For. Report of Geotechnical Exploration. Beaver St Lane Ave to Carnegie St Trans Water Main Project Jacksonville, FL

Size: px
Start display at page:

Download "For. Report of Geotechnical Exploration. Beaver St Lane Ave to Carnegie St Trans Water Main Project Jacksonville, FL"

Transcription

1 Report of Geotechnical Exploration For Beaver St Lane Ave to Carnegie St Trans Water Main Project Jacksonville, FL MAE Project No March 30, 2017 Prepared for: CPH, Inc Belfort Road, Suite 220 Jacksonville, FL Prepared by: Phone (904) Fax (904)

2 March 30, 2017 CPH, Inc Belfort Road, Suite 220 Attention: Reference: Mr. Wade Olszewski, P.E. Report of Geotechnical Exploration Beaver St Lane Ave to Carnegie St Trans Water Main Project Jacksonville, Florida MAE Project No Dear Mr. Olszewski: Meskel & Associates Engineering, LLC has completed a geotechnical exploration for the subject project. Our work was performed in general accordance with our revised proposal dated, December 19, The geotechnical exploration was performed to evaluate the encountered subsurface conditions along the proposed pipeline route and to provide recommendations to support design of the proposed pipeline construction. A summary of our findings is presented below for your convenience; however, we recommend that this report be considered in its entirety. In general, beneath the surficial topsoil and asphalt surfaces, our borings encountered fine sands with silt, clayey and silty fine sands to the boring termination depths of up to 10-feet below existing grade. We do not recommend these clayey soils for pipe/structure subgrade or structural backfill. Groundwater was encountered and recorded 24-hours after drilling at depths between 1-foot 7inches and 3-foot 4-inches. Provided site preparation is performed in accordance with the recommendations presented in this report, it is our opinion that the soils encountered at the boring locations are adaptable for support of the proposed pipeline construction. We appreciate this opportunity to be of service as your geotechnical consultant on this phase of the project. If you have any questions, or if we may be of any further service, please contact us. Sincerely, MESKEL & ASSOCIATES ENGINEERING, LLC MAE FL Certificate of Authorization No W. Josh Mele, E.I. Staff Engineer Distribution: Mr. Wade Olszewski, P.E. CPH, Inc. Phone: (904) Fax: (904) Digitally signed by Joey J Joey J Broussard Date: Broussard 13:52:51-04'00' Joey Broussard, P.E. Director of Geotechnical Engineer Registered, Florida No copies; 1 pdf

3 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No TABLE OF CONTENTS Subject Page No. 1.0 PROJECT INFORMATION General Project Description FIELD EXPLORATION SPT and Auger Borings Field Permeability Test LABORATORY TESTING Visual Classification Soil Index Tests Constant Head Test GENERAL SUBSURFACE CONDITIONS General Soil Profile Groundwater Level Soil Survey Data USDA Seasonal High Groundwater Level Permeability Test Results DESIGN RECOMMENDATIONS General Pipeline Support Recommendations SITE PREPARATION AND EARTHWORK RECOMMENDATIONS Clearing Temporary Groundwater Control Preparation of Pipe Bedding Soils Compaction of Pipe Bedding Soil Excavation Protection Pipe Backfill Placement and Compaction QUALITY CONTROL TESTING REPORT LIMITATIONS... 8 Phone: (904) Fax: (904) Page i

4 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No FIGURES Figure 1. Figure 2. Figure 3. Site Location Map Boring Location Plan Generalized Soil Profiles APPENDICES Appendix A. Appendix B. Soil Boring Logs Field Exploration Procedures Key to Boring Logs Key to Soil Classification Laboratory Data Laboratory Test Procedures Phone: (904) Fax: (904) Page ii

5 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No PROJECT INFORMATION 1.1 General Project information was provided to us by Mr. Wade P. Olszewski, P.E., with CPH, Inc. We were provided with the following project documents for review and reference: Plan and Profile sheet for the subject project prepared by JEA, last dated May 2014 (Sheet 1) Scope of work for the geotechnical services prepared by CPH (CPH proposal to JEA dated December 8, 2016) 1.2 Project Description The site for the subject project is located on Beaver Street (between Lane Avenue and Carnegie Street) in Jacksonville, Florida. The general site location is shown on Figure 1. Based on the provided information and our discussions with Mr. Olszewski, it is our understanding the proposed project includes the construction of approximately 425 LF of a 20-inch PVC and DI Water Main. It is understood that the water main will be installed by conventional open cut along the south side of Beaver Street within the ROW. It is further understood that the canal crossing will be supported by the existing bridge and with hangers. 2.0 FIELD EXPLORATION A field exploration was performed on March 1, A copy of the plan provided to us, which shows the approximate boring locations, is included as the Boring Location Plan, Figure 2. The boring locations were determined in the field by our personnel using taped measurements from existing roadways and survey controls adjacent to the site, and should be considered approximate. 2.1 SPT and Auger Borings To explore the subsurface conditions within the area of the proposed pipeline, we located and performed 1 Standard Penetration Test (SPT) boring, drilled to a depth of approximately 10 feet below the existing ground surface, in general accordance with the methodology outlined in ASTM D Split-spoon soil samples recovered during performance of the borings were visually described in the field and representative portions of the samples were transported to our laboratory for further evaluation. To further explore the subsurface conditions within the area of the proposed pipeline transit and to determine the subsurface conditions beneath the existing pavement (asphalt and base course), we located and performed 2 auger borings, drilled to depths of approximately 3-1/2 feet (C-1) and 7 feet (B-2) below the existing ground surface in general accordance with the methodology outlined in ASTM D Representative soil samples also were recovered from the auger borings and returned to our laboratory for further evaluation. A summary of the field procedures is included in Appendix A. 2.2 Field Permeability Test A field permeability test was performed adjacent to the SPT boring (B-1) location. The field permeability test was performed by installing a solid-walled, open-bottom PVC casing snugly fit into Phone: (904) Fax: (904) Page 1

6 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No a 4-inch diameter, 8 foot deep auger borehole. The bottom 1.5 feet of the pipe was screened, and the pipe was then raised one foot above the bottom of the borehole. The pipe was filled to the top with water. The test was conducted as a "falling head" test in which the drop in the water level with respect to the top of the casing was recorded over a 30 -minute period. 3.0 LABORATORY TESTING 3.1 Visual Classification Representative soil samples obtained during our field exploration were visually classified by a geotechnical engineer using the AASHTO Soil Classification System in general accordance with ASTM D A Key to the Soil Classification System is included in Appendix A. 3.2 Soil Index Tests Quantitative laboratory testing was performed on selected samples of the soils encountered during the field exploration. The purpose of the testing was to better define their composition and to provide data for correlation to their anticipated strength and compressibility characteristics. The laboratory testing determined the following soil physical characteristics: The percent passing the US Sieve No. 200 (percent fines) The natural moisture content The results of the soil index tests are shown in the Summary of Laboratory Test Results included in Appendix B. These results are also shown on the Generalized Soil Profiles, Figure 3 and on the Log of Boring records, which are included in Appendix A, at the respective depths from which the tested samples were recovered. 3.3 Constant Head Test The horizontal permeability of the soil adjacent to auger boring B-2 was determined using the Constant Head Method. A bulk sample was obtained from this location and returned to our lab and the test was performed in general accordance with the procedure outlined in the latest revision of ASTM D GENERAL SUBSURFACE CONDITIONS 4.1 General Soil Profile Graphical presentation of the generalized subsurface conditions is presented on Figure 3. Detailed boring records are included in Appendix A. When reviewing these records, it should be understood that the soil conditions will vary between the boring locations. In general, beneath a surficial topsoil layer measuring 4 to 5-inches in thickness (an asphalt layer measuring 12-1/4 inches thick at C-1 location), the borings encountered fine sands with silt (A-3) up to 1-1/4 to 3-1/2 feet below existing grade. This was followed by clayey fine sands (A-2-6, A-6) to about 8 feet in depth, underlain by silty fine sands (A-2-4) to the boring (B-1) termination depth of 10 feet below existing grade. The relative densities of the soils encountered at the B-1 location range from loose to medium dense. Phone: (904) Fax: (904) Page 2

7 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No Groundwater Level The groundwater level was encountered at each of the boring locations and recorded at the time of drilling at depths varying from 1-foot 7-inches to 3-feet 4-inches below the existing ground surface. However, it should be anticipated that the groundwater levels will fluctuate seasonally and with changes in climate. As such, we recommend that the water table be verified prior to construction. Measured groundwater levels are shown the boring profiles and boring logs. 4.3 Soil Survey Data USDA The results of a review of the USDA Soil Conservation Service (SCS) Web Soil Survey of Duval County are shown in the table below. The soil type, drainage class, hydrologic group, and estimated seasonal high groundwater levels reported in the Soil Survey are as follows: Soil No. Soil Type Drainage Class Hydrologic Group Depth to the Water Table (1) (inches) 63 Sapelo fine sand, 0 to 2 percent slopes Poorly Drained B/D 6 to Surrency loamy fine sand, 0 to 2 percent slopes, frequently flooded Very Poorly Drained B/D 0 to 6 (1) The Water table above refers to a saturated zone in the soil which occurs during specified months, typically the summer wet season. Estimates of the upper limit shown in the Web Soil Survey are based mainly on observations of the water table at selected sites and on evidence of a saturated zone, namely grayish colors (redoximorphic features) in the soil. A saturated zone that lasts for less than a month is not considered a water table. 4.4 Seasonal High Groundwater Level In estimating seasonal high groundwater level, a number of factors are taken into consideration including antecedent rainfall, soil redoximorphic features (i.e., soil mottling), stratigraphy (including presence of hydraulically restrictive layers), vegetative indicators, effects of development, and relief points such as drainage ditches, low-lying areas, etc. Based on our interpretation of the current site conditions, including the boring logs and review of published data, we estimate the seasonal high groundwater levels at the site to be generally 1.5 to 2 feet above the water levels measured at the time of our field work. It is possible that higher groundwater levels may exceed the estimated seasonal high groundwater level as a result of significant or prolonged rains. Therefore, we recommend that design drawings and specifications account for the possibility of groundwater level variations, and construction planning should be based on the assumption that such variations will occur. 4.5 Permeability Test Results As part of this exploration, we performed a falling head field permeability test near the location of boring B1, and we performed a laboratory constant head test on a bulk sample of soils obtained from the near-surface soils encountered in boring B2. The procedures used to perform the tests were presented in previous report sections. The results of our permeability testing are presented below: Phone: (904) Fax: (904) Page 3

8 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No Permeability Testing Results Location Depth * (Ft) Coefficient of Permeability (cm/sec) Test Type B x 10-5 Falling Head Field Test B x 10-4 Constant Head Laboratory Test * Below Existing Ground Surface 5.0 DESIGN RECOMMENDATIONS 5.1 General The following evaluation and recommendations are based on the provided project information as presented in this report, results of the field exploration and laboratory testing performed, and the construction techniques recommended in Section 6.0 below. If the described project conditions are incorrect or changed after this report, or subsurface conditions encountered during construction are different from those reported, MAE should be notified so these recommendations can be re-evaluated and revised, if necessary. We recommend that MAE review the plans and earthwork specifications to verify that the recommendations contained in this report have been properly interpreted and implemented. 5.2 Pipeline Support Recommendations It is our understanding that the majority of the soil-supported portion of the 20-inch diameter pipeline will have an invert elevation that is about 5 feet or less below the existing ground surface. Based on the results of the subsurface exploration and laboratory testing as discussed in this report, we consider the subsurface conditions at the site adaptable for supporting the proposed pipeline when constructed upon properly prepared subgrade soils. We note that the majority of the soil-supported portion of the pipeline will bear within or near clayey fine sands. We do not recommend this material for direct support of the pipeline. We recommend pipe bedding consist of one foot of over-excavation (below pipe invert elevation) where the invert elevation is in or within 1-foot of clayey fine sands. The resulting excavation should be lined with a geotextile fabric, such as a Mirafi 650X or equivalent, then backfilled to the planned invert elevation with compacted FDOT No. 57 stone, with the fabric wrapped over the top of the compacted gravel. The intent of the fabric wrapped compacted gravel bedding is to provide for a more stable and uniform bedding material, and to reduce the potential for the creation of excessive pore water pressures within the saturated clayey sands. We do not recommend clayey soils for use as pipe backfill. These soils should be separated from the other soils during excavation and stockpiled for removal from the site. Assuming the project information as understood at the beginning of this report is correct, and provided the site preparation and earthwork construction recommendations outlined in Section 6.0 of this report are performed, the following parameters may be used for design. Phone: (904) Fax: (904) Page 4

9 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No Lateral Pressure Design Parameters Below-grade structures that are backfilled on one side and restrained against rotation at the top, should be designed to resist lateral pressures from soil and groundwater based on the following equivalent fluid unit weights: Above Water Table - Equivalent Fluid Density 60 lb/ ft 3 Below Water Table - Equivalent Fluid Density 90 lb/ ft 3 For the design of lateral loads on underground structures, we recommend that the groundwater level be assumed to be at the ground surface. Lateral pressure distributions in accordance with the above do not take into account forces from construction equipment, wheel loads or other surcharge loads. To account for this loading, a pressure equal to 0.5 times the anticipated surface surcharge should be applied over the full height of all walls Resisting Lateral Forces Horizontal forces that act on pipeline structures such as thrust and anchor blocks can be resisted to some extent by the earth pressures that develop in contact with the buried perpendicular face of the block structure, and by shearing resistance mobilized along the block structures base and subgrade interface. Allowable passive earth pressure resistance may be determined using the following equivalent fluid densities: Above Water Table - Equivalent Fluid Density 100 lb/ft 3 Below Water Table - Equivalent Fluid Density 60 lb/ft 3 A factor of safety of 3 was used for the above values. It is assumed the block structures are surrounded by well compacted structural backfill, as described in Section 6.6 below, extending at least 5 feet horizontally beyond the vertical bearing face. In addition, it is presumed that the block structures can withstand horizontal movements on the order of 0.5-inch before mobilizing full passive resistance. The allowable sliding shearing resistance mobilized along the base of the block structure may be determined by the following formula: Where: P = 1 / 3V tan ( 2 / 3 ɸ) P = Allowable shearing resistance force V = Net vertical force (total weight of block and soil overlying the structure minus hydrostatic uplift forces) ɸ = Angle of internal friction = 30 The following unit weights can be used to calculate the weight of the overburden soil: Compacted Moist Soil 110 lb/ ft 3 Saturated Soil 120 lb/ ft Hydrostatic Uplift Resistance It is anticipated that the buried structures will exert little or no net downward pressure on the soils; rather, the structures may be subject to hydrostatic uplift pressure when empty. Underground structures should be designed to resist hydrostatic uplift pressures appropriate for their depth below final grade and the seasonal high groundwater table. Hydrostatic uplift forces can be resisted by: Phone: (904) Fax: (904) Page 5

10 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No Addition of dead weight to the structure. Mobilizing the dead weight of the soil surrounding the structure through extension of footings outside the perimeter of the structure. A moist compacted soil unit weight of 110 lb/ft 3 may be used in designing structures to resist buoyancy Thrust Block Soil Bearing Pressure The maximum allowable net soil bearing pressure for use in design of thrust blocks should not exceed 2,000 psf. Net bearing pressure is defined as the soil bearing pressure at the foundation bearing level in excess of the natural overburden pressure at that level. The structure should be designed based on the maximum load that could be imposed by all loading conditions. The structure should bear in either compacted suitable natural soils or compacted structural fill. The bearing level soils, after compaction, should exhibit densities equivalent to 95 percent of the modified Proctor Maximum Dry Density (ASTM D 1557, AASHTO T-180), to a depth of at least one foot below the bearing level. If clayey soils are encountered at bearing level, then the bearing level soils should be over-excavated to a depth of at least 12 inches and backfilled with compacted crushed stone (i.e., FDOT No. 57 stone), 6.0 SITE PREPARATION AND EARTHWORK RECOMMENDATIONS Site preparation as outlined in this section should be performed to provide more uniform pipe bearing conditions, and to reduce the potential for post-construction settlements of the planned pipelines and associated structures. 6.1 Clearing Prior to construction, the location of existing underground utility lines within the construction area should be established. Provisions should then be made to relocate interfering utilities to appropriate locations. It should be noted that if underground pipes are not properly removed or plugged, they may serve as conduits for subsurface erosion which may subsequently lead to excessive settlement of overlying structures or pavements. We understand that the alignment of the new pipe will be beneath the existing roadway shoulder. Initial site preparation should therefore consist of removing the existing paved shoulder, and any adjacent topsoils within the proposed trenching area. This material is not suitable for pipe backfill, and should be removed from the site. We note that the core sample of the existing asphalt obtained within the existing shoulder consisted of 12 ¼ inches of asphaltic concrete, which was underlain by fine sand with silt. 6.2 Temporary Groundwater Control The groundwater level was encountered at the boring locations at depths varying from1 foot 7 inches to 3 feet 4 inches below the existing ground surface at the time of our exploration. Because of the need for excavation to the pipeline invert and manhole bottom elevations, followed by compaction of the bedding and backfill soils, it may be necessary to install temporary groundwater control measures to dewater the area to facilitate the excavation and compaction processes. The groundwater control measures should be determined by the contractor but could consist of sumps or wellpoints (or a combination of these or other methods) capable of lowering the Phone: (904) Fax: (904) Page 6

11 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No groundwater level to at least 3 feet below the required depth of excavation. The dewatering system should not be decommissioned until excavation, compaction, and fill placement is complete, and sufficient deadweight exists on the pipe and associated structures to prevent uplift. 6.3 Preparation of Pipe Bedding Soils Each of the borings encountered a relatively thin veneer of surficial fine sands with silt (classified as A-3 on the attached Boring Logs. These materials are suitable for reuse as pipe backfill provided that they are placed and compacted as discussed in the sections below. Beneath the near-surface layer of fine sands with silt, the borings encountered clayey materials (classified as A-2-6 and A-6 on the attached Boring Logs). These soils are not considered suitable for support of the pipeline at the invert elevation (pipe bedding), structural bearing levels, or as pipe backfill. Organic soils as encountered at this boring that are within 12 inches of the pipe invert should be removed to a depth of at least 12 inches below the pipe invert elevation, and should be replaced with fabric-wrapped compacted crushed stone as described in Section 6.6 below. The purpose of this is to provide more uniform bearing conditions, and to reduce the potential for post construction settlements of the pipeline. 6.4 Compaction of Pipe Bedding Soil After installing the temporary groundwater control measures, and achieving the required depth of excavation, the exposed sandy soil surface should be compacted using hand-operated equipment. Typically, the material should exhibit moisture contents within ±2 percent of the modified Proctor optimum moisture content (AASHTO T-180) during the compaction operations. Compaction should continue until densities of at least 98 percent of the modified Proctor maximum dry density (AASHTO T-180) have been achieved within the upper one foot below the exposed surface within the pipeline excavation. In areas where clayey soils are encountered at (or within 12 inches of) the pipe invert depth, 12- inches of the clayey material should be removed from below the planned invert elevation. The resulting excavation should be lined with a geotextile fabric, such as a Mirafi 650X or equivalent, then backfilled to the planned invert elevation with compacted FDOT No. 57 stone, with the fabric wrapped over the top of the compacted gravel. The intent of the fabric wrapped compacted gravel bedding is to provide for a more stable and uniform bedding material, and to reduce the potential for the creation of excessive pore water pressures within the saturated clayey sands. Should the bearing level soils experience pumping and soil strength loss during the compaction operations, compaction work should be immediately terminated and (1) the disturbed soils removed and backfilled with dry structural fill soils that are then compacted, or (2) the excess moisture content within the disturbed soils allowed to dissipate before recompacting. Care should be exercised to avoid damaging any nearby structures while the compaction operations are underway. Compaction should cease if deemed detrimental to adjacent structures. 6.5 Excavation Protection Excavation work for the water main construction will be required to meet OSHA Excavation Standard Subpart P regulations for Type C Soils. The use of excavation support systems will be necessary where there is not sufficient space to allow the side slopes of the excavation to be laidback to at least 2H:1V (2 horizontal to 1 vertical) to provide a safe and stable working area and to facilitate adequate compaction along the sides of the excavation. In addition, it should be anticipated that an excavation Phone: (904) Fax: (904) Page 7

12 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No support system may be necessary to protect adjacent existing structures, pavement and/or utilities that are located along the proposed pipeline alignment. The method of excavation support should be determined by the contractor but can consist of a trench box, drilled-in soldier piles with lagging, interlocking steel sheeting or other methods. The support structure should be designed according to OSHA sheeting and bracing requirements by a Florida licensed Professional Engineer. Where pipeline excavations and the construction of excavation support systems are within 50 feet of existing structures, the existing structures should be monitored for adverse reactions to construction vibrations and dewatering activities. 6.6 Pipe Backfill Placement and Compaction Structural backfill placed within the pipeline excavation, and in areas in which over-excavation of unsuitable soils is required below the pipeline invert elevation, should be placed in loose lifts not exceeding six inches in thickness and compacted using hand-operated compaction equipment. This procedure should continue until the backfill elevation is 12 inches above the top of the pipe. At elevations greater than 12 inches above the top of pipe, structural backfill may be placed in loose lifts not exceeding 12 inches in thickness and compacted by hand-operated compaction equipment. Structural backfill is defined as a non-plastic, granular soil having less than 10 percent material passing the No. 200 mesh sieve and containing less than 4 percent organic material. The sandy soils (A-3) meeting the properties given above, as encountered in the borings, may be used as backfill; however, we note that this material was encountered in limited quantities at the boring locations. Typically, the backfill material should exhibit moisture contents within ±2 percent of the modified Proctor optimum moisture content (AASHTO T-180) during the compaction operations. Compaction should continue until densities of at least 98 percent of the modified Proctor maximum dry density (AASHTO T-180) have been achieved within each lift of compacted structural backfill. In areas where existing pavements are removed, we recommend matching existing grades with fulldepth asphalt, placed and compacted in accordance with applicable FDOT requirements. 7.0 QUALITY CONTROL TESTING A representative number of field in-place density tests should be made in the upper 2 feet of compacted pipe or structure bedding soils, and in each lift of compacted backfill. The density tests are considered necessary to verify that satisfactory compaction operations have been performed. We recommend density testing be performed at a minimum of one location for every 300 feet of pipeline. 8.0 REPORT LIMITATIONS This report has been prepared for the exclusive use of CPH, Inc. and their clients for specific application to the design and construction of the Beaver St Lane Ave to Carnegie St Trans Water Main project. An electronically signed and sealed version, and a version of our report that is signed and sealed in blue ink, may be considered an original of the report. Copies of an original should not be relied on unless specifically allowed by MAE in writing. Our work for this project was performed in accordance with generally accepted geotechnical engineering practice. No warranty, express or implied, is made. The analyses and recommendations contained in this report are based on the data obtained from the borings performed for this project. This testing indicates subsurface conditions only at the specific locations and times, and only to the depths explored. These results do not reflect subsurface Phone: (904) Fax: (904) Page 8

13 Beaver St Lane Ave to Carnegie St Trans Water Main Project MAE Report No variations that may exist away from the boring locations and/or at depths below the boring termination depths. Subsurface conditions and water levels at other locations may differ from conditions occurring at the tested locations. In addition, it should be understood that the passage of time may result in a change in the conditions at the tested locations. If variations in subsurface conditions from those described in this report are observed during construction, the recommendations in this report must be re-evaluated. The scope of our services did not include any environmental assessment or testing for the presence or absence of hazardous or toxic materials in the soil, groundwater, or surface water within or beyond the subject site. Any statements made in this report, and/or notations made on the generalized soil profiles or boring logs, regarding odors or other potential environmental concerns are based on observations made during execution of our scope of services and as such are strictly for the information of our client. No opinion of any environmental concern of such observations is made or implied. Unless complete environmental information regarding the site is already available, an environmental assessment is recommended. If changes in the design or location of the structure occur, the conclusions and recommendations contained in this report may need to be modified. We recommend that these changes be provided to us for our consideration. MAE is not responsible for conclusions, interpretations, opinions or recommendations made by others based on the data contained in this report. Phone: (904) Fax: (904) Page 9

14 Figures

15 N Approximate Site Location Site Location Map PREPARED BY PROJECT NAME Beaver St-Lane to Carnegie St-Trans Water Main Project Jacksonville, Florida REFERENCE SCALE Delorme XMap 7.0 NTS PREPARED FOR MAE PROJECT NO. FIGURE NO. CPH, Inc

16

17 B-1 B-2 C-1 0 N Topsoil (4") Topsoil (5") Loose, Dark gray brown fine SAND with silt, poorly graded. (A-3) Asphalt (12 1/4") 1 2 Very dark brown fine SAND with silt, poorly graded. (A-3) Very dark grayish brown fine SAND with silt, poorly graded. (A-3) w = = Loose to medium dense, Dark grayish brown to dark gray clayey fine SAND, poorly graded. (A-2-6) w = = 44 4'. Date Drilled: 3/1/2017 GNR Very pale brown and dark gray fine SAND with silt, poorly graded. (A-3) Very dark brown fine SAND with silt, poorly graded. (A-3) 3 4 Grayish brown very clayey SAND. (A-6) Depth (ft) 6 7 w = = 25 6 Medium dense to loose, Gray clayey fine SAND, poorly graded. (A-2-6) 7'. Date Drilled: 3/1/2017 GNR Light brownish yellow clayey fine SAND, poorly graded. (A-2-6) 6 7 Depth (ft) Loose, Gray silty fine SAND, poorly graded. (A-2-4) '. Date Drilled: 3/1/2017 GNR Legend Topsoil Fine Sand with Silt Clayey Fine Sand Silty Fine Sand Asphalt Very Clayey Sand N BT Standard Penetration Resistance, Blows/Foot Boring Terminated at Depth Below Existing Grade (A-3) AASHTO Soil Classification System Depth to Groundwater 24 Hrs After Drilling w -200 Natural Moisture Content (%) GNR % Passing No. 200 U.S. Standard Sieve Stabilized Groundwater Level Not Recorded at Time of Drilling DATE BY DESCRIPTION DATE BY DESCRIPTION JOEY BROUSSARD, P.E. P.E. NO.: CPH, Inc. SHEET TITLE: Generalized Soil Profiles FL Certificate of Authorization No , Jacksonville, FL DATE: 3/29/2017 MAE PROJECT NO PROJECT NAME: Beaver St-Lane to Carnegie St-Trans Water Main Project Jacksonville, Florida FIGURE NO. 3

18 Appendix A

19 Meskel & Associates Engineering, PLLC FL Certificate of Authorization No Jacksonville, FL P: (904) F: (904) PROJECT NAME DATE STARTED 3/1/17 DRILLING CONTRACTOR Beaver St-Lane to Carnegie St-Trans Water Main Project PROJECT LOCATION Jacksonville, Florida CLIENT CPH, Inc. Ellis & Associates, Inc. COMPLETED 3/1/17 BORING LOCATION DRILLING METHOD See Boring Location Plan Standard Penetration Test BORING B-1 PAGE 1 OF 1 PROJECT NO LOGGED BY D.Francis CHECKED BY W. Josh Mele GROUND ELEVATION HAMMER TYPE Safety DEPTH (ft) 0.0 SAMPLE DEPTH NUMBER Topsoil (4") MATERIAL DESCRIPTION AASHTO GRAPHIC LOG BLOW COUNTS N-VALUE MOISTURE CONTENT (%) FINES CONTENT (%) ORGANIC CONTENT (%) LIQUID LIMIT PLASTICITY INDEX POCKET PEN. (tsf) RECOVERY % (RQD) REMARKS 1 Loose, Dark gray brown fine SAND with silt, poorly graded. A NEW MAE LOG AASTHO BORING LOCATION - NEW TEMPLATE GDT - 3/3/17 09:22 - M:\GINT\GINT FILES\PROJECTS\ \BEAVER ST.GPJ NOTES Loose to medium dense, Dark grayish brown to dark gray clayey fine SAND, poorly graded. Medium dense to loose, Gray clayey fine SAND, poorly graded. Loose, Gray silty fine SAND, poorly graded. Bottom of borehole at 10 feet. GNR - Stabilized Groundwater Level Not Recorded at Time of Drilling. A-2-6 A-2-6 A AT TIME OF DRILLING GNR GROUND WATER LEVELS 24 HRS AFTER 1 ft 7 in

20 Meskel & Associates Engineering, PLLC FL Certificate of Authorization No Jacksonville, FL P: (904) F: (904) PROJECT NAME Beaver St-Lane to Carnegie St-Trans Water Main Project PROJECT LOCATION Jacksonville, Florida CLIENT CPH, Inc. DATE STARTED 3/1/17 DRILLING CONTRACTOR Ellis & Associates, Inc. COMPLETED 3/1/17 BORING LOCATION DRILLING METHOD See Boring Location Plan Hand Auger LOGGED BY D.Francis CHECKED BY W. Josh Mele GROUND ELEVATION HAMMER TYPE BORING B-2 PAGE 1 OF 1 PROJECT NO DEPTH (ft) 0.0 SAMPLE DEPTH NUMBER MATERIAL DESCRIPTION AASHTO GRAPHIC LOG BLOW COUNTS N-VALUE MOISTURE CONTENT (%) FINES CONTENT (%) ORGANIC CONTENT (%) LIQUID LIMIT PLASTICITY INDEX POCKET PEN. (tsf) RECOVERY % (RQD) REMARKS Topsoil (5") 1 NEW MAE LOG AASTHO BORING LOCATION-HA - NEW TEMPLATE GDT - 3/3/17 09:24 - M:\GINT\GINT FILES\PROJECTS\ \BEAVER ST.GPJ NOTES Very dark brown fine SAND with silt, poorly graded. Grayish brown very clayey SAND. Light brownish yellow clayey fine SAND, poorly graded. Bottom of borehole at 7 feet. GNR - Stabilized Groundwater Level Not Recorded at Time of Drilling. A-3 A-6 A GROUND WATER LEVELS AT TIME OF DRILLING GNR 24 HRS AFTER 3 ft 4 in

21 Meskel & Associates Engineering, PLLC FL Certificate of Authorization No Jacksonville, FL P: (904) F: (904) PROJECT NAME DATE STARTED 3/1/17 DRILLING CONTRACTOR Beaver St-Lane to Carnegie St-Trans Water Main Project PROJECT LOCATION Jacksonville, Florida CLIENT CPH, Inc. Ellis & Associates, Inc. COMPLETED 3/1/17 BORING LOCATION DRILLING METHOD See Boring Location Plan Hand Auger LOGGED BY D.Francis CHECKED BY W. Josh Mele GROUND ELEVATION HAMMER TYPE BORING C-1 PAGE 1 OF 1 PROJECT NO DEPTH (ft) 0.0 SAMPLE DEPTH NUMBER MATERIAL DESCRIPTION AASHTO GRAPHIC LOG BLOW COUNTS N-VALUE MOISTURE CONTENT (%) FINES CONTENT (%) ORGANIC CONTENT (%) LIQUID LIMIT PLASTICITY INDEX POCKET PEN. (tsf) RECOVERY % (RQD) REMARKS Asphalt (12 1/4") NEW MAE LOG AASTHO BORING LOCATION-HA - NEW TEMPLATE GDT - 3/3/17 09:24 - M:\GINT\GINT FILES\PROJECTS\ \BEAVER ST.GPJ NOTES Very dark grayish brown fine SAND with silt, poorly graded. Very pale brown and dark gray fine SAND with silt, poorly graded. Very dark brown fine SAND with silt, poorly graded. Bottom of borehole at 4 feet. GNR - Stabilized Groundwater Level Not Recorded at Time of Drilling. A-3 A-3 A-3 AT TIME OF DRILLING GNR GROUND WATER LEVELS AFTER DRILLING ---

22 FIELD EXPLORATION PROCEDURES Standard Penetration Test (SPT) Borings The Standard Penetration Test (SPT) boring(s) were performed in general accordance with the latest revision of ASTM D 1586, Standard Test Method for Standard Penetration Test (SPT) and Split-Barrel Sampling of Soils. The borings were advanced by rotary drilling techniques. A split-barrel sampler was inserted to the borehole bottom and driven 18 to 24 inches into the soil using a 140-pound hammer falling an average of 30 inches per hammer blow. The number of hammer blows for the final 12 inches of penetration (18 sample) or for the sum of the middle 12 inches of penetration (24 sample) is termed the penetration resistance, blow count, or N-value. This value is an index to several in-situ geotechnical properties of the material tested, such as relative density and Young s Modulus. After driving the sampler, it was retrieved from the borehole and representative samples of the material within the split-barrel were containerized and sealed. After completing the drilling operations, the samples for each boring were transported to the laboratory where they were examined by a geotechnical engineer to verify the field descriptions and classify the soil, and to select samples for laboratory testing. Hand Auger Boring The auger boring(s) were performed manually by the use of a hand-held bucket auger in general accordance with the latest revision of ASTM D 1452, Standard Practice for Soil Exploration and Sampling by Auger Borings. Representative samples of the soils brought to the ground surface by the auger were placed in sealed containers and transported to our laboratory where they were examined by a geotechnical engineer to verify the field descriptions and classify the soil, and to select samples for laboratory testing. Revised: March 2017

23 S o i l C l a s s i f i c a t i o n K E Y T O B O R I N G L O G S AASHTO Soil classification of samples obtained at the boring locations is based on the American Association of State Highway and Transportation Officials (AASHTO) Classification System. Coarse grained soils have more than 50% of their dry weight retained on a #200 sieve. Their principal descriptors are: sand, cobbles and boulders. Fine grained soils have less than 50% of their dry weight retained on a #200 sieve. They are principally described as clays if they are plastic and silts if they are slightly to non-plastic. Major constituents may be added as modifiers and minor constituents may be added according to the relative proportions based on grain size. In addition to gradation, coarse-grained soils are defined on the basis of their in-place relative density and fine-grained soils on the basis of their consistency. Symbol N BORING LOG LEGEND Description Standard Penetration Resistance, the number of blows required to advance a standard spoon sampler 12" when driven by a 140-lb hammer dropping 30". WOR Split Spoon sampler advanced under the weight of the drill rods WOH Split Spoon sampler advanced under the weight of the SPT hammer 50/2 Indicates 50 hammer blows drove the split spoon 2 inches; 50 Hammer blows for less than 6- inches of split spoon driving is considered Refusal. (A-3) AASHTO Soil Classification System -200 Fines content, % Passing No. 200 U.S. Standard Sieve w Natural Moisture Content (%) OC Organic Content (%) LL Liquid Limit PI Plasticity Index NP PP Non-Plastic Pocket Penetrometer in tons per square foot (tsf) MODIFIERS RELATIVE DENSITY (Coarse-Grained Soils) Relative Density N-Value SECONDARY CONSTITUENTS Very Loose Less than 4 (Sand, Silt or Clay) Loose 4 to 10 Trace Less than 5% Medium Dense 10 to 30 With 5% to 12% Dense 30 to 50 Sandy, Silty or Clayey 12% to 35% Very Dense Greater than 50 Very Sandy, Very Silty or Very Clayey 35% to 50% CONSISTENCY (Fine-Grained Soils) ORGANIC CONTENT Consistency N-Value Trace 2% or less Very Soft Less than 2 Few 3% to 5% Soft 2 to 4 Little 5% to 10% Firm 4 to 8 With Greater than 10% Stiff 8 to 15 Very Stiff 15 to 30 Hard Greater than 30 MINOR COMPONENTS (Shell, Rock, Debris, Roots, etc.) RELATIVE HARDNESS (Limestone) Trace Less than 5% Relative Hardness N-Value Few 5% to 10% Soft Less than 50 Little 15% to 25% Hard Greater than 50 Some 30% to 45% KBL-AASHTO-safety

24 AASHTO Soil Classification System (from AASHTO M 145 or ASTM D 3282) General Classification Group Classification A-1 Granular Materials (35% or less passing the mm sieve) A-2 A-3 A-1-a A-1-b A-2-4 A-2-5 A-2-6 A-2-7 Silt-Clay Materials (>35% passing the mm sieve) A-4 A-5 A-6 A-7 A-7-5* A-7-6* Sieve Analysis, % passing: 2.00 mm (No. 10) 50 max (No. 40) 30 max 50 max 51 min (No. 200) 15 max 25 max 10 max 35 max 35 max Characteristics of fraction passing mm (No. 40): Liquid Limit 40 max 41 min 35 max 40 max 35 max 36 min 36 min 36 min 36 min 41 min 40 max 41 min 40 max 41 min Plasticity Index 6 max N.P. 10 max 10 max 11 min 11 min 10 max 10 max 11 min 11 min Usual types of significant constituent materials General local** rating as a subgrade stone fragments, gravel and sand fine sand excellent to good silty or clayey gravel and sand silty soils clayey soils fair to poor * Plasticity index of A-7-5 subgroup is equal to or less than the LL Plasticity index of A-7-6 subgroup is greater than LL 30 ** Northeast Florida

25 Appendix B

26 Meskel & Associates Engineering, PLLC FL Certificate of Authorization No Jacksonville, FL P: (904) F: (904) PROJECT NAME Beaver St-Lane to Carnegie St-Trans Water Main Project PROJECT LOCATION Jacksonville, Florida CLIENT CPH, Inc. SUMMARY OF LABORATORY TEST RESULTS PROJECT NO DATE. 3/21/2017 Borehole Sample No. Approx. Depth (ft) %<#200 Sieve Water Content (%) Organic Content (%) B A-2-6 B A-2-6 B A-6 Liquid Limit Plastic Limit Plasticity Index USCS Classification Comments Note: "---" Untested Parameter LAB SUMMARY_MAE_ALL PROJECTS - GINT STD US LAB.GDT - 3/21/17 08:51 - M:\GINT\GINT FILES\PROJECTS\ \LAB_BEAVER ST.GPJ

27 LABORATORY TEST PROCEDURES Percent Fines Content The percent fines or material passing the No. 200 mesh sieve of the sample tested was determined in general accordance with the latest revision of ASTM D The percent fines are the soil particles in the silt and clay size range. Natural Moisture Content The water content of the tested sample was determined in general accordance with the latest revision of ASTM D The water content is defined as the ratio of pore or free water in a given mass of material to the mass of solid material particles.

Subsurface Investigation Report. Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois

Subsurface Investigation Report. Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois AGI Project No. -11 Subsurface Investigation Report For the Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois Prepared for Mr. Steve Panko Key Development Partners, LLC North State Street,

More information

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois AGI Project No. 13-276 Subsurface Investigation Report For the Proposed New Retail Center 9601 South Pulaski Road Evergreen Park, Illinois Prepared for Mr. Feras Sweis FHS Design + Build LLC 2010 West

More information

April 7, Webster Street Sub-Surface Stormwater Storage System Bid No Bid Date: 4/13/17 ADDENDUM NO 1

April 7, Webster Street Sub-Surface Stormwater Storage System Bid No Bid Date: 4/13/17 ADDENDUM NO 1 PUBLIC WORKS DEPARTMENT David A. Jones, P.E., Director April 7, 2017 Webster Street Sub-Surface Stormwater Storage System Bid No. 2017-022 Bid Date: 4/13/17 ADDENDUM NO 1 Please make the following changes

More information

REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS

REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS FIGURE 3 Geotechnical Report (2) REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS RIVER TOWER RESTORATION RIVER TOWER PARK TAMPA, FLORIDA AREHNA PROJECT NO. B-13-002 February 22, 2013 Prepared

More information

Site Location. Figure 1: Site Location Map US-24 and I-275 Interchange Ash Township, Monroe County, Michigan

Site Location. Figure 1: Site Location Map US-24 and I-275 Interchange Ash Township, Monroe County, Michigan Site Location 0606 1771 North Dixie Highway Monroe, Michigan 48162 Tel: 734-289-2200 Fax: 734-289-2345 www.manniksmithgroup.com Figure 1: Site Location Map US-24 and I-275 Interchange Ash Township, Monroe

More information

GEOTECHNICAL ENGINEERING REPORT

GEOTECHNICAL ENGINEERING REPORT GEOTECHNICAL ENGINEERING REPORT PROJECT MINECRAFT ACCESS ROAD BOYDTON PLANK ROAD DINWIDDIE COUNTY, VIRGINIA JOB NUMBER: 37775.003 PREPARED FOR: DINWIDDIE COUNTY PO BOX 70 DINWIDDIE COUNTY, STATE 23841

More information

FIGURES Printed By: aday Print Date: 3/23/2011 12:48:08 PM File Name: \\geodesign.local\files\jobs\m-r\penskeauto\penskeauto-1\penskeauto-1-01\figures\cad\penskeauto-1-01-vm01.dwg Layout: FIGURE 1 VICINITY

More information

Subsurface Investigation Report

Subsurface Investigation Report AGI Project No. 17-154 Subsurface Investigation Report For the Proposed New One-Story Building Addition 7030 West 111 th Street Worth, Illinois Prepared for T63 Development LLC 11052 Mayflow er Lane Orland

More information

Geotechnical Investigation Report

Geotechnical Investigation Report MC Squared, Inc. Geotechnical Investigation Report City of St. Petersburg Forcemain Pinellas County, Florida Prepared for: Hazen and Sawyer 10002. Princess Palm Ave., Suite 200 Tampa, Florida 33610 Prepared

More information

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants SUBSURFACE SOIL EXPLORATION ANALYSIS AND RECOMMENDATIONS PROPOSED WEIRS AT STATIONS 130+00 AND 16+00 DRAINAGE IMPROVEMENTS TO THE FOUR CORNERS MSBU HENDRY COUNTY, FLORIDA Ardaman & Associates, Inc. Geotechnical,

More information

August 15, 2006 (Revised) July 3, 2006 Project No A

August 15, 2006 (Revised) July 3, 2006 Project No A August 15, 2006 (Revised) July 3, 2006 Project No. 01-05-0854-101A Mr. David Reed, P.E. Protean Design Group 100 East Pine Street, Suite 306 Orlando, Florida 32801 Preliminary Soil Survey Report Polk Parkway

More information

Please include this addendum in your Bid proposal for the above referenced project. Questions are in black ink, and the answers are in red ink.

Please include this addendum in your Bid proposal for the above referenced project. Questions are in black ink, and the answers are in red ink. JAHarchitects, LLC PROJECT NO. 393 RIVERCREST CDD 11560 RAMBLE CREEK DRIVE, RIVERVIEW FL ADDENDUM TO BID PROJECT: RIVERCREST CDD MULTI PURPOSE FIELD MAINTENANCE BUILDING & DOG PARK POOL & CABANNA JAH PROJECT

More information

File No Supplemental November Geotechnical and Environmental Consulting Engineers

File No Supplemental November Geotechnical and Environmental Consulting Engineers Supplemental Information & Geotechnical Recommendations Proposed New Solar Valley Location B (East of Building No. 7) Cañada Community College 4200 Farm Hill Boulevard Submitted to: Mr. Peter Hempel Construction

More information

SUBSURFACE EXPLORATION & GEOTECHNICAL ENGINEERING EVALUATION

SUBSURFACE EXPLORATION & GEOTECHNICAL ENGINEERING EVALUATION Report of Subsurface Exploration and Geotechnical Engineering Evaluation Proposed Courtyard Marriott Phenix City, Alabama BHATE Project Number: 112263 October 9, 2012 SUBSURFACE EXPLORATION & GEOTECHNICAL

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Pavement Subgrade Survey State Highway 125 over Hudson Creek Ottawa County, Oklahoma September 23, 21 Terracon Project No. 415121 Prepared for: Guy Engineering Services,

More information

Prepared for: HDR Engineering, Inc. 200 West Forsyth Street, Suite 800 Jacksonville, Florida Prepared by:

Prepared for: HDR Engineering, Inc. 200 West Forsyth Street, Suite 800 Jacksonville, Florida Prepared by: REPORT OF GEOTECHNICAL EXPLORATION REHABILITATE WHARF STRUCTURE AT BERTHS 6 AND ½ OF BERTH 5 TALLEYRAND MARINE TERMINAL, JACKSONVILLE, FLORIDA E&A PROJECT NO. 0756-0081 Prepared for: HDR Engineering, Inc.

More information

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois AGI Project No. 13-109B Subsurface Investigation Report For the Proposed Roosevelt Middle School Site Improvements 7560 Oak Avenue River Forest, Illinois Prepared for Mr. Jerry Pilipowicz Terra Engineering,

More information

GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota Phone Fax

GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota Phone Fax GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota 57104 Phone 605-335-5512 Fax 605-335-0773 October 28, 2016 City of Vermillion 25 Center Street 57069 Attn:

More information

GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO E

GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO E GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO. 15-945E TO VILLAGE OF TIKI ISLAND TIKI ISLAND, TEXAS BY SERVICING TEXAS, LOUISIANA, NEW MEXICO, OKLAHOMA

More information

GEOTECHNICAL INVESTIGATION I-15 SIGN BRIDGES LAS VEGAS EA JANUARY

GEOTECHNICAL INVESTIGATION I-15 SIGN BRIDGES LAS VEGAS EA JANUARY GEOTECHNICAL INVESTIGATION I-15 SIGN BRIDGES LAS VEGAS EA 73171 JANUARY 06 MATERIALS DIVISION STATE OF NEVADA DEPARTMENT OF TRANSPORTATION MATERIALS DIVISION GEOTECHNICAL SECTION GEOTECHNICAL REPORT I-15

More information

This report presents the findings of the subsurface exploration concerning the design of the taxiway rehabilitation. Description

This report presents the findings of the subsurface exploration concerning the design of the taxiway rehabilitation. Description September 22, 2016 American Infrastructure Development, Inc. 3810 Northdale Boulevard, Suite 170 Tampa, Florida 33624 Attn: Mr. Mohsen Mohammadi, Ph.D., P.E. Senior Consultant Mob: (813) 244-6609 E-mail:

More information

Typical Subsurface Profile. November 28, 2016

Typical Subsurface Profile. November 28, 2016 November 28, 2016 RSCCD Facility Planning, District Construction and Support Services 2323 N. Broadway, Suite 112, Santa Ana, CA 92706 Attn: Re: Ms. Allison Coburn Facilities Project Manager P: (714) 480-7530

More information

APPENDIX A DRAINAGE STUDY PHASE 2 ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE 4C IMPROVEMENTS LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC

APPENDIX A DRAINAGE STUDY PHASE 2 ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE 4C IMPROVEMENTS LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC DRAINAGE STUDY PHASE ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE C IMPROVEMENTS ` FOR: LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC APPENDIX A J-.000 Prepared by: Savannah, GA Charleston, SC Myrtle

More information

Earth Mechanics, Inc. Geotechnical & Earthquake Engineering

Earth Mechanics, Inc. Geotechnical & Earthquake Engineering Earth Mechanics, Inc. Geotechnical & Earthquake Engineering TECHNICAL MEMORANDUM DATE: June 3, 2009 EMI PROJECT NO: 01-143 TO: COPY: FROM: SUBJECT: John Chun, P.E. / Port of Long Beach (POLB) Jorge Castillo

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular

More information

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 00 and Division

More information

GEOTECHNICAL INVESTIGATION MDACC GUHN ROAD FLOOD MITIGATION PROJECT 5610 GUHN ROAD HOUSTON, TEXAS REPORT NO

GEOTECHNICAL INVESTIGATION MDACC GUHN ROAD FLOOD MITIGATION PROJECT 5610 GUHN ROAD HOUSTON, TEXAS REPORT NO GEOTECHNICAL INVESTIGATION MDACC GUHN ROAD FLOOD MITIGATION PROJECT 5610 GUHN ROAD HOUSTON, TEXAS REPORT NO. 1140189301 Reported to: URS CORPORATION Houston, Texas Reported by: GEOTEST ENGINEERING, INC.

More information

C. Foundation stabilization for pipe and utility structures.

C. Foundation stabilization for pipe and utility structures. PART 1 - GENERAL 1.1 SECTION INCLUDES A. Excavating, backfilling, and compacting for utilities, including pipe, structures, and appurtenances. B. Control of water in trenches. C. Foundation stabilization

More information

Utility Cut Restoration

Utility Cut Restoration Design Manual Chapter 9 - Utilities 9D - Utility Cut Restoration 9D-1 Utility Cut Restoration A. General Utility cuts are made in existing pavement sections to install a myriad of utilities and to repair

More information

SECTION TRENCHING & BACKFILLING

SECTION TRENCHING & BACKFILLING SECTION 02225 - TRENCHING & BACKFILLING 1.0 GENERAL 1.1 Work included in this Section includes trenching and backfilling for underground pipelines and related structures only. 1.2 Reference Specifications

More information

PRELIMINARY ENGINEERING DESIGN MEMORANDUM WATER TREATMENT PLANT FLOOD WALL TO PROTECT BACKWASH SETTLING BASIN CITY OF NEW BUFFALO, MI

PRELIMINARY ENGINEERING DESIGN MEMORANDUM WATER TREATMENT PLANT FLOOD WALL TO PROTECT BACKWASH SETTLING BASIN CITY OF NEW BUFFALO, MI PRELIMINARY ENGINEERING DESIGN MEMORANDUM WATER TREATMENT PLANT FLOOD WALL TO PROTECT BACKWASH SETTLING BASIN CITY OF NEW BUFFALO, MI City of New Buffalo, MI Preliminary Engineering Design Memorandum Water

More information

Subsurface Environmental Investigation

Subsurface Environmental Investigation Subsurface Environmental Investigation Lake Development East Lake and 21 st Avenue South February 23, 201 Terracon Project No. MP14738A Prepared for: Minneapolis Public Schools Prepared by: Terracon Consultants,

More information

GEOTECHNICAL REPORT B-1942

GEOTECHNICAL REPORT B-1942 GEOTECHNICAL REPORT TUSCARORA BRIDGE REPLACEMENT B-1942 E.A. 73561 March 2011 MATERIALS DIVISION STATE OF NEVADA DEPARTMENT OF TRANSPORTATION MATERIALS DIVISION GEOTECHNICAL SECTION GEOTECHNICAL REPORT

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Turner Turnpike Widening Milepost 210 to 218 Drainage Structure Pipe Jacking Creek County, Oklahoma July 1, 2016 Terracon Project No. 04165017 Prepared for: Benham Tulsa,

More information

Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W340) AID Project No. GOA16001 Orange County, Florida GEC Project No.

Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W340) AID Project No. GOA16001 Orange County, Florida GEC Project No. Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W40) AID Project No. GOA16001 Orange County, Florida GEC Project No. 956G July 6, 2017 American Infrastructure Development, Inc. 7 North

More information

SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING REPORT MMS OFFICE BUILDING OLATHE, KS PREPARED FOR

SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING REPORT MMS OFFICE BUILDING OLATHE, KS PREPARED FOR 1308 Adams I Kansas City, Kansas 66103 913.321.8100 I kctesting.com Su SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING REPORT MMS OFFICE BUILDING OLATHE, KS PREPARED FOR Mr. Chris Herre, AIA Rose Design

More information

Washtenaw Community College Design & Construction Facilities Management 4800 East Huron River Drive Ann Arbor, MI

Washtenaw Community College Design & Construction Facilities Management 4800 East Huron River Drive Ann Arbor, MI Washtenaw Community College Design & Construction Facilities Management 4800 East Huron River Drive Ann Arbor, MI 4810-4800 GEOTECHNICAL INVESTIGATION FOR Proposed Pavement Rehabilitation Parking Lots

More information

SECTION RIPRAP, BOULDERS, AND BEDDING

SECTION RIPRAP, BOULDERS, AND BEDDING SECTION 31 37 00 RIPRAP, BOULDERS, AND BEDDING PART 1 GENERAL 1.01 SECTION INCLUDES A. The WORK includes excavation, grading, and installation of riprap, boulders, soil riprap, void-filled riprap, and

More information

SCG INTERNATIONAL TRINIDAD AND TOBAGO LIMITED COUVA CHILDREN S HOSPITAL

SCG INTERNATIONAL TRINIDAD AND TOBAGO LIMITED COUVA CHILDREN S HOSPITAL SCG INTERNATIONAL TRINIDAD AND TOBAGO LIMITED COUVA CHILDREN S HOSPITAL GEOTECHNICAL CONSULTANT Prepared by Checked by Approved by Mr. C Allen Dr. Derek Gay Dr. Derek Gay Signature Date Signature Date

More information

PARKING LOTS 4, 7, AND 8 RECONSTRUCTION REPORT

PARKING LOTS 4, 7, AND 8 RECONSTRUCTION REPORT PARKING LOTS 4, 7, AND 8 RECONSTRUCTION REPORT Converse Project No. 15-81-177-01 Prepared For: David Evans and Associates, Inc. 17782 17th Street, Suite 200 Tustin, California 92780 Prepared By: 10391

More information

B. Backfill and compact utility bedding and fill placed in the utility trenches between the top of the utility bedding and the subgrade elevation.

B. Backfill and compact utility bedding and fill placed in the utility trenches between the top of the utility bedding and the subgrade elevation. SECTION 312333 TRENCHING AND BACKFILLING PART 1 - GENERAL 1.1 SUMMARY A. Excavate trenches for new electric and telephone conduits, gas lines, and their appurtenances from at least 5 feet outside the building

More information

Memorandum. FOUNDATION ENGINEERING, INC. Professional Geotechnical Services. Date: August 13, 2012 To:

Memorandum. FOUNDATION ENGINEERING, INC. Professional Geotechnical Services. Date: August 13, 2012 To: FOUNDATION ENGINEERING, INC. Professional Geotechnical Services Memorandum Date: August 13, 2012 To: From: Subject: Project: Brett C. Martin, P.E. LEI Engineering & Surveying, LLC James K. Maitland, P.E.,

More information

GENERAL SOILS EVALUATION REPORT. For

GENERAL SOILS EVALUATION REPORT. For GENERAL SOILS EVALUATION REPORT For EL PASO WATER UTILITIES (EPWU) PROPOSED AUSTIN STORMWATER POND IMPROVEMENTS NE OF ALTURA AVE. & LACKLAND ST. EL PASO, EL PASO COUNTY, TEXAS Prepared For MORENO CARDENAS

More information

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions.

B. Subsurface data is available from the Owner. Contractor is urged to carefully analyze the site conditions. SECTION 31 23 33 - TRENCHING, BACKFILLING AND COMPACTION PART 1 - GENERAL 1.1 SCOPE A. This Section specifies the requirements for excavating and backfilling for storm sewer, sanitary sewer, water distribution

More information

Preliminary Geotechnical Exploration Armstrong Tract Rivers Avenue and Hanahan Road North Charleston, South Carolina S&ME Project No.

Preliminary Geotechnical Exploration Armstrong Tract Rivers Avenue and Hanahan Road North Charleston, South Carolina S&ME Project No. Preliminary Geotechnical Exploration Rivers Avenue and Hanahan Road S&ME Project No. 4213-16-016 Prepared for: Charleston Water System 103 Saint Phillip Street Charleston, South Carolina 29403 Prepared

More information

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS Section Page 19-1 TRENCH EXCAVATION... 19-1 19-1.01 Exploratory Excavation... 19-1 19-1.02 Trench... 19-1 19-1.02.AStorm Drain Pipe...

More information

Geotechnical Engineering Report South Shore Carter Lake Campground Expansion Northwest of CR 31 and Cougar Run Lane Larimer County, Colorado

Geotechnical Engineering Report South Shore Carter Lake Campground Expansion Northwest of CR 31 and Cougar Run Lane Larimer County, Colorado Geotechnical Engineering Report South Shore Carter Lake Campground Expansion Northwest of CR 31 and Cougar Run Lane Larimer County, Colorado July 15, 2016 Terracon Project No. 20165057 Prepared for: Larimer

More information

BLEINC. August 17, Black & Veatch Corporation 201 Brookfield Parkway, Suite 150 Greenville, SC 29607

BLEINC. August 17, Black & Veatch Corporation 201 Brookfield Parkway, Suite 150 Greenville, SC 29607 BLEINC. BUNNELL-LAMMONS ENGINEERING, INC. GEOTECHNICAL, ENVIRONMENTAL AND CONSTRUCTION MATERIALS CONSULTANTS August 17, 2017 Black & Veatch Corporation 201 Brookfield Parkway, Suite 150 Greenville, SC

More information

REPORT. Explorations and Geotechnical Engineering Services. Proposed Seaport Village Healthcare Facility Ellsworth, Maine. March 27, S

REPORT. Explorations and Geotechnical Engineering Services. Proposed Seaport Village Healthcare Facility Ellsworth, Maine. March 27, S REPORT March 27, 2013 S Explorations and Geotechnical Engineering Services Proposed Seaport Village Healthcare Facility Ellsworth, Maine PREPARED FOR: First Atlantic Corporation Attention: Craig Coffin,

More information

SUBSURFACE INVESTIGATION, LABORATORY TESTING PROGRAM, AND PAVEMENT RECOMMENDATIONS

SUBSURFACE INVESTIGATION, LABORATORY TESTING PROGRAM, AND PAVEMENT RECOMMENDATIONS February 7, 2017 EDR Architects, PLLC PO Box 271613 Corpus Christi, TX 78427 Attention: Ms. Emily D. Rozypal, AIA SUBJECT: SUBSURFACE INVESTIGATION, LABORATORY TESTING PROGRAM, AND PAVEMENT RECOMMENDATIONS

More information

SECTION EXCAVATION AND BACKFILL FOR UTILITIES AND STRUCTURES

SECTION EXCAVATION AND BACKFILL FOR UTILITIES AND STRUCTURES SECTION 02215 EXCAVATION AND BACKFILL FOR UTILITIES AND STRUCTURES PART 1 - GENERAL 1.1 DESCRIPTION: This section includes materials, testing, and installation of earthwork for excavations, fills, and

More information

REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING SERVICES

REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING SERVICES REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ENGINEERING SERVICES NORTH SHORE SCHOOL DISTRICT 11 HIGHLAND PARK, ILLINOIS ECS PROJECT NO. 1:8 FOR NORTH SHORE SCHOOL DISTRICT 11 SEPTEMBER, 1 REPORT

More information

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS Section Page 19-1 TRENCH EXCAVATION... 19.1 19-1.01 Exploratory Excavation... 19.1 19-1.02 Trench Width... 19.1 19-1.02.A Storm Drain

More information

GENERAL SOILS EVALUATION REPORT. For

GENERAL SOILS EVALUATION REPORT. For GENERAL SOILS EVALUATION REPORT For EPWU PROPOSED KENTUCKY DAM (DAM 5) DRAINAGE SYSTEM IMPROVEMENTS KENTUCKY ST. & ALABAMA ST. EL PASO, EL PASO COUNTY, TEXAS Prepared For MORENO CARDENAS INC. 2505 E. MISSOURI

More information

SECTION EXCAVATING, BACKFILLING, AND COMPACTION FOR UTILITIES

SECTION EXCAVATING, BACKFILLING, AND COMPACTION FOR UTILITIES SECTION 02221 EXCAVATING, BACKFILLING, AND COMPACTION FOR UTILITIES PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02200 - Earthwork. 2. 02660 - Water Systems. 3. 02720 - Storm Drainage System. 4.

More information

SITE INVESTIGATION Validation and Interpretation of data

SITE INVESTIGATION Validation and Interpretation of data SITE INVESTIGATION Validation and Interpretation of data Dr. G.Venkatappa Rao The Impact 1 The Need To determine the type of foundation To assess bearing capacity/settlement Location of Ground water table,issues

More information

MAPLES COMMUNITY CENTRE ADDITION GEOTECHNICAL INVESTIGATION 434 ADSUM DRIVE WINNIPEG, MANITOBA

MAPLES COMMUNITY CENTRE ADDITION GEOTECHNICAL INVESTIGATION 434 ADSUM DRIVE WINNIPEG, MANITOBA MAPLES COMMUNITY CENTRE ADDITION GEOTECHNICAL INVESTIGATION 434 ADSUM DRIVE WINNIPEG, MANITOBA Prepared for: Maples Recreation Association c / o Wolfrom Engineering Ltd. Winnipeg, Manitoba February 2014

More information

PROJECT NO A. ISSUED: February 29, 2016

PROJECT NO A. ISSUED: February 29, 2016 INTERPRETIVE REPORT FOR INFILTRATION SYSTEM DESIGN, PROPOSED VILLA VERONA APARTMENT COMMUNITY, ASSESSOR S PARCEL NUMBERS 311-040-015, 311-040-021, 311-040-024, 311-040-026 AND 311-040-013, LOCATED ON THE

More information

SECTION 1100 GRADING 1102 MATERIALS AND DEFINITIONS.

SECTION 1100 GRADING 1102 MATERIALS AND DEFINITIONS. SECTION 1100 GRADING 1101 SCOPE. This section covers the performance of all work required for grading the project in coordination with all previous work performed at the locations shown on the contract

More information

REPORT OF SUBSURFACE INVESTIGATION AND GEOTECHNICAL ENGINEERING SERVICES

REPORT OF SUBSURFACE INVESTIGATION AND GEOTECHNICAL ENGINEERING SERVICES REPORT OF SUBSURFACE INVESTIGATION AND GEOTECHNICAL ENGINEERING SERVICES Elizabeth City, North Carolina G E T Project No: EC14-188G May 30, 2014 PREPARED FOR: 106 Capital Trace, Unit E Elizabeth City,

More information

geotechnical and construction materials consultants

geotechnical and construction materials consultants geotechnical and construction materials consultants City of Dallas Public Works and Transportation Department 320 E. Jefferson Blvd, Room 307 Dallas, Texas 75203 ATTN: Mr. Vincent Lewis, P.E. Email: Vincent.lewis@dallascityhall.com

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Shaw AFB East Gate Entrance Control Facility Amendment Sumter, South Carolina September 13, 2010 Terracon Project No. 73105020A Prepared for: TranSystems North Charleston,

More information

SECTION A1 EXCAVATION AND BACKFILL GENERAL

SECTION A1 EXCAVATION AND BACKFILL GENERAL SECTION A1 EXCAVATION AND BACKFILL GENERAL The work under this section shall include all excavation to such width and depth as shown on the drawings, specified herein, or ordered by the Engineer. Such

More information

TRENCH EXCAVATION AND BACKFILL

TRENCH EXCAVATION AND BACKFILL SUDAS Standard Specifications Division 3 - Trench and Trenchless Construction Section 300 - Trench Excavation and Backfill TRENCH EXCAVATION AND BACKFILL PART - GENERAL.0 SECTION INCLUDES A. Trench Excavation

More information

SECTION EXCAVATION AND EMBANKMENT. B. Subbase Grading A samples for gradation analysis.

SECTION EXCAVATION AND EMBANKMENT. B. Subbase Grading A samples for gradation analysis. PART 1 GENERAL 1.1 DESCRIPTION A. The WORK under this Section includes providing all labor, materials, tools and equipment necessary for excavation and embankment construction to the lines, grades and

More information

SECTION UNCLASSIFIED EXCAVATION AND GRADING

SECTION UNCLASSIFIED EXCAVATION AND GRADING SECTION 02210 UNCLASSIFIED EXCAVATION AND GRADING PART 1 GENERAL 1.1 DESCRIPTION Work in this section includes the excavation, undercut excavating, grading, earthwork and compaction required as shown on

More information

BASED ON DFD MASTER SPECIFICATION DATED 2/24/2014

BASED ON DFD MASTER SPECIFICATION DATED 2/24/2014 1 0 1 0 1 0 1 SECTION 1. TRENCHING BASED ON DFD MASTER SPECIFICATION DATED // P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of providing all work, materials, labor, equipment,

More information

Report of Preliminary Geotechnical Engineering Investigation for Ponds

Report of Preliminary Geotechnical Engineering Investigation for Ponds Report of Preliminary Geotechnical Engineering Investigation for Ponds Segment 2: State Road 400 (SR 400)/Interstate 4 (I-4) from West of SR 528 (Beachline Expressway) to West of SR 435 (Kirkman Road)

More information

REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ANALYSIS DMA TAMPA RED BRICK BUILDING TAMPA, FLORIDA FOR MRI ARCHITECTURAL GROUP, INC.

REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ANALYSIS DMA TAMPA RED BRICK BUILDING TAMPA, FLORIDA FOR MRI ARCHITECTURAL GROUP, INC. REPORT OF SUBSURFACE EXPLORATION AND GEOTECHNICAL ANALYSIS DMA TAMPA RED BRICK BUILDING TAMPA, FLORIDA FOR MRI ARCHITECTURAL GROUP, INC. JANUARY 7, 2015 January 7, 2015 Mr. Pete Ikegami MRI Architectural

More information

GEOTECHNICAL EXPLORATION REPORT. For the. Project ID: th Avenue Vogt Drive to Decorah Road Local Street Washington County.

GEOTECHNICAL EXPLORATION REPORT. For the. Project ID: th Avenue Vogt Drive to Decorah Road Local Street Washington County. GEOTECHNICAL EXPLORATION REPORT For the Project ID: 277--9 18 th Avenue Vogt Drive to Decorah Road Local Street Washington County Prepared for: Alfred Benesch & Company 1 West Canal Street, Suite 15 Milwaukee,

More information

In preparation for constructing buildings on a property, the builder. Site Preparation CHAPTER

In preparation for constructing buildings on a property, the builder. Site Preparation CHAPTER CHAPTER 3 Site Preparation In preparation for constructing buildings on a property, the builder must consider a number of factors related to code requirements. The buildings must be located according to

More information

Geotechnical Testing Laboratory, Inc. Engineering and Construction Materials Testing Services

Geotechnical Testing Laboratory, Inc. Engineering and Construction Materials Testing Services Engineering and Construction Materials Testing Services February 27, 15 Central Louisiana Economic and Development Alliance P.O. Box 465 Alexandria, Louisiana 719 Attention: Mr. Rick Ranson Vice President

More information

Performance of Mechanically Stabilized Earth walls over compressible soils

Performance of Mechanically Stabilized Earth walls over compressible soils Performance of Mechanically Stabilized Earth walls over compressible soils R.A. Bloomfield, A.F. Soliman and A. Abraham The Reinforced Earth Company, Vienna, Virginia, USA ABSTRACT: Two projects have recently

More information

REPORT ON GEOTECHNICAL INVESTIGATION 1251 MAIN STREET NORTH. STITTSVILLE, ONTARIO REPORT NO.: G-CPR-A REPORT DATE: SEPTEMBER 24, 2015

REPORT ON GEOTECHNICAL INVESTIGATION 1251 MAIN STREET NORTH. STITTSVILLE, ONTARIO REPORT NO.: G-CPR-A REPORT DATE: SEPTEMBER 24, 2015 REPORT ON GEOTECHNICA INVETIGATION 1251 MAIN TREET NORTH. TITTVIE, ONTARIO REPORT NO.: 4186-15-G-CPR-A REPORT DATE: EPTEMBER 24, 2015 PREPARED FOR CHOICE PROPERTIE REIT 22 T. CAIR AVENUE EAT TORONTO, ONTARIO

More information

SOIL MECHANICS Assignment #2: Soil Classification Solution.

SOIL MECHANICS Assignment #2: Soil Classification Solution. Geotechnical Engineering Research Laboratory One University Avenue Lowell, Massachusetts 01854 Edward L. Hajduk, D.Eng, PE Lecturer PA105D Tel: (978) 934 2621 Fax: (978) 934 3052 e mail: Edward_Hajduk@uml.edu

More information

Subsurface Investigations PDCA Professor s Driven Pile Institute. Loren R. Anderson Utah State University June 25, 2015

Subsurface Investigations PDCA Professor s Driven Pile Institute. Loren R. Anderson Utah State University June 25, 2015 Subsurface Investigations PDCA Professor s Driven Pile Institute Loren R. Anderson Utah State University June 25, 2015 Ralph B. Peck (1962) Subsurface engineering is an art; soil mechanics is an engineering

More information

Addendum 1 - Appendix A - 1 of 22

Addendum 1 - Appendix A - 1 of 22 Addendum 1 - Appendix A - 1 of 22 Erdman Anthony of Florida, Inc. August 1, 2007 1402 Royal Palm Beach Boulevard Building 500 Royal Palm Beach, Florida 33411 Attention: Subject: Ms. Dana I. Gillette, P.E.,

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Foothills Drive Widening Holmes Drive to Lakewood Street Farmington, New Mexico April 9, 2014 Terracon Project No. 69135010 Prepared for: Souder Miller & Associates Farmington,

More information

SECTION VIII GEOTECHNICAL ENGINEERING REPORT

SECTION VIII GEOTECHNICAL ENGINEERING REPORT SECTION VIII GEOTECHNICAL ENGINEERING REPORT Copyright 2014 GFAC ENGINEERING INC. Page i of vi July 31, 2014 GEOTECHNICAL ENGINEERING REPORT PROPOSED SUBDIVISION STREETS AND DETENTION BASIN WEST SILOAM

More information

TRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING)

TRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING) PART 1 - GENERAL TRENCHLESS CONSTRUCTION (BORING, JACKING, AND TUNNELING) 1.01 SECTION INCLUDES A. Trenchless Installation of Carrier Pipe with Casing Pipe B. Trenchless Installation of Carrier Pipe without

More information

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS

SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS SECTION 19 - TRENCH EXCAVATION, BEDDING AND BACKFILL TABLE OF CONTENTS Section Page 19-1 TRENCH EXCAVATION...19.1 19-1.01 Exploratory Excavation...19.1 19-1.02 Trench Width...19.1 19-1.02.A Storm Drain

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Science & Health Careers Center Oakton Community College Des Plaines, Illinois October 4, 11 Terracon Project No. 1110 Prepared for: Oakton Community College Des Plaines,

More information

LEVELTON CONSULTANTS LTD. 1.0 Introduction. 2.0 Project Description. December 16, Levelton File # R

LEVELTON CONSULTANTS LTD. 1.0 Introduction. 2.0 Project Description. December 16, Levelton File # R LEVELTON CONSULTANTS LTD. Abbotsford Office 110-34077 Gladys Avenue Abbotsford, BC V2S 2E8 T: 604.855.0206 F: 604.853.1186 abbotsford@levelton.com www.levelton.com December 16, 2015 Levelton File # R715-1604-00

More information

Geotechnical & Environmental Consultants 9725 SW Beaverton-Hillsdale Hwy., Suite 140 Portland, OR FAX

Geotechnical & Environmental Consultants 9725 SW Beaverton-Hillsdale Hwy., Suite 140 Portland, OR FAX Geotechnical & Environmental Consultants 972 SW BeavertonHillsdale Hwy., Suite 140 Portland, OR 9700334 03413478 FAX 03448034 TECHNICAL MEMORANDUM To: Mark Libby, PE / HDR Engineering, Inc. Date: October

More information

A Case Study: Foundation Design in Liquefiable Site

A Case Study: Foundation Design in Liquefiable Site RESEARCH ARTICLE OPEN ACCESS A Case Study: Foundation Design in Liquefiable Site Tahar Ayadat* *(Department of Civil Engineering, College of Engineering, PMU University, P.O. Box 1664, Al-Khobar, 31952,

More information

San Antonio Water System Standard Specifications for Construction ITEM NO. 804 EXCAVATION, TRENCHING AND BACKFILL

San Antonio Water System Standard Specifications for Construction ITEM NO. 804 EXCAVATION, TRENCHING AND BACKFILL ITEM NO. 804 EXCAVATION, TRENCHING AND BACKFILL 804.1 DESCRIPTION: This section shall govern the excavation, trenching, and backfilling for water, sanitary sewer, and recycle mains construction, unless

More information

Subsurface Exploration and Foundation Analysis Proposed New Weight Room / Fieldhouse Building 429 N Highway 83 Leakey, Texas

Subsurface Exploration and Foundation Analysis Proposed New Weight Room / Fieldhouse Building 429 N Highway 83 Leakey, Texas Subsurface Exploration and Foundation Analysis Proposed New Weight Room / Fieldhouse Building 429 N Highway 83 Leakey, Texas InTEC Project No. S161639 April 18, 2016 Leakey ISD P.O. Box 1129 Leakey, Texas

More information

FORT ROUGE GLASS GEOTECHNICAL INVESTIGATION SOUTH LANDING BUSINESS PARK. RM of MacDONALD, MANITOBA

FORT ROUGE GLASS GEOTECHNICAL INVESTIGATION SOUTH LANDING BUSINESS PARK. RM of MacDONALD, MANITOBA FORT ROUGE GLASS GEOTECHNICAL INVESTIGATION SOUTH LANDING BUSINESS PARK RM of MacDONALD, MANITOBA Prepared for: Berntt Holdings Ltd. Winnipeg, Manitoba October 2016 File #163984 Table of Contents 1.0

More information

PD - 6 THRUST RESTRAINT DESIGN EQUATIONS AND SOIL PARAMETERS FOR DUCTILE IRON AND PVC PIPE

PD - 6 THRUST RESTRAINT DESIGN EQUATIONS AND SOIL PARAMETERS FOR DUCTILE IRON AND PVC PIPE PD - 6 THRUST RESTRAINT DESIGN EQUATIONS AND SOIL PARAMETERS FOR DUCTILE IRON AND PVC PIPE 4 3 2 1 D D C C B B A A 4 3 2 1 Thrust Restraint Design Equations and Soil Parameters These equations and soil

More information

REPORT OF SUBSURFACE EXPLORATION

REPORT OF SUBSURFACE EXPLORATION REPORT OF SUBSURFACE EXPLORATION WELDING & JOINING TECHNOLOGY FACILITY NORTH GEORGIA TECHNICAL COLLEGE CLARKESVILLE, GEORGIA S&ME PROJECT NO. 161-10-061 Prepared For: LW Engineering, P.C. Post Office Box

More information

PE Exam Review - Geotechnical

PE Exam Review - Geotechnical PE Exam Review - Geotechnical Resources and Visual Aids Item Page I. Glossary... 11 II. Parameters... 9 III. Equations....11 IV. Tables, Charts & Diagrams... 14 1. Module 1 - Soil Classification... 14

More information

Section 1I-3 - Bioswales

Section 1I-3 - Bioswales BIOSWALES (Numbering pending) These specifications compliment the bioswale design portion of the Iowa Stormwater Management Manual in Chapter 2, Section 2I-3. Sections of the following documents, as referenced

More information

Temporary Structures. Excavations and Excavation Supports

Temporary Structures. Excavations and Excavation Supports UNIVERSITY OF WASHINGTON DEPARTMENT OF CONSTRUCTION MANAGEMENT CM 420 TEMPORARY STRUCTURES Winter Quarter 2007 Professor Kamran M. Nemati Temporary Structures Excavations and Excavation Supports CM 420

More information

PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS PARKING GARAGE STANTON STREET AND AUSTIN BLUFFS PARKWAY COLORADO SPRINGS, COLORADO

PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS PARKING GARAGE STANTON STREET AND AUSTIN BLUFFS PARKWAY COLORADO SPRINGS, COLORADO PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS PARKING GARAGE STANTON STREET AND AUSTIN BLUFFS PARKWAY COLORADO SPRINGS, COLORADO Prepared for: UNIVERSITY OF COLORADO AT COLORADO SPRINGS Facilities Services

More information

SOILS INVESTIGATION REPORT The Sorrento Apartments Hobbs, New Mexico

SOILS INVESTIGATION REPORT The Sorrento Apartments Hobbs, New Mexico SOILS INVESTIGATION REPORT The Sorrento Apartments Hobbs, New Mexico PREPARED FOR: Ted Trout Architect & Associates, LTD. Attn: Cesar Corrales 6363 Woodway Suite 00 Houston, TX 7707 Debra P. Hicks, PE/LSI

More information

Report of Geotechnical Study

Report of Geotechnical Study Report of Geotechnical Study Baltimore Sun Consolidation Baltimore, Maryland F&R Project No. 75V0084 Prepared For: 901 Dulaney Valley Road, Suite 801 Towson, MD 21204 Prepared By: Froehling & Robertson,

More information

Subsurface Investigation and Geotechnical Analysis Target Outparcel Midlothian Turnpike Richmond, Virginia. Client: Interface Properties

Subsurface Investigation and Geotechnical Analysis Target Outparcel Midlothian Turnpike Richmond, Virginia. Client: Interface Properties Subsurface Investigation and Geotechnical Analysis Target Outparcel 11309 Midlothian Turnpike Richmond, Virginia Client: Interface Properties December 5, 2017 December 5, 2017 The Heritage Group, LLC Attn:

More information

Geotechnical Assessment Clackamette Cove Development Oregon City, Oregon

Geotechnical Assessment Clackamette Cove Development Oregon City, Oregon Geotechnical Assessment Development Prepared for: Pacific Property Search, LLC May 26, 2011 Table of Contents 1.0 INTRODUCTION AND LIMITATIONS... 1 2.0 SITE DESCRIPTION AND PROJECT UNDERSTANDING... 1

More information

COMPACTED CLAY LINERS

COMPACTED CLAY LINERS Technical Reference Document for Liquid Manure Storage Structures COMPACTED CLAY LINERS Table of Contents SECTION 1 - PURPOSE AND SCOPE 1.1. Purpose of the Technical Reference Document 1.2. Requirement

More information

ACKNOWLEDGMENT OF SPONSORSHIP

ACKNOWLEDGMENT OF SPONSORSHIP ACKNOWLEDGMENT OF SPONSORSHIP This work was sponsored by the American Association of State Highway and Transportation Officials, in cooperation with the Federal Highway Administration, and was conducted

More information