Subsurface Study. Faulk Assisted Living Facility Boca Raton, Florida. George E. Mueller West Palm Beach, Florida

Size: px
Start display at page:

Download "Subsurface Study. Faulk Assisted Living Facility Boca Raton, Florida. George E. Mueller West Palm Beach, Florida"

Transcription

1 Subsurface Study Faulk Assisted Living Facility Boca Raton, Florida April 24, 2014 Terracon Project No.: HD Prepared for: George E. Mueller West Palm Beach, Florida Prepared by: Dunkelberger Engineering & Testing, a Terracon Company West Palm Beach, Florida

2 Mainsail Healthcare Development 901 North Flagler Drive, Suite 3 West Palm Beach, Florida Attn: Mr. George E. Mueller Subject: Subsurface Study Faulk Assisted Living Facilty 2245 Boca Rio Road Boca Raton, Florida Terracon Project No.: HD Gentlemen: We have completed the subsurface study for the referenced project. It was performed in general accordance with the scope of work described in our proposal dated February 6, This report presents the findings of the subsurface exploration and provides geotechnical engineering recommendations regarding foundation design and related construction. We appreciate the opportunity to be of service during this phase of the project. If you have any questions concerning the report, please feel free to contact us. Sincerely, Dunkelberger Engineering & Testing, a Terracon Company Kevin E. Aubry, P.E. Thomas J. Tepper, P.E. Geotechnical Services Manager Senior Engineer FL Registration No FL License No Terracon Consultants, Inc NW 33 rd Avenue, Suite 204 Fort Lauderdale, Florida P [954] F [954]

3 TABLE OF CONTENTS Page No. EXECUTIVE SUMMARY... I 1.0 INTRODUCTION PROJECT INFORMATION REVIEW OF EXISTING INFORMATION Topographic and Vegetation Information Soil Survey Information SUBSURFACE CONDITIONS Stratigraphy Groundwater BOREHOLE PERMEABILITY TEST ENGINEERING EVALUATION AND RECOMMENDATION Site Geotechnical Suitability Clearing, Grubbing and Stripping Soil Densification Engineered Fill Foundation Design and Construction Ground Floor Slab Pavement Considerations LIMITATIONS OF STUDY...7 APPENDICES APPENDIX A Sheet 1 Boring Location Plan Sheets 2A through 2C Subsurface Profiles Sheets 3A and 3B Field Permeability Test Results

4 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD EXECUTIVE SUMMARY Subsurface conditions at the site were explored with eight 30-foot deep Standard Penetration Test borings and five 6-foot deep auger profile borings. The borings disclosed the property to be mantled by two to five feet of loose to very loose clean, clayey and silty fine sands (i.e. topsoil). At most boring locations the surficial soil is followed by weakly to moderately well cemented silty to sandy limestone that continues to depths of 6 to 8.5 feet below grade. Over the remaining depths the borings penetrated loose to medium dense sands. Groundwater levels were measured in the borings. The depth to the free water surface during the period of field exploration (March 25 to March 31, 2014) varied from 2.5 to 3.7 and averaged 3.2 feet. The site is considered suitable for the planned construction when viewed from a geotechnical engineering perspective. Following normal site preparation that includes clearing, grubbing, stripping and soil densification from the stripped grade, the building may be supported on shallow spread footings designed for an allowable bearing capacity of 2,500 pounds per square foot. Responsive Resourceful Reliable i

5 SUBSURFACE STUDY FAULK ASSITED LIVING FACILITY BOCA RATON, FLORIDA Dunkelberger Project No.: HD April 24, INTRODUCTION This firm has completed the subsurface study in connection with the Faulk Assisted Living Facility to be constructed on the west side of Boca Rio Road slightly north of S.W. 8 th street in Boca Raton, Florida. This site has the physical address of 2245 Boca Rio Road. The study involved the drilling and sampling of Standard Penetration Test and auger profile borings to evaluate the nature, sequencing and condition of the profile components and performance of borehole permeability tests to assess the hydraulic conductivity characteristics of the near surface profile components. The purpose of the work was to provide recommendations and professional advice regarding site preparation, foundation design and related aspects of the project in consideration of the subsurface conditions that exist at the property. 2.0 PROJECT INFORMATION The project will involve the design and construction of a three story assisted living facility which will have an x-shaped configuration in plan and a footprint area of 57,147 square feet, which includes a 3,308 square foot entrance canopy. For foundation evaluation purposes, we have assumed that the structure will be built of reinforced concrete and unit masonry and that its elevated slabs will be supported on a combination of load bearing wells and columns which transmit maximum loads of 12 kips per foot and 300 kips, respectively, to their foundations. We have also assumed that the building area will receive no more than two feet of fill. Areas around the building will be paved to provide access to the structure and parking stalls for visitors and employees. We expect that the paving will be of the flexible type (i.e. asphalt concrete over aggregate base course. 1

6 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD REVIEW OF EXISTING INFORMATION 3.1 Topographic and Vegetation Information Topographic information for the site gathered by Michael B. Schorah & Associates, Inc. shows that ground surface elevations on the property vary from about 14.5 to 16.5 feet with respect to the National Geodetic Vertical Datum of 1929 (NGVD). Most ground surface elevations are somewhat more than 15 feet NGVD. Vegetation on the property consists of low growing grass and weeds, scattered pine trees, seagrape plants and moderately dense clusters of cypress trees. The cypress trees exist in the southwest corner of the property. 3.2 Soil Survey Information Reference to the Soil Survey of Palm Beach County Area, Florida prepared by the U.S. Department of Agriculture Soil Conservation Service of 1978 shows most of the site to be mantled by the Boca fine sand soil association. Riviera sand depressional soils exist in the area covered by the cypress trees. Both taxonomic units are described as loamy (i.e. silty to clayey) sands that are same 20 to 40 inches thick. In the case of the Boca fine sand, limestone underlies the overburden material at depths of 20 to 40 inches below grade. 4.0 SUBSURFACE CONDITIONS 4.1 Stratigraphy Subsurface conditions at the site were explored with eight 30 foot deep Standard Penetration Test (SPT) borings and five 6 foot deep auger profile borings arranged as shown on Sheet 1. The SPT borings were accomplished with a Central Mine Equipment Company Model 45B drill rig using mud rotary methods. The auger borings were also performed with this same drilling rig but by turning a six-inch diameter helical auger. Logs of the borings are furnished on Sheets 2A through 2C. 2

7 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD With minor variations, the borings disclosed the stratigraphy described hereafter. Item Topsoil Upper Sands Limestone Lower Sands Description Topsoil consisting of organic sands with roots covers a majority of the site in thicknesses that vary from 0.4 to 1 foot Very loose to medium dense clean to clayey fine sands exist next in the profile and persist to depths of 1.8 to 5.0 feet below. A formation of weakly to moderately well cemented limestone underlies the upper sands at most boring locations and continues to depths of 6 to 8.5 feet beneath the ground surface. The limestone has suffered erosion in past geologic times. This condition is typified by the variable depth to the carbonate rock formation and the absence of limestone at the location of Boring TB-3 Over the remaining depths of exploration the borings penetrated slightly silty to clean fine sands. These soils typically range from loose to medium dense in terms of relative density. 4.2 Groundwater Groundwater levels were measured in the borings when the free water surface was initially intercepted. The depth to the water table varied from 2.5 to 3.7 feet beneath the surface grades and averaged 3.2 feet during the period of the field exploration (March 28 through March 31, 2014). Given that the borings were drilled near the end of the dry hydroperiod, we estimate that the groundwater level could rise as much as two feet during the wet season of the hydrologic year. 5.0 BOREHOLE PERMEABILITY TEST Two borehole permeability test (denoted BHP-1 and BHP-2) were performed at the site to assess the hydraulic conductivity of the upper six feet of the profile components. Their locations are depicted on Sheet 1. 3

8 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD The tests were conducted in six inch diameter by six foot deep boreholes whose sidewalls were stabilized with a two inch diameter No. 20 slot well casing and 6/20 silica sand. Usual open hole, constant head methodology was used for each test. Results of the tests are furnished on Sheets 3A and 3B along with pertinent stratigraphic, geometric and hydraulic conditions information. Reference to the test results shows that the average hydraulic conductivity of the materials was 1.35 x 10-5 cubic foot per second per square foot- foot head (cfs/sf-ft) for BHP-1 and 9.77 x 10-3 (cfs/sf-ft) for BHP-2. Because of these low values, the civil engineer responsible for stormwater drainage may wish to consider over excavation of the limestone along the exfiltration trenches alignments and backfilling the overexcavated part of the trenches with open graded crushed rock enveloped with a geotextile fabric designed for drainage. This measure is intended to provide connectivity with the lower sands to improve the hydraulic efficiency of the trenches. 6.0 ENGINEERING EVALUATION AND RECOMMENDATIONS 6.1 Site Geotechnical Suitability Results of this study confirm that the site is suitable for the proposed construction when viewed from a geotechnical engineering perspective. Following normal site preparation that includes intensive densification of the surficial soils, the building may be supported on shallow spread footings and employ a slab-on-grade floor system. 6.2 Clearing, Grubbing and Stripping The proposed building and pavement areas should be cleared of all vegetation at the onset of construction. Clearing and grubbing should include the complete removal and disposal of asphalt concrete, timber, stumps, grass, roots, rubbish, debris and all other obstructions resting on or protruding through the surface of the existing ground. All roots greater than one inch in diameter, or high concentrations of smaller diameter roots exposed by clearing and grubbing, should be removed to a depth of not less than 12 inches. We anticipate the average depth of stripping will range from nil to 12 inches in most areas. Deeper stripping may be needed in the area where the cypress trees now exist. 4

9 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD Soil Densification The sandy soils which cover the site should be thoroughly compacted to create a uniform density condition. Improvement of the soils in this fashion should be carried out throughout the structural footprint including a five foot wide perimeter which extends beyond the maximum outside lines of the superstructure. It should be accomplished from a stripped grade that is at least 24 inches above the ambient water table using a heavy vibratory roller which imparts a dynamic drum force of not less than 44,000 pounds. Each section of subgrade should be subjected to multiple, overlapping (minimum of 20 percent overlap) coverages of the compactor as it operates at its highest vibrational frequency and a travel speed of no more than 1.5 miles per hour (normal walking speed). Rolling should be continued until no further settlement can be visually discerned at the ground surface. In no case, however, should any section of subgrade receive less than ten roller coverages, with five made in the longitudinal direction and five in the transverse direction. The densification activities should be carefully monitored to identify signs of subgrade instability such as pumping, weaving and / or shoving. This type of subgrade response will indicate that weak and potentially compressible materials exist within the influence depth of the roller. Correction of the instability may require removal of the weak soils and replacement of them with well compacted granular fill. Density control should be exercised in the upper 12 inches of the subgrade soils. Soils in this interval should be compacted to not less than 95 percent of the ASTM D 1557 maximum dry density. 6.4 Engineered Fill Fill required for the building pad and site grading should consist of clean, granular materials that are free of debris, cinders, combustibles, roots, sod, wood, cellulose and organic material. The fill should have no particle size larger than three inches and not more than 10 percent passing the U.S. Standard Number 200 Sieve (dry weight basis). It should also have an organic content less than three percent. The fill should be placed at a water content within three percent of optimum and thoroughly and uniformly compacted to not less than 95 percent of the ASTM D 1557 maximum dry density. Subgrades receiving fill should be densified to an equivalent relative compaction. 6.5 Foundation Design and Construction Following implementation of the ground modification procedures described earlier in the report, the structure may be supported on shallow foundations that are based in the improved profile components and designed for a net allowable bearing pressure of 2,500 pounds per foot. To 5

10 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD provide an adequate factor of safety against a shearing failure in the subsoils: (1) all foundations should be based not less than 24 inches below the lowest adjacent grade, (2) continuous footings should be at least 24 inches wide, and (3) isolated footings should have a width not less than 30 inches. The recommended bearing pressure refers to dead plus normal live loads and reflects a net increase in pressure over and above that due to the overburden soils. It may be increased by 25 percent for total loads, including wind forces. Foundations subjected to lateral forces will resist those forces through earth pressure mobilized on the vertical faces of the footings located at righ angles to the direction of load application and shearing forces acting at the footing-subgrade interface. Earth pressure resistance may be determined using an equivalent fluid pressure of 180 pounds per square foot depth (psf/ft) for well compacted moist granular soils above the water table. Base shearing resistance may be computed using a coefficient of friction of The design of the footings against sliding should include a factor of safety of not less than 1.5. Individual footing areas should be excavated, formed and maintained in a dry condition until placement of the substructure concrete. The excavation bottoms should be tamped with a hand-held or walk-behind compactor prior to placement of reinforcing steel. The compactive effort should achieve a relative compaction of 95 percent (ASTM D 1557) for a minimum depth of 12 inches below the excavation bottom. Foundations designed and constructed in the recommended manner are estimated to sustain a maximum total settlement of about one inch provided the wall and column loads for the structure do not exceed those presented earlier in the report. Differential settlements that occur between adjacent foundations are not expected to exceed one-half inch. Angular distortions along wall footings due to differential settlement should not be more than 1 in 650. Because the subsurface materials of the iste are granular in texture, foundation settlements should occur as rapidly as the loads are applied and be nearly complete by the end of the construction period. 6.6 Ground Floor Slab Slab-on-grade construction may be used for the ground floor of the structure. The slab concrete should be cast upon granular engineered fill compacted to 95 percent of the ASTM D 1557 maximum dry density. 6

11 Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida April 24, 2014 Terracon Project No. HD A vapor barrier should be installed beneath the bottom of the floor slab to prevent moisture intrusion from the subgrade. Ordinarily a 10-mil thick film of polyethylene is suitable for this purpose. However, floor coverings which are particularly sensitive to moisture flux may require a thicker membrane and/or one of alternative composition. 6.7 Pavement Considerations We believe that conventional flexible (asphalt concrete surfaced) pavement sections can be used for the drive aisles and parking areas of the facility. The sections provided below are typically used in the geographic area for heavy and light duty pavements. Heavy Duty Pavement Component Wearing Course Base Course Subbase Component Wearing Couse Base Course Subbase Thickness and Composition 1.5 inches of structural asphaltic concrete 8 inches of crushed aggregate (LBR = 100 minimum) 12 inches of stabilized subgrade material (LBR = 40 minimum) Light Duty Pavement Thickness and Composition 1 inch of structural asphaltic concrete 6 inches of crushed aggregate (LBR = 100 minimum) 12 inches of stabilized subgrade material (LBR = 40 minimum) 7.0 LIMITATIONS OF STUDY Dunkelberger warrants that the conclusions, recommendations and professional advice provided in this report have been promulgated based on recognized practice in soil mechanics and foundation engineering within this geographic area. No other warranties are expressed or implied. 7

12 APPENDIX A SHEET 1 BORING LOCATION PLAN SHEETS 2A THROUGH 2C SUBSURFACE PROFILES SHEET 3A AND 3B FIELD PERMEABILITY TEST RESULTS

13 NORTH AB-1 AB-2 BHP-1 TB-1 TB-2 AB-3 TB-3 TB-4 AB-4 TB-5 TB-6 AB-5 TB-7 TB-8 BHP-2 SOURCE: URBAN DESIGN KILDAY STUDIOS 0' 50' 100' 200' LEGEND TB-1 STANDARD PENETRATION TEST BORING LOCATION AND NUMBER BHP-1 BOREHOLE PERMEABILITY TEST LOCATION AND NUMBER AB-1 AUGER BORING LOCATION AND NUMBER Locations are approximate. JJ BORING LOCATION PLAN DM FAULK ASSISTED LIVING FACILITY BOCA RIO ROAD KA BOCA RATON, FLORIDA SEE SCALE BAR HD

14 BORING NO. TB-1 TB-2 TB-3 TB-4 LEGEND Dark brown silty organic SAND with roots, grass, some lenses gravel (SM) Gray to dark brown fine to medium SAND, trace silt to slightly silty, trace to some roots and gravel, some lenses with finely divided organic matter (SP, SP-SM) Light gray to light brown fine to medium SAND, some lenses with small roots less than 1/4-inch in diameter (SP) Light brown clayey fine SAND, some fibrous roots less than 1/4-inch in diameter, some silty lenses (SP-SC, SC, SM) Light gray to light brown silty, sandy LIMESTONE Light brown fine to medium SAND with shell fragments, trace silt to slightly silty, some cemented fragments (SP, SP-SM) Dark brown slightly silty fine SAND, some organic staining (SP-SM) DEPTH IN FEET DEPTH IN FEET SP N Light brown to brown fine to medium SAND (SP) Unified Soil Classification System Group Symbol (ASTM D 2487) Indicates the number of blows of a 140 pound hammer, freely falling a distance of 30 inches, required to drive a 2-inch diameter sampler 12 inches (ASTM D 1586) TB-1 Standard Penetration Test (SPT) boring and number Depth of groundwater (feet) & date measured (1) (2) (3) NOTES Borings were drilled on March 28 and 31, 2014 using a Central Mine Equipment Model 45B (CME 45B) drilling rig. Strata boundaries are approximate and represent soil strata at each test hole location only. Soil transitions may be more gradual than implied. Groundwater depths shown on the subsurface profiles represent groundwater surfaces on the dates shown. Groundwater level fluctuations should be anticipated throughout the year. JJ DM KA 1" = 5' SUBSURFACE PROFILES FAULK ASSISTED LIVING FACILITY BOCA RIO ROAD BOCA RATON, FLORIDA HD A

15 BORING NO. TB-5 TB-6 TB-7 TB-8 LEGEND Dark brown silty organic SAND with roots, grass, some lenses gravel (SM) Gray to dark brown fine to medium SAND, trace silt to slightly silty, trace to some roots and gravel, some lenses with finely divided organic matter (SP, SP-SM) Light gray to light brown fine to medium SAND, some lenses with small roots less than 1/4-inch in diameter (SP) Light brown clayey fine SAND, some fibrous roots less than 1/4-inch in diameter, some silty lenses (SP-SC, SC, SM) Light gray to light brown silty, sandy LIMESTONE Light brown fine to medium SAND with shell fragments, trace silt to slightly silty, some cemented fragments (SP, SP-SM) Dark brown slightly silty fine SAND, some organic staining (SP-SM) DEPTH IN FEET DEPTH IN FEET SP N Light brown to brown fine to medium SAND (SP) Unified Soil Classification System Group Symbol (ASTM D 2487) Indicates the number of blows of a 140 pound hammer, freely falling a distance of 30 inches, required to drive a 2-inch diameter sampler 12 inches (ASTM D 1586) TB-5 Standard Penetration Test (SPT) boring and number Depth of groundwater (feet) & date measured (1) (2) (3) NOTES Borings were drilled on March 28 and 31, 2014 using a Central Mine Equipment Model 45B (CME 45B) drilling rig. Strata boundaries are approximate and represent soil strata at each test hole location only. Soil transitions may be more gradual than implied. Groundwater depths shown on the subsurface profiles represent groundwater surfaces on the dates shown. Groundwater level fluctuations should be anticipated throughout the year. JJ DM KA 1" = 5' SUBSURFACE PROFILES FAULK ASSISTED LIVING FACILITY BOCA RIO ROAD BOCA RATON, FLORIDA HD B

16 BORING NO. AB-1 AB-2 AB-3 AB-4 AB-5 DEPTH IN FEET DEPTH IN FEET LEGEND Dark brown silty organic SAND with roots, grass, some lenses gravel (SM) Gray to dark brown fine to medium SAND, trace silt to slightly silty, trace to some roots and gravel, some lenses with finely divided organic matter (SP, SP-SM) Light gray to light brown fine to medium SAND, some lenses with small roots less than 1/4-inch in diameter (SP) Light brown clayey fine SAND, some fibrous roots less than 1/4-inch in diameter, some silty lenses (SP-SC, SC, SM) Light gray to light brown silty, sandy LIMESTONE Light brown fine to medium SAND with shell fragments, trace silt to slightly silty, some cemented fragments (SP, SP-SM) Dark brown slightly silty fine SAND, some organic staining (SP-SM) Light brown to brown fine to medium SAND (SP) SP AB-1 Unified Soil Classification System Group Symbol (ASTM D 2487) Auger boring and number Depth of groundwater (feet) & date measured (1) (2) (3) NOTES Borings were drilled on March 28 and 31, 2014 using a Central Mine Equipment Model 45B (CME 45B) drilling rig. Strata boundaries are approximate and represent soil strata at each test hole location only. Soil transitions may be more gradual than implied. Groundwater depths shown on the subsurface profiles represent groundwater surfaces on the dates shown. Groundwater level fluctuations should be anticipated throughout the year. JJ DM KA 1" = 5' SUBSURFACE PROFILES FAULK ASSISTED LIVING FACILITY BOCA RIO ROAD BOCA RATON, FLORIDA HD C

17 Field Permeability Test Project Name: Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida Project No. HD TEST NUMBER: BHP-1 TEST LOCATION: See Boring Location Plan SUBSURFACE PROFILE Depth (feet) Soil Description Gray brown fine SAND, trace organics Gray brown fine SAND with cobble to boulder size limestone fragments Brown fine to medium SAND Light brown silty LIMESTONE Water Table Depth: 3.2 feet below grade on 03/27/14 Constant Head Maintained at: At ground surface PERMEABILITY RESULTS Uncased (U) or Cased (C): C 6-inch Casing Depth (ft): 6.0 Casing Stick-up (ft): 0.0 Perforated length (ft): 6.0 Constant Head Falling Head Start Stop Volume Used (gallons) Start Stop Drop (Ft) 0 sec sec *K, Hydraulic Conductivity (CFS/Ft 2 - Ft Head) = 1.35 x 10-5 *(Reference: Equations in SFWMD Permit Information Manual, Volume IV) Sheet 3A

18 Field Permeability Test Project Name: Faulk Assisted Living Facility 2245 Boca Rio Road Boca Raton, Florida Project No. HD TEST NUMBER: BHP-2 TEST LOCATION: See Boring Location Plan SUBSURFACE PROFILE Depth (feet) Soil Description Dark brown fine SAND with small roots and organics Light brown aggregate base course Gray fine to medium SAND, trace small roots Brown and light brown fine to medium SAND Light brown silty fine SAND Gray brown to light brown clayey LIMESTONE Water Table Depth: 4.6 feet beneath the ground surface on 3/27/14 Constant Head Maintained at: At ground surface PERMEABILITY RESULTS Uncased (U) or Cased (C): C 6-inch Casing Depth (ft): 6.0 Casing Stick-up (ft): 0.0 Perforated length (ft): 6.0 Constant Head Falling Head Start Stop Volume Used (gallons) Start Stop Drop (Ft) 0 sec sec *K, Hydraulic Conductivity (CFS/Ft 2 - Ft Head) = 9.77 x 10-5 *(Reference: Equations in SFWMD Permit Information Manual, Volume IV) Sheet 3B

Geotechnical Engineering Report

Geotechnical Engineering Report BIG CYPRESS SEMINOLE INDIAN RESERVATION WATER TREATMENT FACILITY October 29, 2015 Terracon Project No. HD155065 Prepared for: REISS ENGINEERING, INC. 1016 Spring Villas Pt. Winter Springs, FL 32708 Prepared

More information

mtec REPORT OF GEOTECHNICAL EXPLORATION FTFA Construct Bin Wall at HERD Eglin AFB, Florida

mtec REPORT OF GEOTECHNICAL EXPLORATION FTFA Construct Bin Wall at HERD Eglin AFB, Florida mtec REPORT OF GEOTECHNICAL EXPLORATION FTFA 14-3001 - Construct Bin Wall at HERD Eglin AFB, Florida MTEC Project Number 2014-101 November 10, 2014 Revised: January 5, 2015 Prepared For: Peterson Engineering,

More information

Geotechnical Investigation Long Timber Brewing Building Highway 99 and Kelly Street Monroe, Oregon TABLE OF CONTENTS

Geotechnical Investigation Long Timber Brewing Building Highway 99 and Kelly Street Monroe, Oregon TABLE OF CONTENTS Highway 99 and Kelly Street TABLE OF CONTENTS PROJECT INFORMATION... 1 FIELD EXPLORATION... 1 SITE CONDITIONS... 2 Surface Conditions:... 2 Subsurface Conditions:... 2 FILL.... 2 Topsoil.... 2 Clay Alluvium....

More information

REPORT OF GEOTECHNICAL EXPLORATION WEST MARJORY AVENUE TAMPA, FLORIDA

REPORT OF GEOTECHNICAL EXPLORATION WEST MARJORY AVENUE TAMPA, FLORIDA REPORT OF GEOTECHNICAL EXPLORATION WEST MARJORY AVENUE TAMPA, FLORIDA AREHNA PROJECT NO. B-15-008 March 11, 2015 Prepared For: City of Tampa Stormwater Division 306 W. Jackson Street, 6N Tampa, Florida

More information

May 2, Mr. Tim Kurmaskie, AIA ARCHITECT KURMASKIE ASSOCIATES, INC Washington Street Raleigh, NC

May 2, Mr. Tim Kurmaskie, AIA ARCHITECT KURMASKIE ASSOCIATES, INC Washington Street Raleigh, NC Mr. Tim Kurmaskie, AIA ARCHITECT KURMASKIE ASSOCIATES, INC. 1030 Washington Street Raleigh, NC 27605-1258 May 2, 2017 Re: Report of Subsurface Investigation Westfield Rehabilitation & Health Care Additions

More information

Appendix A - Vicinity Map Vicinity Map: Palm Beach Gardens City Hall Additions, 000 N Military Trail, Palm Beach Gardens, FL Proposed Location of Police Dept. Attached Addition Proposed Location of New

More information

ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 6 SANFORD, FLORIDA

ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 6 SANFORD, FLORIDA PRELIMINARY GEOTECHNICAL STUDY ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 6 SANFORD, FLORIDA November 9, 2015 Prepared For: Ms. Diane H. Crews, A.A.E. Sanford Airport Authority 1200 Red Cleveland

More information

ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 1 SANFORD, FLORIDA

ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 1 SANFORD, FLORIDA PRELIMINARY GEOTECHNICAL STUDY ORLANDO SANFORD INTERNATIONAL AIRPORT OUTPARCEL 1 SANFORD, FLORIDA November 9, 2015 Prepared For: Ms. Diane H. Crews, A.A.E. Sanford Airport Authority 1200 Red Cleveland

More information

CONDUCTED FOR: PREPARED FOR: 18 October 2010 YPC Project No. 10GY133

CONDUCTED FOR: PREPARED FOR: 18 October 2010 YPC Project No. 10GY133 GEOTECHNICAL EXPLORATION AND ENGINEERING SERVICES REPORT CONDUCTED FOR: Immokalee Stormwater Master Plan Implementation Immokalee, Collier County, Florida PREPARED FOR: Mr. Marc Stonehouse, P. E. Project

More information

This report presents the findings of the subsurface exploration concerning the design of the taxiway rehabilitation. Description

This report presents the findings of the subsurface exploration concerning the design of the taxiway rehabilitation. Description September 22, 2016 American Infrastructure Development, Inc. 3810 Northdale Boulevard, Suite 170 Tampa, Florida 33624 Attn: Mr. Mohsen Mohammadi, Ph.D., P.E. Senior Consultant Mob: (813) 244-6609 E-mail:

More information

Addendum 1 - Appendix A - 1 of 22

Addendum 1 - Appendix A - 1 of 22 Addendum 1 - Appendix A - 1 of 22 Erdman Anthony of Florida, Inc. August 1, 2007 1402 Royal Palm Beach Boulevard Building 500 Royal Palm Beach, Florida 33411 Attention: Subject: Ms. Dana I. Gillette, P.E.,

More information

Subsurface Investigation Report. Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois

Subsurface Investigation Report. Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois AGI Project No. -11 Subsurface Investigation Report For the Proposed New 1-Story Building 6447 Grand Avenue Gurnee, Illinois Prepared for Mr. Steve Panko Key Development Partners, LLC North State Street,

More information

August 15, 2006 (Revised) July 3, 2006 Project No A

August 15, 2006 (Revised) July 3, 2006 Project No A August 15, 2006 (Revised) July 3, 2006 Project No. 01-05-0854-101A Mr. David Reed, P.E. Protean Design Group 100 East Pine Street, Suite 306 Orlando, Florida 32801 Preliminary Soil Survey Report Polk Parkway

More information

REPORT OF GEOTECHNICAL EXPLORATION GLYNN COUNTY DETENTION CENTER GLYNN COUNTY, GEORGIA E&A PROJECT NO

REPORT OF GEOTECHNICAL EXPLORATION GLYNN COUNTY DETENTION CENTER GLYNN COUNTY, GEORGIA E&A PROJECT NO REPORT OF GEOTECHNICAL EXPLORATION GLYNN COUNTY DETENTION CENTER GLYNN COUNTY, GEORGIA E&A PROJECT NO. - Prepared for: IPG Architects, Inc. Northwood Park Drive Valdosta, Georgia Prepared by: Ellis & Associates,

More information

Please include this addendum in your Bid proposal for the above referenced project. Questions are in black ink, and the answers are in red ink.

Please include this addendum in your Bid proposal for the above referenced project. Questions are in black ink, and the answers are in red ink. JAHarchitects, LLC PROJECT NO. 393 RIVERCREST CDD 11560 RAMBLE CREEK DRIVE, RIVERVIEW FL ADDENDUM TO BID PROJECT: RIVERCREST CDD MULTI PURPOSE FIELD MAINTENANCE BUILDING & DOG PARK POOL & CABANNA JAH PROJECT

More information

REPORT OF GEOTECHNICAL EXPLORATION BYFORGE ENGINEERING FOR REFERENCE ONLY

REPORT OF GEOTECHNICAL EXPLORATION BYFORGE ENGINEERING FOR REFERENCE ONLY REPORT OF GEOTECHNICAL EXPLORATION BYFORGE ENGINEERING FOR REFERENCE ONLY HERITAGE BAY MASTER PUMP STATION ISSUED FOR BID REPORT OF GEOTECHNICAL EXPLORATION PROPOSED INLINE WASTEWATER BOOSTER STATION Collier

More information

Civil Geotechnical Surveying

Civil Geotechnical Surveying Civil Geotechnical Surveying Mr. David Burnett Cabarrus County Schools 4425 Old Airport Road Charlotte, North Carolina 28025 May 16, 2017 Reference: Geotechnical Engineering Evaluation Future PLC Site

More information

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois

Applied GeoScience, Inc Hammond Dr., Suite 6 Schaumburg, Illinois AGI Project No. 13-276 Subsurface Investigation Report For the Proposed New Retail Center 9601 South Pulaski Road Evergreen Park, Illinois Prepared for Mr. Feras Sweis FHS Design + Build LLC 2010 West

More information

PROJECT CULVERT REPLACEMENTS GEOTECHNICAL ENGINEERING REPORT CONTRACT No WO01 PALM BEACH COUNTY, FL FEBRUARY 2013

PROJECT CULVERT REPLACEMENTS GEOTECHNICAL ENGINEERING REPORT CONTRACT No WO01 PALM BEACH COUNTY, FL FEBRUARY 2013 SOUTH FLORIDA WATER MANAGEMENT DISTRICT PROJECT CULVERT REPLACEMENTS GEOTECHNICAL ENGINEERING REPORT CONTRACT No. 4600002703-WO01 PALM BEACH COUNTY, FL FEBRUARY 2013 Prepared for: South Florida Water Management

More information

DEPARTMENT OF TRANSPORTATION DIVISION: MATERIALS REPORT COVER SHEET. Revised Soil Survey Report November 24, 2015 Matthew G. Moore, P.E.

DEPARTMENT OF TRANSPORTATION DIVISION: MATERIALS REPORT COVER SHEET. Revised Soil Survey Report November 24, 2015 Matthew G. Moore, P.E. LD-0 /12/09 DEPARTMENT OF TRANSPORTATION DIVISION: MATERIALS REPORT COVER SHEET Revised Soil Survey Report November 2, 201 Matthew G. Moore, P.E. VDOT (Division) or Company Name Insert Location, Virginia

More information

GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO E

GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO E GEOTECHNICAL STUDY PROPOSED CONCRETE ROADWAY TIKI ISLAND COMMUNITY GALVESTON COUNTY, TEXAS PROJECT NO. 15-945E TO VILLAGE OF TIKI ISLAND TIKI ISLAND, TEXAS BY SERVICING TEXAS, LOUISIANA, NEW MEXICO, OKLAHOMA

More information

SECTION TRENCHING

SECTION TRENCHING SECTION 31 23 17 TRENCHING PART 1 GENERAL 1.1 SUMMARY A. Section Includes: 1. Excavating trenches for utilities and utility structures. 2. Bedding. 3. Backfilling and compacting to subgrade elevations.

More information

GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE

GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE Geotechnical Exploration Report Minto Westlake Retail & Sales Center 00 Seminole Pratt Whitney Road, Loxahatchee, Florida September 1, 01 GFA Project

More information

SUMMARY REPORT OF A GEOTECHNICAL SITE EXPLORATION LACROSSE CITRUS REPOSITORY LACROSSE, ALACHUA COUNTY, FLORIDA. GSE PROJECT No.

SUMMARY REPORT OF A GEOTECHNICAL SITE EXPLORATION LACROSSE CITRUS REPOSITORY LACROSSE, ALACHUA COUNTY, FLORIDA. GSE PROJECT No. SUMMARY REPORT OF A GEOTECHNICAL SITE EXPLORATION LACROSSE CITRUS REPOSITORY LACROSSE, ALACHUA COUNTY, FLORIDA GSE PROJECT No. 1128 Prepared For: BURE OF CITRUS BUDWOOD REGISTRATION SEPTEMBER 2011 Certificate

More information

April 7, Webster Street Sub-Surface Stormwater Storage System Bid No Bid Date: 4/13/17 ADDENDUM NO 1

April 7, Webster Street Sub-Surface Stormwater Storage System Bid No Bid Date: 4/13/17 ADDENDUM NO 1 PUBLIC WORKS DEPARTMENT David A. Jones, P.E., Director April 7, 2017 Webster Street Sub-Surface Stormwater Storage System Bid No. 2017-022 Bid Date: 4/13/17 ADDENDUM NO 1 Please make the following changes

More information

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants SUBSURFACE SOIL EXPLORATION ANALYSIS AND RECOMMENDATIONS PROPOSED WEIRS AT STATIONS 130+00 AND 16+00 DRAINAGE IMPROVEMENTS TO THE FOUR CORNERS MSBU HENDRY COUNTY, FLORIDA Ardaman & Associates, Inc. Geotechnical,

More information

MEMORANDUM. TO: STUART OLSON DOMINION CONSTRUCTION LTD. DATE: JANUARY 31, 14 ATTENTION: MR. Dave Bauder, Construction Manager KENNY K. C.KO, P.ENG.

MEMORANDUM. TO: STUART OLSON DOMINION CONSTRUCTION LTD. DATE: JANUARY 31, 14 ATTENTION: MR. Dave Bauder, Construction Manager KENNY K. C.KO, P.ENG. MEMORANDUM Levelton Consultants Ltd. 150-12791 Clarke Place Richmond, BC V6V 2H9 Canada Tel: 604 278-1411 Fax: 604 278-1042 E-Mail: rhillaby@levelton.com Web Site: www.levelton.com TO: STUART OLSON DOMINION

More information

April 21, Odom Investments, Inc. Attn: Mr. Jerry Odom 7100 Westwind Dr., Suite 230 El Paso, TX 79912

April 21, Odom Investments, Inc. Attn: Mr. Jerry Odom 7100 Westwind Dr., Suite 230 El Paso, TX 79912 April 21, 2016 Odom Investments, Inc. Attn: Mr. Jerry Odom 7100 Westwind Dr., Suite 230 El Paso, TX 79912 Re: GEOTECHNICAL ENGINEERING REPORT Proposed San Elizario Retail Center Socorro Road & Chicken

More information

PROPOSED CONDOS 1129 Victoria Drive, Dunedin Parcel: , Pinellas County Geotechnical Services June Report No.

PROPOSED CONDOS 1129 Victoria Drive, Dunedin Parcel: , Pinellas County Geotechnical Services June Report No. Central Florida Testing Laboratories, Inc. Testing, Development and Research 12625-40th Street North Clearwater, Florida 33762 ENGINEERING BUSINESS NO. 1066 GEOLOGY BUSINESS NO. 224 TAMPA BAY AREA (727)

More information

Subsurface Investigation and Geotechnical Engineering Report Proposed Volvo Dealership 1022 Hingham Street Rockland, Massachusetts

Subsurface Investigation and Geotechnical Engineering Report Proposed Volvo Dealership 1022 Hingham Street Rockland, Massachusetts HML ASSOCIATES Geotechnical and Civil Engineers March 31, 17 19 Rockwood Road Hingham, MA 43 (Phone/Fax)781-74-9999 Mr. Joe Rose Prime Motor Group 42 Providence Highway Westwood, MA 9 RE: Subsurface Investigation

More information

GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE

GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE GFA INTERNATIONAL FLORIDA S LEADING ENGINEERING SOURCE Report of Geotechnical Exploration Addie s Corner Entry Bridge and Lake Areas 8799 Immokalee Road Naples, Collier County, Florida October 26, 2016

More information

5.0 SITE CONDITIONS. 5.1 Surface Conditions

5.0 SITE CONDITIONS. 5.1 Surface Conditions 5.0 SITE CONDITIONS 5.1 Surface Conditions The project site is located at approximately along Ashdown Forest Road and Nichols Canyon Road in the Fiddlers Canyon Area of Cedar City, Utah. At the time of

More information

October 11, 2011 Re-Issued November 15, 2011

October 11, 2011 Re-Issued November 15, 2011 Shadow Wood Investors LLC 425 W New England Avenue, Suite 425 Winter Park, FL 32789 October 11, 2011 Re-Issued November 15, 2011 LOCATIONS: Atlanta Daytona Beach Fort Myers Fort Pierce Gainesville Jacksonville

More information

100% Report of Geotechnical Engineering Investigation CENTRAL FLORIDA COMMUTER RAIL TRANSIT SUNRAIL PHASE 2 SOUTH Poinciana Vehicle Storage & Light

100% Report of Geotechnical Engineering Investigation CENTRAL FLORIDA COMMUTER RAIL TRANSIT SUNRAIL PHASE 2 SOUTH Poinciana Vehicle Storage & Light 100% Report of Geotechnical Engineering Investigation CENTRAL FLORIDA COMMUTER RAIL TRANSIT SUNRAIL PHASE 2 SOUTH Poinciana Vehicle Storage & Light Maintenance Facility (VSLMF) Osceola County, Florida

More information

Sepetember 27, Florida Department of Environmental Protection Attn: Dawn Templin 160 Governmental Center Pensacola, FL

Sepetember 27, Florida Department of Environmental Protection Attn: Dawn Templin 160 Governmental Center Pensacola, FL Bay County Solid Waste 11411 Landfill Rd. Panama City Beach, Florida 32413 Telephone: (850) 236-2212 Fax: (850) 233-5053 Board of County Commissioners www.baycountyfl.gov Sepetember 27, 2018 Florida Department

More information

CONDUCTED FOR: PREPARED FOR: 5 May 2016 YPC Project No. 16GY146

CONDUCTED FOR: PREPARED FOR: 5 May 2016 YPC Project No. 16GY146 GEOTECHNICAL EXPLORATION SERVICES REPORT CONDUCTED FOR: Collier Boulevard PREPARED FOR: Mr. Christopher L. Johnson Director of Land Development Stock Development, LLC Professional Circle, Suite 01 Naples,

More information

Geotechnical Investigation for Navajo Gallup Water Supply Project Reach 26.3

Geotechnical Investigation for Navajo Gallup Water Supply Project Reach 26.3 Geotechnical Investigation for Navajo Gallup Water Supply Project Reach 26.3 Geo-Test Geotechnical Engineering Services Report No. 1-718 for Reach 26.3 Tank Site Geo-Test Job No. 1-718, Addendum No. 1

More information

SECTION STRUCTURAL EXCAVATION FOR STRUCTURES

SECTION STRUCTURAL EXCAVATION FOR STRUCTURES 1 1 1 0 1 0 1 0 1 SECTION 1. STRUCTURAL EXCAVATION FOR STRUCTURES BASED ON DFD MASTER SPECIFICATION DATED /1/1 P A R T 1 - G E N E R A L SCOPE The work under this section shall consist of providing all

More information

Subsurface Investigation Report

Subsurface Investigation Report AGI Project No. 17-154 Subsurface Investigation Report For the Proposed New One-Story Building Addition 7030 West 111 th Street Worth, Illinois Prepared for T63 Development LLC 11052 Mayflow er Lane Orland

More information

SOIL AND FOUNDATION INVESTIGATION PROPOSED DUPLEX 3966 VRAIN STREET DENVER, COLORADO

SOIL AND FOUNDATION INVESTIGATION PROPOSED DUPLEX 3966 VRAIN STREET DENVER, COLORADO SOIL AND FOUNDATION INVESTIGATION PROPOSED DUPLEX 3966 VRAIN STREET DENVER, COLORADO Prepared for: G.J. GARDNER HOMES ATTN: DAVE PAGANO 7660 RALEIGH STREET WESTMINSTER, COLORADO 80030 PROJECT NO. 1090

More information

GEOTECHNICAL INVESTIGATION PROPOSED OUTFALL LOCATION CITY OF MORGAN S POINT DRAINAGE HARRIS COUNTY, TEXAS REPORT NO

GEOTECHNICAL INVESTIGATION PROPOSED OUTFALL LOCATION CITY OF MORGAN S POINT DRAINAGE HARRIS COUNTY, TEXAS REPORT NO GEOTECHNICAL INVESTIGATION PROPOSED OUTFALL LOCATION CITY OF MORGAN S POINT DRAINAGE HARRIS COUNTY, TEXAS REPORT NO. 1140198001 Reported to: SIRRUS ENGINEERS, INC. Houston, Texas Submitted by: GEOTEST

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Coquina Beach Drainage Improvements Bradenton Beach, Florida July 16, 2018 Dunkelberger Project No. HC1032 Prepared for: Manatee County Construction Services Division Bradenton,

More information

Report of Geotechnical Exploration For. University of North Florida Kernan Shuttle Stop Jacksonville, Florida

Report of Geotechnical Exploration For. University of North Florida Kernan Shuttle Stop Jacksonville, Florida Report of Geotechnical Exploration For University of North Florida Kernan Shuttle Stop Jacksonville, Florida MAE Project No. 0016-0023 March 18, 2015 Prepared for: Prepared by: Jacksonville, Florida 32256

More information

REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS

REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS FIGURE 3 Geotechnical Report (2) REPORT OF GEOTECHNICAL EXPLORATION AND ENGINEERING ANALYSIS RIVER TOWER RESTORATION RIVER TOWER PARK TAMPA, FLORIDA AREHNA PROJECT NO. B-13-002 February 22, 2013 Prepared

More information

Report of Exploratory Test Pits

Report of Exploratory Test Pits Report of Exploratory Test Pits UNF Transportation Projects Stockpile Investigation Osprey Ridge Road Extension Jacksonville, Florida CSI Geo Project No.: 71-17-135-20 Arcadis Project No.: JK017002.0001

More information

REPORT OF GEOTECHNICAL EXPLORATION PEPSI PLACE WATER MAIN REPLACEMENT JACKSONVILLE, FLORIDA E&A PROJECT NO CLIENT ID: 4784

REPORT OF GEOTECHNICAL EXPLORATION PEPSI PLACE WATER MAIN REPLACEMENT JACKSONVILLE, FLORIDA E&A PROJECT NO CLIENT ID: 4784 REPORT OF GEOTECHNICAL EXPLORATION PEPSI PLACE WATER MAIN REPLACEMENT JACKSONVILLE, FLORIDA E&A PROJECT NO. 35-55 CLIENT ID: 78 Prepared for: Construction & Engineering Services Consultants, Inc. 93 Baymeadows

More information

GEOTECHNICAL ENGINEERING REPORT

GEOTECHNICAL ENGINEERING REPORT GEOTECHNICAL ENGINEERING REPORT Crews Park at Peace River 130 Park Drive Wauchula, FL PREPARED FOR: Kimley-Horn and Associates 116 South Kentucky Avenue Lakeland, FL 33801 NOVA Project Number: 10106-2017013

More information

For. Report of Geotechnical Exploration. University of North Florida Parking Lot 11 Jacksonville, Florida

For. Report of Geotechnical Exploration. University of North Florida Parking Lot 11 Jacksonville, Florida Report of Geotechnical Exploration For University of North Florida Parking Lot 11 Jacksonville, Florida MAE Project No. 0019-0008 January 13, 2017 Prepared for: GAI Consultants 1301 Riverplace Boulevard,

More information

September 9, Corzo Castella Carballo Thompson Salman, P.A. 901 Ponce de Leon Boulevard Suite 900 Coral Gables, Florida 33134

September 9, Corzo Castella Carballo Thompson Salman, P.A. 901 Ponce de Leon Boulevard Suite 900 Coral Gables, Florida 33134 September 9, 2009 Corzo Castella Carballo Thompson Salman, P.A. 90 Ponce de Leon Boulevard Suite 900 Coral Gables, Florida 3334 Attn: Mr. Ian John, E.I. Re: Exfiltration Test Results Glenroyal East Phase

More information

GEOTECHNICAL ENGINEERING REPORT

GEOTECHNICAL ENGINEERING REPORT GEOTECHNICAL ENGINEERING REPORT Project: NW Bucklin Hill at Silverdale Way NW Project Number: 12023 Prepared for: Barber Development P.O. Box 473 Redmond, WA 98073 Prepared by: South Sound Geotechnical

More information

GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota Phone Fax

GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota Phone Fax GEOTEK ENGINEERING & TESTING SERVICES, INC. 909 East 50 th Street North Sioux Falls, South Dakota 57104 Phone 605-335-5512 Fax 605-335-0773 May 10, 2016 Banner Associates, Inc. 2307 W. 57 th Street, Suite

More information

Geotechnical Investigation Report

Geotechnical Investigation Report Geotechnical Investigation Report Proposed,000-Gallon Water Storage Tank Fagasa Pass Tank Upper Pago Pago, American Samoa Prepared for: ASPA Water Engineering Division Tafuna, American Samoa PO Box PPB

More information

Typical Subsurface Profile. November 28, 2016

Typical Subsurface Profile. November 28, 2016 November 28, 2016 RSCCD Facility Planning, District Construction and Support Services 2323 N. Broadway, Suite 112, Santa Ana, CA 92706 Attn: Re: Ms. Allison Coburn Facilities Project Manager P: (714) 480-7530

More information

REPORT OF GEOTECHNICAL EXPLORATION KINLOCK FM REPLACEMENT NEW MANHOLE STRUCTURE JACKSONVILLE, FLORIDA ECS PROJECT NO A CLIENT ID: 0199

REPORT OF GEOTECHNICAL EXPLORATION KINLOCK FM REPLACEMENT NEW MANHOLE STRUCTURE JACKSONVILLE, FLORIDA ECS PROJECT NO A CLIENT ID: 0199 REPORT OF GEOTECHNICAL EXPLORATION KINLOCK FM REPLACEMENT NEW MANHOLE STRUCTURE JACKSONVILLE, FLORIDA ECS PROJECT NO. 3-6187-A CLIENT ID: 0199 Prepared for: JEA 1 West Church Street Jacksonville, Florida

More information

GEOTECHNICAL ENGINEERING REPORT

GEOTECHNICAL ENGINEERING REPORT GEOTECHNICAL ENGINEERING REPORT 58.6 ROAD (KIMBALL CREEK) 58.9 ROAD TO 58.7 ROAD MESA COUNTY, COLORADO February 9, 2018 Prepared By: Prepared For: Mr. Eric Krch, P.E. SGM, Inc. 744 Horizon Court, Suite

More information

1.02 RELATED WORK: Refer to the following sections for related work: Section 4000-Concrete Materials and Methods

1.02 RELATED WORK: Refer to the following sections for related work: Section 4000-Concrete Materials and Methods SECTION 2000- EARTHWORK PART 1- GENERAL 1.01 SCOPE: This Section covers excavation, fill, and compaction of earth and rock for roadway, embankments, structural foundations, and planted areas. Topics include

More information

Geotechnical Engineering Evaluation Campbell County Athletic Play Fields Campbell County High School South Campus Gillette, Wyoming

Geotechnical Engineering Evaluation Campbell County Athletic Play Fields Campbell County High School South Campus Gillette, Wyoming March 9, 2016 Proposal No. WYP16064 Campbell County School District Mr. Andy Mravlja 1000 W. 8 th Street Gillette, WY 82716 amravlja@ccsd.k12.wy.us RE: PROPOSAL Geotechnical Engineering Evaluation Campbell

More information

Report of Subsurface Exploration and Geotechnical Evaluation Services

Report of Subsurface Exploration and Geotechnical Evaluation Services Final Report of Subsurface Exploration and Geotechnical Evaluation Services Noho 2 Apartments Multi-Family Development Tampa, Florida Prepared for: Pollack Shores Real Estate Group Conestoga-Rovers & Associates

More information

Geotechnical Exploration and Evaluation Report

Geotechnical Exploration and Evaluation Report Geotechnical Exploration and Evaluation Report Nassau Reclaimed Water Main From Radio Avenue to Harts Road Nassau County, Florida CSI Geo Project No.: 71-17-329-04 Client Project No.: JEA 09302-049-01

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 APRIL 2004 CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT TABLE OF CONTENTS 422.01 SCOPE 422.02

More information

Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W340) AID Project No. GOA16001 Orange County, Florida GEC Project No.

Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W340) AID Project No. GOA16001 Orange County, Florida GEC Project No. Report of Geotechnical Engineering Investigation OIA SOUTH CELL LOT (W40) AID Project No. GOA16001 Orange County, Florida GEC Project No. 956G July 6, 2017 American Infrastructure Development, Inc. 7 North

More information

May 1, THE CORRADINO GROUP 4055 N.W. 97 th Avenue Miami, Florida Mr. Carlos E. Verson, P.E. Project Manager

May 1, THE CORRADINO GROUP 4055 N.W. 97 th Avenue Miami, Florida Mr. Carlos E. Verson, P.E. Project Manager May 1, 213 THE CORRADINO GROUP 455 N.W. 97 th Avenue Miami, Florida 33178 Attention: Mr. Carlos E. Verson, P.E. Project Manager Re: Report of Geotechnical Engineering Services - Roadway Soil Survey Bird

More information

Subsurface Environmental Investigation

Subsurface Environmental Investigation Subsurface Environmental Investigation Lake Development East Lake and 21 st Avenue South February 23, 201 Terracon Project No. MP14738A Prepared for: Minneapolis Public Schools Prepared by: Terracon Consultants,

More information

Florida s Leading Engineering Source

Florida s Leading Engineering Source Since 1988 Florida s Leading Engineering Source Environmental Geotechnical Construction Materials Testing Threshold and Special Inspections Plan Review & Code Compliance Mr. Ron Ridenour Hanson Professional

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS IN OPEN CUT

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS IN OPEN CUT ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 November 2015 CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS IN OPEN CUT TABLE OF CONTENTS D 422.01 D 422.02 D 422.03

More information

Foundations, Excavation & Shoring Specialists

Foundations, Excavation & Shoring Specialists Foundations, Excavation & Shoring Specialists July 8, 017 Reference: 17-7 McElhanney Consulting Services Ltd. Suite 00 Central City Tower 10 10 nd Avenue Surrey, BC VT X Via email: mflorendo@mcelhanney.com

More information

REPORT OF GEOTECHNICAL CONSULTING SERVICES

REPORT OF GEOTECHNICAL CONSULTING SERVICES REPORT OF GEOTECHNICAL CONSULTING SERVICES Escambia County Public Works Department Thompson, Crary and McNeal Roadway Project Escambia County, Century,FL Thompson Engineering Project No.: 15-1101-0297

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Geotechnical Engineering Report Pavement Subgrade Survey State Highway 125 over Hudson Creek Ottawa County, Oklahoma September 23, 21 Terracon Project No. 415121 Prepared for: Guy Engineering Services,

More information

Geotechnical Investigation

Geotechnical Investigation REVISED Geotechnical Investigation Pueblo Pintado Tank Site Includes NGWSP Reaches 26.1 & 26.2 Pueblo Pintado in New Mexico Prepared for: Souder, Miller & Associates Project No.: 15-1-057 June 9, 2016

More information

SUBSURFACE INVESTIGATION & GEOTECHNICAL RECOMMENDATIONS PROPOSED MONOPOLE CELL TOWER INDIANAPOLIS, INDIANA A&W PROJECT NO: 15IN0464

SUBSURFACE INVESTIGATION & GEOTECHNICAL RECOMMENDATIONS PROPOSED MONOPOLE CELL TOWER INDIANAPOLIS, INDIANA A&W PROJECT NO: 15IN0464 SUBSURFACE INVESTIGATION & GEOTECHNICAL RECOMMENDATIONS PROPOSED MONOPOLE CELL TOWER INDIANAPOLIS, INDIANA A&W PROJECT NO: 15IN0464 PREPARED FOR: AAA DEVELOPMENT AND CONSULTING, INC GREENFIELD, INDIANA

More information

EXHIBIT G GEOTECHNICAL REPORT (DRAFT)

EXHIBIT G GEOTECHNICAL REPORT (DRAFT) EXHIBIT G GEOTECHNICAL REPORT (DRAFT) APPENDIX 1 PROJECT SITE 'B' B-1 B-2 I-2 B-3 B-4 B-5 I-1 PROJECT LOCATION LEGEND B-1 = APPROXIMATE BORING LOCATION I-1 = APPROXIMATE INFILTRATION

More information

Geotechnical Engineering Report

Geotechnical Engineering Report Mobile Offices and Future Service Center Range Road Eglin Air Force Base, Florida November 2, 2016 Project No. EA165075 Prepared for: American States Utility Services, Inc. Prepared by: Terracon Consultants,

More information

APPENDIX A DRAINAGE STUDY PHASE 2 ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE 4C IMPROVEMENTS LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC

APPENDIX A DRAINAGE STUDY PHASE 2 ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE 4C IMPROVEMENTS LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC DRAINAGE STUDY PHASE ALTERNATIVE IMPROVEMENTS CRYSTAL LAKE ALTERNATIVE C IMPROVEMENTS ` FOR: LAKEWOOD PIRATELAND SWASH HORRY COUNTY, SC APPENDIX A J-.000 Prepared by: Savannah, GA Charleston, SC Myrtle

More information

CITY OF CAPE CORAL. City of Cape Coral Procurement Division 1015 Cultural Park Boulevard, 2 nd Floor Cape Coral, FL 33990

CITY OF CAPE CORAL. City of Cape Coral Procurement Division 1015 Cultural Park Boulevard, 2 nd Floor Cape Coral, FL 33990 PROJECT MANUAL CITY OF CAPE CORAL UTILITIES EXTENSION PROJECT (UEP) NORTH 2 - CONTRACT 13 CANAL PUMP STATION (WEST) NO. 9 AND (EAST) NO. 10 ITB-UEP17-18/SH City of Cape Coral Procurement Division 1015

More information

Stanford University Facilities Design Guidelines SECTION STONE FINES PAVING. American Society for Testing and Materials.

Stanford University Facilities Design Guidelines SECTION STONE FINES PAVING. American Society for Testing and Materials. SECTION 32 15 40 STONE FINES PAVING PART 1 GENERAL 1.1 RELATED WORK Section 32 11 00: Base Courses 1.2 QUALITY ASSURANCE A. Applicable Standards: Any reference shall mean the current or latest editions

More information

South Sound Geotechnical Consulting P.O. Box Lakewood, WA (253) Figure 1 Site Plan. SERA Playground Tacoma, WA.

South Sound Geotechnical Consulting P.O. Box Lakewood, WA (253) Figure 1 Site Plan. SERA Playground Tacoma, WA. N TP -3, E3RA TP -4, E3RA TP -2, E3RA B -6, Terracon HA -2 HA -3 HA -1 TP -1, E3RA Legend HA-1 Approximate Hand Excavation Location by SSGC Approximate Exploration Location by others Scale: NTS South Sound

More information

PRELIMINARY GEOTECHNICAL INVESTIGATION REPORT

PRELIMINARY GEOTECHNICAL INVESTIGATION REPORT PRELIMINARY GEOTECHNICAL INVESTIGATION REPORT HAMPTON INN 14 Geronimo Avenue Parker, Arizona Prepared For: Greens Group 14252 Culver Drive, A 358 Irvine, CA 92604 October 22, 2014 Project No.: 14238 Prepared

More information

For. Report of Geotechnical Exploration. University of North Florida Parking Lot 47 Jacksonville, Florida

For. Report of Geotechnical Exploration. University of North Florida Parking Lot 47 Jacksonville, Florida Report of Geotechnical Exploration For University of North Florida Parking Lot 47 Jacksonville, Florida MAE Project No. 0019-0009 April 5, 2017 Revised: April 6, 2017 Prepared for: Prepared by: Jacksonville,

More information

B. The Bidder shall acknowledge receipt of this Addendum in the appropriate space on the Bid Form.

B. The Bidder shall acknowledge receipt of this Addendum in the appropriate space on the Bid Form. City of Casper Baler Building / MRF Expansion DOCUMENT 9113 ADDENDUM.1 ADDENDUM NUMBER: 1.2 PROJECT INFORMATION A. Project Name: Baler Building / MRF Expansion B. Owner: City of Casper C. Architect: Hein

More information

PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS ACADEMIC OFFICE BUILDING COLORADO SPRINGS, COLORADO

PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS ACADEMIC OFFICE BUILDING COLORADO SPRINGS, COLORADO PRELIMINARY GEOTECHNICAL INVESTIGATION UCCS COLORADO SPRINGS COLORADO Prepared for: UNIVERSITY OF COLORADO AT COLORADO SPRINGS Facilities Services 1420 Austin Bluffs Parkway Colorado Springs Colorado 80918

More information

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL

SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL SECTION XXXXX AGGREGATE PIERS PART 1 - GENERAL 1.1 RELATED DOCUMENTS: Drawings and general provisions of the Contract, including General and Supplementary Conditions and other Division 00 and Division

More information

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT

CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT ONTARIO PROVINCIAL STANDARD SPECIFICATION METRIC OPSS 422 APRIL 2004 (Reissued November 2010) CONSTRUCTION SPECIFICATION FOR PRECAST REINFORCED CONCRETE BOX CULVERTS AND BOX SEWERS IN OPEN CUT TABLE OF

More information

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants

Ardaman & Associates, Inc. Geotechnical, Environmental and Materials Consultants SUBSURFACE SOIL EXPLORATION ANALYSIS AND RECOMMENDATIONS CREEKSIDE BOULEVARD FORCE MAIN EXTENSION AND INTERCONNECT NAPLES, COLLIER COUNTY, FLORIDA COLLIER COUNTY PROJECT NO. 700.2. P.O. #0003, CN #3-66

More information

Earth Mechanics, Inc. Geotechnical & Earthquake Engineering

Earth Mechanics, Inc. Geotechnical & Earthquake Engineering Earth Mechanics, Inc. Geotechnical & Earthquake Engineering TECHNICAL MEMORANDUM DATE: June 3, 2009 EMI PROJECT NO: 01-143 TO: COPY: FROM: SUBJECT: John Chun, P.E. / Port of Long Beach (POLB) Jorge Castillo

More information

TABLE OF CONTENTS 1.00 INTRODUCTION GENERAL PROJECT DESCRIPTION SUBSURFACE EXPLORATION SUBSURFACE CONDITIONS...

TABLE OF CONTENTS 1.00 INTRODUCTION GENERAL PROJECT DESCRIPTION SUBSURFACE EXPLORATION SUBSURFACE CONDITIONS... TABLE OF CONTENTS 1.00 INTRODUCTION...1 1.10 GENERAL...1 1.20 PROJECT DESCRIPTION...1 2.00 SUBSURFACE EXPLORATION...2 3.00 SUBSURFACE CONDITIONS...3 4.00 GEOTECHNICAL CONSIDERATIONS AND RECOMMENDATIONS...4

More information

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7)

SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) Page 1 of 7 STONE STRONG SYSTEMS SPECIFICATIONS FOR PRECAST MODULAR BLOCK RETAINING WALL SYSTEM (revised 5/8/7) PART 1: GENERAL 1.01 Description A. Work includes furnishing and installing precast modular

More information

GEOTECHNICAL INVESTIGATION ADDENDUM Pavement Improvements for Imperial Avenue, Wake Avenue, and Danenberg Drive, El Centro, California

GEOTECHNICAL INVESTIGATION ADDENDUM Pavement Improvements for Imperial Avenue, Wake Avenue, and Danenberg Drive, El Centro, California Mr. Victor Garcia The Holt Group 1601 N. Imperial Ave. El Centro, California 92243 September 28, 2017 Project No. EC595 SUBJECT: REFERENCE: GEOTECHNICAL INVESTIGATION ADDENDUM Pavement Improvements for

More information

File No Supplemental November Geotechnical and Environmental Consulting Engineers

File No Supplemental November Geotechnical and Environmental Consulting Engineers Supplemental Information & Geotechnical Recommendations Proposed New Solar Valley Location B (East of Building No. 7) Cañada Community College 4200 Farm Hill Boulevard Submitted to: Mr. Peter Hempel Construction

More information

REPORT OF SUBSURFACE EXPLORATION. Burn and Rescue Facility Spartanburg County Emergency Services Academy Duncan, SC GeoTrack Project No.

REPORT OF SUBSURFACE EXPLORATION. Burn and Rescue Facility Spartanburg County Emergency Services Academy Duncan, SC GeoTrack Project No. 3620 Pelham Road, PMB #292 Phone: 8643290013 Greenville, SC 296155044 FAX: 8643290014 REPORT OF SUBSURFACE EXPLORATION Burn and Rescue Facility Spartanburg County Emergency Services Academy Duncan, SC

More information

ITEM NO. 1: NEW MAINTENANCE BAY TECHNICAL SPECIFICATIONS, SECTION :

ITEM NO. 1: NEW MAINTENANCE BAY TECHNICAL SPECIFICATIONS, SECTION : ADDENDUM NO. 3 Project: FMS #8 LIFE CYCLES UPGRADE AND NEW MAINTENANCE BAY Florida National Guard Lake City, Florida September 10, 2018 This Addendum forms a part of the contract documents and modifies

More information

FIGURES Printed By: aday Print Date: 3/23/2011 12:48:08 PM File Name: \\geodesign.local\files\jobs\m-r\penskeauto\penskeauto-1\penskeauto-1-01\figures\cad\penskeauto-1-01-vm01.dwg Layout: FIGURE 1 VICINITY

More information

Facility Number South Goldenrod Road Orlando, Florida 07/05/2017

Facility Number South Goldenrod Road Orlando, Florida 07/05/2017 Facility Number 21144 2300 South Goldenrod Road Orlando, Florida 07/05/2017 Specifications based on Unified Design Standards Specifications, FY15 BI-Annual Release #2(UDSv15-2), Issued: March 13, 2015

More information

SECTION SOILS REPORT

SECTION SOILS REPORT SECTION 02300 SOILS REPORT 1. GENERAL: 1.1 All work included under this heading shall be subject to the General Conditions of the entire operation. This Contractor is required to refer especially thereto.

More information

Section 1I-3 - Bioswales

Section 1I-3 - Bioswales BIOSWALES (Numbering pending) These specifications compliment the bioswale design portion of the Iowa Stormwater Management Manual in Chapter 2, Section 2I-3. Sections of the following documents, as referenced

More information

Geotechnical Investigation Report

Geotechnical Investigation Report MC Squared, Inc. Geotechnical Investigation Report City of St. Petersburg Forcemain Pinellas County, Florida Prepared for: Hazen and Sawyer 10002. Princess Palm Ave., Suite 200 Tampa, Florida 33610 Prepared

More information

PROJECT NO A. ISSUED: February 29, 2016

PROJECT NO A. ISSUED: February 29, 2016 INTERPRETIVE REPORT FOR INFILTRATION SYSTEM DESIGN, PROPOSED VILLA VERONA APARTMENT COMMUNITY, ASSESSOR S PARCEL NUMBERS 311-040-015, 311-040-021, 311-040-024, 311-040-026 AND 311-040-013, LOCATED ON THE

More information

March 10, 2017 SITE AND PROJECT INFORMATION

March 10, 2017 SITE AND PROJECT INFORMATION March 10, 2017 Derek Hawkes, PE NASH COUNTY 120 W. Washington Street - Suite 2004 Nashville, NC 27856 Re: Report of Subsurface Investigation Middlesex Corporate Park, Lot 3 Middlesex, North Carolina GeoTechnologies

More information

DIVISION 31 EARTHWORK 2006 Edition, Published January 1, 2006; Division Revision Date: January 31, 2012

DIVISION 31 EARTHWORK 2006 Edition, Published January 1, 2006; Division Revision Date: January 31, 2012 2006 Edition, Published January 1, 2006; Division Revision Date: January 31, 2012 PART FIVE DOCUMENTS FOR SITE AND INFRASTRUCTURE 31 00 00. EARTHWORK 31 10 00. SITE CLEARING.1 STRUCTURE REMOVAL: Include

More information

DIVISION 4100 SITEWORK

DIVISION 4100 SITEWORK DIVISION 4100 SITEWORK SECTION 4115 EARTHWORK PART 1 - GENERAL 1.01 SCOPE This section covers the grading and compaction of excavations, embankments, structural foundations, and planted areas. 1.02 REFERENCES

More information

( KLEINFEL DER. November 17,2008 File No MARINA COAST WATER DISTRICT th Avenue Marina, California ATTENTION: Mr.

( KLEINFEL DER. November 17,2008 File No MARINA COAST WATER DISTRICT th Avenue Marina, California ATTENTION: Mr. ( KLEINFEL DER L Bright People. Right Solutions. November 17,2008 File No. 82142 40 Clark Street, Suite J Salinas, CA 93901 p1 831.755.7900 f 1831.755.7909 kleinfelder.com MARINA COAST WATER DISTRICT 2840

More information