1 St. Mark s Presbyterian Church Hawkins County, Tennessee Preservation Assessment and Recommendations
2 St. Mark s Presbyterian Church Hawkins County, Tennessee Historic Overview, Needs Assessment, and Recommendations Prepared for: The Hawkins County Board of Education Rogersville, Tennessee Prepared by: Amber Clawson, Graduate Research Assistant; Jessica Lauren White, Preservation Specialist; and Dr. Carroll Van West, Project Supervisor Winter Sponsored by the Tennessee Civil War National Heritage Area
3 Major Concerns Roof- Several holes are visible along the roof ridge and around the church s bell tower. These holes have allowed rainwater to leak into the interior of the building, causing water damage to the roofing system, acoustic ceiling tiles, and interior space below (e.g. pews and flooring). Note the apparent hole in the west side of the church s roof. There are several other leaks along the edge of the bell tower. The poor condition of the roof and its soffits is due to years of exposure to water and few repairs or maintenance efforts.
4 Note the severe water damage to the acoustic ceiling tiles and underlying roof materials caused by openings in the church s roof. This leak is located on the northwest side of the church in the rear sanctuary. Note the severe water damage to the acoustic ceiling tiles and underlying roof materials caused by flashing issues with the church s bell tower. This leak is located on the west entrance stairwell beneath the church s bell tower.
5 Fallen acoustic ceiling tiles and water damage to the pew in the rear sanctuary due to a leak in the church s roof. Water damage to a pew in the main sanctuary due to a leak in the church s roof.
6 Foundation Water Damage- St. Marks is situated in a gully with sloping embankments surrounding the east and south side of the building. These embankments have allowed rainwater to drain directly down hill onto the foundation of the church, causing severe moisture and stability issues. Water leakages from the above roof along with drainage problems from below work together to severely compromise the building s stability. Pictured here is the deep embankment on the east side of the church. Pictured here is the embankment on the south wall of the church. Note the water stains on brickwork.
7 Continuous exposure to moisture around the east and south side of the building has help to rot wood door surrounds and deteriorate the brick and mortar surface of the foundation. Note the water stains on the brickwork. It is evident that moisture is a continuous issue even on dry days. Continuous exposure to moisture around the east and south side of the building has help to deteriorate the brick and mortar surface of the foundation. Note the water stains on the brickwork. It is evident that moisture is a continuous issue even on dry days
8 Foundation and Wall Deterioration- As stated previously repeated contact with water run-off has caused severe damage to the existing building. Repeated exposure of the foundation walls to water has caused the brick walls to buckle and the frame walls to bow outward. Standing water has caused the ground around to soften. This in turn has caused the foundation to buckle in some areas. As seen in these four pictures some of the bricks have pulled apart causing significant cracking in the above walls.
9 Weakening of the foundation walls has caused the second story frame portion of the building to bow and warp. This outward bowing can be see predominately on the east and west walls of the church.
10 An interior view of the west wall bowing. Pictured here is the west side stairwell. Note that the stairs slope dramatically to the left.
11 Flooring System- For the most part the flooring system for the church remains intact. The flooring on the first floor of the east side of the building, however, after sustaining years of water damage, has suffered significant deterioration. Repeated contact with water has rotted the underlying joists, subflooring, and flooring. In several areas the flooring has rotted completely through leaving behind openings for pest infiltration. A small hallway running along the first floor of the east side of the building features the most significant damage to the flooring system. Pictured here is a large gapping hole that runs through the flooring and subflooring. The flooring in this section of the house has also begun to sag significantly.
12 Pest Infiltration and Hazardous Environment- St. Marks Presbyterian Church has been vacant since Since that time pests (e.g. birds, rodents and other small animals, and insects) have broken in to the church. These pests have not only caused physical damage to the building, but have also created a biohazard through the accumulation of fecal matter. **All future work in the church should be done while wearing gloves and masks. Pictured here is just one of many access points used my pest to enter the church. An accumulation of guano is a major concern of this building it not only provides a hazardous environment but also further degrades artifacts and the interior of the church.
13 Minor Concerns: 1. Missing stained glass windows 2. Damaged pews 3. Damaged stained glass windows 4. Damaged/fallen acoustical ceiling tiles. Immediate Solutions: 1. Roof Place tarpaulins over holes in the roof to prevent further water damage to the interior of the space. 2. Foundation Water Damage Reroute water run-off by digging a trench approximately four feet away from the foundation walls. Insert a PVC or some other type of impermeable channel in the trench to catch water and redirect it to the street. This will have to be cleaned periodically to prevent debris build up. 3. Pest Infiltration and Hazardous Environment Cover and secure all openings in the building to prevent further pest infiltration and damage to the building. Clean all debris, dust, and guano from building surfaces. Remove old carpet and other soft surfaces that are not easily cleaned. Workers must wear gloves, jumpsuits, and masks when cleaning this space. Long-term Solutions: ** Most of the concerns that threaten the stability of the church will be costly to repair, but it is essential that these repairs be completed to ensure the preservation of this significant site. 1. Consult a structural engineer/architect on the proper system needed to prevent further bowing or eventual collapse of the exterior walls. A buttress system may have to be used rather than a turn buckle system to add support along the entire height of the walls and not just along the bottom. 2. A new roof should be put on the building as soon as possible. This will prevent further interior water damage.
14 3. A permanent concrete gutter system should be added to the east and south side of the church to redirect water away from the foundation. Pictured above is an example of the type of trench system that should be installed at St. Mark s to prevent further water damage to the building s foundation. 4. Due to the exterior moisture damage the joist system, subflooring, and flooring system on the first floor of the east side of the building to rot through. These elements will likely have to be replaced. The flooring system should not be fixed until the gutter system has been installed to redirect outside water.
MAINTENANCE PLAN Wing Village Hall, Morcott Road, Wing, Oakham LE15 8SA
MAINTENANCE PLAN Roof Covering Roof slates Yearly Maintenance & Finishes 1 1, 8 & 13 Timber fascia and soffit boards Slates in good condition, some have been replaced during routine maintenance of roof.
More informationSTRUCTURAL CONDITION ASSESSMENT
STRUCTURAL CONDITION ASSESSMENT ALLEN JAY ROCK GYM 1201 FAIRFIELD ROAD HIGH POINT, NC Prepared for: Prepared by: Guilford County Schools 617 West Market Street Greensboro, NC Adrian S. Durham, PE, SE,
More informationCounty of Santa Barbara, California Facility Condition Assessment 2014
Project No.: P05000.001 Building Number: P05000 Lompoc VMB Grounds Project Description: Overlay, Seal Coat and Restripe Parking Lots Background: The asphalt paving comprises approximately 135,600 square
More informationHomebuyers Survey. Final Report. Mr Client. A Home, A Street, A Town. 3rd July 2014
Homebuyers Survey Final Report Mr Client A Home, A Street, A Town 3rd July 2014 Alpine Water Management Ltd Dorset House Regent Park Kingston Road Leatherhead KT22 7PL Tel: 0845 319 9 319 www.alpinedamp.co.uk
More informationHOT SPRINGS FIRE DEPARTMENT EVALUATION OF DOWNTOWN LEGACY STRUCTURES Savoy Hotel Thompson Building Dugan Stewart Building May 16, 2012
HOT SPRINGS FIRE DEPARTMENT EVALUATION OF DOWNTOWN LEGACY STRUCTURES Savoy Hotel Thompson Building Dugan Stewart Building May 16, 2012 0 On May 16,, 2012 Hot Springs Firefighters conducted an evaluation
More informationUSER INSTRUCTIONS The FIT is comprised of three parts as follows:
GENERAL INFORMATION The Facility Inspection Tool (FIT) has been developed by the Office of Public School Construction to determine if a school facility is in good repair as defined by Education Code (EC)
More informationVILLAGE OF ORLAND PARK, ILLINOIS ADDENDUM NO. 1 REBID # STELLWAGEN FARMHOUSE RESTORATION: PHASE 1 EXTERIOR FOUNDATION
VILLAGE OF ORLAND PARK, ILLINOIS ADDENDUM NO. 1 REBID #15-019 STELLWAGEN FARMHOUSE RESTORATION: PHASE 1 EXTERIOR FOUNDATION Date: Wednesday, April 13, 2016 To: From: RE: All Potential Bidders Village of
More informationConnaught. Facility Audit report for: Connaught Regina, SK. Report Created: Page 1 of 20
Connaught Facility Audit report for: Connaught Regina, SK Report Created: 2012-04-02 Page 1 of 20 Facility Details Facility Connaught Address: Location: Regina, SK Facility Zone: 8 Grade Configuration:
More informationFacility Assessment Report, Montgomery Independent School District
NATATORIUM CAMPUS DATA NATATORIUM 22628 Hwy 105 West, Montgomery TX 77356 Year Built 2009 Approx. Total Square Footage Grades Served 30,420 n/a Current Enrollment n/a Building Levels 1 1 MASTER PLAN 2
More informationAtlas Property Inspections, LLC
Website: http://atlaspropertyinspections.com Email: atlaspropertyinspections@gmail.com Phone: (609) 828-2294 127 Belle Arbor Drive Cherry Hill, NJ 08034 Inspector: Eric Mathiesen NJ Home Inspection License
More informationWarranty At-A-Glance ONE YEAR WARRANTY PERFORMANCE STANDARDS
Warranty At-A-Glance ONE YEAR WARRANTY PERFORMANCE STANDARDS A. Performance Standards for Foundations and Slabs. (1) Performance Standards for Raised Floor Foundations or Crawl Spaces. (a) A crawl space
More informationExample Schedule of Condition Report
1 INTERIOR Ground Garage Ceiling Timber members. Members appear to be in a fair and reasonable condition with no signs of any penetration marks noted. Walls Flank wall Brickwork. Part solid construction,
More informationOctober 26, 2017 Ref.: Newfoundland & Labrador English School District 95 Elizabeth Avenue St. John s, NL A1B 1R6
October 26, 2017 Ref.: 351-1 Newfoundland & Labrador English School District 95 Elizabeth Avenue St. John s, NL A1B 1R6 Attention: Mr. Jim Sinnott Director of Facilities & Custodial Management Dear Sir:
More informationInterNACHI. Advanced Inspection of Crawlspaces for home inspectors
CRAWLSPACE INACCESSIBLE Crawlspace conditions which in the Inspector s opinion posed a personal safety hazard limited examination of the crawlspace to only those home systems and their components visible
More informationMargaret Batts Tobin Laboratory
Roof Evaluation of Margaret Batts Tobin Laboratory The University of Texas At San Antonio Performed for UTSA Zero/Six Consulting, LLC 8423 Stewart Road Galveston, Texas 77554 409 740 0090 voice Table of
More informationChapter 2 Understanding The Problem
Chapter 2 Understanding The Problem What Causes Most Of The Problems With Stucco? EIFS was originally intended to seal and insulate the exterior of the home from the elements. Problems occur when poorly
More informationInfrared Inspection Report
Infrared Inspection Report 1234 Sample St, Anywhere Inspection Date/Time: 3/12/2007-11:00 AM Prepared For: Dave Smith Prepared By: Norton Inspection Co. 6632 Telegraph Rd, #346 Bloomfield Hills, MI 48301
More informationFOR HOME REPAIR AND CONSTRUCTION
FOR HOME REPAIR AND CONSTRUCTION A home located within the Wildland Urban Interface (WUI) may be at risk in the event of a wildfire. Lands and communities adjacent to and surrounded by wildlands are part
More informationRIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES
RIVERS EDGE CONDOMINIUM ASSOCIATION MAINTENANCE RESPONSIBILITIES This Policy Document outlines the separation of responsibilities between the Rivers Edge Condominium Association (RECA) and the Unit Owners
More information3D Home Improvement and Inspection Services, Inc
Property Inspection Report Cover Page ABC Disney Lane, Winter Garden FL, 34787 Inspection prepared for: John Doe Inspection Date: 7/15/2010 Time: 11:00 am Age: 6 Years Size: 3,378 LSF / 4,427 TSF Weather:
More informationUniversity of New Mexico Environmental Services Design & Development Standard Requirements
University of New Mexico Environmental Services Design & Development Standard Requirements Please review the following standards to be considered on all construction specifications. Your consideration
More informationPresenter: Mr. Rob Orwig, P.E. Senior Forensic Engineer/Heartland Regional Manager
Water Intrusion Presenter: Mr. Rob Orwig, P.E. Senior Forensic Engineer/Heartland Regional Manager CV Highlights: Lots of years of engineering experience 2-1/2 years with Donan Engineering Goals Identify
More informationCONDITION OF PROPERTY SURVEY Structural Integrity of Framing.
September 29, 2017 TO: REF: CONDITION OF PROPERTY SURVEY Structural Integrity of Framing. Dear Ms. : HEDDERMAN ENGINEERING, INC. performed an inspection today on the property located at, Houston, Texas.
More informationGarage Conversions. Technical Issues
Garage Conversions Introduction: if you need more space and you do not want to move house you may wish to consider converting your garage. Your home is probably your most valuable asset so it is important
More informationSabine Hill. Elizabethton, Carter County, Tennessee. Historic Structure Assessment
Sabine Hill Elizabethton, Carter County, Tennessee Historic Structure Assessment Sabine Hill Elizabethton, Carter County, Tennessee Historic Structure Assessment Prepared for: Tennessee Historical Commission
More informationSubject: Lucretia Mott School No. 3 Rehabilitation. Figure 1 Figure 2 Figure 3
MEMORANDUM To: Ashley Rosenthal Payne, Indianapolis Historic Preservation Commission Adrienne Schmetzer, Indiana Housing and Community Development Authority Architecture Preservation Interior Design Landscape
More informationConditions Report St. John s Episcopal Church Youngstown, NY. June Hamilton Houston Lownie Architects Siracuse Consulting Engineers
Conditions Report St. John s Episcopal Church Youngstown, NY June 2009 Lownie Architects Siracuse Consulting Engineers St. John s Episcopal Church Main & Chestnut Streets Youngstown, NY 14174 Conditions
More informationDivision 09 FINISHES TABLE OF CONTENTS
Division 09 FINISHES TABLE OF CONTENTS 09 1000 GENERAL... 3 A. RELATED SECTIONS... 3 B. MAINTENANCE OF FINISHES... 3 C. PUBLIC AREAS... 3 D. CUTTING AND PATCHING... 3 E. CLEANING... 3 F. RECOMMENDED FLOORING
More informationProject Findings: Appendix 2
NSF Final Report CMMI-1034874 Project Findings: Appendix 2 Selected Damage Photos of Engineered Buildings PART 2. Teleco Office Tower Civil Engineering and Engineering Mechanics Department University of
More informationHome Inspection Report Report Number: For The Property Located On:
Home Inspection Report Report Number: 416-129 For The Property Located On: Some Place Dr Prepared For Exclusive Use By: John and Jane Doe Report Prepared By: Adam Duncan; License No.: 3533 Inspector Signature:
More informationSTRUCTURAL ASSESSMENT OBSERVATION REPORT
Consulting Engineers THORSON BAKER & Associates, Inc. 3030 West Streetsboro Road (330) 659-6688 phone Richfield, Ohio 44286 (330) 659-6675 fax www.thorsonbaker.com STRUCTURAL ASSESSMENT OBSERVATION REPORT
More informationConstruction Technology Revision Guide
Construction Technology Revision Guide Sub structures and Super structures Super structure (Wall, floors roof) Sub structure (Foundations) 2 Thermal Insulation Thermal insulation helps to prevent heat
More informationPLYWOOD FLOATING FLOOR
PLYWOOD FLOATING FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Enka Building Products. These instructions may be followed, modified, or rejected
More informationLetter of Intent 1026 Sherman Ave
Letter of Intent 1026 Sherman Ave Overview We would like to tear down the existing structure which is not fit for occupancy or renovation and build a new home which is appropriate to the feel, class, size
More informationToronto Community Housing Executive Summary 2016/2017. BCA Report. Sample House High FCI
BCA Report Porfolio Development Size Construction TCHC - All Op Units Scattered Units (CHU 20),005 Sq.Ft. 925 Floor Above Grade 2 Divisional Units Page of 43 Description This dwelling unit is a detached
More informationItem Photographs Comments Completed Date Prior to Entering Home Address Verification Ensure you are at the Front of home
Initial Secure/1 st Time Lock Change Checklist The items listed in this checklist are to be completed on every property at initial secure. Item Photographs Comments Completed Date Prior to Entering Home
More informationChecklist #1 Questions to Ask Real Estate Agents
Checklist #1 Questions to Ask Real Estate Agents Whether you re selling or buying, hiring the right agent can be an important part of the home inspection process. Don t be afraid to ask lots of questions
More informationQuality Inspection 8618 London Heights San Antonio, TX Phone: (210)
Quality Inspection 8618 London Heights San Antonio, TX 78254 Phone: (210) 240-0476 PRE DRYWALL INSPECTION REPORT Prepared For: DELETED (Name of Client) Concerning: DELETED, San Antonio, TX 78258 (Address
More informationSlave Housing Data Base
Slave Housing Data Base Building Name: Tuckahoe Plantation, Quarter B Evidence Type: Extant Site ID: Historical Site Name: Tuckahoe Plantation City or Vicinity: County: Goochland State: Virginia UTM: @NW
More informationReflections After The Thaw Maine Water Utilities
Matthew J. Ashe, Jr. Kevin Gallerie Reflections After The Thaw Maine Water Utilities April 14, 2011 Winter 2010 2011 Snowfall Data (Boston) Season total was 7 th highest on record Maximum (1995 1996):
More informationMy Home Was Built In What Can I Expect To See On My Report?
My Home Was Built In 1956. What Can I Expect To See On My Report? Common Issues in 40 70 Year Old Homes Evidence of foundation settlement Older roof, limited service life remaining Older electrical system
More informationabout your house Assessing the Renovation Project Figure 1 Problems that should be addressed
about your house CE 28 a Furnace combustion gas backdrafting Limited headroom Moisture between window panes Damaged chimney Water stains Leaky skylight or windows Shingle missing Moss Over the years, we
More informationSNAGGING REPORT. Plot 19 Snag Close Unfinished Avenue Oxford OX90 1AB. for. Mr T & Mrs N Sample
SNAGGING REPORT on Plot 19 Snag Close Unfinished Avenue Oxford OX90 1AB for Mr T & Mrs N Sample Prepared By: Marshalls Chartered Surveyors Rochester House The Grange Farm Eynsham Road Oxford OX2 9NH Tel:
More informationMAJOR DEFECTS BUILDING SURVEY REPORT
MAJOR DEFECTS BUILDING SURVEY REPORT XXXXXX Road Bedminster Bristol BS3 XXX Prepared for Mr XXXXXXX July 2017 T J Maggs MRICS MAGGS AND ALLEN 22 Richmond Hill Clifton Bristol BS8 1BA 0117 973 4049 survey@maggsandallen.co.uk
More informationGUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev )
Milk and Dairy Food Safety Branch 1220 N Street, Sacramento, CA 95814 GUIDELINES FOR SANITARY DESIGN AND CONSTRUCTION OF MILK PRODUCTS PLANTS (rev. 10-20-2011) The outline below lists sanitary requirements
More informationFor Review Only, Sample Report. All About Homes, Inc. Residential Inspections
All About Homes, Inc. Residential Inspections 24326 Mission Blvd. Suite 7 Hayward, California 94544 Office: (510) 537-6000 Fax: (510) 537-8666 www.allabouthomes.com PROPERTY INSPECTED ~ Single Family Home
More informationHOUSECHARLOTTE MINIMUM HOUSING INSPECTION
HOUSECHARLOTTE MINIMUM HOUSING INSPECTION The primary objective of a minimum housing inspection is to ensure the City s housing stock is safe and sanitary. Please note Effective March 2014 Tenant occupied
More informationTERMINAL BUILDING EVALUATION
TERMINAL BUILDING EVALUATION 1.0 INTRODUCTION This report evaluates the existing Terminal Building at Frederick Municipal Airport (FDK) to determine the suitability of the building for continued use as
More informationBuilding Inspection Report
Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941
More informationCHECKLIST Inspecting a Garage
CHECKLIST Inspecting a Garage By Ben Gromicko This section deals with the details of the garage or carport inspection that may be performed. At the end of this section, you shall be able to: describe the
More informationOur ref: EJM/CE/17226~01. 4 th April Tim Heath - Chair The Blake Cottage Trust House of William Blake 17 South Molton Street London W1K 5QT
Registered in England No. 2727193 THE MORTON PARTNERSHIP LTD. CONSULTING CIVIL & STRUCTURAL ENGINEERS, HISTORIC BUILDING SPECIALISTS Old Timber Yard House, 55 The Timber Yard Drysdale Street, London N1
More informationGeotechnical problems on historic buildings consolidation
Geotechnical problems on historic buildings consolidation Ph. D. St. Nicoleta Maria ILIEŞ Faculty of Civil Enigineering and Building Services Technical University of Cluj Napoca, Romania 1. Considerations
More informationThe Inspection Process. Waxhaw N.C.
The Inspection Process In Waxhaw N.C. This information is provided by the Waxhaw Enforcement Division to assist you in the progression of your project. Nothing in this document should be considered "Code"
More informationCorium Brick Rainscreen System Specifications
CORIUM BRICK RAINSCREEN SYSTEM PART 1 - GENERAL 1.1 SUMMARY A. Work Included: The Work of this Section shall include but not be limited to the following: 1. Corium brick plates 2. Galvanized and coated
More informationStructural Inspection
General: Background: An inspection and structural analysis have been performed for the purpose of evaluating the buildings structural systems and components. A full set of structural drawings was utilized
More informationMETHOD STATEMENT First Fix Joinery
North West Facilities Ltd 17-18 Gaerwen Industrial Gaerwen Isle of Anglesey LL60-6HR Tel: 01248-422555 Fax: 01248-422556 Mobile: 07891-557581 Project/Contract CCG Contractor Apollo Property Services Group
More informationOhio s Historic Courthouses
Ohio s Historic Courthouses Preservation of the Courthouse s Building Characteristics: Roofs, Masonry, Windows, and More Jim Turissini, AIA Garmann/Miller Architects Engineers Ron Smallwood, AIA Garmann/Miller
More informationOREGON ROOF CONSULTING - ROOF INSPECTION FORM
Oregon CCB: 199121 PO Box 220190, Milwaukie, OR 97222 Washington License: OREGORC871MR OREGON ROOF CONSULTING - ROOF INSPECTION FORM General Roof Conditions: NA = Not Applicable Debris on Roof Physical
More informationTOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ FAX
TOWNSHIP OF LOGAN 125 MAIN STREET, PO BOX 314 BRIDGEPORT, NJ 08014 856-467-3626--- FAX 856-467-9260 Application for Certificate of Occupancy for Change of Occupancy Pursuant to Chapter 119 of the Township
More informationPresented by The National Association of Certified Home Inspectors Chicago Chapter
Top 10 Defects Found in New Homes Presented by The National Association of Certified Home Inspectors Chicago Chapter - The National Association of Certified Home Inspectors 1 Top 10 New Home Defects New
More informationTile on Existing. Viewpoint
Viewpoint Tile on Existing Exterior Reinforced Concrete BalconieS By Steven C. Turner Exterior reinforced concrete balconies are often covered by tile set in mortar beds with grouted joints. These installations
More informationInstallation Instructions
Installation Instructions RainTight Decks www.raintightdecks.com Underdeck Installation Instructions Table of Contents Page 3 Page 4 Page 5 Page 6 Page 7 Tools Required Introduction and How the system
More informationDominion Traditional Building Group Fox Groves Road Remington, VA 22734
Dominion Traditional Building Group 6625 Wilson Road, Marshall, VA 20115 Phone: 540 326 1882 info@traditionalbuilders.net July 13, 2016 Property: Presqu Isle Address: 8183 Fox Groves Road Remington, VA
More informationRockland Library Assessment Executive Summary
Rockland Library Assessment Executive Summary performed for City of Rockland, Maine 270 Pleasant Street Rockland, ME 04841 February 2, 2016 Civil & Structural Engineering 132 Brentwood Street Portland,
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationInspections Unlimited 12:38 August 20, 2013 Page 1 of 23 Sampleweb2013.pt6
12:38 August 20, 2013 Page 1 of 23 Table of Contents General Information 2 Component Ratings 3 Roof Surface 4 Lots and Grounds 5 Exterior Surface and Components 7 Garage/Carport 8 Kitchen 8 Living Space
More informationMOLD INSPECTION REPORT Block Home Inspections LLC
Block Home Inspections LLC David Block - 913-220-7762 MOLD INSPECTION REPORT Block Home Inspections LLC David M. Block Certified Mold Inspector #CMI-06-2024 INSPECTION AGREEMENT Mold screening is intended
More informationSHS Building Consultants. Ph Job Details. Photograph shows the front elevation of the residence.
Practical Completion Report Inspection date 1 st January Client Mohit Vir Job Details Address Lot 3349 Limone street Aveley. W.A. Photograph shows the front elevation of the residence. DESCRIPTION OF THE
More informationSchool Without Walls
INITIAL YEAR BUILT 1938 BUILDING AREA 59,400 SF CURRENT PROGRAM CAPACITY 304 ENROLLMENT 2008 276 WARD 1 PROPOSED PROGRAM CAPACITY 400 SCHOOL WITHOUT WALLS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationLASALLE - BACKUS EDUCATION CAMPUS
INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationEC The Effective Detective : Finding Energy Savings at Home
University of Nebraska - Lincoln DigitalCommons@University of Nebraska - Lincoln Historical Materials from University of Nebraska- Lincoln Extension Extension 1978 EC78-2051 The Effective Detective : Finding
More informationORDER OF AN EXECUTIVE OFFICER CLOSED FOR TENANT ACCOMMODATION PURPOSES ORDER TO VACATE
Environmental Public Health ORDER OF AN EXECUTIVE OFFICER CLOSED FOR TENANT ACCOMMODATION PURPOSES ORDER TO VACATE To: Amy Shun Foon Wong The Owner Albert Wong The manager And To: All Occupant(s) of the
More informationBUILDING SURVEYOR S INSPECTION REPORT OLD CO-OP BAKERY SUBSTATION - WEST CALDER FOR COMMUNITY DEVELOPMENT TRUST WEST CALDER.
BUILDING SURVEYOR S INSPECTION REPORT OF OLD CO-OP BAKERY SUBSTATION - WEST CALDER FOR COMMUNITY DEVELOPMENT TRUST WEST CALDER Prepared by SEPTEMBER 2017 Accessibility Statement In accordance with the
More informationO DONNELL & NACCARATO Nick Cinalli, PE, SECB / President & CEO
ATTACHMENT I PHILADELPHIA PRINCETON LEHIGH VALLEY WASHINGTON DC ORLANDO WEST PALM BEACH 111 South Independence Mall East / Suite 950 / Philadelphia, PA 19106-2524 Tel 215.925.3788 / 800.607.7284 / Fax
More informationHome Inspection Report
Home Inspection Report 1234 School House Road Yourtown, Yourstate 12345 Prepared for: Mr. and Mrs. Home Buyer Prepared by: 1217 Cape Coral Parkway East #177 Cape Coral, Florida 33904 Phone: (239) 322-0836
More informationTEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM. Form 15 Work Write-Up
TEXAS DEPARTMENT OF HOUSING AND COMMUNITY AFFAIRS OFFICE OF COLONIA INITIATIVES TEXAS BOOTSTRAP LOAN PROGRAM Form 15 Work Write-Up Owner-Builder Applicant Owner-Builder Co-Applicant Physical Address: City,
More informationPOC: John Roberts, or (843)
NAVAL FACILITIES ENGINEERING COMMAND, MID-ATLANTIC FACILITIES ENGINEERING AND ACQUISITION DIVISION (FEAD) PARRIS ISLAND 62 ATSUGI STREET (BUILDING 852) PARRIS ISLAND, SC 29905 POC: John Roberts, john.b.roberts@navy.mil
More informationMothball Plan And Existing Conditions Survey For Fort Ord, East Garrison Monterey, California
And Existing Conditions Survey For Fort Ord, East Garrison Monterey, California March 14, 2006 Prepared by Architectural Resources Group, Architects Planners & Conservators San Francisco, California For
More informationBuilding Construction Occupations
Job Ready Assessment Blueprint Building Construction Occupations Test Code: 2011 / Version 01 Measuring What Matters Specific Competencies and Skills Tested in this Assessment: Safety and General Knowledge
More informationNatrona County Development Department 200 North Center Street, Room 205 Casper, WY Phone: Fax:
Natrona County Development Department 200 North Center Street, Room 205 Casper, WY 82601 Phone: 307-235-9435 Fax: 307-235-9436 The purpose of the Natrona County Development Department is to provide necessary
More informationSURESILL WATER MANAGEMENT GUIDE
THE SURE LEVEL OF PROTECTION SURESILL WATER MANAGEMENT GUIDE FOR WINDOWS AND DOORS *1 SLOPED SILL PAN ASSEMBLY Cut the channel plate ¼ smaller than the rough opening. Check the fit with end caps before
More informationExample Building Condition Survey & Summary Report Address Address Address London
Example Building Condition Survey & Summary Report on Address Address Address London Date 2016 Ref. no. London Building Surveyors Ltd, 20 Stanmore Road, London. E11 3BU Tel: 020 8257 5766 Mob: 07854 755
More informationInspection Report Summary
Inspection Report Summary Prepared for: Property Location: XXXXXXXXXXXXXXXX XXXXXXXXXXXXX Dallas, Texas 75XXX Contact Info: Home Phone: XXXXXXXXXXXX E-mail: XXXXXXXXXXXXXXXX Date of Inspection: October
More informationProject Findings: Appendix 2
NSF Final Report CMMI-1034874 Project Findings: Appendix 2 Selected Damage Photos of Engineered Buildings PART 1. St. Louis Gonzague Cafeteria Building Civil Engineering and Engineering Mechanics Department
More informationTECH TALK Sponsored by
TECH TALK Sponsored by Installing ceramic tile, glass tile and stone in interior wet areas Slope, weeps, and flashing are key to managing water and avoiding failures By Donato Pompo, CTC, CSI, CDT, MBA,
More informationWILKINSON ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1976 BUILDING AREA 144,900 SF CURRENT PROGRAM CAPACITY 508 ENROLLMENT 2008 451 WARD 8 PROPOSED PROGRAM CAPACITY 600 Site Plan WILKINSON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationExhibit A Declaration of Restrictions Development and Design Standards For Ridge Park Estates
Exhibit A Declaration of Restrictions Development and Design Standards For Ridge Park Estates Spokane County, Washington For All Property Owners The following Development and Design Standards shall be
More informationU.S. General Services Administration Historic Preservation Technical Procedures. Galvanized Iron And Steel: Characteristics, Uses And Problems
U.S. General Services Administration Historic Preservation Technical Procedures Galvanized Iron And Steel: Characteristics, Uses And Problems 05010-09 GALVANIZED IRON AND STEEL: CHARACTERISTICS, USES AND
More informationRESIDENTIAL BUILDING PLAN REQUIREMENTS
CITY OF MANSFIELD BUREAU OF BUILDING AND CODES 30 NORTH DIAMOND STREET 3RD FLOOR MANSFIELD, OHIO 44902 Phone (419) 755-9688 Fax (419) 755-9453 www.ci.mansfield.oh.us RESIDENTIAL BUILDING PLAN REQUIREMENTS
More information1. The subfloor must be structurally sound and able to withstand live and dead loads with a deflection limitation of L/360.
HARDWOOD FLOOR Read First These suggestions represent generally accepted procedures for successful installation of Maxxon Products. These instructions may be followed, modified or rejected by the owner,
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationProperty Inspection Report
Property Inspection Report 17763 ABC Court San Diego, CA 92131 Page 1 of 26 Table of Contents Definitions 2 General Information 2 Lots and Grounds 2 Exterior Surface and Components 4 Roof 6 Garage/Carport
More informationCITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE Residential Accessory Structures
CITY OF CEDAR FALLS DEPARTMENT OF DEVELOPMENTAL SERVICES INSPECTION SERVICES DIVISION PHONE - 268-5161 Residential Accessory Structures This information has been compiled for the benefit of any person
More informationANNUNCIATION OF THE LORD PARISH Report on Roofing and Structural Repairs
ANNUNCIATION OF THE LORD PARISH Report on Roofing and Structural Repairs Prepared by: Parish Finance Council November 2017 TABLE OF CONTENTS Section 1: Introduction Section 2: The Roofs - Birds Eye View
More informationCARL E. SCHLUTER ELEMENTARY SCHOOL
CARL E. SCHLUTER ELEMENTARY SCHOOL Carl E. Schluter Elementary School Campus Data CARL E. SCHLUTER ELEMENTARY SCHOOL 1220 Mesa Crest Drive, Haslet, Texas 76052 Year Built 2011 Approx. Total Square Footage
More informationTHE DISASTERS OF SEPTEMBER 11, 2001 DAVID T. BIGGS, P.E. Principal Ryan-Biggs Associates, P.C. Troy, New York USA
THE DISASTERS OF SEPTEMBER 11, 2001 DAVID T. BIGGS, P.E. Principal Ryan-Biggs Associates, P.C. Troy, New York USA SUMMARY This paper presents some structural observations, findings, and recommendations
More informationPROPERTY CONDITION ASSESSMENT
PROPERTY CONDITION ASSESSMENT The Enclave at Kennedy Ridge Apartments 24870 Kennedy Ridge Rd, North Olmsted, OH 44070 Prepared for Zaremba Management Company May 15, 2015 Zaremba Management Company 22730
More informationVertigo Cladding Board
Installation guide Vertigo Cladding Board Geolam: a stunning alternative to wood cladding Vertigo is a composite wood cladding board requiring minimum maintenance. Durable and fade resistant, it will not
More informationCommercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists
Commercial Roof Cover Maintenance and Repair Risk Engineering Your Business Insurance Specialists With information provided by the Insurance Institute for Business & Home Safety Protection from the top
More information2003 International Residential Building Code
2003 International Residential Building Code Section R305 Ceiling Height Habitable rooms, hallways, corridors, bathrooms, toilet rooms, laundry rooms and basements shall have a ceiling height of not less
More information