950 2,049 TOTAL FIRE STATION 1 (GSF) 6,000 15,546 13,249 13,678 *additional 1,716 SF in shared spaces in town hall for training and fitness, totaling 15,394 SF of area for fire use 4
5 Admin and Training Creech & Associates conducted an interview with the Fire Chief and staff. The discussions were focused around current working environments and potential space needs both current and future. Responses from the previously completed surveys were used as the basis for discussion. The following pertinent items regarding administration and training spaces were discussed: 26 January :30 11:30 Fire Department Bo Fitzgerald 1. Training for staff is an ongoing need and requires space. Multiple departments need space for different types of training. The ideal size for DFD would be 30 with seminar style seating and adequate AV for presentations and a white board. 2. Would prefer anchor points on trusses in the apparatus bay for harness training. 3. The training room could also serve as the Emergency Operations Center (EOC) for the Town and possibly a community room also. Additional lighting levels and infrastructure in floor boxes including power and data is required to facilitate the EOC function. 4. Dispatch is handled by the County and not required at Station The Chief s office would ideally have space for meetings with 4 people within the office and the ability to project computer images on a flat screen for group meetings. 6. Prefer to plan for 3 Deputy Chiefs with individual private offices in the future when the staff model changes to full time. 7. A report writing /computer station is required for firefighter use and would ideally be located in a separate space. 8. The captains can share a bullpen office with room for 2 workstations. 9. There is not much office space provided at Station A conference room for 8 is preferred to host management meetings in private. 11. Prefer a separate workroom with cabinet space for storage and counter space for printers and charging station. 12. A public lobby with restrooms is required that is separated from the rest of the station. A watch room is not required. Separation between the lobby and dayroom is preferred so firefighters can be given a warning before bring visitors back. 5
6 Admin and Training Personnel Area Subtotal Description SqFt Quantity Staff NSF Remarks Chief meeting space for 4, flatscreen with data port Captain bullpen with 2 workstations, 2 staff per shift Engineer per company per shift, 2 total per shift, beds accounted for in residential & living Firefighter per company per shift, 2 total per shift, beds accounted for in residential & living Deputy Chief future positions, private office for each deputy chief future positions, beds accounted for in residential & Firefighter living, 1 per company Subtotal Net Square Feet (NSF) 608 Current Staff 67 Future Staff 33 Total Staff 100 Sqft/person 6 Personnel Space Subtotal 608 Support Area/ Equip. Area Subtotal Description SqFt Quantity Staff NSF Remarks Entry Vestibule Lobby seating for 4 visitors, secured from facility Toilet public access adjacent to lobby Report Writing private area with 2 workstations Conference Room table seating for 8 Work Room IT Room local server and communications closet, dedicated cooling Training Room seminar seating for 30, AV for presentations, white board, also serves as EOC, located in police Furniture/ Equipment Storage adjacent to training room, contains mats, FATS, projection screen, etc. Support Space Subtotal 1,050 TOTAL NET USABLE AREA REQ'D. (NUSF) 1,658 6
7 Residential and Living Creech & Associates conducted an interview with the Fire Chief and staff. The discussions were focused around current working environments and potential space needs both current and future. Responses from the previously completed surveys were used as the basis for discussion. The following pertinent items regarding residential and living spaces were discussed: 26 January :30 11:30 Fire Department Bo Fitzgerald 1. Individual sleeping quarters are not preferred. Staff prefers the open cubicle sleeping quarters with private rooms for the Chief and each Captain (2) for a total of 3. The largest number on shift in the future in the open sleeping quarters is projected at 9 (2 companies of 4 plus a Battalion Chief). Linen lockers should be provided in the sleeping quarters for all part time staff. 2. Desire a fitness area with space for 2 crews and a combination of aerobic, nautilus and free weight equipment. Should have some open floor area for cross-fit activities. 3. Locker room should have full height 18 W x 24 D units for staff. The Chief and Captains lockers will be in the private sleeping quarters. Male locker room should have 20 lockers, 2 urinals, 3 water closets, and a pedastal shower with 4-6 heads. Female locker room should have 5 lockers, 2 water closets, and 1 private shower. 4. The kitchen should have commercial grade appliances, stainless steel countertops, a single refrigerator with the potential to expand to 3, 1 large pantry, and access to an outdoor patio with a grill. The dining area should share this space with seating for The day room should have soft but durable seating for 9 and should be separated from the kitchen and dining area. It would be great if this area could flex to seat up to 16 for staff working holidays that need space to share time with their family. 6. Need space for a janitor s closet with a mop sink and supply storage. 7. Need space for a server room or communications closet. 8. Sprinkler riser room is preferred to be located on the apparatus side of the station with hose bibs on the system if possible. 9. Storage in general is lacking and should be adequately sized in a future station. Support Area/ Equip. Area Subtotal Description SqFt Quantity NSF Remarks Kitchen refrigerator, large pantry, contiguous with dining room Dining Room seating for 10, flex to seat 16, contiguous with kitchen Day Room lounge seating for 10, flex to seat 16, separate from kitchen free weights and aerobic equipment, located in police department, Fitness Room shared fitness room with town hall and police Laundry washer/dryer and folding area Male Locker lockers Male Shower head pedestal shower Male Toilet wc, 1 urinal Female Locker lockers Female Shower private shower Female Toilet wc Chief Sleep Room bed with wardrobe and desk Captain Sleep Room bed with wardrobe Sleep Room 1, ,350 open cubicle quarters for 10 with linen lockers for all staff General Storage TOTAL NET USABLE AREA REQ'D. (NUSF) 3,483 7
8 Apparatus and Support Creech & Associates conducted an interview with the Fire Chief and staff. The discussions were focused around current working environments and potential space needs both current and future. Responses from the previously completed surveys were used as the basis for discussion. The following pertinent items regarding apparatus and support spaces were discussed: 26 January :30 11:30 Fire Department Bo Fitzgerald 1. The department is currently a 2 company service with 3 staff per company. The department has moved from a volunteer base to a paid staff model, with all staff currently serving part time. There are approximately 60 part time staff working 12 hour shifts currently filling these positions. Most of the staff are also full time career firefighters in Charlotte- Mecklenburg. 2. The existing station has 6 apparatus bays with one recently converted to sleeping quarters, bringing the current total to 5 bays. Two of the bays are deeper to facilitate ladder apparatus. The department has 3 engines, 1 ladder, a marine and an RV unit, in addition to the Battalion Chief vehicle and an antique engine currently held in storage. Two of these vehicles, including possibly the ladder, will move to Station 2. For future growth the ladder truck may return to Station 1 as an added company. In addition to the footprint of Davidson the department serves Lake Davidson and Lake Cornelius. 3. The bay configuration does not allow for pull through access which is preferred by the department. 4. The ceiling height in the apparatus bays is adequate for storage but not for tilt-forward cab access required for maintenance. Those functions are currently conducted on the apron or by mechanics off site. 5. Diesel exhaust control is a hose-based direct-source capture system on rails. 6. Station has traditional roll-up doors but would prefer bi-fold doors if feasible within the budget. 7. Turnout gear lockers are kept in the bay and would ideally be located in a separate space shared by everyone. 8. Turnout washers will be located at Station 2 and not needed at Station Tank filler is a cascade system that will remain at Station 1. It is currently located in the bay and should be kept in a separate room. 10. Hose storage is currently located in the bay and should be kept in a separate room with adequate racks. 11. All tools are currently located in the bay and should be kept in a separate tool room with a workbench for repairs, storage for spare parts, and flammable liquid storage. The department performs many in-house repairs to station equipment and performs building maintenance. 12. Hazmat responses are by Mecklenburg County so no hazmat storage of any kind is required. 13. Staff is EMS trained and requires separate space for supply storage. 14. The ideal apparatus bay depth is 80 which allows for double stacking of engines if needed. Radiant heat in the ceiling is preferred over area heaters, along with large industrial fans to circulate air. The apparatus continue to get longer and taller as newer models are introduced. 15. Every bay should have a center trench drain. 16. The station is geographically located in an appropriate area for response range, but could also move to the Griffith Street site near the railroad nearby and maintain service. 17. There is no fueling station or tank at Station 1, nor are there plans for one in the future. Current fueling is at area stations but may eventually move to the Public Works facility. 8
9 Apparatus and Support Support Area/ Equip. Area Subtotal Description SqFt Quantity NSF Remarks Vehicle Bay 1, ,800 80'x20' each, 6 vehicles double stacked, pull through access, center trench drain each bay, radiant heat in ceiling, large ceiling fans PPE Lockers "x24" compartments with boot and helmet shelves Decontamination Room basin sink, eyewash/shower, floor drain SCBA Maintenance and Storage existing cascade system and bottle storage racks Hose Storage mobile storage racks and parts storage Tool Shop tool boxes, workbench, parts storage, flammable liquid storage Radio Charging Area corridor alcove EMS Storage adjacent to bay Janitor's Closet mop sink, shelf storage Sprinkler Room locate near bays, hose bibs IT Room local server and communications closet, dedicated cooling General Storage attic stock USABLE AREA REQUIRED (NUSF) 6,488 9
Custer County Sheriff s Office and Detention Center Space Needs Justice Center Committee needs assessment group
ATTACHMENT B Custer County Sheriff s Office and Detention Center Space Needs Justice Center Committee needs assessment group Square Footages are an estimate and may need to be modified depending on building
More information2017 City of Ortonville Northridge Study
2017 City of Ortonville Northridge Study HASSLEN CONSTRUCTION AND RICE STROMGREN ARCHITECTS / STUDY / Page 1 CONTENTS Existing City Facilities Executive Summary 3 Location of Facilities 4 City Hall/Community
More informationSpatial Needs Assessment
Spatial Needs Assessment for the 430 Main Street Agawam, MA 01001-1827 Tel. (413) 786-9600 www.reinhardtassoc.com December 9, 2013 Reinhardt Associates, Inc. SUMMARY OF SPACE NEEDS ADMINISTRATION General
More informationNC State University Design and Construction Guidelines Division 00 Planning & Design Space Planning
1.0 Purpose A. These guidelines provide requirements for the Designer and Contractor to follow related to space planning. 2.0 General Requirements A. Single Occupant Toilet Room Each new or renovated building
More informationRequest For Proposal (RFP) New Fire Station Design/Construction
Request For Proposal (RFP) New Fire Station Design/Construction Submit Complete Package To: Northern Monroe Fire Territory Attn: Joel Bomgardner, Chief 5081 N. Old State Road 37 Bloomington, IN 47408 812-339-1115
More informationFacilities Management Service and Support Function Needs
Facilities Management Service and Support Function Needs In addition to mechanical and electrical equipment rooms, Facilities Management requires the following minimum amount of space in each building
More informationForm 919, Facility Planning Data
235 Facility Planning Concept Original: Revised: 237 Space Requirements U. S. Postal Service FACILITY PLANNING CONCEPT Post Office, State and ZIP+4 Code Postal Unit County DATE Original: Revised: A1. GENERAL
More informationGerald Desmond Bridge Replacement
Item # Room # icip. # of Occupants 101 12 Conference / Crew Room 1 400 400 Supervisor Offices Conference and secondary training room for up to 12 people Flooring: VCT Electrical Type: rmal (utility power)
More informationGEORGIA DEPARTMENT OF CORRECTIONS Standard Operating Procedures
Policy Number: 410.04 Effective Date: 10/30/2017 Page Number: 1 of 13 I. Introduction and Summary: This policy provides guidance for space planning for new construction, renovations, or additions for detention
More informationChapter 11. Dwelling Units and Sleeping Units
1101 General Chapter 11. Dwelling Units and Sleeping Units 1101.1 Scoping. Dwelling units and sleeping units required by the scoping provisions adopted by the administrative authority to be Accessible
More informationThis section applies to service areas and loading docks for new construction and major renovations.
Basis of Design This section applies to service areas and loading docks for new construction and major renovations. Programming Minimum requirements: Defined custodial area, service area and loading docks
More information3. 21st Century Learning A. Districtwide Flexible Learning $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades $300,000 C. Tilden Entrance Upgrades $50,000 D. Door and Glass Improvements $500,000 E. Alert Systems $800,000
More informationMinimum Requirements for Residential Occupancy Codes and FAQs
City of McMinnville, Planning & Zoning Department 101 East Main, McMinnville, TN 37110 (931) 473-1204 Fax (931) 473-6231 Email: nming@mcminnvilletenn.com Minimum Requirements for Residential Occupancy
More information5. ESTIMATING SPACE REQUIREMENTS
5. ESTIMATING SPACE REQUIREMENTS There are two methods for estimating space requirements for your library building: Standards approach - employs a standard square footage based on service area population.
More informationCheshire, CT. By: A.M. Napolitano, LLC. Project Manager: Carolyne Sakonchick Ext. 323
Cheshire, CT By: A.M. Napolitano, LLC Project Manager: Carolyne Sakonchick 203-272-1821 Ext. 323 Country Club Acres, Two beautiful homes, to be built on one acre lots, with city water/sewer. Meet the builders
More informationUNIFIED FACILITIES CRITERIA (UFC) FACILITY PLANNING FOR NAVY AND MARINE CORPS SHORE INSTALLATIONS APPENDIX F AUSTERE FACILITIES (NAVY)
UNIFIED FACILITIES CRITERIA (UFC) FACILITY PLANNING FOR NAVY AND MARINE CORPS SHORE INSTALLATIONS APPENDIX F AUSTERE FACILITIES (NAVY) DISTRIBUTION: FOR OFFICIAL USE ONLY UNIFIED FACILITIES CRITERIA PROGRAM
More informationUNIFIED FACILITIES CRITERIA (UFC) FACILITY PLANNING FOR NAVY AND MARINE CORPS SHORE INSTALLATIONS APPENDIX F AUSTERE FACILITIES (NAVY)
UNIFIED FACILITIES CRITERIA (UFC) FACILITY PLANNING FOR NAVY AND MARINE CORPS SHORE INSTALLATIONS APPENDIX F AUSTERE FACILITIES (NAVY) DISTRIBUTION: FOR OFFICIAL USE ONLY UNIFIED FACILITIES CRITERIA PROGRAM
More informationJV PROPERTIES, LLC (AQUA GLASS/MASCO) 320 INDUSTRIAL ROAD ADAMSVILLE, MCNAIRY COUNTY, TN Approximately 511,807 square feet
(AQUA GLASS/MASCO) 320 INDUSTRIAL ROAD ADAMSVILLE, MCNAIRY COUNTY, TN 38310 SIZE: GROUND: NUMBER OF BUILDINGS: NUMBER OF FLOORS: Approximately 511,807 square feet Approximately 59 acres, mostly level with
More informationSingamas Container Holdings
Singamas Corporate Highlights One of the world s leading Container Manufacturers State of the Art manufacturing facilities More than 10 factories in China, with a capacity of over 1 million TEUs a year
More informationSpace Program & Concept Design
Rossmoor&Del&Valle&Aqua/cs,&Sports&&&Fitness&Complex& Space Program & Concept Design Presentation to FCAC & AAC July 8, 2015 Programming Allocation of available square footage Programming Considerations:
More informationCITY OF NOVI. Police Department
CITY OF NOVI Police Department Indoor Gun Range and Training Facility Assessment Analysis with Master Plan for Novi Police Department at Community Build Out Field Services Complex Facility Needs Master
More informationTOLEDO FIRE STATION #6
Location Toledo, Ohio v Services Provided Architecture, Landscape Architecture, Site, Structural, Mechanical, and Electrical Engineering, Grant Administration, and Construction Administration $4 million
More informationUniversity of North Carolina at Charlotte Design and Construction Manual Section 2, Division 11 Equipment SECTION 2 DIVISION 11 EQUIPMENT
SECTION 2 DIVISION 11 EQUIPMENT DIVISION 11 - EQUIPMENT Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s contract documents. GENERAL
More informationSECTION 2 DIVISION 11 EQUIPMENT
SECTION 2 DIVISION 11 EQUIPMENT DIVISION 11 - EQUIPMENT Note: This is a guide for Designers only. Contents shall not be used in lieu of specifications as part of the Designer s contract documents. GENERAL
More informationBrad Richmond & Jeremy Knoll
Model Home Open Daily WWW.HALLMARKHOMESCDA.COM All information is deemed reliable is not guaranteed and should be verified by buyer or buyers agent. PRICE LIST SINGLE LEVEL Marlin 1042 SQ FT $119,900 Ruby
More informationWAre they admired because they are
By Paul Erickson Contain the Design: Contaminants How architects and fire departments can help reduce cancer among firefighters hy is it that emergency service professionals are so respected by the public
More informationCivil District Court Parish of New Orleans. Image Courtesy of EDR MA. Renovation & Utilization Feasibility
Civil District Court Parish of New Orleans Image Courtesy of EDR MA Renovation & Utilization Feasibility Challenges with Courthouse Design Courthouse Space Standards and Requirements Charity Hospital Building
More informationApplying the Building Code During Design
Applying the Building Code During Design A Step-By-Step Process AIA Learning Units The Salt Lake City CSI Chapter is a Registered Provider with The American Institute of Architects Continuing Education
More informationADDENDUM NO. 2 CITY OF FORT MORGAN BUILDING MAINTENANCE DEPARTMENT CITY JANITORIAL SERVICES. November 21, 2017
ADDENDUM NO. 2 CITY OF FORT MORGAN BUILDING MAINTENANCE DEPARTMENT CITY JANITORIAL SERVICES November 21, 2017 To all prospective bidders: This Addendum is part of the Bid Documents and modifies the original
More informationAvalon Guest House 7 Upper Rock Gardens Brighton BN2 1QE EIGHT BEDROOM GUEST HOUSE IN POPULAR TRADING POSITION 645,000 FREEHOLD
Avalon Guest House 7 Upper Rock Gardens Brighton BN2 1QE EIGHT BEDROOM GUEST HOUSE IN POPULAR TRADING POSITION 645,000 FREEHOLD 2 Occupying a popular and convenient trading position between St James s
More informationRALEIGH - SINGLE FAMILY HOME INCLUDED FEATURES
RALEIGH - SINGLE FAMILY HOME INCLUDED FEATURES Interior Features Hardwood Flooring in Foyer, Butler s Pantry, Family Room and Kitchen Wall-to-Wall Carpeting in Bedrooms Upgraded Padding Ceramic Flooring
More informationALBANY. hsr 900 Klamath Avenue Klamath Falls, OR T: (541) F: (541) CITY OF FIRE ASSESSMENT. PROGRAMMING and NEEDS
CITY OF ALBANY FIRE DEPARTMENT, STATION 11 FACILITIES ASSESSMENT AND PRELIMINARY DESIGN PHASE 1 PART A: DEPARTMENT PROGRAMMING AND NEEDS ASSESSMENT CITY OF ALBANY FIRE PROGRAMMING and NEEDS ASSESSMENT
More informationGARLAND HEALTH DEPARTMENT
GARLAND HEALTH DEPARTMENT Construction and Equipment Standards for Food Service Establishments CLASS 2 FOOD SERVICE ESTABLISHMENTS 1720 Commerce St. Garland, TX 75040 Phone: (972) 205-3460 Fax: (972) 205-3505
More information35.0 Sterile Supply Unit (SSU)
35.0 Sterile Supply Unit (SSU) 35.1 Introduction 35.1.1 General A Hospital must provide adequate facilities for cleaning, sterilisation and storage of equipment and instruments to ensure the care and safety
More informationTownhouse 33. Central Park on Copeland Townhouses
22/11/2018 12:22:56 PM Townhouse 33 Wardobe joinery shown provided. Other furniture on plan NOT INCLUDED. Areas shown are approximate, subject to final survey. Refer to Landscape Architect's drawing for
More informationPhone: (+974) / Fax: (+974)
Company Profile Who we are We ARE Sky Creative! With the combined experience of over 35 years of trading and contracting experience, our team has established an enviable reputation as a global and regional
More informationA 16' x 28' Cottage with two lofts and a bedroom addition. Plans can be modified for simple or expanded layouts.
A 16' x 28' Cottage with two lofts and a bedroom addition. Plans can be modified for simple or expanded layouts. Here is a very livable small house. The main house section is 16' wide by 28' long with
More informationC ID-2.00 E ID-2.1 ISSUE DATE: 12/30/2016 SCALE: 1/2" = 1'-0" BUILT IN BENCH "NOOK" SEATING WITH STORAGE BELOW. SEE ELEVATIONS FOR DETAILS.
CD W BUILT IN BENCH "NOOK" SEATING WITH STORAGE BELOW. SEE ELEVATIONS FOR DETAILS. B ID-2.00 A ID-2.00 ST-01 BUILT IN SHELVING SEE ELEVATIONS FOR DETAILS C ID-2.00 [ST-01] CAESARSTONE COUNTERTOP, COLOR
More information4. CIRCULATION SERVICES 6,213 SF
4. CIRCULATION SERVICES 6,213 SF Subcomponents: a. Circulation Desk - Reserve Material b. Self Service c. Sorting Areas d. Interior Book Drop e. OPAC Terminals f. Circulation Workroom g. Circulation Services
More informationSPACE TYPES & REQUIREMENTS
28 October 20 Janitorial Administration E M H 2 3 5 6 7 8 9 0 2 Functional Area Descriptions Janitorial Administration This space provides office space for the janitorial staff to perform administrative
More informationC ID-2.00 ISSUE DATE: SCALE: 1/2" = 1'-0" BUILT IN BENCH "NOOK" SEATING WITH STORAGE BELOW. SEE ELEVATIONS FOR DETAILS.
CD W BUILT IN BENCH "NOOK" SEATING WITH STORAGE BELOW. SEE ELEVATIONS FOR DETAILS. B ID-2.00 A ID-2.00 ST-01 BUILT IN SHELVING SEE ELEVATIONS FOR DETAILS C ID-2.00 [ST-01] CAESARSTONE COUNTERTOP, COLOR
More informationTownhouse 3. Central Park on Copeland Townhouses
22/11/2018 12:22:54 PM Townhouse 3 Wardobe joinery shown provided. Other furniture on plan NOT INCLUDED. Areas shown are approximate, subject to final survey. Refer to Landscape Architect's drawing for
More informationHelms Builders, Inc.
Helms Builders, Inc. President 9669 Fred Rd. Steve Helms Stanfield NC. 28163 Locust Town Center Lot #31, 261 Harrison Ln. Locust NC. Scope of Construction & General Conditions: Building Contract contingent
More informationResidential Outline Specifications
Residential Outline Specifications September 2014 1. General a. Site i. Direct elevator access from parkade to residential floors ii. Separate commercial elevator access from parkade to 10th Street NW
More informationTicking Form - Lodge - 1 -
Swaziland Tourism Authority Registration of Accommodation Establishments Ticking Form Lodge Name of Establishment: Name of Contact / Manager: Reference number: 1 Guest rooms Single/Double/Family 1.2 Size
More informationbuilding audit & site analysis
bowen island firehall bowen island municipality & bowen island fire department bowen island, b.c. building audit & site analysis issued june 30, 2008 johnston davidson architecture + planning inc. 200-1300
More informationOwen County Jail Needs Assessment Summary FEBRUARY 23, 2016
Owen County Jail Needs Assessment Summary FEBRUARY 23, 2016 Introduction Purpose of the Study Approach and Methodology Strategic Planning/Facility Evaluation Interview Summary Analytics Summary Existing
More informationPRESENTATION TO THE FARMINGTON CITY COUNCIL FOR THE PROPOSED FARMINGTON CIVIC CENTER EXPANSION SEPTEMBER 20, 2016
PRESENTATION TO THE FARMINGTON CITY COUNCIL FOR THE PROPOSED FARMINGTON CIVIC CENTER EXPANSION SEPTEMBER 20, 2016 WORK LEGEND OVERALL WORK TO BOTH BUILDINGS 1 2 3 4 Existing corridors will receive new
More informationAPPENDIX A CHECK-LIST FOR SCIENCE SAFETY REQUIREMENTS. (Required Minimums for Approval by the N.C. Board of Education)
P APPENDIX A CHECK-LIST FOR SCIENCE SAFETY REQUIREMENTS (Required Minimums for Approval by the N.C. Board of Education) Revised July 11, 2013 Page 1 CHECKLIST FOR SCIENCE SAFETY REQUIREMENTS Middle and
More informationPossible Format for the layout of a DAC application. - Part M
Possible Format for the layout of a DAC application - Part M 2010 - This document should only be used with the clear understanding of the following: a. The aim of this document is to illustrate one possible
More informationAPPENDIX A DEFINITIONS OF BUILDING AREAS
A. GENERAL REQUIREMENTS DEFINITIONS OF BUILDING AREAS 1. The Project Architect/Engineer shall submit an estimate with the Schematic Design Phase submission, and shall submit calculations with the Design
More informationStudent Experience. Student Study Spaces
Student Experience The new SJ Quinney College of Law building offers a number of amenities for students, as well as a number of new sustainable features that you should know about. Here are some of the
More informationat Venetian Bay New Smyrna Beach, FL CARL VASILE
at Venetian Bay New Smyrna Beach, FL CARL VASILE 386.852.3948 General Features 9 4 Steel Reinforced Concrete Block Walls Loxon Exterior Paint 10-year Structural Warranty; insured by a third party Architectural
More informationTechnical Services Talk
Technical Services Talk October 2016 Inside This Issue 1 Newsletter Overview 2 Fire Dispatch/Comm 3 Fleet 4 Facilities 5 Line Shop 6 Warehouse Newsletter Overview This is the second of our Technical Services
More informationHome Features. ELECTRICAL COMPONENTS Copper wire electrical system Minimum 150-amp electrical panel with circuit breakers
Home Features STRUCTURAL ELEMENTS Steel reinforced 3000 psi monolithic foundation Concrete masonry block exterior walls Professionally engineered roof and floor trusses with hurricane structural hardware
More informationMarch 2018 Progress. Work Completed, Week Ending 3/23/18:
March 2018 Progress Work Completed, Week Ending 3/23/18: Continued draft curtains and liner panels. Continued running power to hangar doors. Continued installation of bath accessories in the gang bathrooms.
More informationWork Write Up / Specification of Repairs HUD DIVISION 1. MASONRY HUD DIVISION 2. SIDING. Toll Free
/ / Paperport 2000 official estimating report Work Write Up / Specification of Repairs Toll Free 1-877-932-7177 Clients Name. GREAT CLIENT Property Address. NUMBER ONE GOOD ROAD METRO, VA 20000 Primary
More informationPlan Check No. f) Where only half baths are provided, at least one half bath. g) Carports, garages or parking spaces. (1111B.4.2.
Plan Check No. A. GROUP R OCCUPANCIES 1. Hotels, motels, inns, dormitories, resorts, homeless shelters, halfway houses, transient group homes, and similar places of transient lodging shall provide access
More informationTownes at Shady Grove Metro from the low $600s Rockville, Maryland
Townes at Shady Grove Metro from the low $600s Rockville, Maryland Set in one of Montgomery County s most appealing communities, offering 36 townhomes with 2,460 square feet, in a transit-friendly neighborhood.
More informationJ e w e l S e r i e s. Marquis Elevation A. Elevation B
Marquis Elevation A Elevation B Marquis 4 Bedrooms 2 1/2 Baths 1 Car Garage Living Area: 1885 Square Feet Second Floor First Floor Plans, elevations and/or renderings are artists conception, not to scale
More information185 DISCOVERY DRIVE COLMAR, HATFIELD TOWNSHIP MONTGOMERY COUNTY, PA. 2.9+/- acres. Approximately 38,000 square feet
Ten Penn Center 1801 Market Street, Suite 550 Philadelphia, PA 19103 www.colliers.com/philadelphia MAIN +1 215 925 4600 FAX +1 215 925 1040 Submitted By 185 DISCOVERY DRIVE COLMAR, HATFIELD TOWNSHIP MONTGOMERY
More informationBuilding Area Definitions Authored by: The Office of Space Management and Analysis
Building Area Definitions Authored by: The Office of Space Management and Analysis Adopted from: Postsecondary Education Facilities Inventory and Classification Manual (FICM): 2006 Edition November 30,
More informationValues That Matter PLAN CERTIFICATION WORKSHEET
Values That Matter PLAN CERTIFICATION WORKSHEET Builder Name: Main Floor: sq. ft. Plan Name/Number: Upper Floor: sq. ft. Contact Person: Total: sq. ft. Phone: Email: For any item labeled as (option), you
More informationNew Homes Starting at $124,900
Chicora New Homes Starting at $124,900 New Homes - The Best Locations - The Right Price Sales & Marketing By: Keller Williams New Homes Division www.newhomesatmyrtlebeach.com Chicora C & R Builders, with
More informationWater s Edge Parkview Collection Jill Delmastro
Water s Edge Parkview Collection Jill Delmastro 980.277.1322 J.delmastro@mybrooklinehome.com Www.mybrooklinehome.com Included Features Parkview Collection @ Waters Edge ENERGY EFFICIENT FEATURES
More informationFeatures & Amenities
Features & Amenities COMMUNITY FEATURES EXTERIOR FINISHES All New community featuring town homes with a Maintenance-free lifestyle Located in just 5 minutes away from vibrant downtown Royal Oak including,
More informationSAN JOAQUIN COUNTY PURCHASING AND SUPPORT SERVICES PURCHASING DIVISION
SAN JOAQUIN COUNTY PURCHASING AND SUPPORT SERVICES PURCHASING DIVISION David M. Louis, C.P.M., CPPO, CPPB Director Jon Drake, C.P.M. Deputy Director Date: November 7, 2011 To: From: Bid#6767 Janitorial
More informationCOOL AMENITIES for Modern Living
COOL AMENITIES for Modern Living EXTERIOR FEATURES BATH FEATURES Stucco & siding exteriors 6 panel fiberglass front door Front door entry set deadbolt lock Metal sectional roll up garage door Garage door
More informationAn Equal Opportunity Employer. October 24, 2017
[Type here] Exhibit A Semcac An Equal Opportunity Employer October 24, 2017 The following document was prepared by Semcac in preparation with CRW architecture & Design. Plans, drawings and square footage
More informationChapter 3. Chapter Overview
Chapter 3 Reading Floor Plans, Part 1: Floor Plan Symbols Chapter Overview Introduction to Reading Floor Plan Symbols Wall Symbols Door Symbols Window Symbols Schedules Cabinets, Fixtures, and Appliances
More informationRESIDENTIAL BUILDING REQUIREMENTS
RESIDENTIAL BUILDING REQUIREMENTS Residential Building Requirements This is an informational booklet with some of the general residential construction requirements taken from the codes adopted by Campbell
More informationSECTION 1 FIRE STATION 11 FIREHOUSE LANE
12 Great Hollow Road Hanover, New Hampshire 03755 T: (603) 643-6111 F: (603) 643-2374 SECTION 1 FIRE STATION 11 FIREHOUSE LANE INTRODUCTION The following report was prepared for the Town of Norwich Vermont
More informationRISK CONTROL MANUAL SCHOOL SAFETY CHECKLIST (sample)
RISK CONTROL MANUAL SCHOOL SAFETY CHECKLIST (sample) The following checklist covers both physical condition of the facility and work practices of school personnel. On inspections, please be aware of potentially
More informationREHABILITATION STANDARDS CHECKLIST
Project Name Date Built Date Last Rehabilitated (If applicable) EXTERIORS REHABILITATION STANDARDS CHECKLIST ROOF Age (Yrs) Poor Fair Good Excellent Roof /Pitch/Flat # of Layers Substrate Material Insulation
More informationCopyright 2002-present, Natural Element Homes CABIN (2224)
80'-0" 37'-" 8'-0" '-0" 8'-0" 1 28'-0" '-0" 20'-0" 20'-0" 4'-0" 4'-0" '-0" 4'-0" '-0" 4'-6 1/2" 5'-4 1/4" 5'-4 1/4" 2'-7" 17'-11 3/4" 19'- 1/4" 4'-0" 4'-5 1/4" 9'-6 1/2" 2'-9 1/2" 17'-2 1/2" O MASTER BEDROOM
More informationKristin A. Park Residential Design
Kristin A. Park Residential Design December, 208 Jennifer Cappeto, Landmark Preservation Manager Denver Community Planning and Development 20 West Colfax Avenue Denver, Colorado 80202 Subject: Administrative
More informationQUINN COMMONS. Quinn Ln. SOLD
Quinn Ln. SOLD SOLD Specifications, square footage, renderings and floor plans are for illustration purposes only and are subject to change. Pictures are of similar Sage Built home. Prices may change without
More informationTimberglen Recreation Center Summary
Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,
More informationFACILITY COMPONENTS - ELEMENTARY SCHOOL
SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Two stalls fewer than minimum standard. Parking and Access - Service / Delivery 2.0 1.0 0.16 Parking and Access - Staff 1.0 3.0 0.24 Thirty-seven stalls
More informationEdouard AVANT GROVE U I C U I C. Modern Living Made Easy uichomes.com
Edouard Modern Living Made Easy uichomes.com - new construction - 3 stories + full basement - 4 bedrooms - 2.5 baths - 2,380 s.f. call 314.881.2333 or e-mail sales@uicstl.com PLAN NTS DECK 13' 0" X 12'-0"
More information108 North Grant Street Westmont, IL
Come home to 108 North Grant Street Westmont, IL The Manchester, an exceptional two-story home ideal for everyday living and entertaining. Home features convenient flex rooms, spacious kitchen with casual
More informationAPPENDIX B FF&E RESPONSIBILITY MATRIX
APPENDIX B FF&E RESPONSIBILITY MATRIX The -Build Contractor () shall work with the Government and be responsible for the development of the Furniture, Fixtures and Equipment (FF&E) Plan and Schedule for
More information2018 IRC Sections R303 through R310 Building Planning II
Study Session 3 2018 IRC Sections R303 through R310 Building Planning II OBJECTIVE: REFERENCE: KEY POINTS: To develop an understanding of the health and safety criteria of the code, including light and
More informationMoonlight Architecture, Inc. Architecture Interior Design Site Planning
Moonlight Architecture, Inc. Architecture Interior Design Site Planning 22 May 2018 18057 Mr. Michael J. Petit de Mange, County Administrator Kent County Levy Court 555 Bay Road Dover, DE 19901 RE: Facilities
More informationTOWN OF WESTON MASSACHUSETTS WESTON POLICE STATION CONDITIONS ASSESSMENT AND FEASIBILITY STUDY
TOWN OF WESTON MASSACHUSETTS WESTON POLICE STATION CONDITIONS ASSESSMENT AND FEASIBILITY STUDY DIMARINISI & WOLFE ARCHITECTS URBAN DESIGNERS 2 PARK PLAZA - SUITE 400 BOSTON, MASSACHUSETTS 02116 617-451-5799
More informationFACILITY COMPONENTS - ELEMENTARY SCHOOL
SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking
More informationConstruction of Frederick- Firestone Fire Protection District Station 4 FESA- 467 Joshua Williams
Construction of Frederick- Firestone Fire Protection District Station 4 FESA- 467 Joshua Williams 2 [CONSTRUCTION OF FREDERICK- FIRESTONE FIRE PROTECTION DISTRICT STATION 4] Executive Summary...3 Project
More informationTRIPLEX BUILDING 3 TOWNHOUSE UNITS
743 MAIN STREET TEWKSBURY, MA TRIPLEX BUILDING 3 TOWNHOUSE UNITS 2 BR, 2.5 BA page 2 FIVEPLEX BUILDING 5 TOWNHOUSE UNITS 2 BR, 2.5 BA page 3 MIXED BUILDING 2 GARDEN STYLE UNITS 2 BR, 2 BA page 4 3 COMMERCIAL
More information2) These Standards are available on the University s website at:
March 2014, rev 00 A) General 1) Definitions a. The University: Northern Illinois University; NIU. b. Prime Professional (s): Architects and Engineers and Contractors. c. EHS: NIU Environmental Health
More informationWelcome Home. The living is easy at Bayshore Dunes!
Welcome Home www.bayshoredunes.com The living is easy at Bayshore Dunes! Welcome to your new backyard! Welcome Home to Bayshore Dunes www.bayshoredunes.com Areas of Interest Direct Private Beach Access
More informationWEST COAST EXTERIORS GOURMET KITCHENS RELIABLE SECURITY ELEGANT ENSUITES & BATHROOMS SOPHIARESIDENCES.CA
AFFORDABLE LUXURY & LASTING QUALITY Bold use of West Coast exterior materials, including Western Red Cedar siding; painted, corrugated metal panels; cementitious composite sheathing; and smooth acrylic
More informationThe Inspector. Property Inspection Report
Cover Page The Inspector Property Inspection Report Inspection prepared for: ******** ******* Date of Inspection: 11/18/2013 Time: 12PM Age of Home: unknown Size: 2000sf Weather: overcast / 40 Inspector:
More informationEADO SQUARE STARTING AT $294,900. Contact: Maggie Houston at
STARTING AT $294,900 SITE PLAN N O RT H EV E RTON ST RE ET CANAL STRE ET 114 1 116 2 118 3 120 4 122 5 124 6 112 7 110 8 108 9 106 10 104 11 102 12 86 13 88 14 90 15 92 16 94 17 96 18 84 19 82 20 80 21
More informationEADO SQUARE. Contact: Maggie Houston at
SITE PLAN N O RT H EV E RTON ST RE ET CANAL STRE ET 114 1 116 2 118 3 120 4 122 5 124 6 112 7 110 8 108 9 106 10 104 11 102 12 86 13 88 14 90 15 92 16 94 17 96 18 84 19 82 20 80 21 78 22 76 23 74 24 25
More informationPembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS
Pembridge The Country Club Collection TOWNHOMES AT CRYSTAL SPRINGS STANDARD FEATURES LIST Foundation Concrete walls 4 concrete floor slab Interior basement unfinished Standard nine foot foundation walls
More informationPlantation Park. DSLD Homes At. Debbie Drake Price Bed/Bath Living Area Price
Region: Limestone County City/State: Harvest, AL Price Range: From the $200s www.dsldhomes.com Plantation Park American Craftsman Series Community Plans Price Bed/Bath Living Area Price Rosita II A 4B/2B
More informationNew Homes Forestbrook Road. Yes, it s INCLUDED!
Sugar Mill is a Covenant Restricted Community. New Homes Forestbrook Road Yes, it s INCLUDED! Granite Countertops Ceramic Tile Kitchen Floors Front Brick Accents Upgraded Kitchen Cabinets Ceramic Tile
More informationCHARTRES COURT Washington Avenue Houston, Texas ChartresCourtHouston.com CHARTRES COURT LLC
CHARTRES COURT 713-868 - 7226 5023 Washington Avenue Houston, Texas 77007 ChartresCourtHouston.com CHARTRES COURT LLC Features Open floor concept living/dining with spacious island kitchen Great master
More informationcase study LaMar Smith, Fire/EMS Warehouse Coordinator
ASAP Systems Helps Arlington County Fire Department Extinguish Inefficiencies With Better Tracking Case Study Overview Company: Arlington County Fire Department www.fire.arlingtonva.us Industry: Fire and
More information