STEPHEN F. AUSTIN ELEMENTARY SCHOOL
|
|
- Adela Gibson
- 5 years ago
- Views:
Transcription
1 STEPHEN F. AUSTIN ELEMENTARY SCHOOL
2
3 BUS LANE CAMPUS DATA BUS LANE PORTABLES STEPHEN F. AUSTIN ELEMENTARY SCHOOL 1776 Texas Dr., Weatherford, TX Year Built 1988 No. of Buildings 1 No. of Portables 2 Approx. Total Square Footage Grades Served 61,500 K through 6th PEIMS 583 Original Planning Capacity 645 Building Levels 1 NOTICE: Issues designated as non-compliant or code deficiencies may have become non-compliant or deficient as codes have been updated or changes in the site conditions have progressed into non-compliant conformance. Identification of these deficiencies does not indicate the facility was constructed out of code compliance at the time of actual construction, and declaration of certain items may not warrant immediate action. 1
4 MASTER PLAN COLOR LEGEND Administration Athletics Cafeteria/Kitchen Circulation Fine Arts Computer Lab Library Toilets/Support Spaces Resource 2
5 MASTER PLAN 3
6
7 CIVIL - SITE Introduction This report provides the results of the Civil/Site assessment of the above referenced school performed by Pacheco Koch Consulting Engineers, Inc. (PKCE) The Civil /Site assessment consisted of: 1) a site visit for a visual evaluation; and 2) a meeting between Weatherford ISD faculty members and PKCE staff, focused on the following items: 1. Paving 2. Surface Drainage 3. Accessible Route / Parking 4. Utilities (no subsurface verified during site visit) 5. Erosion Based on observed conditions, recommended improvements for each of the deficiencies identified have been accompanied with estimated quantities and an opinion of probable construction cost, to be used as a budgetary tool. Site Visit: March 17, 2014 On the above date, PKCE personnel visited Stephen F. Austin Elementary to observe the items discussed above. The table below shows each deficiency found, the photograph number, an estimated quantity, a unit cost, and a construction cost estimate, all based on available construction cost data at the time of this assessment. Items not included in this assessment are as follows: design fees, overhead contractor cost including mobilization, bonding, permitting, on-site job office cost, etc Meeting with Weatherford ISD Staff On Tuesday, April 1, 2014, PKCE personnel met with representatives of the School District s Maintenance Department to learn about any known issues that may not be discovered/visible during the site visit and to gain historical/current knowledge of the site. During the meeting, the following Civil/Site issues were brought up for Stephen F. Austin Elementary: Sidewalks around the building have settled, creating tripping hazards, specifically around southwest area of the building. Existing handrails on multiple ramps throughout the site are damaged and need replacing. Installation of perimeter fencing around playground areas is desired. A new sidewalk route from the south drop-off loop west along Washington Drive is desired. 5
8 CIVIL - SITE
9 CIVIL - SITE Sidewalk settlement adjacent to building Sidewalk/Specialty pavers settled at interior courtyard Sidewalk settlement adjacent to building Sidewalk settlement at concrete ramp Surface drainage issues adjacent to building Surface drainage issues in north parking lot 7
10 CIVIL - SITE Surface drainage issues at portable buildings Surface drainage issues adjacent to building Surface drainage issues in north parking lot Erosion Issues at concrete stairs Slope stability/erosion issues Lack of pedestrian route along Washington Drive 8
11 CIVIL - SITE Concrete curb damage Accessible ramp at front entrance Accessible parking space 9
12 CIVIL - SITE SUMMARY OF FINDINGS STEPHEN F. AUSTIN ELEMENTARY Photo # Description Level Approx. Quantity Concrete sidewalk settlement adjacent to building. 1,2,3,4 5,6,7, 8,9 10, Demo Recompact subgrade and install new concrete sidewalk. Demo existing courtyard on west side of building and replace with new concrete courtyard. Surface drainage issues adjacent to building and throughout site parking lots. Install/improve site drainage system. Slope stability/erosion issues Sod affected areas to eliminate further erosion around concrete structures. Lack of pedestrian route along Washington Drive. Install concrete sidewalk. Concrete curb damage. Sawcut and replace affected concrete curbs. 300 SY 300 SY 1 LS 1 LS 1,500 SF 120 SY 150 LF 14 Non-compliant accessible ramp at front entrance. Install ADA compliant curb ramp. 1 EA 15 Accessible parking space violates ADA maximum slope. (Ex. slope =2.5%) Sawcut and install new concrete pavement to achieve maximum allowable slope of 2%. 50 SY ** Playground area fence Install new fence around playground area. 300 LF * An engineer s drainage study and plan is needed to verify the extent of the site drainage system needed to eliminate existing surface drainage issues. The engineer s study will define the exact construction scope for the required improvements. 10
13 CIVIL - SITE ** Installation of a new fence around the playground area was an item discussed with the Weatherford ISD maintenance department at the meeting on April 1, 2014, and has thus been included in this cost estimate exhibit. 11
14
15 BUILDING CONDITION: EXTERIOR 13
16 BUILDING CONDITION: EXTERIOR In this view, the concrete walk has settled and the concrete walk surface is non-compliant. This photo of the wing wall indicates cracks at the exterior brick face. Here, you will notice cracks appearing in the sealant at the control joint. The typical length of control joints in this area are between 18-0 to 20-0 above the window lintel. (The control joint locations are noted on the plan.) This view reveals cracks that were found in the sealant at both sides of the aluminum window at the cafeteria. The typical window size of this window type is 9-0 long by 6-8 in height. The light pattern on this type of window is 3 wide and 3 high, with the lower left and lower right glazing being operable. This photo shows rust build up at the steel lintel beam. (See plan for all locations where this similar condition is noted.) This condition is found at various locations at the Main Entry. There are two areas located at the height of 9-0, two areas at 8-0, and two areas at There are three areas at the Library, where this condition is shown at the height of At the plaster soffit, we noticed damage and overflow extension is missing. 14
17 BUILDING CONDITION: EXTERIOR Here, you will notice cracks appearing in the sealant at the control joint. The typical length of control joints in this area are between 8-0 to 10-0 above the window lintel. (The control joint locations are noted on the plan.) The concrete walk, shown in this photo at the main entry, is damaged and the threshold is non-compliant. This photo indicates where soil erosion has occurred because of drainage toward the building. This picture shows damage at the aluminum window sills. The window size where this damage at the sills occurs is 9-0 long by 6-8 in height. The light pattern on this type of window is 3 wide and 3 high, with the lower left and lower right glazing being operable. The location of this photo is at the Library, and it shows the main window to the Library. We noticed that the mortar joints, at this location, are damaged at the brick face. Here, you will notice cracks appearing in the sealant at the control joint. The typical length of control joints in this area are 5-0 above the window lintel. (The control joint locations are noted on the plan.) 15
18 BUILDING CONDITION: EXTERIOR This ramp is located near the entry. We have two major issues at this location. The issues are as follows: Cracks in the concrete, and the ramp slope is non-compliant. At the porch light fixture, we noticed that birds are nesting above the fixture. We also noticed that the fixture is showing wear and discolored stains. At this location, it is noted that the decorative steel railings are showing wear with chipped paint in certain spots. This photo is located at the courtyard. The exterior wall joint, at the walk, indicates damage in the sealant. The concrete walk at this location is settled and is non-compliant. This location shows cracks in the sealant around the perimeter of the aluminum door and windows. The dimensions of this door window unit are as follows: 9-3 height by 6-0 length by -6-0 height by 3-0 length by -3-0 height. 16
19 BUILDING CONDITION: EXTERIOR This location shows cracks in the sealant around the perimeter of the aluminum window. The dimensions of this window unit are as follows: 6-8 height by 6-0 length. This location shows cracks in the sealant around the perimeter of the aluminum window. The dimensions of this window unit are as follows: 6-8 height by 3-4 length. This location shows cracks in the sealant around the perimeter of the aluminum door with transom unit. The dimensions of this door with transom unit are as follows: 9-2 height by 3-4 length. At the porch stoop edge, we noticed that the sealant at the concrete walk indicated damage and exposed rebar in some areas. At this location, it is noted that the decorative steel railings are showing wear with chipped paint and rust in certain spots. We also noticed that the decorative gate is misaligned. This photo shows soil erosion due to water drainage issues and cracks in brick face at the corner. 17
20 BUILDING CONDITION: EXTERIOR Here, you will notice cracks appearing in the sealant at the control joint. The typical length of control joints in this area are between 18-0 to 20-0 above the window lintel. (The control joint locations are noted on the plan.) The brick face at this corner shows major damage, discoloration of bricks, and soil erosion. The brick face at this corner shows cracks in it. The mow strip, in this photo, is settled along the perimeter. (Mow strips are typically 4 below grade) In this photo, you will observe that the leaves and debris covers the area drains for the water drainage. This photo was taken in the Courtyard area. This location shows cracks in the sealant around the perimeter of the aluminum door with transom unit. At both locations in the courtyard, the lintel length is at
21 BUILDING CONDITION: EXTERIOR This location shows cracks in the sealant around the perimeter of the aluminum door with transom unit. At both locations in the courtyard, the lintel length is at 3-0. This photo indicates cracks near the corner of the exposed grade beam, along with soil erosion. In this view, we noticed that the sealant at the expansion joint is showing major damage in it. (The control joint locations are noted on the plan.) (This is typical at the west elevation.) We noticed that the sealants at each of the control joints are showing major damage. (The control joint locations are noted on the plan.) Here, you will notice cracks and damage appearing in the sealant at the control joint at the Gym wall. The typical length of control joints in this area are between /- long. (The control joint locations are noted on the plan.) This view is the Kitchen exit door. The concrete at the threshold of this exit door is cracked, broken, and chipped. 19
22 BUILDING CONDITION: EXTERIOR Here, you will notice cracks and damage appearing in the sealant at the control joint at the screen wall for mechanical units. (The control joint locations are noted on the plan.) 20
23 BUILDING CONDITION: INTERIOR 21
24 BUILDING CONDITION: INTERIOR Damaged plastic laminate and floor base in high traffic areas of Cafeteria. Damaged tile sill in Cafeteria. Damaged/missing floor base. Stained ceiling tile. Source of leaker should be identified and repaired. Stained carpet finishes in various locations. Cracking of gypsum board finish in select ceiling locations. 22
25 BUILDING CONDITION: INTERIOR Delaminating vinyl wall covering in restroom locations. Non-compliant egress door clearance. Wall nicks and dings in various locations. Damaged plastic laminate and floor base in high traffic areas of Cafeteria. Non-compliant electric water cooler installation Damaged/missing VCT flooring at entry door transitions select locations. 23
26 BUILDING CONDITION: INTERIOR Rusting HVAC grilles in high humidity locations. Damaged plastic laminate finishes. Non-compliant sink installation Damaged floor base and wall finishes in select locations. Discolored/stained tile at HVAC grilles in select locations. Mis-seated exhaust shaft in custodial area. 24
27 BUILDING CONDITION: INTERIOR Damaged wall tile in select locations. Non-compliant sink installation access. Non-compliant sink installation - Pipe Protection. 25
28
29 ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING Stephen F. Austin Elementary was built in This facility does not include a fire sprinkler system. The air conditioning systems consists of single zone and multizone air handling units served by two air-cooled water chilling units and two cast iron hot water boilers. In addition, the building also has rooftop a/c equipment as well as splitsystems a/c equipment. The chillers were replaced in The systems and equipment all seem to be in good working order, but after 25 years of service with most of the equipment, some upgrades are necessary in order to provide continued reliable service. Our recommendations for these upgrades are listed below. Building electrical service is 277/480 volt, 3 phase, 4 wire, 2000 amp main PBS switch, served from power company pad-mounted transformer. The building interior lighting system was retrofitted with T8 lamps in the majority of the building, with the exception being the office and main corridor, and cafeteria addition. These areas utilize T12 type lamps. Light levels in the cafeteria are very low, with the lit space appearing to be too dark. Gym lighting is HID type. The building fire alarm system is equipped with an addressable type manufactured by Notifier. It appears to be in good operating condition. MECHANICAL: Provide new fire sprinkler system throughout building in order to improve life safety. In the gymnasium, replace the existing split system a/c units and gas-fired unit heaters with new rooftop a/c units with gas heat. Thoroughly clean and overhaul all existing air handling units throughout the building. This would include (but not be limited to) cleaning the cooling and heating coils to improve heat transfer and replacing inefficient motors and/or drives. Replace existing chilled and heating water circulating pumps with new. To avoid rusting and premature failure, paint all exposed gas piping on the roof. To avoid shutting down large systems of water or gas service during routine maintenance procedures, install service and isolation valves throughout the building. In 6 to 10 years, replace existing kitchen area rooftop a/c unit with a new, more efficient unit. 10 Year Plan: Replace the existing air-cooled condensing unit sections of the Administration split system a/c units with new, more efficient equipment. 10 Year Plan: As the chillers, boilers and circulating pumps reach the end of their useful lives, replace all such equipment with new, more efficient equipment. ELECTRICAL: Replace remaining T12 type fixtures with T8 type. Replace Cafeteria lighting with new energy saving type to improve lighting output. Provide occupancy sensors in classrooms and offices for automatic lighting shut-off as required by the International Energy Conservation Code (IECC) for effective energy savings. Replace HID lighting in Gym with T5HO fluorescent or LED type for energy savings and east ON-OFF switching. Replace all fire alarm devices throughout building and add horn/strobe lights to all classrooms for code compliance. Provide stage and front of stage lights with all controls. Provide surge protection device (SPD) at main panel. Provide additional parking lot lighting. Replace existing site and wall pack light fixtures with LED type. 27
30 ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING 28
31 ENGINEERING REPORT - MECHANICAL / ELECTRICAL / PLUMBING 1 2 Replace existing light fixtures with more efficient type and provide additional light fixtures. Replace with T8 lamps. 3 4 Replace existing HID light fixtures with T5HO fluorescent or LED type fixtures. Replace all fire alarm devices throughout building. 5 6 Existing chillers installed in Gas piping on roof in need of cleaning/painting. 29
32
33 ENGINEERING REPORT - STRUCTURAL Further Study is recommended of the corrosion of the floor joists and beams in the crawlspace where standing water, a very humid environment, and corrosion was observed. Based on extent of corroded floor framing members, we recommend that corroded elements be sand-blasted, re-painted, and reinforced with carbon strips. Further study is recommended to determine if the unreinforced masonry will have any net axial tension or excessive flexural tension under code required design wind forces, which is not permitted by the code. Retrofitting new structural components may be recommended. Further Study is recommended to determine if the structural unreinforced masonry has cracked behind wall finishes such as interior coverings and exterior veneers due to foundation movement. Repair of such cracks or retrofitting new structural components may be recommended. Repairing all known cracks in all structural unreinforced masonry due to foundation movement is recommended. If any modification to the Unreinforced Masonry is desired, Special Analysis will be required and significant Architectural and Structural limitations may be required. Further study is recommended to determine the design and condition of the connectors between wythes. Installing new connectors may be recommended after study. Further Study is recommended to determine if there is sufficient lateral anchorage at the top of all exterior unreinforced masonry walls that are parallel to roof joists. Installing lateral restraints may be recommended after further study. Further Study is recommended to determine if installation of new bottom chord net uplift horizontal bridging angles along the ends of the steel joist is required. Installing new bottom chord net uplift horizontal bridging angles along the ends of the steel joist is recommended when an opportunity presents itself such as a building remodel. 31
34 ENGINEERING REPORT - STRUCTURAL 32
35 ENGINEERING REPORT - STRUCTURAL Rusted crawl space beam 33
36
37 FOOD SERVICE 35
38 FOOD SERVICE Cold Storage Assembly Poor condition. Cold Storage Assembly Poor condition. Compartment sink present. Convection Oven in poor condition. Steamer Kettle in poor condition. Serving Counters in poor condition. 36
39 FOOD SERVICE Mobile Milk Coolers in poor condition. 37
40
41 SECURITY NOTICE: For the safety and welfare of the faculty, students, and staff, the security portion of the assessment report has been removed from this report. 39
DISTRICT SERVICES BUILDING
DISTRICT SERVICES BUILDING BUILDING DATA DISTRICT SERVICES BUILDING 1100 Longhorn Dr., Weatherford, TX 76086 Year Built 1993 No. of Buildings 1 No. of Portables 0 Approx. Total Square Footage Grades Served
More informationBOWIE LEARNING CENTER
BOWIE LEARNING CENTER Bowie Learning Center BUILDING DATA BOWIE LEARNING CENTER 900 North Elm St., Weatherford, TX 76086 Year Built 1936 No. of Buildings No. of Portables 0 Approx. Total Square Footage
More informationBILL W. WRIGHT ELEMENTARY SCHOOL
BILL W. WRIGHT ELEMENTARY SCHOOL PORTABLES Bill W. Wright Elementary School CAMPUS DATA BILL W. WRIGHT ELEMENTARY SCHOOL 1309 W. Charles St., Weatherford, TX 76086 Year Built 1979 No. of Buildings 1 No.
More informationWHS NINTH GRADE CENTER
WHS NINTH GRADE CENTER CAMPUS DATA WHS NINTH GRADE CENTER 1007 S. Main St., Weatherford, TX 76086 Year Built 1957 No. of Buildings 7 No. of Portables 2 Approx. Total Square Footage 298,458 Grades Served
More informationLake Highlands North Recreation Center Summary
Lake Highlands North Recreation Center Summary Address Building Purpose 9940 White Rock Trail Dallas, TX 75238 Recreation Center Original Year of Construction 1971 Building Area 33,036 SF Inspection Date
More informationChenango Valley Central School District Potential Capital Project BCK-IBI Group Project No October 23, 2017
Chenango Bridge Elementary School Phase 1 Asphalt Pavement Reconstruction Reconstruct asphalt parking located on west side of building including access drive. Sidewalk Replacement Replace cracked sections
More informationMills Elementary School Site Summary
1 Mills Elementary School Site Summary Address 6201 Davis Lane Austin, TX 78749 Number of Permanent Campus Facilities 1 Original Year of Construction 1998 Total Campus Building Area (combined) 81,368 SF
More informationFacilities Feasibility Study Laurence G. Paquin Building Condition Assessment
Summary of Findings The Laurence G. Paquin Building Facility located at 2200 SINCLAIR LANE in Baltimore, Maryland, was built in 1975. It comprises 65,666 gross square feet. The total current deficiencies
More informationFacility Assessment Report, Montgomery Independent School District
NATATORIUM CAMPUS DATA NATATORIUM 22628 Hwy 105 West, Montgomery TX 77356 Year Built 2009 Approx. Total Square Footage Grades Served 30,420 n/a Current Enrollment n/a Building Levels 1 1 MASTER PLAN 2
More informationCARL E. SCHLUTER ELEMENTARY SCHOOL
CARL E. SCHLUTER ELEMENTARY SCHOOL Carl E. Schluter Elementary School Campus Data CARL E. SCHLUTER ELEMENTARY SCHOOL 1220 Mesa Crest Drive, Haslet, Texas 76052 Year Built 2011 Approx. Total Square Footage
More informationNALLE ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1950 BUILDING AREA 83,900 SF CURRENT PROGRAM CAPACITY 460 ENROLLMENT 2008 372 WARD 7 PROPOSED PROGRAM CAPACITY 400 Site Plan NALLE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationExisting Site Aerial Frederick High School Feasibility Study September 5, 2012
Existing Site Aerial Building Developmental History 1981 1966 1939 1977 1978 1955 1966 Exterior Roof: Most of existing roof has multi ply built up roofing. Some areas have gravel ballast, others have cap
More informationCollins Middle School
Contents Collins Middle School...2 General comments, campus capacity, and student demographics:...2 1.0 School Site...4 2.0 Building Systems and Components...5 3.0 Building Safety and Security...19 4.0
More informationHartsville Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 8, 2012 Hartsville Area Schools - Building Evaluations School Name: West Hartsville Elementary Observed By: Cannon/Carter Principal:
More informationThurgood Marshall Recreation Center Summary
Thurgood Marshall Recreation Center Summary Address Building Purpose 5150 Mark Trail Way Dallas, TX 75232 Recreation Center Original Year of Construction 1970 Building Area 21,300 SF Inspection Date August
More informationMADELEY RANCH ELEMENTARY SCHOOL
MADELEY RANCH ELEMENTARY SCHOOL CAMPUS DATA MADELEY RANCH ELEMENTARY SCHOOL 3500 Madeley Ranch Road, Montgomery TX 77356 Year Built 2009 Approx. Total Square Footage Grades Served 94,750 Pre-K - 4 th
More informationDeficiency ID Qty UoM Priority. Concrete Walks Are Damaged And Require Replacement ,000 SF 3
School and Site Level Deficiencies Site Concrete Walks Are Damaged And Require Replacement 5539 4,000 SF 3 Bus drop-off area does not have a canopy. 14005 250 LF 5 Paved Play Requires Recoating And Resurfacing
More informationTimberglen Recreation Center Summary
Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,
More informationDAVIS ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1943 BUILDING AREA 71,100 SF CURRENT PROGRAM CAPACITY 507 ENROLLMENT 2008 227 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan DAVIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-
More informationDeficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2
School and Site Level Deficiencies Site K Play Area Requires Impact Resistant Material 1320 1 Ea. 2 Exterior Basketball Goals Are Damaged And Require Replacement 1322 1 Ea. 4 Bus drop-off area does not
More information2 Main School Building BLDG-124A Building Purpose Building Area Administrative, Classrooms, Cafeteria and Gymnasium 61,905 SF Inspection Date June 28-
1 Metz Elementary School Site Summary Address 84 Robert Martinez Jr. Austin, TX 78702 Number of Permanent Campus Facilities 1 Original Year of Construction 1993 Total Campus Building Area (combined) 61,905
More informationMenchaca Elementary School Site Summary
1 Menchaca Elementary School Site Summary Address 12120 Manchaca Road Austin, TX 78704 Number of Permanent Campus Facilities 1 Original Year of Construction 1975 Total Campus Building Area (combined) 60,104
More informationDarlington Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 2, 2012 Darlington Area Schools - Building Evaluations School Name: Brunson-Dargan Observed By: Creed/Carter Principal: Mrs. Ada O Sindab
More informationFacilities Feasibility Study Frederick Douglass HS Condition Assessment
Summary of Findings The Frederick Douglass HS Facility located at 2301 Gwynns Falls Parkway in Baltimore, Maryland, was built in 1927. It comprises 194,249 gross square feet. The total current deficiencies
More informationGODLEY INTERMEDIATE SCHOOL
GODLEY INTERMEDIATE SCHOOL Facility Profiles Campus Data GODLEY INTERMEDIATE SCHOOL 309 North Pearson, Godley TX, 760 1938, 1965, 1997, 2001, 2009 Year Built Approx. Total Square Footage 91,92 sf Grades
More informationBALLOU SENIOR HIGH SCHOOL
INITIAL YEAR BUILT 1960 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1565 ENROLLMENT 2008 9-12 (1,252) STAY (753) WARD 8 PROPOSED PROGRAM CAPACITY 1200 Site Plan BALLOU - 1 PROPOSED PROGRAM PROFILE
More information1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %
BartelsRode Gymnasium 8/11/ Building Rating System Percent Site: 1.0 Total 0 13 77% Building: 2.1 Building Exterior Elements 0 8 8% 2.2 Accessibility 0 74 74% 2.3 Structural 0 76 76% 2.4 Building Envelope
More information3. 21st Century Learning A. Districtwide Flexible Learning $600,000 Subtotal $600,000
1. Safety and Security A. Additional Cameras District Wide $382,000 B. Interior Locks Upgrades $300,000 C. Tilden Entrance Upgrades $50,000 D. Door and Glass Improvements $500,000 E. Alert Systems $800,000
More informationRAYMOND EDUCATION CAMPUS
INITIAL YEAR BUILT 1924 BUILDING AREA 73,600 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 302 WARD 1 PROPOSED PROGRAM CAPACITY 600 Site Plan RAYMOND - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationBarrington Elementary School Site Summary
1 Barrington Elementary School Site Summary Address 400 Cooper Drive Austin, TX 78753 Number of Permanent Campus Facilities 3 Original Year of Construction 1969 Total Campus Building Area (combined) 79,689
More informationDarlington Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 2, 2012 Darlington Area Schools - Building Evaluations School Name: Pate Elementary School Observed By: Creed/Carter Principal: Grade
More informationAdministration Building Needs Assessment
Town Hall Meeting with the Habersham County Board of Commissioners Administration Building Needs Assessment JUNE 13, 2016 Detailed Evaluation Performed in 2015 Engineering Evaluation Site/Civil Architectural
More informationReilly Elementary School Site Summary
1 Reilly Elementary School Site Summary Address 405 Denson Drive Austin, TX 78752 Number of Permanent Campus Facilities 1 Original Year of Construction 1954 Total Campus Building Area (combined) 41,622
More informationFACILITY COMPONENTS - ELEMENTARY SCHOOL
SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Two stalls fewer than minimum standard. Parking and Access - Service / Delivery 2.0 1.0 0.16 Parking and Access - Staff 1.0 3.0 0.24 Thirty-seven stalls
More informationHartsville Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 8, 2012 Hartsville Area Schools - Building Evaluations School Name: Southside Early Childhood Observed By: Cannon/Carter Principal: Grade
More informationFACILITY COMPONENTS - ELEMENTARY SCHOOL
SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking
More informationFacility Assessment Report, Montgomery Independent School District
ATHLETIC FACILITY CAMPUS DATA ATHLETIC FACILITY 22628 Hwy 105 West, Montgomery TX 77356 1 MASTER PLAN 2 CIVIL - SITE General Existing Conditions and Deficiencies Overall concrete site paving: Good Overall
More informationFacility Improvements
AR-SI-08 CURB RAMP ADDITIONS AR-SI-10 DISCUS THROW MODIFICATIONS Curb ramps needed to provide wheelchair access and to meet ADA requirements. Modifications are needed at the discus throw pad to comply
More informationCorsicana High School
Contents Corsicana High School...2 General comments, campus capacity, and student demographics...2 1.0 School Site...4 2.0 Building Systems and Components...6 3.0 Building Safety and Security...19 4.0
More informationJ. C. THOMPSON ELEMENTARY SCHOOL
J. C. THOMPSON ELEMENTARY SCHOOL J. C. Thompson Elementary School Campus Data J. C. THOMPSON ELEMENTARY SCHOOL 440 Wishbone Lane, Haslet, Texas 76052 Year Built 2011 Approx. Total Square Footage Grades
More informationDr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018
G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake
More informationLOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN
INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS
More informationHILLSIDE ELEMENTARY SCHOOL. Overview: Livingston School District Hillside Elementary School
HILLSIDE ELEMENTARY SCHOOL Overview: The is located at 98 Belmont Drive and consists of a two-story building which has had a number of additions added to it over the years, the latest of which was a two-story
More informationJAMES M. STEELE ACCELERATED HIGH SCHOOL
JAMES M. STEELE ACCELERATED HIGH SCHOOL Campus Data JAMES M. STEELE ACCELERATED HIGH SCHOOL 606 N. Walnut, Roanoke, Texas 76262 Year Built 1992, 2010 Approx. Total Square Footage 55,418 Grades Served
More informationSite Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks
Site Bldg Fiscal Yr System Sub-System Site site 2014/15 Parking Paving Site site 2014/15 Sidewalks Skill Center L 2015/16 Architectural Partitions Site Site 2015/16 Parking Striping Arc Center M 2014/15
More informationDarlington Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 2, 2012 Darlington Area Schools - Building Evaluations School Name: Cain Elementary School Observed By: Creed/Carter Principal: Grade
More informationBoard Work Session Feasibility Study. January 9, 2017
Board Work Session Feasibility Study January 9, 2017 1 Process Staff Input Sessions at all schools What can you tell us about your building, your site, your space? Group collaboration exercise looking
More informationFACILITY COMPONENTS - MIDDLE SCHOOL
SITE AREAS Parking and Access - Buses 2.0 2.0 0.30 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 1.0 3.0 0.22 Four fewer stalls
More informationFrederic Chopin Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationWILKINSON ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1976 BUILDING AREA 144,900 SF CURRENT PROGRAM CAPACITY 508 ENROLLMENT 2008 451 WARD 8 PROPOSED PROGRAM CAPACITY 600 Site Plan WILKINSON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationHartsville Area Schools - Building Evaluations
Darlington County School District Darlington, South Carolina August 8, 2012 Hartsville Area Schools - Building Evaluations School Name: Principal: Grade Levels: Site Size: Student Population: Staff Size:
More informationLASALLE - BACKUS EDUCATION CAMPUS
INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: HS FOR MATH, SCI & ENGINEERING-M, 240 CONVENT AVENUE, New York, 10031 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2017-12-20
More informationADDENDUM 2 - JULY 14, 2015
7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures
More informationTable of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities
Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)
More informationREHABILITATION STANDARDS CHECKLIST
Project Name Date Built Date Last Rehabilitated (If applicable) EXTERIORS REHABILITATION STANDARDS CHECKLIST ROOF Age (Yrs) Poor Fair Good Excellent Roof /Pitch/Flat # of Layers Substrate Material Insulation
More informationPOWELL ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1925 BUILDING AREA 38,500 SF CURRENT PROGRAM CAPACITY 304 ENROLLMENT 2008 319 WARD 4 PROPOSED PROGRAM CAPACITY 325 Site Plan POWELL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-3
More informationHUGHES STADIUM CONTROLLED MAINTENANCE THROUGH 2020 Description of Projects on Facilities Management List September 18, 2014
HUGHES STADIUM CONTROLLED MAINTENANCE THROUGH 2020 Description of Projects on Facilities Management List September 18, 2014 1. Upgrade Video Security and Surveillance Systems - Replace with New a. Existing
More informationSHEPHERD ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1932 BUILDING AREA 79,700 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 355 WARD 4 PROPOSED PROGRAM CAPACITY 400 Site Plan SHEPHERD - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationEvansville Public Schools. Facility Assessment Report January 28, 2 , General Building Data
Evansville Public Schools Facility Assessment Report January 28, 2, 2013 SGN/Wendel Architects, Design Tree Engineering and R.A. Morton Construction Managers were retained by the Evansville Public School
More informationSEATON ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1969 BUILDING AREA 65,000 SF CURRENT PROGRAM CAPACITY 428 ENROLLMENT 2008 280 WARD 2 PROPOSED PROGRAM CAPACITY 325 Site Plan SEATON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5
More informationBuilding Inspection Report
Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941
More information1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %
8/11/ Building Rating System Percent Site: 1.0 Total 0 163 82% Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 92 92% 2.3 Structural 0 91 91% 2.4 Building Envelope 0 84 84% 2. Interior
More informationCOOLIDGE SENIOR HIGH SCHOOL
INITIAL YEAR BUILT 1940 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1240 ENROLLMENT 2008 652 WARD 4 PROPOSED PROGRAM CAPACITY 1100 Site Plan COOLIDGE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationNYC Department of Education
Architectural Inspection Building Assessment Survey 2017-2018 Asset: P.S./I.S. 266 - QUEENS, 74-10 COMMONWEALTH BLVD, New York, 11426 Inspection Id Inspection Type Time In Last Edited SA : Architectural
More informationSAMUEL BECK ELEMENTARY SCHOOL
SAMUEL BECK ELEMENTARY SCHOOL Campus Data SAMUEL BECK ELEMENTARY SCHOOL 401 Parkview Drive, Trophy Club, Texas 76262 Year Built 1998, 2012, 2014 Approx. Total Square Footage 87,032 Grades Served K-5 Nominal
More informationAppendix J - Custom Uniformat for EDU Migration
Appendix J - Custom Uniformat for EDU Migration Nr. MTC Uniformat for VFA.facility Life (Years) Weight (1-100) Out of Scope Cost Y/N 1 A Substructure 150 N 2 A10 Foundations 150 N 3 A1010 Standard Foundations
More informationDelco Activity Center Site Summary
1 Site Summary Address 4601 Pecan Brook Austin, TX 78724 Number of Permanent Campus Facilities 1 Original Year of Construction 2003 Total Campus Building Area (combined) 60,294 SF Introduction The is located
More informationTABLE OF CONTENTS Public Safety Building
DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary
More informationHERITAGE MIDDLE SCHOOL. Overview: Livingston School District Heritage Middle School
HERITAGE MIDDLE SCHOOL Overview: The is located at 20 Foxcroft Drive and consists of a three-story building with Three-Story Classroom and Multi-Purpose Room Additions completed in 2002. The building has
More informationFacilities Feasibility Study Matthew A. Henson ES Condition Assessment
Summary of Findings The Matthew A. Henson ES Facility located at 1600 N. Payson Street in Baltimore, Maryland, was built in 1964. It comprises 75,228 gross square feet. The total current deficiencies for
More information1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %
8/11/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 82 82% 2.3 Structural 0 7 7% 2.4 Building Envelope 0 47 47% 2. Interior
More informationDIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT
TABLE OF CONTENTS INTRODUCTORY INFORMATION Section 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Invitation
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: LAFAYETTE ACADEMIES - BRONX, 1231 LAFAYETTE AVENUE, New York, 10474 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2018-01-02
More informationSPACE TYPE: OUTSIDE PARKING (STRUCTURE)
SPACE TYPE: OUTSIDE PARKING (STRUCTURE) Construction Criteria The unit costs for Outside Parking (Structure) space types are based on the construction quality and design features in the following table.
More informationBARNARD ELEMENTARY SCHOOL
INITIAL YEAR BUILT 2002 BUILDING AREA 67,000 SF CURRENT PROGRAM CAPACITY 520 ENROLLMENT 2008 329 WARD 4 PROPOSED PROGRAM CAPACITY 450 Site Plan BARNARD - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationCharles H Wacker Elementary School
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationPiping system (steam, hot water, chilled water system) including pipe and duct insulation needs replacement.
NW Corridor Transit Planning Union Station Existing Conditions Technical Memorandum (Physical and Operational Assessments) Executive Summary Capitol Region Council of Governments Prepared in cooperation
More informationFacility Improvements
CA-SI-01 ACCESSIBLE PARKING STALL ADDITIONS CA-SI-07 BASEBALL & SOFTBALL INFIELD IMPROVEMENTS Additional parking stalls and signage needed for disabled individuals and to meet ADA requirements. Installation
More informationProperty Condition Assessment
Property Condition Assessment Pewaukee, WI 53072 Inspection Date: 1/6/15 Prepared For: Report Number: Prepared By: Shamrock Building Inspection Consultants LLC N29 W29951 Shel-Mar Dr. Pewaukee, WI 53072
More informationNYC Department of Education
Architectural Inspection Building Assessment Survey 2017-2018 Asset: MIDWOOD HS ADDITION - BROOKLYN, 2886 BEDFORD AVENUE, New York, 11210 Inspection Id Inspection Type Time In Last Edited SA : Architectural
More informationDRAFT. Govalle Elementary School Site Summary Valley Hill Circle Austin, TX Number of Permanent Campus Facilities 2
1 Govalle Elementary School Site Summary Address 3601 Valley Hill Circle Austin, TX 78741 Number of Permanent Campus Facilities 2 Original Year of Construction Total Campus Building Area (combined) 1930-1931
More informationVelma F Thomas Early Childhood Center
Facility Assessment Summary This report summarizes the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationArchitect and Engineer: Friar Associates inc.
Architect and Engineer: Friar Associates inc. BACKGROUND In June, after soliciting and interviewing several professional firms, Friar Associates was hired to perform an Existing Conditions Survey and Facilities
More informationNYC Department of Education
Building Assessment Survey 2017-2018 Asset: SAINT FRANCIS COLLEGE - BROOKLYN, 180 REMSEN STREET, New York, 11201 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior 2018-02-05
More informationWATKINS ELEMENTARY SCHOOL
INITIAL YEAR BUILT 1962 BUILDING AREA 69,300 SF CURRENT PROGRAM CAPACITY 578 ENROLLMENT 2008 550 WARD 6 PROPOSED PROGRAM CAPACITY 550 Site Plan WATKINS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION
More informationAlabama Home Inspections
Cover Page Property Inspection Report 1000 Sample Dr., Sampletown USA Inspection prepared for: Report Sample Inspection Date: 1/21/2010 Time: 400pm Size: Approx. 2,200sf Weather: Cloudy 62 Inspector: Bobby
More informationAmos Alonzo Stagg Elementary School 7424 S Morgan St Chicago, IL 60621
2 S Morgan St Chicago, IL 21 Facility Assessment Report This report contains a summary of the results from the facility assessment completed on the date noted in the document footer below. This report
More informationWalter Q Gresham Elementary School
Facility Assessment Detail This report contains the findings of a facility assessment completed on the date noted in the document footer below. Assessors rate each facility feature and system by visual
More informationNYC Department of Education
Architectural Inspection Building Assessment Survey 2017-2018 Asset: I.S. 323 (OLD IS 180) - QUEENS, 320 BEACH 104 STREET, New York, 11694 Inspection Id Inspection Type Time In Last Edited SA : Architectural
More informationCHANCELLORS RESIDENCE ANNUAL INSPECTION REPORT BY BOT GOVERNANCE COMMITTEE MEMBERS A. ITEMS FROM PREVIOUS SITE INSPECTIONS-INCOMPLETE OR ON HOLD
TAB D-2b CHANCELLORS RESIDENCE ANNUAL INSPECTION REPORT BY BOT GOVERNANCE COMMITTEE MEMBERS August 5, 2015 Items added to Inspection performed by Facilities Management Team of July 16, 2015 The care of
More informationHERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW
HERMIT S REST GRAND CANYON NATIONAL PARK BUILDING CODE REVIEW 27 September 2007 prepared by: J. CHRIS EVANS ARCHITECT 3220 E. Terra Alta Blvd. No. 9 Tucson, Arizona 85716 520.319.8835 evansarch@hotmail.com
More informationSimcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Warnica PS, 9283
5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1964 3,035 Page 1 of 27 1. Architectural / Structural & Site Exec Summary Warnica Public School is a one storey structure of masonry construction
More informationNYC Department of Education
Architectural Inspection Building Assessment Survey 2017-2018 Asset: P.S. 52 - STATEN ISLAND, 450 BUEL AVENUE, New York, 10305 Inspection Id Inspection Type Time In Last Edited SA : Architectural - Senior
More informationFacility Improvements
AL-SI-02 ASPHALT PLAY AREA UPGRADE AL-SI-09 CURB RAMP ADDITIONS Asphalt improvements needed around building and playshed to provide a safe play area. Curb ramps needed to provide wheelchair access and
More informationOverbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements %
8/13/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 64 64% 2.2 Accessibility 0 66 66% 2.3 Structural 0 77 77% 2.4 Building Envelope 0 4 4% 2. Interior
More informationHarry Stone Recreation Center Summary
Harry Stone Recreation Center Summary Address Building Purpose 2400 Millmar Drive Dallas, TX 75228 Recreation Center Original Year of Construction 1957 (Expansion 2013) Building Area 22,281 SF Inspection
More informationK.B. Polk Recreation Center Summary
K.B. Polk Recreation Center Summary Address Building Purpose 6801 Roper Street Dallas, TX 75209 Recreation Center Original Year of Construction 1988 Building Area 14,305 SF Inspection Date July 20, 2016
More informationSimcoe County District School Board. 5yr Condition Assessment 2006/07 to 2010/11. Hillcrest PS (Barrie), 9205
5yr Condition Assessment 2006/07 to 2010/11 Construction Year Area 1951 3,813 Page 1 of 25 1. Architectural / Structural & Site Exec Summary Hillcrest Public School is a two storey structure of masonry
More informationPriority 1 Maintenance Projects Total Investment Needed: $54,875,317. Elementary Schools
Priority 1 Maintenance Projects Total Investment Needed: $54,875,317 Appleton Elementary Elementary Schools Total Priority 1 Need: $1,513,280 * Replace roofing in 3 areas * Add air handling units in cafeteria,
More information