CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE

Size: px
Start display at page:

Download "CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE"

Transcription

1 CITY OF GLENDORA COUNTRY CLUB RESERVOIR IMPROVEMENTS PLAN NO REQUEST FOR INFORMATION (RFI) LOG RFI # DATE SHEET # RFI RESPONSE DATE 1 4/13/2016 Questions below pertain to note 4 per drawing, which states: Slope of excavation and the extent of over-excavation shall be field determined by the geotechnical engineer or his representative. Shoring shall be provided if necessary to support sides of excavation. Field determination of slope excavation results to unforeseen cost at time of bid. Please provide the degree/angle/steepness of the cut slope for bidding purposes. Per geotechnical report section Construction Cut - " no steeper than 1:1 (horizontal:vertical) with the lower 5 feet being vertical " 2 4/13/ /13/ /13/2016 Limits of over-excavation is not clearly defined and refers to field determination. Please provide a limit of over-excavation so the necessary cost can be accounted for at time of bid. Shoring to be provided if necessary is ambiguous and assumed to be contingent upon field determination by the geotechnical engineer or his representative. Cost cannot be determined until further direction is provided. Please clarify if shoring should be accounted for at time of bid. Residential homes are located near the jobsite. Please clarify if noise control regulations need to be followed. In addition, please specify if sound barriers are needed. Lateral overexcavation beyond footing is not necessary since retaining wall "A" is built on piles. Construction cuts shall be per geotechnical report section Construction Cut. Contractor shall be responsible for shoring and shoring design if shoring is necessary. No sound barrier is required. See Glendora Municipal Code Chapter 9.44 NOISE REGULATION. Section X, General Conditions, Working Times, "The Contractor shall not begin work before 7:00 a.m. and shall cease work by 4:00 p.m. and shall not work on Saturdays, Sundays or the following Holidays as observed in the City." / 5/3/16 5 4/13/2016 Refer to general condition, article no. 8, regarding water supply. Please indicate the nearest fire hydrant to the jobsite. City Map Page FH located at 2401 Country Club Drive 6 4/13/2016 G-5 7 4/13/2016 Reference note 1 under phase 1 on drawing G-5. Discharge connection point for the temporary overflow pipe is not shown. Please clarify where the pipe is to be routed and specify discharge location. Cost for temporary pipe is not called out on the bid item list, please specify the bid item to carry this cost. Approximate locations are described in Note #1. Contractor to field locate connection point and discharge location based on contractor's plan for demolition and grading. 4/27/2016 Include under Bid Item #7 - Demolition of Existing Site Piping 4/27/2016

2 8 4/13/2016 C-4 TANK 2C NOTE 1 Contractor acknowledges all work associated with interior columns are unknown. Please provide as-built of Tank No. 2C, or specify assumptions so associated cost for column demolition can be accounted for. If unknown, contractor suggest allowance to be carried for unknown scope of work. No allowance. For bidding purposes we have determined a total of sixteen (16) columns, reinforced, 18-inch diameter. 9 4/13/ /13/ /14/ /14/ /14/ /14/ /14/ /14/ /14/2016 C-4 TANK 2C NOTE 2 C-4 TANK 2C C-16 C A E G-2 NOTE 9 Note 2, please specify thickness and reinforcing of concrete floor and walls to be assumed for the bid. Note 4 implies contactor to empty existing tank. Please clarify if contractor is responsible to empty all existing water located inside the take. If contactor is responsible, please indicate water level and discharge location. Cathodic protection clarification: please reference the attachment for description and details. Please provide requirements for bolts, nuts and gaskets for different types of piping. Please provide detail for pipe supports for 12 DIP shown in Section C/C-16 and other similar locations. Identifies HRC Type 150. Type 150 is not offered by HRC. Please specify the correct Series. Slotted Pipe Drain calls for 4 corrugated, slotted polyethylene pipe by ADS. Section A/C-15 shows a callout for underdrain pipe as 4 PVC Sch40 perforated drain pipe. Please advise which requirement applies. Flushing/Disinfecting Procedures for New Main Installation, Dwg.G-2. Per Note 9, the City will chose the laboratory for water quality testing, but City is not responsible for laboratory errors or other situations beyond the City s control. Laboratory errors or other situations are beyond Contractor s control as well. We suggest an allowance item be created, if necessary, to cover cost. In the event of a discrepancy with quantities listed on the bid form versus actual quantities in the field, will the work be paid based on contract lump sum or unit price per bid items? Walls 12-inch reinforced concrete; floor 18-inch reinforced concrete. Contractor is responsible to empty the contents in the tank which consist of silt, sand and water at a depth of 5-feet. Contractor shall remove and dispose of material offsite. There will be no change in design. Bid per plans & specifications. See specifications section Pipe supports shall be per specification Section Callout shall be ammended to the following: #8 HEADED REBARS TYPE 555 BY HRC. REBAR TO MATCH VERT. REINF. (TYP. SEE NOTE 3.) LAP WITH MAIN BARS, IF REQUIRED, SHALL BE 5'-6" Use 4-inch PVC Sch 40 perforated drain pipe. No allowance. This is City policy and the language in City's procedures stands. See Specifications, Section II, Instructions to Bidders. The lump sum shall cover all items per the plans and specifications.

3 18 4/15/ /15/2016 BID ITEM 45 This is to confirm that the low bidder will be determined by the bid amount for the total bid including the alternate although the alternate may not be awarded. Does the chainlink fence have barb wire? See Specifications, Section II - Instructions to Bidders, Article 10 - Award of Contract, 10.2., "If alternate bids are called for in the Specifications, the contract may be awarded at the election of the City to the sucessful bidder on the base bid or on the base bid and any alternate or combination of alternatives." Yes, the chain link fence shall be installed with barb wire per C-7, Construction Note 7, SPPWC standard /15/ /15/ /15/2016 ALT. BID ITEM Can specifications for the gate operator & controller be provided. There are 2 types of cold tar, is this the liquid emulsion version or the heavy tar version. The 2 nd one required chipping the product, the first one can be sandblasted. Also, is that product consider hazardous? The contract states we have 390 working days to perform the work. Is this for the base bid or for both the base bid and alternate? Eliminate gate opener & controller. Gate will be manually opened and closed. For bidding purposes the City will assume the exisiting tank is coated with the heavy tar version that will require chipping. The City will test the material to determine if it is hazardous. The contract duration allows 390 working days for the total base bid and alternate bid, complete. No additional days will be provided if the alternate bid is accepted. 23 4/15/2016 C-17 DETAILS Manholes 1 through 4 as precast, with core drilled pipe openings and Press Seal Manhole Connectors, and floor grout. Note (1) refers to SPPWC which shows bottom portion of the manhole as cast-inplace. Please clarify the design of the manholes and, if necessary, provide specification for precast structures. Replace Note (1) on sheet C-17 with the following: Manhole components conform to current specifications, ASTM C-478. Construction Manhole per SSPWC 321-2, either method is acceptable. 4/27/ /15/2016 C-11 Your profile on Retaining Wall A shows the top of footing elevation but the footing only scales (scaled drawing) 1 ft. Your pile cap is 1 and footing is 2 for a total of 3 correct? Total thickness of footing is 3' with top of pile extending 1 foot into bottom of footing. 25 E-2 NOTE 2 Drawing E-2, Note # 2 Remove existing RTU and MDS 900 radio and relocate to new RTU cabinet at new tank. Note # 13 states to provide new RTU cabinet with Micro-hybrid rtu/plc with I/O modules. City has determined that both existing RTU and radio will be removed and a new RTU and radio will be installed in new RTU cabinet /20/ What size is the new RTU cabinet and is the micro-hybrid rtu/plc with i/o modules, the relocated RTU backboard from existing RTU cabinet or new? Please clarify. Spec section 1.02 "Pre Qualification of contractor" states "Bids will only be accepted from experienced..." Please confirm this section applies to Tank Subcontractor. City has requested engineer to prepare design drawings and specifications for new RTU/PLC. Subcontractors apply to Specification 13205, Part 1, Section Qualified subscontractors shall submit a list of at least five (5) such projects with bid proposal.

4 28 4/20/ /22/ Same Spec section 1.05 " Submittals" - Is the City wanting a submittal attached to the bid proposal? Intent is to subcontract the Welded Steel Water Storage Tank to a contractor that will meet the specifications. Please confirm subcontractors who meet this pre-qualification will be accepted in the bid package submitted by PCL. Submittals are required by the succesful bidder following the contract award; submittals shall not be submitted with bid proposal. See RFI # /22/2016 PLANS SHT. 32 NOTE 13 PLC is required to be furnished. Please provide a specification for this PLC, as well as any other requirements related to it. Is programming required? If so, please provide the requirements. Please describe the purpose of the PLC. City has requested engineer to prepare design drawings and specifications for new RTU/PLC. Programming will be performed by City. Purpose of the PLC is to collect data from level gages and hatch open alarm, process data, and send data to City's SCADA system. 31 4/22/ /22/2016 C-1 NOTE 11 Specifies to remove 10 reservoir drain pipe. The line called out on the grading plan shows the pipe extending underneath Tanks 2C and extending out into the existing roadway. Since the pipe is a drain pipe and shown within Tank 2C, depth is presumed to be approximately 20ft below grade. Please confirm depth of pipe. The depth is approximate for bidding purposes. Contractor is responsible to pothole exisitng pipe once projects commences and remove 5-feet outisde tank wall. The drawings and the specifications require the tank height meet the freeboard requirements of AWWA D100. AWWA D100 states the freeboard is measured from the Mean Operating Level (MOL) to the lowest portion of the roof framing (rafters). The specifications on the drawings show the freeboard measured from the overflow elevation to the bottom of the roof plate. How should the freeboard be measured? If it is per AWWA D100, what is the mean operating level? AWWA D100 governs. Mean Operating Level is /22/2016 This seems like it will be a potential problem with the altitude selection and the very low inlet pressure. They also want the check function which means the discharge of the pilots will be connected to downstream which just worsens the pressure differential condition. Control valves (Singer and Clay) generally require a minimum of 10 psi pressure differential. Max inlet is 9.8 psi. Min inlet is 0 psi. Plus the tank as the outlet pressure which could be 5-10 psi depending on height. So we don t have enough differential to open the valve. Revise table in specification section A as follows: Maximum inlet pressure (valve closed), psi = 20 psi; Minimum inlet pressure (valve open), psi = 9 psi. Valve will close once closing set point (Mean Operating Level = ) is reached and 9 psi valve inlet pressure will fill cover chamber to close valve. Valve will open once opening set point is reached, pressure in cover chamber will be released, and pumps will provide necessary line pressure (10+ psi) and open valve. Cla-Val representative has confirmed that a line pressure of 3-5 psi is sufficient in order to open or close altitude valve.

5 34 4/22/2016 Specification does not indicated if the tank is to be designed using Use Group II, or Use Group III. The free board requirement for these two Use Groups vary approximately 3-feet which means that the shell height is determined by which Use Group is correct. Design using Use Group III per Sheet S-1, Loads, item 3. 4/26/ /22/ States under 1.05, Submittals E, "The Owner will provide the services of an independent radiopraph inspector." The cost of the inspector is paid for by the Owner. Whereas Section 3.03.B states, "The Contractor shall employ the services of a welding supervisor and that the paying for the inspection and testing shall be paid for by the Contractor." Which of these two statements is correct? The Contractor is to pay for all required inspections for all work performed per specifications B. The Owner will, at their discretion, perform and pay for any additional independent inspections and testing per C. 36 4/22/2016 BID ITEM 50 Clarification on Bid Item #50: Alternative Bid Item: Please clarify whether the entire interior (i.e., roof, rafters, shell and floor) has coal tar enamel to be removed & recoated with epoxy. For bidding purposes the entire interior cold tar enamel is to be removed and recoated. 37 4/22/ B Specification Section 13205, 3.03B, states that the Contractor is to employ the services of a welding inspector independent of the tank erection forman's jurisdiction. How long is the welding inspector to be employed? For the duration of the project? Or for the first week? Please clarify. An independent welding supervisor shall be onsite during the entire tank erection. Special inspection is required for all tank welds and shall be paid for by the Contractor. Certified reports shall be submitted to the City prior to the application of coating. 38 4/22/2016 Addendum No. 1 states, Contractor is responsible to size the tanks and ring footings per the Specifications, Section Welded Steel Water Storage Tank. Is this statement allowing the tank contractor to size the ringwall and reinforcing according to their calculations and the geotech report (and ignore the size and reinforcing in the Contract Drawings)? Per specification G minimum requirements shown in contract documents shall be used. City's structural engineer will review contractor's design and determine if revisions to foundation are necessary. 39 4/22/ /22/ /22/2016 Contract Drawing S-4 calls out the ring thicknesses on the tank shell. If the stamped calculations can prove thinner material is adequate, can thinner material be used? Section 14 of AWWA D was not cited in the Contract Specifications. Can the allowable stresses in Section 14 be used to design the tank shell? Is the wind speed called out in the Contract Specifications (115 mph) an ultimate value per ASCE 7-10 and 2013 CBC or an Allowable Stress Value to be directly designed for in AWWA D100-11? For reference, the wind maps in ASCE 7-10 and 2013 CBC are ultimate values. Plate thickness shall not be less than minimum plate thicknesses noted on drawings. Section 14 of AWWA D100 may be used where applicable, however, plate thicknesses shown on drawings are minimum. 115 mph wind speed is an ultimate, strength level, value for Risk Category III/IV structures per ASCE 7-10 and 2013 CBC. The tank shall be designed in accordance with the wind provisions of ASCE 7-10 and CBC 2013.

6 42 4/22/2016 Contract Specification 13205, Section 2.03-Q references seismic anchor bolts. However, the foundation cross section in the drawings does not show anchor bolts. Please confirm whether the tank needs to be anchored or not (or if it depends on the stamped calculations). Preliminary tank calculations indicate that the tank is stable and anchor bolts are not required. However, this will need to be verified by the tank designer as part of their stamped calculation package.

Invitation to Bid # CC Project Title: High Zone 5.0 Million Gallon Reinforced Concrete Culinary Water Tank Project No.

Invitation to Bid # CC Project Title: High Zone 5.0 Million Gallon Reinforced Concrete Culinary Water Tank Project No. Riverton City Purchasing Department 12830 South 1700 West Riverton, UT 84065 801-208-3175 Fax: 801-254-1810 May 5, 2017 ADDENDUM #3 Invitation to Bid # CC17-332 Project Title: High Zone 5.0 Million Gallon

More information

SECTION GROUND WATER STORAGE TANKS

SECTION GROUND WATER STORAGE TANKS SECTION 33 16 13 GROUND WATER STORAGE TANKS PART 1: GENERAL 1.01 SCOPE A. Section includes requirements for designing, fabricating, and erecting a welded steel ground storage tank. 1.02 SYSTEM DESCRIPTION

More information

UNITED INDUSTRIES GROUP INC.

UNITED INDUSTRIES GROUP INC. SECTION 13205 AWWA D100-05 WELDED STEEL RESERVOIR SPECIFICATIONS REFERENCE SPECIFICATIONS, CODES AND STANDARDS. Commercial Standards: AWWA/ANSI D100-05 Welded Steel Tanks for Water Storage ASTM A36-01

More information

JANUARY 25, 2016 ADDENDUM NO. 3 FOR. ORD Baggage Service Road Retaining Wall Repair

JANUARY 25, 2016 ADDENDUM NO. 3 FOR. ORD Baggage Service Road Retaining Wall Repair JANUARY 25, 2016 ADDENDUM NO. 3 FOR ORD Baggage Service Road Retaining Wall Repair Specifications and Contract Documents Number: 132110 CDA Project Number: H6163.15-02 For which bids are scheduled to be

More information

SPECIAL INSPECTION AND TESTING AGREEMENT

SPECIAL INSPECTION AND TESTING AGREEMENT COUNTY OF MENDOCINO DEPARTMENT OF PLANNING AND BUILDING SERVICES 860 NORTH BUSH STREET UKIAH CALIFORNIA 95482 120 WEST FIR STREET FT. BRAGG CALIFORNIA 95437 STEVE DUNNICLIFF, DIRECTOR PHONE: 707-234-6650

More information

SECTION SLUDGE HOLDING TANK DEWATERING

SECTION SLUDGE HOLDING TANK DEWATERING SECTION 13215 SLUDGE HOLDING TANK DEWATERING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Dewatering and cleaning of sludge holding tank and sludge disposal. Contractor shall pay for all sludge removal,

More information

CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1

CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1 Addendum No. 1 September 26, 2016 Page 1 of 8 CITY OF PORTSMOUTH, NEW HAMPSHIRE GREENLAND WELL PUMP STATION REPLACEMENT ADDENDUM NO. 1 This Addendum forms part of the original contract drawings and specifications

More information

SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address:

SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION. Project Address: SPECIAL INSPECTION AND OBSERVATION PROGRAM CITY OF CONCORD BUILDING DIVISION Permit Application #: Project Address: Purpose: To meet the requirements of CBC Section 1704.3 this form may be used as a statement

More information

HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS

HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS Appendix A HAMPTON ROADS AREA STATEMENT OF SPECIAL INSPECTIONS PROJECT PERMIT APPLICANT PRIMARY RDP OF RECORD STRUCTURAL ENGINEER OF RECORD This Statement of Special Inspections is submitted as a condition

More information

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications.

ADDENDUM NO. 5. Except as hereinafter specified, the work shall be in accordance with the drawings and specifications. ADDENDUM NO. 5 ITB-CD-CME-16-10 Southern Well Field Expansion: Equip 5 Wells and New Raw Water Main Phase 2 ISSUE DATE: August 22, 2016 DUE DATE: August 25, 2016 @ 2:00 p.m. SUBJECT: Addendum No. 5 INTENT:

More information

SECTION GROUND STORAGE TANK

SECTION GROUND STORAGE TANK SECTION 13210 GROUND STORAGE TANK PART 1 GENERAL 1.01 Summary A. Section Includes: Provision for welded steel storage tank design, fabrication, construction and erection, including tank accessories. B.

More information

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address:

SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division. Project Address: SPECIAL INSPECTION AND OBSERVATION PROGRAM City of Walnut Creek Building Division Permit Application #: Project Address: Purpose: To meet the requirements of City of Walnut Creek Municipal Code Section

More information

CIVIC CENTER NORTH PUMP STATION AND JOHN DUCKETT PUMP STATION STANDBY GENERATOR REPLACEMENT PROJECT

CIVIC CENTER NORTH PUMP STATION AND JOHN DUCKETT PUMP STATION STANDBY GENERATOR REPLACEMENT PROJECT FOR BIDDING ONLY MARIN COUNTY, CALIFORNIA CIVIC CENTER NORTH PUMP STATION AND JOHN DUCKETT PUMP STATION STANDBY GENERATOR REPLACEMENT PROJECT JOB NO. 10300-11/-09 VOLUME 4: DRAWINGS NOVEMBER 2011 DISTRICT

More information

Bi-Directional Static Load Testing of Drilled Shafts

Bi-Directional Static Load Testing of Drilled Shafts Supplemental Technical Specification for Bi-Directional Static Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 2, 2015 1.0 GENERAL This work shall consist of furnishing all

More information

Bi-Directional Static Load Testing of Drilled Shafts

Bi-Directional Static Load Testing of Drilled Shafts Supplemental Technical Specification for Bi-Directional Static Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (01/18) 1.0 GENERAL This work shall consist of furnishing all materials, equipment,

More information

STATEMENT OF SPECIAL INSPECTION FORM

STATEMENT OF SPECIAL INSPECTION FORM Project Title: Permit #: Project Address: STATEMENT OF SPECIAL INSPECTION FORM This Statement of Special Inspections is submitted in fulfillment of the requirements of CBC Sections 1704 and 1705. Special

More information

SPECIFICATIONS - DETAILED PROVISIONS Section Welded Steel Tanks for Water Storage C O N T E N T S

SPECIFICATIONS - DETAILED PROVISIONS Section Welded Steel Tanks for Water Storage C O N T E N T S SPECIFICATIONS - DETAILED PROVISIONS Section 13311 - Welded Steel Tanks for Water Storage C O N T E N T S PART 1 - GENERAL... 1 1.01 REQUIREMENT... 1 1.02 QUALITY ASSURANCE... 2 1.03 SUBMITTALS... 2 1.04

More information

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction.

2. A preconstruction meeting with the TWA s staff is required prior to initiating construction. General: 1. Construct utilities in accordance to TWA approved plans and shop drawings. Any deviation from the approved plans shall be approved by the DEVELOPER S ENGINEER and TWA 2. A preconstruction meeting

More information

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS

2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS 2012 VIRGINIA TECH SCHEDULE OF SPECIAL INSPECTIONS HECO-6 GENERAL Pre-construction conference Preconstruction meeting Scheduled by SI with the Contractor, UBO, A/E, and relevant subs prior to commencement

More information

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831)

PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA (831) FAX: (831) County of Santa Cruz PLANNING DEPARTMENT 701 OCEAN STREET, 4 TH FLOOR, SANTA CRUZ, CA 95060 (831) 4542580 FA: (831) 4542131 STATEMENT OF SPECIAL INSPECTIONS California Building Code 1704.3 Prior to issuance,

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS

SECTION 39 - MANHOLES TABLE OF CONTENTS Section SECTION 39 - MANHOLES TABLE OF CONTENTS Page 39-1 GENERAL... 39.1 39-2 CONCRETE MANHOLES... 39.1 39-2.01 NOT USED... 39.1 39-2.02 Concrete Storm Drain Manholes... 39.1 39-3 SADDLE SEWER MANHOLES...

More information

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans. INC. ENGINEERING/CONSTRUCTION/MANUFACTURING /WWW.CONTAINWATER.COM SPRINGS, TEXAS. 78620 MODEL SPECIFICATION FOR CONTAIN WATER INC. 30 DEGREE ROOF CORRUGATED STEEL WATER STORAGE Part 1 GENERAL 1.01 SECTION

More information

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications

MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications MODEL SPECIFICATIONS: Hydraulically Driven Steel Underpinning Pile Specifications Mar/2008 v1.0 SECTION 02255 HYDRAULICLY DRIVEN STEEL UNDERPINNING PILES PART 1 GENERAL 1.01 SCOPE OF WORK The work shall

More information

ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14

ADDENDUM #4. Lanier Filter Plant Ozone System Safety Improvements BL079-14 September 24, 2014 ADDENDUM #4 Lanier Filter Plant Ozone System Safety Improvements BL079-14 Q1. Please clarify how many submarine doors the perimeter gaskets and gasket hardware must be replaced on. A1.

More information

Project Address: Name of Person Completing Form:

Project Address: Name of Person Completing Form: Statement of Inspections This form is provided as a way to list aspects of the project that require special inspection and testing in accordance with IBC Sections 107.1, 1704, and 1705 and define duties

More information

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans.

1.02 RELATED SECTIONS: Water supply piping, water use piping, electrical, irrigation, foundations, site plans. INC. ENGINEERING/CONSTRUCTION/MANUFACTURING /WWW.CONTAINWATER.COM SPRINGS, TEXAS. 78620 MODEL SPECIFICATION FOR CONTAIN WATER INC. DOME ROOF CORRUGATED STEEL WATER STORAGE TANKS. Part 1 GENERAL 1.01 SECTION

More information

Statement of Special Inspections 2013 CBC

Statement of Special Inspections 2013 CBC BUILDIG & SAFET DIVISIO 2729 Prospect Park Drive Rancho Cordova, CA 95670 Phone: (916) 851-8760 Fax: (916) 851-8762 Statement of Special Inspections 2013 CBC PERMIT #: PROJECT ADDRESS: This Statement of

More information

SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION

SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION 820-1 SCOPE OF WORK: SECTION 820 PUMP STATION DEMOLITION AND SITE RESTORATION a. Furnish all labor, materials, equipment, and incidentals required for demolition and/or removal and disposal of existing

More information

Final Estimates Level 2

Final Estimates Level 2 Florida Department of TRANSPORTATION Final Estimates Level 2 Module 6: Structures 11/1/2017 FDOT Final Estimates Level 2 Release 11, Module 6 1 6-1 Module Content Concrete Structures Bridges Substructure

More information

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2)

Structural Tests and Special Inspections Form. Inspection of Fabricators (1704.2) Inspection of Fabricators (1704.2) Furnish inspection reports (1704.2.1) - Fabricators that have not been approved Provide a Certificate of Compliance (1704.2.2) - Approved Fabricators Steel Construction

More information

Statement of Special Inspection Requirements

Statement of Special Inspection Requirements Statement of Special Inspection Requirements California Building Code Chapter 17 Construction plans shall include a statement of special inspection in accordance with CBC chapter 17. The statement of special

More information

CLARIFICATIONS TO TECHNICAL SPECIFICATIONS SECTIONS

CLARIFICATIONS TO TECHNICAL SPECIFICATIONS SECTIONS C-44 Reservoir/STA System Discharge Project RFB: 6000000620 Addendum No. 1 March 2014 CLARIFICATIONS TO TECHNICAL SPECIFICATIONS SECTIONS HDR Engineering, Inc. SECTION 02401 DEWATERING, COFFERDAM AND BYPASS

More information

PUBLIC WORKS SKAGIT COUNTY SAMISH ISLAND ROAD SAMISH ISLAND ROAD SLIDE REPAIR

PUBLIC WORKS SKAGIT COUNTY SAMISH ISLAND ROAD SAMISH ISLAND ROAD SLIDE REPAIR EASEMENT NOTES:. EASEMENT LIMIT SHOWN AS PROVIDED BY. TESC NOTES:. CONTRACTOR SHALL DEVELOP TEMPORARY EROSION AND SEDIMENT CONTROL PLAN AND PROVIDE ONSITE CERTIFIED EROSION AND SEDIMENT CONTROL LEAD (CESCL)

More information

UNIFIED FACILITIES GUIDE SPECIFICATIONS

UNIFIED FACILITIES GUIDE SPECIFICATIONS USACE / NAVFAC / AFCEC / NASA UFGS-33 16 13.16 (April 2006) ----------------------------- Preparing Activity: NAVFAC Replacing without change UFGS-13208 (August 2004) UNIFIED FACILITIES GUIDE SPECIFICATIONS

More information

TG Structural Steel Superstructure

TG Structural Steel Superstructure TG07.1 - Structural Steel Superstructure Questions are numbered in the order received. Numbers missing in the sequence either have been answered in a previous response set or will be included in a future

More information

ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. PS 061 SEVEN SPRINGS WASTEWATER TREATMENT FACILITY IMPROVEMENTS PASCO COUNTY,

More information

SPECIAL INSPECTION AGREEMENT

SPECIAL INSPECTION AGREEMENT DEVELOPMENT SERVICES DEPARTMENT BUILDING AND SAFETY DIVISION 156 S. BROADWAY, SUITE 130 TURLOCK, CALIFORNIA 95380 PHONE 209-668-5560 FAX 209-668-5107 SPECIAL INSPECTION AGREEMENT PERMIT NUMBER: DATE: OWNER:

More information

CHARLES COUNTY GOVERNMENT ITB NO MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY CLARIFIER NO. 1 IMPROVEMENTS

CHARLES COUNTY GOVERNMENT ITB NO MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY CLARIFIER NO. 1 IMPROVEMENTS CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 February 07, 2017 ITB NO. 17-17 MATTAWOMAN WATER RECLAMATION FACILITY (MWRF) PRIMARY

More information

Statement of Special Inspections

Statement of Special Inspections Statement of Special Inspections SUCF Project No: Project Title: Registered Design Professionals in Responsible Charge: (Name) (Address) Architect: Structural Engineer: Mechanical Engineer: Identification

More information

DISTRICT OF TOFINO BARRS MOUNTIAN RESERVOIR REPLACEMENT PROJECT. Attached, please find Addendum # 1 for the above noted project.

DISTRICT OF TOFINO BARRS MOUNTIAN RESERVOIR REPLACEMENT PROJECT. Attached, please find Addendum # 1 for the above noted project. DATE DESTINATION EMAIL NO OF PAGES (INCL THIS PAGE) FILE January 13, 2017 n/a 11 2231-35306-02 TO FROM ALL DOCUMENT HOLDERS C. Pogson COMPANY CITY ORIGINALS TO BE: Filed Mailed Couriered OTHER (SPECIFY)

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2014 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) Plan Check Engineer:

More information

Building Department Informational Handout

Building Department Informational Handout City of Sonoma Building Department Informational Handout Statement of Special Inspections Handout No: 7 Revised 1/12/2017 Project Name: Project Address: For building permit applications of projects requiring

More information

SCALE BAR 1:2500 RM OF WOODLANDS OVERALL PLAN - LOW PRESSURE SEWER MAIN. Certificate of Authorization JESSICA MANNESS ENGINEERING, INC. No.

SCALE BAR 1:2500 RM OF WOODLANDS OVERALL PLAN - LOW PRESSURE SEWER MAIN. Certificate of Authorization JESSICA MANNESS ENGINEERING, INC. No. OF SURVEY OVERALL PLAN - LOW PRESSURE SEWER MAIN 0 50 100 SCALE BAR 1:2500 200 500 THIS IS NOT A LEGAL PLAN - CONCEPT ONLY OF SURVEY PLAN - LOW PRESSURE SEWER MAIN 0 50 100 SCALE BAR 1:2500 200 500 THIS

More information

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities

ADDENDUM NO. 1. Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities ADDENDUM NO. TO Mallory Valley Utility District Technical Specifications & Design Criteria for Water Supply & Distribution Facilities Date of Addendum: December, 00 Hethcoat & Davis, Inc. 78 Franklin Road,

More information

Failure to acknowledge all addenda in the BID may cause rejection of the BID. See Instructions to Bidders.

Failure to acknowledge all addenda in the BID may cause rejection of the BID. See Instructions to Bidders. Addendum #1 Project: Coteau Street & Utility Improvements Bid Date: 1:00 P.M., Local Time, March 20, 2017 Bid Location: Office of the City Administrator/Clerk, City of Lake Benton 106 S. Center Street

More information

NOTICE TO BIDDERS FOR THE

NOTICE TO BIDDERS FOR THE NOTICE TO BIDDERS FOR THE STRUCTURAL REPAIRS, APPLICATION OF 150 MIL THICK POLYURETHANE FOR INTERNAL LINING OF RESERVOIR 4A, REMOVAL AND REPLACEMENT OF A 7.5 HP PUMP, PIPES, FITTINGS, ELECTRICAL CONDUITS,

More information

SECTION BASIC ELECTRICAL MATERIALS AND METHODS

SECTION BASIC ELECTRICAL MATERIALS AND METHODS SECTION 26 05 05 BASIC ELECTRICAL MATERIALS PART 1 - GENERAL 1.1 SUMMARY A. Section includes the limited scope construction materials and methods for application with electrical installations as follows:

More information

Port KC RFP NORTHLAND PARK BUILDING V

Port KC RFP NORTHLAND PARK BUILDING V Port KC RFP NORTHLAND PARK BUILDING V 1. The RFP refers to landscaping plans. However, it does not appear that the landscaping plans were issued with the rest of the RFP. Will these be issued with an addendum?

More information

1. Division 01 Section General Requirements - Temporary Facilities and Controls. 2. Division 31 Section Earthwork.

1. Division 01 Section General Requirements - Temporary Facilities and Controls. 2. Division 31 Section Earthwork. PAGE 334000-1 SECTION 334000 PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification sections,

More information

SECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete.

SECTION STORM DRAINAGE SYSTEM Excavating, Backfilling, and Compaction for Utilities Cast-in-place Concrete. SECTION 02720 STORM DRAINAGE SYSTEM PART 1 GENERAL 1.01 SUMMARY A. Related Sections: 1. 02221 - Excavating, Backfilling, and Compaction for Utilities. 2. 03300 - Cast-in-place Concrete. 1.02 REFERENCES

More information

SECTION PRECAST CONCRETE BIOSOLIDS STORAGE TANK

SECTION PRECAST CONCRETE BIOSOLIDS STORAGE TANK PART 1 GENERAL 1.1 Summary SECTION 13200 PRECAST CONCRETE BIOSOLIDS STORAGE TANK A. Biosolids Storage Tank 1.2 System Description A. Precast concrete storage tank with precast concrete roof, beams, columns,

More information

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012)

Statement of Special Inspections Michigan Building Code 2012 (MBC 2012) Gaines Charter Township 8555 Kalamazoo Ave SE Caledonia MI 49316 PH: 616 698-6640 Fax: 616 698-2490 www.gainestownship.org Building Department Statement of Special Inspections Michigan Building Code 2012

More information

STANDARDIZED STRUCTURES

STANDARDIZED STRUCTURES Q, QH & QL TOWERS 16.1 Q, QH, and QL Towers General Description The series includes three and four leg angle towers, which are suited for a variety of antenna mounting positions and load conditions. The

More information

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL

SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL SCHOOL DISTRICT PALM BEACH COUNTY BUILDING DEPARTMENT PLAN REVIEW CHECK LIST -- STRUCTURAL 3300 SUMMIT BOULEVARD WEST PALM BEACH, FLORIDA 33406 TEL (561) 688-7687 FAX (561) 688-7654 http://www.palmbeach.k12.fl.us/fm/bd/index.htm

More information

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY CAST-IN-PLACE. Section CAST-IN-PLACE CONCRETE MANHOLES

NORTH HARRIS COUNTY REGIONAL WATER AUTHORITY CAST-IN-PLACE. Section CAST-IN-PLACE CONCRETE MANHOLES PART 1 GENERAL 1.01 SUMMARY This Section includes: Section 02081 CAST-IN-PLACE A. Cast-in-place concrete manholes for sanitary sewers and storm sewers, including box sewers. B. Pile-supported concrete

More information

Rapid Axial Load Testing of Drilled Shafts

Rapid Axial Load Testing of Drilled Shafts Supplemental Technical Specification for Rapid Axial Load Testing of Drilled Shafts SCDOT Designation: SC-M-712 (9/15) September 4, 2015 1.0 GENERAL This work shall consist of performing a rapid axial

More information

GWINNETT COUNTY STORM SEWER PIPE STANDARDS

GWINNETT COUNTY STORM SEWER PIPE STANDARDS 1.0 Standard Specifications GWINNETT COUNTY STORM SEWER PIPE STANDARDS 1.1 Unless otherwise specifically set forth herein or in the Gwinnett County Standard Drawings, all of the materials, methods of the

More information

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC)

Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Supplemental Plan Correction Sheet for LA Residential Code Prescriptive Design (2011 LARC) Plan Check Submittal Date: Plan Check #: Permit App.# Job Address: Applicant: Phone: ( ) P.C. Engineer: Phone:

More information

Ohio Department of Transportation - Prebid Questions

Ohio Department of Transportation - Prebid Questions Project No. 110467 Sale Date - 8/25/2011 HAM-83469 - CR-CR 239-9.49 (WINTON/ S. GILMORE ROAD) 8/22/2011 9:56:54 AM Pole E on plan page 323 shows that 2" anchor bolts should be used for this pole. However,

More information

SPECIAL INSPECTION AGREEMENT

SPECIAL INSPECTION AGREEMENT PART 1 STATEMENT OF SPECIAL INSPECTIONS When special inspection is required to be performed in accordance with International Building Code Chapter 17, a building permit cannot be issued until a statement

More information

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company

Mechanical Engineer of Record: (Smoke Control Systems Only) Name & License Company. Others: Responsible Party Name & License Company PRINCE WILLIAM COUNTY Department Development Services Building Development Division STATEMENT OF SPECIAL INSPECTIONS (Building/Other Structures other than Retaining Walls) Version 2015-12-31 Building Permit

More information

SPECIAL INSPECTION AGREEMENT FORM

SPECIAL INSPECTION AGREEMENT FORM CITY OF TRACY DEVELOPMENT & ENGINEERING SERVICES 333 CIVIC CENTER PLAZA, TRACY, CA 95376 P :( 209) 831-6400 F :( 209) 831-6439 http://www.ci.tracy.ca.us SPECIAL INSPECTION AGREEMENT FORM Prior to issuance

More information

***************************************************************************************************************

*************************************************************************************************************** 02720 STORM DRAINAGE SYSTEM *************************************************************************************************************** SPECIFIER: CSI MasterFormat 2004 number 33 40 00. ***************************************************************************************************************

More information

Exhibit A Scope Work Inclusions Revised Addendum 2 May 14, 2018

Exhibit A Scope Work Inclusions Revised Addendum 2 May 14, 2018 Exhibit A Scope Work Inclusions Revised Addendum 2 May 14, 2018 ALL BIDDERS ARE REQUIRED TO REVIEW THE APPLICABLE SCOPES OF WORK FOR EACH BID AND INCORPORATE THE FOLLOWING CHANGES PRIOR TO BID SUBMISSION.

More information

Section SPHEROID ELEVATED WATER STORAGE TANK

Section SPHEROID ELEVATED WATER STORAGE TANK Section 13210 SPHEROID ELEVATED WATER STORAGE TANK Note to Contract Specifier Specification clauses requiring revision or insert are highlighted and underlined. Specification notes are highlighted and

More information

2018 YEARLY BID FORMS SUPPLIER BID FORM. ITEM # 1: Fire Hydrants: 3 and 4 Bury, 3 ways, 5 ¼ valve opening, 6 mechanical joint shoe.

2018 YEARLY BID FORMS SUPPLIER BID FORM. ITEM # 1: Fire Hydrants: 3 and 4 Bury, 3 ways, 5 ¼ valve opening, 6 mechanical joint shoe. 2018 YEARLY BID FORMS SUPPLIER BID FORM ITEM # 1: Fire Hydrants: 3 and 4 Bury, 3 ways, 5 ¼ valve opening, 6 mechanical joint shoe. PHONE # OF BIDDER MAKE OF UNIT BID MODEL OF UNIT BID_ ITEM 3 BURY FIRE

More information

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections.

SANITARY SEWERS. B. Construct or relocate building sanitary sewer services, stubs, and connections. SANITARY SEWERS PART 1 - GENERAL 1.01 SECTION INCLUDES A. Sanitary Sewer Gravity Mains B. Sanitary Sewer Force Mains C. Sanitary Sewer Services 1.02 DESCRIPTION OF WORK A. Construct sanitary sewer gravity

More information

Specialty Applications. for Keystone Walls

Specialty Applications. for Keystone Walls for Walls SHEET INDEX Title Sheet Sheet 1 Soil Nail Facing Sheet 2 Rock/Shotcrete Facing Sheet 3 Manta Ray Anchor Wall Sheet 4 H-Pile Wall Facing Sheet 5 Sheet Pile Wall Facing Sheet 6 Railing per Site

More information

November 19, REVISED Bid Opening Date: December 4, 2018

November 19, REVISED Bid Opening Date: December 4, 2018 BOARD OF COUNTY COMMISSIONERS ORANGE COUNTY, FLORIDA Y19-709-CH / ADDENDUM # 3 WESTERN REGIONAL WATER SUPPLY FACILITY IMPROVEMENTS PHASE 3B REVISED Bid Opening Date: December 4, 2018 This addendum is hereby

More information

NOTICE TO BIDDERS FOR THE

NOTICE TO BIDDERS FOR THE NOTICE TO BIDDERS FOR THE STRUCTURAL REPAIR, APPLICATION OF 200 MIL THICK POLYURETHANE FOR INTERNAL LINING OF RESERVOIR 4A, REMOVAL AND REPLACEMENT OF AN EXISTING RETAINING WALL, A 7.5 HP PUMP, PIPES,

More information

Simplified Building Schematic for Typical Floor (Levels 9 through 22):

Simplified Building Schematic for Typical Floor (Levels 9 through 22): Introduction to Structural System Simplified Building Schematic for Typical Floor (Levels 9 through 22): Key: - Tower Columns - Tower Shear Walls - Parking Garage Columns - Parking Garage Shear Walls Solid

More information

RFB for Wastewater Force Main #3. October 2, Addendum 3: Clarifications and Questions from Pre-Bid Meeting Answered

RFB for Wastewater Force Main #3. October 2, Addendum 3: Clarifications and Questions from Pre-Bid Meeting Answered RFB for Wastewater Force Main #3 October 2, 2015 Addendum 3: Clarifications and Questions from Pre-Bid Meeting Answered The proposed force main will be required to transmit up to 1000 gallons of wastewater

More information

Civil and Structural Engineering CONSTRUCTION OF BRIDGE STRUCTURES SHALL BE IN ACCORDANCE WITH THE FOLLOWING SPECIFICATIONS, LISTED IN ORDER OF PRECEDENCE: 1. CDOT STANDARD SPECIFICATIONS FOR ROAD AND

More information

A NEW PRE-K BUILDING FOR BIG SPRING LAKE KINDERGARTEN SCHOOL FOR THE ALBERTVILLE CITY BOARD OF EDUCATION ALBERTVILLE, ALABAMA

A NEW PRE-K BUILDING FOR BIG SPRING LAKE KINDERGARTEN SCHOOL FOR THE ALBERTVILLE CITY BOARD OF EDUCATION ALBERTVILLE, ALABAMA McKee and Associates Architecture and Interior Design Addendum No. FOUR Date: 09.24.18 Project: A NEW PRE-K BUILDING FOR BIG SPRING LAKE KINDERGARTEN SCHOOL FOR THE ALBERTVILLE CITY BOARD OF EDUCATION

More information

SECTION STRUCTURAL STEEL

SECTION STRUCTURAL STEEL SECTION 051200 STRUCTURAL STEEL PART 1 GENERAL 1.01 SECTION INCLUDES A. Structural steel framing members and support members. B. Base plates, shear stud connectors. C. Grouting under base plates. 1.02

More information

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,

More information

INSPECTION REQUIREMENT ACKNOWLEDGEMENTS. Job Site Address:

INSPECTION REQUIREMENT ACKNOWLEDGEMENTS. Job Site Address: SPECIAL INSPECTION FORM and Special Inspection and Testing Agreement City of San Ramon Building & Safety Services 2401 Crow Canyon Rd., San Ramon, CA 94583 Office: (925) 973-2580 Fax (925) 242-9312 www.sanramon.ca.gov

More information

MANDATORY PRE-BID MEETING FLORIDA KEYS AQUEDUCT AUTHORITY

MANDATORY PRE-BID MEETING FLORIDA KEYS AQUEDUCT AUTHORITY MANDATORY PRE-BID MEETING FLORIDA KEYS AQUEDUCT AUTHORITY NAVY SYSTEM UPGRADES WASTEWATER PUMPING SYSTEMS BOCA CHICA KEY, SIGSBEE PARK, AND FLEMING KEY FKAA PROJECT # 4072-17 Date: April 26 th, 2018 1.

More information

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES

SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL PRECAST CONCRETE MANHOLES Section SECTION 39 - MANHOLES TABLE OF CONTENTS 39-1 GENERAL... 39-1 39-2 PRECAST CONCRETE MANHOLES... 39-1 39-2.01 Precast Concrete Storm Drain Manholes... 39-1 39-3 SADDLE MANHOLES... 39-2 39-3.01 Saddle

More information

SECTION PIPE & PIPE FITTINGS PART 1 GENERAL

SECTION PIPE & PIPE FITTINGS PART 1 GENERAL SECTION 02610 PIPE & PIPE FITTINGS PART 1 GENERAL 1.01 DESCRIPTION A. This Section includes the material and bedding requirements for all pipe and pipe fittings for underground pressure and non-pressure

More information

DEPARTMENT OF TRANSPORTATION STATE OF GEORGIA SPECIAL PROVISION. Section 550 Storm Drain Pipe, Pipe-Arch Culverts, and Side Drain Pipe

DEPARTMENT OF TRANSPORTATION STATE OF GEORGIA SPECIAL PROVISION. Section 550 Storm Drain Pipe, Pipe-Arch Culverts, and Side Drain Pipe Revised: October 25, 2007 Revised: June 11, 2010 DEPARTMENT OF TRANSPORTATION STATE OF GEORGIA SPECIAL PROVISION Section 550 Storm Drain Pipe, Pipe-Arch Culverts, and Side Drain Pipe Delete Section 550

More information

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT Effective September 6, 2018, Addendum No. 3 (THREE), {Pages 1-7 and the applicable attachment(s)}, is associated

More information

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE

DESIGN STANDARDS WASHINGTON UNIVERSITY SCHOOL OF MEDICINE SECTION 01 43 29 (00041) SPECIAL INSPECTIONS PART 1 GUIDELINES As defined by the IBC 2003, Section 1704, Special Inspections of materials, installation, fabrication, erection of components and connections

More information

SECTION 2831 ITEM F-162 CHAIN-LINK FENCES

SECTION 2831 ITEM F-162 CHAIN-LINK FENCES SECTION 2831 ITEM F-162 CHAIN-LINK FENCES PART 1 - GENERAL 1.1 DESCRIPTION. This item shall consist of furnishing and erecting a chain-link fence in accordance with these specifications and the details

More information

APPENDIX A MEASUREMENT AND PAYMENT

APPENDIX A MEASUREMENT AND PAYMENT P-150 DEMOLITION 4.01 Removal of pavement shall be measured per square yard based on the area shown on the plans. Any pavement removed outside the designed limits of removal because the pavement was damaged

More information

APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details)

APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details) APPLICATION FOR A BUILDING PERMIT (Retaining Wall/Garden Wall Construction Details) City of San Jacinto 595 S. San Jacinto Ave San Jacinto CA 92583 951.487.7330 fax 951.654.9896 Must print legibly, submit

More information

CITY OF ALBANY Public Works Department ADDENDUM #1 ST , MAIN STREET REHABILITATION

CITY OF ALBANY Public Works Department ADDENDUM #1 ST , MAIN STREET REHABILITATION CITY OF ALBANY Public Works Department ADDENDUM #1 ST-13-04-2014, MAIN STREET REHABILITATION In order to clarify the intent of the Specifications and Drawings, the following provisions are provided and

More information

If a new residence s electrical service is not located within 200 feet of existing

If a new residence s electrical service is not located within 200 feet of existing Primary Line Extensions CHAPTER 4 If a new residence s electrical service is not located within 200 feet of existing primary electrical facilities, a primary line extension is required to place a close

More information

VILLAGE OF LOMBARD CONTRACT DOCUMENT NUMBER SS BID PROPOSAL

VILLAGE OF LOMBARD CONTRACT DOCUMENT NUMBER SS BID PROPOSAL Page 312 VILLAGE OF LOMBARD CONTRACT DOCUMENT NUMBER SS-12-01 BID PROPOSAL I/We hereby agree to furnish to the Village of Lombard all necessary materials, equipment, and labor, to complete the IL ROUTE

More information

ADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs

ADDENDUM NUMBER 3 AUGUST 18, Jackson County Utility Authority Project No Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs ADDENDUM NUMBER 3 AUGUST 18, 2016 Jackson County Utility Authority Project No. 20150619124 Pascagoula/Moss Point WWTP Escatawpa WWTP Repairs FROM: BURK-KLEINPETER, INC. ENGINEERS, ARCHITECTS, PLANNERS,

More information

Fullerton Reservoirs

Fullerton Reservoirs Fullerton Reservoirs 63 Million Gallons of New Finished Water Storage for the Baltimore Distribution System Gannett Fleming, Inc. Nicholas Lewis, PE Dennis Funk, PE Baltimore County Department of Public

More information

SECTION TAPPING SLEEVES AND VALVES

SECTION TAPPING SLEEVES AND VALVES SECTION 33 12 16.17 TAPPING SLEEVES AND VALVES PART 1: GENERAL 1.01 SCOPE Furnish, install and test all tapping sleeves, tapping valves, and tapping saddles as shown on the Drawings. 1.02 RELATED WORK

More information

SECTION 8 SEPARATION OF LINES

SECTION 8 SEPARATION OF LINES SECTION 8 SEPARATION OF LINES 8.01 INDEX 8.01 INDEX 8.02 PURPOSE 8.03 DEFINITIONS 8.04 SEWER SEPARATION 8.05 NON-POTABLE SEPARATION 8.06 REFERENCES 8.02 PURPOSE This section states the requirements and

More information

Response: The due date for receipt of proposals has been extended. Please see Amendment

Response: The due date for receipt of proposals has been extended. Please see Amendment 1) Question: Bid Date Due to the complexity, size, and prebid legwork required on a project of this scope, we request that the bid date be extended 45-60days. We appreciate your consideration of this request.

More information

SECTION STRUCTURAL METAL FRAMING

SECTION STRUCTURAL METAL FRAMING SECTION 05100 STRUCTURAL METAL FRAMING PART 1 GENERAL 1.01 SUMMARY A. Section Includes: Structural steel framing including lintels, shelf angles, bearing plates, anchor bolts and other items as shown on

More information

FS-DUO. Wastewater Flow Distributor Technical Data. Submittal Special Precautions Specifications Installation. (62.2 cm) (62.2 cm)

FS-DUO. Wastewater Flow Distributor Technical Data. Submittal Special Precautions Specifications Installation. (62.2 cm) (62.2 cm) Wastewater Flow Distributor Technical Data Submittal Special Precautions Specifications Installation 24½" (62.2 cm) 12½" (31.8 cm) 24½" (62.2 cm) (30.5 cm) SUBMITTAL STANDARD: 4" plain end inlet/outlet

More information

COUNTY OF SAN JOAQUIN

COUNTY OF SAN JOAQUIN August 1, 2012 COUNTY OF SAN JOAQUIN General Services Department 44 North San Joaquin Street, Suite 590 Stockton, California 95202-2778 (209) 468-3357, Fax (209) 468-2186 GABRIEL E. KARAM Director Capital

More information

Stone and Masonry Veneer

Stone and Masonry Veneer Stone and Masonry Veneer R703.7 Stone and masonry veneer, general. Stone and masonry veneer shall be installed in accordance with this chapter, Table R703.4 and Figure R703.7. These veneers installed over

More information

SPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings

SPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings 1993 Specifications CSJ 0144-01-060 SPECIAL SPECIFICATION 5925 Polyvinyl Cloride (PVC) Sewer Pipe and Fittings 1. General. (1) Scope. This Section includes the furnishing, installation, and subsequent

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular

More information