Appendix I ESTIMATED DESIGN WIND PRESSURE AND STRENGTHS OF CONNECTIONS OF JOPLIN HOME DEPOT BUILDING
|
|
- Chad Lambert
- 6 years ago
- Views:
Transcription
1 ESTIMATED DESIGN WIND PRESSURE AND STRENGTHS OF CONNECTIONS OF JOPLIN HOME DEPOT BUILDING I.1 ESTIMATED DESIGN WIND PRESSURE BASED ON BOCA NBC/1996 Basic design wind speed: V = 90 mph (3 s gust) Exposure category: C Building parameters: Low rise, one story, 470 ft 250 ft in plan, with 28 ft mean roof height and 4 ft parapet Gust effect factor: G = 0.85 (rigid building) Partially enclosed. Internal pressure coefficient GC pi = ± 0.25 Importance factor: I = Design Wind Pressure for MWFRS: Basic velocity pressure: P V = V 2 = 20.7 lb/ft 2. Assume Condition I enclosure: GC Pi = ± 0.25 (see BOCA NBC/1996). The computed net internal pressure and internal suction based on BOCA NBC/1996 for the MWFRS of Home Depot building is shown below in Table I 1. The wind pressure distribution corresponding to the net internal pressure case, shown in Fig. I 1, represents the worst load case for wind uplift, with code level net uplift pressure of 26.2 lb/ft 2 (psf) on the roof. Note this calculated value is slightly less than the design uplift pressure of 28.2 psf indicated on the structural drawings of the Home Depot. This confirms that the wind uplift pressure used in designing the Home Depot was in conformance with (and slightly exceeding) the requirement of the building code in effect (BOCA NBC/1996). Design Wind Pressure for Component and Cladding: For BTS building, the roof system is an integral part of the MWFRS, not just cladding. Thus the estimated design wind pressure computed above for MWFRS that pertains to the roof could arguably be used for designing the roof. However, treating the roof as component and cladding could yield higher design wind pressure acting on the roof deck panels and the fasteners (puddle welds). The following 167 Assumed by NIST for this estimation based on Table Importance Factor (I) of BOCA NBC/1996. Design drawing obtained by NIST indicated a Wind Load Importance Factor I = 1.33 was used. However, this value was inconsistent with value specified by BOCA NBC/1996. NIST NCSTAR 3, Joplin Tornado Investigation 405
2 Draft for Public Comment Table I 1. Net internal pressure and internal suction for MWFRS of the Home Depot building. Surface Z (ft) G h K z C P P V IK h C P G h P V IK h GC Pi Net Pressure (psf) with Internal Pressure Internal Suction Windward ± ± ± ± ± ± Leeward All ± Side wall All ± Roof All ± psf 18.6 psf 17.8 psf MRH 20.4 psf 16.6 psf 15.2 psf psf 15 Figure I 1. Wind pressure distribution for MWFRS of the Home Depot building. calculation estimates the code level net uplift pressures, based on BOCA NBC/1996, on the roof deck panels and the fasterners if they are considered as component and cladding. Where, P = P V IK h [(GC p ) (GC pi )] P V IK h = psf (see above and Table I.1), NIST NCSTAR 3, Joplin Tornado Investigation
3 Draft for Public Comment Appendix I GC pi = ± 0.25, and GC p computed below based on effective wind areas of roof deck panel and tributary area of each fastener (puddle weld): Effective wind areas: Roof deck panel: A = 3 ft ft = ft 2 Fasterner (36/4 pattern): A = 5.8 ft 1.0 ft = 5.8 ft 2 Roof coefficient (GC p ): Component A (sq.ft) Zone 1 GC p 168 Zone 2 Roof deck panel Fastener Net roof component pressures, psf Component Roof deck panel Fastener Net Uplift Pressure Zone 1 Zone I.2 ROOF BRACING FORCES R T Force transferred to roof from lateral pressure on exterior of windward wall: 18.6 psf 17.8 psf 16.6 psf MRH R T Equating moments at base of wall (wall extends 2 ft below ground on top of footing): 15.2 psf 28 ଽ ( ய )( ) ( ) ( ய )( ) ( ) 13.5 psf 1 ( ய )( ) ( ) ( ய)( ) ( ) ( ய )( )( ଽ) ଽ ய ଗଓ ଡ଼ ୟଡ଼ଡ଼ 168 Zone 3 is treated as Zone 2 due to the 4 foot height parapet (greater than 3 ft) NIST NCSTAR 3, Joplin Tornado Investigation 407
4 Draft for Public Comment Force transferred to roof from uniform pressure on leeward wall: 14.6 psf MRH R T ଽ ( ய )( )( ) ய ଗଓ ଈଓଖକ ଙଖଖ 28 3 Force transferred to roof from uniform internal pressures on leeward wall: ± 5.77 psf R T ଽ ( ய )( )( ) L ய plf along roof 28 Net force R T per foot transferred to roof due to lateral wind load: With internal suction: Windward: R T = = plf Leeward: R T = = plf Net design roof bracing force due to lateral wind loads: W = = plf 408 NIST NCSTAR 3, Joplin Tornado Investigation
5 Draft for Public Comment Appendix I I.3 ROOF DIAPHRAGM SHEAR AND STIFFNESS Diaphragm Shear: Design diaphragm shear force: L=470 R = (L/2)(W) = 470 ½ = 137,968.5 lb Required nominal unit shear at side walls (design diaphragm shear): B=250 S = R/B = 137,968.5/250 = 552 plf Note: This calculated roof diaphragm shear value of 552 plf confirms the design diaphragm shear value of 560 plf shown on the Home Depot design drawings. W = plf Diaphragm Shear Stiffness G : Roof diaphragm shear stiffness G is a function of roof deck type and size, support joist spacing, and fastener types and pattern. For the Home Depot: Roof deck: B, 1.5 in. 22 gauge wide rib, 36 in. width, three span continuous Joist spacing L V : Varied from 5.4 ft to 5.8 ft (Note: This conforms to FM Global s recommended span of 6 ft for 22 gauge roof deck) Fasteners: At support: 5/8 in. puddle welds, 36/4 pattern Side laps: #10 Buildex screws, 7 per span G, based on SDI Deck Diaphragm Design Manual (2nd Edition) and CMC Joist and Deck Tables, for 5/8 in. puddle weld with 36/4 weld pattern and #10 Buildex screws side laps connection: ய ଽய ௱ ௫௫ ச ச Where: K 2 = 29,500t = 29,500(0.0295) = 870 (t : deck thickness = in. for 22 gauge deck) D xx = Deck warping factor, dependent on fastener pattern at supports = 1072 (for 36/4 pattern) K 1 = (factor relates to slip coefficient) NIST NCSTAR 3, Joplin Tornado Investigation 409
6 Draft for Public Comment ய ଽ ଽய ଟ ଽ ଟଽய ଟ ய ய ய ଐକ Note: 6.7 k/in. G = 13.9 k/in. 15 k/in. the Home Depot roof is a flexible roof diaphragm based on ACI 551 roof shear stiffness classifications. Roof diaphragm maximum shear deflection due to code level shear force: ( ய )( ଽ) ய ଐକଊଏ ஊ இஐ ௯ ( ய) ଽ ( ଽ) I.4 UPLIFT AND SHEAR CAPACITIES OF ROOF DECK TO JOIST CONNECTIONS Strength based on uplift alone: ASD governing load combination for net uplift force acting on deck to joist connection: 0.6D + W Where: D = 16 psf (service dead load shown on the Home Depot design drawings) W = 26.2 psf (service wind uplift load computed above based on BOCA NBC/1996) Required uplift resistance (or required tensile strength) of puddle welds, T, at service load: T = L V (0.6D + W)(1.1) = (5.8)[(0.6)(16) 26.2](1.1) = plf Nominal uplift resistance per foot along roof of puddle welds, T n, based on 36/4 weld pattern, 5/8 in. puddle weld, and 5.8 ft span length: Where: ଟ ௩ ଟ ௰ ௩ ௩ ௰ K = 2.7 (for 36/4 weld pattern, based on SDI Deck Diaphragm Design Manual, 2nd Edition) C = 3 ft (width of roof deck) P = 0.28t(d t)f u ) (Nominal uplift resistance per puddle weld, per AWS D1.3/D1.3M 2008 Structural Welding Code Sheet Steel) t = in. (thickness of 22 gauge metal roof deck) d = 5/8 in. (weld diameter) F u = 55 ksi 410 NIST NCSTAR 3, Joplin Tornado Investigation
7 Draft for Public Comment Appendix I L ଽய ଟଽயଽ ଟ ( ଽயଽ ) ଟ ଽய ଓଉଚ ଗଌଙ ଞଌଓଋ, ଇ L ௪ணப Thus, ன ய ଟ யଽ ய ଗଓ Safety factor for uplift strength of puddle weld: ௨ ய ଽ ய ய ய ଙଌଘଜଐଙଌଋ ଧ ଖଙ ଜଗଓଐଛ ଈଓଖକଌ Nominal uplift capacity of roof deck to joist connection: Note: L ௩ ய ଗଓ ய ଛ ய ଗଚ The 62.6 psf uplift capacity of the roof deck to joist connection exceeds the design uplift pressure of 26.2 psf by a safety factor of 2.4. This means a code level uplift pressure would not have caused the failure of the roof deck to joist connections (or the disconnection of the metal roof deck panels). Assuming the spatial relationship between lateral wind speed and uplift pressure in tornadoes is similar to that used in ASCE 7 standards, the 62.6 psf uplift capacity is equivalent to a lateral wind speed V = Strength based on combined uplift and shear: ASD shear and tension interaction equation for support fasteners (puddle welds): Where: த ௨௦டபண த ௨பத௧ ய ய ௨ ( ) ( ) யଽ u = 2.5 (safety factor for weld in tension) T = plf (above) T n = 1,800.7 plf (above) Q f no uplift = 2,010 lb (nominal shear strength per 5/8 in. puddle weld (tabulated in SDI manual and CDC Tables) Q f usable : Available nominal shear strength of puddle weld in the presence of an uplift force: ய Lயଅଆ L ௨ L ய ଟ ଽ ய த ௨௦டபண ( யଽ ( ) L ) ଟ த ௨பத௧ L ( யଽ ( ) ) ଟ ଽ ଽ ய ଓଉଚ ଽଽய L ய யଅଆ NIST NCSTAR 3, Joplin Tornado Investigation 411
8 Draft for Public Comment Required nominal unit shear at side walls: S n required = 552 plf (from roof bracing forces calculation above) Nominal shear strength S n of type B 1.5 in. 36 in. wide rib roof deck with 36/5 puddle weld pattern based on the SDI Deck Diaphragm Manual and CMC Joist and Deck Tables: For 5.5 ft deck span S n = 1,318 plf For 6.0 ft deck span S n = 1,230 plf Thus for L V = 5.8 ft deck span S n = 1318 ( )(0.3/0.5) = plf Available nominal deck shear strength adjusted for presence of uplift (accounting for effect of shear and tension interaction): ட௩டபடபண ( த ௨௦டபண த ௨பத௧ ) ய ( ய ଽ ଽ ) ଗଓ Factor of safety in combined shear and tension of deck to joist connection: ட௩டபடபண ய ய ண௨ண Roof deck to joist connection would not have failed under combined shear (lateral wind load) and tension (wind uplift) forces at code level wind load. However, the safety factor is slightly less than is typically required for this design. 412 NIST NCSTAR 3, Joplin Tornado Investigation
2012 Wood Frame Construction Manual: Wind Speed and Design Pressure Determination According to ASCE 7 10
2012 Wood Frame Construction Manual: Wind Speed and Design Pressure Determination According to ASCE 7 10 Presented by: William L. Coulbourne, PE Copyright Materials This presentation is protected by US
More informationOVERALL STRUCTURAL SYSTEM
EXECUTIVE SUMMARY The at the Pittsburgh International Airport, PA, is a 275,000 square foot multi-use building located directly adjacent to the airport s landside terminal. The building consists of an
More informationCALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 2015 WFCM ENGINEERING PROVISIONS (STD342-1)
CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 015 WFCM ENGINEERING PROVISIONS (STD34-1) John Buddy Showalter, P.E. Vice President, Technology Transfer American Wood Council Description The Wood Frame
More informationA REPORT ON THE EFFECTS OF WIND SPEED ON TIMBER CONSTRUCTION JOSHUA HUENEFELD. B.S., Kansas State University, 2012 A REPORT
A REPORT ON THE EFFECTS OF WIND SPEED ON TIMBER CONSTRUCTION by JOSHUA HUENEFELD B.S., Kansas State University, 2012 A REPORT submitted in partial fulfillment of the requirements for the degree MASTER
More informationCalculation of Wind Loads on Structures according to ASCE 7-10
Calculation of Wind Loads on Structures according to ASCE 7-10 Permitted Procedures The design wind loads for buildings and other structures, including the Main Wind-Force Resisting System (MWFRS) and
More informationNorth Shore at Canton Baltimore, MD Beau Menard Technical Report 1
North Shore at Canton Baltimore, MD Beau Menard Technical Report 1 Structural Schneider 10/05/05 Structural Concepts Executive Summary North Shore at Canton is a 4 story town home and parking garage structure
More informationArlington, Virginia December 3, 2007 TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN
TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN EXECUTIVE SUMMARY The is the practice facility for the NHL franchise, Washington Capitals. It is located in Arlington, Virginia just
More informationTECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania
TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering
More informationTechnical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design
Executive Summary Technical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design The Food Science Building in State College, Pennsylvania is a four story above ground steel composite
More informationROOF FRAMING ANCHORAGE FORCES: MWFRS
TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 ROOF FRAMING ANCHORAGE FORCES: MWFRS or C&C Summary: This Technical Note defines
More informationSimplified Building Schematic for Typical Floor (Levels 9 through 22):
Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid
More informationExecutive Summary...2 Introduction...3 Structural System Overview Buffalo,...4 Foundation...4 Floor System...4 Gravity System...4 Lateral System...
Table of Contents University at Buffalo CTRC/Incubator Executive Summary...2 Introduction...3 Structural System Overview Buffalo,...4 New York Foundation...4 Floor System...4 Gravity System...4 Lateral
More informationWind Load Report - Check for uplift
Wind Load Report - Check for uplift 1. Site & Building Data Roof Type: Gable Wind Speed (ult): 115 mph Exposure Category: C Enclosure Class: Enclosed Building Width (W): 43 ft. Building Length (L): 60
More informationINGHOUSE Page 1 of 48
INGHOUSE Page 1 of 48 Lars Jensen P.E., S.E. Web: www.inghouse.net EMAIL: jensen@inghouse.net INGHOUSE Page 2 of 48 OBJECTIVES: DESIGN OPTIONS; WHY ENGINEERED DESIGN DEVELOP AN UNDERSTANDING OF MAGNITUDE
More informationWind Load Report - Naples Residence
Wind Load Report - Naples Residence 1. Site & Building Data Roof Type: Gable Wind Speed (ult): 115 mph Exposure Category: C Enclosure Class: Enclosed Building Width (W): 20 ft. Building Length (L): 23
More informationENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa - UL2-D10-E10
ENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa UL2D10E10 November 16, 2016 AMPS Project Number: 20160200 Designed in compliance with: 2014 Florida Building Code 5th Edition with 2016 Supplements
More informationLoad Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.
R-CONTROL s STRUCTURAL INSULATED PANELS Note: Information deemed reliable at time of printing. Please visit www.r-control.com for latest information. June 2012 CONTROL, NOT COMPROMISE. www.r-control.com
More informationWilliam W. Wilkins Professional Building Columbus, Ohio
William W. Wilkins Professional Building Columbus, Ohio Technical Assignment 1 October 5, 2006 Michelle Structural Option AE 481W Senior Thesis Faculty Advisor: Dr. Boothby Table of Contents Executive
More informationTable of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5
WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 1 OCTOBER 5, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI Table of Contents Table of Contents
More informationSteel Roof Deck EC X
IAPMO ES Cover Sheet Evaluation Criteria of Steel Roof Deck EC 007-200 Posted for public commenting on 10/16/2009 to 11/12/2009 INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION
More informationJohn Jay College Expansion Project
Technical Report #1 Michael Hopper Mike AE Consultant: Dr. Lepage [Type the company name] September 29 th, 2008 Technical Report #1 Table of Contents Executive Summary.3 Introduction.4 Structural System.6
More informationSchool of Engineering and Applied Science Building Miami University, Oxford, OH Technical Assignment 3 December 3, 2007
School of Engineering and Applied Science Building Miami University, Oxford, OH Technical Assignment 3 December 3, 2007 Jonathan Kirk AE 481W Senior Thesis The Pennsylvania State University Faculty Advisor:
More information[TECHNICAL REPORT 3] Lateral System Analysis
Science Center Research Park 3711 Market St. The Pennsylvania State University Department of Architectural Engineering Senior Thesis 2009-2010 Prepared by: November 30, 2009 [TECHNICAL REPORT 3] Lateral
More informationLateral System Analysis and Confirmation Design (S-3)
November 13, 2002 Lateral System Analysis and Confirmation Design (S-3) Executive Summary: This report summarizes the analysis of the lateral systems used in the 250 West Street building in Columbus, Ohio.
More informationPrinciples of STRUCTURAL DESIGN. Wood, Steel, and Concrete SECOND EDITION RAM S. GUPTA. CRC Press. Taylor& Francis Group
SECOND EDITION Principles of STRUCTURAL DESIGN Wood, Steel, and Concrete RAM S. GUPTA CRC Press Taylor& Francis Group Boca Raton London New York CRC Press is an imprint of the Taylor & Francis Croup, an
More informationDIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:
More informationPoint Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan
Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Technical Report #3: Lateral System Analysis and Confirmation Design Table of Contents Introduction... 3 Executive Summary...
More informationExecutive Summary Building Description: Introduction... 13
Table of Contents Executive Summary... 2 Building Description:... 2 Report Summary:... 2 Introduction... 3 Building Description:... 3 Current Framing Layout... 4 Report Topics:... 4 Loads and Load Cases...
More informationThe New SDI Diaphragm Design Manual
Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2006) - 18th International Specialty Conference on Cold-Formed Steel Structures
More informationINTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL ROOF DECK.
INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL ROOF DECK EC 007-2010 e1 1.0 INTRODUCTION 1.1 Purpose: This criteria establishes the requirements
More informationTechnical Report 1. Residence Inn By Marriott. Structural Option September 29, Existing Conditions / Structural Concepts.
Katie Ritter Advisor: Dr. Ali Memari Structural Option September 29, 2008 Technical Report 1 Existing Conditions / Structural Concepts Residence Inn By Marriott Norfolk, Virginia 1 P age TABLE OF CONTENTS
More informationBERRIDGE SPACEFRAME BUILDING COMPONENTS DESIGN GUIDE
BERRIDGE SPACEFRAME BUILDING COMPONENTS DESIGN GUIDE CONTENTS PROPERTIES & LOADS 24 Ga. Stud Properties & Loads... 2 Back to Back Stud Properties & Loads... 2 C-Channel Rafter Properties & Loads... 3 Load
More informationNothing Flat About Steel Joists and Steel Deck On a Pitched Roof
Nothing Flat About Steel Joists and Steel Deck On a Pitched Roof APRIL 18, 2018 Copyright 2018 Steel Joist Institute. All Rights Reserved. Presented by: Ben Pitchford, P.E. Thomas Sputo, Ph.D, P.E., S.E.
More informationFlorida Structural Engineers
Florida Structural Engineers South Florida Chapter January 8, 2008 Miami Lakes, Florida Aluminum Association of Florida, Inc. Joe Belcher ~ David Miller AAF Code Involvement: Historical Perspective 1998:
More informationBrent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan
Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,
More informationDIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104
0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00
More informationSTRUCTURAL NOTES MISCELLANEOUS COLD-FORM STEEL FRAMING MASONRY SITE WORK CAST IN PLACE CONCRETE
STRUCTURAL NOTES MISCELLANEOUS COLD-FORM STEEL FRAMING MASONRY AA 0009 707 US Hwy. 9 Palm Harbor, FL 68 Phone 77. 78. 7 Fax 77. 78. 66 SITE WORK CAST IN PLACE CONCRETE OPEN WEB STEEL JOISTS AND JOIST GIRDERS
More information111 MORGAN ST. Ryan Friis
Technical Report No. 1 September 30, 2002 Executive Summary: 111 Morgan St. is a 9 story cast-in-place concrete condominium building being constructed in Chicago, Illinois. The building s floor system
More informationConsiderations for Outof-Plane. Design
Considerations for Outof-Plane Wall and Uplift Design WoodWorks Texas Workshops December, 2016 Overview Uplift Wall Design Wind Loads Wind loads acting on buildings are modeled as uniform surface loads.
More informationButler Health System New Inpatient Tower Addition/Remodel. Dr. Ali Memari Technical Report #1. Architects Rendering. Technical Report #1
Dr. Ali Memari Technical Report # Architects Rendering Technical Report # Due October 5 th, 2009 Dr. Ali Memari Technical Report # Table of Contents I. Executive Summary 3 II. Introduction 4 III. Structural
More informationOriginally Issued: 03/10/2017 Revised: 08/24/2018 Valid Through: 03/31/ Design
EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue North Fort Payne, Alabama 35967 (256) 845-2460 VERCO DECKING, INC. a NUCOR
More informationSTRUCTURAL TECHNICAL REPORT 1
Technical Report 1 Page 1 David Lee AE 481W Structural Option Advisor: Andres Lepage URS Office Building October 5, 2006 STRUCTURAL TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions
More informationImpact of C&C loads due to ASCE/SEI Overview Revised 3/23/2017
Impact of C&C loads due to ASCE/SEI 7-16 Overview Revised 3/23/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information,
More informationTechnical Assignment 3 December 3, 2007
Technical Assignment 3 December 3, 2007 101 Eola Drive, Orlando, FL Justin Raducha Pennsylvania State University Faculty Advisor: M. Kevin Parfitt Table of Contents Table of Contents... 2 Executive Summary...
More informationDIVISION 5 METALS SECTION METAL DECKING
DIVISION 5 METALS SECTION 05 30 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: All labor and materials required to furnish and install metal decking and accessories including shear connectors, closures,
More informationRutgers University Law School Building Addition and Renovation Camden, NJ
Building Addition and Renovation Camden, NJ Technical Assignment 1 October 5, 2007 Nathan E. Reynolds Structural Option Senior Thesis The Pennsylvania State University Faculty Consultant: Professor M.
More informationStructural Redesign Gravity System
Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides
More information90% Design Submittal Structural Calculations Parking Garage CDRL
NORTH METRO RAIL LINE PROJECT Thornton Crossroads at 104 th Avenue Station 90% Design Submittal Structural Calculations Parking Garage CDRL 03-037.11.06 June 2, 2017 Prepared by: Regional Rail Partners
More informationDesign of Steel Joists and Roof Decks
Design of Steel Joists and Roof Decks Michael R. Miller, P. E. Topics for Discussion Design Responsibility What is a standard joist? Assumptions Dimensions Designations Joist Design for Wind Uplift Properly
More informationOriginally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design
Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/2019 EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue
More informationWood Shear Wall Design Examples For Wind
Wood Design Examples For Wind EARN 0.1 ICC Continuing Education Unit (CEU) and/or AIA/CES HSW 1 Learning Unit (LU) DES413-A Wood Design Examples for Wind Description: In this article, a wood frame shear
More informationProject ULA 120D Snow-0 Seis-IV
ULA Geometry Module Specification Sub-Array Configuration ULA Totals # Rows: 4 Column N-S Length (in): 6 # SubArrays: N-S Dim (in): 40 N-S Spacing (in): 0.25 # Columns: 5 Array E-W Dimension (in): 326
More informationFLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.
Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 29 Ga. GulfRib Roof Panel over Florida Product Approval #11651.27 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:
More informationLetter of Transmittal
Letter of Transmittal November 17, 2014 Ali Said Structural Thesis Advisor The Pennsylvania State University aus59@psu.edu Dear Doctor Said, The following technical report fulfills the fourth Technical
More informationEarth and Engineering Sciences Building University Park, Pennsylvania
Executive Summary The Earth and Engineering Sciences building is a 4 story educational and laboratory facility. An additional basement level is located below grade and provides the foundation for the East
More informationWIND LOADS ON BUILDINGS MWFRS (ENVELOPE PROCEDURE)
Chapter C28 WIND LOADS ON BUILDINGS MWFRS (ENVELOPE PROCEDURE) The Envelope Procedure is the former low-rise buildings provision in Method 2 of ASCE 7-05 for MWFRS. The simplified method in this chapter
More informationMOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS
MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF
More informationTechnical Report 1. Seneca Allegany Casino Hotel Addition. Salamanca, NY
Technical Report 1 Seneca Allegany Casino Hotel Addition Salamanca, NY Nicholas Reed Structural Option Advisor: Prof. Parfitt Executive Summary The purpose of this technical report was to analyze the existing
More informationHIGH RISE CONDO SOHO, NEW YORK, NY
HIGH RISE CONDO SOHO, NEW YORK, NY TECHNICAL ASSIGNMENT 1 October 5, 2006 Joseph The Pennsylvania State University Structural Option Faculty Advisor: Andres Lepage TABLE OF CONTENTS TABLE OF CONTENTS 2
More informationRCKW Kneewall Connectors
This product is preferable to similar connectors because of a) easier installation, b) higher loads, c) lower installed cost, or a combination of these features. The Simpson Strong-Tie RCKW rigid connectors
More informationStructural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report
More informationAPPENDIX. WOOD JOIST/RAFTER MAXIMUM SPANS ( for 16 o.c. spacing) WITH SINGLE ROW OF PV PANELS AT MIDSPAN (ft.) AND PANEL SUPPORT AT 32 o.c.
1 Span Tables The following Wood Joist/Rafter Maximum Span Tables can be used to determine the adequacy of an existing wood framed roof structure to support the additional dead load created by PV panel
More informationJoseph L. Oliveri, AIA
c < < < < < < Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA PARKING BY DISABLED PERMIT ONLY $ xxx FINE F.S. 318.14 Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA Joseph L. Oliveri,
More informationStructural Calculations Amphitheater Middle School Building 400 AC Replacement 315 E. Prince Rd., Tucson, Arizona
Structural Calculations Amphitheater Middle School Building 400 AC Replacement 315 E Prince Rd, Tucson, Arizona Prepared for: Amphitheather Public Schools SCI Project No 17-167A SCI Project No 17-167A
More informationLateral System Analysis and Confirmation Design November 15, 2004
Jonathan Hill Structural AE Faculty Consultant Dr. Hanagan Lynde and Harry Bradley School of Technology & Trade Milwaukee, Wisconsin Lateral System Analysis and Confirmation Design November 15, 2004 Executive
More informationBelmont Executive Center; Building A
Nicholas L. Ziegler: Structural Advisor: Professor M. Kevin Parfitt December 1, 2009 1 Table of Contents Executive Summary...3 Introduction...3 Structural System...4 Foundation System... 4 Column System...
More informationCheck the strength of each type of member in the one story steel frame building below.
CE 331, Summer 2015 nalysis of Steel Braced Frame Bldg 1 / 9 Check the strength of each type of member in the one story steel frame building below. 4 @ 8 ft B 20 f 1 2 3 @ 25 ft Side Elevation 3 4 Plan
More informationDesign Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER
Design Manual and Catalog of Steel Deck Products s STEEL DECK INSTITUTE MEMBER Manufacturers of products History CMC Joist & Deck is a leading producer of steel deck, open-web steel joists, long span steel
More information1000 CONNECTICUT AVENUE
1000 CONNECTICUT AVENUE Gea Johnson Structural Option Faculty Advisor: Dr. Hanagan September 23, 2011 Revised: December 16, 2011 Washington DC Technical : Existing Conditions Table of Contents Executive
More informationTechnical Report #3: Lateral System Analysis. Executive Summary
ERIC MUELLER STRUCTURAL OPTION ADVISOR DR. LEPAGE AE 481W DECEMBER 19, 2006 555 12 TH STREET OAKLAND, CALIFORNIA Technical Report #3: Lateral System Analysis Executive Summary 555 12 th Street is a 21
More informationMetal Roof Certification & Listing Program
145 Limekiln Road, Suite 100B Issue Dated: 10/27/2017 New Cumberland, PA 17070 Revision Date: 10/27/2017 www.keystonecerts.com Expiration Date: 10/27/2022 Construction Specifications Institute (CSI) Category:
More information16.4 FLORIDA BUILDING CODE BUILDING
1604.8-1606.1.2 5. Designs using NAAMM FP-1001 Specification for Design Loads of Metal Flagpoles. 6. Subject to the limitations of 1606.1.1.1, 1606.1.4, and 1606.1.6, the provisions of the FC&PA Guide
More informationLateral Design of Mid- Rise Wood Structures
Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following
More informationDanielle Shetler - Structural option Courtyard by Marriott Lancaster, PA
Structural Analysis Overview: During the structural analysis of the in Lancaster, Pa, a redesign of the lateral and gravity system from masonry bearing and shear walls to a staggered truss system was performed.
More information5 Load Determination and Structural Design Criteria
5 Load Determination and Structural Design Criteria This chapter presents a summary of previous research and testing and outlines the recommended methods and criteria for use in the structural design of
More informationPark Potomac Office Building E
Technical Assignment 1 Kyle Wagner (IP) AE Consultant: Professor Kevin Parfitt October 05, 2009 Table of Contents I. Executive Summary 3 II. Introduction... 4 III. Structural System Overview..... 4 Foundation
More informationBoyds Bear Country Pigeon Forge, TN
Technical Report 3 Lateral System Analysis and Confirmation Design Executive Summary:, located in Pigeon Forge, Tennessee, is designed as a multifunctional space and tourist attraction for Boyds Collections
More informationMarconi Communications Building #5 Warrendale, Pennsylvania
Kelly Hellyer November 14, 2003 Structural Technical Assignment #1 Structural Concepts / Structural Existing Conditions Report Table of Contents Description Page(s) Executive Summary 1 Introduction & Design
More informationStructural Technical Report #1 By Robert Whitaker
Structural Technical Report #1 By Robert Whitaker Robert Whitaker Structural ~ Parfitt Parkview at Bloomfield Station Bloomfield, NJ 10-05-05 Executive summary This report covers the structural concepts
More informationWESTINGHOUSE ELECTRIC COMPANY CORPORATE HEADQUARTERS CRANBERRY, PA
WESTINGHOUSE ELECTRIC COMPANY CORPORATE HEADQUARTERS CRANBERRY, PA Technical Assignment 3 November 21, 2008 Advisor: Dr. Linda Hanagan Page 2 of 57 TABLE OF CONTENTS EXECUTIVE SUMMARY... 3 INTRODUCTION...
More informationANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.
ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC. Paul Lackey, P.E., Muhammad Ghoraba, Nabil A. Rahman, Ph.D., P.E. and Kurtis Kennedy MidWall is a hold-down product intended to
More informationresearch report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2
research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-005 REVISION 006 American Iron and Steel Institute Cold-Formed
More informationFLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.
Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:
More informationFLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R2. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.
Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 29 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #16646.1 R2 Florida Building Code 2017 Per Rule 61G20-3 Method: 1
More informationFLORIDA PRODUCT APPROVAL 5VCRIMP FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.
26 GA. ROOF PANEL OVER 15/32 PLYWOOD Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. 5V Crimp Roof Panel over 15/32 Plywood Florida Product Approval #11651.13 R3 Florida Building
More informationThe Carport - Bryan, Texas
This is going to be an exciting presentation that is of great interest to me. The carport of my house was rotten and falling down and needed to be replaced. I m going to give you all the information you
More informationDESIGNING WITH STEEL FORM DECK
DESIGNING WITH STEEL FORM DECK All rights reserved 2003 P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648 Form deck is a term used to describe deck that is most frequently
More informationLATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES
LATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES W. Mark McGinley 1, PhD, PE and Eric N. Johnson 2, PE ABSTRACT In North American residential construction, brick veneer is typically used as a cladding
More informationICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.
ICC-ES Evaluation Report ESR-409 Reissued June, 00 This report is subject to re-examination in one year. www.icc-es.org (800) 4-6587 (56) 699-054 A Subsidiary of the International Code Council DIVISION:
More informationStructural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report
1 THE ODYSSEY ARLINGTON, VA Aaron Snyder Structural Option Advisor: M. Kevin Parfitt, PE Structural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report Executive
More informationNovember 16, The Pennsylvania State University. Hunter Woron Structural. Professor M. Kevin Parfitt
November 16, 2011 Hunter Woron Structural Professor M. Kevin Parfitt The Pennsylvania State University Table of Contents Executive Summary 2 Introduction 3 Structural System Summary 4 ETABS Model 9 Codes
More informationStructural Concepts and Existing Conditions Report
Daniel Chwastyk F.W. Olin Center Louis Geschwindner Advisor Structural Concepts and Existing Conditions Report Executive Summary The following report discusses many of the structural concepts that were
More informationWIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008
2008 EDITION ANSI/AF&PA SDPWS-2008 Approval Date: August 4, 2008 ASD/LRFD WIND & SEISMIC Special Design Provisions for Wind and Seismic WITH COMMENTARY American Forest & Paper Association Updates and Errata
More informationSTRUCTURAL CALCULATIONS EXTERIOR SIDING CLADDING SYSTEM FLUSH PANEL SIDING SYSTEM AND LAPPED PANEL SIDING SYSTEM
JN 3617 Page 1 of 27 NOTES ON ANALYSIS, DESIGN METHOD, BUILDING CODE REFERENCES, AND ASSUMPTIONS. The exterior phenolic panel siding system is classified under the International Building Code as a Non-
More informationWIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008
2008 EDITION ANSI/AF&PA SDPWS-2008 Approval Date: August 4, 2008 ASD/LRFD WIND & SEISMIC Special Design Provisions for Wind and Seismic WITH COMMENTARY American Forest & Paper Association American Wood
More informationSE APPRENTICE. Stephen Metz PE, LEED AP. Today s Speakers. Company Overview. Company Overview 10/13/2015. SE Apprentice. Who We Are.
Today s Speakers Carrie Bremer, PE Schaefer Stephen Metz, PE SMBH, Inc. Today s Moderators SE APPRENTICE Lecture One Loads Lisa Willard, PE SE Solutions, LLC SE Apprentice Brian Quinn, PE SE Solutions,
More informationLateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.
Outline 2005/2008 Special Design Provisions for Wind & Seismic Standard Lateral load basics Code acceptance of Standard 2005/2008 Wind & Seismic Standard Overview 2008 Wind & Seismic Standard John Buddy
More informationCopyright Materials. American Wood Council
2012 Wood Frame Construction Manual: Foundation Design to Resist Flood Loads and WFCM Calculated Wind Loads Presented by: William L. Coulbourne, PE 2 Copyright Materials This presentation is protected
More informationML200 Panel Technical Data Guide
Description ML200 is a mechanical seamed standing seam roofing panel used on low to steep sloped commercial applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to
More informationHilton Baltimore Convention Center Hotel Western Podium
Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Technical Report 1 TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..
More information