1 SEMINOLE TRIBE OF FLORIDA Denise DeCarolis Carpenter Purchasing Department Director 6300 STIRLING ROAD HOLLYWOOD, FLORIDA PHONE (954) x11170 FAX (954) WEBSITE: Tribal Officers: MARCELLUS W. OSCEOLA, JR. Chairman MITCHELL CYPRESS Vice-Chairman LAVONNE ROSE Secretary REQUEST FOR PROPOSALS FOR HOLLYWOOD WASTEWATER SYSTEM IMPROVEMENTS RFP Addendum No. 4, issued November 29, 2017 PETER HAHN Treasurer This Addendum No. 4 is hereby made a part of RFP and has been issued to amend RFP as follows: Please note, in regards to replacement specifications, some but not all, note changes in bold. Contractor shall review all replacement specifications thoroughly for changes from the original version. ITEMS AFFECTING ALL CONSTRUCTION PACKAGES 1. The following documents have been replaced through this addendum: 1) Exhibit A Bid Form (revised) HOLLYWOOD WASTEWATER TREATMENT PLANT 2. The following documents have been replaced through this addendum: 1) Attachment A Specifications Section Equipment Testing and Plant Startup Section Concrete Block Masonry Section Aluminum Louvers Section Pre-Engineered Metal Building System Section Odor Control System Section Schedules Section Radio Telemetry System (Unlicensed)

2 Section Optical Nitrate Analyzers Section Ammonium Analyzers (ISE Probe) Table Instrument Schedule Appendix B Evoqua Water Technologies Proposal 2) Attachment B - Plans I-22 Instrumentation Details - IV 3. The following questions/inquiries are being addressed through this addendum: 1) On behalf of WACO Products Inc., we request that WACO Products Inc. be included as a named manufacturer under Specification Section RESPONSE: Manufacturers that meet the requirements of the specifications are acceptable. Approval will be during shop drawing review. 2) Section Paragraph 2.04.A.3: Local Control Station (LCS) shall meet the following requirements : NEMA 4/7/9 cast aluminum explosion-proof enclosure. LCS shall be mounted a minimum of 3 feet from any potential leak point to comply with NFPA 820. These two requirements are typically either/or but here are specified as required. To make the LCS explosion proof will be costly and MAY not be necessary. Please confirm if the panel needs to be explosion proof if it is to be mounted >3 from any leak source. Is 316 Stainless Steel an acceptable enclosure material. RESPONSE: Control panel shall have NEMA 4X 316 Stainless Steel enclosure. Specification regarding clearance shall remain. The specification has been revised accordingly, and is included in this addendum. 3) Section Paragraph A. 11. o. Fans to be provided with an inlet box The plans do not show an inlet box on the blower and to accommodate an inlet box, modification to the ductwork layout would almost certainly be required. Please confirm if an inlet box is required. RESPONSE: An inlet box is not required. The specification has been revised accordingly, and is included in this addendum. 4) Section B.1 specifies that the structural framing for the pre-engineered metal buildings shall be shop primed and then field removed/coated in accordance with Section Since the structural bolts will be hot dip galvanized per Section 05035, would it be acceptable to have the building manufacturer hot dip galvanize the structural framing instead of painting it? This would reduce future maintenance on the buildings. RESPONSE: Galvanizing of structural framing instead of painting shall not be acceptable. Structural bolts shall not be galvanized. See revised Section included in this addendum. Seminole Tribe of Florida CONFIDENTIAL Page 2 of 7

3 5) Section A indicates the pre-engineered metal buildings shall be manufactured by United Structures of America, Butler Manufacturing, or approved equal. We have reached out to both companies and have only received confirmation from one of the companies that they might be bidding. We have received inquiries from other manufacturers who would like to bid on the project. Would any of the following pre-engineered building manufacturers be acceptable? - Trident Building Systems, American Building Company, Ceco Corporation, Nucor Building Systems, and Vacro-Pruden Building Systems. We have used all of these manufacturers on previous projects and all should be capable of meeting the specification. If not, the manufacturers have requested us to ask what the pre-approval process is to get approved. RESPONSE: Manufacturers that meet the requirements of the specifications are acceptable. Approval will be during shop drawing review. 6) Sheet A-14 Section F indicates a 8 CMU with 8 Sound Absorbent CMU will be used for the East wall of the Plenum hallway at elevation Clarification of the layout is needed for the interior masonry walls at elevation for the Electrical Building. RESPONSE: No Acoustical CMU will be required for the CMU sections of the wall along Column Line 3. All walls indicated on Floor Plan of drawing A-13 to have sound absorbent CMU shall have such CMU at elevation ) Section does not specify the type of glass block to be used at the Headworks on Sheet S-06 & S-07. Please clarify the specifications for the glass block. RESPONSE: See revised Section 04200, included in this addendum. 8) Section B indicates the ductwork will be 316-L Stainless Steel Ductwork. We have received inquiries about whether 316 Stainless Steel Ductwork is need in the Operations Building as it will not be exposed. Using Aluminum or galvanized ductwork would be cost effective in these types of areas. Please advise if aluminum or galvanizes ductwork would be acceptable. RESPONSE: It has been our experience that stainless steel actually provides an overall lower cost when compared to aluminum. Although aluminum material is less expensive, aluminum has higher installation labor costs since it requires more supports and additional duct reinforcing to meet the design pressure classification. This is also indicated in standard cost estimating manuals similar to MEANS. We don t recommend galvanized steel due to its potential for rust and corrosion. Significant rusting and corrosion for galvanized steel ductwork has been experienced on previous projects in high humid climates at water and wastewater sites just from the transport and storage of the ductwork before it has been installed. 9) Please clarify if trusses need to be light weight gauge steel. RESPONSE: Materials for roof trusses are identified in Specification Pre Engineered Cold Formed Steel Trusses. 10) Is door #206 to be 10 wide X 18 high per door schedule, or 18 wide X 10 high per floor plan & elevations? Please clarify. Seminole Tribe of Florida CONFIDENTIAL Page 3 of 7

4 RESPONSE: Door shall be 18 wide x 10 high. 11) Does door #206 need to have an explosion proof operator or normal operator? Electrical drawings do not show anything for the door. RESPONSE: Neither rolling door at the WWTP is electrically operated. 12) Does door #206 need to have a loop detector? Electrical drawings do not show anything for the door. RESPONSE: Per detail 22 on E-89, electrical contractor is to install conduit and junction boxes for installing position detectors by others. 13) Please clarify the application of the spray applied rock wool insulation over the spray applied polyurethane foam insulation. The specification call for a thermal barrier which we would normally spray directly to our spray foam after we have installed it. This spray applied thermal barrier is water based. If you were to apply the spray applied rock wool on top of the spray applied thermal barrier it would cause the adhesion to release and not stick. RESPONSE: The spray applied rock wool will act as the thermal barrier. In location where spray foam is applied and not covered (if any) a thermal barrier is required. We are unaware of any adhesion concerns between the spray foam and spray applied rock wool. Systems will be required to be compatible. 14) Please clarify the area that need to be sealed, room names and numbers do not correspond to one another. RESPONSE: Note the following corrections/clarifications to the drawings: A- 23 MAINTENANCE/GARAGE 208 should be revised to MAINTENANCE/GARAGE 206 ; A-23 SECURE TOOL STORGE 215 should be revised to STORAGE 206A ; A-26 MAINTENANCE/GARAGE 208 should be revised to MAINTENANCE/GARAGE 206 ; A-31 MAINTENANCE/GARAGE 208 should be revised to MAINTENANCE/GARAGE ) SECTION OPTICAL NITRATE ANALYZERS (ISE PROBE) and SECTION AMMONIUM ANALYZERS (ISE PROBE) Both the Endress + Hauser CAS40D and the YSI VARiON are intended to be immersed in a basin. The drawings depict an inline mounting via a flow-through assembly. Please confirm the mounting requirement. RESPONSE: See revised Sections and included in this addendum. Endress + Hauser manufactures flow through assemblies for both the optical nitrate and ISE ammonia probe. YSI remains in the spec, but YSI will need to provide a flow through assembly for each probe. The design will not be changed to accommodate YSI. 16) Under SECTION RADAR LEVEL INDICATING TRANSMITTER/ TRANSDUCER Tag No. LE-4100 appears to be a LEVEL TRANSDUCER Seminole Tribe of Florida CONFIDENTIAL Page 4 of 7

5 (SUBMERSIBLE PRESSURE TYPE). Dwg. I-12 depicts it as a SUBMERSIBLE, PRESSURE TYPE LEVEL PROBE IN STILLING WELL. RESPONSE: Section Instrument List has been updated to correctly show LE-4100 as a submersible pressure type level transducer. Revised section is included in this addendum. 17) M-03 shows four (4) Stop Gates and refers to Detail 4 on M-11 which shows 3 wide gates in the Screen Influent Channel and 4 wide gates in the Bypass Channel. Thus, it appears that there are two (2) 3 X 4 Stop Gates and two (2) 4 X 4 Stop Gates, but the Stop Gate Schedule in requires three (3) 3 X 4 Stop Gates and one (1) 4 X 4 Stop Gate. It appears that the schedule is incorrect. Please clarify. RESPONSE: Section has been revised to reflect two (2) 3' x 4' Stop Gates and two (2) 4' x 4' Stop Gates. Revised section is included in this addendum. 18) 4-yard dumpster(s) are shown as BY OTHERS on M-08. Does BY OTHERS mean that they are not to be provided as part of the Contract. RESPONSE: Correct. Dumpsters will be furnished by Owner. 19) S-52 indicates a Specialty Concrete Coating for the interior of the Plant Site Pump Station, but SPECIALTY CONCRETE COATINGS only indicates Headworks and Transfer Pump Station. Please clarify what coating is required for the Plant Site Pump Station. RESPONSE: Interior coating of the Plant Site Pump Station is specified on drawings M-33 and M ) A-31 Provides the Operations Building Floor Furniture Plan. Are these furnishings to be provided by the Contractor? If so, please provide a furnishings schedule and associated specifications. RESPONSE: All furnishings are to be provided by the Contractor. General notations are provided on Drawing A-31. Note Control System Furniture is specified in Section ) We have been asked to review the information on this project to submit pricing for select materials, and in our review focusing on the louvers have found some conflicting information thus are submitting this RFI for clarification. Louver spec section under 2.01.C require performance including 57% free area based on 48 x 48 unit, Class A wind driven rain resistance at 50 MPH wind speed with rainfall rate of 8 per hour. None of the louver models shown under 2.01.A meet both the requirements, and no louver researched with a current NOA meets the combined requirements. Do you wish a 57% free area unit with a damper to meet the TAS wind driven requirement, or a standard wind driven rain resistant unit with free area in the 40-43% free area range. Some of the schedules conflict in calling for lesser free area and also for damper units Seminole Tribe of Florida CONFIDENTIAL Page 5 of 7

6 Louver spec notes a Kynar paint finish, but notes on some of the louver schedules note an Anodized finish. Which is desired, and if an Anodized finish clarify if a Class I clear anodized or a Class I color anodized finish, and color desired RESPONSE: See revised Section included in this addendum. On Drawing H-05, in Louver Schedule under Manufacturer & Model No. column, DELETE Greenheck ELF6375DXD and REPLACE with Greenheck EHH-601D. INJECTION WELL PUMP STATION 4. The following documents have been replaced through this addendum: 1) Attachment A Specifications Section Equipment Testing and Startup Section Pre-Engineered Metal Building System Section Radio Telemetry System (Unlicensed) 2) Attachment B - Plans E-03 Electrical Site Plan Injection Well Area Sheet 1 of 2 E-04 Electrical Site Plan Injection Well Area Sheet 2 of 2 E-05 Electrical Site Plan IWPS Area E-17 Panel Schedules and Riser Diagrams E-24 Electrical Details I-08 Instrumentation Details III 5. The following documents have been added through this addendum: 1) General Shed Drawings by Superior Sheds, Inc (6 pages) 6. The following questions/inquiries are being addressed through this addendum: 1) Can you provide the details for the concrete paving (reinforcement and thickness) that is to be demolished on C-03. RESPONSE: Demolition limits and duct bank routing were revised in previous addenda. Refer to revised drawings C-03 and C-06 including in Addendum 3. Refer to E-05 in Addendum 2 for duct bank reroute. 2) Can you provide any as-built drawings for the storage buildings that we are to relocate per C-03 and C-06 including any details on the slab under those buildings. Seminole Tribe of Florida CONFIDENTIAL Page 6 of 7

7 RESPONSE: Shed Drawings by Superior Sheds, Inc are included in this addendum. 3) Is there information on the existing electrical service that gets fed to the new location? RESPONSE: Please refer to revised Drawings E-05 and E-17 included in this addendum. Seminole Tribe of Florida CONFIDENTIAL Page 7 of 7

ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT WEST VALLEY COLLEGE

ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT WEST VALLEY COLLEGE ADDENDUM #4 FOR THE WEST VALLEY FACILITIES INCREMENT 2 REPLACEMENT PROJECT AT WEST VALLEY COLLEGE Owner West Valley-Mission Community College District Saratoga, California Bid #01-1516 12-22-15 WEST VALLEY-MISSION

More information

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School

Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School A D D E N D U M # 1 DATE: TO: FROM: PROJECT: All Bidders Michael Teller, CBI Consulting Inc. Gymnasium & Auditorium Restoration at South Middle School CBI JOB NO.: 11063 The following items shall modify

More information

This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated.

This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated. BIDDER RESPONSES RIARNG P-6 ADDITION TO ALL BIDDERS OF RECORD: This Addendum forms a part of the Contract Documents and modifies the Drawings and Project Manual as hereinafter indicated. ADDENDUM 001 2/14/2019

More information

ADDENDUM NO. 1 FOR RENOVATIONS TO LINCOLN ANIMAL SHELTER RFP # February 1, 2018

ADDENDUM NO. 1 FOR RENOVATIONS TO LINCOLN ANIMAL SHELTER RFP # February 1, 2018 ADDENDUM NO. 1 FOR RENOVATIONS TO LINCOLN ANIMAL SHELTER RFP #2018-09-01 NOTICE TO PROSPECTIVE BIDDERS February 1, 2018 Prospective bidders are hereby informed of the following corrections, additions,

More information

ADDENDUM NO. 1. PROJECT: Lowell High School DATE: January 28, Eucalyptus Drive, SF, CA 94132

ADDENDUM NO. 1. PROJECT: Lowell High School DATE: January 28, Eucalyptus Drive, SF, CA 94132 SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2011 PROPOSITION A BOND PROGRAM LOWELL HIGH SCHOOL PROJECT #11493 INTERIM HOUSING for VOLUNTARY SEISMIC STRENTHENING ADDENDUM NO. 1 PROJECT: Lowell High School DATE:

More information

CHARLES COUNTY GOVERNMENT ITB NO WAKEFIELD PUMPING STATION UPGRADE

CHARLES COUNTY GOVERNMENT ITB NO WAKEFIELD PUMPING STATION UPGRADE CHARLES COUNTY GOVERNMENT Department of Fiscal and Administrative Services Purchasing Division Telephone: 301-645-0656 February 27, 2014 ITB NO. 14-33 WAKEFIELD PUMPING STATION UPGRADE ADDENDUM NUMBER

More information

Addendum No. 3: EAST HIGH SCHOOL AUDITORIUM RENOVATIONS

Addendum No. 3: EAST HIGH SCHOOL AUDITORIUM RENOVATIONS Rockford Board of Education 501 Seventh Street Rockford, IL 61104 May 30, 2014 Addendum No. 3: 14-70 EAST HIGH SCHOOL To All Bidders: Attached are modification, clarifications and/or corrections for the

More information

Please note: Drawings M105, M109, M203, M204, M205 and M207 were attached to ADDENDUM 2 and replace the previous drawings.

Please note: Drawings M105, M109, M203, M204, M205 and M207 were attached to ADDENDUM 2 and replace the previous drawings. Procurement Department Bid Office Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 June 20, 2016 ADDENDUM NUMBER: THREE (3) TITLE: 081-16 Arlington East WRF Secondary

More information

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R

HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO R HURON PUBLIC WORKS BUILDING HURON, SOUTH DAKOTA BID NO. 2017-26R Stone Group Architects Project No. 1731 ADDENDUM DATE: September 14, 2017 BID DATE: September 18, 2017 2:00 P.M. C.S.T. SCOPE OF THIS ADDENDUM:

More information

Addendum No. 1. City of Chicago Department of Water Management Bureau of Engineering Services

Addendum No. 1. City of Chicago Department of Water Management Bureau of Engineering Services Addendum No. 1 City of Chicago Department of Water Management Bureau of Engineering Services South Water Purification Plant Filter Backwash Controls Replacement DWM PROJECT NO. 13-202 SPECIFICATION NO.

More information

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen:

March 6, Subject: Addendum No. 2 Invitation for Bid No Toyota Park Transit Center Phase II. Ladies and Gentlemen: March 6, 2018 Subject: Addendum No. 2 Toyota Park Transit Center Phase II Ladies and Gentlemen: This Addendum No. 2 is being issued to provide responses to questions submitted by potential bidders and

More information

SECTION LOW-VOLTAGE TRANSFORMERS

SECTION LOW-VOLTAGE TRANSFORMERS PART 1 GENERAL 1.1 DESCRIPTION SECTION 26 22 00 SPEC WRITER NOTE: Use this section only for NCA projects. Delete between // // if not applicable to project. Also, delete any other item or paragraph not

More information

RFI REPLY. Project: Palm Coast Readiness Center Date: 07/22/16 Flagler County, Florida Comm. No.: 09005

RFI REPLY. Project: Palm Coast Readiness Center Date: 07/22/16 Flagler County, Florida Comm. No.: 09005 Project: Palm Coast Readiness Center Date: 07/22/16 Flagler County, Florida Comm. No.: 09005 To: All Bidding General Contractors Fax Email U.S. Mail Attn. Messenger We are sending the following: Quick

More information

See attached answers to questions and requests for clarification received.

See attached answers to questions and requests for clarification received. Office of the Vice President 971 Elmore Drive and Chief Financial Officer PO Box 115250 Procurement Services Gainesville, FL 32611-5250 http://procurement.ufl.edu/ (352) 392-1331 Fax 352-392-8837 June

More information

SECTION SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 418 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT

SECTION AIR-TO-AIR ENERGY RECOVERY EQUIPMENT SECTION 23 72 00 AIR-TO-AIR ENERGY RECOVERY EQUIPMENT PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division

More information

APPENDIX 1 PROJECT REQUIREMENTS

APPENDIX 1 PROJECT REQUIREMENTS APPENDIX 1 PROJECT REQUIREMENTS I) Scope of Work This section contains a general summary of the work the Contractor shall perform under this contract. If any conflict exists between the work described

More information

REBECCA LG BOSTICK, ARCHITECTS, INC

REBECCA LG BOSTICK, ARCHITECTS, INC REBECCA LG BOSTICK, ARCHITECTS, INC 703-768-2250 ADDENDUM NO. 3 Page 1 of 4 (plus attachments -2 pages) SILVERBROOK ELEMENTARY SCHOOL RENOVATION Fairfax County Public Schools 9350 Crosspointe Drive, Fairfax

More information

SECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 432 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 422 SERIES INSULATED STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO.

ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. ADDENDUM NO. 3 TO THE CONTRACT DOCUMENTS AND SPECIFICATIONS DATED JULY 2017 FLORIDA GOVERNMENTAL UTILITY AUTHORITY PROJECT NO. PS 061 SEVEN SPRINGS WASTEWATER TREATMENT FACILITY IMPROVEMENTS PASCO COUNTY,

More information

SOLICITATION ADDENDUM

SOLICITATION ADDENDUM CITY OF PALM BEACH GARDENS PURCHASING DEPARTMENT SOLICITATION ADDENDUM Addendum No. 7 DATE: August 22, 2018 TO: SOLICITATION NO.: TITLE: OPENING DATE: All Potential Bidders ITB2018-095RC Construction of

More information

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336)

603 Summit Avenue, Suite 102 Greensboro, N.C Voice/FAX (336) Ricky L. Loman, AIA Architect 603 Summit Avenue, Suite 102 Greensboro, N.C. 27405-7700 Voice/FAX (336) 273-7999 ADDENDUM: Number 1 ISSUED: March 14, 2017 SUBJECT: New Agriculture & Equipment Storage Barn

More information

TECHNICAL QUESTIONS FOR ITB-DOT-17/ LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE

TECHNICAL QUESTIONS FOR ITB-DOT-17/ LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE TECHNICAL QUESTIONS FOR ITB-DOT-17/18-7004LV DEMOLITION AND CONSTRUCTION OF DISTRICT SEVEN OFFICE SPACE Question 1: Question 2: Question 3: Question 4: Question 5: Question 6: When area configurations

More information

ADDENDUM NO.2 REQUEST FOR PROPOSALS FOR CITY OF PALM COAST

ADDENDUM NO.2 REQUEST FOR PROPOSALS FOR CITY OF PALM COAST ADDENDUM NO.2 REQUEST FOR PROPOSALS FOR CITY OF PALM COAST WASTEWATER TREATMENT PLANT NO.2 MEMBRANE BIOREACTOR EQUIPMENT City Project No. RFP- U- 08-10 DATE: March 28, 2008 TO: Prospective Membrane Bioreactor

More information

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS

TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS AIA General Conditions... GC-1 to GC-44 Amendments to General Conditions... AM-1 to AM-2 Supplements to General Conditions... SU-1 to SU-7 00200 Instructions To Bidders... 1 3 00201 Contractor s Bidding

More information

SECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON

SECTION MISCELLANEOUS METALS THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION MISCELLANEOUS AND ORNAMENTAL IRON SECTION 055000 THIS SECTION TO BE INCLUDED IN SUB BID FOR SECTION 050001 MISCELLANEOUS AND ORNAMENTAL IRON PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a

More information

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES

SECTION COMPOSITE WALL PANELS PART 1 GENERAL 1.01 SECTION INCLUDES SECTION 07 4243 - PART 1 GENERAL 1.01 SECTION INCLUDES A. Composite wall panel system consisting of aluminum-faced composite panels in a rainscreen application as part of the assembly described below.

More information

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL

HOLLOW METAL DOORS AND FRAMES SECTION HOLLOW METAL DOORS AND FRAMES PART 1 - GENERAL 13686.00 HOLLOW METAL DOORS AND FRAMES 081113-1 SECTION 081113 - HOLLOW METAL DOORS AND FRAMES 1.1 RELATED DOCUMENTS: PART 1 - GENERAL A. Drawings and general provisions of Contract, including General

More information

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE

Addendum #4 NEW LOW HEAD OXYGEN SYSTEM Contractor EXHIBIT T SPECIAL PROVISIONS SECTION METAL SHADE STRUCTURE SECTION 13 34 00 METAL SHADE STRUCTURE PART 1 - GENERAL 1.01 STRUCTURE TYPE A. Structure shall be free standing rigid frame and gable roof with slopes as indicated. Structure shall also include foundation,

More information

ADDENDUM NO. 2 Consisting of 3 pages and Attachments

ADDENDUM NO. 2 Consisting of 3 pages and Attachments 10404-125 Street, Edmonton, AB. T5N 1T2 Tel: 780.455.5975 Fax: 780.454.2397 info@cdyarchitect.com ADDENDUM NO. 2 Consisting of 3 pages and Attachments PROJECT: Maina Centre Ville Phase II, Beaumont, Alberta

More information

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist

CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist CONSTRUCTION DOCUMENTS CHECKLIST for the 2012 Michigan Building Code Including Building Permit Application Checklist This checklist is a convenient reference to the 2012 Michigan Building Code. The checklist

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

ADDENDUM #9 DATE: 1/12/17 TO:

ADDENDUM #9 DATE: 1/12/17 TO: ADDENDUM #9 DATE: 1/12/17 TO: Vince O Brien (Anne Arundel County Public Schools) FROM: Andy Locke (Jacobs Engineering) RE: Arnold Elementary School Replacement, All Bid Packages ADDENDUM #9: Revisions

More information

TITLE: Construction Services for the US-1 South Re-Pump and Booster Pump Station Project

TITLE: Construction Services for the US-1 South Re-Pump and Booster Pump Station Project Procurement Department Bid Office Customer Center 1 st Floor, Room 002 21 W. Church Street Jacksonville, Florida 32202 June 06, 2018 ADDENDUM NUMBER: One (1) TITLE: Construction Services for the US-1 South

More information

ADDENDA #5- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services

ADDENDA #5- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services ADDENDA #5- RFP Sylvania CC building Re-Roof Progressive Design Build for Sylvania Campus CC Building Re-Roof Services Addenda Dated: 01/16/2018 PURPOSE: The purpose of this Addenda #5 is to provide a

More information

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2006 PROPOSITION A BOND PROGRAM 300 SENECA NEW ACADEMIC CAMPUS ADDENDUM NO. 1

SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2006 PROPOSITION A BOND PROGRAM 300 SENECA NEW ACADEMIC CAMPUS ADDENDUM NO. 1 SAN FRANCISCO UNIFIED SCHOOL DISTRICT 2006 PROPOSITION A BOND PROGRAM 300 SENECA NEW ACADEMIC CAMPUS ADDENDUM NO. 1 PROJECT: 300 Seneca New Academic Campus DATE: September 23, 2013 300 Seneca Ave., S.F.,

More information

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED

SECTION ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED SECTION 08350 ELECTRIC FOUR FOLD DOORS MODEL 46 FLAT SHEETED PART 1 GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and

More information

SECTION HOLLOW METALWORK. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION.

SECTION HOLLOW METALWORK. A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. SECTION 081113 PART 1 GENERAL 1.01 GENERAL REQUIREMENTS A. PART A and DIVISION 1 of PART B are hereby made a part of this SECTION. B. Examine all conditions as they exist at the project prior to submitting

More information

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications.

A. The work consists of furnishing a Chiller Noise Reduction System as listed in the specifications. SECTION 32 31 14 PART 1 - GENERAL 1.01 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 1 Specification Sections, apply

More information

APPLICATION AND CERTIFICATE FOR PAYMENT

APPLICATION AND CERTIFICATE FOR PAYMENT AND CERTIFICATE FOR PAYMENT TO OWNER: MASTER TEMPLATE - SAVE PROJECT FILE 1 DATE: 10/5/2012 PERIOD TO: ARCHITECT: PROJECT NO: CONTRACTOR'S FOR PAYMENT Application is made for payment, as shown below, in

More information

ADDENDUM # 1 To: RFP for: Blanco Store Fronts, Lighting & Mechanical Improvements

ADDENDUM # 1 To: RFP for: Blanco Store Fronts, Lighting & Mechanical Improvements 818 S. FLORES ST. SAN ANTONIO, TEXAS 78204 www.saha.org Procurement Department ADDENDUM # 1 To: 1110-909-62-3655 RFP for: Blanco Store Fronts, Lighting & Mechanical Improvements Remove and replace in their

More information

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows:

ADDENDUM NO Refer to Specifications Section Alternates. Clarifications to alternate descriptions are as follows: ADDENDUM NO. 1 TO THE DRAWINGS AND SPECIFICATIONS FOR THE New Dishman-McGinnis Elementary School Bowling Green Independent Schools Bowling Green, Kentucky BG 12-256 RTA 1209 March 11, 2013 To All Plan

More information

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON

MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 440 / 533 WEST MAIN STREET TUPELO, MS / FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON ADDENDUM NUMBER FROM: MCCARTY ARCHITECTS, P.A. POST OFFICE BOX 0 / 533 WEST MAIN STREET TUPELO, MS 3880 / 3880 FOR ANSWERS TO QUESTIONS CONTACT: JUSTIN HARRINGTON PHONE: -8-00 PROJECT: ACADEMIC STUDENT

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

ADDENDUM NO. 3. IFB J Emergency Communication Center Renovation and Addition Project

ADDENDUM NO. 3. IFB J Emergency Communication Center Renovation and Addition Project ADDENDUM NO. 3 DATE: May 26, 2017 INVITATION FOR BID: DATED: May 4, 2017 RECEIPT DATE: May 31, 2017 OPENING DATE: June 1, 2017 SUBJECT: Ladies/Gentlemen: Please take note of the following: Receipt/Opening

More information

Via Internet Posting 14 pages

Via Internet Posting 14 pages Michael Pacholok Director Purchasing and Materials Management Division City Hall, 18 th Floor, West Tower 100 Queen Street West Toronto, Ontario M5H 2N2 Joanne Kehoe Manager Construction Services March

More information

SECTION Coiling Counter Shutters

SECTION Coiling Counter Shutters SECTION 083313 Coiling Counter Shutters PART 1 GENERAL 1.1 SECTION INCLUDES A. Rolling Steel Doors B. Guides and Framing 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry Assemblies: Prepared opening

More information

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS

SECTION COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS SECTION 08620 COMMERCIAL CURB-MOUNT ACRYLIC DOUBLE DOME SKYLIGHTS PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions

More information

ADDENDUM NUMBER TWO (2) DATE: May 1, 2015

ADDENDUM NUMBER TWO (2) DATE: May 1, 2015 ADDENDUM NUMBER TWO (2) DATE: May 1, 2015 PROJECT: FROM: TO: Tenant Improvements for: RELOCATION OF TIME INC. LIFESTYLE GROUP KPS GROUP, INC. 2101 First Avenue North Birmingham, Alabama 35203 All Bidders

More information

SECTION Coiling Counter Shutters

SECTION Coiling Counter Shutters SECTION 08 3313 Coiling Counter Shutters PART 1 GENERAL 1.1 SECTION INCLUDES A. Rolling Steel Doors B. Guides and Framing 1.2 RELATED SECTIONS A. Section 04810 - Unit Masonry Assemblies: Prepared opening

More information

City of Westerville Guide to Commercial Inspections

City of Westerville Guide to Commercial Inspections City of Westerville Guide to Commercial Inspections FOOTINGS - After the excavation, with the form work and any required reinforcing steel in place. All footings shall have loose soil removed, reinforcing

More information

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM

SECTION STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM SECTION 13 34 21 - STRUCTURAL RETROFIT ROOF SUB-FRAMING SYSTEM PART 1 - GENERAL 1.1 DESCRIPTION A. The structural retrofit roof sub-framing system will provide support for a new metal roofing system constructed

More information

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE:

SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: IRC CODE UPDATES TO: RESIDENTIAL BUILDING CONTRACTORS FROM: GARY STABER, BUILDING OFFICIAL SUBJECT: NEW 2000 INTERNATIONAL RESIDENTIAL CODE (IRC) DATE: 6/1/2003 INTERNATIONAL RESIDENTIAL CODE (IRC) APPLICABILITY:

More information

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500

1.2 DEFINITIONS, REFERENCES, AND OVERALL STANDARDS Follow 07500 07721 ROOF ASSEMBLY SUPPORTS FOR ROOFTOP EQUIPMENT ****************************************** SPECIFIER: All roof-related items above or outside the structural roof deck, including such work as blocking,

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport

MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport MPA Project No. L1429-C1 Project Title: Terminal C Enhancements Location: Logan International Airport RESPONSES TO QUESTIONS and/or RFI s Date: 6/1/2018 The attention of Contractors submitting Filed Sub-Bids

More information

SEISMIC RESTRAINT SYSTEM

SEISMIC RESTRAINT SYSTEM 1. GENERAL 1.1. Description: SECTION 16012 SEISMIC RESTRAINT SYSTEM 1.1.1. This specification covers design and installation of seismic bracing and anchorage required for conduit, cable tray, bus duct,

More information

SECTION SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 416 SERIES SECTIONAL STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

SECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS

SECTION SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 424 SERIES SECTIONAL STEEL DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word click on

More information

ADDENDUM # 3 CITY OF CAPE CANAVERAL BID # CITY OF CAPE CANAVERAL WWTP IMPROVEMENTS FOR OXIDATION DITCH REHABILITATION June 24, 2016

ADDENDUM # 3 CITY OF CAPE CANAVERAL BID # CITY OF CAPE CANAVERAL WWTP IMPROVEMENTS FOR OXIDATION DITCH REHABILITATION June 24, 2016 ADDENDUM # CITY OF CAPE CANAVERAL BID #- CITY OF CAPE CANAVERAL WWTP IMPROVEMENTS FOR OXIDATION DITCH REHABILITATION June, All contents of this addendum shall be incorporated into the solicitation documents

More information

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019

QUESTIONS & ANSWERS FOR B SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 QUESTIONS & ANSWERS FOR B1900051 SOUTHWEST SERVICE CENTER BOOKING REMODEL 02/20/2019 Answers to questions: 1) Question: Is the existing slab post tensioned? Answer: No. Existing slab is 4 thick with welded

More information

DALLAS-FORT WORTH INTERNATIONAL AIRPORT

DALLAS-FORT WORTH INTERNATIONAL AIRPORT DALLAS-FORT WORTH INTERNATIONAL AIRPORT ADDENDUM NO. 2 TO THE REQUEST FOR BIDS Contract No. 9500445 Restroom Rehabilitation at Terminal B (Phase 3 & 4) December 20, 2010 THE REQUEST FOR BIDS (RFB) FOR

More information

SECTION AIR OUTLETS AND INLETS

SECTION AIR OUTLETS AND INLETS PART 1 - GENERAL 1.1 DESCRIPTION A. Roof Curbs SECTION 23 37 00 AIR OUTLETS AND INLETS SPEC WRITER NOTE: 1. Delete between //----// if not applicable to project. Also delete any other item or paragraph

More information

HEAVY STEEL CONSTRUCTION

HEAVY STEEL CONSTRUCTION HEAVY STEEL CONSTRUCTION PRE-ENGINEERED PRE ENGINEERED STEEL BUILDINGS Prismatic Constructions Work Shops, Storage Buildings etc. Figure 1 Figure 2 Prismatic steel constructions can be manufactured as

More information

SECTION ROOF MOUNTED ATTIC EXHAUST VENT

SECTION ROOF MOUNTED ATTIC EXHAUST VENT SECTION 07 72 00 ROOF MOUNTED ATTIC EXHAUST VENT **This is a CSI Three-Part Specification using CSI MasterFormat 2004-2010 Section Numbers and Titles. This specification must be edited to suit your particular

More information

CITY OF GRAND RIVERS LIVINGSTON COUNTY, KENTUCKY

CITY OF GRAND RIVERS LIVINGSTON COUNTY, KENTUCKY CONTRACT I CONTRACT II CONTRACT III WASTEWATER TREATMENT PLANT INFLUENT PUMP STATION, FORCE MAIN, AND WATER MAIN EXTENSION WWTP & INFLUENT PUMP STATION ELECTRICAL CITY OF GRAND RIVERS LIVINGSTON COUNTY,

More information

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT

ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT ADDENDUM NO. 3 REQUEST FOR PROPOSALS HANGAR 1610/1612 FIRE SUPPRESSION RETROFIT PROJECT Effective September 6, 2018, Addendum No. 3 (THREE), {Pages 1-7 and the applicable attachment(s)}, is associated

More information

SECTION ACCESS PANELS

SECTION ACCESS PANELS SECTION 08310 ACCESS PANELS PART 1: GENERAL 1.01 RELATED DOCUMENTS Drawings and general provisions of the contract, including supplementary conditions and Division 1 specification sections, apply to this

More information

SECTION NON-STRUCTURAL METAL FRAMING

SECTION NON-STRUCTURAL METAL FRAMING PART 1 - GENERAL 1.1 DESCRIPTION SECTION 09 22 16 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or paragraph not applicable

More information

Summary of Modifications/Changes in this Update

Summary of Modifications/Changes in this Update Summary of Modifications/Changes in this Update This Summary of Changes is for information only. It is not a part of the referenced document, and should not be used for project documentation. U.S. Department

More information

MITTERSILL WARMING HUT

MITTERSILL WARMING HUT STATE OF NEW HAMPSHIRE DEPARTMENT OF RESOURCES AND ECONOMIC DEVELOPMENT DIVISION OF PARKS AND RECREATION PROJECT #: CAP 1786 FRANCONIA NOTCH STATE PARK FRANCONIA, NEW HAMPSHIRE DRAWING LIST: COVER SHEET

More information

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how?

SECTION SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS. Display hidden notes to specifier. (Don't know how? SECTION 08360 SECTIONAL OVERHEAD DOORS 522 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier. (Don't know how? Click Here) PART 1 GENERAL 1.1 SECTION INCLUDES A. Glazed Aluminum

More information

SECTION HVAC GRAVITY VENTILATORS

SECTION HVAC GRAVITY VENTILATORS SECTION 23 37 23 HVAC GRAVITY VENTILATORS PART 1 GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification

More information

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D

BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS ARCHITECTURE, LLC 1827 1 ST AVENUE NORTH, SUITE 104 BIRMINGHAM, ALABAMA 35203 205.321.4122 ADDENDUM NO. 3 PROJECT: BIRMINGHAM CITY SCHOOLS (BCS) OPERATIONAL CENTER COMPLEX: BID PACKAGE D HOSKINS

More information

Nassau County Building Department

Nassau County Building Department July 6, 2018 Nassau County Building Department Inspection Types ALL INSPECTION REQUESTS ARE REQUIRED TO BE INITIATED BY THE PERMIT HOLDER, ALL INSPECTION REQUESTS SHALL SUPPLY THE PERMIT NUMBER FOR EACH

More information

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers.

A. This Section includes ceiling- and wall-mounted diffusers, registers, grilles and louvers. SECTION 23 37 13 - PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general provisions of the Contract, including General and Supplementary Conditions and Division 01 Specification Sections, apply

More information

INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION / SLAB AND SITE WORK

INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION / SLAB AND SITE WORK ADDENDUM 3 TO: FROM: RE: Vendors Christie Hutchinson, Purchasing Director INVITATION TO BID NUMBER ITB/PI-12/13-50 CONSTRUCTION OF CITRUS GERMPLASM INTRODUCTION PROGRAM BUILDING AND GREENHOUSE FOUNDATION

More information

N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System

N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System Version 5.22.13 N-SERIES: NTH2700 SPECIFICATIONS Tubular Composite Top Hung Sliding Door System OPTIONS ARE LISTED IN BOLD, PLEASE MODIFY THESE AREAS AS NEEDED BASED ON YOUR PROJECT CONSULT MANUFACTURER

More information

Grimes Elementary School Renovation September 7, 2010 Houston Independent School District SECTION 102800 - TOILET, BATH, AND LAUNDRY ACCESSORIES PART 1 - GENERAL 1.1 RELATED DOCUMENTS A. Drawings and general

More information

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement

Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement DATE: July 15, 2011 ADDENDUM NUMBER: 2 MODIFYING: Specifications No. 1698 PROJECT: Colorado River Aqueduct Pumping Plants 230 kv Disconnect Switches Replacement BID TIME AND DATE: 2:00 p.m., July 19, 2011

More information

SECTION DUCTS PART 1 GENERAL 1.01 SUMMARY

SECTION DUCTS PART 1 GENERAL 1.01 SUMMARY 1 1 1 1 1 1 1 1 0 1 0 1 SECTION 1 DUCTS PART 1 GENERAL 1.01 SUMMARY A. Section Includes: 1. Duct Materials.. Insulated flexible ducts.. Single wall spiral round ducts.. Ductwork fabrication.. Duct cleaning.

More information

AMBICO Limited Section and DETENTION STEEL DOOR AND FRAME ASSEMBLIES Page 1

AMBICO Limited Section and DETENTION STEEL DOOR AND FRAME ASSEMBLIES Page 1 Page 1 This section includes AMBICO Detention Steel Door and Frame assemblies that can be fire rated or non-rated. This section relies on both the Canadian Steel Door Manufacturers Association (CSDMA.org)

More information

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100

COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 COLLEGE CLASSROOM & DORMITORY SPECIFICATION SECTION 08100 Part 1 General 1.01 Work Included A. The work under this section shall include the furnishing of all items shown on the drawings and as specified,

More information

EAST CENTRAL REGIONAL WATER RECLAMATION FACILITY PROCESS WATER SYSTEM PROJECT

EAST CENTRAL REGIONAL WATER RECLAMATION FACILITY PROCESS WATER SYSTEM PROJECT EAST CENTRAL REGIONAL WATER RECLAMATION FACILITY PROCESS WATER SYSTEM PROJECT Addendum No. 2 Attachment B Contract Document Revisions Specifications: TABLE OF CONTENTS ADDENDUM NO. 2 Attachment B Contract

More information

Steel Doors and Frames 101. Steel Door Institute

Steel Doors and Frames 101. Steel Door Institute Steel Doors and Frames 101 Steel Door Institute www.steeldoor.org This presentation provides general information about steel doors such as nomenclature, fire ratings, cores, and performance levels. This

More information

STANMYRE + NOEL Architects, P.C Preston White Drive, Suite 104 Reston, VA v f

STANMYRE + NOEL Architects, P.C Preston White Drive, Suite 104 Reston, VA v f STANMYRE + NOEL Architects, P.C. 1890 Preston White Drive, Suite 104 Reston, VA 20191 v. 703.471.9350 f. 703.834.1031 info@snarchitects.com S E P T E M B E R 19, 2 0 1 6 ADDENDUM #3 PROJECT: WHITE OAKS

More information

SECTION MISCELLANEOUS METALS

SECTION MISCELLANEOUS METALS PART 1 GENERAL 1.1 WORK OF THIS SECTION A. Contractor shall provide all labor, materials, equipment and incidentals as shown, specified and required to furnish and install all miscellaneous metal fabrications

More information

EVH-660D. Miami-Dade Qualified Wind-Driven Rain Louver. Application and Design. Standard Construction. Options (at additional cost)

EVH-660D. Miami-Dade Qualified Wind-Driven Rain Louver. Application and Design. Standard Construction. Options (at additional cost) Application and Design Miami-Dade Qualified Wind-Driven Rain Louver EVH-0D Florida Product Approval No.: 1785.1 EVH-0D is a Florida Product Approved and Miami-Dade Qualified stationary vertical blade wind

More information

COPYRIGHTED MATERIAL. Contents. 1 Making Buildings 3. 3 Wood Foundations and. Preface to the Sixth Edition xi. Sitework 31

COPYRIGHTED MATERIAL. Contents. 1 Making Buildings 3. 3 Wood Foundations and. Preface to the Sixth Edition xi. Sitework 31 Contents Preface to the Sixth Edition xi 1 Making Buildings 3 Learning to Build 4 Buildings and the Environment 5 The Work of the Design Professional 11 The Work of the Construction Professional 19 Trends

More information

SOLICITATION ADDENDUM NO. 1 RFP THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED.

SOLICITATION ADDENDUM NO. 1 RFP THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION ARE ANNOUNCED. Beaverton School District Capital Program Purchasing 16550 SW Merlo Road, Beaverton, OR 97006 Phone: 503-591-4539 SOLICITATION ADDENDUM NO. 1 RFP 15-0013 THE FOLLOWING CHANGES TO THE ABOVE CITED SOLICITATION

More information

Place & Connect Pumping Stations

Place & Connect Pumping Stations Place & Connect Pumping Stations Flo-Pak Integrated Municipal Pumping Systems www.pattersonpumps.com When Quality Matters Flo-Pak Municipal Packaged Pumping Systems Setting the Bar for Packaged Systems

More information

This Addendum forms part of the Tender Documents and amends the Tender Documents as described below.

This Addendum forms part of the Tender Documents and amends the Tender Documents as described below. BRAMALEA SECONDARY SCHOOL ARCHITECTURAL ADDENDUM NO. 1 ADULT EDUCATION - CLASSROOM & OFFICE RENOVATIONS PEEL DISTRICT SCHOOL BOARD Tender No. L18-4165 February 23, 2018 This Addendum forms part of the

More information

COLLEGE OF STATEN ISLAND

COLLEGE OF STATEN ISLAND SECTION 07415 ALUMINUM PLATE CEILING PANELS PART 1 GENERAL 1.01 SUMMARY A. Section Includes 1. The extent of panel system work is indicated on the drawings and in these specifications. The following specification

More information

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034

Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 Melhart Music Center Modular Music Practice Rooms - E3 Ready Specifications Section 13034 PART 1 - General 1.01 Summary A. Section includes labor, material, equipment, and other considerations required

More information

SECTION CONCRETE ABOVE GROUND FUEL STORAGE

SECTION CONCRETE ABOVE GROUND FUEL STORAGE SECTION 23 13 23 CONCRETE ABOVE GROUND FUEL STORAGE SPEC WRITER NOTES: 1. Use this section only for NCA projects. 2. Delete between //----// if not applicable to project. Also delete any other item or

More information

SECTION TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS. ADD the following sections: Commissioning Requirements...

SECTION TABLE OF CONTENTS DIVISION 1 GENERAL REQUIREMENTS. ADD the following sections: Commissioning Requirements... ADDENDUM NO. 01 PULASKI COUNTY MIDDLE SCHOOL FOR THE PULASKI COUNTY PUBLIC SCHOOLS PULASKI COUNTY, VIRGINIA STATE PROJECT CODE NO. 077-30-00-100 COMM. NO. 16196-00 RRMM ARCHITECTS ROANOKE, VA AUGUST 14,

More information

SECTION SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS

SECTION SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS SECTION 08 36 00 SECTIONAL OVERHEAD DOORS 511 SERIES ALUMINUM SECTIONAL OVERHEAD DOORS Display hidden notes to specifier by using Tools / Options / View / Hidden Text. On newer versions of Microsoft Word

More information

EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER

EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER PATENT PENDING 3900 Dr. Greaves Rd. Kansas City, MO 64030 (816) 761-7476 FAX (816) 765-8955 EME6325D WIND-DRIVEN RAIN RESISTANT STATIONARY LOUVER MIAMI-DADE APPROVED MIAMI-DADE COUNTY, FLORIDA NOTICE OF

More information