1 March 15, 2012 Bremerton School District No. 100-C Study and Survey Prepared by:

2 Bremerton School District No. 100-C Study and Survey 1 Prepared by NAC Architecture March 15, 2012

3 2 Bremerton School District Study and Survey March 15, 2012

4 Executive Summary The Bremerton School District had a Study and Survey performed on the facilities in the District. This Study and Survey included a full review of the existing facilities, development of a long range plan that included community and District participants who identified facility needs and education direction. Facilities A 2006 Bond Issue provided additions to the High School and Middle School sites. The existing buildings on these sites were not modernized and are aging. The elementary school buildings are also aging. Most of these buildings will need capital investment to prolong the life of the building and improve the educational setting. The original High School building, West Hills Elementary and Kitsap Lake Elementary are currently eligible for Capital Assistance from the State while the other buildings are not eligible until after The aging condition means that many of the building systems are near the end of their usable life and require more resources to keep the buildings operational. The District will need to consider full modernization and/or new-in-lieu replacement of most of the inventory within the next 15 years. Long Range Educational Plan The Bremerton School District prides itself on meeting the needs of ALL students. The School District recognizes that there is wonderful diversity within their population and that many of the students in the District learn in different ways. To meet the needs of all students, the District has made an effort to provide options and support to meet different students needs in different ways. 3 Input from educators, administrators, community members, facilities personnel, and others provided input to frame the Long Range Plan. The District s Long Range Educational Plan is to continue this focus on providing options and support for students. These options range from Special Education, to programs for Highly Capable Students, to alternative programs such as a Spanish Immersion Elementary, a Montessori School, and a STEM (Science, Technology, Engineering and Math) focused school, in addition to providing comprehensive schools for all K-12 learners. It is important that the facilities in the District support this long range plan. The educational options and special education services provided at the schools require space and put a higher demand on building area and flexibility of the spaces to serve the programmatic needs. As a result the District does not have any surplus space and some programs need more space to better meet the educational needs. Demographic Data The general demographic information indicates that the population is generally stable and outlook indicates current stability with the possibility of modest growth. There is reason to belive that the educational options will increase enrollment at a faster rate than the predicted population growth.

5 Ability to Provide Capital Funds The Bremerton School District meets the statutory and fiscal requirements for eligibility to compete for state assistance for construction projects. The Bremerton School District currently has available bonding capacity. It is noted that the average home value is lower in this District compared with others in the Puget Sound region; accordingly capital bond and levy efforts need to be sensitive to the fact that Bremerton voters are required to accept a higher percentage of taxes on their homes to raise an equivalent amount of capital funds compared to wealthier districts. Housing Emergency and Racial Imbalance There is not a housing emergency nor is there a racial imbalance. New and/or Additions to Existing School Facilities New building area is needed to properly accommodate the growing STEM school and Montessori school at West Hills STEM Academy. The current enrollment levels and OSPI area per student ratios indicate that this addition is not eligible for State Capital assistance funds. Modernization or Replacement of Existing School Facilities The aging inventory of buildings in the District will need to be addressed over the next years with Modernizations and New-in-Lieu construction. These projects are expected to be eligible for state funding assistance. 4 Additionally, the District has some support buildings that do not house direct instruction that need to be replaced. Also there are several small works projects that need to be addressed to provide the needed functionality and/or extend the life of buildings that are not otherwise targeted for modernization in the near term. These projects are not expected to receive state funding assistance. None of the proposed work is a result of defered maintenance, the District has remained active in the upkeep of their buildings. Time Line The time line provided in the Study and Survey reflects a pace that makes sense for facility needs; funding will need to be addressed for these items. The time line is dependent on funding which will require School Board action and approval by the voters. Underutilized School Facilities in Neighboring Districts The neighboring districts do not have underutilized facilities that would be appropriate for the needs of the Bremerton School District. Bremerton School District Study and Survey March 15, 2012

6 Table of Contents Executive Summary PRELIMINARIES Table of Contents Board Approval Form 1066 CHAPTER 1 Inventory and Area Analysis of Existing Facilities School Addresses School District Map Inventory and Area Analysis Bremerton High School Renaissance High School Mountain View Middle School Armin Jahr Elementary School Crownhill Elementary School Kitsap Lake Elementary School Naval Avenue Early Learning Center View Ridge Elementary School West Hills S.T.E.M. Academy West Sound Technical Skills Center Administration Building Consolidated Facilities Child Nutritional Services Center CHAPTER 2 Long-Range Educational Plan CHAPTER 3 Demographic Data CHAPTER 4 Ability to Provide Capital Funding Support CHAPTER 5 Existence of a Housing Emergency CHAPTER 6 Racial Balance or Imbalance CHAPTER 7 Type and Extent of New and/or Additions to Existing Facilities CHAPTER 8 Cost Benefi t Analysis for Modernization or Replacement of Existing School Facilities CHAPTER 9 Estimated Capital Cost to Restore Major Facility Systems Due to Deferred Maintenance CHAPTER 10 Time Line CHAPTER 11 Inventory of Unused or Underutilized School Facilities in Neighboring Districts CHAPTER 12 Need to Adjust School Attendance Area

7 6 Bremerton School District Study and Survey March 15, 2012

8 Chapter 1 Inventory and Area Analysis (1) An inventory and area analysis of existing school facilities within the District, a description of the types and kinds of systems and subsystems used in those facilities and their physical condition. 7

9 8 Bremerton School District Study and Survey March 15, 2012

10 School Addresses Bremerton School District #100-C 134 Marion Avenue North Phone: (360) Bremerton, WA Fax: (360) Schools Bremerton High School Phone: (360) th Street Fax: (360) Bremerton, WA Renaissance High School Phone: (360) st Street Fax: (360) Bremerton, WA Mountain View Middle School (7-8) Phone: (360) Perry Avenue Fax: (360) Bremerton, WA Mountain View Middle School (Annex) Phone: (360) Perry Avenue Fax: (360) Bremerton, WA Armin Jahr Elementary School Phone: (360) Dibb Street Fax: (360) Bremerton, WA Crownhill Elementary School Phone: (360) Rocky Point Road NW Fax: (360) Bremerton, WA Kitsap Lake Elementary School Phone: (360) Carr Boulevard Fax: (360) Bremerton, WA Naval Avenue Early Learning Center Phone: (360) Olympic Avenue Fax: (360) Bremerton, WA 98312

11 View Ridge Elementary School Phone: (360) Spruce Street Fax: (360) Bremerton, WA West Hills S.T.E.M. Academy Phone: (360) National Avenue South Fax: (360) Bremerton, WA West Sound Technical Skills Center Phone: (360) National Avenue North Fax: (360) Bremerton, WA Educational Support Facilities Administration Building Phone: (360) st Street Fax: (360) Bremerton, WA Consolidated Facilities Phone: (360) Bruenn Avenue Fax: (360) Bremerton, WA Child Nutritional Services Center Phone: (360) East 30th Street Fax: (360) Bremerton, WA Bremerton School District Study and Survey March 15, 2012

12 School District Map Bremerton High School 2. Renaissance High School 3. Child Nutritional Services Center 4. Mountain View Middle School 5. Armin Jahr Elementary School 6. Crownhill Elementary School 7. Kitsap Lake Elementary School 8. Naval Avenue Early Learning Center 9. View Ridge Elementary School 10. West Hills S.T.E.M. Academy 11. West Sound Technical Skills Center 12. Administration Building 13. Consolidated Facilities

13 12 Capacity Acres Bldg Rating Year(s) Built Students FTE 11/2010 Portable Classrooms Site Address OSPI Area Classrooms Portable Area Grade Level School/Facility Bremerton High School 9-12 Main Building th Street 193, Addition 27, Auto Shop 1300 High Avenue 5, 's P 604 & 605 1,800 2 P Drawbridge 4,600 4 Totals 227, , ,722 1, (Auto Shop) Renaissance Alternative High School st Street P 1 & 2 1,800 2 P 3 & 4 1,800 2 P 5 & 6 1,800 2 P 7 & 8 1,800 2 P 9 & 10 1,800 2 Totals 9, N/A 2002 TOTAL HS Area 227,338 Mountain View Middle School 6-8 Main Building 2400 Perry Avenue 98, th Grade Building 2442 Perry Avenue 38, P 3,600 4 Totals 137, , , TOTAL MS Area 137,519 Armin Jahr Elementary School K Dibb Street Main Building 34, P 24 & 25 1,800 2 P 26 & 27 1,800 2 P P 29 & 30 1,800 2 Totals 34, , Addition 1993 Add & Mod Crownhill Elementary School K Rocky Point Road Main Building 47, P 1,800 2 Totals 47, , Kitsap Lake Elementary School K Carr Boulevard Main Building 48, P 1,800 2 Totals 48, , Naval Avenue Early Learning Center PS Olympic Avenue Main Building 37, P 19 & 20 1,800 2 P 24 & 25 1,800 2 P 37 & 38 1,800 2 Boys & Girls Club 1,800 2 Totals 37, , Add & Mod Bremerton School District Study and Survey March 15, 2012

14 Capacity Acres Bldg Rating Year(s) Built Students FTE 11/2010 Portable Classrooms Site Address OSPI Area Classrooms Portable Area Grade Level School/Facility View Ridge Elementary School K Spruce Avenue Main Building 37, P 21 & 22 1,800 2 P P P 25 & 26 1,800 2 P 27 & 28 1,800 2 P 29 & 30 1,800 2 Totals 37, , Addition 1967 Addition 1994 Add & Mod West Hills S.T.E.M. Academy PS South National Avenue Main Building 48, KCR 1, Totals 48, , TOTAL Elementary Area 255,175 TOTAL K-12 Area 620,032 West Sound Technical Skills Center - Regional National Avenue Main Building 70, PCC 1,800 1 Totals 70, , Administration Building N/A st Street 31,500 N/A N/A N/A N/A N/A Consolidated Facilities N/A 200 Bruenn Avenue 40,100 N/A N/A N/A N/A N/A N/A 1300 East 30th Street 136,359 Currently off roles 1, Child Nutritional Services Center (old Junior High building) TOTAL Other Area 278,650 13

15 14 Bremerton School District Study and Survey March 15, 2012

16 Bremerton High School 15 Aerial Photo

17 16 Bremerton School District Study and Survey March 15, 2012

18 A. General Facility Basic Information Bremerton High School Name Address th Street Bremerton, WA Academic Grade Levels 9-12 Area of Site Tax Parcels ; ; ; ; Building Area (to date) 227,338 Number of Buildings 3 (HS, physical ed, auto shop) Year Built 1988 Modernizations and 2006 addition (27,985) Additions, Date and (Sq Ft) Total number of classrooms 93 Capacity/Current Enrollment 1,671/1,722 B. Site The high school is sited at the south end of the property. Six tennis courts sit to the northwest of the school and a track/football fi eld and bleachers are situated at the northeast side of the property. There are two large rectangular practice fi elds adjacent the school building and the football fi eld. C. Exterior Walls Split faced structural concrete block construction. 17 D. Roof Concrete tile roof over metal decking with metal trusses. E. Storm Water Control City storm water. F. Mechanical System Boiler with large central air handlers for each fl oor and large area. The auditorium is air conditioned with a heat pump. G. Fuel Source Gas. H. Controls ATS. I. Water City water.

19 J. Electrical Schedule 26. K. Security System Auto shop only has Mountain Alarm. L. Intercom System Dimensional. M. Clocks With intercom. N. Fire Alarm Edwards. 18 Bremerton School District Study and Survey March 15, 2012

20 BREMERTON HIGH SCHOOL SITE 19

21 20 BREMERTON HIGH SCHOOL Bremerton School District Study and Survey March 15, 2012

22 21

23 22 Bremerton School District Study and Survey March 15, 2012

24 Area Calculations for: Bremerton High School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals First Floor Academic Wing 1 37,529 Second Floor Academic Wing 1 41,595 Third Floor Academic Wing 1 37,529 Auditorium/Stage 1 15,855 Gym/Music/Commons First Floor 1 27,210 Gym/Music/Commons Second Floor 1 34,235 Auto Shop 1 5,400 Vocational Ed Building 1 1, Additions: Choir, Media, Commons Extension, Fitness Center 1 27, ,338 23

25 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: Bremerton High School (1988 buidling) Building Name: Main Building Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: High School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 0.92 A1010 Standard Foundation 87% 0.92 A20 Walls 0.00 A2020 Walls for subgrade enclosure 90% 0.00 A40 Slabs on Grade 1.88 A4010 Standard Slabs on Grade 90% 1.88 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.86 A6010 Building Subdrainage 90% 0.86 B10 Superstructure B1010 Floor Construction 90% 6.82 B1020 Roof Construction 47% 2.76 B1080 Stairs 90% 0.44 B20 Exterior Vertical Enclosures 9.67 B2010 Exterior Walls 72% 5.57 B2020 Exterior Windows 86% 3.94 B2050 Exterior Doors and Grilles 33% 0.12 B2070 Exterior Louvers and Vents 90% 0.05 B30 Exterior Horizontal Enclosures 2.19 B3010 Roofing 39% 1.52 B3020 Roof Appurtenances 75% 0.19 B3060 Horizontal Openings/Penetrations 60% 0.02 B3080 Overhead Exterior Enclosures 60% 0.45 C10 Interior Construction 8.31 C1010 Interior Partitions 90% 4.28 C1020 Interior Windows 90% 1.80 C1030 Interior Doors 45% 0.54 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction 90% 0.00 C1070 Suspended Ceiling Const. 30% 1.65 C20 Interior Finishes 7.13 C2010 Wall Finishes 72% 1.73 C2020 Interior Fabrications 90% 0.09 C2030 Flooring 90% 4.86 C2040 Stair Finishes 90% 0.36 Bremerton School District Study and Survey March 15, 2012

26 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 48% 0.10 D10 Conveying 0.50 D1010 Vertical Conveying Systems 99% 0.50 D20 Plumbing Fixtures 5.42 D2010 Domestic Water Distribution 91% 3.59 D2020 Sanitary Drainage 90% 1.74 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air Not Rated Not Rated D30 HVAC D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 60% 2.34 D3030 Cooling Systems 90% D3050 Facility HVAC Dist. System 60% 0.12 D3060 Ventilation 60% 0.06 D40 Fire Protection 2.29 D4010 Fires Suppression 100% 2.28 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 8.41 D5010 Facility Power Generation 90% 0.01 D5020 Electrical Service and Distribution 90% 0.90 D5030 General Purpose Electrical Power 90% 0.76 D5040 Lighting 86% 6.75 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.67 D7010 Access Control and Intrusion Defection 60% 0.30 D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 93% 0.19 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 2.32 E1010 Vehicle and Pedestrian Equipment 90% 0.09 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 90% 1.03 E1070 Entertainment and Recreational Equipment 90% 0.27 E1090 Other Equipment 90% 0.67 E20 Furnishings 0.66 E2010 Fixed Furnishings 60% 0.60 E2050 Movable Furnishings 60%

27 26 Building Condition Assessment Scoring Form Bremerton School District Bremerton High School (1988 buidling) Main Building Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. High School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories boiler room and some other small small walls A1010 Standard Foundation 87% Cracks & Separation x % Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure 90% Cracks & Separation x N/A % Drainage x N/A % Vegetation x N/A 0.1 9% Water Penetration x N/A % A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % Settling x % Bremerton School District Study and Survey March 15, 2012

28 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories heavy tile roof needs evaluation; concern for long term roof structure structural block walls some water problems requiring the wall to be sealed installed in 1987 installed in 1987 and cannot get parts for door hardware a lot of damaged tile throughout all areas of the roof. Flat roof area is also failing. B1010 Floor Construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 47% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 3% Soft spots, swelling or settling x 0.1 6% Structural damage x % B1080 Stairs 90% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 72% Water Penetration x 0.3 9% Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 86% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 33% Hinges x 0.2 6% Locks x % Door x % Closers x 0.1 3% Windows & Grills x 0.1 6% Weather stripping x 0.1 3% B2070 Exterior Louvers and Vents 90% Structural damage x % Screens x % Components secure x % B3010 Roofing 39% Safety systems x 0.1 9% Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % 27

29 28 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories entry and other areas are showing wear Cracks, separations, damaged or missing materials, weather sealant, etc. x 0.4 0% B3020 Roof Appurtenances 75% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 60% Structural damage (ducts, chimneys, etc.) x 0.1 6% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 60% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 45% Locks x 0.3 9% Closers x 0.2 6% Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 90% hardware failing and no parts available Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 90% Levelness x N/A % Soft spots, swelling or settling x N/A % Structural damage x N/A % Bremerton School District Study and Survey March 15, 2012

30 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some bent supprots and water damage wearing installed in 1988 C1070 Suspended Ceiling Const. 30% Levelness x % Components secure x 0.3 9% Structural damage (sagging, separation, breakage. etc.) x 0.3 9% Water Damage x % C2010 Wall Finishes 72% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Sealant x % C2040 Stair Finishes 90% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 48% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 99% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 91% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% No abrasive nosing or contrasting color 29

31 30 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories in shops area only; and fire system works as designed 25 year old system continues to operate, but requires regular maintenance and repair In library computer area and new addition to main buidling Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air Not Rated Compressor 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.3 Not Rated D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 60% Heating Unit x % Controls x % Supply Air x 0.1 6% D3030 Cooling Systems 90% Cooling Unit x % Controls x % Supply Air x 0.1 9% D3050 Facility HVAC Dist. System 60% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 60% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % Components secure x % Bremerton School District Study and Survey March 15, 2012

32 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories only emergency panel is powered by this unit t 8's installed 2010 Aging VOIP system; components failing said to be unsupported in 3 4 years D5010 Facility Power Generation 90% Test schedule x % Maintenance schedule x % Generator unit x % Controls x % D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 86% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection 60% Components x % Distribution x % Controls x 0.1 6% still working on a card system 31

33 32 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories as requested by the principal Edwards panel difficult to program and fix gates work D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 93% Components x 0.1 6% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x % Controls x % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 90% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 90% General equipment condition x % Functionality x % E1090 Other Equipment 90% General equipment condition x % Functionality x % E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 60% General furnishing condition x % Functionality x % starting to show wear Bremerton School District Study and Survey March 15, 2012

34 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: Bremerton High School New Additions (2007) Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Junior/Senior High School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 1.33 A1010 Standard Foundation 100% 1.33 A20 Walls 0.00 A2020 Walls for subgrade enclosure 100% 0.00 A40 Slabs on Grade 2.04 A4010 Standard Slabs on Grade 100% 2.04 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.72 A6010 Building Subdrainage 90% 0.72 B10 Superstructure B1010 Floor Construction 90% 9.11 B1020 Roof Construction 100% 4.12 B1080 Stairs Not Rated Not Rated B20 Exterior Vertical Enclosures B2010 Exterior Walls 100% 8.67 B2020 Exterior Windows 100% 3.94 B2050 Exterior Doors and Grilles 100% 0.42 B2070 Exterior Louvers and Vents 100% 0.05 B30 Exterior Horizontal Enclosures 4.88 B3010 Roofing 100% 3.86 B3020 Roof Appurtenances 100% 0.25 B3060 Horizontal Openings/Penetrations 100% 0.02 B3080 Overhead Exterior Enclosures 100% 0.75 C10 Interior Construction C1010 Interior Partitions 100% 4.35 C1020 Interior Windows 100% 1.00 C1030 Interior Doors 100% 1.10 C1040 Interior Grilles and Grates 100% 0.05 C1060 Raised floor construction N/A N/A C1070 Suspended Ceiling Const. 100% 5.39 C20 Interior Finishes C2010 Wall Finishes 100% 3.51 C2020 Interior Fabrications 100% 0.10 C2030 Flooring 100% 7.35 C2040 Stair Finishes Not Rated Not Rated 33

35 OSPI Building Condition Assessment Summary Form 34 Component Component Score BCA Score C2050 Ceiling Finishes 100% 0.20 D10 Conveying 0.00 D1010 Vertical Conveying Systems Not Rated Not Rated D20 Plumbing Fixtures 6.75 D2010 Domestic Water Distribution 100% 4.47 D2020 Sanitary Drainage 100% 2.13 D2030 Building Support Plumbing Systems 100% 0.10 D2050 General Services Compressed Air 100% 0.05 D30 HVAC 6.41 D3010 Facility Fuel Systems 100% 0.01 D3020 Heating Systems 100% 5.90 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 100% 0.30 D3060 Ventilation 100% 0.20 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 100% 1.00 D5030 General Purpose Electrical Power 100% 1.34 D5040 Lighting 100% 8.39 D60 Communication 1.52 D6010 Data Communications 100% 0.50 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.38 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 99% 0.20 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 2.17 E1010 Vehicle and Pedestrian Equipment 90% 0.09 E1030 Commercial Equipment 100% 0.30 E1040 Institutional Equipment 100% 1.14 E1070 Entertainment and Recreational Equipment Not Rated Not Rated E1090 Other Equipment 100% 0.64 E20 Furnishings 1.60 E2010 Fixed Furnishings 100% 1.50 E2050 Movable Furnishings 100% 0.10 Bremerton School District Study and Survey March 15, 2012

36 Building Condition Assessment Scoring Form Bremerton School District Bremerton High School New Additions (2007) Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Junior/Senior High School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories partial buried wall on one side of building A1010 Standard Foundation 100% Cracks & Separation x % Drainage x % Vegetation x % Water Leaks x % A2020 Walls for subgrade enclosure 100% Cracks & Separation x N/A % Drainage x N/A % Vegetation x N/A % Water Penetration x N/A % A4010 Standard Slabs on Grade 100% Levelness x % Soft spots, swelling or settling x % Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % 35

37 36 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Settling x % B1010 Floor Construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 100% Water Penetration x % Levelness of ridges, eaves, gables, etc. x % Soft spots, swelling or settling x % Structural damage x % B1080 Stairs Not Rated Structural damage 0.5 Not Rated Settling 0.25 Not Rated Components secure 0.25 Not Rated B2010 Exterior Walls 100% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 100% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 100% Hinges x % Locks x % Door x % Closers x % Windows & Grills x % Weather stripping x % B2070 Exterior Louvers and Vents 100% Structural damage x % Screens x % Components secure x % B3010 Roofing 100% Safety systems x % Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % Bremerton School District Study and Survey March 15, 2012

38 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 100% Structural damage x % Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 100% Structural damage (ducts, chimneys, etc.) x % Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 100% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 100% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 100% Window insulation failure x % Structural damage x % C1030 Interior Doors 100% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x % C1040 Interior Grilles and Grates 100% Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A 37

39 38 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories C1070 Suspended Ceiling Const. 100% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 100% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 100% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 100% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x % Structural damage x % Sealant x % C2040 Stair Finishes Not Rated Structural Damage 0.5 Not Rated Settling 0.25 Not Rated Components secure 0.25 Not Rated C2050 Ceiling Finishes 100% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x % Structural damage x % Penetrations x % D1010 Vertical Conveying Systems Not Rated Inspections Current 0.9 Not Rated Aesthetics 0.05 Not Rated Functionality 0.05 Not Rated D2010 Domestic Water Distribution 100% Pressure x % Water quality x % Leakage x % Bremerton School District Study and Survey March 15, 2012

40 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Fixtures x % Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 100% Flow x % Vents x % Traps x % Clean outs x % D2030 Building Support Plumbing Systems 100% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 100% Compressor x % Distribution x % Controls x % D3010 Facility Fuel Systems 100% Distribution x % Controls x % D3020 Heating Systems 100% Heating Unit x % Controls x % Supply Air x % D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 100% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 100% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % 39

41 40 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Many green features Aging VOIP system; componenets failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 100% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 100% Branch panels x % Branch wiring x % D5040 Lighting 100% Fixtures x % Switches, wiring x % Controls x % Coverage x % D6010 Data Communications 100% Components x % Distribution x % Controls x % Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated tied into main buidling system tied into the main buidling system Bremerton School District Study and Survey March 15, 2012

42 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories tied into the main buidling system part of the main buidling Edwards panel which is difficult to maintain and change Uses the main buidling system Controls 0.1 Not Rated D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 99% Components x 0.1 9% Distribution x % Controls x % Up to Date Inspection x % Coverage x % D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x % Controls x % E1030 Commercial Equipment 100% General equipment condition x % Functionality x % E1040 Institutional Equipment 100% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment Not Rated General equipment condition 0.75 Not Rated Functionality 0.25 Not Rated E1090 Other Equipment 100% General equipment condition x % Functionality x % E2010 Fixed Furnishings 100% General furnishing condition x % Functionality x % E2050 Movable Furnishings 100% General furnishing condition x % Functionality x % grat science labs 41

43 Building Condition Assessment Summary Form School District: Bremerton School District 42 Facility Name: Bremerton High School Auto Shop Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: High School Single Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 2.04 A1010 Standard Foundation 51% 2.04 A20 Walls 0.00 A2020 Walls for subgrade enclosure 51% 0.00 A40 Slabs on Grade 2.84 A4010 Standard Slabs on Grade 63% 2.84 A4040 Pits and Bases 60% 0.00 A60 Building Subdrainage 0.72 A6010 Building Subdrainage 60% 0.72 B10 Superstructure 3.71 B1010 Floor Construction 60% 0.00 B1020 Roof Construction 57% 3.71 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures 3.81 B2010 Exterior Walls 35% 2.83 B2020 Exterior Windows 18% 0.83 B2050 Exterior Doors and Grilles 30% 0.12 B2070 Exterior Louvers and Vents 68% 0.03 B30 Exterior Horizontal Enclosures 1.69 B3010 Roofing 33% 1.49 B3020 Roof Appurtenances 72% 0.18 B3060 Horizontal Openings/Penetrations 60% 0.02 B3080 Overhead Exterior Enclosures Not Rated Not Rated C10 Interior Construction 8.41 C1010 Interior Partitions 90% 4.50 C1020 Interior Windows 75% 1.50 C1030 Interior Doors 60% 0.73 C1040 Interior Grilles and Grates 74% 0.04 C1060 Raised floor construction N/A N/A C1070 Suspended Ceiling Const. 30% 1.65 C20 Interior Finishes 6.10 C2010 Wall Finishes 47% 1.16 C2020 Interior Fabrications 60% 0.06 C2030 Flooring 81% 4.78 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

44 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 48% 0.10 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures 5.76 D2010 Domestic Water Distribution 91% 3.89 D2020 Sanitary Drainage 90% 1.74 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air 90% 0.05 D30 HVAC 2.47 D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 60% 2.34 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 30% 0.06 D3060 Ventilation 60% 0.06 D40 Fire Protection 2.61 D4010 Fires Suppression 100% 2.60 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 7.80 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 60% 0.69 D5030 General Purpose Electrical Power 60% 0.60 D5040 Lighting 83% 6.51 D60 Communication 1.44 D6010 Data Communications 84% 0.42 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.49 D7010 Access Control and Intrusion Defection 60% 0.30 D7030 Electronic Surveillance Not Rated Not Rated D7050 Detection and Alarm 93% 0.19 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 2.32 E1010 Vehicle and Pedestrian Equipment 90% 0.09 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 90% 1.03 E1070 Entertainment and Recreational Equipment 90% 0.27 E1090 Other Equipment 90% 0.67 E20 Furnishings 0.66 E2010 Fixed Furnishings 60% 0.60 E2050 Movable Furnishings 60%

45 44 Building Condition Assessment Scoring Form Bremerton School District Bremerton High School Auto Shop Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. High School Single Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories 1940's building built for transit company A1010 Standard Foundation 51% Cracks & Separation x 0.3 9% Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure 51% Cracks & Separation x N/A 0.3 9% Drainage x N/A % Vegetation x N/A 0.1 6% Water Penetration x N/A % A4010 Standard Slabs on Grade 63% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases 60% Settling x N/A % Water Penetration x N/A % Structural damage x N/A % A6010 Building Subdrainage 60% Drainage x % Membrane integrity x % Settling x % Pit for servicing cars Bremerton School District Study and Survey March 15, 2012

46 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Asphalt shingle roof not leaking brick walls uninsulated single pane with orginal wood frames B1010 Floor Construction 60% Levelness x N/A % Soft spots, swelling or settling x N/A % Structural damage x N/A % B1020 Roof Construction 57% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 3% Soft spots, swelling or settling x 0.1 6% Structural damage x % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 35% Water Penetration x 0.3 9% Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 18% Water Penetration x 0.3 9% Weather stripping x % Window insulation failure x 0.4 0% Structural damage x % B2050 Exterior Doors and Grilles 30% Hinges x 0.2 6% Locks x % Door x % Closers x 0.1 3% Windows & Grills x 0.1 3% Weather stripping x 0.1 3% B2070 Exterior Louvers and Vents 68% Structural damage x % Screens x % Components secure x % B3010 Roofing 33% Safety systems x 0.1 3% Slopes and runoffs x % Getting very old and used 1986 roof Gutters, downspouts, scuppers, roof drains, etc. x % 45

47 46 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories none Cracks, separations, damaged or missing materials, weather sealant, etc. x 0.4 0% B3020 Roof Appurtenances 72% Structural damage x 0.1 6% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 60% Structural damage (ducts, chimneys, etc.) x 0.1 6% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures Not Rated Support structure 0.35 Not Rated Components secure 0.15 Not Rated Coverings 0.5 Not Rated C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 75% Window insulation failure x % Structural damage x % C1030 Interior Doors 60% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 74% Installed by maintenance over the years Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A Bremerton School District Study and Survey March 15, 2012

48 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some bent supprots and water damage painted block and brick C1070 Suspended Ceiling Const. 30% Levelness x % Components secure x 0.3 9% Structural damage (sagging, separation, breakage. etc.) x 0.3 9% Water Damage x % C2010 Wall Finishes 47% Water Damage x 0.3 9% Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 60% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 81% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 48% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 91% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% 47

49 48 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories in shop area new boilers with the old heating boxes and distribution Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x % Distribution x % Controls x % D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 60% Heating Unit x % Controls x % Supply Air x 0.1 6% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 30% Supply & Return x 0.3 9% Ducting/Piping x 0.3 9% Controls x % D3060 Ventilation 60% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % Components secure x % Old heating boxes and disitribution Bremerton School District Study and Survey March 15, 2012

50 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Old system t 8's installed 2010 Aging VOIP system; components failing said to be unsupported in 3 4 years D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 60% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 60% Branch panels x % Branch wiring x % D5040 Lighting 83% Fixtures x % Switches, wiring x 0.1 6% Controls x % Coverage x % D6010 Data Communications 84% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection 60% Components x % Distribution x % Controls x 0.1 6% Sonitol 49

51 50 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Edwards panel difficult to program and fix gates work D7030 Electronic Surveillance Not Rated Components 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated Coverage 0.2 Not Rated D7050 Detection and Alarm 93% Components x 0.1 6% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x % Controls x % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 90% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 90% General equipment condition x % Functionality x % E1090 Other Equipment 90% General equipment condition x % Functionality x % E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 60% General furnishing condition x % Functionality x % lifts have been replaced as needed starting to show wear Bremerton School District Study and Survey March 15, 2012

52 Renaissance High School 51 Aerial Photo

53 52 Bremerton School District Study and Survey March 15, 2012

54 A. General - Facility Basic Information Name Address st Street Bremerton, WA Academic Grade Levels Area of Site 4.3 Tax Parcels Building Area to date 9,000 Number of Buildings 5 portables Year Built 2002 Modernizations and N/A Additions, Date and (Sq Ft) Total number of classrooms 10 Capacity/Enrollment XXX/136 Renaissance High School B. Site Renaissance High School consists of fi ve double portables situated around a central courtyard. The School shares its property with the Administration Building. Directly north of the portables there is a long grassy expanse, reaching to the far north property line. Adjacent the east property line is a narrow greenbelt separating a community track and fi eld. C. Exterior Walls Wood frame double portable classrooms with temporary foundations. Wood panel siding, 53 D. Roof Asphalt shingle roof E. Storm Water Control City storm F. Mechanical System About half are strip heating with A/C the rest have heat pumps G. Fuel Source Electric H. Controls Honeywell programmable thermostats

55 I. Water City water J. Electrical Schedule 24 meter at each portable K. Security System Sonitrol L. Intercom System none M. Clocks none N. Fire Alarm Edwards 54 Bremerton School District Study and Survey March 15, 2012

56 RENAISSANCE HIGH SCHOOL SITE 55

57 Area Calculations for: Renaissance High School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals 1/2 Classrooms (2) 1 1,800 3/4 Classrooms (2) 1 1,800 5/6 Classrooms (2) 1 1,800 7/8 Classrooms (2) 1 1,800 9/10 Classrooms (2) 1 1,800 9, Bremerton School District Study and Survey March 15, 2012

58 Mountain View Middle School 57 Aerial Photo

59 58 Bremerton School District Study and Survey March 15, 2012

60 A. General - Facility Basic Information Name Address 2400 Perry Avenue Bremerton, WA Academic Grade Levels 6-8 Area of Site Tax Parcels Building Area to date 137,519 Number of Buildings 2 Year Built 1993 (Main Building) Modernizations and 2008 Addition (6th Grade Building) (38,951) Additions, (Date and Sq Ft) Total number of classrooms 57 Capacity/Enrollment 900/881 Mountain View Middle School B. Site Mountain View is surrounded on the north and east sides by three separate fi elds all at different elevations. To the south east is a soccer/football fi eld, in the northeast corner are two baseball diamonds and directly to the north are two more baseball diamonds (totally six). A clump of trees separates the two northern fi elds and a narrow string of trees lines the length of the east property line, separating the fi elds from a residential zone. C. Exterior Walls Both buildings are steel frame with metal stud walls. The gym area is tilt up concrete construct. The main/older building is brick exterior and the newer building is partial brick with metal siding. D. Roof Main building has metal roof with the insulation between the metal roof and the supporting metal pan deck. The new building has asphalt shingle roofi ng 59 E. Storm Water Control All drain into the city storm water system around the school. The storm detention pond that has an overfl ow that drains into county system at times F. Mechanical System Hydronic heat pump system with a heat pump for each room area. There are 2 multi-step electric boilers to provide heat and a cooling tower for cooling in the main building and two gas fi red boilers and a cooling tower for the newer building. G. Fuel Source Electric only for main building, Gas heating for the newer building. H. Controls ATS controls for both buidings

61 I. Water City water J. Electrical Main building is schedule 43 and the newer building is schedule 25 K. Security System none L. Intercom System Electrocom M. Clocks With intercom N. Fire Alarm Edwards in new building and Simplex in older builiding. 60 Bremerton School District Study and Survey March 15, 2012

62 MOUNTAIN VIEW MIDDLE SCHOOL SITE 61

63 62 MOUNTAIN VIEW MIDDLE SCHOOL First Floor Plan Bremerton School District Study and Survey March 15, 2012

64 MOUNTAIN VIEW MIDDLE SCHOOL Second Floor Plan 63

65 Area Calculations for: Mountain View Middle School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals Main Building First Floor 1 60,847 Main Building Second Floor 1 37,721 6th Grade Building First Floor 1 27,222 6th Grade Building Second Floor 1 11, , Bremerton School District Study and Survey March 15, 2012

66 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: Mountain View Middle School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Middle/Junior High School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 1.16 A1010 Standard Foundation 87% 1.16 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 1.84 A4010 Standard Slabs on Grade 90% 1.84 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.72 A6010 Building Subdrainage 90% 0.72 B10 Superstructure B1010 Floor Construction 90% 9.11 B1020 Roof Construction 80% 3.28 B1080 Stairs 83% 0.78 B20 Exterior Vertical Enclosures 8.37 B2010 Exterior Walls 72% 6.24 B2020 Exterior Windows 47% 1.83 B2050 Exterior Doors and Grilles 60% 0.25 B2070 Exterior Louvers and Vents 83% 0.04 B30 Exterior Horizontal Enclosures 3.24 B3010 Roofing 63% 2.43 B3020 Roof Appurtenances 90% 0.23 B3060 Horizontal Openings/Penetrations 83% 0.02 B3080 Overhead Exterior Enclosures 75% 0.56 C10 Interior Construction 9.97 C1010 Interior Partitions 90% 3.92 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 60% 0.66 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction 90% 0.00 C1070 Suspended Ceiling Const. 83% 4.45 C20 Interior Finishes 8.81 C2010 Wall Finishes 81% 2.84 C2020 Interior Fabrications 60% 0.06 C2030 Flooring 74% 5.40 C2040 Stair Finishes 83%

67 OSPI Building Condition Assessment Summary Form 66 Component Component Score BCA Score C2050 Ceiling Finishes 86% 0.17 D10 Conveying 0.57 D1010 Vertical Conveying Systems 98% 0.57 D20 Plumbing Fixtures 6.03 D2010 Domestic Water Distribution 90% 4.02 D2020 Sanitary Drainage 90% 1.92 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air Not Rated Not Rated D30 HVAC D3010 Facility Fuel Systems Not Rated Not Rated D3020 Heating Systems 90% 5.31 D3030 Cooling Systems 90% 4.50 D3050 Facility HVAC Dist. System 81% 0.24 D3060 Ventilation 81% 0.16 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.29 D5010 Facility Power Generation 90% 0.01 D5020 Electrical Service and Distribution 90% 0.90 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 86% 7.17 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.35 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 84% 0.17 D7050 Detection and Alarm 90% 0.18 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 1.67 E1010 Vehicle and Pedestrian Equipment 90% 0.00 E1030 Commercial Equipment 68% 0.20 E1040 Institutional Equipment 68% 0.77 E1070 Entertainment and Recreational Equipment 68% 0.20 E1090 Other Equipment 68% 0.50 E20 Furnishings 1.42 E2010 Fixed Furnishings 90% 1.35 E2050 Movable Furnishings 68% 0.07 Bremerton School District Study and Survey March 15, 2012

68 Building Condition Assessment Scoring Form Bremerton School District Mountain View Middle School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Middle/Junior High School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories A1010 Standard Foundation 87% Cracks & Separation x % Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % 67

69 68 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some waterproplems along earthquake joints brick surface needs to be sealed; concerns for water infiltration due to prior repairs and vapor barrier weathering stripping is poor and cannot be found for replacing Settling x % B1010 Floor Construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 80% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 9% Soft spots, swelling or settling x 0.1 9% Structural damage x % B1080 Stairs 83% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 72% Water Penetration x 0.3 9% Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 47% Water Penetration x 0.3 9% Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 60% Hinges x % Locks x % Door x % Closers x 0.1 6% Windows & Grills x 0.1 6% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 83% Structural damage x % Screens x % Components secure x % B3010 Roofing 63% Safety systems x 0.1 6% Slopes and runoffs x % sealant and flashing is failing in places Gutters, downspouts, scuppers, roof drains, etc. x % Bremerton School District Study and Survey March 15, 2012

70 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 90% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 83% Structural damage (ducts, chimneys, etc.) x 0.1 9% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 75% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 60% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 90% wire glass for fire rating Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 90% Levelness x N/A % Soft spots, swelling or settling x N/A % Structural damage x N/A % 69

71 70 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories wearing carpet becoming a tripping hazard C1070 Suspended Ceiling Const. 83% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 81% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 60% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 74% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Sealant x % C2040 Stair Finishes 83% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 98% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 90% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% Bremerton School District Study and Survey March 15, 2012

72 OSPI Building Condition Evaluation Form 12/28/201 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories all electric building cooling tower; recently replaced motor, coils aging Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air Not Rated Compressor 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.3 Not Rated D3010 Facility Fuel Systems Not Rated Distribution 0.5 Not Rated Controls 0.5 Not Rated D3020 Heating Systems 90% Heating Unit x % Controls x % Supply Air x 0.1 9% D3030 Cooling Systems 90% Cooling Unit x % Controls x % Supply Air x 0.1 9% D3050 Facility HVAC Dist. System 81% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 81% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % occupancy sensors in rooms 71

73 72 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories t 8's; no occupancy sensor for lights, no daylight switching Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation 90% Test schedule x % Maintenance schedule x % Generator unit x % Controls x % D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 86% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Bremerton School District Study and Survey March 15, 2012

74 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories aging panel, hard to program Controls 0.1 Not Rated D7030 Electronic Surveillance 84% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 90% Components x 0.1 3% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x N/A % Controls x N/A % E1030 Commercial Equipment 68% General equipment condition x % Functionality x % E1040 Institutional Equipment 68% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 68% General equipment condition x % Functionality x % E1090 Other Equipment 68% General equipment condition x % Functionality x % E2010 Fixed Furnishings 90% General furnishing condition x x % Functionality x % E2050 Movable Furnishings 68% General furnishing condition x % Functionality x % 73

75 Building Condition Assessment Summary Form School District: Bremerton School District 74 Facility Name: Mountain View Sixth School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Middle/Junior High School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 1.28 A1010 Standard Foundation 96% 1.28 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 1.62 A4010 Standard Slabs on Grade 80% 1.62 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.80 A6010 Building Subdrainage 100% 0.80 B10 Superstructure B1010 Floor Construction 100% B1020 Roof Construction 100% 4.12 B1080 Stairs 100% 0.94 B20 Exterior Vertical Enclosures B2010 Exterior Walls 100% 8.67 B2020 Exterior Windows 100% 3.94 B2050 Exterior Doors and Grilles 87% 0.37 B2070 Exterior Louvers and Vents 100% 0.05 B30 Exterior Horizontal Enclosures 4.13 B3010 Roofing 100% 3.86 B3020 Roof Appurtenances 100% 0.25 B3060 Horizontal Openings/Penetrations 100% 0.02 B3080 Overhead Exterior Enclosures Not Rated Not Rated C10 Interior Construction C1010 Interior Partitions 100% 4.35 C1020 Interior Windows 100% 1.00 C1030 Interior Doors 100% 1.10 C1040 Interior Grilles and Grates 100% 0.05 C1060 Raised floor construction 100% 0.00 C1070 Suspended Ceiling Const. 99% 5.31 C20 Interior Finishes C2010 Wall Finishes 90% 3.16 C2020 Interior Fabrications 99% 0.10 C2030 Flooring 94% 6.91 C2040 Stair Finishes 100% 0.40 Bremerton School District Study and Survey March 15, 2012

76 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 100% 0.20 D10 Conveying 0.58 D1010 Vertical Conveying Systems 100% 0.58 D20 Plumbing Fixtures 6.75 D2010 Domestic Water Distribution 100% 4.47 D2020 Sanitary Drainage 100% 2.13 D2030 Building Support Plumbing Systems 100% 0.10 D2050 General Services Compressed Air 100% 0.05 D30 HVAC D3010 Facility Fuel Systems 100% 0.01 D3020 Heating Systems 100% 5.90 D3030 Cooling Systems 100% 5.00 D3050 Facility HVAC Dist. System 100% 0.30 D3060 Ventilation 100% 0.20 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical D5010 Facility Power Generation 100% 0.01 D5020 Electrical Service and Distribution 100% 1.00 D5030 General Purpose Electrical Power 100% 1.34 D5040 Lighting 100% 8.39 D60 Communication 1.54 D6010 Data Communications 100% 0.50 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 100% 0.20 D70 Electronic Safety and Security 0.36 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 90% 0.18 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 1.57 E1010 Vehicle and Pedestrian Equipment N/A N/A E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 90% 1.03 E1070 Entertainment and Recreational Equipment 90% 0.27 E1090 Other Equipment Not Rated Not Rated E20 Furnishings 1.60 E2010 Fixed Furnishings 100% 1.50 E2050 Movable Furnishings 100%

77 76 Building Condition Assessment Scoring Form Bremerton School District Mountain View Sixth School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Middle/Junior High School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories building openned in Jan 2008 some settlement in the gym and other areas that are causing some concern A1010 Standard Foundation 96% Cracks & Separation x % Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 80% Levelness x % Soft spots, swelling or settling x 0.1 3% Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 100% Drainage x % Membrane integrity x % Bremerton School District Study and Survey March 15, 2012

78 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories automatic handicap closer is easily damaged by students causing the need for constant repair Settling x % B1010 Floor Construction 100% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 100% Water Penetration x % Levelness of ridges, eaves, gables, etc. x % Soft spots, swelling or settling x % Structural damage x % B1080 Stairs 100% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 100% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 100% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 87% Hinges x % Locks x % Door x % Closers x 0.1 6% Windows & Grills x 0.1 9% Weather stripping x 0.1 9% B2070 Exterior Louvers and Vents 100% Structural damage x % Screens x % Components secure x % B3010 Roofing 100% Safety systems x % Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % 77

79 78 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 100% Structural damage x % Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 100% Structural damage (ducts, chimneys, etc.) x % Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures Not Rated Support structure 0.35 Not Rated Components secure 0.15 Not Rated Coverings 0.5 Not Rated C1010 Interior Partitions 100% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 100% Window insulation failure x % Structural damage x % C1030 Interior Doors 100% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x % C1040 Interior Grilles and Grates 100% Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 100% Levelness x N/A % Soft spots, swelling or settling x N/A % Structural damage x N/A % Bremerton School District Study and Survey March 15, 2012

80 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories telegraphing slab cracks C1070 Suspended Ceiling Const. 99% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 99% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 94% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x % Structural damage x % Sealant x % C2040 Stair Finishes 100% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 100% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x % Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 100% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 100% Pressure x % Water quality x % Leakage x % 79

81 80 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories fire system only Fixtures x % Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 100% Flow x % Vents x % Traps x % Clean outs x % D2030 Building Support Plumbing Systems 100% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 100% Compressor x % Distribution x % Controls x % D3010 Facility Fuel Systems 100% Distribution x % Controls x % D3020 Heating Systems 100% Heating Unit x % Controls x % Supply Air x % D3030 Cooling Systems 100% Cooling Unit x % Controls x % Supply Air x % D3050 Facility HVAC Dist. System 100% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 100% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % Bremerton School District Study and Survey March 15, 2012

82 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation 100% Test schedule x % Maintenance schedule x % Generator unit x % Controls x % D5020 Electrical Service and Distribution 100% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 100% Branch panels x % Branch wiring x % D5040 Lighting 100% Fixtures x % Switches, wiring x % Controls x % Coverage x % D6010 Data Communications 100% Components x % Distribution x % Controls x % Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 100% Components x % Distribution x % Controls x % D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated 81

83 82 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories rated with main building Controls 0.1 Not Rated D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 90% Components x 0.1 9% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment N/A Components N/A 0.75 N/A Controls N/A 0.25 N/A E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 90% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 90% General equipment condition x % Functionality x % E1090 Other Equipment Not Rated General equipment condition 0.75 Not Rated Functionality 0.25 Not Rated E2010 Fixed Furnishings 100% General furnishing condition x % Functionality x % E2050 Movable Furnishings 100% General furnishing condition x % Functionality x % Bremerton School District Study and Survey March 15, 2012

84 Armin Jahr Elementary School 83 Aerial Photo

85 84 Bremerton School District Study and Survey March 15, 2012

86 A. General - Facility Basic Information Armin Jahr Elementary School Name Address 800 Dibb Street Bremerton, WA Academic Grade Levels K-5 Area of Site Tax Parcels Building Area to date 34,895 Number of Buildings 2 Year Built 1968 Modernizations and 1987 Addition (2,097), 1993 (13,282) Modernization & Addition Additions, (Date and Sq Ft) Total number of classrooms 24 Capacity/Enrollment 481/369 B. Site Armin Jahr is surrounded by dense woods to the north and west sides, and in the southwest corner of the property. A playground with play structure exists along the northwest length of the building. Immediately northwest of the playgrounds is a large, irregular shaped fi eld outlined by the woodlands. C. Exterior Walls Wood frame with brick exterior 85 D. Roof Metal roof on metal trusses over an old fl at roof E. Storm Water Control City water F. Mechanical System Boiler and cooling tower with hydronic water loop to heat pumps for each room to heat and cool building has A/C G. Fuel Source Electric H. Controls ATS I. Water City water

87 J. Electrical Schedule 43 K. Security System None L. Intercom System Electricom M. Clocks With intercom N. Fire Alarm Edwards 86 Bremerton School District Study and Survey March 15, 2012

88 ARMIN JAHR ELEMENTARY SCHOOL SITE 87

89 ARMIN JAHR ELEMENTARY SCHOOL Bremerton School District Study and Survey March 15, 2012

90 Area Calculations for: Armin Jahr Elementary School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals 1 Classroom Building 1 15,772 2 Gymnasium 1 2, Addition 1 2, Classroom Addition 1 12,382 5 Covered Play ,895 89

91 Building Condition Assessment Summary Form School District: Bremerton School District 90 Facility Name: Armin Jahr Elementary School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Single Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 3.19 A1010 Standard Foundation 83% 3.19 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 3.66 A4010 Standard Slabs on Grade 90% 3.66 A4040 Pits and Bases N/A N/A A60 Building Subdrainage 0.72 A6010 Building Subdrainage 90% 0.72 B10 Superstructure 2.23 B1010 Floor Construction N/A N/A B1020 Roof Construction 77% 2.23 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures B2010 Exterior Walls 86% 7.52 B2020 Exterior Windows 65% 2.47 B2050 Exterior Doors and Grilles 50% 0.24 B2070 Exterior Louvers and Vents 60% 0.03 B30 Exterior Horizontal Enclosures 4.63 B3010 Roofing 63% 3.88 B3020 Roof Appurtenances 83% 0.21 B3060 Horizontal Openings/Penetrations 68% 0.01 B3080 Overhead Exterior Enclosures 71% 0.53 C10 Interior Construction 9.66 C1010 Interior Partitions 90% 3.48 C1020 Interior Windows 75% 0.75 C1030 Interior Doors 45% 0.54 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction Not Rated Not Rated C1070 Suspended Ceiling Const. 90% 4.85 C20 Interior Finishes 7.33 C2010 Wall Finishes 81% 2.68 C2020 Interior Fabrications 81% 0.08 C2030 Flooring 78% 4.41 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

92 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 83% 0.17 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures D2010 Domestic Water Distribution 87% 7.33 D2020 Sanitary Drainage 90% 2.70 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air N/A N/A D30 HVAC D3010 Facility Fuel Systems Not Rated Not Rated D3020 Heating Systems 71% 7.66 D3030 Cooling Systems 71% 3.53 D3050 Facility HVAC Dist. System 81% 0.24 D3060 Ventilation 69% 0.14 D40 Fire Protection 2.34 D4010 Fires Suppression 90% 2.33 D4030 Fire Suppression Specialties 90% 0.01 D50 Electrical 9.36 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 1.03 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 86% 7.13 D60 Communication 1.13 D6010 Data Communications 71% 0.35 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 60% 0.36 D6060 Distributed Comm/Monitoring 60% 0.12 D70 Electronic Safety and Security 0.31 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 71% 0.14 D7050 Detection and Alarm 85% 0.17 D80 Integrated Automation 0.07 D8010 Integrated Automation Facility Controls 68% 0.07 E10 Equipment 0.90 E1010 Vehicle and Pedestrian Equipment 60% 0.00 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 60% 0.07 E1070 Entertainment and Recreational Equipment 60% 0.06 E1090 Other Equipment 68% 0.50 E20 Furnishings 1.08 E2010 Fixed Furnishings 60% 1.02 E2050 Movable Furnishings 60%

93 92 Building Condition Assessment Scoring Form Bremerton School District Armin Jahr Elementary School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Single Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Pavement around the building with pretty good drainage in most areas slab in good shape A1010 Standard Foundation 83% Cracks & Separation X % Drainage X % Vegetation X 0.1 9% Water Leaks X % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases N/A Settling N/A 0.3 N/A Water Penetration N/A 0.3 N/A Structural damage N/A 0.4 N/A A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % None No signs of moisture on the floor Bremerton School District Study and Survey March 15, 2012

94 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Pitched metal roof installed in 80s over original flat roof. Metal roof is not built to resist shear. No structural damage has occurred yet. no insulation, no structural deck at roof plane None except to attic Most walls built in the 60's out of masonry, stucco and shotcrete, and in fair to good shape Metal framed window installed in 70's and double pane with fairly good protection capability The weather stripping and the dooors are showing signs of use. Most of the other components are changed as they fail. New metal roof is doing good. The gutter sealants are failing. Settling x % B1010 Floor Construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A B1020 Roof Construction 77% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 9% Soft spots, swelling or settling x 0.1 9% Structural damage x % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 86% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 65% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 50% Hinges x % Locks x % Door x % Closers x 0.1 3% Windows & Grills x 0.1 9% Weather stripping x 0.1 3% B2070 Exterior Louvers and Vents 60% Structural damage x % Screens x % Components secure x % B3010 Roofing 63% Safety systems x 0.1 6% Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. X % 93

95 94 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Reworked in 1994 and only flashings to the roof are starting to cause concern Some seals are starting to fail some of the cover walk area shows signs of needing attention wire glass does not meet current safety and fire codes Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 83% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 68% Structural damage (ducts, chimneys, etc.) x 0.1 9% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 71% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 75% Window insulation failure x % Structural damage x % C1030 Interior Doors 45% Locks x 0.3 9% Closers x 0.2 6% Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 90% Redone in 1994 and in good shape. installed in 1994 None Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction Not Rated Levelness 0.25 Not Rated Soft spots, swelling or settling 0.3 Not Rated Structural damage 0.45 Not Rated Bremerton School District Study and Survey March 15, 2012

96 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Overall as installed in 1994 in pretty good shape but used showing signs of wear showing signs of wear C1070 Suspended Ceiling Const. 90% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 81% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 81% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 78% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 83% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 87% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% None 95

97 96 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories for dry sprinkler only None all electric building installed in 1994 hydronic heat pump system electric boiler, working as designed hydrinic system, cooling tower replaced 2009, some compressors and motors replaced as they fail some damage over the years, controls updated twice, filters changed and belts checked 3 times a year could use more cleaning and maintenace, controlled by DDC system certified sprinkler system and extinguishers certified extinguishers annually and properly secured Fixtures x 0.1 6% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air N/A Compressor N/A 0.45 N/A Distribution N/A 0.25 N/A Controls N/A 0.3 N/A D3010 Facility Fuel Systems Not Rated Distribution 0.5 Not Rated Controls 0.5 Not Rated D3020 Heating Systems 71% Heating Unit x % Controls x % Supply Air x 0.1 6% D3030 Cooling Systems 71% Cooling Unit x % Controls x % Supply Air x 0.1 6% D3050 Facility HVAC Dist. System 81% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 69% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 90% Up to Date Inspection x 1 90% D4030 Fire Suppression Specialties 90% Up to Date Inspection x % Bremerton School District Study and Survey March 15, 2012

98 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None installed in 1994 and meets code schedule 43 power with transformer on porperty meets code No occupancy sensors Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 86% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 71% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 60% Components x % Distribution x % Controls x 0.1 6% D6060 Distributed Comm/Monitoring 60% Components x % Distribution x % Controls x 0.1 6% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated none 97

99 98 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories As requested by principal older panel and a problem getting boards or programing. Past the confidence tests and works as designed Works as designed but has a some component failures that have been fixed. Gates work and are used as needed kitchen and janitorial equipment is up to date continually updated but short life and need to keep current is more than budget allows playground equipment is showing wear. Music is good All are showing wear. bookcases are very old, kitchen equipment in good shape and tables are good. Controls 0.1 Not Rated D7030 Electronic Surveillance 71% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 85% Components x 0.1 3% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 68% Components x % Distribution x % Controls x 0.1 6% E1010 Vehicle and Pedestrian Equipment 60% Components x N/A % Controls x N/A % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 60% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 60% General equipment condition x % Functionality x % E1090 Other Equipment 68% General equipment condition x % Functionality x % E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 60% General furnishing condition x % Functionality x % serves needs of the school servicable but is showing wear Bremerton School District Study and Survey March 15, 2012

100 Crownhill Elementary School 99 Aerial Photo

101 100 Bremerton School District Study and Survey March 15, 2012

102 A. General - Facility Basic Information Name Address 1500 Rocky Point Road Bremerton, WA Academic Grade Levels K-5 Area of Site Tax Parcels Building Area to date 47,815 Number of Buildings 1 Year Built 1996 Modernizations and N/A Additions, (Date and Sq Ft) Total number of classrooms 28 Capacity/Enrollment 528/512 Crownhill Elementary School B. Site At the northwest corner of the property lies a baseball diamond, with a narrow stretch of trees on the west edge separating the fi eld from a residential area. To the northeast lies court and playground. At the south end lies a paved playground with foursquare courts and a soft-surface, semi-circular playground with play structure. C. Exterior Walls Metal frame with brick and stucco exterior 101 D. Roof Asphalt shingle roof over wood decking E. Storm Water Control City storm water F. Mechanical System Boiler with heating unit for each room. No A/C G. Fuel Source Gas H. Controls Barber Coleman DDC I. Water City water

103 J. Electrical Schedule 25 K. Security System Sonitol L. Intercom System Dimensional M. Clocks With intercom N. Fire Alarm Edwards 102 Bremerton School District Study and Survey March 15, 2012

104 CROWNHILL ELEMENTARY SCHOOL SITE 103

105 104 Second Floor First Floor CROWNHILL ELEMENTARY SCHOOL Bremerton School District Study and Survey March 15, 2012

106 Area Calculations for: Crownhill Elementary School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals First Floor 1 32,912 Second Floor 1 14,083 Covered Play ,

107 Building Condition Assessment Summary Form School District: Bremerton School District 106 Facility Name: Crownhill Elementary School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 1.20 A1010 Standard Foundation 90% 1.20 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 1.84 A4010 Standard Slabs on Grade 90% 1.84 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.72 A6010 Building Subdrainage 90% 0.72 B10 Superstructure B1010 Floor Construction 83% 8.35 B1020 Roof Construction 80% 3.28 B1080 Stairs 90% 0.85 B20 Exterior Vertical Enclosures B2010 Exterior Walls 90% 7.80 B2020 Exterior Windows 86% 3.37 B2050 Exterior Doors and Grilles 87% 0.37 B2070 Exterior Louvers and Vents 90% 0.05 B30 Exterior Horizontal Enclosures 1.96 B3010 Roofing 45% 1.74 B3020 Roof Appurtenances 83% 0.21 B3060 Horizontal Openings/Penetrations 90% 0.02 B3080 Overhead Exterior Enclosures Not Rated Not Rated C10 Interior Construction C1010 Interior Partitions 90% 3.92 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 90% 0.99 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction 90% 0.05 C1070 Suspended Ceiling Const. 90% 4.85 C20 Interior Finishes 9.32 C2010 Wall Finishes 86% 3.00 C2020 Interior Fabrications 86% 0.09 C2030 Flooring 78% 5.73 C2040 Stair Finishes 83% 0.33 Bremerton School District Study and Survey March 15, 2012

108 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 86% 0.17 D10 Conveying 0.57 D1010 Vertical Conveying Systems 98% 0.57 D20 Plumbing Fixtures 6.03 D2010 Domestic Water Distribution 90% 4.02 D2020 Sanitary Drainage 90% 1.92 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air 90% 0.00 D30 HVAC 5.75 D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 90% 5.31 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 90% 0.27 D3060 Ventilation 81% 0.16 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.66 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 0.90 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 90% 7.55 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.65 D7010 Access Control and Intrusion Defection 60% 0.30 D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 85% 0.17 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 1.64 E1010 Vehicle and Pedestrian Equipment 60% 0.00 E1030 Commercial Equipment 68% 0.20 E1040 Institutional Equipment 60% 0.68 E1070 Entertainment and Recreational Equipment 90% 0.09 E1090 Other Equipment 90% 0.67 E20 Furnishings 1.24 E2010 Fixed Furnishings 68% 1.15 E2050 Movable Furnishings 90%

109 108 Building Condition Assessment Scoring Form Bremerton School District Crownhill Elementary School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories most of the building is on piling with grade beams installed in story building None great shape A1010 Standard Foundation 90% Cracks & Separation x % Drainage x % Vegetation x 0.1 9% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % none Bremerton School District Study and Survey March 15, 2012

110 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories asphalt shingles are failing and needed repaired every year a good window system asphalt shingles are failing and needed repaired every year; mobile safety anchors Settling x % B1010 Floor Construction 83% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 80% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 9% Soft spots, swelling or settling x 0.1 9% Structural damage x % B1080 Stairs 90% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 90% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 86% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 87% Hinges x % Locks x % Door x % Closers x 0.1 9% Windows & Grills x 0.1 9% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 90% Structural damage x % Screens x % Components secure x % B3010 Roofing 45% Safety systems x 0.1 3% Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % 109

111 110 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 83% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 90% Structural damage (ducts, chimneys, etc.) x 0.1 9% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures Not Rated Support structure 0.35 Not Rated Components secure 0.15 Not Rated Coverings 0.5 Not Rated C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 90% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 9% C1040 Interior Grilles and Grates 90% Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % Bremerton School District Study and Survey March 15, 2012

112 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories C1070 Suspended Ceiling Const. 90% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 78% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Sealant x % C2040 Stair Finishes 83% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 98% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 90% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% 111

113 112 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories for dry sprinkler system only installed new boilers in 2008 and 2009 Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x N/A % Distribution x N/A % Controls x N/A % D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 90% Heating Unit x % Controls x % Supply Air x 0.1 9% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 90% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 81% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % None in good shape fan need more cleaning Bremerton School District Study and Survey March 15, 2012

114 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None meets code T 8 with occupancy sensors; no daylight zone switching Aging VOIP system; components failing said to be unsupported in 3 4 years Not enough budget to keep current because of technology changes mostly operator error and sensitive to motion like ceiling hanging displays. Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 90% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection 60% Components x % Distribution x % 113

115 114 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories cameras as principal requests Panel needs to be updated Web based DDC recently updated, other system work gates work okay Always changing and not enough budget to keep up Controls x 0.1 6% D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 85% Components x 0.1 3% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 60% Components x N/A % Controls x N/A % E1030 Commercial Equipment 68% General equipment condition x % Functionality x % E1040 Institutional Equipment 60% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 90% General equipment condition x % Functionality x % E1090 Other Equipment 90% General equipment condition x % Functionality x % E2010 Fixed Furnishings 68% General furnishing condition x % Functionality x % E2050 Movable Furnishings 90% General furnishing condition x % Functionality x % some play toys are old up dated in or newer and repalced as needed Bremerton School District Study and Survey March 15, 2012

116 Kitsap Lake Elementary School 115 Aerial Photo

117 116 Bremerton School District Study and Survey March 15, 2012

118 A. General - Facility Basic Information Kitsap Lake Elementary School Name Address 1111 Carr Boulevard Bremerton, WA Academic Grade Levels K-5 Area of Site Tax Parcels ; ; ; ; ; Building Area to date 48,932 Number of Buildings 2 Year Built 1992 Modernizations and N/A Additions, (Date and Sq Ft) Total number of classrooms 26 Capacity/Enrollment 528/505 B. Site Kitsap Lake Elementary is situated centrally within its property boundaries. To the east and south of the building lies a large grassy expanse. Between the building and the grassy zone, a smaller playground occurs. Along the entire length of the west property line is a narrow, densely wooded area. C. Exterior Walls Wood frame with brick exterior 117 D. Roof Asphalt shingles over wood deck support by wood trusses E. Storm Water Control City storm water F. Mechanical System Boiler with heating unit for each room. No A/C G. Fuel Source Gas H. Controls Barber Coleman DDC I. Water City water

119 J. Electrical Schedule 25 K. Security System none L. Intercom System Dimensional M. Clocks With intercom N. Fire Alarm Silent Knight 118 Bremerton School District Study and Survey March 15, 2012

120 KITSAP LAKE ELEMENTARY SCHOOL SITE 119

121 120 KITSAP LAKE ELEMENTARY SCHOOL Bremerton School District Study and Survey March 15, 2012

122 121

123 Area Calculations for: Kitsap Lake Elementary School Bremerton School District #100-C Bremerton, Washington B10Area Number Area Name SF Factor Totals First Floor 1 35,535 Second Floor 1 12,567 Covered Play , Bremerton School District Study and Survey March 15, 2012

124 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: Kitsap Lake Elementary School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 1.16 A1010 Standard Foundation 87% 1.16 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 1.92 A4010 Standard Slabs on Grade 90% 1.84 A4040 Pits and Bases 90% 0.08 A60 Building Subdrainage 0.72 A6010 Building Subdrainage 90% 0.72 B10 Superstructure B1010 Floor Construction 90% 9.11 B1020 Roof Construction 69% 2.84 B1080 Stairs 90% 0.85 B20 Exterior Vertical Enclosures B2010 Exterior Walls 90% 7.80 B2020 Exterior Windows 72% 2.84 B2050 Exterior Doors and Grilles 84% 0.35 B2070 Exterior Louvers and Vents 83% 0.04 B30 Exterior Horizontal Enclosures 2.67 B3010 Roofing 53% 2.03 B3020 Roof Appurtenances 60% 0.15 B3060 Horizontal Openings/Penetrations 60% 0.01 B3080 Overhead Exterior Enclosures 65% 0.48 C10 Interior Construction 8.75 C1010 Interior Partitions 65% 2.81 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 90% 0.99 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction 90% 0.05 C1070 Suspended Ceiling Const. 74% 3.96 C20 Interior Finishes 9.50 C2010 Wall Finishes 90% 3.16 C2020 Interior Fabrications 90% 0.09 C2030 Flooring 78% 5.73 C2040 Stair Finishes 90%

125 OSPI Building Condition Assessment Summary Form 124 Component Component Score BCA Score C2050 Ceiling Finishes 78% 0.16 D10 Conveying 0.57 D1010 Vertical Conveying Systems 99% 0.57 D20 Plumbing Fixtures 6.03 D2010 Domestic Water Distribution 90% 4.02 D2020 Sanitary Drainage 90% 1.92 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air 90% 0.00 D30 HVAC 6.07 D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 96% 5.63 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 81% 0.24 D3060 Ventilation 90% 0.18 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.66 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 0.90 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 90% 7.55 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.20 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance Not Rated Not Rated D7050 Detection and Alarm 100% 0.20 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 2.03 E1010 Vehicle and Pedestrian Equipment 90% 0.00 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 90% 1.03 E1070 Entertainment and Recreational Equipment 68% 0.07 E1090 Other Equipment 90% 0.67 E20 Furnishings 1.22 E2010 Fixed Furnishings 68% 1.15 E2050 Movable Furnishings 68% 0.07 Bremerton School District Study and Survey March 15, 2012

126 Building Condition Assessment Scoring Form Bremerton School District Kitsap Lake Elementary School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories the back of the buidling has some standing water A1010 Standard Foundation 87% Cracks & Separation x % Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases 90% Settling x % Water Penetration x % Structural damage x % A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % 125

127 126 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories cannot find the weather stripping for the windows Settling x % B1010 Floor Construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 69% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 9% Soft spots, swelling or settling x 0.1 9% Structural damage x % B1080 Stairs 90% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 90% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 72% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 84% Hinges x % Locks x % Door x % Closers x 0.1 9% Windows & Grills x 0.1 6% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 83% Structural damage x % Screens x % Components secure x % B3010 Roofing 53% Safety systems x 0.1 6% Slopes and runoffs x % starting to show wear backdraft dampers need some help asphalt roof failing, library of minimal slope and gutters seem undersized in areas Gutters, downspouts, scuppers, roof drains, etc. x % Bremerton School District Study and Survey March 15, 2012

128 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories getting old installed in 1992 front entry is discoloring, other areas are showing signs of wear reworked in 2011 to put in siesmic sheeting on the existing frame that was not always plumb Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 60% Structural damage x 0.1 6% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 60% Structural damage (ducts, chimneys, etc.) x 0.1 6% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 65% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 65% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 90% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 9% C1040 Interior Grilles and Grates 90% all grills and rollup doors work properly Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 90% Levelness x % Soft spots, swelling or settling x % Structural damage x % 127

129 128 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some damaged and bent because of wear over the years carpet installed in 1992 is becoming tripping hazard C1070 Suspended Ceiling Const. 74% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 78% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Sealant x % C2040 Stair Finishes 90% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 78% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 99% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 90% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% Bremerton School District Study and Survey March 15, 2012

130 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories for fire sprinkler dry system only boilers have been replaced and DDC undated in 2010 Not able to get enough fresh air into buidling as designed Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x N/A % Distribution x N/A % Controls x N/A % D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 96% Heating Unit x % Controls x % Supply Air x 0.1 9% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 81% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 90% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % None replace fire system in

131 130 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None T 8's with occupancy sensors through out the buidling Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 90% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated None Bremerton School District Study and Survey March 15, 2012

132 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None fire system replaced and to current codes in 2010 gates work Controls 0.1 Not Rated D7030 Electronic Surveillance Not Rated Components 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated Coverage 0.2 Not Rated D7050 Detection and Alarm 100% Components x % Distribution x % Controls x % Up to Date Inspection x % Coverage x % D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x N/A % Controls x N/A % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 90% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 68% General equipment condition x % Functionality x % E1090 Other Equipment 90% General equipment condition x % Functionality x % E2010 Fixed Furnishings 68% General furnishing condition x % Functionality x % E2050 Movable Furnishings 68% General furnishing condition x % Functionality x % playground equipment is showing wear 1992 it was new 1992 showing wear and needs updated 131

133 132 Bremerton School District Study and Survey March 15, 2012

134 Naval Avenue Early Learning Center 133 Aerial Photo

135 134 Bremerton School District Study and Survey March 15, 2012

136 A. General - Facility Basic Information Name Address 900 Olympic Avenue Bremerton, WA Academic Grade Levels PS-3 Area of Site 6.35 Tax Parcels Building Area to date 37,342 Number of Buildings 1 Year Built 1957 Modernizations and 1994 Modernization & Addition (6,578) Additions, (Date and Sq Ft) Total number of classrooms 23 Capacity/Enrollment 484/377 Naval Avenue Early Learning Center B. Site The Naval Avenue property is divided by bus only road that go between public streets to the north and south of the property. To the east is a long grassy playfi eld surrounded by a path that fi lls the eastern portion of the site. To the west of the road, between the road and school building are two separate play areas and portables. The southernmost play area contains three play structures. C. Exterior Walls Concrete base walls with metal frame to support the old fl at roof structure. There is window infi ll and framed wall in between the structural colums. 135 D. Roof Metal roof over wood frame deck and supports that were installed in 1986 over the fl at roof. E. Storm Water Control City storm water system F. Mechanical System Gas fi red boiler for hydronic heat system with a unit for each 4 classrooms located in the attic space with a heat coil to adjust the heating into each classroom. No air conditioning G. Fuel Source Gas H. Controls ATS DDC heating controls I. Water Water provided by the city

137 J. Electrical Schedule 25 electric with schedule 24 to the portables K. Security System None L. Intercom System Electrocom M. Clocks With intercom system N. Fire Alarm Edwards installed in Bremerton School District Study and Survey March 15, 2012

138 NAVAL AVENUE EARLY LEARNING CENTER SITE 137

139 138 NAVAL AVENUE EARLY LEARNING CENTER Bremerton School District Study and Survey March 15, 2012

140 Area Calculations for: Naval Avenue Early Learning Center Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals Original Building 1 29, Additions 1 6,578 Covered Play ,

141 Building Condition Assessment Summary Form School District: Bremerton School District 140 Facility Name: Naval Avenue Elementary School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Single Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 2.84 A1010 Standard Foundation 74% 2.84 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 3.48 A4010 Standard Slabs on Grade 86% 3.48 A4040 Pits and Bases N/A N/A A60 Building Subdrainage 0.48 A6010 Building Subdrainage 60% 0.48 B10 Superstructure 2.23 B1010 Floor Construction 83% 0.00 B1020 Roof Construction 77% 2.23 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures 9.01 B2010 Exterior Walls 68% 5.93 B2020 Exterior Windows 74% 2.82 B2050 Exterior Doors and Grilles 48% 0.23 B2070 Exterior Louvers and Vents 68% 0.03 B30 Exterior Horizontal Enclosures 3.78 B3010 Roofing 53% 3.23 B3020 Roof Appurtenances 80% 0.20 B3060 Horizontal Openings/Penetrations 57% 0.01 B3080 Overhead Exterior Enclosures 45% 0.34 C10 Interior Construction 8.29 C1010 Interior Partitions 72% 2.79 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 72% 0.86 C1040 Interior Grilles and Grates 60% 0.03 C1060 Raised floor construction Not Rated Not Rated C1070 Suspended Ceiling Const. 69% 3.72 C20 Interior Finishes 6.75 C2010 Wall Finishes 72% 2.38 C2020 Interior Fabrications 77% 0.08 C2030 Flooring 74% 4.15 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

142 OSPI Building Condition Assessment Summary Form C2050 Ceiling Finishes 69% 0.14 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures 7.83 D2010 Domestic Water Distribution 69% 5.82 D2020 Sanitary Drainage 65% 1.94 D2030 Building Support Plumbing Systems 75% 0.08 D2050 General Services Compressed Air 90% 0.00 D30 HVAC 8.62 D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 77% 8.32 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 60% 0.18 D3060 Ventilation 60% 0.12 D40 Fire Protection 2.60 D4010 Fires Suppression 100% 2.59 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.34 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 1.03 D5030 General Purpose Electrical Power 60% 0.80 D5040 Lighting 90% 7.51 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.36 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 88% 0.18 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 0.41 E1010 Vehicle and Pedestrian Equipment 60% 0.00 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 68% 0.08 E1070 Entertainment and Recreational Equipment 60% 0.06 E1090 Other Equipment Not Rated Not Rated E20 Furnishings 1.08 E2010 Fixed Furnishings 60% 1.02 E2050 Movable Furnishings 60%

143 142 Building Condition Assessment Scoring Form Bremerton School District Naval Avenue Elementary School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Single Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None Old slab some settling A1010 Standard Foundation 74% Cracks & Separation x % Drainage x % Vegetation x 0.1 9% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 86% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases N/A Settling N/A 0.3 N/A Water Penetration N/A 0.3 N/A Structural damage N/A 0.4 N/A A6010 Building Subdrainage 60% Drainage x % Membrane integrity x % Bremerton School District Study and Survey March 15, 2012

144 OSPI Building Condition Evaluation Form 12/28/2 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Old flat roof cover with wood supported metal frame roof in the 80's None water comes in when gutters blocked due to poor design and install new in 1994 Metal roof good. Gutters are under sized and drains all small. Causing blockage which can cause water to get in the building. Settling x % B1010 Floor Construction 83% Levelness x N/A % Soft spots, swelling or settling x N/A % Structural damage x N/A % B1020 Roof Construction 77% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 6% Soft spots, swelling or settling x 0.1 9% Structural damage x % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 68% Water Penetration x 0.3 9% Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 74% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 48% Hinges x % Locks x % Door x % Closers x 0.1 6% Windows & Grills x 0.1 9% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 68% Structural damage x % Screens x % Components secure x % B3010 Roofing 53% Safety systems x 0.1 6% Slopes and runoffs x % new in 1994 Gutters, downspouts, scuppers, roof drains, etc. x % 143

145 144 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Flashing are starting to show wear seals are getting old, and upper windows in the classrooms have some problems Installed in the 80's witht eh roof and starting show wear!! Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 80% Structural damage x 0.1 6% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 57% Structural damage (ducts, chimneys, etc.) x 0.1 6% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 45% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 72% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 72% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 60% many walls are block wall installed in 1956 installed in 1994 all work as designed Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction Not Rated Levelness 0.25 Not Rated Soft spots, swelling or settling 0.3 Not Rated Structural damage 0.45 Not Rated Bremerton School District Study and Survey March 15, 2012

146 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Many ceilings are glue on tile that was reworked in 1994 some block walls in buidling that show are not pleasant to appearance starting to show wear Old original ceiling refinished in 1994 and is showing wear!! C1070 Suspended Ceiling Const. 69% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 72% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 77% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 74% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 69% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 69% Pressure x 0.1 9% Water quality x % Leakage x 0.1 6% Some of the piping was installed in

147 146 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some of the sewer system installed in 1956 Part of sewer piping installed in 56 On fire sprinkler replacing small condensate boilers as needed Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 65% Flow x % Vents x 0.1 6% Traps x % Clean outs x 0.1 6% D2030 Building Support Plumbing Systems 75% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x N/A % Distribution x N/A % Controls x N/A % D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 77% Heating Unit x % Controls x % Supply Air x 0.1 6% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 60% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 60% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % None supply and return air could better Bremerton School District Study and Survey March 15, 2012

148 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None some older panels and wiring still in use T 8's with occupancy sensors Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 60% Branch panels x % Branch wiring x % D5040 Lighting 90% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated 147

149 148 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories As requested by the principal Panel is old DOS system needs to be replaced Gates work Controls 0.1 Not Rated D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 88% Components x 0.1 6% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 60% Components x N/A % Controls x N/A % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 68% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 60% General equipment condition x % Functionality x % E1090 Other Equipment Not Rated General equipment condition 0.75 Not Rated Functionality 0.25 Not Rated E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 60% General furnishing condition x % Functionality x % Playground equipment wearing showing wear showing wear Bremerton School District Study and Survey March 15, 2012

150 View Ridge Elementary School 149 Aerial Photo

151 150 Bremerton School District Study and Survey March 15, 2012

152 A. General - Facility Basic Information View Ridge Elementary School Name Address 3250 Spruce Street Bremerton, WA Academic Grade Levels K-5 Area of Site Tax Parcels ; ; ; ; Building Area to date 37,984 Number of Buildings 1 Year Built 1952 Modernizations and 1960, 1967, 1994 Modernization & Addition (6,235) Additions, (Date and Sq Ft) Total number of classrooms 23 Capacity/Enrollment 528/403 B. Site The View Ridge site contains 3 baseball fi elds, two to the east and one to the south. There is a playground with play structure, and soccer fi eld directly to the north of the building. The property line also severs a football fi eld and track, which is shared with the Bremerton Junior High property, at its southeast edge. A densely wooded area is located in the far southeast corner of the lot. C. Exterior Walls Wood frame with some brick and some concrete metal frame and window infi ll 151 D. Roof Flat built-up roof over wood decking. Some areas sloped shingle. E. Storm Water Control City storm F. Mechanical System Boiler for hot water system that supplies a roof top heating unit for each 4 classrooms with a heating coil to adjust fi nal heat into classroom. No A/C G. Fuel Source Gas H. Controls ATS heating controls

153 I. Water City water J. Electrical Schedule 25 K. Security System none L. Intercom System Dimensional M. Clocks With intercom N. Fire Alarm Edwards with panel being change to Silent Knight in Nov Bremerton School District Study and Survey March 15, 2012

154 VIEW RIDGE ELEMENTARY SCHOOL SITE 153

155 A VIEW RIDGE ELEMENTARY SCHOOL Bremerton School District Study and Survey March 15, 2012

156 Area Calculations for: View Ridge Elementary School Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals 1 Existing Classrooms 1 8,723 2 Classroom Addition 1 4,480 3 Administration 1 3,608 3A Administration Addition 1 1,755 4 Existing Classrooms 1 8,540 5 Library 1 2,989 6 Music Room Addition 1 1,392 7 Gymnasium 1 4,800 8 Kitchen Addition Covered Play Area 0.5 1,137 37,

157 Building Condition Assessment Summary Form School District: Bremerton School District 156 Facility Name: View Ridge Elementary School Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Single Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 3.19 A1010 Standard Foundation 83% 3.19 A20 Walls 0.00 A2020 Walls for subgrade enclosure 83% 0.00 A40 Slabs on Grade 3.36 A4010 Standard Slabs on Grade 83% 3.36 A4040 Pits and Bases N/A N/A A60 Building Subdrainage 0.55 A6010 Building Subdrainage 69% 0.55 B10 Superstructure 1.36 B1010 Floor Construction N/A N/A B1020 Roof Construction 47% 1.36 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures B2010 Exterior Walls 86% 7.52 B2020 Exterior Windows 86% 3.27 B2050 Exterior Doors and Grilles 60% 0.29 B2070 Exterior Louvers and Vents 75% 0.04 B30 Exterior Horizontal Enclosures 2.30 B3010 Roofing 29% 1.76 B3020 Roof Appurtenances 63% 0.16 B3060 Horizontal Openings/Penetrations 75% 0.02 B3080 Overhead Exterior Enclosures 50% 0.37 C10 Interior Construction 9.95 C1010 Interior Partitions 90% 3.48 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 90% 1.07 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction Not Rated Not Rated C1070 Suspended Ceiling Const. 83% 4.45 C20 Interior Finishes 7.39 C2010 Wall Finishes 90% 2.98 C2020 Interior Fabrications 90% 0.09 C2030 Flooring 74% 4.15 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

158 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 86% 0.17 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures D2010 Domestic Water Distribution 87% 7.33 D2020 Sanitary Drainage 90% 2.70 D2030 Building Support Plumbing Systems 75% 0.08 D2050 General Services Compressed Air 90% 0.00 D30 HVAC 9.87 D3010 Facility Fuel Systems 60% 0.01 D3020 Heating Systems 87% 9.46 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 81% 0.24 D3060 Ventilation 81% 0.16 D40 Fire Protection 2.60 D4010 Fires Suppression 100% 2.59 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.74 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 1.03 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 90% 7.51 D60 Communication 1.27 D6010 Data Communications 83% 0.41 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 63% 0.38 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.33 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 81% 0.16 D7050 Detection and Alarm 85% 0.17 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 0.87 E1010 Vehicle and Pedestrian Equipment 90% 0.00 E1030 Commercial Equipment 68% 0.20 E1040 Institutional Equipment 68% 0.08 E1070 Entertainment and Recreational Equipment 90% 0.09 E1090 Other Equipment 68% 0.50 E20 Furnishings 1.22 E2010 Fixed Furnishings 68% 1.15 E2050 Movable Furnishings 68%

159 158 Building Condition Assessment Scoring Form Bremerton School District View Ridge Elementary School Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Single Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories boiler room is only location carpets wearing creating some tippinghazards A1010 Standard Foundation 83% Cracks & Separation x % Drainage x % Vegetation x 0.1 9% Water Leaks x % A2020 Walls for subgrade enclosure 83% Cracks & Separation x N/A % Drainage x N/A % Vegetation x N/A 0.1 9% Water Penetration x N/A % A4010 Standard Slabs on Grade 83% Levelness x % Soft spots, swelling or settling x 0.1 6% Structural damage x % Water Penetration x % A4040 Pits and Bases N/A Settling N/A 0.3 N/A Water Penetration N/A 0.3 N/A Structural damage N/A 0.4 N/A A6010 Building Subdrainage 69% Drainage x % Membrane integrity x % Bremerton School District Study and Survey March 15, 2012

160 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories flat roof near the end of it's life, replaced in 1994 flat roof that needs to be replaced, downspouts are undersize and need to be upgraded Settling x % B1010 Floor Construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A B1020 Roof Construction 47% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 6% Soft spots, swelling or settling x 0.1 3% Structural damage x % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 86% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 86% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 60% Hinges x % Locks x % Door x % Closers x 0.1 6% Windows & Grills x 0.1 6% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 75% Structural damage x % Screens x % Components secure x % B3010 Roofing 29% Safety systems x 0.1 9% Slopes and runoffs x % replaced in 1994 Gutters, downspouts, scuppers, roof drains, etc. x % 159

161 160 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories showing wear showing wear old system is failing and being replaced by wood sheating as needed Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 63% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 75% Structural damage (ducts, chimneys, etc.) x 0.1 9% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 50% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 90% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 90% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 9% C1040 Interior Grilles and Grates 90% installed in 1994 Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction Not Rated Levelness 0.25 Not Rated Soft spots, swelling or settling 0.3 Not Rated Structural damage 0.45 Not Rated Bremerton School District Study and Survey March 15, 2012

162 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories carpets wearing creating some tripping hazards C1070 Suspended Ceiling Const. 83% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 74% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 6% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 87% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% 161

163 162 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories for fire sprinkler system only on same meter as the old Junior High building. Will need ot be changed when buidling is demolished Fixtures x 0.1 6% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 75% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x N/A % Distribution x N/A % Controls x N/A % D3010 Facility Fuel Systems 60% Distribution x % Controls x % D3020 Heating Systems 87% Heating Unit x % Controls x % Supply Air x 0.1 6% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 81% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 81% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % None some velocity problems due to design causing drafty areas Bremerton School District Study and Survey March 15, 2012

164 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None Part of schedule 31 campus with old Junior High bilding that is closed. Will have to be changed when Jr high is demolished t 8's with occupancy sensors Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 90% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 83% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 63% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated 163

165 164 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories as requested by the principal old dos panel needs to be replaced but is still providing coverage for adequate fire protection gates work Playground equipment is wearing and needs to be replaced Controls 0.1 Not Rated D7030 Electronic Surveillance 81% Components x % Distribution x % Controls x 0.1 6% Coverage x % D7050 Detection and Alarm 85% Components x 0.1 3% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x N/A % Controls x N/A % E1030 Commercial Equipment 68% General equipment condition x % Functionality x % E1040 Institutional Equipment 68% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 90% General equipment condition x % Functionality x % E1090 Other Equipment 68% General equipment condition x % Functionality x % E2010 Fixed Furnishings 68% General furnishing condition x % Functionality x % E2050 Movable Furnishings 68% General furnishing condition x % Functionality x % starting to show some wear Bremerton School District Study and Survey March 15, 2012

166 West Hills S.T.E.M. Academy 165 Aerial Photo

167 166 Bremerton School District Study and Survey March 15, 2012

168 A. General - Facility Basic Information West Hills S.T.E.M. Academy Name Address 520 National Avenue South Bremerton, WA Academic Grade Levels PS-6 Area of Site Tax Parcels ; ; ; Building Area to date 48,207 Number of Buildings 4 Year Built 1988 Modernizations and N/A Additions, (Date and Sq Ft) Total number of classrooms 27 Capacity/Enrollment 528/516 B. Site The West Hills building is located at the far west side of its property. To the east of the building are two playgrounds with play structures and further east lies a large bootshaped fi eld outlined by a walking path. At the far northeast corner of the property is a densely wooded area. C. Exterior Walls Wood frame with stucco exterior. 167 D. Roof Concrete tile roof over a wood deck with wood.trusses E. Storm Water Control In the county but storm is into the city storm F. Mechanical System Boilers with central units for each end of the building and the gym No A/C G. Fuel Source Gas H. Controls Barber Coleman DDC I. Water City water

169 J. Electrical Schedule 25 K. Security System None L. Intercom System Electricom M. Clocks With intercom N. Fire Alarm Edwards 168 Bremerton School District Study and Survey March 15, 2012

170 WEST HILLS S.T.E.M. ACADEMY SITE 169

171 Covered Play 170 WEST HILLS S.T.E.M. ACADEMY Bremerton School District Study and Survey March 15, 2012

172 171

173 Area Calculations for: West Hills S.T.E.M. Academy Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals Lower Floor 1 29,015 Upper Floor 1 23,176 Covered Play Area 0.5 2,016 48, Bremerton School District Study and Survey March 15, 2012

174 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: West Hills Elementary Building Name: STEM Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Elementary School Multi Story Overall BCA Score: Component Component Score BCA Score A10 Foundations 0.92 A1010 Standard Foundation 69% 0.92 A20 Walls 0.00 A2020 Walls for subgrade enclosure 51% 0.00 A40 Slabs on Grade 1.84 A4010 Standard Slabs on Grade 90% 1.84 A4040 Pits and Bases Not Rated Not Rated A60 Building Subdrainage 0.65 A6010 Building Subdrainage 81% 0.65 B10 Superstructure B1010 Floor Construction 83% 8.35 B1020 Roof Construction 60% 2.47 B1080 Stairs 90% 0.85 B20 Exterior Vertical Enclosures B2010 Exterior Walls 81% 7.02 B2020 Exterior Windows 72% 2.84 B2050 Exterior Doors and Grilles 66% 0.28 B2070 Exterior Louvers and Vents 90% 0.05 B30 Exterior Horizontal Enclosures 2.11 B3010 Roofing 38% 1.45 B3020 Roof Appurtenances 83% 0.21 B3060 Horizontal Openings/Penetrations 53% 0.01 B3080 Overhead Exterior Enclosures 60% 0.45 C10 Interior Construction C1010 Interior Partitions 77% 3.33 C1020 Interior Windows 90% 0.90 C1030 Interior Doors 78% 0.86 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction 83% 0.04 C1070 Suspended Ceiling Const. 90% 4.85 C20 Interior Finishes 9.74 C2010 Wall Finishes 81% 2.84 C2020 Interior Fabrications 90% 0.09 C2030 Flooring 86% 6.28 C2040 Stair Finishes 90%

175 OSPI Building Condition Assessment Summary Form 174 Component Component Score BCA Score C2050 Ceiling Finishes 83% 0.17 D10 Conveying 0.57 D1010 Vertical Conveying Systems 99% 0.57 D20 Plumbing Fixtures 6.05 D2010 Domestic Water Distribution 91% 4.05 D2020 Sanitary Drainage 90% 1.92 D2030 Building Support Plumbing Systems 90% 0.09 D2050 General Services Compressed Air N/A N/A D30 HVAC 5.74 D3010 Facility Fuel Systems 90% 0.01 D3020 Heating Systems 90% 5.31 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 81% 0.24 D3060 Ventilation 90% 0.18 D40 Fire Protection 2.79 D4010 Fires Suppression 100% 2.78 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 9.28 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 90% 0.90 D5030 General Purpose Electrical Power 90% 1.21 D5040 Lighting 86% 7.17 D60 Communication 1.47 D6010 Data Communications 90% 0.45 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 90% 0.54 D6060 Distributed Comm/Monitoring 90% 0.18 D70 Electronic Safety and Security 0.37 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance 90% 0.18 D7050 Detection and Alarm 93% 0.19 D80 Integrated Automation 0.09 D8010 Integrated Automation Facility Controls 90% 0.09 E10 Equipment 2.03 E1010 Vehicle and Pedestrian Equipment 90% 0.00 E1030 Commercial Equipment 90% 0.27 E1040 Institutional Equipment 90% 1.03 E1070 Entertainment and Recreational Equipment 68% 0.07 E1090 Other Equipment 90% 0.67 E20 Furnishings 1.11 E2010 Fixed Furnishings 60% 1.02 E2050 Movable Furnishings 90% 0.09 Bremerton School District Study and Survey March 15, 2012

176 Building Condition Assessment Scoring Form Bremerton School District West Hills Elementary STEM Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Elementary School Multi Story Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories most of buidling has some below grade aspects that have had some water problems gym wall and other below grade walls are in pretty good shape some drainage problems are addressed each year A1010 Standard Foundation 69% Cracks & Separation x % Drainage x % Vegetation x 0.1 6% Water Leaks x % A2020 Walls for subgrade enclosure 51% Cracks & Separation x N/A 0.3 9% Drainage x N/A % Vegetation x N/A 0.1 6% Water Penetration x N/A % A4010 Standard Slabs on Grade 90% Levelness x % Soft spots, swelling or settling x 0.1 9% Structural damage x % Water Penetration x % A4040 Pits and Bases Not Rated Settling 0.3 Not Rated Water Penetration 0.3 Not Rated Structural damage 0.4 Not Rated A6010 Building Subdrainage 81% Drainage x % Membrane integrity x % 175

177 176 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories tile roof is falling and in need of constent repair to keep water intrusion down Seals at joints require regular maintenance Windows/seals have needed replacing doors and hardware are showing signs of use tile roof system is disappearing and needs to be repalced Settling x % B1010 Floor Construction 83% Levelness x % Soft spots, swelling or settling x % Structural damage x % B1020 Roof Construction 60% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 3% Soft spots, swelling or settling x 0.1 6% Structural damage x % B1080 Stairs 90% Structural damage x % Settling x % Components secure x % B2010 Exterior Walls 81% Water Penetration x % Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 72% Water Penetration x 0.3 9% Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 66% Hinges x % Locks x % Door x % Closers x 0.1 9% Windows & Grills x 0.1 9% Weather stripping x 0.1 6% B2070 Exterior Louvers and Vents 90% Structural damage x % Screens x % Components secure x % B3010 Roofing 38% Safety systems x 0.1 3% Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % Bremerton School District Study and Survey March 15, 2012

178 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Skylights by the front entry have always leaked and cannot find a contractor or solution to this problem. The seals and glazing are showing wear from age partition by front entry has water damage that keeps reoccurring Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 83% Structural damage x 0.1 9% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations 53% Structural damage (ducts, chimneys, etc.) x 0.1 9% Flashings x % Components secure x % Weather seals x % Glazing x % B3080 Overhead Exterior Enclosures 60% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 77% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 78% Locks x % Closers x % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 90% showing wear since installed in 1988 Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction 83% Levelness x % Soft spots, swelling or settling x % Structural damage x % 177

179 178 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Not to current code, but not failures water damage front entry, many hallways have murals as painted by the staff carpet has been replaced but is showing wear again C1070 Suspended Ceiling Const. 90% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 81% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2020 Interior Fabrications 90% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 86% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Sealant x % C2040 Stair Finishes 90% Structural Damage x % Settling x % Components secure x % C2050 Ceiling Finishes 83% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems 99% Inspections Current x % Aesthetics x % Functionality x % D2010 Domestic Water Distribution 91% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% Bremerton School District Study and Survey March 15, 2012

180 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories on sprinkler system only replace condensate boilders as needed hard to get makeup air into the system; question full overhead intake levels Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 90% Flow x % Vents x 0.1 9% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 90% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air N/A Compressor N/A 0.45 N/A Distribution N/A 0.25 N/A Controls N/A 0.3 N/A D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 90% Heating Unit x % Controls x % Supply Air x 0.1 9% D3030 Cooling Systems Not Rated Cooling Unit 0.55 Not Rated Controls 0.35 Not Rated Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 81% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 90% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % None 179

181 180 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None reaching load capacities in some areas t 8's installed 2010; not in current code compliance for daylight controls Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 90% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 86% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 90% Components x % Distribution x % Controls x 0.1 9% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components x % Distribution x % Controls x 0.1 9% D6060 Distributed Comm/Monitoring 90% Components x % Distribution x % Controls x 0.1 9% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Bremerton School District Study and Survey March 15, 2012

182 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories As requested by the principal fire panel works but needs to be replaced Gates work playground equipment needs to be replaced wearing out and replacing formica as needed Controls 0.1 Not Rated D7030 Electronic Surveillance 90% Components x % Distribution x % Controls x 0.1 9% Coverage x % D7050 Detection and Alarm 93% Components x 0.1 6% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 90% Components x % Distribution x % Controls x 0.1 9% E1010 Vehicle and Pedestrian Equipment 90% Components x N/A % Controls x N/A % E1030 Commercial Equipment 90% General equipment condition x % Functionality x % E1040 Institutional Equipment 90% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment 68% General equipment condition x % Functionality x % E1090 Other Equipment 90% General equipment condition x % Functionality x % E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 90% General furnishing condition x % Functionality x % showing wear 181

183 182 Bremerton School District Study and Survey March 15, 2012

184 West Sound Technical Skills Center 183 Aerial Photo

185 184 Bremerton School District Study and Survey March 15, 2012

186 A. General - Facility Basic Information West Sound Technical Skills Center Name Address 101 National Avenue North Bremerton, WA Academic Grade Levels (ages 16-19) Area of Site Tax Parcels Building Area to date 70,691 Number of Buildings 2 Year Built 1977 Modernizations and 1998 miscellaneous tenant improvement type work for program support. Additions, (Date and Sq Ft) Total number of classrooms 15 Capacity/Enrollment 500/505 B. Site The Technical Skills Center is fl anked at the west and northwest property lines by a heavily wooded canopy. A paved zone separates the building from the east edge of the property, which is grassy and spotted with trees. C. Exterior Walls Concrete tilt up walls painted on the exterior and CMU D. Roof Single ply Stevens roof installed in E. Storm Water Control City storm water F. Mechanical System Heat pumps to all the areas G. Fuel Source Electric schedule 43. Some gas to kitchen and paint booth. H. Controls ATS I. Water City water

187 J. Electrical Schedule 43 K. Security System None L. Intercom System Electricom M. Clocks None N. Fire Alarm Edwards 186 Bremerton School District Study and Survey March 15, 2012

188 WEST SOUND TECHNICAL SKILLS CENTER SITE 187

189 188 WEST SOUND TECHNICAL SKILLS CENTER Bremerton School District Study and Survey March 15, 2012

190 Building Condition Assessment Summary Form School District: Bremerton School District Facility Name: West Sound Technical Skills Center Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Skills Center Overall BCA Score: Component Component Score BCA Score A10 Foundations 2.94 A1010 Standard Foundation 74% 2.94 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 2.57 A4010 Standard Slabs on Grade 57% 2.57 A4040 Pits and Bases 90% 0.00 A60 Building Subdrainage 1.08 A6010 Building Subdrainage 90% 1.08 B10 Superstructure 3.71 B1010 Floor Construction 44% 0.00 B1020 Roof Construction 57% 3.71 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures 7.76 B2010 Exterior Walls 51% 4.18 B2020 Exterior Windows 77% 3.53 B2050 Exterior Doors and Grilles 6% 0.02 B2070 Exterior Louvers and Vents 60% 0.03 B30 Exterior Horizontal Enclosures 3.01 B3010 Roofing 53% 2.36 B3020 Roof Appurtenances 80% 0.20 B3060 Horizontal Openings/Penetrations Not Rated Not Rated B3080 Overhead Exterior Enclosures 60% 0.45 C10 Interior Construction 7.90 C1010 Interior Partitions 86% 4.28 C1020 Interior Windows 90% 1.80 C1030 Interior Doors 33% 0.40 C1040 Interior Grilles and Grates 90% 0.05 C1060 Raised floor construction N/A N/A C1070 Suspended Ceiling Const. 69% 1.38 C20 Interior Finishes 4.52 C2010 Wall Finishes 86% 2.14 C2020 Interior Fabrications 60% 0.06 C2030 Flooring 38% 2.21 C2040 Stair Finishes N/A N/A 189

191 OSPI Building Condition Assessment Summary Form 190 C2050 Ceiling Finishes 56% 0.11 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures 4.83 D2010 Domestic Water Distribution 90% 3.87 D2020 Sanitary Drainage 44% 0.84 D2030 Building Support Plumbing Systems 75% 0.08 D2050 General Services Compressed Air 90% 0.05 D30 HVAC D3010 Facility Fuel Systems Not Rated Not Rated D3020 Heating Systems 63% 2.46 D3030 Cooling Systems 63% 8.07 D3050 Facility HVAC Dist. System 69% 0.14 D3060 Ventilation 78% 0.08 D40 Fire Protection 2.61 D4010 Fires Suppression 100% 2.60 D4030 Fire Suppression Specialties 100% 0.01 D50 Electrical 8.61 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 84% 0.97 D5030 General Purpose Electrical Power 90% 0.90 D5040 Lighting 86% 6.75 D60 Communication 1.08 D6010 Data Communications 60% 0.30 D6020 Voice Communications 60% 0.30 D6030 Audio Video Communication 60% 0.36 D6060 Distributed Comm/Monitoring 60% 0.12 D70 Electronic Safety and Security 0.18 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance Not Rated Not Rated D7050 Detection and Alarm 90% 0.18 D80 Integrated Automation 0.06 D8010 Integrated Automation Facility Controls 60% 0.06 E10 Equipment 4.06 E1010 Vehicle and Pedestrian Equipment 90% 0.09 E1030 Commercial Equipment 68% 1.44 E1040 Institutional Equipment 68% 2.03 E1070 Entertainment and Recreational Equipment Not Rated Not Rated E1090 Other Equipment 68% 0.50 E20 Furnishings 0.66 E2010 Fixed Furnishings 60% 0.60 E2050 Movable Furnishings 60% 0.06 Bremerton School District Study and Survey March 15, 2012

192 Building Condition Assessment Scoring Form Bremerton School District West Sound Technical Skills Center Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Skills Center Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories A1010 Standard Foundation 74% Cracks & Separation x % Drainage x % Vegetation x 0.1 9% Water Leaks x % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 57% Levelness x % Soft spots, swelling or settling x 0.1 3% Structural damage x % Water Penetration x % A4040 Pits and Bases 90% Settling x N/A % Water Penetration x N/A % Structural damage x N/A % A6010 Building Subdrainage 90% Drainage x % Membrane integrity x % In automotive area the pits are dry 191

193 192 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories heaviliy cracked single ply roof installed in 1990 showing sigs of wear and requires repairs each year Cracks in tilt up cont, joints show wear, require monitoring. No known struct damage. not many window and reworked in 2009 exposed to elements since 1977 and in need of replcement Roofing 21 years old and due for replacement. flat roof sloped some using insulation in 1990 Settling x % B1010 Floor Construction 44% Levelness x N/A % Soft spots, swelling or settling x N/A 0.3 9% Structural damage x N/A % B1020 Roof Construction 57% Water Penetration x % Levelness of ridges, eaves, gables, etc. x 0.1 3% Soft spots, swelling or settling x 0.1 3% Structural damage x % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 51% Water Penetration x 0.3 9% Plumbness x % Warpage, swelling or settling x % Structural damage x % B2020 Exterior Windows 77% Water Penetration x % Weather stripping x % Window insulation failure x % Structural damage x % B2050 Exterior Doors and Grilles 6% Hinges x 0.2 0% Locks x % Door x % Closers x 0.1 0% Windows & Grills x 0.1 3% Weather stripping x 0.1 3% B2070 Exterior Louvers and Vents 60% Structural damage x % Screens x % Components secure x % B3010 Roofing 53% Safety systems x 0.1 6% Slopes and runoffs x % Gutters, downspouts, scuppers, roof drains, etc. x % Bremerton School District Study and Survey March 15, 2012

194 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories entry and other areas are showing wear and have been installed as budgets permit most are concrete block, Temporary movable partitions in the office areas some classroom areas need to be replaced Cracks, separations, damaged or missing materials, weather sealant, etc. x % B3020 Roof Appurtenances 80% Structural damage x 0.1 6% Flashings x % Components secure x % Weather hoods x % B3060 Horizontal Openings/Penetrations Not Rated Structural damage (ducts, chimneys, etc.) x 0.1 6% Flashings x % Components secure x % Weather seals x % Glazing 0.25 Not Rated B3080 Overhead Exterior Enclosures 60% Support structure x % Components secure x % Coverings x % C1010 Interior Partitions 86% Water Damage x % Plumbness x % Warpage, swelling or settling x % Structural damage x % C1020 Interior Windows 90% Window insulation failure x % Structural damage x % C1030 Interior Doors 33% Locks x 0.3 9% Closers x 0.2 6% Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) x % Lites x 0.1 6% C1040 Interior Grilles and Grates 90% hardware failing and no parts available All work as designed Structural damage (vanes, separation, etc.) x % Components secure x % C1060 Raised floor construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A 193

195 194 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories some bent supports and water damage wearing instaled in 1977 shop areas have exposed insulation which is not dark and grudgey C1070 Suspended Ceiling Const. 69% Levelness x % Components secure x % Structural damage (sagging, separation, breakage. etc.) x % Water Damage x % C2010 Wall Finishes 86% Water Damage x % Aesthetics X % Chipping, swelling, flaking or settling X % Structural damage X % C2020 Interior Fabrications 60% Water Damage x % Aesthetics x % Chipping, swelling, flaking or settling x % Structural damage x % C2030 Flooring 38% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 3% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 56% Water Damage X % Aesthetics X % Chipping, swelling, flaking, scoring, etc. x x 0.1 6% Structural damage x % Penetrations x % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 90% Pressure x 0.1 9% Water quality x % Leakage x 0.1 9% Bremerton School District Study and Survey March 15, 2012

196 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories main sewer line in the budiling has a sag and needs constant maintenance in shops area and fire system works as designed New compressor installed in 2010 for the shop area Electric building. Gas to the kitchen and paint booth only (not heating) Heat pump on east side are from 1989, aging and generally poor condition, HP on westside (shops) installed in 2004 in shop areas in fair to good condition. Fixtures x 0.1 9% Water heaters x % Backflow prevention x % D2020 Sanitary Drainage 44% Flow x % Vents x 0.1 6% Traps x % Clean outs x 0.1 9% D2030 Building Support Plumbing Systems 75% Sewer/Septic System x % Fire loop x % D2050 General Services Compressed Air 90% Compressor x % Distribution x % Controls x % D3010 Facility Fuel Systems Not Rated Distribution 0.5 Not Rated Controls 0.5 Not Rated D3020 Heating Systems 63% Heating Unit x % Controls x % Supply Air x 0.1 9% D3030 Cooling Systems 63% Cooling Unit x % Controls x % Supply Air x 0.1 9% D3050 Facility HVAC Dist. System 69% Supply & Return x % Ducting/Piping x % Controls x % D3060 Ventilation 78% Fans Supply & Exhaust x % Ducting/Piping x % Controls x % D4010 Fires Suppression 100% Up to Date Inspection x 1 100% D4030 Fire Suppression Specialties 100% Up to Date Inspection x % see note above for heat punmps 195

197 196 OSPI Building Condition Evaluation Form 12/28/201 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories t 8's installed 2010 Components secure x % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 84% Transformers x % Vaults x % Main Subpanels x % EMT, wiring x % Motors x % D5030 General Purpose Electrical Power 90% Branch panels x % Branch wiring x % D5040 Lighting 86% Fixtures x % Switches, wiring x 0.1 9% Controls x % Coverage x % D6010 Data Communications 60% Components x % Distribution x % Controls x 0.1 6% Connectivity x % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 60% Components x % Distribution x % Controls x 0.1 6% D6060 Distributed Comm/Monitoring 60% Components x % Distribution x % Controls x 0.1 6% D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Bremerton School District Study and Survey March 15, 2012

198 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Edwards panel difficult to program and fix gates work Controls 0.1 Not Rated D7030 Electronic Surveillance Not Rated Components 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated Coverage 0.2 Not Rated D7050 Detection and Alarm 90% Components x 0.1 3% Distribution x 0.1 9% Controls x % Up to Date Inspection x % Coverage x 0.1 9% D8010 Integrated Automation Facility Controls 60% Components x % Distribution x % Controls x 0.1 6% E1010 Vehicle and Pedestrian Equipment 90% Components x % Controls x % E1030 Commercial Equipment 68% General equipment condition x % Functionality x % E1040 Institutional Equipment 68% General equipment condition x % Functionality x % E1070 Entertainment and Recreational Equipment Not Rated General equipment condition 0.75 Not Rated Functionality 0.25 Not Rated E1090 Other Equipment 68% General equipment condition x % Functionality x % E2010 Fixed Furnishings 60% General furnishing condition x % Functionality x % E2050 Movable Furnishings 60% General furnishing condition x % Functionality x % 197

199 198 Bremerton School District Study and Survey March 15, 2012

200 Administration Building 199 Aerial Photo

201 200 Bremerton School District Study and Survey March 15, 2012

202 A. General - Facility Basic Information Name Address st Street Bremerton, WA Academic Grade Levels N/A Area of Site 4.3 Tax Parcels Building Area to date 31,500 Number of Buildings 1 Year Built 1945 Administration Building Modernizations and Additions, Date and (Sq Ft) Total number of classrooms Capacity/Enrollment N.A N/A B. Site The Administration Building shares its property with the Renaissance High School. There is a long grassy expanse directly east of the building, reaching to the far north property line. Adjacent the east property line is a narrow greenbelt separating a community track and fi eld. Renaissance uses the gym area for PE. C. Exterior Walls Concrete with metal frame in-fi lled with windows and stucco. 201 D. Roof Sloped shingle roof with wood trusses over fl at roof E. Storm Water Control City storm water F. Mechanical System Boiler with unit ventilators in larger spaces and small units in attic for smaller offi ces. No A/C G. Fuel Source Gas H. Controls Pneumatic with time clocks I. Water City water

203 J. Electrical Schedule 25 K. Security System Mountain Alarm L. Intercom System None M. Clocks None N. Fire Alarm Edwards 202 Bremerton School District Study and Survey March 15, 2012

204 ADMINISTRATION BUILDING 203

205 Building Condition Assessment Summary Form School District: Bremerton School District 204 Facility Name: Administration Building Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Administrative Overall BCA Score: Component Component Score BCA Score A10 Foundations 4.74 A1010 Standard Foundation 90% 4.74 A20 Walls 0.00 A2020 Walls for subgrade enclosure 81% 0.00 A40 Slabs on Grade 0.00 A4010 Standard Slabs on Grade 86% 0.00 A4040 Pits and Bases N/A N/A A60 Building Subdrainage 0.00 A6010 Building Subdrainage Not Rated Not Rated B10 Superstructure 6.97 B1010 Floor Construction 83% 3.13 B1020 Roof Construction 63% 3.84 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures 8.63 B2010 Exterior Walls 69% 4.50 B2020 Exterior Windows 81% 2.43 B2050 Exterior Doors and Grilles 80% 1.60 B2070 Exterior Louvers and Vents 60% 0.10 B30 Exterior Horizontal Enclosures 3.41 B3010 Roofing 48% 3.21 B3020 Roof Appurtenances 56% 0.07 B3060 Horizontal Openings/Penetrations 65% 0.06 B3080 Overhead Exterior Enclosures 75% 0.07 C10 Interior Construction 7.62 C1010 Interior Partitions 90% 2.48 C1020 Interior Windows 90% 0.22 C1030 Interior Doors 90% 3.66 C1040 Interior Grilles and Grates 90% 0.09 C1060 Raised floor construction N/A N/A C1070 Suspended Ceiling Const. 90% 1.18 C20 Interior Finishes 9.54 C2010 Wall Finishes 99% 0.91 C2020 Interior Fabrications 99% 0.04 C2030 Flooring 83% 5.19 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

206 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 86% 3.40 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures 3.07 D2010 Domestic Water Distribution 73% 0.67 D2020 Sanitary Drainage 90% 0.51 D2030 Building Support Plumbing Systems 45% 1.89 D2050 General Services Compressed Air 72% 0.00 D30 HVAC 7.87 D3010 Facility Fuel Systems 90% 1.02 D3020 Heating Systems 56% 5.77 D3030 Cooling Systems Not Rated Not Rated D3050 Facility HVAC Dist. System 36% 0.82 D3060 Ventilation 36% 0.26 D40 Fire Protection 3.15 D4010 Fires Suppression 90% 2.71 D4030 Fire Suppression Specialties 90% 0.44 D50 Electrical D5010 Facility Power Generation 90% 0.00 D5020 Electrical Service and Distribution 90% 3.86 D5030 General Purpose Electrical Power 60% 0.26 D5040 Lighting 96% 9.25 D60 Communication 1.92 D6010 Data Communications 90% 0.73 D6020 Voice Communications 60% 0.97 D6030 Audio Video Communication 90% 0.22 D6060 Distributed Comm/Monitoring Not Rated Not Rated D70 Electronic Safety and Security 0.72 D7010 Access Control and Intrusion Defection 100% 0.24 D7030 Electronic Surveillance 100% 0.24 D7050 Detection and Alarm 96% 0.23 D80 Integrated Automation 0.00 D8010 Integrated Automation Facility Controls 0% 0.00 E10 Equipment 0.00 E1010 Vehicle and Pedestrian Equipment 90% 0.00 E1030 Commercial Equipment 90% 0.00 E1040 Institutional Equipment 90% 0.00 E1070 Entertainment and Recreational Equipment N/A N/A E1090 Other Equipment 90% 0.00 E20 Furnishings 0.37 E2010 Fixed Furnishings 90% 0.22 E2050 Movable Furnishings 90%

207 206 Building Condition Assessment Scoring Form Bremerton School District Administration Building Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Administrative Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories structuraly sound some settling over the years A1010 Standard Foundation 90% Cracks & Separation X % Drainage X % Vegetation X 0.1 9% Water Leaks X % A2020 Walls for subgrade enclosure 81% Cracks & Separation X N/A % Drainage x N/A % Vegetation X N/A 0.1 9% Water Penetration X N/A % A4010 Standard Slabs on Grade 86% Levelness X N/A % Soft spots, swelling or settling X N/A 0.1 9% Structural damage X N/A % Water Penetration X N/A % A4040 Pits and Bases N/A Settling N/A 0.3 N/A Water Penetration N/A 0.3 N/A Structural damage N/A 0.4 N/A A6010 Building Subdrainage Not Rated Drainage 0.3 Not Rated Membrane integrity 0.4 Not Rated Bremerton School District Study and Survey March 15, 2012

208 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Asphalt roof is in need of replacement windows installed in the 80's are double pane Settling 0.3 Not Rated B1010 Floor Construction 83% Levelness X % Soft spots, swelling or settling X % Structural damage X % B1020 Roof Construction 63% Water Penetration X % Levelness of ridges, eaves, gables, etc. X 0.1 6% Soft spots, swelling or settling X 0.1 6% Structural damage X % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 69% Water Penetration X % Plumbness X % Warpage, swelling or settling X % Structural damage X % B2020 Exterior Windows 81% Water Penetration X % Weather stripping X % Window insulation failure X % Structural damage X % B2050 Exterior Doors and Grilles 80% Hinges X % Locks X % Door X % Closers X 0.1 9% Windows & Grills X 0.1 9% Weather stripping X 0.1 6% B2070 Exterior Louvers and Vents 60% Structural damage X % Screens X % Components secure X % B3010 Roofing 48% Safety systems X 0.1 6% Slopes and runoffs X % Asphalt roof is in need of replacement Gutters, downspouts, scuppers, roof drains, etc. X % 207

209 208 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Cracks, separations, damaged or missing materials, weather sealant, etc. X % B3020 Roof Appurtenances 56% Structural damage X 0.1 9% Flashings X % Components secure X % Weather hoods X % B3060 Horizontal Openings/Penetrations 65% Structural damage (ducts, chimneys, etc.) X 0.1 6% Flashings X % Components secure X % Weather seals X % Glazing X % B3080 Overhead Exterior Enclosures 75% Support structure X % Components secure X % Coverings X % C1010 Interior Partitions 90% Water Damage X % Plumbness X % Warpage, swelling or settling X % Structural damage X % C1020 Interior Windows 90% Window insulation failure X % Structural damage X % C1030 Interior Doors 90% Locks X % Closers X % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) X % Lites X 0.1 9% C1040 Interior Grilles and Grates 90% Structural damage (vanes, separation, etc.) X % Components secure X % C1060 Raised floor construction N/A Levelness N/A 0.25 N/A Soft spots, swelling or settling N/A 0.3 N/A Structural damage N/A 0.45 N/A Bremerton School District Study and Survey March 15, 2012

210 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories redone in installed in 1997 and starting to show some wear showing wear since some is glue on tile that as refinished in 1997 but is starting to be dated C1070 Suspended Ceiling Const. 90% Levelness X % Components secure X % Structural damage (sagging, separation, breakage. etc.) X % Water Damage X % C2010 Wall Finishes 99% Water Damage X % Aesthetics X % Chipping, swelling, flaking or settling X % Structural damage X % C2020 Interior Fabrications 99% Water Damage X % Aesthetics X % Chipping, swelling, flaking or settling X % Structural damage X % C2030 Flooring 83% Water Damage x % Aesthetics x % Chipping, swelling, flaking, scoring, etc. x 0.1 9% Structural damage x % Sealant x % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 86% Water Damage X % Aesthetics x % Chipping, swelling, flaking, scoring, etc. X 0.1 9% Structural damage X % Penetrations X % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 73% Pressure X 0.1 9% Water quality X % Leakage X 0.1 9% 209

211 210 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories no sprinklers in the building air controls for heating air controls with a time clock needs updated fixed supply air louvers evaporator in Sups area, and AC in computer serverver area Many unit vetalators for each large space. Installed in the 80's and noisey plus very little control for comfort Fixtures X 0.1 9% Water heaters X % Backflow prevention X % D2020 Sanitary Drainage 90% Flow X % Vents X 0.1 9% Traps X % Clean outs X 0.1 9% D2030 Building Support Plumbing Systems 45% Sewer/Septic System X % Fire loop X 0.5 0% D2050 General Services Compressed Air 72% Compressor X N/A % Distribution X N/A % Controls X N/A 0.3 9% D3010 Facility Fuel Systems 90% Distribution x % Controls x % D3020 Heating Systems 56% Heating Unit X % Controls X % Supply Air x 0.1 6% D3030 Cooling Systems Not Rated Cooling Unit X % Controls X % Supply Air 0.1 Not Rated D3050 Facility HVAC Dist. System 36% Supply & Return X % Ducting/Piping X % Controls X 0.4 0% D3060 Ventilation 36% Fans Supply & Exhaust X % Ducting/Piping X % Controls X 0.4 0% D4010 Fires Suppression 90% Up to Date Inspection x 1 90% D4030 Fire Suppression Specialties 100% Up to Date Inspection X % None Bremerton School District Study and Survey March 15, 2012

212 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories somevery old panels in for some areas Aging VOIP system; components failing said to be unsupported in 3 4 years Components secure X % D5010 Facility Power Generation 90% Test schedule X N/A % Maintenance schedule X N/A % Generator unit X N/A % Controls X N/A % D5020 Electrical Service and Distribution 90% Transformers X % Vaults X % Main Subpanels X % EMT, wiring X % Motors X % D5030 General Purpose Electrical Power 60% Branch panels X % Branch wiring X % D5040 Lighting 96% Fixtures X % Switches, wiring X 0.1 9% Controls X % Coverage X % D6010 Data Communications 90% Components X % Distribution X % Controls X 0.1 9% Connectivity X % D6020 Voice Communications 60% Components x % Distribution x % Controls x 0.1 6% D6030 Audio Video Communication 90% Components X % Distribution X % Controls X 0.1 9% D6060 Distributed Comm/Monitoring Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated D7010 Access Control and Intrusion Defection 100% Components X % Distribution X % None 211

213 212 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None use pnumatic controls for heating gates only and they work Controls X % D7030 Electronic Surveillance 100% Components X % Distribution X % Controls X % Coverage X % D7050 Detection and Alarm 96% Components X 0.1 9% Distribution X 0.1 9% Controls X % Up to Date Inspection X % Coverage X 0.1 9% D8010 Integrated Automation Facility Controls 0% Components x % Distribution x % Controls x 0.1 0% E1010 Vehicle and Pedestrian Equipment 90% Components X N/A % Controls X N/A % E1030 Commercial Equipment 90% General equipment condition x N/A % Functionality x N/A % E1040 Institutional Equipment 90% General equipment condition x N/A % Functionality x N/A % E1070 Entertainment and Recreational Equipment N/A General equipment condition N/A 0.75 N/A Functionality N/A 0.25 N/A E1090 Other Equipment 90% General equipment condition x N/A % Functionality x N/A % E2010 Fixed Furnishings 90% General furnishing condition X % Functionality X % E2050 Movable Furnishings 90% General furnishing condition X % Functionality X % audio/visual equipment is good None Bremerton School District Study and Survey March 15, 2012

214 Consolidated Facilities 213 Aerial Photo

215 214 Bremerton School District Study and Survey March 15, 2012

216 A. General - Facility Basic Information Name Address 200 Bruenn Avenue Bremerton, WA Academic Grade Levels N/A Area of Site 3.5 Tax Parcels Building Area to date 40,100 Number of Buildings 1 Year Built 1947 Modernizations and 1985 converted to support building Additions, (Date and Sq Ft) Total number of classrooms N/A Capacity/Enrollment N/A Consolidated Facilities B. Site Consolidated Facilities sits on an industrial site, This site is the location for the District transportation, warehouse, grounds and maintenance departments. Needs parking for busses,,trucks, and service equipment and maintenance vehicles and parking for bus drivers and maintenance people. C. Exterior Walls Masonry and wood frame 215 D. Roof Wood frame fl at roof with built up roofi ng system E. Storm Water Control City storm F. Mechanical System Electric resistance heating in all occupied spaces G. Fuel Source Electric H. Controls In some individual thermostats with an old load shedding controls

217 I. Water City J. Electrical PSE schedule 43 K. Security System none L. Intercom System none M. Clocks none N. Fire Alarm Old Gamewell Zans 200 O. Fire Sprinkler In paint shop and fi re storage room 216 Bremerton School District Study and Survey March 15, 2012

218 CONSOLIDATED FACILITIES SITE 217

219 218 CONSOLIDATED FACILITIES Bremerton School District Study and Survey March 15, 2012

220 Area Calculations for: Consolidated Facilities Bremerton School District #100-C Bremerton, Washington Area Number Area Name SF Factor Totals* Main Building 1 30,673 30,

221 Building Condition Assessment Summary Form School District: Bremerton School District 220 Facility Name: Consolidated Facilities Building Name: Evaluator's Name: Kevin Flanagan & Ron Carpenter Evaluator's Company: NAC Architecture & Bremerton School District Date: 10/31/2011 Building Type: Maintenance and Operations Overall BCA Score: Component Component Score BCA Score A10 Foundations 0.81 A1010 Standard Foundation 38% 0.81 A20 Walls 0.00 A2020 Walls for subgrade enclosure N/A N/A A40 Slabs on Grade 4.92 A4010 Standard Slabs on Grade 56% 4.92 A4040 Pits and Bases 30% 0.00 A60 Building Subdrainage 1.15 A6010 Building Subdrainage 39% 1.15 B10 Superstructure 1.44 B1010 Floor Construction 24% 0.00 B1020 Roof Construction 14% 1.44 B1080 Stairs N/A N/A B20 Exterior Vertical Enclosures 8.75 B2010 Exterior Walls 47% 1.99 B2020 Exterior Windows 14% 1.78 B2050 Exterior Doors and Grilles 48% 4.96 B2070 Exterior Louvers and Vents 30% 0.02 B30 Exterior Horizontal Enclosures 0.32 B3010 Roofing 0% 0.00 B3020 Roof Appurtenances 23% 0.06 B3060 Horizontal Openings/Penetrations 26% 0.04 B3080 Overhead Exterior Enclosures 30% 0.23 C10 Interior Construction 0.35 C1010 Interior Partitions 17% 0.09 C1020 Interior Windows Not Rated Not Rated C1030 Interior Doors 60% 0.15 C1040 Interior Grilles and Grates N/A N/A C1060 Raised floor construction 51% 0.00 C1070 Suspended Ceiling Const. 53% 0.11 C20 Interior Finishes 0.92 C2010 Wall Finishes 33% 0.04 C2020 Interior Fabrications 30% 0.03 C2030 Flooring 41% 0.81 C2040 Stair Finishes N/A N/A Bremerton School District Study and Survey March 15, 2012

222 OSPI Building Condition Assessment Summary Form Component Component Score BCA Score C2050 Ceiling Finishes 33% 0.03 D10 Conveying 0.00 D1010 Vertical Conveying Systems N/A N/A D20 Plumbing Fixtures 4.60 D2010 Domestic Water Distribution 72% 3.79 D2020 Sanitary Drainage 71% 0.71 D2030 Building Support Plumbing Systems 60% 0.06 D2050 General Services Compressed Air 90% 0.05 D30 HVAC 3.35 D3010 Facility Fuel Systems Not Rated Not Rated D3020 Heating Systems 41% 3.20 D3030 Cooling Systems N/A N/A D3050 Facility HVAC Dist. System Not Rated Not Rated D3060 Ventilation 48% 0.15 D40 Fire Protection 0.82 D4010 Fires Suppression 60% 0.81 D4030 Fire Suppression Specialties 60% 0.01 D50 Electrical 5.39 D5010 Facility Power Generation Not Rated Not Rated D5020 Electrical Service and Distribution 83% 0.87 D5030 General Purpose Electrical Power 30% 0.30 D5040 Lighting 36% 4.23 D60 Communication 3.60 D6010 Data Communications 90% 1.80 D6020 Voice Communications 90% 1.80 D6030 Audio Video Communication Not Rated Not Rated D6060 Distributed Comm/Monitoring Not Rated Not Rated D70 Electronic Safety and Security 0.17 D7010 Access Control and Intrusion Defection Not Rated Not Rated D7030 Electronic Surveillance Not Rated Not Rated D7050 Detection and Alarm 85% 0.17 D80 Integrated Automation 0.00 D8010 Integrated Automation Facility Controls Not Rated Not Rated E10 Equipment 0.08 E1010 Vehicle and Pedestrian Equipment 60% 0.00 E1030 Commercial Equipment 60% 0.00 E1040 Institutional Equipment 60% 0.00 E1070 Entertainment and Recreational Equipment N/A N/A E1090 Other Equipment 60% 0.08 E20 Furnishings 0.18 E2010 Fixed Furnishings Not Rated Not Rated E2050 Movable Furnishings 60%

223 222 Building Condition Assessment Scoring Form Bremerton School District Consolidated Facilities Kevin Flanagan & Ron Carpenter NAC Architecture & Bremerton School District 10/31/2011 School District: Facility Name: Building Name: Evaluator's Name: Evaluator's Company: Date: Excellent (E): New or easily restorable to like new condition; only minimal routine maintenance required. Good (G): Some Preventative maintenance and/or corrective repair required. Fair (F): Fails to meet code and functional requirements in some cases; failure(s) are inconvenient; extensive corrective maintenance and repair required. Poor (P): Consistent substandard performance; failures(s) are disruptive and costly; fails most code and functional requirements; requires constant attention, renovation, or replacement. Major Corrective repair or overhaul required. Unsatisfactory (U): Non operational or significantly substandard performance. Replacement required. Maintenance and Operations Building Profile Type: Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Old 1040's foundation still holding but is starting to have problems None Slab on grade in part of the warehouse area that was installed in the 80's old boiler room is blow grade and has water problems and condensate problem because of lack of ventalation Asbestos area and connot enter but have been told there is standing water under sounth end of the buidling A1010 Standard Foundation 38% Cracks & Separation X 0.3 9% Drainage X % Vegetation X 0.1 3% Water Leaks X % A2020 Walls for subgrade enclosure N/A Cracks & Separation N/A 0.3 N/A Drainage N/A 0.25 N/A Vegetation N/A 0.1 N/A Water Penetration N/A 0.35 N/A A4010 Standard Slabs on Grade 56% Levelness X % Soft spots, swelling or settling X 0.1 6% Structural damage X % Water Penetration X % A4040 Pits and Bases 30% Settling X N/A 0.3 9% Water Penetration X N/A 0.3 9% Structural damage X N/A % A6010 Building Subdrainage 39% Drainage X 0.3 9% Membrane integrity X % Bremerton School District Study and Survey March 15, 2012

224 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories wood floor is level but in poor shape. No finish left and is deteriating. flat roof is in bad shape and has been patched for the past 20 years to attempt to keep out water. None keeps out elemets but is in poor shape with no maintenace performed over the past 20 years. Needs insulation. Old wood frame indows with single ply glass. Putty is failing and are difficult to open. Old doors with adequate locks and hardware for security. Old vents that are needed for rest rooms and other areas work. There are not screens. Flat roof with no upgraded safety systems. Gutters undersized and many miising sealants that have cracked or been damaged by birds over the years Settling X % B1010 Floor Construction 24% Levelness X N/A % Soft spots, swelling or settling X N/A 0.3 9% Structural damage X N/A % B1020 Roof Construction 14% Water Penetration X % Levelness of ridges, eaves, gables, etc. X 0.1 0% Soft spots, swelling or settling X 0.1 0% Structural damage X % B1080 Stairs N/A Structural damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A B2010 Exterior Walls 47% Water Penetration X 0.3 9% Plumbness X % Warpage, swelling or settling X % Structural damage X % B2020 Exterior Windows 14% Water Penetration X 0.3 9% Weather stripping X % Window insulation failure X 0.4 0% Structural damage X % B2050 Exterior Doors and Grilles 48% Hinges X 0.2 6% Locks X % Door X % Closers X 0.1 6% Windows & Grills X 0.1 3% Weather stripping X 0.1 3% B2070 Exterior Louvers and Vents 30% Structural damage X % Screens X % Components secure X % B3010 Roofing 0% Safety systems X 0.1 0% Slopes and runoffs X % Gutters, downspouts, scuppers, roof drains, etc. X % 223

225 224 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories All flashing have failed and are now caulking material. Everyhting else is old and deteriating. all in very poor shape porches in poor shape Most are lathe and plaster and have erosion from water and peeling paint. Cracks, separations, damaged or missing materials, weather sealant, etc. X 0.4 0% B3020 Roof Appurtenances 23% Structural damage X 0.1 3% Flashings X % Components secure X % Weather hoods X % B3060 Horizontal Openings/Penetrations 26% Structural damage (ducts, chimneys, etc.) X 0.1 6% Flashings X % Components secure X % Weather seals X % Glazing X % B3080 Overhead Exterior Enclosures 30% Support structure X % Components secure X % Coverings X % C1010 Interior Partitions 17% Water Damage X 0.3 0% Plumbness X % Warpage, swelling or settling X % Structural damage X % C1020 Interior Windows Not Rated Window insulation failure 0.5 Not Rated Structural damage 0.5 Not Rated C1030 Interior Doors 60% Locks X % Closers X % Structural damage (cracks, warpage, swelling or settling, rust, separation, alignment, etc.) X % Lites X 0.1 6% C1040 Interior Grilles and Grates N/A None Locks secure areas and that is about it. None wood flooring is level but wearing Structural damage (vanes, separation, etc.) N/A 0.55 N/A Components secure N/A 0.45 N/A C1060 Raised floor construction 51% Levelness X N/A % Soft spots, swelling or settling X N/A 0.3 9% Structural damage X N/A % Bremerton School District Study and Survey March 15, 2012

226 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories Where there is grid is was installed in the 80's and has some water damge. Water damage and peeling paint or no paint left. All in poor shape concrete okay for warehouse but the rest of the flooring is in very poor shape C1070 Suspended Ceiling Const. 53% Levelness X % Components secure X % Structural damage (sagging, separation, breakage. etc.) X % Water Damage X % C2010 Wall Finishes 33% Water Damage X 0.3 9% Aesthetics X % Chipping, swelling, flaking or settling X % Structural damage X % C2020 Interior Fabrications 30% Water Damage X 0.3 9% Aesthetics X % Chipping, swelling, flaking or settling X % Structural damage X % C2030 Flooring 41% Water Damage X % Aesthetics X % Chipping, swelling, flaking, scoring, etc. X 0.1 3% Structural damage X % Sealant X % C2040 Stair Finishes N/A Structural Damage N/A 0.5 N/A Settling N/A 0.25 N/A Components secure N/A 0.25 N/A C2050 Ceiling Finishes 33% Water Damage X % Aesthetics X % Chipping, swelling, flaking, scoring, etc. X 0.1 3% Structural damage X % Penetrations X % D1010 Vertical Conveying Systems N/A Inspections Current N/A 0.9 N/A Aesthetics N/A 0.05 N/A Functionality N/A 0.05 N/A D2010 Domestic Water Distribution 72% Pressure X 0.1 9% Water quality X % Leakage X 0.1 9% None Water damaged ceiling with patchwork covering areas, the rest is in need of maintenance None System is old but well maintained 225

227 226 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories old but is working fine tied to the city sewer system and there is no fire loop compressors for shops are adequate and working. All electric All electric strip resistance heat. Wall thermastat controls Fixtures X 0.1 9% Water heaters X % Backflow prevention X % D2020 Sanitary Drainage 71% Flow X % Vents X 0.1 9% Traps X % Clean outs X 0.1 9% D2030 Building Support Plumbing Systems 60% Sewer/Septic System X % Fire loop X % D2050 General Services Compressed Air 90% Compressor X % Distribution X % Controls X % D3010 Facility Fuel Systems Not Rated Distribution 0.5 Not Rated Controls 0.5 Not Rated D3020 Heating Systems 41% Heating Unit X % Controls X % Supply Air X 0.1 3% D3030 Cooling Systems N/A Cooling Unit N/A 0.55 N/A Controls N/A 0.35 N/A Supply Air N/A 0.1 N/A D3050 Facility HVAC Dist. System Not Rated Supply & Return 0.3 Not Rated Ducting/Piping 0.3 Not Rated Controls 0.4 Not Rated D3060 Ventilation 48% Fans Supply & Exhaust X % Ducting/Piping X % Controls X % D4010 Fires Suppression 60% Up to Date Inspection X 1 60% D4030 Fire Suppression Specialties 90% Up to Date Inspection X % In old print room and not used. None vents work as designed and windows open sprinkler system in the paint shop and a storage room. extinguishers are where required and certified annually Bremerton School District Study and Survey March 15, 2012

228 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None New service installed in the 80's when kitchen was here and is in good shape Still some fuse panels with the old wiring left in the building. old technology with t 12"s in placed as needed. Switch controls. upgraded in 2008 Components secure X % D5010 Facility Power Generation Not Rated Test schedule 0.15 Not Rated Maintenance schedule 0.15 Not Rated Generator unit 0.4 Not Rated Controls 0.3 Not Rated D5020 Electrical Service and Distribution 83% Transformers X % Vaults X % Main Subpanels X % EMT, wiring X % Motors X % D5030 General Purpose Electrical Power 30% Branch panels X % Branch wiring X % D5040 Lighting 36% Fixtures X % Switches, wiring X 0.1 3% Controls X % Coverage X % D6010 Data Communications 90% Components X % Distribution X % Controls X 0.1 9% Connectivity X % D6020 Voice Communications 90% Components X % Distribution X % Controls X 0.1 9% D6030 Audio Video Communication Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated D6060 Distributed Comm/Monitoring Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated D7010 Access Control and Intrusion Defection Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated upgraded in 2008 None None None 227

229 228 OSPI Building Condition Evaluation Form 12/28/20 Notes Component Score Assessment Category Score E G F P U N/A Weight Component and Component Assessment Categories None Old fire panel still passes confidence tests but uses old devices. docks gates and equipment work and are serviceble Controls 0.1 Not Rated D7030 Electronic Surveillance Not Rated Components 0.45 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated Coverage 0.2 Not Rated D7050 Detection and Alarm 85% Components X 0.1 9% Distribution X 0.1 6% Controls X % Up to Date Inspection X % Coverage X 0.1 6% D8010 Integrated Automation Facility Controls Not Rated Components 0.65 Not Rated Distribution 0.25 Not Rated Controls 0.1 Not Rated E1010 Vehicle and Pedestrian Equipment 60% Components X N/A % Controls X N/A % E1030 Commercial Equipment 60% General equipment condition X N/A % Functionality X N/A % E1040 Institutional Equipment 60% General equipment condition X N/A % Functionality X N/A % E1070 Entertainment and Recreational Equipment N/A General equipment condition N/A 0.75 N/A Functionality N/A 0.25 N/A E1090 Other Equipment 60% General equipment condition X % Functionality X % E2010 Fixed Furnishings Not Rated General furnishing condition 0.75 Not Rated Functionality 0.25 Not Rated E2050 Movable Furnishings 60% General furnishing condition X % Functionality X % adequate for building shop equipment adequate None adequate for building None adequate for building Bremerton School District Study and Survey March 15, 2012

230 Child Nutritional Services Center 229 Aerial Photo

FACILITY COMPONENTS - MIDDLE SCHOOL

FACILITY COMPONENTS - MIDDLE SCHOOL SITE AREAS Parking and Access - Buses 2.0 2.0 0.30 Parking and Access - Serv. / Delivery 3.0 1.0 0.22 Parking and Access - Staff 4.0 3.0 0.89 Parking and Access - Visitors 1.0 3.0 0.22 Four fewer stalls

More information

Timberglen Recreation Center Summary

Timberglen Recreation Center Summary Timberglen Recreation Center Summary Address Building Purpose 3810 Timberglen Road Dallas, TX 75287 Recreation Center Original Year of Construction 2003 Building Area 15,000 SF Inspection Date August 2,

More information

School Without Walls

School Without Walls INITIAL YEAR BUILT 1938 BUILDING AREA 59,400 SF CURRENT PROGRAM CAPACITY 304 ENROLLMENT 2008 276 WARD 1 PROPOSED PROGRAM CAPACITY 400 SCHOOL WITHOUT WALLS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

INFORMATION AND OF SCHOOLS -------2016-2017------- FACILITY BUILDING NAME BUILDING BOARD ACCEPTANCE DATE APP YEAR BUILDING ASSESSMENT % ANNUAL REVIEW COMPLETED BY NEXT CERTIFIED BCA DUE Beaver Lake Middle

More information

FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - ELEMENTARY SCHOOL SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Five fewer bus stalls than minimum standard. Parking and Access - Service / Delivery 1.0 1.0 0.08 No delivery parking adjacent to delivery entrance. Parking

More information

School Assessment Report

School Assessment Report School Assessment Report School: Morningside Elementary School Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:29:07 AM FOR OFFICIAL USE ONLY Final School Assessment

More information

FACILITY COMPONENTS - ELEMENTARY SCHOOL

FACILITY COMPONENTS - ELEMENTARY SCHOOL SITE AREAS Parking and Access - Buses 1.0 2.0 0.16 Two stalls fewer than minimum standard. Parking and Access - Service / Delivery 2.0 1.0 0.16 Parking and Access - Staff 1.0 3.0 0.24 Thirty-seven stalls

More information

School Assessment Report

School Assessment Report School Assessment Report School: Humphries Elementary School Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:35:17 AM FOR OFFICIAL USE ONLY Final School Assessment

More information

School Assessment Report

School Assessment Report School Assessment Report School: Carver High School Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:37:23 AM FOR OFFICIAL USE ONLY Final School Assessment Report

More information

School Assessment Report

School Assessment Report School Assessment Report School: Sutton Middle School (Powers Ferry) Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:32:59 AM FOR OFFICIAL USE ONLY Final School

More information

School Assessment Report

School Assessment Report School Assessment Report School: KIPP Vision Report: Dec 15, 14 Condition Assessment: Suitability Assessment: Generated: 12/15/14 12:33:33 PM Final School Assessment Report - Charter Schools, KIPP Vision

More information

Appendix J - Custom Uniformat for EDU Migration

Appendix J - Custom Uniformat for EDU Migration Appendix J - Custom Uniformat for EDU Migration Nr. MTC Uniformat for VFA.facility Life (Years) Weight (1-100) Out of Scope Cost Y/N 1 A Substructure 150 N 2 A10 Foundations 150 N 3 A1010 Standard Foundations

More information

LECKIE ELEMENTARY SCHOOL

LECKIE ELEMENTARY SCHOOL INITIAL YEAR BUILT 1970 BUILDING AREA 65,000 SF CURRENT PROGRAM CAPACITY 471 ENROLLMENT 2008 321 WARD 8 PROPOSED PROGRAM CAPACITY 400 Site Plan LECKIE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

School Assessment Report

School Assessment Report School Assessment Report School: Morningside Elementary School Report: Dec 15, 2014 Condition Assessment: Suitability Assessment: Generated: 12/15/2014 12:11:31 PM FOR OFFICIAL USE ONLY Final School Assessment

More information

EASTERN HIGH SCHOOL. Site Plan East Capitol Street, N.E., Washington, DC INITIAL YEAR BUILT 1923

EASTERN HIGH SCHOOL. Site Plan East Capitol Street, N.E., Washington, DC INITIAL YEAR BUILT 1923 INITIAL YEAR BUILT 1923 BUILDING AREA 288,800 SF CURRENT PROGRAM CAPACITY 1,425 ENROLLMENT 2008 565 WARD 6 PROPOSED PROGRAM CAPACITY 1,100 Site Plan EASTERN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

2016 BOND INFORMATION

2016 BOND INFORMATION 2016 BOND INFORMATION This publication is provided as a public service by the offices of Operations and Maintenance, Communications and Financial Services. www.svvsd.org @svvsd 395 South Pratt Parkway,

More information

LASALLE - BACKUS EDUCATION CAMPUS

LASALLE - BACKUS EDUCATION CAMPUS INITIAL YEAR BUILT 1957 BUILDING AREA 63,000 SF CURRENT PROGRAM CAPACITY 406 ENROLLMENT 2008 349 WARD 4 PROPOSED PROGRAM CAPACITY 425 Site Plan LASALLE - BACKUS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

RAYMOND EDUCATION CAMPUS

RAYMOND EDUCATION CAMPUS INITIAL YEAR BUILT 1924 BUILDING AREA 73,600 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 302 WARD 1 PROPOSED PROGRAM CAPACITY 600 Site Plan RAYMOND - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

Mills Elementary School Site Summary

Mills Elementary School Site Summary 1 Mills Elementary School Site Summary Address 6201 Davis Lane Austin, TX 78749 Number of Permanent Campus Facilities 1 Original Year of Construction 1998 Total Campus Building Area (combined) 81,368 SF

More information

WATKINS ELEMENTARY SCHOOL

WATKINS ELEMENTARY SCHOOL INITIAL YEAR BUILT 1962 BUILDING AREA 69,300 SF CURRENT PROGRAM CAPACITY 578 ENROLLMENT 2008 550 WARD 6 PROPOSED PROGRAM CAPACITY 550 Site Plan WATKINS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

COOLIDGE SENIOR HIGH SCHOOL

COOLIDGE SENIOR HIGH SCHOOL INITIAL YEAR BUILT 1940 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1240 ENROLLMENT 2008 652 WARD 4 PROPOSED PROGRAM CAPACITY 1100 Site Plan COOLIDGE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

POWELL ELEMENTARY SCHOOL

POWELL ELEMENTARY SCHOOL INITIAL YEAR BUILT 1925 BUILDING AREA 38,500 SF CURRENT PROGRAM CAPACITY 304 ENROLLMENT 2008 319 WARD 4 PROPOSED PROGRAM CAPACITY 325 Site Plan POWELL - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-3

More information

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN

LOGAN SCHOOL SCHOOL WITHOUT WALLS AT LOGAN INITIAL YEAR BUILT 1935 BUILDING AREA 47,200 SF CURRENT PROGRAM CAPACITY 479 ENROLLMENT 2008 418 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan LOGAN - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION HS

More information

WILKINSON ELEMENTARY SCHOOL

WILKINSON ELEMENTARY SCHOOL INITIAL YEAR BUILT 1976 BUILDING AREA 144,900 SF CURRENT PROGRAM CAPACITY 508 ENROLLMENT 2008 451 WARD 8 PROPOSED PROGRAM CAPACITY 600 Site Plan WILKINSON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

SEATON ELEMENTARY SCHOOL

SEATON ELEMENTARY SCHOOL INITIAL YEAR BUILT 1969 BUILDING AREA 65,000 SF CURRENT PROGRAM CAPACITY 428 ENROLLMENT 2008 280 WARD 2 PROPOSED PROGRAM CAPACITY 325 Site Plan SEATON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Corsicana High School

Corsicana High School Contents Corsicana High School...2 General comments, campus capacity, and student demographics...2 1.0 School Site...4 2.0 Building Systems and Components...6 3.0 Building Safety and Security...19 4.0

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % BartelsRode Gymnasium 8/11/ Building Rating System Percent Site: 1.0 Total 0 13 77% Building: 2.1 Building Exterior Elements 0 8 8% 2.2 Accessibility 0 74 74% 2.3 Structural 0 76 76% 2.4 Building Envelope

More information

Cheldelin Middle School

Cheldelin Middle School Facility Information Address: 987 NE Conifer Blvd Corvallis Site Size: Building Area: Construction Date: Improved Parking: Grade Levels Served: Regular Classrooms: Portable Classrooms: Sept. 2007 Enrollment:

More information

Thurgood Marshall Recreation Center Summary

Thurgood Marshall Recreation Center Summary Thurgood Marshall Recreation Center Summary Address Building Purpose 5150 Mark Trail Way Dallas, TX 75232 Recreation Center Original Year of Construction 1970 Building Area 21,300 SF Inspection Date August

More information

SITE AND BUILDING INSPECTION CHECKLIST

SITE AND BUILDING INSPECTION CHECKLIST PARISH BUILDING Page 1 of 6 SITE AND GROUNDS DATE INIT COMMENTS DATE INIT COMMENTS Ramps & Provisions for Handicap Designated parking spaces for Handicap Has soil dropped or heaved Is there standing water

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % 8/11/ Building Rating System Percent Site: 1.0 Total 0 163 82% Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 92 92% 2.3 Structural 0 91 91% 2.4 Building Envelope 0 84 84% 2. Interior

More information

Lake Highlands North Recreation Center Summary

Lake Highlands North Recreation Center Summary Lake Highlands North Recreation Center Summary Address Building Purpose 9940 White Rock Trail Dallas, TX 75238 Recreation Center Original Year of Construction 1971 Building Area 33,036 SF Inspection Date

More information

Facilities Feasibility Study Matthew A. Henson ES Condition Assessment

Facilities Feasibility Study Matthew A. Henson ES Condition Assessment Summary of Findings The Matthew A. Henson ES Facility located at 1600 N. Payson Street in Baltimore, Maryland, was built in 1964. It comprises 75,228 gross square feet. The total current deficiencies for

More information

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural %

1.0 Total Points % 2.1 Building Exterior Elements % 2.2 Accessibility % 2.3 Structural % 8/11/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 82 82% 2.2 Accessibility 0 82 82% 2.3 Structural 0 7 7% 2.4 Building Envelope 0 47 47% 2. Interior

More information

BALLOU SENIOR HIGH SCHOOL

BALLOU SENIOR HIGH SCHOOL INITIAL YEAR BUILT 1960 BUILDING AREA 271,300 SF CURRENT PROGRAM CAPACITY 1565 ENROLLMENT 2008 9-12 (1,252) STAY (753) WARD 8 PROPOSED PROGRAM CAPACITY 1200 Site Plan BALLOU - 1 PROPOSED PROGRAM PROFILE

More information

Minuteman Regional Vocational Technical School

Minuteman Regional Vocational Technical School Minuteman Regional Vocational Technical School List of Recommendations L1 AAB compliance: Improvements to front entrance (concrete ramps, railings, etc.) Required by AAB cost trigger L2 AAB compliance:

More information

DAVIS ELEMENTARY SCHOOL

DAVIS ELEMENTARY SCHOOL INITIAL YEAR BUILT 1943 BUILDING AREA 71,100 SF CURRENT PROGRAM CAPACITY 507 ENROLLMENT 2008 227 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan DAVIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-

More information

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018

Dr. Edward Livingston Trudeau Building. 118 Main Street, Saranac Lake, NY. Building Systems Report. June 24, 2018 G2 Gordon + Gordon Architecture. LLC Dr. Edward Livingston Trudeau Building 118 Main Street, Saranac Lake, NY Building Systems Report June 24, 2018 Harry Gordon, FAIA 164 Otter Slide Road Saranac Lake

More information

Harry Stone Recreation Center Summary

Harry Stone Recreation Center Summary Harry Stone Recreation Center Summary Address Building Purpose 2400 Millmar Drive Dallas, TX 75228 Recreation Center Original Year of Construction 1957 (Expansion 2013) Building Area 22,281 SF Inspection

More information

LEWIS ELEMENTARY SCHOOL

LEWIS ELEMENTARY SCHOOL INITIAL YEAR BUILT 1962 BUILDING AREA 49,500 SF CURRENT PROGRAM CAPACITY 550 ENROLLMENT 2008 288 WARD 1 PROPOSED PROGRAM CAPACITY 450 Site Plan LEWIS - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

GARFIELD ELEMENTARY SCHOOL

GARFIELD ELEMENTARY SCHOOL INITIAL YEAR BUILT 1910 BUILDING AREA 58,908 SF CURRENT PROGRAM CAPACITY 446 ENROLLMENT 2008 278 WARD 8 PROPOSED PROGRAM CAPACITY 400 Site Plan GARFIELD - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

Inspection Report. Property Address:

Inspection Report. Property Address: Inspection Report provided by: Safe Side Home Inspection Inspector: Corey Stuart TN License # 778 434 Margaret Circle McMinnville, TN 37110 safesideinspection@blomand.net Property Address: 1234 Anywhere

More information

Building Excellence IV Capital Levy Projects Under Construction

Building Excellence IV Capital Levy Projects Under Construction Building Excellence IV Capital Levy Projects Under Construction Project Slide Number Arbor Heights Elementary School 2 Cascadia Elementary School & Robert Eagle Staff Middle School 14 Genesee Hill Elementary

More information

NALLE ELEMENTARY SCHOOL

NALLE ELEMENTARY SCHOOL INITIAL YEAR BUILT 1950 BUILDING AREA 83,900 SF CURRENT PROGRAM CAPACITY 460 ENROLLMENT 2008 372 WARD 7 PROPOSED PROGRAM CAPACITY 400 Site Plan NALLE - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

Collins Middle School

Collins Middle School Contents Collins Middle School...2 General comments, campus capacity, and student demographics:...2 1.0 School Site...4 2.0 Building Systems and Components...5 3.0 Building Safety and Security...19 4.0

More information

ADDENDUM 2 - JULY 14, 2015

ADDENDUM 2 - JULY 14, 2015 7/9/2015 The Professional(s) of Record above has signed for the following specification sections: DIVISION 1 GENERAL REQUIREMENTS Section 01 10 00 Summary of Work Section 01 25 00 Substitution Procedures

More information

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP

PROCUREMENT AND CONTRACTING DOCUMENTS GROUP PROCUREMENT AND CONTRACTING DOCUMENTS GROUP DIVISION 00 - PROCUREMENT AND CONTRACTING REQUIREMENTS 00 11 00 Notice To Bidders 00 21 00 Instructions To Bidders 00 22 00 Supplementary Instructions To Bidders

More information

Invitation to Bid. RLS Construction Group requests your firm to submit a quotation on the following project:

Invitation to Bid. RLS Construction Group requests your firm to submit a quotation on the following project: RLS CONSTRUCTION GROUP Phone: 717-502-6680 Fax: 717-502-6681 www.rlscg.com Invitation to Bid RLS Construction Group requests your firm to submit a quotation on the following project: Project: Location:

More information

STUART-HOBSON MIDDLE SCHOOL

STUART-HOBSON MIDDLE SCHOOL INITIAL YEAR BUILT 1927 BUILDING AREA 105,900 SF CURRENT PROGRAM CAPACITY 460 ENROLLMENT 2008 399 WARD 6 PROPOSED PROGRAM CAPACITY 450 Site Plan STUART-HOBSON - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

SHEPHERD ELEMENTARY SCHOOL

SHEPHERD ELEMENTARY SCHOOL INITIAL YEAR BUILT 1932 BUILDING AREA 79,700 SF CURRENT PROGRAM CAPACITY 332 ENROLLMENT 2008 355 WARD 4 PROPOSED PROGRAM CAPACITY 400 Site Plan SHEPHERD - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

K.B. Polk Recreation Center Summary

K.B. Polk Recreation Center Summary K.B. Polk Recreation Center Summary Address Building Purpose 6801 Roper Street Dallas, TX 75209 Recreation Center Original Year of Construction 1988 Building Area 14,305 SF Inspection Date July 20, 2016

More information

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities

Table of Contents. Division 2 Site Work Site Preparation Site Demolition Tree Protection Excavation, Trenching, and Backfilling for Utilities Division 1 Requirements Design and Construction Quality Campus Master Plans Texas Tech University System Operating and Building Maintenance Project Administration Historically Underutilized Business (HUB)

More information

PLUMMER ELEMENTARY SCHOOL

PLUMMER ELEMENTARY SCHOOL INITIAL YEAR BUILT 1959 BUILDING AREA 69,400 SF CURRENT PROGRAM CAPACITY 481 ENROLLMENT 2008 228 WARD 7 PROPOSED PROGRAM CAPACITY 325 Site Plan PLUMMER - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION

More information

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT

DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT TABLE OF CONTENTS INTRODUCTORY INFORMATION 00 00 10 Title Page 00 00 20 Table of Contents DIVISION 0 - BIDDING REQUIREMENTS, CONTRACTOR FORMS AND CONDITIONS OF THE CONTRACT Section 00 02 00 Notice to Bidders

More information

National Property Inspections

National Property Inspections Monday, August 22, 2011 Inspector Joe Smith 548-254-3658 Page 1 of 33 GENERAL INFORMATION GENERAL CONDITIONS AT TIME OF INSPECTION : No Property Occupied : Property Faces : North South East þ West Year(s)

More information

School Assessment Report

School Assessment Report School Assessment Report School: Cascade Elementary School Report: Nov 17, 2015 Condition Assessment: Suitability Assessment: Generated: 11/17/2015 10:37:55 AM FOR OFFICIAL USE ONLY Final School Assessment

More information

TABLE OF CONTENTS Public Safety Building

TABLE OF CONTENTS Public Safety Building DOCUMENT 00 01 10 - TABLE OF CONTENTS VOLUME I DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS 00 01 10 Table of Contents 00 31 32 Geotechnical Data DIVISION 01 GENERAL REQUIREMENTS 01 10 00 Summary

More information

SECTION : OPERATION & MAINTENANCE MANUALS

SECTION : OPERATION & MAINTENANCE MANUALS SECTION 01 17 73: OPERATION & MAINTENANCE MANUALS 1. GENERAL: A. This section includes requirements for Contract Record - Operations and Maintenance manuals required prior to project closeout including,

More information

Alabama Home Inspections

Alabama Home Inspections Cover Page Property Inspection Report 1000 Sample Dr., Sampletown USA Inspection prepared for: Report Sample Inspection Date: 1/21/2010 Time: 400pm Size: Approx. 2,200sf Weather: Cloudy 62 Inspector: Bobby

More information

Overbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements %

Overbrook Theater / Fruenthal Foundation Art Center. 1.0 Total Points % 2.1 Building Exterior Elements % 8/13/ Building Rating System Percent Site: 1.0 Total 0 9 8 Building: 2.1 Building Exterior Elements 0 64 64% 2.2 Accessibility 0 66 66% 2.3 Structural 0 77 77% 2.4 Building Envelope 0 4 4% 2. Interior

More information

Biddeford School Department

Biddeford School Department Biddeford School Department 5 Plan Buildings, Grounds & Equipment Table of Contents: John F Kennedy Memorial School Page: 1-2 Biddeford Primary School Page: 3-4 Biddeford Intermediate School Page: 5-6

More information

Building Excellence IV Capital Levy Projects Under Construction

Building Excellence IV Capital Levy Projects Under Construction Building Excellence IV Capital Levy Projects Under Construction Project Slide Number Arbor Heights Elementary School 2 Cascadia Elementary School & Robert Eagle Staff Middle School 14 Genesee Hill Elementary

More information

Facilities Feasibility Study Laurence G. Paquin Building Condition Assessment

Facilities Feasibility Study Laurence G. Paquin Building Condition Assessment Summary of Findings The Laurence G. Paquin Building Facility located at 2200 SINCLAIR LANE in Baltimore, Maryland, was built in 1975. It comprises 65,666 gross square feet. The total current deficiencies

More information

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6

FRANKLIN VILLAGE APARTMENTS Building I Franklin Street Morristown, NJ Block: 3901 Lots: 4,5,6 PROJECT MANUAL for: FRANKLIN VILLAGE APARTMENTS Building I Morristown, NJ 07960 Block: 3901 Lots: 4,5,6 Owner: Atlantic Health Investment Corp. 200 American Road Morris Plains, NJ 07950 Architect NETTA

More information

Building Information Modeling (BIM) Execution Plan

Building Information Modeling (BIM) Execution Plan 10/19/2017 for [Stanford Project Name] [Stanford Project Number] Developed by [Primary A/E] TABLE OF CONTENTS USE OF THE BIM EXECUTION PLAN... 3 1. PROJECT INFORMATION... 3 2. PROJECT SCHEDULE AND MILESTONES...

More information

1234 Main St Denver CO 80210

1234 Main St Denver CO 80210 BEST HOME INSPECTIONS 555-555-5555 best@inspections.com https://www.spectora.com HOME INSPECTION REPORT 1234 Main St Denver CO 80210 NOVEMBER 21, 2016 Inspector John Smith sample@spectora.com Buyer Michael

More information

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011

Inspection Report. Prepared for: Yossi Berg. Property Address: 4925 Diggers Way Sugar Hill, GA. Date: July 20, 2011 Inspection Report Prepared for: Yossi Berg Property Address: Sugar Hill, GA. Date: July 20, 2011 Inspector: Charles Mann (770) 594-2222 www.edificeinspections.com Page 1 INSPECTION CONDITIONS CLIENT &

More information

Chenango Valley Central School District Potential Capital Project BCK-IBI Group Project No October 23, 2017

Chenango Valley Central School District Potential Capital Project BCK-IBI Group Project No October 23, 2017 Chenango Bridge Elementary School Phase 1 Asphalt Pavement Reconstruction Reconstruct asphalt parking located on west side of building including access drive. Sidewalk Replacement Replace cracked sections

More information

Madison School District. Strategic Five-Year Facility Maintenance Plan

Madison School District. Strategic Five-Year Facility Maintenance Plan Madison School District Strategic Five-Year Facility Maintenance Plan 2016 2020 Dear Madison Stakeholder, Throughout the past twenty years, Madison School District has experienced tremendous growth. Since

More information

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington

Franklin Hall Renovation TABLE OF Document Indiana University Bloomington VPS Project No. 2013022.00 Page 1 SPECIFICATIONS VOLUME I INTRODUCTORY INFORMATION Document 000010 - Table of Contents... 6 Document 000011 - Certification and Seals... 2 Document 000012 - Project Directory...

More information

Water Management & Damage Prevention: A Guide for Homeowners

Water Management & Damage Prevention: A Guide for Homeowners Water Management & Damage Prevention: A Guide for Homeowners This article provides homeowners with basic information to make these decisions and take the appropriate actions to keep their homes dry and

More information

MAURY ELEMENTARY SCHOOL

MAURY ELEMENTARY SCHOOL INITIAL YEAR BUILT 1886 BUILDING AREA 46,800 SF CURRENT PROGRAM CAPACITY 276 ENROLLMENT 2008 238 WARD 6 PROPOSED PROGRAM CAPACITY 325 Site Plan MAURY - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-5

More information

North Tonawanda City School District

North Tonawanda City School District N.T. CAPIT AL I MPROVE MENT PROJECT North Tonawanda City School District Vincent J. Vecchiarella Superintendent of Schools Special Edition April 2008 $48 Million Capital Project at NO COST to the Taxpayers

More information

LEVEL TWO NUMBERS AND TITLES. Introductory Information. Bidding Requirements. Contracting Requirements. Facilities and Spaces. Systems and Assemblies

LEVEL TWO NUMBERS AND TITLES. Introductory Information. Bidding Requirements. Contracting Requirements. Facilities and Spaces. Systems and Assemblies MasterFormat LEVEL TWO NUMBERS AND TITLES Introductory Information 00001 Project Title Page 00005 Certifications Page 00007 Seals Page 00010 Table of Contents 00015 List of Drawings 00020 List of Schedules

More information

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2

Deficiency ID Qty UoM Priority. K Play Area Requires Impact Resistant Material Ea. 2 School and Site Level Deficiencies Site K Play Area Requires Impact Resistant Material 1320 1 Ea. 2 Exterior Basketball Goals Are Damaged And Require Replacement 1322 1 Ea. 4 Bus drop-off area does not

More information

SYLVAN. inspire MIDDLE SCHOOL. which is to. instruction and programs. in a safe, caring, and. collaborative learning community.

SYLVAN. inspire MIDDLE SCHOOL. which is to. instruction and programs. in a safe, caring, and. collaborative learning community. SYLVAN MIDDLE SCHOOL The mission of Sylvan Middle School is consistent with that of the San Juan Unified School District, which is to inspire each student tosucceed and responsibly contribute to a radically

More information

NOYES EDUCATION CAMPUS

NOYES EDUCATION CAMPUS INITIAL YEAR BUILT 1930 BUILDING AREA 49,700 SF CURRENT PROGRAM CAPACITY 321 ENROLLMENT 2008 337 WARD 5 PROPOSED PROGRAM CAPACITY 450 Site Plan NOYES - 1 PROPOSED PROGRAM PROFILE GRADE CONFIGURATION PK-8

More information

Paulsboro Public Schools

Paulsboro Public Schools BOND REFERENDUM PRESENTATION January 27, 2015 713 Creek Road Bellmawr, NJ 08031 Telephone (856) 396-6200 Facsimile (856) 396-6205 Please visit us on the web at www.garrisonarch.com 1 05-12-14 AGENDA NJDOE

More information

6 Holub Middle School Overall Site Plan Gymnasium Floor Plan Exterior Perspective Before Exterior Perspective - After

6 Holub Middle School Overall Site Plan Gymnasium Floor Plan Exterior Perspective Before Exterior Perspective - After Contents 1 Program Outline Gymnasium Restrooms Storage rooms IDF 2 Finish Outline Walls Flooring Ceiling Roof 3 MEP Outline Plumbing Mechanical Electrical 4 Communication and Security Guideline Communication

More information

2 Main Building BLDG-959A Building Purpose Building Area Bus Terminal 14,890 SF Inspection Date August 18, 2016 Inspection Conditions Facility Conditi

2 Main Building BLDG-959A Building Purpose Building Area Bus Terminal 14,890 SF Inspection Date August 18, 2016 Inspection Conditions Facility Conditi 1 Site Summary Address 7105 Berkman Drive Austin, TX 78752 Number of Permanent Campus Facilities 1 Original Year of Construction 1995 Total Campus Building Area (combined) 14,890 SF Introduction is located

More information

County of Santa Barbara, California Facility Condition Assessment Total: $238,124. Appendix 1 Probable Cost Estimates Detail

County of Santa Barbara, California Facility Condition Assessment Total: $238,124. Appendix 1 Probable Cost Estimates Detail Project No.:P03000.001 Building Number: P03000-Lompoc County Offices Grounds Project Description: Mill and Overlay with some Partial Depth Patching Background: The site comprises asphalt pavement for the

More information

National Property Inspections

National Property Inspections National Property Inspections Anywhere, USA (325) 382-8754 Property Location 9375 Burt Street Anywhere USA Prepared for John Investor Consultant Al Standard (325) 382-8754 Page 1 of 27 TABLE OF CONTENTS

More information

A/E Design Deliverable Checklist

A/E Design Deliverable Checklist A/E Design Deliverable Checklist Design deliverables for the Design Development phase shall include all items listed in the Design Development column as well as those all items listed in the Schematic

More information

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS

SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS SERIES 0 BIDDING REQUIREMENTS AND CONTRACT FORMS INDIANA UNIVERSITY BIDDING REQUIREMENTS NOTICE TO BIDDERS BID FORM INSTRUCTIONS TO BIDDERS CONTRACTOR S BID FOR PUBLIC WORK - FORM 96 (REVISED 2005) MINORITY,

More information

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS

Watercrest - Sand Hill - Columbia, SC TABLE OF CONTENTS PROCUREMENT AND CONTRACTING REQUIREMENTS Watercrest - Sand Hill - Columbia, SC 00 0110-1 TABLE OF CONTENTS DIVISION 00 PROCUREMENT AND CONTRACTING REQUIREMENTS INTRODUCTORY INFORMATION Document 00 0101 Document 00 0110 Project Title Page CONTRACTING

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Building Assessment Survey 2017-2018 Asset: P.S./I.S. 266 - QUEENS, 74-10 COMMONWEALTH BLVD, New York, 11426 Inspection Id Inspection Type Time In Last Edited SA : Architectural

More information

PROPERTY PRESERVATION AND CAPITAL PLANNING

PROPERTY PRESERVATION AND CAPITAL PLANNING PROPERTY PRESERVATION AND CAPITAL PLANNING Overview What am I looking for Remaining Useful Life Estimating Planning TERMINOLOGY Shake Siding Service Head Barge Board Soffit / Overhang Belly Band Knee Brace

More information

DRAFT. Mathews Elementary School Site Summary. 906 West Lynn Street Austin, TX Number of Permanent Campus Facilities 4

DRAFT. Mathews Elementary School Site Summary. 906 West Lynn Street Austin, TX Number of Permanent Campus Facilities 4 1 Mathews Elementary School Site Summary Address 906 West Lynn Street Austin, TX 78703 Number of Permanent Campus Facilities 4 Original Year of Construction 1916 Total Campus Building Area (combined) 42,123

More information

Site Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks

Site Bldg Fiscal Yr System Sub-System. Verde Valley Site site 2014/15 Parking Paving. Verde Valley Site site 2014/15 Sidewalks Site Bldg Fiscal Yr System Sub-System Site site 2014/15 Parking Paving Site site 2014/15 Sidewalks Skill Center L 2015/16 Architectural Partitions Site Site 2015/16 Parking Striping Arc Center M 2014/15

More information

Seattle Public Schools Building Excellence IV Projects Under Construction

Seattle Public Schools Building Excellence IV Projects Under Construction Seattle Public Schools Building Excellence IV Projects Under Construction Project Slide Number Arbor Heights Elementary School 2 Cascadia Elementary School & Robert Eagle Staff Middle School 13 Genesee

More information

Beckley-Saner Recreation Center Summary

Beckley-Saner Recreation Center Summary Beckley-Saner Recreation Center Summary Address Building Purpose 114 West Hobson Avenue, Dallas, TX 75224 Recreation Center Original Year of Construction 1949 Building Area 34,510 SF Inspection Date July

More information

STATE PREFERENTIAL PROPERTY TAX ASSESSMENT PROGRAM

STATE PREFERENTIAL PROPERTY TAX ASSESSMENT PROGRAM GEORGIA DEPARTMENT OF NATURAL RESOURCES (DNR) - HISTORIC PRESERVATION DIVISION (HPD) PART A PRELIMINARY CERTIFICATION Section I Property and Owner Information STATE PREFERENTIAL PROPERTY TAX ASSESSMENT

More information

Building Inspection Report

Building Inspection Report Building Inspection Report Sample Commercial Inspection Report Inspection Date: Prepared For: Prepared By: Professional Property Inspection Consultants 4857 Winterset Drive Columbus, OH 43220 (614) 459-5941

More information

SUFFIELD PUBLIC SCHOOLS Suffield, Connecticut

SUFFIELD PUBLIC SCHOOLS Suffield, Connecticut SUFFIELD PUBLIC SCHOOLS Suffield, Connecticut DATE: January 30, 2018 TO: FROM: RE: Karen Berasi Bill Hoff Board Approval of Final Spaulding Roof Cost Estimates and Plans The Board of Education approved

More information

NYC Department of Education

NYC Department of Education Architectural Inspection Building Assessment Survey 2017-2018 Asset: P.S. 54 MINISCHOOL - QUEENS, 86-02 127TH STREET, New York, 11418 Inspection Id Inspection Type Time In Last Edited SA : Architectural

More information

Edmonton Public School District No. 7

Edmonton Public School District No. 7 EXECUTIVE SUMMARY 1. Overall Impressions The 1966 non-core school has actively pursued an ongoing maintenance and upgrade program to improve a number of past problem areas within the school. Extensive

More information

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY

BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY BELLA PALERMO HOMEOWNERS ASSOCIATION MAINTENANCE MATRIX DIVISION OF MAINTENANCE AND REPAIR RESPONSIBILITY The list below contains those building elements most commonly found in buildings found in a condominium

More information

La Conner School District

La Conner School District hoarch.com La Conner School District Capital Bond Planning Meeting 4 - Master Plan Options / Budget Estimates July 18th, 2012 4010 Lake Washington Blvd, NE, Suite 320 Kirkland, Wa 425 828 8948 Agenda Meeting

More information

NYC Department of Education

NYC Department of Education Building Assessment Survey 2017-2018 Asset: P.S. 65 - BROOKLYN, 158 RICHMOND STREET, New York, 11208 Inspection Id Inspection Type Time In Last Edited Architectural - Senior 2018-05-15 11:22 AM 2018-06-12

More information

SUMMARY 792 Youngfield Ct., Lakewood CO Frank Oz January 13, 2018

SUMMARY 792 Youngfield Ct., Lakewood CO Frank Oz January 13, 2018 SUMMARY 792 Youngfield Ct., Lakewood CO 80228 Frank Oz January 13, 2018 Christopher Grabbe internachi Certified Professional Inspector FirePower Inspections 7204645889 info@firepowerinspections.com 2.1.1

More information