Appendix I ESTIMATED DESIGN WIND PRESSURE AND STRENGTHS OF CONNECTIONS OF JOPLIN HOME DEPOT BUILDING

Size: px
Start display at page:

Download "Appendix I ESTIMATED DESIGN WIND PRESSURE AND STRENGTHS OF CONNECTIONS OF JOPLIN HOME DEPOT BUILDING"

Transcription

1 ESTIMATED DESIGN WIND PRESSURE AND STRENGTHS OF CONNECTIONS OF JOPLIN HOME DEPOT BUILDING I.1 ESTIMATED DESIGN WIND PRESSURE BASED ON BOCA NBC/1996 Basic design wind speed: V = 90 mph (3 s gust) Exposure category: C Building parameters: Low rise, one story, 470 ft 250 ft in plan, with 28 ft mean roof height and 4 ft parapet Gust effect factor: G = 0.85 (rigid building) Partially enclosed. Internal pressure coefficient GC pi = ± 0.25 Importance factor: I = Design Wind Pressure for MWFRS: Basic velocity pressure: P V = V 2 = 20.7 lb/ft 2. Assume Condition I enclosure: GC Pi = ± 0.25 (see BOCA NBC/1996). The computed net internal pressure and internal suction based on BOCA NBC/1996 for the MWFRS of Home Depot building is shown below in Table I 1. The wind pressure distribution corresponding to the net internal pressure case, shown in Fig. I 1, represents the worst load case for wind uplift, with code level net uplift pressure of 26.2 lb/ft 2 (psf) on the roof. Note this calculated value is slightly less than the design uplift pressure of 28.2 psf indicated on the structural drawings of the Home Depot. This confirms that the wind uplift pressure used in designing the Home Depot was in conformance with (and slightly exceeding) the requirement of the building code in effect (BOCA NBC/1996). Design Wind Pressure for Component and Cladding: For BTS building, the roof system is an integral part of the MWFRS, not just cladding. Thus the estimated design wind pressure computed above for MWFRS that pertains to the roof could arguably be used for designing the roof. However, treating the roof as component and cladding could yield higher design wind pressure acting on the roof deck panels and the fasteners (puddle welds). The following 167 Assumed by NIST for this estimation based on Table Importance Factor (I) of BOCA NBC/1996. Design drawing obtained by NIST indicated a Wind Load Importance Factor I = 1.33 was used. However, this value was inconsistent with value specified by BOCA NBC/1996. NIST NCSTAR 3, Joplin Tornado Investigation 405

2 Draft for Public Comment Table I 1. Net internal pressure and internal suction for MWFRS of the Home Depot building. Surface Z (ft) G h K z C P P V IK h C P G h P V IK h GC Pi Net Pressure (psf) with Internal Pressure Internal Suction Windward ± ± ± ± ± ± Leeward All ± Side wall All ± Roof All ± psf 18.6 psf 17.8 psf MRH 20.4 psf 16.6 psf 15.2 psf psf 15 Figure I 1. Wind pressure distribution for MWFRS of the Home Depot building. calculation estimates the code level net uplift pressures, based on BOCA NBC/1996, on the roof deck panels and the fasterners if they are considered as component and cladding. Where, P = P V IK h [(GC p ) (GC pi )] P V IK h = psf (see above and Table I.1), NIST NCSTAR 3, Joplin Tornado Investigation

3 Draft for Public Comment Appendix I GC pi = ± 0.25, and GC p computed below based on effective wind areas of roof deck panel and tributary area of each fastener (puddle weld): Effective wind areas: Roof deck panel: A = 3 ft ft = ft 2 Fasterner (36/4 pattern): A = 5.8 ft 1.0 ft = 5.8 ft 2 Roof coefficient (GC p ): Component A (sq.ft) Zone 1 GC p 168 Zone 2 Roof deck panel Fastener Net roof component pressures, psf Component Roof deck panel Fastener Net Uplift Pressure Zone 1 Zone I.2 ROOF BRACING FORCES R T Force transferred to roof from lateral pressure on exterior of windward wall: 18.6 psf 17.8 psf 16.6 psf MRH R T Equating moments at base of wall (wall extends 2 ft below ground on top of footing): 15.2 psf 28 ଽ ( ய )( ) ( ) ( ய )( ) ( ) 13.5 psf 1 ( ய )( ) ( ) ( ய)( ) ( ) ( ய )( )( ଽ) ଽ ய ଗଓ ଡ଼ ୟଡ଼ଡ଼ 168 Zone 3 is treated as Zone 2 due to the 4 foot height parapet (greater than 3 ft) NIST NCSTAR 3, Joplin Tornado Investigation 407

4 Draft for Public Comment Force transferred to roof from uniform pressure on leeward wall: 14.6 psf MRH R T ଽ ( ய )( )( ) ய ଗଓ ଈଓଖକ ଙଖଖ 28 3 Force transferred to roof from uniform internal pressures on leeward wall: ± 5.77 psf R T ଽ ( ய )( )( ) L ய plf along roof 28 Net force R T per foot transferred to roof due to lateral wind load: With internal suction: Windward: R T = = plf Leeward: R T = = plf Net design roof bracing force due to lateral wind loads: W = = plf 408 NIST NCSTAR 3, Joplin Tornado Investigation

5 Draft for Public Comment Appendix I I.3 ROOF DIAPHRAGM SHEAR AND STIFFNESS Diaphragm Shear: Design diaphragm shear force: L=470 R = (L/2)(W) = 470 ½ = 137,968.5 lb Required nominal unit shear at side walls (design diaphragm shear): B=250 S = R/B = 137,968.5/250 = 552 plf Note: This calculated roof diaphragm shear value of 552 plf confirms the design diaphragm shear value of 560 plf shown on the Home Depot design drawings. W = plf Diaphragm Shear Stiffness G : Roof diaphragm shear stiffness G is a function of roof deck type and size, support joist spacing, and fastener types and pattern. For the Home Depot: Roof deck: B, 1.5 in. 22 gauge wide rib, 36 in. width, three span continuous Joist spacing L V : Varied from 5.4 ft to 5.8 ft (Note: This conforms to FM Global s recommended span of 6 ft for 22 gauge roof deck) Fasteners: At support: 5/8 in. puddle welds, 36/4 pattern Side laps: #10 Buildex screws, 7 per span G, based on SDI Deck Diaphragm Design Manual (2nd Edition) and CMC Joist and Deck Tables, for 5/8 in. puddle weld with 36/4 weld pattern and #10 Buildex screws side laps connection: ய ଽய ௱ ௫௫ ச ச Where: K 2 = 29,500t = 29,500(0.0295) = 870 (t : deck thickness = in. for 22 gauge deck) D xx = Deck warping factor, dependent on fastener pattern at supports = 1072 (for 36/4 pattern) K 1 = (factor relates to slip coefficient) NIST NCSTAR 3, Joplin Tornado Investigation 409

6 Draft for Public Comment ய ଽ ଽய ଟ ଽ ଟଽய ଟ ய ய ய ଐକ Note: 6.7 k/in. G = 13.9 k/in. 15 k/in. the Home Depot roof is a flexible roof diaphragm based on ACI 551 roof shear stiffness classifications. Roof diaphragm maximum shear deflection due to code level shear force: ( ய )( ଽ) ய ଐକଊଏ ஊ இஐ ௯ ( ய) ଽ ( ଽ) I.4 UPLIFT AND SHEAR CAPACITIES OF ROOF DECK TO JOIST CONNECTIONS Strength based on uplift alone: ASD governing load combination for net uplift force acting on deck to joist connection: 0.6D + W Where: D = 16 psf (service dead load shown on the Home Depot design drawings) W = 26.2 psf (service wind uplift load computed above based on BOCA NBC/1996) Required uplift resistance (or required tensile strength) of puddle welds, T, at service load: T = L V (0.6D + W)(1.1) = (5.8)[(0.6)(16) 26.2](1.1) = plf Nominal uplift resistance per foot along roof of puddle welds, T n, based on 36/4 weld pattern, 5/8 in. puddle weld, and 5.8 ft span length: Where: ଟ ௩ ଟ ௰ ௩ ௩ ௰ K = 2.7 (for 36/4 weld pattern, based on SDI Deck Diaphragm Design Manual, 2nd Edition) C = 3 ft (width of roof deck) P = 0.28t(d t)f u ) (Nominal uplift resistance per puddle weld, per AWS D1.3/D1.3M 2008 Structural Welding Code Sheet Steel) t = in. (thickness of 22 gauge metal roof deck) d = 5/8 in. (weld diameter) F u = 55 ksi 410 NIST NCSTAR 3, Joplin Tornado Investigation

7 Draft for Public Comment Appendix I L ଽய ଟଽயଽ ଟ ( ଽயଽ ) ଟ ଽய ଓଉଚ ଗଌଙ ଞଌଓଋ, ଇ L ௪ணப Thus, ன ய ଟ யଽ ய ଗଓ Safety factor for uplift strength of puddle weld: ௨ ய ଽ ய ய ய ଙଌଘଜଐଙଌଋ ଧ ଖଙ ଜଗଓଐଛ ଈଓଖକଌ Nominal uplift capacity of roof deck to joist connection: Note: L ௩ ய ଗଓ ய ଛ ய ଗଚ The 62.6 psf uplift capacity of the roof deck to joist connection exceeds the design uplift pressure of 26.2 psf by a safety factor of 2.4. This means a code level uplift pressure would not have caused the failure of the roof deck to joist connections (or the disconnection of the metal roof deck panels). Assuming the spatial relationship between lateral wind speed and uplift pressure in tornadoes is similar to that used in ASCE 7 standards, the 62.6 psf uplift capacity is equivalent to a lateral wind speed V = Strength based on combined uplift and shear: ASD shear and tension interaction equation for support fasteners (puddle welds): Where: த ௨௦டபண த ௨பத௧ ய ய ௨ ( ) ( ) யଽ u = 2.5 (safety factor for weld in tension) T = plf (above) T n = 1,800.7 plf (above) Q f no uplift = 2,010 lb (nominal shear strength per 5/8 in. puddle weld (tabulated in SDI manual and CDC Tables) Q f usable : Available nominal shear strength of puddle weld in the presence of an uplift force: ய Lயଅଆ L ௨ L ய ଟ ଽ ய த ௨௦டபண ( யଽ ( ) L ) ଟ த ௨பத௧ L ( யଽ ( ) ) ଟ ଽ ଽ ய ଓଉଚ ଽଽய L ய யଅଆ NIST NCSTAR 3, Joplin Tornado Investigation 411

8 Draft for Public Comment Required nominal unit shear at side walls: S n required = 552 plf (from roof bracing forces calculation above) Nominal shear strength S n of type B 1.5 in. 36 in. wide rib roof deck with 36/5 puddle weld pattern based on the SDI Deck Diaphragm Manual and CMC Joist and Deck Tables: For 5.5 ft deck span S n = 1,318 plf For 6.0 ft deck span S n = 1,230 plf Thus for L V = 5.8 ft deck span S n = 1318 ( )(0.3/0.5) = plf Available nominal deck shear strength adjusted for presence of uplift (accounting for effect of shear and tension interaction): ட௩டபடபண ( த ௨௦டபண த ௨பத௧ ) ய ( ய ଽ ଽ ) ଗଓ Factor of safety in combined shear and tension of deck to joist connection: ட௩டபடபண ய ய ண௨ண Roof deck to joist connection would not have failed under combined shear (lateral wind load) and tension (wind uplift) forces at code level wind load. However, the safety factor is slightly less than is typically required for this design. 412 NIST NCSTAR 3, Joplin Tornado Investigation

2012 Wood Frame Construction Manual: Wind Speed and Design Pressure Determination According to ASCE 7 10

2012 Wood Frame Construction Manual: Wind Speed and Design Pressure Determination According to ASCE 7 10 2012 Wood Frame Construction Manual: Wind Speed and Design Pressure Determination According to ASCE 7 10 Presented by: William L. Coulbourne, PE Copyright Materials This presentation is protected by US

More information

OVERALL STRUCTURAL SYSTEM

OVERALL STRUCTURAL SYSTEM EXECUTIVE SUMMARY The at the Pittsburgh International Airport, PA, is a 275,000 square foot multi-use building located directly adjacent to the airport s landside terminal. The building consists of an

More information

CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 2015 WFCM ENGINEERING PROVISIONS (STD342-1)

CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 2015 WFCM ENGINEERING PROVISIONS (STD342-1) CALCULATING WIND LOADS ON LOW-RISE STRUCTURES PER 015 WFCM ENGINEERING PROVISIONS (STD34-1) John Buddy Showalter, P.E. Vice President, Technology Transfer American Wood Council Description The Wood Frame

More information

A REPORT ON THE EFFECTS OF WIND SPEED ON TIMBER CONSTRUCTION JOSHUA HUENEFELD. B.S., Kansas State University, 2012 A REPORT

A REPORT ON THE EFFECTS OF WIND SPEED ON TIMBER CONSTRUCTION JOSHUA HUENEFELD. B.S., Kansas State University, 2012 A REPORT A REPORT ON THE EFFECTS OF WIND SPEED ON TIMBER CONSTRUCTION by JOSHUA HUENEFELD B.S., Kansas State University, 2012 A REPORT submitted in partial fulfillment of the requirements for the degree MASTER

More information

Calculation of Wind Loads on Structures according to ASCE 7-10

Calculation of Wind Loads on Structures according to ASCE 7-10 Calculation of Wind Loads on Structures according to ASCE 7-10 Permitted Procedures The design wind loads for buildings and other structures, including the Main Wind-Force Resisting System (MWFRS) and

More information

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1

North Shore at Canton Baltimore, MD Beau Menard Technical Report 1 North Shore at Canton Baltimore, MD Beau Menard Technical Report 1 Structural Schneider 10/05/05 Structural Concepts Executive Summary North Shore at Canton is a 4 story town home and parking garage structure

More information

Arlington, Virginia December 3, 2007 TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN

Arlington, Virginia December 3, 2007 TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN TECHNICAL REPORT III LATERAL SYSTEM ANALYSIS AND CONFIRMATION DESIGN EXECUTIVE SUMMARY The is the practice facility for the NHL franchise, Washington Capitals. It is located in Arlington, Virginia just

More information

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania

TECHNICAL REPORT 1. Structural Concepts / Structural Existing Conditions. Penn State Hershey Medical Center Children s Hospital. Hershey, Pennsylvania TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions Penn State Hershey Medical Center Children s Hospital Matthew V Vandersall The Pennsylvania State University Architectural Engineering

More information

Technical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design

Technical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design Executive Summary Technical Assignment #3 November 15, 2004 Lateral System Analysis and Confirmation Design The Food Science Building in State College, Pennsylvania is a four story above ground steel composite

More information

ROOF FRAMING ANCHORAGE FORCES: MWFRS

ROOF FRAMING ANCHORAGE FORCES: MWFRS TECHNICAL NOTE On Cold-Formed Steel Construction 1201 15th Street, NW, Suite 320 W ashington, DC 20005 (202) 785-2022 $5.00 ROOF FRAMING ANCHORAGE FORCES: MWFRS or C&C Summary: This Technical Note defines

More information

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Simplified Building Schematic for Typical Floor (Levels 9 through 22): Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid

More information

Executive Summary...2 Introduction...3 Structural System Overview Buffalo,...4 Foundation...4 Floor System...4 Gravity System...4 Lateral System...

Executive Summary...2 Introduction...3 Structural System Overview Buffalo,...4 Foundation...4 Floor System...4 Gravity System...4 Lateral System... Table of Contents University at Buffalo CTRC/Incubator Executive Summary...2 Introduction...3 Structural System Overview Buffalo,...4 New York Foundation...4 Floor System...4 Gravity System...4 Lateral

More information

Wind Load Report - Check for uplift

Wind Load Report - Check for uplift Wind Load Report - Check for uplift 1. Site & Building Data Roof Type: Gable Wind Speed (ult): 115 mph Exposure Category: C Enclosure Class: Enclosed Building Width (W): 43 ft. Building Length (L): 60

More information

INGHOUSE Page 1 of 48

INGHOUSE Page 1 of 48 INGHOUSE Page 1 of 48 Lars Jensen P.E., S.E. Web: www.inghouse.net EMAIL: jensen@inghouse.net INGHOUSE Page 2 of 48 OBJECTIVES: DESIGN OPTIONS; WHY ENGINEERED DESIGN DEVELOP AN UNDERSTANDING OF MAGNITUDE

More information

Wind Load Report - Naples Residence

Wind Load Report - Naples Residence Wind Load Report - Naples Residence 1. Site & Building Data Roof Type: Gable Wind Speed (ult): 115 mph Exposure Category: C Enclosure Class: Enclosed Building Width (W): 20 ft. Building Length (L): 23

More information

ENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa - UL2-D10-E10

ENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa - UL2-D10-E10 ENGINEERING STRUCTURAL CALCULATIONS For HiPower/Himoinsa UL2D10E10 November 16, 2016 AMPS Project Number: 20160200 Designed in compliance with: 2014 Florida Building Code 5th Edition with 2016 Supplements

More information

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS. CONTROL, NOT COMPROMISE.

Load Design Charts. R-CONTROL SIPs STRUCTURAL INSULATED PANELS.   CONTROL, NOT COMPROMISE. R-CONTROL s STRUCTURAL INSULATED PANELS Note: Information deemed reliable at time of printing. Please visit www.r-control.com for latest information. June 2012 CONTROL, NOT COMPROMISE. www.r-control.com

More information

William W. Wilkins Professional Building Columbus, Ohio

William W. Wilkins Professional Building Columbus, Ohio William W. Wilkins Professional Building Columbus, Ohio Technical Assignment 1 October 5, 2006 Michelle Structural Option AE 481W Senior Thesis Faculty Advisor: Dr. Boothby Table of Contents Executive

More information

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5

Table of Contents 2. Structural Systems.4 Foundations.4 Floor System...4 Columns..5 Lateral System...5 WISCONSIN PLACE RESIDENTIAL TECHNICAL ASSIGNMENT 1 OCTOBER 5, 2007 KURT KRASAVAGE THE PENNSYLVANIA STATE UNIVERSITY STRUCTURAL OPTION FACULTY ADVISOR: DR. ALI MEMARI Table of Contents Table of Contents

More information

Steel Roof Deck EC X

Steel Roof Deck EC X IAPMO ES Cover Sheet Evaluation Criteria of Steel Roof Deck EC 007-200 Posted for public commenting on 10/16/2009 to 11/12/2009 INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION

More information

John Jay College Expansion Project

John Jay College Expansion Project Technical Report #1 Michael Hopper Mike AE Consultant: Dr. Lepage [Type the company name] September 29 th, 2008 Technical Report #1 Table of Contents Executive Summary.3 Introduction.4 Structural System.6

More information

School of Engineering and Applied Science Building Miami University, Oxford, OH Technical Assignment 3 December 3, 2007

School of Engineering and Applied Science Building Miami University, Oxford, OH Technical Assignment 3 December 3, 2007 School of Engineering and Applied Science Building Miami University, Oxford, OH Technical Assignment 3 December 3, 2007 Jonathan Kirk AE 481W Senior Thesis The Pennsylvania State University Faculty Advisor:

More information

[TECHNICAL REPORT 3] Lateral System Analysis

[TECHNICAL REPORT 3] Lateral System Analysis Science Center Research Park 3711 Market St. The Pennsylvania State University Department of Architectural Engineering Senior Thesis 2009-2010 Prepared by: November 30, 2009 [TECHNICAL REPORT 3] Lateral

More information

Lateral System Analysis and Confirmation Design (S-3)

Lateral System Analysis and Confirmation Design (S-3) November 13, 2002 Lateral System Analysis and Confirmation Design (S-3) Executive Summary: This report summarizes the analysis of the lateral systems used in the 250 West Street building in Columbus, Ohio.

More information

Principles of STRUCTURAL DESIGN. Wood, Steel, and Concrete SECOND EDITION RAM S. GUPTA. CRC Press. Taylor& Francis Group

Principles of STRUCTURAL DESIGN. Wood, Steel, and Concrete SECOND EDITION RAM S. GUPTA. CRC Press. Taylor& Francis Group SECOND EDITION Principles of STRUCTURAL DESIGN Wood, Steel, and Concrete RAM S. GUPTA CRC Press Taylor& Francis Group Boca Raton London New York CRC Press is an imprint of the Taylor & Francis Croup, an

More information

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC.

DIVISION: METALS SECTION: METAL FASTENINGS SECTION: STEEL DECKING REPORT HOLDER: HILTI, INC. 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 43 6587 (56) 699 0543 www.icc es.org ESR 97 Reissued /7 This report is subject to renewal /8. DIVISION: 05 00 00 METALS SECTION:

More information

Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan

Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Consultant: Dr. Hanagan Point Pleasant Apartments Point Pleasant, NJ Ryan P. Flynn Structural Option Faculty Technical Report #3: Lateral System Analysis and Confirmation Design Table of Contents Introduction... 3 Executive Summary...

More information

Executive Summary Building Description: Introduction... 13

Executive Summary Building Description: Introduction... 13 Table of Contents Executive Summary... 2 Building Description:... 2 Report Summary:... 2 Introduction... 3 Building Description:... 3 Current Framing Layout... 4 Report Topics:... 4 Loads and Load Cases...

More information

The New SDI Diaphragm Design Manual

The New SDI Diaphragm Design Manual Missouri University of Science and Technology Scholars' Mine International Specialty Conference on Cold- Formed Steel Structures (2006) - 18th International Specialty Conference on Cold-Formed Steel Structures

More information

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL ROOF DECK.

INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL ROOF DECK. INTERNATIONAL ASSOCIATION OF PLUMBING AND MECHANICAL OFFICIALS, EVALUATION SERVICES EVALUATION CRITERIA FOR STEEL ROOF DECK EC 007-2010 e1 1.0 INTRODUCTION 1.1 Purpose: This criteria establishes the requirements

More information

Technical Report 1. Residence Inn By Marriott. Structural Option September 29, Existing Conditions / Structural Concepts.

Technical Report 1. Residence Inn By Marriott. Structural Option September 29, Existing Conditions / Structural Concepts. Katie Ritter Advisor: Dr. Ali Memari Structural Option September 29, 2008 Technical Report 1 Existing Conditions / Structural Concepts Residence Inn By Marriott Norfolk, Virginia 1 P age TABLE OF CONTENTS

More information

BERRIDGE SPACEFRAME BUILDING COMPONENTS DESIGN GUIDE

BERRIDGE SPACEFRAME BUILDING COMPONENTS DESIGN GUIDE BERRIDGE SPACEFRAME BUILDING COMPONENTS DESIGN GUIDE CONTENTS PROPERTIES & LOADS 24 Ga. Stud Properties & Loads... 2 Back to Back Stud Properties & Loads... 2 C-Channel Rafter Properties & Loads... 3 Load

More information

Nothing Flat About Steel Joists and Steel Deck On a Pitched Roof

Nothing Flat About Steel Joists and Steel Deck On a Pitched Roof Nothing Flat About Steel Joists and Steel Deck On a Pitched Roof APRIL 18, 2018 Copyright 2018 Steel Joist Institute. All Rights Reserved. Presented by: Ben Pitchford, P.E. Thomas Sputo, Ph.D, P.E., S.E.

More information

Florida Structural Engineers

Florida Structural Engineers Florida Structural Engineers South Florida Chapter January 8, 2008 Miami Lakes, Florida Aluminum Association of Florida, Inc. Joe Belcher ~ David Miller AAF Code Involvement: Historical Perspective 1998:

More information

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan

Brent Ellmann Structural Option 200 Minuteman Park, Andover, MA Structural Consultant: Dr. Hanagan Brief Building Overview: 200 Minuteman Park stands as a 200,000 square foot Class A office building in Andover, Massachusetts, worth roughly $15,000,000. Although the building has a large square footage,

More information

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104

DIVISION: METALS SECTION: STEEL DECKING REPORT HOLDER: EPIC METALS CORPORATION 11 TALBOT AVENUE RANKIN, PENNSYLVANIA 15104 0 Most Widely Accepted and Trusted ICC ES Evaluation Report ICC ES 000 (800) 423 6587 (562) 699 0543 www.icc es.org ESR 2047 Reissued 07/207 This report is subject to renewal 07/209. DIVISION: 05 00 00

More information

STRUCTURAL NOTES MISCELLANEOUS COLD-FORM STEEL FRAMING MASONRY SITE WORK CAST IN PLACE CONCRETE

STRUCTURAL NOTES MISCELLANEOUS COLD-FORM STEEL FRAMING MASONRY SITE WORK CAST IN PLACE CONCRETE STRUCTURAL NOTES MISCELLANEOUS COLD-FORM STEEL FRAMING MASONRY AA 0009 707 US Hwy. 9 Palm Harbor, FL 68 Phone 77. 78. 7 Fax 77. 78. 66 SITE WORK CAST IN PLACE CONCRETE OPEN WEB STEEL JOISTS AND JOIST GIRDERS

More information

111 MORGAN ST. Ryan Friis

111 MORGAN ST. Ryan Friis Technical Report No. 1 September 30, 2002 Executive Summary: 111 Morgan St. is a 9 story cast-in-place concrete condominium building being constructed in Chicago, Illinois. The building s floor system

More information

Considerations for Outof-Plane. Design

Considerations for Outof-Plane. Design Considerations for Outof-Plane Wall and Uplift Design WoodWorks Texas Workshops December, 2016 Overview Uplift Wall Design Wind Loads Wind loads acting on buildings are modeled as uniform surface loads.

More information

Butler Health System New Inpatient Tower Addition/Remodel. Dr. Ali Memari Technical Report #1. Architects Rendering. Technical Report #1

Butler Health System New Inpatient Tower Addition/Remodel. Dr. Ali Memari Technical Report #1. Architects Rendering. Technical Report #1 Dr. Ali Memari Technical Report # Architects Rendering Technical Report # Due October 5 th, 2009 Dr. Ali Memari Technical Report # Table of Contents I. Executive Summary 3 II. Introduction 4 III. Structural

More information

Originally Issued: 03/10/2017 Revised: 08/24/2018 Valid Through: 03/31/ Design

Originally Issued: 03/10/2017 Revised: 08/24/2018 Valid Through: 03/31/ Design EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue North Fort Payne, Alabama 35967 (256) 845-2460 VERCO DECKING, INC. a NUCOR

More information

STRUCTURAL TECHNICAL REPORT 1

STRUCTURAL TECHNICAL REPORT 1 Technical Report 1 Page 1 David Lee AE 481W Structural Option Advisor: Andres Lepage URS Office Building October 5, 2006 STRUCTURAL TECHNICAL REPORT 1 Structural Concepts / Structural Existing Conditions

More information

Impact of C&C loads due to ASCE/SEI Overview Revised 3/23/2017

Impact of C&C loads due to ASCE/SEI Overview Revised 3/23/2017 Impact of C&C loads due to ASCE/SEI 7-16 Overview Revised 3/23/2017 SBCA has been the voice of the structural building components industry since 1983, providing educational programs and technical information,

More information

Technical Assignment 3 December 3, 2007

Technical Assignment 3 December 3, 2007 Technical Assignment 3 December 3, 2007 101 Eola Drive, Orlando, FL Justin Raducha Pennsylvania State University Faculty Advisor: M. Kevin Parfitt Table of Contents Table of Contents... 2 Executive Summary...

More information

DIVISION 5 METALS SECTION METAL DECKING

DIVISION 5 METALS SECTION METAL DECKING DIVISION 5 METALS SECTION 05 30 00 PART 1 GENERAL 1.01 SUMMARY A. Section Includes: All labor and materials required to furnish and install metal decking and accessories including shear connectors, closures,

More information

Rutgers University Law School Building Addition and Renovation Camden, NJ

Rutgers University Law School Building Addition and Renovation Camden, NJ Building Addition and Renovation Camden, NJ Technical Assignment 1 October 5, 2007 Nathan E. Reynolds Structural Option Senior Thesis The Pennsylvania State University Faculty Consultant: Professor M.

More information

Structural Redesign Gravity System

Structural Redesign Gravity System Redesign Gravity System Design Considerations A composite floor system was used for this design to maximize the efficiency of the material being used. This type of system requires less material and provides

More information

90% Design Submittal Structural Calculations Parking Garage CDRL

90% Design Submittal Structural Calculations Parking Garage CDRL NORTH METRO RAIL LINE PROJECT Thornton Crossroads at 104 th Avenue Station 90% Design Submittal Structural Calculations Parking Garage CDRL 03-037.11.06 June 2, 2017 Prepared by: Regional Rail Partners

More information

Design of Steel Joists and Roof Decks

Design of Steel Joists and Roof Decks Design of Steel Joists and Roof Decks Michael R. Miller, P. E. Topics for Discussion Design Responsibility What is a standard joist? Assumptions Dimensions Designations Joist Design for Wind Uplift Properly

More information

Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design

Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/ Design Originally Issued: 03/10/2017 Revised: 03/30/2019 Valid Through: 03/31/2019 EVALUATION SUBJECT: STEEL DECK PANELS REPORT HOLDER NUCOR CORPORATION - VULCRAFT/VERCO GROUP VULCRAFT GROUP 7205 Gault Avenue

More information

Wood Shear Wall Design Examples For Wind

Wood Shear Wall Design Examples For Wind Wood Design Examples For Wind EARN 0.1 ICC Continuing Education Unit (CEU) and/or AIA/CES HSW 1 Learning Unit (LU) DES413-A Wood Design Examples for Wind Description: In this article, a wood frame shear

More information

Project ULA 120D Snow-0 Seis-IV

Project ULA 120D Snow-0 Seis-IV ULA Geometry Module Specification Sub-Array Configuration ULA Totals # Rows: 4 Column N-S Length (in): 6 # SubArrays: N-S Dim (in): 40 N-S Spacing (in): 0.25 # Columns: 5 Array E-W Dimension (in): 326

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 29 Ga. GulfRib Roof Panel over Florida Product Approval #11651.27 R3 Florida Building Code 2017 Per Rule 61G20-3 Method: 1 D Category:

More information

Letter of Transmittal

Letter of Transmittal Letter of Transmittal November 17, 2014 Ali Said Structural Thesis Advisor The Pennsylvania State University aus59@psu.edu Dear Doctor Said, The following technical report fulfills the fourth Technical

More information

Earth and Engineering Sciences Building University Park, Pennsylvania

Earth and Engineering Sciences Building University Park, Pennsylvania Executive Summary The Earth and Engineering Sciences building is a 4 story educational and laboratory facility. An additional basement level is located below grade and provides the foundation for the East

More information

WIND LOADS ON BUILDINGS MWFRS (ENVELOPE PROCEDURE)

WIND LOADS ON BUILDINGS MWFRS (ENVELOPE PROCEDURE) Chapter C28 WIND LOADS ON BUILDINGS MWFRS (ENVELOPE PROCEDURE) The Envelope Procedure is the former low-rise buildings provision in Method 2 of ASCE 7-05 for MWFRS. The simplified method in this chapter

More information

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS

MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS MOUNTAIN STATE BLUE CROSS BLUE SHIELD HEADQUARTERS PARKERSBURG, WEST VIRGINIA DOMINIC MANNO STRUCTURAL OPTION FACULTY CONSULTANT: DR. ANDRES LEPAGE Technical Report 3 11-21-08 TABLE OF CONTENTS TABLE OF

More information

Technical Report 1. Seneca Allegany Casino Hotel Addition. Salamanca, NY

Technical Report 1. Seneca Allegany Casino Hotel Addition. Salamanca, NY Technical Report 1 Seneca Allegany Casino Hotel Addition Salamanca, NY Nicholas Reed Structural Option Advisor: Prof. Parfitt Executive Summary The purpose of this technical report was to analyze the existing

More information

HIGH RISE CONDO SOHO, NEW YORK, NY

HIGH RISE CONDO SOHO, NEW YORK, NY HIGH RISE CONDO SOHO, NEW YORK, NY TECHNICAL ASSIGNMENT 1 October 5, 2006 Joseph The Pennsylvania State University Structural Option Faculty Advisor: Andres Lepage TABLE OF CONTENTS TABLE OF CONTENTS 2

More information

RCKW Kneewall Connectors

RCKW Kneewall Connectors This product is preferable to similar connectors because of a) easier installation, b) higher loads, c) lower installed cost, or a combination of these features. The Simpson Strong-Tie RCKW rigid connectors

More information

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report Michael A. Troxell Structural Option Advisor: Professor Parfitt College of Business Administration Oct. 5, 2005 Structural Technical Report 1 Structural Concepts / Structural Existing Conditions Report

More information

APPENDIX. WOOD JOIST/RAFTER MAXIMUM SPANS ( for 16 o.c. spacing) WITH SINGLE ROW OF PV PANELS AT MIDSPAN (ft.) AND PANEL SUPPORT AT 32 o.c.

APPENDIX. WOOD JOIST/RAFTER MAXIMUM SPANS ( for 16 o.c. spacing) WITH SINGLE ROW OF PV PANELS AT MIDSPAN (ft.) AND PANEL SUPPORT AT 32 o.c. 1 Span Tables The following Wood Joist/Rafter Maximum Span Tables can be used to determine the adequacy of an existing wood framed roof structure to support the additional dead load created by PV panel

More information

Joseph L. Oliveri, AIA

Joseph L. Oliveri, AIA c < < < < < < Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA PARKING BY DISABLED PERMIT ONLY $ xxx FINE F.S. 318.14 Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA Joseph L. Oliveri, AIA Joseph L. Oliveri,

More information

Structural Calculations Amphitheater Middle School Building 400 AC Replacement 315 E. Prince Rd., Tucson, Arizona

Structural Calculations Amphitheater Middle School Building 400 AC Replacement 315 E. Prince Rd., Tucson, Arizona Structural Calculations Amphitheater Middle School Building 400 AC Replacement 315 E Prince Rd, Tucson, Arizona Prepared for: Amphitheather Public Schools SCI Project No 17-167A SCI Project No 17-167A

More information

Lateral System Analysis and Confirmation Design November 15, 2004

Lateral System Analysis and Confirmation Design November 15, 2004 Jonathan Hill Structural AE Faculty Consultant Dr. Hanagan Lynde and Harry Bradley School of Technology & Trade Milwaukee, Wisconsin Lateral System Analysis and Confirmation Design November 15, 2004 Executive

More information

Belmont Executive Center; Building A

Belmont Executive Center; Building A Nicholas L. Ziegler: Structural Advisor: Professor M. Kevin Parfitt December 1, 2009 1 Table of Contents Executive Summary...3 Introduction...3 Structural System...4 Foundation System... 4 Column System...

More information

Check the strength of each type of member in the one story steel frame building below.

Check the strength of each type of member in the one story steel frame building below. CE 331, Summer 2015 nalysis of Steel Braced Frame Bldg 1 / 9 Check the strength of each type of member in the one story steel frame building below. 4 @ 8 ft B 20 f 1 2 3 @ 25 ft Side Elevation 3 4 Plan

More information

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER

Design Manual and Catalog of Steel Deck Products STEEL DECK INSTITUTE MEMBER Design Manual and Catalog of Steel Deck Products s STEEL DECK INSTITUTE MEMBER Manufacturers of products History CMC Joist & Deck is a leading producer of steel deck, open-web steel joists, long span steel

More information

1000 CONNECTICUT AVENUE

1000 CONNECTICUT AVENUE 1000 CONNECTICUT AVENUE Gea Johnson Structural Option Faculty Advisor: Dr. Hanagan September 23, 2011 Revised: December 16, 2011 Washington DC Technical : Existing Conditions Table of Contents Executive

More information

Technical Report #3: Lateral System Analysis. Executive Summary

Technical Report #3: Lateral System Analysis. Executive Summary ERIC MUELLER STRUCTURAL OPTION ADVISOR DR. LEPAGE AE 481W DECEMBER 19, 2006 555 12 TH STREET OAKLAND, CALIFORNIA Technical Report #3: Lateral System Analysis Executive Summary 555 12 th Street is a 21

More information

Metal Roof Certification & Listing Program

Metal Roof Certification & Listing Program 145 Limekiln Road, Suite 100B Issue Dated: 10/27/2017 New Cumberland, PA 17070 Revision Date: 10/27/2017 www.keystonecerts.com Expiration Date: 10/27/2022 Construction Specifications Institute (CSI) Category:

More information

16.4 FLORIDA BUILDING CODE BUILDING

16.4 FLORIDA BUILDING CODE BUILDING 1604.8-1606.1.2 5. Designs using NAAMM FP-1001 Specification for Design Loads of Metal Flagpoles. 6. Subject to the limitations of 1606.1.1.1, 1606.1.4, and 1606.1.6, the provisions of the FC&PA Guide

More information

Lateral Design of Mid- Rise Wood Structures

Lateral Design of Mid- Rise Wood Structures Lateral Design of Mid- Rise Wood Structures Presented by Ricky McLain, MS, PE, SE Technical Director WoodWorks Texas Workshops December, 2016 Insert picture of me graduating college Follow the load Following

More information

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA

Danielle Shetler - Structural option Courtyard by Marriott Lancaster, PA Structural Analysis Overview: During the structural analysis of the in Lancaster, Pa, a redesign of the lateral and gravity system from masonry bearing and shear walls to a staggered truss system was performed.

More information

5 Load Determination and Structural Design Criteria

5 Load Determination and Structural Design Criteria 5 Load Determination and Structural Design Criteria This chapter presents a summary of previous research and testing and outlines the recommended methods and criteria for use in the structural design of

More information

Park Potomac Office Building E

Park Potomac Office Building E Technical Assignment 1 Kyle Wagner (IP) AE Consultant: Professor Kevin Parfitt October 05, 2009 Table of Contents I. Executive Summary 3 II. Introduction... 4 III. Structural System Overview..... 4 Foundation

More information

Boyds Bear Country Pigeon Forge, TN

Boyds Bear Country Pigeon Forge, TN Technical Report 3 Lateral System Analysis and Confirmation Design Executive Summary:, located in Pigeon Forge, Tennessee, is designed as a multifunctional space and tourist attraction for Boyds Collections

More information

Marconi Communications Building #5 Warrendale, Pennsylvania

Marconi Communications Building #5 Warrendale, Pennsylvania Kelly Hellyer November 14, 2003 Structural Technical Assignment #1 Structural Concepts / Structural Existing Conditions Report Table of Contents Description Page(s) Executive Summary 1 Introduction & Design

More information

Structural Technical Report #1 By Robert Whitaker

Structural Technical Report #1 By Robert Whitaker Structural Technical Report #1 By Robert Whitaker Robert Whitaker Structural ~ Parfitt Parkview at Bloomfield Station Bloomfield, NJ 10-05-05 Executive summary This report covers the structural concepts

More information

WESTINGHOUSE ELECTRIC COMPANY CORPORATE HEADQUARTERS CRANBERRY, PA

WESTINGHOUSE ELECTRIC COMPANY CORPORATE HEADQUARTERS CRANBERRY, PA WESTINGHOUSE ELECTRIC COMPANY CORPORATE HEADQUARTERS CRANBERRY, PA Technical Assignment 3 November 21, 2008 Advisor: Dr. Linda Hanagan Page 2 of 57 TABLE OF CONTENTS EXECUTIVE SUMMARY... 3 INTRODUCTION...

More information

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC.

ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC. ANALYSIS AND DESIGN OF MOMENT RESISTING MIDWALL BY THE STEEL NETWORK, INC. Paul Lackey, P.E., Muhammad Ghoraba, Nabil A. Rahman, Ph.D., P.E. and Kurtis Kennedy MidWall is a hold-down product intended to

More information

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2

research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-2 research report Cold-Formed Steel Gable End Wall Design Using the Prescriptive Method for One and Two Family Dwellings RESEARCH REPORT RP05-005 REVISION 006 American Iron and Steel Institute Cold-Formed

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #11651.22 R3 Florida Building Code 2017 Per Rule 61G20-3 Method:

More information

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R2. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL GULFRIBTM FLORIDA PRODUCT APPROVAL NO R2. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 29 Ga. GulfRib Roof Panel over 15/32 Plywood Florida Product Approval #16646.1 R2 Florida Building Code 2017 Per Rule 61G20-3 Method: 1

More information

FLORIDA PRODUCT APPROVAL 5VCRIMP FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC.

FLORIDA PRODUCT APPROVAL 5VCRIMP FLORIDA PRODUCT APPROVAL NO R3. Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 GA. ROOF PANEL OVER 15/32 PLYWOOD Product Evaluation Report GULF COAST SUPPLY & MANUFACTURING, LLC. 26 Ga. 5V Crimp Roof Panel over 15/32 Plywood Florida Product Approval #11651.13 R3 Florida Building

More information

The Carport - Bryan, Texas

The Carport - Bryan, Texas This is going to be an exciting presentation that is of great interest to me. The carport of my house was rotten and falling down and needed to be replaced. I m going to give you all the information you

More information

DESIGNING WITH STEEL FORM DECK

DESIGNING WITH STEEL FORM DECK DESIGNING WITH STEEL FORM DECK All rights reserved 2003 P.O. Box 25 Fox River Grove, IL 60021 Phone: (847) 458-4647 Fax: (847) 458-4648 Form deck is a term used to describe deck that is most frequently

More information

LATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES

LATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES LATERAL LOADS ON BRICK VENEER RESIDENTIAL STRUCTURES W. Mark McGinley 1, PhD, PE and Eric N. Johnson 2, PE ABSTRACT In North American residential construction, brick veneer is typically used as a cladding

More information

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year.

ICC-ES Evaluation Report Reissued June 1, 2010 This report is subject to re-examination in one year. ICC-ES Evaluation Report ESR-409 Reissued June, 00 This report is subject to re-examination in one year. www.icc-es.org (800) 4-6587 (56) 699-054 A Subsidiary of the International Code Council DIVISION:

More information

Structural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report

Structural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report 1 THE ODYSSEY ARLINGTON, VA Aaron Snyder Structural Option Advisor: M. Kevin Parfitt, PE Structural Technical Report I October 5, 2006 Structural Concepts / Structural Existing Conditions Report Executive

More information

November 16, The Pennsylvania State University. Hunter Woron Structural. Professor M. Kevin Parfitt

November 16, The Pennsylvania State University. Hunter Woron Structural. Professor M. Kevin Parfitt November 16, 2011 Hunter Woron Structural Professor M. Kevin Parfitt The Pennsylvania State University Table of Contents Executive Summary 2 Introduction 3 Structural System Summary 4 ETABS Model 9 Codes

More information

Structural Concepts and Existing Conditions Report

Structural Concepts and Existing Conditions Report Daniel Chwastyk F.W. Olin Center Louis Geschwindner Advisor Structural Concepts and Existing Conditions Report Executive Summary The following report discusses many of the structural concepts that were

More information

WIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008

WIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008 2008 EDITION ANSI/AF&PA SDPWS-2008 Approval Date: August 4, 2008 ASD/LRFD WIND & SEISMIC Special Design Provisions for Wind and Seismic WITH COMMENTARY American Forest & Paper Association Updates and Errata

More information

STRUCTURAL CALCULATIONS EXTERIOR SIDING CLADDING SYSTEM FLUSH PANEL SIDING SYSTEM AND LAPPED PANEL SIDING SYSTEM

STRUCTURAL CALCULATIONS EXTERIOR SIDING CLADDING SYSTEM FLUSH PANEL SIDING SYSTEM AND LAPPED PANEL SIDING SYSTEM JN 3617 Page 1 of 27 NOTES ON ANALYSIS, DESIGN METHOD, BUILDING CODE REFERENCES, AND ASSUMPTIONS. The exterior phenolic panel siding system is classified under the International Building Code as a Non-

More information

WIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008

WIND & SEISMIC 2008 EDITION ASD/LRFD WITH COMMENTARY. American Forest & Paper Association. American Wood Council ANSI/AF&PA SDPWS-2008 2008 EDITION ANSI/AF&PA SDPWS-2008 Approval Date: August 4, 2008 ASD/LRFD WIND & SEISMIC Special Design Provisions for Wind and Seismic WITH COMMENTARY American Forest & Paper Association American Wood

More information

SE APPRENTICE. Stephen Metz PE, LEED AP. Today s Speakers. Company Overview. Company Overview 10/13/2015. SE Apprentice. Who We Are.

SE APPRENTICE. Stephen Metz PE, LEED AP. Today s Speakers. Company Overview. Company Overview 10/13/2015. SE Apprentice. Who We Are. Today s Speakers Carrie Bremer, PE Schaefer Stephen Metz, PE SMBH, Inc. Today s Moderators SE APPRENTICE Lecture One Loads Lisa Willard, PE SE Solutions, LLC SE Apprentice Brian Quinn, PE SE Solutions,

More information

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604.

Lateral load basics Code acceptance of Standard. Standard Overview 2008 Wind & Seismic Standard. Wind. Wind Load Path. IBC Section 1604. Outline 2005/2008 Special Design Provisions for Wind & Seismic Standard Lateral load basics Code acceptance of Standard 2005/2008 Wind & Seismic Standard Overview 2008 Wind & Seismic Standard John Buddy

More information

Copyright Materials. American Wood Council

Copyright Materials. American Wood Council 2012 Wood Frame Construction Manual: Foundation Design to Resist Flood Loads and WFCM Calculated Wind Loads Presented by: William L. Coulbourne, PE 2 Copyright Materials This presentation is protected

More information

ML200 Panel Technical Data Guide

ML200 Panel Technical Data Guide Description ML200 is a mechanical seamed standing seam roofing panel used on low to steep sloped commercial applications. The panel is factory formed in continuous lengths up to 60-0 long. Attachment to

More information

Hilton Baltimore Convention Center Hotel Western Podium

Hilton Baltimore Convention Center Hotel Western Podium Hilton Baltimore Convention Center Hotel Western Podium CHRIS SIMMONS Structural Option Faculty Consultant: Dr. Ali M. Memari Technical Report 1 TABLE OF CONTENTS EXECUTIVE SUMMARY. Page 3 INTRODUCTION..

More information